Sunteți pe pagina 1din 2

1

3 4

TECHNICAL SPECIFICATION FOR 30 KVA UPS (Non Modular) TECHNOLOGY Microprocessor/DSP controlled True On-line, Pure Sine Wave with Double conversion PWM Technology, using IGBT as switching devices. DISPLAY Monitoring panel with LCD/LED display to provide complete information for: Mains on, DC ON, UPS on, Bypass Voltage, Battery Voltage, Input Voltage, Rectifier Voltage, Output Frequency, Output Current, Load on Battery POWER RATING 30 KVA single unit (1:1) in hot standby parallel auto redundancy mode ELECTRICAL INPUT Rated Voltage 400 V AC, 3 Phase + Neutral + Earth Frequency Range 45Hz ~ 55Hz Power factor >=0.98 under all load conditions Efficiency Overall >95% under all load conditions >90% under all load conditions in case of internal isolation transformer 230V AC, selectable (220, 230, 240 V), 3-Phase 50Hz +/- 0.2Hz 0.8 (it should not be de-rated at any load condition) 3:1 <=2% total harmonic with 100% linear load 105% for 1 minute 150% for 30 seconds Automatic, Manual The two UPS systems should work in parallel auto redundancy mode.

ELECTRICAL OUTPUT Voltage Frequency Power factor Crest Factor Voltage distortion Overload Capacity Bypass Redundant System

PROTECTIONS

AUDIBLE ALARMS

a) b) c) d) e) f) g) h) a) b) c) d)

Input MCB Battery MCB Output Under Voltage Output Over Voltage Output Short Circuit Battery charging current limit Over Temperature Protection Protection against input phase change Mains Fail Low Battery Overload Overheat

BATTERY Type Backup Time

Sealed maintenance free Lead Acid battery with steel rack for battery housing. 1 hrs; Minimum VAH required = 38000 (for each UPS)

10

11 12

Charger Constant Voltage Constant Current Charger Bypass Static Bypass/ Manual Maintenance Bypass COMMUNICATION INTERFACE Standard Computer Interface; RS 232 port for Software Interface SNMP SNMP network adapter interface for remote monitoring Temperature sensors Interface/adapter with temperature sensor ENVIRONMENTAL Operating Temperature 0 Deg. to 45 Deg. C Relative Humidity 0 ~ 95% Non Condensing Acoustic Noise < 60 dB @ 1meter Cooling Forced air cooled SAFETY STANDARD IEC 62040, EN50091-1, EN50091-2 Conformance to EN50091-1, EN50091-2 International

S-ar putea să vă placă și