TRANSFORMERS MOUNTED IN G.S.S.

ARE DETAILED AS UNDER WITH THEIR RATINGS AND SPECIFICATION:

TECHNlCAL PARAMETERS MANUFACTURER AREVA Applicable Standards No. of Units Type of cooling Rating HV (MVA) Rating IV (MVA) Rating LV(MVA) No load voltage HV (kV) No load voltage IV (kV) No load voltage LV (kV) Line Current HV (Amps) : : : : : : : : : One ONAN/ONAF/OFAF 189/252/315 189/252/315 63/84/105 : 400 220 33 273.12/364.16/455.20 IS-2026 :

Line Current IV (Amps) Line Current LV (Amps) 1103.52/1471.36/1839.20 No. of Phases Frequency Hz Connection symbol Impedance (315 MVA Base) HV-IV (Normal tap) HV IV (Maximum tap) lV-LV (Normal tap)

: :

496.58/662.11/827.64

: : : : : : :

3 50 YN20d11

l2.93% 41.19% 26.01%

RATINGS FOR AUXILIARY SUPPLY KVA Rating Volt at No load : : 630 KVA H.V. 33000 V , L.V. 415 V

Amperes 876.46 A Phases Max. temp. Oil/wdg C Winding material Cooling Frequency Impedance Vector Group Core & wdg. Weight of oil Volume of oil Total weight Year of manufacture :

H.V. l1.02 A , L.V.

H.V. 3 , L.V. 3 : : : : : : : : : 45/50 Copper ONAN 50 Hz 5% Pyn 11 1850 Kg 850 Kg 1024 Ltr : 3650 Kg : 2007

TEMPERATURE RISES Oil by thermometer Winding by resistance Ambient temperature INSULATION LEVELS LV IV HV : : : 250 KVp 900 KVp 13000 KVp : : 45O C

50O C : 50O C

WEIGHTS (Kgs.) Core and Winding Tank & Fittings Bushings Marshalling Box & Wiring : : : 130,000 79,000

78,410 : 915

Radiator bank assembly Conservator & pipe work etc. Weight of Oil (kg) Total Weight with oil (kg) Shipping Weight (kg)

: :

41060 64090 : 78410 : : 287410 175,000

OIL QUANTITY (Litres) Oil in transformer tank Oil in Radiator Bank Conservator & pipe work, etc. Total Oil Quantity Year of Manufacture 2008 : 73670 : : 56060 : 17610