ARCB Setting at Trashiyangtse (Bomdelling feeder)

CONTROL AND HARDWARE CONFIGURATION


Set Clock
Write Maximum Interrupter Duty: 7.0 [amp^1.5 * 10^6]
Write Line Frequency: 50 [Hz]
Write CT Ratio: 500:1

BASIC CONTROL SETTINGS


Write Phase Minimum Trip: 50 [amps]
Write Earth Minimum Trip: 10 [amps]
Write Sensitive Earth Fault Minimum Trip: 10 [amps]
Write Phase Alternate Minimum Trip: 50 [amps]
Write Earth Alternate Minimum Trip: 10 [amps]
Write Sensitive Earth Fault Alternate Minimum Trip: 10 [amps]
Write Reclose Interval 1: 2.0 [secs]
Write Reclose Interval 2: 2.0 [secs]
Write Reclose Interval 3: 5.0 [secs]
Write Reclose Attempts: 1
Write Reclose Retry Time: 1 [secs]
Write Reclaim Time: 30 [secs]
Write Phase Operations to Lockout: 3
Write Earth Operations to Lockout: 3
Write Sensitive Earth Fault Operations to Lockout: 3
Write Earth Trip Block On/Off: Off
Write Sensitive Earth Fault Protection On/Off: On
Write Alternate Minimum Trip On/Off: Off
Write Non-Reclose On/Off: Off

TIME CURRENT CURVES (TCCS)


Write Sensitive Earth Fault Trip Time: 50.0 [secs]

COLD LOAD PICKUP (CLPU)


Write CLPU Time: 60 [secs]
Write CLPU Phase Operations to Lockout: 3
Write CLPU Earth Operations to Lockout: 3

ADVANCED CONTROL SETTINGS


Write Earth HCLO Multiple: 30 [Amps/Amps]
Write Phase HCLO Multiple: 30 [Amps/Amps]
Write Sequence Coordination On/Off: On
Write Earth Trip Precedence On/Off: On
Write Target Reset on Reclose On/Off: On
Write Operation Counter On/Off: On
Write Event Recorder On/Off: On
Write Interrupter Duty On/Off: On
Write Earth HCLO On/Off: On
Write Phase HCLO On/Off: On
Write HCLO Phase Operation 1 Flag On
Write HCLO Phase Operation 2 Flag Off
Write HCLO Phase Operation 3 Flag Off
Write HCLO Phase Operation 4 Flag Off
Write HCLO Earth Operation 1 Flag On
Write HCLO Earth Operation 2 Flag Off
Write HCLO Earth Operation 3 Flag Off
Write HCLO Earth Operation 4 Flag Off

DIAGNOSTICS

METERING, COUNTERS, AND CONTROL STATE


Reset Earth Targets
Reset Phase 1-2 Targets
Reset Phase 3-4 Targets
Reset Phase 5-6 Targets
Reset Sensitive Earth Fault Targets
Reset Operation Counter
Reset Events Since Last Reset
Reset Auxiliary Events Since Last Reset
Reset Earth Maximum Thermal Current
Reset Phase 1-2 Maximum Thermal Current
Reset Phase 3-4 Maximum Thermal Current
Reset Phase 5-6 Maximum Thermal Current
Write Maximum Thermal Demand Update Interval: 15 [minutes]
Write Phase Thermal Demand Integration Time: 15 [minutes]
Write Earth Thermal Demand Integration Time: 5 [minutes]
Reset Target Flag-Earth
Reset Target Flag-Phase 1-2
Reset Target Flag-Phase 3-4
Reset Target Flag-Phase 5-6
Reset Target Flag-Sensitive Earth Fault