Sunteți pe pagina 1din 80

Split System

Cooling Product
& Performance Data
50 Hz

Air Handler Models

Condensing Models

TWE030CA
TWE040CA
TWE050CA

TTB0520
2TTB0524-536AA
2TTA0030-060AD

PUB. NO. TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

9/15/2003, 4:38 PM

General
Features
Split System Cooling Units . . .
The Evolution Continues
2TTB0, 2TTA0 split systems represent a
product that is not only an engineers
dream, its also a customers dream. The
design teams mission and accomplishment is enhanced performance and
efficiency, improved reliability and
durability, and improved installability
and serviceability.

technology and customer research to


develop the next generation of leadership
outdoor products.
Couple the Trane reputation for reliability
and durability with the above mentioned
mission and accomplishments and you
continue to have systems that prove
Its Hard to Stop a Trane.

Tranes experienced design team applied


six sigma principles, the latest computer

2003 American Standard Inc. All Rights Reserved

TWE5_PRC002_EN_081703.PMD

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Contents

General Features

Features and Benefits

Condensing Units
Air Handling Units
Optional Equipment
Low Outdoor Ambient Cooling

Selection Procedure

Model Number Nomenclature for Condensing Units


Model Number Nomenclature for Air Handlers

General Data

7
7
7
8
8
8
8
9
9
9
9

Performance Data

10

TTB/TWE Cooling
2TTB/TWE Cooling
2TTA/TWE Cooling
Evaporator Fan Performance
Air Pressure Drop

10
10
16
23
24

Minimum Airflow (CFM) Heater Matrix

25

Electrical Data

26

Dimensions

30

Convertibility

34

Mechanical Specification Options

35

Condensing Units
Air Handling Units

TWE5_PRC002_EN_081703.PMD

6
6

TWE030CA40B
TWE040CA40C
TWE050CA50D
TTB520CA00B0
2TTB0524AA000A
2TTB0530AA000A
2TTB0536AA000A
2TTA0030AD000A
2TTA0040AD000A
2TTA0050AD000A
2TTA0060AD000A

TWE5-PRC002-EN-08-17-03

4
4
5
5

35
36

9/15/2003, 4:38 PM

Features and
Benefits
Condensing Units
(TTB05_CA)
Flexibility in application
Quality and reliability
Uniform covering for a smooth,
attractive and corrosion-resistant finish

Vertical Air Discharge


High Efficiency TRANE Climatuff
Compressor
Powder Paint finish
Brazed or flare connections

TTB05

Condensing Units
(2TTB05_AA, 2TTA00_AD)
Climatuff compressor
Efficiency up to 10 SEER
All aluminum Spine Fin coil
Duratuff base, fast complete drain,
weather proof
WeatherGuard fasteners

2TTB05 &
2TTA00

New appearance with enhanced


consumer cues
New tarpaulin gray cabinet with
anthracite gray base
Quick-Sess cabinet, service access
and refrigerant connections with full coil
protection
Corrosion resistant finish
High/low pressure & temperature
protection
Liquid line filter-drier
Easy single side service
Brazed or flared connections
Multi-use liquid and suction line
service valves

Easy top & fan removal


Full length control and service valve
cover
Sure Fast seams louver panel
removal
HCFC-22 refrigerant
S.E.E.T. design testing
100% line run test
Low ambient to 55F as shipped
Low ambient to 40F with
EDC accessory AY28X079
Low ambient to 30F with EDC
accessory AY28X079 and TXV

Air Handling Units


(2TWE0_CA)
Ships horizontal
Six way convertibility horizontal (left
and right), upflow, downflow (front and
rear access)

TWE

Electrical, refrigerant, condensate and


blower access convertible to either side
Corrosion resistant galvanized steel
with attractive finish
Internally enhanced finned coil tubes
Direct drive motor
Standard filters
Multi-speed blower
220 volt primary and 24 volt secondary
transformer
Insulated cabinet
External access to heater circuit
breakers
Start kits are not required
Built-in indoor fan delay function for
increased efficiency. No kit required.
Improved filter access and latch
Eliminate current T-bar and shipping
bracket.

Provision for 1-1/8 inches thick field


supplied electrostatic filter
Reversible Duct Flanges Fits up to
1-1/2 inches duct board
Improve controls access with control
box mounted next to blower.
40 VA transformer with 5 amp automotive style fuse on 3 tons and less
5 Amp automotive style fuse replaces
Bussman red cap fuse on 3.5 to 5 ton
models
Blower mounting brackets improved
Front access to screw with power driver
Improved bottom carton cushioning
1 inch thick foil faced insulation for all
models

TWE5_PRC002_EN_081703.PMD

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Features and
Benefits
Optional Equipment
] indicates accessories included).
OPTIONAL EQUIPMENT FOR CONDENSING UNITS (Check mark [
Indoor Thermostats Htg./Clg. Programmable Thermostat ................................................................................. TAYSTAT300C [
Electronic, 2-Stg. Htg./1 Clg. ............................................................................................. TAYSTAT302C [
Prog., 5/2 Day, Manual, 1 Htg./1 Clg. .................................................................................. TAYSTAT340 [
Prog., 5/2 Day, Manual, 2 (Gas) 1 Htg./1 Clg. ..................................................................... TAYSTAT350 [
Electronic, 1 Htg. (Gas)/1 Clg. (Non Prog.) .......................................................................... TAYSTAT370 [
Electronic, 1 Htg. (Elec.)/1 Clg. (Non Prog.)2 ..................................................................... TAYSTAT371 [
Electronic, 2 Htg. (Gas)/1 Clg. (Non Prog.) .......................................................................... TAYSTAT380 [
Manual, 2-Stg. Htg./1 Clg. ................................................................................................... TAYSTAT241 [
Heating/Cooling Horizontal ................................................................................................. AY28X092 [
Cooling Only with Fan Switch .............................................................................................. BAYSTAT304 [
Heating/Cooling Vertical ................................................................................................. BAYSTAT305 [
Two-Stage Heating/Cooling Horizontal1 ......................................................................... BAY28X183 [
One-Stage Heating/Cooling Horizontal1 ......................................................................... BAY28X182 [
Thermostat Locking Cover3 ................................................................................................. BAY28X190 [
Outdoor Thermostat ............................................................................................................................................... TAYSTAT250B [
Sub-base BAY28X182, 183 (Manual changeover)2 ................................................................................................. BAY28X185 [
Evaporator Defrost Control .......................................................................................................................................... AY28X079 [
Fan Delay Relay Kit ................................................................................................................................................... BAY24X045 [
5 Minute Delay Relay ............................................................................................................................................ TAYASCT501A [
Outdoor Temperature Sensor ............................................................................................................................... TAYSENS100A [
Start Kit 1.5-5 ton) ................................................................................................................................................... BAYKSKT257 [
Extreme Conditions Mounting Kit (2TTB05_AA, 2TTA0_AD) ................................................................................. BAYECMT001 [
Seacoast Kit ........................................................................................................................................................... BAYSEAC001 [

]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]

1 Requires sub-base
2 Specifically designed for electric heat applications (instant on fan)
3 Not for use with programmable thermostats

BRAZED TUBING REFRIGERANT LINE SETS (All Suction Lines are Insulated.)
5/8" ODM (90 bend, one end), 5/8" and 1/4" tubing ............................................................................................ TAYREFLN1__* [ ]
3/4" ODM (90 bend, one end), 3/4" and 5/16" tubing .......................................................................................... TAYREFLN2__* [ ]
7/8" ODM (90 bend, one end), 7/8" and 3/8" tubing ............................................................................................ TAYREFLN3__* [ ]
1-1/8" ODM (90 bend, one end), 1-1/8" and 3/8" tubing ...................................................................................... TAYREFLN4__* [ ]
* Line lengths: 15, 20, 25, 30, 40 & 50 ft. Insert desired line length in catalog number at right for the complete number.
Example: TAYREFLN220

Low Outdoor Ambient Cooling


Low Ambient
Cooling
FCCV Accutron
Thermal Expansion Valve (TXV)

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

As
Manufactured

Evaporator
Defrost Control

55F
55F

40F
30F

9/15/2003, 4:38 PM

Selection
Procedure
Model Number Nomenclature for Condensing Units (2TTB05, 2TTA00)
1

10

11

12

13

14

15

Refrigerant Type
2 = R-22
4 = R-410A

Unit Parts
Identifier
Minor Design
Modifications

TRANE
Product Type
W = Split Heat Pump
T = Split Cooling

Secondary
Function
Power Supply
1 = 200 - 230 / 1 / 60 or 208 - 230 / 1 / 60
3 = 200 - 230 / 3 / 60
4 = 460 / 3 / 60
A = 220 / 1 / 50
D = 380-415 / 3 / 50

Product Family
Z = LEADERSHIP - 2 STAGE
X = LEADERSHIP
R = REPLACEMENT / RETAIL
B = BASIC
A = LIGHT COMMERCIAL

Major Design Modifications

Family SEER
0 = 10 2 = 12
1 = 11 3 = 13

4 = 14
6 = 16

Nominal Capacity in 000s of BTUs


8 = 18

Split System Connections 1 - 6 Tons


0 = Brazed
5 = Flare

Model Number Nomenclature for Air Handlers


1

10

11

12

Product Type
TW = Split System Component
Heat Pump Compatible

Product
Service Change

Airflow Configuration
E = Convertible

Minor Design
Modification

Refrigerant Connections
0 = Brazed

Not Used
Refrigerant Flow Control
4 = Accutron Flow Control/Check Valve
5 = Bleed TXV

Nominal Net Cooling


Capacity
30 = 30 MBh
40 = 40 MBh
50 = 50 MBh

Electrical Characteristics
A = 220V/1/50

Major Design Modification


6

TWE5_PRC002_EN_081703.PMD

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

General
Data

TWE

TWE Product Specifications


Model
Power Conn. Volts/Ph/Hz
Indoor Coil - Type
Rows
Fins per inch (Fins per 25.4 mm)
Face Area sq ft (sq m)
Tube Size in. (mm)
Refrigerant Control
Drain Conn. Size in. (mm)
Duct Connections
Indoor Fan - Type
No. Used
Diameter in. (mm)
Width in. (mm)
Type Drive - No. Speeds
Airflow (High)
CFM @ 0.0 in. w.g.
CMH @ 0.0 Pa
No. Motors - HP
Motor RPM
Volts/Ph/Hz
F.L. Amps
L.R. Amps
Filters
Vertical Applications
Filter Furnished
Type Furnished
No.-Size-Thickness
Horizontal Applications
Filter Furnished
Type Recommended
No.-Size-Thickness
Refrigerant Line Size
Line Size ID Gas in. (mm)
Line Size ID Liquid in. (mm)
Dimensions (H x W x D)
Crated - in.
- (mm)
Uncrated - in.
- (mm)
Weight Ibs. (kg)
Shipping
Net

TWE030CA40B
220/1/50
Plate Fin
3
14
3.21 (.30)
3/8 (9.52)
FCCV
3/4 NPT
See Outline Drawing
Centrifugal
1
10.0 (254.0)
8.0 (203.2)
Direct - 3

TWE040CA40C
220/1/50
Plate Fin
3
14
5.04 (.47)
3/8 (9.52)
FCCV
3/4 NPT
See Outline Drawing
Centrifugal
1
10.0 (254.0)
10.0 (254.0)
Direct - 3

TWE050CA50D
220/1/50
Plate Fin
3
14
6.19 (.58)
3/8 (9.52)
FCCV
3/4 NPT
See Outline Drawing
Centrifugal
1
11.0 (279.4)
10.0 (254.0)
Direct - 3

See Fan Performance Table


See Fan Performance Table
1 - 1/3
1000
220/1/50
2.6
3.3

See Fan Performance Table


See Fan Performance Table
1 - 1/3
900
220/1/50
2.1
4.2

See Fan Performance Table


See Fan Performance Table
1 - 3/4
900
220/1/50
4.5
10.1

Yes
Throwaway
1 - 20 x 20 - 1

Yes
Throwaway
1 - 20 x 20 - 1

Yes
High Velocity
1 - 2 2 x 20 - 1

No
See Note Below
See Note Below

No
See Note Below
See Note Below

No
See Note Below
See Note Below

7/8 (22.23)
3/8 (9.52)

1-1/8 (28.56)
3/8 (9.52)

1-1/8 (28.56)
3/8 (9.52)

44.5 x 24.0 x 23.5


(1130 x 610 x 597)
43.0 x 21.5 x 21.0
(1092 x 546 x 533)

53.25 x 26.0 x 23.5


(1353 x 660 x 597)
52.0 x 23.5 x 21.0
(1321 x 597x 533)

59.5 x 26.0 x 23.5


(1511 x 660 x 597)
58.0 x 23.5 x 21.0
(1473 x 597 x 533)

125 (56.7)
115 (52.2)

165 (74.8)
150 (68.0)

198 (898)
183 (83.0)

Minimum filter size for horizontal applications based on airflow selection and calculated as follows:
Low Velocity Filter: Face Area (sq ft) = CFM/300
High Velocity Filter: Face Area (sq ft) = CFM/500

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

9/15/2003, 4:38 PM

General
Data

TTB/2TTB

TTB/2TTB Product Specifications 12


TTB520CA00B0
Model
200/230/1/50
Power Conn. - Volts/Ph/Hz
PER LOCAL CODES
Fuse Size - max. amps
14
Min. Brch. Cir. Ampacity
20
Br. Cir.
Max. (Amps)
20
Prot. Rtg. Min. (Amps)
CLIMATUFF
Compressor - Type
1
No. Used - No. Speeds
200/230/1/50
Volts/Ph/Hz
9.6 - 66
R.L. Amps 6 - L.R. Amps
Factory Installed
Start Components 7
NO
NO
Insulation/Sound Blanket
NO
Compressor Heat
PROPELLER
Outdoor Fan - Type
1
No. Used
13.7 (348)
Diameter in. (mm)
DIRECT - 1
Type Drive - No. Speeds
1300
CFM @ 0.0 in. w.g. 3
602
(M) 3/HR. @ 0.0 mm w.g. 3
CMH @ 0.0 mm. w.g. 3
1 - 1/8
No. Motors - HP
1620
Motor Speed (RPM)
200/230/1/50
Volts/Ph/Hz
1.1
F.L. Amps
SPINE FIN
Outdoor Coil - Type
1
No. Rows
24 (.945)
Fins/in. (mm)
6.62 (.615)
Face Area sq ft (sq m)
3/8 (9.52)
Tube Size in. (mm)
Refrigerant
3-LBS., 6-OZ. (110)
R-22 (O.D. Unit) 4 - lbs. (kg)
NOM.
Factory Supplied
3/4 (0.053)
Line Size - OD Gas 5 in. (mm)
5/16 (1.35)
Line Size - OD Liq. 5 in. (mm)
FCCV
Restrictor Orifice Size in. (mm)
Dimensions (H x W x D)
24-3/4 X 20 X 20
Crated - in.
(629 X 508 X 508)
- (mm)
SEE OUTLINE DRAWINGS
Uncrated
Weight lbs. (kg)
121 (54.9)
Shipping
117 (53.1)
Net

2TTB0524AA000A
200/230/1/50

2TTB0530AA000A
200/230/1/50

2TTB0536AA000A
200/230/1/50

16
25
20
CLIMATUFF
1-1
200/230/1/50
12.2 - 74.8

17
25
20
CLIMATUFF
1-1
200/230/1/50
12.9 - 77.9

26
40
40
CLIMATUFF
1-1
200/230/1/50
19.9 - 124

NO
NO
NO
PROPELLER
1
19 (483)
DIRECT - 1
1825

NO
NO
NO
PROPELLER
1
19 (483)
DIRECT - 1
1825

YES
NO
NO
PROPELLER
1
19 (483)
DIRECT - 1
2075

3103
1 - 1/8
1075
200/230/1/50
0.9
SPINE FIN
1
24 (0.945)
9.72 (0.90)
3/8 (9.53)

3103
1 - 1/8
1075
200/230/1/50
0.9
SPINE FIN
1
24 (0.945)
9.72 (0.90)
3/8 (9.53)

3528
1 - 1/4
1075
200/230/1/50
1.3
SPINE FIN
1
24 (0.945)
11.32 (1.05)
3/8 (9.53)

4-LBS., 0-OZ. (1.82)


YES
3/4 (19.1)
5/16 (7.94)

4-LBS., 12-OZ. (2.16)


YES
7/8 (22.2)
3/8 (9.53)

5-LBS., 15-OZ. (2.70)


YES
7/8 (22.2)
3/8 (9.53)

.059

.065

.069

30.1 x 26.7 x 30.2


765 x 678 x 767

30.1 x 26.7 x 30.2


(765 x 678 x 767)

33.2 x 26.7 x 30.2


(843 x 678 x 767)

175 (79.5)
156 (70.9)

178 (80.9)
159 (72.3)

215 (97.7)
195 (88.6)

NOTES:
1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.
2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.
NO SUPPLEMENTARY HEAT INCLUDED.
3 STANDARD AIR - DRY COIL - OUTDOOR
4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.
5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.
6 THIS VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAX. FUSE SIZE. THE VALUE
SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.
7 NO MEANS NO START COMPONENTS. YES MEANS QUICK START KIT COMPONENTS. PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

TWE5_PRC002_EN_081703.PMD

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

General
Data

2TTA

2TTA Product Specifications 12


Model
Power Conn. - Volts/Ph/Hz
Fuse Size - max. amps
Min. Brch. Cir. Ampacity
Br. Cir.
Max. (Amps)
Prot. Rtg. Min. (Amps)
Compressor - Type
No. Used - No. Speeds
Volts/Ph/Hz
R.L. Amps 6 - L.R. Amps
Factory Installed
Start Components 7
Insulation/Sound Blanket
Compressor Heat
Outdoor Fan - Type
No. Used
Diameter in. (mm)
Type Drive - No. Speeds
CFM @ 0.0 in. w.g. 3
(M) 3/HR. @ 0.0 mm w.g. 3
CMH @ 0.0 mm. w.g. 3
No. Motors - HP
Motor Speed (RPM)
Volts/Ph/Hz
F.L. Amps
Outdoor Coil - Type
No. Rows
Fins/in. (mm)
Face Area sq ft (sq m)
Tube Size in. (mm)
Refrigerant
R-22 (O.D. Unit) 4 - lbs. (kg)
Factory Supplied
Line Size - OD Gas 5 in. (mm)
Line Size - OD Liq. 5 in. (mm)
FCCV
Restrictor Orifice Size in. (mm)
Dimensions (H x W x D)
Crated - in.
- (mm)
Uncrated
Weight lbs. (kg)
Shipping
Net

2TTA0030AD000A
380/415/3/50

2TTA0040AD000A
380/415/3/50

2TTA0050AD000A
380/415/3/50

2TTA0060AD000A
380/415/3/50

7
15
15
CLIMATUFF
1-1
380/415/3/50
8.3 - 46

9
15
15
CLIMATUFF
1-1
380/415/3/50
10 - 51

12
20
20
CLIMATUFF
1-1
380/415/3/50
14 - 70

14
20
20
CLIMATUFF
1-1
380/415/3/50
9 - 73

NO
NO
YES
PROPELLER
1
19 (483)
DIRECT - 1
2075

NO
NO
YES
PROPELLER
1
19 (483)
DIRECT - 1
2075

NO
NO
YES
PROPELLER
1
23 (584)
DIRECT - 1
3075

NO
NO
YES
PROPELLER
1
27.6 (701)
DIRECT - 1
3525

3528
1 - 1/4
1075
380/415/3/50
0.7
SPINE FIN
1
24 (0.945)
11.32 (1.05)
3/8 (9.53)

3528
1 - 1/4
1075
380/415/3/50
0.7
SPINE FIN
1
24 (0.945)
13.75 (1.28)
3/8 (9.53)

5228
1 - 1/4
825
380/415/3/50
1.00
SPINE FIN
1
24 (0.945)
18.75 (1.74)
3/8 (9.53)

5993
1 - 1/6
825
380/415/3/50
0.7
SPINE FIN
1
24 (0.945)
27.75 (2.59)
3/8 (9.53)

5-LBS., 15-OZ. (2.70)


YES
7/8 (22.2)
3/8 (9.53)

6-LBS., 13-OZ. (3.10)


YES
1-1/8 (28.54)
3/8 (9.53)

7-LBS., 7-OZ. (3.38)


YES
1-1/8 (28.54)
3/8 (9.53)

10-LBS., 0-OZ. (4.55)


YES
1-1/8 (28.54)
3/8 (9.53)

.069

.075

.089

33.2 x 26.7 x 30.2


(843 x 678 x 767)

33.2 x 26.7 x 30.2


(843 x 678 x 767)

.083
H X W X D
38 x 30.1 x 33.8
(965 x 765 x 859)

46.4 x 35.1 x 38.7


(1179 x 892 x 983)

207 (94.1)
187 (85.0)

216 (98.2)
196 (89.1)

254 (115.5)
227 (103.2)

298 (135.5)
263 (119.5)

NOTES:
1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.
2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.
NO SUPPLEMENTARY HEAT INCLUDED.
3 STANDARD AIR - DRY COIL - OUTDOOR
4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.
5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.
6 THIS VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAX. FUSE SIZE. THE VALUE
SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.
7 NO MEANS NO START COMPONENTS. YES MEANS QUICK START KIT COMPONENTS. PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

9/15/2003, 4:38 PM

Performance Data
Cooling
English Units
TTB520CA-B WITH TWE030CA4 AT 700 CFM
O.D.
D.B.
85

90

95

100

105

115

120

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
18.4
19.9
21.3
22.8
18.1
19.4
20.9
22.3
17.7
19.0
20.4
21.8
17.2
18.5
19.8
21.2
16.8
18.0
19.3
20.6
15.8
16.9
18.1
19.4
15.3
16.4
17.6
18.7

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
15.6
16.9
18.2
18.8*
19.3*
13.1
14.4
15.7
17.0
18.2
10.4
11.7
12.9
14.2
15.5
7.6
8.9
10.1
11.4
12.7
15.5
16.7
18.0
18.5*
19.0*
13.0
14.2
15.5
16.8
18.1
10.2
11.5
12.8
14.0
15.3
7.4
8.7
10.0
11.2
12.5
15.3
16.6
17.8*
18.2*
18.6*
12.8
14.1
15.3
16.6
17.9
10.0
11.3
12.6
13.9
15.1
7.2
8.5
9.8
11.1
12.3
15.1
16.4
17.4*
17.8*
18.2*
12.6
13.9
15.1
16.4
17.7
9.8
11.1
12.4
13.7
14.9
7.0
8.3
9.6
10.8
12.1
14.9
16.2
17.0*
17.4*
17.8*
12.4
13.7
14.9
16.2
17.5
9.6
10.9
12.2
13.4
14.7
6.8
8.1
9.4
10.6
11.9
14.5
15.8
16.2*
16.6*
17.0*
12.0
13.2
14.5
15.8
17.0*
9.2
10.5
11.8
13.0
14.3
6.4
7.7
8.9
10.2
11.5
14.3
15.4*
15.8*
16.2*
16.6*
11.8
13.0
14.3
15.6
16.6*
9.0
10.3
11.5
12.8
14.1
6.2
7.5
8.7
10.0
11.3

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
23.9
25.7
27.6
29.6
23.6
25.4
27.3
29.3
23.3
25.1
27.0
28.9
22.6
24.3
26.2
28.0
21.9
23.6
25.3
27.1
20.4
22.0
23.6
25.3
19.7
21.2
22.8
24.4

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
21.1
22.8
24.1*
24.7*
25.3*
17.8
19.5
21.2
22.9
24.6
14.2
15.9
17.6
19.3
20.9
10.5
12.2
13.9
15.5
17.2
21.0
22.7
23.9*
24.5*
25.1*
17.7
19.4
21.1
22.8
24.5
14.1
15.8
17.5
19.1
20.8
10.4
12.1
13.7
15.4
17.1
20.9
22.6
23.7*
24.3*
24.9*
17.6
19.3
21.0
22.7
24.3
14.0
15.6
17.3
19.0
20.7
10.2
11.9
13.6
15.3
17.0
20.5
22.2
23.1*
23.7*
24.2*
17.3
18.9
20.6
22.3
24.0
13.6
15.3
17.0
18.7
20.4
9.9
11.6
13.3
15.0
16.7
20.2
21.9*
22.5*
23.0*
23.6*
16.9
18.6
20.3
22.0
23.6*
13.3
15.0
16.7
18.3
20.0
9.6
11.3
13.0
14.6
16.3
19.5
20.7*
21.2*
21.8*
22.3*
16.2
17.9
19.6
21.3
22.3*
12.6
14.3
16.0
17.7
19.4
8.9
10.6
12.3
14.0
15.7
19.2
20.1*
20.6*
21.1*
21.6*
15.9
17.6
19.3
21.0
21.6*
12.3
14.0
15.7
17.3
19.0
8.6
10.3
12.0
13.6
15.3

COMPR.
KW
1.41
1.45
1.50
1.55
1.47
1.52
1.57
1.62
1.54
1.59
1.63
1.68
1.61
1.66
1.70
1.75
1.68
1.73
1.78
1.82
1.83
1.87
1.92
1.96
1.91
1.95
1.99
2.03

APP. DEW
PT.
47.2
51.1
55.3
59.5
47.5
51.4
55.6
59.9
47.8
51.7
55.9
60.2
48.1
52.0
56.2
60.5
48.4
52.4
56.6
60.9
49.1
53.1
57.3
61.6
49.5
53.4
57.7
62.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

625
X0.99
X0.95
X0.99
-1.1

825
X1.02
X1.08
X1.01
1.4

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 20500 BTUH
AIRFLOW = 725 CFM
APP. DEW PT. = 56.2 DEG. F
COMPRESSOR POWER = 1638 WATTS
I.D. FAN POWER = 310 WATTS
O.D. FAN POWER = 130 WATTS
E.E.R. = 9.40 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCT.
AND 5/16 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TTB0524AA WITH TWE030CA4 AT 900 CFM


O.D.
D.B.
85

90

95

100

105

115

120

COMPR.
KW
2.40
2.46
2.52
2.58
2.50
2.56
2.62
2.68
2.59
2.65
2.71
2.78
2.67
2.73
2.79
2.85
2.76
2.81
2.87
2.93
2.92
2.97
3.02
3.08
3.01
3.05
3.10
3.15

APP. DEW
PT.
48.3
52.1
56.3
60.5
48.4
52.3
56.4
60.7
48.6
52.5
56.6
60.8
49.0
52.9
57.1
61.3
49.5
53.3
57.5
61.7
50.3
54.2
58.4
62.6
50.8
54.6
58.8
63.1

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

10

1025
X1.01
X1.06
X1.01
1.2

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 27000 BTUH
AIRFLOW = 900 CFM
APP. DEW PT. = 56.6 DEG. F
COMPRESSOR POWER = 2143 WATTS
I.D. FAN POWER = 425 WATTS
O.D. FAN POWER = 146 WATTS
S.E.E.R. = 10.19 BTUH/WATT
E.E.R. = 9.33 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCT.
AND 5/16 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

10

TWE5_PRC002_EN_081703.PMD

775
X0.98
X0.94
X0.99
-1.5

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Performance Data
Cooling

Metric Units

TTB520CA-B WITH TWE030CA4 AT 1189 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
5.4
5.8
6.2
6.7
5.3
5.7
6.1
6.5
5.2
5.6
6.0
6.4
5.0
5.4
5.8
6.2
4.9
5.3
5.7
6.0
4.6
5.0
5.3
5.7
4.5
4.8
5.2
5.5

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
4.6
5.0
5.3
5.5*
5.7*
3.8
4.2
4.6
5.0
5.3
3.0
3.4
3.8
4.2
4.5
2.2
2.6
3.0
3.3
3.7
4.5
4.9
5.3
5.4*
5.6*
3.8
4.2
4.5
4.9
5.3
3.0
3.4
3.8
4.1
4.5
2.2
2.5
2.9
3.3
3.7
4.5
4.9
5.2*
5.3*
5.4*
3.8
4.1
4.5
4.9
5.2
2.9
3.3
3.7
4.1
4.4
2.1
2.5
2.9
3.3
3.6
4.4
4.8
5.1*
5.2*
5.3*
3.7
4.1
4.4
4.8
5.2
2.9
3.3
3.6
4.0
4.4
2.1
2.4
2.8
3.2
3.5
4.4
4.7
5.0*
5.1*
5.2*
3.6
4.0
4.4
4.7
5.1
2.8
3.2
3.6
3.9
4.3
2.0
2.4
2.8
3.1
3.5
4.2
4.6
4.7*
4.9*
5.0*
3.5
3.9
4.2
4.6
5.0*
2.7
3.1
3.5
3.8
4.2
1.9
2.3
2.6
3.0
3.4
4.2
4.5*
4.6*
4.7*
4.9*
3.5
3.8
4.2
4.6
4.9*
2.6
3.0
3.4
3.8
4.1
1.8
2.2
2.5
2.9
3.3

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
7.0
7.5
8.1
8.7
6.9
7.4
8.0
8.6
6.8
7.4
7.9
8.5
6.6
7.1
7.7
8.2
6.4
6.9
7.4
7.9
6.0
6.4
6.9
7.4
5.8
6.2
6.7
7.1

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
6.2
6.7
7.1*
7.2*
7.4*
5.2
5.7
6.2
6.7
7.2
4.2
4.7
5.2
5.7
6.1
3.1
3.6
4.1
4.5
5.0
6.2
6.7
7.0*
7.2*
7.4*
5.2
5.7
6.2
6.7
7.2
4.1
4.6
5.1
5.6
6.1
3.0
3.5
4.0
4.5
5.0
6.1
6.6
6.9*
7.1*
7.3*
5.2
5.7
6.2
6.7
7.1
4.1
4.6
5.1
5.6
6.1
3.0
3.5
4.0
4.5
5.0
6.0
6.5
6.8*
6.9*
7.1*
5.1
5.5
6.0
6.5
7.0
4.0
4.5
5.0
5.5
6.0
2.9
3.4
3.9
4.4
4.9
5.9
6.4*
6.6*
6.7*
6.9*
5.0
5.4
5.9
6.4
6.9*
3.9
4.4
4.9
5.4
5.9
2.8
3.3
3.8
4.3
4.8
5.7
6.1*
6.2*
6.4*
6.5*
4.7
5.2
5.7
6.2
6.5*
3.7
4.2
4.7
5.2
5.7
2.6
3.1
3.6
4.1
4.6
5.6
5.9*
6.0*
6.2*
6.3*
4.7
5.2
5.7
6.2
6.3*
3.6
4.1
4.6
5.1
5.6
2.5
3.0
3.5
4.0
4.5

COMPR.
KW
1.4
1.5
1.5
1.5
1.5
1.5
1.6
1.6
1.5
1.6
1.6
1.7
1.6
1.7
1.7
1.8
1.7
1.7
1.8
1.8
1.8
1.9
1.9
2.0
1.9
2.0
2.0
2.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1061
X0.99
X0.95
X0.99

1401
X1.02
X1.08
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 6.01 KW
AIRFLOW = 1231 CMH
COMPRESSOR POWER = 1638 WATTS
I.D. FAN POWER = 310 WATTS
O.D. FAN POWER = 130 WATTS
E.E.R. = 9.40 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCT.
AND 5/16 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TTB0524AA WITH TWE030CA4 AT 1528 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

11

COMPR.
KW
2.4
2.5
2.5
2.6
2.5
2.6
2.6
2.7
2.6
2.7
2.7
2.8
2.7
2.7
2.8
2.8
2.8
2.8
2.9
2.9
2.9
3.0
3.0
3.1
3.0
3.0
3.1
3.2

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1316
X0.98
X0.94
X0.99

1741
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 7.91 KW
AIRFLOW = 1528 CMH
COMPRESSOR POWER = 2143 WATTS
I.D. FAN POWER = 425 WATTS
O.D. FAN POWER = 146 WATTS
S.E.E.R. = 10.19 BTUH/WATT
E.E.R. = 9.33 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCT.
AND 5/16 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

11

9/15/2003, 4:38 PM

Performance Data
Cooling
English Units
2TTB0530AA WITH TWE030CA4 AT 1000 CFM
O.D.
D.B.
85

90

95

100

105

115

120

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
26.7
28.7
30.7
32.8
26.4
28.3
30.3
32.4
26.1
28.0
30.0
32.1
25.2
27.1
29.0
31.0
24.3
26.1
28.0
30.0
22.6
24.3
26.0
27.8
21.7
23.3
25.0
26.8

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
23.4
25.3
26.8*
27.5*
28.2*
19.8
21.6
23.5
25.3
27.2
15.8
17.6
19.4
21.3
23.1
11.6
13.5
15.3
17.2
19.0
23.3
25.1
26.6*
27.3*
27.9*
19.6
21.5
23.3
25.2
27.0
15.6
17.5
19.3
21.2
23.0
11.5
13.4
15.2
17.0
18.9
23.1
25.0
26.3*
27.0*
27.6*
19.5
21.3
23.2
25.0
26.9
15.5
17.3
19.2
21.0
22.9
11.4
13.2
15.1
16.9
18.8
22.7
24.6
25.6*
26.3*
26.9*
19.1
20.9
22.8
24.6
26.5
15.1
16.9
18.8
20.6
22.5
11.0
12.8
14.7
16.5
18.4
22.3
24.2
24.9*
25.5*
26.1*
18.7
20.5
22.4
24.2
26.1
14.7
16.5
18.4
20.2
22.1
10.6
12.4
14.3
16.1
18.0
21.5
22.8*
23.5*
24.0*
24.6*
17.9
19.7
21.6
23.4
24.6*
13.9
15.7
17.6
19.4
21.3
9.8
11.7
13.5
15.3
17.2
21.1
22.1*
22.7*
23.3*
23.8*
17.5
19.4
21.2
23.0
23.8*
13.5
15.3
17.2
19.0
20.9
9.4
11.3
13.1
15.0
16.8

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
28.7
30.7
32.8
35.0
28.3
30.3
32.3
34.5
27.9
29.9
31.9
34.0
26.9
28.9
30.8
32.9
26.0
27.9
29.8
31.8
24.1
25.9
27.6
29.5
23.2
24.8
26.6
28.4

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
25.7
27.8
29.1*
29.8*
30.5*
21.5
23.6
25.7
27.8
29.9
16.9
19.0
21.1
23.2
25.3
12.2
14.3
16.4
18.5
20.6
25.5
27.6
28.8*
29.5*
30.1*
21.3
23.4
25.5
27.6
29.8
16.7
18.8
20.9
23.0
25.1
12.0
14.1
16.3
18.4
20.5
25.3
27.4
28.5*
29.1*
29.8*
21.1
23.3
25.4
27.5
29.6
16.5
18.7
20.8
22.9
25.0
11.9
14.0
16.1
18.2
20.3
24.9
27.0*
27.7*
28.3*
28.9*
20.7
22.8
24.9
27.0
28.9*
16.1
18.2
20.3
22.4
24.6
11.5
13.6
15.7
17.8
19.9
24.5
26.2*
26.9*
27.5*
28.1*
20.3
22.4
24.5
26.6
28.1*
15.7
17.8
19.9
22.0
24.1
11.0
13.2
15.3
17.4
19.5
23.7
24.6*
25.2*
25.8*
26.4*
19.5
21.6
23.7
25.8
26.4*
14.9
17.0
19.1
21.2
23.3
10.2
12.3
14.4
16.6
18.7
23.2*
23.8*
24.4*
25.0*
25.6*
19.1
21.2
23.3
25.0*
25.6*
14.5
16.6
18.7
20.8
22.9
9.8
11.9
14.0
16.1
18.3

COMPR.
KW
2.79
2.86
2.93
3.01
2.91
2.98
3.05
3.13
3.03
3.10
3.18
3.25
3.13
3.20
3.28
3.36
3.24
3.31
3.38
3.46
3.45
3.51
3.58
3.65
3.56
3.62
3.68
3.75

APP. DEW
PT.
48.0
51.9
56.1
60.4
48.2
52.1
56.3
60.6
48.4
52.3
56.5
60.7
48.9
52.8
57.0
61.2
49.4
53.3
57.5
61.7
50.3
54.2
58.4
62.7
50.8
54.7
58.9
63.2

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

875
X0.98
X0.94
X0.99
-1.4

1125
X1.01
X1.05
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 30000 BTUH
AIRFLOW = 1000 CFM
APP. DEW PT. = 56.5 DEG. F
COMPRESSOR POWER = 2591 WATTS
I.D. FAN POWER = 437 WATTS
O.D. FAN POWER = 149 WATTS
S.E.E.R. = 9.95 BTUH/WATT
E.E.R. = 8.96 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TTB0530AA WITH TWE040CA4-B AT 1100 CFM


O.D.
D.B.
85

90

95

100

105

115

120

COMPR.
KW
2.71
2.78
2.85
2.93
2.83
2.90
2.98
3.06
2.96
3.03
3.11
3.18
3.06
3.13
3.21
3.29
3.16
3.24
3.31
3.39
3.38
3.45
3.52
3.59
3.49
3.55
3.62
3.69

APP. DEW
PT.
48.4
52.4
56.6
61.0
48.6
52.6
56.8
61.2
48.8
52.8
57.0
61.3
49.2
53.2
57.4
61.8
49.7
53.6
57.9
62.2
50.5
54.5
58.7
63.0
50.9
54.9
59.1
63.5

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

12

1250
X1.01
X1.06
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 32000 BTUH
AIRFLOW = 1125 CFM
APP. DEW PT. = 57.2 DEG. F
COMPRESSOR POWER = 2660 WATTS
I.D. FAN POWER = 309 WATTS
O.D. FAN POWER = 149 WATTS
S.E.E.R. = 11.00 BTUH/WATT
E.E.R. = 9.80 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

12

TWE5_PRC002_EN_081703.PMD

950
X0.98
X0.93
X0.99
-1.4

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Performance Data
Cooling

Metric Units

2TTB0530AA WITH TWE030CA4 AT 1698 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
7.8
8.4
9.0
9.6
7.7
8.3
8.9
9.5
7.6
8.2
8.8
9.4
7.4
7.9
8.5
9.1
7.1
7.6
8.2
8.8
6.6
7.1
7.6
8.1
6.4
6.8
7.3
7.9

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
6.9
7.4
7.9*
8.1*
8.3*
5.8
6.3
6.9
7.4
8.0
4.6
5.2
5.7
6.2
6.8
3.4
4.0
4.5
5.0
5.6
6.8
7.4
7.8*
8.0*
8.2*
5.7
6.3
6.8
7.4
7.9
4.6
5.1
5.7
6.2
6.7
3.4
3.9
4.5
5.0
5.5
6.8
7.3
7.7*
7.9*
8.1*
5.7
6.2
6.8
7.3
7.9
4.5
5.1
5.6
6.2
6.7
3.3
3.9
4.4
5.0
5.5
6.7
7.2
7.5*
7.7*
7.9*
5.6
6.1
6.7
7.2
7.8
4.4
5.0
5.5
6.0
6.6
3.2
3.8
4.3
4.8
5.4
6.5
7.1
7.3*
7.5*
7.6*
5.5
6.0
6.6
7.1
7.6
4.3
4.8
5.4
5.9
6.5
3.1
3.6
4.2
4.7
5.3
6.3
6.7*
6.9*
7.0*
7.2*
5.2
5.8
6.3
6.9
7.2*
4.1
4.6
5.2
5.7
6.2
2.9
3.4
4.0
4.5
5.0
6.2
6.5*
6.7*
6.8*
7.0*
5.1
5.7
6.2
6.7
7.0*
4.0
4.5
5.0
5.6
6.1
2.8
3.3
3.8
4.4
4.9

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
8.4
9.0
9.6
10.3
8.3
8.9
9.5
10.1
8.2
8.8
9.3
10.0
7.9
8.5
9.0
9.6
7.6
8.2
8.7
9.3
7.1
7.6
8.1
8.6
6.8
7.3
7.8
8.3

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
7.5
8.1
8.5*
8.7*
8.9*
6.3
6.9
7.5
8.1
8.8
5.0
5.6
6.2
6.8
7.4
3.6
4.2
4.8
5.4
6.0
7.5
8.1
8.4*
8.6*
8.8*
6.2
6.9
7.5
8.1
8.7
4.9
5.5
6.1
6.7
7.4
3.5
4.1
4.8
5.4
6.0
7.4
8.0
8.4*
8.5*
8.7*
6.2
6.8
7.4
8.1
8.7
4.8
5.5
6.1
6.7
7.3
3.5
4.1
4.7
5.3
5.9
7.3
7.9*
8.1*
8.3*
8.5*
6.1
6.7
7.3
7.9
8.5*
4.7
5.3
5.9
6.6
7.2
3.4
4.0
4.6
5.2
5.8
7.2
7.7*
7.9*
8.1*
8.2*
5.9
6.6
7.2
7.8
8.2*
4.6
5.2
5.8
6.4
7.1
3.2
3.9
4.5
5.1
5.7
6.9
7.2*
7.4*
7.6*
7.7*
5.7
6.3
6.9
7.6
7.7*
4.4
5.0
5.6
6.2
6.8
3.0
3.6
4.2
4.9
5.5
6.8*
7.0*
7.1*
7.3*
7.5*
5.6
6.2
6.8
7.3*
7.5*
4.2
4.9
5.5
6.1
6.7
2.9
3.5
4.1
4.7
5.4

COMPR.
KW
2.8
2.9
2.9
3.0
2.9
3.0
3.0
3.1
3.0
3.1
3.2
3.3
3.1
3.2
3.3
3.4
3.2
3.3
3.4
3.5
3.5
3.5
3.6
3.7
3.6
3.6
3.7
3.8

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1486
X0.98
X0.94
X0.99

1910
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 8.79 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 2591 WATTS
I.D. FAN POWER = 437 WATTS
O.D. FAN POWER = 149 WATTS
S.E.E.R. = 9.95 BTUH/WATT
E.E.R. = 8.96 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TTB0530AA WITH TWE040CA4-B AT 1868 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

13

COMPR.
KW
2.7
2.8
2.8
2.9
2.8
2.9
3.0
3.1
3.0
3.0
3.1
3.2
3.1
3.1
3.2
3.3
3.2
3.2
3.3
3.4
3.4
3.5
3.5
3.6
3.5
3.5
3.6
3.7

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1613
X0.98
X0.93
X0.99

2123
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 9.38 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 2660 WATTS
I.D. FAN POWER = 309 WATTS
O.D. FAN POWER = 149 WATTS
S.E.E.R. = 11.00 BTUH/WATT
E.E.R. = 9.80 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

13

9/15/2003, 4:38 PM

Performance Data
Cooling
English Units
2TTB0536AA WITH TWE030CA4 AT 1100 CFM
O.D.
D.B.
85

90

95

100

105

115

120

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
32.4
35.0
37.8
40.6
32.0
34.6
37.3
40.1
31.6
34.2
36.9
39.7
30.5
33.0
35.6
38.3
29.4
31.8
34.3
36.9
27.1
29.4
31.7
34.2
26.0
28.2
30.5
32.8

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
27.1
29.1
31.1
32.7*
33.6*
23.3
25.3
27.3
29.3
31.3
19.0
21.0
23.0
25.0
27.0
14.6
16.6
18.6
20.6
22.6
26.9
28.9
30.9
32.4*
33.2*
23.1
25.1
27.1
29.1
31.1
18.8
20.8
22.8
24.8
26.8
14.4
16.4
18.4
20.4
22.4
26.7
28.7
30.7
32.0*
32.9*
22.9
24.9
26.9
28.9
30.9
18.6
20.6
22.6
24.6
26.6
14.2
16.2
18.2
20.2
22.3
26.2
28.2
30.2
31.2*
32.0*
22.3
24.4
26.4
28.4
30.4
18.1
20.1
22.1
24.1
26.1
13.7
15.7
17.7
19.7
21.7
25.7
27.7
29.5*
30.3*
31.1*
21.8
23.8
25.8
27.9
29.9
17.5
19.6
21.6
23.6
25.6
13.2
15.2
17.2
19.2
21.2
24.6
26.6
27.7*
28.5*
29.2*
20.8
22.8
24.8
26.8
28.8
16.5
18.5
20.5
22.5
24.5
12.1
14.1
16.2
18.2
20.2
24.1
26.1*
26.8*
27.5*
28.2*
20.3
22.3
24.3
26.3
28.2*
16.0
18.0
20.0
22.0
24.0
11.6
13.6
15.6
17.7
19.7

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
35.5
38.2
41.1
44.0
35.0
37.7
40.5
43.4
34.5
37.1
39.9
42.8
33.2
35.8
38.5
41.2
32.0
34.5
37.0
39.7
29.5
31.8
34.2
36.7
28.2
30.5
32.8
35.2

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
32.0
34.6
36.1*
37.1*
38.0*
26.9
29.5
32.2
34.8
37.4
21.3
23.9
26.5
29.1
31.7
15.5
18.1
20.7
23.4
26.0
31.8
34.4
35.7*
36.6*
37.5*
26.7
29.3
31.9
34.5
37.2
21.0
23.7
26.3
28.9
31.5
15.3
17.9
20.5
23.1
25.8
31.5
34.2
35.3*
36.2*
37.1*
26.4
29.1
31.7
34.3
36.9
20.8
23.4
26.0
28.7
31.3
15.0
17.7
20.3
22.9
25.5
31.0
33.3*
34.3*
35.1*
36.0*
25.9
28.5
31.1
33.7
36.0*
20.2
22.9
25.5
28.1
30.7
14.5
17.1
19.7
22.3
25.0
30.4
32.3*
33.2*
34.0*
34.9*
25.3
27.9
30.5
33.2
34.9*
19.7
22.3
24.9
27.5
30.1
13.9
16.5
19.2
21.8
24.4
29.3
30.3*
31.1*
31.9*
32.7*
24.2
26.8
29.4
31.9*
32.7*
18.6
21.2
23.8
26.4
29.0
12.8
15.4
18.1
20.7
23.3
28.4*
29.2*
30.0*
30.8*
31.5*
23.6
26.3
28.9
30.8*
31.5*
18.0
20.6
23.2
25.9
28.5
12.3
14.9
17.5
20.1
22.8

COMPR.
KW
3.21
3.30
3.39
3.48
3.34
3.43
3.53
3.63
3.48
3.57
3.67
3.76
3.59
3.68
3.78
3.87
3.71
3.79
3.89
3.98
3.94
4.02
4.10
4.19
4.06
4.14
4.21
4.29

APP. DEW
PT.
47.0
50.7
54.7
58.8
47.2
50.9
55.0
59.1
47.4
51.2
55.2
59.3
48.1
51.8
55.8
59.9
48.7
52.4
56.4
60.6
49.8
53.6
57.7
61.8
50.4
54.2
58.2
62.4

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

950
X0.98
X0.94
X0.99
-1.8

1250
X1.02
X1.05
X1.01
1.4

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 37000 BTUH
AIRFLOW = 1125 CFM
APP. DEW PT. = 55.4 DEG. F
COMPRESSOR POWER = 2959 WATTS
I.D. FAN POWER = 541 WATTS
O.D. FAN POWER = 187 WATTS
S.E.E.R. = 10.48 BTUH/WATT
E.E.R. = 9.43 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TTB0536AA WITH TWE040CA4-B AT 1400 CFM


O.D.
D.B.
85

90

95

100

105

115

120

COMPR.
KW
3.21
3.30
3.40
3.50
3.36
3.45
3.55
3.65
3.50
3.60
3.69
3.80
3.61
3.71
3.80
3.90
3.72
3.81
3.91
4.01
3.95
4.04
4.12
4.22
4.07
4.15
4.23
4.32

APP. DEW
PT.
48.6
52.5
56.6
60.9
48.8
52.7
56.8
61.1
49.0
52.9
57.0
61.3
49.5
53.4
57.5
61.8
49.9
53.8
58.0
62.2
50.9
54.7
58.9
63.2
51.3
55.2
59.4
63.6

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

14

1575
X1.01
X1.06
X1.01
1.0

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 40000 BTUH
AIRFLOW = 1430 CFM
APP. DEW PT. = 57.2 DEG. F
COMPRESSOR POWER = 3114 WATTS
I.D. FAN POWER = 410 WATTS
O.D. FAN POWER = 187 WATTS
S.E.E.R. = 11.61 BTUH/WATT
E.E.R. = 10.31 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

14

TWE5_PRC002_EN_081703.PMD

1225
X0.98
X0.94
X0.99
-1.3

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Performance Data
Cooling

Metric Units

2TTB0536AA WITH TWE030CA4 AT 1868 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
9.5
10.3
11.1
11.9
9.4
10.1
10.9
11.7
9.3
10.0
10.8
11.6
8.9
9.7
10.4
11.2
8.6
9.3
10.0
10.8
7.9
8.6
9.3
10.0
7.6
8.3
8.9
9.6

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
7.9
8.5
9.1
9.6*
9.8*
6.8
7.4
8.0
8.6
9.2
5.6
6.2
6.7
7.3
7.9
4.3
4.9
5.4
6.0
6.6
7.9
8.5
9.1
9.5*
9.7*
6.8
7.4
7.9
8.5
9.1
5.5
6.1
6.7
7.3
7.9
4.2
4.8
5.4
6.0
6.6
7.8
8.4
9.0
9.4*
9.6*
6.7
7.3
7.9
8.5
9.1
5.4
6.0
6.6
7.2
7.8
4.2
4.7
5.3
5.9
6.5
7.7
8.3
8.8
9.1*
9.4*
6.5
7.1
7.7
8.3
8.9
5.3
5.9
6.5
7.1
7.6
4.0
4.6
5.2
5.8
6.4
7.5
8.1
8.6*
8.9*
9.1*
6.4
7.0
7.6
8.2
8.8
5.1
5.7
6.3
6.9
7.5
3.9
4.5
5.0
5.6
6.2
7.2
7.8
8.1*
8.4*
8.6*
6.1
6.7
7.3
7.9
8.4
4.8
5.4
6.0
6.6
7.2
3.5
4.1
4.7
5.3
5.9
7.1
7.6*
7.9*
8.1*
8.3*
5.9
6.5
7.1
7.7
8.3*
4.7
5.3
5.9
6.4
7.0
3.4
4.0
4.6
5.2
5.8

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
10.4
11.2
12.0
12.9
10.3
11.0
11.9
12.7
10.1
10.9
11.7
12.5
9.7
10.5
11.3
12.1
9.4
10.1
10.8
11.6
8.6
9.3
10.0
10.8
8.3
8.9
9.6
10.3

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
9.4
10.1
10.6*
10.9*
11.1*
7.9
8.6
9.4
10.2
11.0
6.2
7.0
7.8
8.5
9.3
4.5
5.3
6.1
6.9
7.6
9.3
10.1
10.5*
10.7*
11.0*
7.8
8.6
9.3
10.1
10.9
6.2
6.9
7.7
8.5
9.2
4.5
5.2
6.0
6.8
7.6
9.2
10.0
10.3*
10.6*
10.9*
7.7
8.5
9.3
10.0
10.8
6.1
6.9
7.6
8.4
9.2
4.4
5.2
5.9
6.7
7.5
9.1
9.8*
10.0*
10.3*
10.5*
7.6
8.4
9.1
9.9
10.5*
5.9
6.7
7.5
8.2
9.0
4.2
5.0
5.8
6.5
7.3
8.9
9.5*
9.7*
10.0*
10.2*
7.4
8.2
8.9
9.7
10.2*
5.8
6.5
7.3
8.1
8.8
4.1
4.8
5.6
6.4
7.1
8.6
8.9*
9.1*
9.3*
9.6*
7.1
7.9
8.6
9.3*
9.6*
5.4
6.2
7.0
7.7
8.5
3.8
4.5
5.3
6.1
6.8
8.3*
8.6*
8.8*
9.0*
9.2*
6.9
7.7
8.5
9.0*
9.2*
5.3
6.0
6.8
7.6
8.4
3.6
4.4
5.1
5.9
6.7

COMPR.
KW
3.2
3.3
3.4
3.5
3.3
3.4
3.5
3.6
3.5
3.6
3.7
3.8
3.6
3.7
3.8
3.9
3.7
3.8
3.9
4.0
3.9
4.0
4.1
4.2
4.1
4.1
4.2
4.3

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1613
X0.98
X0.94
X0.99

2123
X1.02
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 10.84 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 2959 WATTS
I.D. FAN POWER = 541 WATTS
O.D. FAN POWER = 187 WATTS
S.E.E.R. = 10.48 BTUH/WATT
E.E.R. = 9.43 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TTB0536AA WITH TWE040CA4-B AT 2378 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

15

COMPR.
KW
3.2
3.3
3.4
3.5
3.4
3.5
3.5
3.7
3.5
3.6
3.7
3.8
3.6
3.7
3.8
3.9
3.7
3.8
3.9
4.0
4.0
4.0
4.1
4.2
4.1
4.2
4.2
4.3

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2080
X0.98
X0.94
X0.99

2675
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 11.72 KW
AIRFLOW = 2428 CMH
COMPRESSOR POWER = 3114 WATTS
I.D. FAN POWER = 410 WATTS
O.D. FAN POWER = 187 WATTS
S.E.E.R. = 11.61 BTUH/WATT
E.E.R. = 10.31 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

15

9/15/2003, 4:38 PM

Performance Data
Cooling
English Units
2TTA0030AD WITH TWE030CA4 AT 1000 CFM
O.D.
D.B.
85

90

95

100

105

115

120

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
30.5
32.9
35.4
38.0
30.1
32.5
35.0
37.5
29.7
32.0
34.5
37.0
28.6
30.8
33.2
35.7
27.4
29.6
31.9
34.3
25.2
27.2
29.3
31.5
24.0
26.0
28.0
30.1

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
25.3
27.1
29.0
30.6*
31.4*
21.7
23.6
25.4
27.3
29.1
17.7
19.6
21.5
23.3
25.2
13.7
15.5
17.4
19.2
21.1
25.1
26.9
28.8
30.3*
31.1*
21.5
23.4
25.2
27.1
28.9
17.6
19.4
21.3
23.1
25.0
13.5
15.3
17.2
19.0
20.9
24.9
26.7
28.6
30.0*
30.8*
21.3
23.2
25.0
26.9
28.7
17.4
19.2
21.1
22.9
24.8
13.3
15.2
17.0
18.9
20.7
24.3
26.2
28.1
29.1*
29.8*
20.8
22.6
24.5
26.3
28.2
16.8
18.7
20.5
22.4
24.2
12.8
14.6
16.5
18.3
20.2
23.8
25.7
27.5*
28.2*
28.9*
20.3
22.1
24.0
25.8
27.7
16.3
18.1
20.0
21.9
23.7
12.2
14.1
15.9
17.8
19.6
22.8
24.6
25.6*
26.3*
27.0*
19.2
21.1
22.9
24.8
26.6
15.2
17.1
18.9
20.8
22.6
11.2
13.0
14.9
16.7
18.6
22.3
24.1*
24.8*
25.4*
26.0*
18.7
20.5
22.4
24.2
26.0*
14.7
16.6
18.4
20.3
22.1
10.7
12.5
14.4
16.2
18.1

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
32.5
35.0
37.5
40.2
32.0
34.4
36.9
39.5
31.5
33.9
36.4
38.9
30.3
32.6
35.0
37.4
29.0
31.3
33.6
35.9
26.6
28.6
30.7
32.9
25.4
27.3
29.3
31.4

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
27.5
29.6
31.7
33.0*
33.8*
23.3
25.5
27.6
29.7
31.8
18.8
20.9
23.0
25.1
27.2
14.2
16.3
18.4
20.5
22.6
27.2
29.3
31.4
32.6*
33.4*
23.1
25.2
27.3
29.4
31.5
18.6
20.7
22.8
24.9
27.0
13.9
16.0
18.1
20.2
22.4
27.0
29.1
31.2
32.2*
33.0*
22.9
25.0
27.1
29.2
31.3
18.3
20.4
22.6
24.7
26.8
13.7
15.8
17.9
20.0
22.1
26.4
28.5
30.4*
31.2*
31.9*
22.3
24.4
26.5
28.6
30.7
17.8
19.9
22.0
24.1
26.2
13.1
15.2
17.4
19.5
21.6
25.9
28.0
29.4*
30.2*
30.9*
21.8
23.9
26.0
28.1
30.2
17.2
19.3
21.4
23.5
25.6
12.6
14.7
16.8
18.9
21.0
24.8
26.7*
27.4*
28.1*
28.8*
20.6
22.7
24.9
27.0
28.8*
16.1
18.2
20.3
22.4
24.5
11.5
13.6
15.7
17.8
19.9
24.2
25.7*
26.4*
27.0*
27.7*
20.1
22.2
24.3
26.4
27.7*
15.6
17.7
19.8
21.9
24.0
10.9
13.0
15.2
17.3
19.4

COMPR.
KW
2.88
2.95
3.03
3.11
3.00
3.08
3.15
3.23
3.13
3.21
3.28
3.36
3.24
3.31
3.38
3.46
3.34
3.41
3.48
3.56
3.56
3.62
3.69
3.75
3.67
3.73
3.79
3.85

APP. DEW
PT.
46.4
50.5
54.5
58.6
46.9
50.7
54.7
58.9
47.2
51.0
55.0
59.1
47.9
51.6
55.7
59.9
48.5
52.3
56.4
60.6
49.8
53.6
57.7
61.9
50.4
54.2
58.4
62.6

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

875
X0.98
X0.95
X0.99
-1.6

1125
X1.02
X1.05
X1.01
1.3

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 34500 BTUH
AIRFLOW = 1000 CFM
APP. DEW PT. = 55.0 DEG. F
COMPRESSOR POWER = 2662 WATTS
I.D. FAN POWER = 437 WATTS
O.D. FAN POWER = 184 WATTS
S.E.E.R. = 11.07 BTUH/WATT
E.E.R. = 9.91 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TTA0030AD WITH TWE040CA4-B AT 1100 CFM


O.D.
D.B.
85

90

95

100

105

115

120

COMPR.
KW
2.81
2.88
2.96
3.04
2.94
3.01
3.09
3.17
3.07
3.14
3.22
3.30
3.17
3.24
3.32
3.40
3.27
3.35
3.42
3.50
3.49
3.55
3.62
3.69
3.60
3.66
3.72
3.79

APP. DEW
PT.
47.1
51.0
55.2
59.4
47.4
51.3
55.4
59.7
47.6
51.5
55.7
59.9
48.2
52.1
56.3
60.5
48.8
52.7
56.9
61.1
49.9
53.8
58.0
62.3
50.5
54.4
58.6
62.9

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

16

1250
X1.02
X1.06
X1.01
1.3

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 36500 BTUH
AIRFLOW = 1125 CFM
APP. DEW PT. = 55.9 DEG. F
COMPRESSOR POWER = 2742 WATTS
I.D. FAN POWER = 309 WATTS
O.D. FAN POWER = 184 WATTS
S.E.E.R. = 12.31 BTUH/WATT
E.E.R. = 10.90 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

16

TWE5_PRC002_EN_081703.PMD

950
X0.97
X0.93
X0.99
-1.6

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Performance Data
Cooling

Metric Units

2TTA0030AD WITH TWE030CA4 AT 1698 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
8.9
9.6
10.4
11.1
8.8
9.5
10.3
11.0
8.7
9.4
10.1
10.8
8.4
9.0
9.7
10.5
8.0
8.7
9.3
10.0
7.4
8.0
8.6
9.2
7.0
7.6
8.2
8.8

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
7.4
7.9
8.5
9.0*
9.2*
6.4
6.9
7.4
8.0
8.5
5.2
5.7
6.3
6.8
7.4
4.0
4.5
5.1
5.6
6.2
7.4
7.9
8.4
8.9*
9.1*
6.3
6.9
7.4
7.9
8.5
5.2
5.7
6.2
6.8
7.3
4.0
4.5
5.0
5.6
6.1
7.3
7.8
8.4
8.8*
9.0*
6.2
6.8
7.3
7.9
8.4
5.1
5.6
6.2
6.7
7.3
3.9
4.5
5.0
5.5
6.1
7.1
7.7
8.2
8.5*
8.7*
6.1
6.6
7.2
7.7
8.3
4.9
5.5
6.0
6.6
7.1
3.8
4.3
4.8
5.4
5.9
7.0
7.5
8.1*
8.3*
8.5*
5.9
6.5
7.0
7.6
8.1
4.8
5.3
5.9
6.4
6.9
3.6
4.1
4.7
5.2
5.7
6.7
7.2
7.5*
7.7*
7.9*
5.6
6.2
6.7
7.3
7.8
4.5
5.0
5.5
6.1
6.6
3.3
3.8
4.4
4.9
5.4
6.5
7.1*
7.3*
7.4*
7.6*
5.5
6.0
6.6
7.1
7.6*
4.3
4.9
5.4
5.9
6.5
3.1
3.7
4.2
4.7
5.3

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
9.5
10.3
11.0
11.8
9.4
10.1
10.8
11.6
9.2
9.9
10.7
11.4
8.9
9.6
10.3
11.0
8.5
9.2
9.8
10.5
7.8
8.4
9.0
9.6
7.4
8.0
8.6
9.2

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
8.1
8.7
9.3
9.7*
9.9*
6.8
7.5
8.1
8.7
9.3
5.5
6.1
6.7
7.4
8.0
4.2
4.8
5.4
6.0
6.6
8.0
8.6
9.2
9.6*
9.8*
6.8
7.4
8.0
8.6
9.2
5.4
6.1
6.7
7.3
7.9
4.1
4.7
5.3
5.9
6.6
7.9
8.5
9.1
9.4*
9.7*
6.7
7.3
7.9
8.6
9.2
5.4
6.0
6.6
7.2
7.9
4.0
4.6
5.2
5.9
6.5
7.7
8.4
8.9*
9.1*
9.3*
6.5
7.1
7.8
8.4
9.0
5.2
5.8
6.4
7.1
7.7
3.8
4.5
5.1
5.7
6.3
7.6
8.2
8.6*
8.8*
9.1*
6.4
7.0
7.6
8.2
8.8
5.0
5.7
6.3
6.9
7.5
3.7
4.3
4.9
5.5
6.2
7.3
7.8*
8.0*
8.2*
8.4*
6.0
6.7
7.3
7.9
8.4*
4.7
5.3
5.9
6.6
7.2
3.4
4.0
4.6
5.2
5.8
7.1
7.5*
7.7*
7.9*
8.1*
5.9
6.5
7.1
7.7
8.1*
4.6
5.2
5.8
6.4
7.0
3.2
3.8
4.5
5.1
5.7

COMPR.
KW
2.9
3.0
3.0
3.1
3.0
3.1
3.2
3.2
3.1
3.2
3.3
3.4
3.2
3.3
3.4
3.5
3.3
3.4
3.5
3.6
3.6
3.6
3.7
3.8
3.7
3.7
3.8
3.8

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1486
X0.98
X0.95
X0.99

1910
X1.02
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 10.11 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 2662 WATTS
I.D. FAN POWER = 437 WATTS
O.D. FAN POWER = 184 WATTS
S.E.E.R. = 11.07 BTUH/WATT
E.E.R. = 9.91 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TTA0030AD WITH TWE040CA4-B AT 1868 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

17

COMPR.
KW
2.8
2.9
3.0
3.0
2.9
3.0
3.1
3.2
3.1
3.1
3.2
3.3
3.2
3.2
3.3
3.4
3.3
3.3
3.4
3.5
3.5
3.5
3.6
3.7
3.6
3.7
3.7
3.8

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1613
X0.97
X0.93
X0.99

2123
X1.02
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 10.69 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 2742 WATTS
I.D. FAN POWER = 309 WATTS
O.D. FAN POWER = 184 WATTS
S.E.E.R. = 12.31 BTUH/WATT
E.E.R. = 10.90 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

17

9/15/2003, 4:38 PM

Performance Data
Cooling
English Units
2TTA0040AD WITH TWE040CA4-B AT 1500 CFM
O.D.
D.B.
85

90

95

100

105

115

120

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
38.5
41.4
44.4
47.5
37.9
40.8
43.7
46.8
37.3
40.1
43.0
46.1
35.8
38.5
41.3
44.2
34.2
36.8
39.5
42.3
31.1
33.5
36.0
38.5
29.5
31.8
34.2
36.6

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
34.5
37.3
39.1*
40.1*
41.0*
29.0
31.8
34.6
37.4
40.2
23.0
25.8
28.6
31.4
34.1
16.8
19.6
22.4
25.2
28.0
34.2
37.0
38.6*
39.6*
40.5*
28.8
31.6
34.3
37.1
39.9
22.7
25.5
28.3
31.1
33.9
16.5
19.3
22.1
24.9
27.7
34.0
36.8
38.1*
39.1*
40.0*
28.5
31.3
34.1
36.9
39.7
22.4
25.2
28.0
30.8
33.6
16.3
19.1
21.9
24.6
27.4
33.3
35.9*
36.8*
37.7*
38.6*
27.8
30.6
33.4
36.2
38.6*
21.7
24.5
27.3
30.1
32.9
15.6
18.4
21.2
24.0
26.7
32.6
34.6*
35.5*
36.4*
37.2*
27.1
29.9
32.7
35.4
37.2*
21.0
23.8
26.6
29.4
32.2
14.9
17.7
20.5
23.3
26.0
31.1*
32.0*
32.8*
33.6*
34.5*
25.7
28.5
31.3
33.6*
34.5*
19.6
22.4
25.2
28.0
30.8
13.5
16.3
19.1
21.9
24.7
29.8*
30.7*
31.5*
32.3*
33.0*
25.0
27.8
30.6
32.3*
33.0*
19.0
21.8
24.5
27.3
30.1
12.8
15.6
18.4
21.2
24.0

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
39.7
42.6
45.6
48.8
38.7
41.6
44.5
47.6
37.8
40.5
43.4
46.4
36.5
39.2
41.9
44.8
35.2
37.8
40.5
43.2
32.7
35.0
37.5
40.1
31.4
33.7
36.1
38.5

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
34.8
37.7
40.0*
41.0*
41.9*
29.3
32.1
34.9
37.8
40.6
23.2
26.0
28.8
31.6
34.5
17.0
19.8
22.6
25.4
28.2
34.4
37.2
39.2*
40.2*
41.1*
28.9
31.7
34.5
37.3
40.1
22.7
25.6
28.4
31.2
34.0
16.5
19.3
22.2
25.0
27.8
34.0
36.8
38.4*
39.4*
40.3*
28.4
31.2
34.1
36.9
39.7
22.3
25.1
27.9
30.8
33.6
16.1
18.9
21.7
24.5
27.4
33.4
36.2
37.4*
38.3*
39.1*
27.9
30.7
33.5
36.3
39.1
21.7
24.6
27.4
30.2
33.0
15.5
18.3
21.2
24.0
26.8
32.8
35.3*
36.3*
37.2*
38.0*
27.3
30.1
32.9
35.7
38.0*
21.2
24.0
26.8
29.6
32.4
14.9
17.8
20.6
23.4
26.2
31.7
33.3*
34.1*
34.9*
35.7*
26.2
29.0
31.8
34.6
35.7*
20.0
22.9
25.7
28.5
31.3
13.8
16.6
19.5
22.3
25.1
31.2
32.2*
33.0*
33.8*
34.6*
25.6
28.4
31.2
33.8*
34.6*
19.5
22.3
25.1
27.9
30.7
13.3
16.1
18.9
21.7
24.5

COMPR.
KW
3.58
3.71
3.84
3.97
3.74
3.88
4.01
4.16
3.91
4.04
4.19
4.34
4.04
4.18
4.33
4.48
4.16
4.31
4.47
4.62
4.42
4.58
4.74
4.91
4.55
4.71
4.88
5.05

APP. DEW
PT.
48.4
52.3
56.5
60.8
48.7
52.6
56.7
61.0
48.9
52.8
57.0
61.2
49.5
53.4
57.5
61.8
50.0
53.9
58.1
62.4
51.1
55.0
59.2
63.5
51.6
55.5
59.7
64.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

1300
X0.98
X0.94
X0.99
-1.4

1700
X1.01
X1.06
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 43000 BTUH
AIRFLOW = 1498 CFM
APP. DEW PT. = 57.0 DEG. F
COMPRESSOR POWER = 3591 WATTS
I.D. FAN POWER = 423 WATTS
O.D. FAN POWER = 175 WATTS
S.E.E.R. = 11.18 BTUH/WATT
E.E.R. = 9.86 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TTA0040AD WITH TWE050CA5-C AT 1500 CFM


O.D.
D.B.
85

90

95

100

105

115

120

COMPR.
KW
3.69
3.82
3.95
4.09
3.84
3.97
4.11
4.25
3.98
4.12
4.26
4.41
4.13
4.27
4.42
4.57
4.28
4.42
4.58
4.74
4.57
4.73
4.89
5.06
4.72
4.88
5.05
5.22

APP. DEW
PT.
48.0
51.9
56.1
60.4
48.3
52.2
56.4
60.7
48.6
52.6
56.8
61.1
49.1
53.0
57.2
61.5
49.5
53.5
57.7
62.0
50.4
54.3
58.6
62.8
50.8
54.7
59.0
63.3

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

18

1700
X1.01
X1.06
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 43500 BTUH
AIRFLOW = 1546 CFM
APP. DEW PT. = 57.1 DEG. F
COMPRESSOR POWER = 3593 WATTS
I.D. FAN POWER = 521 WATTS
O.D. FAN POWER = 175 WATTS
S.E.E.R. = 10.99 BTUH/WATT
E.E.R. = 9.63 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

18

TWE5_PRC002_EN_081703.PMD

1300
X0.98
X0.94
X0.99
-1.4

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Performance Data
Cooling

Metric Units

2TTA0040AD WITH TWE040CA4-B AT 2547 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
11.3
12.1
13.0
13.9
11.1
12.0
12.8
13.7
10.9
11.7
12.6
13.5
10.5
11.3
12.1
13.0
10.0
10.8
11.6
12.4
9.1
9.8
10.5
11.3
8.6
9.3
10.0
10.7

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
10.1
10.9
11.5*
11.7*
12.0*
8.5
9.3
10.1
11.0
11.8
6.7
7.6
8.4
9.2
10.0
4.9
5.7
6.6
7.4
8.2
10.0
10.8
11.3*
11.6*
11.9*
8.4
9.3
10.0
10.9
11.7
6.7
7.5
8.3
9.1
9.9
4.8
5.7
6.5
7.3
8.1
10.0
10.8
11.2*
11.5*
11.7*
8.4
9.2
10.0
10.8
11.6
6.6
7.4
8.2
9.0
9.8
4.8
5.6
6.4
7.2
8.0
9.8
10.5*
10.8*
11.0*
11.3*
8.1
9.0
9.8
10.6
11.3*
6.4
7.2
8.0
8.8
9.6
4.6
5.4
6.2
7.0
7.8
9.6
10.1*
10.4*
10.7*
10.9*
7.9
8.8
9.6
10.4
10.9*
6.2
7.0
7.8
8.6
9.4
4.4
5.2
6.0
6.8
7.6
9.1*
9.4*
9.6*
9.8*
10.1*
7.5
8.4
9.2
9.8*
10.1*
5.7
6.6
7.4
8.2
9.0
4.0
4.8
5.6
6.4
7.2
8.7*
9.0*
9.2*
9.5*
9.7*
7.3
8.1
9.0
9.5*
9.7*
5.6
6.4
7.2
8.0
8.8
3.8
4.6
5.4
6.2
7.0

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
11.6
12.5
13.4
14.3
11.3
12.2
13.0
13.9
11.1
11.9
12.7
13.6
10.7
11.5
12.3
13.1
10.3
11.1
11.9
12.7
9.6
10.3
11.0
11.7
9.2
9.9
10.6
11.3

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
10.2
11.0
11.7*
12.0*
12.3*
8.6
9.4
10.2
11.1
11.9
6.8
7.6
8.4
9.3
10.1
5.0
5.8
6.6
7.4
8.3
10.1
10.9
11.5*
11.8*
12.0*
8.5
9.3
10.1
10.9
11.7
6.7
7.5
8.3
9.1
10.0
4.8
5.7
6.5
7.3
8.1
10.0
10.8
11.3*
11.5*
11.8*
8.3
9.1
10.0
10.8
11.6
6.5
7.4
8.2
9.0
9.8
4.7
5.5
6.4
7.2
8.0
9.8
10.6
11.0*
11.2*
11.5*
8.2
9.0
9.8
10.6
11.5
6.4
7.2
8.0
8.8
9.7
4.5
5.4
6.2
7.0
7.9
9.6
10.3*
10.6*
10.9*
11.1*
8.0
8.8
9.6
10.5
11.1*
6.2
7.0
7.9
8.7
9.5
4.4
5.2
6.0
6.9
7.7
9.3
9.8*
10.0*
10.2*
10.5*
7.7
8.5
9.3
10.1
10.5*
5.9
6.7
7.5
8.4
9.2
4.0
4.9
5.7
6.5
7.4
9.1
9.4*
9.7*
9.9*
10.1*
7.5
8.3
9.1
9.9*
10.1*
5.7
6.5
7.4
8.2
9.0
3.9
4.7
5.5
6.4
7.2

COMPR.
KW
3.6
3.7
3.8
4.0
3.7
3.9
4.0
4.2
3.9
4.0
4.2
4.3
4.0
4.2
4.3
4.5
4.2
4.3
4.5
4.6
4.4
4.6
4.7
4.9
4.6
4.7
4.9
5.1

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2208
X0.98
X0.94
X0.99

2887
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 12.60 KW
AIRFLOW = 2544 CMH
COMPRESSOR POWER = 3591 WATTS
I.D. FAN POWER = 423 WATTS
O.D. FAN POWER = 175 WATTS
S.E.E.R. = 11.18 BTUH/WATT
E.E.R. = 9.86 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN.
SUCT. AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TTA0040AD WITH TWE050CA5-C AT 2547 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

19

COMPR.
KW
3.7
3.8
4.0
4.1
3.8
4.0
4.1
4.3
4.0
4.1
4.3
4.4
4.1
4.3
4.4
4.6
4.3
4.4
4.6
4.7
4.6
4.7
4.9
5.1
4.7
4.9
5.1
5.2

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2208
X0.98
X0.94
X0.99

2887
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 12.75 KW
AIRFLOW = 2626 CMH
COMPRESSOR POWER = 3593 WATTS
I.D. FAN POWER = 521 WATTS
O.D. FAN POWER = 175 WATTS
S.E.E.R. = 10.99 BTUH/WATT
E.E.R. = 9.63 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

19

9/15/2003, 4:38 PM

Performance Data
Cooling
English Units
2TTA0050AD WITH TWE040CA4-B AT 1500 CFM
O.D.
D.B.
85

90

95

100

105

115

120

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
46.9
50.3
53.9
57.6
46.3
49.7
53.3
56.9
45.7
49.1
52.6
56.2
44.0
47.3
50.7
54.2
42.4
45.5
48.8
52.2
39.1
42.0
45.1
48.2
37.4
40.3
43.2
46.2

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
38.6
41.4
44.2
46.9*
48.0*
33.2
36.0
38.8
41.6
44.4
27.0
29.9
32.7
35.5
38.3
20.8
23.6
26.4
29.2
32.0
38.3
41.2
44.0
46.5*
47.5*
32.9
35.7
38.5
41.3
44.1
26.8
29.6
32.4
35.2
38.0
20.5
23.3
26.1
28.9
31.7
38.1
40.9
43.7
46.0*
47.1*
32.6
35.4
38.2
41.0
43.8
26.5
29.3
32.1
34.9
37.7
20.2
23.1
25.9
28.7
31.5
37.3
40.1
42.9
44.6*
45.8*
31.8
34.6
37.4
40.2
43.0
25.7
28.5
31.3
34.1
36.9
19.5
22.3
25.1
27.9
30.7
36.5
39.3
42.1
43.3*
44.4*
31.0
33.8
36.6
39.4
42.2
24.9
27.7
30.5
33.4
36.2
18.7
21.5
24.3
27.1
29.9
35.0
37.8
39.6*
40.6*
41.6*
29.5
32.3
35.1
37.9
40.7
23.4
26.2
29.0
31.8
34.6
17.2
20.0
22.8
25.6
28.4
34.2
37.0
38.2*
39.2*
40.2*
28.7
31.5
34.3
37.1
39.9
22.6
25.4
28.3
31.1
33.9
16.4
19.2
22.1
24.9
27.7

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
49.5
53.1
56.8
60.6
48.4
51.9
55.5
59.3
47.3
50.7
54.3
57.9
46.0
49.2
52.7
56.2
44.6
47.8
51.1
54.5
41.8
44.8
47.9
51.1
40.4
43.3
46.3
49.4

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
42.8
46.1
49.5
50.7*
51.9*
36.2
39.5
42.9
46.2
49.6
28.9
32.2
35.6
38.9
42.3
21.4
24.8
28.1
31.5
34.8
42.3
45.6
48.6*
49.9*
51.0*
35.7
39.0
42.4
45.7
49.1
28.4
31.7
35.1
38.4
41.8
20.9
24.3
27.6
31.0
34.3
41.8
45.1
47.7*
48.9*
50.0*
35.2
38.5
41.9
45.2
48.6
27.9
31.2
34.6
37.9
41.3
20.4
23.8
27.1
30.5
33.8
41.2
44.5
46.6*
47.8*
48.8*
34.5
37.9
41.2
44.6
47.9
27.2
30.6
33.9
37.3
40.6
19.8
23.1
26.5
29.8
33.2
40.5
43.9
45.4*
46.6*
47.6*
33.9
37.3
40.6
43.9
47.3
26.6
29.9
33.3
36.6
40.0
19.2
22.5
25.8
29.2
32.5
39.3
42.1*
43.2*
44.2*
45.1*
32.6
36.0
39.3
42.7
45.1*
25.3
28.7
32.0
35.4
38.7
17.9
21.2
24.6
27.9
31.3
38.7
40.9*
42.0*
42.9*
43.9*
32.0
35.4
38.7
42.1
43.9*
24.7
28.1
31.4
34.7
38.1
17.3
20.6
24.0
27.3
30.7

COMPR.
KW
4.44
4.58
4.74
4.89
4.64
4.79
4.95
5.11
4.84
5.00
5.16
5.32
5.01
5.16
5.33
5.49
5.18
5.33
5.50
5.66
5.52
5.68
5.84
6.00
5.70
5.85
6.01
6.17

APP. DEW
PT.
46.1
50.3
54.5
58.7
46.4
50.6
54.7
58.9
47.0
50.8
55.0
59.2
47.6
51.5
55.6
59.9
48.3
52.1
56.3
60.5
49.5
53.4
57.6
61.8
50.1
54.0
58.2
62.4

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

1300
X0.97
X0.94
X0.98
-1.8

1700
X1.02
X1.05
X1.01
1.4

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 52500 BTUH
AIRFLOW = 1494 CFM
APP. DEW PT. = 54.9 DEG. F
COMPRESSOR POWER = 4475 WATTS
I.D. FAN POWER = 464 WATTS
O.D. FAN POWER = 217 WATTS
S.E.E.R. = 11.01 BTUH/WATT
E.E.R. = 9.79 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TTA0050AD WITH TWE050CA5-C AT 1800 CFM


O.D.
D.B.
85

90

95

100

105

115

120

COMPR.
KW
4.81
4.96
5.12
5.28
5.00
5.15
5.31
5.48
5.19
5.34
5.51
5.68
5.38
5.54
5.70
5.87
5.57
5.73
5.89
6.07
5.95
6.11
6.28
6.45
6.15
6.31
6.47
6.64

APP. DEW
PT.
47.6
51.5
55.7
60.0
47.9
51.9
56.1
60.4
48.3
52.2
56.4
60.7
48.7
52.6
56.9
61.2
49.1
53.1
57.3
61.6
49.9
53.9
58.1
62.4
50.4
54.3
58.6
62.9

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

20

2025
X1.01
X1.05
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 54000 BTUH
AIRFLOW = 1750 CFM
APP. DEW PT. = 56.1 DEG. F
COMPRESSOR POWER = 4533 WATTS
I.D. FAN POWER = 731 WATTS
O.D. FAN POWER = 217 WATTS
S.E.E.R. = 10.54 BTUH/WATT
E.E.R. = 9.34 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

20

TWE5_PRC002_EN_081703.PMD

1575
X0.99
X0.95
X0.99
-1.4

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Performance Data
Cooling

Metric Units

2TTA0050AD WITH TWE040CA4-B AT 2547 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
13.7
14.7
15.8
16.9
13.6
14.6
15.6
16.7
13.4
14.4
15.4
16.5
12.9
13.9
14.9
15.9
12.4
13.3
14.3
15.3
11.5
12.3
13.2
14.1
11.0
11.8
12.7
13.5

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
11.3
12.1
13.0
13.7*
14.1*
9.7
10.5
11.4
12.2
13.0
7.9
8.8
9.6
10.4
11.2
6.1
6.9
7.7
8.6
9.4
11.2
12.1
12.9
13.6*
13.9*
9.6
10.5
11.3
12.1
12.9
7.9
8.7
9.5
10.3
11.1
6.0
6.8
7.6
8.5
9.3
11.2
12.0
12.8
13.5*
13.8*
9.6
10.4
11.2
12.0
12.8
7.8
8.6
9.4
10.2
11.0
5.9
6.8
7.6
8.4
9.2
10.9
11.7
12.6
13.1*
13.4*
9.3
10.1
11.0
11.8
12.6
7.5
8.4
9.2
10.0
10.8
5.7
6.5
7.4
8.2
9.0
10.7
11.5
12.3
12.7*
13.0*
9.1
9.9
10.7
11.5
12.4
7.3
8.1
8.9
9.8
10.6
5.5
6.3
7.1
7.9
8.8
10.3
11.1
11.6*
11.9*
12.2*
8.6
9.5
10.3
11.1
11.9
6.9
7.7
8.5
9.3
10.1
5.0
5.9
6.7
7.5
8.3
10.0
10.8
11.2*
11.5*
11.8*
8.4
9.2
10.0
10.9
11.7
6.6
7.4
8.3
9.1
9.9
4.8
5.6
6.5
7.3
8.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
14.5
15.6
16.6
17.8
14.2
15.2
16.3
17.4
13.9
14.9
15.9
17.0
13.5
14.4
15.4
16.5
13.1
14.0
15.0
16.0
12.2
13.1
14.0
15.0
11.8
12.7
13.6
14.5

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
12.5
13.5
14.5
14.9*
15.2*
10.6
11.6
12.6
13.5
14.5
8.5
9.4
10.4
11.4
12.4
6.3
7.3
8.2
9.2
10.2
12.4
13.4
14.2*
14.6*
14.9*
10.5
11.4
12.4
13.4
14.4
8.3
9.3
10.3
11.3
12.2
6.1
7.1
8.1
9.1
10.0
12.2
13.2
14.0*
14.3*
14.6*
10.3
11.3
12.3
13.2
14.2
8.2
9.1
10.1
11.1
12.1
6.0
7.0
7.9
8.9
9.9
12.1
13.0
13.7*
14.0*
14.3*
10.1
11.1
12.1
13.1
14.0
8.0
9.0
9.9
10.9
11.9
5.8
6.8
7.8
8.7
9.7
11.9
12.9
13.3*
13.7*
13.9*
9.9
10.9
11.9
12.9
13.9
7.8
8.8
9.8
10.7
11.7
5.6
6.6
7.6
8.6
9.5
11.5
12.3*
12.7*
13.0*
13.2*
9.6
10.5
11.5
12.5
13.2*
7.4
8.4
9.4
10.4
11.3
5.2
6.2
7.2
8.2
9.2
11.3
12.0*
12.3*
12.6*
12.9*
9.4
10.4
11.3
12.3
12.9*
7.2
8.2
9.2
10.2
11.2
5.1
6.0
7.0
8.0
9.0

COMPR.
KW
4.4
4.6
4.7
4.9
4.6
4.8
4.9
5.1
4.8
5.0
5.2
5.3
5.0
5.2
5.3
5.5
5.2
5.3
5.5
5.7
5.5
5.7
5.8
6.0
5.7
5.8
6.0
6.2

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2208
X0.97
X0.94
X0.98

2887
X1.02
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 15.38 KW
AIRFLOW = 2537 CMH
COMPRESSOR POWER = 4475 WATTS
I.D. FAN POWER = 464 WATTS
O.D. FAN POWER = 217 WATTS
S.E.E.R. = 11.01 BTUH/WATT
E.E.R. = 9.79 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TTA0050AD WITH TWE050CA5-C AT 3057 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

21

COMPR.
KW
4.8
5.0
5.1
5.3
5.0
5.2
5.3
5.5
5.2
5.3
5.5
5.7
5.4
5.5
5.7
5.9
5.6
5.7
5.9
6.1
5.9
6.1
6.3
6.4
6.2
6.3
6.5
6.6

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2675
X0.99
X0.95
X0.99

3439
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 15.82 KW
AIRFLOW = 2972 CMH
COMPRESSOR POWER = 4533 WATTS
I.D. FAN POWER = 731 WATTS
O.D. FAN POWER = 217 WATTS
S.E.E.R. = 10.54 BTUH/WATT
E.E.R. = 9.34 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

21

9/15/2003, 4:38 PM

Performance Data
Cooling
English Units
2TTA0060AD WITH TWE050CA5-C AT 1800 CFM
O.D.
D.B.
85

90

95

100

105

115

120

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
55.2
59.3
63.5
67.9
54.3
58.3
62.4
66.7
53.3
57.2
61.3
65.5
52.0
55.8
59.8
63.9
50.7
54.4
58.3
62.4
48.1
51.7
55.4
59.2
46.8
50.3
53.9
57.6

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
45.5
48.9
52.2
55.4*
56.6*
39.0
42.3
45.7
49.0
52.4
31.7
35.0
38.4
41.7
45.1
24.2
27.6
30.9
34.3
37.6
45.1
48.4
51.8
54.6*
55.9*
38.5
41.9
45.2
48.6
51.9
31.2
34.6
37.9
41.3
44.6
23.8
27.1
30.5
33.8
37.2
44.6
48.0
51.3
53.8*
55.1*
38.1
41.4
44.8
48.1
51.5
30.8
34.1
37.5
40.8
44.2
23.3
26.7
30.0
33.4
36.7
44.0
47.4
50.7
52.8*
54.1*
37.4
40.8
44.1
47.5
50.8
30.2
33.5
36.9
40.2
43.6
22.7
26.1
29.4
32.8
36.1
43.4
46.8
50.1
51.7*
53.0*
36.8
40.2
43.5
46.9
50.2
29.6
32.9
36.3
39.6
43.0
22.1
25.5
28.8
32.2
35.5
42.2
45.6
48.4*
49.7*
50.8*
35.6
39.0
42.3
45.7
49.0
28.4
31.7
35.1
38.4
41.8
20.9
24.3
27.6
31.0
34.3
41.6
45.0
47.3*
48.6*
49.7*
35.0
38.4
41.7
45.1
48.4
27.8
31.1
34.5
37.8
41.2
20.3
23.7
27.0
30.4
33.7

COMPR.
KW
5.23
5.33
5.43
5.53
5.50
5.61
5.72
5.83
5.77
5.89
6.01
6.14
6.08
6.21
6.35
6.49
6.38
6.53
6.68
6.84
6.96
7.15
7.35
7.56
7.24
7.46
7.69
7.92

APP. DEW
PT.
46.1
50.3
54.4
58.7
46.8
50.6
54.8
59.0
47.1
50.9
55.1
59.3
47.5
51.4
55.5
59.8
47.9
51.8
56.0
60.2
48.7
52.6
56.8
61.1
49.1
53.0
57.2
61.5

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

1575
X0.98
X0.95
X0.99
-1.7

2025
X1.01
X1.05
X1.01
1.3

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 61000 BTUH
AIRFLOW = 1750 CFM
APP. DEW PT. = 54.8 DEG. F
COMPRESSOR POWER = 5033 WATTS
I.D. FAN POWER = 731 WATTS
O.D. FAN POWER = 224 WATTS
S.E.E.R. = 11.08 BTUH/WATT
E.E.R. = 9.76 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL

Performance Data
Cooling

Metric Units

2TTA0060AD WITH TWE050CA5-C AT 3057 CMH


O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

48.9

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
16.2
17.4
18.6
19.9
15.9
17.1
18.3
19.5
15.6
16.8
18.0
19.2
15.2
16.3
17.5
18.7
14.9
15.9
17.1
18.3
14.1
15.1
16.2
17.3
13.7
14.7
15.8
16.9

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
13.3
14.3
15.3
16.2*
16.6*
11.4
12.4
13.4
14.4
15.4
9.3
10.3
11.3
12.2
13.2
7.1
8.1
9.1
10.0
11.0
13.2
14.2
15.2
16.0*
16.4*
11.3
12.3
13.2
14.2
15.2
9.1
10.1
11.1
12.1
13.1
7.0
7.9
8.9
9.9
10.9
13.1
14.1
15.0
15.8*
16.1*
11.2
12.1
13.1
14.1
15.1
9.0
10.0
11.0
12.0
13.0
6.8
7.8
8.8
9.8
10.8
12.9
13.9
14.9
15.5*
15.9*
11.0
12.0
12.9
13.9
14.9
8.8
9.8
10.8
11.8
12.8
6.7
7.6
8.6
9.6
10.6
12.7
13.7
14.7
15.1*
15.5*
10.8
11.8
12.7
13.7
14.7
8.7
9.6
10.6
11.6
12.6
6.5
7.5
8.4
9.4
10.4
12.4
13.4
14.2*
14.6*
14.9*
10.4
11.4
12.4
13.4
14.4
8.3
9.3
10.3
11.3
12.2
6.1
7.1
8.1
9.1
10.0
12.2
13.2
13.9*
14.2*
14.6*
10.3
11.3
12.2
13.2
14.2
8.1
9.1
10.1
11.1
12.1
5.9
6.9
7.9
8.9
9.9

COMPR.
KW
5.2
5.3
5.4
5.5
5.5
5.6
5.7
5.8
5.8
5.9
6.0
6.1
6.1
6.2
6.3
6.5
6.4
6.5
6.7
6.8
7.0
7.2
7.3
7.6
7.2
7.5
7.7
7.9

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

22

3439
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 17.87 KW
AIRFLOW = 2972 CMH
COMPRESSOR POWER = 5033 WATTS
I.D. FAN POWER = 731 WATTS
O.D. FAN POWER = 224 WATTS
S.E.E.R. = 11.08 BTUH/WATT
E.E.R. = 9.76 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

22

TWE5_PRC002_EN_081703.PMD

2675
X0.98
X0.95
X0.99

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Performance
Data
Evaporator Fan Performance
Blower Performance TWE030CA40B Wet Coil

CFM
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200

CMH
1018.8
1103.7
1188.6
1273.5
1358.4
1443.3
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6

0.89
0.81
0.72
0.63
0.53
0.42
0.31
0.20
0.08

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)


UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
220 VOLTS
Hl
MED
LO
Hl
MED
LO
0.72 (179.4)
0.71 (176.9)
0.62 (154.4)
0.61 (152.0)
0.86 (214.2)
0.51 (127.0)
0.84 (209.2)
0.50 (124.6)
0.75 (186.8)
0.40
(99.6)
0.72 (179.4)
0.39
(97.1)
(221.7)
0.65 (161.9)
0.29
(72.2)
0.87 (216.7)
0.62 (154.4)
0.28
(69.7)
(201.8)
0.54 (134.5)
0.18
(44.8)
0.79 (196.8)
0.51 (127.0)
0.17
(42.3)
(179.4)
0.43 (107.1)
0.06
(14.9)
0.69 (171.9)
0.40
(99.6)
0.08
(19.9)
(156.9)
0.32
(79.7)
0.61 (152.0)
0.30
(74.7)
(132.0)
0.21
(52.3)
0.51 (127.0)
0.17
(42.3)
(104.6)
0.10
(24.9)
0.40
(99.6)
0.02
(5.0)
(77.2)
0.31
(77.2)
(49.8)
0.22
(54.8)
(19.9)
0.10
(24.9)

NOTES:
Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

Blower Performance TWE040CA40C Wet Coil

CFM
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500

CMH
1188.6
1273.5
1358.4
1443.3
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6
2122.5
2207.4
2292.3
2377.2
2462.1
2547.0

0.61
0.57
0.53
0.49
0.45
0.40
0.36
0.31
0.26
0.21
0.17
0.11
0.06
0.01
0.00

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)


UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
220 VOLTS
Hl
MED
LO
Hl
MED
LO
0.58 (144.5)
0.61 (152.0)
0.55 (137.0)
(152.0)
0.58 (144.5)
0.52 (129.5)
0.58 (144.5)
(142.0)
0.54 (134.5)
0.48 (119.6)
0.52 (129.5)
(132.0)
0.51 (127.0)
0.44 (109.6)
0.49 (122.1)
(122.1)
0.47 (117.1)
0.40
(99.6)
0.57 (142.0)
0.45 (112.1)
(112.1)
0.43 (107.1)
0.34
(84.7)
0.53 (132.0)
0.50 (124.6)
0.40
(99.6)
(99.6)
0.38
(94.7)
0.28
(69.7)
0.48 (119.6)
0.45 (112.1)
0.35
(87.2)
(89.7)
0.34
(84.7)
0.22
(54.8)
0.43 (107.1)
0.40
(99.6)
0.30
(74.7)
(77.2)
0.29
(72.2)
0.15
(37.4)
0.39
(97.1)
0.37
(92.2)
0.22
(54.8)
(64.8)
0.24
(59.8)
0.08
(19.9)
0.35
(87.2)
0.32
(79.7)
0.17
(42.3)
(52.3)
0.18
(44.8)
0.00
(0.0)
0.31
(77.2)
0.28
(69.7)
0.10
(24.9)
(42.3)
0.13
(32.4)
0.26
(64.8)
0.22
(54.8)
0.01
(2.5)
(27.4)
0.07
(17.4)
0.21
(52.3)
0.18
(44.8)
(14.9)
0.01
(2.5)
0.15
(37.4)
0.12
(29.9)
(2.5)
0.11
(27.4)
0.08
(19.9)
0.05
(12.5)
0.02
(5.0)

NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

23

23

9/15/2003, 4:38 PM

Performance
Data
Evaporator Fan Performance
Blower Performance TWE050CA50D Wet Coil

CFM
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950

CMH
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6
2122.5
2207.4
2292.3
2377.2
2462.1
2547.0
2631.9
2716.8
2801.7
2886.6
2971.5
3056.4
3141.3
3226.2
3311.1

Hl

0.59
0.56
0.52
0.48
0.44
0.40
0.35
0.31
0.26
0.21
0.16
0.11
0.05

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)


UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
220 VOLTS
MED
LO
Hl
MED

0.61
0.57
0.53
0.49
0.45
0.40
0.35
0.30
0.25
0.20
0.14
0.08
0.02

(147.0)
(139.5)
(129.5)
(119.6)
(109.6)
(99.6)
(87.2)
(77.2)
(64.8)
(52.3)
(39.9)
(27.4)
(12.5)

0.63
0.61
0.58
0.54
0.50
0.45
0.39
0.33
0.26
0.18
0.10
0.01

(152.0)
(142.0)
(132.0)
(122.1)
(112.1)
(99.6)
(87.2)
(74.7)
(62.3)
(49.8)
(34.9)
(19.9)
(5.0)

(156.9)
(152.0)
(144.5)
(134.5)
(124.6)
(112.1)
(97.1)
(82.2)
(64.8)
(44.8)
(24.9)
(2.5)

0.62
0.59
0.56
0.52
0.49
0.47
0.45
0.41
0.36
0.30
0.24
0.17
0.10
0.02

(154.4)
(147.0)
(139.5)
(129.5)
(122.1)
(117.1)
(112.1)
(102.1)
(89.7)
(74.7)
(59.8)
(42.3)
(24.9)
(5.0)

0.64
0.61
0.58
0.55
0.52
0.48
0.44
0.40
0.35
0.28
0.20
0.13
0.07
0.01

(159.4)
(152.0)
(144.5)
(137.0)
(129.5)
(119.6)
(109.6)
(99.6)
(87.2)
(69.7)
(49.8)
(32.4)
(17.4)
(2.5)

LO

0.62
0.60
0.57
0.53
0.49
0.44
0.38
0.32
0.25
0.18
0.11
0.00

(154.4)
(149.5)
(142.0)
(132.0)
(122.1)
(109.6)
(94.7)
(79.7)
(62.3)
(44.8)
(27.4)
(0.0)

NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G (12.5) for horizontal left.

Air Pressure Drop (Inches) Electric Heaters


Pressure Drop For Electric Heaters In Air Handler Models

1
AIRFLOW
CFM
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000

AIRFLOW
CMH
1018.8
1188.6
1358.4
1528.2
1698.0
1867.8
2037.6
2207.4
2377.2
2547.0
2716.8
2886.6
3056.4
3226.2
3396.0

0.01
0.01
0.02
0.03
0.04
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14

(2.5)
(2.5)
(5.0)
(7.5)
(10.0)
(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(22.4)
(24.9)
(27.4)
(32.4)
(34.9)

0.02
0.02
0.03
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.15
0.17

NUMBER OF RACKS
3
AIR PRESSURE DROP
IN. W.G. (PASCALS)
(5.0)
0.02
(5.0)
(5.0)
0.02
(5.0)
(7.5)
0.03
(7.5)
(7.5)
0.04
(10.0)
(10.0)
0.05
(12.5)
(12.5)
0.06
(14.9)
(14.9)
0.07
(17.4)
(17.4)
0.08
(19.9)
(19.9)
0.10
(24.9)
(22.4)
0.11
(27.4)
(24.9)
0.12
(29.9)
(27.4)
0.14
(34.9)
(32.4)
0.16
(39.9)
(37.4)
0.18
(44.8)
(42.3)
0.20
(49.8)

0.04
0.05
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.19
0.21
0.23

(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(22.4)
(27.4)
(32.4)
(37.4)
(42.3)
(47.3)
(52.3)
(57.3)

0.08
0.09
0.11
0.13
0.15
0.17
0.19
0.21
0.23
0.26

(19.9)
(22.4)
(27.4)
(32.4)
(37.4)
(42.3)
(47.3)
(52.3)
(57.3)
(64.8)

NOTES:
1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
2. Heater model numbers may have additional suffix digits.

24

TWE5_PRC002_EN_081703.PMD

24

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Minimum Airflow (CFM)


Heater Matrix
THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.

A Heater Matrix for All TWE


MINIMUM HEATING AIRFLOW CFM HEATER MATRIX
AIR
HANDLER

HEATER MODEL NUMBER BAYHTR

MODEL
NUMBER

1405 000
BRK
PDC
4.80kw

1408 000
BRK
PDC
7.68kw

1410 000
BRK
PDC
3410 000
9.60kw

1415 BRK
15.36kw

3415 000
15.36kw

1419 BRK
19.20kw

1425 BRK
24.96kw

NUMBER OF
HEATER RACKS

NUMBER OF
CIRCUITS

TWE030C

L/L

L/L

L/L

L/L

L/L

TWE040C

L/L

L/L

L/L

L/L

L/L

L/H

L/H

TWE050C

L/L

L/L

L/L

L/L

L/L

L/H

L/H

000 = Pigtails, BRK = Contains circuit breakers, PDC = Contains Pull Disconnect
RBR = Contains recessed circuit breaker (for 14" deep TVF018-024 Models only)
RPD = contains recessed pull disconnect (for 14" deep TV0F18-024 Models only)
* For upflow position only minimum setting is 1200

(Example: L=Low, M=Medium, H=High Speed)


Cooling/Heat Pump Air Flow
AS = Heater application is affected based on whether the outdoor unit is
a heat pump or cooling unit.
PS = Minimum speed tap varies based on air handler installation position.

CAUTION: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local electrical codes.

HEATER RACKS
HEATER
NO. OF
MODEL NO.
RACKS
BAY96X1405
1
BAY96X1406
2
BAY96X1408
2
BAY96X1410
2
BAY96X1411
3
BAY96X1415
3
BAY96X1419
4
BAY96X1421
4
BAY96X1426
5
BAY96X3411
3
BAY96X3415
3

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

25

25

9/15/2003, 4:38 PM

Electrical
Data
TTB0520 System Wiring Diagram

Legend

Symbols

From Dwg. 21D150992 P01


26

TWE5_PRC002_EN_081703.PMD

26

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Electrical
Data
2TTB0524-0536AA System Wiring Diagram
Legend

Symbols

NOTES:
1. IF ODT-B IS NOT USED, ADD JUMPER BETWEEN W2 & W3
AT AIR HANDLER.
IF USED, ODT-B MUST BE MOUNTED REMOTE OF
CONTROL BOX IN AN APPROVED WEATHER PROOF
ENCLOSURE.
2. IF ODT-A IS NOT USED, ADD JUMPER BETWEEN W1 & W2
AT AIR HANDLER.

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

27

27

9/15/2003, 4:38 PM

Electrical
Data
2TTA0030-060AD System Wiring Diagram
Legend

Symbols

NOTES:
1. IF ODT-B IS NOT USED, ADD JUMPER
BETWEEN W2 & W3 AT AIR HANDLER.
IF USED, ODT-B MUST BE MOUNTED
REMOTE OF CONTROL BOX IN AN
APPROVED WEATHER PROOF
ENCLOSURE.
2. IF ODT-A IS NOT USED, ADD JUMPER
BETWEEN W1 & W2 AT AIR HANDLER.
3. LOW VOLTAGE (24 V.) FIELD WIRING
MUST BE 18 AWG MIN.

28

TWE5_PRC002_EN_081703.PMD

28

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Electrical
Data
TWE030-050C System Wiring Diagram
Legend

Symbols

NOTES:
1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION
2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC SPEED
CHANGE FOR HEATING/COOLING OPERATION IS DESIRED.
3. A 220V HIGH VOLTAGE CONTROL IN TTB5-C/2TTB05-A NEEDS TO BE
CHANGED WITH 24V LOW VOLTAGE CONTROL KIT (ACYLVCR006A)
WHEN MATCHED WITH TWE-C AIR HANDLING UNITS.

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

29

29

9/15/2003, 4:38 PM

Dimensions
TWE030-050C Outline Drawing
ALL DIMENSIONS ARE IN INCHES (MM)

SIDES
FRONT
BACK
INLET DUCT
OUTLET DUCT

MINIMUM UNIT CLEARANCE SALE


TO COMBUSTIBLE
SERVICE CLEARANCE
MATERIAL (REQUIRED)
(RECOMMENDED)
0
(0)
2
(50.8)
0
(0)
21
(533.4)
0
(0)
0
(0)
0
(0)
1
(25.4)
1
(25.4)

MODEL NO.
TWE030CA4
TWE040CA4
TWE050CA5

A
B
43.00
15.57
(1092.2) (395.5)
51.75
24.32
(1134.5) (617.7)
57.90
30.47
(1470.7) (773.9)

C
21.50
(761.1)
23.50
(596.9)
23.50
(596.9)

30

TWE5_PRC002_EN_081703.PMD

30

D
E
F
19.50
20.28
21.63
(495.3) (515.1) (549.4)
21.50
22.28
23.63
(761.1) (565.9) (600.2)
21.50
22.28
23.63
(761.1) (565.9) (600.2)

FLOW
CONTROL

FCCV
FCCV
TXV

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Dimensions
TTB520CA Outline Drawing
All dimensions are in inches (mm)

1 INCH = (25.40 MILLIMETERS)


PT. NO.
A
B
1
P02
11/16
/2
14 UNS-2A
20UNF-2A

C
/4
(19)
3

D
/16
(8)

FLARE NUT TORQUE


TORQUE FT-LBS (NEWTON METERS)
APPLIED TUBE SIZE
1
/4 (6.35)

MINIMUM
8 (11.0)

MAXIMUM
10 (14.0)

/16 (7.94)
/8 (9.52)

10 (14.0)
15 (20.0)

15 (20.0)
25 (34.0)

/2 (12.70)
/8 (15.88)

25 (34.0)
40 (54.0)

35 (47.0)
55 (75.0)

/4 (19.05)

50 (68.0)

60 (81.0)

3
1
5
3

BACK-UP
HEX SIZE
7
/8 - 14 = 7/8
(22)
7
/16 - 20 = 7/16
(11)
11/16 - 14 = 11/16
(27)
1
/2 - 20 = 1/2
(13)

From Dwg. 21D151122 Rev. 0


TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

31

31

9/15/2003, 4:38 PM

Dimensions
2TTB0524-536AA Outline Drawing
All dimensions are in inches (mm)

MODELS

BASE FIG.

2TTB0524AA

561 (25-5/8) 724 (28-1/2) 651 (25-5/8) 3/4 5/16

127 (5)

57 (2-1/4) 181 (7-1/8) 44 (1-3/4)

457 (18)

1-1/1614 UNF- 2A 1/220 UNF- 2A

2TTB0530AA

561 (25-5/8) 724 (28-1/2) 651 (25-5/8) 3/4 5/16

127 (5)

57 (2-1/4) 181 (7-1/8) 44 (1-3/4)

457 (18)

1-1/1614 UNF- 2A 1/220 UNF- 2A

2TTB0536AA

730 (28-3/4) 724 (28-1/2) 651 (25-5/8) 3/4 5/16 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4)

457 (18)

1-1/1614 UNF- 2A 1/220 UNF- 2A


From Dwg. 21D153509 Rev. 1

32

TWE5_PRC002_EN_081703.PMD

32

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Dimensions
2TTA0030-060AD Outline Drawing
All dimensions are in inches (mm)

MODELS

BASE FIG.

D
7/8

2TTA0030AD

730 (28-3/4) 724 (28-1/2) 651(25-5/8)

3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18)

2TTA0040AD

730 (28-3/4) 724 (28-1/2) 651(25-5/8) 1-1/8 3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18)

2TTA0050AD

832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 1-1/8 3/8 143 (5-5/8) 92 (3-5/8) 210 (8-1/4) 79 (3-1/8) 508 (20)

2TTA0060AD

1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8

152 (6)

98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)


From Dwg. 21D153074 Rev. 5

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

33

33

9/15/2003, 4:38 PM

Convertibility
TWE030 Through 050 Convertibility
Six (6) Way Convertibility

One Unit - 4 Applications

Easy Conversion to Opposite Side Access

34

TWE5_PRC002_EN_081703.PMD

34

TWE5-PRC002-EN-08-17-03

9/15/2003, 4:38 PM

Mechanical
Specification Options
Condensing Units
General
The unit shall be fully charged from the
factory for matched indoor section and up
to 15 feet of piping. This unit must be
designed to operate at outdoor ambient
temperatures as high as 115F. Cooling
capacities shall be matched with a wide
selection of air handlers. Exterior must be
designed for outdoor application.
Casing
Unit casing is constructed of heavy
gauge, galvanized steel and painted with
a weather-resistant powder paint.
Corrosion and weatherproof CMBP-G30
Duratuff base.(2TTB/2TTA)
Refrigerant Controls
Refrigeration system controls include
condenser fan and compressor
contactor. High and low pressure controls
are inherent to the compressor. Another
standard feature is the liquid line dryer.
Compressor
The Climatuff compressor features
internal over temperature and pressure
protector, total dipped hermetic motor
and thermostatically controlled sump
heater. Other features include: roto lock
suction and discharge refrigeration
connections, centrifugal oil pump, and
low vibration and noise.

TWE5-PRC002-EN-08-17-03

TWE5_PRC002_EN_081703.PMD

35

Condenser Coil
The Spine Fin coil shall be continuously
wrapped, corrosion resistant all aluminum with minimum brazed joints. This
coil is 3/8 inch O.D. seamless aluminum
glued to a continuous aluminum fin. Coils
are lab tested to withstand 2,000 pounds
of pressure per square inch. The outdoor
coil provides low airflow resistance and
efficient heat transfer. The coil is protected on all four sides by louvered
panels and has a 10 year limited warranty.
Low Ambient Cooling
As manufactured, this unit has a cooling
capability to 55F. The addition of an
evaporator defrost control permits
operation to 40F. The addition of an
evaporator defrost control with TXV
permits low ambient cooling to 30F.
Accessories
Thermostats Heating/Cooling
(manual and automatic changeover).
Sub-base to match thermostat and
locking thermostat cover.
Evaporator Defrost Control See Low
Ambient Cooling.
Outdoor Thermostat Supplemental
heat outdoor ambient lockout from
46 to 10F.

35

9/15/2003, 4:38 PM

Mechanical
Specification Options
Air Handling Units
General
Blower coil units shall be completely
factory assembled including coil, condensate drain pan, fan, motor, filters and
controls in an insulated casing that can
be applied in horizontal or vertical
configuration.
This new line of TWE-C air handlers
provides exclusive compact size combined with simple four-way convertibility
in three sizes. The unit ships in the right
hand horizontal configuration and
converts to vertical upflow just by
standing the unit on end. No tools
required. Simple coil rotation provides
downflow and horizontal left applications.
The four-way convertibility provides you
inventory benefits and service/installation
flexibility. The simple conversion provides
opposite side access for installation
and service.
Casing
Units shall have rugged sheet metal and
steel frame construction and shall be
painted with an enamel finish. Casing
shall be insulated and knockouts shall
be provided for electrical power and
control wiring.

Refrigerant Circuits
The TWE units shall have a single
refrigerant circuit. TWE03-040C refrigerant circuit shall be controlled by a flow
control check valve (FCCV). The
TWE050C refrigerant circuit shall be
controlled by a factory-installed thermal
expansion valve.
Coil
Aluminum fin surface shall be mechanically bonded to 3/8-inch OD copper
tubing. Coils shall be factory pressure
and leak tested.
Fan
Forward curved, dynamically and
statically balanced with three-speed
direct drive shall be standard, fan motor
bearing shall be permanently lubricated.
Controls
Fan contactor, and plug-in module for
accessory electric heat control shall be
included. TWE models shall also include
check valves.
Filters
Filters shall be included as standard.
Accessories
Electric Heaters Shall be available in
a wide range of capacities and voltages
with various staging options and plug in
control wiring. Heaters shall fit inside
internal compartment.

P.I.

Trane
A business of
American Standard Companies
www.trane.com

TWE5_PRC002_EN_081703.PMD

36

Trane has a policy of continuous product and product data improvement and it reserves the right to change
design and specifications without notice.

9/15/2003, 4:38 PM

Split System
Heat Pump Product
& Performance Data
50 Hz

Air Handler Models

Condensing Models

TWE030CA
TWE040CA
TWE050CA

2TWB0012-036AA
2TWA0030-060AD

PUB. NO. TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

9/15/2003, 3:07 PM

General
Features
Split System Heat Pump Units . . .
The Evolution Continues
2TWB0/2TWA0 split systems represent
a product that is not only an engineers
dream, it's also a customers dream.
The design teams mission and accomplishment is enhanced performance
and efficiency, improved reliability and
durability, and improved installability
and serviceability.

technology, and customer research to


develop the next generation of leadership
outdoor products.
Couple the Trane reputation for reliability
and durability with the above mentioned
mission and accomplishments and you
continue to have systems that prove
Its Hard to Stop a Trane.

Tranes experienced design team applied


six sigma principles, the latest computer

2003 American Standard Inc. All Rights Reserved

TWE5_PRC001_EN_081703.PMD

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Contents

General Features

Features and Benefits

Condensing Units
Air Handling Units
Optional Equipment
Low Outdoor Ambient Cooling

Selection Procedure

Model Number Nomenclature for Condensing Units


Model Number Nomenclature for Air Handlers

General Data

7
7
7
7
8
8
8
8
8
9
9
9
9

Performance Data

10

10
16
20
26
30
32

Minimum Airflow (CFM) Heater Matrix

33

Electrical Data

34

Dimensions

37

Convertibility

40

Mechanical Specification Options

41

Condensing Units
Air Handling Units

TWE5_PRC001_EN_081703.PMD

6
6

TWE030CA40B
TWE040CA40C
TWE050CA50D
2TWB0012AA000A
2TWB0018AA000A
2TWB0024AA000A
2TWB0030AA000A
2TWB0036AA000A
2TWA0030AD000A
2TWA0040AD000A
2TWA0050AD000A
2TWA0060AD000A

2TWB/TWE Cooling
2TWA/TWE Cooling
2TWB/TWE Heating
2TWA/TWE Heating
Evaporator Fan Performance
Air Pressure Drop

TWE5-PRC001-EN-08-17-03

4
4
5
5

41
42

9/15/2003, 3:07 PM

Features and
Benefits
Condensing Units
(2TWB00_AA, 2TWA00_AD)
Climatuff compressor

Multi-use liquid and suction line


service valves

All aluminum Spine Fin coil


DuraTuff base, fast complete drain,
weather proof

Brazed connections

New cabinet with polystate gray


cabinet

Full length control cover

Quick-Sess cabinet, service access


and refrigerant connections with full coil
protection

S.E.E.T. design testing

Corrosion resistant finish and fastners

Low ambient cooling to 55F as


shipped

Easy top & fan removal


HCFC-22 refrigerant

Internal high/low pressure & temperature protection


2TWB00 & 2TWA00

100% line run test

Low ambient to 40F with


EDC accessory AY28X084

Liquid line filter-drier

Low ambient cooling to 30F with


EDC accessory AY28X084 and TXV

Easy single side service

Air Handling Units


(2TWE0_CA)
Features
Ships horizontal

New Features
Improved filter access and latch
Eliminate current T-bar and shipping
bracket.

Six way convertibility-horizontal (left


and right), upflow, downflow (front
and rear access)
Electrical, refrigerant, condensate and
blower access convertible to either side
Corrosion resistant galvanized steel
with attractive finish
Internally enhanced finned coil tubes

Reversible Duct Flanges Fits up to


1-1/2 inches duct board
Improve controls access with control
box mounted next to blower.
40 VA transformer with 5 amp automotive style fuse on 3 tons and less

Direct drive motor


Standard filters
Multi-speed blower
220 volt primary and 24 volt secondary
transformer
Insulated cabinet

TWE

Provision for 1-1/8 inches thick field


supplied electrostatic filter

External access to heater circuit


breakers
Start kits are not required

5 Amp automotive style fuse replaces


Bussman red cap fuse on 3.5 to 5 ton
models
Blower mounting brackets improved
Front access to screw with power driver
Improved bottom carton cushioning
1 inch thick foil faced insulation for all
models

Built-in indoor fan delay function for


increased efficiency. No kit required.

TWE5_PRC001_EN_081703.PMD

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Features and
Benefits
Optional Equipment
] indicates accessories included).
OPTIONAL EQUIPMENT FOR CONDENSING UNITS (Check mark [
Indoor Thermostats Elec. Setback Thermostat .................................................................................................. TAYSTAT500C [
Prog., 5/2 Day, Manual ........................................................................................................ TAYSTAT540 [
Electronic, 2 Htg./1 Clg. (Non Prog.) .................................................................................... TAYSTAT570 [
Automatic Heat/Cool (Two Stage Heating) ........................................................................... BAY28X138A [
Manual Seasonal Selector Heat/Cool (Two Stage Heating) .............................................. BAYSTAT239A [
Locking Thermostat Cover ......................................................................................................................................... BAY28X190 [
Humidistat ............................................................................................................................................................... BAYSTAT253 [
Outdoor Thermostats 46F. to 10F. (Adjustable) ................................................................................................ TAYSTAT250B [
Evaporator Defrost Control Kit ..................................................................................................................................... AY28X084 [
Indoor Fan Delay Relay ............................................................................................................................................. BAY24X045 [
5 Minute Delay Relay 1 ....................................................................................................................................... TAYASCT501A [
Outdoor Temperature Sensor (TAYSTAT500C) ..................................................................................................... TAYSENS100A [
Snow Legs Base and Cap 4" High ....................................................................................................................... BAYLEGS002 [
Snow Legs addition 4" extension (used with BAYLEGS002) ................................................................................ BAYLEGS003 [
Start Kit (1-5 ton models) ........................................................................................................................................ BAYKSKT257 [
Extreme Conditions Mounting Kit ........................................................................................................................... BAYECMT001 [
Seacoast Kit ........................................................................................................................................................... BAYSEAC001 [
Isolators .................................................................................................................................................................... BAYISLT101 [
Low Ambient Kit ..................................................................................................................................................... BAYLOAM103 [

]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]
]

1 Do not use with programmable thermostats

BRAZED TUBING REFRIGERANT LINE SETS (All Suction Lines are Insulated.)
5/8" ODM (90 bend, one end), 5/8" and 1/4" tubing ............................................................................................ TAYREFLN1__* [ ]
3/4" ODM (90 bend, one end), 3/4" and 5/16" tubing .......................................................................................... TAYREFLN2__* [ ]
7/8" ODM (90 bend, one end), 7/8" and 3/8" tubing ............................................................................................ TAYREFLN3__* [ ]
3/4" ODM (90 bend, one end), 1-1/8" and 3/8" tubing ......................................................................................... TAYREFLN4__* [ ]
* Line lengths: 15, 20, 25, 30, 40 & 50 ft. Insert desired line length in catalog number at right for the complete number.
Example: TAYREFLN220

Low Outdoor Ambient Cooling


Low Ambient
Cooling
FCCV Accutron
Thermal Expansion Valve (TXV)

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

As
Manufactured

Evaporator
Defrost Control

55F
55F

40F
30F

9/15/2003, 3:07 PM

Selection
Procedure
Model Number Nomenclature for Condensing Units
1

10

11

12

13

14

15

Refrigerant Type
2 = R-22
4 = R-410A

Unit Parts
Identifier
Minor Design
Modifications

TRANE
Product Type
W = Split Heat Pump
T = Split Cooling

Secondary
Function
Power Supply
1 = 200 - 230 / 1 / 60 or 208 - 230 / 1 / 60
3 = 200 - 230 / 3 / 60
4 = 460 / 3 / 60
A = 220 / 1 / 50
D = 380-415 / 3 / 50

Product Family
Z = LEADERSHIP - 2 STAGE
X = LEADERSHIP
R = REPLACEMENT / RETAIL
B = BASIC
A = LIGHT COMMERCIAL

Major Design Modifications

Family SEER
0 = 10 2 = 12
1 = 11 3 = 13

4 = 14
6 = 16

Nominal Capacity in 000s of BTUs


8 = 18

Split System Connections 1 - 6 Tons


0 = Brazed
5 = Flare

Model Number Nomenclature for Air Handlers


1

10

11

12

Product Type
TW = Split System Component
Heat Pump Compatible

Product
Service Change

Airflow Configuration
E = Convertible

Minor Design
Modification

Refrigerant Connections
0 = Brazed

Not Used
Refrigerant Flow Control
4 = Accutron Flow Control/Check Valve
5 = Bleed TXV

Nominal Net Cooling


Capacity
30 = 30 MBh
40 = 40 MBh
50 = 50 MBh

Electrical Characteristics
A = 220V/1/50

Major Design Modification


6

TWE5_PRC001_EN_081703.PMD

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

General
Data

TWE

TWE Product Specifications


Model
Power Conn. Volts/Ph/Hz
Indoor Coil - Type
Rows
Fins per inch (Fins per 25.4 mm)
Face Area sq ft (sq m)
Tube Size in. (mm)
Refrigerant Control
Drain Conn. Size in. (mm)
Duct Connections
Indoor Fan - Type
No. Used
Diameter in. (mm)
Width in. (mm)
Type Drive - No. Speeds
Airflow (High)
CFM @ 0.0 in. w.g.
CMH @ 0.0 Pa
No. Motors - HP
Motor RPM
Volts/Ph/Hz
F.L. Amps
L.R. Amps
Filters
Vertical Applications
Filter Furnished
Type Furnished
No.-Size-Thickness
Horizontal Applications
Filter Furnished
Type Recommended
No.-Size-Thickness
Refrigerant Line Size
Line Size ID Gas in. (mm)
Line Size ID Liquid in. (mm)
Dimensions (H x W x D)
Crated - in.
- (mm)
Uncrated - in.
- (mm)
Weight Ibs. (kg)
Shipping
Net

TWE030CA40B
220/1/50
Plate Fin
3
14
3.21 (.30)
3/8 (9.52)
FCCV
3/4 NPT
See Outline Drawing
Centrifugal
1
10.0 (254.0)
8.0 (203.2)
Direct - 3

TWE040CA40C
220/1/50
Plate Fin
3
14
5.04 (.47)
3/8 (9.52)
FCCV
3/4 NPT
See Outline Drawing
Centrifugal
1
10.0 (254.0)
10.0 (254.0)
Direct - 3

TWE050CA50D
220/1/50
Plate Fin
3
14
6.19 (.58)
3/8 (9.52)
FCCV
3/4 NPT
See Outline Drawing
Centrifugal
1
11.0 (279.4)
10.0 (254.0)
Direct - 3

See Fan Performance Table


See Fan Performance Table
1 - 1/3
1000
220/1/50
2.6
3.3

See Fan Performance Table


See Fan Performance Table
1 - 1/3
900
220/1/50
2.1
4.2

See Fan Performance Table


See Fan Performance Table
1 - 3/4
900
220/1/50
4.5
10.1

Yes
Throwaway
1 - 20 x 20 - 1

Yes
Throwaway
1 - 20 x 20 - 1

Yes
High Velocity
1 - 2 2 x 20 - 1

No
See Note Below
See Note Below

No
See Note Below
See Note Below

No
See Note Below
See Note Below

7/8 (22.23)
3/8 (9.52)

1-1/8 (28.56)
3/8 (9.52)

1-1/8 (28.56)
3/8 (9.52)

44.5 x 24.0 x 23.5


(1130 x 610 x 597)
43.0 x 21.5 x 21.0
(1092 x 546 x 533)

53.25 x 26.0 x 23.5


(1353 x 660 x 597)
52.0 x 23.5 x 21.0
(1321 x 597x 533)

59.5 x 26.0 x 23.5


(1511 x 660 x 597)
58.0 x 23.5 x 21.0
(1473 x 597 x 533)

125 (56.7)
115 (52.2)

165 (74.8)
150 (68.0)

198 (898)
183 (83.0)

Minimum filter size for horizontal applications based on airflow selection and calculated as follows:
Low Velocity Filter: Face Area (sq ft) = CFM/300
High Velocity Filter: Face Area (sq ft) = CFM/500

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

9/15/2003, 3:07 PM

General
Data

2TWB

2TWB Product Specifications 12


Model
2TWB0012AA000A
Power Conn. - Volts/Ph/Hz
200/230/1/50
Fuse Size - max. amps
Min. Brch. Cir. Ampacity
10
Br. Cir.
Max. (Amps)
15
Prot. Rtg. Min. (Amps)
15
Compressor - Type
CLIMATUFF
No. Used - No. Speeds
1-1
Volts/Ph/Hz
200/230/1/50
R.L. Amps 6 - L.R. Amps
7.2 - 47
Factory Installed
Start Components 7
NO
Insulation/Sound Blanket
NO
Compressor Heat
YES
Outdoor Fan - Type
PROPELLER
No. Used
1
Diameter in. (mm)
19 (483)
Type Drive - No. Speeds
DIRECT - 1
CFM @ 0.0 in. w.g. 3
1300
(M) 3/HR. @ 0.0 mm w.g. 3
CMH @ 0.0 mm. w.g. 3
2210
No. Motors - HP
1 - 1/8
Motor Speed (RPM)
1075
Volts/Ph/Hz
200/230/1/50
F.L. Amps
0.9
Outdoor Coil - Type
SPINE FIN
No. Rows
1
Fins/in. (mm)
24 (0.945)
Face Area sq ft (sq m)
9.72 (0.90)
Tube Size in. (mm)
3/8 (9.53)
Refrigerant
R-22 (O.D. Unit) 4 - lbs. (kg) 4 LBS., 5 OZ. (1.96)
Factory Supplied
YES
Line Size - OD Gas 5 in. (mm)
5/8 (15.9)
Line Size - OD Liq. 5 in. (mm)
1/4 (6.35)
FCCV
Restrictor Orifice Size in. (mm)
.045
Dimensions (H x W x D)
Crated - in.
30.1 x 26.7 x 30.2
- (mm)
765 x 678 x 767
Uncrated
Weight lbs. (kg)
Shipping
170 (77.3)
Net
151 (68.6)

2TWB0018AA000A
200/230/1/50

2TWB0024AA000A
200/230/1/50

2TWB0030AA000A
200/230/1/50

2TWB0036AA000A
200/230/1/50

13
20
20
CLIMATUFF
1-1
200/230/1/50
9.6 - 66

17
25
20
CLIMATUFF
1-1
200/230/1/50
12.2 - 82

17
30
30
CLIMATUFF
1-1
200/230/1/50
12.9 - 78

26
45
40
CLIMATUFF
1-1
200/230/1/50
19.9 - 124

NO
NO
YES
PROPELLER
1
19 (483)
DIRECT - 1
1825

NO
NO
YES
PROPELLER
1
19 (483)
DIRECT - 1
2075

NO
NO
YES
PROPELLER
1
19 (483)
DIRECT - 1
2075

YES
NO
YES
PROPELLER
1
23 (584)
DIRECT - 1
2775

3103
1 - 1/8
1075
200/230/1/50
0.9
SPINE FIN
1
24 (0.945)
9.72 (0.90)
3/8 (9.53)

3528
1 - 1/4
1075
200/230/1/50
1.3
SPINE FIN
1
24 (0.945)
13.75 (1.28)
3/8 (9.53)

3528
1 - 1/4
1075
200/230/1/50
1.3
SPINE FIN
1
24 (0.945)
11.32 (1.05)
3/8 (9.53)

4718
1 - 1/6
825
200/230/1/50
1.4
SPINE FIN
1
24 (0.945)
15.18 (1.41)
3/8 (9.53)

4 LBS., 8 OZ. (2.05)


YES
3/4 (19.1)
5/16 (7.94)

4 LBS., 11 OZ. (2.13)


YES
3/4 (19.1)
5/16 (7.94)

5 LBS., 15 OZ. (2.70)


YES
7/8 (22.2)
3/8 (9.53)

6 LBS., 8 OZ. (2.95)


YES
7/8 (22.2)
3/8 (9.53)

.051

.057

.061

.071

30.1 x 26.7 x 30.2


765 x 678 x 767

33.2 x 26.7 x 30.2


843 x 678 x 767

33.2 x 26.7 x 30.2


843 x 678 x 767

38 x 30.1 x 33.8
965 x 765 x 859

179 (81.4)
160 (72.7)

193 (87.7)
173 (78.6)

192 (87.3)
172 (78.2)

254 (115.5)
227 (103.2)

NOTES:
1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.
2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.
NO SUPPLEMENTARY HEAT INCLUDED.
3 STANDARD AIR - DRY COIL - OUTDOOR
4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.
5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.
6 THIS VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAX. FUSE SIZE. THE VALUE
SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.
7 NO MEANS NO START COMPONENTS. YES MEANS QUICK START KIT COMPONENTS. PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

TWE5_PRC001_EN_081703.PMD

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

General
Data

2TWA

2TWA Product Specifications 12


Model
Power Conn. - Volts/Ph/Hz
Fuse Size - max. amps
Min. Brch. Cir. Ampacity
Br. Cir.
Max. (Amps)
Prot. Rtg. Min. (Amps)
Compressor - Type
No. Used - No. Speeds
Volts/Ph/Hz
R.L. Amps 6 - L.R. Amps
Factory Installed
Start Components 7
Insulation/Sound Blanket
Compressor Heat
Outdoor Fan - Type
No. Used
Diameter in. (mm)
Type Drive - No. Speeds
CFM @ 0.0 in. w.g. 3
(M) 3/HR. @ 0.0 mm w.g. 3
CMH @ 0.0 mm. w.g. 3
No. Motors - HP
Motor Speed (RPM)
Volts/Ph/Hz
F.L. Amps
Outdoor Coil - Type
No. Rows
Fins/in. (mm)
Face Area sq ft (sq m)
Tube Size in. (mm)
Refrigerant
R-22 (O.D. Unit) 4 - lbs. (kg)
Factory Supplied
Line Size - OD Gas 5 in. (mm)
Line Size - OD Liq. 5 in. (mm)
FCCV
Restrictor Orifice Size in. (mm)
Dimensions (H x W x D)
Crated - in.
- (mm)
Uncrated
Weight lbs. (kg)
Shipping
Net

2TWA0030AD000A
380/415/3/50

2TWA0040AD000A
380/415/3/50

2TWA0050AD000A
380/415/3/50

2TWA0060AD000A
380/415/3/50

7
15
15
CLIMATUFF
1-1
380/415/3/50
5.5 - 46

9
15
15
CLIMATUFF
1-1
380/415/3/50
6.4 - 51

12
20
20
CLIMATUFF
1-1
380/415/3/50
9.0 - 70

12
20
20
CLIMATUFF
1-1
380/415/3/50
9.0 - 74

NO
NO
YES
PROPELLER
1
19 (483)
DIRECT - 1
2775

NO
NO
YES
PROPELLER
1
23 (584)
DIRECT - 1
3075

NO
NO
YES
PROPELLER
1
27.6 (701)
DIRECT - 1
3675

NO
NO
YES
PROPELLER
1
27.6 (701)
DIRECT - 1
3300

4718
1 - 1/4
1075
380/415/3/50
.7
SPINE FIN
1
24 (0.945)
15.18 (1.41)
3/8 (9.53)

5228
1 - 1/4
825
380/415/3/50
1.0
SPINE FIN
1
24 (0.945)
15.18 (1.41)
3/8 (9.53)

6248
1 - 1/6
825
380/415/3/50
.7
SPINE FIN
1
24 (0.945)
21.99 (2.04)
3/8 (9.53)

5610
1 - 1/4
825
380/415/3/50
1.0
SPINE FIN
2
24 (0.945)
27.86 (2.59)
3/8 (9.53)

5 LBS., 12 OZ. (2.61)


YES
7/8 (22.2)
3/8 (9.53)

8 LBS., 6 OZ. (3.81)


YES
1 -1/8 (28.5)
3/8 (9.53)

9 LBS., 8 OZ. (4.32)


YES
1 -1/8 (28.5)
3/8 (9.53)

14 LBS., 1 OZ. (6.39)


YES
1 -1/8 (28.5)
3/8 (9.53)

.071

.075

.086

.086

33.2 x 26.7 x 30.2


843 x 678 x 767

38 x 30.1 x 33.8
965 x 765 x 859

38.4 x 35.1 x 38.7


975 x 892 x 983

46.4 x 35.1 x 38.7


1179 x 892 x 983

212 (96.4)
192 (87.3)

254 (115.5)
226 (102.7)

289 (131.4)
256 (116.4)

329 (149.5)
293 (133.2)

NOTES:
1 RATING CONDITIONS (COOLING): 80F (27C) D.B. 67F (20C) W.B. ENTERING AIR TO INDOOR COIL OF APPLICABLE TYPE.
95F (35C) D.B. ENTERING AIR TO OUTDOOR COIL.
INDOOR COIL AND UNIT CONNECTED BY 25 FT. (7.62 METERS) TUBING.
2 RATING CONDITIONS (HEATING): 70F (21C) D.B. ENTERING AIR TO INDOOR COIL; 47F (8C) D.B.
43F (6C) W.B. ENTERING AIR TO OUTDOOR COIL.
NO SUPPLEMENTARY HEAT INCLUDED.
3 STANDARD AIR - DRY COIL - OUTDOOR
4 THIS VALUE APPROXIMATE. FOR MORE PRECISE VALUE SEE UNIT NAMEPLATE AND SERVICE INSTRUCTIONS.
5 MAX. OF 80 FT. (24.38 METERS) TOTAL MEASURED LENGTH INCLUDING 60 FT. (18.29 METERS) MAX. LIFT BETWEEN O.D. AND I.D. SECTIONS.
6 THIS VALUE SHOWN FOR COMPRESSOR RLA ON THE UNIT NAMEPLATE AND ON THIS SPECIFICATION SHEET IS USED TO COMPUTE MINIMUM BRANCH CIRCUIT AMPACITY AND MAX. FUSE SIZE. THE VALUE
SHOWN IS THE BRANCH CIRCUIT SELECTION CURRENT.
7 NO MEANS NO START COMPONENTS. YES MEANS QUICK START KIT COMPONENTS. PTC MEANS POSITIVE TEMPERATURE COEFFICIENT STARTER.

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

9/15/2003, 3:07 PM

Performance Data
Cooling
English Units
2TWB0012AA WITH TWE030CA4 AT 450 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
13.7
14.8
16.0
17.2
13.5
14.6
15.8
17.0
13.3
14.4
15.6
16.8
12.9
13.9
15.1
16.3
12.4
13.5
14.6
15.7
11.5
12.5
13.5
14.6

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
11.5
12.4
13.3
13.9*
14.2*
9.8
10.7
11.6
12.5
13.4
7.9
8.8
9.7
10.6
11.5
6.0
6.9
7.8
8.7
9.6
11.4
12.3
13.2
13.8*
14.1*
9.7
10.6
11.5
12.4
13.3
7.8
8.7
9.6
10.5
11.4
5.9
6.8
7.7
8.6
9.5
11.3
12.2
13.1
13.6*
14.0*
9.6
10.5
11.4
12.3
13.2
7.8
8.7
9.6
10.4
11.3
5.9
6.7
7.6
8.5
9.4
11.1
12.0
12.9*
13.3*
13.6*
9.4
10.3
11.2
12.1
13.0
7.6
8.5
9.3
10.2
11.1
5.6
6.5
7.4
8.3
9.2
10.9
11.8
12.5*
12.9*
13.2*
9.2
10.1
11.0
11.9
12.8
7.4
8.2
9.1
10.0
10.9
5.4
6.3
7.2
8.1
9.0
10.5
11.4
11.8*
12.1*
12.5*
8.8
9.7
10.6
11.5
12.4
6.9
7.8
8.7
9.6
10.5
5.0
5.9
6.8
7.7
8.6

COMPR.
KW
1.41
1.42
1.43
1.45
1.46
1.47
1.48
1.50
1.51
1.52
1.53
1.54
1.56
1.57
1.58
1.59
1.61
1.62
1.62
1.63
1.72
1.72
1.71
1.71

APP. DEW
PT.
47.1
50.9
55.0
59.2
47.3
51.1
55.2
59.4
47.5
51.3
55.3
59.5
48.0
51.8
55.8
60.0
48.5
52.2
56.3
60.5
49.4
53.2
57.3
61.5

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

400
X0.98
X0.95
X0.99
-1.3

500
X1.01
X1.05
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 15700 BTUH
AIRFLOW = 450 CFM
APP. DEW PT. = 55.3 DEG. F
COMPRESSOR POWER = 1098 WATTS
I.D. FAN POWER = 342 WATTS
O.D. FAN POWER = 93 WATTS
S.E.E.R. = 9.88 BTUH/WATT
E.E.R. = 9.41 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 5/8 SUCT.
AND 1/4 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TWB0018AA WITH TWE030CA4 AT 700 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
19.2
20.7
22.2
23.8
19.1
20.5
22.1
23.7
18.9
20.4
21.9
23.5
18.3
19.8
21.3
22.8
17.8
19.2
20.6
22.1
16.7
18.0
19.4
20.8

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
16.9
18.2
19.3*
19.9*
20.3*
14.2
15.6
16.9
18.3
19.6
11.3
12.7
14.0
15.4
16.7
8.4
9.7
11.1
12.4
13.8
16.8
18.1
19.2*
19.7*
20.2*
14.2
15.5
16.9
18.2
19.5
11.3
12.6
14.0
15.3
16.7
8.3
9.7
11.0
12.4
13.7
16.7
18.1
19.1*
19.6*
20.1*
14.1
15.4
16.8
18.1
19.5
11.2
12.6
13.9
15.2
16.6
8.3
9.6
11.0
12.3
13.6
16.5
17.8
18.6*
19.1*
19.6*
13.8
15.2
16.5
17.9
19.2
11.0
12.3
13.6
15.0
16.3
8.0
9.4
10.7
12.1
13.4
16.2
17.5
18.2*
18.7*
19.1*
13.6
14.9
16.3
17.6
19.0
10.7
12.1
13.4
14.7
16.1
7.8
9.1
10.5
11.8
13.1
15.7
16.8*
17.3*
17.7*
18.1*
13.1
14.4
15.8
17.1
18.1*
10.2
11.6
12.9
14.2
15.6
7.3
8.6
10.0
11.3
12.7

COMPR.
KW
1.95
1.99
2.02
2.06
2.03
2.07
2.10
2.14
2.11
2.15
2.18
2.22
2.17
2.21
2.24
2.27
2.24
2.27
2.30
2.33
2.37
2.39
2.41
2.44

APP. DEW
PT.
48.1
52.0
56.1
60.4
48.2
52.1
56.2
60.5
48.3
52.2
56.3
60.6
48.7
52.6
56.8
61.0
49.2
53.0
57.2
61.4
50.0
53.8
58.0
62.2

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

600
X0.98
X0.94
X0.98
-1.6

800
X1.01
X1.06
X1.01
1.3

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 21800 BTUH
AIRFLOW = 675 CFM
APP. DEW PT. = 56.0 DEG. F
COMPRESSOR POWER = 1625 WATTS
I.D. FAN POWER = 387 WATTS
O.D. FAN POWER = 148 WATTS
S.E.E.R. = 10.06 BTUH/WATT
E.E.R. = 9.47 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCT.
AND 5/16 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TWB0024AA WITH TWE030CA4 AT 900 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
23.9
25.7
27.5
29.5
23.7
25.5
27.4
29.3
23.6
25.4
27.2
29.2
22.9
24.7
26.5
28.4
22.2
24.0
25.8
27.6
20.9
22.6
24.3
26.0

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
21.1
22.8
24.1*
24.7*
25.3*
17.8
19.5
21.2
22.8
24.5
14.1
15.8
17.5
19.2
20.9
10.4
12.1
13.8
15.5
17.2
21.0
22.7
23.9*
24.6*
25.2*
17.7
19.4
21.1
22.8
24.5
14.1
15.8
17.5
19.1
20.8
10.4
12.1
13.7
15.4
17.1
20.9
22.6
23.8*
24.5*
25.0*
17.7
19.3
21.0
22.7
24.4
14.0
15.7
17.4
19.1
20.8
10.3
12.0
13.7
15.4
17.1
20.6
22.3
23.3*
23.9*
24.5*
17.4
19.0
20.7
22.4
24.1
13.7
15.4
17.1
18.8
20.5
10.0
11.7
13.4
15.1
16.8
20.3
22.0
22.7*
23.4*
23.9*
17.1
18.7
20.4
22.1
23.8
13.4
15.1
16.8
18.5
20.2
9.7
11.4
13.1
14.8
16.5
19.7
21.1*
21.7*
22.2*
22.8*
16.5
18.1
19.8
21.5
22.8*
12.8
14.5
16.2
17.9
19.6
9.2
10.8
12.5
14.2
15.9

COMPR.
KW
2.40
2.45
2.50
2.55
2.50
2.55
2.59
2.64
2.60
2.65
2.69
2.74
2.68
2.72
2.76
2.81
2.76
2.80
2.84
2.88
2.92
2.95
2.98
3.01

APP. DEW
PT.
48.3
52.1
56.3
60.6
48.4
52.2
56.4
60.6
48.5
52.3
56.5
60.7
48.9
52.7
56.9
61.1
49.2
53.1
57.3
61.5
50.0
53.9
58.0
62.3

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
775
1025
TOTAL CAP.
X0.98
X1.01
SENS. CAP.
X0.94
X1.06
COMPR. KW
X0.99
X1.01
A.D.P.
-1.6
1.2
VALUES AT 95/80/67 RATING CONDITIONS
GROSS CAPACITY = 27300 BTUH
AIRFLOW = 900 CFM
APP. DEW PT. = 56.5 DEG. F
COMPRESSOR POWER = 2086 WATTS
I.D. FAN POWER = 425 WATTS
O.D. FAN POWER = 181 WATTS
S.E.E.R. = 10.24 BTUH/WATT
E.E.R. = 9.58 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 3/4 SUCT.
AND 5/16 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

10

TWE5_PRC001_EN_081703.PMD

10

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Cooling

Metric Units

2TWB0012AA WITH TWE030CA4 AT 764 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
4.0
4.3
4.7
5.0
4.0
4.3
4.6
5.0
3.9
4.2
4.6
4.9
3.8
4.1
4.4
4.8
3.6
4.0
4.3
4.6
3.4
3.7
4.0
4.3

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
3.4
3.6
3.9
4.1*
4.2*
2.9
3.1
3.4
3.7
3.9
2.3
2.6
2.8
3.1
3.4
1.8
2.0
2.3
2.5
2.8
3.3
3.6
3.9
4.0*
4.1*
2.8
3.1
3.4
3.6
3.9
2.3
2.5
2.8
3.1
3.3
1.7
2.0
2.3
2.5
2.8
3.3
3.6
3.8
4.0*
4.1*
2.8
3.1
3.3
3.6
3.9
2.3
2.5
2.8
3.0
3.3
1.7
2.0
2.2
2.5
2.8
3.3
3.5
3.8*
3.9*
4.0*
2.8
3.0
3.3
3.5
3.8
2.2
2.5
2.7
3.0
3.3
1.6
1.9
2.2
2.4
2.7
3.2
3.5
3.7*
3.8*
3.9*
2.7
3.0
3.2
3.5
3.8
2.2
2.4
2.7
2.9
3.2
1.6
1.8
2.1
2.4
2.6
3.1
3.3
3.5*
3.5*
3.7*
2.6
2.8
3.1
3.4
3.6
2.0
2.3
2.5
2.8
3.1
1.5
1.7
2.0
2.3
2.5

COMPR.
KW
1.4
1.4
1.4
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.5
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.6
1.7
1.7
1.7
1.7

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

679
X0.98
X0.95
X0.99

849
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 4.60 KW
AIRFLOW = 764 CMH
COMPRESSOR POWER = 1098 WATTS
I.D. FAN POWER = 342 WATTS
O.D. FAN POWER = 93 WATTS
S.E.E.R. = 9.88 BTUH/WATT
E.E.R. = 9.41 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 5/8 IN. SUCT.
AND 1/4 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TWB0018AA WITH TWE030CA4 AT 1189 CMH (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
5.6
6.1
6.5
7.0
5.6
6.0
6.5
6.9
5.5
6.0
6.4
6.9
5.4
5.8
6.2
6.7
5.2
5.6
6.0
6.5
4.9
5.3
5.7
6.1

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
5.0
5.3
5.7*
5.8*
5.9*
4.2
4.6
5.0
5.4
5.7
3.3
3.7
4.1
4.5
4.9
2.5
2.8
3.3
3.6
4.0
4.9
5.3
5.6*
5.8*
5.9*
4.2
4.5
5.0
5.3
5.7
3.3
3.7
4.1
4.5
4.9
2.4
2.8
3.2
3.6
4.0
4.9
5.3
5.6*
5.7*
5.9*
4.1
4.5
4.9
5.3
5.7
3.3
3.7
4.1
4.5
4.9
2.4
2.8
3.2
3.6
4.0
4.8
5.2
5.4*
5.6*
5.7*
4.0
4.5
4.8
5.2
5.6
3.2
3.6
4.0
4.4
4.8
2.3
2.8
3.1
3.5
3.9
4.7
5.1
5.3*
5.5*
5.6*
4.0
4.4
4.8
5.2
5.6
3.1
3.5
3.9
4.3
4.7
2.3
2.7
3.1
3.5
3.8
4.6
4.9*
5.1*
5.2*
5.3*
3.8
4.2
4.6
5.0
5.3*
3.0
3.4
3.8
4.2
4.6
2.1
2.5
2.9
3.3
3.7

COMPR.
KW
2.0
2.0
2.0
2.1
2.0
2.1
2.1
2.1
2.1
2.2
2.2
2.2
2.2
2.2
2.2
2.3
2.2
2.3
2.3
2.3
2.4
2.4
2.4
2.4

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1019
X0.98
X0.94
X0.98

1358
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 6.39 KW
AIRFLOW = 1146 CMH
COMPRESSOR POWER = 1625 WATTS
I.D. FAN POWER = 387 WATTS
O.D. FAN POWER = 148 WATTS
S.E.E.R. = 10.06 BTUH/WATT
E.E.R. = 9.47 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCT.
AND 5/16 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TWB0024AA WITH TWE030CA4 AT 1528 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
7.0
7.5
8.1
8.6
6.9
7.5
8.0
8.6
6.9
7.4
8.0
8.6
6.7
7.2
7.8
8.3
6.5
7.0
7.6
8.1
6.1
6.6
7.1
7.6

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

11

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
6.2
6.7
7.1*
7.2*
7.4*
5.2
5.7
6.2
6.7
7.2
4.1
4.6
5.1
5.6
6.1
3.0
3.5
4.0
4.5
5.0
6.2
6.7
7.0*
7.2*
7.4*
5.2
5.7
6.2
6.7
7.2
4.1
4.6
5.1
5.6
6.1
3.0
3.5
4.0
4.5
5.0
6.1
6.6
7.0*
7.2*
7.3*
5.2
5.7
6.2
6.7
7.1
4.1
4.6
5.1
5.6
6.1
3.0
3.5
4.0
4.5
5.0
6.0
6.5
6.8*
7.0*
7.2*
5.1
5.6
6.1
6.6
7.1
4.0
4.5
5.0
5.5
6.0
2.9
3.4
3.9
4.4
4.9
5.9
6.4
6.7*
6.9*
7.0*
5.0
5.5
6.0
6.5
7.0
3.9
4.4
4.9
5.4
5.9
2.8
3.3
3.8
4.3
4.8
5.8
6.2*
6.4*
6.5*
6.7*
4.8
5.3
5.8
6.3
6.7*
3.8
4.2
4.7
5.2
5.7
2.7
3.2
3.7
4.2
4.7

COMPR.
KW
2.4
2.5
2.5
2.5
2.5
2.5
2.6
2.6
2.6
2.7
2.7
2.7
2.7
2.7
2.8
2.8
2.8
2.8
2.8
2.9
2.9
3.0
3.0
3.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1316
X0.98
X0.94
X0.99

1741
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 8.00 KW
AIRFLOW = 1528 CMH
COMPRESSOR POWER = 2086 WATTS
I.D. FAN POWER = 425 WATTS
O.D. FAN POWER = 181 WATTS
S.E.E.R. = 10.24 BTUH/WATT
E.E.R. = 9.58 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 3/4 IN. SUCT.
AND 5/16 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

11

9/15/2003, 3:07 PM

Performance Data
Cooling
English Units
2TWB0030AA WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
26.8
28.8
30.8
32.9
26.6
28.5
30.6
32.7
26.4
28.3
30.3
32.4
25.5
27.4
29.3
31.4
24.6
26.4
28.3
30.3
22.8
24.6
26.4
28.2

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
23.5
25.3
27.0*
27.7*
28.3*
19.8
21.7
23.5
25.4
27.2
15.8
17.7
19.5
21.4
23.2
11.7
13.5
15.4
17.2
19.1
23.4
25.2
26.8*
27.5*
28.1*
19.7
21.6
23.4
25.3
27.1
15.7
17.6
19.4
21.3
23.1
11.6
13.4
15.3
17.1
19.0
23.3
25.1
26.6*
27.3*
27.9*
19.6
21.5
23.3
25.2
27.0
15.6
17.5
19.3
21.2
23.0
11.5
13.4
15.2
17.1
18.9
22.9
24.7
25.8*
26.5*
27.1*
19.2
21.1
22.9
24.8
26.6
15.2
17.1
18.9
20.8
22.6
11.1
13.0
14.8
16.7
18.5
22.5
24.3
25.1*
25.8*
26.4*
18.8
20.7
22.5
24.4
26.2
14.8
16.7
18.5
20.4
22.2
10.7
12.6
14.4
16.3
18.1
21.7
23.0*
23.7*
24.3*
24.8*
18.0
19.9
21.7
23.6
24.8*
14.0
15.9
17.7
19.6
21.4
9.9
11.8
13.6
15.5
17.3

COMPR.
KW
2.80
2.87
2.93
3.00
2.93
2.99
3.06
3.13
3.05
3.11
3.18
3.25
3.16
3.22
3.29
3.36
3.27
3.33
3.39
3.46
3.49
3.54
3.60
3.66

APP. DEW
PT.
48.0
51.9
56.1
60.4
48.2
52.1
56.3
60.5
48.3
52.2
56.4
60.6
48.8
52.7
56.9
61.1
49.3
53.2
57.4
61.6
50.2
54.1
58.3
62.6

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

875
X0.98
X0.95
X0.99
-1.4

1125
X1.01
X1.05
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 30400 BTUH
AIRFLOW = 1000 CFM
APP. DEW PT. = 56.4 DEG. F
COMPRESSOR POWER = 2566 WATTS
I.D. FAN POWER = 437 WATTS
O.D. FAN POWER = 179 WATTS
S.E.E.R. = 9.91 BTUH/WATT
E.E.R. = 9.06 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TWB0030AA WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
28.5
30.5
32.5
34.7
28.2
30.2
32.2
34.3
27.8
29.8
31.9
34.0
26.9
28.8
30.8
32.8
25.9
27.8
29.7
31.7
24.0
25.7
27.5
29.4

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
25.5
27.6
28.9*
29.6*
30.2*
21.3
23.4
25.5
27.6
29.7
16.7
18.8
20.9
23.0
25.1
12.0
14.1
16.2
18.3
20.4
25.3
27.4
28.6*
29.3*
30.0*
21.2
23.3
25.4
27.4
29.5
16.6
18.7
20.8
22.9
25.0
11.9
14.0
16.1
18.2
20.3
25.2
27.3
28.4*
29.0*
29.7*
21.0
23.1
25.2
27.3
29.4
16.4
18.5
20.6
22.7
24.8
11.8
13.9
16.0
18.1
20.2
24.7
26.8
27.6*
28.2*
28.8*
20.6
22.7
24.8
26.9
28.8*
16.0
18.1
20.2
22.3
24.4
11.4
13.5
15.6
17.7
19.8
24.3
26.1*
26.8*
27.4*
28.0*
20.2
22.3
24.4
26.4
28.0*
15.6
17.7
19.8
21.9
24.0
11.0
13.1
15.1
17.2
19.3
23.5
24.5*
25.1*
25.7*
26.3*
19.3
21.4
23.5
25.6
26.3*
14.8
16.9
19.0
21.0
23.1
10.1
12.2
14.3
16.4
18.5

COMPR.
KW
2.74
2.80
2.87
2.94
2.86
2.93
3.00
3.07
2.99
3.06
3.13
3.20
3.10
3.16
3.23
3.30
3.21
3.27
3.34
3.40
3.43
3.49
3.55
3.61

APP. DEW
PT.
48.4
52.4
56.6
61.0
48.6
52.5
56.8
61.1
48.7
52.7
56.9
61.3
49.2
53.1
57.4
61.7
49.6
53.6
57.8
62.1
50.5
54.4
58.7
63.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

950
X0.98
X0.93
X0.99
-1.4

1250
X1.01
X1.06
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 32000 BTUH
AIRFLOW = 1125 CFM
APP. DEW PT. = 57.1 DEG. F
COMPRESSOR POWER = 2651 WATTS
I.D. FAN POWER = 309 WATTS
O.D. FAN POWER = 179 WATTS
S.E.E.R. = 10.90 BTUH/WATT
E.E.R. = 9.84 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TWB0036AA WITH TWE030CA4 AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
33.1
35.7
38.5
41.3
32.8
35.4
38.2
41.0
32.5
35.1
37.9
40.7
31.4
34.0
36.6
39.4
30.3
32.8
35.4
38.1
28.1
30.4
32.9
35.4

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
27.4
29.4
31.4
33.2*
34.0*
23.5
25.5
27.5
29.5
31.5
19.2
21.2
23.2
25.2
27.2
14.8
16.8
18.8
20.8
22.8
27.2
29.2
31.2
33.0*
33.8*
23.4
25.4
27.4
29.4
31.4
19.1
21.1
23.1
25.1
27.1
14.7
16.7
18.7
20.7
22.7
27.1
29.1
31.1
32.7*
33.6*
23.2
25.3
27.3
29.3
31.3
19.0
21.0
23.0
25.0
27.0
14.6
16.6
18.6
20.6
22.6
26.5
28.6
30.6
31.9*
32.7*
22.7
24.7
26.7
28.7
30.7
18.5
20.5
22.5
24.5
26.5
14.1
16.1
18.1
20.1
22.1
26.0
28.0
30.0
31.0*
31.8*
22.2
24.2
26.2
28.2
30.2
17.9
19.9
22.0
24.0
26.0
13.6
15.6
17.6
19.6
21.6
25.0
27.0
28.5*
29.3*
30.0*
21.2
23.2
25.2
27.2
29.2
16.9
18.9
20.9
22.9
24.9
12.6
14.6
16.6
18.6
20.6

COMPR.
KW
3.30
3.38
3.47
3.56
3.44
3.53
3.62
3.71
3.59
3.68
3.77
3.86
3.72
3.80
3.89
3.98
3.85
3.93
4.02
4.11
4.11
4.19
4.27
4.35

APP. DEW
PT.
46.3
50.4
54.4
58.6
46.5
50.6
54.6
58.7
47.0
50.8
54.8
58.9
47.6
51.4
55.4
59.5
48.2
52.0
56.0
60.1
49.4
53.2
57.2
61.4

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

12

1250
X1.02
X1.05
X1.01
1.5

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 38100 BTUH
AIRFLOW = 1125 CFM
APP. DEW PT. = 55.0 DEG. F
COMPRESSOR POWER = 3067 WATTS
I.D. FAN POWER = 541 WATTS
O.D. FAN POWER = 177 WATTS
S.E.E.R. = 10.49 BTUH/WATT
E.E.R. = 9.56 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

12

TWE5_PRC001_EN_081703.PMD

950
X0.97
X0.94
X0.99
-1.8

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Cooling

Metric Units

2TWB0030AA WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
7.9
8.4
9.0
9.6
7.8
8.4
9.0
9.6
7.7
8.3
8.9
9.5
7.5
8.0
8.6
9.2
7.2
7.7
8.3
8.9
6.7
7.2
7.7
8.3

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
6.9
7.4
7.9*
8.1*
8.3*
5.8
6.4
6.9
7.4
8.0
4.6
5.2
5.7
6.3
6.8
3.4
4.0
4.5
5.0
5.6
6.9
7.4
7.9*
8.1*
8.2*
5.8
6.3
6.9
7.4
7.9
4.6
5.2
5.7
6.2
6.8
3.4
3.9
4.5
5.0
5.6
6.8
7.4
7.8*
8.0*
8.2*
5.7
6.3
6.8
7.4
7.9
4.6
5.1
5.7
6.2
6.7
3.4
3.9
4.5
5.0
5.5
6.7
7.2
7.6*
7.8*
7.9*
5.6
6.2
6.7
7.3
7.8
4.5
5.0
5.5
6.1
6.6
3.3
3.8
4.3
4.9
5.4
6.6
7.1
7.4*
7.6*
7.7*
5.5
6.1
6.6
7.1
7.7
4.3
4.9
5.4
6.0
6.5
3.1
3.7
4.2
4.8
5.3
6.4
6.7*
6.9*
7.1*
7.3*
5.3
5.8
6.4
6.9
7.3*
4.1
4.7
5.2
5.7
6.3
2.9
3.5
4.0
4.5
5.1

COMPR.
KW
2.8
2.9
2.9
3.0
2.9
3.0
3.1
3.1
3.0
3.1
3.2
3.3
3.2
3.2
3.3
3.4
3.3
3.3
3.4
3.5
3.5
3.5
3.6
3.7

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1486
X0.98
X0.95
X0.99

1910
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 8.91 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 2566 WATTS
I.D. FAN POWER = 437 WATTS
O.D. FAN POWER = 179 WATTS
S.E.E.R. = 9.91 BTUH/WATT
E.E.R. = 9.06 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TWB0030AA WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
8.4
8.9
9.5
10.2
8.3
8.8
9.4
10.0
8.1
8.7
9.3
10.0
7.9
8.4
9.0
9.6
7.6
8.1
8.7
9.3
7.0
7.5
8.1
8.6

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
7.5
8.1
8.5*
8.7*
8.8*
6.2
6.9
7.5
8.1
8.7
4.9
5.5
6.1
6.7
7.4
3.5
4.1
4.7
5.4
6.0
7.4
8.0
8.4*
8.6*
8.8*
6.2
6.8
7.4
8.0
8.6
4.9
5.5
6.1
6.7
7.3
3.5
4.1
4.7
5.3
5.9
7.4
8.0
8.3*
8.5*
8.7*
6.2
6.8
7.4
8.0
8.6
4.8
5.4
6.0
6.7
7.3
3.5
4.1
4.7
5.3
5.9
7.2
7.9
8.1*
8.3*
8.4*
6.0
6.7
7.3
7.9
8.4*
4.7
5.3
5.9
6.5
7.1
3.3
4.0
4.6
5.2
5.8
7.1
7.6*
7.9*
8.0*
8.2*
5.9
6.5
7.1
7.7
8.2*
4.6
5.2
5.8
6.4
7.0
3.2
3.8
4.4
5.0
5.7
6.9
7.2*
7.4*
7.5*
7.7*
5.7
6.3
6.9
7.5
7.7*
4.3
5.0
5.6
6.2
6.8
3.0
3.6
4.2
4.8
5.4

COMPR.
KW
2.7
2.8
2.9
2.9
2.9
2.9
3.0
3.1
3.0
3.1
3.1
3.2
3.1
3.2
3.2
3.3
3.2
3.3
3.3
3.4
3.4
3.5
3.5
3.6

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1613
X0.98
X0.93
X0.99

2123
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 9.38 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 2651 WATTS
I.D. FAN POWER = 309 WATTS
O.D. FAN POWER = 179 WATTS
S.E.E.R. = 10.90 BTUH/WATT
E.E.R. = 9.84 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TWB0036AA WITH TWE030CA4 AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
9.7
10.5
11.3
12.1
9.6
10.4
11.2
12.0
9.5
10.3
11.1
11.9
9.2
10.0
10.7
11.5
8.9
9.6
10.4
11.2
8.2
8.9
9.6
10.4

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

13

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
8.0
8.6
9.2
9.7*
10.0*
6.9
7.5
8.1
8.6
9.2
5.6
6.2
6.8
7.4
8.0
4.3
4.9
5.5
6.1
6.7
8.0
8.6
9.1
9.7*
9.9*
6.9
7.4
8.0
8.6
9.2
5.6
6.2
6.8
7.4
7.9
4.3
4.9
5.5
6.1
6.7
7.9
8.5
9.1
9.6*
9.8*
6.8
7.4
8.0
8.6
9.2
5.6
6.2
6.7
7.3
7.9
4.3
4.9
5.4
6.0
6.6
7.8
8.4
9.0
9.3*
9.6*
6.7
7.2
7.8
8.4
9.0
5.4
6.0
6.6
7.2
7.8
4.1
4.7
5.3
5.9
6.5
7.6
8.2
8.8
9.1*
9.3*
6.5
7.1
7.7
8.3
8.8
5.2
5.8
6.4
7.0
7.6
4.0
4.6
5.2
5.7
6.3
7.3
7.9
8.4*
8.6*
8.8*
6.2
6.8
7.4
8.0
8.6
5.0
5.5
6.1
6.7
7.3
3.7
4.3
4.9
5.4
6.0

COMPR.
KW
3.3
3.4
3.5
3.6
3.4
3.5
3.6
3.7
3.6
3.7
3.8
3.9
3.7
3.8
3.9
4.0
3.8
3.9
4.0
4.1
4.1
4.2
4.3
4.3

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1613
X0.97
X0.94
X0.99

2123
X1.02
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 11.16 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 3067 WATTS
I.D. FAN POWER = 541 WATTS
O.D. FAN POWER = 177 WATTS
S.E.E.R. = 10.49 BTUH/WATT
E.E.R. = 9.56 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

13

9/15/2003, 3:07 PM

Performance Data
Cooling
English Units
2TWB0036AA WITH TWE040CA4-B AT 1400 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
36.4
39.2
42.0
45.0
36.0
38.8
41.6
44.6
35.7
38.4
41.2
44.2
34.4
37.0
39.8
42.6
33.1
35.7
38.3
41.1
30.6
33.0
35.5
38.0

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
32.6
35.2
36.9*
37.9*
38.7*
27.4
30.0
32.7
35.3
37.9
21.7
24.4
27.0
29.6
32.2
15.9
18.6
21.2
23.8
26.4
32.4
35.0
36.6*
37.6*
38.4*
27.2
29.9
32.5
35.1
37.8
21.6
24.2
26.8
29.5
32.1
15.8
18.4
21.0
23.7
26.3
32.2
34.8
36.3*
37.3*
38.1*
27.1
29.7
32.3
35.0
37.6
21.4
24.0
26.7
29.3
31.9
15.6
18.3
20.9
23.5
26.1
31.6
34.3
35.2*
36.2*
37.0*
26.5
29.1
31.8
34.4
37.0
20.8
23.5
26.1
28.7
31.3
15.1
17.7
20.3
22.9
25.6
31.0
33.3*
34.2*
35.1*
35.9*
25.9
28.5
31.2
33.8
35.9*
20.3
22.9
25.5
28.1
30.8
14.5
17.1
19.7
22.4
25.0
29.9
31.2*
32.1*
32.9*
33.7*
24.8
27.4
30.0
32.7
33.7*
19.1
21.8
24.4
27.0
29.6
13.4
16.0
18.6
21.3
23.9

COMPR.
KW
3.26
3.35
3.44
3.53
3.42
3.51
3.60
3.69
3.58
3.67
3.76
3.85
3.70
3.79
3.88
3.98
3.83
3.92
4.01
4.10
4.09
4.17
4.26
4.35

APP. DEW
PT.
48.5
52.4
56.5
60.8
48.6
52.5
56.7
60.9
48.8
52.6
56.8
61.0
49.3
53.1
57.3
61.5
49.7
53.6
57.8
62.0
50.7
54.6
58.7
63.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

14

1575
X1.01
X1.06
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 41000 BTUH
AIRFLOW = 1350 CFM
APP. DEW PT. = 56.5 DEG. F
COMPRESSOR POWER = 3201 WATTS
I.D. FAN POWER = 356 WATTS
O.D. FAN POWER = 177 WATTS
S.E.E.R. = 11.89 BTUH/WATT
E.E.R. = 10.65 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

14

TWE5_PRC001_EN_081703.PMD

1225
X0.98
X0.94
X0.99
-1.3

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Cooling

Metric Units

2TWB0036AA WITH TWE040CA4-B AT 2378 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
10.7
11.5
12.3
13.2
10.5
11.4
12.2
13.1
10.5
11.3
12.1
13.0
10.1
10.8
11.7
12.5
9.7
10.5
11.2
12.0
9.0
9.7
10.4
11.1

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

15

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
9.6
10.3
10.8*
11.1*
11.3*
8.0
8.8
9.6
10.3
11.1
6.4
7.1
7.9
8.7
9.4
4.7
5.4
6.2
7.0
7.7
9.5
10.3
10.7*
11.0*
11.3*
8.0
8.8
9.5
10.3
11.1
6.3
7.1
7.9
8.6
9.4
4.6
5.4
6.2
6.9
7.7
9.4
10.2
10.6*
10.9*
11.2*
7.9
8.7
9.5
10.3
11.0
6.3
7.0
7.8
8.6
9.3
4.6
5.4
6.1
6.9
7.6
9.3
10.0
10.3*
10.6*
10.8*
7.8
8.5
9.3
10.1
10.8
6.1
6.9
7.6
8.4
9.2
4.4
5.2
5.9
6.7
7.5
9.1
9.8*
10.0*
10.3*
10.5*
7.6
8.4
9.1
9.9
10.5*
5.9
6.7
7.5
8.2
9.0
4.2
5.0
5.8
6.6
7.3
8.8
9.1*
9.4*
9.6*
9.9*
7.3
8.0
8.8
9.6
9.9*
5.6
6.4
7.1
7.9
8.7
3.9
4.7
5.4
6.2
7.0

COMPR.
KW
3.3
3.3
3.4
3.5
3.4
3.5
3.6
3.7
3.6
3.7
3.8
3.8
3.7
3.8
3.9
4.0
3.8
3.9
4.0
4.1
4.1
4.2
4.3
4.3

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2080
X0.98
X0.94
X0.99

2675
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 12.01 KW
AIRFLOW = 2293 CMH
COMPRESSOR POWER = 3201 WATTS
I.D. FAN POWER = 356 WATTS
O.D. FAN POWER = 177 WATTS
S.E.E.R. = 11.89 BTUH/WATT
E.E.R. = 10.65 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

15

9/15/2003, 3:07 PM

Performance Data
Cooling
English Units
2TWA0030AD WITH TWE030CA4 AT 1000 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
30.0
32.4
34.8
37.3
29.7
32.1
34.5
37.0
29.4
31.7
34.1
36.6
28.2
30.4
32.8
35.2
27.0
29.1
31.4
33.7
24.6
26.6
28.6
30.7

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
24.9
26.8
28.6
30.2*
31.0*
21.4
23.2
25.1
26.9
28.7
17.4
19.2
21.1
22.9
24.8
13.3
15.2
17.0
18.9
20.7
24.8
26.6
28.5
30.0*
30.7*
21.2
23.1
24.9
26.8
28.6
17.3
19.1
21.0
22.8
24.6
13.2
15.1
16.9
18.7
20.6
24.6
26.5
28.3
29.7*
30.5*
21.1
22.9
24.8
26.6
28.5
17.1
19.0
20.8
22.7
24.5
13.1
14.9
16.8
18.6
20.4
24.1
25.9
27.7
28.7*
29.5*
20.5
22.4
24.2
26.0
27.9
16.6
18.4
20.2
22.1
23.9
12.5
14.4
16.2
18.0
19.9
23.5
25.3
27.1*
27.8*
28.5*
19.9
21.8
23.6
25.5
27.3
16.0
17.8
19.7
21.5
23.4
11.9
13.8
15.6
17.5
19.3
22.4
24.2
25.1*
25.8*
26.4*
18.8
20.7
22.5
24.4
26.2
14.9
16.7
18.6
20.4
22.3
10.8
12.7
14.5
16.4
18.2

COMPR.
KW
3.03
3.11
3.20
3.29
3.17
3.25
3.34
3.43
3.30
3.39
3.48
3.57
3.41
3.50
3.58
3.68
3.52
3.60
3.69
3.78
3.74
3.82
3.90
3.99

APP. DEW
PT.
46.8
50.5
54.6
58.8
46.9
50.7
54.8
59.0
47.1
50.9
55.0
59.1
47.8
51.6
55.7
59.9
48.5
52.4
56.4
60.6
49.9
53.7
57.8
62.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

875
X0.98
X0.94
X0.98
-1.6

1125
X1.01
X1.05
X1.01
1.3

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 34200 BTUH
AIRFLOW = 1000 CFM
APP. DEW PT. = 55.0 DEG. F
COMPRESSOR POWER = 2859 WATTS
I.D. FAN POWER = 437 WATTS
O.D. FAN POWER = 181 WATTS
S.E.E.R. = 10.36 BTUH/WATT
E.E.R. = 9.39 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TWA0030AD WITH TWE040CA4-B AT 1100 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
32.1
34.5
37.0
39.6
31.7
34.1
36.6
39.1
31.3
33.6
36.1
38.6
29.8
32.1
34.4
36.9
28.4
30.6
32.8
35.1
25.5
27.5
29.5
31.6

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
27.2
29.3
31.4
32.7*
33.5*
23.1
25.2
27.3
29.4
31.5
18.6
20.7
22.8
24.9
27.0
13.9
16.0
18.1
20.2
22.3
27.0
29.1
31.2
32.3*
33.1*
22.9
25.0
27.1
29.2
31.3
18.4
20.5
22.6
24.7
26.8
13.7
15.8
17.9
20.0
22.2
26.8
28.9
31.0
32.0*
32.8*
22.7
24.8
26.9
29.0
31.1
18.2
20.3
22.4
24.5
26.6
13.5
15.7
17.8
19.9
22.0
26.2
28.3
30.0*
30.8*
31.5*
22.1
24.2
26.3
28.4
30.5
17.5
19.6
21.7
23.8
25.9
12.9
15.0
17.1
19.2
21.3
25.5
27.6
28.9*
29.6*
30.3*
21.4
23.5
25.6
27.7
29.8
16.9
19.0
21.1
23.2
25.3
12.3
14.4
16.5
18.6
20.7
24.2
25.8*
26.5*
27.2*
27.8*
20.1
22.2
24.3
26.4
27.8*
15.6
17.7
19.8
21.9
24.0
11.0
13.1
15.2
17.3
19.4

COMPR.
KW
3.00
3.09
3.18
3.27
3.14
3.23
3.32
3.41
3.28
3.36
3.46
3.55
3.39
3.48
3.57
3.67
3.51
3.60
3.69
3.78
3.75
3.83
3.91
4.00

APP. DEW
PT.
47.2
51.1
55.3
59.6
47.4
51.3
55.5
59.8
47.7
51.5
55.7
60.0
48.3
52.2
56.4
60.7
49.0
52.9
57.1
61.4
50.3
54.2
58.4
62.7

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

950
X0.98
X0.94
X0.98
-1.6

1250
X1.02
X1.06
X1.01
1.3

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 36200 BTUH
AIRFLOW = 1125 CFM
APP. DEW PT. = 56.0 DEG. F
COMPRESSOR POWER = 2982 WATTS
I.D. FAN POWER = 309 WATTS
O.D. FAN POWER = 181 WATTS
S.E.E.R. = 11.28 BTUH/WATT
E.E.R. = 10.12 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 7/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TWA0040AD WITH TWE040CA4-B AT 1300 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
38.3
41.3
44.4
47.7
37.6
40.6
43.6
46.8
36.9
39.8
42.8
45.9
36.0
38.8
41.7
44.8
35.0
37.8
40.6
43.6
33.2
35.8
38.5
41.3

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
30.2
32.5
34.8
37.1
38.9*
25.8
28.1
30.4
32.7
35.0
20.9
23.2
25.5
27.8
30.1
15.8
18.1
20.4
22.7
25.0
29.9
32.2
34.5
36.8
38.3*
25.5
27.8
30.1
32.4
34.7
20.6
22.9
25.1
27.4
29.7
15.5
17.8
20.1
22.4
24.7
29.6
31.9
34.2
36.5
37.7*
25.2
27.5
29.8
32.1
34.3
20.2
22.5
24.8
27.1
29.4
15.2
17.5
19.8
22.1
24.4
29.2
31.5
33.8
36.1*
37.0*
24.8
27.1
29.3
31.6
33.9
19.8
22.1
24.4
26.7
29.0
14.8
17.1
19.4
21.7
24.0
28.8
31.1
33.4
35.4*
36.2*
24.4
26.6
28.9
31.2
33.5
19.4
21.7
24.0
26.3
28.6
14.4
16.7
19.0
21.3
23.6
28.0
30.3
32.6
33.9*
34.7*
23.6
25.8
28.1
30.4
32.7
18.6
20.9
23.2
25.5
27.8
13.6
15.9
18.2
20.5
22.8

COMPR.
KW
3.31
3.41
3.53
3.64
3.44
3.55
3.67
3.79
3.58
3.70
3.82
3.94
3.73
3.85
3.97
4.09
3.88
4.00
4.12
4.25
4.18
4.30
4.43
4.56

APP. DEW
PT.
44.9
48.8
52.9
57.1
45.3
49.1
53.2
57.4
45.6
49.4
53.5
57.7
46.0
49.8
53.9
58.1
46.3
50.2
54.3
58.5
47.1
51.0
55.1
59.3

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

16

1500
X1.02
X1.07
X1.01
1.4

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 43000 BTUH
AIRFLOW = 1325 CFM
APP. DEW PT. = 53.7 DEG. F
COMPRESSOR POWER = 3236 WATTS
I.D. FAN POWER = 360 WATTS
O.D. FAN POWER = 232 WATTS
S.E.E.R. = 12.25 BTUH/WATT
E.E.R. = 10.74 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

16

TWE5_PRC001_EN_081703.PMD

1150
X0.98
X0.95
X0.99
-1.4

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Cooling

Metric Units

2TWA0030AD WITH TWE030CA4 AT 1698 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
8.8
9.5
10.2
10.9
8.7
9.4
10.1
10.8
8.6
9.3
10.0
10.7
8.3
8.9
9.6
10.3
7.9
8.5
9.2
9.9
7.2
7.8
8.4
9.0

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
7.3
7.9
8.4
8.8*
9.1*
6.3
6.8
7.4
7.9
8.4
5.1
5.6
6.2
6.7
7.3
3.9
4.5
5.0
5.5
6.1
7.3
7.8
8.4
8.8*
9.0*
6.2
6.8
7.3
7.9
8.4
5.1
5.6
6.2
6.7
7.2
3.9
4.4
5.0
5.5
6.0
7.2
7.8
8.3
8.7*
8.9*
6.2
6.7
7.3
7.8
8.4
5.0
5.6
6.1
6.7
7.2
3.8
4.4
4.9
5.4
6.0
7.1
7.6
8.1
8.4*
8.6*
6.0
6.6
7.1
7.6
8.2
4.9
5.4
5.9
6.5
7.0
3.7
4.2
4.7
5.3
5.8
6.9
7.4
7.9*
8.1*
8.4*
5.8
6.4
6.9
7.5
8.0
4.7
5.2
5.8
6.3
6.9
3.5
4.0
4.6
5.1
5.7
6.6
7.1
7.4*
7.6*
7.7*
5.5
6.1
6.6
7.1
7.7
4.4
4.9
5.4
6.0
6.5
3.2
3.7
4.2
4.8
5.3

COMPR.
KW
3.0
3.1
3.2
3.3
3.2
3.3
3.3
3.4
3.3
3.4
3.5
3.6
3.4
3.5
3.6
3.7
3.5
3.6
3.7
3.8
3.7
3.8
3.9
4.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1486
X0.98
X0.94
X0.98

1910
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 10.02 KW
AIRFLOW = 1698 CMH
COMPRESSOR POWER = 2859 WATTS
I.D. FAN POWER = 437 WATTS
O.D. FAN POWER = 181 WATTS
S.E.E.R. = 10.36 BTUH/WATT
E.E.R. = 9.39 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TWA0030AD WITH TWE040CA4-B AT 1868 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
9.4
10.1
10.8
11.6
9.3
10.0
10.7
11.5
9.2
9.8
10.6
11.3
8.7
9.4
10.1
10.8
8.3
9.0
9.6
10.3
7.5
8.1
8.6
9.3

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
8.0
8.6
9.2
9.6*
9.8*
6.8
7.4
8.0
8.6
9.2
5.4
6.1
6.7
7.3
7.9
4.1
4.7
5.3
5.9
6.5
7.9
8.5
9.1
9.5*
9.7*
6.7
7.3
7.9
8.6
9.2
5.4
6.0
6.6
7.2
7.9
4.0
4.6
5.2
5.9
6.5
7.9
8.5
9.1
9.4*
9.6*
6.7
7.3
7.9
8.5
9.1
5.3
5.9
6.6
7.2
7.8
4.0
4.6
5.2
5.8
6.4
7.7
8.3
8.8*
9.0*
9.2*
6.5
7.1
7.7
8.3
8.9
5.1
5.7
6.4
7.0
7.6
3.8
4.4
5.0
5.6
6.2
7.5
8.1
8.5*
8.7*
8.9*
6.3
6.9
7.5
8.1
8.7
5.0
5.6
6.2
6.8
7.4
3.6
4.2
4.8
5.4
6.1
7.1
7.6*
7.8*
8.0*
8.1*
5.9
6.5
7.1
7.7
8.1*
4.6
5.2
5.8
6.4
7.0
3.2
3.8
4.5
5.1
5.7

COMPR.
KW
3.0
3.1
3.2
3.3
3.1
3.2
3.3
3.4
3.3
3.4
3.5
3.5
3.4
3.5
3.6
3.7
3.5
3.6
3.7
3.8
3.8
3.8
3.9
4.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1613
X0.98
X0.94
X0.98

2123
X1.02
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 10.61 KW
AIRFLOW = 1910 CMH
COMPRESSOR POWER = 2982 WATTS
I.D. FAN POWER = 309 WATTS
O.D. FAN POWER = 181 WATTS
S.E.E.R. = 11.28 BTUH/WATT
E.E.R. = 10.12 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 7/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TWA0040AD WITH TWE040CA4-B AT 2208 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
11.2
12.1
13.0
14.0
11.0
11.9
12.8
13.7
10.8
11.7
12.5
13.4
10.5
11.4
12.2
13.1
10.3
11.1
11.9
12.8
9.7
10.5
11.3
12.1

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

17

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
8.8
9.5
10.2
10.9
11.4*
7.6
8.2
8.9
9.6
10.3
6.1
6.8
7.5
8.1
8.8
4.6
5.3
6.0
6.7
7.3
8.8
9.4
10.1
10.8
11.2*
7.5
8.1
8.8
9.5
10.2
6.0
6.7
7.4
8.0
8.7
4.5
5.2
5.9
6.6
7.2
8.7
9.3
10.0
10.7
11.0*
7.4
8.1
8.7
9.4
10.0
5.9
6.6
7.3
7.9
8.6
4.5
5.1
5.8
6.5
7.1
8.6
9.2
9.9
10.6*
10.8*
7.3
7.9
8.6
9.3
9.9
5.8
6.5
7.1
7.8
8.5
4.3
5.0
5.7
6.4
7.0
8.4
9.1
9.8
10.4*
10.6*
7.1
7.8
8.5
9.1
9.8
5.7
6.4
7.0
7.7
8.4
4.2
4.9
5.6
6.2
6.9
8.2
8.9
9.6
9.9*
10.2*
6.9
7.6
8.2
8.9
9.6
5.4
6.1
6.8
7.5
8.1
4.0
4.7
5.3
6.0
6.7

COMPR.
KW
3.3
3.4
3.5
3.6
3.4
3.5
3.7
3.8
3.6
3.7
3.8
3.9
3.7
3.8
4.0
4.1
3.9
4.0
4.1
4.3
4.2
4.3
4.4
4.6

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

1953
X0.98
X0.95
X0.99

2547
X1.02
X1.07
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 12.60 KW
AIRFLOW = 2250 CMH
COMPRESSOR POWER = 3236 WATTS
I.D. FAN POWER = 360 WATTS
O.D. FAN POWER = 232 WATTS
S.E.E.R. = 12.25 BTUH/WATT
E.E.R. = 10.74 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

17

9/15/2003, 3:07 PM

Performance Data
Cooling
English Units
2TWA0040AD WITH TWE050CA5-C AT 1600 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
40.1
43.2
46.4
49.7
39.2
42.2
45.3
48.6
38.3
41.2
44.3
47.4
37.1
39.9
42.9
45.9
35.9
38.7
41.5
44.5
33.6
36.1
38.8
41.5

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
36.1
39.0
40.8*
41.9*
42.9*
30.2
33.2
36.2
39.2
42.2
23.8
26.8
29.8
32.8
35.7
17.3
20.2
23.2
26.2
29.2
35.7
38.6
40.1*
41.1*
42.1*
29.8
32.8
35.8
38.8
41.8
23.4
26.4
29.4
32.3
35.3
16.8
19.8
22.8
25.8
28.8
35.2
38.2
39.3*
40.3*
41.3*
29.4
32.4
35.4
38.4
41.3*
23.0
26.0
28.9
31.9
34.9
16.4
19.4
22.4
25.4
28.4
34.7
37.3*
38.3*
39.3*
40.2*
28.9
31.9
34.8
37.8
40.2*
22.4
25.4
28.4
31.4
34.4
15.9
18.9
21.9
24.8
27.8
34.2
36.3*
37.3*
38.3*
39.2*
28.4
31.3
34.3
37.3
39.2*
21.9
24.9
27.9
30.9
33.8
15.4
18.3
21.3
24.3
27.3
33.2
34.4*
35.3*
36.2*
37.0*
27.3
30.3
33.3
36.2*
37.0*
20.9
23.8
26.8
29.8
32.8
14.3
17.3
20.3
23.3
26.2

COMPR.
KW
3.61
3.72
3.83
3.95
3.77
3.89
4.00
4.13
3.93
4.05
4.17
4.30
4.09
4.21
4.34
4.47
4.25
4.38
4.51
4.65
4.57
4.71
4.85
4.99

APP. DEW
PT.
48.5
52.4
56.5
60.8
48.8
52.7
56.8
61.1
49.1
53.0
57.1
61.4
49.5
53.4
57.5
61.8
49.8
53.7
57.9
62.2
50.6
54.5
58.7
63.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

1400
X0.98
X0.94
X0.99
-1.2

1800
X1.01
X1.06
X1.01
1.0

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 44200 BTUH
AIRFLOW = 1575 CFM
APP. DEW PT. = 57.0 DEG. F
COMPRESSOR POWER = 3403 WATTS
I.D. FAN POWER = 529 WATTS
O.D. FAN POWER = 232 WATTS
S.E.E.R. = 11.67 BTUH/WATT
E.E.R. = 10.17 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TWA0050AD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
49.2
52.9
56.8
60.8
48.2
51.9
55.6
59.6
47.2
50.8
54.5
58.3
46.0
49.5
53.1
56.8
44.7
48.1
51.6
55.2
42.2
45.4
48.7
52.1

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
42.5
45.9
49.2
50.5*
51.7*
36.0
39.3
42.7
46.0
49.3
28.8
32.1
35.5
38.8
42.1
21.4
24.8
28.1
31.4
34.8
42.1
45.4
48.4*
49.7*
50.8*
35.6
38.9
42.2
45.6
48.9
28.3
31.7
35.0
38.3
41.7
21.0
24.3
27.6
31.0
34.3
41.6
45.0
47.6*
48.9*
50.0*
35.1
38.4
41.8
45.1
48.4
27.9
31.2
34.6
37.9
41.2
20.5
23.9
27.2
30.5
33.9
41.1
44.4
46.6*
47.8*
48.9*
34.5
37.9
41.2
44.5
47.9
27.3
30.6
34.0
37.3
40.6
19.9
23.3
26.6
29.9
33.3
40.5
43.8
45.6*
46.7*
47.8*
34.0
37.3
40.6
44.0
47.3
26.7
30.1
33.4
36.7
40.1
19.4
22.7
26.0
29.4
32.7
39.4
42.4*
43.6*
44.6*
45.6*
32.8
36.1
39.5
42.8
45.6*
25.6
28.9
32.3
35.6
38.9
18.2
21.6
24.9
28.2
31.6

COMPR.
KW
4.67
4.78
4.91
5.04
4.87
4.99
5.12
5.24
5.08
5.20
5.32
5.45
5.28
5.40
5.53
5.66
5.49
5.61
5.73
5.86
5.92
6.03
6.14
6.26

APP. DEW
PT.
47.7
51.5
55.7
59.9
48.0
51.8
56.0
60.2
48.3
52.1
56.3
60.6
48.6
52.5
56.7
61.0
49.0
52.9
57.1
61.4
49.8
53.7
57.9
62.1

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

1575
X0.98
X0.94
X0.99
-1.4

2025
X1.01
X1.05
X1.01
1.1

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 54300 BTUH
AIRFLOW = 1750 CFM
APP. DEW PT. = 56.0 DEG. F
COMPRESSOR POWER = 4376 WATTS
I.D. FAN POWER = 731 WATTS
O.D. FAN POWER = 189 WATTS
S.E.E.R. = 11.05 BTUH/WATT
E.E.R. = 9.78 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1 1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

2TWA0060AD WITH TWE050CA5-C AT 1800 CFM (CAPACITIES ARE GROSS IN BTUH/1000-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
85

90

95

100

105

115

I.D.
W.B.
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71
59
63
67
71

TOTAL
CAP.
54.2
58.1
62.3
66.5
53.2
57.1
61.1
65.3
52.2
56.1
60.0
64.1
48.4
51.9
55.6
59.4
44.5
47.7
51.1
54.6
36.7
39.4
42.2
45.1

SENS. CAP. AT ENTERING D.B. TEMP.


72
74
76
78
80
44.9
48.3
51.6
54.5*
55.8*
38.4
41.7
45.1
48.4
51.8
31.1
34.4
37.8
41.1
44.5
23.7
27.0
30.3
33.7
37.0
44.5
47.8
51.2
53.7*
55.0*
37.9
41.3
44.6
48.0
51.3
30.6
34.0
37.3
40.7
44.0
23.2
26.5
29.9
33.2
36.6
44.0
47.4
50.7
52.9*
54.2*
37.5
40.8
44.2
47.5
50.8
30.2
33.5
36.9
40.2
43.6
22.7
26.1
29.4
32.8
36.1
42.2
45.6
48.6*
49.8*
50.9*
35.7
39.0
42.3
45.7
49.0
28.4
31.7
35.1
38.4
41.7
21.0
24.3
27.6
31.0
34.3
40.5
43.8
45.4*
46.5*
47.6*
33.9
37.2
40.6
43.9
47.2
26.6
29.9
33.3
36.6
40.0
19.2
22.5
25.9
29.2
32.6
36.8*
37.8*
38.8*
39.7*
40.6*
30.4
33.7
37.1
39.7*
40.6*
23.1
26.5
29.8
33.1
36.5
15.7
19.1
22.4
25.8
29.1

COMPR.
KW
5.21
5.30
5.40
5.50
5.48
5.59
5.70
5.81
5.75
5.87
5.99
6.12
6.77
6.92
7.08
7.25
7.78
7.97
8.17
8.38
9.76
10.05
10.36
10.67

APP. DEW
PT.
46.6
50.5
54.6
58.9
46.9
50.8
55.0
59.2
47.2
51.1
55.3
59.6
48.5
52.4
56.6
60.8
49.6
53.6
57.8
62.1
51.9
55.9
60.1
64.4

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW
A.D.P.

18

2025
X1.01
X1.05
X1.01
1.3

VALUES AT 95/80/67 RATING CONDITIONS


GROSS CAPACITY = 59800 BTUH
AIRFLOW = 1750 CFM
APP. DEW PT. = 55.0 DEG. F
COMPRESSOR POWER = 5059 WATTS
I.D. FAN POWER = 731 WATTS
O.D. FAN POWER = 179 WATTS
S.E.E.R. = 11.09 BTUH/WATT
E.E.R. = 9.58 BTUH/WATT
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCT.
AND 3/8 LIQUID LINE
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES F.

18

TWE5_PRC001_EN_081703.PMD

1575
X0.98
X0.95
X1.00
-1.6

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Cooling

Metric Units

2TWA0040AD WITH TWE050CA5-C AT 2717 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
11.7
12.7
13.6
14.6
11.5
12.4
13.3
14.2
11.2
12.1
13.0
13.9
10.9
11.7
12.6
13.4
10.5
11.3
12.2
13.0
9.8
10.6
11.4
12.2

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
10.6
11.4
12.0*
12.3*
12.6*
8.8
9.7
10.6
11.5
12.4
7.0
7.9
8.7
9.6
10.5
5.1
5.9
6.8
7.7
8.6
10.5
11.3
11.7*
12.0*
12.3*
8.7
9.6
10.5
11.4
12.2
6.9
7.7
8.6
9.5
10.3
4.9
5.8
6.7
7.6
8.4
10.3
11.2
11.5*
11.8*
12.1*
8.6
9.5
10.4
11.3
12.1*
6.7
7.6
8.5
9.3
10.2
4.8
5.7
6.6
7.4
8.3
10.2
10.9*
11.2*
11.5*
11.8*
8.5
9.3
10.2
11.1
11.8*
6.6
7.4
8.3
9.2
10.1
4.7
5.5
6.4
7.3
8.1
10.0
10.6*
10.9*
11.2*
11.5*
8.3
9.2
10.0
10.9
11.5*
6.4
7.3
8.2
9.1
9.9
4.5
5.4
6.2
7.1
8.0
9.7
10.1*
10.3*
10.6*
10.8*
8.0
8.9
9.8
10.6*
10.8*
6.1
7.0
7.9
8.7
9.6
4.2
5.1
5.9
6.8
7.7

COMPR.
KW
3.6
3.7
3.8
4.0
3.8
3.9
4.0
4.1
3.9
4.1
4.2
4.3
4.1
4.2
4.3
4.5
4.3
4.4
4.5
4.7
4.6
4.7
4.8
5.0

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2378
X0.98
X0.94
X0.99

3057
X1.01
X1.06
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 12.95 KW
AIRFLOW = 2675 CMH
COMPRESSOR POWER = 3403 WATTS
I.D. FAN POWER = 529 WATTS
O.D. FAN POWER = 232 WATTS
S.E.E.R. = 11.67 BTUH/WATT
E.E.R. = 10.17 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TWA0050AD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
14.4
15.5
16.6
17.8
14.1
15.2
16.3
17.5
13.8
14.9
16.0
17.1
13.5
14.5
15.6
16.6
13.1
14.1
15.1
16.2
12.4
13.3
14.3
15.3

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
12.5
13.4
14.4
14.8*
15.1*
10.5
11.5
12.5
13.5
14.4
8.4
9.4
10.4
11.4
12.3
6.3
7.3
8.2
9.2
10.2
12.3
13.3
14.2*
14.6*
14.9*
10.4
11.4
12.4
13.4
14.3
8.3
9.3
10.3
11.2
12.2
6.2
7.1
8.1
9.1
10.0
12.2
13.2
13.9*
14.3*
14.6*
10.3
11.3
12.2
13.2
14.2
8.2
9.1
10.1
11.1
12.1
6.0
7.0
8.0
8.9
9.9
12.0
13.0
13.7*
14.0*
14.3*
10.1
11.1
12.1
13.0
14.0
8.0
9.0
10.0
10.9
11.9
5.8
6.8
7.8
8.8
9.8
11.9
12.8
13.4*
13.7*
14.0*
10.0
10.9
11.9
12.9
13.9
7.8
8.8
9.8
10.8
11.7
5.7
6.7
7.6
8.6
9.6
11.5
12.4*
12.8*
13.1*
13.4*
9.6
10.6
11.6
12.5
13.4*
7.5
8.5
9.5
10.4
11.4
5.3
6.3
7.3
8.3
9.3

COMPR.
KW
4.7
4.8
4.9
5.0
4.9
5.0
5.1
5.2
5.1
5.2
5.3
5.4
5.3
5.4
5.5
5.7
5.5
5.6
5.7
5.9
5.9
6.0
6.1
6.3

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2675
X0.98
X0.94
X0.99

3439
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 15.91 KW
AIRFLOW = 2972 CMH
COMPRESSOR POWER = 4376 WATTS
I.D. FAN POWER = 731 WATTS
O.D. FAN POWER = 189 WATTS
S.E.E.R. = 11.05 BTUH/WATT
E.E.R. = 9.78 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

2TWA0060AD WITH TWE050CA5-C AT 3057 CMH (CAPACITIES ARE GROSS IN KILOWATTS-INDOOR FAN HEAT IGNORED)
O.D.
D.B.
29.4

32.2

35.0

37.8

40.6

46.1

I.D.
W.B.
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7
15.0
17.2
19.4
21.7

TOTAL
CAP.
15.9
17.0
18.3
19.5
15.6
16.7
17.9
19.1
15.3
16.4
17.6
18.8
14.2
15.2
16.3
17.4
13.0
14.0
15.0
16.0
10.8
11.5
12.4
13.2

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

19

SENS. CAP. AT ENTERING D.B. TEMP.


22.2
23.3
24.4
25.6
26.7
13.2
14.2
15.1
16.0*
16.3*
11.3
12.2
13.2
14.2
15.2
9.1
10.1
11.1
12.0
13.0
6.9
7.9
8.9
9.9
10.8
13.0
14.0
15.0
15.7*
16.1*
11.1
12.1
13.1
14.1
15.0
9.0
10.0
10.9
11.9
12.9
6.8
7.8
8.8
9.7
10.7
12.9
13.9
14.9
15.5*
15.9*
11.0
12.0
13.0
13.9
14.9
8.8
9.8
10.8
11.8
12.8
6.7
7.6
8.6
9.6
10.6
12.4
13.4
14.2*
14.6*
14.9*
10.5
11.4
12.4
13.4
14.4
8.3
9.3
10.3
11.3
12.2
6.2
7.1
8.1
9.1
10.0
11.9
12.8
13.3*
13.6*
13.9*
9.9
10.9
11.9
12.9
13.8
7.8
8.8
9.8
10.7
11.7
5.6
6.6
7.6
8.6
9.6
10.8*
11.1*
11.4*
11.6*
11.9*
8.9
9.9
10.9
11.6*
11.9*
6.8
7.8
8.7
9.7
10.7
4.6
5.6
6.6
7.6
8.5

COMPR.
KW
5.2
5.3
5.4
5.5
5.5
5.6
5.7
5.8
5.8
5.9
6.0
6.1
6.8
6.9
7.1
7.3
7.8
8.0
8.2
8.4
9.8
10.1
10.4
10.7

CORRECTION FACTORS - OTHER AIRFLOWS


(MULTIPLY OR ADD AS INDICATED)
AIRFLOW
TOTAL CAP.
SENS. CAP.
COMPR. KW

2675
X0.98
X0.95
X1.00

3439
X1.01
X1.05
X1.01

VALUES AT ARI RATING CONDITIONS


GROSS CAPACITY = 17.52 KW
AIRFLOW = 2972 CMH
COMPRESSOR POWER = 5059 WATTS
I.D. FAN POWER = 731 WATTS
O.D. FAN POWER = 179 WATTS
S.E.E.R. = 11.09 BTUH/WATT
E.E.R. = 9.58 BTUH/WATT
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN. SUCT.
AND 3/8 IN. LIQUID LINES
* DRY COIL CONDITION (TOTAL CAPACITY =
SENSIBLE CAPACITY)
TOTAL CAPACITY, COMP. KW AND APP. DEW PT.
ARE VALID ONLY FOR WET COIL
ALL TEMPERATURES IN DEGREES C.

19

9/15/2003, 3:07 PM

Performance Data
Heating
English Units
2TWB0012AA WITH TWE030CA4 AT 450 CFM
O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
3.77
3.65
3.59
3.53
4.85
4.68
4.60
4.51
5.93
5.71
5.60
5.50
7.01
6.75
6.61
6.48
7.61
7.32
7.17
7.02
8.21
7.89
7.73
7.57
8.81
8.46
8.28
8.11
9.40
9.03
8.84
8.65
10.0
9.60
9.40
9.20
13.5
12.9
12.7
12.4
14.6
14.0
13.7
13.4
15.7
15.0
14.7
14.3
16.7
16.0
15.7
15.3
17.8
17.1
16.7
16.3
18.9
18.1
17.7
17.3

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
5.21
5.10
5.04
4.99
6.47
6.32
6.25
6.18
7.73
7.55
7.46
7.36
8.99
8.77
8.66
8.55
10.3
10.0
9.87
9.74
11.5
11.2
11.1
10.9
12.0
11.7
11.5
11.4
12.5
12.1
12.0
11.8
12.9
12.6
12.4
12.3
13.4
13.1
12.9
12.7
13.9
13.5
13.3
13.2
19.1
18.6
18.3
18.1
20.3
19.8
19.5
19.2
21.6
21.0
20.7
20.4
22.9
22.2
21.9
21.6
24.1
23.5
23.1
22.8
25.4
24.7
24.3
24.0

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
7.29
7.14
7.06
6.99
8.82
8.64
8.54
8.45
10.4
10.1
10.0
9.90
11.9
11.6
11.5
11.4
13.4
13.1
13.0
12.8
15.0
14.6
14.5
14.3
15.9
15.5
15.4
15.2
16.8
16.4
16.2
16.0
17.8
17.4
17.1
16.9
18.7
18.3
18.0
17.8
19.6
19.2
18.9
18.7
24.2
23.6
23.3
23.0
25.7
25.1
24.8
24.5
27.3
26.6
26.3
26.0
28.8
28.1
27.8
27.4
30.4
29.6
29.2
28.9
31.9
31.1
30.7
30.3

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
.887
.908
.919
.929
.919
.941
.953
.964
.951
.975
.987
.998
.983
1.01
1.02
1.03
1.02
1.04
1.06
1.07
1.05
1.08
1.10
1.11
1.09
1.12
1.13
1.15
1.12
1.15
1.17
1.19
1.16
1.19
1.21
1.22
1.18
1.21
1.22
1.24
1.21
1.24
1.26
1.28
1.24
1.27
1.29
1.31
1.27
1.31
1.33
1.34
1.30
1.34
1.36
1.38
1.34
1.37
1.39
1.41

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 450 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
400
500
HEATING CAP.
X0.98
X1.02
COMPR. KW
X1.01
X0.99
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 450 CFM
HEATING CAP. (HIGH TEMP.) = 12936 BTUH
HEATING CAP. (LOW TEMP.) = 6745 BTUH
COMPR. POWER (HIGH TEMP.) = 773 WATTS
COMPR. POWER (LOW TEMP.) = 573 WATTS
HSPF (MIN DHR) = 6.98
COEFF. OF PERF. (HIGH TEMP.) = 3.13
COEFF. OF PERF. (LOW TEMP.) = 1.95
OUTDOOR FAN POWER = 93 WATTS
INDOOR FAN POWER = 342 WATTS
NOTE: RATED WITH 25 FEET OF 5/8 SUCTION
AND 1/4 LIQUID LINE

2TWB0018AA WITH TWE030CA4 AT 700 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.16
1.20
1.22
1.25
1.20
1.25
1.27
1.29
1.24
1.29
1.32
1.34
1.28
1.33
1.36
1.39
1.32
1.38
1.41
1.44
1.36
1.42
1.45
1.48
1.38
1.44
1.47
1.50
1.40
1.47
1.50
1.53
1.42
1.49
1.52
1.55
1.44
1.51
1.54
1.57
1.46
1.53
1.56
1.59
1.61
1.69
1.73
1.76
1.66
1.73
1.77
1.81
1.70
1.78
1.82
1.86
1.74
1.82
1.86
1.90
1.78
1.87
1.91
1.95
1.82
1.91
1.95
2.00

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 700 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
600
800
HEATING CAP.
X0.98
X1.02
COMPR. KW
X1.02
X0.99
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 675 CFM
HEATING CAP. (HIGH TEMP.) = 18480 BTUH
HEATING CAP. (LOW TEMP.) = 11151 BTUH
COMPR. POWER (HIGH TEMP.) = 1145 WATTS
COMPR. POWER (LOW TEMP.) = 878 WATTS
HSPF (MIN DHR) = 7.83
COEFF. OF PERF. (HIGH TEMP.) = 3.21
COEFF. OF PERF. (LOW TEMP.) = 2.30
OUTDOOR FAN POWER = 148 WATTS
INDOOR FAN POWER = 387 WATTS
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION
AND 5/16 LIQUID LINE

2TWB0024AA WITH TWE030CA4 AT 900 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.57
1.64
1.67
1.70
1.63
1.69
1.73
1.76
1.68
1.75
1.78
1.82
1.73
1.80
1.84
1.87
1.78
1.86
1.89
1.93
1.83
1.91
1.95
1.99
1.86
1.94
1.98
2.02
1.90
1.98
2.02
2.06
1.93
2.01
2.05
2.09
1.96
2.04
2.09
2.13
1.99
2.08
2.12
2.16
2.14
2.24
2.28
2.33
2.19
2.29
2.34
2.39
2.25
2.35
2.40
2.45
2.30
2.40
2.45
2.50
2.35
2.46
2.51
2.56
2.40
2.51
2.56
2.62

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 900 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
775
1025
HEATING CAP.
X0.98
X1.02
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 900 CFM
HEATING CAP. (HIGH TEMP.) = 23620 BTUH
HEATING CAP. (LOW TEMP.) = 14629 BTUH
COMPR. POWER (HIGH TEMP.) = 1631 WATTS
COMPR. POWER (LOW TEMP.) = 1304 WATTS
HSPF (MIN DHR) = 7.92
COEFF. OF PERF. (HIGH TEMP.) = 3.09
COEFF. OF PERF. (LOW TEMP.) = 2.24
OUTDOOR FAN POWER = 181 WATTS
INDOOR FAN POWER = 425 WATTS
NOTE: RATED WITH 25 FEET OF 3/4 SUCTION
AND 5/16 LIQUID LINE

20

TWE5_PRC001_EN_081703.PMD

20

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Heating

Metric Units

2TWB0012AA WITH TWE030CA4 AT 764 CMH


O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.1
1.1
1.1
1.0
1.4
1.4
1.3
1.3
1.7
1.7
1.6
1.6
2.1
2.0
1.9
1.9
2.2
2.1
2.1
2.1
2.4
2.3
2.3
2.2
2.6
2.5
2.4
2.4
2.8
2.6
2.6
2.5
2.9
2.8
2.8
2.7
4.0
3.8
3.7
3.6
4.3
4.1
4.0
3.9
4.6
4.4
4.3
4.2
4.9
4.7
4.6
4.5
5.2
5.0
4.9
4.8
5.5
5.3
5.2
5.1

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.5
1.5
1.5
1.5
1.9
1.9
1.8
1.8
2.3
2.2
2.2
2.2
2.6
2.6
2.5
2.5
3.0
2.9
2.9
2.9
3.4
3.3
3.3
3.2
3.5
3.4
3.4
3.3
3.7
3.5
3.5
3.5
3.8
3.7
3.6
3.6
3.9
3.8
3.8
3.7
4.1
4.0
3.9
3.9
5.6
5.4
5.4
5.3
5.9
5.8
5.7
5.6
6.3
6.2
6.1
6.0
6.7
6.5
6.4
6.3
7.1
6.9
6.8
6.7
7.4
7.2
7.1
7.0

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.1
2.1
2.1
2.0
2.6
2.5
2.5
2.5
3.0
3.0
2.9
2.9
3.5
3.4
3.4
3.3
3.9
3.8
3.8
3.8
4.4
4.3
4.2
4.2
4.7
4.5
4.5
4.5
4.9
4.8
4.7
4.7
5.2
5.1
5.0
5.0
5.5
5.4
5.3
5.2
5.7
5.6
5.5
5.5
7.1
6.9
6.8
6.7
7.5
7.4
7.3
7.2
8.0
7.8
7.7
7.6
8.4
8.2
8.1
8.0
8.9
8.7
8.6
8.5
9.3
9.1
9.0
8.9

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.9
0.9
0.9
0.9
0.9
0.9
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.0
1.1
1.1
1.0
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.1
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.3
1.3
1.2
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.3
1.4
1.4
1.3
1.4
1.4
1.4

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 764 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
679
849
HEATING CAP.
X0.98
X1.02
COMPR. KW
X1.01
X0.99
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 764 CMH
HEATING CAP. (HIGH TEMP.) = 3.79 KW
HEATING CAP. (LOW TEMP.) = 1.98 KW
COMPR. POWER (HIGH TEMP.) = 773 WATTS
COMPR. POWER (LOW TEMP.) = 573 WATTS
HSPF (MIN DHR) = 6.98
COEFF. OF PERF. (HIGH TEMP.) = 3.13
COEFF. OF PERF. (LOW TEMP.) = 1.95
OUTDOOR FAN POWER = 93 WATTS
INDOOR FAN POWER = 342 WATTS
NOTE: RATED WITH 7.62 METERS OF 5/8 IN.
SUCTION AND 1/4 LIQUID LINE

2TWB0018AA WITH TWE030CA4 AT 1189 CMH


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.2
1.2
1.2
1.3
1.2
1.3
1.3
1.3
1.2
1.3
1.3
1.3
1.3
1.3
1.4
1.4
1.3
1.4
1.4
1.4
1.4
1.4
1.5
1.5
1.4
1.4
1.5
1.5
1.4
1.5
1.5
1.5
1.4
1.5
1.5
1.5
1.4
1.5
1.5
1.6
1.5
1.5
1.6
1.6
1.6
1.7
1.7
1.8
1.7
1.7
1.8
1.8
1.7
1.8
1.8
1.9
1.7
1.8
1.9
1.9
1.8
1.9
1.9
2.0
1.8
1.9
2.0
2.0

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1189 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1019
1358
HEATING CAP.
X0.98
X1.02
COMPR. KW
X1.02
X0.99
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1146 CMH
HEATING CAP. (HIGH TEMP.) = 5.41 KW
HEATING CAP. (LOW TEMP.) = 3.27 KW
COMPR. POWER (HIGH TEMP.) = 1145 WATTS
COMPR. POWER (LOW TEMP.) = 878 WATTS
HSPF (MIN DHR) = 7.83
COEFF. OF PERF. (HIGH TEMP.) = 3.21
COEFF. OF PERF. (LOW TEMP.) = 2.30
OUTDOOR FAN POWER = 148 WATTS
INDOOR FAN POWER = 387 WATTS
NOTE: RATED WITH 7.62 METERS OF 3/4 IN.
SUCTION AND 5/16 LIQUID LINE

2TWB0024AA WITH TWE030CA4 AT 1528 CMH

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

21

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.6
1.6
1.7
1.7
1.6
1.7
1.7
1.8
1.7
1.8
1.8
1.8
1.7
1.8
1.8
1.9
1.8
1.9
1.9
1.9
1.8
1.9
2.0
2.0
1.9
1.9
2.0
2.0
1.9
2.0
2.0
2.1
1.9
2.0
2.0
2.1
2.0
2.0
2.1
2.1
2.0
2.1
2.1
2.2
2.1
2.2
2.3
2.3
2.2
2.3
2.3
2.4
2.3
2.3
2.4
2.5
2.3
2.4
2.5
2.5
2.3
2.5
2.5
2.6
2.4
2.5
2.6
2.6

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1528 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1316
1741
HEATING CAP.
X0.98
X1.02
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1528 CMH
HEATING CAP. (HIGH TEMP.) = 6.92 KW
HEATING CAP. (LOW TEMP.) = 4.29 KW
COMPR. POWER (HIGH TEMP.) = 1631 WATTS
COMPR. POWER (LOW TEMP.) = 1304 WATTS
HSPF (MIN DHR) = 7.92
COEFF. OF PERF. (HIGH TEMP.) = 3.09
COEFF. OF PERF. (LOW TEMP.) = 2.24
OUTDOOR FAN POWER = 181 WATTS
INDOOR FAN POWER = 425 WATTS
NOTE: RATED WITH 7.62 METERS OF 3/4 IN.
SUCTION AND 5/16 LIQUID LINE

21

9/15/2003, 3:07 PM

Performance Data
Heating
English Units
2TWB0030AA WITH TWE030CA4 AT 1000 CFM
O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
8.66
8.49
8.41
8.33
10.6
10.4
10.3
10.2
12.6
12.3
12.2
12.1
14.5
14.2
14.1
13.9
16.5
16.1
16.0
15.8
17.0
16.6
16.5
16.3
17.5
17.1
16.9
16.7
18.0
17.6
17.4
17.2
18.5
18.1
17.9
17.7
19.0
18.6
18.4
18.2
28.2
27.6
27.3
27.0
30.2
29.5
29.2
28.9
32.1
31.4
31.1
30.7
34.1
33.3
33.0
32.6
36.1
35.3
34.9
34.5
38.0
37.2
36.7
36.3

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
8.14
7.98
7.89
7.81
10.1
9.94
9.83
9.73
12.2
11.9
11.8
11.6
14.2
13.9
13.7
13.6
16.2
15.8
15.7
15.5
16.7
16.4
16.2
16.0
17.3
16.9
16.7
16.5
17.8
17.4
17.2
17.1
18.4
18.0
17.8
17.6
18.9
18.5
18.3
18.1
28.2
27.6
27.3
27.0
30.2
29.6
29.2
28.9
32.3
31.5
31.2
30.8
34.3
33.5
33.1
32.7
36.3
35.5
35.1
34.6
38.3
37.4
37.0
36.6

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
7.66
7.55
7.49
7.44
10.2
10.1
9.97
9.89
12.8
12.6
12.5
12.3
15.3
15.1
14.9
14.8
17.9
17.6
17.4
17.3
20.4
20.1
19.9
19.7
21.6
21.3
21.1
20.9
22.8
22.4
22.2
22.0
24.0
23.6
23.4
23.2
25.3
24.8
24.6
24.4
26.5
26.0
25.7
25.5
35.8
35.1
34.8
34.4
38.3
37.6
37.3
36.9
40.9
40.1
39.7
39.4
43.4
42.6
42.2
41.8
46.0
45.1
44.7
44.3
48.5
47.6
47.2
46.7

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.87
1.96
2.01
2.06
1.94
2.04
2.09
2.14
2.02
2.12
2.17
2.23
2.10
2.20
2.26
2.31
2.17
2.28
2.34
2.40
2.22
2.33
2.39
2.45
2.26
2.38
2.44
2.50
2.31
2.43
2.49
2.55
2.35
2.48
2.54
2.60
2.40
2.53
2.59
2.66
2.62
2.77
2.84
2.91
2.70
2.85
2.92
2.99
2.78
2.93
3.00
3.08
2.85
3.01
3.09
3.17
2.93
3.09
3.17
3.25
3.00
3.17
3.25
3.34

CORRECTION FACTORS - OTHER AIRFLOWS

(VALUE AT 1000 CFM TIMES CORR. FACTOR


= VALUE AT NEW AIRFLOW)
AIRFLOW
875
1125
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1000 CFM
HEATING CAP. (HIGH TEMP.) = 27612 BTUH
HEATING CAP. (LOW TEMP.) = 16141 BTUH
COMPR. POWER (HIGH TEMP.) = 2151 WATTS
COMPR. POWER (LOW TEMP.) = 1668 WATTS
HSPF (MIN DHR) = 6.96
COEFF. OF PERF. (HIGH TEMP.) = 2.91
COEFF. OF PERF. (LOW TEMP.) = 2.06
OUTDOOR FAN POWER = 179 WATTS
INDOOR FAN POWER = 437 WATTS
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION
AND 3/8 LIQUID LINE

2TWB0030AA WITH TWE040CA4-B AT 1100 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.73
1.83
1.88
1.93
1.79
1.89
1.95
2.00
1.85
1.96
2.02
2.07
1.91
2.03
2.08
2.14
1.98
2.09
2.15
2.21
2.01
2.13
2.19
2.25
2.05
2.17
2.24
2.30
2.09
2.21
2.28
2.34
2.13
2.25
2.32
2.38
2.16
2.29
2.36
2.43
2.35
2.49
2.57
2.64
2.41
2.56
2.64
2.71
2.47
2.63
2.70
2.78
2.54
2.69
2.77
2.85
2.60
2.76
2.84
2.92
2.66
2.83
2.91
2.99

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1100 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
950
1250
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1125 CFM
HEATING CAP. (HIGH TEMP.) = 27658 BTUH
HEATING CAP. (LOW TEMP.) = 15867 BTUH
COMPR. POWER (HIGH TEMP.) = 2007 WATTS
COMPR. POWER (LOW TEMP.) = 1608 WATTS
HSPF (MIN DHR) = 7.47
COEFF. OF PERF. (HIGH TEMP.) = 3.23
COEFF. OF PERF. (LOW TEMP.) = 2.20
OUTDOOR FAN POWER = 179 WATTS
INDOOR FAN POWER = 309 WATTS
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION
AND 3/8 LIQUID LINE

2TWB0036AA WITH TWE030CA4 AT 1100 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.86
1.95
2.00
2.05
1.98
2.09
2.14
2.19
2.10
2.22
2.27
2.33
2.23
2.35
2.41
2.47
2.35
2.48
2.55
2.61
2.47
2.61
2.68
2.75
2.57
2.72
2.79
2.86
2.67
2.82
2.90
2.98
2.76
2.93
3.01
3.09
2.86
3.03
3.11
3.20
2.96
3.14
3.22
3.31
3.21
3.40
3.50
3.59
3.33
3.53
3.63
3.74
3.45
3.66
3.77
3.88
3.58
3.80
3.91
4.02
3.70
3.93
4.04
4.16
3.82
4.06
4.18
4.30

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1100 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
950
1250
HEATING CAP.
X0.98
X1.01
COMPR. KW
X1.03
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1125 CFM
HEATING CAP. (HIGH TEMP.) = 35184 BTUH
HEATING CAP. (LOW TEMP.) = 20137 BTUH
COMPR. POWER (HIGH TEMP.) = 2683 WATTS
COMPR. POWER (LOW TEMP.) = 1897 WATTS
HSPF (MIN DHR) = 7.74
COEFF. OF PERF. (HIGH TEMP.) = 3.01
COEFF. OF PERF. (LOW TEMP.) = 2.24
OUTDOOR FAN POWER = 177 WATTS
INDOOR FAN POWER = 541 WATTS
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION
AND 3/8 LIQUID LINE

22

TWE5_PRC001_EN_081703.PMD

22

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Heating

Metric Units

2TWB0030AA WITH TWE030CA4 AT 1698 CMH


O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.5
2.5
2.5
2.4
3.1
3.0
3.0
3.0
3.7
3.6
3.6
3.5
4.2
4.2
4.1
4.1
4.8
4.7
4.7
4.6
5.0
4.9
4.8
4.8
5.1
5.0
5.0
4.9
5.3
5.2
5.1
5.0
5.4
5.3
5.2
5.2
5.6
5.4
5.4
5.3
8.3
8.1
8.0
7.9
8.8
8.6
8.6
8.5
9.4
9.2
9.1
9.0
10.0
9.8
9.7
9.6
10.6
10.3
10.2
10.1
11.1
10.9
10.8
10.6

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.4
2.3
2.3
2.3
3.0
2.9
2.9
2.9
3.6
3.5
3.5
3.4
4.2
4.1
4.0
4.0
4.7
4.6
4.6
4.5
4.9
4.8
4.7
4.7
5.1
5.0
4.9
4.8
5.2
5.1
5.0
5.0
5.4
5.3
5.2
5.2
5.5
5.4
5.4
5.3
8.3
8.1
8.0
7.9
8.8
8.7
8.6
8.5
9.5
9.2
9.1
9.0
10.0
9.8
9.7
9.6
10.6
10.4
10.3
10.1
11.2
11.0
10.8
10.7

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.2
2.2
2.2
2.2
3.0
3.0
2.9
2.9
3.8
3.7
3.7
3.6
4.5
4.4
4.4
4.3
5.2
5.2
5.1
5.1
6.0
5.9
5.8
5.8
6.3
6.2
6.2
6.1
6.7
6.6
6.5
6.4
7.0
6.9
6.9
6.8
7.4
7.3
7.2
7.1
7.8
7.6
7.5
7.5
10.5
10.3
10.2
10.1
11.2
11.0
10.9
10.8
12.0
11.7
11.6
11.5
12.7
12.5
12.4
12.2
13.5
13.2
13.1
13.0
14.2
13.9
13.8
13.7

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.9
2.0
2.0
2.1
1.9
2.0
2.1
2.1
2.0
2.1
2.2
2.2
2.1
2.2
2.3
2.3
2.2
2.3
2.3
2.4
2.2
2.3
2.4
2.5
2.3
2.4
2.4
2.5
2.3
2.4
2.5
2.5
2.3
2.5
2.5
2.6
2.4
2.5
2.6
2.7
2.6
2.8
2.8
2.9
2.7
2.8
2.9
3.0
2.8
2.9
3.0
3.1
2.8
3.0
3.1
3.2
2.9
3.1
3.2
3.3
3.0
3.2
3.3
3.3

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1698 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1486
1910
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1698 CMH
HEATING CAP. (HIGH TEMP.) = 8.09 KW
HEATING CAP. (LOW TEMP.) = 4.73 KW
COMPR. POWER (HIGH TEMP.) = 2151 WATTS
COMPR. POWER (LOW TEMP.) = 1668 WATTS
HSPF (MIN DHR) = 6.96
COEFF. OF PERF. (HIGH TEMP.) = 2.91
COEFF. OF PERF. (LOW TEMP.) = 2.06
OUTDOOR FAN POWER = 179 WATTS
INDOOR FAN POWER = 437 WATTS
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
SUCTION AND 3/8 LIQUID LINE

2TWB0030AA WITH TWE040CA4-B AT 1868 CMH


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.7
1.8
1.9
1.9
1.8
1.9
2.0
2.0
1.9
2.0
2.0
2.1
1.9
2.0
2.1
2.1
2.0
2.1
2.2
2.2
2.0
2.1
2.2
2.3
2.0
2.2
2.2
2.3
2.1
2.2
2.3
2.3
2.1
2.3
2.3
2.4
2.2
2.3
2.4
2.4
2.3
2.5
2.6
2.6
2.4
2.6
2.6
2.7
2.5
2.6
2.7
2.8
2.5
2.7
2.8
2.8
2.6
2.8
2.8
2.9
2.7
2.8
2.9
3.0

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1868 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1613
2123
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEATING CAP. (HIGH TEMP.) = 8.10 KW
HEATING CAP. (LOW TEMP.) = 4.65 KW
COMPR. POWER (HIGH TEMP.) = 2007 WATTS
COMPR. POWER (LOW TEMP.) = 1608 WATTS
HSPF (MIN DHR) = 7.47
COEFF. OF PERF. (HIGH TEMP.) = 3.23
COEFF. OF PERF. (LOW TEMP.) = 2.20
OUTDOOR FAN POWER = 179 WATTS
INDOOR FAN POWER = 309 WATTS
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
SUCTION AND 3/8 LIQUID LINE

2TWB0036AA WITH TWE030CA4 AT 1868 CMH

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

23

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.9
2.0
2.0
2.0
2.0
2.1
2.1
2.2
2.1
2.2
2.3
2.3
2.2
2.3
2.4
2.5
2.3
2.5
2.5
2.6
2.5
2.6
2.7
2.8
2.6
2.7
2.8
2.9
2.7
2.8
2.9
3.0
2.8
2.9
3.0
3.1
2.9
3.0
3.1
3.2
3.0
3.1
3.2
3.3
3.2
3.4
3.5
3.6
3.3
3.5
3.6
3.7
3.5
3.7
3.8
3.9
3.6
3.8
3.9
4.0
3.7
3.9
4.0
4.2
3.8
4.1
4.2
4.3

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1868 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1613
2123
HEATING CAP.
X0.98
X1.01
COMPR. KW
X1.03
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEATING CAP. (HIGH TEMP.) = 10.31 KW
HEATING CAP. (LOW TEMP.) = 5.90 KW
COMPR. POWER (HIGH TEMP.) = 2683 WATTS
COMPR. POWER (LOW TEMP.) = 1897 WATTS
HSPF (MIN DHR) = 7.74
COEFF. OF PERF. (HIGH TEMP.) = 3.01
COEFF. OF PERF. (LOW TEMP.) = 2.24
OUTDOOR FAN POWER = 177 WATTS
INDOOR FAN POWER = 541 WATTS
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
SUCTION AND 3/8 LIQUID LINE

23

9/15/2003, 3:07 PM

Performance Data
Heating
English Units
2TWB0036AA WITH TWE040CA4-B AT 1400 CFM
O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
7.16
7.05
6.99
6.94
9.83
9.67
9.58
9.50
12.5
12.3
12.2
12.1
15.2
14.9
14.8
14.6
17.8
17.5
17.4
17.2
20.5
20.1
19.9
19.8
21.8
21.4
21.2
21.0
23.1
22.7
22.5
22.2
24.4
23.9
23.7
23.5
25.7
25.2
25.0
24.7
26.9
26.5
26.2
26.0
36.5
35.8
35.5
35.2
39.2
38.5
38.1
37.7
41.9
41.1
40.7
40.3
44.5
43.7
43.3
42.8
47.2
46.3
45.9
45.4
49.9
48.9
48.4
48.0

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.75
1.86
1.91
1.97
1.85
1.97
2.03
2.08
1.95
2.08
2.14
2.20
2.05
2.19
2.25
2.32
2.15
2.30
2.37
2.44
2.25
2.40
2.48
2.56
2.33
2.49
2.57
2.65
2.41
2.58
2.66
2.74
2.50
2.67
2.75
2.84
2.58
2.75
2.84
2.93
2.66
2.84
2.93
3.02
2.86
3.06
3.16
3.26
2.96
3.17
3.28
3.38
3.07
3.28
3.39
3.50
3.17
3.39
3.50
3.62
3.27
3.50
3.62
3.73
3.37
3.61
3.73
3.85

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1400 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1225
1575
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1350 CFM
HEATING CAP. (HIGH TEMP.) = 35733 BTUH
HEATING CAP. (LOW TEMP.) = 20058 BTUH
COMPR. POWER (HIGH TEMP.) = 2533 WATTS
COMPR. POWER (LOW TEMP.) = 1871 WATTS
HSPF (MIN DHR) = 8.40
COEFF. OF PERF. (HIGH TEMP.) = 3.40
COEFF. OF PERF. (LOW TEMP.) = 2.43
OUTDOOR FAN POWER = 177 WATTS
INDOOR FAN POWER = 356 WATTS
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION
AND 3/8 LIQUID LINE

24

TWE5_PRC001_EN_081703.PMD

24

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Heating

Metric Units

2TWB0036AA WITH TWE040CA4-B AT 2378 CMH


O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.1
2.1
2.0
2.0
2.9
2.8
2.8
2.8
3.7
3.6
3.6
3.5
4.5
4.4
4.3
4.3
5.2
5.1
5.1
5.0
6.0
5.9
5.8
5.8
6.4
6.3
6.2
6.2
6.8
6.7
6.6
6.5
7.1
7.0
6.9
6.9
7.5
7.4
7.3
7.2
7.9
7.8
7.7
7.6
10.7
10.5
10.4
10.3
11.5
11.3
11.2
11.0
12.3
12.0
11.9
11.8
13.0
12.8
12.7
12.5
13.8
13.6
13.4
13.3
14.6
14.3
14.2
14.1

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

25

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.8
1.9
1.9
2.0
1.9
2.0
2.0
2.1
2.0
2.1
2.1
2.2
2.0
2.2
2.3
2.3
2.2
2.3
2.4
2.4
2.3
2.4
2.5
2.6
2.3
2.5
2.6
2.7
2.4
2.6
2.7
2.7
2.5
2.7
2.8
2.8
2.6
2.8
2.8
2.9
2.7
2.8
2.9
3.0
2.9
3.1
3.2
3.3
3.0
3.2
3.3
3.4
3.1
3.3
3.4
3.5
3.2
3.4
3.5
3.6
3.3
3.5
3.6
3.7
3.4
3.6
3.7
3.8

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 2378 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
2080
2675
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2293 CMH
HEATING CAP. (HIGH TEMP.) = 10.47 KW
HEATING CAP. (LOW TEMP.) = 5.88 KW
COMPR. POWER (HIGH TEMP.) = 2533 WATTS
COMPR. POWER (LOW TEMP.) = 1871 WATTS
HSPF (MIN DHR) = 8.40
COEFF. OF PERF. (HIGH TEMP.) = 3.40
COEFF. OF PERF. (LOW TEMP.) = 2.43
OUTDOOR FAN POWER = 177 WATTS
INDOOR FAN POWER = 356 WATTS
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
SUCTION AND 3/8 LIQUID LINE

25

9/15/2003, 3:07 PM

Performance Data
Heating
English Units
2TWA0030AD WITH TWE030CA4 AT 1000 CFM
O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
8.86
8.70
8.62
8.55
11.0
10.8
10.7
10.6
13.2
12.9
12.8
12.7
15.3
15.0
14.9
14.7
17.4
17.1
16.9
16.8
17.9
17.5
17.3
17.2
18.3
17.9
17.8
17.6
18.7
18.4
18.2
18.0
19.1
18.8
18.6
18.4
19.6
19.2
19.0
18.8
30.3
29.7
29.4
29.1
32.5
31.8
31.5
31.2
34.6
33.9
33.6
33.2
36.8
36.0
35.6
35.3
38.9
38.1
37.7
37.3
41.1
40.2
39.8
39.4

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
8.37
8.21
8.13
8.06
10.6
10.4
10.3
10.2
12.8
12.6
12.4
12.3
15.0
14.7
14.6
14.4
17.3
16.9
16.7
16.6
17.7
17.4
17.2
17.0
18.2
17.8
17.6
17.5
18.7
18.3
18.1
17.9
19.1
18.7
18.5
18.4
19.6
19.2
19.0
18.8
30.6
30.0
29.6
29.3
32.8
32.1
31.8
31.5
35.0
34.3
33.9
33.6
37.3
36.5
36.1
35.7
39.5
38.7
38.3
37.8
41.7
40.8
40.4
40.0

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
9.23
9.08
9.01
8.93
12.0
11.8
11.7
11.6
14.8
14.6
14.5
14.3
17.7
17.3
17.2
17.0
20.5
20.1
19.9
19.7
21.4
21.1
20.9
20.7
22.4
22.0
21.8
21.6
23.4
23.0
22.8
22.6
24.4
23.9
23.7
23.5
25.3
24.9
24.7
24.5
37.3
36.6
36.3
36.0
40.1
39.4
39.0
38.7
42.9
42.1
41.7
41.4
45.7
44.9
44.5
44.1
48.5
47.6
47.2
46.8
51.3
50.4
49.9
49.5

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.91
2.03
2.08
2.14
2.00
2.12
2.18
2.24
2.09
2.22
2.28
2.35
2.18
2.32
2.38
2.45
2.27
2.41
2.49
2.56
2.32
2.47
2.54
2.61
2.37
2.52
2.59
2.67
2.42
2.57
2.65
2.72
2.46
2.62
2.70
2.78
2.51
2.67
2.75
2.83
2.81
3.00
3.09
3.18
2.90
3.09
3.19
3.28
2.99
3.19
3.29
3.39
3.08
3.29
3.39
3.49
3.17
3.38
3.49
3.60
3.26
3.48
3.59
3.70

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1000 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
875
1125
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.03
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1000 CFM
HEATING CAP. (HIGH TEMP.) = 29711 BTUH
HEATING CAP. (LOW TEMP.) = 17106 BTUH
COMPR. POWER (HIGH TEMP.) = 2378 WATTS
COMPR. POWER (LOW TEMP.) = 1796 WATTS
HSPF (MIN DHR) = 6.91
COEFF. OF PERF. (HIGH TEMP.) = 2.89
COEFF. OF PERF. (LOW TEMP.) = 2.06
OUTDOOR FAN POWER = 181 WATTS
INDOOR FAN POWER = 437 WATTS
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION
AND 3/8 LIQUID LINE

2TWA0030AD WITH TWE040CA4-B AT 1100 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.76
1.89
1.95
2.01
1.84
1.97
2.03
2.10
1.91
2.05
2.12
2.19
1.99
2.13
2.21
2.28
2.07
2.22
2.29
2.37
2.11
2.26
2.34
2.41
2.15
2.30
2.38
2.46
2.18
2.34
2.42
2.51
2.22
2.39
2.47
2.55
2.26
2.43
2.51
2.60
2.52
2.71
2.81
2.90
2.60
2.79
2.89
2.99
2.67
2.88
2.98
3.08
2.75
2.96
3.06
3.17
2.83
3.04
3.15
3.26
2.90
3.12
3.23
3.34

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1100 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
950
1250
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1125 CFM
HEATING CAP. (HIGH TEMP.) = 30013 BTUH
HEATING CAP. (LOW TEMP.) = 16951 BTUH
COMPR. POWER (HIGH TEMP.) = 2219 WATTS
COMPR. POWER (LOW TEMP.) = 1726 WATTS
HSPF (MIN DHR) = 7.46
COEFF. OF PERF. (HIGH TEMP.) = 3.23
COEFF. OF PERF. (LOW TEMP.) = 2.24
OUTDOOR FAN POWER = 181 WATTS
INDOOR FAN POWER = 309 WATTS
NOTE: RATED WITH 25 FEET OF 7/8 SUCTION
AND 3/8 LIQUID LINE

2TWA0040AD WITH TWE040CA4-B AT 1300 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
1.94
2.05
2.11
2.17
2.05
2.17
2.23
2.29
2.15
2.28
2.35
2.41
2.26
2.40
2.46
2.53
2.37
2.51
2.58
2.65
2.45
2.60
2.67
2.75
2.53
2.68
2.76
2.84
2.61
2.77
2.85
2.93
2.69
2.86
2.94
3.02
2.77
2.94
3.03
3.11
3.01
3.20
3.29
3.38
3.11
3.31
3.41
3.51
3.22
3.42
3.53
3.63
3.33
3.54
3.64
3.75
3.43
3.65
3.76
3.87
3.54
3.77
3.88
3.99

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1300 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1150
1500
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1325 CFM
HEATING CAP. (HIGH TEMP.) = 36683 BTUH
HEATING CAP. (LOW TEMP.) = 20141 BTUH
COMPR. POWER (HIGH TEMP.) = 2601 WATTS
COMPR. POWER (LOW TEMP.) = 1918 WATTS
HSPF (MIN DHR) = 7.91
COEFF. OF PERF. (HIGH TEMP.) = 3.35
COEFF. OF PERF. (LOW TEMP.) = 2.34
OUTDOOR FAN POWER = 232 WATTS
INDOOR FAN POWER = 360 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION
AND 3/8 LIQUID LINE

26

TWE5_PRC001_EN_081703.PMD

26

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Heating

Metric Units

2TWA0030AD WITH TWE030CA4 AT 1698 CMH


O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.6
2.5
2.5
2.5
3.2
3.2
3.1
3.1
3.9
3.8
3.8
3.7
4.5
4.4
4.4
4.3
5.1
5.0
5.0
4.9
5.2
5.1
5.1
5.0
5.4
5.2
5.2
5.2
5.5
5.4
5.3
5.3
5.6
5.5
5.4
5.4
5.7
5.6
5.6
5.5
8.9
8.7
8.6
8.5
9.5
9.3
9.2
9.1
10.1
9.9
9.8
9.7
10.8
10.5
10.4
10.3
11.4
11.2
11.0
10.9
12.0
11.8
11.7
11.5

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.5
2.4
2.4
2.4
3.1
3.0
3.0
3.0
3.8
3.7
3.6
3.6
4.4
4.3
4.3
4.2
5.1
5.0
4.9
4.9
5.2
5.1
5.0
5.0
5.3
5.2
5.2
5.1
5.5
5.4
5.3
5.2
5.6
5.5
5.4
5.4
5.7
5.6
5.6
5.5
9.0
8.8
8.7
8.6
9.6
9.4
9.3
9.2
10.3
10.0
9.9
9.8
10.9
10.7
10.6
10.5
11.6
11.3
11.2
11.1
12.2
12.0
11.8
11.7

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.7
2.7
2.6
2.6
3.5
3.5
3.4
3.4
4.3
4.3
4.2
4.2
5.2
5.1
5.0
5.0
6.0
5.9
5.8
5.8
6.3
6.2
6.1
6.1
6.6
6.4
6.4
6.3
6.9
6.7
6.7
6.6
7.1
7.0
6.9
6.9
7.4
7.3
7.2
7.2
10.9
10.7
10.6
10.5
11.7
11.5
11.4
11.3
12.6
12.3
12.2
12.1
13.4
13.2
13.0
12.9
14.2
13.9
13.8
13.7
15.0
14.8
14.6
14.5

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.9
2.0
2.1
2.1
2.0
2.1
2.2
2.2
2.1
2.2
2.3
2.3
2.2
2.3
2.4
2.5
2.3
2.4
2.5
2.6
2.3
2.5
2.5
2.6
2.4
2.5
2.6
2.7
2.4
2.6
2.7
2.7
2.5
2.6
2.7
2.8
2.5
2.7
2.8
2.8
2.8
3.0
3.1
3.2
2.9
3.1
3.2
3.3
3.0
3.2
3.3
3.4
3.1
3.3
3.4
3.5
3.2
3.4
3.5
3.6
3.3
3.5
3.6
3.7

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1698 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1486
1910
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.03
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1698 CMH
HEATING CAP. (HIGH TEMP.) = 8.71 KW
HEATING CAP. (LOW TEMP.) = 5.01 KW
COMPR. POWER (HIGH TEMP.) = 2378 WATTS
COMPR. POWER (LOW TEMP.) = 1796 WATTS
HSPF (MIN DHR) = 6.91
COEFF. OF PERF. (HIGH TEMP.) = 2.89
COEFF. OF PERF. (LOW TEMP.) = 2.06
OUTDOOR FAN POWER = 181 WATTS
INDOOR FAN POWER = 437 WATTS
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
SUCTION AND 3/8 LIQUID LINE

2TWA0030AD WITH TWE040CA4-B AT 1868 CMH


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.8
1.9
2.0
2.0
1.8
2.0
2.0
2.1
1.9
2.0
2.1
2.2
2.0
2.1
2.2
2.3
2.1
2.2
2.3
2.4
2.1
2.3
2.3
2.4
2.2
2.3
2.4
2.5
2.2
2.3
2.4
2.5
2.2
2.4
2.5
2.5
2.3
2.4
2.5
2.6
2.5
2.7
2.8
2.9
2.6
2.8
2.9
3.0
2.7
2.9
3.0
3.1
2.8
3.0
3.1
3.2
2.8
3.0
3.2
3.3
2.9
3.1
3.2
3.3

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1868 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1613
2123
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 1910 CMH
HEATING CAP. (HIGH TEMP.) = 8.79 KW
HEATING CAP. (LOW TEMP.) = 4.97 KW
COMPR. POWER (HIGH TEMP.) = 2219 WATTS
COMPR. POWER (LOW TEMP.) = 1726 WATTS
HSPF (MIN DHR) = 7.46
COEFF. OF PERF. (HIGH TEMP.) = 3.23
COEFF. OF PERF. (LOW TEMP.) = 2.24
OUTDOOR FAN POWER = 181 WATTS
INDOOR FAN POWER = 309 WATTS
NOTE: RATED WITH 7.62 METERS OF 7/8 IN.
SUCTION AND 3/8 LIQUID LINE

2TWA0040AD WITH TWE040CA4-B AT 2208 CMH

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

27

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.9
2.0
2.1
2.2
2.0
2.2
2.2
2.3
2.2
2.3
2.3
2.4
2.3
2.4
2.5
2.5
2.4
2.5
2.6
2.7
2.5
2.6
2.7
2.8
2.5
2.7
2.8
2.8
2.6
2.8
2.8
2.9
2.7
2.9
2.9
3.0
2.8
2.9
3.0
3.1
3.0
3.2
3.3
3.4
3.1
3.3
3.4
3.5
3.2
3.4
3.5
3.6
3.3
3.5
3.6
3.8
3.4
3.7
3.8
3.9
3.5
3.8
3.9
4.0

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 2208 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1953
2547
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2250 CMH
HEATING CAP. (HIGH TEMP.) = 10.75 KW
HEATING CAP. (LOW TEMP.) = 5.90 KW
COMPR. POWER (HIGH TEMP.) = 2601 WATTS
COMPR. POWER (LOW TEMP.) = 1918 WATTS
HSPF (MIN DHR) = 7.91
COEFF. OF PERF. (HIGH TEMP.) = 3.35
COEFF. OF PERF. (LOW TEMP.) = 2.34
OUTDOOR FAN POWER = 232 WATTS
INDOOR FAN POWER = 360 WATTS
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN.
SUCTION AND 3/8 LIQUID LINE

27

9/15/2003, 3:07 PM

Performance Data
Heating
English Units
2TWA0040AD WITH TWE050CA5-C AT 1600 CFM
O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
9.83
9.68
9.60
9.53
12.7
12.5
12.4
12.3
15.6
15.3
15.2
15.1
18.5
18.1
18.0
17.8
21.3
21.0
20.8
20.6
22.3
21.9
21.7
21.5
23.3
22.9
22.7
22.5
24.3
23.9
23.7
23.4
25.3
24.8
24.6
24.4
26.3
25.8
25.6
25.3
38.6
37.9
37.6
37.2
41.5
40.7
40.3
40.0
44.3
43.5
43.1
42.7
47.2
46.4
45.9
45.5
50.1
49.2
48.7
48.3
53.0
52.0
51.5
51.1

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
12.0
11.9
11.8
11.7
15.4
15.1
15.0
14.9
18.7
18.4
18.2
18.1
22.0
21.6
21.4
21.2
25.3
24.9
24.6
24.4
28.6
28.1
27.9
27.6
29.7
29.2
29.0
28.7
30.9
30.3
30.1
29.8
32.0
31.4
31.2
30.9
33.1
32.6
32.3
32.0
34.3
33.7
33.4
33.0
48.5
47.6
47.2
46.7
51.8
50.9
50.4
49.9
55.1
54.1
53.6
53.1
58.4
57.4
56.8
56.3
61.8
60.6
60.0
59.5
65.1
63.9
63.3
62.7

O.D.
TEMP.
F.
-18
-13
-8
-3
2
7
12
17
22
27
32
37
42
47
52
57
62
67
72

HEATING CAPACITY (BTUH/1000) AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
20.1
20.0
19.9
19.9
23.3
23.2
23.2
23.1
26.5
26.4
26.4
26.3
29.8
29.7
29.6
29.6
33.0
32.9
32.8
32.8
36.2
36.1
36.0
36.0
36.9
36.8
36.7
36.7
37.6
37.5
37.4
37.3
38.3
38.2
38.1
38.0
39.0
38.9
38.8
38.7
39.7
39.5
39.5
39.4
55.7
55.5
55.4
55.3
58.9
58.7
58.6
58.5
62.2
61.9
61.8
61.7
65.4
65.2
65.0
64.9
68.6
68.4
68.2
68.1
71.9
71.6
71.5
71.3

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
2.11
2.23
2.29
2.35
2.21
2.33
2.40
2.46
2.30
2.44
2.50
2.57
2.40
2.54
2.61
2.68
2.49
2.64
2.71
2.79
2.56
2.72
2.79
2.87
2.63
2.79
2.87
2.95
2.70
2.87
2.95
3.03
2.77
2.94
3.03
3.11
2.84
3.02
3.11
3.19
3.06
3.25
3.34
3.44
3.15
3.35
3.45
3.55
3.25
3.45
3.55
3.66
3.34
3.55
3.66
3.77
3.44
3.66
3.76
3.87
3.53
3.76
3.87
3.98

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1600 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1400
1800
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1575 CFM
HEATING CAP. (HIGH TEMP.) = 37841 BTUH
HEATING CAP. (LOW TEMP.) = 20922 BTUH
COMPR. POWER (HIGH TEMP.) = 2486 WATTS
COMPR. POWER (LOW TEMP.) = 1875 WATTS
HSPF (MIN DHR) = 7.85
COEFF. OF PERF. (HIGH TEMP.) = 3.40
COEFF. OF PERF. (LOW TEMP.) = 2.32
OUTDOOR FAN POWER = 232 WATTS
INDOOR FAN POWER = 529 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION
AND 3/8 LIQUID LINE

2TWA0050AD WITH TWE050CA5-C AT 1800 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
2.58
2.71
2.78
2.84
2.73
2.87
2.94
3.01
2.87
3.02
3.09
3.17
3.01
3.17
3.25
3.33
3.15
3.32
3.41
3.49
3.30
3.48
3.57
3.66
3.41
3.60
3.69
3.79
3.52
3.72
3.82
3.92
3.64
3.84
3.95
4.05
3.75
3.97
4.07
4.18
3.87
4.09
4.20
4.31
4.15
4.39
4.51
4.63
4.29
4.54
4.67
4.79
4.43
4.70
4.83
4.96
4.58
4.85
4.98
5.12
4.72
5.00
5.14
5.28
4.86
5.15
5.30
5.44

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1800 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1575
2025
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1750 CFM
HEATING CAP. (HIGH TEMP.) = 47491 BTUH
HEATING CAP. (LOW TEMP.) = 28015 BTUH
COMPR. POWER (HIGH TEMP.) = 3465 WATTS
COMPR. POWER (LOW TEMP.) = 2547 WATTS
HSPF (MIN DHR) = 7.81
COEFF. OF PERF. (HIGH TEMP.) = 3.17
COEFF. OF PERF. (LOW TEMP.) = 2.36
OUTDOOR FAN POWER = 189 WATTS
INDOOR FAN POWER = 731 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION
AND 3/8 LIQUID LINE

2TWA0060AD WITH TWE050CA5-C AT 1800 CFM


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
60
70
75
80
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
4.64
4.96
5.12
5.28
4.68
5.00
5.16
5.32
4.72
5.04
5.20
5.37
4.75
5.08
5.24
5.41
4.79
5.12
5.29
5.45
4.83
5.16
5.33
5.49
4.75
5.08
5.24
5.40
4.67
5.00
5.16
5.32
4.60
4.91
5.07
5.23
4.52
4.83
4.99
5.14
4.45
4.75
4.90
5.05
5.04
5.39
5.57
5.75
5.08
5.43
5.61
5.79
5.12
5.47
5.65
5.83
5.15
5.51
5.69
5.87
5.19
5.55
5.73
5.91
5.23
5.59
5.77
5.96

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 1800 CFM TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
1575
2025
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.03
X0.97
VALUES AT ARI RATING CONDITIONS OF:
70&47/43 (HIGH TEMP. POINT)
70&17/15 (LOW TEMP. POINT)
AIRFLOW = 1750 CFM
HEATING CAP. (HIGH TEMP.) = 55384 BTUH
HEATING CAP. (LOW TEMP.) = 36031 BTUH
COMPR. POWER (HIGH TEMP.) = 4494 WATTS
COMPR. POWER (LOW TEMP.) = 4257 WATTS
HSPF (MIN DHR) = 7.57
COEFF. OF PERF. (HIGH TEMP.) = 2.99
COEFF. OF PERF. (LOW TEMP.) = 2.02
OUTDOOR FAN POWER = 179 WATTS
INDOOR FAN POWER = 731 WATTS
NOTE: RATED WITH 25 FEET OF 1-1/8 SUCTION
AND 3/8 LIQUID LINE

28

TWE5_PRC001_EN_081703.PMD

28

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance Data
Heating

Metric Units

2TWA0040AD WITH TWE050CA5-C AT 2717 CMH


O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.9
2.8
2.8
2.8
3.7
3.7
3.6
3.6
4.6
4.5
4.5
4.4
5.4
5.3
5.3
5.2
6.2
6.2
6.1
6.0
6.5
6.4
6.4
6.3
6.8
6.7
6.7
6.6
7.1
7.0
6.9
6.9
7.4
7.3
7.2
7.1
7.7
7.6
7.5
7.4
11.3
11.1
11.0
10.9
12.2
11.9
11.8
11.7
13.0
12.7
12.6
12.5
13.8
13.6
13.4
13.3
14.7
14.4
14.3
14.2
15.5
15.2
15.1
15.0

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
3.5
3.5
3.5
3.4
4.5
4.4
4.4
4.4
5.5
5.4
5.3
5.3
6.4
6.3
6.3
6.2
7.4
7.3
7.2
7.1
8.4
8.2
8.2
8.1
8.7
8.6
8.5
8.4
9.1
8.9
8.8
8.7
9.4
9.2
9.1
9.1
9.7
9.6
9.5
9.4
10.0
9.9
9.8
9.7
14.2
13.9
13.8
13.7
15.2
14.9
14.8
14.6
16.1
15.9
15.7
15.6
17.1
16.8
16.6
16.5
18.1
17.8
17.6
17.4
19.1
18.7
18.5
18.4

O.D.
TEMP.
C.
-27.8
-25.0
-22.2
-19.4
-16.7
-13.9
-11.1
-8.3
-5.6
-2.8
0.0
2.8
5.6
8.3
11.1
13.9
16.7
19.4
22.2

HEATING CAPACITY IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
5.9
5.9
5.8
5.8
6.8
6.8
6.8
6.8
7.8
7.7
7.7
7.7
8.7
8.7
8.7
8.7
9.7
9.6
9.6
9.6
10.6
10.6
10.5
10.5
10.8
10.8
10.8
10.8
11.0
11.0
11.0
10.9
11.2
11.2
11.2
11.1
11.4
11.4
11.4
11.3
11.6
11.6
11.6
11.5
16.3
16.3
16.2
16.2
17.3
17.2
17.2
17.1
18.2
18.1
18.1
18.1
19.2
19.1
19.0
19.0
20.1
20.0
20.0
20.0
21.1
21.0
20.9
20.9

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.1
2.2
2.3
2.3
2.2
2.3
2.4
2.5
2.3
2.4
2.5
2.6
2.4
2.5
2.6
2.7
2.5
2.6
2.7
2.8
2.6
2.7
2.8
2.9
2.6
2.8
2.9
3.0
2.7
2.9
3.0
3.0
2.8
2.9
3.0
3.1
2.8
3.0
3.1
3.2
3.1
3.3
3.3
3.4
3.2
3.3
3.5
3.5
3.3
3.5
3.5
3.7
3.3
3.5
3.7
3.8
3.4
3.7
3.8
3.9
3.5
3.8
3.9
4.0

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 2717 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
2378
3057
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2675 CMH
HEATING CAP. (HIGH TEMP.) = 11.09 KW
HEATING CAP. (LOW TEMP.) = 6.13 KW
COMPR. POWER (HIGH TEMP.) = 2486 WATTS
COMPR. POWER (LOW TEMP.) = 1875 WATTS
HSPF (MIN DHR) = 7.85
COEFF. OF PERF. (HIGH TEMP.) = 3.40
COEFF. OF PERF. (LOW TEMP.) = 2.32
OUTDOOR FAN POWER = 232 WATTS
INDOOR FAN POWER = 529 WATTS
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN.
SUCTION AND 3/8 LIQUID LINE

2TWA0050AD WITH TWE050CA5-C AT 3057 CMH


TOTAL POWER IN KILOWATTS AT
INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
2.6
2.7
2.8
2.8
2.7
2.9
2.9
3.0
2.9
3.0
3.1
3.2
3.0
3.2
3.3
3.3
3.2
3.3
3.4
3.5
3.3
3.5
3.6
3.7
3.4
3.6
3.7
3.8
3.5
3.7
3.8
3.9
3.6
3.8
4.0
4.1
3.8
4.0
4.1
4.2
3.9
4.1
4.2
4.3
4.2
4.4
4.5
4.6
4.3
4.5
4.7
4.8
4.4
4.7
4.8
5.0
4.6
4.8
5.0
5.1
4.7
5.0
5.1
5.3
4.9
5.2
5.3
5.4

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 3057 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
2675
3439
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.02
X0.98
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2972 CMH
HEATING CAP. (HIGH TEMP.) = 13.91 KW
HEATING CAP. (LOW TEMP.) = 8.21 KW
COMPR. POWER (HIGH TEMP.) = 3465 WATTS
COMPR. POWER (LOW TEMP.) = 2547 WATTS
HSPF (MIN DHR) = 7.81
COEFF. OF PERF. (HIGH TEMP.) = 3.17
COEFF. OF PERF. (LOW TEMP.) = 2.36
OUTDOOR FAN POWER = 189 WATTS
INDOOR FAN POWER = 731 WATTS
NOTE: RATED WITH 7.62 METERS OF 1 1/8 IN.
SUCTION AND 3/8 LIQUID LINE

2TWA0060AD WITH TWE050CA5-C AT 3057 CMH

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

29

TOTAL POWER IN KILOWATTS AT


INDICATED INDOOR DRY BULB TEMP.
15.6
21.1
23.9
26.7
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
4.6
5.0
5.1
5.3
4.7
5.0
5.2
5.3
4.7
5.0
5.2
5.4
4.8
5.1
5.2
5.4
4.8
5.1
5.3
5.4
4.8
5.2
5.3
5.5
4.8
5.1
5.2
5.4
4.7
5.0
5.2
5.3
4.6
4.9
5.1
5.2
4.5
4.8
5.0
5.1
4.4
4.8
4.9
5.1
5.0
5.4
5.6
5.8
5.1
5.4
5.6
5.8
5.1
5.5
5.7
5.8
5.2
5.5
5.7
5.9
5.2
5.6
5.7
5.9
5.2
5.6
5.8
6.0

CORRECTION FACTORS - OTHER AIRFLOWS


(VALUE AT 3057 CMH TIMES CORR. FACTOR
= VALUE AT NEW AIRFLOW)
AIRFLOW
2675
3439
HEATING CAP.
X0.99
X1.01
COMPR. KW
X1.03
X0.97
VALUES AT ARI RATING CONDITIONS OF:
21.1& 8.3/ 6.1(HIGH TEMP. POINT)
21.1&-8.3/-9.4(LOW TEMP. POINT)
AIRFLOW = 2972 CMH
HEATING CAP. (HIGH TEMP.) = 16.23 KW
HEATING CAP. (LOW TEMP.) = 10.56 KW
COMPR. POWER (HIGH TEMP.) = 4494 WATTS
COMPR. POWER (LOW TEMP.) = 4257 WATTS
HSPF (MIN DHR) = 7.57
COEFF. OF PERF. (HIGH TEMP.) = 2.99
COEFF. OF PERF. (LOW TEMP.) = 2.02
OUTDOOR FAN POWER = 179 WATTS
INDOOR FAN POWER = 731 WATTS
NOTE: RATED WITH 7.62 METERS OF 1-1/8 IN.
SUCTION AND 3/8 LIQUID LINE

29

9/15/2003, 3:07 PM

Performance
Data
Evaporator Fan Performance
Blower Performance TWE030CA40B Wet Coil

CFM
600
650
700
750
800
850
900
950
1000
1050
1100
1150
1200

CMH
1018.8
1103.7
1188.6
1273.5
1358.4
1443.3
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6

0.89
0.81
0.72
0.63
0.53
0.42
0.31
0.20
0.08

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)


UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
220 VOLTS
Hl
MED
LO
Hl
MED
LO
0.72 (179.4)
0.71 (176.9)
0.62 (154.4)
0.61 (152.0)
0.86 (214.2)
0.51 (127.0)
0.84 (209.2)
0.50 (124.6)
0.75 (186.8)
0.40
(99.6)
0.72 (179.4)
0.39
(97.1)
(221.7)
0.65 (161.9)
0.29
(72.2)
0.87 (216.7)
0.62 (154.4)
0.28
(69.7)
(201.8)
0.54 (134.5)
0.18
(44.8)
0.79 (196.8)
0.51 (127.0)
0.17
(42.3)
(179.4)
0.43 (107.1)
0.06
(14.9)
0.69 (171.9)
0.40
(99.6)
0.08
(19.9)
(156.9)
0.32
(79.7)
0.61 (152.0)
0.30
(74.7)
(132.0)
0.21
(52.3)
0.51 (127.0)
0.17
(42.3)
(104.6)
0.10
(24.9)
0.40
(99.6)
0.02
(5.0)
(77.2)
0.31
(77.2)
(49.8)
0.22
(54.8)
(19.9)
0.10
(24.9)

NOTES:
Vertical: With filter, no horizontal drip tray. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

Blower Performance TWE040CA40C Wet Coil

CFM
700
750
800
850
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500

CMH
1188.6
1273.5
1358.4
1443.3
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6
2122.5
2207.4
2292.3
2377.2
2462.1
2547.0

0.61
0.57
0.53
0.49
0.45
0.40
0.36
0.31
0.26
0.21
0.17
0.11
0.06
0.01
0.00

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)


UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
220 VOLTS
Hl
MED
LO
Hl
MED
LO
0.58 (144.5)
0.61 (152.0)
0.55 (137.0)
(152.0)
0.58 (144.5)
0.52 (129.5)
0.58 (144.5)
(142.0)
0.54 (134.5)
0.48 (119.6)
0.52 (129.5)
(132.0)
0.51 (127.0)
0.44 (109.6)
0.49 (122.1)
(122.1)
0.47 (117.1)
0.40
(99.6)
0.57 (142.0)
0.45 (112.1)
(112.1)
0.43 (107.1)
0.34
(84.7)
0.53 (132.0)
0.50 (124.6)
0.40
(99.6)
(99.6)
0.38
(94.7)
0.28
(69.7)
0.48 (119.6)
0.45 (112.1)
0.35
(87.2)
(89.7)
0.34
(84.7)
0.22
(54.8)
0.43 (107.1)
0.40
(99.6)
0.30
(74.7)
(77.2)
0.29
(72.2)
0.15
(37.4)
0.39
(97.1)
0.37
(92.2)
0.22
(54.8)
(64.8)
0.24
(59.8)
0.08
(19.9)
0.35
(87.2)
0.32
(79.7)
0.17
(42.3)
(52.3)
0.18
(44.8)
0.00
(0.0)
0.31
(77.2)
0.28
(69.7)
0.10
(24.9)
(42.3)
0.13
(32.4)
0.26
(64.8)
0.22
(54.8)
0.01
(2.5)
(27.4)
0.07
(17.4)
0.21
(52.3)
0.18
(44.8)
(14.9)
0.01
(2.5)
0.15
(37.4)
0.12
(29.9)
(2.5)
0.11
(27.4)
0.08
(19.9)
0.05
(12.5)
0.02
(5.0)

NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G. (12.5) for horizontal left.

30

TWE5_PRC001_EN_081703.PMD

30

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Performance
Data
Evaporator Fan Performance
Blower Performance TWE050CA50D Wet Coil

CFM
900
950
1000
1050
1100
1150
1200
1250
1300
1350
1400
1450
1500
1550
1600
1650
1700
1750
1800
1850
1900
1950

CMH
1528.2
1613.1
1698.0
1782.9
1867.8
1952.7
2037.6
2122.5
2207.4
2292.3
2377.2
2462.1
2547.0
2631.9
2716.8
2801.7
2886.6
2971.5
3056.4
3141.3
3226.2
3311.1

Hl

0.59
0.56
0.52
0.48
0.44
0.40
0.35
0.31
0.26
0.21
0.16
0.11
0.05

EXTERNAL STATIC PRESSURE INCHES OF WATER (PASCALS)


UPFLOW & DOWNFLOW (See Notes)
HORIZONTAL; NO FILTER (See Notes)
220 VOLTS
220 VOLTS
MED
LO
Hl
MED

(147.0)
(139.5)
(129.5)
(119.6)
(109.6)
(99.6)
(87.2)
(77.2)
(64.8)
(52.3)
(39.9)
(27.4)
(12.5)

0.61
0.57
0.53
0.49
0.45
0.40
0.35
0.30
0.25
0.20
0.14
0.08
0.02

(152.0)
(142.0)
(132.0)
(122.1)
(112.1)
(99.6)
(87.2)
(74.7)
(62.3)
(49.8)
(34.9)
(19.9)
(5.0)

0.63
0.61
0.58
0.54
0.50
0.45
0.39
0.33
0.26
0.18
0.10
0.01

(156.9)
(152.0)
(144.5)
(134.5)
(124.6)
(112.1)
(97.1)
(82.2)
(64.8)
(44.8)
(24.9)
(2.5)

0.62
0.59
0.56
0.52
0.49
0.47
0.45
0.41
0.36
0.30
0.24
0.17
0.10
0.02

(154.4)
(147.0)
(139.5)
(129.5)
(122.1)
(117.1)
(112.1)
(102.1)
(89.7)
(74.7)
(59.8)
(42.3)
(24.9)
(5.0)

0.64
0.61
0.58
0.55
0.52
0.48
0.44
0.40
0.35
0.28
0.20
0.13
0.07
0.01

NOTES:
Vertical: With filter, no horizontal drip tray. Small apex baffle. Subtract 0.06" W.G. (15) for downflow.
Horizontal: As shipped, but without filter. Subtract 0.05" W.G (12.5) for horizontal left.

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

31

31

9/15/2003, 3:07 PM

(159.4)
(152.0)
(144.5)
(137.0)
(129.5)
(119.6)
(109.6)
(99.6)
(87.2)
(69.7)
(49.8)
(32.4)
(17.4)
(2.5)

0.62
0.60
0.57
0.53
0.49
0.44
0.38
0.32
0.25
0.18
0.11
0.00

LO
(154.4)
(149.5)
(142.0)
(132.0)
(122.1)
(109.6)
(94.7)
(79.7)
(62.3)
(44.8)
(27.4)
(0.0)

Performance
Data
Air Pressure Drop (Inches) - Electric Heaters
Pressure Drop For Electric Heaters In Air Handler Models

1
AIRFLOW
CFM
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
1900
2000

AIRFLOW
CMH
1018.8
1188.6
1358.4
1528.2
1698.0
1867.8
2037.6
2207.4
2377.2
2547.0
2716.8
2886.6
3056.4
3226.2
3396.0

0.01
0.01
0.02
0.03
0.04
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14

(2.5)
(2.5)
(5.0)
(7.5)
(10.0)
(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(22.4)
(24.9)
(27.4)
(32.4)
(34.9)

0.02
0.02
0.03
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.15
0.17

NUMBER OF RACKS
3
AIR PRESSURE DROP
IN. W.G. (PASCALS)
(5.0)
0.02
(5.0)
(5.0)
0.02
(5.0)
(7.5)
0.03
(7.5)
(7.5)
0.04
(10.0)
(10.0)
0.05
(12.5)
(12.5)
0.06
(14.9)
(14.9)
0.07
(17.4)
(17.4)
0.08
(19.9)
(19.9)
0.10
(24.9)
(22.4)
0.11
(27.4)
(24.9)
0.12
(29.9)
(27.4)
0.14
(34.9)
(32.4)
0.16
(39.9)
(37.4)
0.18
(44.8)
(42.3)
0.20
(49.8)

0.04
0.05
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.19
0.21
0.23

(10.0)
(12.5)
(14.9)
(17.4)
(19.9)
(22.4)
(27.4)
(32.4)
(37.4)
(42.3)
(47.3)
(52.3)
(57.3)

0.08
0.09
0.11
0.13
0.15
0.17
0.19
0.21
0.23
0.26

(19.9)
(22.4)
(27.4)
(32.4)
(37.4)
(42.3)
(47.3)
(52.3)
(57.3)
(64.8)

NOTES:
1. See Product Data or Air Handler nameplate for approved combinations of Air Handlers and Heaters.
2. Heater model numbers may have additional suffix digits.

HEATER RACKS
HEATER
NO. OF
MODEL NO.
RACKS
BAY96X1405
1
BAY96X1406
2
BAY96X1408
2
BAY96X1410
2
BAY96X1411
3
BAY96X1415
3
BAY96X1419
4
BAY96X1421
4
BAY96X1426
5
BAY96X3411
3
BAY96X3415
3

32

TWE5_PRC001_EN_081703.PMD

32

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Minimum Airflow (CFM)


Heater Matrix
THESE AIR HANDLERS ARE CONVERTIBLE AND MOTOR SPEED TAPS VARY BY THE UNIT ORIENTATION.

A Heater Matrix for All TWE


MINIMUM HEATING AIRFLOW CFM HEATER MATRIX
AIR
HANDLER

HEATER MODEL NUMBER BAYHTR

MODEL
NUMBER

1405 000
BRK
PDC
4.80kw

1408 000
BRK
PDC
7.68kw

1410 000
BRK
PDC
3410 000
9.60kw

1415 BRK
15.36kw

3415 000
15.36kw

1419 BRK
19.20kw

1425 BRK
24.96kw

NUMBER OF
HEATER RACKS

NUMBER OF
CIRCUITS

TWE030C

L/L

L/L

L/L

L/L

L/L

TWE040C

L/L

L/L

L/L

L/L

L/L

L/H

L/H

TWE050C

L/L

L/L

L/L

L/L

L/L

L/H

L/H

000 = Pigtails, BRK = Contains circuit breakers, PDC = Contains Pull Disconnect
RBR = Contains recessed circuit breaker (for 14" deep TVF018-024 Models only)
RPD = contains recessed pull disconnect (for 14" deep TV0F18-024 Models only)
* For upflow position only minimum setting is 1200

(Example: L=Low, M=Medium, H=High Speed)


Cooling/Heat Pump Air Flow
AS = Heater application is affected based on whether the outdoor unit is
a heat pump or cooling unit.
PS = Minimum speed tap varies based on air handler installation position.

CAUTION: Any power supply and/or combination power supply, circuit or circuits must be wired and protected in accordance with local electrical codes.

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

33

33

9/15/2003, 3:07 PM

Electrical
Data
2TWB0012-0536AA System Wiring Diagram
Legend

Symbols

NOTES:
1. IF ODT-B IS NOT USED, ADD JUMPER
BETWEEN W2 & W3 AT AIR HANDLER.
IF USED, ODT-B MUST BE MOUNTED
REMOTE OF CONTROL BOX IN AN
APPROVED WEATHER PROOF
ENCLOSURE.
2. IF ODT-A IS NOT USED, ADD JUMPER
BETWEEN W1 & W2 AT AIR HANDLER.
3. LOW VOLTAGE (24 V.) FIELD WIRING
MUST BE 18 AWG MIN.

34

TWE5_PRC001_EN_081703.PMD

34

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Electrical
Data
2TWA0030-060AD System Wiring Diagram
Legend

Symbols

NOTES:
1. IF ODT-B IS NOT USED, ADD JUMPER
BETWEEN W2 & W3 AT AIR HANDLER.
IF USED, ODT-B MUST BE MOUNTED
REMOTE OF CONTROL BOX IN AN
APPROVED WEATHER PROOF
ENCLOSURE.
2. IF ODT-A IS NOT USED, ADD JUMPER
BETWEEN W1 & W2 AT AIR HANDLER.
3. LOW VOLTAGE (24 V.) FIELD WIRING
MUST BE 18 AWG MIN.

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

35

35

9/15/2003, 3:07 PM

Electrical
Data
TWE030-050C System Wiring Diagram
Legend

Symbols

NOTES:
1. DO NOT USE REQ TRANSFORMER LEAD IN THIS APPLICATION
2. ACCESSORY KIT BAY24X038 MAY BE USED WHEN AUTOMATIC SPEED
CHANGE FOR HEATING/COOLING OPERATION IS DESIRED.
3. A 220V HIGH VOLTAGE CONTROL IN TTB5-C NEEDS TO BE CHANGED
WITH 24V LOW VOLTAGE CONTROL KIT (ACYLVCR006A) WHEN MATCHED
WITH TWE-C AIR HANDLING UNITS.

36

TWE5_PRC001_EN_081703.PMD

36

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Dimensions
TWE030-050C Outline Drawing
ALL DIMENSIONS ARE IN INCHES (MM)

SIDES
FRONT
BACK
INLET DUCT
OUTLET DUCT

MINIMUM UNIT CLEARANCE SALE


TO COMBUSTIBLE
SERVICE CLEARANCE
MATERIAL (REQUIRED)
(RECOMMENDED)
0
(0)
2
(50.8)
0
(0)
21
(533.4)
0
(0)
0
(0)
0
(0)
1
(25.4)
1
(25.4)

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

37

MODEL NO.
TWE030CA4

A
B
43.00
15.57
(1092.2) (395.5)
TWE040CA4
51.75
24.32
(1134.5) (617.7)
TWE050CA5
57.90
30.47
(1470.7) (773.9)

C
21.50
(761.1)
23.50
(596.9)
23.50
(596.9)

37

9/15/2003, 3:07 PM

D
E
F
19.50
20.28
21.63
(495.3) (515.1) (549.4)
21.50
22.28
23.63
(761.1) (565.9) (600.2)
21.50
22.28
23.63
(761.1) (565.9) (600.2)

FLOW
CONTROL

FCCV
FCCV
TXV

Dimensions
2TWB0012-036AA Outline Drawing
All dimensions are in inches (mm)

MODELS

BASE FIG.

2TWB0012AA

651
724
651
( 25-5/8) (28-1/2) ( 25-5/8)

5/8

1/4

127
(5)

57
(2-1/4)

181
(7-1/8)

44
(1-3/4)

457
(18)

7/8-14 UNF- 2A

7/16-20 UNF- 2A

2TWB0018AA

651
724
651
( 25-5/8) (28-1/2) ( 25-5/8)

3/4

5/16

127
(5)

57
(2-1/4)

181
(7-1/8)

44
(1-3/4)

457
(18)

1 1/16-14 UNF- 2A

1/2-20 UNF- 2A

2TWB0024AA

730
(28-3/4)

724
651
(28-1/2) ( 25-5/8)

3/4

5/16

137
(5-3/4)

65
(2-5/8)

210
(8-1/4)

57
(2-1/4)

457
(18)

1 1/16-14 UNF- 2A

1/2-20 UNF- 2A

2TWB0030AA

730
(28-3/4)

724
651
(28-1/2) ( 25-5/8)

3/4

3/8

137
(5-3/4)

65
(2-5/8)

210
(8-1/4)

57
(2-1/4)

457
(18)

1 1/16-14 UNF- 2A

1/2-20 UNF- 2A

2TWB0036AA

832
(32-3/4)

829
(32-5/8)

3/4

3/8

137
(5-3/4)

86
(3-3/8)

210
(8-1/4)

79
(3-1/8)

508
(20)

1 1/16-14 UNF- 2A

1/2-20 UNF- 2A

756
(29-3/4)

From Dwg. 21D153509 Rev. 1


38

TWE5_PRC001_EN_081703.PMD

38

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Dimensions
2TWA0030-060AD Outline Drawing
All dimensions are in inches (mm)

MODELS

BASE FIG.

D
7/8

2TWA0030AD

730 (28-3/4) 724 (28-1/2) 651(25-5/8)

3/8 137 (5-3/8) 65 (2-5/8) 210 (8-1/4) 57 (2-1/4) 457 (18)

2TWA0040AD

832 (32-3/4) 829 (32-5/8) 756 (29-3/4) 1-1/8 3/8 137 (5-3/8) 86 (3-3/8) 210 (8-1/4) 79 (3-1/8) 508 (20)

2TWA0050AD

841 (33-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8

152 (6)

98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)

2TWA0060AD

1045 (41-1/8) 946 (37-1/4) 870 (34-1/4) 1-1/8 3/8

152 (6)

98 (3-7/8) 219 (8-5/8) 86 (3-3/8) 508 (20)

From Dwg. 21D153074 Rev. 6


TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

39

39

9/15/2003, 3:07 PM

Convertibility
TWE030 Through 050 Convertibility
Six (6) Way Convertibility

One Unit - 4 Applications

Easy Conversion to Opposite Side Access

40

TWE5_PRC001_EN_081703.PMD

40

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Mechanical
Specification Options
Condensing Units
General
The 2TWB0/2TWA0 is fully charged from
the factory for up to 15 feet of piping. This
unit is designed to operate at outdoor
ambient temperatures as high as 115F.
Cooling capacities are matched with a
wide selection of air handlers. Exterior is
designed for outdoor application.
Casing
Unit casing is constructed of heavy
gauge, G90 galvanized steel and painted
with a weather-resistant powder paint on
all louvers, panels, prepaint on all other
panels. Corrosion and weatherproof
CMBP-G30 DuraTuff base.
Refrigerant Controls
Refrigeration system controls include
condenser fan, compressor contactor
and high pressure switch. High and low
pressure controls are inherent to the
compressor. A factory installed liquid line
drier is standard.

Condenser Coil
The outdoor coil provides low airflow
resistance and efficient heat transfer. The
coil is protected on all four sides by
louvered panels and has a 5 year
limited warranty.
Low Ambient Cooling
As manufactured, this unit has a cooling
capability to 55F. The addition of an
evaporator defrost control permits
operation to 40 F. The addition of an
evaporator defrost control with TXV
permits low ambient cooling to 30 F.
Accessories
Thermostats Cooling only and
heat/cooling (manual and automatic
changeover). Sub-base to match thermostat and locking thermostat cover.
Evaporator Defrost Control See Low
Ambient Cooling.

Compressor
The Climatuff compressor features
internal over temperature and pressure
protection and total dipped hermetic
motor. Other features include: roto lock
suction and discharge refrigerant
connections, centrifugal oil pump and low
vibration and noise.

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

41

41

9/15/2003, 3:07 PM

Mechanical
Specification Options
Air Handling Units
General
Blower coil units shall be completely
factory assembled including coil, condensate drain pan, fan, motor, filters and
controls in an insulated casing that can
be applied in horizontal or vertical
configuration.
This new line of TWE-C air handlers
provides exclusive compact size combined with simple four-way convertibility
in three sizes. The unit ships in the right
hand horizontal configuration and
converts to vertical upflow just by
standing the unit on end. No tools
required. Simple coil rotation provides
downflow and horizontal left applications.
The four-way convertibility provides you
inventory benefits and service/installation
flexibility. The simple conversion provides
opposite side access for installation
and service.
Casing
Units shall have rugged sheet metal and
steel frame construction and shall be
painted with an enamel finish. Casing
shall be insulated and knockouts shall be
provided for electrical power and
control wiring.

Refrigerant Circuits
The TWE units shall have a single
refrigerant circuit. TWE03-040C refrigerant circuit shall be controlled by a flow
control check valve (FCCV). The
TWE050C refrigerant circuit shall be
controlled by a factory-installed thermal
expansion valve.
Coil
Aluminum fin surface shall be mechanically bonded to 3/8-inch OD copper
tubing. Coils shall be factory pressure
and leak tested.
Fan
Forward curved, dynamically and
statically balanced with three-speed
direct drive shall be standard, fan motor
bearing shall be permanently lubricated.
Controls
Fan contactor, and plug-in module for
accessory electric heat control shall be
included. TWE models shall also include
check valves.
Filters
Filters shall be included as standard.
Accessories
Electric Heaters Shall be available in
a wide range of capacities and voltages
with various staging options and plug in
control wiring. Heaters shall fit inside
internal compartment.

42

TWE5_PRC001_EN_081703.PMD

42

TWE5-PRC001-EN-08-17-03

9/15/2003, 3:07 PM

Notes

TWE5-PRC001-EN-08-17-03

TWE5_PRC001_EN_081703.PMD

43

43

9/15/2003, 3:07 PM

File Number

Trane
A business of
American Standard Companies
www.trane.com

TWE5_PRC001_EN_081703.PMD

44

TWE5-PRC001-EN-08-17-03

Supersedes

TWE5-PRC001-EN-10-15-99

Stocking Location

P.I.

Trane has a policy of continuous product and product data improvement and it reserves the right to change
design and specifications without notice.

9/15/2003, 3:07 PM