Sunteți pe pagina 1din 14

Heat pipes and Thermosyphons

Cold end

Heat pipes and Thermosyphons


Cold end

Hot end

Inside the system, there is a fluid (usually termed refrigerant) Hot end

Heat is transferred as latent heat of evaporation which means that the fluid inside the system is continuously changing phase from liquid to gas. The fluid is evaporating at the hot end, thereby absorbing heat from the component. At the cold end, the fluid is condensed and the heat is dissipated to a heat sink (usually ambient air).

Heat pipes and Thermosyphons

Heat pipes

Heat pipes
In Heat Pipes, capillary forces in the wick ensures the liquid return from the hot end to the cold end. This means that a Heat Pipe can operate independent of gravity. The heat pipe was actually developed for zero gravity (i.e. space) applications.

Heat pipes

Heat pipes

Heat pipes - Applications

Heat pipes - Applications

Thermosyphons
Are always gravity driven! Loop system enables enhancement of heat transfer and minimization of flow losses (pressure drop). Generally have better performance compared to Heat Pipes working with gravity.

Condenser Rising tube

Schematic of a Thermosyphon Example of a Thermosyphon cooling three components in parallel


1200

Falling tube

PCB LiquidVapor Mixture

Condenser

Liquid Hot Component Evaporator

Air

1510 10

Evaporator

5 hole with d_f=1.5 mm Falling tube length=1750mm Rising tube height=1200 mm Liquid head:988+27=1015 mm

988

27 273

Areas in a thermosyphon
Example of a Thermosyphon cooling three components in series
Component, 1 cm2 Evaporator, front, 2.2 cm2 Evaporator, inside, 3.5 cm2 Condenser, inside, 108 cm2 Condenser, facing air, (heat sink included), 5400 cm2

4 times

Advantages with Thermosyphon cooling:


Large heat fluxes can be dissipated from small areas with small temperature differences (150 W/cm2) Heat can be transferred long distances without any (or with very small) decrease in temperature.
Temp Boiling Saturation temp Condensation Hot side Cold side

Temperatures obtained experimentally in a Thermosyphon system that has three evaporators that each cool one component. The total heat dissipation is 170 W.
Component Contact resistance Evaporation Saturation temperature Condensation Contact resistance

Condenser
Thermosyphon Fin to air

Evaporator

Air

Temperature difference as a function of the heat dissipation


(Prototype C, Condenser is fan cooled)
Data: P8F2MAX.STA 10v * 23c

Evaporator geometries
d=1.1 mm d=1.5 mm d=2.5 mm d=3.5 mm

12 R142b 10 Temp.difference (C) Filling Ratio = 39% 8 6 4 Condenser 2 0 Evaporator2

10 mm

14.7 mm

Tc, d=0.8 mm

40

80 P (W)

120

160

Cooling of Power Amplifiers in a Radio Base Station

Thermosyphons - Applications

Thermosyphons - Applications

Thermosyphons - Applications

Immersion cooling

Two phase flow in a large diameter tube:


Flow regimes determine heat transfer mechanism

Classification and application of thermosyphon systems.


Open thermosyphon Closed thermosyphon
Pipe thermosyphon
Single-phase flow Two-phase flow

Thermosyphon is a circulating fluid system whose motion is caused by density difference in a body force field which result from heat transfer. Thermosyphon can be categorized according to:
1. 2. 3. 4. The nature of boundaries (Is the system open or closed to mass flow) The regime of heat transfer (convection, boiling or both) The number of type of phases present (single- or two-phase state) The nature of the body force (is it gravitational or rotational)

Simple loop Thermosyphon


Single-phase flow Two-phase flow

Closed advanced two-phase flow thermosyphon loop

All thermosyphon systems removes heat from prescribed source and transporting heat and mass over a specific path and rejecting the heat or mass to a prescribed sink.

The most common industrial thermosyphon applications include:


gas turbin blade cooling electrical machine rotor cooling transformer cooling nuclear reactor cooling steam tubes for bakers oven cooling for internal combustion engines electronics cooling.

Open Thermosyphon:
Single-phase, naturalconvection open system in the form of a tube open at the top and closed at the bottom. For open thermosyphon Nua=C1Raam(a/L)C2, Nua=(ha)/k a: based on radius

Closed Thermosyphon (simple pipe)


A simple single-phase naturalconvection closed system in the form of a tube closed at both ends. It has been found that the closed single-phase thermosyphon can be treated as two simple open thermosyphon appropriately joined at the midtube exchange region. The primary problem is that of modeling the exchange region. It has been found that the exchange mechanism is basically convective.

Condenser

Evaporator

Thermosyphon pipe

Simple thermosyphon loop

Advanced thermosyphon loop

Closed loop thermosyphon

Two distinct advantages make the closed-loop thermosyphon profitable to study: Natural geometric configuration which can be found or created in many industrial situation. It avoid the entry choking or mixing that occurs in the pipe thermosyphon For single phase loop: NuL=0.245(GrPr2L/d)0.5 can be used

Two-phase thermosyphon

1. 2. 3. 4.

The advantages of operating two-phase thermosyphons are: 1. The ability to dissipate high heat fluxes due to the latent heat of evaporation and condensation 2. The much lower temperature gradients associated with these process. 3. Reduced weight and volume with smaller heat transfer area compared to other systems.

Heat pipe and thermosyphon


Thermosyphon and heat pipe cooling both rely on evaporation and condensation. The difference between the two types is that in a heat pipe the liquid is returned from the condenser to the evaporator by surface tension acting in a wick, but thermosyphon rely on gravity for the liquid return to the evaporator. However the cooling capacity of heat pipes are lower in general compared to the thermosyphon with the same tube diameter.

Closed advanced two-phase thermosyphon loop


Thermosyphon cooling offers passive circulation and the ability to dissipate high heat fluxes with low temperature differences between evaporator wall and coolant when implemented with surface enhancement. An advanced two-phase loop has the possibility of reducing the total cross section area of connecting tubes and better possibility of close contact between the component and the refrigerant channels than a thermosyphon pipe or a heat pipe.

Heat Transfer Coefficient

Thermosyphons Heat Transfer and Pressure Drop


Rahmatollah Khodabandeh

At least two different mechanisms behind flow boiling heat transfer: convective and nucleate boiling heat transfer. General accepted that the convective boiling increases along a tube with increasing vapor fraction and mass flux. Increasing convective boiling reduces the wall superheat and suppresses the nucleate boiling. When heat transfer increases with heat flux with almost constant vapor fraction and mass flux, the nucleate boiling dominates the flow boiling process. Due to the fact that the mechanism of convective and nucleate boiling can coexist, a good procedure for calculating flow boiling must have both elements.

all heat transfer correlations can be divided into three basic models: 1) Superposition model 2) Enhancement model 3) Asymptotic model In the superposition model, the two contributions are simply added to each other, while in the enhancement model the contribution of nucleate and convective boiling are multiplied to obtain a single-phase model. In the asymptotic model the two mechanisms are respectively dominant in opposite regions. The local heat transfer coefficient as sum of the two n contributions htp = h n + h n = (EhL )n + (F hnb )n cb b Where n is an asymptotic factor equal to 1 for the superposition model and above 1 for the asymptotic model

With larger n, the htp is implying more asymptotic behavior in the respectively dominant region. hL and hnb are the heat transfer coefficients for one-phase liquid flow and pool boiling respectively. E and F are enhancement and suppression factors. Chen, Gungor-Winterton [1986] and Jungs correlations are based on superposition model. Shah, Kandlikar and Gungor-Wintertons [1987] correlations are based on enhancement model. Liu-Winterton, Steiner-Taborek and VDI-Wrmeatlas are based on asymptotic model.

Lazarek-Black, Tran and Crnwell-Kew have developed heat transfer correlations for small diameter channel. Coopers pool boiling correlation or Liu-Wintertons flow boiling correlation can be used for heat transfer coefficient in an advanced closed two-phase flow thermosyphon loop. Liu-Winterton correlation 0.5 h tp = [(E h l )2 + (s h pool )2 ] 0.12 ( log 10(p r ))(0.55 ) M (0.5 ) q 0.67 h pool = 55 p r
E = 1 + (x ) Prl l 1 g
0.35

Total thermal resistance in an advanced closed two-phase flow thermosyphon loop


The thermosyphons thermal resistance can be considered to the sum of four major component resistances: (K/W) Rtot=Rcr+Rbo+Rco+Rcv Rcr is the contact resistance between the simulated component and the evaporator front wall. In order to reduce Rcr a thermally conductive epoxy can be used. Rbo, is the boiling resistance. Rco, is the condensing resistance. This resistance is in fact very low due to the high heat transfer coefficient in condensation and the large condensing area. Rcv is the convection resistance between the condenser wall and the air.

s = 1 + 0.055 E 0.1 (Re l )0.16

](

1)

k h l = 0.023 l (Re l )0.8 (Prl )0.4 d

Heat transfer depends on pressure level, vapor fraction, flow rate, geometry of evaporator and thermal properties of refrigerant. The influence of pressure level, choice of working fluid, geometry of evaporator, pressure drop, heat transfer coefficient, critical heat flux and overall thermal resistance were investigated during the present project.

Considerations when choosing refrigerant


A fluid which needs small diameter of tubing A fluid which gives low temp. diff. in boiling and condensation A fluid which allows high heat fluxes in the evaporator.

For turbulent singlephase we can derive pressure drop as: For a certain tube length, diameter and cooling capacity, the pressure drop is a function of viscosity, density and heat of vaporization.

p = f1 w2

L d

Figure of merit (Dp)

f1 = 0.158Re1 / 4 Re =

wd

V w= = A

d 2
4 LQ d

Q/ h fg

d 2
4

4Q h fg d 2

7/4

p = 0.241

19 / 4

1/ 4 h7 / 4 fg

Fig. shows ratio of viscosity to density and heat of vaporization vs. Saturated pressure, we find that the general trend is decreasing pressure drop with increasing pressure and decreasing molcular weights. The Two-phase pressure drops expected to follow the same trends. For Saturated temperature between 0-60 C.

2.50E -08 2.00E -08 1.50E -08 1.00E -08 5.00E -09 0.00E +00 0 5 10 15 20 25 30 35 40 Pres ure (bar) s R M 32, =52.02 N 3, M H =17.03 R M 12, =120.9 R 134a, M =102 R M 22, =86.47 R 600a, M =58.12

Coopers pool boiling correlation is plotted versus saturated pressure for different fluids: (for saturated temp. between 0-60 C) As can been seen heat transfer coefficient generally increases with increasing pressure and decreasing the molecular weights.

400 50 400 00 h-Cooper (W/mK) 300 50 300 00 200 50 200 00 100 50 100 00 50 00 0 0 5 1 0 1 5 2 0 P (b s ar) 2 5 3 0 3 5
N 3, M17.03 H = R M52.02 32, = R , M5 600a = 8.12 R , M1 134a = 02 R M120 12, = .9 R M86.47 22, = R M137 11, = .4

4 0

Another important parameter when choosing working fluid is the critical heat flux. Figure shows calculation of Kutateladze CHF correlation versus reduced pressure for pool boiling. As can been seen ammonia once again shows outstanding properties with 3-4 times higher than the other fluids.

2400 2100 1800 CHF (W) 1500 1200 900 600 300 0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 R educed pres ure s R 600a, M=58.12 R M=137.4 11, N M=17.03 H3, R 134a, M=102 R M=120.9 12, R M=86.47 22, R M=52.02 32,

FC fluids

Influence of system pressure and threaded surface R600a (Isobutane) Tests were done at five reduced pressures ; p r = p cr ; 0.02, 0.05, 0.1, 0.2 and 0.3. Two types of evaporators: smooth and threaded tube surfaces.
p

In immersion boiling FC fluids have been used FC fluids generally have poor heat transfer properties: -Low thermal conductivity
-Low specific heat -Low heat of vaporization -Low surface tension -Low critical heat flux -Large temperature overshoot at boiling incipience

The picture shows heat flux vs. temperature difference between inside wall temperature and refrigerant. As can be seen, the temperature difference increases with increasing heat flux, but with different slopes, depending on the saturation pressure in the system As the heat transfer coefficient is the heat flux divided by the temp. difference, this indicates higher heat transfer coefficient with increasing pressure

350000 300000 250000 q (W/m) 200000 150000 100000 50000 0 0

pr=0.3

pr=0.02

DT (C)

The Fig. shows temperature difference between inside wall temperature and refrigerant vs. heat input. As can be seen, the temperature difference increases with increasing heat input, but with different slopes, depending on the saturation pressure in the system As the heat transfer coefficient is the heat flux divided by the temp. difference, this indicates higher heat transfer coefficient with increasing pressure

Isobutane Smooth tube 5 10 15 20 25

24 22 20 18 16 14 12 10 8 6 4 2 0 0

pr=0.3 pr=0.2 pr=0.1 pr=0.05 pr=0.02

DT (C)

20

40

60 Q (W)

80

100

120

The Fig. shows, heat transfer coeff. vs. reduced pressure for 110 W heat input to each one of the evaporators. The dependence of heat transfer coefficient on reduced pressure are often expressed in the form of h=f (prm), in which m is generally between 0.2-0.35. In the present case, m=0.317, correlates the experimental data well for the smooth tube with Isobutane as refrigerant.

45000 40000 35000 h (W/m.K) 30000 25000 20000 15000 10000 5000 0 0 0.05 0.1 0.15 pr 0.2 0.25 0.3 0.35

Effect of threaded surface at different reduced pressure on heat transfer coefficient


The fig. shows temp. diff. vs. reduced pressure from 10 to 110 W heat input for each one of evaporators on threaded surface. Relatively low temp. diff can be achieved. Temp. diff. In the most points will be reduced to less than a third by increasing the reduced pressure from 0.02 to 0.3.
10 9 8 7 6 5 4 3 2 1 0 0 0.1 0.2 pr 0.3
10 W 30 W 50 W 70 W 90 W 110 W

Q=110 W

DT (C)

h = constantpr R2 = 0.9957

0.317

0.4

Effect of heat flux on heat transfer coefficient Figur shows the relation between heat transfer coefficient and heat flux for Pr=0.1, with smooth tube. The dependence of heat transfer coefficient on heat flux can be expressed as h=f (qn), n, in most cases varies between 0.6-0.8 Presented data follows h=f (q0.57)

Comparison between Coopers correlation and experimental results


25 20 h (kW/m.K) 15 10 5 0 0 40 80 120 160 200 240 280 q (kW/m)
n

h- Coope r (W/m K)

R600a

y = 0.8761x0.5755 R2 = 0.9984

h=f (q ) h=f (q
0.57

The Fig. shows heat transfer coeff. comparison between Coopers pool boiling correlation versus experimental results for smooth tube surfaces at different reduced pressure.
)

Q=10 W 50 000 40 000 30 000 20 000 10 000 0 0 10000 20000 30000 400 00 50000 Q=30 W Q=50 W Q=70 W Q=90 W Q=110 W

25%

25%

As can be seen the heat transfer coeff. calculated by Coopers correlation is in good agreement with the experimental results For the most points the deviation is less than 25 percent.

h-e xp (W/mK)

Comparison between LiuWintertons correlation and experimental results


The Fig. shows heat transfer coeff., comparison between Liu-Wintertons correlation versus experimental results for smooth tube surfaces at different reduced pressure. As can be seen the heat transfer coeff. calculated by Liu-Wintertons correlation is in good agreement with the experimental results For the most points the deviation is less than 25 percent.
50000 40000 h- LW( W/m K) 30000 20000 10000 0 0 10000 20000 30000 40000 50000 10 W 30 W 50 W 70 W 90 W 110 W

Influence of diameter Testing condition


25%

25%

h-exp (W/mK)

R600a as refrigerant Tests were done with 7, 5,4, 3, 2 and 1 vertical channels with diameter of 1.1, 1.5,1.9, 2.5 3.5 and 6 mm. Smooth surface At reduced pressure 0.1 (p/pcr)

Influence of diameter
Heat transfer coefficient vs. heat flux at different diameters. The influence of diameter on the heat transfer coefficients for these small diameter channels was found to be small and no clear trends could be seen.
h-exp. (kW/mK)

Conclusions
30 25 20 15 10 5 0 0 50 100 150 200 250 300 350 Heat flux (kW/m )
d=6 m m d=3.5 m m d=2.5 m m d=1.9 m m 1.5 m m d=1.1m m

Heat transfer coefficients and CHF can be expected to Increase with increasing reduced pressure and with decreasing molecular weight The effects of pressure, and threaded surface on heat transfer coefficient have been investigated. The pressure level has a significant effect on heat transfer coefficient. h=f (prm) m=0.317 h=f (qn) where n=0.57

Conclusion
Heat transfer coefficient can be improved by using threaded surfaces. Heat transfer coefficient at a given heat flux is more than three times larger at the reduced pressure 0.3 than 0.02 on threaded surfaces. The experimental heat transfer coefficients are in relatively good agreement with Coopers Pool boiling and Liu-Wintertons correlations.

Conclusion
The effects of pressure, mass flow, vapor quality, and enhanced surface on CHF have been investigated. Threaded surface has a minor effect on CHF. The pressure level has a significant effect on CHF. The CHF can be increased by using a higher pressure. The influence of diameter on the heat transfer coefficients for these small diameter channels was found to be small and no clear trends could be seen.

10

Operation condition of an advanced two-phase thermosyphon loop


The net driving head caused by the difference in density between the liquid in the downcomer and the vapor/liquid mixture in the riser must be able to overcome the pressure drop caused by mass flow, for maintaining fluid circulation. The pressure changes along the thermosyphon loop due to gravitation, friction, acceleration, bends, enlargements and contractions.

In design of a compact two-phase thermosyphon system, the dimensions of connecting tubing and evaporator, affects the packaging and thermal performance of the system. The pressure drop is a limiting factor for small tubing diameter and compact evaporator design. By determining the magnitude of pressure drops at different parts of a thermosyphon, it may be possible to reduce the most critical one, therby optimizing the performance of the thermosyphon system.

Single-phase flow pressure drop in downcomer


The total pressure drop in the downcomer consists of two components: frictional pressure drop and pressure drop due to bends respectively. For fully developed laminar flow in circular tubes, the frictional pressure drop can be calculated by:
pl =
l For the turbulent flow regime, the Blasius correlation for the friction factor can used: 2 G L pl = 0.079 Re 0.25 d
l

The pressure loss around bends can be calculated by:


plb = G 2 l

where is an empirical constant which is a function of curvature and inner diameter.

16 2 G L Re d

In the downcomer section, the pressure drop due to friction is much larger than the pressure loss around bends.

1. 2. 3. 4. 5. 6. 7.

Two-phase flow pressure drop Two-phase flow in the riser and evaporator:
The total two-phase flow pressure drop consists of six components:
Acceleration pressure drop Friction pressure drop Gravitational pressure drop Contraction pressure drop Enlargement pressure drop Pressure drop due to the bends Frictional and gravitational pressure drop are most important pressure drops in the riser

Method of analysis two-phase flow pressure drop


The methods used to analyse a two-phase flow are often based on extensions of single-phase flows. The procedure is based on writing conservation of mass, momentum and energy equations. To solve these equations, often needs simplifying assumptions, which give rise different models.

11

Homogeneous flow model


One of the simplest predictions of pressure drop in twophase flow is a homogeneous flow approximation. Homogeneous predictions treat the two-phase mixture as a single fluid with mixture properties. In the homogeneous flow model it is assumed that the two phases are well mixed and therefore have equal actual vapor and liquid velocities. In other words in this model, the frictional pressure drop is evaluated as if the flow were a single-phase flow, by introducing modified properties in the single-phase friction coefficient.

Separated flow model


The separated flow model is based on assumption that two phases are segregated into two separated flows that have constant but not necessarily equal velocities.

Drift flux model


This model is a type of separated flow model, which looks particularly at the relative motion of the phases. The model is most applicable when there is a well-defined velocity in the gas phase

Pressure drop in the riser


The total two-phase flow pressure drop in the riser is mainly the sum of two contributions: the gravitationaland the frictional pressure drop. The most used correlations for calculation of frictional pressure drop are: Lockhart-Martinelli correlation CESNEF-2 correlation Friedel correlation Homogeneous flow model correlation

In the homogeneous model, the analysis for single-phase flow is valid for homogeneous density and viscosity. The homogeneous density is given by: x 1 x 1
h g L Several different correlations have been proposed for estimation of two-phase viscosity, such as: Cicchitti et al. h = x g + 1 x L x 1 x 1 Beattie- Whalley = +
= +

1. 2. 3. 4.

h = L (1 )(1 + 2.5 ) + g
h = g x h L (1 x ) h + g L

Mc Adams et al.

x h

Dukler et al.

Gravitational pressure drop

p G , R = m g H r The gravitational or head pressure change at the riser

1. 2. 3. 4. 5. 6.

The momentum equation gives: m = g + (1 ) L Where is void fraction A = g A: total cross-section area (m2) A Ag: average cross-section area occupied by the gas phase (m2) Void fraction can be calculated by: Homogeneous model Zivi model [1963] Turner& Wallis two-cylinder model [1965] Lockhart-Martinelli correlation [1949] Thom correlation [1964] Baroczy correlation [1963]

1 u g (1 x) g 1+ uL x L

For the homogeneous flow the phase velocities are equal, uL=ug, S = u g , where S is the slip ratio.
uL
h =
1 (1 x) g 1+ x L

12

Fig. 1

77

Acceleration pressure drop


Acceleration pressure drop in the evaporator, resulting from the expansion due to the heat input during the evaporation process can be calculated: (homogeneous model) p = G 2 ( v g v L ) x v specific volume

Experimental setup

glass tube

Condenser 150 255 186


Abs. pressure transduc er

939

Downcomer

ID=6.1 mm 974 8 B 1160

Evaporator 10 15 10

Not to scale

95 5 hl med d_f=1.5 mm hole with d_f=1.5 mm All dimensions in the figure are in mm

CHF
Testing condition
R600a (Isobutane) Tests were done at three reduced pressures; 0.035, 0.1, and 0.2. Two types of evaporators: smooth and threaded tube surfaces.

CHF=f(pr, G, x) Effect of pressure on CHF:


The Fig shows temperature difference between inside wall temperature and refrigerant for three evaporators, vs CHF. For pr =0.2 the CHF is 690 W which correspond to 230 W/cm front area of the component which correspond to 650 kW/m heat flux for smooth channels. As can be seen, the saturation pressure strongly affected the temp. diff. With increased pressure the temp. diff. decreases in the total range of heat load up to CHF.
DT(C)

35 30 25 20 15 10 5 0

pr=0.035

pr=0.1

pr=0.2

smooth channel

0.035 0.1 0.2

350 400 450 500 550 600 650 700 750 Qto t (W)

Effect of mass flow on CHF


The mass flow is a function of both heat flux and system pressure. As can be seen simulations at CHF shows that mass flow increases with increasing reduced pressure. This is believed to be the explanation for the higher CHF. Higher pressure gives higher mass flow on CHF, which facilitates the deposition and replenishment of liquid film.
m _dot (k g/s ) 0.006 0.005 0.004 0.003 0.002 pr =0.035 pr =0.1 pr =0.2

Effect of vapor quality on CHF


The Fig. shows, vapor quality vs. CHF for three evaporators. According to the simulations the vapor quality at different pressure on CHF is almost constant.

smooth channel
0.001 0 0 100 200 300 400 500 600 700 Qcri (W)

1 pr =0.035 0.9 0.8 pr =0.1 0.7 pr =0.2 0.6 0.5 0.4 0.3 0.2 smooth channel 0.1 0 0 100 200 300 400 500 600 700 Qcri (W)

13

Effect of enhanced surface on CHF


Generally at enhanced surfaces increases the heat transfer. In this study threaded surfaces have been used to investigate the effect of surface structure on CHF. The picture shows the CHF versus reduced pressure for both surfaces. However the CHF is independent on surface condition. The fact that the surface condition is unimportant for CHF were reported by other researcher.
700 600 Qcr i (W) 500 400 300 200 100 0 0 0.05 0.1 pr 0.15 0.2 0.25
threaded smooth

Comparison between Kutateladzes correlation and experimental results The Fig. shows CHF, comparison between Kutateladzes pool boiling correlation versus experimental results for smooth tube surfaces. Deviation is less than 15 percent.

700 600 Q_cri_pb. (W) 500 400 300 200 100 0 0

15%

-15%

100 200 300 400 500 600 700 Q_cri_exp. (W)

Old Exam Problem 2003-03-07


A thermosyphon can be quite complex to model. In this assignment we will investigate the behavior of a simplified thermosyphon. The difference in height between the condenser and the evaporator is 15 cm. The tube diameter is 5 mm and the downcomer tube length is 16 cm. The heat exchanger area in the condenser and the evaporator is 40 cm and 4 cm respectively. The total pressure drop in the rising tube can be calculated using pRiser = 6.21x, where pRiser is in kPa, x is the change in vapor quality in the evaporator. The refrigerant is R134a for which the latent heat of vaporization, hfg = 163 kJ/kg, the liquid density, L=1146 kg/m, and dynamic viscosity, L=1.7810-4 Pas. The temperature of the evaporator walls is 50 C, the boiling heat transfer coefficient is 20.000 W/(mK), and the heat dissipation is 60 W. Calculate the mass flow & rate, m , the change in vapor quality, x, and the saturation temperature of the refrigerant (6 credits).

14

S-ar putea să vă placă și