Sunteți pe pagina 1din 58

d h

domnick hunter
Breathing Air Purification Modules

Installation, Operating & Maintenance Instructions

ARRANGEMENT DRAWINGS
Section 1. BAM102 - BAM110 2. BA-DME012 to BA-DME030 3. BA-DME040 4. BA-DME050 to BA-DME060 5. BA-DME080 Page 4 6 7 8 9

MAXI DRYER
Section 1. General Description 2. Technical Specification 3. Operation of DDS Controller 4. DDS Heatless Control Schematic (See Figs.) 5. Installation 6. Maintenance 7. Known Misuse 8. Fault Finding 9. Warranty Page 12 12 13 14 17 17 18 18 19

MIDI DRYER
Section Safety Warning 1. General Description 2. Technical Specification 3. Unpacking 4. Installation 5. Electrical Details 6. Operation 7. Maintenance 8. Fault Diagnosis 9. Known Misuse 10. Declaration 11. Warranty
1

Page 21 21 22 23 23 26 27 28 29 29 30 31

PURIFIERS BAH101
Section 1. Installation 2. Service Life 3. Maintenance Page 33 35 35

PURIFIERS BAH102 - BAH106


Section 1. Installation 2. Service Life 3. Maintenance Page 37 39 39

OIL - X FILTERS
Section 1. Declaration 2. Technical Specification 3. Installation 4. Maintenance 5. Element Replacement 6. Differential Pressure Gauge 7. Accessories 8. Declaration of Conformity Page 41 41 42 43 44 46 47 48

CARBON MONOXIDE MONITOR


Section 1. General Description 2. Operation 3. Maintenance Internal and external wiring looms V4 Page 51 51 53 55

Breathing Air (Maxi) Purification Modules General Notes


Flow Rate @ 7 barg 160 to 800 scfm Max.Operating Pressure 13 barg Min.Operating Pressure 4 barg Max. Inlet Temperature 50C Min. Outlet Temperature 5C Power Supply 230V. 110V. or Pneumatic

Breathing Air Maxi Modules 110V

Breathing Air Maxi Modules 240V

Breathing Air Maxi Modules Pneumatic

BAM102 - BAM110
4

Technical Specification General Notes


Flow Rates @ 7bar g - 24 to 176 cfm Max. Working Pressure BA-DME012-D to BA-DME040-D - 16 bar g Max. Working Pressure BA-DME050-D to BA-DME080-D- 13 bar g Min. Operating Pressure 4 bar g Recommended Max. Inlet Temperature 30C Absolute Max. Inlet Temperature 50C Absolute Min. Inlet Temperature 5C Dewpoint -40C

Breathing Air Midi Purification Modules Type DDS 230V / 1PH / 50-60Hz
MODEL COMP.REF. DIM A 1045 1211 1376 1541 1707 1960 1750 1916 2076 DIM B 476 490 490 490 521 732 1275 1275 1200 FLOW @7bar 24 32 42 53 65 88 106 130 176 MAX.INLET TEMPC 50 50 50 50 50 50 50 50 50 WEIGHT Kg 37.6 42.6 47.6 52.6 57.6 73.9 211.0 223.8 224 INLET OUTLET BSP BSP 1/2 1/2 1/2 1/2 1/2 3/4 1 1 1 3/8 3/4 3/4 3/3 3/4 3/4 1 1 1 OUTLET FILTER 0013G 0040G 0040G 0040G 0040G 2X0040G BAH101 BAH101 BA102 INLET FILTER 0013G 0025G 0025G 0025G 0040G 0040G 0080G 0080G 0080G

BA-DME012 BA-DME015 BA-DME020 BA-DME025 BA-DME030 BA-DME040 BA-DME050 BA-DME060 BA-DME080

606033110 606033120 606033130 606033140 606033150 606033160 606033170 606033180 606033190

Breathing Air Midi Purification Modules Type 230V / 1PH / 50-60Hz


MODEL COMP.REF. DIM A 1045 1211 1376 1541 1707 1960 1750 1916 2076 DIM B 476 490 490 490 521 732 1275 1275 1200 FLOW @7bar 24 32 42 53 65 88 106 130 176 MAX.INLET TEMPC 50 50 50 50 50 50 50 50 50 WEIGHT Kg 37.6 42.6 47.6 52.6 57.6 73.9 211.0 223.8 224 INLET OUTLET BSP BSP 1/2 1/2 1/2 1/2 1/2 3/4 1 1 1 3/8 3/4 3/4 3/3 3/4 3/4 1 1 1 OUTLET FILTER 0013G 0040G 0040G 0040G 0040G 2X0040G BAH101 BAH101 BA102 INLET FILTER 0013G 0025G 0025G 0025G 0040G 0040G 0080G 0080G 0080G

BA-DME012 BA-DME015 BA-DME020 BA-DME025 BA-DME030 BA-DME040 BA-DME050 BA-DME060 BA-DME080

606033210 606033220 606033230 606033240 606033250 606033260 606033270 606033280 606033290

Breathing Air Midi Purification Modules Type 110V / 1PH / 50-60Hz


MODEL COMP.REF. DIM A 1045 1211 1376 1541 1707 1960 1750 1916 2076 DIM B 476 490 490 490 521 732 1275 1275 1200 FLOW @7bar 24 32 42 53 65 88 106 130 176 MAX.INLET TEMPC 50 50 50 50 50 50 50 50 50 WEIGHT Kg 37.6 42.6 47.6 52.6 57.6 73.9 211.0 223.8 224 INLET OUTLET BSP BSP 1/2 1/2 1/2 1/2 1/2 3/4 1 1 1 3/8 3/4 3/4 3/3 3/4 3/4 1 1 1 OUTLET FILTER 0013G 0040G 0040G 0040G 0040G 2X0040G BAH101 BAH101 BA102 INLET FILTER 0013G 0025G 0025G 0025G 0040G 0040G 0080G 0080G 0080G

BA-DME012 BA-DME015 BA-DME020 BA-DME025 BA-DME030 BA-DME040 BA-DME050 BA-DME060 BA-DME080

606033310 606033320 606033330 606033340 606033350 606033360 606033370 606033380 606033390

BA-DME012 to BA-DME030

BA-DME040

BA-DME040 to BA-DME060

BA-DME080

d h

domnick hunter
DESICCANT AIR DRYER HEATLESS
Dewpoint Dependant Switching

Installation Operating & Maintenance Instructions

SAFETY WARNING!
Do not operate the dryer until the instructions in the operation section of this manual have been read and understood by all personnel concerned. It is essential that personnel employ safe working practices and observe all related regulations and legal requirements for safety when operating the dryer. When handling, operating or carrying out maintenance on the dryer, personnel must employ safe engineering practices and observe all relevant local health and safety requirements and regulations. The attention of UK users is drawn to the Health and Safety at Work Act 1974, and the Institute of Electrical Engineers Regulations. Most accidents which occur during the operation and maintenance of machinery are the result of failure to observe basic safety rules or precautions. An accident can often be avoided by recognising a situation that is potentially hazardous. Improper operation or maintenance of the dryer could be dangerous and result in an accident causing injury or even death. domnick hunter can not anticipate every possible circumstance which may represent a potential hazard. The WARNINGS in this manual cover the most common potential hazards and are therefore not all-inclusive. If the user employs an operating procedure, an item of equipment or a method of working which is not specifically recommended by domnick hunter he must ensure that the dryer will not be damaged or made unsafe and that there is no risk to persons or property.

IMPORTANT
Safety Signs Operations or procedures involving specific hazards which could cause injury or death if precautions are not heeded, are identified by the following symbols which are displayed on the desiccant air dryer to indicate potential danger points.

WARNING: RISK OF DANGER

CAUTION: RISK OF ELECTRIC SHOCK

CAUTION: RISK OF HIGH PRESSURE

IT IS STRONGLY RECOMMENDED THAT THE INSTALLATION AND OPERATING INSTRUCTIONS ARE READ THOROUGHLY BEFORE PROCEEDING ANY FURTHER. PLEASE NOTE: YOUR WARRANTY MAY BE INVALIDATED IF THE EQUIPMENT HAS NOT BEEN INSTALLED, COMMISSIONED OR MAINTAINED BY domnick hunter OR ITS APPROVED AGENTS.

11

1. GENERAL DESCRIPTION
The adsorptive capacity of the desiccant within the dryer is essentially constant whereas the moisture loading and the air flow through the dryer are continuously varying. In order to maintain the specified air quality downstream of the dryer, it has to be sized for the worst case conditions, namely lowest pressure, highest flow and highest inlet temperature. These conditions may only occur for a small part of the service life of the dryer, for example, the highest inlet temperatures may only be present during the summer months. This means that the moisture loading on the desiccant beds is below the dryers capacity for much of its service life e.g. quiet periods in between shifts usually have lower air supply requirements. To gain access to this adsorptive capacity, a moisture sensor is fitted which monitors the downstream dewpoint, this system is known as Dewpoint Dependent Switching (DDS). This interrupts the normal sequence of the controller which then instructs the dryer to change over only when the desiccant has adsorbed moisture to its capacity. This effectively elongates the drying cycle. However, as regeneration has been optimised for a fully laden desiccant bed, this remains of constant duration resulting in a period of zero energy consumption; purging is discontinued. In this way energy savings are obtained when compared to the operation of a fixed cycle, without sacrificing the resulting air quality. Dewpoint Dependent Switching (DDS) is available in two variants, with or without dewpoint monitoring display. This manual describes the operation of and equipment used in the DDS system only, and should be used in conjunction with the standard PNEUDRI I.O.M.I.

2. TECHNICAL SPECIFICATION
MODEL Code Suffix Pressure Dewpoint Controls WITH DEWPOINT DISPLAY DS -40C Cam Timer fitted with full Hygrometer 240V 1ph 50Hz 110V 1ph 60Hz Digital LCD 4 to 20 mA linear (Max Load 800) 0 to 1V linear Alarm Output Volt free contact; rated 2A 240 Vac or 30 Vdc Power On Dewpoint Switching Active Dewpoint Alarm Volt free contact; rated 2A 240 Vac or 30 Vdc Power On Dewpoint Switching Active Dewpoint Alarm WITHOUT DEWPOINT DISPLAY DS-ND -40C Cam Timer fitted with PCB

Electrical Supply

240V 1ph 50Hz 110V 1ph 60Hz None 1 to 6V non-linear

Dewpoint Display Analogue Output

Indicators

12

3. OPERATION OF DDS CONTROLLER


1. INTRODUCTION The Dewpoint Switching Systems with and without dewpoint display options incorporate two relays designated Alarm 1 and Alarm 2. These relays are preset by domnick hunter and are configured such that Alarm 1 controls the dewpoint switching function and Alarm 2 operates the fault and remote alarm functions. Alarm 1 is configured HI normally closed, and Alarm 2 is configured HI normally closed. The HI function causes an alarm signal to be generated when a high moisture content (i.e. wet dewpoint) is encountered. 2. OPERATION OF DEWPOINT DEPENDENT SWITCHING References should be made to Figure 1 (PCB option without dewpoint display) and Figure 2 (Hygrometer Display). Alarm 1 on both options controls the activation of the Dewpoint Dependent Switching. When the dryer outlet dewpoint is wetter than the set point for Alarm 1, an alarm signal is generated. Consequently the normally closed contact of the Alarm 1 relay opens and the cam timer relay coil is de-energised, the normally closed contact of the cam timer relay remains closed and the cam timer operates. Conversely, when the outlet dewpoint of the dryer becomes drier than the set point for Alarm 1, an alarm signal is not generated, and the normally closed Alarm 1 relay contact closes. The cam timer coil becomes energised causing the normally closed contact of the cam timer relay to open, thereby stopping the cam timer and producing a period of zero energy consumption. This will only occur when the offline bed has been fully regenerated and repressurised. 3. OPERATION OF ALARM (FAULT) FUNCTION Alarm 2 on both options controls the activation of the fault alarm function. When the dryer outlet dewpoint is wetter than the set point for Alarm 2 an alarm signal is generated which opens the normally closed contact of the Alarm 2 relay. This causes the fault alarm relay coil to become de-energised, the normally closed contact of the fault alarm relay closes and the alarm lamp illuminates. Conversely, when the outlet dewpoint of the dryer becomes drier than the set point for Alarm 2 an alarm signal is not generated. Consequently the normally closed contact of the Alarm 2 relay remains closed and the fault alarm relay coil becomes energised. The normally closed contact of the fault alarm relay opens, and the alarm lamp does not become illuminated. 4. FAILURE MODES Should a fault develop on the system the normally closed contacts on the cam timer relay and fault alarm relay close, thereby allowing continued operation of the cam timer and illuminating the alarm lamp. In addition a pair of volt free contacts are provided which open on alarm, these may be used to provide remote indication that a fault has occurred. In the event of a power failure (i.e. transformer fault or blown fuse) the normally closed contacts of the fault alarm relay will close thereby activating a remote alarm. The remote alarm contacts are rated at 240Vac and any external equipment or remote indicators should not exceed this level. 5. INDICATION OF DRYER DEWPOINT A voltage output (1-6V) corresponding to the dewpoint being monitored by the hygrometer sensor may be taken from the PCB on the non-display option and this may be used to indicate the dryer dewpoint. However this output is non-linear and direct conversion to a dewpoint value requires the linearisation data for the sensor version used (available on request). If the full display hygrometer is fitted, a linear 4 to 20 mA (max load 800) and linear 0 to 1V analogue outputs are available.

13

4. DDS HEATLESS CONTROL SCHEMATIC

FIG. 1 PCB Option Without Dewpoint Display


14

FIG. 2 Hygrometer Display


15

FIG. 3 Pneumatic Schematic


16

5. INSTALLATION

Rear View of Control Box 1) Hygrometer Power Connection (Display Variant) Hygrometer Sensor (PCB Variant) 4) 7) Indicator Lights Hygrometer Alarm Cable (with display option only) 5) Solenoid Side A 6) Solenoid Side B 2) Power Connection 3) Remote Alarm (where fitted)

A) Constant Pressure

B) Column Pressure Side A

C) Column Pressure Side B 5.1 REMOTE OUTPUTS Two remote outputs are available. The first is a remote alarm which provides fault indication via the volt free contacts (and the normally open contact on the fault alarm relay). The second is an analogue voltage output which may be taken from the hygrometer display or PCB board on the non-display option to remotely indicate the dryer dewpoint.

6. MAINTENANCE
The controller is designed to be maintenance free, however, if required, periodic replacement of the AA0003G filter element upstream of the sensor may be undertaken, in addition to annual recalibration of the hygrometer sensor. If any other maintenance or repair work is deemed to be required, please contact domnick hunter, or a domnick hunter approved distributor.

17

7. KNOWN MISUSE
(Please ensure that the following situations do not occur in your installation) * * * * * * Tampering with the controller. Disconnection of hygrometer sensor. Kinking of pneumatic tubing Tampering with hygrometer settings. Operation of dryer whilst the ON/OFF switch is in the OFF position. Power not connected to the controller

8. FAULT FINDING
VISUAL INDICATION Cam timer not running PROBABLE CAUSE Power failure CHECK Is power lamp on? Incoming supply present? Fuses intact? Is dewpoint dryer than set point for Alarm 1? Use service engineers sensor simulator to simulate wet dewpoint REMEDY Check for incoming supply, replace fuses if blown If Dewpoint drier than set point then DDS is functioning correctly. If not call service engineer Call Call Call Call service service service service engineer engineer engineer engineer

Dryer in DDS mode

Warning lamp illuminated

Power on lamp not illuminating

Controller fault Cam timer fault Hygrometer sensor fault Dewpoint wetter than set point for Alarm 2 Controller fault Hygrometer settings incorrect Blown bulb No incoming power

Use service engineers sensor simulator to simulate dry dewpoint

Bulb intact? Incoming supply present? Fuses intact? Simulate dry dewpoint using service engineers sensor simulator Kinking of pneumatic tubing, air leakage Bulb intact? Is dewpoint wetter than set point for Alarm 1 (use service engineers sensor simulator) As above Simulate wet dewpoint using service engineers sensor simulator

Dewpoint Switching inoperative

Dewpoint wetter than set point for Alarm 1 Controller fault Loss of pneumatic signals to controller Bulb blown Dryer not in Dewpoint Switching mode Dewpoint Switching Inoperative Dewpoint dryer than DDS setpoint Sensor fault (open circuit) Controller fault Dewpoint dryer than -80C Sensor fault (open circuit) Controller fault Dewpoint wetter than set point for Alarm 1 Alarm fault active Controller fault Loss of pneumatic signal to controller

Call service engineer Call service engineer Replace if necessary Replace fuses if blown If fault persists call service engineer Call service engineer

Energy saving lamp not illuminating

Call service engineer Rectify kinking of tube if possible, otherwise call service engineer Replace if necessary Call service engineer

Dryer always in Dewpoint Switching mode

Call service engineer Call service engineer

Hygrometer display permanently indicates -80 Dryer never in Dewpoint Dependent Switching mode

Simulate wet dewpoint using service engineers sensor simulator Use service engineers sensor simulator to simulate dry dewpoint Is Dewpoint wetter than set point for Alarm 2 Kinking or leaks from pneumatic tubing

Call Call Call Call Call Call

service service service service service service

engineer engineer engineer engineer engineer engineer

If not, call service engineer Call service engineer Rectify kinking or leaks from tube if possible, otherwise call service engineer

18

9. WARRANTY
This warranty applies to dryers and associated pre-filters (the Equipment) manufactured and supplied by domnick hunter. Use of the dryer without the recommended genuine domnick hunter manufactured filtration or genuine parts, will expressly invalidate the warranty. Should the Equipment by defective as to materials or workmanship, domnick hunter warrants that it will remedy such defect for a period of 12 months from the date of despatch. Where the Equipment is a desiccant dryer, the warranty period will be 12 months from the date of commissioning or 18 months from date of despatch, whichever is the earlier, provided such commissioning is carried out by domnick hunter or its authorised agent. In the case of Equipment other than a desiccant dryer, the warranty period shall commence from the date of despatch. Should any defect occur during the warranty period and be notified in writing to domnick hunter or its authorised agent within the said period, domnick hunter will, at its sole option, remedy such defects by repair or by provision of a replacement part, provided that the Equipment has been used strictly in accordance with the instructions provided with each item of the Equipment and has been stored, installed, commissioned, operated and maintained in accordance with such instruction and good practice. domnick hunter shall not be under any liability whatsoever under the warranty if, before giving notification in writing to domnick hunter as aforesaid, the Customer or any third party meddles, interferes, tampers with or carries out any work whatsoever (apart from normal maintenance as specified in the said instructions) in relation to the Equipment or any part thereof. Any accessories, parts and equipment supplied by domnick hunter but not manufactured by domnick hunter, shall carry whatever warranty the manufacturer has given domnick hunter provided it is possible for domnick hunter to pass on such warranty to the Customer. To claim under the warranty, the goods must have been installed and continuously maintained in the manner specified in the Installation, Operating and Maintenance Instruction (I.O.M.I.). Our Product Support Engineers are qualified and equipped to assist you in this respect. They are also available to make repairs that may become necessary in which event they will require an official order before carrying out the work. If such work is to be the subject of warranty claim, the order should be endorsed for consideration under warranty. Any substitution of parts not manufactured or approved by domnick hunter will expressly invalidate the warranty.

19

d h

domnick hunter

MIDI

PLUS

HIGH EFFICIENCY COMPRESSED AIR DRYERS

USER GUIDE

SAFETY WARNING!
Do not operate the dryer until the instructions in this manual have been read and understood by all personnel concerned. When handling, installing or operating, personnel must employ safe engineering practices and observe all related regulations, health and safety procedures, and legal requirements for safety. Most accidents that occur during the operation and maintenance of machinery are the result of failure to observe basic safety rules and procedures. Accidents can be avoided by recognising that any machinery is potentially hazardous. domnick hunter can not anticipate every possible circumstance which may represent a potential hazard. The WARNINGS in this manual cover the most known potential hazards, but by definition cannot be all inclusive. If the dryer user employs an operating procedure, item of equipment or a method of working which is not specifically recommended by domnick hunter the user must ensure that the dryer will not be damaged or made a potential hazard to persons or property. IMPORTANT DME Facia

Caution: Power Risk of Electric Shock

Power on LED

Attention
ECO (DDS) LED

PLEASE NOTE THAT YOUR WARRANTY MAY BE INVALIDATED IF THE EQUIPMENT HAS NOT BEEN INSTALLED, COMMISSIONED OR MAINTAINED BY domnick hunter OR A domnick hunter APPROVED AGENT.

1. GENERAL DESCRIPTION
The MIDI PLUS range of compressed air dryers are designed to remove moisture from compressed air by utilising state of the art technology to obtain dewpoints of -40 oC, and by appropriate de-rating, -70oC. The MIDI PLUS range of dryers have been designed to require minimal maintenance and can be installed virtually anywhere. The MIDI PLUS dryer consists of an inlet and an outlet manifold joined together with an aluminium column. The column has twin internal chambers both filled with desiccant material. During operation one chamber is on-line (drying) while the other is regenerating, using the Pressure Swing Adsorption (PSA) process. Pressure Swing Adsorption (PSA) A small percentage of dried air is taken from the dryer output flow and is used to regenerate the saturated chamber by expanding the dried air from line pressure to atmospheric pressure. During this process, the moisture is physically removed from the regenerating chamber and vented to atmosphere through the exhaust silencers. Dewpoint Dependent Switching (DDS) - Optional If DDS is fitted, this will adjust the dryers cycle in line with the moisture loading placed upon it, by constantly monitoring the processed air moisture content. Also available as a retrofit to all DME dryer models.
21

KEY
1 2 3 4 5 6 7 8 9 10 By-pass Valve Inlet Valve Inlet Filter By-pass Line Outlet Valve Outlet Filter Outlet Sight Glass Pressure Gauges Control Box Feed Line (Optional with Dewpoint Dependent Switching)
1

5 6

OUT

IN

10

2. TECHNICAL SPECIFICATION
Type Model Operating flow range Dewpoint: Air quality : inc filtration (dirt. water. oil) Maximum operating pressure Minimum operating pressure Maximum inlet temperature Minimum inlet temperature Regeneration Nominal pressure drop across desiccant bed Standard electrical supply ( 10% ) (Others on request) Controls Noise level Media Material Column Inlet/Outlet head Finish Construction Heatless DME 14 cfm - 299 cfm ( 0.4m3/min - 8.47 m3/min ) Nominal -40oC (-40oF) Optional -70oC (-94oF) SO 8573.1 Class 1.2.1. Class 1.1.1 Optional DME012 to DME040 16 Bar(g) (232 psig) DME050 to DME080 13 Bar(g) (188 psig) 4 Bar(g) (58 psig) 50oC (122oF) 5oC ( 41oF) Pressure Swing Adsorption (PSA) 140 mBar (g) (2 psi g) 230 VAC . 1phase. 50/60 Hz 110 VAC . 1phase. 50/60 Hz Electronic Control Timer <75 dB (A) Desiccant High tensile extruded aluminium. Pressure die cast high tensile aluminium. Alocrom anti-corrosion protection and dry powder epoxy painted. Column snow storm filled with desiccant material and contained between the inlet and outlet head using high tensile bolts.
22

3. UNPACKING
Every care is taken during product packaging by domnick hunter. It is advisable after carefully unpacking the dryer to carry out a thorough visual inspection of the unit for any signs of transit damage incurred after leaving our factory. If any damage is found please report this immediately to the carrier and the distributor involved (if applicable), or directly to domnick hunter ltd.

4. INSTALLATION (Refer to figure 1)


1. General Care must be taken to ensure that the dryer is not subject to flows (even peaks) in excess of the dryers rated capacity. The dryer must be vertical, and level, with the inlet at the bottom. Position the dryer to allow safe maintenance and operation. The dryer can be free standing or secured to the floor via the fastener points provided in the base. The purge air flow is factory set for 6 Bar g (87 psi g) minimum system pressure. Should your minimum pressure be lower, the purge air flow must be reset by trained domnick hunter personnel to maintain specified dewpoint. Suitably rated pipework and connections must be used during installation. All pipework must be secure and safely positioned. If required the exhaust assembly can be piped away, remote from the dryer. DME012 to DME040 range Two inlet port connections are available. Only remove the fitted sight glass from the port chosen as the inlet to the dryer. Two outlet port connections are available. Only remove the fitted sight glass from the port chosen as the outlet side from the dryer. Note: The remaining sight glass will adsorb moisture from the atmosphere and require replacing if the outlet head is not piped up immediately. DME050 to DME080 range One port is available for the inlet to the dryer. One port is available for the outlet from the dryer only. Remove the fitted plug. Note: The sight glass will adsorb moisture from the atmosphere and require replacing if the outlet head is not piped up immediately. Dewpoint Dependent Switching (DDS) - Optional The DDS system requires a sampling point to be inserted in the pipework at the outlet of the dryer, downstream of the after-filter but before the isolation valve. P.T.F.E. tubing must be used to link the sampling point to the 4mm push-in connector of the DDS system on the dryer. 2. Filtration domnick hunter inlet and outlet filtration must be fitted to the dryer, e.g. WS (optional), AO (recommended), an AA grade pre-filter and an AR grade after-filter are essential. All filtration must be installed using the practices described in the User Guide supplied with the filters.
23

24

25

3. By-pass line It is recommended that a by-pass line is installed to ensure a constant air supply, and safety, during maintenance. This allows untreated air to by-pass the dryer, at the customers discretion during dryer maintenance. The by-pass valve should only be open when the dryer is undergoing maintenance following the shut down procedure. 4. Valves Isolation valves are recommended on the inlet, outlet and by-pass lines.

5.ELECTRICAL DETAILS
This only applies to electrically powered units. Competent qualified electricians must work on dryer supply circuitry. Check the rating plate for power supply requirements. Correct isolator switches must be provided at a safe and accessible point near to the dryer. The dryer must be connected with a live, neutral and earth. The live pin on the dryer has a fuse fitted. Connect power to the dryer via an IEC320 socket cord set, and retain with clip.

L
AC MODELS

FUSE BAY

26

6. OPERATING THE DME DESICCANT AIR DRYER


Start up procedure Ensure the dryer inlet and outlet isolation valves are fully closed and that all covers on the dryer are secure. Ensure that a suitable supply of compressed air to within the dryers technical specifications is available. Turn ON external electrical isolator, the yellow power on LED should illuminate and the dryer should commence cycling. NB - all valves must be opened and closed gradually Proceed as follows Using by-pass line With the by-pass valve fully open, introduce air into the dryer by opening the inlet valve until fully open. Allow the dryer to fully pressurise to full system pressure, then open the outlet valve while simultaneously closing the by-pass valve. The dryer is now on stream. Without by-pass line Introduce air into the dryer by opening the inlet valve until fully open. Allow dryer to fully pressurise to full system pressure, then open the outlet valve. The dryer is now on stream. During operation During normal operating conditions the dryer is fully automatic and requires no further attention until shutdown. The yellow power on LED should be ON continuously. The dryer column contains two chambers of desiccant material. Whilst one chamber is drying the compressed air (adsorption) the other chamber is simultaneously undergoing regeneration (desorption). Every two minutes the chambers are reversed in function, this is the changeover point. Changeover is characterised by a immediate venting of compressed air from the chamber entering regeneration. The adsorption chamber is indicated by the relevant pressure gauge on the dryer reading full system air pressure. The desorption chamber is indicated by the relevant pressure gauge on the dryer reading virtually zero. After 1 1/2 minutes the desorption chamber repressurises to equal the adsorption chamber pressure, ready for changeover of the chambers. The pressure gauges and sight glass moisture indicator are for indication purposes only. Dewpoint Dependent Switching (DDS) - optional The DDS system operates as described above, with the following modifications. If the dryer is producing air at a better dewpoint than specified the DDS system will hold the dryer at a point just before the changeover occurs. The green ECO LED will illuminate. Both pressure gauges will read full system pressure. The dryer will resume normal operation the instant the DDS system monitors a fall in dewpoint to the specified level. The crystals in the outlet sight glass moisture indicator should be blue for correct operation, however, if these change colour to pink the dryer is producing a wetter dewpoint than required, and the cause of this must be investigated (refer to fault diagnosis table). Shut-down procedure The dryer can be shut down at any point in its cycle.

27

Using by-pass line Close the dryer outlet valve whilst simultaneously opening the by-pass valve. Close the dryer inlet valve. The air will now by-pass the dryer, allow the dryer to depressurise before isolating electrical supply, vent pressure from inlet and outlet filters using methods described in the filter User Guide. The dryer may still be pressurised if this is not done. Without by-pass line Close the dryer outlet valve. Close the dryer inlet valve Allow the dryer to depressurise before isolating electrical supply, vent pressure from inlet and outlet filters using methods described in the filter User Guide. The dryer may still be pressurised if this is not done.

7. MAINTENANCE RECOMMENDATIONS
Daily Ensure yellow POWER ON LED is not flashing. Visually check crystals in sight glass moisture indicator for blue colour. Weekly Check dryer seals, fittings and pipe work for air leaks Check inlet and outlet filtration for indication of element blockage (see User Guide for Filters) Ensure correct operation of filtration condensate drainage (if applicable). The desiccant material in the dryer has a finite life dependent upon operating conditions but it will typically exceed 10,000 hours use before it needs replacing. It will also require replacing if contaminated. Care must be taken prior to any routine pipe flushing operations. The outlet sight glass moisture indicator requires replacing once the crystals are no longer blue. A service kit is available. Desiccant changes, service kits and service training courses are available for the MIDI PLUS range of dryers on request. Service kits must only be used by domnick hunter trained personnel. Only domnick hunter trained personnel can remove the covers on the dryer.

28

8. FAULT DIAGNOSIS TABLE


Problem
Poor Dewpoint

Indication
Crystals go pink in outlet moisture indicator

Probable cause
Entrained water

Remedy
Check pre-filtration and pre-filtration drains

Excessive air flow demand

Check actual flow against rated flow of dryer Check for recent additions to air system Check against technical specification

Inlet pressure too low

Excessive inlet air temperature Check against technical specification Insufficient purge air flow Factory set for 6 bar g (87 psig) system pressure. domnick hunter trained personnel to adjust Exhaust silencers blocked Contaminated desiccant Change by domnick hunter trained personnel Eliminate source of contamination. Desiccant change by domnick hunter trained personnel Contact domnick hunter customer services Check and regulate air demand domnick hunter trained personnel to adjust Change by domnick hunter trained personnel Electrical fault Contact domnick hunter customer services Blown fuse in plug Damaged valve Change by competent personnel Change by domnick hunter trained personnel

Electrical fault High differential pressure Failure to purge

Flashing Yellow LED Pressure gauges No depressurisation and poor dewpoint Downstream pressure drops Yellow LED OFF

Hardware fault Excessive outlet flow Purge valve blocked or shut. Exhaust silencers blocked

Outlet air flow stops

Constant depresurisation

Erratic air flow from exhaust

9. KNOWN MISUSE
Filters Lack of filtration. Installation of inlet filters remote from the dryer inlet head, allowing possible condensation to occur between filters and dryer. Blow down valve upstream of filters causing back flow / possible collapse of filter element. Installing filters in wrong flow direction. Opening inlet valve too quickly, causing initial high differential pressure across filter element. Differential pressure gauge/indicator fitted wrong way around giving false differential pressure reading. Combining drain pipes from filters to a single drain valve. Inlet / outlet head Pipe diameter too small. Pipework unsupported. Inlet pipework taken from low point of manifold range, allowing bulk water intrusion into the dryer. Control box/electrics Incorrect wiring configuration by user, or incorrect supply voltage. No neutral or earth wire fitted by user to dryer. Additional Items Use of non recommended componentry. Untrained / unauthorised maintenance or installation personnel used. Subsequent increase in air consumption without relation to dryer flow capacity. Purging of pneumatic system and dryer with cleaning agents that have the potential to damage desiccant material. Covers removed or loose during operation.
29

Declaration of Conformity
DECLARATION OF CONFORMITY 98/37/EC Name of manufacturer or supplier: domnick hunter limited Full postal address including country of origin Dukesway, Team Valley Trading Estate, Gateshead, Tyne & Wear, England, NE11 0PZ Description of product
Adsorption Dryer

GB

Name type or model, batch or serial number


DME012, DME015, DME020, DME025, DME030, DME040, DME050, DME060, DME080.

Standards used, including number, title, issue date and other relative documents
EN292-1 : 1991, EN292-2 : 1991, EN50081-2:1994, EN50081-1:1992 EN50082-1:1998, EN50082-2:1995, EN61010-1:1993

Place of issue:

GATESHEAD, TYNE & WEAR, ENGLAND

Name of authorised representative ERIC W. BLAKIE Position of authorised representative MANAGING DIRECTOR (INDUSTRIAL DIV.) Full postal address if different from manufacturers Declaration I declare that as the authorised representative, the above information in relation to the supply/manufacture of this product, is in conformity with the stated standards and other related documents following the provisions of the 98/37/EC Directive. Signature of authorised representative:

30

11. WARRANTY

This warranty applies to dryers and associated pre-filters (the Equipment) manufactured and supplied by domnick hunter. Use of the dryer without the recommended genuine domnick hunter manufactured filtration or genuine parts, will expressly invalidate the warranty. Should the Equipment by defective as to materials or workmanship, domnick hunter warrants that it will remedy such defect for a period of 12 months from the date of despatch. Where the Equipment is a desiccant dryer, the warranty period will be 12 months from the date of commissioning or 18 months from date of despatch, whichever is the earlier, provided such commissioning is carried out by domnick hunter or its authorised agent. In the case of Equipment other than a desiccant dryer, the warranty period shall commence from the date of despatch. Should any defect occur during the warranty period and be notified in writing to domnick hunter or its authorised agent within the said period, domnick hunter will, at its sole option, remedy such defects by repair or by provision of a replacement part, provided that the Equipment has been used strictly in accordance with the instructions provided with each item of the Equipment and has been stored, installed, commissioned, operated and maintained in accordance with such instruction and good practice. domnick hunter shall not be under any liability whatsoever under the warranty if, before giving notification in writing to domnick hunter as aforesaid, the Customer or any third party meddles, interferes, tampers with or carries out any work whatsoever (apart from normal maintenance as specified in the said instructions) in relation to the Equipment or any part thereof. Any accessories, parts and equipment supplied by domnick hunter but not manufactured by domnick hunter, shall carry whatever warranty the manufacturer has given domnick hunter provided it is possible for domnick hunter to pass on such warranty to the Customer. To claim under the warranty, the goods must have been installed and continuously maintained in the manner specified in the User Guide. Our Product Support Engineers are qualified and equipped to assist you in this respect. They are also available to make repairs that may become necessary in which event they will require an official order before carrying out the work. If such work is to be the subject of warranty claim, the order should be endorsed for consideration under warranty. Any substitution of parts not manufactured or approved by domnick hunter will expressly invalidate the warranty.

31

d h

domnick hunter

CATALYST/ACTIVATED CARBON PURIFIER MODEL BAH101

USER GUIDE

1.

INSTALLATION
HEAD BOLTS

Figure 1

1. The purifier should be securely mounted on a suitable structure, which is free from vibration. It should be secured using the two 12 holes through the centre of the column.

OUTLET HEAD

GASKET PLATE

INLET HEAD

3/4 BSPP FEMALE THREADED CONNECTIONS

Figure 2

2. Filtration a. Pre-filtration This must be positioned as close to the inlet as possible. domnick hunter grade AO and AA filters must be fitted upstream of the inlet to prevent contamination of the activated carbon bed. In case of extreme water contamination, a domnick hunter Water separator should also be incorporated into the system prior (upstream) to the AO filter. b. After-filtration A domnick hunter grade AR filter must be fitted downstream of the purifier to prevent activated carbon dust carryover.
33

C. Filter Sizing It is recommended that each purifier bank has its own filtration. Filter sizes for each purifier are shown in Table 1. 5. Shut-off valves (Figure 2) should be fitted to the inlet and outlet pipework of each purifier to allow isolation for maintenance. 6. By-pass lines should be avoided whenever possible as contamination may leak through valves and by-pass filters. 7. In line valves should be opened slowly to avoid high surge flows. 8. The inlet valve should be carefully opened to pressurise the purifier, then slowly opening the outlet valve will bring the purifier on-line.

Table 1
MODEL Nominal Flow Rate Dim A Pipe NL/s@ 7 scfm @ (see fig.2) conns. bar g 100 psi g mm 61 130 535 3/4 Inlet * Recommended Filtration Outlet ** Dryer BADME050 BADME060 Filter/Dryer Pipe size 1

BAH 101

AO-0080G/G AR-0080G/G AA-0080G/G

* Grade AO - General purpose filter : particle removal down to 1 micron, maximum remaining oil content 0.5 mg/m3 at 210C. Grade AA - High efficiency filter: particle removal down to 0.01 micron, maximum remaining oil content 0.01 mg/m3 at 210C. Note - Fixing kits are available for bolting AO and AA filters together dispensing with unnecessary inter-connecting pipework for 0058G/G and 0145G/G order Fixing Kit FXK3. ** Grade AR - Dust filter: 100% particle removal down to 1 micron, 98% removal at 0.3 micron.

34

2.

SERVICE LIFE

The service life of the purifier is determined by the temperature of the air flowing through it. With mineral type compressor oils the expected service life of the purifier at a line pressure of 7 bar g is: 6000 hours at an air temperature of 300C, and 2000 hours at an air temperature of 450C.

3.

MAINTENANCE

1. Replacing Activated Carbon/Catalyst To replace the activated carbon/catalyst the top head should first be removed by unbolting the head bolts (see Figure 1). The top gasket then removed. The activated carbon/catalyst may now be extracted using an industrial vacuum cleaner (the use of a suitable face mask is recommended during this operation). Replacement activated carbon/catalyst packs are available from domnick hunter (see table 2). The use of a snow storm filling device (see table 2) is essential to achieve maximum packing of new carbon/catalyst. New gasket seals should be fitted. The top head replaced and head bolts tightened in sequential manner to a torque of 25 lb.ft (34Nm). Note - Do not attempt to remove heads or replace activated carbon/catalyst whilst AC purifier is pressurised. Always check that purifier is not pressurised.

Table 2
MODEL BAH 101 Replacement Desiccant Pack RP 101 dh Comp. Gasket No. Seal Kit 605009772 COL. GKT. dh Comp. No. 608202114 Additional Service Tool Snow Storm Filler

Note - If replacing both top and bottom heads please order 2-off of the Gasket Seal Kits.

2. Maintenance Plans domnick hunter offers service plans which are tailored to each customers requirements. Through these plans, the service/maintenance responsibility becomes domnick hunters. For details please contact our Service Department.

35

d h

domnick hunter

CATALYST/ACTIVATED CARBON PURIFIER MODELS BAH102 - BAH106

User Guide

1. INSTALLATION
1. Provision is made for lifting the purifier as a complete unit by two eye bolts located in the top of the unit (see Figure 1). Ensure that the eye bolts are screwed fully home before attempting a lift (each bank of a multibank system should be lifted separately.) 2. The purifier should be securely mounted on a suitably structured, flat and level floor or base which is free from vibration. It may be secured to the base using bolts located through the slots in the mounting feet. 3. A clearance of approximately 2 metres around the purifier and 300mm between banks allow comfortable access for maintenance.
HEAD BOLTS EYE BOLTS

Figure 1

OUTLET FLANGE

COLUMNS

FEMALE THREADED/FLANGED CONNECTIONS

OUTLET MANIFOLD MOUNTING FEET

MANUAL DRAIN VALVE

Figure 2

4. Filtration a. Pre-filtration This must be positioned as close to the inlet as possible. domnick hunter grade AO and AA filters must be fitted upstream of the inlet to prevent contamination of the activated carbon bed. In case of extreme water contamination, a domnick hunter Water separator should also be incorporated into the system prior (upstream) to the AO filter. b. After-filtration A domnick hunter grade AR filter must be fitted downstream of the purifier to prevent activated carbon dust carryover.
37

C. Filter Sizing It is recommended that each purifier bank has its own filtration. Filter sizes for each purifier are shown in Table 1. 5. Shut-off valves (Figure 2) should be fitted to the inlet and outlet pipework of each purifier to allow isolation for maintenance. 6. By-pass lines should be avoided whenever possible as contamination may leak through valves and by-pass filters. 7. In line valves should be opened slowly to avoid high surge flows. 8. The inlet valve should be carefully opened to pressurise the purifier, then slowly opening the outlet valve will bring the purifier on-line.

Table 1
MODEL Nominal Flow Rate Dim A Pipe conns. 2 2 2 2 2 Weight kg 66 90 114 138 162 Recommended Filtration Inlet * AO-0220G/G AA-0220G/G AO-0220G/G AA-0220G/G AO-0405G/G AA-0405G/G AO-0405G/G AA-0405G/G AO-0405G/G AA-0405G/G Outlet ** AR-0220G/G AR-0220G/G AR-0405G/G AR-0405G/G AR-0405G/G Dryer DX104BA DX105 BA DX107 BA DX108 BA DX110 BA Filter/Dryer Pipe size 2 2 2.5 2.5 2.5 NL/s@ 7 scfm @ (see fig.2) bar g 100 psi g mm 132 280 521 198 264 330 396 420 560 700 840 628 734 840 947

BAH 102 BAH 103 BAH 104 BAH 105 BAH 106

Grade AO - General purpose filter : particle removal down to 1 micron, maximum remaining oil content 0.5 mg/m3 at 210C. Grade AA - High efficiency filter: particle removal down to 0.01 micron, maximum remaining oil content 0.01 mg/m3 at 210C. Note - Fixing kits are available for bolting AO and AA filters together dispensing with unnecessary inter-connecting pipework for 0220G/G and 0405G/G order Fixing Kit FXK4.

** Grade AR - Dust filter: 100% particle removal down to 1 micron, 98% removal at 0.3 micron.

38

2. SERVICE LIFE
The service life of the purifier is determined by the temperature of the air flowing through it. With mineral type compressor oils the expected service life of the purifier at a line pressure of 7 bar g is: 6000 hours at an air temperature of 300C, and 2000 hours at an air temperature of 450C.

3. MAINTENANCE
1. Routine Maintenance Any build-up of carbon dust in the outlet manifold may be cleared by opening the manual drain valve (in an anticlockwise direction) located on the underside of the outlet manifold. 2. Replacing Activated Carbon/Catalyst To replace the activated carbon/catalyst the top manifold should first be removed by unbolting the head bolts (see Figure 1). The top gaskets are then removed. The activated carbon/catalyst may now be extracted using an industrial vacuum cleaner (the use of a suitable face mask is recommended during this operation). Replacement activated carbon/catalyst packs are available from domnick hunter (see table 2). The use of a snow storm filling device (see table 2) is essential to achieve maximum packing of new carbon/catalyst. New gasket seals should be fitted. The top manifold replaced and head bolts tightened in sequential manner to a torque of 25 lb.ft (34Nm). Note - Do not attempt to remove manifolds or replace activated carbon/catalyst whilst AC purifier is pressurised. Always open manual drain valve (on underside of inlet manifold) to check that purifier is not pressurised. Table 2
MODEL BAH BAH BAH BAH BAH 102 103 104 105 106 Replacement Desiccant Pack RP 102 RP 103 RP 104 RP 105 RP 106 dh Comp. No. 605009240 605009250 605009260 605009270 605009280 Gasket Seal Kit GK 102 GK 103 GK 104 GK 105 GK 106 dh Comp. No. 605009190 605009200 605009210 605009220 605009230 Additional Service Tool Snow Snow Snow Snow Snow Storm Storm Storm Storm Storm Filler Filler Filler Filler Filler 608200622 608200622 608200622 608200622 608200622

Note - If replacing both top and bottom manifolds please order 2-off of the Gasket Seal Kits.

3. Maintenance Plans domnick hunter offers service plans which are tailored to each customers requirements. Through these plans, the service/maintenance responsibility becomes domnick hunters. For details please contact our Service Department.

39

d h

domnick hunter

OIL-X
Filters for compressed air and gasses

0009G-0620G (PF, AO, AA, ACS, AX, AR, AAR) AC-0006G-0085G

User Guide

?
THIS FILTER MUST BE INSTALLED AND MAINTAINED BY A COMPETENT PERSON

TECHNICAL SPECIFICATION
Maximum working pressure and temperature 66C (151F) 30C (86F)

1.5C (35F) 16 bar g 232 psi with auto drain 20 bar g 290 psi with manual drain

1.5C (35F)

AO, AA, AR

AC, ACS

41

INSTALLATION

AC AC

PF PF

AO AO

AA AA

ACS ACS

PF PF

AO

AA

42

MAINTENANCE

AC-0006G-0085G

0009G-0145G

0205G-0620G

B A

A C

SEE ACCESSORIES

43

FILTER ELEMENT REPLACEMENT

PF, AO, AA, ACS, AX, AR, AAR 0009G-0620G

(1) ISOLATE AIR SUPPLY

(2) DEPRESSURISE FILTER HOUSING

(4) (3)

(5)

(6)

(7)

!
44

FILTER ELEMENT REPLACEMENT

AC 0006G-0085G

(1) ISOLATE AIR SUPPLY

(2) DEPRESSURISE FILTER HOUSING

45

FITTING DIFFERENTIAL PRESSURE GAUGE

ISOLATE AIR SUPPLY

DEPRESSURISE FILTER HOUSING

1/2AA

DPG

DPGL

DPI

46

ACCESSORIES

AUTOMATIC DRAIN

MANUAL DRAIN

No. 60864

No. 69203

MOUNTING BRACKET KIT

FIXING KIT

0009G 0017G-0030G 0058G-0145G 0205G-0330G 0405G-0620G 0009G 0017G-0030G 0058G-0145G 0205G-0330G 0405G-0620G

MBK1 MBK2 MBK3 MBK4 MBK5 MAK1 MAK2 MAK3 MAK4 MAK5

0009G 0017G-0030G 0058G-0145G 0205G-0330G 0405G-0620G

FXK1 FXK2 FXK3 FXK4 FXK5

SGK1

DPGL
47

DPI

DPG

Declaration of Conformity

DECLARATION OF CONFORMITY 98/37/EC Name of manufacturer or supplier: domnick hunter limited Full postal address including country of origin Dukesway, Team Valley Trading Estate, Gateshead, Tyne & Wear, England, NE11 0PZ Description of product

GB

OIL-X FILTERS FOR COMPRESSED AIR AND GASSES

Name type or model, batch or serial number PF, AO, AA, ACS,AX, AR, AAR-0009G-0620G AC-0006G-AC-0085G Standards used, including number, title, issue date and other relative documents EN292-1:1991 EN 292-2:1991 Place of issue: GATESHEAD, TYNE & WEAR, ENGLAND

Name of authorised representative ERIC W. BLAKIE Position of authorised representative MANAGING DIRECTOR (INDUSTRIAL DIV.) Full postal address if different from manufacturers Declaration I declare that as the authorised representative, the above information in relation to the supply/manufacture of this product, is in conformity with the stated standards and other related documents following the provisions of the 98/37/EC Directive.

Signature of authorised representative:

48

d h

domnick hunter
CARBON MONOXIDE MONITOR

Installation, Operating & Maintenance Instructions

CO MONITOR
GENERAL DETAILS

Sample/test Gas Inlet

LED Display

Test Button

MODE UP
Electrical Connection From Transformer

DOWN ENTER

PPM CO

80mm (3.15")

90dba Alarm Horn 160mm (6.30") 85mm depth (3.35") Exhaust Gas Remote Alarm Connection

50

CARBON MONOXIDE MONITOR


1. GENERAL DESCRIPTION 1.1 The ANOLOX 3050 instrument is designed to measure and indicate the concentration of Carbon Monoxide (CO) in the gas sample presented to its input port. The range of measurement can be specified by the user, but the present design is configured for 0 to 50ppm with a resolution of approximately 0.3ppm. CO concentration is measured using an electro-chemical sensor the electrical signal is then passed to a microprocessor, which carries out the following functions : a. b. c. d. e. f. g. Linearisation of the signal using calibration constants. Conversion of the signal into a form, suitable for the instrument display. Monitoring for an alarm condition with reference to a pre-set level. Provide facilities for audible and visual gas alarms. Provide simple means of user calibration. Provide authorised personnel access to change the alarm set-point. Carry out continuous monitoring of the battery condition and warns when low.

1.2

2. OPERATION 2.1 SWITCHING ON When the instrument is first switched on, it carries out a self test procedure and during this operation, the display will show the word TEST. This procedure takes about 5 seconds and also allows a period for the electro-chemical sensor to stabilise. After this time, the instrument is ready to monitor the input gas. 2.1.1 Carbon monoxide concentration in the input sample is indicated on the 4 Digit LCD display. GAS ALARM As long as the measured CO concentration remains below the pre-set alarm level (see 2.2.4), the relay will be energised and the normally open contact will be connected to the common contact. The alarm LED and audible alarm will be inactive. If the CO concentration exceeds the pre-set alarm level, then the following actions will take place : a. b. c. 2.2.3 The relay will de-energise resulting in the common contact connecting to the normally closed contact and breaking the connection to the normally open contact. The alarm LED will be turned on. The audible alarm will be activated.

2.2 2.2.1

2.2.2

These conditions will prevail until the measured CO concentration drops 1ppm below the alarm set-point. The alarm set-point value depends on local health and safety regulations and varies depending on country of use. The instruments are normally pre-set at the factory to 10ppm but authorised personnel may be instructed on the procedure for changing this setting.
51

2.2.4

2.3 CALIBRATION 2.3.1 This is a fairly simple procedure which should be carried out at least every 12 months, or after changing the sensor. Calibration requires a source of clean, CO free air or nitrogen, and a mixture of CO/air of concentration around 50ppm CO. IT SHOULD BE CARRIED OUT WITH CARE, SINCE THE ACCURACY OF THE SUBSEQUENT READINGS IS ONLY AS GOOD AS THE ACCURACY OF THE LAST CALIBRATION. 2.3.2 The procedure uses the four membrane keys on the front panel, just to the left of the display, marked MODE, UP , DOWN and ENTER . The keys carry out simple functions allowing the zero and span calibration points to be entered. 2.3.3 The information entered during this procedure is stored in non-volatile memory which means that it is not lost when the Instrument is switched off or when the battery is being replaced. 2.3.4 The basic key functions are :

a. MODE key - is used to initiate the calibration process. It also acts as an abort key, if say the calibration process is entered accidentally or the user realises that a wrong value has been entered and he wishes to cancel the operation. b. UP key - is used to increment the displayed value, during the span calibration process. 1 is added to the displayed value, each time the key is pressed and released. c. DOWN key - is used to decrement the displayed value, during the span calibration process. 1 is subtracted from the displayed value, each time the key is pressed and released. d. ENTER key - is used to confirm the end of each step in the calibration procedure. When pressed and released it automatically advances the calibration process to the next level. 2.3.5 During the first two stages of the calibration procedure, a 3 digit number will appear on the display. These numbers DO NOT actually mean anything to the user, they are only used to indicate a steady input condition. 2.3.6 Setting zero - connect a source of clean air or nitrogen to the calibration or gas inlet and adjust the flow rate to between 30 and 60 Litres/Hour. Press and release the MODE key once. The display will show three short horizontal bars in the left hand digit position followed by three numbers. As the zero gas flows, the numbers on the display will change. Wait until the reading is steady (the right hand digit may flicker (1 Digit) and then press the ENTER Key. The display will change to show CXXX where XXX are the three digits which were displayed before the ENTER key was pressed. 2.3.7 Setting span - connect a source of air/CO having a concentration of around 50ppm CO and adjust the flow rate to between 30 and 60 litres/hour. Observe the display and ensure that the numeric value is increasing. Wait until the reading is steady - this should occur at about 200 with a 50ppm air/CO mixture. When the reading is steady, press and release the ENTER key. The display will then change to show E050. NOTE : If a reading of between 180 and 220 cannot be achieved then the sensor is probably exhausted. The calibration procedure should be aborted by pressing the MODE key and the sensor should be replaced. (See section 3.2 below). 2.3.8 Setting the gas concentration - when the display is showing E050, pressing and releasing the UP key will add 1 to the displayed value and pressing the DOWN key will subtract 1 from the displayed value. Use the UP and DOWN keys to change the displayed reading to match the actual concentration of the air/CO mixture being used. When the air/CO concentration

52

reading is correct, press the ENTER key and the process is complete. 2.3.9 Note that there are built-in upper and lower limits for the air/CO gas concentration. These are set at 55ppm and 35ppm respectively. Values outside these limits, cannot be entered during the process in 2.4.8 2.3.10 The procedure may be aborted at any time up to this point, simply by pressing the MODE key. The data entered during the previous calibration will then be used to linearise the measurement. 2.3.11 Pressing the keys in combinations other than as described above, will have no effect on the Instruments operation. During the operation of the keys the actual effect of the key only takes place when it is released.

3. MAINTENANCE
3.1 Sensor replacement - the electrochemical sensor has a life, in air, of about 18 months. However, this will be shortened if it is constantly subjected to carbon monoxide, particularly high concentrations. 3.1.1 Switch off the instrument and disconnect the DC supply. Undo the four corner screws in the front panel (they are captive in the front panel) and carefully withdraw the panel from the housing body. Disconnect the wiring loom from the front panel by releasing the small retaining clips on the 2 x white plastic connectors and remove the front panel. Locate the sensor cell - this is a 32mm diameter component at the end of the printed circuit board. It is a plug-in device having 4 small pins. Carefully ease the sensor out of its 4 sockets. 3.1.2 Replacement sensors are supplied in a gas tight package, which should NOT be opened until they are to be fitted in an instrument. Examine the new sensor and note that there is a thin spring shorting clip fitted to three of the gold pins. Remove this spring clip and carefully fit the new sensor in to the 4 PCB sockets, ensuring that it is secure. Check that the O ring seal is correctly located on the front of the sensor and that there is no foreign matter on the face of the seal. At this point, it is a good policy to make a note of the sensor serial number and enter the date of replacement in a record book, so that the next replacement may be anticipated. 3.1.3 Refit the white plastic connectors on the front panel and refit the front panel to the housing body checking that the orientation is correct, i.e. that the sensor will mate with the gas flow adaptor in the housing body. Secure the 4 corner screws and re-connect the battery. 3.1.4 Switch on the instrument and allow the new sensor to settle for about 30 minutes, then carry out a full calibration procedure, as described in section 2 above. 3.1.5 There are no other user-serviceable parts in the instrument. If the instrument fails to perform as expected, then contact domnick hunter ltd for assistance.

53

All replacement parts are available directly from domnick hunter ltd or its approved agents. The adoption of a regular servicing policy is strongly recommended and will help to ensure that correct performance is achieved and maintained. Serial numbers and customer order numbers should be referred to in any communications regarding this equipment. Any warranty will be invalidated if any part is substituted with a non-original manufacturers part. Substitute parts could reduce the performance or service life of this equipment in addition to creating potential hazards. domnick hunter ltd standard conditions of sale and warranty apply to this equipment.

54

INTERNAL AND EXTERNAL WIRING LOOMS V4

55

d h
domnick hunter limited Dukesway, Team Valley Trading Estate, Gateshead, Tyne and Wear, England NE11 0PZ Tel: +44 (0)191 402 9000 Telefax: +44 (0)191 482 6296 http://www.domnickhunter.com
domnick hunter pty ltd Tel: +61 (0)3 9762 9922 Telefax: +61 (0)3 9762 9911 hb-domnick hunter equipamentos Itda Tel: +55 (0)11 3766-3977 Telefax: +55 (0)11 3768-1421 domnick hunter Canada inc Tel: (905) 820-7146 Telefax: (905) 820-5463 Toll Free: 1-888-342-2623 domnick hunter China Tel: +86 10 646 33523 Telefax: +86 10 646 33521 domnick hunter Skandinavien A/S Tel: +45 47 38 06 44 Telefax: +45 47 38 06 43 domnick hunter France S.A. Tel: +33 4 74 62 34 51 Telefax: +33 4 74 62 35 44 domnick hunter gmbh Tel: +49 (0) 2151 83660 Telefax: +49 (0) 2151 395779 domnick hunter India Pvt Ltd Tel: +91 11 61 92172 Telefax: +91 11 6185279 P.T. domnick hunter Indonesia Tel: +62 21 458 40488 Telefax: +62 21 452 4323 domnick hunter Nihon Tel: +81 (0)78 391 8055 Telefax: +81 (0)78 391 8056 domnick hunter - RL (Malaysia) Sdn Bhd Tel: +60 3 733 3415 Telefax: +60 3 735 1699 domnick hunter group Polska Tel: +48 22 7230367 Telefax: +48 22 7230368 domnick hunter group Pte Ltd Tel: +65 744 4088 Telefax: +65 744 9959 domnick hunter Iberica Tel: +34 93 351 4807 Telefax: +34 93 351 7102 domnick hunter SweTec AB Tel: +46 (0)31 748 0610 Telefax: +46 (0)31 748 0621
dh, and domnick hunter, are registered trademarks of domnick hunter limited.

ORDEM e PRO GR

ES

SO

domnick hunter - RL (Thailand) Co. Ltd Tel: +66 2 255 5305 Telefax: +66 2 255 5340 domnick hunter inc Tel: +1 (704) 921 9303 Telefax: +1 (704) 921 1960 Toll Free: 1-800-345-8462

domnick hunter limited has a continuous policy of product development and although the Company reserves the right to change specifications, it attempts to keep customers informed of any alterations. This publication is for general information only and customers are requested to contact our Industrial Division Sales Department for detailed information and advice on a products suitability for specific applications. All products are sold subject to the Companys standard conditions of sale.

Your Partner in ment T reat Compressed Air

a member of the domnick hunter group plc

For the latest information visit the domnick hunter website on http://www.domnickhunter.com

Copyright domnick hunter limited 1999 Stock No: 176033090 REV 002

S-ar putea să vă placă și