MULTILIN SR750 COURSE

QUIZ #1A OPEN BOOK


Student Name: (Please print) First: Last:

ANSWER KEY Date: May 13, 2011 Score: / 50 Bonus: /6


Circle the correct answer

General Electric SR-750 Feeder Management Relay. Chapter 2.2, Theory of Operation and Chapter 2.4, Specifications 1 mark each 1 mark deducted for each INCORRECT answer. Currents and voltage are sampled at a rate of 16 times per 60 hz cycle. The Fast Fourier Transform algorithm removes the DC component from the AC current input. The Phase Instantaneous Overcurrent element operates between 10-16 mSec for high multiples of its pick-up setting. The Phase Time Overcurrent element pick-up level accuracy is +/- 50 mAmp @ less than 2 x CT or +/- 1 A @ > 2 x CT to 20 x CT. The Phase Current inputs (I2t overload rating) will withstand a current input of 100A for 16 second. The maximum Bus voltage input rating is 273 Volt phase-toground at 60 Hz. The Phase Time Overcurrent operating time has an accuracy of +/- 3% or +/- 40 mSec of the calculated time. SR750 Manual: Chapter 3: Installation The relay can be withdrawn and inserted when the control power is still energized. The Self Test Warning output relay is energized when control power is present and NO Self Test Warning conditions are present. Voltage and current inputs has a designated polarity terminals.

10 Marks

1. 2. 3. 4.

T T T T

F F F F

5. 6. 7.

T T T

F F F

8. 9.

T T

F F

10.

MULTILIN SR750 COURSE

QUIZ #1A OPEN BOOK

ANSWER KEY

General Electric SR-750 Feeder Management Relay. 1 mark each 1 mark deducted for each INCORRECT answer. The SR-750 relay is a multi-function digital relay. The operators interface panel can be accessed using a laptop computer. EnerVista is a graphical user interface software for communicating with the SR-750. You need a special key to program the SR-750 from the operators interface panel. The circuit breaker OPEN and CLOSE status can be indicated on the operators interface panel if the circuit breaker auxiliary contacts are connected to the SR-750. You can order the SR-750 with a green LED to represent a circuit breaker CLOSE status. The CT and VT inputs are opto-isolated to the internal digital circuitry. The CT and VT inputs are scaled down into very low values. There is more than one micro-processor in the SR-750. The Phase Instantaneous Overcurrent element can be incorporated with a definite time delay.

11. 12. 13. 14. 15.

Circle the correct answer T F T T T T F F F F

10 Marks

16. 17. 18. 19. 20.

T T T T T

F F F F F

MULTILIN SR750 COURSE

QUIZ #1A OPEN BOOK


General Electric SR-750 Feeder Management Relay. 1 mark each 1 mark deducted for each INCORRECT answer. VT connections to the SR-750 must be WYE connected.

ANSWER KEY

21.

Circle the correct answer T F

10 Marks

22.

The polarity marked terminals of the CT secondary must be connected to the polarity marked terminal of the SR-750 CT input terminals. The control power module of the SR-750 is a universal power supply and can be supplied by either an AC or a DC source. The SR-750 has two power supply input voltage range, HI and LO. The front panel communication port is a parallel communication port. There are 8 output relays in the SR-750. All the output relay contacts are normally open contacts. Logic input contacts can be connected to the internal 300 Vdc power supply, There are three current transformer input channels and three voltage input channels. Chassis grounding is not required if the CT secondary and VT secondary circuits are grounded.

23. 24. 25. 26. 27. 28. 29. 30.

T T T T T T T T

F F F F F F F F

MULTILIN SR750 COURSE

QUIZ #1A OPEN BOOK


General Electric SR-750 Feeder Management Relay. Chapter 5: Setpoints 31 . Given the VT connection below, it is to be connected to the SR-750 relay.

ANSWER KEY

8 Marks

What is the required Bus VT Sensing parameters for the S2 System Setup Sensing page ?

Bus VT Connection type WYE Bus Nominal VT Secondary Voltage 72.17 V Bus VT Ratio 200 31 . 3 marks Given the Current Sensing setting has a Phase CT Primary setting of 2500A: What is the per phase Power and Reactive values when the secondary current has a value of 2.5 A at 30 lagging (or at .866 power factor) as connected above ? Power 15.63 MW Vars 9.02 MVARS + or signs are not considered if given 5 marks

MULTILIN SR750 COURSE

QUIZ #1A OPEN BOOK


General Electric SR-750 Feeder Management Relay. Chapter 5: Setpoints 33 . Given the Phase Time Overcurrent 1 setting page below:

ANSWER KEY

5 Marks

What is the expected relay operating time for a 6250 Amp primary fault current with the Phase CT Primary setting of 2500A

M=1 K = .14 E = .02 I/Ipu = 6250 A / 2500 A = 2.5 T = 1 x [( .14 )] .02 [( 2.5) 1)] T = 7.56 Calculated Relay operating time: 7.56 seconds. 5 marks

MULTILIN SR750 COURSE

QUIZ #1A OPEN BOOK


General Electric SR-750 Feeder Management Relay. Chapter 5: Setpoints 34 . Given the Phase Directional setting page below:

ANSWER KEY

7 Marks

What are the calculated angular operating limits for the directional elements for a fault in forward direction.

Show the calculated operating limits using 0 to +/- 180 convention in real angles and not the test set values, using Va referenced at 0 on the x-axis. Phase-A angular directional limits: -125 cw , +55 ccw ; MTA = -35 Phase-B angular directional limits: +115 cw , -65 ccw ; MTA = -155 Phase-C angular directional limits: -5 cw , +85 ccw ; MTA = +85

6 marks 35 . What is meant by per unit ? Per 100 % or 100 % of its rating. 1 mark

MULTILIN SR750 COURSE

QUIZ #1A OPEN BOOK


General Electric SR-750 Feeder Management Relay. Bonus Questions 36 . Given the following negative sequence formulae from the SR-750 manual:

ANSWER KEY

6 Marks

What is the phase-A negative sequence Current value when: Ia = 10 A Ib = 0.0 A Ic = 0.0 A 0 - 120 + 120

Ia2 = 3.33 A

0 3 marks

What is the phase-A negative sequence Voltage value when: Va = 69.3 V Vb = 69.3 V Vc = 69.3 V 0 + 120 - 120

Va2 = 69.3 V

0 3 marks