Sunteți pe pagina 1din 26

Governor and AGC Control

of System Frequency

TRE Technical Workshop


March 31, 2009
Bob Green
Garland Power and Light
Two generators equipped with
governors having output feedback
Schematic of a governor with output feedback
Response of governor with output feedback
Steady-state speed characteristic (droop) curve
Calculation of steady-state speed characteristic
R(per unit), the slope of the “droop” curve, is defined
as f(p.u.)/ P(p.u.), where f(p.u.)= f(HZ) / 60.0,
and P(p.u.)= P(MW) / Unit Capacity.
For a 600 MW unit that has a governor response of 20
MW for a frequency excursion that settles out at 59.9
HZ, R=f(p.u.) / P(p.u.) = (0.1/60)/(20/600)
=0.05 or 5% droop.

Once the droop is known, the MW response to


frequency deviation can be determined by
(P/f)=(1/R), or P=(1/R) X f.
For the 600 MW unit with 5% droop,
(P/600)=(1/0.05) X (f/60), or P=200MW/HZ
So, how do governors with the
steady-state speed characteristic
interact when there are multiple
generators in a power system?

What determines the steady state


system frequency after a load is
added to the system?
Multiple Generator Governor Response
Consider an isolated power system with three generators on-line and
operating at 60HZ. The load is 360 MW and the generator outputs for
units #1, #2 and #3 are 80MW, 120MW and 160MW, respectively.
A load of 21MW (P) is added. What frequency does the system settle at?
How much does each unit pick-up (MW)?
Since R(p.u.)=( f(HZ)/60)/( P(MW)/Capacity),
then (P/f)=(1/R) X Capacity/60).
UNIT CAPACITY R (DROOP) P/f
#1 300MW 0.100 (10%) 50MW/HZ
#2 450MW 0.075 (7.5%) 100MW/HZ
#3 600MW 0.050 (5%) 200MW/HZ
Solution:
Unit #1: P1=50 X f P1=50 X 0.06=3MW
Unit #2: P2=100 X f P2=100 X 0.06=6MW
Unit #3: P3=200 X f P3=200 X 0.06=12MW
Pi=350f=21MW, check: Pi=21MW
and f=21/350=0.06HZ
Frequency=60-0.06=59.94HZ
Three generators serving 360MW
Three generators serving 367MW
Three generators serving 374MW
Three generators serving 381MW
The system frequency reaches steady-
state at a value that causes the sum of
the on-line generator output MW to be
equal to the system load MW.
With this type of governor, when the
system load increases, the system
frequency decreases and visa versa.
How do we control frequency to 60HZ,
no matter what the load is?
Power system equipped for supplemental control
Addition of a speed changer
Steady-state speed characteristic with speed changer
Power output as a function of frequency
How does the addition of the
speed changer to the governor
facilitate the control of frequency?

Hint: The system frequency


reaches steady-state at a value
that causes the sum of the on-line
generator output MW to be equal
to the system load MW.
From a central site, you increase or
decrease the 60HZ set-points until
the sum of the 60HZ set-points is
equal to the system load. Then the
frequency will stabilize at 60HZ.
This form of supplemental control is
called Automatic Generation Control
(AGC) and more specifically, Load
Frequency Control (LFC).
Load of 367MW and 60HZ SPs increased by 7 MW
Load as a function of frequency (load damping)
Governor and load characteristic curve intersection
Illustration of typical governor dead band
Generation oscillations at the dead band frequency
Primary Control Secondary or Supplementary Control
Common Name Governor Control/Response AGC Control/Response
Function-Generic Holds the system together as load changes Shifts generation between units to achieve
occur and also as un-commanded security and economic objectives plus
generation excursions occur restores frequency to the rated value.
Function-Technical Provides the correct amount of mechanical Changes the 60HZ governor set-points of the
input to turbines to match the electrical units to achieve scheduled values established
output of the corresponding generators by the market.
Control Input Frequency/rotational speed of the turbine In ERCOT, the SCE for the portfolio of units
Control Time Constant Fast - Seconds Slower - Tens of seconds and minutes
Style of Control Local within the Units/PGCs—A QSE has no Centralized from ERCOT to Units via QSEs
direct control over governor response.
Performance Having more governors on-line (with a given Having more units being controlled by AGC
Optimization droop characteristic) will minimize the will minimize the duration of frequency
magnitude of frequency deviations deviations
Key Parameters Steady state speed characteristic (droop), Base power schedule plus deployments of
governor dead-band, first stage boiler balancing energy, regulation energy,
pressure (steam units) and head (hydro responsive and non-spinning reserve. AGC
units) dead-band, gains and frequency bias term.
Market Characteristics If there ever is a governor response market, Bids, awards, deployments and settlement
there will probably be bids, awards and through the Ancillary Service Market.
settlement, but the market will never Performance monitoring of individual
deploy the governor response. Services is approximate and complicated.
Disturbance Timeline Initial governor response (to point B) is over There needs to be recognition of governor
completely by the time units start receiving response and coordination between RRS and
secondary control signals in response to the RegUp deployments to insure smooth , rapid
disturbance. and sustained frequency recovery.

S-ar putea să vă placă și