Sunteți pe pagina 1din 20

Fire fighting System in Anta Gas power Project

Automated Fire Detection and fire fighting system

Hydrant and Spray Mulsifier system

Helon gas System

Hydrant and Spray Mulsifier system

Type of pumps:(a) (b) (c) (d) (e) AC Hydrant Pump (01) DD Hydrant Pump (01) AC Spray Pump (01) DD Common Pump (01) Jockey pump (02)

Type of Hydrant valves: Water Monitors 08 Single Hydrant 92 Foam Hydrant 08 Internal Hydrant 07 Test Hydrant 05

Hydrant and Spray Mulsifier system

Hydro pneumatic tank


(a) Capacity 18.15 m3 (b) Design Pr 11.55 bar

Compressors for H/N tank (a) Type Single stage reciprocating air cooled belt drived (b) FAD 135 LPM (c) Motor capacity 2 HP (d) Qty 02

Schematic of Hydrant and spray Pumps

AC Spray P/P

Test Hydrants

DD Common P/P

Jockey pumps H/N Tank

Spray water Header

Spray water strainers

DD Hydrant P/P

Hydrant Header
AC Hydrant P/P

Hydrant Pump Operation


S NO TYPE OF PUMP FLOW M3/HR AUTO MOTOR START /ENGINE HEADER PR. CAPACITY ( BAR) 6.5 6.0 5.5 5.0 at 30% Lvl of H/N TANK 150 KW 150KW 231 HP 231 HP 15 KW MOTOR CURRENT/ DIESEL TANK CAPACITY 255 AMP 255 AMP 250 Lt 250 Lt 22 AMP

1 2 3 4 5

AC HYDRANT AC SPRAY DD HYDRANT DD COMMON JOCKEY PUMP

410 410 410 410 30

F/F MULSIFIER SYSTEM


DELUDGE VALVE SIZE 100 MM
MAKE - THE RELIABLE AUTOMATIC SPRINKLER CO., INC. SIZE - 100MM OPERATION - PNEUMATICALLY OPERATED MODEL - B LOCATION - GT& ST main Transformers, Naphtha unloading & storage TOTAL QTY - 8 Nos.

F/F MULSIFIER SYSTEM


DELUDGE VALVE SIZE 65 MM
MAKE - THE RELIABLE AUTOMATIC SPRINKLER CO., INC. SIZE - 65MM OPERATION - PNEUMATICALLY OPERATED MODEL - A LOCATION - GT& ST Aux Transformers, GRS Diesel Day tank and Oil room TOTAL QTY - 8 Nos.

DELUDGE SYSTEM OF NAPHTHA FOAM SYSTEM


HIGH PR SWITCH

SPRAY WATER HEADER

LOW PR SWITCH

PUSH ROD CHAMBER

AIR DETECTION HEADER

DIAPHRAG M VALVE

DELUDGE VALVE

COMMON DELUDGE V/V OF NAPHTHA FOAM SYSTEM


SPRAY WATER LINE
HIGH PR SWITCH

FOAM LINE
SOLENOID VALVE

LOW PR SWITCH

PUSH ROD CHAMBER

F/F AIR LINE DELUDGE VALVE


FOAM PUMPS
DIAPHRAGM VALVE

2
FOAM TANKS

Hydrant water

DELUDGE SYSTEM OF DISEL DAY TANK diaphragm type


HIGH PR SWITCH

SPRAY WATER HEADER

LOW PR SWITCH

PUSH ROD CHAMBER

AIR DETECTION HEADER

F/F AIR LINE

DIAPHRAG M VALVE

DELUDGE VALVE

DELUDGE VALVE OF GTs AND STG

HIGH PR SWITCH

LOW PR SWITCH

PUSH ROD CHAMBER

SPRAY WATER LINE

F/F AIR LINE DELUDGE VALVE


DIAPHRAGM VALVE

Transformer

Hydrant water

HALON 1301 SYSTEM

HALON 1301 - Bromotriflouromethane ( CBrF) or BTM - Liquefied gas chemical - Breaks the chain reaction of fire

HALON 1301 SYSTEM

Halon Cylinders and nozzles:(a) Manufacturer - Amalon (b) Cylinder capacity 6.8/27.2/56.7/113.4/159 kg (c) Nozzle type - 20 Dia 180 Deg 20/360, 25/180, 40/180, 40/360 (a) System pr 25 bar (b) Approval FM

Detectors :- Ionization, Optical, Heat Detectors

Container and valve details


Feed pipe Shuttle valve Changeover switch

Junction Box Manual operating lever

Junction Box Manual operating lever

Solenoid valve

Solenoid valve

HALON 1301 SYSTEM

Halon Cylinders and nozzles:(a) Manufacturer - Amalon (b) Cylinder capacity 6.8/27.2/56.7/113.4/159 kg (c) Nozzle type - 20 Dia 180 Deg 20/360, 25/180, 40/180, 40/360 (a) System pr 25 bar (b) Approval FM

New Proposals in fire fighting system

Changing of Under ground Hydarnt and spray water line to above ground Phase out of Halon 1301

THANK YOU

S-ar putea să vă placă și