Termix BTD

Direct substation for single-family houses or apartments

District heating substation for direct heating with tank for domestic hot water preparation
and with thermostatic or electronic control.

Application loop including a pump, control valve, is completed by a white steel cover
The Termix BTD substation is a electronic controller and non-return in modern design with door and
complete solution for hot water and valve. including external thermometers.
heating systems with differential
pressure control. The Termix BTD is Domestic hot water (DHW)
applicable for single-family houses or The domestic hot water circuit consists
apartments. of a hot water tank with coil and self-
acting thermostatic control valve or
District heating (DH) electronic controller. The hot water FEATURES AND BENEFITS
The substation is prefabricated with a tank and coil are enamelled and the
• Substation for single-family houses or
differential pressure controller, fitting tank contains a magnesium anode.
apartments
piece and sensor pockets for insertion The substation is delivered with a
• Direct heating and DHW regulation
of a heat meter as well as a strainer built-in non-return valve and safety with a thermostatic control valve or
and ball valves. valve mounted in the cold water electronic controller
supply. • Mixing loop with thermostatic or
Heating (HE) electronic controller (optional)
The heating circuit is designed Options • 100 or 150 ltr. tank for DHW
for direct generation of heat. The Termix BTD can also be supplied
• Operates independently of differential
The differential pressure control sets with a thermostatic circulation valve. pressure and flow temperature
the optimal operation conditions for
• Suitable in cases of low district heating
radiator thermostatic valves in order Construction capacity
to enable individual temperature All pipes are made of stainless steel.
• Pipes made of stainless steel
control in each room. Furthermore the The connections are made with
station can be delivered with a mixing nuts and gaskets. The Termix BTD

VC.KE.N1.02 © Danfoss 06/2009


Termix BTD
Circuit diagram - example
E DHW tank with coil
1 Ball valve
DHW 6 Thermostatic/non-return
valve
7 Thermostatic valve
9 Strainer
14 Sensor pocket, heat meter
DCW 18 Thermometer
20 Filling/drain valve
Circ. 21 To be ordered separately
31 Differential pressure
controller
41 Fitting piece, heat meter
42 Safety valve/non-return
DH HE valve
supply supply

DH HE
return return

Technical parameters: Connections: Options:


Nominal pressure: PN 10 (16) The connections are situated underneath • Booster pump (increases DH flow)
DH supply temperature: Tmax = 120 °C the hot water tank • Electronic controller for heating in
Brazing material (HEX): Copper connection with a mixing loop
Connections sizes: • Electronic controller for heating and
Weight incl. cover: 90-130 kg DH supply + HE: ¾” G (int. thread) DHW in connection with a mixing loop
DCW + DHW + DH return: ¾” G (ext. thread) • Thermostatic circulation set
Cover: White lacquered • Room thermostat
steel sheet • Zone valve with actuator
• Air screw (DH supply)
Dimensions (mm): • Fitting piece for wall mounting
With cover:
H 1720 x W 540 x D 645 (type BTD-1)
H 1870 x W 540 x D 645 (type BTD-2)

DHW: Capacity examples, 10 °C/50 °C


Tank Coil DHW DHW DHW
Substation
volume supply/return temp. constant output output first hour* constant output
type
l °C l/h l/h kW
80/40 486 546 22,6
BTD-1 100 70/30 245 305 11,4
60/30 172 232 8,0
80/40 486 576 22,6
BTD-2 150 70/30 245 335 11,4
60/30 172 262 8,0
* Output first hour = constant output + 60% of tank volume

Gemina Termix A/S · Member of the Danfoss Group · Navervej 15-17 · DK-7451 Sunds · Denmark
Tel.: +45 9714 1444 · Fax: +45 9714 1159 · mail@termix.dk · www.heating.danfoss.com

VC.KE.N1.02 © Danfoss 06/2009 DH-SMT/PL