Sunteți pe pagina 1din 1

PCB

CLICK analog PLC used Signal 1 kΩ


-Xmtr +Xmtr
as PID loop controller +24 V
10 kΩ

 2010 Tony R. Kuphaldt


5.3 V

400 Ω

Creative Commons Attribution 3.0 License


Gnd
C0-02DD1-D PCB scales 4-20 mA transmitter
24 VDC CLICK signal into 1-5 VDC PLC input signal
(comm) Koyo as well as protects PLC against
C1 transmitter short-circuits
X1
X2 PLC variable list:
X3
X4 PV = DF1 (floating point)
PWR
R B W G RUN C2 SP = DF10 (floating-point)
RUN
ERR STOP Y1 Output = DF3 (floating-point)
Y2
PORT 1 Y3 K_P = DF12 (floating-point)
Y4 K_I = DF13 (floating-point)

Output
TX1

Input
Fuse

RX1 +V
K_D = DF14 (floating-point)
AD1V
TX2 AD1I Auto/Man = C1 (bit) 1=Auto 0=Man
RX2 AD2V
PORT 2 Dir/Rev = C2 (bit) 1=Dir 0=Rev
AD2I
ACOM ISA/Parallel = C3 (bit) 1=ISA 0=Parallel
PORT 3 RS-485
DA1V
TX3 DA1I
RX3 DA2V
LG
DA2I
0 24V
C-More Micro HMI panel plugs 4-20 mA
into port 2, leaving port 1 free Loop-powered transmitter
for PLC programming
4-20 mA
Final control element
(e.g. valve, VFD)