Documente Academic
Documente Profesional
Documente Cultură
MAC0501011C3
Air Conditioner
CS-C9DKZW CU-2C18DKH
CS-C9DKZW CU-3C20DKH
CONTENTS
Page Page
1 Features 2 8.1. Cooling Operation 17
2 Functions 3 8.2. Soft Dry Operation 18
3 Product Specifications 6 8.3. Automatic Operation 19
3.1. CS-C9DKZW CU-2C18DKH 6 8.4. Operation Control 20
3.2. CS-C9DKZW CU-3C20DKH 8 8.5. Indoor Fan Speed Control 23
4 Dimensions 10 8.6. Outdoor Fan Speed Control 25
4.1. Indoor Unit & Remote Control 10 8.7. Vertical Airflow Direction Control 25
4.2. Outdoor Unit 11 8.8. Horizontal Airflow Direction Control 26
5 Refrigeration Cycle Diagram 12 8.9. Powerful Operation 26
6 Block Diagram 13 8.10. Quiet Operation 27
7 Wiring Diagram 15 8.11. Ionizer Operation 28
8 Operation Details 17
1 Features
• High Efficiency • Quality Improvement
− Gas leakage protection
• Compact Design − Prevent compressor reverse cycle
− 2-stage OLP to protect compressor
• Comfort Environment − Noise prevention during soft dry operation.
− Ionizer control for generating negative ion in discharge − Blue Coated Condenser
air − High resistance to corrosion.
− Air filter with function to reduce dust and smoke
− Wider range of horizontal discharge air • Operation Improvement
− Quiet mode to provide extra quiet operation
• Auto Restart − Powerful mode to reach the desired room temperature
− Random auto restart after power failure for safety restart quickly
operation
• Long Installation Piping
• Removable and Washable Front Panel − Long piping up to 15 meter
2
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
2 Functions
3
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
4
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Outdoor Unit
Overload Protector
• 2-stage OLP to protect the compressor.
Overload Protector will trip when
– Temperature of compressor increases
to 120°C.
– High temperature or high current flows
to compressor.
(Refer circuit diagram for OLP
characteristic)
5
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
3 Product Specifications
3.1. CS-C9DKZW CU-2C18DKH
Unit Indoor unit Outdoor unit
INTAKE
EER W/W (BTU/hW) (1 unit) 3.17 - 3.29 (10.8 - (2 units) 3.17 - 3.29 (10.8 -
11.2) 11.2)
6
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Note:
• Specifications are subjected to change without prior notice for further improvement.
7
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
INTAKE
Running Current A 0.23 - 0.23 3.6 - 3.7 4.9 - 5.1 5.3 - 5.5 8.1 - 8.3 8.3 - 8.7
EER W/W — 2.93 - 3.04 2.52 - 2.60 2.98 - 3.06 2.82 - 2.93 3.13 - 3.18
(BTU/hW) (10.0 - 10.4) (8.6 - 8.9) (10.2 - 10.5) (9.6 - 10.0) (10.7 - 10.9)
8
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Note:
• Specifications are subjected to change without prior notice for further improvement.
9
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
4 Dimensions
4.1. Indoor Unit & Remote Control
10
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
11
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
12
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
6 Block Diagram
13
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
14
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
7 Wiring Diagram
15
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
16
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
8 Operation Details
8.1. Cooling Operation
17
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
18
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
• Then, the unit start to operate at determined operation mode, until it is switched off using remote control, with the setting
temperature as shown in below table.
• The setting temperature for all the operations can be changed one level up or one level down from the standard temperature
as shown in below table by pressing on the temperature up or temperature down button at remote control.
• The operation mode judging temperature and standard setting temperature can be increased by 2°C permanently, by open the
circuit of JX1 at indoor electronic controller.
19
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
20
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
21
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
• Narrowing
1. Vertical Airflow Direction
During Anti-dew condensation prevention, Airflow Direction Auto-control angle change from 0° - 32° to 20° - 30° under
Cooling and Soft Dry operation mode.
22
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
During Anti-dew condensation prevention, Airflow Direction Manual control angle change from 10°, 15°, 20°, 32° to 22°, 24°,
26°, 28°, 30°.
23
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
24
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
25
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
26
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
27
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
d. Vertical airflow direction can be adjusted using remote control during Ionizer individual operation.
e. During Ionizer individual operation, operated mode (Auto, Cool, Dry, Fan) can be activated by turning on the OFF/ON
operation button. (2 → 4)
f. If power failure occur during Ionizer individual operation, after power resume, Ionizer operation will be activated immediately.
g. When the Ionizer circuit feedback process error occur for 24 times (about 11hr 30 min.), Ionizer operation will turn off with
ION LED blinks continuously.
(For details, please refer to Ionizer Error detection control)
28
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
8.12.1. ON Timer
• When ON Timer is set by using the remote control, the unit will start to operate slightly before the set time, so that the room will
reach nearly to the set temperature by the set time.
• For Cooling and Soft Dry operation, the operation will start 15 minutes before the set time.
• For Automatic operation, the indoor fan will operate at SLo speed for 25 seconds, 30 minutes before the set time to detect the
intake air temperature to determine the operation mode. The operation indication lamp will blink at this time.
29
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
9 Operating Instructions
30
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
31
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
32
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
33
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
34
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
35
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
10 Installation Instructions
Required tools for Installation Works
1. Philips screw driver 5. Spanner 9. Gas leak detector 13. Multimeter
2. Level gauge 6. Pipe cutter 10. Measuring tape 14. Torque wrench
18 N.m (1.8 kgf.m)
42 N.m (4.2 kgf.m)
55 N.m (5.5 kgf.m)
3. Electric drill, hole core drill 7. Reamer 11. Thermometer 15. Vacuum pump
(ø70 mm)
4. Hexagonal wrench (4 mm) 8. Knife 12. Megameter 16. Gauge manifold
This indication shows the possibility of causing injury or damage to properties only.
Symbol with background white denotes item that is PROHIBITED from doing.
• Carry out test running to confirm that no abnormality occurs after the installation. Then, explain to user the operation, care and
maintenance as stated in instructions. Please remind the customer to keep the operating instructions for future reference.
1. Engage dealer or specialist for installation. If installation done by the user is defective, it will cause water leakage, electrical shock or fire.
2. Install according to this installation instruction strictly. If installation is defective, it will cause water leakage, electrical shock or fire.
3. Use the attached accessories parts and specified parts for installation. Otherwise, it will cause the set to fall, water leakage, fire or
electrical shock.
4. Install at a strong and firm location which is able to withstand the set’s weight. If the strength is not enough or installation is not properly
done, the set will drop and cause injury.
5. For electrical work, follow the local national wiring standard, regulation and this installation instruction. An independent circuit and single
outlet must be used. If electrical circuit capacity is not enough or defect found in electrical work, it will cause electrical shock or fire.
6. Use the specified cable (1.5 mm2) and connect tightly for indoor/outdoor connection. Connect tightly and clamp the cable so that no
external force will be acted on the terminal. If connection or fixing is not perfect, it will cause heat-up or fire at the connection.
7. Wire routing must be properly arranged so that control board cover is fixed properly. If control board cover is not fixed perfectly, it will
cause heat-up at connection point of terminal, fire or electrical shock.
8. When carrying out piping connection, take care not to let air substances other than the specified refrigerant go into
refrigeration cycle. Otherwise, it will cause lower capacity, abnormal high pressure in the refrigeration cycle, explosion
and injury.
9. Do not damage or use unspecified power supply cord. Otherwise, it will cause fire or electrical shock.
10. Do not use extension cord, and do not share the single outlet with other electrical appliances. Otherwise, it will cause
fire or electrical shock.
36
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
1. The equipment must be earthed. It may cause electrical shock if grounding is not perfect.
2. Do not install the unit at place where leakage of flammable gas may occur. In case gas leaks and accumulates at
surrounding of the unit, it may cause fire.
3. Carry out drainage piping as mentioned in installation instructions. If drainage is not perfect, water may enter the room and damage the
furniture.
37
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct
sunlight or rain, be careful that heat radiation from the
condenser is not obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short • This illustration is for explanation purposes only.
circuit of the discharged air. The indoor unit will actually face a different way.
• If piping length is over the common length, additional
refrigerant should be added as shown in the table.
38
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
The mounting wall is strong and solid enough to prevent it from Caution
the vibration. When the wall is hollow, please be sure to use the
sleeve for tube ass’y to prevent dangers caused by
mice biting the connecting cable.
39
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
(This can be used for left rear piping & left bottom piping also.)
40
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
• Secure the cable onto the control board with the holder
(clamper).
INSTALLATION OF SUPER ALLERU-BUSTER FILTER
41
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Please follow the steps below to take out front grille if The below operations will be performed by pressing the
necessary such as when servicing. “AUTO” switch.
1. Open the intake grille and remove the screw at the front of 1. AUTO OPERATION MODE
the front grille. The Auto operation will be activated immediately once the
2. Set the vertical airflow direction louver to the horizontal Auto Switch is pressed.
position. 2. TEST RUN OPERATION (FOR PUMP DOWN/SERVICING
3. Slide down the 2 caps on the front grille as shown in the PURPOSE)
illustration below, and then remove the 2 mounting screws. The Test Run operation will be activated if the Auto Switch
4. Pull the lower section of the front grille towards you to is pressed continuously for more than 5 sec. A “pep” sound
remove the front grille. will occur at the fifth sec., in order to identify the starting of
Test Run operation
When reinstalling the front grille, first set the vertical 3. REMOTE CONTROLLER RECEIVING SOUND ON/OFF
airflow direction louver to the horizontal position and
then carry out above steps 2 - 3 in the reverse order. The ON/OFF of Remote Controller receiving sound can be
change over by the following steps:
a. Release the Auto Switch after Test Run operation is
activated.
b. Then, within 20 sec. after (a), press Auto Switch for
more than 5 sec.
A “beep” “beep” sound will occur at the fifth sec., then
release the Auto switch.
c. Within 20 sec. after (b), press Auto Switch again.
Everytime Auto Switch is pressed (within 20 sec.
interval), remote controller receiving sound status will be
reversed between ON and OFF.
Long “beep” sound indicates that remote controller
receiving sound is OFF.
Short “beep” sound indicates that remote controller
receiving sound is ON.
42
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Caution
The CU-3C20DKH/C9DKZW have different cooling capacities depending on the connection to A1, A2 and/or B on CU-
3C20DKH individually.
(Refer to SPECIFICATIONS on CATALOG)
1. The Cooling Capacity of Indoor Unit connecting “B” on CU-3C20DKH (Called B unit) is different from that of A1 and A2
Units.
2. A1 and A2 Units share the same compressor, their cooling capacities thus change depending on whether one, the other,
or both of the units is in use.
3. Reflect the B or A (A1 and/or A2) on the Indoor Unit for later reference.
43
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
44
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
2) Air purging
The air which contains remaining moisture in the refrigeration
cycle may cause a malfunction on the compressor.
1. To purge the air, push the pin on the gas side 3-way valve
for three seconds using with a hexagonal wrench and set it
free for one minute.
• Repeat this three times.
2. To balance the refrigerant, close the low pressure side
valve on the manifold gauge and release a refrigerant from
the piping through service port until the gauge indicates
0.49 ~ 0.294 MPa.
3. Set the both 3-way valves to open position with the
hexagonal wrench for the unit operation.
3. Secure the cable onto the control board with the holder (clamper).
4. Confirm the SW1 Switch at AUTO position. (CU-3C20DKH)
5. Attach the control board cover back to the original position with the screw.
45
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
• Open front panel and remove air filters. • Operate the unit at cooling operation mode for fifteen
(Drainage checking can be carried out without removing the minutes or more.
front grille.) • Measure the temperature of the intake and discharge air.
• Pour a glass of water into the drain tray-styrofoam. • Ensure the difference between the intake temperature and
• Ensure that water flows out from drain hose of the indoor the discharge is more than 8°C.
unit.
CHECK ITEMS
46
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
11 3-way Valve
3-way Valve (Liquid Side) 3-way Valve (Gas Side)
47
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Procedure:
1. Recheck the piping connections. 6. Use torque wrench CWHAD-9211 to tighten the service port
2. Open the valve of the low pressure side of Manifold nut to a torque of 1.8 kg.cm.
gauge counter-clockwise for 10 seconds, and then 7. Set both the 3-way valves to the open position.
close it. 8. Mount the valve stem nuts to the 3-way valves.
3. Check for gas leakage. 9. Check for gas leakage.
• Check the flare connections for gas leakage. • At this time, especially check for gas leakage from both
4. Purge the air from the system. the 3-way valve’s stem nuts, and from the service port
• Open the Low pressure side valve of the manifold caps.
gauge.
• Press the valve core pin with the hexaganol wrench to Caution
If gas leakage is discovered in step 3 above, take the
purge the air for three seconds and then wait for one following procedures:
minute.
1. Re-tighten the connecting portion with torque
Repeat this three times or more. wrenches.
5. Balance the refrigerant in the pipings and the indoor If the leakage ceases, continue the works from
unit. step 4.
2. Locate and repair the leak. (Gas leak detector)
• Close the Low pressure side valve of the manifold
gauge. Repeat the works from step 1.
48
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Procedure:
1. Confirm that both the 3-way valves are set to the open 6. Operate the air conditioner at the cooling cycle and
position. stop it when the gauge indicates 0 kg/cm2G.
• Remove the valve stem caps and confirm that the valve • If the unit cannot be operated at the cooling (weather is
stems are in the raised position. rather cool), press the Pump Down switch on the Indoor
• Be sure to use a hexagonal wrench to operate the valve unit.
stems. • So that the unit can be operated.
2. Operate the unit for 10 to 15 minutes. 7. Immediately set the 3-way valve to the closed position.
• Do this quickly so that the gauge ends up indicating 1 to
3. Stop operation and wait for 3 minutes, then connect the 3 kg/cm2G.
charge set to the service port of the 3-way valves.
• Connect the charge hose with the push pin to the gas 8. Disconnect the charge set, and mount both the 3-way
side service port. valve’s stem nuts and the service port caps.
• Use torque wrench CWHAD-9211 to tighten the service
4. Air purging of the charge hose. port nut to a torque of 1.8 N.m.
• Open the low-pressure valve on the charge set slightly • Be sure to check for gas leakage.
to purge air from the charge hose.
49
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Procedure:
1. Remove the cap nut from 3-way valves. 5. Check for gas leakage.
• Remove the cap nut from 3-way valves after carefully • Check the flare connections for gas leakage.
checked whether the piping connection was properly
and certainly done.
6. Discharge the refrigerant.
• Close the valve on the gas cylinder and discharge the
2. Confirm that the valve in both 3-way valves are set to refrigerant until the gauge indicates 3 to 5 kg/cm2G.
the CLOSED position.
50
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Procedure:
1. Confirm that both the 3-way valves are set to the open
position.
51
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
11.3. Evacuation
(No refrigerant in the refrigeration cycle)
Procedure:
1. Connect the vacuum pump to the charge set’s centre
hose.
3. Close the valve (Lo side) on the charge set, turn off the
vacuum pump, and confirm that the gauge needle does
not move (approximately 5 minutes after turning off the
vacuum pump).
52
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Procedure:
1. Connect the charge hose to the charging cylinder. 4. Immediately disconnect the charge hose from both the
• Connect the charge hose which you disconnected from 3-way valve’s service ports.
the vacuum pump to the valve at the bottom of the • Stopping partway will allow the refrigerant to be
cylinder. discharged.
• If you are using a gas cylinder, also use a scale and • If the system has been charged with liquid refrigerant
reverse the cylinder so that the system can be charged while operating the air conditioner, turn off the air
with liquid. conditioner before disconnecting the hose.
2. Purge the air from the charge hose. 5. Mount the valve stem nuts and the service port caps.
• Open the valve at the bottom of the cylinder and press • Use a torque wrench CWHAD-9211 to tighten the
the check valve on the charge set to purge the air (Be service port nut to a torque of 1.8 N.m.
careful of the liquid refrigerant). The procedure is the • Be sure to check for gas leakage.
same if using a gas cylinder.
3. Open the valve (Lo side) on the charge set and charge
the system with liquid refrigerant.
• If the system cannot be charged with the specified
amount of refrigerant, it can be charged with a little at a
time (approximately 150 g each time) while operating
the air conditioner in the cooling cycle; however, one
time is not sufficient, wait approximately 1 minute and
then repeat the procedure. (pumping down-pin)
53
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
12 Servicing Information
12.1. Distinction of Lead Free (PbF) Printed Circuit Board
Printed circuit boards (manufactured) using lead free solder will have a PbF stamp on the Printed Circuit board.
CAUTION
• Pb free solder has a higher melting point than standard solder; typically the melting point is 50 - 70°F (30 - 40°C) higher.
Please use a high temperature solder iron and set it to 700 ± 20°F (370 ± 10°C).
• Pb free solder will tend to splash when heated too high (about 1100° F/600°C).
• If you must use Pb solder, please completely remove all of the Pb free solder on the pin or solder area before applying Pb
solder. If this is not pratical, be sure to heat the Pb free solder until it melts, before applying Pb solder.
Fig. 1
Fig. 2
54
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Fig. 4
12.3. Indoor Fan Motor and Cross Flow Fan Removal Procedures
Fig. 7
Fig. 6
Fig. 8
55
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
− Remove the earth wire from the evaporator (Fig. 7) − Remove the cross flow fan bushing from the chassis.
− Release the generator complete wire (green and red). (Fig. 9)
(Fig. 8) − Loosen the fan boss screw at the cross flow fan. (Fig. 9)
− Remove 2 screws on the right and 1 screw at the left
side of the control board. (Fig. 7)
− Press down the hook on the left side of control board.
(Fig. 7)
− Then pull out the Control Board Complete from the unit.
(Fig. 7)
Fig. 10
Fig. 9
56
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
• Under various setting mode, after select the transmission code combination of remote control, press any button of remote
control to transmit a signal to indoor unit. The transmission code will be stored in EEPROM.
• After signal is received, the various setting mode is cancelled and return to normal operation.
57
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
13 Troubleshooting Guide
13.1. Refrigeration cycle system
In order to diagnose malfunctions, make sure that there are no
electrical problems before inspecting the refrigeration cycle.
Such problems include insufficient insulation, problem with the
power source, malfunction of a compressor and a fan.
The normal outlet air temperature and pressure of the
refrigeration cycle depends on various conditions, the standard
values for them are shown in the table to the right.
58
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Inefficient compression
• Carry out the measurements of pressure, electric current, and temperature fifteen minutes after an operation is started.
• Electric current during operation becomes approximately 20% lower than the normal value.
Insufficient compressing of a compressor • The discharge tube of the compressor becomes abnormally hot (normally 70 to 90°C).
• The difference between high pressure and low pressure becomes almost zero.
• Electric current reaches a high level abnormally, and the value exceeds the limit of an
ammeter. In some cases, a breaker turns off.
Locked compressor
• The compressor has a humming sound.
59
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
14 Technical Data
14.1. Thermostat characteristics
60
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
61
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
62
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
63
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
64
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
(Note)
• All parts are supplied from PHAAM, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
65
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
Note:
The above exploded view is for the purpose of parts disassembly and replacement.
The non-numbered parts are not kept as standard service parts.
66
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
(Note)
• All parts are supplied from MAICO, Malaysia (Vendor Code: 061).
• “O” marked parts are recommended to be kept in stock.
67
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
c
R55 b
1k
Q01
Auto C143XKTX
SW BZ
2
BZ01 e
SW01 1
R11 R07
C01
1k 10k
0.01
SUPERSONIC COMPLETE R12 R88
1k C02 5.1k
0.01
R78
10k
R602 CN-SONIC CN-SONIC
C601 5.1k
IC601 1 1
0.1
2 2
R601 3 3
R603 1k
X601
1M
R68
100
DISPLAY COMPLETE
IC401
C24 0.01
1 R13 220
R401 47 C25 0.01
2 R14 220
C26 0.01
3
+ C401
R15
47
220
6.3V CN-DISP
10 1
TIMER/AIR SW(ORG) D402
9 2
POWER(GRN) D401 C29
8 3
7 4 0.1 R17
POWERFUL(ORG)
6 5 220
D403
5 6
QUIET(ORG) D404
4 7 R27 220
ION(GRN) D405
3 8
2 9
D406 c
1 10 R73
SUPERSONIC(BLU) C28 C27 C35 b
3.3k
0.01 0.01 0.01
CN-DISP
Q09
R31
1k
R56
1k
R58
C22
CN-HA 0.01 10k
R59 1k
4
3 JP5
2
1
C23 R60
0.01 10k
68
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
3XKTX
C38
1000p
R10
10k
R18 D12
R19 D11
R20 D10
R21 D09
R22 D08
R23 D07
R24 D06
R25 D05
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
P67
P66
P65
P75
P47
P46
P45
P44
P43
P42
P41
P40
P64
P74
P73
P72
P71
1 48
P50
2 RY-PWR DRIVE SIGNAL STEPPING TOD 47
P51 MOTOR AUTO OPERATION
DRIVE TEST RUN P03 46
3 SIGNAL REMOTE CONTROL
P52
SOUND
INTP2
4 BUZZER 45
P53 POWER CLOCK INPUT
DISPLAY INTP1
5 44
P54
REMOTE-CONTROL
6 COMMAND INPUT INTP0 43
P55
7 Vss1 42
P56
IC01 X1 41
8 P57
R06 24k OSC X2 40
9 Vss0
JP2
10 VDD0 IC(VPP) 39
R75 1k
C39 11 P30 XT1 38
R76 1k
12 P31 XT2 37
R74 1k RESET 36
13 P32 RESET
INTAKE AIR TEMP
R77 1k AVDD
14 POWER 35
P33 PIPE TEMP
15
TIMER SHORTEN AVref 34
P34 AUTO RESTART GROU ND
AN10
16 33
P35
SCK30
AN17
AN16
AN15
AN14
AN13
AN12
AN11
VDD1
AV55
S130
S030
P36
P23
P24
P25
17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32
1 8 16
2 15
8 RY-PWR 5 DI
1 16 3 14 R09 SK 4
2 15
10k JX2
R05 4 13
6 DO CS 3
3 14 43 5 12
4 13 1/2W 6 11 7 GND Vcc 2
5 12 7 10 C05
R04 8 RS 0.1
6 11 R/B 1
43 9 16V
7 10 1/2W
9
IC02
IC05 IC06 C3EBDG000021
B1HBGGF00013
B1HBGGF00013 C04 R30 R33 C08
0.1 20k 15k 0.1
16V 16V
5 4 3 2 1 4 3 2 1
CN-STM1 (PH) CN-TH (RED)
5 4 3 2 1 (ZH5)
PIPE TEMP. SENSOR AIR TEMP. SENSOR
(20k 3950) (15k 3950)
VERTICAL
69
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
R66 R48
IC04 IC03
T01 REGULATOR REGULATOR
DB01
5 8 ~
+
2 13 I 12V O I 5V O
C17 C14 C11
~ 3300 G 470 G 100
35V 25V 16V
c
b R03 1.3k D16 R57 12k
Q02
C143XKTX c C07 RY-PWR
e R29
0.1 L
b 4.7k 1.6k D15
16V R47 12k
FUSE
P
10k T 2A L 250V
C03 TEMPERATURE
e ZNR01
0.047 FUSE
AC-WHT
Q03 SSR01
C143XKTX c
b 4.7k L01 1
125 H
TO
10k 2 OUTDOOR
e
3
SSR01
CR03
R32 X01
150k C19
0.047
4.096 MHz
(47pF X 2) CN-FM
1
C-FM 2
3 FAN MOTOR
R50 1.5 4
5
JP3 R49 1k 100k
R51
Z01 0.1
c 16V
JP4 10 k 7.5V
b Q06 C21
C10
C36 c C2412KTX R53 R52 10
0.1 Q05
C37 10k 6.2k 50V
16V R79 e b
0.01 C2412KTX
10k
+
e R54
6.2k
R38 C15 R43
0.01
CN-ION
JX1 4
3
2
R37 1
10k R61
R62 10 k
C31
D01
c Q08 0.01
TEST
R02 1k 1 2 b
R67
R01
Q07
10 k
e R64 c C32
6.2k 0.01
b
R63
6.2k e
70
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
R101 CN2
F1 T1 D101 R102 HV
CH1
4 R2 R3
3 R6
VIN
2
GND
1 D102
ERR
c c Q4
Q1 R13 R9 C5
EH-4P b b
Q2
e c C101
C8 D1 e D3 D5 -4.2kV
b Q5 R15
c
C2 C1 e C3 R4 b Z02
4.7k 10k e R10
R5 R14
C6 R12 C7
D4 CN3
D2 Z01 GND
71
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
CU-2C18DKH
TO
INDOOR
UNIT
AC 220-230-240 V
50 Hz
SINGLE PHASE TO INDOOR
UNIT B
OUTDOOR UNIT
L N 1 2 3 1 2 3 TERMINAL FUSE
YELLOW
W W BL BR Y W Y B W
W
1
TO
2 BLUE
OUTDOOR
RED
BR 3 MARK
Y
COMPRESSOR
TERMINAL
OLP A CAPACITOR A
3
B B
R B Y
1 11 A
MAGNETIC Y BL BR B CAPACITOR B
RELAY A
12 B OLP B
Y CN-CTL
FM1 (B)
1 7 R B
3
COMPRESSOR A
1
B B
FUSE
(3.15A, 250V) Y
R
11 A COMPRESSOR B
Y
MAGNETIC
RY1 RELAY B
FM2 (Y) RY2 12 B
B FAN MOTOR
BL
CAPACITOR
72
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
CU-3C20DKH
3 3
RED BLU RED BLU
GRY BLU
CAPACITOR BLU CAPACITOR
BLU
CAPACITOR
ELECTRONIC
COMP-A (GRN) BLU
AC(WHT) COMP-B
P L
(WHT) (YEL) L P
VH7-4 CONTROL DEVICE
CN-V 1 3 5 7
RY-CA RY-CB FM(YEL) FM(BLU)
FUSE
3.15A CR2 CR3 CR1
250V
120 120 120
AC(BLU)
T(BLK)
T(BLK)
ZNR1
511
TRANSFORMER
ZD1
DB101
IC3 IC2 R16 R28 7.5EL1
100k
S1VB20 78M12H 78N05 1k
RED R27
C7 10k R25
I 12V O I 5V O 1 6.8k
RED C1 C2 C3 GND 50V
2200 470 100
G G
CN-T 35V 25V 16V Q7
R26 C6
VH-2 2SC1740S Q6 6.2k 0.01
2SC1740S
IC1 R13
10k RY-FM
A52C401828CP
Q3
DTC113ZS
28 Vdd RESET 1 D11
WHT
1k
TO L X1 10k
POWER SOURCE 4KHz 27 OSC 1 IRQ 2
AC240- 230-220 V R15
BLU
50 Hz N PC1 150k
26 OSC 2 R24
PA 7 3
(RED) R1 TLP620-1G4 82
C12
A1 AC 47k 2W 1 4 0.01 Q2 2W
1 25 TCAP/PD 7 PA 6 4
2SC1741R RY-CB
BLK
(RED) C4
TO A1 AC 2 3 470
INDOOR 2 24 TCMP PA 5 5 50V
WHT
UNIT A1 R2
R7
C9 R8 R21 D8
47k 2W 10 R22
PC2 10k 1k 2.2k RA15-01 R23
3 TLP620-1G4
16V 23 PD 5 PA 4 6 10k
82
(BLUE) R3
2W
A2 AC 47k 2W 1 4
1 22 PC 0 PA 3 7
R19
RY-CA
BLK
(BLUE) C5
TO 2.2k
A2 AC 2 3 470
INDOOR 2 21 PC 1 PA 2 8 35V
WHT
TO (YEL) RY-VA2
INDOOR B AC 2 3
UNIT 2 18 PC 4/AD 2 PB 5/SDO 11
R6 C11 R17
R11 R12
47k 2W 10 1k
10k 1k
3 16V 17 PC 5/AD 1 PB 6/SDI 12 D9
1k 10k
OUTDOOR UNIT 16 PC 6/AD 0 R14
PB 7/SCK 13
TERMINAL 10k
SW1
15 PC 7/VREFH Vss 14 Q4
DTC113ZS
RY-VA1
MANUAL AUTO
R18
TEST 1k
YELLOW
2 1 D10
NH-2 1k 10k
Q5
BLUE RED RA1
DTC113ZS
10k x 5
MARK
COMPRESSOR
TERMINAL
73
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
74
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
TIMER TABLE
Test Mode
Name Time (When test point Remarks
Short-circuited)
Real Timer 1 hr. 1 min.
10 min. 10 sec.
1 min. 1 sec.
Time Delay Safety Control 2 min. 58 sec. 0 sec.
Forced Operation 60 sec. 0 sec.
Time Save Control 7 min. 4.2 sec.
Anti-Freezing 4 min. 0 sec.
Auto Mode Judgement 20 sec. 0 sec.
Soft Dry OFF 6 min. 36 sec.
ON 10 min. 60 sec. Soft Dry: 10 min. operation
Cooling 40 sec. 4 sec.
70 sec. 7 sec.
Deodorizing Control 20 sec. 2 sec.
180 sec. 18 sec.
Soft Dry 40 sec. 4 sec.
360 sec. 36 sec.
Comp. Reverse Rotation Detection 5 min. 30 sec. Comp. ON 5 min. and above
2 min. 0 sec.
Comp./ Fan Motor Delay Timer 1.6 sec. 0 sec.
Powerful Mode Operation 15 min. 15 sec.
Random Auto Restart Control 0 ~ 62 sec. 0 ~ 6.2 sec.
Ion OFF Timer 10 min. 10 sec.
Random FM Timer (Economy Mode) 5 sec. 5 sec.
75
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
76
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
77
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
78
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH
79
CS-C9DKZW CU-2C18DKH / CS-C9DKZW CU-3C20DKH