Sunteți pe pagina 1din 16

MiCOM P342, P343 Generator Protection Relays

MiCOM P342, P343 Generator Protection Relays

T&D
Protection & Control

MiCOM P342, P343 Generator Protection Relays


Introduction
The MiCOM generator protection relays provide flexible and reliable integration of protection, control, monitoring and measurement functions. Extensive functionality is available to provide complete protection and control with two models for a wide range of applications, covering most installations from small generators up to sophisticated systems.

Control
Programmable scheme logic Programmable optically isolated inputs and relay outputs Multiple settings groups

Measurements
Comprehensive measurement values Instantaneous Integrated
Figure 1: MiCOM P342

Protection
Generator differential (P343 only) 100% stator earth fault (P343 only) Non-directional phase overcurrent Non-directional earth fault Neutral displacement/residual overvoltage Sensitive directional earth fault Restricted earth fault Voltage dependent overcurrent/ underimpedance Under/overvoltage Under/overfrequency Reverse power/low forward power/overpower Loss of field Negative phase sequence thermal Overfluxing Unintentional energisation at standstill (P343 only) 10 RTDs (option) Circuit breaker failure Voltage transformer supervision Current transformer supervision

Post Fault Analysis


Event and fault records Disturbance records

Software Support
Available in conjunction with MiCOM S1 support software: Settings editor Programmable scheme logic editor Viewing of fault diagnostics and measurements Disturbance recorder viewer Fully programmable menu text

Monitoring
Trip circuit monitoring Breaker state monitoring Breaker condition monitoring Temperature monitoring

Communications
A choice of protocols Front and rear communication ports

Application
The MiCOM P342 is suitable for protection of generators which require cost effective high quality protection. Protection includes overcurrent, earth fault, neutral displacement, sensitive or restricted earth fault, voltage dependent overcurrent or underimpedance, under and overvoltage, under and overfrequency, reverse, low forward or overpower, field failure, negative phase sequence thermal and overfluxing, as well as VT and CT supervision. Figure 2a shows an LV application with a solidly earthed system.

Diagnostics
Power-up diagnostics Continuous self monitoring Test facilities

User Friendly Interface


Liquid crystal display with backlight Programmable LED indications Password protection Optional secondary cover Fully programmable menu text

The MiCOM P343 is suitable for protection of larger or more important generators, providing generator differential, 100% stator earth fault and unintentional energisation at standstill in addition to the features of the P342. Figure 2b shows a MiCOM P343 application with a resistance earthed generator.

VTS 27 59
81O 81U

24

CTS
VTS 27/59 81O/81U 24 87G RTD CTS 50/51 51V/21 Voltage transformer supervision Under/overvoltage Under/overfrequency Overfluxing Generator differential 10 resistance thermal devices Current transformer supervision Non-directional phase overcurrent Voltage dependent overcurrent/ underimpedance 32R/32L/32O Reverse power/low forward power/ overpower 40 Loss of field 46 Negative phase sequence 50/27 Unintentional energisation at standstill 64/67N Restricted earth fault/sensitive earth fault 50N\51N Non-directional earth fault 27TN 100% stator earth fault 59N Residual overvoltage/neutral displacement 67N Sensitive earth fault

50 51

51V 21

32R 32L 32O

40

46

Protection Functions
Three phase generator differential protection is provided to detect stator phase faults. This can be set as either a percentage bias scheme with a dual slope characteristic or as a high impedance scheme. Three phase tripping with faulted phase indication is provided for all protection functions.
Generator differential (P343 only)

RTD

50N 51N

64

Figure 2a: MiCOM P342

VTS
27 59
81O 81U

24

Three phase generator differential protection is provided to detect stator phase faults. This can be set as either a percentage bias scheme with a dual slope characteristic or as a high impedance scheme.
100% stator earth fault (P343 only)
64

87G RTD 50 51 51V 21


32R 32L 32O

CTS

40

46

50 27

50N 51N

Third harmonic neutral undervoltage protection covers the final 15% of the stator winding and, in conjunction with the other earth fault elements, provides 100% earth fault protection for the stator. This is supervised by a three phase undervoltage element.
Phase overcurrent

27TN

59N

Figure 2b: MiCOM P343

Figures 2a and 2b

Two independent stages are available for each phase overcurrent. Both stages have definite time (DT) delayed characteristics, the first stage may also be independently set to one of nine inverse definite minimum time (IDMT) curves (IEC and IEEE).
Standard earth fault

overcurrent. Both stages have definite time (DT) delayed characteristics, the first stage may also be independently set to one of nine inverse definite minimum time (IDMT) curves (IEC and IEEE).
Sensitive earth fault

fault protection directional characteristic, but with a directional residual power threshold providing an additional constraint on operation.
Restricted earth fault

The standard earth fault element operates from an earth fault input connection to measure the fault current in the earth path of the generator. Two independent stages are available for each phase

A core balance CT should be used to drive the sensitive earth fault function. The directionality is provided by the residual voltage.
Wattmetric

The restricted earth fault protection may be configured as either high impedance or low impedance biased differential.

The sensitive earth fault protection is also suitable for Petersen Coil earthed systems by enabling a wattmetric element. This form of protection uses the sensitive earth
3

Voltage dependent overcurrent/underimpedance

In order to provide backup protection for phase faults, an element is included which can be set as either voltage controlled overcurrent, voltage restrained overcurrent or underimpedance. If selected as voltage controlled or voltage restrained overcurrent, the timing characteristic can be set as either definite time or IDMT. If selected as underimpedance, a three phase non-directional underimpedance element is provided.
Neutral displacement/residual overvoltage

against motoring and/or CB interlocking to prevent overspeeding during machine shutdown.


Loss of field

Timers ensure that the element will be stable for normal voltage dips that could occur for system faults or machine reconnection.
Resistance temperature devices (RTDs)

To detect failure of the machine excitation a two stage offset mho impedance element is provided. This allows a small instantaneous characteristic to be used to provide fast tripping for loss of excitation at high power outputs, where system stability could be affected. The second stage can be set with a larger time delayed characteristic to provide stable, secure tripping under low power conditions. Integrating timers are provided to enable the impedance characteristic to provide time delayed pole slipping protection. A power factor alarm element is also available to offer more sensitive protection for unusual operating conditions, for example a lightly loaded unit operating as an induction generator.
Negative phase sequence

In order to monitor temperature accurately, an option allowing measurement of temperatures using up to 10 platinum RTDs is available. This provides an instantaneous alarm and time-delayed trip output for each RTD.
Blocked overcurrent logic

Residual overvoltage protection is available for detecting earth faults where there is an isolated or high impedance earth. The residual voltage can be measured from a broken delta VT, from the secondary winding of a distribution transformer earth at the generator neutral, or can be calculated from the three phase to neutral voltage measurements. Two independent stages of protection are provided, each can be set with a definite time delay and one stage can be configured to have an inverse time characteristic.
Under/overvoltage

Each stage of overcurrent and earth fault protection can be blocked by an optically isolated input. This enables the overcurrent and earth fault protection to be integrated into a blocked overcurrent busbar protection scheme.

Supervisory Functions
Circuit breaker failure protection

To protect against unbalanced stator currents caused by external faults or unbalanced loading, two stages of negative sequence protection are provided. These comprise a definite time alarm stage and a trip stage that operates with a thermal characteristic.
Overfluxing

Two stage circuit breaker failure protection may be used for tripping upstream circuit breakers and/or the local secondary trip coil. The circuit breaker failure logic may also be initiated externally from other protection devices if required.
Voltage transformer supervision

Under/overvoltage protection may be configured to operate from either phase-phase or phase-neutral voltage elements. Two independent stages with definite time elements are available. The first stage can also be configured to an inverse characteristic.
Under/overfrequency

To protect the generator, or connected transformer, against overexcitation a two stage V/Hz element is provided. The first stage is a definite time alarm, the second stage can be used to provide an inverse/definite time trip characteristic.
Unintentional energisation at standstill (P343 only)

Two independent stages of overfrequency and four of under frequency are provided. Each stage functions as a definite time element.
Power protection

The power protection element provides two stages which may be independently configured to operate as reverse power, over power or low forward power protection. These can be used to provide simple overload protection, protection

If the machine circuit breaker is closed accidentally, when the machine is not running, very high current will result. A voltage supervised overcurrent scheme is available to protect against this condition. When the machine voltage is low, that is, the machine is not running, an instantaneous overcurrent element is enabled.
4

Voltage transformer supervision (VTS) is provided to detect loss of one, two or three VT signals, providing indication and inhibition of voltage dependent protection elements. An optically isolated input may also be configured to initiate the voltage transformer supervision alarm and blocking when used with miniature circuit breakers (MCBs) or other external forms of voltage transformer supervision.
Current transformer supervision

Current transformer supervision (CTS) is provided to detect loss of phase CT signals and inhibit the operation of current dependent protection elements.

Control
Programmable scheme logic

Programmable scheme logic allows the user to customise the protection and control functions. It is also used to programme the functionality of the optically isolated inputs, relay outputs and LED indications. The programmable scheme logic comprises gate logic and general purpose timers. The gate logic includes OR, AND and majority gate functions, with the ability to invert the inputs and outputs, and provide feedback. The system is optimised to evaluate changes to the scheme logic signals and thus minimise any delays in logic execution. The programmable scheme logic may be configured using the graphical MiCOM S1 PC based support software, as illustrated in Figure 3. The required logic is drawn as shown and is then downloaded directly into the relay. The logic may also be uploaded from the relay and then modified using MiCOM S1 support software.
Independent protection settings groups

Figure 3: Programmable scheme logic editor (MiCOM S1)

Measurements

Temperature

RTD1 RTD10

The measurements provided, which may be viewed in primary or secondary values, can be accessed by the back-lit liquid crystal display, or the communications ports. Phase notation is user definable using the MiCOM S1 text editor.
Instantaneous measurements

Phase currents and phase to neutral voltages are available in true rms and fundamental quantities.
Integrated values

Wh VArh Peak, average and rolling demand:

The settings are divided into two categories; protection settings and control and support settings. Four setting groups are provided for the protection settings to allow for different operating conditions and adaptive relaying.

Phase voltages Line voltages Neutral voltage Phase current Neutral currents Frequency

Van Vbn Vcn Vab Vbc Vca Vn

Ia Ib Ic
W VAr

Post Fault Analysis


Event records

Ia1 Ib1 Ic1 Ia2 Ib2 Ic2 In ISEF

Measurement and Recording Facilities


The P340 series is capable of measuring and storing the values of a wide range of quantities. All events, fault and disturbance records are time tagged to a resolution of 1ms using an internal real time clock. An optional IRIG-B port is also provided for accurate time synchronisation. A lithium battery provides a back-up for the real time clock and all records in the event of supply failure. This battery is supervised and is easily replaced from the front of the relay.

Sequence currents and voltages Single and three phase power factor Active power Reactive power Apparent power Bias current Differential current 3rd harmonic neutral voltage
5

Up to 250 time-tagged event records are stored in non-volatile memory, and can be extracted using the communication ports or viewed on the front panel display.
Fault records

Wa Wb Wc Wtotal VAra VArb VArc VArtotal VAa VAb VAc VAtotal

Records of the last 5 faults are stored in non-volatile memory. The information provided in the fault record includes: Indication of faulted phase Protection operation Active setting group Relay and CB operating time Current, voltage, power and frequency Fault duration Temperatures

Iabias Ibbias Icbias Iadiff Ibdiff Icdiff


Vn3

Disturbance records

Remote communications

The internal disturbance recorder has 8 analogue channels, 32 digital and 1 time channel. Data is sampled 12 times a cycle and typically 20 disturbance records, each of up to 10.5 seconds duration are stored in non-volatile memory. All channels and the trigger source are user configurable. Disturbance records can be extracted from the relay via the remote communications and saved in the COMTRADE format. These records may be examined using MiCOM S1 or any suitable software program.

The remote communications are based on RS485 voltage levels. Any of the protocols listed below can be chosen at the time of ordering.
Courier/K-Bus

The Courier language is a protocol which has been developed specifically for the purpose of developing generic PC programs that will, without modification, communicate with any device using the Courier language.
Modbus

non-volatile memory. Test features available on the user interface provide examination of input quantities, states of the digital inputs and relay outputs. A local monitor port providing digital outputs, selected from a prescribed list of signals, including the status of protection elements, may be used in conjunction with test equipment. These test signals can also be viewed using the Courier and Modbus communications ports.

Hardware Description
All models within the MiCOM P340 series include; A back-lit liquid crystal display 12 LEDs An optional IRIG-B port An RS232 port An RS485 port A download/monitor port A battery (supervised) N/O and N/C watchdog contacts Supervised +48V field voltage 1A/5A dual rated CTs The hardware variations between the P342 and P343 are: P342 100 120V or 380 480V VTs CTs Optically isolated inputs Relay output RTDs 4 5 8 P343 4 8 16

Plant Supervision
Trip circuit monitoring

Monitoring of the trip circuit in both breaker open and closed states can be realised using the programmable scheme logic.
Circuit breaker state monitoring

Modbus is a master/slave protocol, whereby the master must have knowledge of the slaves databases and addresses. The Modbus implementation supported by the MiCOM P340 series is RTU mode.
IEC 60870-5-103

An alarm will be generated if there is a discrepancy between the open and closed contacts of the circuit breaker.
Circuit breaker condition monitoring

The relay is compliant with the transmission protocol defined by the specification IEC 60870-5-103. The standarised messages based on the VDEW communication protocol are supported.
DNP 3.0

The circuit breaker condition monitoring features include: monitoring the number of breaker trip operations recording the sum of the broken current quantity Ix, 1.0 x 2.0 monitoring the breaker operating time monitoring the fault frequency counter

The DNP 3.0 protocol is defined and administered by the DNP User Group. The relay operates as a DNP 3.0 slave and supports subset level 2 of the protocol plus some of the features from level 3.
Local communications

Local and Remote Communications


Two communication ports are available; a rear port providing remote communications and a front port providing local communications.

The front serial communications port has been designed for use with MiCOM S1, which fully supports functions within the relay by providing the ability to program the settings off-line, configure the programmable scheme logic, extract and view event, disturbance and fault records, view the measurement information dynamically and perform control functions. PAS&T can also be used with the local communications port.

3N/O 6N/O 4C/O 8C/O 10 10

Diagnostics
Automatic tests performed including power-on diagnostics and continuous self-monitoring ensure a high degree of reliability. The results of the self-test functions are stored in
6

The optically isolated inputs, relay outputs and 8 of the LEDs are preconfigured as a default, but may be programmed by the user. The optically isolated inputs are independent and may be powered from the +48V field voltage. The relay outputs may be configured as latching or self reset. All CT connections have integral shorting. A system overview of the MiCOM P343 is shown in Figure 4.

E1

5A

IA(2)
E2 E3 E4

Watchdog
1A 5A

IB(2)
E5 E6 E7

1A 5A

50P 51N

50N
67N 64

51P 46 87G 27TN 81 40 59N

IC(2)
E8 E9 C13 C14

Measurements

kA, kV, Hz kW, kVA, kVArs kWh, kVArh Sequence components Thermal state Temperature

J11 Relay failed J12 J13 Relay healthy J14 + J7 48V field voltage J9 + J8 48V field voltage J10 + J2 Auxiliary voltage J1

1A 5A

50BF

CTS

Sensitive
C19

IN

C15

1A

51V 27

21 59 24 VTS

250 Event records

IN > 1 Start ON 00:12:00 01/01/99 Trip A B C ON 00:12:01 01/01/99

See note 3 IRIG-B RS232 Time synchronisation Courier J17 J18 Courier Modbus IEC60870-5-103

VA
C20

32
50 27
C21

20 Disturbance records

RS485 LEDs

VB VC C22

5 Fault reports
C1

52
See note 1 See note 2

Fault A-B-C 15ms Ia = 1000 A Ib = 1000 A Ic = 1000 A RL1 1 & 1 & RL2 RL3 RL4

User programmble

IA

5A

C2 C3 C4

1A 5A

IB

C5 C6 C7

Programmable scheme logic

1A 5A

IC

C8 C9 C10 C11 C12

Breaker monitoring

No. trips SUM I2 CB opt time

= 100 = 1000 kA = 100 ms

RL5 RL6 RL7

1A 5A

H1 H2 H3 H4 H5 H6 H7 H8 H9 H10 H11 H12 H13 H14 H15 H16 H17 H18 G1 G2 G3 G4 G5 G6 G7 G8 G9 G10 G11 G12 G13 G14 G15 G16 G17 G18

R1 Trip CB R2 Trip PrimeMov R3 Any trip R4 General alarm R5 CB fail R6 E/F trip R7 Volt trip User programmable (defaults shown)

1A

RL8 RL9 RL10

R8 Freq trip R9 Diff trip R10 SysBack trip R11 NPS trip R12 FFail trip R13 Power trip R14 V/Hz trip User programmable (defaults shown)

C23 VN C24 D2 D1 D4 D3 D6 D5 D8 D7 D10 D9 D12 D11 D14 D13 D16 D15 F2 F1 F4 F3 F6 F5 F8 F7 F10 F9 F12 F11 F14 F13 F16 F15 L1 Setting group L2 Setting group L3 Block IN>2 L4 BlockI>2 L5 Reset L6 Ext prot trip L7 52a L8 52b L9 Not used L10 Not used L11 Not used L12 Not used L13 Not used L14 Not used L15 Not used L16 Not used User programmable (defaults shown) User programmable (defaults shown)

RL11 RL12 RL13 RL14

49T 38 26

B1 B2 B3

RTD 1 Optional 10 RTDs

B28 B29 B30

RTD 10

ANSI Numbers 50P 50N 51P 51N 67N/64 46 50BF CTS Instantaneous phase overcurrent Instantaneous neutral overcurrent Time delayed phase overcurrent Time delayed neutral overcurrent Sensitive earth fault/restricted earth fault Negative phase sequence Breaker failure and backtrip Current transformer supervision 51V 21 27TN 27 59 81 32 24 Voltage controlled overcurrent Underimpedance 100% stator earth fault Undervoltage Overvoltage Over/underfrequency Reverse/low forward/over power Overfluxing 40 50/27 VTS 87G 59N 26 38 49 Loss of field Unintentional energisation at standstill Voltage transformer supervision Generator differential Residual overvoltage Field winding temperature Becering temperature Stator winding temperature

Note 1: All CT connectors have integral shorting. These contacts are made before the internal CT circuits are disconnected. Note 2: 1A CT connections shown. Note 3: The bridge rectifier is not present on the 24 48V dc version.

Figure 4: MiCOM P343 system overview (not intended for wiring purposes, refer to external connection diagram 10 P343 01 for connection details) 7

4 2

Figure 5: User interface

User Interface
The front panel user interface comprises: (1) A 2 x 16 character back-lit liquid crystal display. (2) Four fixed function LEDs. (3) Eight user programmable LEDs. (4) Menu navigation and data entry keys. (5) READ and CLEAR C keys for viewing and acknowledging alarms. (6) An upper cover identifying the product name. The cover may be raised to provide access to the product model number, serial number and ratings. (7) A lower cover concealing the front RS232 port, down load/ monitor port and battery compartment. The front of the cover can display the name of the product or any user defined name. (8) Facility for fitting a security lead seal.

The user interface and menu text are available in English, French, German and Spanish as standard. Labels supplied with the device allow customised descriptions of the LEDs. A user selectable default display provides measurement information, time/date, protection functions and plant reference information. The ability to customise the menu text and alarm descriptions is also supported.
Password protection

Protection Setting Ranges


Generator differential

Mode

Percentage bias/ high impedance 0.05In to 0.5In 0 to 20% 1In to 5In 20 to 150%

Is1
k1

Is2
k2

100% stator earth fault

Password protection may be independently applied to the front user interface, front communications port and rear communications port. Two levels of password protection are available providing access to the controls and settings respectively.

3rd harmonic undervoltage 0.3 to 20V 1.2 to 80V (100 120V) (380 480V)

Vph-ph< inhibit 30 to 120V 120 to 480V (100 120V) (380 480V)

Unintentional energisation at standstill

I> Vph-ph< 10 to 120V 40 to 480V Definite time Drop-off timer

0.08 to 4In (100 120V) (380 480V) 0 to 10s 0 to 10s

IEC/UK curves TMS = 1


1000 100

IEEE/US curves TD = 7

100
Operating time (s)

10
Operating time (s)

10 UK LTI IEC SI 1 IEC VI IEC EI 0.1 1 10 Current (Multiples of Is) 100

1 IEEE MI IEEE VI US CO2 US CO8 IEEE EI 1 10 Current (Multiples of Is) 100

0.1

TMS 0.025 to 1.2


0.14

TD 0.5 to 15

IEC Standard inverse

t = TMS x

()
I Is I Is

0.02

IEEE Moderately inverse t= TD x 7 0.0515

-1

()
I Is I Is

0.02

+ 0.114

-1

IEC Very inverse

t = TMS x

13.5

( ) -1
80

IEEE Very inverse t= TD x 7 19.61

( ) -1
28.2

+ 0.491

IEC Extremely inverse

t = TMS x

( )-1
I Is 120

IEEE Extremely inverse t= TD x 7

( ) -1
I Is 5.95

+ 0.1217

UK Long time inverse

t = TMS x

US CO8 Inverse t= TD x 7

( )-1
I Is US CO2 Short time inverse

( ) -1
I Is 0.02394

+ 0.18

t=

TD x 7

()
I Is

0.02

+ 0.01694

-1

Figure 6: IEC and IEEE/ANSI IDMT curves 9

Biased differential/restricted earth fault


I DIFF

Vs Vs1, Vs2 20 to 120V 80 to 480V

(Voltage controlled) (Voltage restrained) (Vn 100 120V) (Vn 380 480V)

Reverse power/low forward power

4W to 40W (In = 1A, Vn = 100 120V) 16W to 160W (In = 1A, Vn = 380 480V) 20W to 200W (In = 5A, Vn = 100 120V) 80W to 800W (In = 5A, Vn = 380 480V) Time settings Definite time DO timer
Overpower

Trip K2 No trip

Underimpedance

Z<

2 to 120 (Vn 100 120V, In 1A) 0.4 to 24 (Vn 100 120V, In 5A)

I s1

K1

I s2

I BIAS

8 to 480 (Vn 380 480V, In 1A) 1.6 to 96 (Vn 380 480V, In 5A)

Phase fault

0 to 100s 0 to 100s

IDMT/definite time stages

0.08 to 4.0In

Definite time
Undervoltage

0 to 100s

Definite time stages 0.08 to 10In Definite time 0 to 100s

Voltage settings, Vs 10 to 120V 80 to 480V (100 120V) (Vn 380 480V)

4W to 300W (In = 1A, Vn = 100 120V) 16W to 1200W (In = 1A, Vn = 380 480V) 20W to 1500W (In = 5A, Vn = 100 120V) 80W to 6000W (In = 1A, Vn = 380 480V) Time settings Definite time Drop-off timer
Loss of field

Standard earth fault

IDMT and definite time stages

0.02 to 4.0In

Definite time stages 0.02 to 10In Definite time 0 to 200s

Time settings Definite time IDMT k


Overvoltage

0 to 100s t = k/(1 V/Vs) 0.5 to 100

Sensitive earth fault

IDMT/definite time stages

0.005 to 0.1In

0 to 100s 0 to 100s

Definite time stages 0.005 to 0.8In Definite time 0 to 200s

Voltage settings, Vs 60 to 185V (100 120V)

Wattmetric characteristic

240 to 740V (Vn 380 480V) Time settings Definite time IDMT k 0 to 100s t = k/(V/Vs 1) 0.5 to 100

Mho characteristic settings (secondary ohms) Mho offset 0 to 40/In 0 to 160/In Diameter 25/In to 325/In (100 120V) (100 120V) (380 480V)

Power threshold (1A) 0 to 20W 0 to 80W (100 120V) (380 480V)

Power threshold (5A) 0 to 100W 0 to 400W (100 120V) (380 480V)

Residual overvoltage

Voltage settings, Vs 1 to 50V 4 to 200V Time settings Definite time IDMT k 0 to 100s t = k/(V/Vs 1) 0.5 to 100 (100 120V) (Vn 380 480V)

The IEC and IEEE/ANSI IDMT curves for the above protection settings are shown in Figure 6.
Voltage dependent overcurrent

100/In to 1300/In (380 480V) Linear characteristic Time delays 15 to 75 0 to 100s

Operating mode Current threshold Definite time K factor TMS

Negative phase sequence thermal

Voltage controlled/ voltage restrained 0.8 to 4In 0 to 100s 0.25 to 1.00 0.025 to 1.2

Alarm t> Trip k tmax tmin

0.03 to 0.5In 0 to 100s 0.05 to 0.5In 2 to 40s 500 to 2000s 0 to 100s

Under and overfrequency

Frequency settings Time settings

45 to 65Hz 0 to 100s

10

Overfluxing (V/Hz)

Nominal current circuit Phase and neutral <0.1 at 1A <0.02 at 5A


Thermal withstand

V/Hz trip and alarm 1.5 to 3.5V/Hz 6.0 to 14V/Hz TMS (trip) (100 120V) (380 480V) 1 to 63

Subject to maxima of 5A and 300V Watchdog contact ratings dc 30W resistive dc 15W inductive (L/R = 40ms) ac 375VA inductive (P.F. = 0.5) Durability: Loaded contact 10,000 operations minimum Unloaded contact 100,000 operations minimum
Rear communications port

DT (trip and alarm) 0 to 100s


Resistive temperature detectors (RTDs)

AC current inputs 4.0In continuous 30In for 10s 100In for 1s AC voltage inputs 2 Vn continuous 2.6 Vn for10s
Current transformer requirements

RTD alarm temperature 0 to 200C RTD trip temperature 0 to 200C Alarm and trip time delays 0 to 100s

Connection Multidrop (32 units) Cable type Screened twisted pair Cable length Connector Signal levels Isolation Remote access
Protocols supported

Technical Data
Ratings Inputs:

AC current (In) 1A/5A dual rated ac rms AC voltage (Vn) 100 120V or 380 480V rms nominal phase-phase Rated frequency 50/60Hz Operative range 5 to 70Hz Auxiliary voltage (Vx) Nominal (V) dc 24 54 48 110 110 250
Outputs:

The following CT requirements are based on a maximum prospective fault current of 50In and the relay having a maximum high set setting of 25In. The CT requirements are designed to provide operation of: Phase and standard earth fault elements 1A rated currrent circuits 2.5VA 10P 20 5A rated current circuits 7.5VA 10P 20 For generator differential protection: Low impedance diff Vk > 50In(Rct + 2RL) High impedance diff Vk > 2 Vs where Vs = 1.5If (Rct + 2RL)
Digital inputs

1000m max Screw terminals RS485 SELV

Courier Modbus IEC 60870-5-103 DNP 3.0 Note: An interface to an optical fibre, type 850nm, BFOC 2.5 connector is available for IEC 60870-5-103.
Front communications port

Operative range (V) dc 19 65 37 150 87 300 ac 24 110 80 265

Field voltage supply 48V dc (current limit: 112mA)


Burdens

Optically isolated inputs may be energised from the supervised 48V field voltage provided or an external battery. Operating voltage Max. input voltage AC immunity
Contacts

Connection Cable type Cable length

Point to point Multi-core 15m max

>30V dc 60V dc 50V rms

DC auxiliary voltage 10W typical (P342) 12W typical (P343) AC auxiliary voltage 10W typical (P342) 12W typical (P343) Optically isolated inputs 0.24W per input at 48V Nominal voltage circuit Vn 110 120V <0.02VA at 110V Vn 380 440V <0.1VA at 440V

Connector RS232 DTE 9 pin D-type female Protocol Isolation Local access
IRIG-B Port

Courier ELV

Contact ratings: Make: 30A and carry for 3s Carry: 5A continuous Break: dc 50W resistive 25W inductive (L/R = 40ms) ac 1250VA resistive ac 1250VA inductive (P.F. = 0.7)
11

Carrier signal Amplitude modulated Cable type 50 ohm coaxial cable Connection Isolation BNC SELV

Internal battery

Electrical environment
1/ AA, 2

IEC 60255-22-2: 1996 Class 3 8kV discharge in air to all communication ports. 6kV point contact discharge to any part of the front of the product. Surge immunity IEC 61000-4-5: 1995 Level 4 4kV peak, 1.2/50s between all groups and case earth. 2kV peak, 1.2/50s between terminals of each group. Excluding the RS232 and download/monitor ports EMC compliance 89/336/EEC Compliance to the European Commission Directive on EMC is claimed via the Technical Construction File route. Generic Standards were used to establish conformity: EN50081-2: 1994 EN50082-2: 1995 Product safety 73/23/EEC Compliance with European Commission Low Voltage Directive. Compliance is demonstrated by reference to generic safety standards: EN61010-1: 1993/A2: 1995 EN60950: 1992/A11: 1997
Atmospheric environment

Battery type:

3.6V

DC supply interruption IEC 60255-11: 1979 The unit will withstand a 20ms interruption in the auxiliary supply, in its quiescent state, without de-energising. AC ripple on dc supply IEC 60255-11: 1979 The unit will withstand a 12% ac ripple on the dc supply. AC voltage dips and short interruptions IEC 61000-4-11: 1994 20ms interruptions/dips. High frequency disturbance IEC 60255-22-1: 1988 Class III At 1MHz, for 2s with 200 source impedance: 2.5kV peak between independent circuits and independent circuits and case earth. 1.0kV peak across terminals of the same circuit. Excluding the RS232 and download/monitor ports Fast transient disturbance IEC 60255-22-4 : 1992 Class IV 4kV, 2.5kHz applied directly to auxiliary supply 4kV, 2.5kHz applied to all inputs. Excluding the RS232 and download/monitor ports Surge withstand capability IEEE/ANSI C37.90.1 (1989) 4kV fast transient and 2.5kV oscillatory applied directly across each output contact, optically isolated input, power supply circuit, RS485, IRIG-B, VT and CT circuits Radiated immunity C37.90.2: 1995 25MHz to 1000MHz, zero and 100% square wave modulated. Field strength of 35V/m. Electrostatic discharge IEC 60255-22-2: 1996 Class 4 15kV discharge in air to user interface, display and exposed metal work.
12

Download/monitor port

This is a 25 pin D-type female connector located on the front user interface and is specifically designed for test purposes and software download. Isolation Local access
High voltage withstand

ELV

Dielectric withstand IEC 60255-5: 1977 2kV rms for 1 minute between all case terminals connected together and the case earth. 2kV rms for 1 minute between all terminals of independent circuits with terminals on each independent circuit connected together. ANSI/IEEE C37.90-1989 (r1994) 1kV rms for 1 minute across the open contacts of the watchdog relays. 1kV rms for 1 minute across open contacts of changeover output relays. 1.5kV rms for 1 minute across open contacts of normally open output relays. High voltage impulse IEC 60255-5: 1977 Three positive and three negative impulses of 5kV peak, 1.2/50s, 0.5J between all terminals and all terminals and case earth. This is not applicable to the RS232 and download/monitor ports.

Temperature IEC 60255-6:1988 Operating 25C to +55C Storage and transit 25C to +70C IEC 60068-2-1: 1990/A2:1994 Cold IEC 60068-2-2: 1974/A2:1994 Dry heat Humidity IEC 60068-2-3: 1969 56 days at 93% RH and +40C

Enclosure protection IEC 60529: 1989 IP52 Protection (front panel) against dust and dripping water at 15 to the vertical.
Mechanical environment
23.30
A B

155.40
BA

8 off holes Dia. 3.4 Sealing strip

159.00
AB BA

168.00

177.0 (4U)

Vibration IEC 60255-21-1: 1996 Response Class 2 Endurance Class 2 Shock and bump IEC 60255-21-2: 1995 Shock response Class 2 Shock withstand Class 1 Bump Class 1 Seismic IEC 60255-21-3: 1995 Class 2
Cases

10.35

181.30 202.00 A = Clearance holes B = Mounting holes 200.00 Flush mounting panel Panel cut-out detail

483 (19 rack)

Note: If mounting plate is required use flush mounting cut out dimensions All dimensions in mm

Secondary cover (when fitted) Front view 240.00 Incl. wiring

177.00

157.5 max

P342 P343 Weight P342 P343

MiCOM 40TE MICOM 60TE


206.00 30.00

Side view

7.9 kg 11.5 kg
Figure 7: Case sizes P342 (40TE)

Additional Information
Technical Guide Operation Guide Courier Communications TG8617 OG8617 R4113
23.25
AB

116.55

142.45
A B BA

12 off holes Dia. 3.4

Sealing strip

168.00
AB B A BA

MiCOM S1 User Manual R8610 Midos Parts Catalogue and Assembly Instructions R7012

159.00

177.0 (4U)

10.30

129.50 155.40 305.50 303.50

483 (19 rack) A Clearance holes B Mounting holes

Case
The MiCOM relays are housed in a specially designed case providing a high density of functionality within the product, a customisable user interface, and additional functions/ information concealed by upper and lower covers. Physical protection of the front panel user interface and prevention of casual access is provided by an optional transparent front cover, which can be fitted or omitted according to choice since the front panel has been designed to IP52 protection against dust and water. The case is suitable for either rack or panel mounting as shown in Figures 7 and 8.

All dimensions in mm

Secondary cover (when fitted) Front view 240.00 Incl. wiring

177.00

157.5 max

309.60

30.00

Side view

Figure 8: Case size P343 (60TE) 13

MiCOM P342/P343 Specification


An integrated generator protection solution shall provide comprehensive protection against phase and earth faults and abnormal voltage, frequency, power, field failure and overfluxing conditions. Specific protection functions shall include; overcurrent, standard, sensitive and restricted earth faults, (100% stator earth fault), neutral displacement, voltage dependent overcurrent, under and overvoltage, under and overfrequency, reverse power/low forward power/over power, loss of field, negative phase sequence thermal, overfluxing, (unintentional energisation at standstill) and (generator differential) protections, as well as 10 temperature measuring points using RTDs Two stages of phase overcurrent and earth fault protection shall be provided, with a selection of nine IDMT characteristics for one of the stages. An additional CT shall be provided for sensitive and restricted earth fault protection. It shall be possible to set the power element for under power or reverse power as well as for over power. It shall be possible to configure the loss of field protection in such a way that it can be used for pole slipping protection.

Programming of the device shall be possible using a front panel user interface, local and remote communications ports. A configuration feature shall be provided to enable selection of required functions. This shall allow menu customisation, removing unwanted functions and settings groups from the settings displays. The front panel user interface shall provide independent keys for the viewing and acknowledgement of alarms. Fixed and programmable scheme logic shall be provided uploadable from relay to PC and PC to relay. The relay shall store factory default protection and scheme logic settings for restoration or upload to a PC. Time-tagged event, fault and disturbance records shall be stored in non-volatile memory. The internal disturbance recorder shall have a capacity to store 20 records, each record shall store sampled data from 8 analogue and 32 digital channels over a period of 10 seconds.

The vendor shall be able to provide software support for local and remote programming, and extraction of records from the device. A comprehensive range of instantaneous and integrated measurement values shall be available for viewing on the user interface and the communications ports. These values shall include the temperature measurements that are taken from the ten monitoring points. Note: The functions in brackets should be included if the P343 is required and excluded for the P342.

Accessories Rack frame, (in accordance with IEC 60297). Case to rack sealing gaskets are available to improve the overall IP rating of the panel, (10 per order). M4 90 pre-insulated ring terminals: Blue Wire size 1.04 to 2.63mm2 (100 per order) Red Wire size 0.25 to 1.65mm2 (100 per order) Secondary cover: Blanking plates: P342 P343 Size Size Size Size 10TE 20TE 30TE 40TE
14

Please quote on order FX0021 001 GN2044 001 ZB9124 900 ZB9124 901 GN0037 001 GN0038 001 GJ2028 GJ2028 GJ2028 GJ2028 002 004 006 008

Size 40TE Size 60TE

Information Required with Order


Relay type Generator Protection Relay Version Generator protection Generator protection with differential protection and 100% stator earth fault Vx aux rating 24 48V dc 48 110V dc (30 100V ac) 110 250V dc (100 240V ac) Vn rating 100 120V ac 380 480V ac Hardware options Standard version IRIG-B input Fibre optic converter (IEC 60870-5-103) IRIG-B input & fibre optic converter (IEC 60870-5-103) Product specific No resistive temperature devices 10 resistive temperature devices Protocol options K-Bus Modbus IEC 60870-5-103 (VDEW) DNP 3.0 1 2 3 4 A B 1 2 3 4 1 2 1 2 3 2 3 MiCOM P 3 4

Your contact:

15

TRANSMISSION & DISTRIBUTION Protection & Control, HQ, 60 Route de Sartrouville, BP58, 78230 Le Pecq Cedex, France Tel: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: pcs.enquiries@tde.alstom.com Internet: www.alstom.com
2000 ALSTOM. ALSTOM, the ALSTOM logo and any alternative version thereof are trademarks and service marks of ALSTOM. Other names mentioned, registered or not, are the property of their respective companies. Our policy is one of continuous development. Accordingly the design of our products may change at any time. Whilst every effort is made to produce up to date literature, this brochure should only be regarded as a guide and is intended for information purposes only. Its contents do not constitute an offer for sale or advice on the application of any product referred to in it. We cannot be held responsible for any reliance on any decisions taken on its contents without specific advice.

Publication R6614B

120030 CPS Printed in England.

S-ar putea să vă placă și