THIS SUBMISSION IS DECLARED TO BE STRICTLY IN ACCORDANCE WITH THE REQUIREMENTS OF THE CONTRACT SIGNATURE

QATAR POWER TRANSMISSION SYSTEM EXPANSION PHASE VII (Substations) CONTRACT NO. GTC/123/2006

SIEMENS CONSORTIUM-GTC/123/2006
SIEMENS AG GERMANY
SUBSTATION NAME / CIRCUIT NAME

SIEMENS LIMITED INDIA PROJECT DRAWING NUMBER

Mosemeer, Abu Hamour central, Al Soudan, Ain Khalid South, Al Wadi, MIC-2, MIC-3,QRE,EDS,Khore Community, Al Dhahiya West, Al Jumailyah, Khore Junction, NDQ, Muraikh North, South West Wakrah-1, NBK-2, Abu Thaila Modification, RLF-3, Al Dhahiya, Al Waab Super, MIC Super, Wakrah-2, Lusail Development Super1,Ain Hamad, Ain Khalid south.

PH7-3B-10-15-C001

SUBCONTRACTOR / SUPPLIER

DRAWING/DOCUMENT DESCRIPTION

0 REV

29-11-2007 DATE

FIRST ISSUE MODIFICATION

R.K. DRAWN SCALE N.A.

V.H CHECK

V.A. APPRD SIZE A4

DESIGN REPORT FOR CURRENT TRANSFORMER (CT) & VOLTAGE TRANSFORMER (VT) SIZING FOR 11kV SYSTEM Document No.:VER

TOTAL NO. OF PAGES 91 PAGES


3

SIEMENS

GTC123-BN00-AQA-10001

SIEMENS

PROJECT:GTC/123/2006

Index

S.No.
1 2 3 4 5 6 7 PURPOSE DESIGN INPUT ASSUMPTIONS DESIGN CRITERIA CALCULATIONS RESULT OF STUDY ATTACHMENTS ANNEXURE 1 ANNEXURE 2 ANNEXURE 3 ANNEXURE 4 ANNEXURE 5

DESCRIPTION

PAGE NUMBER
1 1 1 2 2 3 3 6-80 81-82 83 84-90 91

PH7-3B-10-15-C001, Rev 0

Page 2 of 91

SIEMENS
1.0 PURPOSE:

PROJECT:GTC/123/2006

This document is intended to establish the minimum sizes of Current transformer in terms of Knee point voltage & Rated burden Voltage transformer in terms of Rated burden for various feeders of 11KV for the following mentioned substations: Mosemeer Abu Hamour Central Al Soudan Al Wadi Al Jumailyah Khore Junction MIC -2 MIC -3 QRE EDS Khore Community Al Dhahiya West Muraikah North South West Wakrah 1 NDQ NBK -2 RLF-3 MIC Super Al Dhahiya Al Waab Super Lusail Development Super 1 Wakrah 2 Abu Thaila substation modification Ain Hamad Ain Khalid south

2.0

DESIGN INPUT :
1. Project contract document 2. Relay catalogue for relay burden

PH7-3B-10-15-C001, Rev 0

Page 3 of 91

SIEMENS

PROJECT:GTC/123/2006

3.0

ASSUMPTIONS :
1. Power Transformer 32/40MVA, 66/11kV, %age impedance at principal tapping is assumed as 16.33%. 2. Power Transformer 20/25MVA, 66/11kV, %age impedance at principal tapping is assumed as 12.58%.. 3. Power Transformer 7.5/10MVA, 33/11kV, %age impedance at principal tapping is assumed as 12%. 4. Power Transformer 25/30MVA, 33/11kV, %age impedance at principal tapping is assumed as 12.58%. 5. 500kVA, 11/0.415kV Earthing Transformer, %age impedance at principal tapping is assumed as 9.60% 6. 1000kVA, 11/0.415kV Earthing Transformer, %age impedance at principal tapping is assumed as 6.00 % 7. 2000kVA, 11/0.415kV Earthing Transformer, %age impedance at principal tapping is assumed as 12.0%

4.0

DESIGN CRITERIA:
KNEE POINT VOLTAGE Apart from rated short time rating of the system, to arrive at minimum knee point voltage, value for steady state through fault current values needs to be determined. Considering the rated capacity of the bus bars of 11kV, the fault level considered is 31.5kA. PARAMETERS FOR CABLE BETWEEN CT & RELAY PANEL Cross section taken is 4 mm2. Calculation for resistance at 75 deg. C: Resistance at 20 deg. C = 4.61 ohms / Km Value of Alpha (Temp. coefficient) at 20 deg. C for copper = 0,00393 / deg. C Resistance at 75 deg. C = 4.61 (1 + 0.00393 (75-20)) = 5.61 ohms / kM Calculation of Loop resistance of the cable between CT & Relay panel: Taking length of cable between CT & Relay panel as 50 meter Loop resistance = 2 x Length of cable (in kM) X resistance at 75 deg. C (in ohms/kM) = (2 x 70 x 5.61) / 1000 = 0.785 ohms Considering 20% safety margin as per contract requirement, (clause 12), = 0.785 * 1.2 = 0.942 ohms All CT sizing calculations, have been done for a cable length of 50mts. This is the maximum length possible.

PH7-3B-10-15-C001, Rev 0

Page 4 of 91

SIEMENS
RATED BURDEN

PROJECT:GTC/123/2006

Rated burden selected for a CT/VT shall be more than the sum of relay/metering burden connected across CT/VT.

5.0

CALCULATIONS:
Calculations performed for the CT/VT parameters are enclosed in following annexure: Annexure # 1: CT Knee point voltage calculations for the 11kV feeders Annexure # 2: CT burden (in VA) calculations for the 11kV feeders Annexure # 3: VT burden (in VA) calculations for 11kV the feeders

6.0

RESULT OF STUDY:
Calculation results show that selected parameters for CT/VT are adequate to meet the minimum requirements.

7.0

ATTACHMENTS:
1. Annexure # 1: CT Knee point voltage calculations for 11kV feeders 2. Annexure # 2: CT burden (in VA) calculations for 11kV feeders 3. Annexure # 3: VT burden (in VA) calculations for 11kV feeders 4. Annexure # 4: Relay back-up sheets 5. Annexure #5: LSOH Power Cable Data Sheet

PH7-3B-10-15-C001, Rev 0

Page 5 of 91

SIEMENS
Incomer Feeder (Typical bay no: A18,A28) Type:1 Configuration 40MVA, 66/11kV transformer,Earthing/auxiliary transformer rating of 500kVA

PROJECT:GTC/123/2006

ANNEXURE 1

Applicable substations:Mosemeer,Abu Hamour central,Al Wadi,MIC-2,MIC-3,QRE,Khore Community,Al Dhahiya West, NBK-2, Al Soudan, Ain Khalid south

66kV side
66/11KV 32/40MVA ONAN/ONAF Core-1 50/1 Class-PX Vk100 Rct1.2 Io<30ma at Vk Core-2 50/1 Class-5P20 15VA

11/0.415KV 500KVA

Core-1 750/1 Class-PX Vk250 Rct6 Io<25ma 15VA

Core-4 2500/1 Class-PX Vk250 Rct9 Io<30ma

To Back-up earth fault (7SJ61)

Core-1 750/1 Class-5P20 15VA Core-2 50/1 Class-PX Vk100 Rct1.2 Io<30ma Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma

Cable and trafo differential protection (7SD52)

To REF protection for Earthing transformer (7SJ61)

Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma Core-2 2500/1 Class-5P20/1.0 Rct8 10VA

To partial busbar differential protection (7SJ61)

To REF protection for 11kV side (7SJ61)

To Directional Overcurrent & earth fault / Metering (6MD6 & 7SJ62)

Core-1 2500/1 Class-PX Vk250 Rct9 Io<30ma

To Transformer REF (11kV side) & Main differential protection (7SJ61 & 7UT613)

11kV Bus

Feeder =A18, =A28

Note: - 40 MVA LV side Core-4 is not applicable for NDQ, Muraikh North, South West Wakrah-1, NBK-2

CT knee point voltage calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on Cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = = = = 2500 /1 1 amp. 70 meter 5.610 Ohms/Km 5.61x1.2 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = (Relay will be mounted in Relay panel)

0.942 9.00

PH7-3B-10-15-C001, Rev 0

Page 6 of 91

SIEMENS
Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = The required K'SSC IN Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point voltage is = = (0.942+0.1) 0.100 VA 1.042 VA

PROJECT:GTC/123/2006

ANNEXURE 1

20

atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn

Knee Point voltage required

20 x (9+1.042) x 1 1.3 154.49 volts 185.39

= 20% margin on Vk value =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 40 MVA transformer would be: %age impedance at 40 MVA = 0.1633 Taking a negative tolerance of 15% = 0.1388 If = 40 1.732 x 11 x 0.1388 15.1262 kA 1.5x15126.2x(9+0.942 )x2 2500 > 180.46 volts

If Vk

= >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 7 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Formula Used a) Transient dimensioning factor (k td): 3 For transformer, k td = b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC I SCC x ktd = I PN Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11 kV ,the maximum through fault current on 40 MVA transformer would be: %age impedance at 40 MVA = 0.1633 Taking negative tolerance of 15% = 0.1388 ISSC = 40 1.732 x 11 x 0.1388 15.1262 kA 15126.2 x 3 2500 18.15

ISSC K'SSC K'SSC to be considered for calculations

= = =

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) =

(0.942+0.1)

0.100 VA 1.042 VA

c) Knee point voltage : The calculated value of knee point voltage is Knee Point voltage required

(RBC+ Ri ) X ISN X K'SSC 1.3 (1.042 + 9) x 1 x 18.15 1.3 140.20 168.24 volts volts

Knee Point voltage required 20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 8 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequacy checking calculations for 7SJ62 and 6MD6 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-2 ) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = = (0.942+0.1) = (10+8) x20 (1.042+8) 39.81 > 20 = = = 8.0 VA 10 VA 0.100 VA 1.042 VA = = 20 atleast RBN+ Ri x KSSC RBC + Ri

Calculated Value for K' SSC

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 9 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for Partial Bus bar protection Feeders =A18,=A28 (connected across core-3 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = = = 2500 1 amp. 70 5.610 6.732 0.942 meter Ohms/Km Ohms/Km Ohms (Relay will be mounted in Relay panel)

(I) x 0.942 = 9.00 Ohms =

0.942 9.000

CT Internal Burden in VA = (I) x 9 Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = 20 The required K'SSC IN RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 = = RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point voltage is Knee Point voltage required =

atleast

(0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (1.042+9) x 1 1.3 154.49 185.39 volts volts

0.100 VA 1.042 VA

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 10 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SD5 relay for 11kV incoming feeders =A18, =A28(connected across Core-4) Current Transformer Ration (CTR) = 2500 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA Formula Used a) Transformer dimensioning factor (k td): For line differential protection ktd = = = = = = = 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = (Relay will be mounted in Relay panel)

0.942 9.000

1.20

b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11kV, the maximum through fault current on 40 MVA trafo would be : %age impedance at 40 MVA = 0.1633 Taking negative tolerance of 15% = 0.1388 = 40 ISSC 1.732 x 11 x 0.1388 ISSC = 15.1262 kA = I SCC x ktd I PN

K'SSC

15126.2x1.2 2500

K'SSC to be considered for calculations

7.26

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = = RBC = (Loop Burden+ Relay Burden) c) Knee point voltage : The calculated value of knee point voltage is =

(0.942+0.1)

0.100 VA 1.042 VA

(RBC+ Ri ) X ISN X K'SSC 1.3

Knee Point voltage required

(1.042+9) x1x7.26 1.3 56.08 67.30 volts

Knee Point voltage required 20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 11 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across 11kV Neutral side CTs of 500KVA) Current Transformer Ration (CTR) = 2500 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance = = = = = = = = 70 meter 5.610 Ohms/Km 5.61x1.2 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = 0.942 9.00 (Relay will be mounted in Relay panel) (As per contract document)

Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = = (0.942+0.1) 0.100 VA 1.042 VA = I High set point = IN 20 atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (9+1.042) x 1 1.3 154.49 185.39 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 40 MVA transformer would be: %age impedance at 40 MVA = 0.1633 Taking a negative tolerance of 15% = 0.1388 If = 40 1.732 x 11 x 0.1388 15.1262 kA

If

Vk

>

1.5x15126.2x(9+0.942 )x2 2500

>

180.46

volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 12 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for Phase and Neutral side CTs) Current Transformer Ration (CTR) = 50 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = 70 meter 5.610 Ohms/Km 6.732 0.942 Ohms (I) x 0.942 = 1.20 Ohms (I) x 1.2 = (Relay will be mounted in Relay panel)

0.942 1.2

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = (0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 1.2 x (1.2+1.042) x 1 1.3 34.49 41.39 volts 0.100 VA 1.042 VA = I High set point = IN 20 atleast

= =

20% margin on vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition Vk > 1.5(I f x (Rct + 2RL ) x 2) Where I f is magnitude of through fault current

Considering infinite source,the maximum through fault current on 500 KVA transformer would be: %age impedance at 500 KVA Overall Impedance ( taking 15% negative tolerance) If = 500 1.732 x 11 x 0.0816 321.6172 A = = 0.0960 0.0816

If =

As the through fault current could be ground fault current which can be max 750A, the stablility is being checked for this max value. Vk > 1.5 x 750 x (1.2 + 0.942 ) x 2 50 > 96.39 volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 13 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for 500 KVA HV Neutral side CTs) Current Transformer Ration (CTR) Relay Normal Current (IN) = = 750 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC =

20 atleast

RBN+ Ri x KSSC RBC + Ri

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+6) x20 6+0.992 60.06

= = = =

6.0 VA 15 VA 0.050 VA 0.992 VA

Calculated Value for K' SSC

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 14 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequecy check for 7SJ61 type used for O/C protection of 11kV side of Earthing transformer Current Transformer Ration (CTR) Relay Normal Current (IN) = = 50 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+1.2) x20 1.2+0.992 147.80 =

20 atleast

RBN+ Ri x KSSC RBC + Ri

= = = =

1.2 VA 15 VA 0.050 VA 0.992 VA

Calculated Value for K' SSC

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 15 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for REF protection of 433 V side of Earthing transformer (Applicable for Neutral side CTs) Current Transformer Ration (CTR) = 750 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 6.00 Ohms = (Relay will be mounted in Relay panel)

0.942 6.000

CT Internal Burden in VA = (I) x 6 Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = 20 The required K'SSC IN Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) = = (0.942+0.1)

atleast

0.100 VA 1.042 VA

b) Knee point voltage : The calculated value of knee point Knee Point voltage required

= =

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (6+1.042) x 1 1.3 108.34 130.01 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source, the maximum through fault current on 500 KVA transformer would be: %age impedance at 500 KVA Overall Impedance ( taking 15% negative tolerance) If = 500 1.732 x 0.415 x 0.0816 8.5248 kA 1.5x8524.8x(6+0.942 )x2 750 > 236.72 volts = = 0.0960 0.0816

If = Vk >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 16 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Incomer Feeder (Typical bay no: A18,A28) Type:2 Configuration 25MVA, 66/11kV transformer,Earthing/auxiliary transformer rating of 500kVA Applicable substations:Al Jumailyah, Khore Junction

66kV side
66/11KV 20/25MVA ONAN/ONAF Core-1 50/1 Class-PX Vk100 Rct1.2 Io<30ma at Vk Core-2 50/1 Class-5P20 15VA

11/0.415KV 500KVA

Core-1 750/1 Class-PX Vk250 Rct6 Io<25ma 15VA

Core-4 2500/1 Class-PX Vk250 Rct9 Io<30ma

To Back-up earth fault (7SJ61)

Core-1 750/1 Class-5P20 15VA Core-2 50/1 Class-PX Vk100 Rct1.2 Io<30ma Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma

Cable and trafo differential protection (7SD52)

To REF protection for Earthing transformer (7SJ61)

Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma Core-2 2500/1 Class-5P20/1.0 Rct8 10VA

To partial busbar differential protection (7SJ61)

To REF protection for 11kV side (7SJ61)

To Directional Overcurrent & earth fault / Metering (6MD6 & 7SJ62)

Core-1 2500/1 Class-PX Vk250 Rct9 Io<30ma

To Transformer REF (11kV side) & Main differential protection (7SJ61 & 7UT613)

11kV Bus

Feeder =A18, =A28

CT knee point voltage calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on Cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = = = = 2500 /1 1 amp. 70 meter 5.610 Ohms/Km 5.61x1.2 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = (Relay will be mounted in Relay panel)

0.942 9.00

PH7-3B-10-15-C001, Rev 0

Page 17 of 91

SIEMENS
Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = The required K'SSC IN Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point voltage is = = (0.942+0.1) 0.100 VA 1.042 VA

PROJECT:GTC/123/2006

ANNEXURE 1

20

atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn

Knee Point voltage required

20 x (9+1.042) x 1 1.3 154.49 volts 185.39

= 20% margin on Vk value =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 25 MVA transformer would be: %age impedance at 25 MVA = 0.1258 Taking a negative tolerance of 15% = 0.1069 If = 25 1.732 x 11 x 0.1069 12.2750 kA 1.5x12275x(9+0.942 )x2 2500 > 146.45 volts

If Vk

= >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 18 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Formula Used a) Transient dimensioning factor (k td): 3 For transformer, k td = b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC I SCC x ktd = I PN Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11 kV ,the maximum through fault current on 25 MVA transformer would be: %age impedance at 25 MVA = 0.1258 Taking negative tolerance of 15% = 0.1069 ISSC = 25 1.732 x 11 x 0.1069 12.2750 kA 12275 x 3 2500 14.73

ISSC K'SSC K'SSC to be considered for calculations

= = =

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) =

(0.942+0.1)

0.100 VA 1.042 VA

c) Knee point voltage : The calculated value of knee point voltage is Knee Point voltage required

(RBC+ Ri ) X ISN X K'SSC 1.3 (1.042 + 9) x 1 x 14.73 1.3 113.78 136.54 volts volts

Knee Point voltage required 20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 19 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequacy checking calculations for 7SJ62 and 6MD6 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-2 ) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = = (0.942+0.1) = (10+8) x20 (1.042+8) 39.81 > 20 = = = 8.0 VA 10 VA 0.100 VA 1.042 VA = = 20 atleast RBN+ Ri x KSSC RBC + Ri

Calculated Value for K' SSC

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 20 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for Partial Bus bar protection Feeders =A18,=A28 (connected across core-3 ) Current Transformer Ration (CTR) = 2500 Relay Normal Current (IN) = 1 amp. Length of cable between CT and Relay = 70 meter Cable Resistance for mmat 75C = 5.610 Ohms/Km 20% margin on cable resistance = 6.732 Ohms/Km = 0.942 Ohms Loop Resistance ( 2R L ) Loop Burden in VA = (I) x 0.942 = = 9.00 Ohms Current Transformer resistance (R ct) CT Internal Burden in VA = (I) x 9 = Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = 20 The required K'SSC IN RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 = = RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required

(Relay will be mounted in Relay panel)

0.942 9.000

atleast

(0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (1.042+9) x 1 1.3 154.49 185.39 volts volts

0.100 VA 1.042 VA

= =

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 21 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SD5 relay for 11kV incoming feeders =A18, =A28(connected across Core-4) Current Transformer Ration (CTR) = 2500 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA Formula Used a) Transformer dimensioning factor (k td): For line differential protection ktd = = = = = = = 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = (Relay will be mounted in Relay panel)

0.942 9.000

1.20

b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11kV, the maximum through fault current on 25 MVA trafo would be : %age impedance at 25 MVA = 0.1258 Taking negative tolerance of 15% = 0.1069 = 25 ISSC 1.732 x 11 x 0.1069 ISSC = 12.2750 kA = I SCC x ktd I PN

K'SSC

12275x1.2 2500

K'SSC to be considered for calculations

5.89

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = = RBC = (Loop Burden+ Relay Burden) c) Knee point voltage : The calculated value of knee point voltage is =

(0.942+0.1)

0.100 VA 1.042 VA

(RBC+ Ri ) X ISN X K'SSC 1.3

Knee Point voltage required

(1.042+9) x1x5.89 1.3 45.50 54.60 volts

Knee Point voltage required 20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 22 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across 11kV Neutral side CTs of 500KVA) Current Transformer Ration (CTR) = 2500 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance = = = = = = = = 70 meter 5.610 Ohms/Km 5.61x1.2 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = 0.942 9.00 (Relay will be mounted in Relay panel) (As per contract document)

Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = = (0.942+0.1) 0.100 VA 1.042 VA = I High set point = IN 20 atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (9+1.042) x 1 1.3 154.49 185.39 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 25 MVA transformer would be: %age impedance at 25 MVA = 0.1258 Taking a negative tolerance of 15% = 0.1069 If = 25 1.732 x 11 x 0.1069 12.2750 kA

If

Vk

>

1.5x12275x(9+0.942 )x2 2500

>

146.45

volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 23 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for Phase and Neutral side CTs) Current Transformer Ration (CTR) = 50 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = 70 meter 5.610 Ohms/Km 6.732 0.942 Ohms (I) x 0.942 = 1.20 Ohms (I) x 1.2 = (Relay will be mounted in Relay panel)

0.942 1.2

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = (0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 1.2 x (1.2+1.042) x 1 1.3 34.49 41.39 volts 0.100 VA 1.042 VA = I High set point = IN 20 atleast

= =

20% margin on vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition Vk > If x (Rct + 2RL ) x 2 Where I f is magnitude of through fault current

Considering infinite source,the maximum through fault current on 500 KVA transformer would be: %age impedance at 500 KVA Overall Impedance ( taking 15% negative tolerance) If = 500 1.732 x 11 x 0.0816 321.6172 A = = 0.0960 0.0816

If =

As the through fault current could be ground fault current which can be max 750A, the stablility is being checked for this max value. Vk > 750 x (1.2 + 0.942 ) x 2 50 > 64.26 volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 24 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequecy check for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for 500 KVA HV Neutral side CTs) Current Transformer Ration (CTR) Relay Normal Current (IN) = = 750 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+6) x20 6+0.992 60.06 =

20 atleast

RBN+ Ri x KSSC RBC + Ri

= = = =

6.0 VA 15 VA 0.050 VA 0.992 VA

Calculated Value for K' SSC

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 25 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequecy check for 7SJ61 type used for O/C protection of 11kV side of Earthing transformer Current Transformer Ration (CTR) Relay Normal Current (IN) = = 50 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+1.2) x20 1.2+0.992 147.80 =

20 atleast

RBN+ Ri x KSSC RBC + Ri

= = = =

1.2 VA 15 VA 0.050 VA 0.992 VA

Calculated Value for K' SSC

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 26 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for REF protection of 433 V side of Earthing transformer (Applicable for Neutral side CTs) Current Transformer Ration (CTR) = 750 /1 Relay Normal Current (IN) = 1 amp. Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 6.00 Ohms = (Relay will be mounted in Relay panel)

0.942 6.000

CT Internal Burden in VA = (I) x 6 Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = I High set point = 20 IN Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) = = (0.942+0.1)

atleast

0.100 VA 1.042 VA

b) Knee point voltage : The calculated value of knee point Knee Point voltage required

= =

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (6+1.042) x 1 1.3 108.34 130.01 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source, the maximum through fault current on 500 KVA transformer would be: %age impedance at 500 KVA Overall Impedance ( taking 15% negative tolerance) If = 500 1.732 x 0.415 x 0.0816 8.5248 kA 1.5x8524.8x(6+0.942 )x2 750 > 236.72 volts = = 0.0960 0.0816

If = Vk >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 27 of 91

SIEMENS
Incomer Feeder (Typical bay no: A18,A28) Type:3 Configuration 40MVA, 66/11kV transformer,Earthing/auxiliary transformer rating of 1000kVA Applicable substations : NDQ, Murraikh North, South west wakrah,Lusail Development Super 1

PROJECT:GTC/123/2006

ANNEXURE 1

66kV side
66/11KV 32/40MVA ONAN/ONAF Core-2 100/1 Class-5P20 15VA Core-1 100/1 Class-PX Vk100 Rct0.4 Io<30ma at Vk/2

11/0.415KV 1000KVA

Core-1 1500/1 Class-PX Vk500 Rct7.5 Io<25ma

Core-3 400/1 Class-PX Vk250 Rct9 Io<30ma at Vk

To Back-up earth fault (7SJ61)

Core-1 750/1 Class-5P20 15VA Core-2 100/1 Class-PX Vk100 Rct0.4 Io<30ma at Vk/2

To REF protection for Earthing transformer (7SJ61)

Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma Core-2 2500/1 Class-5P20/1.0 Rct8 10VA
To partial busbar differential protection (7SJ61)
To REF protection for 11kV side (7SJ61)

To Directional Overcurrent & earth fault / Metering (6MD6 & 7SJ62)

Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma

Core-1 2500/1 Class-PX Vk250 Rct9 Io<30ma

To Transformer REF (11kV side) & Main differential protection (7SJ61 & 7UT613)

11kV Bus

Feeder =A18, =A28

CT knee point voltage calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on Cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = = = = 2500 /1 1 amp. 70 meter 5.610 Ohms/Km 5.61x1.2 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = (Relay will be mounted in Relay panel)

0.942 9.00

PH7-3B-10-15-C001, Rev 0

Page 28 of 91

SIEMENS
Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = The required K'SSC IN Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point voltage is = = (0.942+0.1) 0.100 VA 1.042 VA

PROJECT:GTC/123/2006

ANNEXURE 1

20

atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn

Knee Point voltage required

20 x (9+1.042) x 1 1.3 154.49 volts 185.39

= 20% margin on Vk value =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 40 MVA transformer would be: %age impedance at 40 MVA = 0.1633 Taking a negative tolerance of 15% = 0.1388 If = 40 1.732 x 11 x 0.1388 15.1262 kA 1.5x15126.2x(9+0.942 )x2 2500 > 180.46 volts

If Vk

= >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 29 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Formula Used a) Transient dimensioning factor (k td): 3 For transformer, k td = b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC I SCC x ktd = I PN Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11 kV ,the maximum through fault current on 40 MVA transformer would be: %age impedance at 40 MVA = 0.1633 Taking negative tolerance of 15% = 0.1388 ISSC = 40 1.732 x 11 x 0.1388 15.1262 kA 15126.2 x 3 2500 18.15

ISSC K'SSC K'SSC to be considered for calculations

= = =

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) =

(0.942+0.1)

0.100 VA 1.042 VA

c) Knee point voltage : The calculated value of knee point voltage is Knee Point voltage required

(RBC+ Ri ) X ISN X K'SSC 1.3 (1.042 + 9) x 1 x 18.15 1.3 140.20 168.24 volts volts

Knee Point voltage required 20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 30 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequacy checking calculations for 7SJ62 and 6MD6 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-2 ) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = = (0.942+0.1) = (10+8) x20 (1.042+8) 39.81 > 20 = = = 8.0 VA 10 VA 0.100 VA 1.042 VA = = 20 atleast RBN+ Ri x KSSC RBC + Ri

Calculated Value for K' SSC

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 31 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for Partial Bus bar protection Feeders =A18,=A28 (connected across core-3 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay #REF! 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = = = 2500 1 amp. 70 5.610 6.732 0.942 meter Ohms/Km Ohms/Km Ohms (Relay will be mounted in Relay panel)

(I) x 0.942 = 9.00 Ohms =

0.942 9.000

CT Internal Burden in VA = (I) x 9 Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = 20 The required K'SSC IN RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point voltage is Knee Point voltage required =

atleast

= = (0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (1.042+9) x 1 1.3 154.49 185.39 volts volts

0.100 VA 1.042 VA

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 32 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across 11kV Neutral side CTs of 1000KVA) Current Transformer Ration (CTR) = 2500 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance = = = = = = = = 70 meter 5.610 Ohms/Km 5.61x1.2 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = 0.942 9.00 (Relay will be mounted in Relay panel) (As per contract document)

Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = = (0.942+0.1) 0.100 VA 1.042 VA = I High set point = IN 20 atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (9+1.042) x 1 1.3 154.49 185.39 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 40 MVA transformer would be: %age impedance at 40 MVA = 0.1633 Taking a negative tolerance of 15% = 0.1388 If = 40 1.732 x 11 x 0.1388 15.1262 kA

If

Vk

>

1.5x15126.2x(9+0.942 )x2 2500

>

180.46

volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 33 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for Phase and Neutral side CTs) Current Transformer Ration (CTR) = 100 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = 70 meter 5.610 Ohms/Km 6.732 0.942 Ohms (I) x 0.942 = 0.40 Ohms (I) x 0.4 = (Relay will be mounted in Relay panel)

0.942 0.4

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = (0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (0.4+1.042) x 1 1.3 22.18 26.62 volts 0.100 VA 1.042 VA = I High set point = IN 20 atleast

= =

20% margin on vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition Vk > 1.5(I f x (Rct + 2RL ) x 2) Where I f is magnitude of through fault current

Considering infinite source,the maximum through fault current on 1000 KVA transformer would be: %age impedance at 1000 KVA Overall Impedance ( taking 15% negative tolerance) If = 1000 1.732 x 11 x 0.051 1029.1751 A = = 0.0600 0.0510

If =

As the through fault current could be ground fault current which can be max 750A, the stablility is being checked for this max value. Vk > 1.5 x 750 x (0.4 + 0.942 ) x 2 100 > 30.20 volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 34 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequacy check for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for 1000 KVA HV Neutral side CTs) Current Transformer Ration (CTR) Relay Normal Current (IN) = = 750 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC =

20 atleast

RBN+ Ri x KSSC RBC + Ri

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+6) x20 6+0.992 60.06

= = = =

6.0 VA 15 VA 0.050 VA 0.992 VA

Calculated Value for K' SSC

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 35 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequecy check for 7SJ61 type used for O/C protection of 11kV side of Earthing transformer Current Transformer Ration (CTR) Relay Normal Current (IN) = = 100 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+1.2) x20 1.2+0.992 147.80 =

20 atleast

RBN+ Ri x KSSC RBC + Ri

= = = =

1.2 VA 15 VA 0.050 VA 0.992 VA

Calculated Value for K' SSC

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 36 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders to 1000 KVA EAT-(connected across core-3 ) Formula Used a) Transient dimensioning factor (k td): = 3 For transformer, k td b) Effective symmetrical short-circuit current factor (K' SSC): I SCC x ktd The required K'SSC = Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current I PN

Considering infinite source at 11 kV ,the maximum through fault current on 1 MVA transformer would be: %age impedance at 1 MVA = 0.0600 Taking negative tolerance of 15% = 0.0510 ISSC = 1 1.732 x 11 x 0.051 ISSC K'SSC = = = K'SSC to be considered for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) c) Knee point voltage : The calculated value of knee point voltage is = 0.100 VA 1.042 VA = 1.0292 kA 1029.17505444336 x 3 400 7.72 7.72

(0.942+0.1)

(RBC+ Ri ) X ISN X K'SSC 1.3

Knee Point voltage required Knee Point voltage required 20% margin on Vk value

= = =

(1.042 + 9) x 1 x 7.72 1.3 59.62 71.55 volts volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 37 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for REF protection of 433 V side of Earthing transformer (Applicable for Neutral side CTs) Current Transformer Ration (CTR) = 1500 /1 Relay Normal Current (IN) = 1 amp. Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 7.50 Ohms = (Relay will be mounted in Relay panel)

0.942 7.500

CT Internal Burden in VA = (I) x 7.5 Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = I High set point = 20 IN Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) = = (0.942+0.1)

atleast

0.100 VA 1.042 VA

b) Knee point voltage : The calculated value of knee point Knee Point voltage required

= =

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (7.5+1.042) x 1 1.3 131.42 157.70 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source, the maximum through fault current on 1000 KVA transformer would be: %age impedance at 1000 KVA Overall Impedance ( taking 15% negative tolerance) If = 1000 1.732 x 0.415 x 0.051 27.2793 kA 1.5x27279.3x(7.5+0.942 )x2 1500 > 460.58 volts = = 0.0600 0.0510

If = Vk >

PH7-3B-10-15-C001, Rev 0

Page 38 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Incomer Feeder (Typical bay no: A18,A28) Type:4 Configuration 25MVA, 66/11kV transformer,Earthing/auxiliary transformer rating of 1000kVA Applicable substations:Abu Thaila Substation Modification

66kV side
66/11KV 20/25MVA ONAN/ONAF Core-2 100/1 Class-5P20 15VA Core-3 400/1 Class-PX Vk250 Rct9 Io<30ma

11/0.415KV 1000KVA

Core-1 1500/1 Class-PX Vk500 Rct7.5 Io<25ma

Core-1 100/1 Class-PX Vk100 Rct0.4 Io<30ma

To Back-up earth fault (7SJ61)

Core-1 750/1 Class-5P20 15VA Core-2 100/1 Class-PX Vk100 Rct0.4 Io<30ma Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma

To REF protection for Earthing transformer (7SJ61)

Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma Core-2 2500/1 Class-5P20/1.0 Rct8 10VA

To partial busbar differential protection (7SJ61)

To REF protection for 11kV side (7SJ61)

To Directional Overcurrent & earth fault / Metering (6MD6 & 7SJ62)

Core-1 2500/1 Class-PX Vk250 Rct9 Io<30ma

To Transformer REF (11kV side) & Main differential protection (7SJ61 & 7UT613)

11kV Bus

Feeder =A18, =A28

CT knee point voltage calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on Cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = = = = 2500 /1 1 amp. 70 meter 5.610 Ohms/Km 5.61x1.2 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = (Relay will be mounted in Relay panel)

0.942 9.00

PH7-3B-10-15-C001, Rev 0

Page 39 of 91

SIEMENS
Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = The required K'SSC IN Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point voltage is = = (0.942+0.1) 0.100 VA 1.042 VA

PROJECT:GTC/123/2006

ANNEXURE 1

20

atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn

Knee Point voltage required

20 x (9+1.042) x 1 1.3 154.49 volts 185.39

= 20% margin on Vk value =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 25 MVA transformer would be: %age impedance at 25 MVA = 0.1258 Taking a negative tolerance of 15% = 0.1069 If = 25 1.732 x 11 x 0.1069 12.2750 kA 1.5x12275x(9+0.942 )x2 2500 > 146.45 volts

If Vk

= >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 40 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Formula Used a) Transient dimensioning factor (k td): 3 For transformer, k td = b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC I SCC x ktd = I PN Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11 kV ,the maximum through fault current on 25 MVA transformer would be: %age impedance at 25 MVA = 0.1258 Taking negative tolerance of 15% = 0.1069 ISSC = 25 1.732 x 11 x 0.1069 12.2750 kA 12275 x 3 2500 14.73

ISSC K'SSC K'SSC to be considered for calculations

= = =

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) =

(0.942+0.1)

0.100 VA 1.042 VA

c) Knee point voltage : The calculated value of knee point voltage is Knee Point voltage required

(RBC+ Ri ) X ISN X K'SSC 1.3 (1.042 + 9) x 1 x 14.73 1.3 113.78 136.54 volts volts

Knee Point voltage required 20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 41 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequacy checking calculations for 7SJ62 and 6MD6 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-2 ) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = = (0.942+0.1) = (10+8) x20 (1.042+8) 39.81 > 20 = = = 8.0 VA 10 VA 0.100 VA 1.042 VA = = 20 atleast RBN+ Ri x KSSC RBC + Ri

Calculated Value for K' SSC

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 42 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for Partial Bus bar protection Feeders =A18,=A28 (connected across core-3 ) Current Transformer Ration (CTR) = 2500 Relay Normal Current (IN) = 1 amp. Length of cable between CT and Relay = 70 meter #REF! = 5.610 Ohms/Km 20% margin on cable resistance = 6.732 Ohms/Km = 0.942 Ohms Loop Resistance ( 2R L ) Loop Burden in VA = (I) x 0.942 = = 9.00 Ohms Current Transformer resistance (R ct) CT Internal Burden in VA = (I) x 9 = Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = 20 The required K'SSC IN RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 = = RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required

(Relay will be mounted in Relay panel)

0.942 9.000

atleast

(0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (1.042+9) x 1 1.3 154.49 185.39 volts volts

0.100 VA 1.042 VA

= =

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 43 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across 11kV Neutral side CTs of 1000KVA) Current Transformer Ration (CTR) = 2500 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance = = = = = = = = 70 meter 5.610 Ohms/Km 5.61x1.2 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = 0.942 9.00 (Relay will be mounted in Relay panel) (As per contract document)

Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = = (0.942+0.1) 0.100 VA 1.042 VA = I High set point = IN 20 atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (9+1.042) x 1 1.3 154.49 185.39 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 25 MVA transformer would be: %age impedance at 25 MVA = 0.1258 Taking a negative tolerance of 15% = 0.1069 If = 25 1.732 x 11 x 0.1069 12.2750 kA

If

Vk

>

1.5x12275x(9+0.942 )x2 2500

>

146.45

volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 44 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for Phase and Neutral side CTs) Current Transformer Ration (CTR) = 100 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = 70 meter 5.610 Ohms/Km 6.732 0.942 Ohms (I) x 0.942 = 0.40 Ohms (I) x 0.4 = (Relay will be mounted in Relay panel)

0.942 0.4

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = (0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 0.4 x (0.4+1.042) x 1 1.3 22.18 26.62 volts 0.100 VA 1.042 VA = I High set point = IN 20 atleast

= =

20% margin on vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition Vk > If x (Rct + 2RL ) x 2 Where I f is magnitude of through fault current

Considering infinite source,the maximum through fault current on 1000 KVA transformer would be: %age impedance at 1000 KVA Overall Impedance ( taking 15% negative tolerance) If = 1000 1.732 x 11 x 0.051 1029.1751 A = = 0.0600 0.0510

If =

As the through fault current could be ground fault current which can be max 750A, the stablility is being checked for this max value. Vk > 750 x (0.4 + 0.942 ) x 2 100 > 20.13 volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 45 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequecy check for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for 1000 KVA HV Neutral side CTs) Current Transformer Ration (CTR) Relay Normal Current (IN) = = 750 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+6) x20 6+0.992 60.06 =

20 atleast

RBN+ Ri x KSSC RBC + Ri

= = = =

6.0 VA 15 VA 0.050 VA 0.992 VA

Calculated Value for K' SSC

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 46 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequecy check for 7SJ61 type used for O/C protection of 11kV side of Earthing transformer Current Transformer Ration (CTR) Relay Normal Current (IN) = = 100 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+1.2) x20 1.2+0.992 147.80 =

20 atleast

RBN+ Ri x KSSC RBC + Ri

= = = =

1.2 VA 15 VA 0.050 VA 0.992 VA

Calculated Value for K' SSC

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 47 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders to 1000 KVA EAT-(connected across core-3 ) Formula Used a) Transient dimensioning factor (k td): = 3 For transformer, k td b) Effective symmetrical short-circuit current factor (K' SSC): I SCC x ktd The required K'SSC = Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current I PN

Considering infinite source at 11 kV ,the maximum through fault current on 1 MVA transformer would be: %age impedance at 1 MVA = 0.0600 Taking negative tolerance of 15% = 0.0510 ISSC ISSC K'SSC K'SSC to be considered for calculations = = = = 1 1.732 x 11 x 0.051 1.0292 kA 1029.17505444336 x 3 400 7.72

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) = c) Knee point voltage : The calculated value of knee point Knee Point voltage required Knee Point voltage required 20% margin on Vk value

(0.942+0.1)

0.100 VA 1.042 VA

= = = =

(RBC+ Ri ) X ISN X K'SSC (1.042 + 9) x 1 x 7.72 1.3 59.62 71.55 volts volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 48 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for REF protection of 433 V side of Earthing transformer (Applicable for Neutral side CTs) Current Transformer Ration (CTR) = 1500 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 7.50 Ohms = (Relay will be mounted in Relay panel)

0.942 7.500

CT Internal Burden in VA = (I) x 7.5 Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = 20 The required K'SSC IN Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) = = (0.942+0.1)

atleast

0.100 VA 1.042 VA

b) Knee point voltage : The calculated value of knee point Knee Point voltage required

= =

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (7.5+1.042) x 1 1.3 131.42 157.70 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source, the maximum through fault current on 1000 KVA transformer would be: %age impedance at 1000 KVA Overall Impedance ( taking 15% negative tolerance) If = 1000 1.732 x 0.415 x 0.051 27.2793 kA 1.5x27279.3x(7.5+0.942 )x2 1500 > 460.58 volts = = 0.0600 0.0510

If = Vk >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 49 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Incomer Feeder (Typical bay no: A18,A28) Type:5 Configuration 40MVA, 66/11kV transformer,Earthing/auxiliary transformer rating of 2000kVA Applicable substations:MIC Super , Al Dhahiya,Al Waab Super, Wakrah 2, EDS

66kV side
66/11KV 32/40MVA ONAN/ONAF Core-2 200/1 Class-5P20 15VA Core-3 400/1 Class-PX Vk100 Rct9 Io<30ma at Vk/2

11/0.415KV 2000KVA

Core-1 3000/1 Class-PX Vk450 Rct15 Io<25ma

Core-1 200/1 Class-PX Vk100 Rct0.6 Io<30ma at Vk/2

To Back-up earth fault (7SJ61)

Core-1 750/1 Class-5P20 15VA Core-2 200/1 Class-PX Vk100 Rct0.6 Io<30ma Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma

To REF protection for Earthing transformer (7SJ61)

Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma Core-2 2500/1 Class-5P20/1.0 Rct8 10VA

To partial busbar differential protection (7SJ61)

To REF protection for 11kV side (7SJ61)

To Directional Overcurrent & earth fault / Metering (6MD6 & 7SJ62)

Core-1 2500/1 Class-PX Vk250 Rct9 Io<30ma

To Transformer REF (11kV side) & Main differential protection (7SJ61 & 7UT613)

11kV Bus

Feeder =A18, =A28

CT knee point voltage calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on Cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = = = = 2500 /1 1 amp. 70 meter 5.610 Ohms/Km 5.61x1.2 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = (Relay will be mounted in Relay panel)

0.942 9.00

PH7-3B-10-15-C001, Rev 0

Page 50 of 91

SIEMENS
Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = The required K'SSC IN Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point voltage is = = (0.942+0.1) 0.100 VA 1.042 VA

PROJECT:GTC/123/2006

ANNEXURE 1

20

atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn

Knee Point voltage required

20 x (9+1.042) x 1 1.3 154.49 volts 185.39

= 20% margin on Vk value =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 40 MVA transformer would be: %age impedance at 40 MVA = 0.1633 Taking a negative tolerance of 15% = 0.1388 If = 40 1.732 x 11 x 0.1388 15.1262 kA 1.5x15126.2x(9+0.942 )x2 2500 > 180.46 volts

If Vk

= >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 51 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Formula Used a) Transient dimensioning factor (k td): 3 For transformer, k td = b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC I SCC x ktd = I PN Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11 kV ,the maximum through fault current on 40 MVA transformer would be: %age impedance at 40 MVA = 0.1633 Taking negative tolerance of 15% = 0.1388 ISSC = 40 1.732 x 11 x 0.1388 15.1262 kA 15126.2 x 3 2500 18.15

ISSC K'SSC K'SSC to be considered for calculations

= = =

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) =

(0.942+0.1)

0.100 VA 1.042 VA

c) Knee point voltage : The calculated value of knee point voltage is Knee Point voltage required

(RBC+ Ri ) X ISN X K'SSC 1.3 (1.042 + 9) x 1 x 18.15 1.3 140.20 168.24 volts volts

Knee Point voltage required 20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 52 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequacy checking calculations for 7SJ62 and 6MD6 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-2 ) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = = (0.942+0.1) = (10+8) x20 (1.042+8) 39.81 > 20 = = = 8.0 VA 10 VA 0.100 VA 1.042 VA = = 20 atleast RBN+ Ri x KSSC RBC + Ri

Calculated Value for K' SSC

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 53 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for Partial Bus bar protection Feeders =A18,=A28 (connected across core-3 ) Current Transformer Ration (CTR) = 2500 Relay Normal Current (IN) = 1 amp. Length of cable between CT and Relay = 70 meter Cable Resistance for mmat 75C = 5.610 Ohms/Km 20% margin on cable resistance = 6.732 Ohms/Km = 0.942 Ohms Loop Resistance ( 2R L ) Loop Burden in VA = (I) x 0.942 = = 9.00 Ohms Current Transformer resistance (R ct) CT Internal Burden in VA = (I) x 9 = Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = 20 The required K'SSC IN RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 = = RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required

(Relay will be mounted in Relay panel)

0.942 9.000

atleast

(0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (1.042+9) x 1 1.3 154.49 185.39 volts volts

0.100 VA 1.042 VA

= =

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 54 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across 11kV Neutral side CTs of 2000KVA) Current Transformer Ration (CTR) = 2500 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance = = = = = = = = 70 meter 5.610 Ohms/Km 5.61x1.2 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = 0.942 9.00 (Relay will be mounted in Relay panel) (As per contract document)

Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = = (0.942+0.1) 0.100 VA 1.042 VA = I High set point = IN 20 atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (9+1.042) x 1 1.3 154.49 185.39 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 40 MVA transformer would be: %age impedance at 40 MVA = 0.1633 Taking a negative tolerance of 15% = 0.1388 If = 40 1.732 x 11 x 0.1388 15.1262 kA

If

Vk

>

1.5x15126.2x(9+0.942 )x2 2500

>

180.46

volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 55 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT calculation for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for Phase and Neutral side CTs) Current Transformer Ration (CTR) = 200 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = 70 meter 5.610 Ohms/Km 6.732 0.942 Ohms (I) x 0.942 = 0.60 Ohms (I) x 0.6 = (Relay will be mounted in Relay panel)

0.942 0.6

Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = = (0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (0.6+1.042) x 1 1.3 25.26 30.31 volts 0.100 VA 1.042 VA = I High set point = IN 20 atleast

= =

20% margin on vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition Vk >1.5( I f x (Rct + 2RL ) x 2) Where I f is magnitude of through fault current

Considering infinite source,the maximum through fault current on 2000 KVA transformer would be: %age impedance at 2000 KVA Overall Impedance ( taking 15% negative tolerance) If = 2000 1.732 x 11 x 0.102 1029.1751 A = = 0.1200 0.1020

If =

As the through fault current could be ground fault current which can be max 750A, the stablility is being checked for this max value. Vk > 750 x (0.6 +, 0.942 ) x 2x1.5 200 > 17.34 volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 56 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequacy check for 7SJ61 type used for REF protection of 11kV side of Earthing transformer (Applicable for 2000 KVA HV Neutral side CTs) Current Transformer Ration (CTR) Relay Normal Current (IN) = = 750 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+6) x20 6+0.992 Calculated Value for K' SSC = 60.06 =

20 atleast

RBN+ Ri x KSSC

= = = =

6.0 VA 15 VA 0.050 VA 0.992 VA

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 57 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequecy check for 7SJ61 type used for O/C protection of 11kV side of Earthing transformer Current Transformer Ration (CTR) Relay Normal Current (IN) = = 200 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+1.2) x20 1.2+0.992 Calculated Value for K' SSC = 147.80 =

20 atleast

RBN+ Ri x KSSC

= = = =

1.2 VA 15 VA 0.050 VA 0.992 VA

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 58 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders to 2000 KVA EAT-(connected across core-3 ) Formula Used a) Transient dimensioning factor (k td): 3 For transformer, k td = b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11 kV ,the maximum through fault 40 current on 2 MVA transformer would be: %age impedance at 2 MVA = 0.1200 Taking negative tolerance of 15% = 0.1020 ISSC = 2 1.732 x 11 x 0.102 ISSC K'SSC K'SSC to be considered for calculations = = = 1.0292 kA 1029.17505444336 x 3 400 7.72 = I SCC x ktd I PN

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) =

(0.942+0.1)

0.100 VA 1.042 VA

c) Knee point voltage : The calculated value of knee point voltage is Knee Point voltage required Knee Point voltage required 20% margin on Vk value

= = = =

(RBC+ Ri ) X ISN X K'SSC 1.3 (1.042 + 9) x 1 x 7.72 1.3 59.62 71.55 volts volts

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 59 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for REF protection of 433 V side of Earthing transformer (Applicable for Neutral side CTs) Current Transformer Ration (CTR) = 3000 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 15.00 Ohms = (Relay will be mounted in Relay panel)

0.942 15.000

CT Internal Burden in VA = (I) x 15 Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = I High set point = 20 IN Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) = = (0.942+0.1)

atleast

0.100 VA 1.042 VA

b) Knee point voltage : The calculated value of knee point Knee Point voltage required

= =

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (15+1.042) x 1 1.3 246.80 296.16 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source, the maximum through fault current on 2000 KVA transformer would be: %age impedance at 2000 KVA Overall Impedance ( taking 15% negative tolerance) If = 2000 1.732 x 0.415 x 0.102 27.2793 kA 1.5x27279.3x(15+0.942 )x2 3000 > 434.89 volts = = 0.1200 0.1020

If = Vk >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 60 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Incomer Feeder (Typical bay no: A18,A28) Type:6 Configuration: 10MVA, 33/11kV transformer Applicable substations:Ain Hamad 33 KV SIDE Core-2 750/1 Class - 5P20 15 VA Core-1 600-300/1 Class - PX Vk Rct9 - 4.5 Io=30mA at Vk/2

33/11 KV 7.5/10MVA ONAN/ONAF

8.47ohm 750A, 30s NER

Backup earth fault (7SJ61)

11kV side REF Protection (7SJ61)

Core-3 800/1 Class - PX Vk250 Rct9 Io=30mA at Vk/2 Core-2 600-300/1 Class - 5P20/1.0 20 - 10 VA

Partial Bus Bar protection (7SJ61)

To Directional Overcurrent & earth fault / Metering (6MD6 & 7SJ62)

Core-1 600-300/1 Class - PX Vk600 - 300 Rct9 - 4.5 Io=30mA at Vk/2

To Transformer REF (11kV side) & Main differential protection (7SJ61 & 7UT613)

11kV Bus

Feeder =A18, =A28

CT knee point voltage calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay #REF! 20% margin on Cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = = = = 600 /1 1 amp. 70 meter 5.610 Ohms/Km 5.61x1.2 Ohms/Km 6.730 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = (Relay will be mounted in Relay panel)

0.942 9.00

PH7-3B-10-15-C001, Rev 0

Page 61 of 91

SIEMENS
Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = The required K'SSC IN Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point voltage is = (0.942 + 0.1) 0.1 VA 1.042 VA

PROJECT:GTC/123/2006

ANNEXURE 1

20

atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn Ratio 600/1 20 x (9 + 1.042) x 1 1.3 154.49 volts 185.39 Ratio 300/1 20 x (4.5 + 1.042) x 1 1.3 85.26 volts 102.31

Knee Point voltage required

= 20% margin on Vk value =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 10 MVA transformer would be: %age impedance at 10 MVA = 0.1200 Taking a negative tolerance of 15% = 0.102 If = 10 1.732 x 11 x 0.102 5.146 kA Ratio 600/1 Vk > 1.5 x 5146 x (9 + 0.942 ) x 2 600 > 255.81 volts 280.05 Ratio 300/1 1.5 x 5146 x (4.5 + 0.942 ) x 2 300 volts

If

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 62 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Formula Used a) Transient dimensioning factor (k td): 3.00 For transformer, k td = b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC I SCC x ktd = I PN Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11 kV ,the maximum through fault current on 10 MVA transformer would be: %age impedance at 10 MVA = 0.1200 Taking negative tolerance of 15% = 0.1020 ISSC = 10.00 1.732 x 11 x 0.102 5.146 kA Ratio 600/1 K'SSC K'SSC to be considered for calculations = = 5146 x 3 600 25.73 Ratio 300/1 5146 x 3 300 51.46

ISSC

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = = RBC = (Loop Burden+ Relay Burden)

(0.942 + 0.1)

0.1 VA 1.042 VA

c) Knee point voltage : The calculated value of knee point voltage is

(RBC+ Ri ) X ISN X K'SSC 1.3 Ratio 600/1 Ratio 300/1 (1.042 + 4.5) x 1 x 51.46 1.3 219.38 volts 263.25 volts

Knee Point voltage required

(1.042 + 9) x 1 x 25.73 1.3 198.75 volts 238.51 volts

Knee Point voltage required 20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 63 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequacy checking calculations for 7SJ62 and 6MD6 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-2 ) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) 0.1 VA 1.042 VA Ratio 300/1 (10 + 4) x 20 (1.042 + 4) 55.53 = = 20 atleast RBN+ Ri x KSSC RBC + Ri

(0.942 + 0.1) Ratio 600/1 (20 + 8) x 20 (1.042 + 8) 61.93

K'SSC

Calculated Value for K' SSC

> 20 20 Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 64 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for Partial Bus bar protection Feeders =A18,=A28 (connected across core-3 ) Current Transformer Ration (CTR) = 800 Relay Normal Current (IN) = 1 amp. Length of cable between CT and Relay = 70 meter Cable Resistance for mmat 75C = 5.610 Ohms/Km 20% margin on cable resistance = 6.732 Ohms/Km = 0.942 Ohms Loop Resistance ( 2R L ) Loop Burden in VA = (I) x 0.942 = = 9.00 Ohms Current Transformer resistance (R ct) CT Internal Burden in VA = (I) x 9 = Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): = I High set point = 20 The required K'SSC IN RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 = = RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required

(Relay will be mounted in Relay panel)

0.942 9.000

atleast

(0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (1.042+9) x 1 1.3 154.49 185.39 volts volts

0.100 VA 1.042 VA

= =

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 65 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for REF protection with 7SJ61 relay (connected across LV neutral core-1) Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = I High set point = IN RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden =0.05VA RBC = (Loop Burden+ Relay Burden) = (0.942 + 0.05) Ratio 600/1 Knee Point voltage required = (0.992 + 9) x 1 x 20 1.3 Knee Point voltage required 20% margin on Vk value (As per contract document) = = 153.72 184.47

20 atleast

0.05 VA 0.992 VA Ratio 300/1 (0.992 + 4.5) x 1 x 20 1.3 84.49 101.39

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 10 MVA transformer would be: %age impedance at 10 MVA = 0.1200 Taking a negative tolerance of 15% = 0.1020 If = 10 1.732 x 11 x 0.102 5.146 kA

If

Ratio 600/1 Vk > 1.5 x 5146 x (9 + 0.942 ) x 2 600 > 255.81

Ratio 300/1 1.5 x 5146 x (4.5 + 0.942 ) x 2 300 280.05

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 66 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequecy check for 7SJ61 type used for O/C protection of 11kV side of Earthing transformer -Core-2 Current Transformer Ration (CTR) Relay Normal Current (IN) = = 750 amp. 1 amp.

a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = (15+2.2) x20 2.2+0.992 Calculated Value for K' SSC = 107.76 =

20 atleast

RBN+ Ri x KSSC RBC + Ri

= = = =

2.2 VA 15 VA 0.050 VA 0.992 VA

>

20

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 67 of 91

SIEMENS
Incomer Feeder (Typical bay no: A18,A28) Type:7 Configuration 30MVA, 33/11kV transformer,Earthing/auxiliary transformer rating of 1000kVA Applicable substations:RLF-3

PROJECT:GTC/123/2006

ANNEXURE 1

33kV side
33/11KV 25/30MVA ONAN/ONAF

NER

Core-1 75/1 Class-PX Vk250 Rct0.4 Io<30ma at Vk

Core-3 2500/1 Class-PX Vk250 Rct9 Io<30ma Core-2 2500/1 Class-5P20/1.0 Rct8 10VA
To partial busbar differential protection (7SJ61)

To Directional Overcurrent & earth fault / Metering (6MD6 & 7SJ62)

Core-1 2500/1 Class-PX Vk 250 Rct9 Io<30ma

To Transformer Main differential protection ( 7UT613)

11kV Bus

Feeder =A18, =A28

CT knee point voltage calculation for 7SJ61 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on Cable resistance Loop Resistance ( 2RL ) Loop Burden in VA Current Transformer resistance (Rct) CT Internal Burden in VA = = = = = = = = = = 2500 /1 1 amp. 70 meter 5.610 Ohms/Km 5.61x1.2 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = (Relay will be mounted in Relay panel)

0.942 9.00

PH7-3B-10-15-C001, Rev 0

Page 68 of 91

SIEMENS
Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = I High set point = IN Value 20 will be selected for calculations RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point voltage is = = (0.942+0.1) 0.100 VA 1.042 VA

PROJECT:GTC/123/2006

ANNEXURE 1

20

atleast

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn

Knee Point voltage required

20 x (9+1.042) x 1 1.3 154.49 volts 185.39

= 20% margin on Vk value =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x If x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source,the maximum through fault current on 30 MVA transformer would be: %age impedance at 30 MVA = 0.1258 Taking a negative tolerance of 15% = 0.1069 If = 30 1.732 x 11 x 0.1069 14.7300 kA 1.5x14730x(9+0.942 )x2 2500 > 175.73 volts

If Vk

= >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 69 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7UT613 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-1 ) Formula Used a) Transient dimensioning factor (ktd): For transformer, ktd 3 = b) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC I SCC x ktd = I PN Where: ISSC = symmetrical short-circuit current IPN = CT rated primary current ISN = CT rated secondary current Considering infinite source at 11 kV ,the maximum through fault current on 30 MVA transformer would be: %age impedance at 30 MVA = 0.1258 Taking negative tolerance of 15% = 0.1069 ISSC = 30 1.732 x 11 x 0.1069 14.7300 kA 14730 x 3 2500 17.68

ISSC K'SSC K'SSC to be considered for calculations

= = =

Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 = = RBC = (Loop Burden+ Relay Burden)

(0.942+0.1)

0.100 VA 1.042 VA

c) Knee point voltage : The calculated value of knee point voltage is Knee Point voltage required

(RBC+ Ri ) X ISN X K'SSC 1.3 (1.042 + 9) x 1 x 17.68 1.3 136.57 163.89 volts volts

Knee Point voltage required 20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 70 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Adequacy checking calculations for 7SJ62 and 6MD6 relay for 11kV Incomer Feeders =A18,=A28 (connected across core-2 ) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = = = = = (0.942+0.1) = (10+8) x20 (1.042+8) 39.81 > 20 8.0 VA 10 VA 0.100 VA 1.042 VA = = 20 atleast RBN+ Ri x KSSC RBC + Ri

Calculated Value for K'SSC

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 71 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT Knee point voltage calculation for 7SJ61 type used for Partial Bus bar protection Feeders =A18,=A28 (connected across core-3 ) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for mmat 75C 20% margin on cable resistance Loop Resistance ( 2RL ) Loop Burden in VA Current Transformer resistance (Rct) CT Internal Burden in VA Formula Used a) Effective symmetrical short-circuit The required K'SSC = = = = = = = = = 2500 1 amp. 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 =

(Relay will be

0.942 9.000

I High set point = IN

20

atleast

RBC = Connected Burden across CT in Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required

= = (0.942+0.1) Ihigh set point x I2N x 1.3 x Ipn 20 x (1.042+9) x 1 1.3 154.49 185.39 volts volts

0.100 VA 1.042 VA

= =

20% margin on Vk value The minimum CT knee point Voltage

= =

PH7-3B-10-15-C001, Rev 0

Page 72 of 91

SIEMENS
Outgoing Feeder (Typical bay no: A10,A20) Type:1 Applicable substations:All substations with 11kV switchgear except Ain Hamad

PROJECT:GTC/123/2006

ANNEXURE 1

11kV Bus

Core-1 400-300/1 Class-PX Vk250-300 Rct1.75-1.25 Io<30ma Core-2 400-300/1 Class-5P20/1.0 Rct3-2 VA Burden -10 VA

To Pilot wire differential, Cable overload protection (SOLKOR)

To Feeder Overcurrent & earth fault protection / metering (7SJ61 + 6MD6)

CT Knee point voltage calculation for SOLKOR type relay used for Pilot wire protection Applicable for 11kV Outgoing Feeders Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance (2RL ) Loop burden in VA; (I) 2 x 2RL Current Transformer resistance (R ct) Short time rating of 11kV system (I sc) Formula Used Knee point voltage requirement V k = = = = = = = = = = 300 /1 1 amp. 70 5.610 5.61 x 1.2 6.732 0.942 meter Ohms/Km Ohms/Km Ohms (Relay will be mounted in Relay panel)

0.942 VA 1.25 Ohms 31.50 kA

>

50 / In + If / In * (Rct + 2Rl)

Where: In = Rated current, amps. = 1A If = Primary current under maximum steady state through fault cnditions. N = CT ratio = 400-300/1A RL = Lead resistance of single lead from relay to current transformer Rct = Secondary resistance Lead resistance of single lead from relay to current transformer If = Maximum through fault current = 50 x In 50 0.05 ohm Guard relay burden per element (R G) = Knee point voltage requirement V k Required parameters for CTs > > 20% margin on Vk value > > 50 / In + If / In * (Rct + 2R L + 2RG) Ratio 300/1 50/1+50/1 x (1.25+0.942+2x0.05) 164.60 197.52 Ratio 400/1 50/1+50/1 x (1.75+0.942+2x0.05) 189.60 227.52

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 73 of 91

SIEMENS
Adequacy checking calculation for 7SJ61 & 6MD6 relay for 11kV Cable feeders (connected across core-2) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Ri = Internal CT burden in VA Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) Required parameters for CTs K'SSC = = = (0.942+0.1) Ratio 300/1 (10+2) x20 (1.042+2) 78.90 20 0.100 VA 1.042 VA = = RBN+ Ri x KSSC RBC + Ri 20 atleast

PROJECT:GTC/123/2006

ANNEXURE 1

Ratio 400/1 (+3) x20 (1.042+3) 14.84 20

Calculated Value for K' SSC >

Since the calculated K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 74 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Outgoing Feeder (A30,A40) Type:2 Applicable substations:Ain Hamad

11kV Bus

Core-1 100/1 Class - 5P10 10VA

To Over current / Earth fault (7SJ61)

Core-2 100/1 Class - 1.0 10VA

Metering

11/0.415 kV 500 KVA ONAN/ONAF

Core-1 750/1 Class - PX Vk Rct6 Io<25mA


415V side REF Protection (7SJ61)

Core-1 750/1 Class - PX Vk Rct6 Io<25mA

415V side REF Protection (7SJ61)

Adequacy checking calculations for 7SJ61 relay for 11kV Incomer Feeders (connected across core-1) Current Transformer Ration (CTR) Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4.0mm 2 at 750C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) CT Internal Burden in VA = = = = = = = = = 100 /1 1 amp. 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 1.500 Ohms (I) x 1.5 = 0.942 1.50

a) Effective symmetrical short-circuit current factor (K' SSC): = The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 = RBC = (Loop Burden+ Relay Burden) = RBN+ Ri x KSSC RBC + Ri

20 atleast

(0.942+0.1)

0.1 VA 1.042 VA

K'SSC

(10 + 1.5) x 20 (1.042 + 1.5)

Calculated Value for K' SSC

90.48

>

20.00

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 75 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

CT knee point voltage calculations for 7SJ61 type used for REF protection of 415 V side of 315kVA transformer (Applicable for Phase and Neutral side CTs) Current Transformer Ration (CTR) = 750 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4.0mm 2 at 750C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = 70 meter 5.610 Ohms/Km 6.732 Ohms/Km 0.942 Ohms (I) x 0.942 = 6.000 Ohms (I) x 6 = 0.942 6.000

CT Internal Burden in VA = Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = IN Value 20 will be selected for calculations Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = .1 VA RBC = (Loop Burden+ Relay Burden) =

IHigh set point =

20

atleast

(0.942+0.1)

0.1 VA 1.042 VA

b) Knee point voltage : The calculated value of knee point Knee Point voltage required

= =

Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (6 + 1.042) x 1 1.3 108.34 130.01 volts

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above Stability check for REF protection for through fault condition To establish that CT rated knee point volatge is atleast 2 times that voltage developed across the CT in case of through fault condition with one of the CT saturated, the formula used is : (For determining the Voltage developed across CT, a current of 1.5 times of the maximum possible through fault current has been considered) Vk > 2 x 1.5 x I f x (Rct + 2RL ) Where If is magnitude of through fault current Considering infinite source, the maximum through fault current on 500 KVA transformer would be: %age impedance at 500 KVA Overall Impedance ( taking 15% negative tolerance) If = 500 (1.732 x415 x 0.0816) 8.525 kA 1.5 x 8525 x (6 +0.942) x 2 750 > 236.72 volts = = 0.0960 0.082

If = Vk >

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 76 of 91

SIEMENS

PROJECT:GTC/123/2006

ANNEXURE 1

Bus Coupler (Typical bay no.A12) Type:1

Applicable substations: All substations with 11kV switchgear except Ain Hamad

11kV Bus-1
Core-1 2500/1 Class-PX Vk250 Rct9 Io<30ma
To partial busbar differential protection (7SJ61)

11kV Bus-2
Core-2 2500/1 Class-PX Vk250 Rct9 Io<30ma Core-1 2500/1 Class-5P20/1.0 Rct8.5 10 VA
To partial busbar differential protection (7SJ61)

To Overcurrent/Earth fault and Metering (6MD6 + 7SJ61)

CT Knee point voltage calculation for 7SJ61 type used for Partial Bus bar differential protection Applicable for I/C and B/C Current Transformer Ration (CTR) = 2500 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4 mmat 75C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = 70 5.610 6.732 0.942 meter Ohms/Km Ohms/Km Ohms (Relay will be mounted in Relay panel)

(I) x 0.942 = 9.00 Ohms (I) x 9 =

0.942 9.000

CT Internal Burden in VA = Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = IN RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required = =

I High set point =

20

atleast

0.100 VA (0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (9+1.042) x 1 1.3 154.49 185.39 volts volts 1.042 VA

= =

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 77 of 91

SIEMENS
Adequacy checking calculation for 7SJ61 & 6MD6 relay (connected across core-2 ) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 RBC = (Loop Burden+ Relay Burden) K'SSC = = = (0.942+0.1) (10+8.5) x20 (1.042+8.5) 38.78 > 20.00 0.100 VA 1.042 VA = = RBN+ Ri x KSSC RBC + Ri 20 atleast

PROJECT:GTC/123/2006

ANNEXURE 1

Calculated Value for K' SSC

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 78 of 91

SIEMENS
Bus Coupler (A12) Type:2 Applicable substations:Ain Hamad

PROJECT:GTC/123/2006

ANNEXURE 1

11kV Bus-1
Core-1 800/1 Class-PX Vk250 Rct9 Io<30mA at Vk/2
To partial busbar differential protection (7SJ61)

11kV Bus-2
Core-2 800/1 Class-PX Vk250 Rct9 Io<30mA at Vk/2 Core-1 800/1 Class-5P20/1.0 Rct8.5 15 VA
To Overcurrent/Earth fault and Metering (6MD6 + 7SJ61) To partial busbar differential protection (7SJ61)

CT knee point voltage calculations for 7SJ61 type used for Partial Bus bar differential protection Applicable for I/C and B/C Current Transformer Ration (CTR) = 800 /1 = 1 amp. Relay Normal Current (IN) Length of cable between CT and Relay Cable Resistance for 4.0mm 2 at 750C 20% margin on cable resistance Loop Resistance ( 2R L ) Loop Burden in VA Current Transformer resistance (R ct) = = = = = = 70 meter 5.610 Ohms/Km 6.730 Ohms/Km 0.942 Ohms (I) x 0.942 = 9.00 Ohms (I) x 9 = 0.942 9.000

CT Internal Burden in VA = Formula Used a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC = IN RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA I2N = Relay Normal Current Relay Burden = 0.1 VA RBC = (Loop Burden+ Relay Burden) b) Knee point voltage : The calculated value of knee point Knee Point voltage required =

I High set point =

20

atleast

0.1 VA (0.942+0.1) Ihigh set point x I2N x (Ri+RBC) 1.3 x Ipn 20 x (9+1.042) x 1 1.3 154.49 185.39 volts volts 1.042 VA

= =

20% margin on Vk value

= =

The minimum CT knee point Voltage shall be selected more than above

PH7-3B-10-15-C001, Rev 0

Page 79 of 91

SIEMENS
Adequacy checking calculation for 7SJ61 & 6MD6 relay (connected across core-1 ) a) Effective symmetrical short-circuit current factor (K' SSC): The required K'SSC Also K'SSC Where RBC = Connected Burden across CT in VA Ri = Internal CT burden in VA RBN = Nominal Burden of CT in VA Relay Burden = 2*0.05 = 0.10VA RBC = (Loop Burden+ Relay Burden) 0.1 VA 1.042 VA = = RBN+ Ri x KSSC RBC + Ri 20 atleast

PROJECT:GTC/123/2006

ANNEXURE 1

(0.942+0.1)

K'SSC

(15+8.5) x20 (1.042+8.5) 49.26 > 20.00

Calculated Value for K' SSC

Since the selected K' SSC is more than Minimum required K' SSC (20), Hence selected CT is OK

PH7-3B-10-15-C001, Rev 0

Page 80 of 91

SIEMENS
Sr. No. Feeder Description CT Ratio used CT Knee Point CT Resistance Voltage (V) (ohms) Relays connected Relay Burden (in VA) VA burden due to Secondary leads Total VA burden Remarks

PROJECT:GTC/123/2006
ANNEXURE 2

Applicable substations

Bay =A18,=A28 (Incomer feeder) Core-1, Cl. PX Core-2, 5P20/1.0 2500/1 2500/1 250 9 7SJ61 6MD6 Ammeter Core-3, Cl. PX Core-4, Cl. PX 2500/1 2500/1 250 250 9 9 7SJ61 7SD52 7UT613 7SJ62 0.050 0.050 0.250 0.050 0.050 0.942 0.942 0.992 0.992 0.050 0.050 0.942 0.942 1.042 1.292 Rated Burden selected= 10 VA

Al Jumailyah, Khore Junction,Mosemeer,Abu Hamour central,Al Wadi,MIC-2,MIC-3,QRE,Khore Community,Al Dhahiya West, NBK-2, Al Soudan, Ain Khalid south,Abu Thaila Substation Modification,NDQ, Murraikh North, South west wakrah,Lusail Development Super 1,MIC Super , Al Dhahiya,Al Waab Super, Wakrah 2, EDS,RLF-3 Mosemeer,Abu Hamour central,Al Wadi,MIC-2,MIC3,QRE,Khore Community,Al Dhahiya West, NBK-2, Al Soudan, Ain Khalid south,Al Jumailyah, Khore Junction

Earthing transformer (500KVA) Core-1, Cl. PX Core-2, 5P20/1.0 Trafo Neutral, Cl. PX (11kV side) Trafo Neutral, Cl. PX (11kV side) Trafo Neutral, 5P20/1.0 (11kV side) Trafo Neutral, Cl. PX (415 V side) 50/1 50/1 2500/1 50/1 750/1 750/1 100 250 100 250 1.20 9.0 1.20 6 7SJ61 7SJ61 7SJ61 7SJ61 7SJ61 7SJ61 0.050 0.050 0.050 0.050 0.050 0.050 0.942 0.942 0.942 0.942 0.942 0.942 0.992 0.992 0.992 0.992 0.992 0.992 Rated Burden selected= 15 VA Mosemeer,Abu Hamour central,Al Wadi,MIC-2,MIC3,QRE,Khore Community,Al Dhahiya West, NBK-2, Al Soudan, Ain Khalid south,Al Jumailyah, Khore Junction

Rated Burden selected= 15 VA

Earthing transformer (1000KVA) Core-1, Cl. PX Core-2, 5P20/1.0 Trafo Neutral, Cl. PX (11kV side) Trafo Neutral, Cl. PX (11kV side) Trafo Neutral, 5P20/1.0 (11kV side) Trafo Neutral, Cl. PX (415 V side) 100/1 100/1 2500/1 100/1 750/1 1500/1 200/1 200/1 400/1 2500/1 200/1 750/1 3000/1 2500/1 100 250 100 500 100 100 250 100 450 0.40 9.0 0.40 7.50 0.60 9.00 9.0 0.40 15.00 7SJ61 7SJ61 7SJ61 7SJ61 7SJ61 7SJ61 7SJ61 7SJ61 7UT613 7SJ61 7SJ61 7SJ61 7SJ61 7SJ61 6MD6 Ammeter T1, Core-2, Cl. PX T2, Core-1, Cl. PX 2500/1 2500/1 9 9 7SJ61 7SJ61 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.050 0.250 0.050 0.050 0.942 0.942 0.992 0.992 0.050 0.942 0.942 0.942 0.942 0.942 0.942 0.942 0.942 0.942 0.942 0.942 0.942 0.942 0.942 0.992 0.992 0.992 0.992 0.992 0.992 0.992 0.992 0.992 0.992 0.992 0.992 0.992 1.292 Rated Burden selected= 15 VA

NDQ, Murraikh North, South west wakrah,Lusail Development Super 1,Abu Thaila Substation Modification.

Rated Burden selected= 15 VA MIC Super , Al Dhahiya,Al Waab Super, Wakrah 2, EDS

Earthing transformer (2000KVA) Core-1, Cl. PX Core-2, 5P20/1.0 Core-3, Cl. PX Trafo Neutral, Cl. PX (11kV side) Trafo Neutral, Cl. PX (11kV side) Trafo Neutral, 5P20/1.0 (11kV side) Trafo Neutral, Cl. PX (415 V side) Bay =A12 (Bus sectionalizer) T1, Core-1, 5P20/1.0

Rated Burden selected= 15 VA

Rated Burden selected= 15 VA Common for all substations with 11kV switchgear except Ain Hamad

Rated Burden selected= 10 VA

PH7-3B-10-15-C001, Rev 0

Page 81 of 91

SIEMENS
Sr. No. Feeder Description CT Ratio used CT Knee Point CT Resistance Voltage (V) (ohms) Relays connected Relay Burden (in VA) VA burden due to Secondary leads Total VA burden Remarks

PROJECT:GTC/123/2006
ANNEXURE 2

Applicable substations

Outgoing Feeders =Typ. A10,A20 T1, Core-1, Cl. PX T2, Core-1, 5P20/1.0 Bay =A18,=A28 (Incomer feeder) Core-1, Cl. PX Core-2, 5P20/1.0 Core-3, Cl. PX

400-300/1 400-300/1

1.75-1.25

SOLKOR 7SJ61

6MD6 Ammeter 7UT613 7SJ62

3.500 0.050 0.250 0.050 0.050 0.250 0.050

0.050

0.942 0.942

4.442 1.292

Rated Burden selected= 15 VA

Common for all substations with 11kV switchgear except Ain Hamad

600-300/1 600-300/1 800/1

600-300

9-4.5

250

7SJ61 6MD6 Ammeter 7SJ61

0.050 0.050

0.942 0.942 0.942

1.042 1.292 0.992

Rated Burden selected= 10 VA

Ain Hamad

Bay =A18 & =A28 (LV neutral) Core-1, Cl. PX Core-2, 5P20

600-300/1 750/1

9-4.5

7SJ61

0.050

0.942

0.992

Ain Hamad Rated Burden selected= 15 VA

10 Bay =A30 & =A40 (315kVA transformer feeders) Core-1, 5P10/1.0 Core-2, Cl. 1.0 Cl. PX (415V side) 11 Bay =A12,=A22 (Bus sectionalizer) T1, Core-1, CL5P20/1.0 T1, Core-2, Cl. PX T2, Core-1, Cl. PX 12 Outgoing Feeders =A90, =A70, =A50, =A10,= A20, =A60, =A80, =A100, T1, Core-1, Cl. PX T2, Core-2, 5P20/1.0

100/1 100/1 750/1

7SJ61 6.00 7SJ61

0.050 0.050

0.942 0.942

0.992 0.992

Rated Burden selected= 10 VA Rated Burden selected= 10 VA

Ain Hamad

800/1 800/1 800/1

250 250

8.5 9 9

7SJ61 7SJ61 7SJ61

6MD6

0.050 0.050 0.050

0.050

0.942 0.942 0.942

1.092 0.992 0.992

Rated Burden selected= 15 VA

Ain Hamad

400-300/1 400-300/1

300-250

1.25-1.75

SOLKOR 7SJ61

6MD6 Ammeter

3.500 0.050 0.250

0.050

0.942 0.942

4.442 1.292

Rated Burden selected= 15 VA

Ain Hamad

PH7-3B-10-15-C001, Rev 0

Page 82 of 91

SIEMENS
Sr. Feeder Description No. 1 Bay =A14 -T15 Winding-1, 1.0/3P 2 Bay =A24 -T16 Winding-1, 1.0/3P Bay =A18, =A28 (Incomer feeder) Winding-1, 1.0/3P VT Ratio used 11/ 3 : 0.11/3 Relays connected 6MD6 Voltmeter 6MD6 Voltmeter 6MD6 Voltmeter AVR 6MD6 Voltmeter 7SJ62 Relay Burden (in VA) 0.050 1.400 0.050 1.400 0.050 1.400 1.000 0.050 1.400 0.050

PROJECT:GTC/123/2006
ANNEXURE 3 Total VA Remarks burden 1.450 Rated Burden selected= 30 VA

11/ 3 : 0.11/3

1.450

Rated Burden selected= 30 VA .

11/ 3 : 0.11/3

2.500

Rated Burden selected= 30 VA

Outgoing Feeders (Typ.) =A10,A20 Winding-1, 1.0/3P

11/ 3 : 0.11/3

0.050

1.500

Rated Burden selected= 30 VA

PH7-3B-10-15-C001, Rev 0

Page 83 of 91

A
2 Overview

CT dimensioning formulae K'ssc = Kssc Rct + Rb (effective) Rct + R' b with K'ssc W Ktd I SCC max (required) I pn

CT design according to BS 3938/IEC 60044-1 (2000) The design values according to IEC 60044 can be approximately transfered into the BS standard definition by following formula:
VK =

The effective symmetrical short-circuit current factor K'ssc can be calculated as shown in the table above. The rated transient dimensioning factor Ktd depends on the type of relay and the primary DC time constant. For relays with a required saturation free time from w 0.4 cycle, the primary (DC) time constant TP has only little influence.

(Rb

+ Rct ) I sn K ssc 13 .

Example: IEC 600/1, 5P10, 15 VA, Rct = 4 . 60044: IEC PX or BS: VK =

(15 + 4) 1 10 V = 146 V
1.3

Rct = 4 .

For CT design according to ANSI/IEEE C 57.13 please refer to page 2/56

Table 2/1 CT requirements

Relay type Overcurrent-time protection 7SJ511, 512, 531 7SJ45, 46, 60 7SJ61, 62, 63, 64 Line differential protection (pilot wire) 7SD600

Transient dimensioning factor Ktd

Min. required sym. shortcircuit current factor Kssc K'ssc = I High set point I pn

Min. required kneepoint voltage VK VK = I High set point 13 I pn . (Rct + R'b) Isn

at least: 20 I scc max (ext. fault) I pn

at least:

20 (Rct + R'b) Isn 13 .

K'ssc = and:

VK = and:

I scc max (ext. fault) (Rct + R'b) Isn 13 I pn .

3 ( K' ssc I pn )end1 4 = = 4 ( K' ssc I pn )end2 3 Line differential protection (without distance function) 7SD52x, 53x, 610 (50 Hz) 7SD52x, 53x, 610 (60 Hz) Transformer / Generator differential protection 7UT612 7UT613, 633, 635 7UM62 Busbar protection 7SS5, 7SS600 Distance protection 7SA522, 7SA6, 7SD5xx*) *) with distance function Busbar / Line 1.2 1.6 Busbar / Line 4 3 Gen. / Motor 1.2 1.6 Gen. / Motor 5 5 5 K'ssc = I Ktd scc max (ext. fault) I pn and (only for 7SS):

3 (VK I pn / I sn )end1 4 = = 4 (VK I pn / I sn )end2 3 VK = Ktd I scc max (ext. fault) (Rct + R'b) Isn 13 I pn .

Transformer 1.2 1.6 Transformer 4 3 4

K'ssc = 100 (measuring range) VK =

and (only for 7SS): 100 (Rct + R'b) Isn (measuring range) 13 .

for stabilizing factors k = 0.5 0.5 primary DC time constant TP [ms] = 30 Ktd (a) 1 Ktd (b) 4 = 50 2 5 K'ssc = I scc max (close -in fault) I pn
I scc max (zone 1- end fault) I pn

VK = Ktd (a) and: Ktd (b)

= 100 = 200 Ktd (a) 4 5 4 5 and: Ktd (b)

I scc max (close -in fault) (Rct + R'b) Isn 13 I pn . I scc max (zone 1-end fault) (Rct + R'b) Isn 13 I pn .

PH7-3B-10-15-C001, Rev 0 Siemens SIP 2006

Page 84 of 91 2/53

A
2 Overview

Protection Coordination
Example 2: Stability-verification of the numerical busbar protection relay 7SS52

Relay burden The CT burdens of the numerical relays of Siemens are below 0.1 VA and can therefore be neglected for a practical estimation. Exceptions are the busbar protection 7SS60 and the pilot-wire relays 7SD600. Intermediate CTs are normally no longer necessary as the ratio adaptation for busbar and transformer protection is numerically performed in the relay. Analog static relays in general have burdens below about 1 VA. Mechanical relays, however, have a much higher burden, up to the order of 10 VA. This has to be considered when older relays are connected to the same CT circuit.

Fig. 2/93

In any case, the relevant relay manuals should always be consulted for the actual burden values.
= 30 ,000 A = 50 600 A

I SCC.max. I pn

Burden of the connection leads The resistance of the current loop from the CT to the relay has to be considered:
Rlead l = 2 . l A

According to table 2/1 on page 2/53 Ktd = ) K'ssc Rb Rrelay Rlead R'b K'ssc 1 50 = 25 2 15 VA = = 15 . 1 A2 = = 0.1 . = 2 0.0175 50 = 0.3 . 6 . 4 . + 15 Rct + Rb K ssc = . 4 . + 0.4 Rct + R' b

= single conductor length from the CT to the relay in m. = 0.0175 . mm 2 (copper wires) at 20 C m

Specific resistance: . A

= Rl + Rrelay = 0.3 . + 0.1 . = 0.4 . = 10 = 43.2

= conductor cross-section in mm2

CT design according to ANSI/IEEE C 57.13 Class C of this standard defines the CT by ist secondary terminal voltage at 20 times rated current, for which the ratio error shall not exceed 10 %. Standard classes are C100, C200, C400 and C800 for 5 A rated secondary current. This terminal voltage can be approximately calculated from the IEC data as follows: ANSI CT definition
Vs.t.max with Rb Vs.t.max = 20 5 A Rb = = Pb I sn
2

Result: The effective K'ssc is 43.2, the required K'ssc is 25. Therefore the stability criterion is fulfilled.

K ssc 20

and I Nsn = 5 A , we get

Pb K ssc 5A

Example: IEC 600/5, 5P20, 25 VA 60044: ANSI C57.13: Vs.t.max =

(25 VA 20) = 100 V, acc. to class C100


5A

2/56 PH7-3B-10-15-C001, Rev 0

PageSiemens 91 2006 85 of SIP

A
4 Technical Data

4.1
4.1.1

General Device Data


Analog Inputs

Current Inputs
Nominal Frequency Nominal Current Ground Current, Sensitive fNom INom INs 50 Hz or 60 Hz 1 A or 5 A = linear range 1.6 A 1) Approx. 0.05 VA Approx. 0.3 VA Approx. 0.05 VA 100 INom for 1 s 30 INom for 10 s 4 INom continuous 250 INom (half-cycle) 300 A for 1 s 100 A for 10 s 15 A continuous 750 A (half-cycle) (adjustable)

Burden per Phase and Ground Path - at INom = 1 A - at INom = 5 A - for sensitive ground fault detection at 1 A Current overload capability - Thermal (rms)

- Dynamic (peak value) - Thermal (rms)

Current overload capability for high-sensitivity input INs 1)

- Dynamic (peak value)


1)

only in models with input for sensitive ground fault detection (see ordering data in Appendix A.1)

4.1.2

Auxiliary Voltage

DC Voltage
Voltage supply using integrated converter Rated auxiliary DC VAux Permissible Voltage Ranges Rated auxiliary DC VAux Permissible Voltage Ranges Permissible AC ripple voltage, Peak to Peak, IEC 60 255-11 Power Input Bridging Time for Failure/Short Circuit, IEC 6025511 (in not energized operation) 24/48 VDC 19 to 58 VDC 110/125/220/250 VDC 88 to 300 VDC 15 % of the auxiliary voltage Quiescent Energized = 50 ms at V = 110 VDC = 20 ms at V = 24 VDC Approx. 3 W Approx. 7 W 60/110/125 VDC 48 to 150 VDC

268

PH7-3B-10-15-C001, Rev 0

7SJ61 Manual Page 86 of 91 C53000-G1140-C118-7

A
4.1 General

4.1
4.1.1

General
Analog Inputs

Nominal frequency

fN

50 Hz or 60 Hz (adjustable)

Current Inputs
Nominal current Power Consumption per Phase and Earth Path - at IN = 1 A - at IN = 5 A - for sensitive earth fault detection at 1A Current Overload Capability per Current Input - thermal (rms) 100 IN for 1 s 30 IN for 10 s 4 IN continuous 250 IN (half-cycle) 300 A for 1 s 100 A for 10 s 15 A continuous - dynamic (pulse current) 750 A (half-cycle) Approx. 0.05 VA Approx. 0.3 VA Approx. 0.05 VA IN 1 A or 5 A

- dynamic (pulse current) Current Overload Capability for Sensitive Earth Current Input - thermal (rms)

Requirements for current transformers


1st Condition: For a maximum fault current the current transformers must not be saturated under steady-stateconditions n' = 30 2nd Condition: The operational accuracy limit factor n' must be at least 30 or a non- or saturated period of t'AL of at least 1/4 AC cycle after fault inception t'AL = 1/4cycle must be ensured 3 rd Condition: Maximum ratio between primary currents of current transformers at the ends of the protected object

Voltage inputs
Nominal voltage UN Measuring range Power consumption Voltage overload capability per phase - thermal (rms) 230 V continuous At 100 V 80 V to 125 V (adjustable) 0 V to 218.5 V (rms) = 0.1 VA

7SD5 Manual PH7-3B-10-15-C001, C53000-G1176-C169-1

Rev 0

Page 87 of 91

519

A
4

Page 10 of 10
PH7-3B-10-15-C001, Rev 0 Page 88 of 91

PH7-3B-10-15-C001, Rev 0

Page 89 of 91

AVR TECHNICAL DATA SHEET

PH7-3B-10-15-C001, Rev 0

Page 90 of 91

TECHNICAL PARTICULARS - LSOH POWER CABLES


Sr DATA REQUIRED 4CX4 1 LV POWER CABLES 1.1 Manufacturer 1.2 Cable type 1.3 Standards 1.4 Rated Voltage V 1.5 Test Voltage (1 min) VAC/min 1.6 Conductor 1) Cross sectional area (Nominal) mm 2) Material Copper 3) Design (Stranded, sectoral ect) 4) Overall diameter (Approx) mm 5) No. of cores 1.7 Insulation 1.8 Fillers Material - Polypropylene 1.9 Armour bedding Type Nominal Thickness mm 1.10 Armour Type of wire Number of wires No. Diameter of wires - Nominal mm * Wire size higher than specified in BS 6724 1.11 Outer covering Material Nominal Thickness mm Min. thickness mm 1.12 Completed cable Overall diameter - Approx mm Weight per meter - Approx kg Maximum drum length m 1.13 Cable drums Overall diameter - Approx m Width - Approx m Weight loaded - Approx kg 1.14 Continuous current carrying capacity based on the conditions Laid in the ground (Touching each other) a) One circuit A b) Two circuits A c) Three circuits A Drawn in to ducts a) One circuit A b) Two circuits A c) Three circuits A In air One circuit at 50 C A 1.15 Max conductor temp C 1.16 Conductor short circuit current carrying capacity for 1 sec. Cable loded as above prior to kA short ckt & final conductor temp of C 1.17 Min radius of bend around which cable can be laid a) Laid direct m b) In ducts m c) In air m 1.18 Ducts Nominal internal diameter of pipes or mm ducts through which cable can be pulled 1.19 Maximum dc resistance per km of cable at 20 C of conductor ohm/Km 1.20 Maximum ac resistance of conductor per km of cable at max. ohm/Km conductor temp - 90 C 1.21 insulation resistance per km of cable per core Mohm 1.22 Manufacturer quality assurance according to ISO 9000, 9001, 9003 & 9004 1.23 Type test certificate to be issued by independent laboratory OMAN CABLES Cu/XLP/SWA/LSOH Cu/XLP/SWA/LSOH BS 6724 600/1000 4000/min 600/1000 4000 4 6 10 16 25 50 120 150 240 120 95 Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper t a Standed/Circular anded/Circuanded/Circuranded/Sectranded/Sectranded/Sectranded/Sectranded/Sect nded/Circuanded/Circuanded/Circu 2.52 3.12 4.02 N.A. N.A. N.A. N.A. N.A. 18.4 13 11.4 4 4 4 4 4 4 4 4 1 1 1 XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE Polypropylene fillers - Wherever necessary Polymeric LSOH 1 1 1.4 Cu Stranded XLPE 0.8 Galvanized Steel Wire Armour 35 37 36 1.25 1.25 1.6 44 1.6 LSOH Type LTS-1 LSOH Type LTS-1 1.7 1.9 1.16 1.32 26.1 1850 1000 1200 1040 1345 1400 1040 2030 32.0 2860 1000 1600 1070 3150 0.8 0.8 0.8 1.4 1 1 AWA 31 1.6* 44 2.5 48 2.5 44 1.6 0.8 27 1.25* LSOH 1.4 0.92 16.4 600 1000 1000 710 690 1200 740 880 1200 1040 1110 18.7 750 1000 21.1 960 1000 21.3 1195 1000 1.5 1.00 1.5 1.00 1.6 1.08 30 1.25 28 1.6* 2.3 1.64 47.1 6900 500 1800 1130 3710 2.4 1.72 51.4 8190 500 2000 1135 4395 1.8 1.24 32.8 2740 1000 1600 1070 3030 1.6 1.08 32.8 1460 1000 1800 1130 1720 1.6 1.08 22.3 1210 1000 1200 1040 1360 47 38.07 32.90 39 31.20 27.30 37 90 59 47.79 41.30 48 38.40 33.60 46 90 79 63.99 55.30 65 52.00 45.50 64 90 102 82.62 71.40 83 66.40 58.10 83 90 131 106.11 91.70 107 85.60 74.90 109 90 187 151.47 130.90 152 121.60 106.40 163 90 312 252.72 218.40 258 206.40 180.60 293 90 349 282.69 244.30 291 232.80 203.70 335 90 480 388.80 336.00 421 336.80 294.70 510 90 332 268.92 232.40 315 252.00 220.50 328 90 292 236.52 204.40 281 224.80 196.70 282 90 90 0.57 250 0.86 250 1.43 250 2.29 250 3.58 250 7.15 250 17.16 250 21.45 250 34.32 250 17.16 250 13.59 250 6 x OD 6 x OD 6 x OD 100 6 x OD 6 x OD 6 x OD 100 6 x OD 6 x OD 6 x OD 100 8 x OD 8 x OD 8 x OD 100 8 x OD 8 x OD 8 x OD 100 8 x OD 8 x OD 8 x OD 100 8 x OD 8 x OD 8 x OD 100 8 x OD 8 x OD 8 x OD 100 6 x OD 6 x OD 6 x OD 100 6 x OD 6 x OD 6 x OD 100 6 x OD 6 x OD 6 x OD 100 4.61 5.88 3.08 3.93 1.83 2.33 1.15 1.47 0.727 0.927 0.387 0.494 0.153 0.197 0.124 0.16 0.0754 0.0968 0.153 0.197 0.193 0.247 Will be calculated form the insulation resistance constant at 90 C I.e. 3.67 megaohm.km COMPLY COMPLY 4CX6 4CX10 4CX16 OFFERED 4CX25 4CX50 4CX120 4CX150 1CX240 1CX120 1CX95 2CX4 OCI Cu/XLP/SWA/LSOH BS 6724 600/1000 3500 (5 min) 4 Copper Standed/Circular 2.52 2 XLPE 2CX10 2CX6 2CX16 2CX25 LV CABLES UNIT

DATA OFFERED 2CX35 3CX4

3CX6

3CX10

3CX16

3CX35

5CX10

5CX6

10 6 16 25 35 4 6 10 16 35 10 6 Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper Copper anded/Circuanded/Circuanded/Circuranded/Sectranded/Secanded/Circuanded/Circuanded/Circuanded/Circu t t tranded/Sect nded/Circuanded/Circular a 4.02 3.12 4.8 N.A. N.A. 2.52 3.12 4.02 4.8 N.A. 4.02 3.12 2 2 2 2 2 3 3 3 3 3 5 5 XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE XLPE

Polypropylene fillers - Wherever necessary

0.8

0.8

0.8

0.8

0.8

Polymeric LSOH 0.8

0.8

0.8

0.8

0.8

0.8

23 1.25*

29 1.25*

25 1.25*

33 1.25

32 1.25

Galvanised Steel Wire 30 22 24 1.6 1.25* 1.25*

32 1.25

36 1.25

34 1.6

39 1.25

33 1.25

1.4 0.92 14.7 460 1000 1000 700 560

1.5 1.00 18 715 1000 1200 740 845

1.4 0.92 15.9 550 1000 1000 700 650

1.5 1.00 20.4 905 1000 1200 1040 1055

1.6 1.08 20.4 985 1000 1200 1040 1135

LSOH Type LTS1 LSOH Type LTS 1 1.7 1.4 1.16 0.92

1.4 0.92

1.5 1.00

1.6 1.08

1.8 1.24

1.6 1.08

1.5 1.00

23.3 1395 1000

15.3 515 1000

16.6 625 1000

19.5 840 1000

21.6 1025 1000

25.7 1830 1000

22.9 1130 1000

20 860 1000

1200 1040 1545

1000 710 615

1000 710 725

1200 740 970

1200 1040 1175

1400 1040 2010

1200 1040 1280

1200 1040 1010

56 45.36 39.20 46 36.80 32.20 43 90

94 76.14 65.80 77 61.60 53.90 74 90

70 56.70 49.00 58 46.40 40.60 55 90

121 98.01 84.70 99 79.20 69.30 98 90

157 127.17 109.90 127 101.60 88.90 128 90

188 152.28 131.60

47 38.07 32.90

59 47.79 41.30

79 63.99 55.30

102 82.62 71.40

157 127.17 109.90

79 63.99 55.30

59 47.79 41.30

153 122.40 107.10 158 90

39 31.20 27.30

48 38.40 33.60

65 52.00 45.50

83 66.40 58.10

128 102.40 89.60

65 52.00 45.50

48 38.40 33.60

37 90

46 90

64 90

83 90

134 90

64 90

46 90

6 x OD 6 x OD 6 x OD 100

6 x OD 6 x OD 6 x OD 100

6 x OD 6 x OD 6 x OD 100

6 x OD 6 x OD 6 x OD 100

8 x OD 8 x OD 8 x OD 100

8 x OD 8 x OD 8 x OD 100

6 x OD 6 x OD 6 x OD

6 x OD 6 x OD 6 x OD

6 x OD 6 x OD 6 x OD

6 x OD 6 x OD 6 x OD

8 x OD 8 x OD 8 x OD

6 x OD 6 x OD 6 x OD

6 x OD 6 x OD 6 x OD

100

100

100

100

100

100

100

4.61 5.88

1.83 2.33

3.08 3.93

1.15 1.47

0.727 0.927

0.524

4.61

3.08

1.83

1.15

0.524

1.83

3.08

0.668

5.88

3.93

2.33

1.47

0.668

2.33

3.93

Will be calculated form the insulation resistance constant at 90 C I.e. 3.67 megaohm.km COMPLY

COMPLY

PH7-3B-10-15-C001, Rev 0

0.57 250

1.43 250

0.86 250

2.29 250

3.58 250

5.01 250

0.57 250

0.86 250

1.43 250

2.29 250

5.01 250

1.43 250

0.86 250

Page 91 of 91