Sunteți pe pagina 1din 8

This article looks at the sizing of batteries for stationary applications (i.e.

they don't
move). Batteries are used in many applications such as AC and DC uninterruptible power
supply (UPS) systems, solar power systems, telecommunications, emergency lighting,
etc. Whatever the application, batteries are seen as a mature, proven technology for
storing electrical energy. In addition to storage, batteries are also used as a means for
providing voltage support for weak power systems (e.g. at the end of small, long
transmission lines).

Why do the calculation?

Sizing a stationary battery is important to ensure that the loads being supplied or the
power system being supported are adequately catered for by the battery for the period of
time (i.e. autonomy) for which it is designed. Improper battery sizing can lead to poor
autonomy times, permanent damage to battery cells from over-discharge, low load
voltages, etc.

When to do the calculation?

The calculation can typically be started when the following information is known:

• Battery loads that need to be supported


• Nominal battery voltage
• Autonomy time(s)

Calculation Methodology
The calculation is based on a mixture of normal industry practice and technical standards
IEEE Std 485 (1997, R2003) "Recommended Practice for Sizing Lead-Acid Batteries for
Stationary Applications" and IEEE Std 1115 (2000, R2005) "Recommended Practice for
Sizing Nickel-Cadmium Batteries for Stationary Applications". The calculation is based
on the ampere-hour method for sizing battery capacity (rather than sizing by positive
plates).

The focus of this calculation is on standard lead-acid or nickel-cadmium (NiCd) batteries,


so please consult specific supplier information for other types of batteries (e.g. lithium-
ion, nickel-metal hydride, etc). Note also that the design of the battery charger is beyond
the scope of this calculation.

There are five main steps in this calculation:


1) Collect the loads that the battery needs to support
2) Construct a load profile and calculate the design energy (VAh)
3) Select the battery type and determine the characteristics of the cell
4) Select the number of battery cells to be connected in series
5) Calculate the required Ampere-hour (Ah) capacity of the battery

Step 1: Collect the battery loads

The first step is to determine the loads that the battery will be supporting. This is largely
specific to the application of the battery, for example an AC UPS System or a Solar
Power System.

Step 2: Construct the Load Profile

Refer to the Load Profile Calculation for details on how to construct a load profile and

calculate the design energy, , in VAh.

The autonomy time is often specified by the Client (i.e. in their standards). Alternatively,
IEEE 446, "IEEE Recommended Practice for Emergency and Standby Power Systems for
Industrial and Commercial Applications" has some guidance (particularly Table 3-2) for
autonomy times. Note that IEEE 485 and IEEE 1115 refer to the load profile as the "duty
cycle".

Step 3: Select Battery Type

The next step is to select the battery type (e.g. sealed lead-acid, nickel-cadmium, etc).
The selection process is not covered in detail here, but the following factors should be
taken into account (as suggested by IEEE):

• Physical characteristics, e.g. dimensions, weight, container


material, intercell connections, terminals
• application design life and expected life of cell
• Frequency and depth of discharge
• Ambient temperature
• Charging characteristics
• Maintenance requirements
• Ventilation requirements
• Cell orientation requirements (sealed lead-acid and NiCd)
• Seismic factors (shock and vibration)

Next, find the characteristics of the battery cells, typically from supplier data sheets. The
characteristics that should be collected include:

• Battery cell capacities (Ah)


• Cell temperature
• Electrolyte density at full charge (for lead-acid batteries)
• Cell float voltage
• Cell end-of-discharge voltage (EODV).

Battery manufacturers will often quote battery Ah capacities based on a number of


different EODVs. For lead-acid batteries, the selection of an EODV is largely based on
an EODV that prevents damage of the cell through over-discharge (from over-expansion
of the cell plates). Typically, 1.75V to 1.8V per cell is used when discharging over longer
than 1 hour. For short discharge durations (i.e. <15 minutes), lower EODVs of around
1.67V per cell may be used without damaging the cell.

Nickel-Cadmium (NiCd) don't suffer from damaged cells due to over-discharge. Typical
EODVs for Ni-Cd batteries are 1.0V to 1.14V per cell.

Step 4: Number of Cells in Series

The most common number of cells for a specific voltage rating is shown below:

Rated Lead-
Ni-Cd
Voltage Acid
12V 6 9-10
24V 12 18-20
48V 24 36-40
125V 60 92-100
250V 120 184-200

However, the number of cells in a battery can also be calculated to more accurately match
the tolerances of the load. The number of battery cells required to be connected in series
must fall between the two following limits:

(1)

(2)

where is the maximum number of battery cells

is the minimum number of battery cells


is the nominal battery voltage (Vdc)

is the maximum load voltage tolerance (%)


is the minimum load voltage tolerance (%)
is the cell charging voltage (Vdc)
is the cell end of discharge voltage (Vdc)

The limits are based on the minimum and maximum voltage tolerances of the load. As a
maximum, the battery at float voltage (or boost voltage if applicable) needs to be within
the maximum voltage range of the load. Likewise as a minimum, the battery at its end of
discharge voltage must be within the minimum voltage range of the load. The cell
charging voltage depends on the type of charge cycle that is being used, e.g. float, boost,
equalising, etc, and the maximum value should be chosen.

Select the number of cells in between these two limits (more or less arbitrary, though
somewhere in the middle of the min/max values would be most appropriate).

Step 5: Determine Battery Capacity

The minimum battery capacity required to accommodate the design load over the
specified autonomy time can be calculated as follows:

where is the minimum battery capacity (Ah)

is the design energy over the autonomy time (VAh)


is the nominal battery voltage (Vdc)
is a battery ageing factor (%)
is a temperature correction factor (%)
is a capacity rating factor (%)
is the maximum depth of discharge (%)

Select a battery Ah capacity that exceeds the minimum capacity calculated above. The
battery discharge rate (C rating) should also be specified, approximately the duration of
discharge (e.g. for 8 hours of discharge, use the C8 rate). The selected battery
specification is therefore the Ah capacity and the discharge rate (e.g. 500Ah C10).
Temperature correction factors for vented lead-acid cells (from IEEE 485)

An explanation of the different factors:

• Ageing factor captures the decrease in battery performance due to


age.

The performance of a lead-acid battery is relatively stable but drops markedly at


latter stages of life. The "knee point" of its life vs performance curve is
approximately when the battery can deliver 80% of its rated capacity. After this
point, the battery has reached the end of its useful life and should be replaced.
Therefore, to ensure that battery can meet capacity throughout its useful life, an
ageing factor of 1.25 should be applied (i.e. 1 / 0.8). There are some exceptions,
check with the manufacturer.
For Ni-Cd batteries, the principles are similar to lead-acid cells. Please consult the
battery manufacturer for suitable ageing factors, but generally, applying a factor
of 1.25 is standard. For applications with high temperatures and/or frequent deep
discharges, a higher factor of 1.43 may be used. For more shallower discharges, a
lower factor of 1.11 can be used.

• Temperature correction factor is an allowance to capture the


ambient installation temperature. The capacity for battery cells are typicall
quoted for a standard operating temperature of 25C and where this differs
with the installation temperature, a correction factor must be applied.
IEEE 485 gives guidance for vented lead-acid cells (see figure right),
however for sealed lead-acid and Ni-Cd cells, please consult manufacturer
recommendations. Note that high temperatures lower battery life
irrespective of capacity and the correction factor is for capacity sizing
only, i.e. you CANNOT increase battery life by increasing capacity.

• Capacity rating factor accounts for voltage depressions during


battery discharge. Lead-acid batteries experience a voltage dip during the
early stages of discharge followed by some recovery. Ni-Cds may have
lower voltages on discharge due to prolonged float charging (constant
voltage). Both of these effects should be accounted for by the capacity
rating factor - please see the manufacturer's recommendations. For Ni-Cd
cells, IEEE 1115 Annex C suggests that for float charging applications, Kt
= rated capacity in Ah / discharge current in Amps (for specified discharge
time and EODV).

Worked Example

Load profile for this example

Step 1 and 2: Collect Battery Loads and Construct Load Profile

The loads and load profile from the simple example in the Energy Load Profile
Calculation will be used (see the figure right). The design energy demand calculated for
this system is Ed = 3,242.8 VAh.

Step 3: Select Battery Type

Vented lead acid batteries have been selected for this example.

Step 4: Number of Cells in Series


Suppose that the nominal battery voltage is Vdc = 120Vdc, the cell charging voltage is Vc
= 2.25Vdc/cell, the end-of-discharge voltage is Veod = 1.8Vdc/cell, and the minimum and
maximum load voltage tolerances are Vl,min = 10% and Vl,max = 20% respectively.

The maximum number of cells in series is:

cells

The minimum number of cells in series is:

cells

The selected number of cells in series is 62 cells.

Step 5: Determine Battery Capacity

Given a depth of discharge kdod = 80%, battery ageing factor ka = 25%, temperature
correction factor for vented cells at 30 deg C of kt = 0.956 and a capacity rating factor of
kc = 10%, the minimum battery capacity is:

Ah

Computer Software
Some battery manufacturers (such as Alcad) also provide software programs to size
batteries using basic input data such as load profiles, autonomies, etc. The software will
size the batteries and will often also provide details regarding different battery rack (or
enclosure) dimensions.

What Next?
Using the results of the battery sizing calculation, the approximate dimensions of the
batteries can be estimated based on typical vendor information. This will assist in
determining the size, number and dimensions of the battery racks or cabinets required,
which can then be used as input into the equipment / room layouts. Preliminary budget
pricing can also be estimated based on the calculation results.

S-ar putea să vă placă și