Fire Protection system, CYE10 FCU Fire Control Unit Ensure the protection & safety of the machine as well as the operator Manual & automatic fire detection & Alarm system Manual & automatic fire Extinguishing system
Interface - Overview
Detectors/ Sensors
Inputs
to the FCU Convert Physical signal to Electric signal Heat Detector CLTD Smoke Detector Flame Detector Switches Pressure, Limit, Lock-out, etc
& Output modules LCD Front Panel LED status display Power Supply & Backup battery CPU Central Card for processing Relays
Central Card
Supervision & Alarm Activate the Extinguishing system Initiate Trip to the GT Control System Initiate PLST to the GT Control System Exhaust End Bearing Switch OFF Ventilation System in case of Fire: Combined Pump Block GT Thermal Block Switch ON Ventilation System in case of >20% LEL Combustible Gas detected: GT Thermal Block
Logic Diagram
Modules - I/O Card Physical connections to Detector/Sensors Segregate the signals based on Areas and Groups MxM Bus communication Conventional Detector Module Control Group Relay Module
Wiring Diagram
Extinguishing System
CO2
Area: GT Auxiliary Block Supervision: Wire break Supervision Pressure Supervision Activation: Manual Release Button Heat Detector Smoke Detector Flame Detector
Area: GT Thermal Block Exhaust End Bearing Supervision: Wire break Supervision Pressure Supervision Weight Loss Supervision Limit Switches Lock-out switches Activation: Manual Release Button Heat Detector CLTD Smoke Detector Flame Detector
Area: Combined Pump Block Supervision: Wire break Supervision Weight Loss Supervision Activation: Manual Release Button Heat Detector