Sunteți pe pagina 1din 315

 

Faculty of Engineering, The University of Auckland 

Commentary to 
Assessment and 
Improvement of 
Unreinforced 
Masonry Buildings 
for Earthquake 
Resistance 
Supplement to “Assessment and Improvement of the Structural Performance of 
Buildings in Earthquakes” 

Draft 
12/2011 
 
 
 

Contents 
Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand .......... 1‐1

C1.1 Introduction ....................................................................................................................... 1‐1

C1.3 URM Performance in Past Earthquakes ............................................................................ 1‐3

C1.4 New Zealand URM Building Stock ..................................................................................... 1‐8

C1.5 New Zealand Building Codes Pertaining to URM Construction ...................................... 1‐13

C1.6 Acknowledgements ......................................................................................................... 1‐18

C1.7 References ....................................................................................................................... 1‐18

Section C2 ‐ Material Properties of Masonry Walls ...................................................................... 2‐1

C2.1 Notation ............................................................................................................................ 2‐1

C2.3 In‐situ and Extracted Sample Testing ................................................................................ 2‐1

C2.4 Brick and Mortar Field Assessment Procedure ................................................................. 2‐5

C2.5 Additional Information ...................................................................................................... 2‐6

C2.7 Masonry Stress Block Parameters ................................................................................... 2‐22

C2.8 Worked Examples ............................................................................................................ 2‐23

C2.9 References ....................................................................................................................... 2‐27

Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms ........................................ 3‐1

C3.3 Timber properties .............................................................................................................. 3‐1

C3.4 Classification ...................................................................................................................... 3‐3

C3.5 Configuration and Condition Assessment ......................................................................... 3‐3

C3.6 Characteristic Values ......................................................................................................... 3‐5

C3.7 Diaphragm Stiffness ........................................................................................................ 3‐14

C3.8 Worked Example 1 .......................................................................................................... 3‐15

C3.9 Worked Example 2 .......................................................................................................... 3‐17

C3.10 Worked Example 3 ........................................................................................................ 3‐19

C3.11 References ..................................................................................................................... 3‐21

Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry Walls ............................ 4‐1

C4.1 Notation ............................................................................................................................ 4‐1

C4.2 Scope ................................................................................................................................. 4‐1

C4.3 Analysis Procedures ........................................................................................................... 4‐1

C4.4 Design Example ............................................................................................................... 4‐16

  i
 
 

C4.5 References ...................................................................................................................... 4‐24

Section C5 ‐ Determination of Diaphragm Design Actions ........................................................... 5‐1

C5.2 Scope ................................................................................................................................. 5‐1

C5.3 Load Distribution .............................................................................................................. 5‐1

C5.4 Design Actions ................................................................................................................... 5‐1

C5.5 Worked Example ............................................................................................................... 5‐1

C5.6 References ........................................................................................................................ 5‐3

Section C6 ‐ Design Actions on URM Walls and Parapets loaded out‐of‐plane ........................... 6‐1

C6.1 Notations .......................................................................................................................... 6‐1

C6.2 Scope ................................................................................................................................. 6‐1

C6.3 Design Lateral Force on Walls loaded out‐of‐plane .......................................................... 6‐3

C6.4 Design Example ................................................................................................................. 6‐3

C6.5 References ........................................................................................................................ 6‐7

Section C7 ‐ Design Actions on Wall Diaphragm Anchorages ....................................................... 7‐1

C7.1 Notation ............................................................................................................................ 7‐1

C7.2 Scope ................................................................................................................................. 7‐1

C7.3 Design Shear for In‐plane Loaded Connections ................................................................ 7‐1

C7.4 Design Tension for Out‐of‐plane Loaded Connections ..................................................... 7‐1

C7.5 Design Example ................................................................................................................. 7‐2

C7.6 References ........................................................................................................................ 7‐4

Section C8 ‐ Response of walls loaded in‐plane ........................................................................... 8‐1

C8.1 Notation ............................................................................................................................ 8‐1

C8.2 Scope ................................................................................................................................. 8‐1

C8.3 Properties of walls loaded in‐plane .................................................................................. 8‐3

C8.4 Nominal Shear Capacity of walls loaded in‐plane ............................................................ 8‐4

C8.5 Deformation Limits ........................................................................................................... 8‐9

C8.6 Worked Examples ........................................................................................................... 8‐10

References .............................................................................................................................. 8‐17

Section C9 ‐ Strength and Deformation Assessment of Flexible Timber Floor Diaphragms ........ 9‐1

C9.3 Lateral Deformation .......................................................................................................... 9‐1

C9.4 Strength ............................................................................................................................ 9‐1

ii   
 
 

C9.5 Worked Example 1 ............................................................................................................ 9‐2

C9.6 Worked Example 2 ............................................................................................................ 9‐3

C9.7 Worked Example 3 ............................................................................................................ 9‐4

C9.8 References ......................................................................................................................... 9‐5

Section C10 ‐ Strength and Deformation Assessment of Timber Roof Diaphragms ................... 10‐1

C10.2 Scope ............................................................................................................................. 10‐1

C10.3 Material Properties ....................................................................................................... 10‐2

C10.4 Lateral Deformation ...................................................................................................... 10‐2

C10.5 Strength ......................................................................................................................... 10‐2

C10.6 References ..................................................................................................................... 10‐2

Section C11 ‐ Out‐of‐plane Wall and Parapet Response ............................................................. 11‐1

C11.2 Scope ............................................................................................................................. 11‐1

C11.3 Wall Thickness, Height, and Slenderness Ratio ............................................................. 11‐2

C11.4 Load‐bearing walls......................................................................................................... 11‐3

C11.5 Assessment .................................................................................................................... 11‐3

C11.6 Worked example ........................................................................................................... 11‐7

C11.7 References ................................................................................................................... 11‐13

Section C12 ‐ Wall‐diaphragm Anchorages ................................................................................. 12‐1

C12.1 Notation ........................................................................................................................ 12‐1

C12.2 Scope ............................................................................................................................. 12‐1

C12.3 Diaphragm Joist Seating ................................................................................................ 12‐3

C12.4 Masonry Anchorage Failures ......................................................................................... 12‐3

C12.5 Steel Anchorage Failures ............................................................................................... 12‐4

C12.6 Timber Anchorage Failures ........................................................................................... 12‐5

C12.7 Examples........................................................................................................................ 12‐7

C12.8 References ..................................................................................................................... 12‐9

Section  C13  ‐  Heritage  Characteristics  of  URM  Buildings  and  the  Impacts  of  Seismic 
Improvements ............................................................................................................................. 13‐1

C13.1 Introduction ................................................................................................................... 13‐1

C13.2 Heritage and Conservation ............................................................................................ 13‐2

C13.3 Architectural Character ................................................................................................. 13‐7

C13.4 Initial Considerations for Seismic Improvement ......................................................... 13‐15

  iii
 
 

C13.5 Stabilisation for Seismic Improvement ....................................................................... 13‐17

C13.6 Enhancing Existing Walls ............................................................................................. 13‐21

C13.7 New Building Strengthening Systems ......................................................................... 13‐25

C13.8 Reduction of Forces .................................................................................................... 13‐31

C13.9 Approaches to Seismic Improvement ......................................................................... 13‐32

C13.10 Conclusions ............................................................................................................... 13‐35

C13.11 References ................................................................................................................ 13‐36

Section  C14  ‐  Methods  for  Stiffening  and  Strengthening  of  Flexible  Timber  Floor  and  Roof 
Diaphragms ................................................................................................................................. 14‐1

C14.2 Scope ............................................................................................................................. 14‐1

C14.3 Retrofit Selection .......................................................................................................... 14‐1

C14.4 Revised Diaphragm Assessment ................................................................................... 14‐5

C14.5 Diaphragm Chord Design .............................................................................................. 14‐5

C14.6 Subdiaphragm Design ................................................................................................... 14‐8

C14.7 Diaphragm Penetrations ............................................................................................... 14‐9

C14.8 Worked Example ......................................................................................................... 14‐10

C14.9 References .................................................................................................................. 14‐10

Section C15 ‐ Methods for Improving Wall Diaphragm Connections ......................................... 15‐1

Section C16 ‐ Unbonded Post‐tensioning ................................................................................... 16‐1

C16.1 Notation ........................................................................................................................ 16‐1

C16.2 Scope ............................................................................................................................. 16‐2

C16.3 Post‐tensioning Tendon Types, Stresses and Spacing .................................................. 16‐5

C16.4 In‐plane Wall Behaviour................................................................................................ 16‐6

C16.5 Out‐of‐plane Wall Behaviour ...................................................................................... 16‐10

C16.6 Design Example ........................................................................................................... 16‐15

C16.7 References .................................................................................................................. 16‐19

Section C17 ‐ Surface Bonded Fibre Reinforced Polymer Systems ............................................. 17‐1

C17.2 Notation ........................................................................................................................ 17‐1

C17.2 Scope ............................................................................................................................. 17‐2

C17.3 General Design Information .......................................................................................... 17‐2

C17.4 Shear Strength Provided by Fibre Reinforced Polymer ................................................ 17‐2

iv   
 
 

Relatively little data is available for shear strength enhancement  using vertical FRP systems, 
and hence a constant effective strain value is proposed. ..................................................... 17‐11

C17.5 Design Examples .......................................................................................................... 17‐11

C17.6 References ................................................................................................................... 17‐16

Section C18 ‐ Near Surface Mounted (NSM) Fibre Reinforced Polymer Systems ....................... 18‐1

C18.1 Notation ........................................................................................................................ 18‐1

C18.2 Scope ............................................................................................................................. 18‐2

C18.3 Retrofit Parameters ....................................................................................................... 18‐3

C18.4 In‐plane Design .............................................................................................................. 18‐3

C18.5 Out‐of‐plane Design ...................................................................................................... 18‐3

C18.6 Other Considerations .................................................................................................... 18‐7

C18.7 Design examples ............................................................................................................ 18‐9

C18.8 References ................................................................................................................... 18‐13

Section C19 ‐ Fibre Reinforced Shotcrete (FRS) .......................................................................... 19‐1

C19.1 Notation ........................................................................................................................ 19‐1

C19.2 Scope ............................................................................................................................. 19‐2

C19.3 In‐plane General Design Information ............................................................................ 19‐3

C19.4 Out‐of‐plane General Design Information .................................................................... 19‐6

C19.5 References ................................................................................................................... 19‐13

Section C20 ‐ Near Surface Mounted Steel Reinforcement ........................................................ 20‐1

Section C21 ‐ Textile Reinforced Mortars .................................................................................... 21‐1

Section C22 ‐ Restraining Parapets and Chimneys ...................................................................... 22‐1

Section C23 ‐ Pounding ................................................................................................................ 23‐1

   

  v
 
 

List of Figures 
Figure C1‐1: Raupo whare (house) at Wairau Pa, ca. 1880 (Alexander Turnbull Library). ........... 1‐1

Figure C1‐2: Raupo and timber whares of a Maori village at Maketu, Kawhia, 1895 (Alexander 
Turnbull Library). ........................................................................................................................... 1‐1

Figure C1‐3:  New Zealand total population data, 1858‐2007. ..................................................... 1‐2

Figure C1‐4: Shops on Queen Street, Auckland, 1859 (Alexander Turnbull Library). ................... 1‐3

Figure C1‐5: Queen Street and Queen Street Wharf, Auckland, in 1882 (Alexander Turnbull 
Library). ......................................................................................................................................... 1‐3

Figure C1‐6: Group photograph of the construction workers that built the Stratford Public 
Hospital during 1906‐1907 (Alexander Turnbull Library). ............................................................ 1‐4

Figure C1‐7: Brick building under construction, ca 1920 (Alexander Turnbull Library). ............... 1‐4

Figure C1‐8: The 1833 Stone Store at Kerikeri was built by the Church Missionary Society. (A P 
Godber Collection, Alexander Turnbull Library). .......................................................................... 1‐4

Figure C1‐9: Two Chinese miners in front of a stone cottage in central Otago, ca 1860 (Alexander 
Turnbull Library). ........................................................................................................................... 1‐4

Figure C1‐10: Collapse of a new masonry auction market building, Queen Street, 1865 
(Alexander Turnbull Library). ........................................................................................................ 1‐5

Figure C1‐11: Looking along a row of commercial buildings on Queen Street, Auckland, ca 1910 
(Alexander Turnbull Library). ........................................................................................................ 1‐5

Figure C1‐12: Victorian Christchurch in 1885 (Coxhead 1885) ..................................................... 1‐5

Figure C1‐13: Christchurch’s first ‘skyscraper’, photo circa 1910 (Brittenden Collection 1910) .. 1‐5

Figure C1‐14: General store damaged by the 1929 Murchison earthquake (Alexander Turnbull 
Library). ......................................................................................................................................... 1‐6

Figure C1‐15: Damaged business premises after the earthquake of 17 June 1929 (Alexander 
Turnbull Library). ........................................................................................................................... 1‐6

Figure C1‐16: Hastings Street, Napier, circa 1914 (Alexander Turnbull Library). ......................... 1‐6

Figure C1‐17: View down Hastings Street, Napier after the 1931 earthquake (Alexander Turnbull 
Library). ......................................................................................................................................... 1‐6

Figure C1‐18: Looking over Napier at the buildings ruined by the 1931 earthquake and the fires 
(Alexander Turnbull Library). ........................................................................................................ 1‐7

Figure C1‐19: Ruins of the Napier Anglican Cathedral after the 1931 Napier earthquake 
(Alexander Turnbull Library). ........................................................................................................ 1‐7

Figure C1‐20: Toppled parapet in the 2007 Gisborne earthquake. .............................................. 1‐8

Figure C1‐21 Out‐of‐plane failure of a gable wall in the 2007 Gisborne earthquake. .................. 1‐8

vi   
 
 

Figure C1‐22: Out‐of‐plane wall failure at the corner of Worcester and Manchester streets in the 
2010 Darfield earthquake. ............................................................................................................. 1‐8

Figure C1‐23: Out‐of‐plane wall failure at 118 Manchester Street in the 2010 Darfield 
earthquake. ................................................................................................................................... 1‐8

Figure C1‐24: Photographic examples of New Zealand URM typologies ...................................... 1‐9

Figure C1‐25: Estimated %NBS of URM buildings in Provinces throughout New Zealand ......... 1‐12

Figure C2‐1: Steps to determine brick properties ......................................................................... 2‐2

Figure C2‐2: Determination of mortar compression strength ...................................................... 2‐3

Figure C2‐3: Preparation for prism compression test ................................................................... 2‐3

Figure C2‐4: Masonry flexural bond test ....................................................................................... 2‐4

Figure C2‐5: In‐situ and laboratory bed‐joint shear test ............................................................... 2‐4

Figure C2‐6: Difference between exposed and unexposed brick surface ..................................... 2‐6

Figure C2‐7: Colour spectrum intensity vs. compressive strength plot ........................................ 2‐8

Figure C2‐8: Brick compressive strength vs. visible colour plot .................................................... 2‐8

Figure C2‐9: Plot of brick compressive strength vs. scratch index .............................................. 2‐10

Figure C2‐10: Plot of Mortar compressive strength vs. scratch index ........................................ 2‐11

Figure C2‐11 Plot of brick Modulus of Rupture vs. brick compressive strength ......................... 2‐12

Figure C2‐12: Plot of mortar compressive strength vs. h/t ratio ................................................ 2‐13

Figure C2‐13: 3‐D plot relating the brick, mortar and masonry compressive strengths ............. 2‐15

Figure C2‐14: Plot of masonry Modulus of Elasticity vs. compressive strength plot .................. 2‐15

Figure C2‐15: Unreinforced masonry module for density approximation .................................. 2‐16

Figure C2‐16: Plot of masonry flexural bond strength vs. masonry compressive strength ........ 2‐17

Figure C2‐17: Different types of bond failure ............................................................................. 2‐18

Figure C2‐18: Plot of masonry flexural bond strength vs. mortar compressive strength ........... 2‐18

Figure C2‐19: Plot of shear stress vs. axial compression for laboratory manufactured samples2‐20

Figure C2‐20: Plot of shear stress vs. axial compression for field samples ................................. 2‐20

Figure C2‐21: Plot of cohesion vs. masonry compressive strength ............................................. 2‐21

Figure C2‐22: Plot of cohesion vs. mortar compressive strength ............................................... 2‐21

Figure C2‐23: Campbell Free Kindergarten ................................................................................. 2‐23

Figure C2‐24: Two‐storey Irish Pub ............................................................................................. 2‐25

Figure C2‐25: Two‐storey commercial building ........................................................................... 2‐26

Figure C3‐1: Test piece for embedded strength tests ................................................................... 3‐2

  vii
 
 

Figure C3‐2: Test setup for embedded strength tests .................................................................. 3‐2

Figure C3‐3: Pure block test setup to determine compression strength of wood ....................... 3‐3

Figure C3‐4: Diaphragm configuration details .............................................................................. 3‐4

Figure C3‐5: Full‐scale diaphragm testing results ......................................................................... 3‐9

Figure C3‐6: Idealised bilinear response curve ........................................................................... 3‐10

Figure C3‐7: Bilinear curves from full‐scale diaphragm testing .................................................. 3‐13

Figure C4‐1: Modal testing and system identification procedure ................................................ 4‐7

Figure C4‐2: Plots of Force‐displacement response of URM assemblages ................................. 4‐11

Figure C4‐3: Seismic hazard zonation for the North Island of New Zealand for ground motion 
record selection .......................................................................................................................... 4‐14

Figure C4‐4: Layout of example building .................................................................................... 4‐17

Figure C6‐1: Flowchart for Out‐of‐plane Seismic Design of URM buildings with Flexible 
Diaphragms. .................................................................................................................................. 6‐2

Figure C6‐2: Definition of heights ................................................................................................. 6‐3

Figure C6‐3: Building cross‐section ............................................................................................... 6‐4

Figure C8‐1: Effective pier model (Yi et al. 2008) ......................................................................... 8‐2

Figure C8‐2: Shear stress distribution in a rectangular wall ......................................................... 8‐3

Figure C8‐3: Tributary areas for determining normal force on each wall (Russell 2010) ............. 8‐4

Figure C8‐4: Diagonal Tension failure mode ................................................................................. 8‐5

Figure C8‐5: Rocking/toe crushing failure mode .......................................................................... 8‐8

Figure C8‐6: Bed‐joint sliding failure mode .................................................................................. 8‐9

Figure C8‐7:  Equivalent bilinear approximation (Magenes and Calvi 1997) .............................. 8‐10

Figure C8‐8: Plan layout of building ............................................................................................ 8‐10

Figure C10‐1: Examples of roof configurations ........................................................................... 10‐1

Figure C11‐1: Procedure for seismic assessment of out‐of‐plane loaded URM walls ................ 11‐5

Figure C11‐2: Zonation map for the North Island ....................................................................... 11‐6

Figure C11‐3: Zonation map for the South Island ....................................................................... 11‐6

Figure C11‐4: Summary of North Island parametric study results (single‐storey 2‐leaf wall ‐ 
Shallow soil) ................................................................................................................................ 11‐7

Figure C12‐1: Photographs of damage in the 2010 Darfield (Canterbury) earthquake due to 
deficient or absent diagram anchorages .................................................................................... 12‐2

Figure C12‐2:  Examples of wall‐diaphragm anchorages that were partially or fully successful 
during the 2010 Darfield earthquake ......................................................................................... 12‐4

viii   
 
 

Figure C12‐3: Examples of failed anchorages where steel shows no indication of failure ......... 12‐5

Figure C12‐4: Joist oriented parallel to URM wall ....................................................................... 12‐6

Figure C12‐5: Joist oriented perpendicular to URM wall ............................................................ 12‐6

Figure C12‐6: Observed row failure modes for timber connections loaded parallel to grain. ... 12‐7

Figure C12‐7: Assumed failure plain for punching shear failure. ................................................ 12‐8

Figure C13‐1: The Birdcage hotel prior to seismic improvement and being moved ................... 13‐2

Figure C13‐2: Napier School of Music before and after retrofit. (reproduced from Robinson and 
Bowman 2000) ............................................................................................................................ 13‐7

Figure C13‐3: Before and after cross sections through Cranmer Square Normal School, 
Christchurch (reproduced from Wilby, 1983). Showing changed interior layouts and surfaces and 
removed a large amount of the historic material ....................................................................... 13‐7

Figure C13‐4: Primary form of a URM building in Auckland. At this stage the basic shape and the 
broad gestures that make up the building are noted. In this case the building has a reasonably 
simple form and displays a typical 3 part vertical hierarchy ....................................................... 13‐9

Figure C13‐5: A study of the building’s openings in two dimensions. This has been done firstly as 
the physical openings in the URM, and secondly as the forms surrounding the openings. 
Interfering with these patterns will change the way that the building reads; something as simple 
as changing the colour of the window frames will bring these forward and make the openings 
smaller and less distinct ............................................................................................................ 13‐10

Figure C13‐6: Shed 13 on the Wellington waterfront features a distinctive roof that is integral 
with its character ....................................................................................................................... 13‐11

Figure C13‐7: A parapet that is integral with the design of the rest of the facade and which 
contributes historic information ............................................................................................... 13‐11

Figure C13‐8: The Auckland Ferry Building is integral with its waterfront setting and altering this 
relationship would remove historic meaning ........................................................................... 13‐11

Figure C13‐9: Details of openings. Things to take note of here are the bond pattern and 
technique used for laying bricks, colouring, striking of mortar, changes in surface, recesses and 
depressions, and proportions of windows and other components .......................................... 13‐12

Figure C13‐10: Arcades in Auckland with complex spatial relationships where blocking lines of 
sight between spaces or impeding established pedestrian routes will have significant negative 
effects ........................................................................................................................................ 13‐14

Figure C13‐11: Severely degraded brick and mortar due to moisture ...................................... 13‐18

Figure C13‐12: Parapets strengthened using near‐surface mounted FRP strips ...................... 13‐19

Figure C13‐13: An extreme case in the 2010 Darfield earthquake where inadequate connections 
have resulted in wall collapse ................................................................................................... 13‐19

Figure C13‐14: An assortment of diaphragm fixings ................................................................. 13‐20

  ix
 
 

Figure C13‐15: Spiral threaded rods being installed to secure an outer layer of bricks ........... 13‐21

Figure C13‐16: Struts from the floor above to improve out‐of‐plane performance ................ 13‐23

Figure C13‐17: Post‐tensioning bars used in the Birdcage hotel with concrete load spreaders cut 
into the brick ............................................................................................................................. 13‐24

Figure C13‐18: Simple and visually interesting in‐plane strengthening ................................... 13‐25

Figure C13‐19: Pier damage between openings in the Darfield Earthquake ............................ 13‐26

Figure C13‐20: A concrete moment frame inside the façade of a large URM building in 
Wellington (Dunning Thornton Consultants). ........................................................................... 13‐27

Figure C13‐21: Eccentric bracing in a walkway (Dunning Thornton Consultants). ................... 13‐27

Figure C13‐22: An eccentrically braced core (Dunning Thornton Consultants). ...................... 13‐27

Figure C13‐23: Shotcrete walls on the rear of the birdcage hotel ............................................ 13‐29

Figure C13‐24: FRP applied to a wall (Dunning Thornton Consultants). .................................. 13‐29

Figure C13‐25: It is possible to make diaphragm improvements visibly interesting, as with this 
recently installed floor .............................................................................................................. 13‐30

Figure C13‐26: A roof bracing system which clashes with the existing structure, resulting in a 
confused ceiling space .............................................................................................................. 13‐33

Figure C13‐27: The ornate façade of this building made exterior strengthening difficult ....... 13‐34

Figure C13‐28: The solution was to innovatively strengthen the interior, which allowed retention 
of its most important visual elements ...................................................................................... 13‐34

Figure C13‐29: Openings in this Christchurch café allowed placement of frames which 
compliments the space ............................................................................................................. 13‐34

Figure C13‐30: Steel structure installed in an intrusive way which is visually distracting ........ 13‐34

Figure C13‐31: No attempt has been made to conceal this new shear wall, rather the aesthetic is 
celebrated by the rest of the architecture ................................................................................ 13‐35

Figure C13‐32: Excessive floor and wall ties somehow work with this façade ......................... 13‐35

Figure C14‐1: Diaphragm retrofit examples ............................................................................... 14‐4

Figure C14‐2: Photographs of tested retrofitted diaphragms .................................................... 14‐6

Figure C14‐3: Full‐scale retrofitted diaphragm test results ........................................................ 14‐7

Figure C14‐4: Diaphragm chord schematic ................................................................................. 14‐7

Figure C14‐5: Subdiaphragm example (from Oliver 2010) ......................................................... 14‐9

Figure C14‐6: Typical Out‐of‐Plane Wall Support Detail at Diaphragm Opening (from Oliver 2010)
 .................................................................................................................................................. 14‐10

Figure C16‐1: Post‐tensioning Retrofit Technique ...................................................................... 16‐3

Figure C16‐2: Definition of Limit States ...................................................................................... 16‐3

x   
 
 

Figure C16‐3: Flowchart for Post‐tensioning Seismic Retrofit Design ......................................... 16‐4

Figure C16‐4: Typical Stress‐Strain Plots ..................................................................................... 16‐5

Figure C16‐5: Post‐tensioned In‐plane Pier Definition and Stress Profile at Initial State ........... 16‐6

Figure C16‐6: Post‐tensioned In‐plane Pier Equilibrium at Nominal Strength Limit State ......... 16‐7

Figure C16‐7: Post‐tensioned In‐plane Pier Equilibrium at First Cracking Limit State ................ 16‐8

Figure C16‐8: Post‐tensioned In‐plane Pier Equilibrium at Hinge Formation Limit State ........... 16‐9

Figure C16‐9: Test Frame Dimensions ....................................................................................... 16‐10

Figure C16‐10: Calculated Vs Experimental Values ................................................................... 16‐10

Figure C16‐11: Post‐tensioned Out‐of‐plane Wall Definition and Stress Profile at Initial State ... 16‐
11

Figure C16‐12: Post‐tensioned Out‐of‐plane Wall at Nominal Strength Limit State ................ 16‐11

Figure C16‐13: Calculated Vs Experimental Values ................................................................... 16‐14

Figure C16‐14: URM Wall Details .............................................................................................. 16‐16

Figure C17‐1: Examples of FRP systems. ..................................................................................... 17‐2

Figure C17‐2: Examples of non‐vertical FRP retrofit systems. .................................................... 17‐4

Figure C17‐3: Examples of vertical FRP retrofit systems. ............................................................ 17‐4

Figure C17‐4: FRP continuous fabric system extended ld beyond the top of the doors. The vertical 
FRP system was designed for the pier between the two doors. ................................................. 17‐6

Figure C17‐5: FRP design flowchart ............................................................................................. 17‐7

Figure C17‐6: Truss analogy for FRP‐retrofitted URM wall ......................................................... 17‐8

Figure C17‐7: Plot showing the relationship between fe and  .............................................. 17‐10

Figure C17‐8: FRP retrofit for wall in Example 15.1 .................................................................. 17‐13

Figure C17‐9: FRP retrofit for building in Example 15.2 ............................................................ 17‐14

Figure C18‐1: NSM CFRP retrofit application .............................................................................. 18‐3

Figure C18‐2: Stress and strain profile ........................................................................................ 18‐4

Figure C18‐4: Typical wall failure mechanisms ........................................................................... 18‐7

Figure C18‐3: Out‐of‐plane design procedure ............................................................................. 18‐7

Figure C18‐5: Experimental program .......................................................................................... 18‐8

Figure C18‐6: Experimental results of NSM CFRP wall testing .................................................... 18‐9

Figure C18‐7: CFRP wall retrofit for Example C18.7.2 ............................................................... 18‐13

Figure C19‐1: Sequence of FRS strengthening procedures. ........................................................ 19‐3

Figure C19‐2: In‐plane FRS design procedure ............................................................................. 19‐4

  xi
 
 

Figure C19‐3: Distances of xt and xc with respect to axial load ................................................... 19‐6

Figure C19‐4: Out‐of‐plane FRS design procedure ..................................................................... 19‐7

Figure C19‐5: NSM reinforcement .............................................................................................. 19‐8

Figure C19‐6: Illustration of FRS effective depth ........................................................................ 19‐8
 

   

xii   
 
 

List of Tables 
Table C1‐1: New Zealand URM typologies .................................................................................. 1‐10

Table C1‐2: Number of URM buildings from QV according to construction decade .................. 1‐11

Table C1‐3: Estimated number of potentially earthquake prone and earthquake risk URM 
buildings ...................................................................................................................................... 1‐13

Table C2‐1: Height to thickness ratio correction factor for mortar compressive strength ........... 2‐2

Table C2‐2: Parameters used in the NZSEE (2006) guideline ........................................................ 2‐7

Table C2‐3: Mohs hardness scale .................................................................................................. 2‐9

Table C2‐4: Mortar dividing factors based on h/t ratio ............................................................... 2‐14

Table C2‐5: List of αf'm values from publications ........................................................................ 2‐23

Table C3‐1: Full‐scale diaphragm testing summary ...................................................................... 3‐8

Table C3‐2: Example backbone force‐displacement data for time‐history analysis ................... 3‐10

Table C4‐1: Modal parameter extraction methods ....................................................................... 4‐8

Table C4‐2: Recommended suite profile for each seismic zone ................................................. 4‐15

Table C8‐1: Wall Schematics ......................................................................................................... 8‐6

Table C8‐2: Wall Specifications (Russell et al. 2012) ..................................................................... 8‐6

Table C8‐3: Comparison of predicted strength accounting for and neglecting flanges (Russell et 
al. 2012) ......................................................................................................................................... 8‐6

Table C11‐1: Estimated wall dimensions ..................................................................................... 11‐8

Table C11‐2: %NBS.Z for slenderness ratio of 17.1, lower storey ............................................... 11‐9

Table C11‐3: %NBS.Z for slenderness ratio of 19.6, top‐storey .................................................. 11‐9

Table C11‐4: Estimated parapet dimensions ............................................................................. 11‐10

Table C11‐5: Calculating %NBS for regions excluding near fault effect .................................... 11‐10

Table C11‐6: Calculating %NBS for regions including near fault effect ..................................... 11‐10

Table C11‐7: Calculating shear demand .................................................................................... 11‐11

Table C11‐8: Calculating shear capacity .................................................................................... 11‐11

Table C11‐9: One‐leaf wall assessment ..................................................................................... 11‐12

Table C11‐10: One‐leaf wall assessment ................................................................................... 11‐13

Table C16‐1: k Value for Moment Capacity Evaluation at Hinge Formation Limit State ............ 16‐9

Table C16‐2: Post‐tensioned Wall Dimensions and Post‐tensioning Details ............................ 16‐13

Table C16‐3: Masonry Materials ............................................................................................... 16‐15

  xiii
 
 

Table C16‐4: Input Parameters ................................................................................................. 16‐15

Table C17‐1: Typical values of FRP thickness, design rupture strain and modulus of elasticity. .. 17‐
11

Table 18‐1: Typical values of material properties for CFRP ........................................................ 18‐3

xiv   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C1 ‐ History and Prevalence of Unreinforced 
Masonry Buildings in New Zealand 

C1.1 Introduction 
New Zealand’s masonry construction heritage is comparatively young, spanning from 1833 until 
the  present  time  –  a  period  of  less  than  200  years.  Furthermore,  the  majority  of  URM 
construction  in New Zealand occurred  between 1880 and 1935.  Consequently, a study of  New 
Zealand’s URM building stock has a narrow scope in comparison with international norms (see 
for  instance  Binda  and  Saisi  (2005),  Lourenço  (2006)  and  Magenes  (2006)).  This  comparatively 
narrow time  period has the advantage  of facilitating the  documentation and reporting of New 
Zealand URM construction practice with a greater  degree of accuracy than is often  possible in 
countries with an older and more diverse history of URM construction (Binda 2006). 

C1.2.1 Early Settlement 
The  first  inhabitants  of  Aotearoa  New  Zealand  were  groups  of  Polynesian  explorers  who 
discovered and settled the islands in the period A.D. 800‐1000 (King 2003). These people did not 
develop  a  tradition  of  building  in  masonry,  but  instead  built  using  timber,  earth  and  most 
commonly raupo (bulrush). There are however, numerous stone‐related archaeological sites in 
New Zealand attributed to Maori society, the majority of which are garden walls or associated 
with fortifications. Examples of Maori construction are shown in Figure C1‐1 and Figure C1‐2. 

Figure C1‐1: Raupo whare (house) at Wairau  Figure C1‐2: Raupo and timber whares of a 
Pa, ca. 1880 (Alexander Turnbull Library).  Maori village at Maketu, Kawhia, 1895 
(Alexander Turnbull Library). 

Captain James Cook anchored off the coast of New Zealand on 9 October 1769. This event was 
followed by a gradual haphazard increase in the population of Europeans in New Zealand over 
the  next  70  years,  initially  primarily  associated  with  whaling,  but  also  involving  kauri  timber 
extraction and gold mining. Jacobs (1985) reports that the European population of New Zealand 
in 1830 was probably a little more than 300. By 1839 the number had risen to possibly 2000, and 

  C1‐1
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

at the beginning of the 1850s there was 26,000 Europeans in New Zealand (see Figure C1‐3 for 
recorded population data). These first European settlers found themselves without their familiar 
building  materials,  so  initially  emulated  the  style  and  construction  of  Maori  dwellings  (Shaw 
2003).  For  the  most  significant  early  buildings,  such  as  churches  and  assembly  buildings, 
architects from Australia or England were commissioned. 

5,000,000

4,000,000
Population

3,000,000

2,000,000

1,000,000

0
1840 1860 1880 1900 1920 1940 1960 1980 2000 2020
Year  
Figure C1‐3:  New Zealand total population data, 1858‐2007. 

Captain William Hobson’s arrival in 1840 as the First Governor General of New Zealand marked 
the beginning of New Zealand as a British colony. Construction during the 1840s to 1860s was 
primarily of timber for residential and small commercial buildings (see Figure C1‐4), but masonry 
buildings did begin to appear close to harbours (see Figure C1‐5) and in city centres. In the late 
1850’s Christchurch prospered from the wool trade and this allowed the transition from wood to 
stone and clay brick masonry for public buildings. In Christchurch the town hall was built in stone 
in 1862‐1863, the first stone building of Christ’s College was constructed in 1863, and the stone 
Provincial  Council  Chambers  was  completed  in  1864  (Wilson  1984).  Oliver  (2006)  reports  that 
clay bricks were first manufactured in Auckland in 1852, with production of about 5,000 bricks 
per day. In Auckland central city the construction of timber buildings was not restricted until the 
City  of  Auckland  Building  Act  of  1856,  with  a  fire  in  central  Auckland  in  1858  provided  further 
impetus for the transition from timber to clay brick masonry construction. Similar fires in other 
city  centres  resulted  in  this  transition  from  timber  to  masonry  construction  being  mirrored 
throughout  New Zealand, such as fires in inner city Christchurch in 1861, 1864, and 1866. The 
centre of Lyttelton was also destroyed in a fire on October 24th, 1870 (Christchurch City Libraries 
2006;  Wilson  1984).  The  combustibility  of  timber  structures  prompted  the  move  to  URM 
construction  due  to  its  fire  resistant  properties,  with  the  high  level  of  seismic  activity  in  New 
Zealand not influencing the decision, as the poor lateral force resisting properties of URM were 
largely unknown at this time of mass URM construction. The fire‐proof nature of masonry led to 
it being readily adopted as the appropriate building material for high importance structures such 
as government buildings, schools, and churches. 

C1‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Figure C1‐4: Shops on Queen Street, Auckland,  Figure C1‐5: Queen Street and Queen Street 
1859 (Alexander Turnbull Library).  Wharf, Auckland, in 1882 (Alexander Turnbull 
Library). 

Figure C1‐6 and Figure C1‐7 illustrate  typical  URM  construction scenes (although dated from a 


slightly later period). In other parts of New Zealand there was a more plentiful supply of natural 
stone, with New Zealand’s earliest masonry building having been constructed of stone in 1833 
(see  Figure  C1‐8).  Figure  C1‐9  shows  an  example  of  early  rural  construction  in  parts  of  New 
Zealand  where  timber  was  scarce  and  natural  stone  was  the  primary  construction  material. 
Evident  in  several  of  these  figures  is  a  predisposition  to  emulate  ‘mother  country’  British 
architecture.  To  some  extent  this  emulation  was  due  to  the  fact  that  there  were  very  few 
architects  in  New  Zealand  prior  to  1880,  with  many  distinctive  buildings  designed  by  overseas 
architects  (Haarhoff  2003).  However  Figure  C1‐10  shows  that  not  all  masonry  buildings  were 
well  constructed.  Hodgson  (1992)  reports  that  inferior  materials  and  uncertain  ground 
conditions  were  not  uncommon  in  building  projects  of  this  period.  Figure  C1‐11  show  that  by 
1910  central  Auckland  was  composed  almost  entirely  of  unreinforced  masonry  buildings. 
Stacpoole  and  Beaven  (1972)  have  similarly  reported  that  Auckland’s  early  wooden  buildings 
dating from the 1840s were badly in need of replacement by the 1860s. 

By  1914  the  central  area  of  Christchurch  had  been  largely  rebuilt,  resulting  in  a  city  that  was 
“interesting  for  its  architectural  variety,  pleasing  for  its  scale  and  distinctively  New  Zealand” 
(Wilson 1984). Figure C1‐12 and Figure C1‐13 show photos of historical Christchurch from 1885 
and 1910 respectively. Two of the many influential architects of Christchurch were J.C. Maddison 
(1850‐1923),  whose  design  focus  was  inspired  by  the  Italianate  style,  and  J.J.  Collins  (1855–
1933), who in partnership with R.D. Harman (1859‐1927) chose brick masonry as their medium 
for large commercial and institutional buildings. By the 1920’s wooden structures in Christchurch 
were rare, and were seen as small irregular relics of the past. 

C1.3 URM Performance in Past Earthquakes 

C1.3.1 Wairarapa, Canterbury and Murchison Earthquakes 
The Wairarapa earthquake occurred on Tuesday 23 January 1855, had an estimated magnitude 
of  M8.2  (Grapes  and  Downes  1997)  and  is  the  largest  earthquake  to  have  occurred  in  New 

  C1‐3
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

Zealand since the time of systematic European colonisation (see Dowrick and Rhoades (1998) for 
a  catalogue  of  major  New  Zealand  earthquakes  from  1901‐1993).  The  shock  was  felt  across 
almost the whole country, was highly destructive in Wellington, and also caused severe damage 
in Wanganui and Kaikoura. Between seven and nine people were killed in the earthquake, and 
five others sustained injuries that required hospitalisation. 

 
Figure C1‐6: Group photograph of the  Figure C1‐7: Brick building under 
construction workers that built the Stratford  construction, ca 1920 (Alexander Turnbull 
Public Hospital during 1906‐1907 (Alexander  Library). 
Turnbull Library). 

Figure C1‐8: The 1833 Stone Store at Kerikeri  Figure C1‐9: Two Chinese miners in front of 
was built by the Church Missionary Society. (A  a stone cottage in central Otago, ca 1860 
P Godber Collection, Alexander Turnbull  (Alexander Turnbull Library). 
Library). 

The M7.1 North Canterbury earthquake in 1888 (Stirling et al. 2008) caused severe damage to 
buildings made of cob and stone masonry and caused minor damage to buildings in Christchurch 
(PapersPast  2010).  A  later  earthquake  in  1901  centred  in  Cheviot  damaged  the  spire  on  the 
Canterbury Cathedral for the third time in its short life and led to reconstruction of the spire in 
timber. Further details are reported in Dizhur et al. (2010). 

C1‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Figure C1‐10: Collapse of a new masonry  Figure C1‐11: Looking along a row of 
auction market building, Queen Street,  commercial buildings on Queen Street, 
1865 (Alexander Turnbull Library).  Auckland, ca 1910 (Alexander Turnbull 
Library). 

   
Figure C1‐12: Victorian Christchurch in 1885  Figure C1‐13: Christchurch’s first 
(Coxhead 1885)  ‘skyscraper’, photo circa 1910 
(Brittenden Collection 1910) 

The M7.8 earthquake that struck Murchison on the 17th of June 1929 was felt throughout New 
Zealand (Dowrick 1994). Fortunately, the most intense shaking occurred in a mountainous and 
densely wooded area that was sparsely populated. Casualties were therefore comparatively light 
and the damage was mostly confined to the surrounding landscape, where the shaking triggered 
extensive landslides over thousands of square kilometres. Nonetheless, the shock impacted with 
damaging intensities as far away as Greymouth, Cape Farewell and Nelson (see Figure C1‐14 and 
Figure C1‐15). Fifteen people were killed in the Murchison earthquake. 

C1.3.2 The 1931 Hawke’s Bay Earthquake, Napier 
As  reported  above,  it  was  the  combustibility  of  timber  construction  that  prompted  the  focus 
towards  building  in  clay  brick  unreinforced  masonry,  and  occasionally  in  stone  masonry.  Early 
earthquakes  in  the  Wellington  region  resulted  in  a  slower  adoption  of  masonry  construction. 
This  caution  proved  to  be  well  justified.  On  the  morning  of  3  February  1931  the  Hawke’s  Bay 
region of the eastern North Island was struck by an M7.8 earthquake that completely destroyed 
much of the city of Napier (see Figure C1‐16 to Figure C1‐18). Fires swept through the wreckage, 
destroying much of what was left. Eight nurses died when the reinforced concrete Napier nurses 
home  collapsed,  and  perhaps  the  largest  brick  masonry  building  to  collapse  was  the  Napier 
Anglican  Cathedral  (see  Figure  C1‐19).  The  shaking  resulted  in  damage  from  Taupo  to 

  C1‐5
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

Wellington,  and  left  30,000  people  homeless.  The  official  death  toll  was  256,  and  the  event 
remains the worst disaster of any type to occur on New Zealand soil (Dalley and McLean 2005; 
Dowrick 1998). 

   
Figure C1‐14: General store damaged by the  Figure C1‐15: Damaged business premises 
1929 Murchison earthquake (Alexander  after the earthquake of 17 June 1929 
Turnbull Library).  (Alexander Turnbull Library). 

Figure C1‐16: Hastings Street, Napier, circa  Figure C1‐17: View down Hastings Street, 
1914 (Alexander Turnbull Library).   Napier after the 1931 earthquake (Alexander 
Turnbull Library). 
 

   

C1‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

   
Figure C1‐18: Looking over Napier at the  Figure C1‐19: Ruins of the Napier Anglican 
buildings ruined by the 1931 earthquake and the  Cathedral after the 1931 Napier 
fires (Alexander Turnbull Library).  earthquake (Alexander Turnbull Library). 

Following  the  demonstrated  poor  seismic  response  of  URM  buildings  during  the  Hawke’s  Bay 
earthquake there was a rapid decline in the use of unreinforced clay brick masonry construction, 
which  was  eventually  prohibited  in  1965  (New  Zealand  Standards  Institute  1965a).  The 
devastation  of  the  1931  Hawke’s  Bay  earthquake  prompted  the  New  Zealand  Government  to 
ban  the  use  of  unreinforced  masonry  on  public  buildings  (Oliver  2006)  and  also  prompted  the 
government  to  develop  a  national  building  code,  with  the  New  Zealand  Standards  Institution 
formed  in  1932.  This  institution  has  survived  to  the  present  day,  and  is  now  referred  to  as 
Standards New Zealand. 

C1.3.3 Gisborne and Darfield Earthquakes 
The M6.8 2007 Gisborne earthquake (Francois‐Holden et al. 2008) caused damage to numerous 
unreinforced masonry buildings, including the collapse of 22 parapets (Davey and Blaikie 2010). 
Examples  of  damage  to  URM  buildings  in  the  2007  Gisborne  earthquake  are  shown  in  Figure 
C1‐20 and Figure C1‐21. The 2010 Darfield earthquake caused extensive damage to a number of 
unreinforced  masonry  buildings  (Dizhur  et  al.  2010;  Ingham  and  Griffith  2011).  Whilst  this 
damage to important heritage buildings was the largest natural disaster to occur in New Zealand 
since  the  1931  Hawke’s  Bay  earthquake,  the  damage  was  consistent  with  projections  for  the 
scale of this earthquake, and indeed even greater damage might have been expected. In general, 
the  nature  of  damage  was  consistent  with  observations  previously  made  on  the  seismic 
performance  of  unreinforced  masonry  buildings  in  large  earthquakes,  with  aspects  such  as 
toppled chimneys and parapets, failure of gables and poorly secured face‐loaded walls, and in‐
plane damage to masonry frames all being extensively documented (see Figure C1‐22 and Figure 
C1‐23). 

  C1‐7
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

 
Figure C1‐20: Toppled parapet in the 2007  Figure C1‐21 Out‐of‐plane failure of a gable 
Gisborne earthquake.  wall in the 2007 Gisborne earthquake. 

 
Figure C1‐22: Out‐of‐plane wall failure at the  Figure C1‐23: Out‐of‐plane wall failure at 118 
corner of Worcester and Manchester streets in  Manchester Street in the 2010 Darfield 
the 2010 Darfield earthquake.  earthquake. 

C1.4 New Zealand URM Building Stock 
In order to foster a general understanding of the architectural character of New Zealand’s URM 
building  stock,  a  characterisation  study  was  performed  that  identified  the  seven  building 
typologies shown in Figure C1‐24 and reported in Table C1‐1. The intent of the typology study is 
to assist in initial seismic assessment. Further details are reported in Russell and Ingham (2010) 
and Russell and Ingham (2011). 

C1‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

   
Typology A building ‐ one storey isolated  Typology B building ‐ one storey row 

   
Typology C building ‐ two storey isolated  Typology D building ‐ two storey row 

   
Typology E building ‐ three+ storey isolated  Typology F building ‐ three+ storey row 

   
Typology G building ‐ religious  Typology G building ‐ institutional 

Figure C1‐24: Photographic examples of New Zealand URM typologies 

  C1‐9
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

Table C1‐1: New Zealand URM typologies 

Importance 
level 
Type  Description  Details 
(from 
NZS 1170.0) 

A  One storey,  2, 4  One storey URM buildings.  Examples include 


isolated  convenience stores in suburban areas, and small 
offices in a rural town. 

B  One storey,  2, 4  One storey URM buildings with multiple occupancies, 


row  joined with common walls in a row.  Typical in main 
commercial districts, especially along the main street 
in a small town. 

C  Two storey,  2, 4  Two storey URM buildings, often with an open front.  


isolated  Examples include small cinemas, a professional office 
in a rural town and post offices. 

D  Two storey,  2, 4  Two storey URM buildings with multiple occupancies, 


row  joined with common walls in a row.  Typical in 
commercial districts. 

E  Three+  2, 4  Three + storey URM buildings, for example office 


storey,  buildings in older parts of Auckland and Wellington.   
isolated 

F  Three+  2, 4  Three + storey URM buildings with multiple 


storey, row  occupancies, joined with common walls in a row.  
Typical in industrial districts, especially close to a port 
(or historic port). 

G  Institutional,  2, 3, 4  Churches (with steeples, bell towers etc), water 


Religious,  towers, chimneys, warehouses.  Prevalent 
Industrial  throughout New Zealand. 

C1.4.1 Estimation of URM Population and Value 
In  order  to  better  understand  the  aggregated  seismic  performance  of  the  nationwide  URM 
building stock, two parallel exercises were performed to estimate the number and distribution 
of URM buildings throughout New Zealand. The first method involved an assumption that URM 
buildings were constructed approximately in proportion to the national population distribution 
of the era, and the second method was based upon data purchased from Quotable Value (QV) 
regarding the exterior building fabric in the QV database. Both methods are estimates only, but 

C1‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

provided  similar  findings,  with  further  details  reported  in  Russell  and  Ingham  (2010).  The  QV 
database was analysed according to construction date, building height and financial value, with 
Table C1‐2 reporting the decade in which each URM building was constructed.  

 
Table C1‐2: Number of URM buildings from QV according to 
construction decade 

Decade  URM Buildings 

1870 – 1880  43 

1880 – 1890  23 

1890 – 1900  71 

1900 – 1910  469 

1910 – 1920  646 

1920 – 1930  878 

1930 – 1940  514 

1940 – 1950  218 

Mixed  726 

Total  3590 

Table C1‐2 clearly shows a trend where the number of URM buildings initially increased until the 
end of the 1920s, and subsequently declined. This trend follows the increasing rate of European 
immigration  and  associated  infrastructure  development  in  New  Zealand  in  the  early  20th 
Century (see Figure C1‐3), until the 1931 M7.8 Hawke’s Bay earthquake, after which URM was 
no longer considered a favourable building material.  

A  report  prepared  for  the  Department  of  Internal  Affairs  in  2002  (Hopkins  2002;  Hopkins  and 
Stuart 2003) showed that the total floor area of buildings in 32 cities and towns throughout New 
Zealand was approximately 27,200,000 m2. The total floor area of URM buildings extracted from 
the  QV  database  was  approximately  2,100,000 m2,  suggesting  that  URM  buildings  make  up 
approximately  8%  of  the  total  New  Zealand  commercial  building  stock  in  terms  of  floor  area. 
From the QV database it was also possible to establish that 86% of the nationwide URM building 
stock  is  either  a  one  or  two  storey  building,  and  that  the  aggregated  value  of  these  buildings 
(based  on  an  assessment  period  between  July  2005  and  September  2008)  is  approximately 
NZ$1.5 billion. However, it must be recognised that many buildings have a worth greater than 

  C1‐11
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

their financial valuation, including an architectural, historic or heritage value to the community, 
which can be difficult to quantify (Goodwin 2008; Goodwin et al. 2009).  

C1.4.2 Estimated Vulnerability of URM Buildings 
Following  determination  of  the  number  of  URM  buildings  and  their  approximate  regional 
distribution,  an  analysis  was  performed  to  estimate  the  expected  vulnerability  of  the  URM 
building population. The details of the analysis are reported in Russell and Ingham (2010), with 
the  results  reported  in  Figure  C1‐25  and  in  Table  C1‐3.  It  is  recognised  that  the  analysis  was 
essentially  qualitative  in  nature  and  can  be  expected  to  overestimate  the  number  of  poorly 
performing  URM  buildings,  primarily  because  of  the  conservative  nature  of  the  IEP. 
Nevertheless,  as  an  informative  estimate  of  the  nature  of  the  vulnerability  of  New  Zealand’s 
URM building stock, this analysis is considered robust. Additionally, this analysis does not take 
into  account  the  number  of  buildings  which  have  already  been  seismically  improved,  which 
Thornton  (2010)  notes  is  not  insignificant.      Data  that  became  available  following  damage  to 
URM  buildings  in  the  2010  Darfield  earthquake  (reported  in  Ingham  and  Griffith  (2011)) 
indicated general support for this analysis, although it was evident following the earthquake that 
the analysis presented in Figure C1‐25 underestimated the total number of URM buildings in the 
Canterbury region (see Dizhur et al. (2010)).  

 
Figure C1‐25: Estimated %NBS of URM buildings in Provinces throughout New Zealand 

   

C1‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Table C1‐3: Estimated number of potentially earthquake prone and earthquake risk URM 
buildings 

Province  Potentially earthquake  Potentially  Unlikely to be 


prone  earthquake risk  significant risk 

Auckland  41  3%  628  31%  357  74% 

Taranaki  59  4%  105  5%  0  0% 

Hawke’s Bay  85  6%  1  0%  0  0% 

Wellington  622  45%  55  3%  0  0% 

Marlborough  42  3%  5  0%  0  0% 

Nelson  94  7%  37  2%  0  0% 

Westland  39  3%  2  0%  0  0% 

Canterbury  338  24%  513  26%  0  0% 

Otago and 
66  5%  664  33%  126  26% 
Southland 

Total  1386  36%  2010  52%  483  12% 

C1.5 New Zealand Building Codes Pertaining to URM Construction 
The  Great  Depression  in  the  1930s  and  the  outbreak  of  World  War  II  significantly  slowed 
progress in the construction sector, and few large buildings of any material were constructed in 
the  period  between  1935  and  1955  (Megget  2006;  Stacpoole  and  Beaven  1972).  Equally 
important  in  the  history  of  URM  buildings  in  New  Zealand  was  the  1931  M7.8  Hawkes  Bay 
earthquake,  and  the  changes  in  building  provisions  which  it  precipitated.  Later  in  1931,  in 
response  to  that  earthquake,  the  Building  Regulations  Committee  presented  a  report  to  the 
Parliament of New Zealand entitled “Draft General Building By‐Law” (Cull 1931), which was the 
first step towards requiring seismic provisions in the design and construction of new buildings. In 
1935,  this  report  evolved  into  NZSS  no.  95,  published  by  the  newly  formed  New  Zealand 
Standards  Institute,  and  required  a  horizontal  acceleration  for  design  of  0.1g,  and  this 
requirement applied to the whole of New Zealand (New Zealand Standards Institute 1935). NZSS 
no.  95  also  suggested  that  buildings  for  public  gatherings  should  have  frames  constructed  of 
reinforced concrete or steel.  The By‐Law was not enforceable,  but it  is understood that it  was 
widely  used  especially  in  the  larger  centres  of  Auckland,  Napier,  Wellington,  Christchurch  and 
Dunedin (Megget 2006). The provisions of NZSS no. 95 were confined to new buildings only, but 
the  draft  report  acknowledged  that  strengthening  of  existing  buildings  should  also  be 

  C1‐13
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

considered, and that alterations to existing buildings were required to comply (Davenport 2004). 
In 1939 and 1955 new editions of this By‐Law were published, and apart from suggesting in 1955 
that the seismic coefficient vary linearly from zero at the base to 0.12 at the top of the building 
(formerly  the  seismic  coefficient  was  uniform  up  the  height  of  the  building),  there  were  few 
significant changes (Beattie et al. 2008). It was not until 1965 that much of the recent research 
at  the  time  into  seismic  design  was  incorporated  into  legislation.  The  New  Zealand  Standard 
Model  Building  By‐Law  NZSS  1900  Chapter  8:1965  explicitly  prohibited  the  use  of  URM:  (a)  in 
Zone A; (b) of more than one storey or 15 ft (4.6 m) eaves height in Zone B; (c) of more than two 
storeys or 25 ft (7.6 m) eaves height in Zone C. These zones refer to the seismic zonation at the 
time, which have subsequently changed and evolved. Zone A consisted of regions of the highest 
seismic risk and Zone C consisted of regions of the lowest seismic risk (New Zealand Standards 
Institute 1965b). Again, the provisions of this By‐Law did not apply automatically and had to be 
adopted by local authorities. 

The 1965 code required that buildings be designed and built with “adequate ductility”, although 
further details were not given. The next version of the loadings code was published in 1976 as 
NZS 4203 (Standards Association of New Zealand 1976), and was a major advance on the 1965 
code. Most importantly, the 1976 loadings code was used in conjunction with revised material 
codes:  steel,  reinforced  concrete,  timber  and  reinforced  masonry,  which  all  required  specific 
detailing for ductility. Thus after the publication of this code in 1976, unreinforced masonry was 
explicitly prohibited as a building material throughout the whole of New Zealand. 

The  use  of  URM  was  implicitly  discouraged  through  legislation  from  as  early  as  1935,  and 
although  it  was  still  allowed  in  some  forms  after  1965,  observations  of  existing  building  stock 
show  its  minimal  use  from  1935  onwards,  especially  for  larger  buildings.  This  is  thought  to  be 
significantly attributable to the exceptionally rigorous quality of design and construction by the 
Ministry of Works at the time (Johnson 1963; Megget 2006). Although two storey URM buildings 
were permitted in Auckland (Zone C) after 1965, only three existing URM buildings in Auckland 
City  constructed  after  1940  have  been  identified.  All  three  are  single  storey  and  they  were 
constructed in 1950, 1953 and 1955. 

C1.5.1 Provisions for the Seismic Upgrade of Existing Buildings 
As  building  codes  were  being  developed  for  the  design  of  new  buildings,  attention  was  also 
given to the performance of existing buildings in earthquakes. The first time this was addressed 
in  legislation  was  Amendment  301A  to  the  1968  Municipal  Corporations  Act  (New  Zealand 
Parliament  1968).  This  Act  allowed  territorial  authorities,  usually  being  boroughs,  cities  or 
district  councils,  to  categorise  themselves  as  earthquake  risk  areas  and  thus  to  apply  to  the 
government  to  take  up  powers  to  classify  earthquake  prone  buildings  and  require  owners  to 
reduce or remove the danger. Buildings (or parts thereof) of high earthquake risk were defined 
as  being  those  of  unreinforced  concrete  or  unreinforced  masonry  with  insufficient  capacity  to 
resist earthquake forces that were 50% of the magnitude of those forces defined by NZS 1900 
Chapter 8:1965. If the building was assessed as being “potentially dangerous in an earthquake”, 
the council could then require the owner of the building within the time specified in the notice 
to remove the danger, either by securing the building to the satisfaction of the council, or if the 

C1‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

council  so  required,  by  demolishing  the  building.  Most  major  cities  and  towns  took  up  the 
legislation, and as an indication of the effect of this Act, between 1968 and 2003 Wellington City 
Council  achieved  strengthening  or  demolition  of  500  out  of  700  buildings  identified  as 
earthquake prone (Hopkins et al. 2008).  

Auckland City Council, in spite of having a low seismicity, took a strong interest in the legislation 
and this led to considerable activity in strengthening buildings (Boardman 1983). In Christchurch, 
a  moderately  high  seismic  zone,  the  City  Council  implemented  the  legislation,  but  adopted  a 
more  passive  approach,  generally  waiting  for  significant  developments  to  trigger  the 
requirements. In Dunedin, now seen to be of low seismic risk, little was done in response to the 
1968  legislation  although  strengthening  of  schools,  public  buildings  and  some  commercial 
premises was achieved. As a result, Dunedin has a high percentage of URM buildings compared 
with many other cities in New Zealand (Hopkins 2009). Megget (2006) and Thornton (2010) state 
that much of the strengthening in Wellington was accomplished with extra shear walls, diagonal 
bracing or buttressing and the tying of structural floors and walls together, and that many brittle 
hazards  such  as  parapets  and  clock  towers  had  been  removed  after  the  two  damaging  1942 
South Wairarapa earthquakes (M7.0 & M7.1) which were felt strongly in Wellington. Hopkins et 
al. (2008) noted that “there was criticism at the loss of many older heritage buildings and at the 
use of intrusive retrofitting measures which were not harmonious with the architectural fabric of 
the building (McClean 2009). At the same time, this did provide an opportunity in many cases for 
the land on which the old building was situated to be better utilised with new, larger and more 
efficiently designed structures.”  

“A major drawback of the 1968 legislation, which endured until 2004, surviving intact with the 
passage of the Building Act 1991, was that the definition of an earthquake prone building and 
the required level to which such buildings should be improved remained tied to the 1965 code. 
Most territorial authorities called for strengthening to one‐half or two‐thirds of the 1965 code, 
and many buildings which were strengthened to these requirements were subsequently found 
to fall well short of the requirements of later design standards for new buildings” (Hopkins et al. 
2008).  (Wellington  City  Council  found  that  in  January  2008,  of  97  buildings  which  had  been 
previously strengthened, 61 (63%) were subsequently identified as potentially earthquake prone 
(Bothara  et  al.  2008;  Stevens  and  Wheeler  2008)).    This  situation  was  recognised  by  the  New 
Zealand  Society  for  Earthquake  Engineering  (NZSEE),  who  were  also  concerned  about  the 
performance  of  more  modern  buildings,  particularly  after  the  observed  poor  performance  of 
similarly aged buildings in earthquakes in Northridge, California (1994) and Kobe, Japan (1995). 
NZSEE pushed for new, more up‐to‐date and wide‐ranging legislation. This push was supported 
by  the  Building  Industry  Authority,  later  to  become  part  of  the  Department  of  Building  and 
Housing,  and  a  new  Building  Act  came  into  effect  in  August  2004  (New  Zealand  Parliament 
2004). This brought in new changes as to what constituted an “Earthquake Prone Building”. In 
particular,  the  definition  of  an  earthquake  prone  building  was  tied  to  the  current  design 
standard of the time, and no longer to the design standard of any particular year. The legislation 
allowed any territorial authority that is satisfied that a building is earthquake prone to require 
the owner to take action to reduce or remove the danger. Each territorial authority was required 
to have a policy on earthquake prone buildings, and to consult publicly on this policy before its 

  C1‐15
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

adoption. Policies were required to address the approach and priorities and to state what special 
provisions  would  be  made  for  heritage  buildings.  The  2004  legislation  applied  to  all  types  of 
buildings  except  small  residential  ones,  (residential  buildings  were  excluded  unless  they 
comprised 2 or more storeys and contained 3 or more household units). 

As soon as the 1968 legislation came into effect to attempt to mitigate the effects of earthquake 
prone buildings, the New Zealand National Society for Earthquake Engineering set up a steering 
committee to provide a code of practice in an effort to assist local authorities to implement the 
legislation.  Since  the  first  draft  code  of  practice  published  by  the  NZNSEE  (1972),  several 
successive  publications  have  been  produced,  each  extending  on  the  previous  version.  These 
guidelines have been instrumental in helping engineers and territorial authorities to assess the 
expected  seismic  performance  of  existing  buildings  consistent  with  the  requirements  of  the 
legislation. Guidelines for assessing and upgrading earthquake risk buildings were published as a 
bulletin article in 1972 (NZNSEE 1972) and then separately published the following year, which 
became  colloquially  known  as  the  “Brown  Book”  (NZNSEE  1973).  This  document  provided 
guidelines  for  surveying  earthquake  risk  buildings  and  for  the  identification  of  particularly 
hazardous  buildings  and  features,  and  was  found  to  be  helpful  in  many  respects.  It  did  not 
establish  or  recommend  strength  levels  to  which  earthquake  prone  buildings  should  be 
upgraded, and thus standards varied from one area to another. It was implicit that strengthening 
be to more than half the  standard required in Chapter 8 of the 1965 NZSS  Model Building By‐
Law. 

In 1982, NZSEE established a study group to examine and rationalise the use of these guidelines 
and  to  produce  further  guidelines  and  recommendations.  This  activity  culminated  in  the 
publication in 1985 of what became known as the “1985 Red Book” (NZNSEE 1985). Again, this 
document  was  primarily  of  a  technical  nature  and  the  responsibilities  of  what  to  do  with 
buildings still rested with local authorities. The publication was intended to promote a consistent 
approach  throughout  New  Zealand  for  the  strengthening  of  earthquake  risk  buildings  and 
included a recommended level to which buildings should be strengthened plus the time scale to 
complete  the  requirements.  The  basic  objective  was  to  establish  a  reasonably  consistent 
reduction  of  the  overall  risk  to  life  which  the  country’s  stock  of  earthquake  risk  buildings 
represented. Based on overseas experiences, particularly in Los Angeles in Southern California, a 
philosophy  was  accepted  of  providing  owners  of  earthquake  risk  buildings  with  the  option  of 
interim  securing  to  gain  limited  extension  of  useful  life,  after  which  the  building  should  be 
strengthened to provide indefinite future life. The design of interim securing systems was to be 
based on minimum seismic coefficients which represented two‐thirds of those specified in NZSS 
1900,  Chapter  8  (New  Zealand  Standards  Institute  1965b).  For  “permanent”  strengthening 
measures,  it  was  recommended  that  the  building  be  strengthened  to  the  standard  of  a  new 
building,  but  with  the  design  lateral  forces  reduced  depending  on  the  occupancy  classification 
and type of strengthening system. This publication was widely used by territorial authorities and 
designers. 

In 1992 the NZNSEE again set up a study group to review the 1985 publication, and this resulted 
in  another  publication,  which  similarly  became  colloquially  known  as  the  “1995  Red  Book” 
(NZNSEE 1995). This document extended the approach and content of its predecessor and took 

C1‐16   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

into  account  the  changing  circumstances,  technical  developments  and  improved  knowledge  of 
the  behaviour of URM buildings in earthquakes. In  particular,  earthquake risk buildings in  that 
document  were  taken  to  include  all  unreinforced  masonry  buildings,  and  not  just  those  which 
were defined as “earthquake prone” in terms of the Building Act of the time, which still referred 
back to the 1965 code. Another key difference from the 1985 Red Book was that a single stage 
approach  to  strengthening  was  suggested,  in  contrast  to  the  two  stage  securing  and 
strengthening procedure of the 1985 document. The guidelines also highlighted the differences 
in  analysis  for  unsecured  buildings  in  comparison  to  a  building  which  has  positive  connections 
between  floor,  roof  and  wall  elements,  and  cantilever  elements  secured  or  removed.  Greater 
emphasis  was  placed  on  the  assessment  of  the  likely  performance  of  URM  buildings  in  their 
original  form  and  with  interim  securing  only  in  place,  as  distinct  from  the  performance  of  the 
building  with  any  strengthening  work  which  was  subsequently  found  to  be  necessary. 
Furthermore,  material  strengths  were  given  in  ultimate  limit  state  format.  Historic  or  heritage 
buildings were not given any specific or separate treatment, and the guidelines stated that “the 
issues of risk versus the practicalities of strengthening associated with historic buildings require 
evaluation on a case‐by‐case basis. The principal problem with such buildings is that the greater 
the level of lateral forces that is specified for strengthening, the greater the risk of damaging the 
fabric that is to be preserved” (NZNSEE 1995). 

After  the  introduction  of  a  new  Building  Act  in  2004  (New  Zealand  Parliament  2004)  the 
Department  of  Building  and  Housing  supported  NZSEE  in  producing  a  set  of  guidelines, 
“Assessment  and  Improvement  of  the  Structural  Performance  of  Buildings  in  Earthquakes” 
(NZSEE 2006). This was a major review and extension of previous guidelines, to account for the 
wider scope of the proposed new legislation. Prior to enacting The Building Act 2004, the term 
‘earthquake risk building’ related only to URM buildings, but now an earthquake prone building 
could be of any material; steel, concrete, timber or masonry. The level of risk posed by buildings 
constructed as recently as the 1970s was more widely appreciated, in particular the inadequate 
performance  of  reinforced  concrete  structures  due  to  deficient  detailing.  Definitions  of 
“earthquake prone” and “earthquake risk” also changed. Essentially, earthquake prone buildings 
were  defined  as  those  with  one‐third  or  less  of  the  capacity  of  a  new  building.  While  The 
Building  Act  itself  still  focussed  on  buildings  of  high  risk  (earthquake  prone  buildings),  NZSEE 
considered  earthquake  risk  buildings  to  be  any  building  which  is  not  capable  of  meeting  the 
performance  objectives  and  requirements  set  out  in  its  guidelines,  and  earthquake  prone 
buildings  formed  a  subset  of  this.  Moreover,  NZSEE  expressed  a  philosophical  change,  in 
acknowledgment of the wide range of options for improving the performance of structures that 
are  found  to  have  high  earthquake  risk.  Some  of  these  options  involve  only  the  removal  or 
separation of components, and others affect a relatively small number of members. In line with 
performance‐based design thinking, the term “strengthening” was replaced with “improving the 
structural performance of”, highlighting the fact that such solutions as base isolation were not 
“strengthening” but were an effective way of improving structural performance. 

The  2006  guidelines  (NZSEE  2006)  provided  both  an  initial  evaluation  procedure  (IEP)  and  a 
detailed  analysis  procedure.  The  IEP  can  be  used  for  a  quick  and  preliminary  evaluation  of 
existing buildings, and takes into account the building form, natural period of vibration, critical 

  C1‐17
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

structural weaknesses  (vertical irregularity, horizontal irregularity, short columns and  potential 


for  building‐to‐building  impact)  and  the  design  era  of  the  building.  Based  on  this  analysis,  if  a 
territorial  authority  determines  a  building  to  be  earthquake  prone,  the  owner  may  then  be 
required to take action to reduce or remove the danger, depending on the territorial authority’s 
policy  and  associated  timeline.  The  level  required  to  reduce  or  remove  the  danger  is  not 
specified  in  The  Building  Act  or  its  associated  regulations.  The  Department  of  Building  and 
Housing  suggested  that  territorial  authorities  adopt  as  part  of  their  policies  that  buildings  be 
improved to a level “as near as is reasonably practical to that of a new building”. Most territorial 
authorities  took  the  view  that  they  could  not  require  strengthening  beyond  one‐third  of  new 
building standard, but a significant number included requirements to strengthen to two‐thirds of 
new  building  standard,  in  line  with  NZSEE  recommendations.  In  developing  policies  on 
earthquake  prone  buildings,  most  territorial  authorities  recognised  the  need  for  special 
treatment and dialogue with owners when heritage buildings were affected. It is believed by the 
Department of Building and Housing that “the legislation has required each local community to 
put  earthquake  risk  reduction  on  its  agenda,  and  has  left  the  local  community  to  develop 
appropriate policies that reflect local conditions and perceptions of earthquake risk” (Hopkins et 
al. 2008). 

C1.6 Acknowledgements 
The assistance of David Hopkins, Patrick Cummuskey, Richard Deakin, Claire Stevens, Katherine 
Wheeler, Neil McLeod and Bruce Mutton in providing information is gratefully acknowledged.  

C1.7 References 
Beattie, G. J., Megget, L. M. and Andrews, A. L. (2008). "The historic development of earthquake 
engineering  in  New  Zealand"  14th  World  Conference  on  Earthquake  Engineering,  Beijing, 
China, 12 ‐ 17 Oct. 
Binda, L. (2006). "The difficult choice of materials used for the repair of brick and stone masonry 
walls"  The  First  International  Conference  on  Restoration  of  Heritage  Masonry  Structures, 
Cairo, Egypt, 24 ‐ 27 April. 
Binda, L. and Saisi, A. (2005). "Research on historic structures in seismic areas in Italy." Progress 
in Structural Engineering and Materials, 7(2), 71‐85. 
Boardman,  P.  R.  (1983).  "Case  studies:  earthquake  risk  buildings.  Restoration  of  Old  Auckland 
Customhouse."  Bulletin  of  the  New  Zealand  National  Society  for  Earthquake  Engineering, 
16(1), 73 ‐ 79. 
Bothara, J. K., Jury, R. D., Wheeler, K. and Stevens, C. (2008). "Seismic assessment of buildings in 
Wellington:  Experiences  and  challenges"  14th  World  Conference  on  Earthquake 
Engineering, Beijing, China, 12 ‐ 17 Oct. 
Brittenden  Collection  (1910).  "View  south‐east  from  the  Cathedral  tower"  CHAC/CM  1199, 
Christchurch. 
Christchurch  City  Libraries  (2006).  "Early  Christchurch." 
<http://christchurchcitylibraries.com/heritage/earlychristchurch>. (18 October, 2010). 
Coxhead, F. A. (1885). "Victorian Christchurch" CM 182, Christchurch. 

C1‐18   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Cull,  J.  E.  L.  (1931).  Report  of  the  Building  Regulations  Committee,  Report  to  the  New  Zealand 
House of Representatives, H‐21. 
Dalley, B. and McLean, G. (2005). Frontier of Dreams; The Story of New Zealand, Hodder Moa, 
Auckland. 
Davenport,  P.  N.  (2004).  "Value  of  assessing  seismic  vulnerability."  New  Zealand  Society  for 
Earthquake Engineering Conference, Rotorua, New Zealand, 19 ‐ 21 March. 
Davey, R. A. and Blaikie, E. L. (2010). "Predicted and observed performance of masonry parapets 
in the 2007 Gisborne earthquake" 2010 Annual Conference of the New Zealand Society for 
Earthquake Engineering, Wellington, New Zealand, 26 ‐ 28 March. 
Dizhur,  D.,  Ismail,  N.,  Knox,  C.,  Lumantarna,  R.  and  Ingham,  J.  M.  (2010).  "Performance  of 
unreinforced  and  retrofitted  masonry  buildings  during  the  2010  Darfield  earthquake." 
Bulletin of the New Zealand Society for Earthquake Engineering, 43(4), 321‐339. 
Dowrick,  D.  J.  (1994).  "Damage  and  intensities  in  the  magnitude  7.8  1929  Murchison,  New 
Zealand,  earthquake."  Bulletin  of  the  New  Zealand  National  Society  for  Earthquake 
Engineering, 27(3), 190‐204. 
Dowrick,  D.  J.  (1998).  "Damage  and  intensities  in  the  magnitude  7.8  1931  Hawke’s  Bay,  New 
Zealand,  earthquake."  Bulletin  of  the  New  Zealand  National  Society  for  Earthquake 
Engineering, 31(3), 139‐163. 
Dowrick, D. J. and Rhoades, D. A. (1998). "Magnitudes of New Zealand earthquakes, 1901‐1993." 
Bulletin of the New Zealand National Society for Earthquake Engineering, 31(4), 260‐280. 
Francois‐Holden,  C.,  Bannister,  S.,  Beaven,  J.,  Cousins,  J.  F.,  B.,  McCaffrey,  R.,  McVerry,  G., 
Reyners,  M.,  Ristau,  J.,  Samsonov,  S.  and  Wallace,  L.  (2008).  "The  Mw  6.6  Gisborne 
earthquake of 2007: Preliminary records and general source characterisation." New Zealand 
Society for Earthquake Engineering Bulletin, 41(4), 266‐277. 
Goodwin,  C.  O.  (2008).  "Architectural  considerations  in  the  seismic  retrofit  of  unreinforced 
masonry  heritage  buildings  in  New  Zealand."  Master  of  Architecture,  M.  Arch  Thesis, 
Department of Architecture and Planning, The University of Auckland, New Zealand. 
Goodwin,  C.  O.,  Tonks,  G.  and  Ingham,  J.  M.  (2009).  "Identifying  heritage  value  in  URM 
buildings." Journal of the Structural Engineering Society New Zealand, 22(2), 16‐28. 
Grapes, R. and Downes, G. (1997). "The 1855 Wairarapa, New Zealand, earthquake: Analysis of 
historical  data."  Bulletin  of  the  New  Zealand  National  Society  for  Earthquake  Engineering, 
30(4), 271‐368. 
Haarhoff, E. (2003). Architecture of Central Auckland, Balasoglou Books. 
Hodgson, T. (1992). The Heart of Colonial Auckland 1865‐1910, Random Century. 
Hopkins,  D.  C.  (2009).  "Earthquakes  and  Existing  Buildings:  New  Zealand  Experience  1968  to 
2008" ATC & SEI Conference on Improving the Seismic Performance of Existing Buildings and 
Other Structures, San Francisco, California, 9 ‐ 11 Dec. 
Hopkins,  D.  C.  (2002).  "Report  on  cost  benefit  of  improving  the  performance  of  buildings  in 
earthquake." Department of Internal Affairs, Wellington. 
Hopkins,  D.  C.,  Stannard,  M.,  Lawrance,  G.  and  Brewer,  I.  (2008).  "Strengthening  buildings  for 
earthquake implementing New Zealand legislation" 14th World  Conference on Earthquake 
Engineering, Beijing, China, 12 ‐ 17 Oct. 

  C1‐19
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

Hopkins,  D.  C.  and  Stuart,  G.  (2003).  "Strengthening  existing  New  Zealand  buildings  for 
earthquake, An analysis of cost benefit using annual Probabilities" 2003 Pacific Conference 
on Earthquake Engineering, Christchurch, New Zealand, 13 ‐ 15 February. 
Ingham,  J.  M.  and  Griffith,  M.  (2011).  "Performance  of  unreinforced  masonry  buildings  during 
the  2010  Darfield  (Christchurch,  NZ)  earthquake."  Australian  Journal  of  Structural 
Engineering, 11(3), February 2011. 
Jacobs, W. (1985). The Birth of New Zealand, A Nation’s Heritage, Kowhai Publishing Ltd. 
Johnson,  J.  A.  R.  (1963).  "Earthquake  engineering  in  New  Zealand."  New  Zealand  Engineering, 
18(9), 305. 
King, P. (2003). The Penguin History of New Zealand, Auckland. 
Lourenço, P. B. (2006). "Recommendations for restoration of ancient buildings and the survival 
of a masonry chimney." Construction and Building Materials, 20(4), 239‐251. 
Magenes,  G.  (2006).  "Masonry  building  design  in  seismic  areas:  recent  experiences  and 
prospects from a european standpoint." 1st ECEES, Geneva, Switzerland, 3 ‐ 8 September. 
McClean,  R.  (2009).  Toward  improved  national  and  local  action  on  earthquake‐prone  heritage 
buildings, New Zealand Historic Places Trust Pouhere Taonga, Wellington, New Zealand. 
Megget,  L.  (2006).  "From  Brittle  to  Ductile:  75  Years  of  Seismic  Design  in  New  Zealand"  New 
Zealand  Society  for  Earthquake  Engineering  Conference,  Napier,  New  Zealand,  10  ‐  12 
March. 
New Zealand Parliament (2004). Building Act 2004, Department of Building and Housing ‐ Te Tari 
Kaupapa  Whare,  Ministry  of  Economic  Development,  New  Zealand  Government, 
Wellington, New Zealand, Date of assent: 24 August 2004. 
New  Zealand  Parliament  (1968).  Municipal  Corporations  Act,  incorporating  Amendment  301A, 
The  Department  of  Internal  Affairs  ‐  Te  Tari  Taiwhenua,  New  Zealand  Government, 
Wellington, New Zealand, Date of assent: 1968. 
New Zealand Standards Institute (1935). NZSS No. 95:1935, Model Building By‐Law, New Zealand 
Standrds Institute, Wellington, New Zealand. 
New  Zealand  Standards  Institute  (1965a).  NZS  1900:1965,  Model  Building  Bylaw,  New  Zealand 
Standards Institute, Wellington, New Zealand. 
New  Zealand  Standards  Institute  (1965b).  NZSS  1900:1965,  Model  Building  By‐Law.  Chapter  8: 
Basic Design Loads, New Zealand Standrds Institute, Wellington, New Zealand. 
NZNSEE  (1972).  "Classification  of  high  earthquake  risk  buildings."  Bulletin  of  the  New  Zealand 
National Society for Earthquake Engineering, 5(2). 
NZNSEE  (1973).  Recommendations  for  the  classification  of  high  earthquake  risk  buildings,  New 
Zealand National Society for Earthquake Engineering, Wellington, New Zealand. 
NZNSEE  (1985).  Recommendations  and  guidelines  for  classifying,  interim  securing  and 
strengthening earthquake risk buildings, [1985 Red Book], New Zealand National Society for 
Earthquake Engineering. 
NZNSEE (1995). Draft guidelines for assessing and strengthening earthquake risk buildings, [1995 
Red Book], New Zealand National Society for Earthquake Engineering. 
NZSEE  (2006).  Assessment  and  improvement  of  the  structural  performance  of  buildings  in 
earthquakes: Recommendations of a NZSEE study group on earthquake risk buildings, New 
Zealand Society for Earthquake Engineering. 

C1‐20   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Oliver, J. (2006). John Oliver's Brick Book, Lifetime Books, Auckland. 
PapersPast  (2010).  "Official  report  on  public  buildings."  Star,  Issue  6333,  3  September, 
<http://paperspast.natlib.govt.nz/cgi‐bin/paperspast?a=d&d=TS18880903.2.25&cl=CL2.188
8.09.03>. (20th October, 2010). 
Russell,  A.  P.  and  Ingham,  J.  M.  (2010).  "Prevalence  of  New  Zealand's  unreinforced  masonry 
buildings." Bulletin of the New Zealand Society for Earthquake Engineering, 43(3), 192‐207. 
Russell,  A.  P.  and  Ingham,  J.  M.  (2011).  "Characterisation  of  New  Zealand’s  unreinforced 
masonry building stock." Earthquake Spectra, xx(xx), xxxx, xx‐yy. 
Shaw, P. (2003). A History of New Zealand Architecture, Hodder Moa Beckett Publishers Ltd. 
Stacpoole,  J.  and  Beaven,  P.  (1972).  New  Zealand  Art;  Architecture  1820‐1970,  A.  H.  &  A.  W. 
Reed, Wellington, New Zealand. 
Standards Association of New Zealand (1976). NZS 4203: Code of Practice for General Structural 
Design  and  Design  Loadings  for  Buildings,  Standards  Association  of  New  Zealand, 
Wellington, New Zealand. 
Stevens, C. M. and Wheeler, K. E. (2008). "Implementing earthquake prone building policy under 
the  Building  Act  2004  ‐  Wellington  City's  Approach"  New  Zealand  Society  for  Earthquake 
Engineering Conference,Wairakei, New Zealand, 11 ‐ 13 April. 
Stirling, M., Gerstenberger, M., Litchfield, N., McVerry, G. H., Smith, W., Pettinga, J. and Barnes, 
P. (2008). "Seismic hazard of the Canterbury region, New Zealand: New earthquake source 
model  and  methodology."  Bulletin  of  the  New  Zealand  National  Society  for  Earthquake 
Engineering, 41(2), 51‐67. 
Thornton, A.  W. (2010). "Twenty‐five years of strengthening Wellington." New Zealand Society 
for Earthquake Engineering Conference, Te Papa, Wellington, New Zealand, 26 ‐ 28 March. 
Wilson, J. (1984). Lost Christchurch, Te Waihora Press, Springston, New Zealand. 
 

  C1‐21
 
  Section C1 ‐ History and Prevalence of Unreinforced Masonry Buildings in New Zealand 
 
 

C1‐22   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C2 ‐ Material Properties of Masonry Walls 

C2.1 Notation 
c  Bed‐joint cohesion, MPa 
Em  Masonry modulus of Elasticity, MPa 
f’b  Average brick compressive strength, MPa 
f’bl  Lower characteristic brick compressive strength, MPa 
f’fb  Flexural bond strength, MPa 
f’j  Average mortar compressive strength, MPa 
f’jl  Lower characteristic mortar compressive strength, MPa 
f’m  Average masonry compressive strength, MPa 
MoR  Brick modulus of rupture strength, MPa 
 mb  Mass of brick units, kg 
m j    Mass of mortar, kg   
N  Axial compression stress, MPa 
νb  Volume of brick units, m3 
νj  Volume of mortar, m3 
µf  Bed‐joint coefficient of friction 
ρm  Masonry density, kg/m3 
τ  Bed‐joint shear stress, MPa 

C2.3 In‐situ and Extracted Sample Testing 

C2.3.1 Introduction 
Whilst  many  aspects  associated  with  the  seismic  response  of  URM  buildings  are  significantly 
influenced by characteristics such as boundary conditions and the behaviour of connections, the 
accurate determination of material properties will clearly lead to improved seismic assessments, 
less  conservative  retrofit  designs  and  superior  numerical  models  describing  the  seismic 
behaviour of URM buildings. However, the non‐homogenous nature of masonry, combined with 
the  age  of  URM  buildings,  make  it  difficult  to  accurately  predict  the  material  properties  of 
masonry walls. 

It is recommended that, whenever a project permits, field sampling or field testing is conducted. 
Field sampling refers to the extraction of samples from an existing building and testing them in a 
laboratory, while field testing refers to testing for material properties in‐situ. A set of techniques 
are described below that can be used to determine masonry material properties. 

Individual brick units and mortar samples shall be tested as per C2.3.2 and C2.3.3 when sampling 
of large building sections is not permitted. Masonry properties shall then be predicted using the 
obtained brick and mortar properties as per Section 2.5.  When field sampling  or testing is  not 
possible,  the  recommendations  detailed  in  Section  2.6  shall  be  used  to  predict  the  masonry 
constituent material properties. 

  C2‐1
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

C2.3.2 Brick Properties 
Individual brick units shall be extracted for the half brick compression test ASTM C 67‐03a (ASTM 
2003c). The extracted brick units shall be cut into halves and capped using gypsum plaster prior 
to compression testing. Figure C2‐1 shows brick sample preparation and the brick compression 
testing. 

     
(a) Brick cutting process  (b) Gypsum plaster capping  (c) Half brick comp. test 

Figure C2‐1: Steps to determine brick properties 

C2.3.3 Mortar Properties 
Irregular  mortar  samples  shall  be  extracted  for  laboratory  testing.  The  method  to  determine 
mortar compressive strength is detailed in ASTM C  109‐08 (ASTM 2008).  This method involves 
testing of 50 mm cube mortar samples, which generally are not attainable in existing buildings as 
most mortar joints are only 12 to 18 mm thick. Consequently, irregular mortar samples shall be 
cut into approximately cubical sizes with two parallel sides (top and bottom). The height of the 
mortar samples shall exceed 15 mm in order to satisfactorily maintain the proportion between 
sample  size  and  the  maximum  aggregate  size.  The  prepared  samples  shall  be  capped  using 
gypsum  plaster  to  ensure  a  uniform  stress  distribution  and  tested  in  compression  (Valek  and 
Veiga 2005).  

The  height  to  least  lateral  dimension  (h/t)  ratio  of  the  mortar  samples  shall  be  measured  and 
used  to  determine  the  mortar  compressive  strength  correction  factors  as  in  Table  C2‐1.  The 
compression test result shall be divided by the corresponding correction factors listed in Table 
C2‐1, and the average corrected strength is equal to the average mortar compressive strength, 
f’j.  Figure  C2‐2  shows  examples  of  irregular  mortar  samples  and  the  mortar  compression  test. 
See Section C2.5.3 for further details regarding the correction factors and the influence of height 
to  thickness  ratio  on  mortar  compressive  strength.  When  conducting  tests  on  laboratory 
manufactured  samples,  50 mm  mortar  cubes  shall  be  made,  left  to  cure  under  room 
temperature  (±20 °C)  for  28  days  and  tested  in  compression  following  the  mortar  cube 
compression test ASTM C 109‐08 (ASTM 2008). 

 
Table C2‐1: Height to thickness ratio correction factor for mortar compressive strength 

h/t ratio  0.6  0.7  0.8  0.9  1.0  1.1  1.2 

Correction factor  1.3  1.225  1.15  1.075  1.00  0.925  0.85 

C2‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

   

(a) Irregular mortar samples  (b) Irregular mortar compression 
test 
Figure C2‐2: Determination of mortar compression strength 

C2.3.4 Masonry Properties 

C2.3.4.1 Masonry Compressive Strength and Stiffness 

Masonry  assemblage  (prism)  samples  shall  be  extracted  for  laboratory  testing.  This  extraction 
must be conducted using a masonry chainsaw, operated by experienced personnel or by a hired 
cutting contractor. The prism samples shall be single leaf and at least three bricks high. Samples 
that are two leaf thick or more are to be cut into single leaf masonry prism samples. Rendering 
plaster shall be removed from both sides of the sample, if present. The prepared samples shall 
be capped using gypsum plaster to ensure uniform stress distribution and tested in compression 
following ASTM C 1314‐03b (ASTM 2003a).  

Laboratory  calibrated  displacement  measurement  devices  may  be  attached  on  the  masonry 
prisms during the compression tests. At least two measurement devices shall be incorporated to 
record  displacements  at  opposing  faces,  and  their  gauge  lengths  shall  cover  the  distance  from 
the middle of the top brick to the middle of the bottom brick, which furthermore shall be used 
to  derive  the  masonry  stress‐strain  relationship  and  Modulus  of  Elasticity,  Em.  The  stress  and 
strain values considered in the calculation of Em shall be those between 0.05 and 0.70 times the 
masonry  compressive  strength  (f’m).  Figure  C2‐3  shows  examples  of  sample  extraction, 
arrangement of displacement gauges and the prism compression test. 

   
(a) Sample extraction  (b) Prism with displacement  (c) Prism compression test 
gauges 
Figure C2‐3: Preparation for prism compression test 

  C2‐3
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

C2.3.4.2 Masonry Flexural Bond Strength 

Two  brick  high  masonry  prisms  shall  be  extracted  and  subjected  to  the  flexural  bond  test 
AS 3700‐2001  (Australian  Standards  2001).  The  removal  of  rendering  plaster  from  the  sides  of 
the sample is necessary prior to performing the flexural bond  test.  Samples that are two  leafs 
thick or more shall be cut into single leaf masonry prism samples. Alternatively, the flexural bond 
test  may  be  conducted  in‐situ  if  deemed  to  be  more  practical  (refer  to  Figure  C2‐4  (b)).  The 
flexural bond test is shown in Figure C2‐4. 

 
(a) Laboratory flexural bond test  (b) In‐situ flexural bond 
test 
Figure C2‐4: Masonry flexural bond test 

C2.3.4.3 Masonry Bed‐joint Shear Strength 

The in‐situ bed‐joint shear test ASTM C 1531‐03 (ASTM 2003b) shall be conducted to determine 
the  masonry  bed‐joint  properties.  Alternatively,  three  brick  high  masonry  prisms  shall  be 
extracted  for  laboratory  testing  following  the  triplet  shear  test  BS  EN  1052‐3  (BSI  2002).  The 
triplet  shear  test  shall  be  conducted  whilst  applying  axial  compression  loads  of  approximately 
0.2 MPa,  0.4 MPa  and  0.6 MPa.  At  least  three  masonry  triplet  samples  shall  be  tested  at  each 
level of axial compression. Rendering plaster shall be removed from both sides of the sample, if 
present. Masonry samples that are two leafs thick or more shall be cut into single leaf masonry 
prism samples. Bed‐joint shear tests in‐situ and in the laboratory are shown in Figure C2‐5. 

     
(a) Laboratory shear triplet  (b) In‐situ shear test without  (c) In‐situ shear test with flat 
test  flat jacks  jacks 
Figure C2‐5: In‐situ and laboratory bed‐joint shear test 

C2‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C2.4 Brick and Mortar Field Assessment Procedure 
The scratch test to determine brick and mortar properties shall be conducted as follows: 

(1) Prepare the appropriate scratch test tools. 
(2) Use 400 grit sand paper to clean and level the surface of the brick unit or mortar sample. 
For  brick  units  in  particular,  ensure  that  the  degraded  exterior  of  the  sample  is  suitably 
removed  and  the  interior  of  the  brick  is  exposed.  Refer  to  Figure  C2‐6  for  an  example  of 
exposed and unexposed brick surfaces. 
(3) Begin  by  using  a  scratch  tool  having  the  lowest  scratch  number  and  apply  just  enough 
pressure to ensure a firm contact on the brick or mortar surface at a 70 degree angle from 
the test material surface. 
(4) With uniform pressure, draw the scratch test tool along the test material surface for at least 
20 mm. 
(5) If no scratch is formed use the next scratch tool specified in Table 2‐1 and Table 2‐3. 
(6) Repeat step (5) until a scratch is formed. 
(7) Repeat step (1) to (7) at least six times at different locations within a wall section. 
(8) Use Table 2‐1 or Table 2‐3 to determine the brick or mortar scratch index. 
(9) The  average  scratch  index  of  the  material  shall  be  equal  to  the  average  of  the  six  scratch 
tests.   
(10) The average and lower characteristic brick compressive strength shall be obtained based on 
the average scratch index using Table 2‐2. 
(11) The mean and lower characteristic mortar compressive strength shall be obtained based on 
the average scratch index using Table 2‐4. 
(12) Use linear interpolation when required. 

Note that for a scratch test on brick samples, the scratch test shall create visible indentation on 
the brick surface.  

Note that for a scratch test on mortar samples, the definition “Easily scratches using fingernail” 
(scratch index of 1.5 in Table 2‐3) applies when the mortar can be scratched using minimal effort 
and the particles become loose as the fingernail is drawn along the sample. A scratch index of 2 
corresponds to the scenario when a fingernail leaves an indented mark whilst the mortar is not 
heavily  raked.  A  scratch  index  of  2  is  commonly  indicated  by  a  worn  fingernail  although  the 
mortar surface is scratched. See Section C2.3.1 for more details on the scratch test. 

Most  Mortars  have  a  scratch  index  below  2.5  (aluminium).  Mortars  that  cannot  be  scratched 
using  aluminium  are  likely  to  be  cement  based  mortars,  and  mechanical  tests  according  to 
Section  C2.3.3  are  strongly  recommended  when  this  type  of  mortar  is  present,  because  these 
mortars were not included within the scope of the study reported here. 

  C2‐5
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

Exposed  Unexposed 
interior  interior 
surface  surface 

 
Figure C2‐6: Difference between exposed and unexposed brick surface 

C2.5 Additional Information 

C2.5.1 Scratch Test Procedure 
The  material  assessment  technique  detailed  in  Section  2.2  is  a  departure  from  the  technique 
detailed  in  the  2006  NZSEE  guideline  (NZSEE  2006).  The  reasons  for  the  departure  and  the 
background research conducted in order to support the introduction of the new technique are 
discussed below.  

C2.5.1.1 Recommendations Provided in the 2006 NZSEE Guideline 

The NZSEE (2006) guideline provided the recommended masonry material strength parameters 
for preliminary assessments as in Table C2‐2.  

   

C2‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Table C2‐2: Parameters used in the NZSEE (2006) guideline 

Material  Visual Characteristic and hand tests 

Mortar 

Stiff  High Portland cement content. Punch test < 10 mm 

Firm  Lime based. Punch test < 20 mm 

Soft  Lime binding, possibly mildly leached, can be raked out of joint, but 
stays bound. Punch test < 30 mm 

Non‐cohesive  Lime‐based mortar that is heavily leached and weathered. Sand like, 
easily raked out by hand, aggregate is unbound. Not suitable for 
earthquake resistance 

Bricks 

Hard  Dense, hard surface, well fired, dark reddish brown 

Stiff  Common brick, can be scored with a knife, red. Lower figures if split 

Soft  Weathered, pitted, distinct colour variation with depth, probably 
under fired, bright orange 
 

As detailed in Table C2‐2, the field assessment procedure for mortar characterisation measured 
the  penetration  depth  of  a  standard  carpenter  3 mm  diameter  nail  driven  with  a  standard 
carpenter hammer for 6 blows. This test was difficult to quantify as the nail penetration depth is 
highly dependent on the force applied by the hammer blow.  

The  brick  unit  characterisation  technique  detailed  in  the  NZSEE  (2006)  guideline  was  heavily 
reliant on the brick physical attributes and visual appearance. Lumantarna (2011) concluded that 
there is no direct relationship between brick unit colour and compressive strength. It was found 
that brick colour is influenced by the presence of minerals such as iron oxides and calcium oxides 
(Cultrone et al. 2005; Kreimeyer 1987), while brick compressive strength is highly dependent on 
the  firing  temperature  and  level  of  porosity  (Elert  et  al.  2003;  Karaman  et  al.  2006;  Tite  and 
Maniatis 1975). Therefore, the use of brick colour as a classification parameter is invalid. 

Figure  C2‐7  shows  a  plot  of  brick  unit  compressive  strength  against  the  Red  Green  Blue  (RGB) 
colour model, which commonly is used to represent a wide array of colours. Figure C2‐7 shows 
that there is no relationship between each of the three different colour spectrums and the brick 
unit  compressive  strength.  In  addition,  Figure  C2‐8  shows  the  relationship  between  brick  unit 
compressive strength and the visible brick colour. Although the visible brick colour is subjective, 
Figure C2‐8 shows that there is no discernable relationship between brick visible colour and brick 
compressive strength. 

  C2‐7
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

350

300

250
Intensity

200

150

100
Red
50 Green
Blue
0
0 10 20 30 40 50
Compressive Strength (MPa)  
Figure C2‐7: Colour spectrum intensity vs. compressive strength plot 

50
45
Compressive Strength (MPa)

40
35
30
25
20
15
10
5
0

 
Figure C2‐8: Brick compressive strength vs. visible colour plot 

C2.5.1.2 Developed Assessment Technique 

Alternative  assessment  techniques  were  investigated  due  to  the  inadequacy  of  the 
recommendations in the NZSEE (2006) guideline. For brick unit characterisation, non‐destructive 
testing techniques including ultrasonic pulse velocity, Schmidt hammer and porosity tests were 
studied (Lumantarna 2011). Although some of these techniques to a certain extent enabled the 
characterisation  of  brick  units,  conducting  these  tests  was  not  practical.  The  ultrasonic  pulse 
velocity  test  involved  a  set  of  tools  such  as  a  pundit,  a  transmitter  and  a  receiver,  while  the 
Schmidt hammer test required a Schmidt hammer, which was not widely available. Extraction of 
brick  units  was  necessary  to  perform  an  accurate  ultrasonic  pulse  velocity  test,  as  an  in‐situ 
ultrasonic pulse velocity test would encounter interference due to discontinuity in the brickwork 
between  the  wall  leafs.  The  porosity  test  ASTM  C  20‐00  (ASTM  2000)  also  required  brick  unit 
extraction. For the mortar, the characterisation technique detailed in the NZSEE (2006) guideline 
was deemed to be insufficient.  

C2‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Hardness has often been used to measure the mechanical strength of metals, rocks and minerals 
(Shalabi  et  al.  2007;  Tabor  1956),  and  therefore  the  scratch  test  based  on  the  Mohs  hardness 
scale was nominated as an alternative assessment technique. Principally, the scratch test based 
on  the  Mohs  hardness  scale  is  similar  to  the  abrasion  test  described  by  Shalabi  et  al.  (2007), 
where  the  resistance  of  one  material  against  another  material  of  different  hardness  is  tested. 
Shalabi  et  al.  (2007)  also  reported  that  there  is  a  linear  relationship  between  the  compressive 
strength of rocks and their abrasion hardness. 

The Mohs hardness scale uses 10 minerals with different hardness values, where Mohs numbers 
of  1  to  10  are  used  to  rank  the  hardness  of  the  different  minerals  (Tabor  1956).  Although  the 
Mohs  minerals  in  Table  C2‐3  are  not  commonly  available,  there  are  materials  (denoted  as 
‘Equivalent  Materials’  in  Table  C2‐3)  which  have  similar  hardness  values  to  the  Mohs  minerals 
(MineralTown  2010;  Nicholson  and  Shaw  2000).  Due  to  their  accessibility  for  use  by 
practitioners,  these  equivalent  materials  were  investigated,  and  the  scratch  index  assigned  to 
the tested sample was equal to the Moh’s number of the tool that scratched it. 

 
Table C2‐3: Mohs hardness scale 

Mohs Number  Mineral  Equivalent Material 

1  Talc  Baby powder 

2  Gypsum  Fingernail 

3  Calcite  Copper coin 

4  Flourspar  Iron nail 

5  Apatite  Glass 

6  Feldspar  Folding pocket knife 

7  Quartz  Kitchen steel knife 

8  Topaz  Sandpaper 

9  Corundum  Ruby 

10  Diamond  Synthetic diamond 


 

Individual brick units were collected from numerous historic buildings throughout New Zealand 
and  were  cut  into  halves  for  laboratory  testing.  These  half  bricks  were  capped  using  gypsum 
plaster,  subjected  to  the  Mohs  scratch  test  and  were  subsequently  tested  in  compression  in 
accordance  with  C2.3.2  to  determine  the  direct  relationships  between  the  scratch  test  results 
and the brick unit compressive strengths. It was found that the strongest brick units used in the 
experimental  programme  were  scratched  using  an  iron  nail.  However,  the  increment  from 
fingernail (Mohs number 2) to copper coin (Mohs number 3) was found to be too wide, as most 
brick units were scratched using a copper coin, whilst none were scratched using a fingernail. Shi 
and  Atkinson  (1990)  reported  that  aluminium  has  a  lower  hardness  value  than  copper,  and 

  C2‐9
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

therefore it was decided that an aluminium pick (given a Mohs number of 2.5) could be used as 
an  intermediate  material  between  fingernail  and  copper  coin.  Figure  C2‐9  shows  the  brick 
compressive  strength‐scratch  index  relationship.  The  box  and  whisker  plots  (see  Figure  C2‐9) 
were calculated according to Peck et al. (2009).  

2.5: aluminium pick 
Median = 14.4 MPa  
50

Lower Quartile = 10.8 MPa 
Compressive Strength (MPa)

Sample Size = 100 
40

3.0: 10 cent copper coin 
30

Median = 26.9 MPa  
Lower Quartile = 21.7 MPa 
20

Sample Size = 45      
4.0: iron nail 
10

Median = 35.6 MPa  
Lower Quartile = 28.6 MPa 
2.5 3 4
Sample Size = 30     
Scratch Index  
Figure C2‐9: Plot of brick compressive strength vs. scratch index 

Mortar  samples  were  extracted  from  a  number  of  historic  buildings  and  were  cut  into 
approximately cubical shapes having two parallel sides (top and bottom). These mortar samples 
were capped using gypsum plaster, subjected to the Mohs scratch test and were subsequently 
tested  in  compression  in  accordance  with  C2.3.3.  Although  most  mortars  had  equivalent 
hardness values corresponding to being scratched by a fingernail, extremely weak mortars could 
be easily scratched using a fingernail, where the mortar was scraped and the particles became 
loose as the  fingernail was drawn along the sample. When  this scraping of  mortar occurred, a 
Mohs number of 1.5 was assigned. A Mohs number of 2 was assigned when a fingernail left an 
indented scratch mark on the mortar joint while the mortar was not heavily raked.  Figure C2‐10 
shows box and whisker plots of the mortar compressive strength‐scratch index relationship. 

C2‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

1.5: fingernail (easy) 
Median = 1.4 MPa  
12
10
Lower Quartile = 1.0 MPa
Compressive Strength (MPa)

Sample Size = 76  
2.0: fingernail 
8

Median = 5.5 MPa  
6

Lower Quartile = 3.2 MPa

Sample Size = 54 
4

3.0: 10 cent copper coin 
2

Median = 7.4 MPa  
0

Lower Quartile = 5.8 MPa
1.5 2 2.5
Sample Size = 43 
Scratch Index

Figure C2‐10: Plot of Mortar compressive strength vs. scratch index 

One‐way  analysis  of  variance  and  Tukey  multiple  comparison  tests  revealed  that  there  are 
significant statistical differences between the means of the sample groups shown in Figure C2‐9 
and Figure C2‐10 (Bewick et al. 2004; Chrichton 1999), which implies that for both brick unit and 
mortar,  each  scratch  index  represents  a  different  group  of  samples.  This  statistical  analysis 
emphasised  that  the  scratch  test  based  on  the  Mohs  hardness  scale  is  an  adequate  tool  to 
characterise brick unit and mortar joint properties. Refer to C2.4 for scratch test methodology. 

C2.5.2 Brick Unit Modulus of Rupture and Modulus of Elasticity 
Brick  units  that  were  extracted  from  different  buildings  were  subjected  to  the  Modulus  of 
Rupture test ASTM C 67‐03a (2003c). The remainder of the bricks from the Modulus of Rupture 
test were then subjected to the half brick compression test ASTM C 67‐03a (2003c) in order to 
obtain  a  direct  relationship  between  the  brick  Modulus  of  Rupture,  MoR,  and  compressive 
strength,  f’b.  Figure  C2‐11  shows  that  the  brick  unit  MoR  can  be  approximated  to  be  equal  to 
0.13f’b. 

  C2‐11
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

6
Modulus of Rupture (MPa)
5

4
y = 0.1296x
3 R² = 0.6249

1
Sample Size = 75
0
0 10 20 30 40 50 60
Compressive Strength (MPa) 
 
Figure C2‐11 Plot of brick Modulus of Rupture vs. brick compressive strength 

C2.5.3 Height to Least Lateral Dimension Ratio of Mortar 
The characterisation of mortars in existing buildings has long been known to be difficult. Several 
overseas  studies  (Moropoulou  et  al.  2005a;  Moropoulou  et  al.  2000;  Papayianni  2006)  have 
previously  focused  mainly  on  the  chemical  and  microstructural  analyses  of  mortars,  which 
enabled in‐depth characterisation of the mineralogical and chemical constituents of the mortar, 
but  provide  insufficient  information  on  mechanical  properties.  This  focus  on  chemical  and 
microstructural  analyses  was  due  to  the  difficulty  of  extracting  samples  of  a  sufficiently  large 
volume  from  existing  buildings  (Drdacky  et  al.  2008;  Magalhaes  and  Veiga  2009).  Whilst  the 
number  of  samples  allowed  for  extraction  is  usually  restricted,  most  mortar  joints  in  existing 
URM  buildings  are  between  12 mm  and  18 mm  thick,  and  therefore  the  size  of  the  attainable 
samples is small in comparison to the standardised size of 50mm x 50mm x 50mm. (ASTM 2008).  

The small sample dimensions combined with restrictions on the number of samples allowed for 
extraction  makes  mechanical  tests  unreliable  as  knowledge  on  testing  techniques  for  non‐
standard mortar samples is currently insufficient. Investigations on non‐standard mortar testing 
techniques  have  been  conducted  by  several  researchers  (Drdacky  et  al.  2008;  Magalhaes  and 
Veiga  2009;  Valek  and  Veiga  2005).  Valek  and  Veiga  (2005)  and  Magalhaes  and  Veiga  (2009) 
performed compression tests on non‐standard mortar samples using two different methods. The 
first method  involved cutting of two  mortar sides to produce flat and parallel  loading surfaces 
prior  to  compression  testing,  while  the  second  method  used  strong  confinement  mortars  to 
transfer the compression load to the mortar sample.  

Drdacky  et  al.  (2008)  conducted  experiments  on  mortar  samples  with  varying  dimensions  and 
found  that  the  mortar  compressive  strength,  f’j,  is  primarily  influenced  by  the  sample 
slenderness  ratio  and  quality.  An  experimental  programme  involving  three  different  mortar 
mixes  and  ten  different  sample  dimensions  with  varying  slenderness  ratio  was  conducted  to 
investigate the relationship between mortar compressive strength and dimensions. Five mortar 

C2‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

samples  were  tested  for  each  sample  group.  The  materials  used  in  the  mortar  mixes  were 
ordinary Portland cement, hydrated lime and river sand. The water/cement ratio during the time 
of  mixing  was  monitored  to  ensure  consistency  within  each  mortar  mix.  The  mortar  samples 
were cast using timber moulds, left to cure under room temperature (±20 °C) for 28 days, and 
were  then  capped  using  gypsum  plaster  and  tested  in  compression.  Figure  C2‐12  shows  the 
relationship  between  average  mortar  compressive  strength  and  slenderness  ratio  (height  to 
least lateral dimension ratio) of the mortar samples. 

6
Mortar compressive strength (MPa)

4 Mortar 1:2:9

Mortar 1:3:12
3
Mortar 0:3:9
2

0
0 0.2 0.4 0.6 0.8 1 1.2 1.4
h/t ratio  
Figure C2‐12: Plot of mortar compressive strength vs. h/t ratio 

Figure C2‐12 reveals that there was an overall increase in compressive strength with increasing 
cement  proportion.  The  mortar  compressive  strength  dividing  factors  for  samples  having  h/t 
ratios other than 1.0 are shown in Table C2‐4, which shows that the dividing factors at the same 
h/t  ratio  increments  for  the  three  different  mortar  grades  were  similar.  Therefore,  the  mortar 
correction factor for each h/t ratio increment (see Table C2‐4) was determined as the average 
dividing  factor  of  the  three  different  mortar  grades.  The  laboratory  experiments  have  covered 
different types of lime based mortars, and therefore it is assumed that the correction factors in 
Table C2‐4 are valid for heritage mortars, which rarely have a compression strength exceeding 
7.5 MPa (Lumantarna 2011). 

   

  C2‐13
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

Table C2‐4: Mortar dividing factors based on h/t ratio 

Mortar dividing factor 
h/t ratio  Average mortar 
0:3:9 Mortar  1:3:12 Mortar  1:2:9 Mortar  correction factor 

0.6  1.287  1.302  1.310  1.3 

0.7  1.215  1.226  1.233  1.225 

0.8  1.143  1.151  1.155  1.15 

0.9  1.072  1.075  1.078  1.075 

1.0  1  1  1  1 

1.1  0.928  0.925  0.922  0.925 

1.2  0.857  0.859  0.845  0.85 

C2.5.4 Masonry Compressive Strength, Modulus of Elasticity and Density 
The  importance  of  masonry  assemblage  properties  such  as  compressive  strength,  stress‐strain 
relationship  and  Modulus  of  Elasticity  in  the  analyses  of  masonry  structures  has  been 
emphasised  by  many  authors  (Drysdale  et  al.  1999;  Kaushik  et  al.  2007b).  As  the  masonry 
assemblage properties are related to the constituent material properties (Kaushik et al. 2007b), 
an experimental programme to investigate the relationship between brick, mortar and masonry 
compressive  strengths  was  conducted.  Laboratory  manufactured  samples  with  18  different 
brick‐mortar combinations and samples extracted from 9 historic buildings in New Zealand were 
tested  in  compression.  Displacement  measurement  devices  were  attached  during  the 
compression tests to derive the masonry stress‐strain relationship and Modulus of Elasticity. The 
density  of  masonry  is  an  essential  property  for  in‐plane  and  out‐of‐plane  assessments  of 
masonry walls (Derakhshan 2011; Russell 2010), and therefore was investigated as reported in 
Section C2.3.4.3.    

C2.5.4.1 Masonry Compressive Strength 

The  predictive  equation  relating  the  brick,  mortar  and  masonry  compressive  strengths  was 
developed  based  on  both  laboratory  manufactured  and  field  extracted  masonry  prisms.  The 
brick,  mortar  and  masonry  prism  compressive  strengths  were  determined  following  the 
procedures detailed in Section C2.3.2, C2.3.3 and C2.3.4.1 respectively. The mortar properties of 
some of the laboratory manufactured and field prism types were not determined, and therefore 
only  14  different  laboratory  manufactured  brick‐mortar  combinations  and  8  different  field 
sample types were included in the analysis. Nonlinear regression analysis was performed and a 
three  dimensional  plot  relating  the  average  brick,  average  mortar  and  average  masonry  prism 
compressive strengths is shown in Figure C2‐13. The surface plot in Figure C2‐13 represents the 
prediction on the compressive strength of masonry with different brick and mortar properties. 
The  predictive  expression  relating  the  brick,  mortar  and  masonry  compressive  strengths  is 
shown in Equation C2‐1. 

C2‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 
Figure C2‐13: 3‐D plot relating the brick, mortar and masonry compressive strengths 

′ . .
0.7                 (C2‐1) 

C2.5.4.2 Masonry Modulus of Elasticity 

The  masonry  Modulus  of  Elasticity  was  obtained  following  the  procedure  outlined  in  Section 
C2.3.4.1.  The  masonry  Modulus  of  Elasticity‐compressive  strength  relationships  for  both  the 
laboratory manufactured and the field extracted samples are presented in Figure C2‐14, which 
shows that the Em/f’m relationship of the field samples was generally consistent with the results 
from laboratory manufactured samples. The combination of data from laboratory manufactured 
and  field  extracted  samples  suggests  that  the  masonry  Modulus  of  Elasticity,  Em,  can  be 
satisfactorily equated to 300f’m (see Figure C2‐14). 

14000

12000

10000
y = 296.94x
R² = 0.732
Em (MPa)

8000

6000

4000
Field Samples
2000
Lab Samples
0
0 5 10 15 20 25 30 35 40
f'm (MPa)
 
Figure C2‐14: Plot of masonry Modulus of Elasticity vs. compressive strength plot 

  C2‐15
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

C2.5.4.3 Masonry Density 

The  density  of  masonry  was  determined  by  creating  a  masonry  module  which  consisted  of  a 
single brick unit, two‐half mortar bed‐joints and two half mortar head joints (see Figure C2‐15). 
Using  the  brick‐mortar  volumetric  proportion  and  a  relationship  shown  in  Equation  C2‐2,  the 
density of masonry, ρm, was approximated. 

URM 
Module 
 
Figure C2‐15: Unreinforced masonry module for density approximation 

  (C2‐2)

The mechanical strengths of brick units and mortar are related to the level of porosity (Elert et 
al.  2003;  Papayianni  and  Stefanidou  2006;  Tite  and  Maniatis  1975),  which  furthermore  is 
inversely proportional to density. Therefore, it was thought that having an expression to relate 
masonry density to the brick and mortar compressive strengths would be useful. 

The  brick  and  mortar  density‐compressive  strength  relationships  were  investigated  in  the 
laboratory.  Brick  units  and  mortar  samples  that  were  extracted  from  existing  buildings  were 
subjected to the bulk density test ASTM C 20‐00 (2000b). These samples were then subjected to 
the half brick compression test ASTM C 67‐03a (2003c) and irregular mortar compression tests 
following the procedure detailed by Valek and Veiga (2005).  The density‐compressive strength 
relationships  of  the  brick  unit  and  mortar  were  incorporated  into  Equation  C2‐2,  and  the 
masonry  density  was  furthermore  expressed  in  terms  of  the  brick  and  mortar  compressive 
strengths (see Equation C2‐3). 

1578 5 8                   (C2‐3) 

C2.5.5 Masonry Flexural Bond Strength and Mortar Bed‐joint Shear Strength 
The importance of masonry flexural bond strength and bed‐joint shear strength properties in the 
out‐of‐plane  and  in‐plane  analyses  of  unreinforced  masonry  walls  has  been  emphasised  by 
Derakhshan  (2011)  and  Russell  (2010).  Flexural  bond  tests  (Australian  Standards  2001),  triplet 
shear tests (BSI 2002) and prism compression tests (ASTM 2003a) were conducted on laboratory 
manufactured  samples  with  6  different  brick‐mortar  combinations  and  on  samples  extracted 
from  6  historic  buildings,  in  order  to  investigate  the  relationships  of  masonry  flexural  bond 
strength and mortar bed‐joint shear strength with other properties such as masonry and mortar 
compressive  strengths.  The  laboratory  manufactured  samples  were  left  to  cure  under  room 

C2‐16   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

temperature  (±20 °C)  for  28  days  prior  to  testing.  The  brick  unit  and  mortar  compressive 
strengths were determined following the procedures detailed in Section C2.3.2 and C2.3.3. 

C2.5.5.1 Masonry Flexural Bond Strength  

A  number  of  researchers  have  investigated  the  relationship  between  masonry  flexural  bond 
strength and masonry compressive strength (Sarangapani et al. 2005; Venkatarama Reddy and 
Gupta  2006).  However,  these  investigations  were  performed  on  masonry  samples  constructed 
using soft brick units and stiff mortar, which are commonly used in India (Gumaste et al. 2006; 
Kaushik  et  al.  2007a).  When  a  soft  brick‐stiff  mortar  masonry  prism  is  subjected  to  axial 
compression  forces,  the  brick  units  have  a  greater  tendency  to  expand  laterally  than  does  the 
mortar, due to their low stiffness. Due to the presence of the brick‐mortar bond, the stiff mortar 
joints  prevent  the  lateral  expansion  of  brick  units,  thus  subjecting  the  brick  units  to  bilateral 
compression forces, whilst the mortar joints are subjected to bilateral tension forces as the soft 
bricks  try  to  expand  the  mortar  joints  laterally  (Kaushik  et  al.  2007a;  Sarangapani  et  al.  2005). 
The masonry prism consequently fails after the brick‐mortar interface bond failure occurs. These 
occurrences  explain  that,  for  soft  brick‐stiff  mortar  combinations,  the  brick‐mortar  interface 
bond strength is one factor that often governs the masonry compressive strength, and therefore 
the  masonry  compressive  strength  can  be  related  to  the  masonry  flexural  bond  strength 
(Sarangapani et al. 2005).    

The  existence  of  a  relationship  between  masonry  flexural  bond  strength  and  masonry 
compressive  strength  for  strong  brick‐weak  mortar  combinations,  which  are  commonly 
encountered in North America and New Zealand (Aryana and Matthys 2008; Lumantarna 2011), 
is  currently  poorly  documented.  In  order  to  investigate  the  existence  of  this  relationship, 
laboratory  manufactured  and  field  extracted  masonry  prisms  were  subjected  to  compression 
and flexural bond tests according to Sections C2.3.4.1 and C2.3.4.2. The masonry flexural bond 
strength‐masonry compressive strength relationships of the laboratory manufactured and field 
samples are shown in Figure C2‐16.  

0.6

Field Samples
Flexural Bond Strength (MPa)

0.5
Lab Samples
0.4

0.3

0.2

0.1

0
0 5 10 15 20 25
Masonry Compressive Strength (MPa)
 
Figure C2‐16: Plot of masonry flexural bond strength vs. masonry compressive strength 

  C2‐17
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

Figure  C2‐16  shows  the  absence  of  a  distinct  relationship  between  masonry  flexural  bond 
strength and masonry compressive strength. It was furthermore observed that the flexural bond 
failures of most of the field samples had occurred within the mortar joint instead of at the brick‐
mortar  interface  (see  Figure  C2‐17),  and  therefore  the  failures  were  governed  by  the  flexural 
strength  of  the  mortar.  Several  authors  (Cizer  et  al.  2008;  Moropoulou  et  al.  2005b)  have 
documented  that  both  flexural  and  compressive  strengths  of  mortar  increase  over  time. 
Therefore, relating masonry flexural bond strength to mortar compressive strength, as in Figure 
C2‐18,  was  deemed  to  be  more  appropriate  than  plotting  masonry  flexural  bond  strength 
against masonry compressive strength.  

   
(a) Mortar failure in flexure  (b) Failure at the brick‐mortar interface 
bond 
Figure C2‐17: Different types of bond failure 

0.8
Field Samples
0.7 y = 0.0786x
Lab Samples R² = 0.7742
Flexural Bond Strength (MPa)

0.6

0.5

0.4

0.3 y = 0.0281x
R² = 0.7428
0.2

0.1

0
0 2 4 6 8 10
Mortar Compressive Strength (MPa)
 
Figure C2‐18: Plot of masonry flexural bond strength vs. mortar compressive strength 

Figure C2‐18 indicates that there is a relationship between masonry flexural bond strength and 
mortar  compressive  strength,  although  the  relationship  for  the  laboratory  manufactured 
samples is different to that of the field extracted samples. This difference exists as the flexural 

C2‐18   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

bond failures of some laboratory manufactured samples occurred at the brick‐mortar interface, 
and therefore those failures were governed by the quality of the brick‐mortar interface bond.  

The three data points  marked in Figure C2‐18 represent the  laboratory manufactured samples 


which flexural bond failures that occurred at the brick‐mortar interface. The mortar joints of the 
other  two  laboratory  manufactured  sample  types  failed  in  flexure.  However,  these  two 
laboratory manufactured sample types had relatively high flexural bond strengths in comparison 
to  the  field  extracted  samples,  which  had  similar  mortar  compressive  strengths.  This  variation 
exists due to two reasons. Firstly, although a high proportion of mortars in existing buildings are 
thought  to  be  lime  based  (Lumantarna  2011),  the  material  compositions  of  the  field  mortars 
were  unknown,  whilst  the  laboratory  manufactured  mortars  were  made  using  new  materials 
and  were  produced  under  a  controlled  environment.  Secondly,  this  variation  exists  due  to  the 
difference in the rate of strength development over time between the compressive strength and 
the  flexural  strength  of  lime  mortars,  where  the  rate  is  lower  for  the  flexural  strength 
development in comparison to the compressive strength (Moropoulou et al. 2005b). Given that 
the  laboratory  manufactured  samples  were  only  cured  for  28  days,  their  mortars  would  gain 
more compressive strength than flexural strength over time, and therefore the masonry flexural 
bond strength‐mortar compressive strength relationships of these two laboratory manufactured 
sample types would eventually be similar to those of the field samples. When considering field 
samples only, the masonry flexural bond strength, f’fb, can be approximated as 0.025f’j. 

C2.5.5.2 Masonry Mortar Bed‐joint Shear Strength  

It is not always possible to perform mechanical tests to determine the masonry bed‐joint shear 
strength,  and  therefore  an  expression  to  predict  this  property  based  on  other  strength 
parameters  was  sought.  Sarangapani  et  al.  (2005)  tested  masonry  prisms  in  shear  and 
determined the relationship between masonry compressive strength and mortar bed‐joint shear 
strength by recognising that the brick‐mortar interface bond strength often governed the failure 
of  masonry  in  compression  (see  Section  C2.3.5.1).  These  shear  tests  were  performed  without 
applying  axial  compression  forces,  and  therefore  the  Mohr‐Coulomb  friction  envelope  of  the 
mortar joints could not be derived. It was known that the shear failure of mortar joints may be 
represented  by  the  Mohr‐Coulomb  friction  law  as  shown  in  Equation  C2‐4  (ASTM  2003b; 
Lourenco et al. 2004): 

μ                          (C2‐4) 

Where: τ = Shear stress; c = Shear stress at zero axial compression (cohesion); µf = Coefficient of 
friction; and N = Axial compression stress. 

Laboratory  manufactured  and  field  masonry  prisms  were  tested  in  shear  according  to  Section 
C2.3.4.3, where three different levels of axial compression forces were applied. Some laboratory 
manufactured and field extracted prism  types were not subjected  to shear triplet tests due  to 
the limited availability of the samples, and therefore only 5 different laboratory manufactured 
brick‐mortar  combinations  and  5  different  field  sample  types  were  included  in  the  analysis. 

  C2‐19
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

Figure  C2‐19  and  Figure  C2‐20  show  plots  of  the  mortar  bed‐joint  shear  strength  against  axial 
compression load of the laboratory manufactured and field extracted samples respectively. 

1.8
1.6
1.4
Shear Stress (MPa)

1.2
1
0.8
0.6
0.4
0.2
0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Axial Compression (MPa)
 
Figure C2‐19: Plot of shear stress vs. axial compression for laboratory manufactured samples 

1.4

1.2

1
Shear Stress (MPa)

0.8

0.6

0.4

0.2

0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7
Axial Compression (MPa)
 
Figure C2‐20: Plot of shear stress vs. axial compression for field samples 

Instead of following the procedure recommended in BS EN 1052‐3 (2002), the axial compression 
loads were maintained at 0.2 MPa, 0.4 MPa and 0.6 MPa to simplify the triplet shear tests. Shear 
stresses  at  axial  compression  levels  below  0.2  MPa  for  the  field  extracted  samples  (marked  in 
Figure C2‐20) were obtained in‐situ, and therefore the axial compression loads were estimated 
using  the  overburden  above  the  test  locations.  Figure  C2‐19  and  Figure  C2‐20  reveal  that  the 
shear strength variation at each level of axial compression was wide, which was also observed by 
Lourenco et al. (2004).  

C2‐20   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

The mortar bed‐joint shear strengths at zero axial compression (Cohesion), c, were calculated as 
the y‐intercepts of the shear stress‐axial compression relationships of the different sample types 
(see Figure C2‐19 and Figure C2‐20). Following Sarangapani et al. (2005), the bed‐joint cohesion 
was plotted against masonry compressive strength as in Figure C2‐21. 

0.6

Field Samples
0.5
Lab Samples
0.4
Cohesion (MPa)

0.3

0.2

0.1

0
0 5 10 15 20 25
Masonry Compressive Strength (MPa)  
Figure C2‐21: Plot of cohesion vs. masonry compressive strength 

Figure  C2‐21  reveals  that  there  is  no  discernable  relationship  between  bed‐joint  cohesion  and 
masonry compressive strength. However, similar to observations during the flexural bond tests 
(see  Section  C2.3.5.1),  most  bed‐joint  shear  failures  of  the  field  samples  occurred  within  the 
mortar, and therefore these failures were governed by the mortar properties instead of by the 
quality  of  the  brick‐mortar  interface  bond.  Figure  C2‐22  shows  the  mortar  bed‐joint  cohesion‐
mortar  compressive  strength  relationships  of  the  laboratory  manufactured  and  field  extracted 
samples. 

0.6

0.5

0.4
Cohesion (MPa)

Joint interface 
0.3 failure 

0.2
y = 0.0479x Field Samples
0.1 R² = 0.8553
Lab Samples

0
0 2 4 6 8 10
Mortar Compressive Strength (MPa)  
Figure C2‐22: Plot of cohesion vs. mortar compressive strength 

  C2‐21
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

The  relationship  between  mortar  bed‐joint  shear  strength  and  mortar  compressive  strength  is 
apparent,  in  particular  for  the  field  extracted  samples  (see  Figure  C2‐22).  This  relationship  is 
weak  for  the  laboratory  manufactured  samples  as  the  mortar  bed‐joint  shear  failures  of  some 
laboratory samples had occurred at the brick‐mortar interface, and therefore those failures were 
governed by the brick‐mortar bond quality.  

The three laboratory data points marked in Figure C2‐22 represent the samples in which mortar 
bed‐joint  shear  failures  had  occurred  at  the  brick‐mortar  interface.  Shear  failure  within  the 
mortar joints had occurred for the other two types of laboratory manufactured samples. Due to 
differences  in  the  failure  modes  and  mortar  compositions,  it  was  decided  that  the  laboratory 
manufactured  samples  were  not  representative  of  the  field  samples.  The  mortar  bed‐joint 
cohesion, c, can be approximated as 0.045f’j when considering field samples only.  

The mortar bed‐joint coefficient of friction, µf, was calculated as the gradient of the shear stress‐
axial compression relationships. Russell (2010) had previously suggested that µf shall be equal to 
0.65.  To  validate  this  suggestion,  the  average  µf  of  the  field  samples  was  considered,  and  the 
average field value of  µf = 0.88  was deemed to be reasonably close to  the value suggested  by 
Russell (2010), especially when considering that there were only five different field sample types 
available.  The  value  of  μf  =  0.65  that  is  recommended  in  Equation  2‐6  is  also  consistent  with 
values presented in Table 10‐2 of NZSEE (2006), where in that document μf was specified to have 
a range of 0.0‐0.8 depending on the condition of the mortar. Therefore, it was decided that the 
previously suggested value of µf = 0.65 shall be used.  

C2.7 Masonry Stress Block Parameters 
Table C2‐5 provides a list of  αf'm values from recent publications that address either clay brick 
masonry or methods for improving the earthquake resistance of unreinforced masonry. In this 
guideline  αf'm  has  been  taken  as  0.85f'm  consistent  with  both  NZS 4230:2004  and  most  other 
relevant recommendations. 

   

C2‐22   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Table C2‐5: List of αf'm values from publications 

αf'm  Publications  References 

Designs of Structures for Earthquake Resistance Part 3: 
0.86f'm  CEN (2005) 
Assessment and Retrofitting of Buildings, Eurocode 8 

Design Guideline for the Strengthening of Unreinforced 
Galati et al. 
0.855f'm  Masonry Structures Using Fibre Reinforced Polymers (FRP) 
(2005) 
Systems 

Masonry: Design on the Basis of Semi‐Probabilistic Safety  Din 1053‐100 
0.85f'm 
Concept, Din 1053‐100  (2004) 

0.8f'm  Building Code Requirement for Masonry Structures  MSJC (2002) 

Prestandard and Commentary for the Seismic Rehabilitation of 
0.7f'm  BSCC (2000) 
Buildings.” Building Society Safety Council 

C2.8 Worked Examples 
Worked  examples  are  briefly  presented  here  to  demonstrate  the  correct  use  of  the  equations 
presented  in  Section  2  and  the  indicative  values  for  masonry  material  properties  when  using 
these equations. 

C2.8.1 Example 1 
Site: 1910 Campbell Free Kindergarten, Auckland (see Figure C2‐23) 

Scenario: No mechanical test performed and sample extraction was not permitted. 

 
Figure C2‐23: Campbell Free Kindergarten 

Step 1: Perform scratch tests according to Section C2.4 to assess URM material properties:  

  C2‐23
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

Brick 

Scratch index (6 locations)   = 2.5, 2.5, 2.5, 2.5, 3.0, 3.0 

Average  = 2.67 

Linear interpolate from Table 2‐2, f’b   = 18.17 MPa 

Mortar 

Scratch index (6 locations)  = 2.0, 2.0, 2.0, 2.0, 2.5, 2.5 

Average  = 2.17 

Linear interpolate from Table 2‐4, f’j   = 6.13 MPa 

Step 2: Predict brick unit Modulus of Rupture strength: 

From Equation 2‐1, MoR   = 0.130 x 18.17 

  = 2.36 MPa 

Step 3: Predict masonry compressive strength and Modulus of Elasticity: 

From Equation 2‐2, f’m  = 0.7 x 18.17 0.75 x 6.13 0.3 

  = 10.61 MPa 

From Equation 2‐4, Em  = 300 x 10.61 

  = 3183 MPa 

Step 4: Predict masonry density: 

From Equation 2‐3, ρm  = 1578 + 5 x 18.17 + 8 x 6.13 

  = 1718 kg/m3 

Step 5: Predict masonry flexural bond strength and bed‐joint cohesion: 

From Equation 2‐5, f’fb  = 0.025 x 6.13 

  = 0.15 MPa 

From Equation 2‐6, c  = 0.045 x 6.13 

  = 0.276 MPa 

From Equation 2‐7, µ  = 0.65 

C2.8.2 Example 2 
Site: 1930’s Two‐storey Irish Pub, Auckland (see Figure C2‐24) 

Scenario: Brick and mortar samples were extracted and tested in compression. 

C2‐24   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 
Figure C2‐24: Two‐storey Irish Pub 

Step  1:  Perform  brick  and  mortar  compression  tests  in  accordance  with  Section  C2.3.2  and 
C2.3.3  

Brick 

Average of six half brick samples, f’b  = 22.33 MPa 

Mortar 

Average of 6 mortar samples subjected to correction factors, f’j  = 6.5 MPa 

Step 2: Predict brick unit Modulus of Rupture strength: 

From Equation 2‐1, MoR   = 0.130 x 22.33 

  = 2.90 MPa 

Step 3: Predict masonry compressive strength and Modulus of Elasticity: 

From Equation 2‐2, f’m  = 0.7 x 22.33 0.75 x 6.5 0.3 

  = 12.61 MPa 

From Equation 2‐4, Em  = 300 x 12.61 

  = 3783 MPa   

Step 4: Predict masonry density: 

From Equation 2‐3, ρm  = 1578 + 5 x 22.33 + 8 x 6.5 

  = 1742 kg/m3 

Step 5: Predict masonry flexural bond strength and bed‐joint cohesion: 

From Equation 2‐5, f’fb  = 0.025 x 6.5 

  = 0.163 MPa 

From Equation 2‐6, c  = 0.045 x 6.5 

  = 0.293 MPa 

From Equation 2‐7, µ  = 0.65 

  C2‐25
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

C2.8.3 Example 3 
Site: 1907 two‐storey commercial building, Gisborne (see Figure C2‐25) 

Scenario:  Sample  extraction  was  not  possible,  but  moderately  destructive  in‐situ  tests  were 
permitted. In‐situ shear tests were performed in accordance with Section C2.3.4.2. 

 
Figure C2‐25: Two‐storey commercial building 

Step 1: Perform scratch tests according to Section C2.4 to assess URM material properties:  

Brick 

Scratch index (6 locations)  = 2.5, 2.5, 2.5, 2.5, 2.5, 2.5 

Average  = 2.5 

Linear interpolate from Table 2‐2, f’b  = 14.0 MPa 

Mortar 

Scratch index (6 locations)  = 2.0, 2.0, 2.0, 2.0, 2.5, 2.5 

Average  = 2.17 

Linear interpolate from Table 2‐4, f’j  = 6.13 MPa 

Step 2: Predict brick unit Modulus of Rupture strength: 

From Equation 2‐1, MoR   = 0.13 x 14.0 

  = 1.82 MPa 

Step 3: Predict masonry compressive strength and Modulus of Elasticity: 

From Equation 2‐2, f’m  = 0.7 x 14.0 0.75 x 6.13 0.3 

  = 8.73 MPa   

From Equation 2‐4, Em  = 300 x 8.73 

  = 2619 MPa   

Step 4: Predict masonry density: 

From Equation 2‐3, ρm  = 1578 + 5 x 14.0 + 8 x 6.13 

C2‐26   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

  = 1697 kg/m3 

Step 5: Predict masonry flexural bond strength and bed‐joint cohesion: 

From Equation 2‐5, f’fb  = 0.025 x 6.13 

  = 0.153 MPa 

From Equation 2‐6, c  = 0.045 x 6.13 

  = 0.276 MPa 

From Equation 2‐7, µ  = 0.65 

C2.9 References 
Aryana,  S.  A.,  and  Matthys,  J.  H.  (2008).  "Statistical  Analysis  of  Compressive  Strength  of  Clay 
Brick Masonry: Testing." The Masonry Society Journal, 26(2), 43‐52. 
ASTM  (2000a).  "Standard  test  method  for  measurement  of  masonry  flexural  bond  strength." 
C 1072 ‐ 00a, ASTM International, Pennsylvania, United States. 
ASTM  (2000b).  "Standard  test  methods  for  apparent  porosity,  water  absorption,  apparent 
specific  gravity,  and  bulk  density  of  burned  refractory  brick  and  shapes  by  boiling  water." 
C 20 ‐ 00, ASTM International, Pennsylvania, United States. 
ASTM (2003a). "Standard Test Method for Compressive Strength of Masonry Prisms." C 1314 ‐ 
03b, ASTM International, Pennsylvania, United States. 
ASTM (2003b). "Standard test methods for in situ measurement of masonry mortar joint shear 
strength index." C 1531 ‐ 03, ASTM International, Pennsylvania, United States. 
ASTM  (2003c).  "Standard  test  methods  for  sampling  and  testing  brick  and  structural  clay  tile." 
C 67 ‐ 03a, ASTM International, Pennsylvania, United States. 
ASTM  (2008).  "Standard  Test  Method  for  Compressive  Strength  of  Hydraulic  Cement  Mortars 
(Using  2‐in.  or  [50‐mm]  Cube  Specimens)."  C  109/C  109M  ‐  08,  ASTM  International, 
Pennsylvania, United States. 
Australian Standards (2001). "Appendix D: Method of test for flexural strength." AS 3700 ‐ 2001. 
Bewick,  V.,  Cheek,  L.  and  Ball,  J.  (2004).  "Statistics  review  9:  One‐way  analysis  of  variance." 
Critical Care, 8(2), 130‐136. 
BSI  (2002).  "Methods  of  test  for  masonry.  Determination  of  initial  shear  strength."  BS  EN 
1052 ‐ 3, British Standards Institution, London, England. 
Chrichton, N. (1999). "Tukey Multiple Comparison test." Journal of Clinical Nursing, 8, 304. 
Cizer, O., Van Balen, K., Van Gemert, D., and Elsen, J. (2008). "Blended lime‐cement mortars for 
conservation  purposes:  Microstructure  and  strength  development."  Structural  Analysis  of 
Historical Constructions: Preserving Safety and Significance, Bath, UK, 2 965‐972. 
Cultrone, G., Sidraba, I., and Sebastian, E. (2005). "Mineralogical and physical characterization of 
the  bricks  used  in  the  construction  of  the  "Triangul  Bastion",  Riga  (Latvia)."  Applied  Clay 
Science, 28(1‐4), 297‐308. 
Derakhshan,  H.  (2011).  "Seismic  assessment  of  out‐of‐plane  loaded  unreinforced  masonry 
walls."  PhD  thesis,  Department  of  Civil  and  Environmental  Engineering,  The  University  of 
Auckland, Auckland, New Zealand. 

  C2‐27
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

Drdacky,  M.,  Masin, D., Mekonone,  M.  D., and Slizkova, Z. (2008). "Compression tests on non‐


standard historic mortar specimens" Historical Mortar Conference, Lisbon, Portugal, 24 ‐ 26 
September.  
Drysdale,  R.,  Hamid,  A.,  and  Baker,  L.  (1999).  Masonry  Structures:  Behaviour  and  Design,  The 
Masonry Society, Boulder, Colorado. 
Elert,  K.,  Cultrone,  G.,  Navarro,  C.  R.,  and  Pardo,  E.  S.  (2003).  "Durability  of  bricks  used  in  the 
conservation of historic buildings ‐ influence of composition and microstructure." Journal of 
Cultural Heritage, 4(2), 91‐99. 
Gumaste,  K.  S.,  Nanjunda  Rao,  K.  S.,  Venkatarama  Reddy,  B.  V.,  and  Jagadish,  K.  S.  (2006). 
"Strength  amd  elasticiy  of  brick  masonry  prisms  and  wallettes  under  compression." 
Materials and Structures, 40(2), 241‐253. 
Institute  of  Statistics  and  Mathematics.  (2010).  "The  R  Project  for  Statistical  Computing." 
Institute of Statistics and Mathematics, Vienna, Austria. 

Karaman,  S.,  Gunal,  H.,  and  Ersahin,  S.  (2006).  "Assesment  of  clay  bricks  compressive  strength 
using  quantitative  values  of  colour  components."  Construction  and  Building  Materials, 
20(5), 348‐354. 
Kaushik,  H.  B.,  Rai,  D.  C.,  and  Jain,  S.  K.  (2007a).  "Stress‐strain  characteristics  of  clay  brick 
masonry  under  uniaxial  compression."  Journal  of  Materials  in  Civil  Engineering,  19(9), 
728‐738. 
Kaushik,  H.  B.,  Rai,  D.  C.,  and  Jain,  S.  K.  (2007b).  "Uniaxial  compressive  stress‐strain  model  for 
clay brick masonry." Current Science, 92(4), 497‐501. 
Kreimeyer, R. (1987). "Some notes on the firing colour of clay bricks." Applied Clay Science, 2(2), 
175‐183. 
Lourenco, P. B., Barros, J. O., and Oliveira, J. T. (2004). "Shear testing of stack bonded masonry." 
Construction and Building Materials, 18(2), 125‐132. 
Lumantarna,  R.  (2011).  "Material  characterisation  of  New  Zealand  unreinforced  masonry 
buildings." PhD thesis, Department of  Civil and  Environmental Engineering,  The  University 
of Auckland, Auckland, New Zealand. 
Magalhaes,  A.,  and  Veiga,  R.  (2009).  "Physical  and  mechanical  characterisation  of  historic 
mortars.  Application  to  the  evaluation  of  the  state  of  conservation."  Materiales  de 
Construccion, 59(295), 61‐77. 
MineralTown (2010). "Minerals identification: Mohs Scale of mineral hardness." Rocks, minerals 
and  fossils,  <http://www.mineraltown.com/infocoleccionar/mohs_scale_of_hardness.htm> 
(September 27, 2010). 
Moropoulou, A., Bakolas, A., and Bisbikou, K. (2000). "Investigation of the technology of historic 
mortars." Journal of Cultura Heritage, 1(1), 45‐58. 
Moropoulou, A., Bakolas, A., and Anagnostopoulou, S. (2005a). "Composite materials in ancient 
structures." Cement & Concrete Composites, 27(2), 295‐300. 
Moropoulou,  A.,  Bakolas,  A.,  Moundoulas,  P.,  Aggelakopoulou,  E.,  and  Anagnostopoulou,  S. 
(2005b).  "Strength  development  and  lime  reaction  in  mortars  for  repairing  historical 
masonries." Cement & Concrete Composites, 27(2), 289‐294. 
Nicholson,  P.  T.,  and  Shaw,  I.  (2000).  Ancient  Egyptian  materials  and  technology,  The  Press 
Syndicate of The University of Cambridge, Cambridge, United Kingdom. 

C2‐28   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

NZSEE  (2006).  Assessment  and  improvement  of  the  structural  performance  of  buildings  in 
earthquakes: Recommendations of a NZSEE study group on earthquake risk buildings, New 
Zealand Society for Earthquake Engineering. 
Papayianni,  I.  (2006).  "The  longevity  of  old  mortars."  Applied  Physics  A:  Materials  Science  & 
Processing, 83(4), 685‐688. 
Papayianni,  I.,  and  Stefanidou,  M.  (2006).  "Strength‐porosity  relationships  in  lime‐pozzolan 
mortars." Construction and Building Materials, 20(9), 700‐705. 
Russell, A. (2010). "Characterisation and seismic assessment of unreinforced masonry buildings." 
PhD thesis, Department of Civil and Environmental Engineering, The University of Auckland, 
Auckland, New Zealand. 
Sarangapani, G., Venkatarama Reddy, B. V., and Jagadish, K. S. (2005). "Brick‐mortar bond and 
masonry compressive strength." Journal of Materials in Civil Engineering, 17(2), 229‐237. 
Shalabi,  F.  I.,  Cording,  E.  J.,  and  Al‐Hattamleh,  O.  H.  (2007).  "Estimation  of  rock  engineering 
properties using hardness tests." Engineering Geology, 90(3‐4), 138‐147. 
Shi,  H.,  and  Atkinson,  M.  (1990).  "A  friction  effect  in  low‐load  hardness  testing  of  copper  and 
aluminium." Journal of Materials Science, 25(4), 2111‐2114. 
Tabor, D. (1956). "The physical meaning of indentation and scratch hardness." British Journal of 
Applied Physics, 7(5), 159‐166. 
Tite,  M.  S.,  and  Maniatis,  Y.  (1975).  "Scanning  electron  microscopy  of  fired  calcareous  clays." 
Transaction of the British Ceramic Society, 74(1), 19‐22. 
Valek,  J.,  and  Veiga,  R.  (2005).  "Characterisation  of  mechanical  properties  of  historic  mortars  ‐ 
testing  of  irregular  samples"  Structural  studies,  repairs  and  maintenance  of  heritage 
architecture  XI:  Ninth  international  conference  on  structural  studies,  repairs  and 
maintenance of heritage architecture, Malta, 22‐24 June.  
Venkatarama  Reddy,  B.  V.,  and  Gupta,  A.  (2006).  "Tensile  Bond  Strength  of  Soil  Cement  Block 
Masonry  Couplets  Using  Cement‐Soil  Mortars."  ASCE  Journal  of  Materials  in  Civil 
Engineering, 18(1), 36‐45. 
 
 

  C2‐29
 
  Section C2 ‐ Material Properties of Masonry Walls
 
 

C2‐30   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C3 ‐ Material Properties of Flexible Timber Floor 
Diaphragms 

C3.3 Timber properties 
Timber diaphragms in New Zealand URM buildings were typically constructed with native timber 
species such as Kauri, Rimu and Matai. It is recommended that wherever possible, the material 
properties of timber be determined from testing samples extracted from the existing diaphragm. 
It  is  recommended  that  at  least  twelve  samples  be  taken.  If  physical  testing  of  timber  is  not 
achievable,  then  the  published  material  properties  may  be  used  as  a  representative  basis  for 
material property values.  

The material properties of Rimu and Matai have been established from testing timber samples 
salvaged from structures that have been demolished around New Zealand. Representative Kauri 
samples  could  not  be  gathered  for  testing  and  subsequently  the  material  properties  of  this 
species  were  not  determined.  Further  information  regarding  the  material  properties  of  native 
New Zealand timbers can be found at http://www.nzwood.co.nz.  

C3.3.1 Density 
The  density  of  Matai  and  Rimu  were  determined  in  accordance  with  the  testing  procedure 
outlined in AS/NZS 1080.3:2000. As recommended by the standard, the test pieces were taken 
from the specimens that were already prepared for bolted connection testing. Thus, the density 
test  pieces  were  prepared  after  conducting  the  main  bolted  connection  tests.  Samples  were 
prepared with average dimensions of 50.0 mm (length)  40.0 mm (width)  10.0 mm (thickness) 
measured to an accuracy of 0.1 mm. Before placing the test pieces into the oven with  105C 
for  drying,  weight  of  each  test  piece  was  recorded  to  an  accuracy  of  0.01 g.  After  the  first  24 
hours  of  the  oven  dry  process,  the  weighing  and  measuring  operations  were  conducted  and 
continued until a consistent weight of the test piece was achieved. 

C3.3.2 Embedded strength 
Rectangular  test  pieces  with  dimensions  100 mm  (length)    50 mm  (width)    90 mm  (height) 
were prepared for embedded strength testing. In accordance with ISO/DIS 10984‐2: 2008, a half 
13 mm diameter hole was notched into each test piece for the placement of a 12 mm diameter 
fastener  during  testing,  as  shown  in  Figure  C3‐1.  The  test  setup  shown  in  Figure  C3‐2  was 
implemented to avoid the bending of the fastener during testing. 

  C3‐1
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

H (height)
half 13 mm 
diameter hole 

W (width) 
L (length) 
 
Figure C3‐1: Test piece for embedded strength tests 

 
Figure C3‐2: Test setup for embedded strength tests 

C3.3.3 Yield compression strength 
The  yield  compression  strength  perpendicular  to  grain  of  Matai  and  Rimu  was  determined  by 
conducting  a  pure  block  test  as  shown  in  Figure  C3‐3.  Dimensions  of  the  tested  timber  blocks 
were  100 mm  (length)    110 mm  (width)    50 mm  (height).  The  yield  compression  strength 
perpendicular to the grain of wood is determined using the yield load divided by the compressed 
wood  area  (AS/NZS 4063.1:2007).  Note  that  the  yield  load  is  evaluated  using  a  2 mm  offset 
method. 

C3‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 
Figure C3‐3: Pure block test setup to determine compression strength of wood 

C3.4 Classification 
Timber  floor  diaphragms  are  routinely  classified  as  flexible  using  the  quantitative  definition 
published in ASCE/SEI 41‐06 (2007):  

‘Diaphragms  shall  be  classified  as  flexible  when  the  maximum  horizontal 
deformation  of  the  diaphragm  along  its  length  is  more  than  twice  the  average 
interstorey  drift  of  the  vertical  lateral‐force  resisting  elements  of  the  story 
immediately below the diaphragm’.  

Given that almost all New Zealand URM buildings comprise timber diaphragms, and that these 
diaphragms  consistently  satisfy  the  ASCE/SEI  41‐06  definition  of  ‘flexible’,  it  is  appropriate  to 
default to a flexible diaphragm classification, unless it is proven otherwise. 

C3.5 Configuration and Condition Assessment 

C3.5.1 Configuration 
Timber  diaphragms  in  New  Zealand  URM  buildings  typically  comprise  either  straight‐edge  or 
tongue & groove floorboards nailed perpendicular to joists that span between vertical support 
elements,  such  as  masonry  walls  or  intermediate  columns.  When  perimeter  walls  were  close 
enough  (approximately  less  than  6 m)  joists  would  often  span  continuously  between  these 
elements. For larger spans, joists were typically lapped or butted, either with or without some 
form  of  mechanical  connection,  over  intermediate  steel  or  timber  cross‐beams  supported  on 
columns.  Diaphragm  blocking  and  chord  elements  were  almost  never  provided,  and  timber 
cross‐bracing between joists to prevent out‐of‐plane buckling may, or may not, have been fitted. 

  C3‐3
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

Joist ends were typically either simply supported on a brick ledge resulting from the perimeter 
walls reducing in width at each storey height, or pocketed into the wall to a depth equal to one 
brick width. Figure C3‐4 shows graphics that illustrate these diaphragm configuration details.  

Diaphragm  properties  determined  in  Sections  3.5  and  3.6  are  based  on  the  typical  diaphragm 
configurations  outlined  above,  and  remain  representative  with  only  minor  variations  to 
configuration values. 

   
(a) Schematic of typical diaphragm  (b) Underside of typical diaphragm 

   
(c) Continuous joists. Diaphragm span L < 6.0  (d) Lapped joist connection. Diaphragm span 
m  L > 6.0m 

   
(e) Joists pocketed into URM wall  (f) Joists seated on ledge of URM wall 

Figure C3‐4: Diaphragm configuration details 

C3‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C3.5.2 Condition Assessment 
Table  3‐5  has  been  developed  from  collaborative  engineering  judgement  and  focuses  on 
diaphragm conditions that most affect the performance of the primary nail connections, which 
have been proven to govern overall diaphragm performance. If the designer is not certain which 
condition  category  the  subject  diaphragm  falls  within,  it  is  recommended  that  a  conservative 
condition rating be selected. 

C3.6 Characteristic Values 
An  integrated  experimental  and  analytical  research  program  undertaken  at  the  University  of 
Auckland  has  quantitatively  established  key  structural  performance  characteristics  of  timber 
floor  diaphragms.  This  research  has  generated  the  much  needed  test  data  on  typical 
configurations  to  improve  the  assessment  of  these  structures.  Table  C3‐1  summarises  the 
cornerstone  of  the  research  program  that  involved  pseudo‐statically  testing  four  full‐scale 
diaphragms  to  establish  the  realistic  behaviour  of  representative  diaphragms.  The  total  force‐
midspan displacement results from  these tests are  presented for reference in Figure C3‐5. For 
use  in  independent  nonlinear  time‐history  analyses,  the  force‐displacement  data  of  the 
backbone curves of diaphragms FS1a (loaded parallel to joists) and FS3a (loaded perpendicular 
to joists) have been provided in Table C3‐2. Equivalent negative values of the data points can be 
used for the reverse direction. 

It is acknowledged that the characteristic values determined below have been established from 
diaphragms  constructed  with  new  pine  timber  and  new  wire‐drawn  nails.  The  completed 
experimental  program,  however,  included  the  testing  of  nailed  timber  connections  and  small‐
scale  diaphragm  samples  extracted  from  heritage  URM  buildings  that  have  provided  the 
necessary  data  to  assess  the  effects  of  age  and  decay  on  diaphragm  performance.  It  is  the 
intention  to  use  these  results  to  appropriately  adjust  the  presented  diaphragm  performance 
values to account for the effects of heritage construction materials, and the effects of age and 
decay.  

C3.6.1 Stiffness, Strength and Ductility 
Timber diaphragms are characterised by highly nonlinear hysteretic response to lateral loading, 
with  no  clearly  defined  yield  point.  The  establishment  of  stiffness,  strength  and  ductility  is 
therefore  difficult, as these values are  sensitive to  their definition and no universally accepted 
method  to  determine  these  values  currently  exists.  Given  the  need  to  provide  simple,  yet 
accurate diaphragm performance properties, a bilinear representation of the force‐displacement 
response  of  each  full‐scale  diaphragm  tested  was  developed  using  the  principle  of  hysteretic 
energy  conservation  (Mahin  and  Bertero  1981).  The  idealised  curves  provided  the  necessary 
characteristics  to  define  recognisable  performance  properties  such  as  stiffness,  strength  and 
ductility as presented in Tables 3‐6 and 3‐7 (see Figure C3‐6 and Figure C3‐7). 

A  distinction  has  been  made  for  the  presence  of  joist  connections  in  the  loading  direction 
perpendicular  to  joists.  The  classification  ‘without  joist  connections’  refers  to  diaphragms  that 

  C3‐5
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

comprise continuously spanning joists between the perimeter URM walls, as discussed in section 
C3.4.1.  The  classification  ‘with  joist  connections’  refers  to  situations  where  the  URM  walls  are 
too far apart for joists to span continuously between them, so that the joists must span between 
walls  and  intermediate  cross‐beams.  This  classification  applies  to  any  type  of  connection 
between  the  joists.  Typically  joists  are  lapped  or  butted  over  the  cross‐beam  either  with  or 
without a mechanical connection.  

Observations from full‐scale diaphragm testing indicated that in the direction parallel to joists, 
the flexural bending of floorboards effectively engaged a shear response from the nail couples to 
resist the applied lateral load. However, in the direction perpendicular to joists, the nail couples 
were  much  less  engaged  and  diaphragm  response  was  governed  by  flexural  bending  of  the 
joists.  Considering  this  observed  response  mechanism,  the  strength  and  stiffness  values  for 
diaphragms  with  joist  connections  in  the  direction  perpendicular  to  joists  have  been  slightly 
reduced to account for the reduced flexural resistance a non‐continuous joist has compared to a 
continuous joist. Further analysis using a calibrated finite element diaphragm model is expected 
to verify this adjustment. 

Methodology for bilinear curve development 

(a) A monotonic backbone (or envelope) curve was fitted to each hysteretic data set. 

(b) The area beneath this backbone curve was calculated using the ‘trapezoidal rule’. This area 
is  analogous  to  the  amount  of  hysteretic  energy  absorbed  by  the  structure  during 
monotonic loading. With no established method for characterising diaphragm response, the 
conservation  of  this  energy  is  the  only  rational  method  available  to  develop  a 
representative bilinear curve. 

(c) The  proposed  bilinear  curve  was  given  the  following  constraints  to  ensure  that  a  unique 
solution could be found when equating hysteretic energy: 

(1) Must pass through zero load and zero displacement. 

(2) Final  displacement  was  set  to  ±150  mm  with  corresponding  load  taken  from  the 
backbone curve. 

(3) Secondary  stiffness,  K2,  was  taken  as  the  average  gradient  of  the  lines  joining 
displacement amplitudes 75 mm, 100 mm and 150 mm. This portion of the backbone 
curve  is  essentially  linear,  therefore  justifying  the  constraint  of  its  gradient  for  the 
bilinear curve. 

(4) Having appropriately constrained the solution, the yield displacement, Δy, was calculated 
using Equation C3‐1. 

1
2
2   (C3‐1)
1
2

(5) And the corresponding yield load, Fy, was calculated using Equation C3‐2. 

C3‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

   (C3‐2)

(6) Finally, the bilinear curve was drawn 

   

  C3‐7
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

Table C3‐1: Full‐scale diaphragm testing summary 

Loading 
Schematic  Test details 
direction 

 Test FS1a 
 10.4 m x 5.535 m 
 Aspect ratio 1.88 : 1 
 Homogeneous sheathing 
Parallel to joists 

 Test FS2a 
 10.4 m x 5.535 m 
 Aspect ratio 1.88 : 1 
 3.2 m x 1.08 m corner 
perforation 

 Test FS3a 
 5.535 x 10.4 m 
 Aspect ratio 1 : 1.88 
 Homogeneous sheathing 
Perpendicular to joists 

 Continuous joists 

 Test FS4a 
 5.535 x 10.4 m 
 Aspect ratio 1 : 1.88 
 Homogeneous sheathing 
 Joists discontinuous with 
central bolted lap 
connection 

C3‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

50 50

40 40

30 30

20 20

10 10
Load (kN)

Load (kN)
0 0

-10 -10

-20 -20

-30 -30

-40 -40

-50 -50
-200 -150 -100 -50 0 50 100 150 200 -200 -150 -100 -50 0 50 100 150 200
Mid-span displacement (mm) Mid-span displacement (mm)

(a) Diaphragm FS1a  (b) Diaphragm FS2a 

120 120
100 100
80 80
60 60
40 40
20 20
Load (kN)

Load (kN)

0 0
-20 -20
-40 -40
-60 -60
-80 -80
-100 -100
-120 -120
-200 -150 -100 -50 0 50 100 150 200 -200 -150 -100 -50 0 50 100 150 200
Mid-span displacement (mm) Mid-span displacement (mm)

(c) Diaphragm FS3a  (d) Diaphragm FS4a 

Figure C3‐5: Full‐scale diaphragm testing results 

 
   

  C3‐9
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

Table C3‐2: Example backbone force‐displacement data for time‐history analysis 

Diaphragm FS1a  Diaphragm FS3a 

Midspan  Midspan 
Load (kN)  Load (kN) 
displacement (mm)  displacement (mm) 

0  0  0  0 
0.2  1.2  0.1  0.8 
0.6  2.9  0.4  2.5 
1.4  3.9  1.1  4.7 
1.8  4.3  1.5  5.6 
2.2  4.6  1.9  6.9 
4.9  6.2  2.1  7.4 
9.9  8.4  5.1  11.9 
14.8  10.2  10.0  17.1 
24.0  13.1  14.7  22.0 
49.4  19.2  24.8  29.9 
74.0  23.7  49.6  45.7 
98.7  27.7  73.9  59.6 
147.3  35.6  98.6  73.9 
157.2  36.0  141.8  102.0 
 

Load 

Fmax 

K2

Fy 

K1 

Δy  Δmax
Displacement 
 
Figure C3‐6: Idealised bilinear response curve 

(d) Steps  (a)  to  (c)  were  performed  for  the  positive  and  negative  displacement  regions 
separately,  and  averaged  to  produce  an  equivalent  bilinear  curve  either  side  of  zero 
displacement. 

The bilinear curves developed for each full‐scale diaphragm test are presented in Figure C3‐7. 

C3‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Diaphragm strength, Qn 

Diaphragm strength is conventionally presented as shear strength per lineal metre depth of the 
diaphragm (kN/m). The shear strength values presented in Table 3‐6 were therefore calculated 
by  taking  the  relevant  bilinear  yield  load,  which  is  the  total  applied  load  to  the  diaphragm, 
halving it to find shear resistance at the diaphragm’s edge, and dividing it by the depth of the 
diaphragm, as illustrated in the following equation: 

   (C3‐3)
2

When  calculating  total  diaphragm  shear  strength,  it  is  recommended  that  the  effective 
diaphragm depth, be, determined from Table 3‐8 be used.  

It is acknowledged that the shear strength values presented in Table 3‐6 are significantly lower 
than those published in NZSEE (2006). It is not fully understood why this discrepancy exists but 
one  theory  suggests  that  the  original  authors  of  the  NZSEE  strengthening  guide  lines 
benchmarked  diaphragm  strength  back  to  ABK  (1981)  test  values.  This  may  have  lead  to 
unconservative  values  because  referring  to  Section  A110.4  of  the  IEBC  (2006),  the  strength 
values, which were also based on the ABK testing, already include an allowance for overstrength 
of  the  wood  framed  elements  and  dynamic  response  of  the  rigid  masonry  walls  (Oliver  2010). 
Nonetheless,  the  shear  strength  values  in  Table  3‐6  have  been  established  directly  from  full‐
scale  diaphragm  testing,  as  detailed  above,  and  provide  a  new  basis  for  expected  diaphragm 
strength in URM buildings.  

Diaphragm  overstrength  has  not  yet  been  thoroughly  considered  and  is  a  subject  for  further 
analysis.  A  basic  interpretation  of  the  bi‐linear  force‐displacement  plots  in  Error!  Reference 
source  not  found.  suggests  that  if  ultimate  diaphragm  strength  was  taken  at  a  midspan 
displacement  of  150  mm,  then  diaphragm  overstrength  factor  would  be  as  high  as  4,  which  is 
considerably  higher  than  conventional  values.  Until  additional  analysis  provides  appropriate 
guidance on diaphragm overstrength, it is recommended that conventional methods taking μ = 
1.25 be adopted in the design of non‐yielding diaphragm components. 

Diaphragm shear stiffness, Gd 

It  is  necessary  to  present  diaphragm  stiffness  in  Table  3‐6  as  shear  stiffness,  Gd,  to  achieve 
independence  from  diaphragm  geometry.  Using  Equation  C3‐3,  the  value  of  Gd  was  back 
calculated by setting diaphragm stiffness, Kd, to the initial stiffness, K1, of  the relevant  bilinear 
curve. 

4
  (C3‐4)

  C3‐11
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

Ductility capacity, µ 

The diaphragm ductility capacities presented in Table 3‐7 were calculated as the ratio of plastic 
displacement to yield displacement assuming elastic‐perfectly plastic behaviour, as presented in 
Equation C3‐5 below:  

μ   (C3‐5)

It can be observed in Figure C3‐5 that failure (strength degradation) did not occur in any of the 
tested diaphragms, even at midspan displacements in excess of 150 mm. Representative values 
of  Δmax  were  therefore  not  captured  during  testing,  and  any  extrapolation  of  the  force‐
displacement  response  plots  would  have  been  speculative.  In  order  to  gauge  some  level  of 
diaphragm  ductility  capacity,  Equation  C3‐5  was  applied  by  taking  the  maximum  recorded 
displacement value of each test as Δmax and the corresponding Δy value determined from bilinear 
representation.  Ductility  capacities  using  these  conservative  definitions  were  calculated  to  be 
between 6.8 and 10.8. Given that AS/NZS 1170 (2002a) stipulates a maximum ductility capacity 
of  μ = 6,  and  that  all  tested  diaphragms  demonstrated  the  ability  to  exceed  this  value,  it  has 
been recommended that diaphragm ductility capacity be defaulted to μ = 6. It is believed that 
this value appropriately reflects the flexible and ductile nature of these diaphragms. 

40 40

30 30

20 20

10 10
Load (kN)

Load (kN)

0 0

-10 -10

-20 -20

-30 -30

-40 -40
-150 -100 -50 0 50 100 150 -150 -100 -50 0 50 100 150
Mid-span displacement (mm) Mid-span displacement (mm)

(a) Diaphragm FS1a  (b) Diaphragm FS2a 

C3‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

125 125

100 100

75 75

50 50

25 25
Load (kN)

Load (kN)
0 0

-25 -25

-50 -50

-75 -75

-100 -100

-125 -125
-150 -100 -50 0 50 100 150 -150 -100 -50 0 50 100 150
Mid-span displacement (mm) Mid-span displacement (mm)

(c) Diaphragm FS3a  (d) Diaphragm FS4a 

Figure C3‐7: Bilinear curves from full‐scale diaphragm testing 

Diaphragm condition effects 

Provisions  for  diaphragm  condition  in  Tables  3‐6  and  3‐7  are  provided  to  reflect  the  adverse 
effect  that  deteriorating  diaphragm  condition  has  on  performance.  The  effect  of  diaphragm 
condition  on  strength,  stiffness  and  ductility  will  be  identified  through  parametric  studies  of 
varying  nail  connection  conditions  using  a  calibrated  finite  element  model.  Until  this  is 
completed, the characteristic values for diaphragms classified as ‘Fair’ and ‘Poor’ will be 85% and 
65% of ‘Good’ diaphragms, respectively. 

C3.6.2 Damping 
Diaphragm damping has been determined using the approximate method presented in Chopra 
(2007).  In  this  method,  the  equivalent  viscous  damping  ratio(eq)  can  be  approximated  by 
determining  the  equivalent  strain  energy,  ES,  dissipated  during  each  cycle  of  the  force‐
displacement response, as described in Equation C3‐6, where do is the average of the maximum 
displacements in the positive and negative directions of the cycle, and k is the secant stiffness to 
the  corresponding  maximum  force.  The  equivalent  viscous  damping  ratio  is  then  determined 
according  to  Equation C3‐7,  where  ED  is  equal  to  the  hysteretic  energy  dissipated  in  the  same 
cycle (see Section C3.5.1). 

1
(C3‐6)
2

1
 (C3‐7)
4

While  preliminary  analysis  demonstrates  that  diaphragm  damping  could  be  in  excess  of  0.20 
(20%) using the above method, it is important to recognise that this hysteretic energy is already 
accounted  for  in  the  concept  of  ductility  and  so  in  the  absence  of  exhaustive  nonlinear  time‐

  C3‐13
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

history  analyses  and  for  the  purpose  of  linear  static  assessment  procedures,  it  is  most 
appropriate to default to a typical damping ratio of 0.05 (5%). 

C3.7 Diaphragm Stiffness 
Diaphragm stiffness is the mathematical gradient of the line joining zero displacement with the 
yield point, as demonstrated in Equation C3‐8: 

  (C3‐8)

Equation 3.1 for diaphragm stiffness, Kd, derives from Equation 8‐3 in ASCE/SEI 41‐06 (2007) for 
yield displacement: 

  (C3‐9)
2

Where: 

 
2

The  inclusion  of  effective  diaphragm  dimensions  be  and  Le,  and  coefficients  αp  and  αc  was 
intended to enhance the application of the equation to a wider range of diaphragm geometries 
and configurations. The basis of these values is described hereafter.  

C3.7.1 Diaphragm Geometry 
Diaphragm  performance  is  a  function  of  the  number  nail  couples  available  to  resist  lateral 
loading. The introduction of effective diaphragm span (Le) and effective diaphragm depth (be) is a 
simple  concept  to  account  for  the  number  of  available  nail  couples  while  maintaining  user 
friendly assessment procedures. 

C3.7.2 Diaphragm Penetrations 
Penetrations in timber diaphragms, such as stairwells and elevator shafts, cause a reduction in 
diaphragm  stiffness  due  to  reduced  nail  couples  available  to  resist  lateral  loads.  The  proposed 
reduction  in  diaphragm  stiffness  by  the  ratio  of  net  diaphragm  area  to  gross  diaphragm  area 
remains under review, and will be validated through parametric studies using a calibrated finite 
element model. 

   

C3‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C3.7.3 Diaphragm Configuration 
The equations to determine the effects of diaphragm configuration will be determined through 
parametric studies using a calibrated finite element model. In the interim, αc shall be taken as 
1.0. 

C3.8 Worked Example 1 

  10.4 m

 5.535 m 

Step 1:  Configuration Details 

Dimensions      See illustration above 
Floorboard type     Tongue & groove 
Floorboard size     135 mm x 21 mm 
Joist size      51 mm x 221 mm 
Joist spacing      515 mm crs 
Joist direction      North‐south 
Joist connection    No ‐ joists continuous 
Joist bracing      50 mm x 70 mm, X‐pattern  
Joist bracing location     1/3 along length of joists 
Nail schedule      2 nails per floorboard‐joist connection 
Nail spacing      100 mm 

Step 2:  Select Condition Rating 

Condition      Good 

Step 3:  Select Characteristic Values 

North South Direction 

Given  the  orientation  of  the  joists,  loading  in  the  north  south  direction  would  be  ‘parallel  to 
joists’. 

Shear stiffness and shear strength from Table 3‐6: 

Gd    = 300 kN/m 

  C3‐15
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

Qn    = 1.5 kN/m 

Ductility capacity from Table 3‐7: 

μ    = 6 

Damping for all diaphragms: 

    = 5% 

East West Direction 

Similarly it can be shown that for loading direction perpendicular to joists: 

Gd    = 175 kN/m 

Qn    = 1.2 kN/m 

μ    = 6 

    = 5% 

Step 4:  Diaphragm Stiffness Calculation 

North South Direction 
4
 

With reference to Table 3‐8: 

L e  = L  = 10.4 m 

be  = b  = 5.535 m 

Using Equation 3‐2: 

αp    = 1.0 (no penetrations)     

And using Equation 3‐3: 

αc  =  1.0  (until  reduction  factors  for  diaphragm  configuration  variations  are 
determined)     

Hence: 
1.0 ∗ 1.0 ∗ 4 ∗ 5.535 ∗ 300
 
10.4
    = 639 kN/m 

East West Direction 

Similarly it can be shown that: 

L e  = L  = 5.535 m 

be  = b  = 10.4 m 

αp    = 1.0     

C3‐16   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

αc    = 1.0     
1.0 ∗ 1.0 ∗ 4 ∗ 10.4 ∗ 175
 
5.535
    = 1315 kN/m 

C3.9 Worked Example 2 

b1 = 9.1 m 

b2 = 4.9 m 

L = 12.2 m 

Step 1:  Configuration Details 

Dimensions      See illustration above 
Floorboard type     Tongue & groove 
Floorboard size     135 mm x 25 mm       
Joist size      55 mm x 295 mm 
Joist spacing      500 mm crs 
Joist direction      North‐south 
Joist connection    Lapped with no mechanical connection 
Joist bracing      50 mm x 70 mm, X‐pattern  
Joist bracing location     1/3 along length of joists 
Nail schedule      2 nails per floorboard‐joist connection 
Nail spacing      95 mm 

Step 2:  Select Condition Rating 

Condition      Fair 

Step 3:  Select Characteristic Values 

North South Direction 

Given  the  orientation  of  the  joists,  loading  in  the  north  south  direction  would  be  ‘parallel  to 
joists’. 

  C3‐17
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

Shear stiffness and shear strength from Table 3‐6: 

Gd    = 255 kN/m 

Qn    = 1.3 kN/m 

Ductility capacity from Table 3‐7: 

μ    = 5 

Damping for all diaphragms: 

    = 5% 

East West Direction 

Similarly it can be shown that for loading direction perpendicular to joists: 

Gd    = 125 kN/m 

Qn    = 0.8 kN/m 

μ    = 5 

    = 5% 

Step 4:  Diaphragm Stiffness Calculation 

North South Direction 
 

4
 
 

With reference to Table 3‐8: 

L e  = L  = 12.2 m 
. .
be  =    = 7.0 m 

Using Equation 3‐2: 

αp    = 1.0 (no penetrations) 

And using Equation 3‐3: 

αc  =  1.0  (until  reduction  factors  for  diaphragm  configuration  variations  are 
determined) 

Hence: 
1.0 ∗ 1.0 ∗ 4 ∗ 7.0 ∗ 255
 
12.2
    = 585 kN/m 

East West Direction 

Similarly it can be shown that: 

C3‐18   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 
. .
L e  =    = 7.0 m 

be  = b  = 12.2 m 

αp    = 1.0     

αc    = 1.0     
1.0 ∗ 1.0 ∗ 4 ∗ 12.2 ∗ 125
 
7.0
    = 871 kN/m 

C3.10 Worked Example 3 

L1 = 7.2 m    L2 = 7.2 m 

b2 = 6.2m 

L1 = 12.4 m 

b1 = 6.2m 

L1 = 14.4 m

Step 1:  Configuration Details 

Dimensions      See illustration above 
Floorboard type     Straight edge 
Floorboard size     150 mm x 25 mm       
Joist size      50 mm x 350 mm 
Joist spacing      400 mm crs 
Joist direction      East‐west 
Joist connection    Butted with bolted light steel plate 
Joist bracing      50 mm x 70 mm, X‐pattern  
Joist bracing location     Approximately 3.0 m crs along joist length 
Nail schedule      2 nails per floorboard‐joist connection 
Nail spacing      110 mm 

Step 2:  Select Condition Rating 

Condition      Fair 

  C3‐19
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

Step 3:  Select Characteristic Values 

North South Direction 

Given the orientation of the joists, loading in the north south direction would be ‘perpendicular 
to joists’. 

Shear stiffness and shear strength from Table 3‐6: 

Gd    = 125 kN/m 

Qn    = 0.8 kN/m 

Ductility capacity from Table 3‐7: 

μ    = 5 

Damping for all diaphragms: 

    = 5% 

East West Direction 

Similarly it can be shown that for loading direction parallel to joists: 

Gd    = 255 kN/m 

Qn    = 1.3 kN/m 

μ    = 5 

    = 5% 

Step 4:  Diaphragm Stiffness Calculation 

North South Direction 
4
 

With reference to Table 3‐8: 

L e  = 7.2 + 7.2  = 14.4 m 

be  = 6.2 + 6.2  = 12.4 m 

Using Equation 3‐2: 
14.4 ∗ 12.4 7.2 ∗ 6.2
0.75 
14.4 ∗ 12.4
And using Equation 3‐3: 

αc  =  1.0  (until  reduction  factors  for  diaphragm  configuration  variations  are 
determined)     

Hence: 
0.75 ∗ 1.0 ∗ 4 ∗ 12.4 ∗ 125
 
14.4

C3‐20   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

    = 323 kN/m 

East West Direction 

Similarly it can be shown that: 

L e  = 6.2 + 6.2  = 12.4 m 

be  = 7.2 + 7.2  = 14.4 m 

αp    = 0.75     

αc    = 1.0     
0.75 ∗ 1.0 ∗ 4 ∗ 14.4 ∗ 255
 
12.4
    = 889 kN/m 

C3.11 References 
ABK.  (1981).  "Methodology  for  mitigation  of  seismic  hazards  in  existing  unreinforced  masonry 
buildings:  Diaphragm  testing."  ABK‐TR‐03,  National  Science  Foundation,  El  Segundo, 
California. 
ASCE.  (2007).  Seismic  rehabilitation  of  existing  buildings,  ASCE/SEI  41‐06.  American  Society  of 
Civil Engineers, Reston, VA. 
Australian/New  Zealand  Standard  (2000).  AS/NZS  1080.3:2000  Timber  ‐  Methods  of  Test  ‐ 
Method 3: Density, Standards New Zealand (electronic copy). 
Australian/New Zealand Standard (2007). AS/NZS 4063.1:2007 Structural timber ‐ Characteristic 
values of strength‐graded timber ‐ Part 1: Test methods. Standards Australia (draft only). 
Chopra, A. K. (2007). Dynamics of Structures: Theory and Applications to Earthquake Engineerin., 
Prentice Hall, Upper Saddle River, NJ, 3rd edition. 
ICC. (2006). International Existing Building Code. Country Club Hills, Illinois, USA. 
International  Organization  for  Standardization  (2008).  Draft  International  Standard 
ISO/DIS 10984‐2  Timber  structures  ‐  Dowel‐type  fasteners  ‐  Part  2:  Determination  of 
embedding strength and foundation values. International Organization for Standardization, 
Geneva, Switzerland. 
Mahin,  S.  A.,  and  Bertero,  V.  V.  (1981).  "An  evaluation  of  inelastic  seismic  design  spectra." 
Journal of the Structural Division, 107(ST9), 1777‐1795. 
NZSEE  (2006).  Assessment  and  improvement  of  the  structural  performance  of  buildings  in 
earthquakes: Recommendations of a NZSEE study group on earthquake risk buildings, New 
Zealand Society for Earthquake Engineering. 
Oliver, S. (2010). "Personal communication." A. W. Wilson, Auckland, New Zealand. 
Standards  Association  of  New  Zealand.  (1993).  NZS  3603:1993,  Timber  Structures.  Standards 
New Zealand, Wellington, New Zealand. 
Standards Association of New Zealand. (2002a). AS/NZS 1170.1:2002, Structural Design Actions 
Part 0: General Principles. Standards New Zealand, Wellington, New Zealand. 
 

  C3‐21
 
  Section C3 ‐ Material Properties of Flexible Timber Floor Diaphragms
 
 

C3‐22   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C4 ‐ Design Actions on In‐plane Loaded 
Unreinforced Masonry Walls 

C4.1 Notation 
C1  Modification  factor  to  relate  expected  maximum  inelastic  displacement  to  that 
calculated for linear elastic response 
C3  Modification  factor  to  represent  increased  displacements  due  to  dynamic  P‐delta 
effects 
C(Ti)  The elastic site hazard spectrum for a period of Ti in the direction being considered 
Cd(Tw)  Horizontal design action coefficient 
Kd  Diaphragm stiffness, kN/m 
n  Number of diaphragms 
Ti  The period of the diaphragm at storey i, s 
Ts  The characteristic period of the response spectrum, s 
Tw  Period of the in‐plane wall, s 
Vd  Shear force transferred from the diaphragm, kN 
Vw  Horizontal seismic shear force induced from the inertial forces of the in‐plane wall, kN 
Vdi  Shear force transfer from the diaphragm at level i, kN 
Vsi  Storey shear force for level i, kN 
Wd  Total seismic weight tributary to the diaphragm, kN 
Ww   Total dead load of the in‐plane wall, kN 
Δd  The  maximum  in‐plane  deflection  of  the  diaphragm,  due  to  a  lateral  load  in  the 
direction under consideration equal to the weight tributary to the diaphragm, m 
αw  Modification factor for period of diaphragms to account for out‐of‐plane wall stiffness 

C4.2 Scope 
This section details recommendations for the determination of design seismic forces for in‐plane 
loaded  walls  of  unreinforced  masonry  buildings  with  flexible  diaphragms.  The  storey  shear 
design action defined in Section 4.3.2.9 shall be considered against the capacity of the individual 
elements calculated in Sections 8–12. 

C4.3 Analysis Procedures 
Linear analysis procedures are appropriate when the expected level of nonlinearity is low. Static 
procedures are appropriate when higher mode effects are not significant, which is generally true 
for  short,  regular  buildings.  Dynamic  procedures  are  required  for  tall  buildings,  buildings  with 
torsional irregularities, or non‐orthogonal systems. 

The  Nonlinear  Static  Procedure  is  acceptable  for  most  buildings,  but  should  be  used  in 
conjunction with the Linear Dynamic Procedure if mass participation in the first mode is low. 

  C4‐1
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

The term “linear” in linear analysis procedures implies “linearly elastic”. The analysis procedure, 
however,  may  include  geometric  nonlinearity  of  gravity  loads  acting  through  lateral 
displacements  and  implicit  material  nonlinearity  of  concrete  and  masonry  components  using 
properties  of  cracked  sections.  The  term  “nonlinear”  in  nonlinear  analysis  procedures  implies 
explicit material nonlinearity or inelastic material response, but geometric nonlinearity may also 
be included. 

C4.3.1 Modelling of the Structure 
Plane  frame  analysis  will  provide  reasonably  accurate  predictive  capacity  if  the  following 
considerations are observed: 

(a) Because  of  the  importance  of  shear  deformation  in  URM  buildings,  the  approach  of 
NZS 3101  of  incorporating  shear  deformation  through  a  reduced  flexural  stiffness  is  not 
recommended.  Instead,  shear  and  longitudinal  strains  should  each  be  specifically  allowed 
for. 

(b) Regions  common  to  two  or  more  intersecting  members  (joint  panel  zones)  may  require 
special  attention.  Parametric  studies  indicate  that  the  member  cross‐sections  may  be 
assumed  to  penetrate  unmodified  to  the  intersection  point  or  may  be  assumed  to  have 
stiffer  (or  rigid)  end  sections.  Examination  of  stresses  in  the  joint  regions  is  seldom 
necessary. 

(c) Much of the seismic mass of most unreinforced masonry buildings (particularly those with 
timber floors) lies in the walls themselves. This mass distribution, coupled with the size of 
the  members,  suggests  that  large  inertia  effects  may  be  involved.  Rocking  modes  in 
particular,  but  also  other  modes,  will  involve  rotational  accelerations  and  vertical 
accelerations that are of greater importance than in modern skeletal structures. Modelling 
of the mass distribution is therefore important. 

(d) To  be  able  to  predict  inelastic  strains,  some  form  of  pushover  analysis  is  desirable. 
However, this exercise need not necessarily require sophisticated software as simple hand 
procedures will often suffice. 

The preferred method is to model the elements as assemblages of plane stress elements, shell 
elements,  or  solid  three‐dimensional  elements  (so‐called  “brick”  elements).  Reasons  for  this 
include the relative ease with which the structure can be accurately described and because the 
strains and stresses can be monitored. However, sufficiently sophisticated software is not readily 
accessible and the computational costs can be high. 

Plane stress element modelling might use one of the following three levels of complexity, with 
each level representing progressively greater abstraction. 

(a) Modelling  may  treat  the  mortar  as  separate  elements  from  the  bricks.  Given  the  relative 
thinness  of  the  mortar  bed  joints  it  seems  appropriate  to  model  these  joints  as  line 
elements,  with  quadrilateral  elements  used  for  the  bricks.  It  is  common  to  ignore  the 
effects of head joints, except to determine failure criteria. Separate failure criteria are used 
for each of the bricks and the mortar. Gap elements can be introduced to model separation 

C4‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

of layers (or laminae) at bed joints. Properties of the materials (or of the earthquake effects 
at  the  site)  are  seldom  known  sufficiently  fully  to  warrant  this  level  of  modelling,  which 
might  be  used  for  very  important  historic  buildings  or  for  smaller  sections  of  larger 
assemblages. 

(b) The  properties  of  the  mortar  joints  and  of  the  bricks  can  be  combined  using 
homogenisation techniques. The weighted properties are then used to produce continuum 
elements.  For  best  results,  sampling  and/or  integration  points  are  aligned  with  the  bed 
joints,  with  or  without  gap  elements.  It  is  common  to  use  the  initial  (elastic)  stiffness 
throughout, with appropriate iteration at each load step. 

(c) The  most  abstract  modelling  combines  the  stiffness  and  strength  properties  of  the  bricks 
and  mortar  as  above,  but  otherwise  treats  the  masonry  as  a  continuum.  It  is  common  to 
assume  that  the  masonry  is  isotropic.  Gap  elements  are  seldom  included.  This  level  of 
complexity  is  suited  to  large  structures  and  produces  adequate  results  for  assessment 
purposes. 

For complex  structures, particularly  those with ineffective or flexible  diaphragms, modelling of 


the structure in three dimensions as an assemblage of walls or frames is often helpful. However, 
it should then be appreciated that for modal response spectrum techniques a large number of 
modes may need to be considered in order to ensure that an adequate proportion of the total 
mass participates (as required by NZS 1170.5). Note that the total effective mass at 90% of the 
total mass, as specified in NZS 1170.5, may be difficult to achieve. 

Plane  stress  elements  can  be  employed  for  modelling  in  three  dimensions.  However,  because 
these elements have only two degrees of freedom at each node, some contrivance is necessary 
to  prevent  numerical  instability.  One  means,  in  which  spring  elements  are  added  to  the 
necessary degrees of freedom, is often sufficient. However, the allocation of mass to the nodes 
must  then  be  made  using  other  techniques,  usually  at  the  expense  of  accurate  predictive 
capacity. Use of shell elements or three‐dimensional “brick” elements overcomes this difficulty, 
but  at  some  computational  expense.  Suitable  approximations  can  often  be  employed  to  allow 
adequate rigour using two‐dimensional analyses. These approximations include: 

(a) Inclusion  of  return  walls  that  might  be  lifted  when  the  wall  under  study  is  deflected.  The 
width  of  return  wall  that  is  affected  can  be  assessed  from  the  shear  stresses  at  the 
intersection  of  the  two  walls.  However,  this  approach  should  be  pursued  with  caution,  as 
there may be discontinuous bonding at corners. 

(b) Because masonry structures are commonly very stiff, even after  cracking, ordinary timber 


floors and roof systems do not possess sufficient stiffness in comparison with the masonry 
elements to qualify the floors and roofs for the normal assumption of rigidity. Collections of 
smaller  assemblages  of  a  few  walls  or  frames  can  then  be  chosen,  with  the  immediately 
tributary areas used for accumulation of masses and gravity loads to these assemblages. As 
deflections are often small, even when the separate assemblages act out‐of‐phase, relative 
deflections between assemblages will seldom pose any serious problems. Care needs to be 
taken to ensure that the building as a whole is torsionally stable. 

  C4‐3
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

Whatever the modelling  employed, it  is usually not necessary to consider interaction  between 


the  in‐plane  and  out‐of‐plane  behaviour.  Throughout  this  section,  in‐plane  behaviour  is 
discussed as if out‐of‐plane behaviour is not involved at all. 

Three‐dimensional  analysis  that  allows  for  the  interaction  of  in‐plane  and  out‐of‐plane  effects 
can  be  conducted,  but  the  necessary  software  is  not  yet  readily  available  and  its  use  requires 
good modelling and interpretative skills. 

It should be appreciated that computer programs are an aid to rapid design and evaluation, and 
are  not  essential  to  the  assessment  procedures  described  in  Section  4.  Some  examples  use 
simple  hand  calculation  for  inelastic  effects.  However,  computer  programs  are  almost 
indispensable for rigorous elastic analyses and for modal response spectrum analyses. 

It is recommended to verify the analytical predictions of the numerical models with the actual 
response  measured  in  the  structure,  and  improve  the  model  accordingly.  For  this  purpose 
experimental  or  operational  modal  analysis  techniques  can  be  applied  in  combination  with 
model updating procedures. 

C4.3.1.1 Numerical Modelling of URM Buildings 

Although  structural  analysis  software  has  existed  since  the  1960’s  and  the  first  non‐linear 
analysis  programs  were  developed  in  the  mid  1970’s  (Kelly  2004),  numerical  modelling  of 
unreinforced  masonry  structures  is  still  a  computationally  demanding  procedure  in  terms  of 
memory capacities and processing time. This elevated numerical cost is related to the intrinsic 
complexity of masonry (arrangements of bricks connected by mortar joints) that requires a large 
number  of  degrees  of  freedom  for  modelling  (Giordano,  et  al.  2002)  and  excludes  the  typical 
simplifications  and  assumptions  that  are  suitable  for  other  kinds  of  structures  (homogeneous 
materials,  rigid  diaphragms,  connections  with  linear  behaviour,  etc.).  Another  reason  for  this 
complexity  is  the  material  non‐linear  behaviour,  whose  mechanical  characteristics  are  strongly 
dependant on the characteristics of local materials and, consequently, are not easy to describe 
by  a  general  constitutive  model.  To  address  these  problems,  different  numerical  procedures 
have  been  proposed  for  URM  structures,  which  can  be  grouped  into  three  main  categories: 
macro‐modelling, micro‐modelling and homogenized finite element modelling. 

C4.3.1.2 Macro‐modelling 

The  simplest  and  most  economical  approach  is  to  model  the  structural  components  (e.g. 
columns,  beams,  walls,  floors)  with  a  single  modelling  resort  (e.g.  truss,  frame,  panel  or  shell 
elements).  In  this  category  are  included  lumped‐mass  models,  equivalent  frame  models  and 
macro  element  representations.  These  models  are  especially  recommended  for  time‐history 
analysis using ground motion records and non‐linear constitutive material models. The models 
provide  information  about  the  overall  performance  of  the  structure,  but  are  poorly 
representative  of  the  local  behaviour  of  the  elements,  such  as:  crack  propagation,  failure  of 
individual elements and damage localization (Lourenço 2004).  

C4‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

In the last decade, some software packages have been developed to analyze masonry structure 
using  a  macro‐modelling  approach  (Lagomarsino  et  al.  2004;  Magenes  et  al.  2003)  and  other 
programs have incorporated modelling resorts to represent the masonry behaviour (Carr 2004). 
Good  examples  of  this  kind  of  approach  are  presented  in  the  works  of  Doherty  et  al.  (2002), 
Pasticier et al. (2007), Chen et al. (2008) and Augenti and Romano (2008).  

C4.3.1.3 Micro‐modelling 

In  a  micro‐modelling  approach,  an  analysis  based  on  the  characteristics  of  each  component 
(brick and mortar) are performed separately. The model discretization of the structure follows 
the actual geometry of the brick and mortar joint arrangement, and adopts different constitutive 
models for each component. Special attention is given to the interfaces, as they are considered 
to be the weakest member where tensile‐sliding failure can be expected. In most cases, it can be 
considered that all the non‐linear behaviour of the combined material occur in the mortar joints. 
A complete micro model must include all the failure mechanisms of masonry, namely: cracking 
of joints, bed‐joint sliding and cracking or crushing of the masonry units (Lourenço 2004).  

Micro‐modelling  is  preferred  for  simple  structures  (such  as  a  single  wall)  and  for  rigorous 
analysis of the local stress‐strain behaviour of masonry to predict crack propagation. The use of 
these  procedures  is  still  primarily  restricted  to  research  applications,  because  the  approach 
demands a high computational effort in terms of numerical processing and memory. 

In micro‐modelling, three models appear to be the most effective and widely used to represent 
URM  structures:  the  finite  elements  method  with  discrete  elements  (FEMDE),  the  discrete 
elements method (DEM) and the rigid blocks limit state analysis (RBLSA).  

In FEMDE, bricks are represented by deformable or rigid continuum elements, while the mortar 
joints are simulated by non‐linear interface layers. The brick‐mesh and the interface‐mesh have 
the same joints along the contact surface. In this group of micro‐models, remarkable works are 
the studies conducted by Lourenço and Rots (1997) and Gambarotta and Lagomarsino (1997a) 
and, more recently, the research of Sacco (2009).  

In  DEM,  the  structure  is  considered  as  an  assembly  of  rigid  or  deformable  blocks,  connected 
through  elasto‐plastic  link  elements  (non‐linear  springs).  These  elements  follow  a  degrading 
hysteretic rule to represent the brittle behaviour of the masonry. The main  advantages of this 
method  are  an  adequate  formulation  for  large  displacements,  the  chance  to  follow  the 
displacement  of  every  block,  and  a  better  prediction  of  the  collapse  mechanism.  The 
disadvantage  of  this  method  is  the  large  number  of  link  points  required  to  represent  the 
interface  stresses  accurately,  which  means  time  and  memory  consuming  analysis.  Interesting 
studies that have applied this method are Formica et al. (2002) and Casolo and Peña (2007). 

The RBLSA method has received less attention from the structural engineering community, even 
though  its  fundamentals  were  established  more  than  thirty  years  ago  (Livesley  1978).  In  this 
approach, the structure is considered as an assembly of non‐deformable blocks. The interactions 
are  represented  through  interfaces  that  are  able  to  transfer  compression  and  shear  stresses 
(using a non‐cohesive Coulomb  criterion),  but not tensile stress. In this method, the kinematic 
problem is mathematically solved by simultaneously satisfying the equilibrium, compatibility and 

  C4‐5
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

the  failure  and  flow  rules  at  each  block’s  contact  surface.  The  numerical  simplicity  and  the 
subsequent fast analysis are the main advantages of this method. However, in this method, it is 
only  possible  to  determinate  the  collapse  load,  but  not  the  collapse  displacement.  Also,  it  is 
difficult  to  include  the  load  history  in  the  analysis  (Lourenço  2008).  A  recent  example  for 
application of this method is presented in Orduña et al. (2007).  

C4.3.1.4 Homogenized Finite Element Modelling  

Homogenized  finite  element  modelling  is  a  meso‐modelling  approach  that  bypasses  the  bi‐
material nature of masonry. URM is considered as a continuum and homogeneous material with 
properties  that  are  equivalent  to  the  average  properties  of  the  combined  material.  These 
properties are incorporated into the model by means of homogenization techniques (Milani et 
al.  2006;  Yu  et  al.  2008;  Addessi  et  al.  2010;  Casolo  and  Milani  2010).  This  representation  of 
masonry  allows  the  use  of  traditional  finite  element  (FE)  modelling  techniques,  which  do  not 
require modelling of the arrangement of each brick. 

Homogenized  FE  modelling  allows  analysis  with  more  complicated  excitations  and  non‐linear 
constitutive  material  models  (non‐linear  time‐history  analysis).  This  procedure  also  provides 
good  information  about  the  local  performance  of  the  structural  elements  (e.g.  crack 
propagation, stress and strain distribution). All these characteristics make this method especially 
interesting  for  the  analysis  of  real  structures;  however,  their  computational  cost  is  high.  The 
main difficulty in implementing these techniques is the lack of experimental data regarding the 
linear  and  non‐linear  behaviour  of  masonry.  However,  several  researchers  have  proposed 
constitutive  models  that  characterize  the  anisotropic  and  quasi‐brittle  behaviour  of  masonry 
(Lourenço and Rots 1997; Formica, et al. 2002; Gambarotta and Lagomarsino 1993). Interesting 
works to refer to about this method are Gambarota and Lagomarsino (1997a; 1997b), Berto et 
al. (2004) and Brasile et al. (2007a; 2007b; 2010)  

C4.3.1.5 Verification and Tuning of Numerical Models of URM Structures 

Currently,  there  is  an  increasing  concern  to  develop  techniques  to  determine  the  degree  of 
coherence  between  model  prediction  and  the  actual  behaviour  of  buildings.  This  interest  has 
originated from the need for accurate models that predict the performance of existing masonry 
structures, not only under operational conditions, but also under extreme events (strong winds, 
earthquakes,  imposed  loads,  etc.).  Accurate  models  aid  in  the  optimal  design  of  retrofit 
interventions. 

In  general,  current  models  have  been  validated  by  studies  based  on  structural  component 
behaviour (e.g. walls, piers, spandrels). However, a validation at system level (entire buildings or 
sections  of  building)  is  still  necessary.  In  the  last  twenty  years,  several  techniques  have  been 
developed for quantitatively assessing the structural health condition of existing buildings and, 
also, to verify the concordance of the proposed models with actual structural response. One of 
the most attractive approaches to this subject corresponds to methods based on recording the 
dynamic  structural  response  generated  by  small  magnitude  excitations.  The  information 
extracted  from  this  test  is  used  later  to  improve  the  numerical  models.  Then,  the  updated 

C4‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

models  are  employed  to  predict  the  structural  response  under  large  magnitude  excitations.  In 
these  techniques,  procedures  such  as  modal  testing,  system  identification,  model  verification 
and updating are applied.  

Modal testing and system identification are two techniques, that combined are able to extract 
data  from  physical  dynamic  tests  (response  time‐series  records)  and  utilize  this  data  to 
determine  the  dynamic  characteristics  of  the  structure,  normally  expressed  in  terms  of  modal 
properties (natural frequencies, mode shape and modal damping). Then, these modal properties 
are used to obtain the physical properties of the system (mass, stiffness and damping matrices) 
required to develop a mechanical model of the system (Figure C4‐1).  

Figure C4‐1: Modal testing and system identification procedure 

Traditionally, modal data has been obtained from measurements of the excitation applied to the 
structure (input) and the structural response (output). This approach is known as experimental 
modal analysis (EMA). Another approach is operational modal analysis (OMA). OMA utilizes only 
response measurements of the structure in its operational condition when subjected to ambient 
or  natural  excitation  to  identify  modal  characteristics.  Further  explanations  about  the 
fundamentals  of  experimental  and  operational  modal  analysis  are  presented  in  the  references 
(Ewins 2000; He and Fu 2001; Heylen et al. 1997; Silva and Maia 1999; Juang 1994; Brownjohn 
2007).  A  number  of  methods  have  been  proposed  to  obtain  the  modal  parameters  from 
vibration  measurements,  which  can  be  classified  as  time‐domain  and  frequency‐domain 
techniques. Some of these procedures are briefly presented in Table C4‐1. Detailed descriptions 
of  each  method  are  presented  in  Ewins  (2000),  He  and  Fu  (2001)  and  the  references  that  are 
presented in Table C4‐1.  

  C4‐7
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

Table C4‐1: Modal parameter extraction methods 

Peak picking method (Bendat and Piersol 1993) 
Frequency‐domain 

Circle‐fit method (Maia 1999) 
Inverse frequency response function method (Ewins 2000) 
Dobson’s method (Dobson 1987) 
Frequency domain decomposition (Brincker et al. 2000) 
Enhanced frequency domain decomposition (Brincker et al. 2001) 

Least square time domain method (Smith 1981) 
Ibrahim’s method (Ibrahim and Mikulcik 1976) 
Time‐domain 

Random decrement method (Ibrahim 1977) 
Auto‐regression moving average (ARMA) method (Andersen et al. 1995) 
Eigen‐system realization algorithm (ERA) (Juang and Pappa 1985) 
Stochastic subspace identification method (van Overschee and de Moor 1996) 
 

Model updating techniques automate the procedures of reducing the discrepancies between the 
numerical  model  predictions  and  the  observed  behaviour  measured  in  the  real  structure  (Link 
2001).  The  basic  steps  to  validate  and  improve  the  predictions  of  a  numerical  model  are:  (a) 
comparison and correlation of model and experimental results, (b) model conciliation and error 
localization, and (c) model correction (Ewins 2001). 

Recently,  many  experiences  on  modal  testing  and  model  updating  techniques  applied  to  civil 
engineering  structures  have  been  published,  such  as:  Bagchi  (2005),  Castillo  and  Boroschek 
(2005), Jaishi and Ren (2005; 2007), Skolnik et al. (2006), Pavic et al. (2007), Pallares et al. (2009), 
and Núñez and Boroschek (2010). However, few studies on URM structures are available, with 
most considering relatively slender structures (towers, minarets, chimneys, etc): De Sortis et al. 
(2005), Bayraktar et al. (2008), Gentile et al. (2009), and Ramos et al. (2010).  

C4.3.2 Equivalent Static Method 
The  simplified  linear  static  analysis  presented  herein  is  based  on  the  simplified  analysis 
presented  in  FEMA  356  (2000),  which  was  the  precursor  document  to  ASCE/SEI  41‐06  (2007). 
The  equivalent  static  method  assumes  that  the  in‐plane  loaded  masonry  shear  walls  are 
relatively  rigid  elements  which  do  not  amplify  the  earthquake  ground  motions  with  increasing 
height.  The  dominant  mode  of  response  of  the  URM  building  is  assumed  to  be  the  in‐plane 
fundamental  mode of each of  the diaphragms excited  by  the inertial force of the out‐of‐plane 
loaded  URM  walls.  The  dynamic  response  of  unreinforced  masonry  buildings  is  dominated  by 
the behaviour of the flexible timber diaphragms in their fundamental mode. An assumption of 
rigid diaphragm behaviour may lead to unconservative assessments of diaphragm accelerations 
and  inaccurate  estimates  of  load  distribution  between  lateral  load  resisting  elements  (Oliver, 
2010). 

C4‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

A URM building with flexible diaphragms does not have a defining fundamental period that can 
be identified by a mass participation of greater than 80%. Instead, the dynamic response is more 
closely described by a system of single degree of freedom systems. Each diaphragm responds at 
its own natural frequency based on its geometry, stiffness and tributary mass, and is considered 
uncoupled from the response of adjacent stories. 

C4.3.2.1 Limitations of this Section 

Section 4.3.2.1 sets out the limitations of the Equivalent Static Method. The simplified method 
for finding the force demand only applies to the specific case of unreinforced masonry buildings 
with  flexible  timber  diaphragms  at  all  storey  levels,  up  to  a  maximum  of  six  stories.  This 
restriction of the analysis method is unlikely to be limiting in its use as a study on the prevalence 
and  typology  of  New  Zealand  URM  buildings  has  found  that  of  all  the  URM  buildings  in  New 
Zealand only 14% exceed two stories in height, and less than 1% are over five stories in height 
(Russell and Ingham 2010). 

C4.3.2.2 In‐plane Loads on Shear Walls 

The  in‐plane  loads  on  shear  walls  are  calculated  from  two  components,  one  based  on  the 
diaphragm response, and the other based on the wall in‐plane response. The dynamic response 
of a multi‐storey unreinforced masonry building with flexible diaphragms is concentrated in the 
diaphragms. The equivalent static method assumes that the in‐plane wall is rigid in comparison 
to  the  flexible  diaphragm  for  the  purpose  of  calculating  the  inertial  force  induced  in  the 
diaphragm.  Adequate  connections  between  the  diaphragm  and  the  in‐plane  loaded  walls  are 
required in order to transfer the inertial force induced in the diaphragms and the out‐of‐plane 
loaded walls into the in‐plane loaded walls.  The wall in‐plane response component is based on 
the shear wall behaving in its fundamental mode. For solid shear walls, calculation of the elastic 
stiffness  and  therefore  period  is  relatively  simple,  but  for  the  case  of  perforated  walls  this 
calculation is much more complicated and hence the recommendation that the in‐plane loaded 
wall period is assumed to lie in the constant acceleration region of the response spectra. 

The two components of shear load are based on the pseudo lateral load calculation outlined in 
FEMA  356  (2000)  and  adopted  by  the  NZSEE  (2006)  guidelines.  Further  explanation  of  the 
background to the equation can be found in section 3.3.1 of FEMA 356. 

C4.3.2.3 Damping 

Unreinforced masonry does not respond is a classical elastic‐plastic manner, exhibiting more of a 
nonlinear elastic response with pinched hysteretic loops. From analysis of full scale pseudo‐static 
tests  on  in‐plane  loaded  flanged  walls  and  spandrel/pier  sub‐structures,  a  range  of  5‐15% 
equivalent  hysteretic  damping  was  found.  The  past  recommendation  of  15%  of  critical  was 
formed  from  a  combination  of  approximately  5%  inherent  viscous  damping  associated  with 
elastic structures, 5% hysteretic damping and 5% damping from dynamic impact (NZSEE, 2006). 
The  hysteretic  damping  includes  Coulomb  (or  “dry”)  damping  associated  with  sliding  shear, 
radiation damping, pinched hysteretic damping associated with flexural/diagonal shear softening 

  C4‐9
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

and  equivalent  damping  due  to  impact  on  rocking.  The  current  recommendation  of  5%  is  a 
reduction from the 15% recommended by Magenes and Calvi (1997) and advocated in the NZSEE 
(2006) guidelines, and is supported by the increase in displacement ductility recommended for 
use in finding demand on in‐plane loaded URM shear walls which allows for a reduction in loads 
based  on  nonlinear  behaviour.  The  recommendation  of  5%  of  critical  is  based  on  the 
understanding  that  the  increase  in  ductility  to  2,  and  the  reduction  due  to  the  structural 
performance  factor,  allows  for  the  reduction  in  load  due  to  nonlinear  response  and  therefore 
the reduction would be two‐fold if damping was also increased. 

C4.3.2.4 Ductility and Structural Performance Factor 

Unreinforced  masonry  is  generally  considered  a  brittle  material  and  therefore  it  has  been 
justified in the past to use a  displacement ductility  factor of 1.  The  notion of  URM as a  brittle 
material  is  inaccurate  and  conservative.  Ductility  is  present  not  from  conventional  yielding  of 
steel  reinforcing  bars,  but  from  inelastic  response  and  energy  dissipation  due  to  shear  sliding 
along mortar joints and rocking of masonry block elements.  When URM walls respond in‐plane, 
particularly with a rocking mechanism, there is significant inelastic displacement capacity and a 
strongly nonlinear behaviour.  A typical shear response is shown in Figure C4‐2(a), and shows no 
rapid and severe strength loss as associated with a typical brittle failure. The force‐displacement 
plot associated with pier and pier/spandrel sub‐structure testing indicates that a flexural failure 
mechanism,  or  a  flexural/shear  combined  failure  mechanism,  is  capable  of  ultimate 
displacements  that  greatly  exceed  the  yield  displacement,  as  shown  in  Figure  C4‐2(b).  URM 
buildings  have  multiple  sources  of  ductility  that  develop  from  energy  dissipation  drawn  from 
shear mechanisms in the in‐plane loaded walls, rocking of in‐plane loaded URM elements, and 
energy dissipation from deformations of the timber diaphragms. The recommendation for using 
a displacement ductility of 2 recognises the nonlinear response of URM walls to in‐plane loading 
and the energy dissipation that occurs during loading cycles beyond the elastic state. This value 
of  displacement  ductility  of  2  corresponds  to  a  structural  performance  factor  of  0.7  as  per 
NZS 1170.5. The structural performance factor of 0.7 allows for a decrease in elastic site hazard 
spectra based on observations of strength reduction and stiffness degradation apparent in the 
second and third testing cycles to a specific displacement. It is noted that these values are put 
forth as a recommendation and it is expected that the designer apply these or other values as 
they  feel  appropriate  for  the  condition  of  the  building  under  assessment.  If  a  value  of  1  is 
adopted  for  both  the  displacement  ductility  and  the  structural  performance  factor  then  an 
increase in damping to 15% is recommended. 

C4‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 
 
(a) URM pier  (b) URM spandrel substructure 

Figure C4‐2: Plots of Force‐displacement response of URM assemblages 

C4.3.2.5 Diaphragm Shear Load Transfer 

Coefficient C1 is a modification factor used to account for the difference in maximum elastic and 
inelastic  displacement  amplitudes  in  a  structure  exhibiting  relatively  stable  and  full  hysteretic 
loops.  The  values  of  the  coefficient  are  based  on  analytical  and  experimental  investigations  of 
the  earthquake  response  of  yielding  structures  (NZSEE,  2006).  See  ASCE/SEI  41‐06  (2007)  for 
further discussion. 

Coefficient  C3  is  the  modification  factor  for  framing  systems  that  exhibit  negative  post‐yield 
stiffness,  as  dynamic  P‐Δ  effects  may  lead  to  significant  amplification  of  displacements  for 
buildings  exhibiting  this  characteristic.  Such  effects  cannot  be  explicitly  addressed  with  linear 
procedures  as  no  measure  of  the  degree  of  negative  post‐yield  stiffness  can  be  explicitly 
included in a linear procedure (NZSEE, 2006).  When the stability coefficient is less than 0.1 in all 
stories the p‐delta effects need not be considered.  If the stability factor is between 0.1 and 0.33, 
the  seismic  actions  and  deformations  shall  be  increased  according  to  equation  4‐4.  When  the 
stability factor exceeds 0.33, the structure shall be considered unstable and retrofit intervention 
to reduce the computed lateral deflections is required (FEMA 356, 2000). 

C4.3.2.6 Period of Diaphragms 

From experimental research it has been established that diaphragm deformations are governed 
primarily  by  shear  deformations  rather  than  flexural  deformations.  The  source  of  the  period 
equation expressed in section 4.3.2.6 is based on the shear deflection of a beam. As outlined in 
Chopra (2001), a shape function can be used to describe the beam deformations, which can then 
be used to develop a generalised mass and generalised stiffness for shear.  This information can 
then  be  introduced  to  the  generalised  period  equation  to  obtain  a  specific  expression  for  the 
period. A more detailed explanation can be found in Knox (2011). 

  C4‐11
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

It  is  important  to  use  the  correct  stiffness  value,  as  the  stiffness  of  the  diaphragm  varies 
significantly with direction of loading with respect to the orientation of the joists. 

The reduction factor   is based on modelling conducted on the effect of the out‐of‐plane wall 
stiffness on the period of the diaphragm. 

C4.3.2.7 In‐plane Inertial Shear Load 

The in‐plane inertial shear load calculation uses the equivalent static method outlined in section 
5.2  of  NZS 1170.5.  The  damping,  ductility  and  structural  performance  factor  pertinent  to  URM 
in‐plane loaded shear walls is applied through the reduction of the response spectra value and 
the calculation of the horizontal design action coefficient. 

C4.3.2.8 Vertical Distribution of Inertial Shear Load 

The  rectangular  distribution  of  the  inertial  shear  load  vertically  up  the  height  of  the  building 
reflects the assumption of effectively rigid wall response in comparison to the flexible diaphragm 
response. A rectangular distribution implies no modification of the ground accelerations up the 
height of the wall. 

C4.3.2.9 Storey Shear Load 

Storey  shear  load  is  the  addition  of  the  diaphragm  shear  load  and  the  component  of  in‐plane 
inertial shear load distributed to that level using the Square Root of Sum of Squares rule. 

C4.3.2.10 Total Shear Load 

Summation  of  the  inertial  storey  shear  load  and  the  individual  diaphragm  shear  loads  using  a 
CQC  or  SRSS  method  allows  for  the  individual  elements  to  respond  at  different  periods  and 
therefore not necessarily in phase.  

The  SRSS  rule  for  modal  combination,  developed  by  Rosenblueth  (1951)  is  given  in  Equation 
C4‐1. 

  (C4‐1)

The complete quadratic combination (CQC) rule is given in Equation C4‐2. 

  (C4‐2)

Where:   is the peak response of  the  nth mode,   is the peak response of  the ith mode,  and  


 is the correlation coefficient for the two modes n and i, seen in Equation C4‐3, and 
varies between 0 and 1. 

C4‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

/
8
  (C4‐3)
1 4 1 4

Where: 
 and   is the damping ratio for mode i.  

A more detailed explanation of the CQC method can be found in Chopra (2007). 

C4.3.3 Modal Response Spectrum Method 
The applicability of this method to URM buildings is currently under review. URM structures do 
not  satisfy  several  of  the  fundamental  hypotheses  required  to  apply  modal  spectral  analysis, 
such  as  rigid  diaphragms,  mass  concentrated  at  diaphragm  levels,  or  well  spaced  and 
differentiated  modes.  In  general,  the  vibration  modes  are  associated  with  the  particular 
response  of  structural  members  (walls,  diaphragms,  parapets,  etc.)  and  not  to  the  global 
building response. 

Although this method might be inappropriate for determining design actions, it is adequate to 
use  the  dynamic  properties  (fundamental  frequency,  modal  damping  and  mode  shapes) 
obtained by this method to update a numerical model. In this process the numerical predictions 
are  contrasted  with  experimental  response  obtained  from  a  vibration  test  (experimental  or 
operational modal test). 

C4.3.4 Inelastic Time History Method 
To assist in the selection of ground motion records for use in inelastic Time History analysis, five 
zones of similar seismological signature have been defined for the North Island of New Zealand 
(Figure C4‐3). The hazard scenarios defined for each of these zones in the period range between 
0.4s and 2.0s are presented in Table C4‐2. 

The  Inelastic  Time‐History  analysis  shall  be  guided  by  the  recommendations  stated  in 
NZS 1170.5:2004. However, it is suggested  to consider the average response of seven or more 
records  for  determining  the  design  actions,  instead  of  the  most  disadvantageous  response  of 
three or more records. 

A companion exercise to identify suitable  ground  motion records for the  South Island, and for 


structures with fundamental periods shorter than 0.4 seconds, has not yet been completed. 

  C4‐13
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

 
Figure C4‐3: Seismic hazard zonation for the North Island of New Zealand for ground motion 
record selection 

   

C4‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Table C4‐2: Recommended suite profile for each seismic zone 

Hazard  Distance
Zone  Magnitude  Tectonic class/Fault mechanism 
scenario  (km) 

A1  5.5 – 6.5  10‐50  Records from regions of extensional 


North A 
A2  6.5 – 7.0  ~20  tectonic regimes 

B1  6.5 ‐ 7.5  40‐70  Shallow crustal earthquakes 

North B  B2  6.5 ‐ 7.0  60‐100  Subduction slab records 

B3  7.5‐8.3  70‐120  Subduction interface records 

C1  7.5 ‐ 8.3  15‐25  Subduction interface records 

C2  7.0 ‐ 7.5  20‐40  Reverse‐faulting records 


North C 
6.5 – 7.0  20‐60  Reverse (or reverse‐oblique) faulting 
C3 
    records 

Shallow crustal earthquakes without 
NF1  7.0 ‐ 7.5  <~10 
pronounced forward‐directivity features 

Records with strong forward directivity 
North NF 
NF2  6.5 ‐ 7.5  <~10  characteristics (2 or 3 records in the suite 
of seven records) 

NF3  7.5 – 8.3  15‐25  Subduction interface records 

Records from regions of extensional 
North V  V1  6.0 – 7.0  <20 
tectonic regimes 
 

NZS1170.5:2004  (SNZ,  2004a  ‐  2004b)  requires  that  suites  of  at  least  three  records  must  be 
considered  for  time‐history  analysis,  and  that  the  most  disadvantageous  response  must  be 
considered  for  design  (for  example,  the  largest  value  of  the  maximum  strength  demands). 
However, when following this criterion the design can be strongly influenced by the response of 
a  specific  ground  motion  with  particularly  strong  peaks.  In  contrast,  other  standards  and 
recommendations  (CEN  2004;  ASCE/SEI  2007)  propose  to  design  considering  the  average 
response of seven or more records. Recent studies (Dhakal et al. 2007; Oyarzo‐Vera and Chouw, 
2008)  have  demonstrated  that  this  latter  option  improves  the  consistency  of  the  time‐history 
analysis,  because  it  reduces  the  influence  of  specific  ground  motions.  Also,  the  results  of 
multiple  simulations  considering  the  average  response  of  seven  time‐history  analyses  offer  a 
lower  dispersion  in  terms  of  the  variability  in  the  results,  than  do  the  results  of  multiple 
simulations  taking  into  account  the  maximum  response  of  three  time‐history  analyses.  In 
addition, in the North Island of New Zealand, there are few locations where the hazard is totally 
dominated  by  one  earthquake  source.  Even  for  sites  adjacent  to  one  of  the  major  strike‐slip 
faults,  there  are  usually  other  nearby  faults,  or  the  underlying  subduction  zone  has  influence, 
especially  for  spectral  periods  of  about  1  second  and  longer.  Thus  seven  accelerograms  for  a 

  C4‐15
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

zone generally covers a wider range of earthquake types or magnitude‐distance combinations. 
Taking into account the international trend, the studies mentioned previously and the particular 
seismic characteristics of the North Island, suites of seven records were defined for each zone 
and soil class. (Oyarzo‐Vera et al. 2011). 

As  URM  structures  do  not  have  well  defined  global  modes,  the  target  period  considered  for 
scaling shall consider the fundamental periods associated with the local modal response of the 
most important structural member (in‐plane wall response, out‐of‐plane wall response, flexible 
diaphragm  response,  parapets,  etc).  For  this  purpose  and  to  reduce  the  number  of  analyses 
required  to  assess  the  response  of  the  different  structural  members,  the  range  of  periods 
considered for scaling can be extended to cover the fundamental periods associated with more 
than one structural member. 

The  study  conducted  by  Oyarzo‐Vera  et  al.  (2011)  suggests  suites  of  records  for  each  zones 
presented  in  Figure  C4‐3,  to  be  used  in  time‐history  analysis  in  the  absence  of  site  specific 
studies.  These  suites  of  records  have  not  been  included  in  this  document,  as  they  can  be 
updated, by replacing or adding new records, according to the state‐of‐the‐knowledge and the 
requirements or future amendments of the Standard. 

C4.4 Design Example 
The  following  is  an  example  calculation  for  finding  the  in‐plane  loads  on  an  unreinforced 
masonry shear wall. 

The example building is a five storey URM building with flexible timber diaphragms at all levels.  
The  building  has  regular  perforations  on  two  parallel  sides  and  mainly  solid  masonry  with 
minimal perforations on the other two sides. The building is located in Auckland, on shallow soil. 
The  floor  plan  is  rectangular,  with  dimensions  of  29.9 m  by  17.9 m.  The  walls  decrease  in 
thickness from five leafs for level one and level two, four leafs for level three and four, and down 
to three leafs for the top level. 

An elevation view of the building’s eastern wall and a plan view of the building dimensions are 
shown in Plan view          (b) Elevation of eastern wall 

Figure C4‐4. Note that this is an extension of the example previously published by Oliver (2010), 
associated with the seismic assessment and improvement of flexible timber diaphragms. 

C4‐16   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

3
0
3
6
0
N

joists
extg

1
7
3
6
0
extg

joists
extg
steel
beam 0
typical 0
0 0
0 2
0
4
5

joists
9
extg 7
3
0
0 0 9
0 6 5
9 3 3
9 0 5
2 3 4
6
3
joists

0
extg

0
7
3
5
5
8
3
0
1
0
joists

4
extg

5
0
2
4
0
0
4 0
4 0
joists

2
extg

2
1
4
0
0

1
4
0
0

1
4
0
0

1
4
0
0

1
4
0
0

1
4
0
0

1
4
0
0
 
(a) Plan view          (b) Elevation of eastern wall 

Figure C4‐4: Layout of example building 

Find Diaphragm Periods: 

Table C4‐3 – Diaphragm Weight 

  Level 1  Level 2  Level 3  Level 4  Level 5 

Diaphragm weight (kN)  1098  1098  1098  1098  1098 

Out‐of‐plane wall weight (kN)  2687  2226.9  1633.9  1199  511.2 

Wd (kN)  3785  3324.9  2731.9  2297  1609.2 


 

Diaphragm Stiffness, Kd:  
4
 

αp    = 1 

αc    = 1 

Gd    =  175 kN/m  (joists perpendicular to loading direction) 

be    = 17.9 m 

L e    = 29.9 m 

  C4‐17
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

1 1 4 17.9 175
419.06 kN/m 
29.9
 

Table C4‐4 – Diaphragm Periods 

  Level 1  Level 2  Level 3  Level 4  Level 5 

= 3785/419   = 3324.9/419 = 2731.9/419  = 2297/419  = 1609.2/419


∆   (m)  
=  9.033  = 7.935  = 6.520  = 5.482  = 3.840 
  = 5.380*0.45  = 5.042*0.45  = 4.570*0.675  = 4.19*0.675  = 3.508*0.9 
1.79 ∆   =2.42  =2.27  =3.08  =2.83  =3.16 
(s) 

  
Note that the deflections calculated in Table C4‐4 are applicable for a 1g acceleration. 

Diaphragm shear load transfer 

 
C1    = 1 

C3    = 1 

Z     = 0.13 

R     =  1 

N(T,D)     = 1 

Ch(Ti)     = spectral shape factor determined from Table 3.1 of NZS 1170.5 

C(Ti)     = Ch(Ti) × Z × R × N(T,D) 

Cd(Ti)     = C(Ti) × Sp / Kμ

Sp     = 0.7 

μ = 2 

kμ    = 2 

Table C4‐5 – Diaphragm Shear Load Transfer 

  Level 1  Level 2  Level 3  Level 4  Level 5 

Ch(Ti)  0.5506  0.5901  0.4196  0.4708  0.4023 

C(Ti)  0.072  0.077  0.055  0.061  0.052 

Cd(Ti)  0.025  0.027  0.019  0.021  0.018 

Vdi (kN)  94.8  89.3  52.2  49.2  29.5 


 

C4‐18   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

In‐plane inertial shear load 

 
Tw     = Unknown, but assume that it lies on the plateau of the design spectrum 

Ww     = 2671 kN 

Ch(Tw)     = 2.36 

C(Tw)     = 2.36 x 0.13 x 1 x 1 =0.3068 

kμ    = 1.2 

Cd(Tw)     = 0.3068 x 0.7 / 1.2 = 0.17897 

C1    = 1 

C3    = 1.2 

Vw    = 1 x 1.2 x 0.17897 x 2671 = 573.62 kN 

Storey Shear Load 

 
2

94.8 2 4.205 2
  573.6  = 131.28 kN 
2 19.7

89.3 2 3.855 2
  573.6  = 120.78 kN 
2 19.7

52.2 2 3.645 2
  573.6  = 109.28 kN 
2 19.7

49.2 2 3.795 2
  573.6  = 113.20 kN 
2 19.7

29.5 2 2.00 2
  573.6  = 60.06 kN 
2 19.7

Total Base Shear Load 

Β = 3.16/3.06 = 1.026 < 1.35 therefore use CQC method 

Note: The CQC method requires an approximation of the in‐plane loaded wall period. 

   

  C4‐19
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

Calculate table of 
 

n  T1  T2  T3  T4  T5  T In‐plane 


i  2.423  2.271 3.088 2.832 3.160  0.190 
T1  2.423 1.000  1.067 0.785 0.856 0.767  12.752 
T2  2.271 0.937  1.000 0.735 0.802 0.719  11.952 
T3  3.088 1.274  1.360 1.000 1.090 0.977  16.251 
T4  2.832 1.169  1.247 0.917 1.000 0.896  14.903 
T5  3.160 1.304  1.391 1.023 1.116 1.000  16.630 
T In‐plane  0.190 0.078  0.084 0.062 0.067 0.060  1.000 
 

Calculate table of   

Note: For this example   is taken as 0.05 for all modes. 
/
8
 
1 4 1 4

n  T1  T2  T3  T4  T5  T In‐plane 


i  2.423  2.423 3.088 2.832 3.160  0.190 
T1  2.423 1.000  0.667 0.176 0.331 0.153  0.000 
T2  2.271 0.743  1.000 0.121 0.203 0.108  0.000 
T3  3.088 0.117  0.073 1.000 0.531 0.968  0.000 
T4  2.832 0.255  0.140 0.613 1.000 0.496  0.000 
T5  3.160 0.098  0.062 0.931 0.414 1.000  0.000 
T In‐plane  0.190 0.004  0.004 0.003 0.004 0.003  1.000 
 

Calculate table of   x Vi x Vn 
/

For example: 

 for i = 3 and n = 2,  = 0.073 

Vd3/2 = 26.04 kN and Vd2/2 = 44.6 kN, so  0.073*26.04*44.6 = 84.49 

   

C4‐20   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Vd1/2  Vd2/2  Vd3/2  Vd4/2  Vd5/2  Vw 


47.362  44.595 26.038 24.582 14.705 573.624  Sum 
Vd1/2  47.362  2243.196  1408.437 216.931 384.962 106.464 1.560  4361.55
Vd2/2  44.595  1569.067  1988.738 140.993 222.419 70.939 1.720  3993.88
Vd3/2  26.038  144.822  84.490 677.976 339.834 370.594 0.477  1618.19
Vd4/2  24.582  296.908  153.983 392.609 604.266 179.450 0.555  1627.77
Vd5/2  14.705  68.396  40.908 356.629 149.475 216.230 0.255  831.89
Vw  573.624  108.586  107.451 49.766 50.105 27.631 329044  329387.99
Sum  4430.975  3784.007 1834.904 1751.061 971.308 329049 
341821
341821 
584.65
Each column and each row is summed, which represents the first sum in the Vb formula. Then 
the sum of the column sums (or row sums) is found (in this example equals 341821 kN), which 
represents the second summation in the Vb formula.  The square of this second sum is 584.6 kN.  

Total base shear load using CQC method = 584.6 kN 

For comparison, using the SRSS method 
/

Total base shear load = (Σ47.362 + 44.602 + 26.042 + 24.582 + 14.712 + 573.62)1/2 = 587.6 Kn 

Storey Shear Force 
584.65 584.65
1.094  
∑ 131.28 120.78 109.28 113.2 60.06
Therefore,  

Shear force level 5 = 1.094*60.06 =65.7 

Shear force level 4 = (1.094*60.06) + (1.094*113.20) = 189.5 

Shear force level 3 = (1.094*60.06 + (1.094*113.20) + (1.094*109.28) = 309.0 

Shear force level 2 = (1.094*60.06 + (1.094*113.20) + (1.094*109.28) + (1.094*120.78) = 441.1 

Shear  force  level  1  =  (1.094*60.06  +  (1.094*113.20)  +  (1.094*109.28)  +  (1.094*120.78)  + 


(1.094*131.28) = 584.6 

   

  C4‐21
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

Shear Force Diagram 

 
Now  repeating  the  exercise  assuming  the  diaphragms  to  be  stiffened  as  reported  in  Oliver 
(2010), we obtain, 

Diaphragm Stiffness, Kd:  

14730 /  

Table C4‐4 – Diaphragm Periods 

  Level 1  Level 2  Level 3  Level 4  Level 5 

∆    =3785/14730  =3324.9/14730 =2731.9/14730 =2297/14730  =1609.2/14730


(m)  =  0.257  = 0.2257  = 0.1854  = 0.1559  = 0.1092 

= 0.907  = 0.850   = 0.771   = 0.707  = 0.592 


1.79 ∆  

Diaphragm shear load transfer 

 
C1    = 1 

C3    = 1 

Z     = 0.13 

R     =  1 

N(T,D)     = 1 

Ch(Ti)     = spectral shape factor determined from Table 3.1 of NZS 1170.5 

C(Ti)     = Ch(Ti) × Z × R × N(T,D) 

C4‐22   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Cd(Ti)     = C(Ti) × Sp / Kμ

Sp     = 0.7 

μ = 2 

kμ    = 2 

Table C4‐5 – Diaphragm Shear Load Transfer 

  Level 1  Level 2  Level 3  Level 4  Level 5 

Ch(Ti)  1.282  1.349  1.451  1.540  1.762 

C(Ti)  0.167  0.175  0.189  0.200  0.229 

Cd(Ti)  0.0584  0.0614  0.0660  0.0701  0.0802 

Vdi (kN)  220.9  204.2  180.3  161.0  129.0 


 

In‐plane inertial shear load 

 
Vw = 1 x 1.2 x 0.17897 x 2671 = 573.62 kN (same as in above example) 

Storey Shear Load 

 
2

220.9 2 4.205 2
  573.6  = 164.9 kN 
2 19.7

204.2 2 3.855 2
  573.6  = 151.7 kN 
2 19.7

180.3 2 3.645 2
  573.6  = 139.3 kN 
2 19.7

161.0 2 3.795 2
  573.6  = 136.7 kN 
2 19.7

129.0 2 2.00 2
  573.6  = 86.9 kN 
2 19.7

Note  that  with  respect  to  the  loads  calculated  for  the  case  of  the  unretrofitted  diaphragms, 
stiffening  of  the  diaphragms  resulted  in  a  significant  increase  in  the  storey  shear  loads.   This 
increase ranged from 21% to 45%, emphasizing the need to re‐evaluate the loads actions for an 
proposed diaphragm improvements. 

Total Base Shear Load 

Β = 0.907/0.850 = 1.067 < 1.35 therefore use CQC method 

  C4‐23
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

Note: The CQC method requires an approximation of the in‐plane loaded wall period. 

Using the CQC method outlined above the total base shear load, Vb, is 651 kN. 

C4.5 References 
Addessi, D., Sacco, E., and Paolone, A. (2010). "Cosserat model for periodic masonry deduced by 
nonlinear homogenization." European Journal of Mechanics ‐ A/Solids, 29(4), 724‐737. 

Andersen, P., Brincker, R., and Kirkegaard, P. H. (1995) "On the uncertainty of identification of 
civil  engineering  structures  using  ARMA  models."  Proc.,  13th  International  Modal  Analysis 
Conference (XIII IMAC), Nashville, Tennesse. 

ASCE.  (2007).  Seismic  rehabilitation  of  existing  buildings,  ASCE/SEI  41‐06,  American  Society  of 
Civil Engineers, Reston, VA. 

Augenti,  N.,  and  Romano,  A.  "Seismic  design  of  masonry  buildings  through  macro‐elements." 
Proc., 14th International Brick and Block Masonry Conference (14IBMAC), Sydney, Australia, 
17 – 20 February. 

Bagchi,  A.  (2005).  "Updating  the  mathematical  model  of  a  structure  using  vibration  data." 
Journal of Vibration and Control, 11(12), 1469‐1486. 

Bayraktar,  A.,  Altunişik,  A.,  Sevim,  B.,  Türker,  T.,  Akköse,  M.,  and  Çoşkun,  N.  (2008).  "Modal 
analysis, experimental validation, and calibration of a historical masonry minaret." Journal 
of Testing and Evaluation, 36(6), 1‐9. 

Bendat, J., and Piersol, A. (1993). Engineering applications of correlations and spectral analysis, 
John Wiley & Sons, New York, USA. 

Berto,  L.,  Saetta,  A.,  Scotta,  R.,  and  Vitaliani,  R.  (2004).  "Shear  behaviour  of  masonry  panel: 
Parametric  FE  analyses."  International  Journal  of  Solids  and  Structures,  41(16‐17), 
4383‐4405. 

Brasile, S., Casciaro, R., and Formica, G. (2007a). "Multilevel approach for brick masonry walls ‐ 
Part  I:  A  numerical  strategy  for  the  nonlinear  analysis."  Computer  Methods  in  Applied 
Mechanics and Engineering, 196(49‐52), 4934‐4951. 

Brasile, S., Casciaro, R., and Formica, G. (2007b). "Multilevel approach for brick masonry walls ‐ 
Part  II:  On  the  use  of  equivalent  continua."  Computer  Methods  in  Applied  Mechanics  and 
Engineering, 196(49‐52), 4801‐4810. 

Brasile,  S.,  Casciaro,  R.,  and  Formica,  G.  (2010).  "Finite  Element  formulation  for  nonlinear 
analysis of masonry walls." Computers & Structures, 88(3‐4), 135‐143. 

Brincker,  R.,  Andersen,  P.,  and  Zhang,  L.  "Modal  identification  from  ambient  responses  using 
frequency  domain  decomposition."  Proc.,  18th  International  Modal  Analysis  Conference 
(XVIII IMAC), San Antonio, Texas, 625‐630. 

C4‐24   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Brincker,  R.,  Ventura,  C.  E.,  and  Andersen,  P.  "Damping  estimation  by  frequency  domain 
decomposition."  Proc.,  19th  International  Modal  Analysis  Conference  (XIX  IMAC), 
Kissimmee, Florida, 698‐703. 

Brownjohn, J. M. W. (2007). "Structural health monitoring of civil infrastructure." Philosophical 
Transactions  of  the  Royal  Society  A:  Mathematical,  Physical  and  Engineering  Sciences, 
365(1851), 589‐622. 

Carr,  A.  J.  (2004).  "Ruaumoko  –  A  program  for  inelastic  time‐history  analysis."  Department  of 
Civil Engineering, University of Canterbury, New Zealand. 

Castillo, A. E., and Boroschek, R. L. "Uso del método de frecuencia no paramétrica y SSI para la 
identificación  de  propiedades  modales  de  edificios."  Proc.,  IX  Jornadas  de  la  Asociacion 
Chilena de Sismologia e Ingenieria Antisismica, Universidad de Concepcion, Chile. 

Casolo,  S.,  and  Peña,  F.  (2007).  "Rigid  element  model  for  in‐plane  dynamics  of  masonry  walls 
considering  hysteretic  behaviour  and  damage."  Earthquake  Engineering  and  Structural 
Dynamics, 36(8), 1029‐1048. 

Casolo, S., and Milani, G. (2010). "A simplified homogenization‐discrete element model for the 
non‐linear  static  analysis  of  masonry  walls  out‐of‐plane  loaded."  Engineering  Structures, 
32(8), 2352‐2366. 

Chen, S. Y., Moon, F. L., and Yi, T. (2008). "A macroelement for the nonlinear analysis of in‐plane 
unreinforced masonry piers." Engineering Structures, 30(8), 2242‐2252. 

Chopra, A.K. (2007) Dynamics of Structures ‐ theory and applications to earthquake engineering. 
Pearson Prentice Hall, New Jersey, United States of America 

Comité  Européen  de  Normalisation  (CEN)  (2004).  Eurocode  8:  Design  of  structures  for 
earthquake  resistance  ‐  Part  1:  General  rules,  seismic  actions  and  rules  for 
buildings.  Eurocode, Brussels, Belgium. 

De  Sortis,  A.,  Antonacci,  E.,  and  Vestroni,  F.  (2005).  "Dynamic  identification  of  a  masonry 
building using forced vibration tests." Engineering Structures, 27(2), 155‐165. 

Dhakal, R., Singh,  S., and  Mander, J.  (2007). “Effectiveness of earthquake selection and scaling 


procedure  method  in  New  Zealand”.  Bulletin  of  the  New  Zealand  Society  for  Earthquake 
Engineering, 40(3), 160‐171. 

Dobson, B. J. (1987). "A straight‐line technique for extracting modal properties from frequency 
response data." Mechanical Systems and Signal Processing, 1(1), 29‐40. 

Doherty, K., Griffith, M. C., Lam, N., and Wilson, J. (2002). "Displacement‐based seismic analysis 
for  out‐of‐plane  bending  of  unreinforced  masonry  walls."  Earthquake  Engineering  & 
Structural Dynamics, 31(4), 833‐850. 

Ewins, D. J. (2000). Modal Testing: Theory, Practice and Application, Research Studies Press Ltd., 
Hertfordshire, England. 

Ewins,  D.  J.  (2001).  "Modal  analysis,  experimental.  Applications."  Encyclopedia  of  Vibration, 
Elsevier, Oxford, 829‐838. 

  C4‐25
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

FEMA  356  (2000)  'FEMA  356'  Prestandard  and  Commentary  for  the  Seismic  Rehabilitation  of 
Buildings. American Society of Civil Engineers and Federal Emergency Management Agency, 
Reston, VA. 

Formica, G., Sansalone, V., and Casciaro, R. (2002). "A mixed solution strategy for the nonlinear 
analysis of brick masonry walls." Computer Methods in Applied Mechanics and Engineering, 
191(51‐52), 5847‐5876. 

Gambarotta, L., and Lagomarsino, S. (1997a). "Damage models for the seismic response of brick 
masonry  shear  walls.  Part  I:  The  mortar  joint  model  and  its  applications."  Earthquake 
Engineering and Structural Dynamics, 26(4), 423‐439. 

Gambarotta, L., and Lagomarsino, S. (1997b). "Damage models for the seismic response of brick 
masonry  shear  walls.  Part  II:  The  continuum  model  and  its  applications."  Earthquake 
Engineering and Structural Dynamics, 26(4), 441‐462. 

Gambarotta, L., and Lagomarsino, S. (1993). "A microcrack damage model for brittle materials." 
International Journal of Solids and Structures, 30(2), 177‐198. 

Gentile, C., Saisi, A., and Gallino, N. (2009) "Operational modal analysis and F.E. modelling of a 
masonry  tower."  Proc.,  3rd  International  Operational  Modal  Analysis  Conference 
(IOMAC'09), Ancona, Italy, 499‐506. 

Giordano,  A.,  Mele,  E.,  and  De  Luca,  A.  (2002).  "Modelling  of  historical  masonry  structures: 
Comparison  of  different  approaches  through  a  case  study."  Engineering  Structures,  24(8), 
1057‐1069. 

He, J., and Fu, Z.‐F. (2001). Modal Analysis, Butterworth‐Heinemann. 

Heylen,  W.,  Lammens,  S.,  and  Sas.,  P.  (1997).  Modal  analysis  theory  and  testing,  Katholieke 
Universiteit Leuven, Belgium. 

Ibrahim,  S.  R.,  and  Mikulcik,  E.  C.  (1976).  "The  experimental  determination  of  vibration 
parameters from time responses." Shock and Vibration Bulletin, 46(5), 187‐196. 

Ibrahim,  S.  R.  (1977).  "Random  decrement  technique  for  modal  identification  of  structures." 
Journal of Spacecraft and Rockets, 14, 696‐700. 

Jaishi,  B.,  and  Ren,  W.‐X.  (2005).  "Structural  finite  element  model  updating  using  ambient 
vibration test results." Journal of Structural Engineering, 131(4), 617‐628. 

Jaishi, B., and Ren, W.‐X. (2007). "Finite element model updating based on eigenvalue and strain 
energy  residuals  using  multiobjective  optimisation  technique."  Mechanical  Systems  and 
Signal Processing, 21(5), 2295‐2317. 

Juang,  J.‐N.,  and  Pappa,  R.  S.  (1985).  "An  eigensystem  realisation  algorithm  (ERA)  for  modal 
parameter identification and modal reduction." Journal of Guidance, Control and Dynamics, 
8(5), 620‐627. 

Juang, J.‐N. (1994). Applied System Identification, Prentice Hall PTR, NJ, USA. 

C4‐26   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Kelly, T. E. (2004). "2003 State‐of‐the‐art report on seismic analysis." Bulletin of the New Zealand 
National Society for Earthquake Engineering, 37(1), 23‐34. 

Lagomarsino,  S.,  Penna,  A.,  and  Falasco,  A.  (2004).  "3Muri  –  Advanced  seismic  analysis  of 
masonry buildings." S.T.A.Data, Italy. 

Link,  M.  (2001).  "Modal  updating  and  validating."  Encyclopedia  of  Vibration,  Elsevier,  Oxford, 
844‐856. 

Livesley,  R.  K.  (1978).  "Limit  analysis  of  structures  formed  from  rigid  blocks."  International 
Journal for Numerical Methods in Engineering, 12(12), 1853‐1871. 

Lourenço, P. B. "Structural masonry analysis: Recent developments and prospects." Proc., 14th 
International  Brick  and  Block  Masonry  Conference  (14IBMAC),  Sydney,  Australia,  17  –  20 
February. 

Lourenço,  P.  B.,  and  Rots,  J.  G.  (1997).  "Multisurface  interface  model  for  analysis  of  masonry 
structures." Journal of Engineering Mechanics, 123(7), 660. 

Lourenço, P. B. (2004) "Current experimental and numerical issues in masonry research." Proc., 
International Workshop on Masonry Walls and Earthquakes, 119‐136. 

Magenes,  G.  and  G.M.  Calvi  (1997)  “In‐Plane  seismic  response  of  brick  masonry  walls”, 
Earthquake Engineering and Structural Dynamics, 26(11), 1091‐1112. 

Magenes, G., Manzini, C., Morandi, P., Calliari, R., and Righetti, G. (2003). ANDILWall – Software 
of structural design and verification of masonry buildings. CRSoft, Italy. 

Maia, N. M. M. (1999). "Modal identification methods in frequency domain." Modal Analysis and 
Testing, J. M. M. Silva, and N. M. M. Maia, eds., Kluwer Academics Publishers, Netherlands, 
251‐264. 

Milani, G., Lourenço, P. B., and Tralli, A. (2006). "Homogenised limit analysis of masonry walls, 
Part I: Failure surfaces." Computers and Structures, 84(3‐4), 166‐180. 

Núñez, T., and Boroschek, R. L. "Monitoreo continuo de una estructura en proceso constructivo." 
Proc., X Jornadas de la Asociacion Chilena de Sismologia e Ingenieria Antisismica, Facultad 
de Ciencia Fisicas y Matematicas, Universidad de Chile. 

NZSEE  (2006).  Assessment  and  improvement  of  the  structural  performance  of  buildings  in 
earthquakes: Recommendations of a NZSEE study group on earthquake risk buildings, New 
Zealand Society for Earthquake Engineering. 

Oliver, S. J. (2010) “A design methodology for the assessment and retrofit of flexible diaphragms 
in unreinforced masonry buildings”, SESOC Journal, 23(1), 19‐49.  

Orduña, A., Roeder, G. and Peña, F. (2007). "Evaluación sísmica de construcciones históricas de 
mampostería:  comparación  de  tres  modelos  de  análisis."  Revista  de  Ingeniería  Sísmica  (In 
Spanish), 77, 71‐88. 

  C4‐27
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

Oyarzo  Vera,  C.  and  Chouw,  N.  (2008).  “Comparison  of  record  scaling  methods  proposed  by 
standards  currently  applied  in  different  countries”.  Proceedings  of  the  14th  World 
Conference on Earthquake Engineering, Beijing, China , 12 ‐ 17 October. 

Oyarzo  Vera,  C.,  McVerry,  G.  and  Ingham,  J.  (2011).  “Seismic  zonation  and  default  suite  of 
ground‐motion  records  for  time‐history  analysis  in  the  North  Island  of  New  Zealand”. 
Earthquake Spectra, Under Review. 

Pallares, F. J., Ivorra, S., and Adam, J. M. (2009) "Monitoring masonry chimneys with operational 
modal  analysis."  Proc.,  3rd  International  Operational  Modal  Analysis  Conference 
(IOMAC'09), Ancona, Italy, 401‐407. 

Pasticier,  L.,  Amadio,  C.  and  Fragiacomo,  M.  (2007).  "Non‐linear  seismic  analysis  and 
vulnerability  evaluation  of  a  masonry  building  by  means  of  the  SAP2000  V.10  code." 
Earthquake Engineering & Structural Dynamics, 37(3), 467‐485. 

Pavic, A., Miskovic, Z., and Reynolds, P. (2007). "Modal testing of finite‐element model updating 
of  a  lively  open‐plan  composite  building  floor."  Journal  of  Structural  Engineering,  133(4), 
550‐558. 

Ramos, L. F., Marques, L., Lourenço, P. B., De Roeck, G., Campos‐Costa, A. and Roque, J. (2010). 
"Monitoring  historical  masonry  structures  with  operational  modal  analysis:  Two  case 
studies." Mechanical Systems and Signal Processing, 24(5), 1291‐1305. 

Rosenblueth, E. (1951) A Basis for a Seismic Design. University of Illinois, Urbana, Illinois 
Russell,  A.P.  (2010)  “Characterisation  and  Seismic  Assessment  of  Unreinforced  Masonry 
Buildings.” Department of Civil Engineering, University of Auckland, Auckland. 

Russell,  A.  P.  and  Ingham,  J.  M.  (2010).  "Prevalence  of  New  Zealand's  unreinforced  masonry 
buildings." Bulletin of the New Zealand Society for Earthquake Engineering, 43(3), 192‐207. 

Sacco,  E.  (2009).  "A  nonlinear  homogenization  procedure  for  periodic  masonry."  European 
Journal of Mechanics ‐ A/Solids, 28(2), 209‐222. 

Silva,  J.  M.  M.,  and  Maia,  N.  M.  M.  (1999).  Modal  Analysis  and  Testing,  Kluwer  Academics 
Publishers, Netherlands. 

Skolnik,  D.,  Lei,  Y.,  Yu,  E.  J.,  and  Wallace,  J.  W.  (2006).  "Identification,  model  updating,  and 
response prediction of an instrumented 15‐story steel‐frame building." Earthquake Spectra, 
22(3), 781‐802. 

Smith,  W.  R.  (1981)  "Least  squares  time‐domain  methods  for  simultaneous  identification  of 
vibration  parameters  from  multiple  free‐response  records."  Proc.,  A1AA/ASME/ASCE/AHS 
22nd SDM Conference, April, 194‐201. 

Standards  New  Zealand  (SNZ)  (2004a).  NZS  1170.5:2004  ‐  Structural  Design  Actions  Part  5: 
Earthquake actions. Standards New Zealand, Wellington, New Zealand. 

Standards New Zealand (SNZ) (2004b). NZS 1170.5:2004 ‐ Structural Design Actions. Earthquake 
actions ‐ Commentary. Standards New Zealand, Wellington, New Zealand.  

C4‐28   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Standards  New  Zealand  (SNZ)  (2006).  NZS  3101:2006,  Concrete  Structures  Standard  Part1:  The 
Design of Concrete Structures. Standards New Zealand, Wellington, New Zealand. 

van  Overschee,  P.,  and  de  Moor,  B.  (1996).  Subspace  identification  for  linear  systems:  theory, 
implementation, applications  Kluwer Academic Publishers, Boston. 

Yu, S., Wu, C., and Griffith, M. C. "Numerical analysis of out‐of‐plane loaded masonry wall using 
homogenization technique." Proc., 14th International Brick and Block Masonry Conference 
(14IBMAC), Sydney, Australia, 17 – 20 February. 

 
 
 
 

  C4‐29
 
  Section C4 ‐ Design Actions on In‐plane Loaded Unreinforced Masonry 
 
 

C4‐30   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C5 ‐ Determination of Diaphragm Design Actions 

C5.2 Scope 
The  recommended  parabolic  load  distribution  and  corresponding  design  actions  are  logically 
based on the assumption that the diaphragm has uniform width (b), and therefore strictly only 
apply  to  rectangular  geometries.  The  capacity  assessment  of  diaphragms  with  more  complex 
geometries will require a rational method to account for varying diaphragm width. 

C5.3 Load Distribution 
The  parabolic  load  distribution  is  recommended  by  NZSEE  (2006)  and  ASCE  41‐06  (2007) 
guidelines  when  assessing  the  capacity  of  flexible  diaphragms.  It  is  intended  to  emulate  the 
expected distribution of horizontal inertia forces developed in the diaphragm. 

C5.4 Design Actions 
Diaphragm  shear  force  and  bending  moment  distributions  have  been  developed  by  simple 
integration  of  the  load  distribution  function.  These  equations  are  simplified  further  when 
determining maximum design actions from the knowledge that maximum shear force occurs at 
the side of the diaphragm and maximum bending moment occurs at midspan.  

C5.5 Worked Example  
Establish the design actions for the diaphragm shown below. 

  10.4 m 

 5.535 m 

Step 1:  Previously Determined Values 

Vd (NS)    = 33 kN (using provisions of Section 4) 
Vd (EW)    = 35 kN (using provisions of Section 4) 
L (NS)    = 10.4 m 
L (EW)    = 5.535 m 
 

  C5‐1
 
  Section C5 ‐ Determination of Diaphragm Design Actions
 
 

Step 2:  Diaphragm Load Distribution 

North South Direction 

1.5 2
1  

1.5 ∗ 33 2
1  
10.4 10.4

4.76 1 0.037  

East West Direction 

Similarly it can be shown that: 

9.49 1 0.131  

Step 3:  Diaphragm Design actions 

North South Direction 

Shear force distribution: 

3 2
 
2

33 3 2
 
10.4 2 10.4

4.76 0.059  

Maximum shear force: 

33
,  
2 2

VE,max (NS)  = 16.5 kN 

Bending moment distribution: 

3 5
 
4 2 32

3 ∗ 33 33 5 ∗ 33 ∗ 10.4
 
4 ∗ 10.4 2 ∗ 10.4 32

2.38 0.015 53.62 

Maximum bending moment: 

C5‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

5 5 ∗ 33 ∗ 10.4
 
32 32

ME,max (NS)  = 53.6 kNm 

East West Direction 

Similarly it can be shown that: 

VE (EW)    = 9.49x – 0.413x2 

VE,max (EW)  = 17.5 kN 

ME (EW)    = 4.74x2 – 0.103x4 – 30.26 

ME,max (EW)  = 30.3 kNm 

C5.6 References 
ASCE.  (2007).  Seismic  rehabilitation  of  existing  buildings,  ASCE/SEI  41‐06,  American  Society  of 
Civil Engineers, Reston, VA. 
NZSEE  (2006).  Assessment  and  improvement  of  the  structural  performance  of  buildings  in 
earthquakes: Recommendations of a NZSEE study group on earthquake risk buildings, New 
Zealand Society for Earthquake Engineering. 

  C5‐3
 
  Section C5 ‐ Determination of Diaphragm Design Actions
 
 

C5‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C6 ‐ Design Actions on URM Walls and Parapets 
loaded out‐of‐plane 

C6.1 Notations 
bw  Wall thickness, m 
C(0)  Site hazard coefficient for Tp = 0 sec, fraction of g 
CHi  Floor acceleration coefficient for level i 
Ci(Tp)  Part spectral shape factor at level i  
Cp(Tp)  Horizontal acceleration coefficient, fraction of g 
g  Acceleration due to gravity, m/s2 
he  Wall height measured between diaphragm restraints, m 
hi  Height of the wall mid‐height hinge measured from ground, m 
hn  Total height of the structure measured from ground, m 
N(0,D)  Near‐fault factor 
Nt  Axial load due to upper storeys, kN 
R  Return period factor 
Rp Part risk factor 
Tp  Natural period of the wall, s 
Vo*  Design out‐of‐plane lateral force, kN 
vo*  Design out‐of‐plane lateral pressure, kN/m2 
Ww  Self weight of the wall, kN 
Z  Seismic hazard factor 
γ Modal participation factor 

C6.2 Scope 
A  linear  static  analysis  procedure,  the  Equivalent  Static  Method,  is  presented  for  assessing 
strength  demands  that  an  unreinforced  masonry  (URM)  wall  loaded  out‐of‐plane  will  be 
subjected  to  in  a  design  level  earthquake.  Although  URM  response  is  highly  inelastic  and 
nonlinear, the outlined detailed linear  static method will provide a reasonable estimate of the 
seismic demands on a URM wall when loaded out‐of‐plane. The procedure is adapted from the 
NZS 1170.5:2004  (SNZ  2004)  loading  standard  and  the  NZSEE  (2006)  guidelines  for  the 
assessment of URM walls loaded out‐of‐plane. The calculated design out‐of‐plane force shall be 
uniformly distributed over the wall height for the calculation of out‐of‐plane flexural demand.  

The procedure is based on the assumption that a single horizontal crack will form at mid‐height, 
which may not be true in some cases when masonry materials have a high flexural strength or 
when  any  retrofit  is  applied  such  that  it  may  redistribute  the  cracks  on  the  tension  face. 
Therefore, the procedure shall be used with care for retrofitted URM walls and for URM walls 
constructed with stronger mortars. 

  C6‐1
 
  Section C6 ‐ Design Actions on URM Walls loaded Out‐of‐plane  
 
 

C6.2.1 Procedure  to  Calculate  Design  Actions  on  Unreinforced  Masonry  walls 
loaded out‐of‐plane 
Figure  C6‐1  shows  a  flow  chart  for  the  determination  of  seismic  design  forces  for  walls  of 
unreinforced masonry (URM) buildings, loaded out‐of‐plane, and having flexible diaphragms. 

Initial assessment  Detailed 
based on percentage  assessment not 
NBS calculations  required 

Calculate self weight of 
the wall and axial load 
due to upper storeys 

Establish factors Z, R, N(0, D) and  Establish hi, hn and he  


Ch(0) for site location and subsoil 
Calculate period of the 
characteristics in accordance 
wall using Equation 13‐
with NZS 1170.5:2004 
8 and find part spectral 
shape factor, Ci(Tp)  Calculate floor 
acceleration 
Calculate C(0) using  coefficient, CHi, using 
Equation 13‐3  Equations 13‐4 to 13‐6 

Calculate horizontal 
acceleration coefficient , 
Cp(Tp), using Equation 13‐2 

Calculate modal 
participation factor in 
accordance with 
Section 13.3.2

Establish part risk factor, 
Rp in accordance with 
NZS 1170.5:2004 

Calculate design lateral 
force, Vo*, using 
Equation 13‐1 

Calculate design uniform pressure, vo*, 
by equally distributing the total design 
lateral force over the tributary area of 
the wall i.e., vo*= Vo*/bwhe 
 
Figure C6‐1: Flowchart for Out‐of‐plane Seismic Design of URM buildings with Flexible 
Diaphragms. 

C6‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C6.3 Design Lateral Force on Walls loaded out‐of‐plane 

C6.3.1.1 Floor Acceleration Coefficient 

Based  on  the  experimental  work  performed  it  was  established  that  a  single  horizontal  crack 
forms at or near the mid‐height of walls loaded out of plane (Derakhshan et al. 2011). Therefore, 
the  wall  is  assumed  to  form  hinges  at  three  locations,  being  at  the  top  and  bottom  locations 
where effective horizontal restraint is applied and at mid‐height between these top and bottom 
hinges. Figure C6‐2 illustrates the definition of heights used in Section 6.3.1. 

h
n

h
i

 
Figure C6‐2: Definition of heights 

C6.3.1.3 Part Spectral Shape Factor 

Equations  for  the  natural  period  of  a  URM  wall  (Equation  6‐8)  and  parapet  (Equation  6‐9), 
loaded  out‐of‐plane,  have  been  extracted  from  the  NZSEE  (2006)  guidelines  for  assessment  of 
out‐of‐plane loaded URM walls. 

C6.4 Design Example 
Calculate  the  design  out‐of‐plane  lateral  seismic  force  for  two  leaf  thick  URM  walls  located  at 
level 2 and for the parapet. The building is founded on soil type D and is located in Christchurch. 
Elevations are shown in Figure C6‐3.  

   

  C6‐3
 
  Section C6 ‐ Design Actions on URM Walls loaded Out‐of‐plane  
 
 

2
5
0
0
3
2
0
0 9
5
0
0
4
1
0
0
 
Figure C6‐3: Building cross‐section 

C6.4.1 Design Lateral Force on Walls loaded out‐of‐plane 
Considering a strip of 1 m width, the self weight of the wall is calculated as 

Ww = Density   Volume of Masonry 

Ww = 1800   9.81   0.22   3.2   1.0 = 12.4 kN 

and the overburden weight is 

Nt = 1.9 kN 

he = 3.2 m 

Site Hazard Coefficient (for Tp = 0 sec) 

0 C 0 ZRN 0, D
Ch(0) = 1.12 for subsoil type D

Z = 0.30 for Christchurch from NZS 1170.5:2004 

R = 1.0   for 1/500 APE 

N(0, D) = 1.0  for D>20 km 

C(0) = 0.336 

Floor Acceleration Coefficient 

1  
6
  for hi < 12 m 

C6‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

hi= 5.7 m 

CHi = 1.95  

Part Spectral Shape Factor  

2 1.75   where 0.5 < Ci(Tp) < 2.0 

The first wall period is calculated as 

0.67
 
1 2

0.67 3.2
 
1.9
1 2
12.4

Tp = 1.28 sec 

2 1.75 1.28  

Ci(Tp) = 0.94  

Horizontal Acceleration Coefficient 

C 0 C C T  

Cp(Tp) = 0.336   1.95   0.94 = 0.616 

Modal Participation Factor 

γ 1.5 

Part Risk Factor 

1.0  for  part  representing  hazard  to  outside  life,  from 


NZS 1170.5:2004 

Design Lateral Force on Out‐of‐plane loaded Walls 

γ  

Vo* = 0.616   1.5   1.0   12.4 = 11.46 kN per metre width of the wall 

Or uniform lateral pressure, vo* = Vo*/he = 3.58 kN/m2 

C6.4.2 Design Lateral Force on Parapet 
Ww = 9.69 kN 

Nt = 0 kN 

  C6‐5
 
  Section C6 ‐ Design Actions on URM Walls loaded Out‐of‐plane  
 
 

Site Hazard Coefficient (for Tp = 0 sec) 

C(0) = 0.336  Same as calculated for wall loaded out‐of‐plane 

Floor Acceleration Coefficient 

1   for hi < 12 m 

hi = 7.3 m 

CHi = 2.22 

 Part Spectral Shape Factor  

2 1.75   where 0.5 < Ci(Tp) < 2.0 

The parapet period is calculated as 

2.67 1  

0.22
T 2.67 2.5 1  
2.50

Tp = 2.59 sec 

Ci(Tp) = 0.5 

 Horizontal Acceleration Coefficient 

0  

Cp(Tp) = 0.336   2.22   0.50 = 0.37 

Modal Participation Factor 
1.5
1.38 
1

Part Risk Factor 

1.0  for  part  representing  hazard  to  outside  life,  from 


NZS 1170.5:2004 

Design Lateral Force on Parapet 

γ  

Vo* = 0.37 × 1.38 × 1.0 × 9.69 = 4.95 kN per metre width of the parapet 

Or uniform lateral pressure, vo* = Vo*/he = 1.98 kN/m2 

   

C6‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C6.5 References 
Derakhshan,  H.,  Griffith,  M.  C.,  Ingham,  J.  M.  (2011).  “Out‐of‐plane  behaviour  of  one‐way 
spanning  unreinforced  masonry  walls”  ASCE  Journal  of  Engineering  Mechanics,  submitted 
June 2010, revised November 2010. 

NZSEE  (2006).  Assessment  and  improvement  of  the  structural  performance  of  buildings  in 
earthquakes: Recommendations of a NZSEE study group on earthquake risk buildings, New 
Zealand Society for Earthquake Engineering. 

Standards  New  Zealand  (SNZ)  (2004).  NZS  1170.5:2004  ‐  Structural  Design  Actions  Part  5: 
Earthquake actions. Standards New Zealand, Wellington, New Zealand. 

  C6‐7
 
  Section C6 ‐ Design Actions on URM Walls loaded Out‐of‐plane  
 
 

C6‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C7 ‐ Design Actions on Wall Diaphragm 
Anchorages 

C7.1 Notation 
b  Diaphragm width, m 
Ci(0.4)  Part spectral shape factor at level i 
Cp(0.4)  Horizontal acceleration coefficient, fraction of g 
g  Acceleration due to gravity, m/sec2 
hi  Height of the connection location, m 
hn  Total height of the structure, m 
Rp Part risk factor 
Vdi  Diaphragm shear load transfer for level i, kN 
Vcsi  Design shear force for In‐plane loaded connections, kN/m 
Vcti  Design tension force for out‐of‐plane loaded connections, kN/m 
Wwt1  Self weight of the top half of the out‐of‐plane wall below the connection, kN 
Wwb2  Self weight of the bottom half of the out‐of‐plane wall above the connection, kN 

C7.2 Scope 
This  section  details  recommendations  for  the  determination  of  design  seismic  forces  for  the 
connections  between  diaphragms  and  out‐of‐plane  loaded  or  in‐plane  loaded  walls.  The 
following  recommendations  for  calculating  connection  design  actions  are  based  on  the 
procedures defined in Section 4 and Section 6 which apply to URM bearing wall buildings with 
the following characteristics: 

(a) Flexible diaphragms at all diaphragm levels above the base of the structure; 

(b) A maximum of six stories above the base of the structure; 

(c) A  minimum  of  two  lines  of  vertical  elements  of  the  lateral  load  resisting  system  in  each 
principal direction, except for single storey buildings with an open front on one side. 

C7.3 Design Shear for In‐plane Loaded Connections 
The design shear load for the connections between the diaphragm and the in‐plane wall comes 
directly from the diaphragm shear load transfer calculated in Section 4. 

C7.4 Design Tension for Out‐of‐plane Loaded Connections 
The process presented here is consistent with the Parts and Portions procedure of NZS 1170.5, 
as no specific research has been performed to more accurately define the magnitude of these 
actions.  Oliver  (2010)  has  questioned  the  validity  of  using  the  Parts  and  Portions  process  of 
NZS 1170.5  for  the  assessment  of  design  loads  on  connections  and  suggests  that  the  values 

  C7‐1
 
  Section C7 ‐ Design Actions on Wall Diaphragm Anchorages
 

obtained  from  this  process  are  too  conservative.  More  conclusive  testing  and  modelling  is 
planned but for the interim the process outlined in section 7 is endorsed. 

C7.5 Design Example 
This  design  example  calculates  the  tension  forces  in  the  connections  between  the  diaphragm 
and  the  out‐of‐plane  loaded  walls,  and  the  shear  forces  in  the  connections  between  the 
diaphragm  and  the  in‐plane  loaded  walls.  The  building  is  a  typical  two  storey  isolated  URM 
building  founded  on  soil  type  D  and  is  located  in  Christchurch.    The  in‐plane  length  of  the 
building is 8 m. The elevation is shown in Figure C7‐1. The masonry density was established to be 
ρm = 1800 kg/m3. 

2
5
0
0
2
3
0

3
2
0
0 9
5
0
0
3
5
0

4
1
0
0

Figure C7‐1: Building cross‐section 

Considering a strip of 1 m width , the self‐weight of the wall is calculated as 

9.81 4.1
1800 0.35 1 12.7 kN  Weight of top half of first storey 
1000 2

9.81 3.2
1800 0.23 1 6.5 kN  Weight of bottom half of second storey 
1000 2

9.81 3.2
1800 0.23 1 6.5 kN  Weight of top half of second storey 
1000 2

C7‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

9.81
1800 0.23 2.5 1 10.15 kN  Weight of parapet 
1000

Calculate Design Shear for In‐plane Loaded Connections 

Assuming that it was previously established that the diaphragm shear load transfer is: 

Vd1 (Diaphragm level one) = 156 kN 

Vdr = (Diaphragm roof level) = 112 kN 

and assuming equal distribution of shear load between the two in‐plane loaded walls, 
156
2 9.75 kN/m 
8
112
2 7 kN/m 
8

Calculate Design Tension for Out‐of‐plane Loaded Connections 

Determine site hazard coefficient 

0 0 0,  
Ch(0) = 1.12    For subsoil type D 

Z = 0.22     for Christchurch from NZS 1170.5 

R = 1.0      for 1/500 probability 

N(0,D) = 1.0    for probability > 1/250 

C(0) = 0.246   

Determine Floor Acceleration Coefficient 

1   for all hi < 12 m                                              (6‐4) 
6

.
Ch1 =  1 1.683 
.
Chr =  1 2.217 

Determine Part Spectral Shape Factor  

0.4 2 

Determine Horizontal Acceleration Coefficient 

0.4 0 0.4  

0.4 0.246 ∗ 1.683 ∗ 2 0.828 

0.4 0.246 ∗ 2.217 ∗ 2 1.091 

  C7‐3
 
  Section C7 ‐ Design Actions on Wall Diaphragm Anchorages
 

Determine the Design Tension Force 

0.4  

0.828 ∗ 0.85 ∗ 1.0 ∗ 12.7 6.5 13.51 kN/m  


1.091 ∗ 0.85 ∗ 1.0 ∗ 6.5 10.15 15.44 kN/m  

C7.6 References 
Oliver, S. J. (2010) “A design methodology for the assessment and retrofit of flexible diaphragms 
in unreinforced masonry buildings”, SESOC Journal, 23(1), 19‐49. 

C7‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C8 ‐ Response of walls loaded in‐plane  

C8.1 Notation 
Af   Cross‐sectional area of flange, m2 
Aw  Cross‐sectional area of wall, m2 
af  Distance to centre of flange from compression edge of wall, m 
ai  Distance to centre of inertia of wall from compression edge of wall, m 
bf   Width of flange, m 
bw  Width of wall, m 
c  Bed‐joint cohesion, kPa 
fdt  Diagonal tension strength of masonry, kPa 
f’m  Compression strength of masonry, kPa 
h  Height of wall, taken as between diaphragms or similar restraint, m 
ler  Effective length of wall in rocking failure mode, m 
letc  Effective length of wall in toe crushing failure mode, m 
lf   Effective length of flange, to be the minimum of 6 × bf or actual length of flange, m 
lw Length of wall, m
Nb Normal force acting on cross‐section of wall base, kN
Nt Normal force acting on cross‐section of top of the wall, kN 
V  Seismic Induced In‐plane shear force applied to top of wall, kN 
Vdt  Nominal shear capacity in diagonal tension failure mode, kN 
Vr  Nominal shear capacity in rocking failure mode, kN 
Vs  Nominal shear capacity in bed‐joint sliding failure mode, kN 
Vtc  Nominal shear capacity in toe crushing failure mode, kN 
Wf   Weight of masonry flange, kN 
Ww   Weight of masonry wall, kN 
Z               Distance from the compression edge of the wall to the line of action of   

γm  Unit weight of masonry, kN/m
µf Coefficient of friction of masonry 
ρm  Masonry density, kg/m3 
σave Average compressive stress, kPa 
Ψ              Effective height factor 

C8.2 Scope 
Equations 8‐8 to 8‐12 have been reworked from research undertaken by Yi et al. (2008), being 
an extension of earlier research into the verification of an effective pier model (Yi et al. 2005), 
with the inclusion of flange effects. The effective pier model assumes a linear stress distribution 
across the base of the wall that is a product of the axial load and the moment at the base of the 
wall. The moment is caused by lateral seismic loading induced by diaphragm motions and wall 
inertia  grouped  at  the  location  of  the  diaphragm  (top  of  the  wall)  in  accordance  with  the 

  C8‐1
 
  Section C8 ‐   of walls loaded in‐plane 
 
 

procedures of Section 4. The model is used to find an effective length, le, of the wall, where any 
masonry failing in tension is outside of the effective length (the flexural cracked area in Error! 
Reference source not found.). The effective length of a wall when subjected to seismic loading is 
the basis for the capacity equations for each of the four failure modes. The effective pier model 
is  shown  in  Error!  Reference  source  not  found.,  where  the  effective  length  of  the  wall  at  the 
base is denoted le,  the tensile strength  of masonry is denoted ft,  the lateral force is V and  the 
axial force is not shown. σave is the average axial stress at the point of inflection of the wall and 
σnmax is the maximum compression stress, occurring at the compression toe of the wall. 

 
Figure C8‐1: Effective pier model (Yi et al. 2008) 

Equations for the capacity of walls loaded in‐plane are compared in Yi et al. (2005), with those in 
FEMA  356  (2000),  the  prestandard  of  ASCE/SEI  41‐06  (2007),  with  very  close  correlation  in 
principles and values generated. Yi et al. (2008) conducted research into the effect of flanges on 
in‐plane  wall  response,  recognising  that  flanges  have  the  potential  to  affect  both  the  failure 
mode induced by seismic loading and the strength of a URM wall (Tomazevic et al. 1993, Costley 
and  Abrams  1996,  Paquette  and  Bruneau  2003,  Yi  et  al.  2006,  Moon  et  al.  2007).  This 
consideration  of  flange  effects  on  in‐plane  loaded  wall,  pier  and  spandrel  capacities  is  why 
equations  in  Yi  et  al.  (2008)  are  endorsed  in  this  document,  being  representative  of  the  most 
comprehensive models of URM wall behaviour. 

Equations 8‐8 to 8‐12 are based on the assumption of a cantilevered URM wall, pier or spandrel, 
but Yi et al. (2008) suggest that the results obtained from this assumption can be extended to 
other, less conservative, boundary conditions by utilising appropriate aspect ratios. 

   

C8‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C8.3 Properties of walls loaded in‐plane 

C8.3.5 Diagonal Tensile Strength 
Equation  8‐5  is  sourced  from  the  procedure  presented  in  FEMA  356  (2000)  for  determining 
masonry diagonal tension strength. The FEMA 356 equation includes a 0.75 reduction factor of 
the average bed‐joint shear strength, νte. In Equation 8‐5 cohesion, c, is taken as equivalent to 
νte. The reduction factor is included in the FEMA 356 equation  as in‐situ shear resistance tests 
used  to  determine  νte  include  shear  resistance  provided  by  the  collar  joint  between  leafs,  but 
seismic shear is not transferred across the collar joint in a multi‐leaf masonry wall. Thus the 0.75 
factor  is  not  required  in  this  guideline,  as  determining  c  does  not  take  collar  joint  shear 
resistance into account and consequently it is not necessary to reduce c. 

The factor of 0.75 that is included in equation 8‐5 is a reduction factor and the 1.5 is a factor to 
convert  peak  stress  to  an  equivalent  average  stress  for  use  with  walls  of  a  rectangular  cross 
section. These factors of 0.75 and 1.5 are consistent with the comparable equation in FEMA 356 
(2000). In a rectangular wall subjected to shear force the shear stress distribution is not linear, 
see Figure C8‐2 below. The shear stress at the ends of the wall is zero, and the maximum shear 
stress is at the centre of the wall. The maximum shear stress is 1.5 (3/2) times the average shear 
stress. Hence the 1.5 denominator in FEMA 273 Equation 7‐1 was to convert the maximum shear 
stress  capacity  at  the  centre  of  the  wall  to  an  average  value  applicable  over  the  length  of 
rectangular walls. For transparency, the strength reduction factor of 0.75 is shown at the front of 
the equation and the denominator of 1.5 is shown separately.  
 

Shear stress distribution


max =3V
2A
1.5 1.0
average =AV

Wall in plan

Shear force, V  
Figure C8‐2: Shear stress distribution in a rectangular wall 

   

  C8‐3
 
  Section C8 ‐   of walls loaded in‐plane 
 
 

C8.3.7 Average Compressive Stress 
In  determining  the  normal  force  acting  on  the  cross‐section  of  the  top  of  the  in‐plane  loaded 
wall, Nt, figure C8‐3 illustrates the tributary area of floor or roof diaphragm, and thus tributary 
seismic weight from diaphragms above that is attributed to the wall. The boundaries of tributary 
area extending from each corner of the floor plan can be assumed to be at 45° to the URM walls 
(Russell  2010).  The  appropriate  imposed  loads  shall  be  applied  in  accordance  with  NZS 1170 
(SNZ 2004) with all levels above the wall being considered, including self weight of the in‐plane 
loaded  wall,  when  determining  seismic  weight  acting  on  the  wall,  and  hence  normal  forces  Nt 
and Nb. 

(a) Long walls tributary area  (b) Short walls tributary area 

Figure C8‐3: Tributary areas for determining normal force on each wall (Russell 2010) 

C8.4 Nominal Shear Capacity of walls loaded in‐plane 
When subjected to in‐plane seismic loading, URM walls have been found to fail by one of four 
different  failure  modes  (Magenes  and  Calvi  1997)  represented  by  individual  equations  in 
Section 8.  Descriptions  of  wall  behaviour  when  loaded  in‐plane,  in  each  of  the  four  failure 
modes, are given as follows. 

C8.4.1 Capacity in Diagonal Tension Failure Mode 
Diagonal tension failure, illustrated in Figure C8‐4, is a force controlled failure mode and occurs 
when the maximum principal tensile stress in the pier exceeds the diagonal tensile strength of 
the  masonry.  Diagonal  tension  failure  leads  to  the  formation  of  inclined  diagonal  cracks  that 
commonly  follow  the  path  of  bed  and  head  joints  through  the  masonry,  or,  when  the  relative 

C8‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

strength  of  the  mortar  is  high,  can  cause  cracking  through  the  bricks  themselves.  Both  test 
results  (Russell  2010)  and  observed  performance  in  earthquakes  (Dizhur  et  al.  2010)  indicates 
that  in  New  Zealand,  stepped  diagonal  cracking  at  mortar  joints  can  be  expected  due  to  brick 
strength  typically  exceeding  mortar  strength  (see  also  Table  2‐2  and  Table  2‐4).  A  URM  wall 
failing in diagonal tension failure suffers a rapid degradation in strength after the formation of 
diagonal cracking and ultimate collapse occurs at small and unpredictable magnitudes of drift.  

 
Figure C8‐4: Diagonal Tension failure mode 

The diagonal tension  capacity equations suggested by Yi et al. (2008) have been amalgamated 
into Equation 8‐8a by way of introducing two flange location factors, α1 and α2. The 0.9 factor 
has been added to the equation consistent with recommendations by Russell et al. (2012) that 
suggests a high level of correlation between the modified equation and experimental results. 

Research completed by Russell et al. (2012) with regards to experimental testing of the in‐plane 
capacity  of  three  flanged  URM  walls  is  summarised  in  Table  C8‐1,  Table  C8‐2  and  Table  C8‐3. 
Table  C8‐2  provides  the  wall  dimensions  and  location  of  attached  flange/s  for  the  three  walls, 
the plan diagrams of which are illustrated in Table C8‐1. The ‘+’ and ‘‐’ are used to denote the 
two directions of loading, which is important due to the asymmetrical nature of wall A7. All of 
the  walls  failed  in  the  diagonal  tension  failure  mode.  Experimental  diagonal  tension  capacities 
(Vmax) are compared in Table C8‐3 to capacities predicted by Yi et al. (2008), the NZSEE (2006) 
guideline and ASCE/SEI 41‐06 (2007). The Yi et al. (2008) model has the closest correlation with 
experimental results.  

  C8‐5
 
  Section C8 ‐   of walls loaded in‐plane 
 
 

Table C8‐1: Wall Schematics 

Wall: A6  Wall: A7  Wall: A8 

     
 
 
 

Table C8‐2: Wall Specifications (Russell et al. 2012) 

bw  hw  lw  μ  fm/f’m  b f  lf 


Wall  Flanges at 
mm  mm  mm  MPa  %  mm  mm 

A6  230  2000  4000  0.7  0.441  both ends both sides 230  2160 

A7  230  2000  4000  0.7  0.468  one end  both sides 230  2160 

A8  230  2000  4000  0.7  0.576  both ends one side  230  1200 

Table C8‐3: Comparison of predicted strength accounting for and neglecting 
flanges (Russell et al. 2012) 

Yi et al. (2008)  NZSEE (2006)  ASCE/SEI (2007) 


  model  expressions  expressions 

Vmax  Vn  Vn  Vn 


Wall  Vmax/Vn  Vmax/Vn  Vmax/Vn 
kN  kN  kN  kN 

A6 (+)  69.3  67.9  1.02  53.0  1.31  46.0  1.51 

A6 (‐)  67.4  67.9  0.99  53.0  1.27  46.0  1.47 

A7c (+)  61.9  53.4  1.16  53.0  1.17  46.0  1.35 

A7t (‐)  75.0  67.5  1.11  53.0  1.42  46.0  1.63 

A8 (+)  66.9  67.5  0.99  53.0  1.26  46.0  1.45 

A8 (‐)  68.5  67.5  1.01  53.0  1.29  46.0  1.49 

Mean      1.05    1.29    1.48 

COV      6.7%    6.2%    6.2% 


 

When  assessing  the  capacity  of  a  wall  loaded  in‐plane,  in  the  diagonal  tension  failure  mode, 
flanges either in tension or compression shall be accounted for separately such that the nominal 
shear capacity for the diagonal tension failure mode is the average of the capacity of the wall in 

C8‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

diagonal  tension  calculated  excluding  all  flanges  and  the  capacities  of  the  wall  calculated  with 
each flange separately. In this instance all flange variables will be calculated accounting for each 
flange separately. Note: A flange located at the centre of a wall, pier or spandrel was found to 
have  no  effect  on  the  diagonal  tension  capacity  of  the  wall  being  considered  and  thus  can  be 
excluded  when  the  average  of  the  diagonal  tension  capacities  is  being  calculated  by  simply 
counting twice the capacity of the wall excluding flanges. A flange located at either side of the 
centre  of  a  wall  will  alter  the  diagonal  tension  capacity  of  the  wall  (Yi  et  al.  2008)  and  hence 
should be included  in  calculations. In this instance the direction  of loading does not affect the 
calculated wall capacity.  

C8.4.2 Capacity in Rocking and Toe Crushing Failure Modes 
The rocking failure mode represents overturning of a URM wall, pier or spandrel when subjected 
to in‐plane seismic loading and is characterised by large flexural cracks at the bottom and top of 
the wall, pier or spandrel. As the displacement increases, the wall, pier or spandrel rotates about 
the  compressive  toe.  When  force  reversal  occurs  the  flexural  cracks  close  and  then  flexural 
cracking  from  the  opposite  direction  occurs.  As  a  result,  rocking  is  generally  considered 
deformation (drift) controlled as large displacements can be withstood with little degradation of 
strength. 

Unlike  rocking,  the  toe  crushing  failure  mode  leads  to  loss  of  stiffness  and  strength  of  a  URM 
wall, pier or spandrel. Toe crushing is a compressive failure of masonry that occurs at the toe of 
the  wall,  pier  or  spandrel  and  initiates  when  the  maximum  compressive  stress  exceeds  the 
maximum  compressive  strength  of  the  masonry.  The  extent  of  the  toe  crushing  that  occurs  is 
dependent upon the ratio of applied axial stress to axial strength.  

Despite being considered separate failure modes, rocking and toe crushing are often intrinsically 
linked  such  that  they  represent  a  single  failure  mode.  In  this  instance  failure  is  defined  by 
overturning  of  the  wall  and  simultaneous  crushing  of  the  compressed  toe  of  the  wall  (Figure 
C8‐5). It is self evident that even for a scenario where rocking initiates, the magnitude of lateral 
displacements  necessary  to  cause  wall  overturning  are  of  a  magnitude  such  that  total 
overturning is unlikely. Rocking however causes a gradual degradation of the wall capacity that 
can  be  correlated  to  the  magnitude  of  deformation  (drift)  that  the  wall  is  subjected  to,  which 
gives rise to the drift limits discussed in Section C8.5. Note: It is sensible to assume that if a wall 
fails the rocking force check then it will also fail the rocking drift limit check.  

When calculating the capacity of a wall in the rocking failure mode, it is important to consider 
that  when  a  wall  possessing  a  non‐centrally  located  flange  it  will  have  a  weak  direction  of 
loading as ai will differ in the two in‐plane directions of the wall. 

In typical New Zealand URM construction it is expected that the masonry compressive strength 
will  not  be  low  enough  to  suffer  toe  crushing  under  average  axial  loads  except  for  minor  and 
inconsequential crushing of a limited length of the toe of the wall where the compressive force 
is concentrated (this is why the toe crushing capacity will always at least slightly understate the 
rocking capacity of a wall). It is important to recognise that attaining the drift required to initiate 
this  crushing  of  the  toe  of  the  wall  is  infeasible.  This  expectation  justifies  neglecting  the 

  C8‐7
 
  Section C8 ‐   of walls loaded in‐plane 
 
 

assessment  of  toe  crushing  capacity  except  in  the  instance  where  a  wall  has  been  retrofitted 
with un‐bonded post tensioning or a seismic improvement intervention such that either or both 
the axial stress on the wall and the wall capacity in the shear failure modes of bed‐joint sliding or 
diagonal  tension  is  increased.  When  calculating  the  toe  crushing  capacity  of  a  URM  wall  the 
flanges shall be accounted for individually as per calculation of diagonal tension capacity. 

 
Figure C8‐5: Rocking/toe crushing failure mode 

Equation 8‐9 is the same equation found in the NZSEE guidelines (2006), re‐arranged to give the 
nominal shear force at rocking failure, instead of the nominal moment at rocking failure. 

Equation  8‐11a  is  the  toe  crushing  failure  mode  capacity  given  by  Yi  et  al.  (2008),  with  no 
modifications and Equation 8‐11b is the same equation with all flange parameters equal to zero. 
The 1.3 factor appearing in Equation 8‐12 is a direct substitution of the factor β from both Yi et 
al.  (2005)  and  Yi  et  al.  (2008).  β  is  inserted  to  take  account  of  the  erroneous  assumption  of  a 
linear stress distribution along the length of a wall, pier or spandrel and is taken as 1.3 in keeping 
with the equivalent stress block analogy as outlined in MSJC 530‐02 (2002). 

Yi et al. (2008) suggest that the effective length of the wall in the toe crushing failure mode shall 
be given by Equation 8‐12a for walls, piers and spandrels with an attached perpendicular flange 
or  flanges  and  Equation  8‐12b  for  walls,  piers  or  spandrels  where  no  perpendicular  flange  is 
attached. 

C8.4.3 Capacity in Bed‐joint Sliding Failure Mode 
Bed‐joint  sliding  occurs  across  a  continuous  bed‐joint  and  is  identifiable  by  the  formation  of 
horizontal  cracks  along  the  bed‐joint.  Deformation  of  the  pier  by  sliding  along  the  bed‐joint 
occurs such that the upper part of the wall is displaced relative to the lower part of the wall as 
shown  in  Figure  C8‐6.  Bed‐joint  sliding  occurs  when  the  average  shear  stress  acting  on  the 
effective  section  of  the  bed‐joint  exceeds  the  maximum  bed‐joint  shear  strength  and  is  likely 
when the axial loads acting on the wall are low. Due to the frictional resistance a large amount 

C8‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

of energy is dissipated and it is typical for large deformations to be endured without significant 
strength deterioration, hence bed‐joint sliding failure is a displacement controlled failure mode. 

 
Figure C8‐6: Bed‐joint sliding failure mode 

Increasing  axial  load  and  wall  area  increases  the  bed‐joint  sliding  capacity  expected  of  a  wall. 
Equation 8‐10 ignores any increase to the bed‐joint sliding capacity due to the self weight of the 
wall being assessed or the effect of any perpendicular flanges as it is possible, and conservative 
to assume, that the failure plane across which the wall bed‐joint slides is located at the top of 
the wall.  

C8.5 Deformation Limits 
Deformation limits, taken as drift and expressed as a percentage of the clear height of the wall 
between  points  of  restraint,  have  been  reworked  from  research  completed  by  Magenes  and 
Calvi (1997). The use of a bilinear approximation for the cyclic envelope is suggested due to the 
largely  non‐linear  response  of  a  URM  wall  and  Figure  C8‐7  shows  a  possible  definition  of 
parameters  of  an  appropriate  bilinear  curve.  The  bilinear  approximation  has  been  utilised  to 
determine the deformation limits seen in Table 8‐4.  

  C8‐9
 
  Section C8 ‐   of walls loaded in‐plane 
 
 

 
Figure C8‐7:  Equivalent bilinear approximation (Magenes and Calvi 1997) 

Failure of a URM wall, pier or spandrel in drift is defined as the drift relating to a degradation of 
seismic  load  capacity  to  80%  of  the  maximum  seismic  load  capacity  of  the  element,  Vmax  as 
shown in Figure C8‐7. 

C8.6 Worked Examples 

8 m  10 m 

10 m 

Figure C8‐8: Plan layout of building 

A single storey stand‐alone URM building having a rectangular plan is illustrated in Figure C8‐8. 
The wall height is 2.8 m. Scratch tests showed that the bricks have a compressive strength, f’b, of 
26.9 MPa  and  the  mortar  has  a  compressive  strength,  f’j,  of  5.5 MPa,  which  are  masonry 
properties considered average to New Zealand URM construction. 

Determine masonry density: 

1578 5 8  

1578 5 26.9 8 5.5 

C8‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

1756.5 kg/m3

Determine masonry unit weight: 

9.81 
1756.5 9.81 
17.23 kN/m3 

Considering the 18 m wall at the rear of the building, the length of wall, lw, is 18 m. All walls are 
two leaves thick and the width of the wall, bw, is 0.25 m. The wall (and flange) height, h, is 2.8 m. 

Determine weight of wall: 

 
17.23 0.25 18 2.8 
217 kN 

The  wall  has  three  flanges,  hereafter  referred  to  as  left  flange,  centre  flange  and  right  flange. 
The width of all flanges, bf, is 0.25 m.  

Determine flange weights: 

Left  flange:  Flange  length,  lf,  is  equal  to  the  minimum  of  the  actual  flange  length,  10 m,  and  6 
times the flange width, 1.5 m, and so is 1.5 m. 

17.23 0.25 1.5 2.8 

         18.1 kN 

Centre flange: Flange length, lf, is equal to the minimum of the actual flange length, 4 m, and 6 
times the flange width, 1.5 m, and so is 1.5 m. 

17.23 0.25 1.5 2.8 

         18.1 kN 

Right flange: Flange length, lf, is equal to the minimum of the actual flange length, 10 m, and 6 
times the flange width, 1.5 m, and so is 1.5 m. 

17.231 0.25 1.5 2.8 

         18.1 kN 

The normal force acting on the cross‐section of the top of the wall, Nt, is 900 kN (0.20 MPa). 

Determine the normal force acting on the cross‐section of the bottom of the wall: 

  C8‐11
 
  Section C8 ‐   of walls loaded in‐plane 
 
 

With all flanges considered separately, and having identical weights: 

  217 18.1 900 


1135 kN 

With all three flanges considered together: 

217 18.1 3 900  


1171 kN 

With no flanges considered: 

217 900  
1117 kN 

Determine cohesion and coefficient of friction (In this case it is decided that no in‐situ testing is 
necessary): 

0.045

0.045 5.5
0.248 MPa

0.65 

Determine the cross‐sectional area of the wall: 

 
0.25 18 
4.5 m2 

Determine the average compressive stress on the wall: 

The wall is considered cantilevered as the building is a single storey in height.  

900
 
0.25 18
0.2 MPa 

Determine diagonal tension strength of the masonry: 
0.75 0.8
 
1.5
0.75 0.248 0.2 0.8 0.65
 
1.5

C8‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

0.176 MPa 

The  distance  to  the  centre  of  inertia  of  the  wall  from  the  compression  edge  is  required  to  be 
determined for various cases of flanges. 

Σ 0.5
 
Σ

Centre flange only, compression edge at left end of wall: 
18.1 8 0.5 217 18
 
18.1 217
8.9 m 

Centre flange only, compression edge at right end of wall: 
18.1 10 0.5 217 18
 
18.1 217
9.1 m 

All three flanges, compression edge at left end of wall: 
18.1 0.125 18.1 8 18.1 17.875 0.5 217 18
 
18.1 3 217
8.9 m 

All three flanges, compression edge at right end of wall: 
18.1 0.125 18.1 10 18.1 17.875 0.5 217 18
 
18.1 3 217
9.1 m  

Capacity in Diagonal Tension Failure Mode 

The shear stress factor, ζ, is equal to 1.0 as per Table 8‐1 (h/lw is equal to 0.16).  

Consider all flanges separately, and a case with no flanges, then take the average capacity. 

Left flange:  

For the case where the compression edge is at the left end of the wall, the first flange location 
factor, α1, is equal to ‐1.0 and the second flange location factor, α2, is equal 1.0 to as per Table 8‐
2 (af is equal to 0.125 m). This is the same case as for the right flange where the compression 
edge is at the right end of the wall. 

1 1
1 . . 1 2. .
0.9 6 2
1 .  
. .
2

  C8‐13
 
  Section C8 ‐   of walls loaded in‐plane 
 
 

0.9 0.25 18 176 200


1  
1.0 176

18.1 1 18.1 18.1 0.125 1


1 1 2
217 6 217 217 18 2
 
18.1 0.125 1.0 18.1
217 18 2 217
735 kN 

For the case where the compression edge is at the right end of the wall, the first flange location 
factor, α1, is equal to 1.0 and the second flange location factor, α2, is equal 0 to as per Table 8‐2 
(af  is  equal  to  17.875 m).  This  is  the  same  case  as  for  the  right  flange  where  the  compression 
edge is at the left end of the wall. 

0.9 0.25 18 176 200


1  
1.0 176

18.1 1 18.1 18.1 10 1


1 1 2
217 6 217 217 18 2
 
18.1 10 1.0
217 18 2
735 kN 

Centre flange:  

For the case where the compression edge is at the left end of the wall, the first flange location 
factor, α1, is equal to ‐1.0 and the second flange location factor, α2, is equal 1.0 to as per Table 8‐
2 (af is equal to 8 m). 

0.9 0.25 18 176 200


1  
1.0 176

18.1 1 18.1 18.1 8 1


1 1 2
217 6 217 217 18 2
 
18.1 8 1.0 18.1
217 18 2 217
685 kN 

For the case where the compression edge is at the right end of the wall, the first flange location 
factor, α1, is equal to 1.0 and the second flange location factor, α2, is equal 0 to as per Table 8‐2 
(af is equal to 10 m). 

C8‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

0.9 0.25 18 1.0 176 200


1  
1.0 176

18.1 1 18.1 18.1 10 1


1 1 2
217 6 217 217 18 2
 
18.1 10 1.0
217 18 2
685 kN 

No flanges: 

For the case where the compression edge is at the left end of the wall (same as for where the 
compression edge is at the right end of the wall). 

0.9
1  

0.9 0.25 18 176 200


1  
1.0 176

1042 kN 

, , , , ,  

, , , , , , ,  
 kN 

Note that the direction of loading makes no difference to the wall capacity and so consideration 
of  the  location  of  the  compression  edge  could  have  been  excluded  from  the  calculations,  but 
was included here for completeness. 

Capacity in Rocking Failure Mode 

1
 
2 0.85

Determine the average masonry compressive strength: 
. .
0.7  
. .
0.7 26.9 5.5  
13.8 MPa 

Determine the average normal force acting on the cross‐section: 

0.5  
0.5 900 1171  
1035.5 kN 

  C8‐15
 
  Section C8 ‐   of walls loaded in‐plane 
 
 

Determine the effective height: 

 
Because this building is a single story in height,  can be taken as 1.0. 

1.0 2.8 
2.8 m 

Determine the distance from the compression edge of the wall to the line of action of  : 

Assuming   acts uniformly over the cross‐section, we can find Z by taking moments of area 
about the left end of the wall. 
0.25 1.5 0.125 8 17.875 18 0.25 9
 
3 0.25 1.5 18 0.25
8.9 m from the left end of the wall 

  9.1 m from the right end of the wall 

Determine the nominal shear capacity corresponding to the rocking failure mode: 

It  has  previously  been  determined;  that  the  compression  block  lies  within  the  flange  area 
regardless  of  which  direction  of  loading  we  consider,  but  in  order  to  take  a  conservative  and 
simplified approach we will simply take    as 0.25 m. It is also clear that the Z value of 8.9 m will 
be critical. 
1
 
2 0.85

1035.5 1 1035.5
8.9  
2.8 2 0.85 13800 0.25
3226 kN 

Alternatively  if   is  taken  as  1.75 m,  i.e  the  effective  flange  area  is  considered  in  the 
compression block,   will equal 3282 kN. 

 Capacity in Bed‐joint Sliding Failure Mode 

Neither the brick nor mortar compressive strengths are classified as “soft” in Table 2‐2 or Table 
2‐4, hence the bed‐joint sliding failure mode need not be considered for this example. However 
for  completeness  of  these  notes,  the  calculations  for  determining  bed‐joint  sliding  capacity 
follow. 

0.75 0.8
 
1.5
0.75 0.25 18 248 0.8 0.65 1171
 
1.5
862.5 kN 

C8‐16   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Capacity in Toe Crushing Failure Mode 

The  wall  in  this  example  has  not  been  retrofitted  with  either  unbonded  post‐tensioning  or  a 
seismic  improvement  intervention  that  inhibits  the  formation  of  the  diagonal  tension  failure 
mode, hence the toe crushing failure mode need not be considered for this example. However 
for completeness the calculations for determining toe crushing capacity of an un‐flanged wall of 
identical dimensions have been included. 

Determine effective length of the wall in toe crushing, with no flanges present (conservative): 
2.
 
1.3. .
2 1117
 
1.3 13800 0.25
0.498 m 

Determine toe crushing wall capacity with no flanges present (conservative): 
1 1
. . .  
2 3
1117 1 1
18 0.498  
2.8 2 3
 kN 

Wall Capacity 

min , , ,  
min 799, 3282, 862.5, 3524  
799 kN 

The diagonal tension failure mode is critical for this wall. 

References 
ASCE.  (2007).  Seismic  rehabilitation  of  existing  buildings,  ASCE/SEI  41‐06,  American  Society  of 
Civil Engineers, Reston, VA. 
Costley,  A.  C.  and  Abrams,  D.  P.  (1996)  “Dynamic  response  of  unreinforced  masonry  buildings 
with flexible diaphragms." NCEER‐96‐0001, University of Buffalo, Buffalo, New York. 

Dizhur, D., Lumantarna, R., Derakhshan, H. and Ingham, J. M. (2010). “Testing of an earthquake‐
damaged  unreinforced  masonry  building.”  7th  International  Conference  on  Urban 
Earthquake  Engineering  and  5th  International  Conference  on  Earthquake  Engineering, 
Tokyo, Japan, 3 ‐ 5 March. 
FEMA (2000). "Prestandard and commentary for the seismic rehabilitation of buildings." FEMA 
356,  American  Society  of  Civil  Engineers  and  Federal  Emergency  Management  Agency, 
Reston, VA. 
Magenes,  G.,  and  Calvi,  G.  M.  (1997).  "In‐plane  seismic  response  of  brick  masonry  walls." 
Earthquake Engineering and Structural Dynamics, 26(11), 1091‐1112. 

  C8‐17
 
  Section C8 ‐   of walls loaded in‐plane 
 
 

Masonry  Standards  Joint  Committee  (MSJC)  (2002).  Building  code  requirements  for  masonry 
structures,  ACI  530‐02/ASCE  5‐02/TMS  402‐02.  America  Concrete  Institute,  Structural 
Engineering  Institute  of  the  American  Society  of  Civil  Engineers,  The  Masonry  Society, 
Detroit, United States. 
Moon, F. L., Yi, T., Leon, R. T. and Kahn, L. F. (2007). "Testing of a full‐scale unreinforced masonry 
building  following  seismic  strengthening."  Journal  of  Structural  Engineering,  133(9),  1215‐
1226. 

NZSEE  (2006).  Assessment  and  improvement  of  the  structural  performance  of  buildings  in 
earthquakes: Recommendations of a NZSEE study group on earthquake risk buildings, New 
Zealand Society for Earthquake Engineering. 
Paquette, J. and Bruneau, M. (2003) “Pseudo‐dynamic testing of unreinforced masonry buildings 
with flexible diaphragm.” Journal of Structural Engineering. 129(6), 708‐716. 

Russell,  A.  P.  (2010).  "In‐plane  seismic  assessment  of  unreinforced  masonry  buildings."  PhD 
thesis,  Department  of  Civil  and  Environmental  Engineering,  The  University  of  Auckland, 
Auckland, New Zealand. 
Russell,  A.  P.,  Elwood,  K.  J.  and  Ingham,  J.  M.  (2012).  "Force‐displacement  response  of 
unreinforced masonry walls with flanges." Journal of Structural Engineering, Under review. 
Standards New Zealand (SNZ) (2004). NZS 1170:2004 ‐ Structural Design Actions. Standards New 
Zealand, Wellington, New Zealand. 
Tomazevic,  M.,  Lutman,  M.  and  Weiss,  P.  (1993).  “The  seismic  resistance  of  historical  urban 
buildings and the interventions in their floor systems: An experimental study.”The Masonry 
Society Journal, 12(1), 77‐86. 

Yi, T., Moon, F. L., Leon, R. T. and Kahn, L. F. (2005). "Effective pier model for the nonlinear in‐
plane analysis of individual URM piers." The Masonry Society Journal, 23(1), 21‐35. 

Yi,  T.,  Moon,  F.  L.,  Leon,  R.T.  and  Kahn,  L.  F.  (2006)  “Quasi‐static  tests  of  a  two‐storey  
unreinforced masonry building with flexible diaphragms.” Journal of Structural Engineering, 
132(5), 643‐652. 

Yi, T., Moon, F. L., Leon, R. T. and Kahn, L. F. (2008). "Flange effects on the nonlinear behaviour 
of URM piers." The Masonry Society Journal, 26(2), 31‐42. 

C8‐18   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

  C8‐19
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C9 ‐ Strength and Deformation Assessment of 
Flexible Timber Floor Diaphragms 

C9.3 Lateral Deformation 
Further  guidance  on  the  strength  and  deformation  assessment  of  flexible  timber  floor 
diaphragms can be found in Oliver (2010). 

C9.3.1 Deformation Limits 
While  it  has  been  proven  experimentally  that  diaphragms  of  this  nature  can  withstand 
deformations in excess of 150 mm (see Figure C3‐5), this limit has been prescribed in accordance 
with ASCE 41‐06 (2007) Clause 3.3.1.3.5 to ensure  that  the assumptions made for linear static 
procedures  are  not  violated.  As  illustrated  in  Figure  C3‐5  and  C3‐6  there  is  considerable 
conservation  in  this  assumption  as  experimental  testing  has  confirmed  that  flexible  timber 
diaphragms typically have a substantial post‐yield stiffness as denoted k2 in Figure C3‐6. 

The  criterion  based  on  wall  thickness  has  been  offered  to  reduce  the  risk  of  out‐of‐plane  wall 
collapse. Although this criterion has not been thoroughly scrutinised, preliminary analysis of out‐
of‐plane  walls  responding  in  the  critical  cantilever  mode  has  indicated  that  diaphragm 
displacements below half wall thickness are within the displacement capacity of the supporting 
URM  wall.  Diaphragms  exceeding  this  deformation  limit  might  jeopardise  the  load  carrying 
capacity  of  the  out‐of‐plane  loaded  walls  and  potentially  induce  a  cantilever‐type  wall  failure. 
Further  analysis  of  diaphragm  displacement  limits  is  recommended  as  a  subject  for  future 
research.  

C9.4 Strength 
Diaphragm characteristic shear strength, Qn, is independent of diaphragm geometry. In order to 
determine the total shear strength of the diaphragm, Rn, the characteristic shear strength must 
be multiplied by the effective depth of the diaphragm, be.  

The  inclusion  of  a  strength  reduction  factor,  ,  preserves  established  design  procedures  while 
coefficients  αo  and  αc  appropriately  reduce  diaphragm  shear  strength  for  penetrations  and 
configuration variations, respectively, as discussed in Sections C3.6.2 and C3.6.3. 

C9.4.1 %NBS 
It is recommended that %NBS be calculated to assess the performance of the existing diaphragm 
against  the  standard  required  for  a  new  diaphragm.  Vd  can  be  used  in  the  absence  of  new 
diaphragm performance requirements, as new diaphragm construction would be designed to at 
least this value.   

  C9‐1
 
  Section C9 ‐ Strength and Deformation Assessment of Flexible Timber Floor Diaphragms 
 
 

C9.5 Worked Example 1 
Determine the deformation and strength of the diaphragm shown below. 

  10.4 m 

 5.535 m 

Step 1:  Previously Determined Values 

Vd (N‐S)      = 33 kN 
Vd (E‐W)      = 35 kN 
Kd (N‐S)      = 639 kN/m 
Kd (E‐W)      = 1315 kN/m  
Qn (N‐S)      = 1.5 kN/m 
Qn (E‐W)      = 1.2 kN/m 
be (N‐S)      = 5.535 m 
be (E‐W)      = 10.4 m 
μ      = 6 
αp      = 1.0 
αc      = 1.0 

Step 2:  Diaphragm Deformation Calculation 

North South Direction 
33
μ 6  
639
Δd(NS)      = 0.3098 m 

      = 310 mm 

East West Direction 
35
μ 6  
1315
Δd(EW)      = 0.1597 m 

      = 160 mm 

Step 3:  Diaphragm Shear Strength Calculation 

C9‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

North South Direction 

Rn  =      = 1.0 × 1.0 × 1.0 × 5.535 × 1.5 

        = 8.3 kN 

East West Direction 

Rn  =      = 1.0 × 1.0 × 1.0 × 10.4 × 1.2 

        = 12.5 kN 

C9.6 Worked Example 2 
Determine the deformation and strength of the diaphragm shown below. 

b1 = 9.1 m 

b2 = 4.9 m 

L = 12.2 m 

Step 1:  Previously Determined Values 

Vd (N‐S)      = 40 kN 
Vd (E‐W)      = 44 kN 
Kd (N‐S)      = 585 kN/m 
Kd (E‐W)      = 871 kN/m  
Qn (N‐S)      = 1.3 kN/m 
Qn (E‐W)      = 0.8 kN/m 
be (N‐S)      = 7.0 m 
be (E‐W)      = 12.2 m 
μ      = 5 
αp      = 1.0 
αc      = 1.0 

Step 2:  Diaphragm Deformation Calculation 

North South Direction 

  C9‐3
 
  Section C9 ‐ Strength and Deformation Assessment of Flexible Timber Floor Diaphragms 
 
 

40
μ 5  
585
Δd(NS)    = 0.342 m 

    = 342 mm 

East West Direction 
44
μ 5  
871
Δd(EW)    = 0.253 m 

    = 253 mm 

Step 3:  Diaphragm Shear Strength Calculation 

North South Direction 

Rn  =       = 1.0 × 1.0 × 1.0 × 7.0 × 1.5 

        = 10.5 kN 

East West Direction 

Rn  =       = 1.0 x 1.0x 1.0 × 12.2 × 1.2 

        = 14.6 kN 

C9.7 Worked Example 3 
Determine the deformation and strength of the diaphragm shown below. 

L1 = 7.2 m    L2 = 7.2 m 

b2 = 6.2m 

L1 = 12.4 m 

b1 = 6.2m 

L1 = 14.4 m

Step 1:  Previously Determined Values 

Vd (N‐S)      = 46 kN 
Vd (E‐W)      = 52 kN 

C9‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Kd (N‐S)      = 323 kN/m 
Kd (E‐W)      = 889 kN/m  
Qn (N‐S)      = 0.8 kN/m 
Qn (E‐W)      = 1.3 kN/m 
be (N‐S)      = 12.4 m 
be (E‐W)      = 14.4 m 
μ      = 5 
αp      = 0.75 
αc      = 1.0 

Step 2:  Diaphragm Deformation Calculation 

North South Direction 
46
μ 5  
323
Δd(NS)    = 0.712 m 

    = 712 mm 

East West Direction 
52
μ 5  
889
Δd(EW)    = 0.292 m 

    = 292 mm 

Step 3:  Diaphragm Shear Strength Calculation 

North South Direction 

Rn  =       = 1.0 × 0.75 × 1.0 × 12.4 × 1.5 

        = 14.0 kN 

East West Direction 

Rn  =       = 1.0 × 0.75 × 1.0 × 14.4 × 1.2 

        = 13.0 kN 

C9.8 References 
ASCE.  (2007).  Seismic  rehabilitation  of  existing  buildings,  ASCE/SEI  41‐06,  American  Society  of 
Civil Engineers, Reston, VA. 
Oliver, S. J. (2010) “A design methodology for the assessment and retrofit of flexible diaphragms 
in unreinforced masonry buildings”, SESOC Journal, 23(1), 19‐49. 
 
 

  C9‐5
 
  Section C9 ‐ Strength and Deformation Assessment of Flexible Timber Floor Diaphragms 
 
 

 
 
 
 

C9‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C10 ‐ Strength and Deformation Assessment of 
Timber Roof Diaphragms 

C10.2 Scope 
Roofing in URM buildings typically consists of corrugated light gauge steel sheathing fastened to 
timber  purlins  that  are  supported  by  timber  trusses  spanning  onto  URM  walls  or  beams  (see 
Figure  C10‐1(a)).  Where  supported  on  the  URM  walls,  the  ends  of  the  purlins  and  trusses  are 
typically  seated  into  pockets  in  the  walls.  Figure  C10‐1(b)  provides  an  example  of  structural 
sheathing fastened to the underside of a roof truss that would effectively behave analogous to a 
floor  diaphragm;  however  ceilings  can  often  comprise  light  panels  that  are  intended  for 
aesthetic purposes only and would not contribute to overall seismic response. 

No  research  to  date  has  quantitatively  established  the  in‐plane  performance  of  roofs  in  URM 
buildings.  As  a  result,  the  development  of  seismic  assessment  procedures  explicitly  for  timber 
roofs  remains  a  subject  for  future  research,  and  has  not  been  included  in  this  document. 
However,  due  to  their  similarities,  the  material  properties  and  the  procedures  to  determine 
lateral  deformation  and  strength  of  timber  floor  diaphragms  have  been  suggested  as  an 
appropriate set of assessment procedures for timber roofs during the interim. Because obvious 
differences  exist  between  the  structural  configurations  of  timber  floors  and  timber  roofs,  it  is 
recommended that the suggested guidelines be applied with consideration and diligence. 

 
(a) Roof trusses  (b) Ceiling sheathing 

Figure C10‐1: Examples of roof configurations 

  C10‐1
 
  Section C10 ‐ Strength and Deformation Assessment of Timber Roof Diaphragms 
 
 
C10.3 Material Properties 
It  is  recommended  that  the  designer  exercise  conservatism  during  the  selection  of  material 
properties in order to account for the uncertainty involved in applying timber floor diaphragm 
properties to timber roofs.  

C10.4 Lateral Deformation 
In the absence of research validation, it has been assumed that given the appropriate selection 
of Kd and μ, lateral deformation can be determined using the same rationale as for timber floor 
diaphragms. Future research will provide accurate values of Kd and μ for timber roofs. Refer to 
Section C9.3 for further information. 

C10.4.1 Deformation Limits 
A deformation limit of 150 mm has been prescribed in accordance with ASCE/SEI 41‐06 (2007) 
Clause  3.3.1.3.5  to  ensure  that  the  assumptions  made  for  linear  static  procedures  are  not 
violated. 

The  criterion  based  on  wall  thickness  has  been  offered  to  reduce  the  risk  of  out‐of‐plane  wall 
collapse. Although this criterion has not been thoroughly scrutinised, preliminary analysis of out‐
of‐plane  walls  responding  in  the  critical  cantilever  mode  has  indicated  that  diaphragm 
displacements below half wall thickness are within the displacement capacity of the supporting 
URM  wall.  Diaphragms  exceeding  this  deformation  limit  might  jeopardise  the  load  carrying 
capacity  of  the  out‐of‐plane  loaded  walls  and  potentially  induce  a  cantilever‐type  wall  failure. 
Further  analysis  of  diaphragm  displacement  limits  is  recommended  as  a  subject  for  future 
research. 

C10.5 Strength 
In the absence of research validation, it has been assumed that roof strength can be determined 
using the same principles as for timber floor diaphragms. Accurate values of αp, αc, and Qn for 
roofs will be established from future research. Refer to Section C9.4 for further information. 

C10.5.1 %NBS 
It is recommended that %NBS be calculated to assess the performance of the existing diaphragm 
against  the  standard  required  for  a  new  diaphragm.  Vd  can  be  used  in  the  absence  of  new 
diaphragm performance requirements, as new diaphragm construction would be designed to at 
least this value. 

C10.6 References 
ASCE.  (2007).  Seismic  rehabilitation  of  existing  buildings,  ASCE/SEI  41‐06,  American  Society  of 
Civil Engineers, Reston, VA. 

C10‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C11 ‐ Out‐of‐plane Wall and Parapet Response 

C11.2 Scope 
This  section  is  based  on  laboratory  and  field  testing  and  subsequent  numerical  analysis 
conducted  by  Derakhshan  (2011),  and  the  assessment  technique  is  suitable  for  walls  and 
parapets  of  single‐storey  and  two‐storey  URM  buildings  in  most  areas  of  New  Zealand.  It  is 
estimated that this section covers an overall 86% of URM buildings in New Zealand (Russell and 
Ingham 2010).  

The  NZSEE  (2006)  guidelines  propose  a  detailed  procedure  for  seismic  evaluation  of  one‐way 
spanning out‐of‐plane loaded URM walls, and the procedure required substantial calculations to 
be  conducted.  Derakhshan  et  al.  (2009)  studied  the  guideline  in  detail  and  showed  by 
comparison  with  ASCE/SEI  41‐06  (2007)  that  the  results  were  unreasonably  conservative.  For 
instance, NZSEE (2006) indicated that walls having a slenderness ratio as low as 3 or 4 may be 
categorised as earthquake‐risk depending on the soil type and seismic zonation. Derakhshan et 
al. (2009) and Derakhshan (2011) further showed that a combination of parameters used in the 
existing procedure led to erroneous results over a range of practical wall slenderness ratios.  

The  unreasonably  conservative  results  obtained  using  the  complicated  method  proposed  in 
NZSEE  (2006)  encouraged  a  simpler  effective  assessment  method  to  be  sought.  Direct  time‐
history analysis was used to investigate the behaviour of out‐of‐plane loaded URM walls when 
subjected  to  various  representative  ground  motion  records.  The  obtained  wall  displacement 
demand  was  compared  with  the  wall  displacement  capacity  assuming  a  displacement  capacity 
reduction factor of 0.6. The numerical analyses were conducted for both single‐storey and two‐
storey  walls,  recognising  that  Russell  and  Ingham  (2010)  found  that  approximately  86%  of  all 
URM buildings in New Zealand are either one or two‐storeys tall. Further description pertaining 
to the preparation of the assessment charts is provided in Section C11.4. 

Four different diaphragm stiffness values of 100 kN/m, 500 kN/m, 1000 kN/m, and 2000 kN/m 
were  assumed  in  the  numerical  analyses  conducted  in  Derakhshan  (2011).  The  results  of  the 
analyses  for  single‐storey  walls  were  found  to  be  insensitive  to  diaphragm  in‐plane  stiffness 
values greater than 500 kN/m, and a diaphragm stiffness of 100 kN/m resulted in a decrease in 
%NBS.Z  of  approximately  10%  when  compared  to  that  obtained  when  assuming  a  diaphragm 
stiffness  value  of  500 kN/m.  The  displacement  demand  on  top‐storey  walls  dramatically 
increased  when  the  wall  was  connected  to  a  diaphragm  having  a  stiffness  value  of  equal  to 
100 kN/m, when compared to the same data when a diaphragm stiffness of 500 kN/m or higher 
was  assumed.  Based  on  these  observations,  it  is  recommended  that  horizontal  diaphragms  of 
both single‐storey and  two‐storey URM buildings  be stiffened  to a level of  diaphragm in‐plane 
stiffness  equal  to  at  least  500 kN/m.  For  the  purpose  of  this  section  the  diaphragm  in‐plane 
stiffness is calculated using Equation 3‐1. 

Walls  tests  reported  in  Derakhshan  (2011)  and  having  a  top  support  with  vertical  stiffness 
demonstrated  significant  resistance  to  cracking  that  is  a  pre‐requisite  to  stable  out‐of‐plane 
rocking.  Such  walls  may  meet  the  out‐of‐plane  seismic  load  demand  in  the  elastic  range,  and 

  C11‐1
 
  Section C11 ‐ Out‐of‐plane Wall and Parapet Response 
 
 

evaluation  of  the  wall  dynamic  stability  as  conducted  here  may  not  be  necessary.  URM  walls 
connected  to  timber  diaphragms  or  having  diaphragm  connections  that  were  strengthened  by 
means  of  vertically  inserted  grouted  steel  bars  were  found  to  have  a  negligible  effect  in 
developing  arching  action  in  the  wall  plane  or  in  restraining  wall  out‐of‐plane  displacements. 
These observations suggested that the procedures recommended in this section are suitable for 
these categories of walls. 

Experimental research conducted in Australia during the last decade (Griffith et al. 2007) and in‐
field  tests  reported  in  Derakhshan  (2011)  showed  that  two‐way  spanning  URM  walls  have 
significantly higher crack resistance than that expected from one‐way spanning URM walls. The 
latter  study  showed  that  a  few  tested  two‐way  spanning  one‐leaf  URM  walls  located  in 
Wellington satisfied the requirements of the New Zealand seismic loading standard in the elastic 
range. It is recommended that URM walls that are expected to behave in a two‐way condition be 
evaluated by testing a few representative walls. Alternatively, analytical methods may be used 
to estimate wall behaviour based on the material properties. 

C11.3 Wall Thickness, Height, and Slenderness Ratio 
Russell  and  Ingham  (2010)  suggested  that  a  regular  construction  form  reflected  from  the 
relatively  short  span  of  masonry  construction  in  New  Zealand  is  observed  in  the  existing  URM 
building  stock,  and  that  this  regularity  facilitates  a  typology  study  of  such  buildings.  The  most 
frequently  observed  configuration  of  wall  thickness  in  two‐storey  URM  buildings  is  that 
containing  a  three‐leaf  wall  in  the  lower‐storey  and  a  two‐leaf  wall  in  the  top‐storey.  This 
assumption  has  been  made  in  various  steps  of  the  development  of  the  assessment  charts, 
including in the calculation of overburden for lower‐storey walls and in the construction of the 
numerical models. 

In‐situ testing reported in Derakhshan (2011) showed that severe degradation of the weak lime‐
based plaster of URM walls occurred when the walls were subjected to out‐of‐plane cyclic static 
uniform loading. Stronger cement‐based plaster layers underwent spalling and separated from 
the original brickwork, suggesting that plaster layers should not be included in the wall thickness 
when estimating the rocking behaviour of walls. 

Seismic  evaluation  of  parapets  is  conducted  assuming  an  effective  slenderness  ratio,  with  the 
value being calculated as four times the height of the parapet divided by its thickness. Research 
by  Lam  et  al.  (1995),  Doherty  (2000),  and  Griffith  et  al.  (2007)  has  shown  that  the  seismic 
behaviour  of  free‐standing  URM  walls  is  analogous  to  that  of  a  four  times  more  slender  URM 
wall  responding  in  a  simply‐supported  condition.  Detailed  investigation  of  the  NZSEE  (2006) 
guidelines show a similar trend, with the calculated %NBS obtained for parapets being virtually 
the same as that obtained for a four times more slender simply‐supported wall. When using the 
assessment charts presented in this section, a chart that corresponds to the actual thickness of 
parapet shall be used. 

For walls having the same slenderness ratio but different thicknesses, the taller and thicker wall 
possesses  a  higher  fundamental  period,  and  thus  larger  displacement  demand  would  be 
expected for thicker walls. This effect of increased period is further accompanied by an increase 

C11‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

in  wall  mass  for  thicker  walls,  resulting  in  higher  inertial  forces  being  associated  with  thicker 
walls.      However,  the  displacement  capacity  of  out‐of‐plane  loaded  URM  walls  increases  with 
increasing  thickness.  Investigation  of  dynamic  time‐history  analysis  results  show  that  the 
obtained %NBS for two‐leaf walls is on average 0.75 times the %NBS for a three‐leaf wall having 
the same slenderness ratio. As the thickness ratio is 0.5 for a one‐leaf wall vs. a two‐leaf wall and 
the thickness ratio is 0.65 for a two‐leaf wall vs. a three‐leaf wall, a larger reduction in %NBS is 
expected  for  the  former  when  compared  to  the  latter.  Based  on  this  observation,  it  is 
recommended that the %NBS for a one‐leaf wall is assumed as 0.6 times the %NBS for a two‐leaf 
wall having the same slenderness ratio. 

C11.4 Load‐bearing walls 
The applied overburden for load‐bearing (LB) walls was assumed to be equal to 3.8 kN/m. The 
weight  of  a  diaphragm  having  dimensions  of  8000  mm  ×  16000  mm  was  assumed  in  the 
calculation of the overburden for LB walls, with the diaphragm seismic weight being calculated 
assuming 0.35 kPa permanent (dead) load, 2 kPa imposed (live) load, and a live load reduction 
factor  of  30%.  Diaphragm  weight  was  assumed  to  be  transferred  entirely  through  two  parallel 
URM walls. 

Walls that have an overburden load of less than 3.8 kN/m can be evaluated using this section by 
interpolating results from the provided assessment charts. Extrapolation of results shall not be 
used for overburden loads in excess of 3.8 kN/m. Research has shown that applied overburden 
improves wall behaviour, but the increase in %NBS has a nonlinear relationship with the applied 
overburden. 

Estimation of the overburden for lower storey walls should be conducted excluding the weight 
of the top‐storey walls as this weight has been previously accounted for in the development of 
the assessment charts. Derakhshan (2011) used geometrical stiffness models that accounted for 
increased wall strength due to the weight of the top‐storey walls, and the stabilising effect of the 
top‐storey  wall  weight  was  taken  into  consideration  when  developing  the  assessment  charts 
included herein. 

C11.5 Assessment 
To  produce  the  graphs  presented  in  this  section,  the  conclusions  of  the  numerical  analyses 
conducted  in  Derakhshan  (2011)  were  used.  %NBS  was  averaged  from  time‐history  analyses 
conducted using a suite of 7 ground motion records recommended by Oyarzo Vera (2011) and 
Oyarzo Vera et al. (2011). The suites of ground motion corresponded to 5 different zones for the 
North Island of New Zealand (see Figure C11‐2) and had different characteristics that reflected 
the  seismological  signature  of  the  site  being  investigated.  The  time‐history  records 
corresponded to 5% damping ratio and an annual probability of exceedance of 1/500. Although 
it had been intended to complete zonation maps for all of New Zealand, the study for the South 
Island is currently in a preliminary stage. The numerical analysis conducted in Derakhshan (2011) 
was limited to the North Island, but the results suggested that the study also addressed most of 
the  URM  building  stock  in  the  South  Island.  The  results  of  the  time‐history  analysis  proved 

  C11‐3
 
  Section C11 ‐ Out‐of‐plane Wall and Parapet Response 
 
 

insensitive  to  the  seismic  zones  North  A‐C  and  V  (see  Figure  C11‐4),  suggesting  that  any  wall 
located in either of zones A, B, C, or V can be evaluated using a single average curve as labelled 
“Elsewhere” in Figures 11‐1 through 11‐4. Walls located in the near‐fault (NF) zone in the North 
Island demonstrated a significantly different behaviour from that of walls located in any of zones 
A, B, C and V.  

All walls located in any region of the South Island except those located in areas that according to 
NZS 1170.5:2004  have  near  fault  characteristics  are  evaluated  using  the  curve  labelled  as 
“Elsewhere” in Figures 11‐1 through 11‐4.  The assessment charts should not be used for regions 
of South Island that have NF characteristics, but this limitation affects only a small percentage of 
all URM buildings in New Zealand (Russell and Ingham 2010). 

C11.5.1 Assessment of Parapets for Shear Capacity 
Stable rocking of cantilever walls is subject  to adequate shear  capacity at their support.  While 
simply‐supported  walls  are  not  usually  prone  to  out‐of‐plane  shear  failure  due  to  sufficient 
friction and axial loads, shorter cantilever parapets are likely to fail in shear especially if a damp 
proof  course  (DPC)  membrane  has  been  used  at  the  parapet  base.  URM  parapets  should 
therefore be assessed for their shear capacity, and the assessment shall account for the effects 
of  DPC  membrane  that  is  often  used  at  the  parapet  base.    Doherty  (2000)  conducted  tests  on 
URM walls with three forms of DPC construction, namely standard, centred, and slip joint. Static 
testing suggested that the coefficient of friction varied from 0.1 to 0.6, with the average being 
0.5. Shake table tests showed that the coefficient of dynamic friction was up to 20% less than 
the  coefficient  of  static  friction.  It  is  considered  reasonably  conservative  to  assume  a  static 
coefficient of friction equal to 0.45 between DPC and masonry.  

   

C11‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C11.5.2 Flowchart for using the Procedure for Seismic Assessment of Out‐of‐plane 
Loaded URM Walls 

Is diaphragm in‐plane 
stiffness calculated using 
Section 3.6 greater than 
500 kN/m?

Yes No

Are there structural elements, e.g. beams, above  Diaphragm should be 
the top wall edge that restrict wall’s vertical  stiffened, then go back 
movements? to start of procedure.

Yes No

The procedure may produce  Measure the wall clear height and 
highly conservative results. the wall thickness excluding plaster 
and renderings, calculate the 
height‐to‐thickness ratio, and 
estimate the applied overburden 
from the dead and live load of the 
diaphragm.

Establish seismic zone, hazard 
factor, and soil type and use one of 
the assessment charts provided as 
appropriate. Interpolate the results 
to account for the correct amount 
of the applied overburden.

 
Figure C11‐1: Procedure for seismic assessment of out‐of‐plane loaded URM walls 

   

  C11‐5
 
  Section C11 ‐ Out‐of‐plane Wall and Parapet Response 
 
 

 
Figure C11‐2: Zonation map for the North Island 

 
Figure C11‐3: Zonation map for the South Island 

C11‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 
Figure C11‐4: Summary of North Island parametric study results (single‐storey 2‐leaf wall ‐ 
Shallow soil) 

C11.6 Worked example 

C11.6.1 Assessment of Walls in a Two‐storey Building in Gisborne 
First‐storey height    6000 mm 
Second‐storey height    4500 mm 
Plan dimension     6000 × 12000 mm 
Live load (both stories)    2 kPa 
Dead load (both stories)   0.35 kPa 
Live load reduction factor  0.3 
Soil type      Deep 
Wall diaphragm connection  Inspections suggests that no structural element with significant 
vertical  stiffness  has  been  used  on  top  of  URM  walls,  but 
grouted steel bars have been used to secure the top wall edge 
to the timber diaphragm 
Diaphragm joist direction  Parallel to shorter building dimension 

  C11‐7
 
  Section C11 ‐ Out‐of‐plane Wall and Parapet Response 
 
 

Diaphragm stiffness  Calculated  from  Section  3.6  as  300 kN/m  parallel  to  joists  and 
3000 kN/m perpendicular to joists 
Diaphragm load transfer  The timber diaphragm loads are transferred to longitudinal walls 
Wall thickness  The wall total thickness is 380 mm in lower storey and 260 mm 
in top‐storey  
Wall finishing  A thin (15 mm) layer of cement plaster on all wall surfaces 

(a) Check if the recommended procedure can be used for this particular buildings: 

Diaphragm  stiffness  parallel  to  joists  is  less  than  500 kN/m,  and  therefore  stiffening  of  the 
timber diaphragm should be undertaken in order for the procedure to be used. The existence of 
steel  anchorage  on  wall  top  edge  is  an  acceptable  condition  that  is  within  the  scope  of  the 
recommended  procedure.  Assuming  that  the  timber  diaphragms  are  stiffened  to  a  level  of  in‐
plane  stiffness  greater  than  500 kN/m  and  that  walls  act  in  a  one‐way  bending  condition,  the 
procedure recommended in this section can be used to evaluate the walls.  

(b) Estimating wall dimensions: 

Wall dimensions may be estimated by use of Table C11‐1  

   
Table C11‐1: Estimated wall dimensions 

Location  Thickness, mm  Height, mm  Slenderness ratio 

Lower‐storey  380 ‐ 2 x 15= 350  6000  17.1 

Top‐storey  260 – 2 x 15= 230  4500  19.6 


 

(c) Estimating overburden: 

Estimation of the overburden is conducted excluding the weight of the top‐storey walls as this 
weight has been previously accounted for in the development of the assessment charts.  

Longitudinal walls: 0.5 x 6 x (0.3 x 2 + 0.35) = 2.85 kN/m 

Short direction walls: 0.0 kN/m 

(d) Seismic zonation and hazard factor (Z): Seismic zone is C and Z = 0.36 

(e) Assessment of lower‐storey walls: 

Assuming  a  slenderness  ratio  of  17.1,  the  following  %NBS.Z  values  are  obtained  from 
Figure 11‐4(b),  and  an  interpolation  of  the  results  is  used  to  determine  the  %NBS.Z  value  for 
lower storey load‐bearing walls. The %NBS.Z value for non‐load‐bearing walls (parallel to short 
dimension of the building) is directly obtained from Figure 11‐4(b). See Table C11‐2. 

   

C11‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Table C11‐2: %NBS.Z for slenderness ratio of 17.1, lower storey 

Wall slenderness  Overburden 
ratio 
Interpolation for 
0.0 kN/mm  3.8 kN/mm 
2.85 kN/mm 

17.1  26.5  35.6  33.33 


 

The %NBS can be calculated for all walls by dividing the %NBS.Z by the hazard factor, thus: 

Lower‐storey longitudinal walls: %NBS = 33.33/0.36 = 92.5% 

Lower‐storey shorter walls: %NBS = 26.5/0.36 = 73.6% 

(f) Assessment of top‐storey wall: 

Repeating the procedure in the previous step but assuming a slenderness ratio of 19.6 and use 
of Figure 11‐3(b), the values presented in Table C11‐3 are obtained.  

 
Table C11‐3: %NBS.Z for slenderness ratio of 19.6, top‐storey 

Wall slenderness  Overburden 
ratio 
Interpolation for 
0.0 kN/mm  3.8 kN/mm 
2.85 kN/mm 

19.6  11.9  19.2  17.38 


 

The %NBS can be calculated for all walls by dividing the %NBS.Z by the hazard factor, thus: 

Top‐storey longitudinal walls: %NBS = 17.38/0.36 = 48.3% 

Top‐storey shorter walls: %NBS = 11.9/0.36 = 33.1% 

C11.6.2 Assessment  of  Free‐standing  Parapets  in  Various  Seismic  Zones  for 
Bending 
Storey height      5000 mm 
Parapet height      450 mm and 1000 mm 
Parapet thickness    230 + 15 mm plaster 
Axial load on top of parapet   Zero (Non load bearing) 
Soil type       Deep 
Cohesion for masonry    25 kPa 
Masonry coefficient of friction   0.6 
DPC membrane     Present at parapet base 
Weight density      18 kN/m3 

  C11‐9
 
  Section C11 ‐ Out‐of‐plane Wall and Parapet Response 
 
 

(a)  Calculating effective slenderness ratio 

 
Table C11‐4: Estimated parapet dimensions 

Parapet  Thickness, mm  Height, mm  Slenderness ratio  Effective slenderness 


ratio 

Short parapets  230  450  1.96  7.8 

Tall parapets  230  1000  4.35  17.4 


 

(b) Assuming slenderness ratios of 7.8 and 17.4 and using Figure 11‐1(b) (Deep soil), the values 
of  %NBS.Z  are  obtained  for  “Elsewhere”.  Table  C11‐5  is  next  formed  to  complete 
assessment for regions without near fault effects. For comparison, the results when using 
the NZSEE (2006) procedure for evaluation of parapets have also been included. 

 
Table C11‐5: Calculating %NBS for regions excluding near fault effect 

%NBS 

Auckland,  Christchurch,  Gisborne, 


Parapet  Method  %NBS.Z  Z=0.13  Z=0.22  Z=0.36 

Short  This guide  25  192  114  69 


parapets 
NZSEE (2006)  N/A  128  75  46 

Tall parapets  This guide  15  115  68  42 

NZSEE (2006)  N/A  119  70  43 


 

(c) Assuming  the  same  slenderness  ratios  and  using  Figure  11‐1(b)  (Deep  soil),  the  values  of 
%NBS.Z are obtained for “Near Fault” regions. 

 
Table C11‐6: Calculating %NBS for regions including near fault effect 

%NBS 

Parapet  %NBS.Z  Wellington, Z=0.40 

Short parapets  17.5  44 

Tall parapets  12.5  31 


 
   

C11‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

(d) Assessment for shear capacity 

Shear demand: 

Using section 6: 

 
Table C11‐7: Calculating shear demand 

Parapet  Parameter  Auckland  Christchurch Gisborne  Wellington 

Short parapets  C(0)  0.15  0.25  0.4  0.467 

Tp  1.231  1.231  1.231  1.231 

Cp(Tp)  0.277  0.467  0.767  0.853 

V0* kN  0.50  0.87  1.43  1.58 

Tall parapets  C(0)  0.146  0.246  0.403  0.448 

Tp  1.677  1.677  1.677  1.677 

Cp(Tp)  0.133  0.226  0.370  0.411 

V0* kN  0.55  0.94  1.53  1.70 


 

Shear capacity: 

0.8  

As DPC has been used at the base of parapet, the coefficient of friction shall be taken as 0.45, 
and the cohesion is 0. Therefore: 

Vn = 0.75*0.23*(0+0.8*18*0.45*h) = 0.1725*(6.48*h) 
 
Table C11‐8: Calculating shear capacity 

%NBS 
Capacity, 
Parapet  kN  Auckland  Christchurch  Gisborne  Wellington 

Short parapets  0.51  102  60  36  31 

Tall parapets  1.1  204  120  75  66 


 

(e) Final  assessment  results  are  governed  by  shear  capacity  for  short  parapets,  and  the 
assessment results of tall parapets are governed by bending capacity.  

   

  C11‐11
 
  Section C11 ‐ Out‐of‐plane Wall and Parapet Response 
 
 

C11.6.3 Assessment of single‐storey and top‐storey one‐leaf walls in Christchurch 
One‐leaf wall properties 

Wall         Single‐storey       Two‐storey 

First‐Storey (wall) height  3500 mm      5000 mm 

Top‐storey height    ‐‐‐        3000 mm 

Wall thickness      115 + 2 x 15 (plaster)     115 + 2 x 15 (plaster) 

Axial load       Zero         Zero 

Soil type       Deep         Deep 

Slenderness  ratio  is  calculated,  and  the  %NBS.Z  value  are  obtained  from  assessment  charts  of 
two‐leaf walls having the same slenderness ratio and in the same storey category: 

 
Table C11‐9: One‐leaf wall assessment 

Wall  Slenderness ratio  %NBS.Z  0.6 * %NBS.Z  %NBS 

Single‐storey  3500/115=30 (ignore plaster  10 (Fig. 11‐1b)  6  27 


thickness) 

Top‐storey  3000/115=26 (ignore plaster  10 (Fig. 11‐3b)  6  27 


thickness) 

C11.6.4 Evaluation of a Cavity Wall 
A  single‐storey  cavity  wall  located  in  Christchurch  is  to  be  evaluated  for  out‐of‐plane  wall 
response. Site investigation shows that the wall leaves are bonded together with steel anchors, 
which have been deteriorated. 

Cavity wall properties 

Property 

Wall height      3500 mm 

Wall thickness      115 x 2 + 50 (gap) 

Axial load       Zero 

Soil type       Deep 

As there are no header courses, and there is almost 100% void ratio in the gap, the walls need to 
be evaluated as single‐leaf walls. %NBS is calculated as that for the previous example, and the 
value is not satisfactory (%NBS=27).  

A  good  approach  to  strengthening  is  to  increase  the  composite  action  between  the  inner  and 
outer  wall  leaves  by  using  new  anchors.  Supplementary  ties  specifically  designed  for  this 
purpose are available from a number of proprietors, and advice on the size and spacing of ties in 

C11‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

order to  ensure full  composite behaviour between the inner and outer leafs of the cavity wall 


should be obtained from the product distributor. The new %NBS is obtained as: 

 
Table C11‐10: One‐leaf wall assessment 

Wall  Slenderness ratio  %NBS.Z  %NBS 

Single‐storey bonded cavity   3500/280=12.5   18 (Fig. 11‐1b)  82 

C11.7 References 
ASCE.  (2007).  Seismic  rehabilitation  of  existing  buildings,  ASCE/SEI  41‐06,  American  Society  of 
Civil Engineers, Reston, Va. 
Derakhshan,  H.,  Ingham,  J.M.,  and  Griffith,  M.C  (2009).  “Out‐of‐Plane  Assessment  of  an 
Unreinforced Masonry Wall: Comparison with NZSEE Recommendations.” Proc. 2009 NZSEE 
Conference, Christchurch, New Zealand, April 3 ‐ 5. 
Derakhshan,  H.  (2011).  "Seismic  assessment  of  out‐of‐plane  loaded  unreinforced  masonry 
walls."  PhD  thesis,  Department  of  Civil  and  Environmental  Engineering,  The  University  of 
Auckland, Auckland, New Zealand. 
Griffith, M. C., Vaculik, J., Lam, N. T. K., Wilson, J., and Lumantarna, E. (2007). “Cyclic testing of 
unreinforced  masonry  walls  in  two‐way  bending.”  Earthquake  Engineering  and  Structural 
Dynamics, 36(6), 801–821. 
NZSEE  (2006).  Assessment  and  improvement  of  the  structural  performance  of  buildings  in 
earthquakes: Recommendations of a NZSEE study group on earthquake risk buildings, New 
Zealand Society for Earthquake Engineering. 
Oyarzo  Vera,  C.  (2011).  “FE‐based  damage  identification  of  unreinforced  masonry  structures.” 
PhD thesis, Department of Civil and Environmental Engineering, The University of Auckland, 
Auckland, New Zealand. 
Oyarzo‐Vera, C., McVerry, G., and Ingham, J. M.  (2011). “Seismic zonation and default suite of 
ground  motion  records  for  time‐history  analysis  in  the  North  Island  of  New  Zealand.” 
Earthquake Spectra, Submitted (081510EQS105M) August 2010. 
Russell,  A.  P.  and  Ingham,  J.  M.  (2010).  "Prevalence  of  New  Zealand's  unreinforced  masonry 
buildings." Bulletin of the New Zealand Society for Earthquake Engineering, 43(3), 192‐207. 
 

  C11‐13
 
  Section C11 ‐ Out‐of‐plane Wall and Parapet Response 
 
 

C11‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C12 ‐ Wall‐diaphragm Anchorages 

C12.1 Notation 
acr i  Minimum of et and sb for row “i”, mm 
CF  calibration factor 
d  fastener diameter, mm 
fc,90y,5th%   5th percentile compression strength 
fc,90y,avg  Average compression strength 
fh,1  Embedding strength corresponding to t1, MPa 
fh,2  Embedding strength corresponding to t2, MPa 
fh,5th%  5th percentile embedding strength 
fh,avg  Average embedding strength 
fv  member shear strength, MPa 
G  relative density of timber for the oven dry condition 
k1  duration of load factor for strength 
k12  factor for the design of bolted connections in green timber 
Kls  factor for member loaded surfaces 
My  fastener yield moment, Nmm 
nfi  number of fasteners in row “i” 
nr  number of rows in the joint as per load component 
RSi min  minimum (RS1, RS2, …, RSnr), N 
RSi  shear capacity along two shear planes of fastener row “i”, N 
t  member thickness, mm 
t1, t2  timber thickness or fastener penetration of member 1 and 2, mm 
  Ratio of the embedding strengths 
  Strength reduction factor 

C12.2 Scope 
It is widely recognised that the single most significant feature responsible for the poor seismic 
performance  of  unreinforced  masonry  buildings  is  the  absence  or  inadequacy  of  connections 
between elements, and primarily the connections between diaphragms and out‐of‐plane loaded 
masonry walls and parapets.  As illustrated in Figure C12‐1, deficient or absent anchorages were 
a  principal  reason  for  the  damage  to  unreinforced  masonry  buildings  during  the  2010  Darfield 
(Canterbury)  earthquake,  along  with  inadequate  restraint  of  parapets.    Currently  a 
comprehensive  study  on  bolt  tear‐out  has  been  completed,  as  reported  in  Section  C12.6.  
However,  insufficient  information  currently  exists  to  make  comprehensive  experimentally‐
validated recommendations on other aspects of connection assessment, and instead guidance in 
the form of observed and probable failure modes is presented in the interim. 

  C12‐1
 
  Section C12 ‐ Wall‐diaphragm Anchorages
 
 

   
(a) Out‐of‐plane wall failure due to  (b) Remains of gable anchorage 
connection failure 

   
(c) No anchorage of diaphragms to wall  (d) Punching shear failure of canopy 
anchorage 

   
(e) Anchorage failure at roof diaphragm  (f) Close up of partial anchorage failure 
connection 

Figure C12‐1: Photographs of damage in the 2010 Darfield (Canterbury) earthquake due to 
deficient or absent diagram anchorages 

C12‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C12.3 Diaphragm Joist Seating 
If anchor plates (also referred to as rosettes) are visible on the exterior of the wall then it is likely 
that some form of mechanical connection exists between the masonry wall and the diaphragm 
joists.    However,  where  no  anchor  plates  are  visible  on  the  exterior  of  the  wall  it  will  be 
necessary  to  establish  whether  anchorages  are  embedded  within  the  wall  (see  for  instance 
Figure C12‐2(a)) or are indeed absent (see for instance Figure C12‐1(c)). 

As  illustrated  in  Figure  C3‐4(f),  it  is  frequently  found  that  there  is  no  mechanical  anchorage 
between  the  diaphragm  and  wall,  and  that  the  diaphragm  is  merely  seated  on  a  ledge  that  is 
developed  by  a  reduction  in  wall  thickness  for  ascending  stories.    An  alternative  seating 
condition is referred to as a ‘joist‐pocket connection’, where the joist in seated on a recess that 
is built into the wall as illustrated in Figure C3‐4(e).  For the purposes of assessment a check may 
be performed regarding the potential for bearing friction to sustain some transfer force between 
the  masonry  wall  and  diaphragm  joist,  but  as  a  general  rule  it  should  be  assumed  that  the 
connection  is  ineffectual  and  that  the  wall  spans  vertically  over  a  greater  height,  including 
potentially acting as a vertical cantilever from the ground.   

The  coefficient  of  static  friction  between  timber  and  masonry  varies  from  0.2  to  0.6,  and  the 
coefficient  of  dynamic  friction  is  between  0.8  and  0.9  times  the  coefficient  of  static  friction 
(Cross and Jones 1993a, Cross and Jones 1993b). The vertical component of the ground motion 
can further reduce the effective friction coefficient.  

Considering  the  above  factors,  it  is  recommended  to  assume  a  lower  bound  of  0.15  and  an 
upper  bound  of  0.45  for  the  effective  coefficient  of  dynamic  friction.  Assuming  an  effective 
coefficient of dynamic friction equal to 0.3 is reasonable. The sum of the weight of floors and the 
reduced  live  load  on  the  floor  should  be  used  when  calculating  the  friction  force  in  the 
connections. 

C12.4 Masonry Anchorage Failures 
Where  anchor  plates  are  visible  on  the  exterior  of  the  wall  there  are  two  failure  modes  that 
should be considered, based upon failure patterns observed in earthquakes.  The first of these 
failure  modes  is  a  punching  type  shear  failure  as  clearly  shown  in  partial  formation  in  Figures 
C12‐1(e) and (f).  Although no laboratory testing has yet been performed to adequately validate 
a prescribed assessment procedure, observations suggest that a mortar failure surface should be 
identified based upon the brick bond pattern and the wall thickness, and that the bed joint shear 
capacity of this failure surface can then be established using the values prescribed in Equation 2‐
5 and Equation 2‐6.  Care should be taken to account for the influence of pointing and etched 
mortar joints due to degradation.  Note also that observations tend to suggest that the failure 
surface can be based upon the notion of a 45° failure cone as commonly assumed for punching 
shear  in  concrete  slabs,  thus  allowing  a  larger  failure  surface  to  be  assumed  than  might 
otherwise be adopted if only considering the geometry of the anchor plate.  It is recommended 
that only cohesion be relied upon for the head joints of the failure surface, and that no effort be 
made to address the fact that in multi‐leaf walls the bond pattern that is visible on the exterior 
of the wall will be offset in other wall leafs. 

  C12‐3
 
  Section C12 ‐ Wall‐diaphragm Anchorages
 
 

Note  that  post‐earthquake  observations  have  shown  that  the  deployment  of  closely  spaced 
anchor  plates,  as  shown  in  Figure  12‐2(b),  can  be  both  structurally  adequate  and  aesthetically 
acceptable,  and  consequently  the  use  of  such  anchor  plates  is  strongly  encouraged  as  an 
improvement technique.  Where such a technique is deployed thought should also be given to 
inspection and probably improvement of the surrounding mortar joints. 

The  second  failure  mode  that  should  be  addressed  when  considering  the  performance  of 
masonry anchorages is the possibility of a flexural failure being initiated along a single bed joint 
at  or  directly  above  where  multiple  anchorages  are  embedded  into  a  single  bed  joint.    This 
failure  mode  is  primarily  associated  with  parapets  and  it  is  recommended  that  parapets 
restraints be provided to address this issue. 

   
(a) Embedded anchorage that partially  (b) Successful anchorages spaced close 
restrained the wall  together 

Figure C12‐2:  Examples of wall‐diaphragm anchorages that were partially or fully successful 
during the 2010 Darfield earthquake 

C12.5 Steel Anchorage Failures 
Observations from the 2010 Darfield earthquake suggest that failure of the steel (or other metal) 
connection linking the diaphragm and masonry wall is less likely than masonry anchorage failure, 
as  illustrated  in  Figure C12‐3(a)  and  Figure C12‐3(b)  where  anchors  have  been  pulled  out  from 
the masonry wall without rupture.  However, failure of the connection due to either bar rupture 
or  timber  tear‐out  was  observed  as  shown  in  Figure C12‐3(c)  and  Figure  C12‐3(d).    Because 
access to the inside of the building was not available, the specific failure mode associated with 
Figure C12‐3(c) and Figure C12‐3(d) was not established. 

Currently  there  is  inadequate  information  regarding  the  material  characteristics  of  the  steels 
used  in  these  anchorage  types,  but  a  simple  check  of  the  expected  axial  stresses  in  these 
connections  should  be  sufficient  to  determine  if  steel  failure  merits  closer  scrutiny.    Particular 
attention should be given to the effective cross‐sectional area should the steel exhibit signs of 
corrosion. 

C12‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

   

(a) Intact anchor – see also Fig. C12‐1(d)  (b) Intact steel anchorage 

   
(c)  Detached anchor  (d)  Detached anchor 

Figure C12‐3: Examples of failed anchorages where steel shows no indication of failure 

C12.6 Timber Anchorage Failures 
This section provides information to assess the capacity of bolted timber connections for existing 
indigenous  New  Zealand  hardwoods  that  were  typically  used  to  construct  the  floor  and  roof 
diaphragms  in  New  Zealand  unreinforced  masonry  buildings.    Representative  details  of  this 
connection type are shown in Figure C12‐4 and Figure C12‐5. 

  C12‐5
 
  Section C12 ‐ Wall‐diaphragm Anchorages
 
 

 
Figure C12‐4: Joist oriented parallel to URM wall 

 
Figure C12‐5: Joist oriented perpendicular to URM wall 

C12.6.1 European Yield Model 
The  European  Yield  Model,  which  considers  ductile  failure  modes  of  bolted  connections,  is 
associated  with  Johansen’s  theory.  This  theory  is  based  on  the  assumption  that  the  materials 
(i.e. timber under embedding stresses and fastener under bending action) behave as rigid‐plastic 
(Blass,  2003).  The  embedding  strength  of  timber,  fh2,  was  determined  experimentally  as 
described in Section C6. For the embedding strength of steel plate, fh1, the value is assumed to 
be  equal  to  C1 b 3.2 fup,  where  C1  is  the  reduction  factor  determination  of  the  design  bearing 
strength  of  the  steel  plate  as  per  Table 12.9.4.3  of  NZS 3404:Part 1:1997,  b  is  the  strength 
reduction factor equal to  0.9 as per Table 3.3(1) of  NZS 3404:Part 1:1997, and fup is the tensile 
strength  of  the  steel  plate.  The  fastener  yield  strength,  fyf,  is  obtained  from  the  grade  of 
fasteners. The first figure from the grade indicates the fastener tensile strength, fuf,. The second 

C12‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

figure  specifies  the  fastener  yield  strength  proportional  to  the  tensile  strength  in  terms  of 
percentage. 

C12.6.2 Row Shear Failure of Timber 
Many  recent  studies  (Quenneville  and  Mohammad  2000;  Mohammad  and  Quenneville  2001; 
Quenneville and Bickerdike 2006; Quenneville et al. 2006; Quenneville 2009) have identified the 
row  shear  failure  of  connections  in  timber  structures.  The  observed  brittle  failure  modes  are 
illustrated  in  Figure 12.6.  An  equation  to  predict  the  ultimate  strength  of  timber  connections 
based  on  the  row  shear  failure  mode  observed  during  tests  was  developed  by  Quenneville 
(Quenneville  and  Mohammad,  2000).  An  optimised  Row  Shear  Model  equation  to  predict  the 
strength of bolted connections for the row shear failure mode when occurring in New Zealand 
hardwood was obtained by using the calibration factor of 4 (Abdul Karim, 2010). 

 
Figure C12‐6: Observed row failure modes for timber connections loaded parallel to grain. 

C12.6.3 Timber Member in Bearing 
Ab is the contact bearing surface area between the timber member and the masonry units, and 
the strength reduction factor, ϕc, of 0.8 can be found in Clause 2.5 of NZS 3603: 1993. 

C12.6.4 Washer Bearing 
Aw,  is  determined  in  Clause 4.4.1.2  of  NZS 3603: 1993,  nw  is  the  number  of  washers,  and  the 
strength reduction factor, ϕc, of 0.8 can be found in Clause 2.5 of NZS 3603: 1993.  

C12.7 Examples 

C12.7.1 Diaphragm joint seating example 
From C6.4.2: 

Vo* = 17.86 kN per metre width of the wall 

  C12‐7
 
  Section C12 ‐ Wall‐diaphragm Anchorages
 
 

Tributary normal force from Dead Load of diaphragm on wall connections: 

N = 1 (kPa) x 4 (half the width of diaphragm) = 4 kN per metre width of the wall 

Tributary normal force from reduced Live Load of diaphragm on wall connections: 

N = 4 (kPa) x 4 (half the width of diaphragm) x 0.3 = 4.8 kN per metre width of the wall 

Coefficient of dynamic friction = 0.3 

Total resisting force due to friction: 

φVn = 0.75 x (4+4.8) x (0.3) = 1.98 kN 

%NBS = 100 x 1.98/17.9 = 11% 

C12.7.2 Masonry anchorage example 
A  2  leaf  masonry  parapet  having  a  height  of  1600 mm  and  a  thickness  of  230 mm  is  located 
above a line of anchorage plates.  The anchor plates have a diameter of 180 mm and are spaced 
at  2.0 m  intervals,  representing  1  anchor  plate  for  every  5  joists.    The  masonry  is  assessed  to 
have  a  density  of  1680 kg/m3.    The  mortar  is  assessed  to  be  of  lower  characteristic  mean 
hardness  (f’j  =  3.2  MPa  from  Table  2‐4).    The  bricks  have  a  length  of  230 mm  and  a  height  of 
90 mm, with a 10 mm mortar joint.  Pointing is measured to be 10 mm on the exterior surface of 
the wall. 

The vertical axial stress at the bed‐joint due to the above parapet is: 

σv* = 1680 x 9.81 x 1.600 / 1000 = 26.4 kPa 

From section 2, C = 0.45 f’j and the dynamic coefficient of friction is 0.8 x 0.65 

Bed joint shear strength   τbj = 0.045 x 3.2 x 1000 + 0.8 x 0.65 x 26.4 = 157.7 kPa 

Head joint shear strength  τhj = 0.045 x 3.2 x 1000 = 144.0 kPa 

 
Figure C12‐7: Assumed failure plain for punching shear failure. 

From Fig. C12‐7 it is established that: 

The horizontal length of the failure plane is 6 bricks @ 240 mm = 1.44 m 

The vertical length of the failure plane is 8 bricks @ 100 mm = 0.80 m 

C12‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Accounting for pointing the assessed strength of the joint is: 

φVn = 0.75 x 0.22 x (1.44 x 157.7 + 0.80 x 144.0) = 56.5 kN 

Assuming joist demand as for the previous example and neglecting ledge friction capacity: 

%NBS = 100 x 56.5/(2 x 17.9) = 158% 

Including the capacity of the 4 joists supported by ledge friction: 

%NBS = 100 x (56.5 + 2 x 1.98)/(2 x 17.9) = 169% 

C12.8 References 
Abdul Karim, A. R. (2010). "Seismic Assessment of Wall‐Diaphragm Connections in New Zealand 
URM  Buildings."  PhD  thesis,  Department  of  Civil  and  Environmental  Engineering,  The 
University of Auckland, Auckland, New Zealand. 

Australian/New  Zealand  Standard  (2000).  AS/NZS  1080.3:  2000  Timber  ‐  Methods  of  Test  ‐ 
Method 3: Density. Standards New Zealand (electronic copy). 

Australian/New Zealand Standard (2007). AS/NZS 4063.1: 2007 Structural timber ‐ Characteristic 
values of strength‐graded timber ‐ Part 1: Test methods. Standards Australia (draft only). 

Blass, H. J. (2003). "Joints with Dowel‐type Fasteners." Timber Engineering, S. Thelandersson and 
H. J. Larsen, eds., John Wiley & Sons Ltd., England, 315‐331. 

Cross,  B.  W.,  and  Jones,  N.  P.  (1993a).  "Seismic  performance  of  joist‐pocket  connections.  I: 
Modelling", Journal of Structural Engineering, 119(10), 2976‐3007. 

Cross,  B.  W.,  and  Jones,  N.  P.  (1993b).  "Seismic  performance  of  joist‐pocket  connections.  II: 
Application", Journal of Structural Engineering, 119(10), October, 1993, 3008‐3023. 

International  Organization  for  Standardization  (2008).  Draft  International  Standard 


ISO/DIS 10984‐2  Timber  structures  ‐  Dowel‐type  fasteners  ‐  Part  2:  Determination  of 
embedding strength and foundation values. International Organization for Standardization, 
Geneva, Switzerland. 

Mohammad,  M.,  and  Quenneville,  J.  H.  P.  (2001).  "Bolted  Wood‐Steel  and  Wood‐Steel‐Wood 
Connections: Verification of a New Design Approach." Canadian Journal of Civil Engineering, 
28(2), 254‐263. 

Quenneville, J. H. P., and Mohammad, M. (2000). "On the Failure Modes and Strength of Steel‐
Wood‐Steel Bolted Timber Connections Loaded Parallel‐To‐Grain." Canadian Journal of Civil 
Engineering, 27(4), 761‐773. 

Quenneville, J. H. P., Smith, I., Aziz, A., Snow, M., and Ing, H. C. (2006). "Generalised Canadian 
Approach for Design of Connections with Dowel Fasteners." CIB‐W18 meeting Proceedings, 
Florence, Italy, paper CIB‐W18/39‐7‐6. 

Quenneville, P. (2009). "Design of Bolted Connections: A Comparison of a Proposal and Various 
Existing Standards." Journal of the Structural Engineering Society (SESOC) New Zealand Inc., 
22(2), 57‐62. 

  C12‐9
 
  Section C12 ‐ Wall‐diaphragm Anchorages
 
 

Quenneville,  P.,  and  Bickerdike,  M.  (2006).  "Effective  In‐Row  Capacity  of  Multiple‐Fastener 
Connections." CIB‐W18 meeting Proceedings, Florence, Italy, paper CIB‐W18/39‐7‐1. 

Standards  New  Zealand  (1993).  NZS  3603:  1993  Timber  Structures  Standard.  Standards  New 
Zealand, Wellington, New Zealand. 

Standards New Zealand (1997). NZS 3404: Part 1: 1997 Steel Structures Standard. Standards New 
Zealand, Wellington, New Zealand. 

C12‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C13 ‐ Heritage Characteristics of URM Buildings 
and the Impacts of Seismic Improvements 

C13.1 Introduction 
A heritage building is more than simply a collection of building materials. As buildings age, they 
become  more  permanent  parts  of  local  culture.  They  become  associated  with  notable  people; 
with  the  memories  of  the  public;  and  places  where  important  historic  events  occurred.  They 
become unique, as buildings are simply no longer made the same way, and time provides them 
with characteristics that could never be designed into a new building, such as the patina of age – 
how a building looks old. Old buildings can become ‘heritage’, where they become important to 
the public rather than just to the owner and occupants; a recent example of this is the birdcage 
hotel in Figure C13‐1. There is no line on one side of which lies ‘heritage’, and on the other ‘not 
heritage’;  all  old  buildings  will  have  some  heritage  value.  The  difficulty  is  in  determining  the 
degree of heritage value, and what is important and what is less important about a building. 

New Zealand’s URM historic buildings form a rapidly diminishing aspect of the nation’s collective 
heritage,  which  is  a  physical  link  to  the  past  and  provides  valuable  evidence  of  cultural 
progression.  There is a real danger that if insufficient consideration is given to the historic and 
architectural qualities of these buildings, seismic retrofit interventions may cause visual damage 
or remove important historic material.  Indeed, this has already occurred many times in recent 
history  (see  Christianson  1983,  Evans  1983,  Leuchars  1989,  Taylor  1983,  Toomath  1979  for 
example).  Some of these retrofits, while possibly resulting in safer buildings, have had an overall 
detrimental effect on the buildings themselves.  

The historic value of the surviving URM building stock is slowly becoming recognised (Trapeznik 
2000)  and  some  buildings  have  been  protected  from  alteration  by  heritage  legislation  and 
organisations.    The  Historic  Places  Trust  (HPT)  is  required  by  the  Historic  Places  Act  1993  to 
maintain  a  register  of  recognised  heritage  buildings,  and  acts  in  the  interests  of  their 
conservation when any significant alteration is proposed. (NZ Historic Places Act 1993)  However 
the  HPT  has  limited  resources,  so  only  the  most  historically  and  architecturally  significant 
buildings tend to be protected.   Many other URM  buildings also have significant historic  value 
and contribute greatly to the character of towns and cities, but are offered no protection from 
demolition or significant alteration.  

As  highlighted  by  the  2010  Darfield  earthquake,  many  older  buildings,  particularly  those 
constructed  from  unreinforced  masonry,  now  require  seismic  improvement  in  order  to 
withstand  earthquake  forces.  There  are  many  approaches  and  techniques  to  seismic 
improvement,  the  most  common  of  which  are  outlined  below  and  analysed  in  terms  of  the 
impact of each on the heritage and architectural value of the building.  

  C13‐1
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

 
Figure C13‐1: The Birdcage hotel prior to seismic improvement and being moved 

Once it has been accepted that seismic improvement of a building is required, it is necessary to 
determine the extent of required intervention and the appropriate methods for that particular 
building.  Generally,  an  analysis  is  undertaken  in  stages,  beginning  with  assessing  the 
architectural  character  of  the  building,  then  addressing  the  basic  known  inadequacies  of  URM 
construction (Russell & Ingham 2010), then determining what types, if any, of additional retrofit 
systems are required. Additional requirements should be met by structural elements which are 
sensitively designed and in keeping with the architectural character of the building, of the least 
extent,  and  reversible  if  possible  (Goodwin  et  al.  2009).  Often,  several  or  many  different 
techniques will be used within one building, and it is vital to have an appreciation of how each 
technique will impact upon the architectural and historic aspects of the building, and the ways in 
which these impacts can be minimised.  

C13.2 Heritage and Conservation 
In  New  Zealand,  acts  which  seek  to  prolong  the  useful  life  of  a  building  while  respecting  its 
history and originality are known collectively as conservation, and seismic retrofitting falls, or by 
virtue of its conservation goals should fall, under this category.  A successful act of conservation 
will ensure that a heritage building is treated with care in order to preserve its historic fabric and 
aesthetics  to  the  greatest  extent  possible.    New  Zealand  has  its  own  particular  history  of 
development  of  heritage  principles,  and  its  own  set  of  unique  problems  in  conservation.    This 
history  and  the  present  day  environment  resulting  from  these  particular  issues  have  been 
amalgamated  with  broader  international  principles  and  adapted  specifically  for  use  with  New 
Zealand buildings in a document produced by the International Council on Monuments and Sites 
(ICOMOS)  New  Zealand  Charter  for  the  Conservation  of  Places  of  Cultural  Heritage  Value 
(ICOMOS  2010).    This  Charter  forms  the  current  foundation  of  heritage  conservation  in  New 
Zealand. 

Seismic improvement of unreinforced masonry (URM) buildings is likely to require invasive work 
and additional structure which could fundamentally change the character of a building.  Before 
engaging  in  any  such  work,  it  is  important  to  understand  the  underlying  principles  of  good 
conservation practice in order to ensure that buildings and sites are sensitively treated and their 

C13‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

future  integrity  can  be  assured.    It  is  also  important  to  understand  that  there  is  more  to  a 
building than simply its physical material.  This intangible component is comprised of concepts 
such  as  its  history  and  social  use,  and  spiritual  significance  of  the  place,  which  are  essentially 
what the building means to an observer or group at a point in time.  When combined with the 
physical elements, these associations are collectively known as its heritage value (Aplin 2002). 

C13.2.1 Heritage  
Heritage  as  a  concept  is  the  collection  of  things  which  relates  people  to  who  they  are,  where 
they have come from, and why they are the way they are.  The cultural aspects of heritage relate 
to human activity, namely; historical, archaeological, architectural, aesthetic, scientific, spiritual, 
social,  traditional,  or  some  other  special  cultural  significance  (ICOMOS  2010).    These  aspects 
represent the ideals of  people and  help  to define  who they think  they are,  so heritage  can be 
said to be a collection of items which represent individual and group histories (Aplin 2002).  This 
knowledge  is  important  in  order  to  gain  an  appreciation  of  sense  of  place  and  culture,  and 
enables  people  to  better  understand  the  greater  physical  and  cultural  environments  in  which 
they live.  Heritage can also be a useful way of defining identity, as well as serving as a cultural 
record, and implies a gift for future generations and for the benefit of communities, in terms of 
both physical and cultural inheritance.  Heritage can be said to be a mark left by a bygone era 
which one can identify with, respect, and which can help people to understand their history.  

The influence of cultural heritage is great; it links people to the past, and gives them a sense of 
place  and  progression.    However,  its  influence  is  also  subtle  and  intangible,  and  has  often  not 
been  given  the  recognition  which  it  deserves.    There  have  been  a  great  many  theories  on  the 
treatment  and  protection  of  cultural  heritage,  particularly  buildings  and  artworks,  throughout 
history.    Some  of  these  have  been  considerate  and  respectful,  and  others  destructive  and 
oblivious.  An  example  of  the  type  of  strengthening  thought  typical  of  the  late  1970’s  can  be 
found  in  Smith  (1983).  Debates  on  the  importance  of  cultural  heritage  and  its  deserved 
treatment continue to this day.  

C13.2.2 Conservation 
Everything which is made has a relationship to the past, as something has always come before 
which has informed it or set a precedent.  As time passes, buildings of a certain type or character 
become  increasingly  rare,  and  as  such  their  social  value  for  heritage  or  scientific  purposes 
increases.    The  ICOMOS  New  Zealand  Charter  explains  that  the  purpose  of  conservation  is  to 
‘…care  for  places  of  cultural  heritage  value,  their  structures,  materials  and  cultural  meaning 
(ICOMOS 2010).’  In general, such places: 

(a) have lasting values and can be appreciated in their own right, 

(b) inform us about the past and the culture of those who came before us, 

(c) provide tangible evidence of the continuity between past, present and future, 

(d) underpin and reinforce community identity and relationships to ancestors and the land; and 

  C13‐3
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

(e) provide  a  measure  against  which  the  achievements  of  the  present  can  be  compared 
(ICOMOS 2010). 

Conservation encompasses all acts which prolong the life of cultural and natural heritage with a 
view  to  ensuring  that  it  is  able  to  be  appreciated  by  future  generations,  and  maintained  in  a 
state  in  which  it  can  continue  to  communicate  heritage  value.    For  a  building,  conservation 
ought to preserve (and potentially enhance) the historic narrative, allow it to have a continuing 
useful life, and retain its value for its owner and the community into the future (Holman 2000).  
Thus  it  becomes  important  to  evaluate  the  building  or  site  in  order  to  discover  just  what  its 
heritage value is, and consider taking action to conserve it if required.  There are several main 
factors which contribute to overall heritage value, all of which relate in some way or another to 
the relative rarity or uniqueness.  Bowron and Harris (1994) defined these values below: 

 Social:  The  notion  of  a  spiritual,  traditional,  political,  national,  or  any  other  cultural 
sentiment expressed by a group. 

 Aesthetic: Considers the formal qualities of the fabric and setting; the form, scale, materials, 
space etc.  It addresses the design and cultural aspects of the place.  

 Scientific: Is concerned with the importance of the place as evidence and with the physical 
survival  of  that  evidence  in  the  fabric.    Scientific  value  is  the  potential  to  provide 
information  about  past  human  activity.    This  may  encompass  technology,  archaeology, 
philosophy, custom, taste and usage as well as technique or material. 

 Historic:  Is  the  ability  to  demonstrate  an  association  with  persons,  ideas,  or  events.    It 
includes the history of all the above concepts (Bowron & Harris 1994). 

These  values  apply  to  parts  of  sites  and  buildings  as  well  as  to  the  whole,  so  a  particularly 
beautiful historic staircase will have strong heritage value, which will add to the site as a whole; 
even if the building which contains the staircase is of comparatively low value.   

The NZ Charter outlines conservation principles which meet the unique cultural requirements of 
New Zealand and suit its particular stock of historic sites (ICOMOS 2010).  To date this is the best 
and  most  comprehensive  document  relating  to  conservation  principles  in  New  Zealand  and 
should be considered as the basis for all conservation work while it remains so.  It is important to 
note  however,  that  the  NZ  Charter  is  a  series  of  guidelines  rather  than  mandates;  almost  all 
heritage projects  will require some degree of compromise in order to arrive  at a  practical and 
practicable solution. 

All conservation projects should have their cultural heritage value identified and defined in order 
to  establish  which  aspects  are  most  important.    On  larger  scale  projects,  this  indentification  is 
usually contained within a Conservation Plan, which is a document authored by a conservation 
professional  which  serves  to  also  suggest  strategies  for  protecting  these  important  elements, 
and for managing potential problems.  There are a number of general principles which guide the 
approach  to  conservation,  outlining  the  responsibilities  of  the  conservator  when  planning 
conservation  work;  in  essence  describing  the  desirable  traits  of  an  act  of  conservation.    The 
outcome of a conservation project should be consistent with the cultural content of the place.  
Thus,  relevant  influence  and  cultural  factors  shall  be  considered  in  the  planning  stage  and  the 

C13‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

scope  and  scale  of  the  result  should  not  be  greatly  removed  from  the  scope  and  scale  of  the 
original structure.  Conservation should: 

 Make use of all relevant conservation values, knowledge, disciplines, arts and crafts; 

 Show  the  greatest  respect  for,  and  involve  the  least  possible  loss  of,  material  of  cultural 
heritage value; 

 Involve the least degree of intervention consistent with long term care and the principles of 
this charter; 

 Take into account the needs, abilities, and resources of the particular communities; and 

 Be fully documented and recorded (ICOMOS 2010). 

In  addition  to  these  principles,  the  conservator  ought  to  respect  a  building’s  alterations  and 
additions  as  they  are  part  of  the  ongoing  history  of  the  building,  and  should  only  be  removed 
where  they  significantly  inhibit  its  heritage  value  or  meaning.    This  respect  for  a  building’s 
history also extends to evidence of age; it is desirable for an old building to look old, and as such 
the  marks  of  age  should  be  considered  as  integral  with  the  fabric  of  the  building.    Sometimes 
alterations will detract from the heritage value of a place, but this cannot be said categorically 
and investigation should always be done.    Similarly,  the contents  and setting of a building  will 
often take on heritage value of their own and as such need to be considered as integral with the 
building  for  purposes  of  conservation  (ICOMOS  2010).    Risks  from  natural  processes  or  events 
need  to  be  assessed,  and  plans  formulated  for  their  mitigation  (ICOMOS  2010).    These  plans 
might  range  from  ground  subsidence  to  fungal  attack  to  earthquake,  all  of  which  can  have 
damaging effects on historic buildings.  This latter aspect is particularly pertinent to this section, 
which  aims  to  minimise  the  adverse  effects  of  earthquake  strengthening  work  upon  heritage 
buildings.  

All  new  work  on  an  historic  site  should  be  distinguished  as  being  new  work.    This 
recommendation ensures that future generations examining the building will have no difficulty 
determining which parts of a building are original and which are later additions or changes.  The 
materials and style of alterations ought to be significantly different in order to best express their 
separation in time.  This work also should be reversible to allow for imperfect solutions (Price et 
al. 1996).  The ideal solution will almost never be arrived at, either due to lack of technology or  
due  to  funding.    If  at  some  time  in  the  future  this  solution  is  possible,  it  ought  not  to  be 
prejudiced by a previous solution.  

The reality of conservation is that experts are only consulted some of the time; public bodies and 
some developers will commission conservation plans, but many projects go ahead without the 
benefit  of  these.    While  New  Zealand  possesses  a  series  of  principles  in  the  ‘New  Zealand 
Charter’ that are well‐founded in established international theory, the sympathetic treatment of 
heritage is still not guaranteed by legislation or by popular opinion.  Many property owners and 
developers are either ignorant of these principles or choose to ignore them, and until they are 
universally  adopted  there  will  continue  to  be  demolition  and  destruction  of  valuable  cultural 
heritage.  Current legislation is inadequate to fully protect heritage buildings or ensure that all 
changes are undertaken in the spirit of the Charter.  

  C13‐5
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

C13.2.3 Historical Approaches  
Advances in seismic engineering in New Zealand between about 1960 and 2000 have tended to 
focus  primarily  on  maximising  life  preservation  and  minimising  costs  (Cattanach  et  al.  2008).  
This neglect of the building itself has led to a mindset where the building is often considered to 
be a liability, where interventions have therefore been undertaken without consideration of the 
architectural impacts of the improvement measures, or preservation of the building fabric after 
the  event  of  an  earthquake  (Cattanach  et  al.  2008).    Rather  than  working  with  the  materials 
which are present, designers have found it easier to add a modern structure around the original 
building,  often  with  inadequate  consideration  of  composite  action  or  stiffness  compatibility 
(Cattanach et al. 2008).  A scarcity of any real guidance on the analysis and treatment of historic 
URM buildings may well have contributed to this evolution.  

A  number  of  seismic  retrofits  were  documented  during  the  1980s  which  tended  to  largely 
prescribe  coating  the  inside  of  the  walls  with  sprayed  concrete  to  form  shear  walls,  and 
upgrading diaphragms, which, while effective in increasing strength, permanently covered much 
historical  evidence  on  the  inside  of  the  building  and  changed  internal  surfaces  and  room 
volumes.    Some  of  the  less  sympathetic  retrofits  advocated  removal  of  ‘inconvenient’  historic 
fabric  as  a  matter  of  course,  altered  interiors  so  as  to  make  them  unrecognisable,  and  were 
almost  completely  irreversible.    Some  retrofits  also  resulted  in  changes  to  the  technical 
performance  of  a  building,  in  some  cases  rendering  them  uninhabitable.    This  approach  has 
created  numerous  problems,  as  the  heritage  value  of  some  of  these  buildings  has  now  been 
recognised  and  steps  are  being  taken  to  restore  them  to  some  semblance  of  their  former 
aesthetic and function, but the retrofit alterations hinder every step of this process. The Napier 
School  of  Music  (Figure  C13‐2)  is  an  example  of  this  problem;  a  retrofit  removed  most  of  ithe 
building’s  exterior  decorative  character  defining  elements,  which  transformed  a  remarkable 
building  into  an  unremarkable  one.    Work  has  been  done  to  attempt  to  return  the  building 
closer to its original form, but the historic material is irrecoverable (Robinson & Bowman 2000). 
Similarly,  the  conversion  of  the  Cranmer  Square  Normal  School  in  Christchurch  (Figure  C13‐3) 
into luxury apartments involved almost total loss of interior  character and of the relationships 
between  interior  spaces,  as  the  interior  surfaces  were  covered  or  replaced,  and  much  of  the 
historic material was removed. 

   

C13‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 
Figure C13‐2: Napier School of Music before and after retrofit. (reproduced from Robinson 
and Bowman 2000) 

 
Figure C13‐3: Before and after cross sections through Cranmer Square Normal School, 
Christchurch (reproduced from Wilby, 1983). Showing changed interior layouts and surfaces 
and removed a large amount of the historic material 

C13.3 Architectural Character  
Every  building  is  unique  and  possesses  many  attributes  that  help  to  define  it  as  being  distinct 
from  all  others,  which  are  collectively  known  as  its  character.    Architectural  character  is  the 
physical  presence  which  gives  a  building  this  distinguished  quality  and  is  defined  by  the 
building’s overall shape (architectural form), its materials and methods of construction, the size 
and  arrangement  of  openings  and  projections,  the  interior  spaces  and  relationships  between 
these,  and  the  setting  and  surroundings  of  the  building  (Nelson  1988).    In  an  old  building, 
preservation of architectural character is particularly important, as its character differentiates it 
from modern buildings.   

  C13‐7
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

There  are  also  many  facets  to  physical  understanding,  beginning  with  the  overall  definition  of 
the  building  style,  material  and  type.  The  building  may  typify  a  period  of  construction,  which 
usually  relates  to  an  architectural  style,  or  exemplify  construction  in  a  certain  material,  or 
represent a  particular type of building  (Nelson 1988).   Style and  archetype will not  necessarily 
affect  the  specific  treatment  of  a  building,  but  will  provide  background  information  as  to  its 
degree of importance and aesthetic qualities.  Once these characteristics have been established, 
further  distinction  can  be  imparted  by  examining  the  architectural  form,  site,  construction 
technique, material use and craftsmanship, evidence of age, furnishings, and decorations.  

It  is  recognised  that  in  many  cases,  time  and  resources  will  not  allow  for  an  extensive 
investigation of architectural and historic significance (Trapeznik 2000).  The technique outlined 
below  considers  only  the  physical  and  tangible  attributes  of  a  building;  the  parts  that  can  be 
seen  and  appraised,  and  constitutes  a  basic  level  of  analysis,  but  it  is  simple  and  is  able  to  be 
performed relatively quickly. This technique is borrowed from the United States Department of 
the  Interior  Preservation  Brief  17  (Nelson  1988)  on  Architectural  Character.  The  methodology 
used is largely the same here, although the examples specifically  reference New Zealand URM 
buildings and retrofits. See http://www.nps.gov/history/HPS/TPS/briefs/brief17.htm for further 
reading. In some cases, where a building is architecturally unremarkable and is of little historical 
interest, this  will be an adequate investigation; however it is  emphasised  that all old buildings 
will possess some degree of historical significance, and unless research is done, the extent of this 
significance  may  not  be  properly  identified.    Recognition  of  character  is  an  imprecise  practice, 
and as such there will always be some debate as to what constitutes an important element. 

C13.3.1 Overall Visual Aspects 
The first step when analysing architectural character is to view the building from a distance, and 
walk  around  it  if  possible  to  view  it  from  each  side  to  ascertain  its  dominant  features.    Some 
sides  will  be  more  important  than  others,  but  this  is  not  to  say  that  rear  walls  have  no  value; 
merely  that  they  contribute  less  to  the  overall  character  than  a  decorative  street  façade.    The 
purpose of this exercise is to identify the elements that make up the architectural form, which is 
essentially  the  combination  of  shape,  size,  colour,  texture,  and  organisation,  that  makes  the 
building identifiable as this particular building.  

The overall visual picture is established by considering the main features of the exterior of the 
building without concentrating too much on details; most of these will be immediately and easily 
recognisable.  The primary form is defined by  the outline of  the  walls and roof, as well as any 
projections  such  as  balconies,  porches,  or  chimneys,  or  where  buildings  are  touching,  by  the 
edge of the change in material or style.  The purpose of this exercise is to consider the geometric 
form of the building as if it were composed of simple blocks (Figure C13‐4). 

C13‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Figure C13‐4: Primary form of a URM building in Auckland. At this stage the basic shape and 
the broad gestures that make up the building are noted. In this case the building has a 
reasonably simple form and displays a typical 3 part vertical hierarchy 

Next  the  elevations  should  be  checked  for  elements  that  define  their  makeup;  openings  are 
important in this regard.  The locations of the primary openings should be noted, along with the 
location  and  nature  of  the  main  entrance,  the  pattern  and  rhythm  of  windows,  and  whether 
these are regular or random, deep or surface set, or have any other distinctive features.  URM 
buildings often have a series of piers with windows between which can form a defining pattern 
(Figure C13‐5).  Projections and recesses should also be noted, particularly further balconies and 
porches,  arcades,  and  any  dominant  decorative  features.    The  depth  and  articulation  of  the 
facades, in particular of elements such as piers, cornices, and windows, and the ways in which 
these elements are layered and relate to each other is an important contributor to the primary 
form.  In essence, it is important that the facades are considered in three dimensions.  

  C13‐9
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

 
 
Figure C13‐5: A study of the building’s openings in two dimensions. This has been done 
firstly as the physical openings in the URM, and secondly as the forms surrounding the 
openings. Interfering with these patterns will change the way that the building reads; 
something as simple as changing the colour of the window frames will bring these forward 
and make the openings smaller and less distinct 

The  roof  can  form  a  particularly  important  element,  although  this  is  less  common  in  URM 
buildings.    A  visible  roof  with  gables,  dormers,  chimneys,  or  an  interesting  surface  material  or 
pattern will be a strong feature for defining character (Figure C13‐6).  More commonly with URM 
buildings, the parapets will obscure a  plain roof behind.   The shape of  the parapets should be 
noted,  and  their  interesting  features  examined  (Figure  C13‐7).    Attention  should  be  paid  to 
materials  and  colours,  particularly  in  the  case  of  URM,  as  even  subtle  deviations  from  the 
original  materials  can  stand  out  starkly  on  an  otherwise  uniform  surface.    Similarly,  any 
ornamentation on the surface or surface features should be conserved wherever possible.  

   

C13‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Figure C13‐6: Shed 13 on the Wellington  Figure C13‐7: A parapet that is integral 
waterfront features a distinctive roof that is  with the design of the rest of the facade 
integral with its character  and which contributes historic information 

The  setting  of  the  building  influences  how  the  building  is  read,  and  therefore  affects  its 
character.    A  building  in  a  garden  setting  is  somewhat  integral  to  that  garden,  and  likewise  a 
building within a row of similar buildings is integral to that row.  Drastically altering the setting in 
which  the  building  has  come  to  be  known  will  affect  the  character  of  that  building  (Figure 
C13‐8).  

 
Figure C13‐8: The Auckland Ferry Building is integral with its waterfront setting and altering 
this relationship would remove historic meaning 

Identifying  the  important  primary  elements  that  make  up  the  exterior  of  the  building  will 
provide  guidance  regarding  suitable  retrofit  techniques.    A  building  with  an  exposed  character 
brick  exterior  will  generally  be  unsuitable  for  strengthening  techniques  involving  exterior 
diaphragms or shear walls.  The size and spacing of primary vertical and horizontal elements will 
inform the layout of  potential  moment frame or  bracing frame  solutions.   Historically, façades 
have  been  considered  the  most  important  aspect  of  a  building.    Unfortunately,  this  belief  has 

  C13‐11
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

given rise to some particularly destructive treatments of buildings where the façade is preserved 
and  integrated  into  a  new  modern  building  directly  behind.    While  marginally  better  than 
complete  demolition,  this  practice  destroys  all  but  a  caricature  of  the  original  building  and 
should be avoided.  While the façades are important, the rest of the building is equally so; it is 
the  interior  that  provides  character  for  the  occupants,  and  the  arrangement  and  volumes  of 
spaces that governs the experience that the building provides. 

C13.3.2 Close‐Up Character  
Once an inspection from afar has been completed, an inspection should be made at arm’s length 
(where  possible)  in  order  to  appreciate  how  the  building  has  been  constructed,  and  the 
particular  characteristics  that  help  to  define  its  surface  and  details.    The  finer  details  of  the 
colour of the materials should be noted; in the case of URM, the colour of the brick and mortar 
will  hint  as  to  its  composition  and  origin,  and  the  bond  type  will  form  a  surface  pattern.    The 
shape of the bricks and striking of mortar may also be distinctive and character defining (Figure 
C13‐9).  Weathering, alterations and demolition, and changes of size or demolition of adjoining 
buildings  will  all  leave  distinctive  marks  that  indicate  age.    Attention  should  be  given  to  the 
craftsmanship  and  craft  details  that  have  been  employed.    In  some  cases  materials  may  have 
been employed in interesting ways that give the building an individual character, or some other 
small  detail  may  make  a  significant  impact  to  the  way  the  overall  building  is  read  and 
understood.  

This process will likely have less impact on the types of seismic retrofit techniques that may be 
used than when assessing the overall aspects, but will provide information on the construction 
of  the  building.    Some  façades  that  look  undistinguished  from  afar  may  contribute  more  to 
character or have more significance than previously thought. 

 
Figure C13‐9: Details of openings. Things to take note of here are the bond pattern and 
technique used for laying bricks, colouring, striking of mortar, changes in surface, recesses 
and depressions, and proportions of windows and other components 

C13‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C13.3.3 Interior Spaces 
Defining  the  distinctive  character  of  internal  spaces  can  be  far  more  challenging  than  for  the 
building exterior.  This exercise can also be done on two scales, as for the exterior assessment, 
except  that  enclosed  spaces  are  three  dimensional  volumes  as  well  as  a  series  of  surfaces.  
Sometimes the spaces themselves or the relationships between several spaces are important to 
the  character  and  nature  of  the  building;  inspections  of  interior  spaces  should  be  carried  out 
progressively by appraising each space in its entirety before moving to the next.  

The first step is to identify primary spaces.  These are essentially the spaces that are important 
to the function or feel of the building.  In many buildings the primary space will be the first space 
you enter from the street; a lobby or circulation space is often designed with special treatment 
as  it  provides  the  first  impression  of  the  building.    Such  spaces  should  be  analysed  and  their 
proportions,  shape,  ceiling  height,  and  massing  of  elements  recorded,  as  well  as  any  large 
features  such  as  stairways  or  columns  that  help  define  them.    There  will  often  be  a  series  of 
interrelated  spaces  that  also  help  to  define  the  character  and  function  of  the  interior  of  the 
building.  Such spaces might include an atrium that connects to one or more circulation spaces, 
or prominent stairways that in turn connect to a mezzanine.  All of these spaces are individually 
defined in their own right, but the visual relationship between them is important to the extent 
that  to  significantly  alter  one  of  these  spaces  would  affect  the  others  (Figure  C13‐10).  
Sequentially important spaces will often involve a primary circulation route, although this is not 
always the case.  Another way in which spaces can be related is through their relationship with 
the function or type of the building.  For example in a church there is often a long, tall nave that 
is  flanked  by  two  shorter  aisles  that  are  separated  from  the  nave  only  by  a  row  of  columns.  
These columns are a sufficient barrier to signify the boundary between two distinct but related 
spaces.    If  the  spaces  between  the  columns  were  filled  in,  or  extra  columns  added,  this 
modification would not only fundamentally alter the spatial feel of the building, but also affect 
the ability of the building to be read as a church.  

  C13‐13
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

   
Figure C13‐10: Arcades in Auckland with complex spatial relationships where blocking lines 
of sight between spaces or impeding established pedestrian routes will have significant 
negative effects 

Once  spaces  have  been  considered,  interior  surfaces  and  features  need  to  be  appraised.    This 
process is similar to that undertaken on the exterior.  Important interior features are original or 
historic elements that add to the feel of the space; these elements might include fireplaces and 
their mantelpieces, decorative ceilings, mouldings, or panelling, lighting fixtures, elevator doors, 
and  open  stairways.    Many  buildings  will  possess  all  of  these  features  in  some  form;  to 
determine their importance, consider whether the space would have the same historic qualities 
if they were removed.   

Many heritage buildings, industrial buildings and warehouses in particular, are likely to feature 
open  plans  with  extensive  exposed  structure.    In  these  cases,  the  exposed  structure  forms  an 
integral part of the industrial nature of the building and therefore contributes to defining of its 
character.    Exposed  brick  load  bearing  walls,  cast  iron  or  steel  columns,  timber  or  steel  roof 
trusses,  posts  and  beams,  and  stone  foundation  walls  were  all  designed  to  be  seen  and 
expressed as part of the nature of the building and it is important to the architectural character 
that they remain so.  

C13.3.4 Other Considerations  
The character of the place as it exists is formed by the visible material in the present; however 
each historic building will have a long history, often involving renovations and alterations, wear 
and  tear,  disaster damage, or removal of some features.   For  these reasons,  it is important to 
attempt to gain a historical knowledge of the building as well as knowledge of its present state.  
This  knowledge  will  help  to  further  understand  the  character  of  the  building,  and  help  inform 

C13‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

the  design  of  retrofit  solutions.    The  developmental  sequence  of  the  place  can  be  important; 
there are a series of events in the development of any building that will affect its current state.  
In  the  late  1970s  and  early  1980s,  a  number  of  New  Zealand  buildings  had  character‐defining 
towers and parapets removed in response to fears about their seismic safety, rather than being 
strengthened by retrofit (Smith 1979).  These elements could possibly be reinstated if they still 
exist, or allusions made to their existence in subsequent treatments.  

The functions of the building or parts of the building can influence treatment, even when these 
have little physical manifestation within the building itself.   An  example of  this is  the series of 
buildings that are now known as Victoria Park Market in Auckland City.  This complex began life 
as a waste incinerator and refuse collection depot, but fell into disuse and was converted into a 
marketplace  in  the  1980s  (Jones,  2008).    Even  though  the  buildings  retain  much  of  their 
industrial  character  and  possess  little  to  distinguish  them  as  markets,  they  are  now  known 
collectively  as  Victoria  Park  Market,  and  it  is  impossible  to  separate  this  new  use  from  the 
original  industrial  use  of  the  buildings  in  their  history.    Any  proposed  development  or  retrofit 
would need to consider the full history of the buildings, paying heed to both their marketplace 
and industrial uses. 

C13.4 Initial Considerations for Seismic Improvement 

C13.4.1 Requirements 
Territorial  Authorities  require  most  buildings  with  strength  of  less  than  33%  of  current 
requirements  to  be  upgraded  under  The  Building  Act  2004.  It  is  recommended  that  building 
performance  be  improved  to  at  least  67%  of  current  code  requirement  in  NZS 1170.5:2004 
(NZSEE  2006).  Buildings  between  33%  and  67%  are  considered  to  be  earthquake  risks  and 
retrofit  should  be  seriously  considered.  Buildings  over  67%  are  generally  considered  to  be 
satisfactory,  although  are  still  up  to  5  times  more  likely  to  suffer  significant  damage  in  an 
earthquake  than  a  building  meeting  NZS 1170.5  requirements  (NZSEE  2006).  Many 
unstrengthened (and some previously strengthened) URM buildings provide less than 67% of the 
strength of NZS 1170.5 requirements, and many fall below the 33% minimum level, particularly 
in more seismically active parts of New Zealand (Russell & Ingham 2010).  

C13.4.2 Objectives 
The  objectives  of  seismic  improvement  are  twofold;  to  protect  the  occupants  from  injury  or 
death,  and  to  protect  the  building  itself  from  damage  due  to  deficiencies  in  its  design.  The 
protection  of  occupants  is  facilitated  by  protection  of  the  building,  so  the  building  itself  is  the 
focus here. The designer needs to consider the building as a functional but potentially deficient 
system which can be modified by various degrees in order to improve its performance.  

Assessing the architectural character will establish the important features of the building.  Many 
well‐intentioned  retrofits  with  clever  engineering  solutions  have  completely  ruined  the 
aesthetics  of  the  building  that  they  were  supposed  to  be  protecting.    There  are  sufficient 
strengthening techniques currently available for all retrofits to be reversible and sympathetic to 

  C13‐15
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

architectural and heritage value.  Strengthening of heritage buildings is difficult and sometimes it 
will be a case of selecting the least of several evils.  Many approaches and options are available 
for strengthening URM buildings, and all solutions will result in some impact on the building, so 
the type of strengthening system used needs to be very carefully considered. The way it looks, 
how it connects, its impact on heritage material and on spaces, and its harmony with the historic 
aesthetic are all important considerations. Furthermore, strengthening technology is constantly 
improving, and it is vital that current best practice is understood. 

The designer may wish to consider the building as a functional but potentially deficient system 
that can be modified by various degrees in order to improve its performance. There are several 
primary objectives to be considered when undertaking this process (Robinson & Bowman 2000). 
These  are  not  rigid  rules,  but  guidelines  for  achieving  a  sensitive  solution,  so  there  is  always 
some leeway for alternative approaches and creativity. If the spirit of these guidelines is adhered 
to,  generally  a  good  outcome  will  be  reached.  Note  that  these  guidelines  are  a  heavily 
summarised reading of the ICOMOS New Zealand Charter (ICOMOS 2010) for the Conservation 
of Places of Cultural Heritage Value. 

C13.4.3 Process 
Once a building has been identified as a seismic risk, a more thorough investigation is required.  
It makes sense at this stage to establish a detailed picture of its intrinsic seismic resistance, and 
assess  whether  simple  measures  that  address  basic  inadequacies  could  be  undertaken  to  give 
significant increases in strength.  This will ensure that the existing fabric is retained and utilised 
as much as possible and will minimise the extent of required additional measures.  It is generally 
considered  that  a  progressive  approach  to  strengthening  is  appropriate,  calculating  the 
resistance  of  progressively  more  extensive  configurations  to  establish  the  most  effective  and 
sympathetic approach (Robinson & Bowman 2000).  

A basic reading of the architectural character of the building will often assist in deciding on an 
appropriate approach, and an appreciation of which parts of the building are visually important 
will  inform  which  strengthening  techniques  will  allow  a  sensitive  solution.    By  considering  the 
elements  that  form  a  building,  a  practical  appreciation  can  be  gained  of  its  character,  and 
understanding will be gained of exactly what is important about it architecturally.  This will give 
cues  as  to  the  type  of  strengthening  systems  that  might  be  appropriate.    Most  solutions  will 
result in some visual impact to the building; invisible strengthening solutions are generally the 
safest option for visual impact, but these are often precluded by some other consideration.  Of 
visible solutions, the best option will work with the existing material if not to blend in, then to 
complement  the  architectural  character.    In  situations  where  strengthening  work  cannot  be 
hidden, an appreciation of the architectural character will assist the designer in deciding on ways 
to incorporate visible strengthening that does not detract from the building.  

There is a perception that façades, the public faces of buildings, are the most important aspects 
when  considering  a  retrofit,  although  this  is  arguable.    This  perception  means  that  many 
improvements are installed within the building’s interior.  The spaces, surfaces and materials will 
provide  information  about  where  and  how  these  might  be  undertaken  in  a  sensitive  manner.  

C13‐16   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

For example, it would generally be poor practice to insert a large steel K‐brace in the middle of a 
primary  circulation  space  or  lobby,  and  a  fine  decorative  wall  covering  would  suggest  that  an 
internal  concrete  shear  wall  is  not  an  ideal  solution.    A  sound  understanding  of  architectural 
character  will  help  to  furnish  the  designer  with  relevant  knowledge  in  order  to  exercise  good 
judgement in determining how to best deal with the problem of retrofitting.  

Once  it  has  been  accepted  that  seismic  improvement  is  required,  it  is  necessary  to  determine 
the required extent, and the methods that are appropriate to a particular building.  Generally, 
this analysis is undertaken in stages, beginning with assessing the architectural character of the 
building, then addressing the basic known inadequacies of URM construction, then determining 
what types of additional strengthening systems are appropriate.  There are myriad approaches 
and options for the strengthening of URM buildings.  The first step that should always be taken is 
to establish the building’s intrinsic resistance and utilise this to the greatest degree possible.  In 
the  likely  event  that  this  proves  to  be  inadequate,  this  resistance  should  be  enhanced  by 
sensitively upgrading connections and other basic URM inadequacies using current best practice, 
or by creating new techniques.  Strengthening is a complex art, and balancing visual impact with 
economy, reversibility, and architectural expression is a delicate act, but one that is possible in 
most situations, and one that ought to be the aim of all seismic retrofits.  With skill and care, a 
good solution can almost always be reached.  

C13.5 Stabilisation for Seismic Improvement 
Once a building has been identified as a seismic risk, a more thorough investigation is required. 
It  makes  sense  at  this  stage  to  establish  a  detailed  understanding  of  the  building’s  intrinsic 
seismic resistance, and assess whether simple measures which address basic inadequacies could 
be  undertaken  to  give  significant  increases  in  strength  (Russell,  2010).  Maximising  the  existing 
strength will ensure that the existing building fabric is retained and utilised as much as possible 
and  will  minimise  the  extent  of  additional  measures.  Various  techniques  for  addressing  these 
basic issues prior to the addition of any large supplementary structure are outlined below. 

Unmodified URM buildings usually have a number of critical structural deficiencies which make 
them  prone  to  earthquake  forces,  but  these  can  often  be  addressed  without  significant 
alteration to the building fabric, resulting in a relatively large increase in strength (Robinson & 
Bowman  2000).  The  overarching  problem  is  that  URM  buildings  were  simply  not  designed  for 
earthquake  loads,  and  while  they  can  be  made  to  perform  adequately  in  an  earthquake,  they 
lack a basic degree of connection to allow all parts of the building to act together as one.  

C13.5.1 URM Material Stabilisation 
URM  deteriorates  in  the  environment  over  time.  Occasionally  this  deterioration  will  result  in 
local failures and cracking which affect the overall effectiveness of the building. Various external 
forces can also cause cracking and damage in URM, such as dampness, subsidence, earthquakes, 
and  impacts.  Deterioration  similar  to  that  shown  in  Figure  C13‐11  can  often  be  remedied  by 
reinstatement  and  repointing  of  mortar,  but  sometimes  more  substantial  measures  are 
required.  Lime  mortars  should  always  be  re‐pointed  with  new  lime  mortars.  Mixing  lime  and 

  C13‐17
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

Portland  cement  mortars  can  cause  numerous  problems.  There  are  various  techniques  for  the 
repair of cracks, securing of lintels, and reinstatement of damage. Bonding agents such as grout 
or  epoxy  can  be  injected  into  the  mortar;  there  are  also  several  metal‐based  inserts  such  as 
shaped dowels, or reinforcing bars, which can be used to reinstate and strengthen the brickwork 
(Croci  1998).  The  visual  impact  of  reinstatement  and  strengthening  can  be  minimal  if  done 
carefully,  and  the  result  is  potentially  far  superior  to  a  cracked  and  broken  façade.  Such 
measures are often irreversible however, and care needs to be taken with colour matching and 
the  concealment  of  holes  drilled  for  inserting  rods.  Lintels  and  arches  will  sometimes  require 
strengthening,  particularly  when  these  are  constructed  from  URM.  One  of  the  best  ways  to 
achieve this is by using drilled and inserted rods which are grouted or epoxied into place. These 
rods  provide  the  requisite  tensile  strength  to  the  structural  element  while  having  little  visual 
impact.  

 
Figure C13‐11: Severely degraded brick and mortar due to moisture 

C13.5.2 Falling Hazards and Parapets 
URM  buildings  will  often  feature  numerous  decorative  elements  built  with  brick  and  plaster 
which are important parts of its architectural character, such as parapets, chimneys, gable walls, 
and other, smaller, decorative features. In the past, some buildings had these elements removed 
wholesale,  rather  than  being  strengthened  or  secured.  Parapets  and  chimneys  are  usually  the 
first  parts  of  a  building  to  fail  in  an  earthquake  due  to  their  low  bending  strength  and  high 
imposed accelerations (FEMA 547). Parapets in particular are simple to strengthen. Generally a 
steel  section  running  along  the  length  of  the  parapet  which  is  fixed  back  to  the  roof  structure 
behind is a suitable  technique, if a little crude. The  back of a parapet is not often seen, which 
makes the visual impact of this method low, and the steel section is bolted to the URM, which 
also has good potential for reversibility.  

Chimneys are more complex but can usually be strengthened using a combination of fixing them 
to  the  building  diaphragms  at  each  level  and  either  strengthening  the  projecting  portion  or 
bracing it back to the roof structure with steel members in a similar way to parapets, or fixing 
steel  sections  to  the  sides  to  provide  flexural  strength.  The  technique  shown  in  Figure  C13‐12 
may  be  appropriate  where  the  exterior  has  been  plastered.  Chimneys  contribute  to  the 

C13‐18   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

architectural  form  of  a  building  and  often  help  define  its  roofscape,  and  as  such  should  be 
preserved if possible.  

Other elements such as decorative plaster features on the face of a wall can be effectively fixed 
with a single bolted connection. Less secure elements, such as plaster finials or balusters, can be 
secured  with  a  single  epoxied  bolt  connected  to  a  strand  of  stainless  steel  wire,  to  mitigate 
falling hazards. However, more complex strengthening work may be appropriate in some cases. 

 
Figure C13‐12: Parapets strengthened using near‐surface mounted FRP strips 

C13.5.3 Floor and Roof Connection Upgrades  

The most problematic deficiency in URM construction is inadequate connection of diaphragms 
to walls (FEMA 547), as failure of these connections can potentially lead to global collapse of the 
building.  The  addition  of  a  network  of  small  ties  can  substantially  increase  the  strength  of  the 
building by fixing the walls to the floor and roof diaphragms (Robinson & Bowman 2000). These 
ties need to resist two actions; shear from the diaphragms trying to slide across the walls, and 
tension from the diaphragm and wall trying to separate. If these ties are missing, the walls will 
be acting in cantilever from ground level under lateral loads, and floors and roofs are far more 
likely to be dislodged from their supports, which is the most common mode of failure for URM 
buildings in an earthquake. This damage pattern is shown in Figure C13‐13.  

 
Figure C13‐13: An extreme case in the 2010 Darfield earthquake where inadequate 
connections have resulted in wall collapse 

  C13‐19
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

Walls are not only secured by floors and roofs however; lateral support is also provided by cross 
walls,  columns,  and  buttresses  and  the  influence  of  these  elements  should  be  taken  into 
account.  The  thickness  and  length  of  walls  both  affect  their  performance;  lower  level  walls  in 
URM buildings are usually several leaves thick and can have significant out‐of‐plane resistance. 
Similarly, the shear response of these walls can be substantial, particularly for walls with few or 
no penetrations (Robinson & Bowman 2000).  Horizontal diaphragms formed  by floors or roofs 
can distribute loads to other load‐resisting elements and tie buildings together. The connections 
of these systems are often inadequate or non‐existent, and require upgrading before they can 
provide any positive effects. If the resistance of the building still falls below the critical level after 
upgrading these connections, then additional strengthening will need to be undertaken.  

The  most  common  form  of  flooring  in  URM  buildings  is  timber,  although  concrete  is  also 
encountered (Russell 2010). Timber floors usually consist of tongue and groove planking nailed 
to  joists  which  are  supported  on  URM  walls,  or  on  bearers  which  are  supported  on  internal 
columns.  The  direction  of  the  joists  affects  the  way  in  which  these  ties  can  be  connected  and 
there are various strategies for fixing in each direction. These strategies usually involve adding 
new  timber  chords  and  blocks  and  a  number  of  steel  fasteners  to  ensure  adequate  fixity 
between the diaphragm material, the chord, and the URM wall, although where access is limited 
this system may be substituted for a steel angle at floor or ceiling level. If done sensitively and 
without excessive visible use of new timber and fasteners, this method can have minimal visible 
impact. Consideration should be given to the type of bolt used, as tensile bolts often require a 
plate  on  the  outside  wall  of  the  building,  which  results  in  exterior  visual  impact  as  shown  in 
Figure  C13‐14.  Systems  have  now  been  developed  which  forego  this  requirement,  but  require 
the  fixing  of  bolts  into  the  brick  with  epoxy.  Through‐bolting  has  good  reversibility,  but  visual 
impact, and epoxying has no visual impact but is irreversible, so a balance must be struck.   

 
Figure C13‐14: An assortment of diaphragm fixings 

C13‐20   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C13.5.4 Outer Layer Fixing 
The outer façade layer of a cavity wall is problematic as it is particularly susceptible to failure by 
peeling off outwards. The steel ties which were commonly installed to connect this layer to the 
more  robust  wall  behind  are  often  missing  or  have  rusted  out,  requiring  attention  during 
retrofits (Russell et al. 2006). One approach to this problem has been to fill the cavity with grout 
and  reinforcing  steel,  which  has  the  dual  benefits  of  bonding  the  outer  layer  to  the  main  wall 
and  also  forming  a  reasonably  strong  shear  wall  which  is  hidden  from  view.  However,  this 
approach fails to consider the purpose of the cavity. Lime mortars are porous whereas concrete 
is  not,  which  means  that  any  moisture  which  finds  its  way  inside  the  building  for  whatever 
reason  will  remain  trapped  there.  This  has  resulted  in  extensive  mould  and  the  subsequent 
destruction of at least one heritage building in Auckland, making this practice hazardous and ill‐
advised. While a filled cavity may seem like an excellent strengthening solution, it is vital that the 
drainage functionality of the cavity is fully considered beforehand.  

The current preferred approach is to use a series of proprietary ties at regular centres which are 
drilled  through the face layer and are epoxied into the structure behind,  the fixing of which  is 
shown in Figure C13‐15. This is effectively a retrofit of the steel ties which ought to have been 
present.  The  visual  impact  of  these  ties  is  minimal,  although  care  needs  to  be  taken  when 
concealing drilled holes. These ties are irreversible, but their presence is visually negligible.  

 
Figure C13‐15: Spiral threaded rods being installed to secure an outer layer of bricks 

C13.6 Enhancing Existing Walls 
Seismic improvement should be designed with an appreciation of the architectural character in 
mind.  The  locations  for  strengthening  elements  will  often  present  themselves;  many 
strengthening elements will be able to be located within hidden or secondary spaces where they 
will  have  little  architectural  or  historic  impact.  However,  structure  will  often  be  required 
immediately  adjacent  to  the  street  façade(s),  in  primary  circulation  spaces,  lobbies,  stairways, 
corridors,  and  large  public  spaces  (Robinson  &  Bowman  2000).  In  these  situations,  particular 
care  needs  to  be  taken  to  ensure  that  the  strengthening  technique  is  appropriate  to  the 
architecture and heritage value of the building. Often it is imprudent to add elements in addition 

  C13‐21
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

to the  URM  itself for reasons of visual impact. This  section explains ways of strengthening the 


existing URM without significantly altering its thickness or aesthetic.  

C13.6.1 Out‐of‐Plane Strengthening 
URM walls are weak when subjected to forces other than compression. Even when fully secured 
to  floors  at  each  level,  out‐of‐plane  forces  can  cause  significant  bending.  This  bending  is 
governed  by  the  ratio  of  the  height  between  levels  of  support  to  the  thickness  of  the  wall 
(Rutherford  &  Chekene  1990).  Some  walls  are  of  sufficient  thickness  or  have  cross‐walls  or 
buttresses  which  enable  them  to  withstand  these  out‐of‐plane  forces  without  modification, 
however  many  walls  will  require  seismic  improvement.  There  are  a  number  of  approaches  to 
combat this problem.  

C13.6.1.1 Inter‐Floor Wall Supports 

A series of vertical steel sections can be bolted to the inside face of the wall at sufficient spacing 
to ensure that the width of wall between supports is capable of resisting the out‐of‐plane forces. 
These sections act in bending to transfer wall loads to the adjacent floor diaphragms, essentially 
breaking up a large planar wall into a number of buttressed segments. This is a simple method 
which  may  be  appropriate  in,  for  example,  an  industrial  building,  where  visible  steel  bolted  to 
the walls is in keeping with the character of the building, or in other buildings where the steel 
can be made to be architecturally appealing. In some other situations it may be less appropriate 
but less intrusive than other techniques. If there is existing internal framing with space behind 
for  these  columns,  and  no  historic  material  is  lost  during  installation,  then  it  is  a  perfectly 
acceptable  method.  Steel  sections  generally  fix  to  the  historic  material  with  bolts  only,  which 
allows a high degree of reversibility.  

In the past, rather than only supporting the URM walls for out‐of‐plane actions, these systems 
have  been  conceived  as  a  method  to  support  the  floors  in  the  event  that  the  walls  fail  and 
collapse (Cattanach et al. 2006). In all URM buildings and in heritage buildings in particular, this 
is a defeatist approach to design. To design for the inevitability of the building collapsing rather 
than attempting to prevent its collapse is to deny the building itself of any inherent value, which 
in most cases is patently untrue.  

A technique in a similar vein to vertical steel is to provide a horizontal steel member at the mid‐
height of the wall and brace this with diagonal struts up to the floor or ceiling diaphragm above, 
as shown in Figure C13‐16. This technique might be more suitable than vertical members if there 
is a cornice part way up the wall which needs to be conserved, or which can be used to disguise 
the  steelwork.  However  care  needs  to  be  taken  to  ensure  than  the  struts  are  visually 
unobtrusive.  Both  of  these  techniques  can  also  be  undertaken  with  the  steel  substituted  with 
concrete, where this is more appropriate visually, or less commonly with timber. Steel struts can 
also be recessed within the width of the wall. Recessing the members results in an irrecoverable 
loss of material and may result in other complications such as cracking, although recesses may 
be preferable if used beneath a plastered surface, as there it will not affect the interior space. 
Concrete will be more massive than steel and therefore more intrusive. Also, once cast, concrete 

C13‐22   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

is  difficult  to  remove  without  significant  damage,  particularly  from  a  porous  and  naturally 
coloured material like clay brick. In‐situ concrete is a fairly permanent measure, so any activity 
which  requires  concrete  to  be  cast  against  brick  should  be  given  careful  thought  before  being 
undertaken.  As  so  often  happens  in  conservation  work,  there  are  a  number  of  measures 
available, all of which have positive and negative aspects.  

 
Figure C13‐16: Struts from the floor above to improve out‐of‐plane performance 

C13.6.1.2 Post‐Tensioning and Other Core Reinforcement 

Post‐tensioning is an  extremely effective way of providing out‐of‐plane strength in  URM  walls. 


The process involves drilling vertical cores through the middle of a URM wall and then inserting 
steel rods into these. The rods may or may not be set in grout, and are then tensioned, which 
provides an additional compressive force in the wall. This loading modifies the stress behaviour 
of  the  URM  in  bending  (i.e.  the  result  of  out‐of‐plane  loading).  Instead  of  bending  instantly 
causing  tensile  forces,  to  which  URM  has  little  resistance,  the  wall  remains  in  compression 
(Ismail et al. 2010). This modification of the mechanical characteristics also results in an increase 
in the shear strength of the wall, making post‐tensioning an attractive strengthening solution.  

Post‐tensioning has very little visual impact, although its installation may be unsuitable in some 
buildings, as access is needed to the top of the wall, and walls need to be of a certain minimum 
thickness. Drilling cores involves some loss of historic material from the holes, though compared 
to some methods this is a very minor impact. A partially completed example is shown in Figure 
C13‐17. If the bars are fully grouted in place, post‐tensioning is essentially irreversible, although 
this does not necessarily have to be done. The presence of post‐tensioning bars is not likely to 
result in any negative effects to the historic material should their function no longer be required, 
provided care is taken with all core reinforcement to ensure that it is adequately protected from 
corrosion. This problem can be completely avoided by using plastic coated steel or FRP bars. 

There are other methods of core reinforcement; the most common being non‐stressed bars set 
in  grout,  where  the  steel  only  becomes  stressed  when  the  wall  is  loaded  laterally.  The  visual 
impact  and  reversibility  of  these  methods  are  exactly  the  same  as  for  fully  grouted  post‐
tensioning, although they are less effective structurally. 

  C13‐23
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

 
Figure C13‐17: Post‐tensioning bars used in the Birdcage hotel with concrete load spreaders 
cut into the brick 

C13.6.1.3 FRP and Others 

There are a number of other methods, such as strips of fibre reinforced polymer (FRP) fitted into 
vertical  saw  cuts  in  URM.  This  is  known  as  near  surface  mounting  (NSM).  NSM  is  a  relatively 
recent  technique  which  involves  epoxying  FRP  into  saw  cuts  in  the  surface  of  the  URM  and 
covering  the  cut with a grout mixed with brick dust (Dizhur et al. 2011). This  technique would 
have some visual impact in naked brick, but little if done within an existing grout line, and none 
if installed in plastered walls being repainted. This technique can be a particularly effective and 
non‐intrusive  method  of  strengthening,  although  the  finishing  of  this  system  is  noticeable  and 
work needs to be done to conceal the inserts. Steel strapping as shown in Figure C13‐18 can also 
be an effective technique.  

C13.6.2  In‐Plane Strengthening 
Most URM walls are required to transfer some degree of shear loading along their length. If a 
building has insufficient shear capacity in a particular direction, the capacity of existing walls can 
be increased instead of inserting additional structure. There are various methods for achieving 
this strength increase which generally involve the application of an additional layer of material 
bonded to the surface of URM to increase its strength, although there are some measures which 
involve  altering  the  wall  itself,  such  as  post‐tensioning,  as  described  above.  Most  of  these 
measures involve a plane of extra independent structure being applied over the surface of the 
URM, effectively forming new shear walls, which are described below. 

C13‐24   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 
Figure C13‐18: Simple and visually interesting in‐plane strengthening 

The presence of openings in a shear wall renders that section less stiff than the surrounding full 
height walls, meaning that the wall above and below, or between closely spaced openings, will 
likely be the first areas to fail in the event of an earthquake. Infilling the openings will eliminate 
this problem by making the wall continuous, and has been advocated as a valid solution in the 
past. Problems with altering the character of the building and matching brick and mortar colours 
mean that this technique should only be used as a last resort and even then preferably not in 
visible  areas.  Infilling  openings  is  likely  to  be  somewhat  reversible  if  done  with  brick,  but  not 
completely, and visual impact will depend on the location. If in‐filled with concrete, the work will 
be  less  reversible  and  the  ductile  behaviour  of  the  wall  may  be  affected  due  to  incompatible 
stiffnesses.  Localised  steel  cross  bracing  near  openings  is  another  technique  which  can  prove 
effective, but again this system is likely to be highly visible and should only be undertaken when 
it does not detract from the character of the building.  

C13.7  New Building Strengthening Systems 
URM  walls  will  often  be  unsuitable  for  strength  upgrades,  or  are  not  of  sufficient  extent  for 
these upgrades to provide enough strength. Taller buildings in particular will frequently require 
additional strengthening elements to supplement their inherent strength, as their facades often 
consist of a series of piers with openings between slender piers, without enough planar surfaces 
to  form  effective  shear  walls.  As  shown  in  Figure  C13‐19,  these  are  susceptible  to  earthquake 
damage. This section describes the more common techniques which can be utilised.  

  C13‐25
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

 
Figure C13‐19: Pier damage between openings in the Darfield Earthquake 

C13.7.1 Moment Frames 
Moment  frames  are  a  common  method  of  gaining  additional  horizontal  resistance  which  can 
also  be  used  as  a  local  strengthening  solution.  The  advantage  of  this  system  is  that  it  is 
comprised  of  beams  and  columns,  so  is  fully  customisable,  and  there  is  space  between  the 
vertical and horizontal elements. Moment frames allow full visual and physical access between 
each  side  of  the  frame,  and  minimal  spatial  disruption.    In  building  façades  with  numerous 
openings, some form of moment frame can often be fitted to the masonry piers on the inside or 
outside (or both) depending on the effect on the architectural character. Moment frames can be 
a  particularly  effective  solution,  especially  where  the  frame  is  tailored  to  the  character  of  the 
building. Care needs to be taken with steel frames in particular to ensure stiffness compatibility 
with  the  existing  structure  (Robinson  &  Bowman  2000). Steel  is  a  ductile  material,  but  URM  is 
not, meaning that under earthquake loads the added stiffness of the steel might not come into 
effect until a load is reached where the URM has already been extensively cracked.  

Moment frames can be an excellent strengthening technique, either to supplement an existing 
wall or as a new, stand alone element. If a steel frame is erected against an existing wall where 
weakness  exists,  the  frame  needs  to  be  fixed  either  directly  to  the  URM  using  bolted 
connections  into  the  wall  or  to  the  diaphragm.  Installing  concrete  frames  is  a  more  complex 
undertaking, as these will often be constructed by thickening existing piers, although a concrete 
frame which is separate from the existing structure is possible. In both situations it is important 
that architectural character is retained, and historic material conserved. Some considerate and 
artful design strategies may need to be undertaken to achieve this.  

Steel  moment  frames  have  a  high  degree  of  reversibility,  as  again  they  rely  on  mechanical 
connections  and  relatively  small  ties  to  connect  to  the  existing  structure.  Concrete  frames  are 
generally far less reversible, but can sometimes be better concealed when this is a requirement. 
Figure  C13‐20  shows  a  large  new  moment  frame  which  is  expressed  as  a  new  element.  Some 
recent  buildings  have  very  effectively  used  precast  concrete  load‐resisting  elements  which  are 
separate from the URM walls, solving the problem of reversibility (Cattanach et al. 2006). 

C13‐26   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 
Figure C13‐20: A concrete moment frame inside the façade of a large URM building in 
Wellington (Dunning Thornton Consultants). 

C13.7.2 Braced Frames 
Braced  frames  are  available  in  various  configurations:  concentric,  tension  only  concentric, 
eccentric,  and  ‘K’  bracing.  The  key  functional  difference  between  braced  frames  and  moment 
frames  is  that  due  to  the  diagonal  braces,  braced  frames  prevent  physical  continuity  between 
spaces  on  either  side  of  the  frame.  Braced  frames  are  also  generally  constructed  from  steel 
rather than concrete, and are much more rigid than moment frames. 

Braced frames are a very efficient method of transferring horizontal forces but have significant 
setbacks,  and  their  use  in  façade  walls  is  usually  precluded  by  the  presence  of  windows,  as 
diagonal braces crossing window openings are generally considered to be poor design. It is also 
difficult to get a braced frame to conform to an existing architectural character; however they 
can be used to very good effect within secondary spaces, and can be made to fit architecturally 
in  some  situations  with  careful  consideration.  Figure  C13‐21  and  Figure  C13‐22  show  braced 
frames in use. Generally speaking, steel braced frames have a good degree of reversibility and 
can provide excellent strengthening when used appropriately. 

Figure C13‐21: Eccentric bracing in a  Figure C13‐22: An eccentrically braced core 
walkway (Dunning Thornton Consultants).  (Dunning Thornton Consultants). 

  C13‐27
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

C13.7.3 Shear Walls 
Shear  walls  are  used  to  increase  the  strength  of  existing  URM  or  are  added  as  new  elements. 
Materials which resist shear loads can be added to the surface of the URM; these might include 
gypsum plasterboard, particle board,  plywood, or plate steel (Robinson & Bowman 2000), and 
are  generally  fixed  to  the  URM  with  bolts  via  a  supplementary  structure.  This  fixing  of  the 
supplementary  material  means  that  the  surface  of  the  URM  is  generally  covered  and  may 
interfere  with  decorative  elements  on  walls  and  openings,  although  this  interference  can  be 
worked around with stronger materials such as plate or strap steel. The supplementary material 
can also increase the thickness of the wall, which is not particularly desirable as it can reduce the 
scale and area of the interior. For these reasons shear walls can be visually detrimental if used 
indiscriminately.  Stand  alone  shear  walls,  which  are  independent  of  URM  walls,  can  be 
introduced,  although  these  can  be  detrimental  for  similar  reasons.  Despite  these  negatives, 
shear walls are a practical and efficient method for strengthening and are commonly used. All of 
these materials can be easily removed in the future, which makes them good solutions for shear 
walls in two to three storey buildings with moderate horizontal loads. 

During  the  1980s,  shotcrete  shear  walls  were  a  common  strengthening  technique.  This 
technique involves spraying concrete onto the surface of a URM wall to essentially cast a new 
wall  against  the  existing  wall,  as  shown  in  Figure  C13‐23.  This  technique  provides  plenty  of 
strength  to  the  wall,  both  in‐plane  and  out‐of‐plane;  however  it  is  now  largely  regarded  as 
unacceptable unless absolutely necessary as it causes a significant increase in wall thickness and 
it is very difficult to remove the concrete, and even more so to restore the wall behind to any 
semblance  of  its  character  prior  to  concreting.  Furthermore,  its  installation  generally  requires 
the  building  to  be  gutted,  which  results  in  the  loss  of  much  heritage  material  and  creates  an 
essentially new interior (Robinson & Bowman 2000). 

Another technique for forming shear walls is the addition of fibre reinforced polymer sheets as 
in Figure C13‐24. These sheets do not require the same invasive installation as shotcrete walls, 
however  are  generally  equally  permanent,  and  have  potentially  limited  application,  although 
new technology may soon change this. If it is possible to provide out‐of‐plane strength using FRP 
inserts,  coupled  with  an  FRP  surface  layer  for  shear,  this  solution  could  be  far  superior  to 
shotcrete from an architectural perspective. An important consideration with the use of sheets 
of  FRP  is  that  it  is  impermeable,  which  can  lead  to  problems  with  water  trapped  within  the 
building, resulting in damp and mould issues, and potential de‐bonding of the epoxy. 

   

C13‐28   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 
Figure C13‐23: Shotcrete walls on the rear of  Figure C13‐24: FRP applied to a wall (Dunning 
the birdcage hotel  Thornton Consultants). 

C13.7.4 Diaphragms 
Diaphragms  are  useful  because  they  provide  a  layer  through  which  lateral  forces  can  be 
distributed  from  their  source  to  remote  resisting  elements,  and  also  act  to  bind  the  whole 
building together at each level. A building which acts as one rigid body rather than a number of 
flexible  panels  is  far  more  likely  to  survive  an  earthquake.  Tying  floors  to  the  outer  walls  is 
generally required regardless to ensure that joists are not dislodged (Robinson & Bowman 2000).  

Floor  diaphragms  consist  of  three  main  elements;  chords,  sheathing  material,  and 
supplementary  structure.  To  form  a  diaphragm  in  a  typical  URM  building,  chords  need  to  be 
established,  and  mechanical  fastenings  added  to  take  shear  and  tensile  loads  (Rutherford  & 
Chekene 1990). Several secondary fastenings between the chord and the floor or roof may also 
be required depending on the technique used. Some tensile ties will penetrate to the outside of 
the building and others will be drilled and epoxied in place. Existing historic sheathing may prove 
inadequate and require strengthening or an additional layer of more rigid material. 

The main visual impact of forming diaphragms is if new sheathing is required. Historic flooring 
material is often a significant contributor to the character of a place and ought to be retained in 
view  whenever  possible.  If  the  existing  sheathing  is  inadequate,  a  ceiling  diaphragm  below,  or 
stiffening  the  existing  material  might  be  preferable  to  covering  it.  Another  approach  is  to 
remove  the  existing  sheathing  and  install  a  structural  layer  beneath  it.  This  exercise  requires 
extreme  care;  firstly  because  existing  sheathing,  particularly  tongue  and  groove,  is  very  easily 
damaged  during  removal;  and  secondly,  care  needs  to  be  taken  to  restore  the  boards  in  the 
correct order.  

  C13‐29
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

 
Figure C13‐25: It is possible to make diaphragm improvements visibly interesting, as with this 
recently installed floor 

Ties to the outside of walls may require metal load spreaders which visually impact the exterior. 
Many New Zealand buildings display these spreaders, and they seem to have become somewhat 
accepted  as  part  of  the  strengthening  process.  Nevertheless,  care  needs  to  be  taken  when 
considering their visual impact and invisible solutions may be preferable. Much of the additional 
required work can be hidden within the floor space, but if this is exposed or the connections are 
extensive,  special  attention  will  be  required  to  preserve  the  visual  character  of  the  inter‐floor 
space. 

Diaphragms which are formed using mechanical connections have a high degree of reversibility; 
where  ties  are  epoxied  into  walls,  there  is  less  reversibility,  but  minimal  visual  intrusion. 
Additional sheathing may damage or alter the nature of the historic timber below, making it less 
desirable as a solution, though this can be mitigated in cases such as that in Figure C13‐25 by an 
interesting  replacement.  Occasionally,  pouring  concrete  over  an  existing  timber  floor  is 
considered. This solution can greatly increase the stiffness of the building, but in turn increases 
its weight and therefore the forces acting upon it. Further, it completely changes the material of 
the floor and is not a reversible action, because even if it can be removed, the concrete would 
essentially  destroy  the  character  of  the  underlying  timber.  This  procedure  is  therefore  not 
recommended except in exceptional circumstances.  

Roof  diaphragms  where  the  structure  is  exposed  are  slightly  different,  as  the  inclusion  of  a 
plywood diaphragm above timber sarking is generally acceptable if this area can be accessed, for 
example  if  the  roofing  is  being  replaced.  This  installation  can  also  help  to  protect  the  sarking 
beneath. Roofs with suspended ceilings can be made to accommodate cross bracing, struts, and 
more innovative solutions, as they can be hidden within the ceiling space. In instances where the 
roof  provides  little  diaphragm  action,  or  the  forming  of  a  diaphragm  is  uneconomical  or 
impossible, a horizontal load resisting member at the level of the top of the walls can be used to 
provide stability to the walls when subjected to out‐of‐plane loads. However, this member needs 
to  be  fixed  to  stiff  elements  at  regular  intervals  to  transfer  horizontal  loads,  and  these  stiff 
elements may need to be introduced to the building if other structure cannot perform this task. 

C13‐30   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C13.7.5 Foundations  
Foundations  in  existing  URM  elements  are  usually  adequate  (FEMA  547).  However,  when 
transferring  horizontal  loads,  new  strengthening  elements  also  usually  induce  significant 
concentrated  vertical  loads.  This  extra  loading,  combined  with  the  added  weight  of  additional 
structure, means that often the foundations in URM buildings will need to be upgraded in order 
to deal with these new loads. There are various techniques for meeting these new requirements, 
which will usually include enlarging the existing foundations by casting a new concrete footing 
beside  the  old  and  tying  these  footings  together  with  drilled  reinforcing  rods.  Existing 
foundations  may  also  need  to  be  tied  together  with  ground  beams  to  increase  stiffness. 
Foundations  themselves  are  generally  considered  to  not  have  a  great  deal  of  heritage  value; 
however the ground level floor often will. 

If the building has a basement or subfloor, strengthening foundations is made much easier, but 
care  needs  to  be  taken  when  considering  foundation  extensions  to  reduce  the  damage  to  the 
existing above ground material as much as possible. Some buildings are also located in historic 
areas and excavations beneath will require the input of an archaeologist.  

C13.8 Reduction of Forces 
Another  approach  to  seismic  improvement  of  URM  stems  from  its  weight.  Seismic  actions  are 
directly proportional to the mass of the building, so if mass is reduced, so are the forces acting 
upon the building. A lighter building requires less lateral strength and therefore less additional 
strengthening.  Reducing  the  mass  of  a  building  may  seem  at  face  value  to  be  a  sensible 
approach;  however  past  experience  has  shown  this  to  not  be  so.  The  mass  must  be  removed 
from somewhere, and the higher up the mass is, the stronger the forces upon it and the more 
difficult it is to strengthen, so the top of the building is the first place which has been looked at. 
Historically this has led to the ad‐hoc removal of decorative elements such as parapets, gables, 
chimneys,  and  occasionally  whole  towers  (Robinson  &  Bowman  2000).  These  elements  will 
almost  always  significantly  contribute  to  heritage  value  and  character,  and  their  retention  is 
essential  to  preserving  this.  Indeed,  it  is  often  desirable  to  replace  these  features  if  they  have 
been removed from buildings and still exist. While reduction of weight may be achieved in more 
minor  ways,  such  as  removal  of  internal  URM  partitions  or  the  removal  of  plant  loads,  the 
wholesale removal of decorative elements is strongly discouraged.  

C13.8.1 Base Isolation 
A more recent approach to reducing forces acting on a building is to introduce a damping layer 
between  the  building  and  the  ground.  This  process  is  known  as  base  isolation,  and  works  by 
separating the mass of the building from the lateral loads induced by ground movement with a 
layer  of  flexible  material.  Base  isolation  is  the  most  effective  but  also  the  most  radical 
strengthening  technique,  as  it  requires  the  building  to  be  physically  separated  from  its 
foundations by a layer of flexible material, and the foundations and the ground floor will usually 
need to be extensively strengthened. However, the strengthening required to the building above 
this level is  minimised,  making base  isolation an  attractive option for  particularly important or 

  C13‐31
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

valuable  buildings  (Robinson  &  Bowman  2000),  or  where  the  contents  of  the  building  are 
valuable;  for  example,  hospitals  or  museums.  Visual  impact  is  minimised  as  most  of  the  work 
takes place at ground level or below, although it is generally not reversible. As it is often below 
ground and largely invisible, this work may be of little consequence. The main problem with base 
isolation is that currently it is often prohibitively expensive to install in retrospect; however as 
new technology emerges this may change.  

There  are  other  methods  for  modifying  the  behaviour  or  the  building.  One  method  which  has 
seldom  been  used  in  New  Zealand  is  the  installation  of  energy  dissipaters  or  dampers.  These 
devices resemble large hydraulic cylinders and work in combination with a steel frame to allow 
some  lateral  displacement,  but  provide  an  increasing  level  of  resistance.  The  downside  of 
systems such as these is that they are expensive and difficult to conceal, as the dissipater works 
on the diagonal in place of a brace. Damping is most relevant to flexible buildings, however, and 
will not be effective in most URM buildings.  

C13.8.2 Torsion 
Torsion can be a significant contributor to the total force in a structural system. It is caused by 
asymmetry  in  the  mass  and  structural  stiffness  of  the  building.  If  the  centre  of  mass  and  the 
centre  of  stiffness  of  a  building  are  aligned,  then  there  is  no  torsional  effect,  however  this 
coincidental alignment is almost never the case as most buildings are not symmetrical. Buildings 
with one or  more weak  walls with extensive openings, such as  shop‐front façades, and one or 
more  stiff  walls,  such  as  party  walls,  are  particularly  susceptible  to  torsional  loads.  In  an 
earthquake the loads are focused through the centre of mass, as mass is the primary generator 
of seismic loads. The building resists these loads through its centre of stiffness, so if the centre of 
mass is offset from the centre of stiffness, then a rotational force is induced in addition to the 
basic horizontal force. In extreme cases the rotational force can be greater than the actual linear 
earthquake forces.  

The  main  way  to  combat  excessive  torsional  response  is  to  make  the  stiffness  of  the  building 
more  uniformly  distributed.  This  exercise  may  involve  stiffening  weak  walls  with  frames  or 
bracing, or in more extreme cases involve placing vertical saw cuts periodically along the length 
of a stiff wall to reduce its stiffness. However, the architectural impact of each of these practices 
must  be  considered.  The  stiffening  of  elements  involves  the  same  considerations  as  the 
strengthening  practices  above,  while  saw‐cutting  requires  a  consideration  of  cut  location  and 
visibility within the structure of the building. Torsional forces must be considered in the retrofit 
of  all  asymmetrical  buildings,  particularly  those  which  have  one  or  more  walls  that  are 
significantly weaker or stronger than others.  

C13.9 Approaches to Seismic Improvement 
There  are  numerous  approaches  to  improving  heritage  buildings  and  it  is  very  important  that 
proposed  retrofit  work  is  considered  and  reviewed  prior  to  installation  to  prevent  well‐
intentioned but insensitive solutions. It is generally accepted that the basic inadequacies of URM 
construction should be addressed in every case, which includes upgrading connections between 

C13‐32   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

the walls and the floors, fixing outer leaves of cavity walls, and securing parapets and chimneys. 
Addressing  these  very  simple  problems  will  ensure  that  the  building  will  behave  as  predicted, 
and allows the designer to focus on any additional requirements.  

The target strength of the building needs to be decided beforehand. In many cases it is accepted 
that  strengthening  to  100%  of  NZS 1170.5  requirements  is  simply  unrealistic  and  uneconomic, 
but the NZSEE recommended 67% of current requirements should be aimed for if possible. The 
approach  taken  should  always  refer  back  to  the  main  principles  of  dealing  with  heritage  as 
outlined in Section C13.2.  

There  are  sufficient  seismic  improvement  techniques  currently  available  for  all  retrofits  to  be 
reversible  and  sympathetic  to  architectural  and  heritage  value.  Many  approaches  and  options 
are  available,  and  all  solutions  will  result  in  some  impact  on  the  building,  so  the  type  of 
strengthening system used needs to be very carefully considered. As illustrated in Figure C13‐26, 
the way a component looks, how it connects, its impact on existing material and spaces, and its 
harmony  with  the  historic  aesthetic  are  all  important  considerations.  Furthermore, 
strengthening  technology  is  constantly  improving,  and  it  is  vital  that  current  best  practice  is 
understood.  

 
Figure C13‐26: A roof bracing system which clashes with the existing structure, resulting in a 
confused ceiling space 

C13.9.1 Improvement Type 
Generally, the architecture and layout of the building will inform the overall approach to seismic 
improvement  as  well  as  individual  strengthening  solutions.  The  impacts  of  the  proposed 
improvement  systems  need  to  be  considered  and  the  simplest  or  most  structurally  efficient 
system may not always be appropriate. The designer needs to ask how a strengthening element 
will impact the building overall: visually and functionally; if it will detract from the heritage of the 
building; involve excessive removal of historic material; and its degree of reversibility.  

A wall with many openings is generally going to be unsuitable for use as a shear wall or for use 
with  diagonal  bracing,  but  might  suit  a  series  of  moment  frames,  whereas  an  ornate  and 
decorative exposed brick  wall or complex forms, as in Figure C13‐27 and Figure C13‐28,  might 

  C13‐33
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

not suit a moment frame, but post‐tensioning bars could be appropriate. An industrial building 
might  already  have  exposed  steel  structure,  so  some  additional  steel,  if  suitably  differentiated 
from the original structure, could be an excellent solution.  

Figure C13‐27: The ornate façade of this  Figure C13‐28: The solution was to innovatively 
building made exterior strengthening  strengthen the interior, which allowed retention of 
difficult  its most important visual elements 

C13.9.2 Placement 
Placement of new structure is also often informed by the layout of the building. It is desirable for 
strengthening elements to be as close as possible to the source of the loads in order to minimise 
additional  work  as  in  Figure  C13‐29.  It  is  generally  undesirable  to  subdivide  interior  spaces, 
particularly  primary  spaces,  into  smaller  secondary  spaces.  The  practice  of  placing  intrusive 
bracing  in walkways or in the  middle  of rooms is discouraged as it forms a  barrier, physical or 
implied, between volumes.  

   
Figure C13‐29: Openings in this Christchurch  Figure C13‐30: Steel structure installed in an 
café allowed placement of frames which  intrusive way which is visually distracting 
compliments the space 

C13‐34   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C13.9.3 Visibility 
It is not always desirable to conceal new structure as if it were part of the building; the new work 
becomes part of the history of the building and it may be preferable to expose the structure if it 
is  done  in  an  architecturally  sensitive  way.  It  is  very  easy  for  an  ill‐considered  yet  simple 
structure  to  negatively  affect  a  building,  as  in  Figure  C13‐30.  A  particularly  important  heritage 
building will need careful treatment overall, and it may be possible and desirable to hide all new 
improvement work, allowing the building to retain as much of its character as possible. In other 
cases,  with  industrial  or  less  ornate  or  important  buildings,  it  is  sometimes  appropriate  to 
celebrate  strengthening  work  by  exposing  it  and  making  it  into  a  feature  of  the  improved 
building as in Figure C13‐31 and Figure C13‐32. These two schools of thought may seem to be 
conflicting, or even mutually exclusive, but careful aesthetic consideration can potentially make 
either approach appropriate for any given case.  

   

Figure C13‐31: No attempt has been  Figure C13‐32: Excessive floor and wall ties somehow 
made to conceal this new shear wall,  work with this façade 
rather the aesthetic is celebrated by 
the rest of the architecture 

C13.10 Conclusions 
There  is  now  no  question  that  something  must  be  done  about  the  seismic  strength  of  a  large 
number  of URM  buildings.    These  buildings  form  a  large  proportion  of  New  Zealand’s  heritage 
structures, and have far more importance to society than simply their functions; thus retrofit for 
seismic strength is not merely a nice idea, but a vital action.  This need is further bolstered by 
recent  legislation  requiring  action  on  buildings  below  a  certain  strength  threshold,  which 
includes  most  URM  buildings.    Aside  from  retrofit,  there  are  two  alternative  options  for  these 
buildings: ignore their inadequacies and hope that there are no earthquakes, or demolish them 
now.  Neither of these options addresses the problem, and both options are likely to result in an 
unacceptable loss of built heritage.  

  C13‐35
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

Retrofitting  is  potentially  invasive  and  destructive;  therefore  a  method  should  be  adopted  to 
guide the design and implementation of any intervention.  Fortunately, a series of authoritative 
principles have been developed, and are prescribed in the ICOMOS New Zealand Charter for the 
Conservation  of  Places  of  Cultural  Heritage  Value,  which  can  be  summarised  into  four  basic 
principles: know the important characteristics of the building; respect its character and integrity; 
only do as much as is necessary; and make new work recognisable and reversible.  

Seismic  improvement  is  a  complex  art.  Balancing  strength  requirements  with  visual  impact, 
economy, reversibility, and architectural expression is a delicate act, but one which is possible in 
most  situations,  and  one  which  ought  to  be  the  aim  of  all  retrofits.  Sometimes  the  design 
process will involve choosing the lesser of many evils, but with skill and care, a good solution can 
always be reached.  

There  are  myriad  approaches  and  options  for  the  seismic  retrofit  of  URM  buildings.  The  first 
step, which must always be taken, is to establish the building’s intrinsic resistance and utilise this 
to  the  greatest  degree  possible.  In  the  likely  event  that  this  intrinsic  resistance  proves  to  be 
inadequate, further resistance should be added by sensitively upgrading connections and other 
basic URM inadequacies using some of the methods described in this article, or by creating new 
techniques.  

A basic reading of the architectural character of the building will often assist in deciding on an 
appropriate approach, and an appreciation of which parts of the building are visually important 
will  inform  which  improvement  techniques  will  allow  a  sensitive  solution.  Most  solutions  will 
result in some visual impact to the building; invisible solutions are generally the safest option for 
visual  impact,  but  these  solutions  are  often  precluded  by  some  other  consideration.  Of  visible 
solutions,  the  best  option  will  work  with  the  existing  material  if  not  to  blend  in,  then  to 
complement the architectural character.  

The most important attribute that a designer can have is creativity.  Conservation principles exist 
to  inform  the  type  of  action  that  will  result  in  a  good  solution  from  the  perspective  of 
conservation of heritage.  Stringent adherence to these principles will not necessarily result in a 
solution that is good from an architectural or usability perspective.  Sound judgment and design 
skill  are  required  to  deploy  conservation  principles  with  imagination  and  artfulness.    The  best 
strengthening  solution  will  work  with  the  existing  material  to  complement  the  architectural 
character  with  a  minimum  of  impact.    There  may  never  be  a  perfect  solution  or  a  single  right 
answer; however, a solution that significantly works towards achieving the above goals can be 
considered to be a successful and effective intervention.  

C13.11 References 
Aplin, G. (2002) Heritage; Identification, Conservation & Management. Oxford University Press, 
Melbourne. 

Bowron,  G,  and  J.  Harris.  (1994)  Guidelines  for  Preparing  Conservation  Plans.  New  Zealand 
Historic Places Trust, Wellington, New Zealand. 

C13‐36   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Cattanach,  A.  G.,  Alley,  G.  W.  and  Thornton,  A.  W.  (2008)  “Appropriateness  of  seismic 
strengthening  interventions  in  heritage  buildings:  A  framework  for  appraisal”  Paper  30 
Presented at the 2008 New Zealand Society for Earthquake Engineering Conference, Napier, 
New Zealand, 11 – 13 April. 

Charleson,  A.  W.  (2008)  Seismic  Design  for  Architects:  Outwitting  the  Quake. 
Elsevier/Architectural Press, Amsterdam, Boston, London.  

Charleson, A. W. (2005) Structure as Architecture. Elsevier, Oxford.  

Charleson,  A.  W.,  Preston,  J  and  Taylor,  M.,  (2001)  “Architectural  expression  of  seismic 
strengthening.” Earthquake Spectra, 17(3), 417‐426. 

Ching, F. D. K. Architecture; form, space, and order. Hoboken, N. J., John Wiley & Sons, 2007. 

Christianson,  J.  (1983)  “State  Opera  House  –  upgrading.”  New  Zealand  Society  for  Earthquake 
Engineering Bulletin, 16(2), 175‐178. 

Croci,  G.  (2008)  The  Conservation  and  Structural  Restoration  of  Architectural  Heritage. 
Computational Mechanics Publications/WIT Press, Southampton, U.K.. 

DBH  (2004).  "Building  Act  2004."  The  Department  of  Building  and  Housing,  Wellington,  New 
Zealand. 

Derakhshan, H., Dizhur, D., Lumantarna, R., Cuthbert, J., Griffith, M. C. and Ingham, J. M. (2010) 
“In‐field simulated seismic testing of as‐built and retrofitted unreinforced masonry partition 
walls of the William Weir House in Wellington.” Journal of the Structural Engineering Society 
of New Zealand, ISSN 0114‐2879, 23(1), 51‐61. 

Dizhur,  D.,  Derakhshan,  H.,  Griffith,  M.  C.  and  Ingham,  J.  M.  (2011)  “In‐situ  testing  of  a  low 
intervention  NSM  seismic  strengthening  technique  for  historical  URM  buildings” 
International Journal of Materials and Structural Integrity (IJMSI), Submitted May 2010. 

Evans, D. S. (1983) “Strengthening of State Trinity Centre, Christchurch.” New Zealand Society for 
Earthquake Engineering Bulletin, 16(2), 162‐164. 

Feilden, B. M. (2003) Conservation of historic buildings. Architectural Press, Oxford, U.K.. 

FEMA.  (2003)  FEMA  397  Incremental  Seismic  Rehabilitation  of  Office  Buildings.  FEMA,  
Washington D.C. 

FEMA. (2004a) FEMA 398 Incremental Seismic Rehabilitation of Multifamily Apartment Buildings. 
FEMA, Washington D.C. 

FEMA.  (2004b)  FEMA  399  Incremental  Seismic  Rehabilitation  of  Retail  Buildings.  FEMA, 
Washington D.C. 

FEMA,  (2006a)  FEMA  454  Risk  Management  Series:  Designing  for  Earthquakes,  A  Manual  for 
Architects. FEMA, Washington D.C. 

FEMA, (2006b) FEMA 547 Techniques for the Seismic Rehabilitation of Existing Buildings. FEMA, 
Washington D.C. 

Gatley, J. (2008) “Salvation by works.” Architecture NZ, 2, 48‐58. 

  C13‐37
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

Goodwin,  C.  O.  (2008).  "Architectural  considerations  in  the  seismic  retrofit  of  unreinforced 
masonry  heritage  buildings  in  New  Zealand."  Master  of  Architecture,  M.  Arch  Thesis, 
Department of Architecture and Planning, The University of Auckland, New Zealand. 
Goodwin,  C.  O.,  Tonks,  G.  and  Ingham,  J.  M.  (2009).  "Identifying  heritage  value  in  URM 
buildings." Journal of the Structural Engineering Society New Zealand, 22(2), 16‐28.  

Holman,  S.  (2000)  Guidelines  for  developing  heritage  buildings.  New  Zealand  Historic  Places 
Trust, Wellington, NZ. 

ICOMOS  NZ.  (2010)  Charter  for  the  Conservation  of  Places  of  Cultural  Heritage  Value.  Revised 
2010, original text 1993. International Council on Monuments and Sites New Zealand (Inc). 
http://www.icomos.org.nz/nzcharters.html. 

Ismail,  N.,  Laursen,  P.  T.  and  Ingham,  J.  M.,  (2011)  “Seismic  performance  of  face  loaded 
unreinforced masonry walls retrofitted using post‐tensioning.” AJSE, In Press. 

Jandl,  H.  W.  (1988)  Preservation  Briefs  18  –  Rehabilitating  Interiors  in  Historic  Buildings; 
Identifying  and  preserving  Character‐Defining  Elements.  U.S.  Department  of  the  Interior, 
National Parks Service, Washington D.C. 

Jokilehto, J. (1986) A History of Architectural Conservation: The Contribution of English, French, 
German,  and  Italian  Thought  Towards  an  International  Approach  to  the  Conservation  of 
Cultural  Property 
<http://www.iccrom.org/pdf/ICCROM_05_HistoryofConservation00_en.pdf>  (6  August, 
2008). 

Jones,  M.  (2004)  “Campbell  Free  Kindergarten  (former),”  New  Zealand  Historic  Places  Trust 
Register  of  Historic  Places,  no.  7537: 
<http://www.historic.org.nz/Register/ListingDetail.asp?RID=7537&sm=> (26 October, 2008) 

Leuchars,  J.  M.  (1989)  “The  Use  of  Sprayed  Concrete  in  the  Strengthening  of  Earthquake  Risk 
Buildings.” New Zealand Society for Earthquake Engineering Bulletin, 22(3), 167‐171. 

Look, D. W., Wong, T. and Augustus, S. R. (1997) Preservation Briefs 41 – The Seismic Retrofit of 
Historic  Buildings;  Keeping  Preservation  in  the  Forefront.  U.S.  Department  of  the  Interior, 
National Parks Service, Washington D.C. 

Mack, R. C., FAIA, and J. P. Speweik. (1997) Preservation Briefs 2 – Repointing Mortar Joints in 
Historic  Masonry  Buildings.  U.S.  Department  of  the  Interior,  National  Parks  Service, 
Washington D.C.. 

Mahmood,  H.  and  Ingham,  J.  M.  (2011)  “Diagonal  compression  testing  of  FRP‐retrofitted 
unreinforced clay brick masonry wallettes.” ASCE Journal of Composites for Construction. In 
Press. 

McLean,  R.  (2010)  Seismic  Strengthening  –  Improving  the  Structural  Performance  of 
Heritage Buildings. New Zealand Historic Places Trust, Wellington, NZ.  

Nelson,  L.  H.  (1988)  Preservation  Briefs  17  ‐  Architectural  Character.  U.S.  Department  of  the 
Interior, National Parks Service, Washington D.C.. 

C13‐38   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

New Zealand Government. (1993). "Historic Places Act." Ministry for Culture and Heritage, ed., 
New Zealand Government, Wellington, New Zealand, Date of assent: 17 May 1993. 
NZSEE  (2006).  Assessment  and  improvement  of  the  structural  performance  of  buildings  in 
earthquakes: Recommendations of a NZSEE study group on earthquake risk buildings, New 
Zealand Society for Earthquake Engineering. 
Park,  S.  C.  (1997)  Preservation  Briefs  16  –  The  Use  of  Substitute  Materials  on  Historic  Building 
Exteriors. U.S. Department of the Interior, National Parks Service, Washington D.C.. 

Price,  N.  S.,  Talley,  M.  K.  and  Vaccaro,  A.  M.  (1996)  Historical  and  philosophical  issues  in  the 
conservation of cultural heritage. Getty Conservation Institute, Los Angeles. 

Robinson,  L.  and  Bowman,  I.  (2000)  Guidelines  for  Earthquake  Strengthening.  New  Zealand 
Historic Places Trust, Wellington, NZ.  

Russell,  A.  P.  (2010).  "In‐plane  seismic  assessment  of  unreinforced  masonry  buildings."  PhD 
thesis,  Department  of  Civil  and  Environmental  Engineering,  The  University  of  Auckland, 
Auckland, New Zealand. 
Russell,  A.  P.  and  Ingham,  J.  M.  (2010).  "Prevalence  of  New  Zealand's  unreinforced  masonry 
buildings." Bulletin of the New Zealand Society for Earthquake Engineering, 43(3), 192‐207. 
Russell,  A.  P.  and  Ingham,  J.  M.  (2008).  "Trends  in  the  architectural  characterisation  of 
unreinforced masonry in New Zealand" 14th International Brick/Block Masonry Conference, 
Sydney, Australia, 17 ‐ 20 February. 
Russell, A., J. Ingham, and M. Griffith. (2006) “Comparing New Zealand’s Unreinforced Masonry 
details  with  those  encountered  in  other  seismically  active  countries.”  7th  International 
Masonry Conference, London, U.K., 30 October ‐ 1 November. 

Rutherford  &  Chekene.  (1990).  “Seismic  retrofit  alternatives  for  San  Francisco’s  unreinforced 
masonry  buildings:  estimates  of  construction  cost  &  seismic  damage.”  San  Francisco,  CA. 
City  and  County  of  San  Francisco  Department  of  City  Planning  (prepared  by  Rutherford  & 
Chekene, Consulting Engineers). 

Schofield, H  A, Ingham, J. M. and Pampanin, S. (2006) “Critical earthquake risk detailing in New 
Zealand’s  multi‐storey  building  stock:  understanding  and  improving  the  current 
perception.” 2008 New Zealand Society for Earthquake Engineering Conference, Napier, NZ. 

Smith, I. C. (1979) “Our old buildings can be safe in earthquake (sic).” New Zealand Society for 
Earthquake Engineering Bulletin, 12(4), 289‐291. 

Taylor, J. M. (1983) “Cashfields Shopping Centre: Christchurch.” NZSEE Bulletin, 16(2), 172‐174. 

Taylor, M., Preston, J. and Charleson, A. (2002) Moments of Resistance. Arcadia Press, Sydney, 
Australia. 

Toomath,  W.  (1979)  “Some  Aspects  of  the  strengthening  of  earthquake  risk  buildings.”  New 
Zealand Society for Earthquake Engineering Bulletin, 12(4), 287‐288. 

Trapeznik, A. (2000) Common Ground? Heritage and Public Places in New Zealand. University of 
Otago Press, Dunedin, NZ. 

  C13‐39
 
  Section C13 ‐ Heritage Characteristics of URM Buildings
 
 

Weeks,  K.  D.  (1997)  Preservation  Briefs  14  –  New  Exterior  Additions  to  Historic  Buildings: 
Preservation Concerns. U.S. Department of the Interior, National Parks Service, Washington 
D.C. 

Wilby, G. K. (1983) “Redevelopment of the normal school: Cranmer Square, Christchurch.” New 
Zealand Society for Earthquake Engineering Bulletin, 16(2), 165‐171. 

C13‐40   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C14 ‐ Methods for Stiffening and Strengthening 
of Flexible Timber Floor and Roof Diaphragms 

C14.2 Scope 
Timber diaphragms in URM buildings are typically predicted to deform excessively during seismic 
loading  such  that  the  long‐established  principle  has  been  to  stiffen  and  strengthen  the 
diaphragm to reduce undesired deformation levels. This intervention is fundamentally based on 
the retrofitted diaphragm possessing the required strength to withstand imposed loads without 
yielding, and to effectively transmit lateral loads between the perimeter URM walls so that out‐
of‐plane  wall  failure  due  to  excessive  deformation  is  mitigated.  This  objective  is  particularly 
important  for  bi‐directional  ground  motions  where  no  wall  is  exclusively  oriented  in‐plane  or 
out‐of‐plane  and  a  rigid  diaphragm  is  highly  desirable  to  adequately  engage  the  URM  walls  as 
load collectors.  

However,  no  strategy  for  optimising  diaphragm  stiffness  and  strength  currently  exists  and  the 
particular impact that diaphragm retrofits have on global or local URM building seismic response 
mechanisms remain largely unknown. For this reason, the intervention techniques presented in 
this  section  shall  be  applied  with  a  degree  of  caution  as  not  to  adversely  affect  the  seismic 
performance of the URM building. Where possible, nonlinear time‐history analysis of complete 
URM building response to applied ground motion is recommended to determine the sensitivity 
of the structure to diaphragm modifications. Further reading on a proposed retrofit strategy of  
timber  diaphragms  for  the  performance‐based  retrofit  of  URM  buildings  can  be  found  in  
Brignola et al. (2008). 

The presented recommendations have been compiled from long‐standing engineering principles 
and  collaborative  judgement,  much  of  which  has  been  taken  from  Oliver  (2010)  and  which  is 
suggested as additional reading. Until future research provides the necessary guidelines for the 
control  and  optimisation  of  diaphragm  stiffness  and  strength,  the  guidelines  presented  in  this 
section serve as the most appropriate to achieve desired URM seismic performance. 

It  is  acknowledged  that  the  recommendations  outlined  in  this  section  predominantly  relate  to 
floor  diaphragms,  with  no  explicit  guidelines  provided  for  the  retrofit  of  timber  roofs.  As 
suggested in Section C8, many similarities exist between the configuration of timber floors and 
timber roofs, so the presented retrofitting guidelines are permitted to be appropriately applied 
to  roofs  at  the  designer’s  discretion.  Future  research  on  timber  floor  and  roof  retrofitting 
techniques  is  anticipated  to  provide  comprehensive  and  explicit  guidelines  for  each  of  these 
structural elements. 

C14.3 Retrofit Selection 
The selection of a diaphragm retrofitting technique needs to be a holistic decision that addresses 
all of the issues surrounding a URM building upgrade. Most obviously the diaphragm needs to 
meet  performance  requirements.  In  the  absence  of  optimal  strength  and  stiffness  targets, 

  C14‐1
 
  Section C14 ‐ Methods for Stiffening and Strengthening of Flexible Timber Floor and Roof 
Diaphragms 
 

timber diaphragms are conventionally designed with sufficient strength to resist lateral loading 
without yielding, and adequate stiffness to limit deformation to within limiting values. The level 
of performance improvement necessary may govern the retrofit material selected; for example, 
a  low  level  performance  increase  may  only  require  additional  light  wood  panelling,  whereas  a 
large performance increase may demand the incorporation of steel members.  

Many  URM  buildings  in  New  Zealand  are  protected  by  the  Historic  Places  Act  (1993)  that 
regulates  the  alteration  or  removal  of  heritage  structures.  This  restriction  adds  additional 
complexity to the retrofit selection process, as Structural Engineers may be limited to the level 
of modification that can be imposed on the diaphragm and surrounding URM structure during 
retrofitting. Examples of diaphragm protection include: 

 Retention  of  all  existing  diaphragm  materials  and  appearance  where  possible.  Some 
floor  section  removal  for  new  elevator  shafts,  stairwells  and  amenities  may  be 
permissible but otherwise is prohibited. 
 Retention of all existing diaphragm materials for architectural preservation. Appearance 
(sheathing)  may  be  permitted  to  be  altered,  but  for  the  possibility  that  future 
generations  would  show  interest  in  historic  construction,  floor  materials  may  be 
required to be retained. 
 No  restriction  to  diaphragm  alteration.  In  such  cases  the  existing  diaphragm  materials 
may be utilised, or be completed removed for new diaphragm construction. Typically, if 
the  existing joists are adequately tied into the  URM perimeter walls, then they can be 
cost‐effectively used as part of the new diaphragm system. 

Other factors such as available budget and practical issues, such as accessibility, may also affect 
diaphragm retrofit selection. It is recommended that a comprehensive case study of the entire 
URM  structure  be  completed  before  making  any  retrofitting  decisions.  Some  common 
diaphragm retrofitting methods, together with appropriate applications, are summarised below. 

Common Diaphragm Retrofitting Techniques 

Plywood  panelling  is  a  popular  and  cost‐effective  diaphragm  retrofit.  Given  that  existing 
diaphragms are almost always constructed of timber, the implementation of plywood and other 
timber members to strengthen the diaphragm is comparatively simple. In situations where the 
existing sheathing must be retained for aesthetic purposes, plywood sheets can be fastened to 
the  underside  of  the  floor  as  a  ‘ceiling’  diaphragm.  Plywood  overlays  can  be  used  when  it  is 
desired  to  retain  the  existing  timber  sheathing  but  appearance  is  not  restricted.  Where  no 
heritage  conditions  exist,  it  may  be  economical  to  completely  remove  the  existing  floorboards 
and replace with new plywood sheathing. 

Blocking must be considered for any plywood retrofit to effectively transfer shear flow between 
panels.  Conventional  blocking  involves  nailing  timber  framing  between  joists  along  plywood 
panel  boundary  lines.  This  method  is  appropriate  for  new  plywood  diaphragms  but  can  be 
problematic  when  the  existing  timber  sheathing  is  required  to  remain.  A  recommended 
alternative is stapled sheet metal blocking that can be fastened without excessive alteration to 
the existing diaphragm, as illustrated in Figure C14‐1(a). In this instance, light gauge sheet metal 

C14‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

strapping (75 mm x 24 gauge typical) is provided at plywood sheet edges and staples (92 Series 
typical)  are  used  to  fasten  the  plywood  to  the  blocking.  Diaphragm  strengthening  using  this 
technique  is  common  in  North  America  and  has  been  used  at  the  Auckland  Art  Gallery  and 
Christchurch Arts Centre Old Arts School as part of seismic refurbishment works. 

Another  retrofit  option  is  incorporation  of  steel  frames.  An  example  of  this  would  be 
incorporating a light steel frame in localised sections of a diaphragm where additional strength 
and  stiffness  is  required,  such  as  adjacent  to  stairwell  or  elevator  shaft  openings  (see  Figure 
C14‐1(b)). The primary concern with steel frame retrofits is its stiffness incompatibility with the 
existing  diaphragm  and  URM  walls.  It  is  crucial  that  a  steel  frame  retrofit  be  adequately 
connected into the existing structure so that uncoupled response is avoided.  

Other  retrofits  seen  around  the  world  include  meshing  the  existing  diaphragm  with  light  steel 
strapping  or  carbon  fibre‐reinforced  polymer  (CFRP)  strips  (see  Figure  C14‐1(c)),  although  the 
application of these intervention types in New Zealand URM buildings is unknown and in reality 
is likely to require further research in order to be a viable retrofitting option. Heavy steel frames 
or  reinforced  concrete  overlays  are  discouraged  as  retrofitting  techniques  because  experience 
has  shown  them  to  be  costly  and  invasive,  and  to  add  considerable  seismic  mass  to  the  URM 
structure with detrimental effects on overall seismic performance. 

   

  C14‐3
 
  Section C14 ‐ Methods for Stiffening and Strengthening of Flexible Timber Floor and Roof 
Diaphragms 
 

   
(a) Plywood overlay with stapled sheet metal  (b) Local light steel frame incorporated into 
blocking  plywood diaphragm 

(c) Meshing retrofit 

Figure C14‐1: Diaphragm retrofit examples 

Expected Retrofit Performance 

To  serve  as  a  reference  for  Structural  Engineers,  a  summary  of  an  experimental  program 
involving  the  in‐plane  cyclic  loading  of  full‐scale  timber  diaphragms  retrofitted  with  plywood 
overlays  is  presented  below  to  illustrate  the  expected  diaphragm  performance  when  using  a 
common retrofitting technique. 

A total of four retrofitted diaphragms measuring 10.4 m x 5.535 m were tested to establish their 
force‐displacement  response  to  lateral  loading.  The  testing  schedule  is  analogous  to  that 
outlined  in  Table  C3‐1  for  tested  as‐built  diaphragms.  All  retrofits  comprised  2400  mm  x 
1200 mm x 15 mm structural grade plywood laid over the existing floorboards with 75 mm x 24 
gauge sheet metal straps fastened to the plywood edges with ECKO SF‐9215 staples at 100 mm 
centres  to  act  as  blocking.  In  the  loading  direction  parallel  to  joists,  full‐depth  double  timber 
blocking was provided between the joists at the diaphragm edges for edge nailing and to act as a 
compression chord.  

C14‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

40 mm x 6 mm  steel  flat  was  fastened  to  the  full‐depth  blocking  with  10  gauge  screws  at 
100 mm centres to act as the tension chord member. In the direction perpendicular to joists, the 
two end joists were utilised as compression and tension chords. Field nailing (approximately 300 
mm centres) was applied to the plywood sheets at the locations of the joists, and all diaphragm 
edge nailing was spaced at 100 mm centres. All diaphragm nails were 90 mm x 3.15 mm power 
driven  nails.  Figure  C14‐2  provides  some  photographs  of  the  tested  retrofitted  diaphragms. 
Further  details  will  be  available  in  journal  articles  and  a  PhD  thesis  that  is  currently  being 
authored. 

The force‐displacement response for each retrofitted diaphragm is provided in Figure C14‐3. 

C14.4 Revised Diaphragm Assessment 
NZS 3603 (1993) can be used to design diaphragms strengthened with new plywood sheathing. 
Good references for the design of new plywood diaphragms include Buchanan (2007) and Smith 
et  al.  (1986).  For  other  retrofitting  techniques  any  rational  and  robust  method  to  determine 
stiffness and strength is permitted. 

The  necessary  techniques  to  revaluate  diaphragm  period,  seismic  loading  and  performance 
characteristics are provided in the suggested sections of this document. 

C14.5 Diaphragm Chord Design 
Tension  and  compression  forces  are  generated  when  a  diaphragm  deforms  laterally  under 
seismic  loading,  as  illustrated  in  Figure  C14‐4.  Chord  elements  are  structural  members  of 
diaphragms  that  are  oriented  perpendicular  to  the  imposed  seismic  loading  and  are  used  to 
resist  these  induced  tension  and  compression  forces.  Chord  members  are  required  at  each 
diaphragm  edge  and  often  adjacent  to  penetrations  to  resist  the  increased  stresses  at  these 
locations. 

   

  C14‐5
 
  Section C14 ‐ Methods for Stiffening and Strengthening of Flexible Timber Floor and Roof 
Diaphragms 
 

(a) Retrofit FS1b overview  (b) Blocking and steel chord 

(c) Retrofit FS3b overview  (d) Blocking construction 

Figure C14‐2: Photographs of tested retrofitted diaphragms 

Formal  diaphragm  chord  elements  are  usually  absent  in  existing  diaphragms,  and  must  be 
designed as part of any diaphragm retrofit. Diaphragm chord elements are typically detailed as 
elastically  responding  elements  by  following  capacity  design  procedures  or  using  nominally 
ductile (μ = 1.25) design loads. This procedure ensures that the chord members remain elastic 
even if the diaphragm is forced into the inelastic regime. 

Diaphragm  chord  elements  can  be  added  as  a  retrofit  intervention  into  existing  diaphragms 
relatively  easily.  Multiple  bays  of  existing  timber  joists  can  be  utilised  by  making  them 
continuous using nail plates and/or bolts. When new chord elements are required perpendicular 
to existing joists, new light gauge steel straps or steel flats nailed or screwed to timber blocking 
can be used. If a steel flat (often 30 – 40 mm x 4 – 6 mm) is required for large chord forces, it is 
recommended that double blocking be implemented to allow the steel flat to be fastened flush 
with the adjacent sheathing. 

C14‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

200 Retrofit 200 Retrofit


As-built As-built
150 150

100 100

50 50
Load (kN)

Load (kN)
0 0

-50 -50

-100 -100

-150 -150

-200 -200

-200 -150 -100 -50 0 50 100 150 200 -200 -150 -100 -50 0 50 100 150 200
Midspan displacement (mm) Midspan displacement (mm)

(a) Diaphragm FS1b  (b) Diaphragm FS2b 
250 250
Retrofit Retrofit
200 200
As-built As-built
150 150

100 100

50 50
Load (kN)

Load (kN)

0 0

-50 -50

-100 -100

-150 -150

-200 -200

-250 -250
-200 -150 -100 -50 0 50 100 150 200 -200 -150 -100 -50 0 50 100 150 200
Midspan displacement (mm) Midspan displacement (mm)

(c) Diaphragm FS3b  (d) Diaphragm FS4b 

Figure C14‐3: Full‐scale retrofitted diaphragm test results 

 
Figure C14‐4: Diaphragm chord schematic 

  C14‐7
 
  Section C14 ‐ Methods for Stiffening and Strengthening of Flexible Timber Floor and Roof 
Diaphragms 
 

C14.6 Subdiaphragm Design 
Diaphragm retrofit design may sufficiently increase diaphragm stiffness and strength to required 
levels  but  may  neglect  the  necessary  provisions  to  adequately  engage  this  improved 
performance. The subdiaphragm methodology is a design method whereby the main diaphragm 
is broken up into a number of smaller (sub) diaphragms at the diaphragm perimeter. The smaller 
subdiaphragms  are  designed  to  resist  the  amplified  out‐of‐plane  wall  anchorage  forces 
previously  described  in  Section  7  and  span  between  diaphragm  cross‐ties  which  are  typically 
provided at approximately 4‐5 m centres.  

Figure C14‐5 illustrates the subdiaphragm concept. Consider the building subject to an east‐west 
direction earthquake.  In  this instance it is recommended that  continuous diaphragm cross ties 
are provided between grid lines A and D. One design solution would be to provide closely spaced 
(i.e. 500 mm centres),  light‐gauge  sheet  metal  straps  with  timber  blocking  to  act  as  the 
diaphragm cross ties/struts across the width of the diaphragm. However such a design solution 
would likely be costly and intrusive to implement as part of a retrofit.  

An alternative design solution using the subdiaphragm concept would be to utilise the existing 
beams  to  act  as  the  diaphragm  cross  tie/strut  forces  and  then  provide  smaller  subdiaphragms 
that  span  horizontally  between  the  diaphragm  cross  ties/struts.  Consider  the  length  of  wall 
between  grid  lines  D5  and  D6.  As  shown  in  Figure  C14‐5,  a  smaller  subdiaphragm  could  be 
designed  to  span  between  grid  lines  5  and  6.  In  this  instance,  when  the  timber  joists  are 
orientated parallel to the wall, the existing joists are often found to be adequate to act as the 
subdiaphragm  chords.  The  depth  of  the  subdiaphragm  is  typically  increased  until  the  chord 
forces  are  sufficiently  reduced  that  the  existing  joists  are  adequate.  Alternatively  the  existing 
joists can be doubled up to increase their capacity. The sheet metal straps described in Section 
C11.5  can  be  used  as  subdiaphragm  cross  ties  to  transfer  the  amplified  out‐of‐plane  wall 
anchorage forces to the rear of the subdiaphragm. 

Once the subdiaphragm design is complete, checks should be made to ensure that the existing 
beams that are utilised to act as diaphragm cross ties/struts have adequate axial load capacity, 
and  that  their  end  connections  are  sufficient  to  transfer  the  necessary  diaphragm  cross  tie 
forces.  Referring  to  Figure  C14‐5  a  similar  strategy  can  be  used  for  the  north‐south  direction 
earthquake. In this direction the existing timber joists can be used as subdiaphragm cross‐ties. 
Note  that  in  this  direction  no  beams  are  available  to  act  as  diaphragm  cross  ties/struts.  As  an 
alternative, existing floor joists can be doubled up and made continuous to act as subdiaphragm 
cross ties/struts. Existing beams can often be utilised to act as the subdiaphragm chords. 

When  designing  subdiaphragm  elements  and  cross  diaphragm  ties  the  out‐of‐plane  wall  loads 
calculated in Section 7 should be used. Current design office practice is that these amplified out‐
of‐plane wall forces are considered to not act concurrently with those calculated in Section 4 for 
main diaphragm design. 

   

C14‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C14.7 Diaphragm Penetrations 
Penetrations  in  diaphragms  due  to  stair  openings,  elevators  shafts  and  service  risers  require 
special  consideration  to  ensure  that  diaphragm  performance  is  not  compromised.  Diaphragm 
penetrations  cause  stress  concentrations  which  can  lead  to  poor  diaphragm  behaviour  if  the 
openings are not addressed in the diaphragm design. 

For retrofits utilising plywood panels, the ‘shear transfer’ method (Smith et al. 1986) is a simple 
design  method  which  can  be  used  by  Structural  Engineers  to  determine  increased  nailing  and 
chord requirements adjacent to diaphragm openings. 

When diaphragm penetrations occur immediately adjacent to URM walls, structural steel beams 
can be used to provide the necessary out‐of‐plane restraint to the walls (refer Figure C14‐6). The 
beams should be tied back into the diaphragm using subdiaphragm cross ties. 

Figure C14‐5: Subdiaphragm example (from Oliver 2010) 

  C14‐9
 
  Section C14 ‐ Methods for Stiffening and Strengthening of Flexible Timber Floor and Roof 
Diaphragms 
 

Figure C14‐6: Typical Out‐of‐Plane Wall Support Detail at Diaphragm Opening (from Oliver 
2010) 

C14.8 Worked Example 
See Oliver (2010) for an example of how to stiffen and strengthen flexible floor diaphragms. 

C14.9 References 
Brignola,  A.,  Pampanin,  S.  and  Podesta,  S.  (2008).  "Evaluation  and  control  of  the  in‐plane 
stiffness of timber floors for the performance‐based retrofit of URM buildings." Bulletin of 
the New Zealand Society for Earthquake Engineering, 42(3), 204‐221. 
Buchanan, A. (2007). Timber Design Guide, University of Canterbury, Canterbury, New Zealand. 
New Zealand Government. (1993). "Historic Places Act." Ministry for Culture and Heritage, ed., 
New Zealand Government, Wellington, New Zealand, Date of assent: 17 May 1993. 
Oliver, S. J. (2010). "A design methodology for the assessment and retrofit of flexible diaphragms 
in unreinforced masonry buildings." SESOC Journal,  23(1) , 19‐49. 
Smith, P. C., Dowrick, D. J. and Dean, J. A. (1986). "Horizontal timber diaphragms for wind and 
earthquake  resistance."  Bulletin  of  the  New  Zealand  National  Society  for  Earthquake 
Engineering, 19(2), 135‐141. 
Standards Association of New Zealand (1993). NZS 3603:1993, Timber Structures. Standards New 
Zealand, Wellington, New Zealand. 
 

C14‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C15 ‐ Methods for Improving Wall Diaphragm 
Connections 
This section has been intentionally left blank. 

  C15‐1
 
  Section C15 ‐ Methods for Improving Wall Diaphragm Connections
 
 

This section has been intentionally left blank. 

C15‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C16 ‐ Unbonded Post‐tensioning 

C16.1 Notation 
a  Length of equivalent rectangular stress block at nominal strength level, m 
Abp  Area of bearing plate or block, m2 
Aps  Effective cross‐sectional area of tendon, m2 
bw  Wall thickness, m 
c  Distance from the neutral axis to the extreme compression fibre, m 
d  Effective depth, m 
D  Outer diameter of tendon, mm 
Em  Masonry modulus of elasticity, Pa 
Eps  Modulus of elasticity for post‐tensioning tendon, Pa 
f’m  Masonry compressive strength, MPa 
fps  Tendon stress at nominal strength limit state, MPa 
fpsi  Tendon stress after all losses, MPa 
fpu  Ultimate tensile strength of tendon, MPa 
fpy  0.1% proof tensile yield strength, MPa 
fr  Masonry modulus of rupture, MPa 
fse  Effective tendon stress after all losses, MPa 
he  Effective height of wall, m 
k  Parameter representing fraction of f’m  at hinge formation limit state 
kcr  Masonry creep parameter, µε/MPa 
kr  Tendon relaxation parameter, MPa/MPa 
ksh  Masonry shrinkage parameter, µε 
lw  Wall effective length, m 
M*  Required flexural strength, kNm 
Nb  Total Axial load at the base of the wall due to Nt, Ww and Apsfse, kN 
Nt  Overburden weight, kN 
Ppsi  Initial post‐tensioning force, kN 
vo*  Design out‐of‐plane pressure, MPa 
V*    Design shear force at section, kN 
Ww   Self weight of post‐tensioned wall, kN 
th
Xi     Distance of i  tendon from extreme compression fibre, m 

α  Parameter representing fraction of f’m at nominal strength limit state 
mv Shear Strength reduction factor 
mf Flexural Strength reduction factor
εmu  Maximum useable masonry strain, m/m 
εpu  Tendon strain at breakage, m/m 
εs  Tendon strain at nominal strength, m/m 
σn  Initial compressive stress at crack location, MPa 
θ  End rotation or storey drift, Radian 

  C16‐1
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 

Units shown are representative of typical unit conventions and units of calculated values should 
be established with respect to the units used for input parameters. 

C16.2 Scope 
One technique to improve the seismic performance of URM walls is to apply vertical unbonded 
post‐tensioning and experimental data used to validate design expressions have been reported 
previously  in  several  research  studies  (Al‐Manaseer  and  Neis  1987;  Ganz  and  Shaw  1997; 
Laursen  and  Ingham  2004;  Laursen  et  al.  2006;  Rosenboom  and  Kowalsky  2004;  Wight  and 
Ingham 2008; Wight et al. 2006; Wight et al. 2007; Bean Popehn et al. 2008; Ismail et al. 2011). 
Research  and  codification  of  post‐tensioned  masonry  originated  from  Switzerland  and  the 
United Kingdom, and over the last two decades significant research and development has led to 
the inclusion of criteria for the design of post‐tensioned masonry into several design codes, such 
as MSJC (2005) and NZS (2004).  

The  performance  of  post‐tensioned  URM  walls  depends  upon  the  initial  post‐tensioning  force, 
tendon type and spacing, restraint conditions, and the level of confinement. Post‐tensioning can 
either be bonded when tendons are fully restrained, by grouting the cavity, or left unbonded by 
leaving  cavities  unfilled.  Lateral  restraint  of  post‐tensioning  tendons  is  important  when 
considering  second‐order  effects.  Because  unbonded  post‐tensioning  is  reversible  to  some 
extent and has minimal impact on the architectural fabric of a building, the technique is deemed 
to  be  a  desirable  retrofit  solution  for  URM  buildings  having  important  heritage  value.  Only 
unbonded post‐tensioning is addressed by the provisions of Section 16. 

C16.2.1 Retrofit Procedure 
A post‐tensioning retrofit is applied either by placing post‐tensioning tendons into cored cavities 
located  at  the  centre  of  the  wall  or  by  placing  post‐tensioning  tendons  externally  at  discrete 
locations. The first procedure involves coring a cavity from the top of the URM wall right through 
to the foundations, then placing a tendon into the cored cavity and finally the application of a 
post‐tensioning  force  to  the  tendon.  From  discussions  with  specialised  local  construction 
contractors it was established that for the seismic retrofit of URM buildings, current techniques 
are capable of coring a cavity up to four stories with a precision of ±10 mm.  

Additioanlly,  discretely  located  external  unbonded  post‐tensioning  has  been  used  in  retrofit 
projects that avoided the coring operation and involved post‐tensioning URM walls using pairs of 
external  post‐tensioning  tendons  typically  located  at  wall  corners.  Figure  C16‐1(a)  shows  a 
photograph  of  the  coring  operation  being  performed  in  Auckland  on  a  heritage  URM  building 
and  Figure  C16‐1(b)  shows  discretely  located  post‐tensioned  strands  in  a  retrofitted  URM 
building  located  in  Christchurch.  Threaded  mild  steel  bars  are  post‐tensioned  by  using  a 
hydraulic jack which is removed after tightening of the nut that clasps the post‐tensioning bar, 
and  strands  are  post‐tensioned  using  a  hydraulic  jack,  with  the  taut  strand  clapsed  by  wedge 
interlocking  at  the  live  end  anchorage.  Figure  C16‐1(c)  and  C16‐3(d)  show  photographs  of  test 
walls being post‐tensioned using a threaded bar and a strand respectively. 

C16‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

   
(a) Coring Operation  (b) External Strands  (c) Bar  (d) Strand 
Post‐tensioning  Post‐tensioning 

Figure C16‐1: Post‐tensioning Retrofit Technique 

C16.2.2 Design Limit States 
In  order  to  interpret  the  seismic  behaviour  of  post‐tensioned  masonry  walls,  four  limit  states  
are defined (see Figure C16‐2), where first cracking is the limit state when the first crack appears 
and corresponds to wall performance in the elastic range; the hinge formation limit state occurs 
when the  upper and  lower wall segments start  to rotate and corresponds to the serviceability 
range;  the nominal  strength  limit  state;  and  the  failure  limit  state  corresponding  to  tendon 
yielding. The selection of a limit state for retrofit design is left to the discretion of the designer, 
and design equations for the nominal limit state are reported in the guideline. 

4
3
2
Total Lateral Force (kN)

1
1 - First Cracking
2 - Hinge Formation
3 - Nominal Strength
4 - Failure

Top Displacement (mm)


 
Figure C16‐2: Definition of Limit States 

C16.2.3 Retrofit Design Procedure 
Figure  C16‐3  shows  a  flow  chart  for  the  post‐tensioning  seismic  retrofit  design  procedure  of 
URM walls. 

  C16‐3
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 

Determine %NBS and 
if retrofit required.

Detailed URM 
assessment.

Out‐of‐plane retrofit  In‐plane retrofit design 
design of URM walls. of URM walls.

Calculation of  Calculation of 
Design Moment.   Design Moment.

Establish nominal tendon 
spacing and shear check.

Calculation of effective  Calculation of effective 
prestress, fse, and tendon  prestress, fse, and tendon 
stress at nominal strength  stress at nominal strength 
limit state, fps, and check  limit state, fps, and check 
within permissable limits. within permissable limits.

Select larger of out‐of‐
Select larger of the 
plane and in‐plane and 
calculated f ps values and 
check within permissable 
limits. If not, return to re‐
establish nominal tendon 
spacing and shear check
spacing and shear check.

Calculation of  Calculation of  Calculation of 


creep losses relaxation  shrinkage losses
losses

Calculation of 
initial post‐
tensioning force

Check for wall stress at 
wall bottom and at 
anchorage. If not ok, re‐
establish nominal 
tendon spacing and 
shear check.

Design 
complete
 
Figure C16‐3: Flowchart for Post‐tensioning Seismic Retrofit Design 

C16‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C16.3 Post‐tensioning Tendon Types, Stresses and Spacing 
Threaded steel bars are typically used for straight post‐tensioning over short distances and have 
relatively  lower  tensile  strength  than  strands.  Figure  C16‐1  shows  representative  experimental 
stress‐strain  plots  for  these  two  types  of  post‐tensioning  tendons.  The  greased  coating  of 
strands enables high corrosion resistance and lower frictional losses, which makes them an ideal 
choice  for  unbonded  post‐tensioning  application.  The  added  advantage  of  high  corrosion 
resistance  facilitates  the  use  of  unbonded  strands  for  external  post‐tensioning  applications  by 
locating  strands  at  discrete  locations,  typically  at  corners  of  flanged  or  buttressed  walls  (see 
Figure C16‐1(b)).  

  Strain (ratio)
  Strain (ratio)
0 0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0 0.01 0.02 0.03 0.04
Fpu = 67.2 kN
60 532 200 2020
Fpy = 58.2 kN Fpu = 289.2 kN
Fpy = 170.6 kN
0.1% Proof Strength

Stress (MPa)

Stress (MPa)
Total Force (kN)

45 399

Total Force (kN)


150 0.1% Proof Strength 1515

30 266 100 1010


Slope Eps = 181 GPa Slope Eps = 184 GPa
15 133 50 505
pu = 8.23 % pu = 4.33 %
0 0 0 0
0 1.0 2.0 3.0 4.0 5.0 6.0 7.0 8.0 0 1.0 2.0 3.0 4.0
Elongation (%) Elongation (%)

(a) Threaded Mild Steel Bar (D = 12 mm)  (b) Sheathed Greased Strand (D = 12.7 mm) 

Figure C16‐4: Typical Stress‐Strain Plots 

C16.3.1 Post‐tensioning Losses 
Current  post‐tensioned  masonry  codes  provide  guidelines  for  assessing  post‐tensioning  losses, 
with these losses typically attributed to shrinkage, creep, tendon relaxation, elastic shortening, 
seating,  undulation  of  tendon,  friction  and  thermal  effects.  Of  these  factors,  steel  relaxation, 
shrinkage and creep are the most important factors that will influence the design and longevity 
of  an  adequate  retrofit.  Testing  performed  in  previous  studies  (Krause  et  al.  1996;  Ganz  and 
Shaw  1997;  Laursen  et  al.  2006)  investigated  prestress  losses  occurring  in  post‐tensioned 
masonry  walls,  and  found  that  the  post‐tensioning  loss  was  mainly  attributable  to  the  use  of 
low‐strength  post‐tensioning  threaded  steel  bars,  whereas  modern  anchorages  and 
low‐relaxation  strands  have  been  proven  to  result  in  much  smaller  losses.  The  experimentally 
determined post‐tensioning losses in concrete masonry ranged from 20‐40% for strands and 25‐
55% for threaded steel bars (Laursen et al. 2006), whereas Ganz (1993) reported observed losses 
in clay brick masonry to be 7%, with 3% loss attributed to strand relaxation and 4% attributed to 
masonry  shortening  due  to  shrinkage  and  creep.  The  parameters  ksh,  kc,  and  kr  reported  in 
Section 16 were established from experimental work performed by Ganz (1993) and Laursen et 
al.  (2006)  and  MSJC  (2005)  suggested  values  of  creep  and  shrinkage  parameters  for  clay  brick 
masonry. 

  C16‐5
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 

C16.4 In‐plane Wall Behaviour  
The  failure  mode  of  URM  walls  when  subjected  to  in‐plane  seismic  excitations  depends  upon 
wall  aspect  ratio  and  the  characteristics  of  the  constituent  materials,  and  are  characterised  as 
either  flexural  controlled  or  shear  controlled  (see  Section  C8  for  details).  Sliding  and  rocking 
failure modes may allow considerable displacement capacity during seismic shaking, and subject 
to ensuring that collapse is avoided, these deformation modes may be tolerable to some extent. 
Therefore, a flexural/rocking controlled mode is instigated in this retrofit technique by applying 
a pre‐compression to the masonry wall. Figure C16‐5 shows a URM pier retrofitted using post‐
tensioning that is subject to a lateral force V* acting at a height he. The pier has a length lw and 
Nb is the axial load at the base of pier due to overburden weight, Nt, self weight of the pier, Ww, 
and effective post‐tensioning force after losses, Pe.  

  N t+Pe

V*
h

n
l

w  
Figure C16‐5: Post‐tensioned In‐plane Pier Definition and Stress Profile at Initial State 

C16.4.1 In‐plane Capacity at Nominal Strength Limit State 
At nominal strength the compression stress distribution becomes non‐uniform, which is typically 
approximated  by  an  equivalent  rectangular  compression  stress  block  idealisation  (see  Figure 
C16‐6). The equivalent stress block has a depth of αf’m and width a, where α is a constant and 
typically has a value of 0.85 (see Equation 2‐8) and f’m is the compression strength of masonry. 
The effective depth is d and the distance from the neutral axis to the extreme compression fibre 
is  denoted  by  c.  Predicting  the  seismic  response  of  a  post‐tensioned  URM  wall  at  the  nominal 
strength  limit  state  is  a  diligent  task  and  requires  accurate  estimation  of  maximum  useable 
masonry  strain  at  the  extreme  compression  fibre,  εmu,  and  increased  tendon  stress,  fps.  It  was 
found  in  an  experimental  investigation  on  URM  materials  (Lumantarna  2011)  that  due  to  the 
higher deformability of prevalent weak lime mortar used in historic URM construction, the strain 
values observed at nominal strength were inflated and much higher than that typically defined 
for URM i.e., 0.0035 (MSJC 2005). But to keep the wall displacement to a safe limit, the nominal 
strength for clay brick post‐tensioned masonry walls is defined herein as the point when the wall 

C16‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

in‐plane  drift  reaches  1.5%  i.e.,  θ =  0.015  (refer  Figure C16‐6)  and  the  corresponding  masonry 
strain value is termed as the maximum useable masonry strain.  

  e P
Nt +P+

V*

h
e

f
'
 m
a
c
l

w  
Figure C16‐6: Post‐tensioned In‐plane Pier Equilibrium at Nominal Strength Limit State 

C16.4.1.1 Tendon Stress at Nominal Strength Limit State 

Figure C16‐6 shows a post‐tensioned URM pier that is assumed to rock about the neutral axis, 
where the post‐tensioning tendon has an effective tendon stress fse and a modulus of elasticity 
Eps. The tendon stress at the  nominal strength increases due  to  tendon elongation and can  be 
presented as. 

  (C16‐1)

If  the  unbonded  length  of  tendon  is  equal  to  the  height  of  the  pier  and  the  rotation  value  is 
small, then εs can be estimated as, 

  (C16‐2)

Equation C16‐6 can be rewritten as, 

0.015 0.7
1   (C16‐3)

Where:  a  maximum  drift  of  1.5%  is  stipulated.  The  maximum  tendon  stress  should  be  taken 
smaller of 0.85fpy or 0.7fpu and as 0.7fpu is generally the smaller of these two calculated 
values, a maximum tendon stress of 0.7fpu is stipulated herein. By substituting Equation 
C16‐3 and values for constants α and β of 0.85 for both (typical in flexural design) into 
Equation C16‐1 yields,  

  C16‐7
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 

0.015 1 0.97    (C16‐4)

C16.4.2 In‐plane Capacity at First Cracking Limit State 
At first cracking limit state one end of the pier reaches zero stress and the other end reaches a 
stress of twice the initial masonry stress at the base of the pier (see Figure C16‐5). At the first 
cracking  limit  state  the  moment  capacity,  Mc,  is  evaluated  by  considering  the  equilibrium  of 
forces  (refer  Equation  C16‐5).  It  should  be  noted  that  the  masonry  modulus  of  rupture  is 
conservatively  assumed  to  be  zero.  Figure  C16‐7  shows  the  stress  profile  at  the  first  cracking 
limit state. 

  N t+Pe

V*
h

e
2

n
l

w  
Figure C16‐7: Post‐tensioned In‐plane Pier Equilibrium at First Cracking Limit State 

where   (C16‐5) 
6

C16.4.3 In‐plane Capacity at Hinge Formation Limit State 
The hinge formation limit state, also referred to as the serviceability limit state, is defined as the 
point at which the stress in the extreme compression fibre reaches a limiting stress of kf’m (see 
Figure  C16‐8),  where  k  is  a  parameter  and  has  a  recommended  value  in  NZS 4230:2004  (see 
Table C16‐1) ranging from 0.45 to 0.55.  

   

C16‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Table C16‐1: k Value for Moment Capacity Evaluation at Hinge Formation Limit State 

Stress Case  Load Category 

Category  I:  Permanent  Category  II:  Specified  Category  III: 


loads  with  variable  load  of  service  loads  for  Permanent  loads 
long  duration,  or  buildings  where  load  with  infrequent 
permanent  loads  with  category I  does  not  combinations  of 
frequently repetitive loads  apply  transient loads 

k  0.40  0.45  0.55 


 

By considering force equilibrium and assuming that 2fm < kf’m, Equation C16‐6 was developed to 
evaluate the moment capacity at the hinge formation limit state. 

4
3 where   (C16‐6)
6

  N t+Pe

V*
h


f
'


l
/
2
-
2
c
/
3

m
c

w
l

w  
Figure C16‐8: Post‐tensioned In‐plane Pier Equilibrium at Hinge Formation Limit State 

C16.4.4 In‐plane Test Results 
A  portal  frame  with  post‐tensioned  piers  (refer  to  Figure  C16‐9)  was  structurally  tested  by 
applying pseudo‐static cyclic in‐plane loading, and the observed performance of this unbonded 
post‐tensioned  URM  frame  (Ismail  2011)  was  compared  to  the  predicted  response  (refer  to 
Figure C16‐10(a) and C16‐10(b)).  

  C16‐9
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 
4424
380 1190 1228 1190 426

942
Average Spandrel

1710

Pier A Pier B

812

 
Figure C16‐9: Test Frame Dimensions 

Drift (%) Drift (%)


-2 -1.5 -1 -0.5 0 0.5 1 1.5 2 -2 -1.5 -1 -0.5 0 0.5 1 1.5 2
140 1,418
100 he = 2652 mm 265 he = 2652 mm
Ppsi = 56 kN Ppsi = 56 kN
Analogous Moment (kNm)

Tendon Stress (MPa)


Mn
Tendon Force (kN)

105 1,064
Lateral Force (kN)

50 133
f ps

0 0 70 709

-50 -133 35 354

-100 -265
0 0
-50 -25 0 25 50
-50 -25 0 25 50
Displacement (mm)
Displacement (mm)

(a) Force‐Displacement Plot  (b) Tendon Stress‐Displacement Plot 
Figure C16‐10: Calculated Vs Experimental Values  

As  the  testing  was  performed  immediately  after  the  application  of  the  post‐tensioning  force, 
post‐tensioning losses were minimal and were not considered in the analysis. Predicted flexural 
capacity  was  directly  compared  with  the  experimental  results  without  applying  a  strength 
reduction factor. 

C16.5 Out‐of‐plane Wall Behaviour  
The  out‐of‐plane  rocking  failure  mode  of  post‐tensioned  URM  walls  enables  utilisation  of  the 
same  concepts  of  flexural  controlled  limit  states  as  defined  in  Section  C16.2.2.  Figure  C16‐11 
shows a URM wall retrofitted using post‐tensioning, subject to an out‐of‐plane lateral uniformly 
distributed  seismic  force  vo*.  The  wall  has  a  pin‐to‐pin  height  he,  Nt  is  the  axial  load  due  to 
overburden weight, Ww is the self weight of the URM wall, and Pe is the effective post‐tensioning 
force. 

C16‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Nt +Pe Nt +Pe +P

v
o

h
/
2

h
/
2
e e
Pe +N t+0.5Ww Pe +P+Nt +0.5Ww

h
e
d

f
'
n m
a

b
w w

Stress Profile Stress Profile


b

b
w w
     
(a) Wall Loads                   (b) Wall Deformations 

Figure C16‐11: Post‐tensioned Out‐of‐plane Wall Definition and Stress Profile at Initial State 

Typically,  additional  axial  load  exacerbates  bending  stresses  in  URM  walls  as  the  wall  displace 
due to P‐Δ effects, whereas ensuring that tendons are laterally restrained eliminates additional 
P‐Δ effects because the line of action of the post‐tensioning force does not change with respect 
to the neutral axis of the wall (Ganz and Shaw 1997). 

C16.5.1 Out‐of‐plane Capacity at Nominal Strength Limit State 
Figure  C16‐12(a)  and  C16‐12(b)  show  the  strain  and  stress  profiles  at  mid‐height  of  an 
out‐of‐plane  loaded  post‐tensioned  URM  wall.  Maximum  allowable  masonry  strain  for  out‐of‐
plane loaded post‐tensioned URM walls is twice the value for in‐plane loaded walls. Therefore, 
the nominal strength for out‐of‐plane loaded post‐tensioned URM walls is defined herein as the 
point when wall the out‐of‐plane drift reaches 3% i.e., θ = 0.03 (refer Figure C16‐11(b)) and the 
corresponding masonry strain value is termed the maximum useable masonry strain.  
d

s 0.5Ww +Nt +Pe +P

0.5he  mu f'm
c

a
b

w w  
    (a) Strain Profile    (b) Stress Profile 

Figure C16‐12: Post‐tensioned Out‐of‐plane Wall at Nominal Strength Limit State 

  C16‐11
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 

C16.5.2 Out‐of‐plane Capacity at First Cracking and Hinge Formation Limit States 
Based on the same definitions of first cracking and hinge formation limit states as discussed in 
previous sections, Equation C16‐9 and  Equation C16‐10 were adapted for out‐of‐plane flexural 
capacities at the first cracking and the hinge formation limit states. It was established from the 
experimental results (refer results presented in Section C16.5.3) that the first crack appeared in 
out‐of‐plane loaded post‐tensioned walls when the resisting stress exceeded the sum of stress 
due to axial loads and the flexural strength of the masonry. 

  (C16‐9) 
6

4
3   (C16‐10) 
6

0.5
where:    

C16.5.3 Out‐of‐plane Test Results 
The  observed  performance  of  unbonded  post‐tensioned  URM  walls  in  out‐of‐plane  structural 
testing  performed  (Ismail  et  al.  2011),  was  compared  to  the  response  predicted  using  the 
equations  described  in  these  guidelines  and  were  plotted  in  Figure  C16‐13.  As  the  testing  was 
performed  immediately  after  the  application  of  a  post‐tensioning  force,  post‐tensioning  losses 
were minimal and were not considered in the analysis. Predicted flexural capacity was directly 
compared  with  the  experimental  results  without  applying  any  strength  reduction  factor.  Table 
C16‐2 gives the dimensions and post‐tensioning details of test walls that were used to validate 
the equations. 

   

C16‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Table C16‐2: Post‐tensioned Wall Dimensions and Post‐tensioning Details
Wall  he  lw  bw  Ww  f’m  Tendon  Post‐ fma/f’m 
(mm)  (mm)  (mm)  (kN)  (MPa)  type  tensioning  (ratio) 
Ppsi  fpsi 
(kN)  (MPa) 
ABO‐01  3760  1200  220  18.2  6.5  ‐  ‐  ‐  ‐ 

PTO‐02  3760  1200  220  18.2  6.5  S  50  506.6  0.19 

PTO‐03  3760  1200  220  18.2  6.5  S  70  709.2  0.27 

PTO‐04  3760  1200  220  18.2  6.5  S  100  1013.2  0.38 

PSO‐05  3900  1170  220  19.0  5.3  S  78  789  0.37 

PSO‐06  3366  1090  210  15.6  8.7  S  100  1013.2  0.38 

PBO‐07  3900  1170  220  19.0  5.3  B  50  442  0.24 


a
fm= (Pi+Nn)/(Abp) where Abp is the base plate area 

Drift (%) Drift (%)


-4 -3 -2 -1 0 1 2 3 4 -4 -3 -2 -1 0 1 2 3 4
15 140 1414
30 Wall Height = 3760 mm
Post-tensioning Force = 50 kN
Analogous Moment (kNm)

20 10 120 1212

Tendon Stress (MPa)


Tendon Force (kN)

Mn
Lateral Force (kN)

10 5
Mc 100 1010

0 0
80 808
Predicted Tendon Stress
-10 -5
60 606
-20 -10
Wall Height = 3760 mm ABO-01
PTO-02
-30 Post-tensioning Force = 50 kN -15
40
-80 -60 -40 -20 0 20 40 60
404
80
-80 -60 -40 -20 0 20 40 60 80 Displacement (mm)
Displacement (mm)

(a) Force‐Displacement Response for PTO‐2  (b) Tendon Stress History for PTO‐2 
Drift (%) Drift (%)
-4 -3 -2 -1 0 1 2 3 4 -4 -3 -2 -1 0 1 2 3 4
15 140 1414
30 Wall Height = 3760 mm
Mn Post-tensioning Force = 70 kN
Analogous Moment (kNm)

20 10 120 1212
Tendon Stress (MPa)
Tendon Force (kN)
Lateral Force (kN)

10 5
Mc 100 Predicted Tendon Stress 1010

0 0
80 808
-10 -5
60 606
-20
Wall Height = 3760 mm ABO-01 -10
PTO-03 40 404
-30 Post-tensioning Force = 70 kN -15 -80 -60 -40 -20 0 20 40 60 80
-80 -60 -40 -20 0 20 40 60 80 Displacement (mm)
Displacement (mm)

(c) Force‐Displacement Response for PTO‐3  (d) Tendon Stress History for PTO‐3 

  C16‐13
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 

Drift (%) Drift (%)


-4 -3 -2 -1 0 1 2 3 4 -4 -3 -2 -1 0 1 2 3 4
15 140 1414
30 Wall Height = 3760 mm
Mn Post-tensioning Force = 100 kN Predicted Tendon Stress

Analogous Moment (kNm)


20 10 120 1212

Tendon Stress (MPa)


Tendon Force (kN)
Lateral Force (kN)

Mc
10 5
100 1010
0 0
80 808
-10 -5
60 606
-20
Wall Height = 3760 mm ABO-01 -10
PTO-04
-30 Post-tensioning Force = 100 kN -15 40 404
-80 -60 -40 -20 0 20 40 60 80 -80 -60 -40 -20 0 20 40 60 80
Displacement (mm) Displacement (mm)

(e) Force‐Displacement Response for PTO‐4  (f) Tendon Stress History for PTO‐4 

Drift (%) Drift (%)


0 2 4 6 8 10 12 0 1.5 3 4.5 6 7.5 9 10.5 12
30 15
160 1616

Analogous Moment (kNm)


24 Predicted Nominal Strength 12

Tendon Stress (MPa)


Tendon Force (kN)
Lateral Force (kN)

Predicted Tendon Stress


120 1212
18 9

80 808
12 6

40 404
6 3
Wall Height = 3360 mm Wall Height = 3360 mm
Post-tensioning Force = 90.5 kN Post-tensioning Force = 90 kN
0 0 0 0
0 30 60 90 120 150 180 210 0 30 60 90 120 150 180 210
Displacement (mm)
Displacement (mm)

(g) Force‐Displacement Response for PSO‐5  (h) Tendon Stress History for PSO‐5 
Drift (%) Drift (%)
0 1.5 3 4.5 6 7.5 9 0 1.5 3 4.5 6 7.5 9
28 15 140 1414
Predicted Nominal Strength Predicted Tendon Stress
Analogous Moment (kNm)

12 120 1212

Tendon Stress (MPa)


Tendon Force (kN)

21
Lateral Force (kN)

9 100 1010
14
6 80 808

7 60 606
3
Wall Height = 4100 mm Wall Height = 4100 mm
Post-tensioning Force = 100 kN Post-tensioning Force = 100 kN
0 40 404
0 0 30 60 90 120 150 180 210
0 30 60 90 120 150 180 210
Displacement (mm)
Displacement (mm)

(i) Force‐Displacement Response for PSO‐6  (j) Tendon Stress History for PSO‐6 
Drift (%) Drift (%)
0 1.5 3 4.5 6 7.5 9 0 1.5 3 4.5 6 7.5 9
28 15 100 884
Analogous Moment (kNm)

12 80 707
Tendon Stress (MPa)
Tendon Force (kN)

21
Lateral Force (kN)

9 60 Predicted Tendon Stress 530


14
6 40 354
Predicted Nominal Strength
7
3 20 177
Wall Height = 4100 mm Wall Height = 4100 mm 
Wall Height = 4100 mm
Post‐tensioning Force = 50 kN
Posttensioning Force = 100 kN Post‐tensioning Force = 50 kN 
Posttensioning Force = 50 kN
0 0 0 0
0 30 60 90 120 150 180 210 0 30 60 90 120 150 180 210
Displacement (mm) Displacement (mm)

(k) Force‐Displacement Response for PBO‐7  (l) Tendon Stress History for PBO‐7 

Figure C16‐13: Calculated Vs Experimental Values 

C16‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C16.6 Design Example 
Design a post‐tensioned seismic retrofit for a URM wall that is two leafs thick 5.0 m long, and 3.2 
m high. Design action calculations were performed and an in‐plane shear force of V* = 88.6 kN 
and an out‐of‐plane uniform pressure of vo* = 5.8 kN/m2 were calculated for a maximum credible 
earthquake.  Masonry  material  properties  were  investigated  and  the  results  of  this  testing  are 
summarised in Table C16‐3. It was decided by stakeholders that post‐tensioning tendons will be 
placed into centrally located cored cavities. The overburden axial stress due to supported roof 
was calculated to be 0.5 kN/m. 

 
Table C16‐3: Masonry Materials 

Parameter  k c  ksh  f’b  f’j  f’m  fr  C  µf 

  µε/MPa  µε  MPa  MPa  MPa  MPa  MPa   

Value  10  0  39.4  1.4  10.7  0.09  0.1  0.47 

COV  ‐  ‐  28%  8%  33%  29%  ‐  ‐ 

C16.6.1 Establishing Tendon Spacing 
Maximum permissible tendon spacing = 0.4he = 1.28 m. So, use a spacing of 1.25 m and 4 equally 
spaced tendons. Table C16‐4 summarises the input parameters and Figure C16‐13 shows details 
of the URM wall that is being retrofitted. 

 
Table C16‐4: Input Parameters 

Parameter  lw  he  bw  fpy  fpu  Eps  kr  Nt 

  m  m  m  MPa  MPa  GPa    kN 

Value  5.0  3.2  0.22  1680  1875  180  0.03  2.5 

  C16‐15
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 

Po
Pe Pe Pe Pe P+P
o e

v*o
V*

0 0
0
2 0
3 2
3
6
2
5

1
2
5
0

15
20
00
5

1
2
5
0

6
2
5

2
2
0
0
 
Figure C16‐14: URM Wall Details 

C16.6.2 Calculating Required Capacity 
V* = 88.6 kN      In‐plane lateral force 

vo* = 5.8 kPa      Out‐of‐plane lateral pressure 

C16.6.2.1 Required In‐plane Capacity 
∗ ∗
      M* = 88.6 x 3.2 = 283.5 kNm 

C16.6.2.2 Required Out‐of‐plane Capacity 

l v∗ h
M∗
8

5.0 5.8 3.2


M∗ 37.1 kNm
8

C16.6.3 Calculating Tendon Stress at Nominal Strength 
It  was  established  from  the  preliminary  assessment  that  the  out‐of‐plane  strength  of  wall  is 
more critical than in‐plane strength, so is designed first in this instance. 

C16.6.3.1 Tendon Stress at Nominal Out‐of‐plane Strength 
a
M∗ ∅ N W nf A d
2
W 0.5γ b l h

Where: γ Density of Masonry = 18.0 kN/m3 

W 0.5 18.0 0.22 5.0 3.0 = 29.7 kN

C16‐16   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

N W 29.7 2.5 = 32.2 kN 

Using a permissible maximum tendon stress ate nominal strength = 0.7fpu, the nominal out‐of‐
plane flexural strength of the wall is established as, 

f 0.7f 1313 MPa and A 98.7 mm2 

f A 98.7 10 1313 10 = 129593.1.2 N or 129.6 kN

d 0.5b d 0.11 m

N W

65.9 4 129.6
0.012 m
0.85 10700 5.0

Substituting the values of a and d, equation for nominal strength yields, 
.
∅ M 0.85 65.9 4 129.6 0.11  = 51.65 kNm

As ∅ M M ∗ , fps assumed is sufficient to provide the wall required out‐of‐plane strength.  

C16.6.4 Calculating Effective Tendon Stress  
As  the  governing  mode  of  failure  is  out‐of‐plane,  the  calculation  of  post‐tensioning  force 
magnitude will be based on out‐of‐plane required tendon stress. 

d 0.11 m 
d f A
f f 0.03E 1 0.97  
h f′ d
0.11 1875 98.7
1176 f 5400 1 0.97  
3.2 10.7 5000 110
f 1176 185.6 1 0.030  = 996.0 MPa 

C16.6.5 Checking for In‐plane Strength 
First checking for cracking moment capacity of the wall, 

where

W γ b l h  

Where: γ Density of Masonry = 18.0 kN/m3

P 18.0 0.22 5.0 3.2 = 63.4 kN 

N W 63.4 2.5 = 65.9 kN 

  C16‐17
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 

65.9 4 98.3
 
220 5
0.417 MPa 

 
6
0.471 0.22 5 10
 
6
382.58 kNm 
∅ M 325.19 kNm M* = 283.5 kNm 

As ∅ M M ∗ , fps assumed is sufficient to provide the wall required out‐of‐plane strength. 

C16.6.6 Calculating Post‐tensioning Losses  

f f 3.7 0.55  

f f 0.18f     

f 0.82f    

996.0 0.82f    

f 1214.6 MPa < 0.7fpu = 1313 MPa  

So, the initial post‐tensioning force is within permissible limits. 

C16.6.7 Calculating Initial Post‐tensioning Force 
1214.6 98.7
P f A 119.9 kN 
1000

C16.6.8 Checking for Bearing Stress 
Let a bearing plate of 200 mm × 200 mm is used at anchorage. 

A 0.04m  

f A 98.7 10 1313 10 = 129593.1 N or 129.6 kN


f A 129.6
3.25 Mpa 
A 0.04

f, 10.7 MPa 
0.6f , 6.4 MPa 

As 0.6f , , so bearing stresses are in permissible limit. 

C16‐18   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

C16.7 References 
Al‐Manaseer, A. A. and Neis, V. V. (1987). “Load tests on post‐tensioned masonry wall panels.” 
ACI Structural Journal, 84(3), 467‐472. 

Bean  Popehn,  J.  R.,  Schultz,  A.  E.,  Lu,  M.,  Stolarski,  H.  K.  and  Ojard,  N.J.  (2008).  "Influence  of 
transverse  loading  on  the  stability  of  slender  unreinforced  masonry  walls,"  Engineering 
Structures, 30(10), 2830‐2839. 

Ganz,  H.  R.  (1993)  “Posttensioning  masonry  structures,”  VSL  International  Limited,  VSL  Report 
Series, Berne, Switzerland.  

Ganz,  H.  R.  and  Shaw,  G.  (1997)  “Stressing  masonry’s  future,”  Civil  Engineering  (New  York). 
67(1), 42‐45. 

Ismail, N., Lazzarini, D. L., Laursen, P. T., and Ingham J. M. (2011). “Seismic performance of face 
loaded unreinforced masonry walls retrofitted using posttensioning,” Australian Journal of 
Structural Engineering, In Press. 

Ismail,  N.  (2011).  “Selected  strengthening  techniques  for  the  seismic  retrofit  of  unreinforced 
masonry  walls.”  PhD  thesis,  Department  of  Civil  and  Environmental  Engineering,  The 
University of Auckland, Auckland, New Zealand. 

Krause, G. L., Devalapura, R., and Tadros, M. K. (1996). “Testing of Prestressed Clay‐Brick Walls.” 
1996 CCMS of the ASCE Symposium in Conjunction with Structures Congress XIV, Chicago, IL, 
United States, 15 ‐ 18 April. 

Laursen, P. T, and Ingham, J. M.  (2004). "Structural testing of large‐scale posttensioned concrete 
masonry walls." Journal of Structural Engineering, 130(10), 1497‐1505. 

Laursen, P. T., Wight,  G.  D. and Ingham, J.  M.  (2006). "Assessing creep and  shrinkage losses in 


post‐tensioned concrete masonry."  ACI Materials Journal, 103(6), 427‐435. 

MSJC.  (2005).  ACI  530‐05/ASCE  5‐05/TMS  402‐05  Building  code  requirements  for  masonry 
structures  and  specification  for  masonry  structures.  The  Masonry  Standards  Joint 
Committee, United States, 2005. 

Rosenboom,O.  A.,  and  Kowalsky,M.  J.  (2004).  "Reversed  in‐plane  cyclic  behavior  of 
posttensioned clay brick masonry walls." Journal of Structural Engineering, 130(5), 787‐798. 

Standards  New  Zealand.  (2004).  NZS  4230:  2004  Design  of  reinforced  concrete  masonry 
structures. Standards New Zealand, Wellington, New Zealand. 

Wight,  G.  D.,  and  Ingham,  J.  M.  (2008).  "Tendon  stress  in  unbonded  posttensioned  masonry 
walls at nominal in‐plane strength." Journal of Structural Engineering, 134(6), 938‐946. 

Wight, G. D., Ingham, J. M., and Kowalsky, M. J. (2006). "Shaketable testing of rectangular post‐
tensioned concrete masonry walls." ACI Structural Journal, 103(4), 587‐595. 

  C16‐19
 
  Section C16 ‐ Unbonded Post‐tensioning
 
 

C16‐20   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C17 ‐ Surface Bonded Fibre Reinforced Polymer 
Systems 

C17.2 Notation 
Afrp  Total FRP area intersected by the tension crack (mm2) 
bfrp  Total thickness of FRP system (mm) 
bw  Wall thickness (mm) 
d  Effective depth of masonry wall (mm) 
Efrp  FRP modulus of elasticity in the primary fibre direction (kN/mm2) 
f’m  Masonry compressive strength (N/mm2) 
f’tm  Masonry tensile strength (N/mm2) 
ffrpe  Effective stress in FRP system just before the nominal shear strength of the section is 
reached (N/mm2) 
hw  Wall height (mm) 
lw  Wall length (mm) 
nc  Number of FRP strips intersected by diagonal shear crack 
nt  Total number of strips in the FRP system 
s  Vertical spacing of FRP strips (mm) 
V*  Design shear force at section (kN) 
Vdt  Shear strength corresponding to diagonal tension failure mode (kN) 
Vfrp  Nominal shear strength contribution of FRP (kN) 
Vm  Nominal shear strength contribution of masonry (kN) 
Vn  Nominal shear strength of section (kN) 
Vs  Shear strength corresponding to bed‐joint sliding failure mode (kN) 
Vtc  Shear strength corresponding to toe crushing failure mode (kN) 
wfrp  Width of each FRP strip (mm) 
α  Angle between the FRP strip or primary fibre of continuous fabric and horizontal axis 
(degrees) 
frpe  Effective strain in FRP system just before the nominal shear strength of the section is 
reached 
frpu  Design FRP tensile rupture strain 
ϕ  Strength reduction factor for shear as in NZS 4230:2004 
frp  FRP reinforcement index 
ρfrp  Area reinforcement ratio 
ρfrph  Horizontal area reinforcement ratio 
ρfrpv  Vertical area reinforcement ratio 
ρfrpi  Inclined area reinforcement ratio 
   

  C17‐1
 
  Section C17 ‐ Surface Bonded Fibre Reinforced Polymer Systems
 
 

C17.2 Scope 
The scope of this guideline is limited to shear retrofit design for in‐plane loaded walls. For out‐
of‐plane loaded walls and in‐plane loaded walls deemed to fail in flexure, the reader is referred 
to other design documents (ACI 2010; CNR 2004; Galati et al. 2005; Garbin et al. 2007). 

Most  data  used  for  the  preparation  of  this  design  document  was  obtained  from  tests  on 
unreinforced clay brick masonry walls being either one leaf thick or two leaves thick. A limited 
number  of  previously  reported  tests  (Haroun  and  Mosallam  2002)  suggest  the  suitability  of 
extrapolating  the  recommendations  of  this  design  document  for  applications  to  thicker  walls, 
however  appropriate  strength  reduction  factors  are  recommended  for  walls  thicker  than  two 
masonry leaves.  

C17.3 General Design Information 
The strength reduction factor when using the nominal shear strength of FRP retrofitted systems 
shall be in accordance with Standards New Zealand (2004) and shall be taken as follows. 

∅ 0.75                         (C17‐1) 

C17.4 Shear Strength Provided by Fibre Reinforced Polymer 
FRP  materials  are  formed  by  the  impregnation  of  high‐strength  fibres  (generally  glass  fibres, 
carbon  fibres  or  aramid  fibres)  in  epoxy  resin.  For  retrofit  applications,  surface  bonded  FRP 
materials are available in two principal forms (see Figure C17‐1): 

   

(a) Fabric (glass)  (b) Plate (carbon) 

Figure C17‐1: Examples of FRP systems. 

1. Fabrics: A fabric is an assembly of high‐strength fibres, which is generally impregnated at site 
with  epoxy  to  form  FRP,  and  the  impregnated  fabric  is  then  bonded  to  the  wall,  which  is 
precured  with  epoxy.  The  fabric  systems  are  flexible,  and  available  in  the  form  of  long  sheets, 

C17‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

which are cut to continuous fabrics covering the whole substrate, or cut to long narrow strips. 
Both glass and carbon FRP fabrics are widely used in New Zealand. 

2. Plates: FRP plates are produced by pultrusion, which is an automated continuous system (and 
takes  place  in  an  industrial  unit)  involving  pulling  of  fibres  through  resin  system  into  a  heated 
die. FRP plates are applied to the substrate using epoxy. Carbon FRP plates are more common 
than glass FRP plates. 

In this design guide, the term ‘strip’ refers to long narrow elements of FRP, which could be either 
plates or strips cut out from fabrics. The term ‘continuous fabric’ refers to FRP fabrics covering 
the whole wall surface. 

FRP  behaves  linearly  until  its  sudden  rupture.  However  for  URM‐retrofitted  walls,  the  FRP 
system  rarely  reaches  its  rupture  (ultimate  or  maximum)  strength,  as  the  failure  usually  takes 
place due to debonding of FRP from the clay brick masonry (i.e. the loss of bond at the FRP‐wall 
interface).  Consequently,  the  peak  stress  assumed  in  retrofit  is  associated  with  the  product  of 
the FRP modulus of elasticity and the calculated effective strain. 

FRP systems can be applied in a number of orientations (see Error! Not a valid bookmark self‐
reference. and Figure C17‐3). Inclined FRP continuous fabrics are not common and are, hence, 
not included in this document. The following factors should be considered when designing FRP 
systems.  

1. Architectural/heritage concerns: 

(a) Is FRP to be  concealed within  mortar joints? If so, near surface  mounted FRP systems 


are to be designed (see Section 18). 
(b) Can FRP be applied on both wall faces? If yes, application of FRP on both wall faces is 
preferred  as  this  configuration  provides  equal  stiffness  and  prevents  wall  twisting  at 
higher  displacements.  Please  note  that  this  wall  twisting  can  be  useful  in  providing 
advanced  failure  warning.  FRP  must  be  applied  on  both  wall  faces  when  out‐of‐plane 
strength controls the wall retrofit design. 
(c) What percentage of wall area can be covered with FRP? If limitations exist, carbon FRP 
may be preferred over glass FRP, as generally lesser area is required when using carbon 
FRP due to the high stiffness of carbon FRP. 
(d) Is  FRP  required  to  be  to  be  painted?  Carbon  FRP  systems  are  more  visually  obtrusive 
due to their black colour than are glass FRP systems. 

2. Construction issues 

(a) The application of FRP plates is more time consuming than the application of FRP fabrics 
and  strips  because  FRP  plates  are  less  flexible  than  fabrics  and  strips  and  require  an 
almost plane substrate for their application. FRP fabrics and strips, being quite flexible, 
can better accommodate any substrate surface imperfections. 
(b) The  preparation  of  continuous  fabrics  requires  a  larger  floor  space  at  site  than  is 
required for FRP strips. 

   

  C17‐3
 
  Section C17 ‐ Surface Bonded Fibre Reinforced Polymer Systems
 
 

(a) Strips              (b) Continuous fabric 

Horizontal FRP systems 

(a) Strips               (b) Continuous fabric 

Combined horizontal‐vertical FRP systems 

      (a) Uniaxial strips                     (b) Biaxial strips 

Inclined FRP systems 

Figure C17‐2: Examples of non‐vertical FRP retrofit systems. 

 
(a) Strips              (b) Continuous fabric 

   
Figure C17‐3: Examples of vertical FRP retrofit systems. 

C17‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

3. Cost 

(a) Carbon FRP is more expensive than glass FRP. 
(b) Cost of application of strips is higher than the cost of application of continuous fabrics. 
New Zealand FRP applicators generally prefer continuous fabrics rather than  strips, as 
the  application  of  continuous  fabrics  involves  minimal  fabric  cutting  and  less  surface 
preparation.  Also,  the  installation  of  plates  is  more  cumbersome  (see  note (a)  under 
‘construction issues’). 

4.  Strength 

(a) Carbon FRP systems are stiffer and stronger than glass FRP systems. 
(b) Inclined  plates  are  greatly  effective  in  increasing  shear  strength  of  URM  walls.  Such 
systems  also  result  in  high  stiffness,  and  are  suitable  when  high  system  strength  and 
low displacements are desired. 
(c) Use  of  a  number  of  FRP  strips  is  preferred  rather  than  only  a  single  strip,  as  multiple 
strips add to redundancy of the system.  
(d) Combined  horizontal‐vertical  systems  are  recommended  as  compared  to  only 
horizontal systems.  
(e) If  inclined  FRP  systems  are  to  be  used,  it  is  better  to  use  FRP  along  both  the  wall 
diagonals. Such an arrangement is also useful for cyclic earthquake loads. 
(f) Where  possible,  FRP  systems  should  be  extended  a  distance,  ld,  beyond  the  wall  (see 
Figure C17‐4) to the adjacent structural members (floor, spandrels, window openings). 
If  such  extension  is  not  possible,  FRP  systems  should  be  mechanically  anchored  along 
the perimeter. Mechanical anchors could be in the form of (i) fibre anchors, which are 
inserted into the wall through the fabrics and left to dry, or (ii) reinforcing bars, which 
are inserted into precut wall grooves after the application of fabrics. Other systems are 
also available. Further information is available from manufacturers. The distance ld can 
be calculated as follows: 

                (CNR 2004)  (C17‐2)
2

Where: f’tm is the average tensile strength of masonry, and may be assumed equal to 0.1f’m in 
the absence of test data.    

The design of FRP systems has been presented in this guideline for an increase in shear strength 
only. Seismic retrofit design involves other parameters in conjunction with shear strength, such 
as ductility, stiffness, energy dissipation and toughness. Guidance for these parameters can be 
obtained from experimental research, where required. 

Recommendations herein have been developed from basic principles and experimental results, 
with  guidelines  obtained  from  procedures  presented  in  ACI  (2010)  and  Garbin  et  al.  (2007). 
Experimental results reported in the literature for surface bonded FRP‐retrofitted clay brick URM 
elements  (Mahmood  and  Ingham  2011;  Alcaino  and  Santa‐Maria  2008;  Elgawady  et  al.  2007; 

  C17‐5
 
  Section C17 ‐ Surface Bonded Fibre Reinforced Polymer Systems
 
 

Wei, et al. 2007; Stratford et al. 2004; Wang et al. 2006; Chuang 2004; Santa‐Maria et al. 2004; 
Haroun  and  Mosallam  2002;  Valluzzi,  et  al.  2002)  have  been  included  for  the  formulation  of 
these design expressions. Other reported tests were not included due to missing data (To‐Nan, 
et al. 2006; Seki, et al. 2008). A flowchart presenting the design procedure for Surface Bonded 
FRP systems is given in Figure C17‐5. 

 
Figure C17‐4: FRP continuous fabric system extended ld beyond the top of the doors. The 
vertical FRP system was designed for the pier between the two doors. 

C17.4.1 Limitations 
FRP is considered ineffective in increasing shear strength of a URM wall that is likely to fail by toe 
crushing failure (ACI 2010). Hence, the provisions of this design guide apply only to walls that are 
likely to fail in a shear‐controlled mode.  

FRP horizontal strips and continuous fabrics may be of limited use in walls which are prone to 
horizontal sliding due to weak mortar and low axial load, as horizontal crack may not intersect 
any FRP strip. 

C17.4.2 General Expression for Non‐Vertical FRP Retrofit Systems 
An  expression  for  Vfrp  is  developed  from  the  truss  analogy  (Figure  C17‐6)  by  considering  a 
number  of  parallel  FRP  strips,  oriented  at  an  angle    to  the  wall  base,  and  crossing  a  45o 
diagonal tension crack in a URM wall loaded by a horizontal in‐plane force as shown. The wall 
has a length, lw, greater than the wall height, h. The shear force resisted by FRP strips is equal to 
the sum of the horizontal components of the tensile forces developed in the strips in accordance 
with Equation C17.3. 

cos   (C17‐3)

Where:  Afrpi  is  the  cross‐sectional  area  of  each  FRP  strip  with  a  vertical  spacing,  s,  ffrpe  is  the 
effective tensile stress in each strip, and nc is the number of strips intersecting the crack 
and can be calculated from the geometry (see Figure C17‐6):   

C17‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Compute V*

Compute Vm = min (Vs, Vdt, Vtc)

V*>Vm V*≤Vm
Check if FRP retrofit can be  Retrofit not 
designed required

Does a shear‐controlled failure mode control? 
i.e Vs or Vdt < Vtc

If yes, design  If no, explore a different 
FRP retrofit retrofit technique

(Vfrp)required = V*/ Vm

Assume a retrofit system and compute Vfrp in accordance with section 15.5. Use 
horizontal strips only if diagonal tension failure mode controls. If (Vfrp)provided. ≥
(Vfrp)required, OK, else redesign.

Compute Vn = [Vm + (Vfrp)provided]

Check Vn ≥ V*

If no, redesign If yes, check, Vn < Vtc

If yes, design is  If no, redesign or explore a different retrofit 
complete. technique.

 
Figure C17‐5: FRP design flowchart 

  C17‐7
 
  Section C17 ‐ Surface Bonded Fibre Reinforced Polymer Systems
 
 

 
Figure C17‐6: Truss analogy for FRP‐retrofitted URM wall 

tan   (C17‐4)

Or 

1 tan
  (C17‐5)

Where: s is the vertical spacing of FRP strips. 

It can be shown that for a wall section with lw < hw,  

1 tan
  (C17‐6)

Hence, the general expression for nc is 

1 tan
  (C17‐7)

Where: d is the effective wall depth, and is computed using Equation C17‐8. 

C17‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

min ,   (C17‐8)

nc must not exceed the total number of FRP strips, nt, comprising the FRP system. Hence, 

1 tan
,   (C17‐9)

The area of each strip, Afrpi, is computed as in Equation C17‐10. 

  (C17‐10)

Where: bfrp is the thickness of each FRP strip, and wfrp is the width of each FRP strip. 

Substituting Afrpi in Equation C17‐3 gives Equations C17‐11. 

cos   (C17‐11)

Equation  C17.11  is  similar  to  the  expression  presented  in  ACI  (2010).  However  ACI  (2010) 
presents expressions only for horizontal or combined horizontal‐vertical strip systems.  

For horizontal continuous fabrics, the total width of the strips intersected by the diagonal crack 
(ncwfrp) can be replaced in Equation C17.11 with the length of the continuous fabric intersected 
by the diagonal crack  √2 . For horizontal FRP retrofit systems, =0. Hence, for horizontal FRP 
continuous fabric systems, Equation 17.11 can be written as: 

√2   (C17‐12)

Or 

1.4   (C17‐13)

Effective  FRP  stress  has  been  related  in  the  available  literature  to  the  FRP  area  reinforcement 
ratio,  FRP  thickness,  FRP  modulus  of  elasticity,  masonry  compression  strength  and  masonry 
tensile strength. A comparison of major FRP design guidelines was performed, and it was found 
that the ACI (2010) expression resulted in the most consistent predicted values. The ACI (2010) 
model  relates  effective  stress  to  FRP  area  reinforcement  ratio,  FRP  modulus  of  elasticity  and 
masonry compression strength, with the product expressed as the FRP reinforcement index. The 
effective stress has also been indirectly related to FRP thickness by limiting the product of FRP 
thickness and effective FRP stress to 260 N/mm. The relation of effective stress to FRP thickness 
has  also  been  reported  in  CNR  (2004),  where  the  effective  FRP  stress  is  considered  to  be 
inversely  proportional  to  the  square  root  of  FRP  thickness.  Thus,  for  the  same  area  of 

  C17‐9
 
  Section C17 ‐ Surface Bonded Fibre Reinforced Polymer Systems
 
 

reinforcement,  thinner  (and  greater  number  of)  FRP  strips  are  likely  to  be  more  efficient  than 
thicker (and hence fewer) FRP strips. 

The  ACI  (2010)  model  was  modified  for  various  retrofit  systems  using  basic  principles,  and 
effective strain values were obtained from reported tests involving FRP and clay brick masonry 
walls  (Figure  C17‐7).  Combined  horizontal‐vertical  systems  generally  provide  higher  shear 
strength  than  exclusively  horizontal  systems,  however  only  limited  data  was  available  for 
combined  horizontal‐vertical  system,  and  effective  strain  values  for  horizontal  systems  were 
adopted for combined horizontal‐vertical systems. For simplicity, only one conservative effective 
strain relationship was presented for various non‐vertical FRP systems. 

 
2.5
Experimental values
Horizontal
2.0 Horizontal-vertical
Inclined

1.5
fe (%)

1.0

Trendline
0.5

0.0
0.0 0.5 1.0 1.5 2.0

 
Figure C17‐7: Plot showing the relationship between fe and  

Typical thickness, bfrp, design rupture strain, frpu, and modulus of elasticity, Efrp, values for 
different FRP systems are given in Table C17‐1.    

C17‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Table C17‐1: Typical values of FRP thickness, design rupture strain and modulus of 
elasticity. 

System  Thickness,  Design rupture  Modulus of elasticity, Efrp 


bfrp  strain, frpu 

mm  (%)  kN/mm2 

Glass FRP fabric  0.25 – 1.3  1.3 – 2.2  15 –25 

Carbon FRP fabric  0.25 – 1.0  0.85 – 1.3  28 – 85 

Glass FRP plate  1.4 – 1.9  2.2  41 

Carbon FRP plate  1.2 – 2.0  0.45 – 1.7  140 – 300 

C17.4.3 Vertical FRP Retrofit System 
Equations for non‐vertical FRP systems cannot be applied to vertical strips as s = ∞. Hence the 
expression proposed by Garbin et al. (2007) has been adopted as follows: 

(a) For FRP strips:   

  (C17‐14)

(b) For continuous FRP fabrics: 

  (C17‐15)

Relatively little data is available for shear strength enhancement using vertical FRP systems, and 
hence a constant effective strain value is proposed. 

C17.5 Design Examples 
Examples are presented here to illustrate use of the design procedure that is detailed in Section 
17. 

C17.5.1 Example 15.1 
Design an FRP retrofit system for a URM wall, measuring 5000 mm long x 2800 mm high x 225 
mm thick. The factored shear force, V* = 180 kN. Any FRP reinforcement can be used, however 
the reinforcement must be provided on one wall face only. It has been determined that the wall 
is likely to fail by the formation of diagonal shear cracks. 

f’m = 10 N/mm2 

  C17‐11
 
  Section C17 ‐ Surface Bonded Fibre Reinforced Polymer Systems
 
 

Vs = 225 kN; Vdt = 174 kN; Vtc = 253 kN 

Vm = min (Vs, Vdt, Vtc) = min (225, 174, 273) = 174 kN 

ϕV 0.75 174 150.5 kN  


V* (180 kN) > ϕVm (150.5 kN) design shear reinforcement. 

As  the  wall  is  likely  to  fail  in  a  shear‐controlled  (diagonal  tension)  mode,  FRP  shear 
reinforcement can be designed. 
V∗ ϕV 180 150.5
V 66 kN 
ϕ 0.75
Wall properties: 

lw = 5000 mm 

hw = 2800 mm 

bw = 225 mm 

FRP reinforcement properties: 

Use 50 mm wide, 1.2 mm thick CFRP strips oriented in the horizontal direction. Horizontal strips 
can be used because diagonal tension failure is the controlling failure mode. 

frp = 0.017 = 1.7% 

Efrp = 165 kN/mm2 

ffrpu = 2800 N/mm2 

tfrp = 1.2 mm 

s = 500 mm (trial) 

wfrp = 50 mm 

Number of strips, nt =  5.6   = use 6 strips 

2800 300 300


s 440 mm 
5
6 1.2 50
0.0005714 
225 2800

Reinforcement index,  0.0005714 0.30 


Effective stress, ffrpe, is computed as; 

         

where 

1 0.50 0.15
min 0.9 , 0.3    
100 0.08 for 0.15

C17‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

frpe = minimum of [(0.08(0.30)‐0.9)/100, 0.3 x 0.017) 

       = minimum of [0.0024, 0.0051] = 0.0024 

ffrpe = (0.0024) (165000) = 390 N/mm2 

bfrp ffrpe = (1.2) (390) = 468 N/mm > 250 N/mm = use 250 N/mm 

1 tan ,  

d = min (lw, hw) = 2800 mm 

 = 0 

nt = 6 
2800
1 tan 0 , 6  
440
6.4, 6  
 = 6 

cos        

Putting values 

V 6 250 50 cos 0 75000N  

= 75 kN > (Vfrp)required (66 kN) OK 

Vn = Vm + Vfrp 

= 150.5 + (0.75 × 75) = 187 kN < Vtc (0.75 x 273 = 205 kN) OK 

Figure C17‐8: FRP retrofit for wall in Example 15.1 

  C17‐13
 
  Section C17 ‐ Surface Bonded Fibre Reinforced Polymer Systems
 
 

C17.5.2 Example 15.2 
Design the following piers in the front wall of the two‐storey high URM building shown in Figure 
C17‐9.  

(1) A  typical  pier  between  any  two  window  openings  on  the  upper  floor.  The  pier  measures 
1000 mm long x 2000 mm high x 200 mm thick. V* = 20 kN 
(2) The pier between the door openings on the ground floor. The pier measures 2000 mm long 
x 2200 mm high x 300 mm thick. V* = 80 kN 

FRP reinforcement can be applied on either face of the piers. f’m = 14 N/mm2. 

(1) A typical pier between two upper piers 

Vs = 30 kN; Vdt = 19.4 kN; Vtc = 9.9 kN 

Vm = min (Vs, Vdt, Vtc) = min (30, 19.4, 9.9) = 9.9 kN 

Vm = 0.75 × 9.9 = 7.4 kN 

V* (20 kN) > Vm (7.4kN), shear reinforcement is required. However, as it was determined that 
the wall will fail by toe crushing, FRP reinforcement cannot be designed, and an alternate retrofit 
system is required. 

 
Figure C17‐9: FRP retrofit for building in Example 15.2 

C17‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

(2) The pier between the doors on the ground floor 

Vs = 90 kN; Vdt = 155 kN; Vtc = 158 kN 

Vm = min (Vs, Vdt, Vtc) = min (90, 155, 158) = 90 kN 

Vm = (0.75) (90) = 67.5 kN 

V* (80 kN) > Vm (67.5 kN) Design shear reinforcement. 

As the wall is likely to fail in a shear‐controlled (bed‐joint sliding) mode, FRP shear reinforcement 
can be designed. Provide vertical reinforcement on one face only to inhibit joint sliding. 

  

(Vfrp)required = (V* ‐ Vm)/  = (80 – 67.5)/0.75 = 16.7 kN 

Pier properties: 

lw = 2000 mm 

hw = 2200 mm 

bw = 300 mm 

FRP reinforcement properties: 

As  a  relatively  smaller  increase  in  shear  strength  is  required,  low‐strength  GFRP  continuous 
fabrics can be used. 

frp = 0.022 = 2.2% 

Efrp = 26.1 kN/mm2 

ffrpu = 575 N/mm2 

bfrp = 0.35 mm 

For continuous FRP fabrics: 

min 0.001,0.05             

frpe = minimum of [0.001, 0.05 x 0.022] = minimum [0.001, 0.0011]  

= 0.001 

                 

ffrpe = (0.001) (26.1) (1000) = 26.1 N/mm2 

bfrp ffrpe = (0.35) (26.1) = 9.1 N/mm < 80 N/mm, OK 

               

V 9.1 2000 18200N  

  C17‐15
 
  Section C17 ‐ Surface Bonded Fibre Reinforced Polymer Systems
 
 

= 18.2 kN > (Vfrp)required (16.7 kN) OK 

Vn = Vm + Vfrp 

= 67.5 + (0.75 × 18.2) = 81.2 kN < Vtc (0.75 x 158 = 103.5 kN) OK 

C17.6 References 
ACI (2010). Guide for the design and construction of externally bonded fiber‐reinforced polymer 
systems  for  strengthening  unreinforced  masonry  structures  (ACI440.7R‐10),  American 
Concrete Institute, Farmington Hills, MI. 
Alcaino,  P.,  and  Santa‐Maria,  H.  (2008).  "Experimental  response  of  externally  retrofitted 
masonry  walls  subjected  to  shear  loading."  Journal  of  Composites  for  Construction,  12(5), 
489‐498. 
CNR.  (2004).  “Guide  for  the  design  and  construction  of  externally  bonded  FRP  systems  for 
strengthening existing structures (CNR‐DT 200/2004)”. Rome, Italy: Advisory Committee on 
Technical Recommendations for Construction. 
Chuang,  S.  (2004).  “Seismic  retrofitting  techniques  for  existing  unreinforced  masonry 
structures.” PhD Thesis. School of Geoscience Minerals and Civil Engineering, University of 
South Australia. Australia 
Elgawady,  M.  A.,  Lestuzzi,  P.,  and  Badoux,  M.  (2007).  "Static  cyclic  response  of  masonry  walls 
retrofitted  with  fiber‐reinforced  polymers."  Journal  of  Composites  for  Construction,  11(1), 
50‐61. 
Galati, N., Garbin, E., Tumialam, G., Nanni, A. (2005). “Design guidelines for masonry structures: 
out  of  plane  loads.”  Proc.,  7th  International  Symposium  on  Fiber‐Reinforced  Polymer  (FRP) 
Reinforcement for Concrete Structures (FRPRCS‐7), Kansas City, USA, 269‐288. 
Garbin,  E.,  Galati,  E.,  Nanni,  A.,  Modena,  C.,  and  Valluzzi,  M.  R.  (2007).  "Provisional  design 
guidelines for strengthening of masonry structures subject to in‐plane loading." Tenth North 
American Masonry Conference (10NAMC) St. Louis, MO., 3‐6 June 2007 
Grando, S., Valluzzi, M. R., Tumialan, J. G., and Nanni, A. "Shear strengthening of URM clay walls 
with  FRP  systems."  Proc.,  6th  International  Symposium  on  Fibre‐Reinforced  Polymer  (FRP) 
Reinforcement  for  Concrete  Structures  (FRPRCS‐6),  World  Scientific  Pub  Co  Inc,  Singapore, 
1229‐1238. 
Haroun,  M.  A.,  &  Mosallam,  A.  S.  (2002).  “Cyclic  shear  test  of  multi‐wythe  existing  brick  wall: 
retrofitted  by  a  single  layer  of  TYFO  SEH‐51A  applied  on  one  side.”  San  Diego,  California: 
University of California, Irvine and California State University, Fresno. 
Mahmood,  H.,  and  Ingham,  J.  M.  (2011).  "Diagonal  compression  testing  of  FRP‐retrofitted  clay 
brick masonry wallettes." ASCE Journal of Composites for Construction, In Press. 
Russo, S., Gottardo, R. and Codato, D. "Effect of FRP mesh reinforcement on shear capacity and 
deformability  of  masonry  walls."  Proc.,  6th  International  Symposium  on  Fibre‐Reinforced 
Polymer  (FRP)  Reinforcement  for  Concrete  Structures  (FRPRCS‐6),  World  Scientific  Pub  Co 
Inc, Singapore, 1239‐1248. 
Santa‐Maria, H., Duarte, G., and Garib, A. (2004). "Experimental investigation of masonry panels 
externally strengthened with CFRP strips and fabric subjected to in‐plane shear load." Proc., 
Thirteenth  World  Conference  on  Earthquake  Engineering  (15WCEE),  Canadian  Association 
for Earthquake Engineering and International Association for Earthquake Engineering (IAEE), 
Vancouver, Canada, Paper no. 1627. 

C17‐16   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Seki,  M.,  Vacareanu,  R.,  Saito,  T.,  Cotofana,  D.,  Lozinca,  E.,  Popa,  V.  and  Chesca,  A.  B.  (2008). 
"Cyclic  shear  tests  on  plain  and  FRP  retrofitted  masonry  walls."  Proc.,  14th  World 
Conference on Earthquake Engineering (14WCEE), International Association for Earthquake 
Engineering, Beijing, China. 
Standards  New  Zealand  (2004).  NZS4230:2004  ‐  Design  of  reinforced  concrete  masonry 
structures, Stanards New Zealand, Wellington, New Zealand. 
Stratford, T., Pascale, G., Manfroni, O., and Bonfiglioli, B. (2004). "Shear strengthening masonry 
panels  with  sheet  glass‐fiber  reinforced  polymer."  Journal  of  Composites  for  Construction, 
8(5), 434‐443. 
To‐Nan,  C.,  Ja‐Shian,  C.,  Yen‐Chih,  L.,  and  Yu‐Chun,  L.  (2006).  "Performance  of  URM  walls 
strengthened  with  CFRP  under  horizontal  cyclic  loading."  First  European  Conference  on 
Earthquake  Engineering  and  Seismology  (1st  ECEES),  European  Association  of  Earthquake 
Engineering and European Seismological Commission, Geneva, Switzerland, 3‐8 September 
2006, Paper no. 299. 
Valluzzi,  M.  R.,  Tinazzi,  D.,  and  Modena,  C.  (2002).  "Shear  behavior  of  masonry  panels 
strengthened by FRP strips." Construction and Building Materials, 16(7), 409‐416. 
Wang,  Q.,  Chai,  Z.,  Huang,  Y.,  Yang,  Y.  and  Zhang,  Y.  (2006).  "Seismic  shear  capacity  of  brick 
masonry wall reinforced by GFRP." Asian Journal of Civil Engineering, 7(6), 563‐580. 
Wei, C. Q., Zhou, X.  G., & Ye, L. P.  (2007). “Experimental study of masonry  walls strengthened 
with CFRP.” Structural Engineering and Mechanics, 25(6), 675‐690. 
 

 
 

  C17‐17
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C18 ‐ Near Surface Mounted (NSM) Fibre 
Reinforced Polymer Systems 

C18.1 Notation 
ad  Demand acceleration (units of ‘g’, acceleration normalised by acceleration of gravity) 
Ap  Cross‐sectional area of FRP, mm2 
bf  Width of the groove cut, mm 
bp  Width of FRP strip, mm  
c  Depth of compression block (neutral axis location), mm 
Cm  Masonry compressive force, kN 
df  Depth of the groove cut, mm 
(EA)p  Axial stiffness of the FRP, MPamm2 
Ep   Modulus of elasticity of FRP, MPa 
Em  Masonry modulus of elasticity, MPa 
f’b  Average brick compressive strength, MPa 
f’bl  Lower characteristic brick compressive strength, MPa 
fd  The (minimum) design compressive stress on the bed joint at the cross‐section under 
consideration, MPa 
f’fb  Characteristic flexural bond strength of masonry, MPa 
f’m  Masonry compressive stress, MPa 
f’up  FRP tensile strength, MPa 
fut  Brick rupture strength, MPa 
Lper  Perimeter of the debonding failure plane, mm 
PIC  Axial force in the FRP required to cause the onset of intermediate crack (IC) debonding 
in clay masonry, kN 
Prupture  Tensile rupture capacity of FRP, kN 
Mch   Horizontal bending capacity of the URM wall, kNm/m 
M*  Design moment at section, kNm 
Mn  Nominal moment resistance of wall section, kNm  
Nt  Overburden weight, kN 
Nn  Nominal axial compression force, kN 
V*  Design shear force at section, kN 
Vdt  Shear resistance corresponding to diagonal tension failure mode, kN 
Vjs  Shear resistance corresponding to joint sliding deformation mode, kN 
Vm  Nominal shear resistance contribution of masonry, kN 
Vn  Nominal shear resistance of section, kN 
Vnsm  Effective shear resistance of NSM FRP, kN 
Vtc  Shear resistance corresponding to toe compression failure mode, kN 
s   Design strip spacing, m 
tb  Distance from edge of strip to edge of groove cut, mm 
td  Distance from edge of strip to edge of groove cut, mm 

  C18‐1
 
  Section C18 ‐ Near Surface Mounted (NSM) Fibre Reinforced Polymer Systems 
 
 

tm  Thickness of URM wall, m 
Tp   FRP tensile force, kN 
tp  Thickness of FRP strip, mm 
wd  Uniformly distributed load, kN/m 
z  Lever arm, mm 
Zd  Section modulus of the bedded area , mm3/m 
Zu  Lateral section modulus of the masonry units, in cubic mm per m length based on the 
gross cross‐section 
γ  Specific weight of masonry, kN/m3 
db  FRP debonding strain 
m  Masonry strain  
φ  Strength reduction factor for flexure 
φch  Strength  reduction  factor  for  horizontal  bending  of  masonry  in  accordance  with 
AS 3700 
f   Failure plane aspect ratio  

C18.2 Scope 
Using fibre reinforced polymer (FRP) material to retrofit URM walls is an established technique 
for  strengthening  and  increasing  the  ductility  capacity  of  URM  walls  subjected  to  in‐plane  and 
out‐of‐plane  earthquake  loading.  Externally  bonded  (EB)  FRP  sheets  or  plates  (Section  17)  and 
near‐surface  mounted  (NSM)  FRP  bars  or  strips,  are  the  two  application  techniques  that  are 
commonly used. Using the NSM technique provides several advantages over EB reinforcement 
which  include:  significantly  higher  axial  strain  at  debonding,  protection  from  fire  and  the 
environment,  minimal  impact  upon  the  aesthetics  of  the  structure  (Goodwin  et  al.  2009),  and 
reduced  construction  time  (Seracino  et  al.  2007;  Petersen  et  al.  2009),  thus  providing  a  cost 
effective and minimally‐invasive option for seismically strengthening URM buildings. 

A  sound  understanding  of  the  bond  behaviour  between  concrete  and  FRP  has  been  achieved 
following extensive research (Stone et al. 2002; Hassan and Rizkalla 2003), and reliable analytical 
models have been established (Seracino et al. 2007). Initial experimental validation of NSM FRP 
as  a  technique  for  seismic  improvement  of  URM  buildings  involved  laboratory  testing  that 
focused  on  strengthening  single  leaf  modern  masonry  walls,  and  based  on  these  experimental 
results an analytical model that predicts the masonry to FRP bond behaviour was developed by 
Willis et al. (2009b). The model was further verified by extensive experimental testing of multi‐
leaf historic clay brick masonry full scale laboratory built walls and on walls tested in‐situ (Dizhur 
et al., 2010a, Dizhur et al. 2010b, Dizhur et al. 2010c, Dizhur et al. 2010d). 

The NSM technique involves insertion of FRP strips. Typically a 15 mm wide × 1.2 mm thick strip 
is positioned in a vertical groove that is cut into the wall so that it extends over the entire height 
of the wall. Epoxy is used to bond the FRP strip into the masonry substrate. To ensure maximum 
bond  area  the  groove  is  typically  entirely  filled  with  epoxy  prior  to  insertion  of  the  CFRP  strip 
(typical installation procedure is illustrated in Figure C18‐1). 

C18‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

  
  

(a) Groove cutting  (b) 15 mm wide  (c) Epoxy  (d) Groove pointing 


CFRP strips  application 
Figure C18‐1: NSM CFRP retrofit application 

C18.3 Retrofit Parameters 
Table  18‐1  indicates  the  key  material  properties  used  for  the  design  of  FRP  reinforcement  in 
unreinforced  masonry  walls  when  subjected  to  out‐of‐plane  bending,  for  the  most  commonly 
used CFRP, unless otherwise provided by the FRP supplier. 

 
Table 18‐1: Typical values of material properties for CFRP 

Parameter  Carbon FRP 

Modulus of elasticity of CFRP, Ep  165 x 103 MPa 

Tensile strength of CFRP, fup  2700 MPa 

C18.4 In‐plane Design 

C18.4.1 Shear Resistance Provided by NSM CFRP 
This section has been intentionally left blank 

C18.5 Out‐of‐plane Design 

C18.5.1 General Design Information 
The  design  process  for  a  URM  wall  strengthened  with  vertical  CFRP  strips  is  based  on  the  aim 
that  the  preferred  wall  behaviour  will  be  governed  by  the  onset  of  intermediate  crack  (IC) 
debonding  in  clay  brick  masonry  of  the  FRP  strip,  rather  than  the  development  of  alternative 
more brittle failure modes, such as CFRP rupture, horizontal bending failure of masonry between 
vertical  FRP  strips,  or  masonry  crushing.  The  methodology  presented  is  generic  for  either  FRP 
material (Carbon CFRP or Glass GFRP) and therefore final selection of the FRP material is at the 

  C18‐3
 
  Section C18 ‐ Near Surface Mounted (NSM) Fibre Reinforced Polymer Systems 
 
 

discretion  of  the  design  engineer.  The  usual  flexural  theory  design  assumptions  for  the  cross‐
sectional analysis of a FRP reinforced section are: 

(a)   Plane sections remains plane after bending; 

(b)   Full composite action exists between the CFRP strip and the masonry interface (i.e. no slip 
or opening‐up at the interface); and, 

(c)   The  tensile  resistance  of  the  masonry  is  neglected  (i.e.  the  FRP  does  not  contribute  to 
strength until the masonry has cracked). 

The design process for earthquake (or wind) loading depends on the horizontal acceleration (or 
wind pressure) that the wall is subject to in the out‐of‐plane direction. The usual flexural theory 
design for the cross‐sectional analysis of a FRP reinforced section applies, as illustrated in Figure 
C18‐2. 

tm  tm 
Nt 

εm≤0.001 
fmc Tp=ApEpεdb 
c  z
εdb 
Cm 
 
 
(a) Strain profile  (b) Cross‐sectional  forces  
Figure C18‐2: Stress and strain profile 

C18.5.2 Resistance of NSM FRP on Tension Surface of Loading 

C18.5.2.1 Horizontal Spacing 

The horizontal spacing, s, of the vertical FRP reinforcement is selected so that the strengthened 
URM wall does not fail in horizontal bending between strips due to inertial load. The horizontal 
bending  capacity  of  the  URM  wall  per  metre  of  wall  height,  Mch, is  calculated  using  Equations 
18‐5 to 18‐7 as adopted from the Australian Standard on Masonry Structures (AS 3700:2010). AS 
3700:2010 refers to a perpend spacing factor, kp, and three section moduli: the section modulus 
of the bedded area, Zd, the lateral section modulus of masonry units, Zu, and the lateral section 
modulus based on the contact area of the perpend joints, Zp. The equations are presented in a 
simplified form where Zp is approximated to equal Zd and dimensions of a typical clay brick found 
in New Zealand were used to calculate kp = 0.95.  

C18.5.2.2 Analytical Prediction Model 

Prediction  of  the  flexural  strength  of  NSM  FRP  retrofitted  URM  walls  is  based  on  an  existing 
generic analytical model that was initially developed by Seracino et al. (2007) for concrete and 

C18‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

later modified by Willis et al. (2009b) for use with modern clay brick masonry. The axial force in 
the FRP strip required to cause the onset of intermediate crack (IC) debonding in clay masonry, 
PIC, is given by Equation C18‐1 (Willis et al. 2009b). The accuracy of this model has been verified 
against 29 pull tests by Yang (2006), 34 pull tests by Dizhur (2011) and full scale laboratory‐built 
and  in‐situ  wall  tests  (Willis  et  al.  2009a,  Dizhur  et  al.  2010a).  Due  to  the  widespread  use  of 
compressive strength of clay brick, f’b, by design engineers the equation is expressed in terms of 
f’b by back substituting into Equation C18‐1 the MacGregor (1988) relationship given in Equation 
C18‐2. From experimental observations td and tb are taken as 1 mm. 

.
.
0. 988   (C18‐1) 
0.53

0.53   (C18‐2) 

Substituting Equation C18‐2 into C18‐1, 

. .
0. 988   (C18‐3)

Simplifying Equation C18‐3, 

. .
  (C18‐4)

C18.5.2.3 Neutral Axis Location 

The neutral axis location, c, is solved in accordance with Equation C18‐5, using Equation C18‐6 to 
satisfy  axial  force  equilibrium  and  Equation  C18‐7  corresponding  to  plane  sections  remaining 
plane.  Masonry  strains  are  assumed  to  be  elastic  such  that  an  elastic  masonry  compression 
stress distribution is appropriate.  

  (C18‐5)

N
 
1 (C18‐6)
2

 
2 (C18‐7)
3

Where: the lever arm,     (see Figure C18‐2) 

For simplicity, it is assumed for the NSM strip that the level of embedment is small compared to 
tp. Therefore the neutral axis location, c, may be approximated by substituting Equation C18‐7 
into C18‐6 to give: 

  C18‐5
 
  Section C18 ‐ Near Surface Mounted (NSM) Fibre Reinforced Polymer Systems 
 
 

4 (C18‐8)
 
2

Use  ≅   to give   
3

2
Where    and   

See Figure C18‐3 for the out‐of‐plane design procedure. 
 

Determine M*

Select strip 
spacing, s

No  Calculate Mch 
and check 

Select strip 
cross‐section, 
calculate PIC

Check if PIC is less  No 
than tensile 
rupture capacity

Calculate neutral 
axis location, c

No  Check masonry 
compressive 
stress

Calculate vertical 
bending 
capacity, Mn

No 
ΦMn  > M*
 

C18‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Figure C18‐3: Out‐of‐plane design procedure 
 

C18.6 Other Considerations 
Vertically oriented NSM FRP strips can be placed either through the brick units or the perpend 
joints.  Due  to  aesthetics  and  ease  of  placement  it  is  likely  that  in  most  applications  the  strip 
would be run through the perpend joints. However, it should be noted that positioning vertical 
NSM FRP strips through the perpend joints can cause a reduction in bond strength in the order 
of  10%.  However,  this  level  of  strength  reduction  may  be  deemed  insignificant  given  the 
beneficial effects of the relative ease of placement (i.e. cutting through half the number of brick 
units) and the reduced aesthetic impact. 

C18.6.1 Failure Modes 
There are three typical modes of failure: gradual debonding of the CFRP strip from the substrate, 
a sudden CFRP strip pull‐out, and shear failure of masonry as illustrated in Figure C18‐4.  

 
(a) Debonding  (b) Sudden pull‐out 

Figure C18‐4: Typical wall failure mechanisms 

C18.6.2 Experimental Results 
In addition to experimental tests described in Section C18.5.2, NSM CFRP retrofitted walls were 
tested by applying lateral face pressure using a system of inflatable airbags (Dizhur et al. 2010a), 
with  the  typical  test  setup  is  illustrated  in  Figure  C18‐5.  The  pressure  in  the  airbag(s)  was 
increased until visible cracking within the vicinity of the CFRP strip occurred, with a typical crack 
pattern that resulted being shown in Figure C18‐4(a). All walls were loaded and unloaded several 
times  to  examine  if  repeated  loading  resulted  in  stiffness  degradation.  The  total  lateral  load  – 
mid‐height  displacement  response  for  laboratory‐built  and  in‐situ  tested  walls  are  shown  in 
Figure C18‐6. The effective wall face pressure was calculated as the total measured lateral force 
sensed by the load cells, divided by the wall total area. All walls exhibited ductile behavior with 
the  exception  of  AH2,  where  a  sudden  debonding  of  the  CFRP  strip  occurred  (Dizhur  et  al. 
2010c).  

  C18‐7
 
  Section C18 ‐ Near Surface Mounted (NSM) Fibre Reinforced Polymer Systems 
 
 

(a) Two vertical CFRP  (b) Single CFRP strip 
strip retrofit (wall R1)  retrofit (wall R2) 
   

 
(c) Typical test setup for  (d) Failure at maximum 
cyclic out‐of‐plane  loading (wall R4) 
testing (wall R3) 
 
Figure C18‐5: Experimental program 

   

C18‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

30 20
R4-R 6
R4-A

Total lateral load (kN)


Total lateral force (kN)

Face pressure (kPa)


Face pressure (kPa)
Prediction 4
20
4
10
2
10 2 AT-A
AT-R
Prediction
0 0 0 0
0 80 160 0 80 160
Mid-height displacement - Δ (mm) Mid-height displacment - Δ (mm)
 
(a) Wall R4 – one direction (b) Allen’s Trade Complex
30 6 1.5
WB-A
WB-R (moderate damage) 6
Total lateral force (kN)

WB-R (severe damage)

Total lateral force (kN)


Face pressure (kPa)

Face pressure (kPa)


Prediction
20 4 1
4

10 AH-R
2 2 0.5
AH-A
Prediction

0 0 0 0
0 60 120 0 40 80
Mid-height displacement - Δ (mm) Mid-height displacement - Δ (mm)  
(c) Wintec Block F (d) Avon House, AH1
 

18
Total lateral force (kN)

AH2-R
4
Face pressure (kPa)

AH2-A
12 Prediction

6 2

0 0
10 60 110
Mid-height displacement - Δ (mm)
 
(e) Avon House,
  AH2

Figure C18‐6: Experimental results of NSM CFRP wall testing 

C18.7 Design examples  

C18.7.1 Example 18.1 
In‐plane design example 

This section has been intentionally left blank 

  C18‐9
 
  Section C18 ‐ Near Surface Mounted (NSM) Fibre Reinforced Polymer Systems 
 
 

C18.7.2 Example 18.2 
Design  an  out‐of‐plane  NSM  FRP  retrofit  system  for  a  URM  wall,  measuring  5000 mm  long  x 
2800 mm high x 225 mm thick (2 leaf). The seismic acceleration is 1.0g with no axial forces acting 
on the wall. The wall is to be strengthened using CFRP strips. Determine the required size and 
spacing of the strips.  

Wall properties and material properties obtained from in‐situ testing:  

Compressive strength of masonry, f’m     = 8 MPa 

Compressive strength of brick, f’b      = 25 MPa 

Flexural bond strength of masonry, f’fb    = 0.1 MPa 

Masonry modulus of elasticity, Em    = 2.5 GPa 

Length of wall, L      = 5000 mm 

Height of wall, H      = 2800 mm 

Width of wall, t      = 225 mm 

CFRP reinforcement properties: 

CFRP Modulus of Elasticity, Ep      = 165 GPa 

CFRP tensile strength, fup      = 2700 MPa 

Weight of wall      = 16 kN/m3 × 2.8 m × 5 m × 225 mm = 50.4 kN    
Horizontal seismic force      = 1.0 × 50.4 kN = 50.4 kN or 18 kN/m 

Design moment, M* 


18 2.8
17.6  
8 8

Calculate horizontal bending strength of wall per metre height of wall: 

1000 225
8437500  /  
6

as there is no mortar pointing in the masonry wall) 

Using equation 18‐5: 

1.9∅ 1  

0
1.9 0.6 √0.1 1 8437500 10 3.0 /  
0.1

C18‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Using equation 18‐6: 

3.8∅  

3.8 0.6 √0.1 8437500 10 6.1 /    

Using equation 18‐7: 

∅ 0.44 0.56  

′ 0.13 ′ 0.13 25 3.25      (as given in equation (2‐1) section 2.4.2) 

0.6 0.44 3.25 8437500 0.56 0.1 8437500 10 7.5 /  

Therefore horizontal bending strength per metre height of wall is: 

3.0, 6.1, 7.5 3.0 /


 

8 8 3.0
2500  
1.0 0.225 16

Try 15 mm × 1.2 mm CFRP strips embedded into 6 mm × 25 mm grooves 

. .
 

Where: Lper is calculated as:  

≅4 2 4 2 15 1.2 35.2  

and φf is calculated as: 

1 1 15
≅ 5 
2 2 1.2

. .
5 25 35.2 165 10 1.2 15 10 35.2  

Check that PIC is less than the tensile rupture capacity of the CFRP strip, Prupture (=fup Ap) 

2700 15 1.2 10 48.6  

Assume strip spacing of 1250 mm centre to centre. 

  C18‐11
 
  Section C18 ‐ Near Surface Mounted (NSM) Fibre Reinforced Polymer Systems 
 
 
.
=  0.125 16 0.225 6.3  

Solve for the neutral axis location, c: 

35.2 10
0.012 
165 10 1.2 15

2 2 35.2 6.3 10
2.21 
0.012 2.5 10 1250

4 2.21 √2.21 4 2.21 225


21.2  
2 2

Check that the masonry compressive stress is less than the masonry strength capacity, f’m 
21.2
0.012 0.0012 
225 21.2
0.0012 2.5 10 2.86 ′ 8 ∴  

Calculate the vertical bending capacity of the FRP reinforced wall, Mn.  
21.2
≅ 225 217.8  
3 3

35.2 6.3 218.5 10 9.0  

0.6 9.0 5.4  

.
Therefore number of strips required  3.26 ∴ 4  
.

Spacing of strips = 5000/4 = 1250 mm  < 2500 mm   ∴ OK 

Adopt 15 mm × 1.2 mm CFRP strips embedded into 6 mm × 25 mm grooves spaced at 
1250 mm centres on both sides of the wall.  

C18‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

15 mm x 1.2 mm CFRP strips embedded


into 25 mm x 6 mm grooves spaced at
625 1250 1250 mm c/c on both faces of wall
2800

5000 225

 
Figure C18‐7: CFRP wall retrofit for Example C18.7.2 

C18.8 References 
Dizhur,  D.  (2011).  “NSM  CFRP  retrofit  of  URM  walls.”  PhD  thesis,  Department  of  Civil  and 
Environmental Engineering, The University of Auckland, Auckland, New Zealand. 
Dizhur, D., Derakhshan, H., Lumantarna, R., Ingham, J.M. and Griffith, M. C (2010a) “Out of plane 
strengthening of unreinforced masonry walls  using near surface mounted fibre reinforced 
polymer strips.” Structural Engineering Society New Zealand (SESOC) Journal , 23(2), 91‐103 
Dizhur,  D.,  Derakhshan,  H.,  Lumantarna,  R.  and  Ingham,  J.  M.  (2010b).  “In‐situ  out‐of‐plane 
testing  of  unreinforced  masonry  wall  segment  in  Wintec  Block  F  building.”  2010  New 
Zealand Society for Earthquake Engineering Technical Conference, Wellington, New Zealand, 
26 ‐ 28 March. 
Dizhur,  D.,  Lumantarna,  R.,  Derakhshan,  H.  and  Ingham,  J.  M.  (2010c).  “In‐situ  testing  of  a 
residential  unreinforced  masonry  building  in  Wellington,  New  Zealand.”  8th  International 
Masonry Conference, Dresden, Germany, 4 ‐ 7 July 2010. 
Dizhur,  D.,  Lumantarna,  R.,  Derakhshan,  H.  and  Ingham,  J.  M.  (2010d).  “Testing  of  an 
earthquake‐damaged  unreinforced  masonry  building.”  7th  International  Conference  on 
Urban  Earthquake  Engineering  and  5th  International  Conference  on  Earthquake 
Engineering, Tokyo, Japan, 3 ‐ 5 March. 
Goodwin,  C.  O.  (2008).  "Architectural  considerations  in  the  seismic  retrofit  of  unreinforced 
masonry  heritage  buildings  in  New  Zealand."  Master  of  Architecture,  M.  Arch  Thesis, 
Department of Architecture and Planning, The University of Auckland, New Zealand. 
Goodwin,  C.  O.,  Tonks,  G.  and  Ingham,  J.  M.  (2009).  “Identifying  heritage  value  in  URM 
buildings.” Journal of the Structural Engineering Society of New Zealand, 22(2), 16‐28. 

  C18‐13
 
  Section C18 ‐ Near Surface Mounted (NSM) Fibre Reinforced Polymer Systems 
 
 

Griffith, M. C., Magenes, G., Melis, G. and Picchi, L. (2003). “Evaluation of out‐of‐plane stability 
of  unreinforced  masonry  walls  subjected  to  seismic  excitation.”  Journal  of  Earthquake 
Engineering, 7(SPEC. 1), 141‐169. 
Hassan,  T.  and  Rizkalla,  S.  (2003).  “Investigation  of  bond  in  concrete  structures  strengthened 
with near surface mounted carbon fiber reinforced polymer strips.” Journal of Composites 
for Construction, 7(3), 248‐257. 
Korany,  Y.  and  Drysdale,  R.  (2006).  “Rehabilitation  of  masonry  walls  using  unobtrusive  FRP 
techniques  for  enhanced  out‐of‐plane  seismic  resistance.”  Journal  of  Composites  for 
Construction, 10(3), 213‐222. 
MacGregor, J. G. (1988). Reinforeced concrete: Mechanics and design. New Jersey: Prentice Hall, 
Englewood Cliffs. 
Mosallam,  A.  S.  (2007).  “Out‐of‐plane  flexural  behavior  of  unreinforced  red  brick  walls 
strengthened with FRP composites.” Composites Part B: Engineering, 38(5‐6), 559‐574. 
Petersen,  R.  B., Masia,  M. J. and  Seracino, R.  (2009). “Bond  behavior of near‐surface  mounted 
FRP strips bonded to modern clay brick masonry prisms: Influence of strip orientation and 
compression  perpendicular  to  the  strip.”  Journal  of  Composites  for  Construction,  13(3), 
169‐178. 
Seracino, R., Jones, N. M., Ali, M. S. M., Page, M. W. and Oehlers, D. J. (2007). “Bond strength of 
near‐surface mounted FRP strip‐to‐concrete joints.” Journal of Composites for Construction, 
11(4), 401‐409. 
Standards Australia (2001) AS 3700‐2001: Masonry structures. Sydney, Australia  
Stone,  D.,  Tumialan,  G.,  Nanni,  A.  and  Perretti,  R.  (2002).  “Near  surface  mounted  FRP 
reinforcement:  Application  of  an  emerging  technology.”  Concrete  International,  35(5), 
42‐44. 
Willis, C. R., Kashyap, J. and Griffith, M. C. (2009a). “Flexural behaviour of NSM CFRP retrofitted 
masonry wallettes under static and cyclic loading.” FRPRCS‐9, Sydney, Australia, 13‐15 July 
2009. 
Willis, C. R., Yang, Q., Seracino, R. and Griffith, C. M. (2007). “Analysis of damaged masonry walls 
retrofitted  with  vertical  FRP  strips  subjected  to  out‐of‐plane  loading.”  8th  International 
Symposium  on  Fibre  Reinforced  Polymer  Reinforcement  for  Concrete  Structures,  FRPRCS‐8, 
Patras, Greece, 16 – 18 July. 
Willis,  C.  R.,  Yang,  Q.,  Seracino,  R.  and  Griffith,  M.  C.  (2009b).  “Bond  behaviour  of  FRP‐to‐clay 
brick masonry joints.” Engineering Structures, 31(11), 2580‐2587. 
Yang, Q. (2006). “Seismic retrofit of URM walls with externally bonded FRP composites.” Masters 
Thesis, School of Civil and Environmental Engineering, The University of Adelaide, Adelaide. 
 
 

C18‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

  C18‐15
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C19 ‐ Fibre Reinforced Shotcrete (FRS) 

C19.1 Notation 
Afrs  Total cross‐sectional area of FRS reinforcement, mm2 
An  Cross‐sectional area of wall, mm2 
As  Area of longitudinal steel reinforcement, mm2 
Av  Total cross‐sectional area of shear reinforcing steel, mm2 
Be  Effective flange width, mm 
d  Effective depth of masonry, mm 
ds  Depth of steel reinforcement embedment, mm 
Efrs  FRS modulus of elasticity, MPa 
f’b  Brick compressive strength, MPa 
f’m  Masonry compressive strength, MPa 
f’frs  FRS compressive strength, MPa 
f’tfrs  FRS tensile strength, MPa 
fvy  Design yield strength of shear reinforcing steel, MPa 
fvcd  Shear strength of FRS, MPa 
H  Wall height, m 
kwt  Reinforcement efficiency factor due to wall thickness  
L  Wall length, m 
Lfrs  Length of FRS applied to wall, m 
M*  Design moment, kNm 
Mn  Nominal moment capacity, kNm 
N*  Design axial compression force, kN 
S  Spacing of shear reinforcing steel, mm 
SNSM  Spacing of the near surface mounted steel reinforcement, mm  
t  Wall thickness prior to applying FRS, mm 
tfrs  Thickness of FRS applied to wall, m 
V*  Design shear force at section, kN 
Vcd  Shear strength provided by cement composite in FRS, kN 
Vdt  Shear resistance corresponding to diagonal tension failure mode Vf, kN  
Vfd  Shear strength provided by reinforcing fibre, kN 
Vfrs  Nominal shear resistance of FRS, kN 
Vτfrs  Nominal shear bond strength of FRS, kN 
Vfrse  Effective shear resistance of FRS, kN 
Vjs  Shear resistance corresponding to joint sliding deformation mode, kN 
Vm  Nominal shear resistance contribution of masonry, kN 
Vn  Nominal shear resistance of section, kN 
Vs  Shear strength provided by steel reinforcement, kN 
Vtc  Shear resistance corresponding to toe compression failure mode, kN 
ws  Width of NSM groove cut into masonry, mm 

  C19‐1
 
  Section C19 ‐ Fibre Reinforced Shotcrete (FRS)
 
 

z  Distance  from  centroid  of  tension  reinforcement  to  centroid  of  compression 
reinforcement, mm 
αf’m  0.85f’m 
αs  Angle of shear reinforcing steel to horizontal member axis 
βd  Effective depth factor on shear strength of cement composite 
βn  Axial load factor on shear strength of cement composite 
βp  Ratio of axial reinforcement factor on shear strength of cement composite 
  Strength reduction factor for FRS, adopted as for concrete in NZS 3101:2006 

C19.2 Scope 
The FRS strengthening methodologies for unreinforced masonry walls are applicable for any FRS 
regardless of the nature of constituent materials and reinforcing fibres, and therefore the final 
selection of FRS is at the discretion of the designer. In the experimental campaign conducted to 
form  the  methodologies,  only  Engineered  Cementitious  Composite  (ECC)  Shotcrete  was  used 
due  to  its  strain‐hardening  characteristic  and  the  capability  to  bond  to  masonry  adequately 
without  the  use  of  chemical  bonding  agents  or  steel  connectors.  The  use  of  ECC  as  a 
strengthening material was first verified by Li et al. (2000) and Kim et al. (2004), who applied ECC 
to concrete slabs and measured an increased flexural capacity. The in‐plane strengthening effect 
of ECC on masonry in‐fills was confirmed from testing conducted by Kesner & Billington (2005) 
and  Kyriakides  &  Billington  (2008).  Bruedern  (2008)  also  tested  masonry  prisms  strengthened 
with ECC and verified the effectiveness. 

When  selecting  other  FRS  types,  the  capability  to  adhere  to  a  URM  surface  should  be  verified 
unless  physical  connections  are  used  to  connect  the  FRS  to  URM.  Currently  there  is  no  NZ  or 
ASTM  standard  testing  method  for  determining  shotcrete  bond  to  substrate,  but  ACI  (2008) 
accepts  the  use  of  ASTM  C1583  as  a  method  of  determining  the  direct  tensile  pull  off  bond 
strength. 

A  design  chart  (see  Figure  C19‐1)  is  provided  to  indicate  the  sequence  of  strengthening 
procedures that is advised when strengthening URM walls using FRS. 

C19‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Does the URM wall 
require strengthening 
in both in‐plane and 
out‐of‐plane direction?

Yes No

Go to flowchart in 
Design for out‐of‐plane  figure 19.2 for in‐plane 
forces first, then in‐ design and flowchart in 
plane forces figure 19.3 for out‐of‐
plane design
 
Figure C19‐1: Sequence of FRS strengthening procedures. 

C19.3 In‐plane General Design Information 
The in‐plane design procedure is shown in Figure C19‐2. Note that flexural strength of masonry 
is not considered here as shear failures tend to be the dominant failure mode. 

  C19‐3
 
  Section C19 ‐ Fibre Reinforced Shotcrete (FRS)
 
 

Determine V*

Determine Vm = min (Vjs, Vdt, Vtc)

фVm ≥ V*
фVm < V*
Retrofit not required

(Vfrse)required = (V*‐фVm)/ф

Select tfrs based on Vfrse required using 


Vfrs of the FRS

Is Vτfrs>Vfrs ?

Yes No
in‐plane design  design shear 
complete connectors
 
Figure C19‐2: In‐plane FRS design procedure 

C19.3.2 Shear Resistance Provided by FRS 
The shear strength that FRS can provide to a URM wall is dependent on the shear strength of the 
FRS  itself,  and  the  amount  of  shear  force  that  the  masonry  wall  can  transfer  (shear  bond 
strength) to the FRS reinforcement before delamination occurs. The shear strength of FRS itself 
is  critical  when  loads  are  expected  to  be  transferred  into  the  FRS  layer  directly,  such  as  loads 
from  diaphragms.  In  the  case  where  the  loads  are  from  the  URM  wall  that  the  FRS  layer  is 
bonded to, the shear bond strength is the governing criteria. 

C19.3.2.1 Shear Resistance of FRS 

Equation  19‐5  is  adopted  from  JSCE  (2008)  which  provides  a  comprehensive  evaluation  on 
various  strength  properties  of  high  performance  fibre  reinforced  composite.  The  design  shear 
capacity of FRS is the sum of the contribution from the cement composite, reinforcing fibre and 
shear reinforcement. 

Equation  19‐6  determines  the  shear  strength  provided  by  the  cement  composite  in  FRS, 
considering the influence of member effective depth, the presence of axial reinforcement, and 

C19‐4   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

the  influence  of  bending  moment  as  a  result  of  axial  force  using  the  factors  βd,  βp  and  βn 
respectively. 

Equation 19‐13 determines the shear strength provided by the reinforcing fibre and is influenced 
by the tensile strength of FRS. Typically the shear strength provided by the FRS is the dominant 
component to the overall shear capacity unless additional steel reinforcing bars are used. If the 
tensile  strength  of  FRS  is  less  than  1.5 MPa,  then  the  contribution  of  the  reinforcing  fibre  to 
shear  strength  shall  be  neglected.  Note  that  the  original  equation  was  also  divided  by  tan  βu, 
where βu is the angle of orientation of  a crack measured with respect to the  horizontal and is 
typically assumed to be 45°, but as tan 45° = 1.0 this term was removed from the equation. 

Equation  19‐14  determines  the  shear  strength  provided  by  the  shear  reinforcement  and  is 
equivalent to methodologies used in reinforced concrete design. The value of z = 0.72L is derived 
from the two commonly adopted assumptions for reinforced masonry that the effective length is 
0.8L and that z being 0.9Le. 

C19.3.2.2 Shear Bond Resistance of FRS 

Equation  19‐15  is  based  on  JCI  (2003).  The  original  equation  was  used  to  predict  FRP  bond  to 
concrete and has been modified for FRS bond to URM by quantifying the discrepancies between 
the predicted strength from the original equation and experimentally measured values. It should 
be noted that debonding does not occur between FRS and masonry, but rather occurs within the 
masonry  itself  near  the  FRS  and  masonry  interface.  As  a  result  of  the  spalling  failure  of  the 
masonry surface, chemical bond agents applied between FRS and masonry do not contribute to 
the  shear  bond  strength  and  physical  connectors  are  required  to  increase  the  bond  of  FRS  to 
masonry.  Other  debonding  equations,  such  as  developed  by  Willis  et  al.  (2009),  were  also 
compared with experimental values obtained but the discrepancy between the predicted values 
and  measured  values  was  higher  than  predictions  obtained  from  the  use  of  the  equation 
suggested by JCI (2003). 

kwt is a surface bonded reinforcement efficiency factor dependent on the thickness of the URM 
wall, in leafs. For a two leaf URM wall with common bond (a header course every 4‐6 courses of 
bricks), kwt is taken as 1.0. As the masonry wall thickness increases, the header courses between 
each leaf are insufficient to connect the wall together to ensure a uniform deformation. The leaf 
of the wall furthest from the FRS reinforcement then exhibits significantly more damage when 
compared with the leaf that the FRS is bonded to. 

C19.3.2.3 Shear Connector Design of FRS 

Shear  connectors  may  be  used  for  two  purposes.  Firstly  shear  connectors  may  be  used  to 
increase  the  bond  capacity  between  FRS  and  URM  and  thus  increase  the  value  of  Vτfrs  and 
secondly shear connectors may be used to connect different leafs of the URM wall together so 
that  they  behave  uniformly  when  subjected  to  loading,  which  increases  the  value  of  kwt,  the 
reinforcement efficiency factor.  

   

  C19‐5
 
  Section C19 ‐ Fibre Reinforced Shotcrete (FRS)
 
 

C19.4 Out‐of‐plane General Design Information 
The  out‐of‐plane  design  philosophy  for  FRS  reinforced  URM  walls  is  analogous  to  the  flexural 
design  of  reinforced  concrete.  In  the  experimental  campaign,  the  FRS  used  (ECC)  exhibited  no 
debonding with the URM wall regardless of the direction of out‐of‐plane loading. For other types 
of FRS the bond capacity will need to be verified. 

C19.4.1 Out‐of‐plane Resistance of Masonry Walls with FRS on Tension Surface of 
Loading 
When  FRS  is  acting  on  the  tension  surface  of  loading,  FRS  is  treated  as  the  tension  resisting 
element and URM as the compression element.  

An illustration of the distance of xt and xc when moment capacity is calculated about the axial 
load is shown in Figure C19‐3. The out‐of‐plane design procedure is shown in Figure C19‐4. 

 
Figure C19‐3: Distances of xt and xc with respect to axial load 

C19‐6   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Is FRS going to be applied on both 
surfaces of the wall?

Yes, design with FRS  No, design with ECC on the compression 
on the tension  surface of loading first with NSM steel 
suface reinforcement

Determine M* and  Nominate the depth and spacing that the 
N* steel reinforcment will be placed in

Assume  Resolve forces and determine area of steel 
thickness of FRS reinforcement required

Determine  Determine the groove width and the 
flexural strength effective flange width

Is ϕMn >M*? Is ϕMn >M*?

Yes No Yes No

Out‐of‐ Increase  Check flexural strength of  Increase steel reinforcement 


plane design  FRS  the wall when FRS is  size, groove depth or 
is complete thickness acting on the tension  decrease spacing of the 
surface groove and reanalyse

 
Figure C19‐4: Out‐of‐plane FRS design procedure 

C19.4.2 Out‐of‐plane  Resistance  of  Masonry  Walls  with  FRS  and  Near  Surface 
Mounted  (NSM)  Steel  Reinforcement  Embedded  on  Compression  Surface  of 
Loading 
When  FRS  is  acting  on  the  compression  surface  of  loading,  the  tensile  capacity  of  the  URM  is 
ignored and only FRS is assumed to be resisting the tensile forces. However, thin layers of FRS 
are generally incapable of sustaining the flexural tension forces generated due to seismic loading 
and therefore the use of Near Surface Mounted (NSM) steel reinforcement is recommended.  An 
illustration  of  NSM  reinforcement  is  shown  in  Figure  C19‐5,  while  Figure  C19‐6  illustrates 
Equation 19‐23 on the relationship between d, ds and tfrs. 

  C19‐7
 
  Section C19 ‐ Fibre Reinforced Shotcrete (FRS)
 
 

(a) Illustration of NSM  (b) actual example of NSM 

Figure C19‐5: NSM reinforcement 

 
Figure C19‐6: Illustration of FRS effective depth 

C19.4.3 Design Examples 

C19.4.4 Example 19.1 
Design a FRS retrofit system for a URM wall, measuring 5000 mm long x 2800 mm high x 225 mm 
thick (2 leafs). The factored in‐plane shear force, V*, is 180.0 kN and there is no axial force acting 
on the wall. The FRS reinforcement must be provided on one wall surface only on the entire wall 
length and no additional longitudinal steel reinforcement can be used. It has been determined 
that the wall is likely to fail by the formation of diagonal shear cracks. 

Compressive strength of masonry, f’m = 10 MPa 

Compressive strength of brick, f’b  = 20 MPa 

Bed‐joint sliding resistance, Vjs  = 225 kN 

Diagonal tension resistance, Vdt  = 174 kN 

Toe crushing resistance, Vtc  = 253 kN 

Nominal shear resistance contribution of masonry, Vm = min (Vjs, Vdt, Vtc)  

min (225, 174, 273)  = 174 kN 

Reduced nominal shear resistance,Vm = (0.75) (174) = 130.5 kN 

V* (180 kN) > Vm (130.5) 

Therefore design shear reinforcement. 

C19‐8   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

 (Vfrse)required = (V* ‐ Vm)/   = (180 – 130.5)/0.75 = 66 kN 

Wall properties: 

Length of wall, L  = 5 m 

Height of wall, H  = 2.8 m 

Width of wall, t  = 0.225 m 

FRS reinforcement properties: 

FRS Modulus of Elasticity, Efrs  = 16000 MPa 

FRS compressive strength, f’frs  = 40 MPa 

FRS tensile strength, f’tfrs  = 4 MPa 

Vfrse = min (Vfrs, Vτfrs) 

Evaluate Vfrs 

Vfrs = Vcd + Vfd + Vs 

Try 10 mm of FRS 

Shear strength provided by the cement composite, Vcd 

0.7 0.20 0.7 0.20 √40 0.48 0.5  

0.67 1.5  

100 √100 0 0 1.5 

Where: pw  = 0 (no longitudinal reinforcement) 

1 ∗
1  (as there is no axial load) 

0.67 0 1 0.48 0.01 5 0  

Shear strength provided by reinforcing fibre, Vfd 

0.01 0.72 5 4 144.0  

Shear strength provided by shear reinforcement, Vs = 0 

Therefore: 

Nominal shear resistance of FRS, Vfrs  = 144.0 kN 

Evaluate nominal shear bond strength of FRS, Vτfrs 

  C19‐9
 
  Section C19 ‐ Fibre Reinforced Shotcrete (FRS)
 
 

.
0.097 10  

.
0.097 1.0 20 0.01 16000 5 2.8 395.6  

Therefore, 

min , min 144.0, 395.6  

0.75 144.0 kN 108.0 66 kN OK 

Adopt 10 mm of FRS on a single surface 

Note:  while  a  lower  thickness  of  FRS  would  be  able  to  sustain  the  shear  force,  in  practical 
applications  the  minimum  thickness  should  not  be  less  than  10 mm  as  difficulties  arise  in 
ensuring  that  the  design  thickness  of  FRS  can  be  applied  on  a  URM  surface  when  the  design 
thickness is less than 10 mm. 

C19.4.5 Example 19.2 
Design a FRS retrofit system for a URM wall, measuring 5000 mm long x 2800 mm high x 225 mm 
thick (2 leaf). The out‐of‐plane seismic acceleration is 1.0g and there are no axial forces acting on 
the wall excepting wall selfweight. First determine the FRS thickness that would be required if 
reinforcement  can  be  applied  on  both  surfaces,  then  determine  the  reinforcement  that  would 
be required on the compression surface if only a single surface can be strengthened. 

(1) FRS can be applied on both surfaces 

Weight of wall        = 16 kN/m3 × 2.8 m × 5 m × 225 mm = 50.4 kN    

Horizontal seismic force     = 1.0 × 50.4 kN = 50.4 kN or 18 kN/m 

Design moment, M*, and required moment capacity, Mn 


18 2.8
17.6
8 8

17.6
20.8
∅ 0.85

Self‐weight of upper half of wall, N* 


16 / 1.4 5 225 25.2  


25.2
29.6
∅ 0.85

Try a FRS thickness of 10 mm on a single surface 

FRS force at failure is: 

C19‐10   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

5 10 4 200

200 29.6 229.6  


Depth of compression block, 
229.6 
5.4   
′ 0.85 10  5

Taking moment about axial load 

 
225 10 225 5.4
200 229.6 48.7 23.3  
2 2
10 mm of FRS is sufficient if FRS is applied on both surfaces 

(2) Now  assuming  that  FRS  can  only  be  applied  on  a  single  surface,  determine  the 
reinforcement required if FRS is on the compression surface of loading. 

Nominate the spacing of the groove, in this example this has been chosen as 1 metre. 

Determine the horizontal seismic force that the wall will be subjected to. 

Given that the groove has a spacing of 1 metre, the width of the section analysed is also 1 metre. 
The weight of the wall is then: 

Weight of wall  16 / 1 2.8 225 10.1

Using the seismic acceleration of 1.0 g, the horizontal seismic force then becomes: 

Horizontal seismic force  1.0 10.1 10.1 3.6 /

Design moment, 


3.6 2.8
3.5
8 8

3.5
4.2
∅ 0.85

Self weight of upper wall, 16 / 1.4 1.0 225 5.0

5.0
5.9
∅ 0.85
With the design nominal moment, Mn, being 4.2 kNm, nominate the groove depth and calculate 
the  reinforcement  area  required  and  consequently  the  groove  width.  It  is  recommended  that 
the depth of the groove does not reach the outer leaf of the URM wall as this may damage the 
outer  leaf  (and  therefore  the  appearance  of  the  building  exterior)  during  the  construction 
process.  

Depth of reinforcement selected = 80 + 10 mm cover 

0.0325   
  4.2 5.9 0.0325  

  C19‐11
 
  Section C19 ‐ Fibre Reinforced Shotcrete (FRS)
 
 

  4.0   
Effective depth d is = 80 + 10 = 90 mm 

Note that high performance FRS (such as ECC used in this experimental campaign) typically have 
a significantly lower permeability when compared with normal structural concrete, therefore a 
reduction in cover thickness can be used, consult the supplier regarding the recommended cover 
thickness. 

The effective flange width be on both side is the lesser of 

(a) 16 50 16 10 210  

(b) 2 50 2 80 210  

(c) 50 750  

(d) 1000  
Try z = 0.9d 

0.9 90 81   
4.0
49.4
81
49.4
7.1  
′ 0.83 40 210

7.1
90 86.5  
2
Using the new z, C = 46.3 kN and a = 6.6 mm 

Then C = 46.1 kN 

Resolving forces vertically T = C‐Nn 

46.1 6.7 39.4  


39.4
78.8  
500

Note that a D12 bar would be sufficient, but here a D14 bar with AS of 153.9 mm2 is selected to 
show the calculation of the compression area centroid. 

153.9 500 77.0

77.0 5.9 82.9


Find centroid of compression block:  

Note that as FRS applied on wall surface could be of very thin sections, and the effective flange 
width could also be short depending on the geometries of the groove selected, it is possible that 
the  compression  force  will  be  outside  the  flange  area  and  consequently  the  centroid  of  the 
compression must be calculated.  

C19‐12   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

82.9
Area of compression block 2497
′ 0.83 40

The compression area is comprised of  

flange area 210 10 50 7.9


Centroid of compression block is then 
7.9
2100 5 397 10
2 6.4
2497
90 6.4 83.6
77.0 83.6 6.4 4.0
Actual  groove  depth  =  80 mm  +  Diameter  of  reinforcing  bar/2  +  cover  thickness  of  10 mm  = 
97 mm 

Adopt 100 mm groove depth 

Adopt  10 mm  of  FRS  thickness  on  masonry  wall  with  grade  500 D14  reinforcing  bar  Near 
Surface Mounted at 1 m spacing with a groove width of 50 mm and a groove depth of 100 mm. 

C19.5 References 
ACI‐Committee‐506  (2008).  Guide  to  Fiber‐Reinforced  Shotcrete.  American  Concrete  Institute, 
1‐18.   

ASTM (2004). “Test Method for Tensile Strength of Concrete surfaces and the Bond Strength or 
Tensile  Strength  of  Concrete  Repair  and  Overlay  Materials  by  Direct  Tension  (Pull‐off 
Method).” American Society for Testing and Materials. Philadelphia. 

Bruedern, A‐E., Abecasis, D. & Mechtcerine, V. (2008). “Strengthening of Masonry Using Sprayed 
Strain  Hardening  Cement‐Based  Composites  (SHCC).”  Seventh  International  RILEM 
Symposium on Fibre Reinforced Concrete: Design and Applications, Chennai (Madras), India, 
451‐460, 17‐19 September. 

BSCC (2000). “Prestandard and Commentary for the Seismic Rehabilitation of Buildings.” FEMA 
356. Building Society Safety Council. Washington, USA. 

CEN  (2005).  “Designs  of  Structures  for  Earthquake  Resistance  Part  3:  Assessment  and 
Retrofitting of Buildings” Eurocode 8. Brussels, Belgium. 

DIN 1053‐100 (2004). Masonry: Design on the Basis of Semi‐Probabilistic Safety Concept. NABau, 
Berlin. 

Galati, N., Garbin, E. & Nanni, A. (2005). Design Guideline for the Strengthening of Unreinforced 
Masonry  Structures  Using  Fibre  Reinforced  Polymers  (FRP)  Systems.  University  of 
Missouri‐Rolla. 

JCI‐SF6  (1990).  “Method  of  Test  for  Shear  Strength  of  Fibre  Reinforced  Concrete.”  Japan 
Concrete Institute. Mubanchi, Yotsuya 1‐Chrome, Shinjuku‐ku, Tokyo, Japan. 

  C19‐13
 
  Section C19 ‐ Fibre Reinforced Shotcrete (FRS)
 
 

JCI  (2003).  “Technical  report  of  technical  committee  on  retrofit  technology.”  International 
Symposium  on  Latest  Achievement  of  Technology  and  Research  on  Retrofitting  Concrete 
Structures, Kyoto, Japan, 1‐8, 14‐15 July. 

JSCE  (2008).  “Recommendations  for  design  and  construction  of  high  performance  riber 
reinforced  cement  composites  with  multiple  fine  cracks  (HPFRCC).”  Japan  Society  of  Civil 
Engineers, 1‐88. 

Kesner,  K.  &  Billington,  S.  L.  (2005).  “Investigation  of  infill  panels  made  from  engineered 
cementitious  composites  for  seismic  strengthening  and  retrofit.”  Journal  of  Structural 
Engineering ASCE, 131(11), 1712‐1720. 

Kim,  Y.  Y.,  Fischer,  G.,  Lim,  Y.  M.  &  Li,  V.  C.  (2004).  “Mechanical  performance  of  sprayed 
engineered  cementitous  composite  using  wet‐mix  shotcreting  process  for  repair 
applications.” ACI Materials Journal, 101(1), 42‐49. 

Kyriakides,  M.  A.  &  Billington,  S.  L.  (2008).  “Seismic  retrofit  of  masonry‐infilled  non‐ductile 
reinforced  concrete  frames  using  sprayable  ductile  fiber‐reinforced  cementitous 
composites.”  The  14th  World  Conference  on  Earthquake  Engineering,  Beijing,  China,  1‐7, 
12 ‐ 17 October. 

Li, V. C., Horii, H., Kabele, P., Kanda, T. & Lim, Y. M. (2000). “Repair and retrofit with engineered 
cementitious composites.” Engineering Fracture Mechanics, 65(2), 317‐334. 

MSJC  (2002).  “Building  code  requirement  for  masonry  structures.”  ACI  530‐04/ASCE  5‐04/TMS 
402‐04. Masonry Standards Joint Committee, Boulder, USA. 

Standards New Zealand. (2006). NZS 3101:2006, Concrete Structures Standard Part1: The Design 
of Concrete Structures. Standards New Zealand, Wellington, New Zealand. 

Willis, C. R. & Yang, Q., Seracino, R. & Griffith M. C. (2009). “Bond behaviour of FRP‐to‐clap brick 
masonry joints.” Engineering Structures, 31, 2580‐2587. 

C19‐14   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C20 ‐ Near Surface Mounted Steel 
Reinforcement 
This section has been intentionally left blank. 

  C20‐1
 
  Section C20 ‐ Near Surface Mounted Steel Reinforcement
 
 

This section has been intentionally left blank. 

C20‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C21 ‐ Textile Reinforced Mortars 
This section has been intentionally left blank. 

  C21‐1
 
  Section C21 ‐ Textile Reinforced Mortars
 
 

This section has been intentionally left blank. 

C21‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C22 ‐ Restraining Parapets and Chimneys 
This section has been intentionally left blank. 

  C22‐1
 
  Section C22 ‐ Restraining Parapets and Chimneys
 
 

This section has been intentionally left blank. 

C22‐2   
 
Commentary to Assessment and Improvement of Unreinforced Masonry Buildings for  12/2011
Earthquake Resistance   
 

Section C23 ‐ Pounding 
This section has been intentionally left blank. 

  C23‐1
 

S-ar putea să vă placă și