800xA Minerals Training

Chapter 5 AC 800M Hardware

TABLE OF CONTENTS

Chapter 5 AC 800M Hardware...................................................................................................................................................... 1


5.1 General Information............................................................................................................................................................. 3
5.1.1 Objectives ..................................................................................................................................................................... 3
5.1.2 Legend .......................................................................................................................................................................... 3
5.1.3 Reference Documentation............................................................................................................................................. 3
5.2 Overview AC 800M Hardware............................................................................................................................................ 4
5.3 Central Processing Unit ....................................................................................................................................................... 5
5.3.1 Components .................................................................................................................................................................. 5
5.3.2 Different Processor Units.............................................................................................................................................. 6
5.3.3 Start Modes................................................................................................................................................................... 7
5.3.4 Battery .......................................................................................................................................................................... 8
5.3.5 AC 800M Communication Ports .................................................................................................................................. 9
5.3.6 AC 800M High Integrity Controller ........................................................................................................................... 10
5.4 Communication Interface Units......................................................................................................................................... 11
5.4.1 Overview..................................................................................................................................................................... 11
5.4.2 Communication Exchange Bus - CEX Bus ................................................................................................................ 12
5.5 Input / Output Modules...................................................................................................................................................... 13
5.5.1 Range of ABB I/O Modules ....................................................................................................................................... 13
5.5.2 I/O Connection Possibilities ....................................................................................................................................... 14
5.5.3 S800 I/O Connected with ModuleBus ........................................................................................................................ 15
5.5.4 S800 I/O Connected with PROFIBUS........................................................................................................................ 16
5.5.5 Limitations of CI801................................................................................................................................................... 17
5.5.6 MTU – Module Terminal Unit for S800 I/O .............................................................................................................. 17
5.6 Hardware Redundancy....................................................................................................................................................... 18
5.6.1 Redundant Processor Unit - PM861/PM864/PM865 .................................................................................................. 18
5.6.2 Controller and I/O Redundancy .................................................................................................................................. 19
5.6.3 Redundant ModuleBus I/O Connections .................................................................................................................... 20
5.6.4 Redundant PROFIBUS I/O Connections.................................................................................................................... 21
5.7 Hardware Configuration .................................................................................................................................................... 22
5.7.1 Configuration Steps .................................................................................................................................................... 22
5.7.2 Adding a Controller CPU ........................................................................................................................................... 23
5.7.3 Adding a Communication Interface Module............................................................................................................... 24
5.7.4 Hardware Libraries ..................................................................................................................................................... 24
5.7.5 Adding S800 I/O on ModuleBus ................................................................................................................................ 26
5.7.6 Adding S800 I/O on PROFIBUS................................................................................................................................ 27
5.7.7 Hierarchical Dot Notation........................................................................................................................................... 28
5.7.8 Settings of I/O Units ................................................................................................................................................... 29
5.7.9 Adding Compact Flash ............................................................................................................................................... 30
5.8 Communication to AC800M Controller ............................................................................................................................ 31
5.8.1 How to Use the IPConfig Utility ................................................................................................................................ 31
5.8.2 How to Configure the IP Address............................................................................................................................... 34
5.8.3 How to Download the Firmware................................................................................................................................. 35
5.9 Application Download....................................................................................................................................................... 37
5.9.1 General........................................................................................................................................................................ 37
5.9.2 Restart Options ........................................................................................................................................................... 37
5.9.3 Download.................................................................................................................................................................... 38
5.9.4 Difference Report ....................................................................................................................................................... 39
5.9.5 Re-Authentication....................................................................................................................................................... 40
5.10 Online Functions.............................................................................................................................................................. 41
5.10.1 General...................................................................................................................................................................... 41

Chapter 5 - 1
05 AC800M Hardware - RevC.doc

5.10.2 Status of I/O-Signals ................................................................................................................................................. 41


5.10.3 Forcing ...................................................................................................................................................................... 42
5.11 Test Mode & SoftController ............................................................................................................................................ 43
5.11.1 Test Mode ................................................................................................................................................................. 43
5.11.2 How to use the SoftController................................................................................................................................... 43

Chapter 5 - 2
800xA Minerals Training

5.1 General Information

5.1.1 Objectives
Upon completion of this chapter, you will be able to:
• Describe the AC 800M hardware components
• Set up communication to controller AC 800M
• Upgrade the controller firmware
• Configure the hardware in the Control Project
• Download and test hardware in online mode

5.1.2 Legend
> Indicates when you go from one menu to a sub-menu
Italic Indicates object and file names
“ “ Indicates dialog box buttons, tabs, menus etc.
Bold Indicates important topics
Indicates start/explanation of student activity

5.1.3 Reference Documentation


3BSE036351 Industrial IT 800xA – Control and I/O
AC 800M Controller - Hardware and Operation
3BSE035980 Industrial IT 800xA – Control and I/O
Basic Control Software – Introduction and Configuration
3BSE020923 Industrial IT 800xA – Control and I/O
S800 I/O – General Information and Installation
3BSE020924 Industrial IT 800xA – Control and I/O
S800 I/O – Modules and Termination Units

Chapter 5 - 3
05 AC800M Hardware - RevC.doc

5.2 Overview AC 800M Hardware


The AC 800M controller consists of a selection of units mounted on horizontal DIN-
rails, which can be housed within an enclosure. The majority of units consist of a base
mounting plate and removable cover attached with screws.

The hardware units that form the AC 800M controller are:


• Central Processor Unit (CPU)
• Communication interface modules for different protocols
• S800 I/O modules
• Power supply modules

Optional up to CPU S800 I/O


12 Communication
modules

RS-232 channels
Redundant Ethernet

Various I/O systems can be connected to the AC 800M controller, either directly
(S800 I/O) or via PROFIBUS or FOUNDATION Fieldbus.

Chapter 5 - 4
800xA Minerals Training

5.3 Central Processing Unit

5.3.1 Components
The CPU consists of a base plate TP830 and a replaceable processor module PM8xx
with various speed and memory combinations.

Fuses for Modulebus


and CEX-bus

CPU Baseplate

The base plate TP830 carries the majority of the connections to processor, the power
supplies and communication interfaces, as well as to the external buses.

A Compact Flash (CF) can be inserted to the card slot located at the front of AC 800M
controllers. The card will be activated and read after a long controller reset (or power
failure) and your application(s) can be loaded into the controller without performing
an application download from a Control Builder station.

Chapter 5 - 5
05 AC800M Hardware - RevC.doc

5.3.2 Different Processor Units


The key differences between the different CPUs are memory, working frequency and
redundancy.

Redundant Redundant
PM864 PM865

Redundant
PM861

PM860
PM856 32MB
32MB
PM851 96 MHz
96 MHz
SIL2
16MB
48 MHz

8MB
48 MHz
8MB
24 MHz
8MB
24 MHz

Unit Description On-line Redundancy


replacement
PM851 24 MHz (48MHz for communication) / 8 Mbytes RAM No No
1 Ethernet port, 1 Serial port and 1 tool port. Application
speed is half of PM860. Maximum one CEX bus module.
PM856 24 MHz (48MHz for communication) / 8 Mbytes RAM No No
2 Ethernet ports, 1 Serial port and 1 tool port. Application
speed is half of PM860.
PM860 48 MHz / 8 Mbytes RAM No No
2 Ethernet ports, 1 Serial port and 1 tool port.
PM861 48 Mhz / 16 Mbytes RAM Yes Yes
2 Ethernet ports, 1 Serial port and 1 tool port. Singular or
redundant.
PM861A Same as PM861 but can use redundant communication unit Yes Yes
CI854A, CI860 and BC810.
PM864 96 Mhz / 32 Mbytes RAM Yes Yes
2 Ethernet ports, 1 Serial port and 1 tool port. Singular or
redundant. PM864 is 50% faster than PM861 in executing
an application.
PM864A Same as PM864 but can use redundant communication unit Yes Yes
CI854A, CI860 and BC810.
PM865 (PA/HI) 96 Mhz / 32 Mbytes RAM Yes Yes
2 Ethernet ports, 1 Serial port and 1 tool port. PM865 can be
used in an AC 800M High Integrity system.

Chapter 5 - 6
800xA Minerals Training

5.3.3 Start Modes


The controller may be started with the following start modes:

Mode Invoked by Description


Warm Init Power Off/On with a Applications restart with retain values.
battery backed up CPU
Cold Init Press Init < 2.5 s Applications restart with cold retain values.
Reset Press Init > 3 s or until Applications are deleted in controller.
Run LED flashes

Chapter 5 - 7
05 AC800M Hardware - RevC.doc

5.3.4 Battery
The memory is backed up by an internal or an external battery. You should mount the
battery when the CPU is up and running with a loaded application.

Internal External

The backup time varies depending on CPU type and battery types.

CPU Type Internal Battery External Battery


min time (hours) min time (weeks)
PM851/PM856/PM860 48 4
PM861 36 4
PM864 36 3
PM861A 118 12
PM864A 235 24
PM865 HI 235 24
PM865 PA 235 24

NOTE! A Compact Flash card can be used for non-volatile


storage of application and data.

Chapter 5 - 8
800xA Minerals Training

5.3.5 AC 800M Communication Ports


Detailed description of the communication ports of the CPU:

Communication CPU
Expansion CEX-bus
S800I/O’s on the
Electrical ModuleBus

RCU link
connection

Fiber opticale
Ethernet ports COM 3-4 ports ModuleBus

• Two built-in Ethernet ports (IEEE 802.3, 10BaseT with TCP/IP):


CN1
CN2 used for redundancy
• Two built-in RS-232 serial ports:
COM3 with modem support for several protocols
COM4 intended as tool port for Control Builder
• Built-in ModuleBus for optical or electrical connection to I/O communication
• Built-in CEX-bus (Communication Extended Bus) for external communication
modules

NOTE! In a configuration with redundant CPUs, COM3 and the


electrical ModuleBus cannot be used.

Chapter 5 - 9
05 AC800M Hardware - RevC.doc

5.3.6 AC 800M High Integrity Controller


AC 800M can easily be configured for usage in safety critical applications. The main
components of such a system are PM865, SM810, SS823 and the S800 I/O High
Integrity system, running a High Integrity version of Control Software.

The PM865 processor unit has higher HW fault tolerance, compared to PM864. The
added functionality on PM865 includes:
• Double over voltage protection on internal voltages
• Additional watchdog timer updated with data from SM810
• Increased oscillator supervision
• Support for S800 I/O High Integrity system
• Increased system diagnostic and online self tests

The main function of the SM810 is to act as a monitor for the HW and SW execution
of PM865 and these two modules together are a SIL2 compliant system according to
IEC61508. The SM810 is running a SIL2 certified operating system and have a very
high degree of self-diagnostic.

Chapter 5 - 10
800xA Minerals Training

5.4 Communication Interface Units

5.4.1 Overview
A number of communication modules can be connected to the CEX bus.

CI854A

PM8xx
CI867
CI865
CI862
CI860
CI858

CI857

CI856
CI855

CI853
PROFIBUS DP
Modbus TCP

DriveBus
TRIO I/O

S100 I/O
FF HSE
Satt I/O

INSUM

MB300

RS232

The table below is a summary of the interfaces (for details refer to hardware manual):

Unit Description On-line Redundancy


replacement
CI851 PROFIBUS DP-V0 communication interface unit. No No
Only to use with S200 I/O.
CI853 RS-232C serial communication interface unit. No No
CI854 PROFIBUS DP-V1 communication interface unit. No No
Redundant Profibus cabling possible.
CI854A PROFIBUS DP-V1 communication interface unit. Yes Yes
Redundant Profibus cabling and redundant interface cards.
CI855 MasterBus 300 communication interface unit for the AC 800M. Yes No
CI856 S100 I/O system communication interface unit. Yes No
Up to five S100 I/O racks can be connected to one CI856 where
each I/O rack can hold up to 20 I/O boards.
CI857 INSUM communication interface unit. Yes No
CI858 Communication interface for ABB Drives using DriveBus No No
CI860 Fieldbus Foundation HSE communication interface unit. Yes No
Not possible to use in AC800M HI.
CI865 Communication interface unit for older Satt I/O systems. Yes No
CI867 Provides communication with Modbus TCP via Ethernet. Yes No

Chapter 5 - 11
05 AC800M Hardware - RevC.doc

5.4.2 Communication Exchange Bus - CEX Bus

TB850

TK850 with DB25P and TB851


or

• Up to 12 communication units can be placed on the CEX bus


• The CEX-bus must be terminated if a communication unit is connected. A CEX-
bus termination is delivered with the CPU: TB850 (male) or TB851 (female).
• An extension cable TK850 with connector DB25P with metal housing and a
length of 0.7 meter (2.3’) can be used for extending the CEX bus to a second DIN
rail.

Chapter 5 - 12
800xA Minerals Training

5.5 Input / Output Modules

5.5.1 Range of ABB I/O Modules


The following I/O types can be connected to an AC 800M system:
• S800 modular I/O
• S800 modular I/O with intrinsic safety (IS)
• S800L I/O
This is a compact I/O with an integrated I/O and terminal unit. This I/O cannot be
replaced on-line.
• S200 I/O
This I/O must be connected through communication module CI865
• S900 I/O
This I/O must be connected through a CI920 PROFIBUS module. The I/O is
suitable for use in hazardous areas.
• S100 I/O
This I/O must be connected through communication module CI856

Chapter 5 - 13
05 AC800M Hardware - RevC.doc

5.5.2 I/O Connection Possibilities


I/O units are connected in two ways:
• ModuleBus (electrical or optical)
• PROFIBUS DP
An I/O cluster consists of one CI830/CI801 or TB820 and a number of I/O modules.
Max. 12 I/O modules can be included in one I/O cluster.
S900 I/O can only be connected through PROFIBUS DP.

The PROFIBUS slave CI830/CI801 can be also be supplied with an adapter TB810 to
extend the ModuleBus by optical cable.
NOTE! CI830 is replaced by CI801 to support the HART
protocol.

Chapter 5 - 14
800xA Minerals Training

5.5.3 S800 I/O Connected with ModuleBus


The ModuleBus interface is used for handling local S800 I/O on the AC 800M
controller. I/O units connected to ModuleBus are organized into clusters. The
ModuleBus in the AC 800M controller consists of:
• Electrical ModuleBus (base cluster) – not extensible and maximum of twelve
S800 I/O units
• Optical ModuleBus –maximum of seven TB820 cluster modems
• Max. 96 I/O modules
• 1-12* S800 I/O modules per cluster
max. 2.5 meters

Base cluster

Modulebus
extension

Termination
TB807
I/O cluster 1
TB820
Optical modem

I/O cluster 2 I/O cluster 3 I/O cluster 4

Duplex
Simplex max. 15 or 200m
max. 15 or 200m

The optical modem TB820 acts as an adapter from optical to electrical ModuleBus. A
maximum of 7 optical modems can be connected to the CPU.

Chapter 5 - 15
05 AC800M Hardware - RevC.doc

5.5.4 S800 I/O Connected with PROFIBUS


The CI854 unit is the main PROFIBUS DP-V1 communication interface and it can be
used to communicate with remote I/O or with actual PROFIBUS devices.
• Max. 24 I/O modules / I/O Station
• 1 base cluster
• 1-7 I/O cluster
• 1-12* S800 I/O modules per cluster
*The memory size and bus load in the CI830/CI801 or TB820 limits the number
of I/O modules per cluster
• Max. cluster length 2.5m (electrical ModuleBus)

CI801
Profibus slave

with CI854
TB810 Profibus
master

Base cluster

Max. 2.5 meters


TB820 I/O cluster 1
Optical modem

I/O cluster 2 I/O cluster 3 I/O cluster 4

Duplex
Simplex max 15 or 200m
max 15 or 200m

NOTE! CI840 is the redundant version of CI801.

Chapter 5 - 16
800xA Minerals Training

5.5.5 Limitations of CI801


The maximum number of I/O modules you can connect to a station is 24 modules.
Due to the PROFIBUS-DPV1 specification it is not possible to always connect 24 I/O
modules. The reason is that the S800 I/O system includes more data and user
parameters than PROFIBUS-DPV1 can handle. The table below shows the maximum
number of I/O modules that can be connected to one CI801.

NOTE! Refer to the manual: Fieldbus Communication Interface


PROFIBUS-DP/DPV1, 3BSE020926.

5.5.6 MTU – Module Terminal Unit for S800 I/O


The S800 I/O unit is attached to an MTU, Module Terminal Unit. A number of MTUs
are available. They can however be divided into two major groups, depending on the
physical layout:
• Compact / 1 connection per channel
• Extended / 3 connections per channel

Compact Extended

NOTE! Mechanical key protection prevents wrong I/O module


type from being inserted.

Chapter 5 - 17
05 AC800M Hardware - RevC.doc

5.6 Hardware Redundancy

5.6.1 Redundant Processor Unit - PM861/PM864/PM865


In a system with redundant Processors, the controller contains two processor units,
each including memory for system and application software. In a redundant system the
two processor units are linked together with the RCU Link Cable (max 1 m).
One unit is acting as primary, the other is backup (hot stand-by). The primary
processor unit controls the process. The backup stands by to take over in case of a
fault in the primary. The primary CPU is always updating the backup CPU.
You can select late in your project if you need redundancy option.

RCU Link

Both CPUs are connected to the CEX bus and either of the two can control the
communication interfaces. BC810 supports online replacement of the CPU baseplate
without disturbing the CEX traffic.
In a redundant configuration an automatic switch-over from the Primary CPU to the
Backup CPU occurs in the following situations, provided they are in synchronized
state (DUAL LED is lit):
• Memory or other hardware error in the Primary CPU.
• Severe communication errors on the Control network, that is, loss of both network
ports in the Primary CPU.
• Severe communication errors on the ModuleBus
NOTE! The changeover is done bumpless and in less than 10 ms.

Chapter 5 - 18
800xA Minerals Training

5.6.2 Controller and I/O Redundancy


Use of redundancy will reduce the maximum number of S800 channels. Each cluster
may contain up to 12 single S800 I/O units or up to 6 redundant S800 I/O units.

CEX -bus splitter


BC810

Redundancy Redundant S800


Redundant I/O as direct I/O
Link Cable
PROFIBUS CI
CI854A

Redundant or Singular
S800 I/O

Optical ModuleBus
Cable

Chapter 5 - 19
05 AC800M Hardware - RevC.doc

5.6.3 Redundant ModuleBus I/O Connections


When you use redundant I/O module configuration, the maximum number of I/O
modules in one cluster is 6 pairs.

Chapter 5 - 20
800xA Minerals Training

5.6.4 Redundant PROFIBUS I/O Connections


When you use redundant I/O module configuration, the maximum number of I/O
modules in one cluster is 6 pairs.
• TU846 is used for Redundant I/O modules
• TU847 is used for non redundant I/O modules
• CI840 is connected to CI854 PROFIBUS master

TU846 or TU847

Chapter 5 - 21
05 AC800M Hardware - RevC.doc

5.7 Hardware Configuration


Hardware units are added to the tree structure in the Project Explorer representing
physical hardware units. Some units contain sub units, such as serial channels, that are
automatically created.

As you can see on the example of a hardware configuration above, there are 4 I/O
modules connected to ModuleBus and 5 I/O modules connected to PROFIBUS.

5.7.1 Configuration Steps


To add a new hardware unit in the Project Explorer, proceed as follows:
1. Select the unit to which you want to add the new hardware unit.
2. With the unit selected, right-click on the unit and select “New unit”. A submenu
listing possible hardware is displayed. Select the type of hardware you wish to
add. If <New unit> is dimmed, the unit you have selected in step 1 may not
contain any sub units, or the maximum number of sub units has been reached.
3. Select a position for the hardware unit in the dialog box displayed. The first
available position is chosen by default. If another position is desired, click the list
box to display available positions. Click “OK”.
4. The hardware unit is now added to the tree, and the name of the hardware unit, as
well as its position, is displayed next to the icon of the hardware unit. The icons
look different depending on which type of unit was added.

Chapter 5 - 22
800xA Minerals Training

5.7.2 Adding a Controller CPU


In the Project Explorer, right click on Controllers and choose “New Controller”.

Then choose the new CPU type that you wish to insert.

ModuleBus Scan Time


Double-click on the “ModuleBus” icon to open the editor. The Scan Cycle Time is the
fastest general interval time used by the CPU to do an I/O copy of all I/O modules.

The parameter “Scan Cycle Time” for the cycle time of the ModuleBus can be set in
the range 0...100 ms. Default setting is 0 (as fast as possible) and can load the CPU
significantly. The minimum scan time in practice will be 6 ms.
NOTE! It is recommended to change the default settings in order
to reduce the CPU load.

Chapter 5 - 23
05 AC800M Hardware - RevC.doc

5.7.3 Adding a Communication Interface Module


Open the just inserted controller structure, right click on Hardware AC 800M and
choose “Insert Unit”.

Choose the communication interface module that you want and click “Insert”

Note that you are not able to insert any other communication unit by default. To do
this, we need first to connect the required hardware libraries.

5.7.4 Hardware Libraries


Hardware types are organized and installed as libraries in Control Builder. The library
containing the hardware type has to be connected to the controller, to make it possible
to add the hardware type (unit) to the controller.
First right click and select “Insert Library” to insert the library to the Control project.

Chapter 5 - 24
800xA Minerals Training

Then choose the relevant hardware library and click “Insert”.

The library needs then to be connected to the controller. Select Connected Libraries,
right click and choose “Connect Library”.

NOTE! An overview of the available hardware libraries is shown


in chapter “Libraries”.

Chapter 5 - 25
05 AC800M Hardware - RevC.doc

5.7.5 Adding S800 I/O on ModuleBus


Open the just inserted controller structure, right click on ModuleBus and choose
“Insert Unit”.

Then choose the appropriate S800 I/O and the position (slot).

Chapter 5 - 26
800xA Minerals Training

5.7.6 Adding S800 I/O on PROFIBUS


Open the just inserted controller structure, right click on the inserted communication
interface module such as a CI851, choose “Insert Unit”.

First insert the PROFIBUS slave (CI830 / CI801 / CI840).

NOTE! Position value must be consistent with the address


settings of the switches on CI830 board.
Then insert the desired I/O module type.

Chapter 5 - 27
05 AC800M Hardware - RevC.doc

5.7.7 Hierarchical Dot Notation


The hardware address of a hardware unit is composed from the hardware tree position
numbers of the unit and its parent units, described from left to right and separated by
dots. For example channel 1 on the I/O unit DI810 has the controller address:

Controller_1.0.11.3.1

Channel 1

Note that the position number for the CI851 is the physical location on the CEX-bus,
while the position for the CI830 is the PROFIBUS node number (set by switches).

Note that an optical modem TB820 is not visible in the Project Explorer. The I/O
cluster is only indicated by the position of the I/O modules e.g. I/O modules in cluster
number 3 have positions from 301 to 312.

Chapter 5 - 28
800xA Minerals Training

5.7.8 Settings of I/O Units


Scaling
For analog inputs and outputs, you can specify the physical minimum and maximum
values corresponding to the signal range 0-100 %. You can also assign a physical unit
to your variable. These settings are accessible in code from the RealIO data type.

Preset Values/OSP/ISP
You can specify what value to assign to an I/O channel in case the I/O unit loses
communication with the CPU or PROFIBUS slave. The choices are: Keep last value,
Reset output/input or Assign OSP/ISP value. The last is a preset value, specified in the
editor for the I/O unit. The degree of configuration you can make for a particular I/O
channel depends on the type of I/O unit.

Signal Range
This setting specifies the electrical signal range; 0-20 mA, 0-10 V etc.

Chapter 5 - 29
05 AC800M Hardware - RevC.doc

5.7.9 Adding Compact Flash


Expand the Controllers structure and right click the CF Reader item. Select “Insert
Unit” from the context menu and insert the CF Card item.

NOTE! You must connect an external Compact Flash writer to


your Engineering station where Control Builder is
loaded (normally connected to the USB port).

Make sure your project is in offline mode and insert a Compact Flash card in the
Writer slot. Right-click on the controller item and select “Compact Flash” from the
context-menu to pick the writer.

Click “OK” to write the application to the Compact Flash card.

For a redundant CPU configuration, you need to write the same application twice (two
CF cards, one in each CPU). Copy (in Windows Explorer) the downloaded application
(two folders) from the CF card and paste them temporarily on your local disk. Insert
the next memory card into the writer and drag your two folders from the hard disk and
drop them on the new CF memory card.
NOTE! Backup of cold retain values to Compact Flash is not
supported for redundant CPU’s.

Chapter 5 - 30
800xA Minerals Training

5.8 Communication to AC800M Controller


All controllers delivered from the factory have the same IP address. You must change
the IP address to an address, which is available in your own network.

5.8.1 How to Use the IPConfig Utility


Use the tool IPConfig to establish contact between the engineering station and the
controller and change the IP address.
You can start the IPConfig tool by:
Start | Programs | ABB Industrial IT 800xA | Engineering | Utilities | IPConfig

1. Connect your PC with the controller using a TK212 cable connected to serial port
on your PC and to the toolport (COM4) on the AC 800M controller.
2. Choose the COM port on your PC by click on “Settings”

Chapter 5 - 31
05 AC800M Hardware - RevC.doc

3. Press “Connect”

The IPConfig status bar will change from Not Connected to Connecting.

4. Make a long (more than 3 seconds) Init of the controller, release the init button
when the Run LED start to blink.

After the system-reset button has been pushed it takes approximately 10s before
IPConfig detects the system reset and the status bar changes to System reset
detected waiting for controller start-up.

If the connection fails, a message box will indicate Connect failed, Time-Out. The
reason may be the following:
- The serial cable is not connected correctly.
- Too long time elapsed between clicking the Connect button and the
system reset of the controller.

5. When IPConfig is connected the status bar will change to Connected.


6. To set the submask, you must enter advanced mode by choose “Settings” and
choose the “Advanced mode”.

Chapter 5 - 32
800xA Minerals Training

7. Modify IP address, press “Set IP” and the text boxes will show the current
controller IP address settings.

When the new IP address has been stored successfully the status bar will show
“Controller IP configuration updated”.
NOTE! Do not use IPConfig for a controller when an application
is running in it. IPConfig will delete every application in
the controller.

Ethernet addresses are kept in the flash memory. Always close IPConfig when you are
done with it, because IPConfig uses the tool port (Com4) and the rest of the CPUs
channels will be locked.

Chapter 5 - 33
05 AC800M Hardware - RevC.doc

5.8.2 How to Configure the IP Address


After setting the controller’s IP address with the IP-config tool, you must do the IP
address settings of the controller in CBM in two steps:
1. Right click the Controller, choose “Properties > System Identity” and then set the
desired IP address of the controller.

The System Identity is the network address of the selected controller. The network
address is shown beside the controller icon in the Project Explorer tree.
NOTE! The default address is 172.16.0.0

2. Open the controller’s PM8xx/TP830 and then double click the first Ethernet.

Chapter 5 - 34
800xA Minerals Training

This will open a new window, click on the “Settings” tab, then set the same IP address
and subnet mask as you have set with the IPConfig tool.

NOTE! The system identity should normally correspond to the


setting for Ethernet 1 on the AC800M.

5.8.3 How to Download the Firmware


The upgrade of the CPU firmware can be done either from the serial line connected to
the toolport (COM4) on your controller or over Ethernet. The Serial Firmware
Upgrade tool is intended to be used as a last resort, if the normal firmware upgrade
procedure, for some reason, fails.
The most comfortable way is to use the Control Builder, because you will be able to
compare the current firmware in the controller with the firmware on the hard disk.
1. Select “Remote System”.

Chapter 5 - 35
05 AC800M Hardware - RevC.doc

2. Press “Show Firmware Information”.

3. Compare the firmware on disk with the firmware in the controller

4. Select the firmware which has to be downloaded and press “Download


Firmware”.

Note that once the firmware has been upgraded to version 5.0, further controller
upgrades and system upgrades can be done online without shutting down the whole
system.

Chapter 5 - 36
800xA Minerals Training

5.9 Application Download

5.9.1 General
During a download, the code that has been written is checked and compiled. The
controller receives the compiled application and begins executing it immediately.
Once your application has been compiled, you can:
• Download the application and go Online.
This updates the application in the controller.
• Go online without download of the application.
Useful when, for example, monitoring values in the controller without disturbing
the controller.
A version analysis of the applications is made when you download. The analysis
results are used to determine if and how applications shall be updated to new versions
in the controllers.

5.9.2 Restart Options


When the system restarts, variables with No Retain, Retain and Cold Retain attributes
will behave differently. It will also matter if the system performs a warm or a cold
restart.

WARM RESTART
At a warm restart, variables with the attribute <retain> or <coldretain> are protected
by the battery during restart. During the time that the controller is stopped, all output
I/Os will keep their last value.
COLD RESTART
At a cold restart, variables with the attribute <coldretain> keep their values, since they
are stored on the hard disk. Variables without the attribute <coldretain> lose their
values. During the stop time, all output I/Os will keep their last safe state/OSP values.
INIT RESTART
At a Init restart, variables with the attribute <coldretain> or <retain> are returned to
the initial value

Chapter 5 - 37
05 AC800M Hardware - RevC.doc

5.9.3 Download
Select “Tools > Download Project and go Online” in the CBM.

If changes have been made to one or several applications in Offline mode, the version
analysis detects it. You can then decide how to restart the changed applications.

Independent of how you restart the applications, the changed application parts are
downloaded to the controllers. The controller will stop the applications and restart
with the new and changed application.
NOTE! Following download the last message should be:
You are now Online!

Chapter 5 - 38
800xA Minerals Training

5.9.4 Difference Report


Just before the download to controllers, the system will open a ‘Difference Report’
window, which shows the differences between the applications on disk & applications
in the controllers. At this time you may decide to continue or to cancel the download.
The purpose of the difference report is validation of configuration changes.

You may disable the difference report function in project context menu “Settings >
Difference Report”.

Chapter 5 - 39
05 AC800M Hardware - RevC.doc

5.9.5 Re-Authentication
If the Re-authenticate function is enabled, the user will be asked to enter user name
and password, before download is completed.

You may disable this function by setting the corresponding system variable to “False”.

Chapter 5 - 40
800xA Minerals Training

5.10 Online Functions

5.10.1 General
In Online mode the Control Builder is connected to one or more controllers and offers
many diagnostic and inspection features when online to the controller. You can:
• View the executing code dynamically
• Force inputs and outputs at the I/O modules
• Rescale analogue input and output channels
• Change values of variables
• Inspect values of variables

To enter Online mode, go to the tool bar menu of the Control Builder, click on
“Tools” and then click on “Online”.

5.10.2 Status of I/O-Signals


Use the status tab of the hardware configuration editor, in online mode, for dynamic
online display of I/O channel values and forcing. I/O channel values are updated once
every second.
NOTE! The tab is available in Offline mode, but is not editable.

Underflow, overflow, channel and unit errors in online mode are indicated in the
Channel value cell by the following icons:
Signal Errors
underflow The signal is below the range.
overflow The signal is above the range.

Hardware Errors
channel error The channel can have under range, power-up or field power errors.
Unit error The unit can be missing or of the wrong type.

Chapter 5 - 41
05 AC800M Hardware - RevC.doc

5.10.3 Forcing
Forcing of I/O is possible in online mode. Check a check box in the Forced column
and then type in a value in the Channel value column for outputs and in the Variable
value column for inputs. This value overrides the values in each of those columns.
When a channel is forced all copying between the I/O value and the application value
is stopped. The forced value is different for inputs and outputs.
• For inputs the forcing changes the variable value to the application.
• For outputs the forcing changes the physical I/O channel value.

NOTE! The background of the forced cell changes to yellow to


indicate forcing.

Forcing is performed in the hardware configuration editor under the “Status” tab or the
POU editor.
Normally only channels with variable connections to application programs can be
forced. However, if no variable is connected you have to change the parameter Copy
Unconnected Channels under the “Settings” tab for the current controller to get a
status update.

Chapter 5 - 42
800xA Minerals Training

5.11 Test Mode & SoftController

5.11.1 Test Mode


Without downloading to a real controller or a SoftController, you may test your
application by using the test mode. In CBM, select “Tools > Test mode”.

5.11.2 How to use the SoftController


You may also test your application and even your hardware by downloading to a
SoftController running on your PC. It is also possible to use the SoftController for
communication purposes, for example, COMLI or MODBUS.
1. Set the controller’s system identity you want to test to your PC’s IP address:2
(such as 172.16.0.1:2).
NOTE! It is also possible to use the loop back adapter address as
127.0.0.1:2.

2. Right click the controller, select “Properties > Simulate Hardware”

Chapter 5 - 43
05 AC800M Hardware - RevC.doc

3. Start the SoftController by double-click the icon on the desktop or choose the path
below:

4. Click “Start”.

5. Choose “Download project and Go online”.