March 31, 2009 Bob Green Garland Power and Light Two generators equipped with governors having output feedback Schematic of a governor with output feedback Response of governor with output feedback Steady-state speed characteristic (droop) curve Calculation of steady-state speed characteristic R(per unit), the slope of the “droop” curve, is defined as f(p.u.)/ P(p.u.), where f(p.u.)= f(HZ) / 60.0, and P(p.u.)= P(MW) / Unit Capacity. For a 600 MW unit that has a governor response of 20 MW for a frequency excursion that settles out at 59.9 HZ, R=f(p.u.) / P(p.u.) = (0.1/60)/(20/600) =0.05 or 5% droop.
Once the droop is known, the MW response to
frequency deviation can be determined by (P/f)=(1/R), or P=(1/R) X f. For the 600 MW unit with 5% droop, (P/600)=(1/0.05) X (f/60), or P=200MW/HZ So, how do governors with the steady-state speed characteristic interact when there are multiple generators in a power system?
What determines the steady state
system frequency after a load is added to the system? Multiple Generator Governor Response Consider an isolated power system with three generators on-line and operating at 60HZ. The load is 360 MW and the generator outputs for units #1, #2 and #3 are 80MW, 120MW and 160MW, respectively. A load of 21MW (P) is added. What frequency does the system settle at? How much does each unit pick-up (MW)? Since R(p.u.)=( f(HZ)/60)/( P(MW)/Capacity), then (P/f)=(1/R) X Capacity/60). UNIT CAPACITY R (DROOP) P/f #1 300MW 0.100 (10%) 50MW/HZ #2 450MW 0.075 (7.5%) 100MW/HZ #3 600MW 0.050 (5%) 200MW/HZ Solution: Unit #1: P1=50 X f P1=50 X 0.06=3MW Unit #2: P2=100 X f P2=100 X 0.06=6MW Unit #3: P3=200 X f P3=200 X 0.06=12MW Pi=350f=21MW, check: Pi=21MW and f=21/350=0.06HZ Frequency=60-0.06=59.94HZ Three generators serving 360MW Three generators serving 367MW Three generators serving 374MW Three generators serving 381MW The system frequency reaches steady- state at a value that causes the sum of the on-line generator output MW to be equal to the system load MW. With this type of governor, when the system load increases, the system frequency decreases and visa versa. How do we control frequency to 60HZ, no matter what the load is? Power system equipped for supplemental control Addition of a speed changer Steady-state speed characteristic with speed changer Power output as a function of frequency How does the addition of the speed changer to the governor facilitate the control of frequency?
Hint: The system frequency
reaches steady-state at a value that causes the sum of the on-line generator output MW to be equal to the system load MW. From a central site, you increase or decrease the 60HZ set-points until the sum of the 60HZ set-points is equal to the system load. Then the frequency will stabilize at 60HZ. This form of supplemental control is called Automatic Generation Control (AGC) and more specifically, Load Frequency Control (LFC). Load of 367MW and 60HZ SPs increased by 7 MW Load as a function of frequency (load damping) Governor and load characteristic curve intersection Illustration of typical governor dead band Generation oscillations at the dead band frequency Primary Control Secondary or Supplementary Control Common Name Governor Control/Response AGC Control/Response Function-Generic Holds the system together as load changes Shifts generation between units to achieve occur and also as un-commanded security and economic objectives plus generation excursions occur restores frequency to the rated value. Function-Technical Provides the correct amount of mechanical Changes the 60HZ governor set-points of the input to turbines to match the electrical units to achieve scheduled values established output of the corresponding generators by the market. Control Input Frequency/rotational speed of the turbine In ERCOT, the SCE for the portfolio of units Control Time Constant Fast - Seconds Slower - Tens of seconds and minutes Style of Control Local within the Units/PGCs—A QSE has no Centralized from ERCOT to Units via QSEs direct control over governor response. Performance Having more governors on-line (with a given Having more units being controlled by AGC Optimization droop characteristic) will minimize the will minimize the duration of frequency magnitude of frequency deviations deviations Key Parameters Steady state speed characteristic (droop), Base power schedule plus deployments of governor dead-band, first stage boiler balancing energy, regulation energy, pressure (steam units) and head (hydro responsive and non-spinning reserve. AGC units) dead-band, gains and frequency bias term. Market Characteristics If there ever is a governor response market, Bids, awards, deployments and settlement there will probably be bids, awards and through the Ancillary Service Market. settlement, but the market will never Performance monitoring of individual deploy the governor response. Services is approximate and complicated. Disturbance Timeline Initial governor response (to point B) is over There needs to be recognition of governor completely by the time units start receiving response and coordination between RRS and secondary control signals in response to the RegUp deployments to insure smooth , rapid disturbance. and sustained frequency recovery.