Transformer calculation sheet, by Manfred Mornhinweg Input data: Iron: Center leg mm: Stack height mm: Loss

W/kg@1T,50Hz: Primary V: Secondary no-load V: Frequency Hz: 100 150 2 230 2000 50 Prices: Design decisions:

Output data:

Cross section mm2: Turns per Volt:

15000 0.3003

Window area mm2: Av. turn length mm:

7500 657.0796

Primary turns: Secondary turns: Input power VA: Power loss %: Voltage drop %: Loaded Vout: Iron weight kg: Copper weight kg: Cost $: $/W:

69.06907 600.6006 9990 2.965957 1.57857 1968.429

Length m: Length m:

45.38388 394.6424

mm2: mm2:

Required thermal transfer coefficient W/m2K: 69.3 17.60316 503.4106 0.050391

Flux Density T: mm2/A: Fill factor: Temperature rise K:

1 0.5 0.4 70

Iron $/kg Copper $/kg

3.2 16

Copper area mm2:

3000

21.71739 2.4975

Ampere: Ampere:

43.43478 4.995

Iron loss W: 138.6 Copper loss W: 157.6991 Total loss W: 296.2991 Surface area m2: 0.3154 Required thermal transfer coefficient W/m2K: 13.42056 7 is easy to get Convection cooling up to 12 Strong fan up to 30 Oil up to 50?