Documente Academic
Documente Profesional
Documente Cultură
MASTER OF SCIENCE
(Engineering)
at the
ACKNOWLEDGEMENTS
encouragement throughout
this project.
grateful for
their help and the knowledge that they have both conveyed to me. The friendship the lab and camaraderie of the fellow RA's in I
enjoyable.
May all your DCM errors disappear. Financial support for this work has been provided by
giving help when it was needed. Finally, the successful completion of this project
would have been insurmountable of my wife, Donna. and downs more up Her moral and less
without the selfless support support and Love made the ups down. Being married to a
graduate student is a lonely event, and I thank you for your patience a million times over. Thanks, and more.
ii
ABSTRACT
Several
experimental
and
analytical
studies
have
currently practiced.
have shown
can be increased on
the order of
The f-Chart
design method are not applicable at low flowrates that the when because they tank is
conventional f-Chart
to the
4,f-Chart methods
developed by running numerous TRNSYS simulations employing a stratified tank model. collector flowrate From this ratio, heat removal A correlation was developed between dimensionless ratio, LX/AXmax*
and a
factor can be
design method, the resulting solar would be achieved preheat tank. from a
The methods
Albuquerque, and
range of
the stratified
relative to *,f-Chart
the TRNSYS
predictions was
iv
TABLE OF CONTENTS
CHAPTER ONE:
INTRODUCTION
1 2 3
1.1 THERMALLY STRATIFIED STORAGE 1.1.1 Effects of Reduced Collector Flowrate 1.2 DESIGN METHODS 1.2.1 Conventional Solar Hot Water Heating Systems 1.2.2 Measures of System Performance 1.2.3 Utilizabilitv 1.3 COLLECTOR OPERATING TIME 1.4 AVERAGE DAYLIGHT AMBIENT TEMPERATURE 1.5 OBJECTIVES CHAPTER TWO: SOLAR FRACTION MODIFICATION 2.1 ANALYTICAL METHODS 2.1.1 Stratification Coefficient 2.1.2 Stratification Index 2.2 EMPIRICAL METHODS 2.2.1 Effect of Collector Flowrate on the Heat Removal Factor 2.2.2 Identification of Important Parameters 2.2.3 System Description 2.2.4 Component Model Description 2.2.5 Af Correlation
V
5 6 10 12 20 28 31 33 34 35 40 42 42 45 49 53 56
CHAPTER THREE: MODIFICATION TO THE F-CHART METHOD FOR THERMALLY STRATIFIED SDHW SYSTEMS 3.1 REVIEW OF THE F-CHART METHOD 3.2 COLLECTOR AREA CORRECTION FACTOR 3.3 COLLECTOR LOSS COEFFICIENT CORRECTION FACTOR 3.3.1 Collector Loss Coefficient Methodology 3.3.2 Results 3.4 EXAMPLE CHAPTER FOUR: MODIFICATION TO THE #,F-CHART METHOD FOR THERMALLY STRATIFIED SDHW SYSTEMS 4.1 THE 0,f-CHART METHOD 4.2 CORRECTION FACTOR METHODOLOGY 4.3 RESULTS 4.4 EXAMPLE
vi
LIST OF FIGURES
Figure 1.1 Effect of Collector Flowrate on the Theoretical, Monthly Solar Fraction for a Stratified and a Fully-Mixed Preheat Tank System for the Base Case System in Madison with a 300 /day Load. Figure 1.2 Open-loop Solar Domestic Hot Water System Schematic. Figure 1.3 Closed-loop Solar Domestic Hot Water System Schematic. From Reference [341. Figure 1.4 Two Sequence of Days with the same Average Radiation. From Reference Ell]. Figure 1.5 Radiation level for a Clear Day. Reference E141. From
16
21
Figure 1.6 Monthly-Average Daily Collector Flowrate from Simulations with a Mixed Preheat Tank Compared to Equation 1.15. Figure 1.7 Monthly-Average Daily Collector Flowrate from Simulations with a Stratified Preheat Tank Compared to Equation 1.15. Figure 2.1 The Stratification Coefficient Compared with the Ratio of Stratified Tank Solar Fraction to Mixed Tank Solar Fraction from TRNSYS. Fiqure 2.2 Comparison of Experimental and Analytical Results Showing the Variation of FR with Collector Flowrate.
25
26
39
43
vii
Figure 2.3 Solar Fraction Variation with the Ratio of-Monthly-Average Daily Collector Flow to Daily Load Flow. Figure 2.4 Operation of the Plug-Flow Storage Tank Model. From Reference [29J. Figure 2.5 The Difference Between the Mixed-Tank and Stratified-Tank Solar Fraction Variation with the Ratio of Monthly-Average Daily Collector Flow to Daily Load Flow for the Base Case System in Madison with a 300 /day Load. Figure 2.6 Af/Af aVersus M /M for the Base Case Syste fan Madisoncwi h a 300 R/day Load. Figure 2.7 Af Variation with the Mixed-Tank So a Fraction for the Base Case System in Albuquerque. Figure 2.8 Af Variation with the Stratified-Tank So a Fraction for the Base Case System in Albuquerque. Figure 3.1 The f-Chart for Liquid Systems. (Equation 3.8) From Reference [4]. Figure 3.2 Annual Solar Fractions from TRNSYS Simulations with a Fully-Mixed Preheat Tank Compared to the f-Chart Method. Figure 3.3 Annual Solar Fractions from TRNSYS Simulations with a Stratified Preheat Tank Compared to the f-Chart Method. Figure 3.4 Collector Area Ratio Variation with the Ratio of the Monthly- Average Daily Collector to L F1 and the Solar Fraction from a Mixed Tank System.
47
54
57
59
61
62
67
71
72
76
viii
Figure 3.5
Co
amr
Solar Fractions from TRNSYS and the Annual Solar Fractions from the f-Chart Method Modified with Equation 3.13.
78
Figure 3.6
The Liquid System f-Chart with an Example of a Varying Collector Area Line. The Relationship Between the Collector Heat Removal Factor and the C llector Loss Coefficient. A = 1.2m M = 10 kg/hr-m ,h=306W/m5C, Wc= 0.15 m, d. = 0.009 m, do = 0.01,6 = 0.001. The Variation of the X and Y Parameters on a Liquid System f-Chart Caused by Increasing ULand Correspondingly Decreasing FR. The Relationship Between the f-Chart Parameters for a Collector with no Thermal Losses, a System with a FullyMixed Storage, and a System with a Stratified Storage.
79
Figure 3.7
83
Figure 3.8
84
Figure 3.9
86
Figure 3.10 Simulation Results of AX/AXmax Versus Mc/ML for Madison, 200 R/day Load, and the Base Case System. Figure 3.11 Annual Solar Fractions from TRNSYS Simulations Versus the f-Chart Method Modified with the Stratification Correction for MC/ML less than 0.3
89
93
ix
Figure 3.12 AX/AXmax for the f-Chart method Figure 3.13 Annual Solar Fractions from TRNSYS Simulations Versus the f-Chart Method Modified with the Stratification Correction, for Mc=10-60 kc/hrm2 and all Locations, Loads, and Systems. Figure 4.1 AX/AXmax for the of-Chart method
94 96
108
Figure 4.2
Annual Solar Fractions from TRNSYS Simulations Versus the Tf-Chart Method a Modified with the Stratification Correction, for Mc=10-60 kg/hrm2 and all Locations, Loads, and Systems.
109
LIST OF TABLES
the Tilt
Angle to
be used
in
19
Equation 1.12, From Reference 13 Table 2.1 Parameter Values for the Systems Simulated in this Study Table 3.1 Parameter Values for the Chart Example Table 4.1 The Error of the Stratified Design Method 107 System in the f97 52
for Varying Ranges of Collector Flowrate Table 4.2 Parameter Values for the System in the 111
0,f-Chart Example
xi
NOMENCLATURE Symbols used in this thesis which do not appear below are defined locally in the text. As AC C D di d0 E F' fmax cross-section area of the storage tank collector area collector fluid specific heat tank diameter. inside riser tube diameter outside riser tube diameter collector effectiveness collector efficiency factor monthly solar fraction for a solar system with a collector that has no thermal losses fmix monthly solar fraction for a solar system with a mixed preheat tank f str monthly solar fraction for a solar system with a stratified preheat tank FR HT collector heat removal factor monthly-average insolation incident upon the collector H0 extraterrestrial radiation storaqe height. Ic the critical radiation from equation 1.5 xii
Hs
It
k K' t Ks KT L
fluid thermal conductivity modified stratification coefficient, equation 1.12 stratification coefficient monthly-average daily clearness index monthly energy removed from the system by the hot water demand
L0tank Mc/ML
Mc Mt M N NP P QaOc Qa qu
collector mass flowrate mass of fluid in the preheat tank mixing number number of days in the month. collector operating time tank perimeter auxiliary energy demand of a conventional DHW system auxiliary energy demand of the solar system instantaneous rate of energy gain monthly-average daily useful energy gain monthly-average ratio of total radiation on a tilted surface to that on ahorizontal surface
Qu
R
Rn
horizonal surface for the average day of the month rtn ratio of the total radiation in the hour around noon to the total daily radiation T Twwater Ta Tday storage tempertature set temperature monthly-average ambient temperature monthly-average temperature during the daylight hours T. Tm T collector inlet water temperature mains water temperature the sunrise time if the sign is negative and the sunset time if it is positive. Ttank TW Ut UL U W X average storage temperature space temperature where the storage is located storage loss coefficient overall collector loss coefficient inlet velocity distance between riser tubes X parameter for the f-Chart correlation, equation 3.1 X Xc Y vertical distance of the storage monthly-average critical radiation level Y parameter for the f-Chart correlation, equation 3.2 xiv
AT At Om
top-to-bottom temperature difference number of seconds in the month monthly optimal collector tilt, from Table 1.1. collector tilt
ws
xv
CHAPTER ONE:
INTRODUCTION
Recent studies have shown that the performance of solar domestic hot water (SDHW) systems may A be improved by of
reducing the
collector fluid
flowrate.
high degree
thermal stratification in
be achieved
in a system that has a low flowrate. assume that the storage tank
is fully-mixed,
assumption when high collector flowrates are used. method that accounts for stratification
is necessary flowrates.
evaluate SDHW
thesis investigated a modification to the f-Chart method and the Ff-Chart method to make them applicable to active SDHW systems discuss methods collector with the of thermal stratification. cause and effect the time, of This chapter storage function, average will and the
stratifed
obtaining operating
ambient
daylight hours. to
modifications
present Chapter
stratification.
correction based on the difference in solar fraction between mixed tank and stratified tank systems. In Chapter Three, a
stratification modification for the f-Chart method is presented. A correlation was developed between collector
flowrate Finally,
and in
modified Four
collector the
loss
Chapter
modified
factor is applied to
,f-Chart
strategy removal
high value
and
consequently
However,
during a
collector
temperature
These are
a low flowrate
experimentally and
1.1.1
the decrease in
heat removal factor. A high collector flowrate does not necessarily mean
that the solar domestic hot water system performance will be increased. High flowrates tend to reduce the degree of
thermal stratification in the storage is recirculated through the collector day and as a consequence, temperature is increased. collector area of
the average daily collector inlet For a typical storage volume per the storage volume is
75 /m2 ,
times per
fluid previously heated by solar the collector again, increasing and experiments E23 have typical storage volumes
ff
0.9 0.80.74-
0
L.
0.60.50.40.30.20.1 0-I--
stratified-tank system
--
LL
mixed-tank system
V)
II
0 20
Collector Flowrate
40
(kg/hr-m2)
1 50
Ficrure 1.1
Effect of Collector Flowrate on the Theoretical, Monthly Solar Fraction for a Stratified and a Fully-Mixed Preheat Tank System for the Base Case System in Madison with a 300 /day Load.
At both
very
low
collector is similar,
flowrates due to
performance
of
systems
At high system
performance
recirculation causes the difference between the tank top and bottom temperatures to be small, close to that of the mixed so that the performance is tank system. The maximum
low-flow control strategy appears to perform better than the high-flow performance suggests strategy. at flowrates it may The rapid than decrease in system flowrate at a
less
the optimal to
that
be advantageous
operate
1.2
DESIGN METHODS
such as system
The advantages
detailed simulations are its disadvantages expertise, unusual or are its high
computer
facilities.
systems, detailed
are impractical as a long-term performance design tool. results from these simulations, however, simple design can be used
developing computationally
methods that
monthly-average meteorological data, rather data required obtained from for TRNSYS. The long-term
are not as
accurate as the data from simulations, but their accuracy is generally sufficient for design purposes. Two SDHW design
methods were investigated in this E43 and the O,f-Chart method E53.
generally broad enough to incorporate the majority of system designs, but is limited to increase the accuracy for typical systems and to reduce the computational effort.
open-loop solar
value dumps fluid, and energy, if the average temperature of the preheat tank is above the fluid boiling the pump point. if A the
differential
controller
activates
temperature difference between the tank outlet and collector outlet is greater than a deadband temperature. A heat
desired
temperature, if
Water is removed from the auxiliary tank to supply the load. During a hot of the preheat tank flows into water draw, mains water flows tank, and water from the top the auxiliary above the storage. into the bottom of the preheat If the delivery valve
set temperature,
a mixing
delivery water to
maintain the
set temperature. In open-loop designs, but also fluid. a load removes not only energy,
This is in contrast to
a closed-loop SDHW
system, shown in
Figure 1.3
When a load
is present, the
TO TAPS
WATER 1 SUPPLY
Figure 1.2
- "Li ,
Figure 1.3
Uhmmatic.
FroRmleference
M3,.
10
heat exchanger.
No
useful energy
1.2.2
measurement of compare
is necessary The
to
quantitatively
rationale
fl
Qa L+L
0
2= 1
L-[12
11
f3 = 1-
a(1.3)
Qac
where, Qa Qa, auxiliary energy demand of the solar system auxiliary energy demand of a conventional
DHW system L L0 hot water load tank losses
The
first
solar fraction
definition,
equation
1.1.
defines the total load as the hot water demand plus the tank losses. This definition may not be appropriate for a
measure of the fraction of displaced fuel, since the load of the solar system may be larger in a two-tank than in a conventional system due to system. Also,
stratification in the storage, and temperature swings in the space where the storage is located. The second hot water load solar fraction in the equation includes Tank only the not
denominator.
losses are
they will increase the auxiliary f2 to decrease. If the solar than the tank losses,
energy energy be
greater
f2can
12
negative.
Experimentally
determining f2 is easy
since the
auxiliary energy and the hot water load are easily measured. From an economic standpoint, the system should be
conventional system that supplies water. supplied solar The third solar
fraction is between
difference to the
conventional system. be
difficult, due
differences between
conventional systems.
For example, SDHW tanks are generally In this study the solar
1.2.3 Utilizability
gain by known
a flat-plate
Hottel-Whillier
equation [7,8,9) qu =AcFRE(TOL)It where, qu Ac FR (to ) instantaneous rate of energy gain collector area collector heat removal factor transmittance-absorbtance product
-
UL(Ti-Ta)J +
[1.4)
13
It
instantaneous
radiation
incident
upon
the
collector per unit area UL Ti Ta collector loss coefficient collector inlet temperature. ambient temperature only positive values of the are considered. This
sqare brackets
pump whenever useful energy can be obtained. The solar level losses before and radiation must the useful be greater exceeds than a the This critical collector critical
produced.
is found by setting
equal to zero
Ic = UL (Ti-Ta)/(TM)
1.5)
qu=AcFR(T)(It
The monthly total
Ic ) +
are constant
14
Qu= AcFR(
If the integral
i)f t (ItIc
+ dt
1.7. it to
is nondimensionalized by referencing
the total
radiation, then a
defining equation
is obtained
for utilizability
=At(It-IC) +dt
fAttdt
is
the
fraction
of
the
incident
solar from a
could be
obtained as
with an
difference
collector
Qu
where,
Ei.91
Ht
15
The
value of
4 cannot
be obtained
the
total radiation
level.
Illustrated in
are two
sequences of three days with the same total radiation level. The utilizability total area. day has a is the ratio of the shaded area to the
radiation. incident
effect is
increasing increase
variation
radiation
monthly-average
radiation days has been shown by Liu and Jordan E10 unique function of the independent of
to be a
month
Klein
could
dimensionless varibles,
/Rn and
x.0
R/R n is a geometric factor that includes the collector year. R is the monthly and time of the
tilt, location,
ratio of radiation incident of a tilted surface to that on a horizontal surface. the tilted surface Rn is the noon ratio of radiation on
to that on a horizontal
ooo
Ic
.1
C U2
Ic
Figure 1.4
Two Sequence of Days with the sane Averaqe Radiation. Frou Reference E113.
Ch
17
critical radiation
level, X c"
is
equation 1.5
to the
noon radiation level for the average day of the month I Xc= rt, nRntH0 Methods for obtaining the variables in the denominator can El[i.i03
be found in Duffie and Beckman 112J. Klein's correlation for the monthly-average
expla+b(Rn/R)JEXc+CXc2 J
(.11)
where, a = 2.943-9.271Kt+4.031Kt 2 b
=
-4.345+8.853Kt -3.602K 2
c = -.170-0.306Kt+2.936Kt2 The maximum error for this correlation is 2.5%. Another relationship for 4 was al E13J. data, but difficult Equation 1.11 developed by Evans, et a wide range of
is accurate over
18
(K 2 -3 81 10 -'3 t )tt
B = 50.43*10 - 6 . l.23-l- 5 K't + 7.62*10-6(K't)2
K't = Kt cosE0"8(m-_P)J
0 Om This
collector tilt monthly optimal collector tilt, from Table 1.1. correlation has a reasonably low error for
utilizability values
The value
collector inlet temperature used in calculating the critical level, equation 1.5, is often not known exactly. the higher error of equation 1.12 may be Therefore, its
offset by
calculation ease and the uncertainty of the input variables. The utilizability design concept can be used whenever a collector operates this is the case, at a known then the monthly critical useful level. can If be
energy gain of a
equation 1.9.
An example
amenable to the
utilizability design is
is nearly constant
Generally,
varying critical
19
Equatim 1.12. f
Month 1 2
3
Om e+29 8+18
e+3
4 5
6
e-i0 6-22
0-25
7 8
9
0-24 e-1O
6-2
10
e+10
0+23 0+30
11
12
20
The number of hours that the collector pump operates is needed to calculate the parasitic energy requirement and the daily mass of fluid that is pumped through the collector.
It will be shown in Chapter Three that the degree of thermal stratification present in a SDHW of the daily mass of fluid the preheat tank is a function is pumped through operating the time
that
collector.
Obtaining
collector
Some relationships
collector operating time were investigated. Mitchell, Theilacker relationship for the and Klein [14) have a A developed a the
pump-on
time as
function of
plot of is shown
level for
differential controller
with a
zero deadband
activate the pump whenever the critical level, Ico equal to the
collector gains.
The daily
the curve above the critical level If the differential area bounded by
21
C
.,-'
0 U)
Ic
Time
Fiture 1.5 Radiation level for a Clear Day.
f ermce E143.
From
22
and
the
critical
level
plus
differential
amount,
Ic + & I c ois
approximated as a
rectangle, then
the monthly
_
Np=Ht
(I c)-Iac +&I c)
[1.13)
c
In the
hand side
c The difficulty in using equation 1.14 is in determining an appropriate critical level. To obtain a monthly-average
daily collector operating time from equation 1.14, a monthly average equation collector inlet 1.6, yielding a temperature, T i must be used in
monthly-average critical
level. be
The monthly-average
collector inlet It is a
temperature cannot
obtained analytically.
function of
the collector
conditions.
is also a measure
of the amount
If the recirculation volume is small, then a for the average inlet temperature
reasonable approximation
23
employed two
the using
reasons.
in the
critical level
high
correlation has
RMS error
utilizability equation 1.12 is small. of equation 1.12 results in operating time, NP,
NP = Ht(A +
given by
11.15J
2 BIc)
where, A and B are the same coefficients as given in equation 1.12. There evaluation temperature collector are of is inlet a the number of sources If for the error mains in the water the
lower
ambient low,
temperature
contoller The
useful energy gain during this nighttime operation is small, but the operating time can be large enough to cause an error in the pump-on time estimation. This behavior is often
24
the assumption that the collector inlet temperature is equal to the mains water temperature. This may be a good for
assumption for
but not
fully-mixed storage
is numerical.
error,
This will cause the RMS error for time to be greater than the
utilizability correlation error. A plot of the monthly-average mixed storage tank obtained from collector flowrate for a TRNSYS compared to the
shown in Figure
caused by
inlet temperature
being greater than or equal to For the 1.6, mixed tank system in did
the collector
not operate
night, since
collector inlet
for a mixed
at night.
in Figure 1.7, comparing stratified storage simulations with the results from previous graph equation 1.15 is not
.
The bias
as evident in
this plot,
2000
1600
1200
800
400
400
800
1200
1600
2000
Iiqr.
1.6
fnothly-Aewraqe fiy Collector Platt. T simatiem with a mma Prehet to qmtln 1.15.
frm C amrei
2000
1600
1200
800
400
0400
800
1200
1600
2000
Nmothly-Avera"e hily Collector r'lmate f m UlmAlatlmmg with a Otrstj~ UA Preheat, Mf Cmpred to 8quation 1.15.
27
stratified tank. The collector operating using a correlation for time can also be the evaluated by daily
monthly-average
correlation, but more accurate over a wide range of critical radiation levels. Evaluating the derivative of Klein's #
where,
4, A, B, and C are from equation 1.11, and
Rn , rtn, and R can be obtained from Duffie and Beckman (123. A program that inplements the CHART4.1 needed for (153, requires the #,f-Chart method, such as Fevaluation For these of the variables
equation 1.16 .
of equation 1.16
variables are previously calculated. Other collector operating time investigated. did An attempt was made utilizability, so The relationships were also to find an equation that that the computational variation with as being range of
not require
be reduced.
pump-on time
28
be a function developed
operating
the
daylength to work
This correlation
found
equations that are not sensitive to the accuracy of the pump operating time. they are Since they are a function of the daylength, biased. For this reason, upon the collector daylength
location
operating
time correlations
depending
The equation
level
from inlet
ambient
level is
exposed The
to
during
while is the
ambient
temperature data is
temperature, night.
mean value
the day
29
Erbs (16) has developed a relationship for the monthlyaverage hourly temperature, Tah
,
as
a function
of
the
monthly-average clearness index, Kt, and the monthly-average ambient (day and night) temperature, Ta Tah = Ta + AEO.4632cos(tA-3.805)
+ 0.0984cos(2tA-0.360) + 0.0168cos(3t-0.822) + 0.0138cos(4t"
-
3.513)]
[1.17)
to sunset daylight
temperature.
sunrise or sunset
obtained from
sunset time if it is positive. The sunset hour angle can be found from Reference (12)
w s = arccos (-tan& tan&)
(1.193
where,
30
the latitude S the declination. equation 1.17 over a day the with the limits
Integrating obtained
from
equation
1.18
yields
monthly-average
does not
qive the
unless The
lower
equation 1.20
will lie is
extremes.
the solar
radiation level
be closer if the
average
temperature amplitude,
A, from equation
1.17 is
large and
the solar radiation level is low, the difference between the operating large. The temperature and daylight temperature could be
operating
temperature, so it
is a better approximation
for T
31
1.5 OBJECTIVES
The objective of this research was to develop a general design method have a for domestic hot water heating The systems that was
thermally stratified
tank.
approach that
parameter and the corresponding stratified tank parameter. Chapter two analyzes attempting to previous work that has develop a been done of solar
analytically Also in
measure
stratification.
Chapter Two,
an empirical
fraction modification is analyzed. In Chapter are discussed. Three, modifications to the A correction factor in the X and from was f-Chart method developed that
achieved from
of parameters
modified the collector loss coefficient and the heat removal factor. The performance of a can be SDHW system with a stratified using the modifed UL and
preheat tank
obtained by
32
Chapter
There
are
many
different approaches
that
could
be
undertaken to water
(SDHW) systems
stratified
storage.
The advantage to
increasing the
design method's
applicability
be getting
learn to
There are a number of accurate, adaptable, and mixed-tank SDHW design methods presently
available. solar
fraction,
correction could be to This as the modify the approach is *,f-Chart f-Chart exchanger
number of
way would
modify
different
would be
a relationship
benefit of such a correction factor is its applicability for all SDHW design methods. The difficulty in a technique such relation of solar fraction to
as this lies in the nonlinear other system variables. fraction directly has
empirically.
A number
of researchers
have attempted
to derive
an
analytical model to predict the effect of stratified storage on solar system performance. the advantage of if the An analytical model could have time and good
simplifying
justifiable,
agreement with experimental results. develop an the partial heat transfer The boundary inlet and the analytical model entails differential equation in a liquid storage conditions are an
tank with no
initial
given
distribution.
Phillips, et al. has studied stratified storacre for air systems E17), and obtained integrated daily performance
predictions of both air systems (18), and liquid-based solar systems (19). He uses a dimensionless variable, the
stratification coefficient, Ks, in solving the heat transfer equation. The stratification coefficient is defined as the
gain
mixed-tank system.
Employing
K5
-.
UL(Ti-Ta)(
E2 .1]
AcFRE(T)It
UL(TtankTa)J
If
the
stratification
coefficient were
known,
then
the
for a daily
36 K
5
storage cross
water draw,
used to obtain ordinary differential equations from the heat transfer equation. In order to solve the ordinary of
it was
assumed that
the number
obvious.
results with detailed daily simulation, flow-rate systems, the analytical model
effectiveness
greater than 0.2, the stratification significant error, as shown below. with a low-flow control strategy
acceptable collector effectivness and tank turnover range. The general solution for dimensionless variables.
as
M=
AMk s m C Hs
E2.2J
37 where, As k m HS For a storage cross sectional area fluid conductance storage mass flowrate storage height. 300 k, 1.5 m tall storage tank with a low-flow the
control
strategy collector
flowrate of
10 kg/hr*m 2 ,
mixing number
dimensionless variable
5 W/m2
0 C,
and a flowrate
of 10 kg/hr-m 2 , the collector effectiveness is 0.43 The general solution to is the root of the equation 4pq(l-E)e p = (p+q) 2 eP-(p-q) 2 e-q E2.4) the stratification coefficient
where,
p q
If
= =
l./(2M)
/(2M)
number is small, then the stratification
the mixing
38
in Ell/(i-E)3
K s EUI+M*Zn EI/(l-E))). (=E2.53 solution to within one percent than 0.1. For vertical tanks, than 0.1, so for the
This agrees with the general if the mixing number is less the mixing number equation 2.5
should
results
stratification coefficient. The flowrate, stratification as calculated coefficient from equation versus 2.5, is collector shown in
fractions from
a stratified
Although the.stratification coefficient was derived energy gains, Phillips and However, it needed for the Dave is SDHW
Figure less
primarily to the
initial assumption
of a
Phillips and Dave state that most larger than [20), von
3.6 3.4 3.2 3 2.8 2.6 2.4 2.2 2 1.8 1.6 1.4 1.2 1 0 20
Collector Flowrate (kg/hr-m2)
40
Figure 2.1
The Stratified Coefficient Compared with the Ratio of Stratified Tank Solar Fraction to Mixed Tank Solar Fraction from TRNSYS.
40
appears to to load
flow ratios and no load, but the restrictions necessary with their method. analysis do not lend it well to a general design
Cole
and
Bellinger [1)
have
analytically
and conduction
tank walls.
stratified
recirculation)
stratification index from their experimental results. investigated tubes, the They
effect and
baffles,
thermal
capacity
stratification. ability of a
41
=
Gr Re 2 (Hs/D) 2
(2.63
where, q gravitational constant fluid volumetric expansion HS AT U D tank heiqht top-to-bottom temperature difference inlet velocity tank diameter. Richardson number stratified. indicates that The the storaqe cause a
A large tank
will remain
system to
inlet velocity.
systems that have a Richardson number less than the critical value of 0.25. the value note The inlet and outlet mixing number. It is is governed by interestin were to
Thompson
unaware
significance a
Richardson for
empirically
derived
correlation
42 Although Cole and Bellinger's work would be valuable to a tank designer interested is not useful in a in increasing stratification, it tool for predicting solar
design
deal with
An
attempt
was
made mixed
to
empirically tank
derive
a tank
relationship
between the
solar fractions.
stratified-tank solar
fraction to a function
The collector
values
of
affected of
by
flowrate
relationship
FR with
between FR and collector flowrate is shown in Fiqure 2.2 and may be expressed as
0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0 20 40 60 80 100
Collector Flowrate (kg/hr-m2) Figure 2.2
Comparison of Experimental and Analytical Results Showing the Variation of FR with Collector Flowrate.
44
FR
MC ..
[2.8J
flowrate
is generally
flowrate of 0.04 kg/s through twenty 1 cm riser tubes yields a Reynolds number of approximately 500, well into the
number
entrance
effects are
generally insignificant,
due to
the range of collector flowrates studied (2.5-60 kg/hrom2), the collector efficiency factor changes by only one percent. If F' is assumed independent for any of collector liquid flowrate flowrate, using an For
then FR can
be modified
in reference E12).
at test conditions,
FR at use
45 MC -e -(AcF'UL/McC P )
FR use AcUL L use WMMFR C fE test M FRetL1-e -(AcF'UL/McCp) ]2.
AcU L
test
UL V2.10)
Ac
Fanney degradation flowrates. equation 2.9 (25) of has
McC p
experimentally performance of his Figure investigated caused by the
collector
reduced and
A comparison is shown in
The
difference
between the experimental and analytical procedures is small, due possibly to the uncertainty of the low flow measurement.
is to find
parameters.
will cause
correlation to An example is
be biased at is the
the extreme
of this
storage
fully-mixed
and the
strictly
46
increases with collector flowrate (assuming no pipe losses.) For high collector flowrates this assumption is valid, but
the design method underpredicts the system performance. Stratification dependent upon Vertical tanks in vertical tanks height to is not strongly
Richardson number
generally not significant for vertical tanks 1261. Wuestling (22) found that the stratified-tank solar
fraction depends upon the collector flowrate, load flow, and the storage volume. As discussed in Section 1.1, stratified
systems perform better than mixed systems due to the reduced collector inlet temperature. The stratified system
should be as high as possible to increase FR, but low enough to avoid recirculation. This is achieved by pumping through
the
collector
on
daily
basis
volume
of
fluid
-r
0.90.80.70.6 0.50
Jun ay
M a r-------
.4 i l Ja J n ,
0.30.20.1 0
4
Mc/ML
Figure 2.3
Solar Fraction Variation with the Ratio of Monthly-Average Daily Collector Flow to Daily Load Flow.
48 efficiency is poor due to a low heat removal factor. To achieve maximum performance, the volume of the
that well-insulated tanks with a volume as least as large as the daily collector flowrate will achieve a similar
performance. The variation of solar system with the in Figure 1.1. fraction from a stratified-tank area was shown
For the reasons discussed above, the optimal depend upon the load, graph shows that the as indicated optimal system
optimal solar
location, collector quality, deadband, collector area, and load distribution. the daily
Although the
collector flowrate
solar fraction
49
2.2.3 oystm
design load
hecrlpeme
pmtsrs were investigated to
for typical ensure the The solar systems.
A rang, of
range from
daily draws.
which is a
load profiles
vary considerably.
load distributions
performance
storage tank
volumes operated
at high
flowrates.
collector operation.
investigating
profiles. He found that the RAND profile achieved an average solar fraction when compared to the other draw
50 patterns. The best performance was achieved by an afternoon useful energy in the afternoon reduces
recirculation and preheat tank losses since the average tank temperature is generally highest in the afternoon. The
worst performance was registered by a late morning draw that caused the most recirculation and difference in solar draw pattern and the tank losses. The maximum or the worst Including the
load pattern in a design method would be difficult since the draw profile is a difficult parameter to quantify. The RAND
profile is a typical draw pattern and was observed to have a performance for stratified tanks between the other profiles. It was, as a result, employed in this study. The weather data used data were [30). SOLMET typical Alb-
meteorological
year (TMY)
Madison, WI,
indices and
temperatures.
regions
meteorological
places except Albuquerque in June that have a Kt of 74%, and few cities with the exception of Seattle in December that have a Kt of 29%. Madison has wide annual weatherswn, with clearness indices ranging from 0.38 to 0.55 and ambient
51 temperature reqions' changing from -70C to 21C. fall Most between other these
weather
statistics
should
Three flat-plate collector designs base-case system being single was a three with
were analyzed.
The
glazed
selective surface absorber plate. polymer single glazed low loss system
was a
design.
The collector
efficiency
factors
collectors are
outside of the range listed in Table 2.1. A wide range of employed in change in maximum monthly flowrates instantaneous collector flowrates were As shown by Wuestling only 3 in E22J, a
this analysis.
reason, fraction
maximum solar
increase the
method's accuracy.
High collector
flowrates
52
Table 2.1 Parameter Values for the Systems Simulated in this Study Locations Madison, WI; Albuquerque, NM; Seattle, WA Collectors A =4.2 m Mc(test)=71.5 kq/hr m c slope=latitude b =0.i Base Case FRUL=4 .7 3 W/m 2 C FR(Tx)n=0. 8 0 5 Higher Quality FRUL= 3 .6 2 W/m 2 C FR(Tcx)n= 0 .7 5 4 Lower Quality FRUL= 8 .5 7 W/m 2 C FR(c(x) n =0.697 Mc= 2
.5 ,
Preheat Tank
53 system will approach the solar fraction from a mixed storage system at high collector to load flow ratios. ranging TRNSYS. system a from 2.5 to 60
2 kg/hr'm 2 were used
optimal and 20
generally
kg/hr-m 2 .
The transient
TRNSYS 12.1
components. The algebraic, preheat tank variable 132]. plug-flow tank model The plug-flow model was used uses a for the number of to
sized constant
of fluid
A description of
profile If
distribution at time t I .
54
TOP
BOTTOM
POSITION
Figure
2.4
From Reference
2W'.
the top of the tank and returns mains water into the bottom, shifting the segments towards the losses are calculated top of the storage. for each Tank
individually
is not The
operation.
position
mode inserts
the fluid
returning
source or the load between segments of adjacent temperatures to avoid temperature inversions. This mode yields an upper
limit on tank stratification, the lower limit being a fullymixed storage. The fixed inlet when the position collector mode fluid combines return
adjacent
segments
a limited set of low-flow experimental data 126J. The pump was activated by a perfect controller (i.e. The auxiliary
turn-off deadbands).
tank contained a 9 kW auxiliary heater and was assumed to be fully mixed. The water mains temperature and set
2.2.5 f Correlation
The difference
between the
mixed and
stratified tank
The maximum value for these curves is not at of one like the stratified
The maximum for the Af function will occur where dLfstr d(M /M For the strictly increasing mixed tank solar fraction
=0
[2.9ii1
function, the maximum difference between stratified tank systems will generally to load ratio flow ratio that maximizes less than
the collector
the stratified
tank solar
fraction.
The exception
is if the
fraction reaches
load flow ratio for which the stratified tank solar fraction is one. The curves shape with the to load flow in Figure 2.5 are approximately the same
0.260.240.22 0.2
0.18 0.160.140.120.1 0.08-
July
0.06 0.04
-
Apr
-
Feb
0.02 0
generated, as
The strategy for developing a design method for is to the find an equation for the maximum lar
flowrates
difference
between
stratifieda
tam At/Afax"
tank solar fractiom cald be tank solar fraction such as the f-Chart
from a
function of the
the monthly-
the load for the stratified tank and mixed tank systems.
the monthly-average tank temperature is equal to the desired set temperature, the maximum solar fraction difference is
also zero since the auxiliary energy demand is also zero for both the stratified and mixed storage systems. Between
these extremes, the maximum difference is a finite, positive quantity due the improved performance of the stratified tank design over the fraction is mixed tank system. The mixed-system solar
a linear function of the monthly-average tank temperature. A plot of the maximum difference between the
-I-
0.9 0.80.7-
0.60.50.40.3 0.20.1 00 0 0
Af/Af Versus mc/Mr for the Base Case Systerrn Madison with a 300 I/day Load.
60 mixed-system and stratified-system solar fraction versus the mixed-tank solar fraction at the flowrate that yields
Figure 2.7.
is fairly
approaces
approaces one.
A similar plot is
time the independent variable is the stratified-system solar fraction at the flowrate that yields Afmax* less scatter, and the trend is linear. This curve has range of
The wide
Afmax data for a stratified-system solar fraction of one is due to energy dumping. A linear regression for Figure 2.8
with the stratified-system solar less than 0.99 Af max - 0.322 fstr with system a correlation solar fraction
fraction constrained to be
correlate the
solar fraction difference instead fraction max A function was as the due to the linear
relationship between
function is maium a
0.45 0.4D
0.35 F0 0.30.25 0.20.1513m 0.1 0.050 0.2 0.4 0.6 0.8 Mixed Tank Solar Fraction
Figure 2.7
-
0%
13
o313
d~o0
Af Variation with the Mixed-Tank Solar FrIffion for the Base Case System in Albuquerque.
0.3
0.28 0.26 0.24 0.22
0 13
0
0P
0
-
0.20.18-
0 0 0 D2Lu 0l o 0 0 a 0
0= no00
oI dD
EJ 0 0
3 0 00 0
0 0
0E
0.2
0.4
0.6
0.8
Figure 2.8
Stratified Tank Solar Fraction Variation with the Stratified-Tank Solar f FrIfion for the Base Case System in Albuquerque.
63 asymptotically approaches zero as the collector to load flow increases. -max A nonlinear Lf
=
C1 M exp(C 2 M + C3M2)
regression routine was then used to
E2.13J
find the
load flow
stratification the
correction is
noniterative, is used
even to of
correlate
the derivative
equation 2.13
to find the
collector to
Afmax*
the mixed-tank solar fraction, since the only unknown is the stratified-system used at solar fraction. to give Equation 2.13 is then
the stratified-system
solar fraction. The RMS error between TRNSYS Madison with simulations and the tf 3
correlation for
10 collector
flowrate and
load flows is 6.9% for monthly annual values reasons for with a bias of the large error.
solar fractions and 4.7% for 2.7%. The There are a maximum solar number of fraction A
difference varies
with the
collector loss
coefficient.
64 stratified mixed-tank temperature. coefficient tank system design due has to a better performance the lower the collector collector than a
inlet loss
fraction
difference
between a mixed and stratified system. Also, the relationship between Af/Af max and the
function of the time of the instantaneous collector difference between relatively high. the This
flowrate stratified
systems is to be
causes recirculation
obtained at
a lower
Mc/M L and
tank losses to be increased. Due to the approach was high error of the taken. A solar Af correlation, another fraction difference is
difficult to correlate due to its nonlinear behavior and the large number of variables that it is dependent upon. next chapter, a stratified tank modification is In the studied
which modifies one or more variables that are used in the fChart method.
65
CHAPTER THREE: MODIFICATION TO THE F-CHART METHOD FOR THERMALLY STRATIFIED SDHW SYSTEMS
a modification to the
is presented.
equivalent collector
the collector
area that a fully mixed system would need to obtain the same solar system. fraction as The an otherwise identical stratified tank
collector area
modification agrees
well with
simulations for the system that it has a high parameters. is then error for SDHW systems
presented.
collector loss coefficient, and it agrees well over the wide range of parameters that were tested.
from
Correlations were
developed for
liquid space
66
correlated to
X = - -
=AcFRUL(I*6+l1l8Tw+3.86TM-2* 3 2
..
Ta )At
..
E3.13
L where, T w Tm At mains water temperature number of seconds in the month Y parameter is related to the ratio of
The dimensionless
Y =
--
3,21
The relation between solar fraction for SDHW systems and the X and Y parameters is shown in squares approximation
3 2 2 f = i.029Y-0.065X-0.245Y +0.0018X +O. 0215Y
E3,31
>-
(9 w
z w
LJ 0
0 (.9 C,) z
w:
L" 0 Uf) m
11
12
16
HEATING LOAD
Figure 3.1 The f-Chart for Liquid Systems. (Equation 3.8)
68
is valid is solar
in Figure
the constant
fraction lines.
[12) recommend
can be analyzed
method by
fractions and
linear extrapolation algorithm was developed computer given by X < 12, and
Y < 0.116-X - 0.128
applications.
For
the X
and
Y parameter
13.4) (3.5)
(3.6)
temperature
must be
between 500
and
70C.
The
design
69
method
was
derived
for
preheat
storage
tank
loss
coefficient of 0.42 W/m 2 OC and an adiabatic auxiliary tank. Auxiliary tank accounted for load as loss coefficients greater by adding the energy loss Klein 16J. than zero to the The can be
hot water
assumed loss
for
the
preheat
tank
is
rather of a DHW
low.
For
tank from
The f-Chart method will tend to for systems with typical tanks were assumed to
solar fraction for thermally stratified storage systems. A number modify either of correction the of X the or factors have Y parameter been derived to For increase liquid to the space
applicability heating a
f-Chart method.
storage
collector can
Variations
capacity
accounted
modifying the X parameter Xc X [actual storage capacity ]-0,25 75 R/m2 is also a correction factor for liquid systems to
There
70
modify size.
the Y
parameter for
variations
in heat
exchanger
flowrates. compared
Figure
1.2, with a
fully-mixed preheat tank and a preheat tank loss coefficient of 0.42 W/m 2 OC. on an The design method to simulation compares to within 2.0% results. For thermally
annual basis
stratified storage the as shown in Figure 3.3. a thermally stratified mixed preheat tank,
highly biased,
The collector inlet temperature for preheat tank is lower decreasing collector than a fullylosses and
method to tank
stratified
simulation, since the f-Chart method was developed for highflowrate, fully-mixed tank solar systems. This chapter will investigate a Chart method storage tank. for systems that The modification to the fthermally stratified presently has
have a
f-Chart design
method
account for
and air
alterations
dimensionless
0.2
0.4
0.6
0.8
0.2
0.4
0.6
0.8
Fiqure 3.3
73
parameters.
The
air
flowrate
correction
is
needed
to
account for thermal stratification in the pebble bed and the dependence of FR on flowrate. The air flow modification
factor adjusts the X parameter. A modification for fluid was tank attempted that stratification decreased with the the X
parameter
same
increase
increasing
stratification
X parameter was studied by equation 3.2 TRNSYS. and the The was the X
then
solved for
parameter modification
simulations by 8%.
the highest error were the high and low collector flowrates. The air flowrate correction factor is limited to air
.
greater than
5 k/s-m 2
a wide range
range of liquid A
thermosyphon system,
may have
74
correlation
for thermally
stratified
storaqe
concept of is the
the collector
actual collector
divided by the area that a fully-mixed tank would require to achieve the same solar fraction that was obtained by a
all else
set-up
of 4
m2 produces a at the
of 43%. with a If
system
operated
to achieve a A/AA, is
fraction is 5 m 2
approaches unity as the tank storage tank becomes mixed; and a minimum value of A/A* (maximum difference occurs when the daily to the load flow, The between fullycollector flow as observed by
also observed to be a function of the solar fraction. A nonlinear regression analysis was employed to
75
parameters
the simulations
system, three
and 5 to 60 kg/hrom 2 collector resulting equation is: A/AA = l.-E3.53(Mc/ML)-l exp-l.15(M--c/ML)where, Mc/ML the ratio of
7 l(Mc/ML
2 +0.655dmi/ML 3
monthly-average
daily
collector
flowrate to load flowrate from TRNSYS f the monthly solar fraction for an equivalent
system with a fully-mixed storage. The solar for a fraction, f, appearing in the A/AA equation was from a A/A*
mixed tank
f-Chart
is 2.31% of annual
solar fractions.
The monthly error is 4.67% with a bias of 0.13%. The equation for the collector area ratio as a function of mixed solar fraction and Mc/ML is shown in Figure 3.4.
range shown
76
o 0.9
0 0.8 0.7 0.6 0.5
0.4
C) 0.3
0
0.2
U0.1
0
0 2 4 6 8 10 12
Mc/Mi
Figure
3.4
Collector Area Ratio Variation with the Ratio of the Monthly- Average Daily Collector to Load Flow and the Solar Fraction from a Mixed Tank System.
77
be done
on the
graph, or
a fully-mixed months
The highest
error was
observed for
with a low clearness index. underpredict monthly solar fractions from in Seattle,
The f-Charts have been shown to WA E121 A due to Seattle's of annual low solar
radiation.
scatter plot
f-Charts using
equation 3.8
appears in Figure 3.5. The agree collector area for the correction factor for was shown which it to was
well
typical
system
FRUL equal to
were analyzed
correction method, the agreement with simulations was not as good. A system with an FRUL value of 3.72 W/m 2 0C was
tested with the area correction factor method, giving an RMS error of 8%. The reason for this error can be seen in
collector
is determined by
the mixed-tank X
In general,
area line to
cause an
increase in
fraction, comparable
increasing the size of the solar collector. The error of the area correction the limit of zero collector factor can be seen in A stratified
loss coefficient.
78
1 0.9
;0.8 C)
0.6 0.7
* 0.5
cd 0.4
093 r>0.2 0.1 0
0 0.2 0.4 0.6 0.8
Figure 3.5
Comparison of the Stratified-Tank Annual Solar Fractions from TRNSYS and the Annual Solar Fractions from the f-Chart Method Modified with Equation 3.1.
(9 0::
1o::g,
CnZ
<
-n J
mWi
Cl) 0
m
I!
The Liquid System f-Chart with an Example of a Varying Collector Area Line.
80
and
a mixed will
with no neglecting
thermal minor
losses
differences in storage tank losses. Chart of and the a collector with no area modification line
than the
modification The
correlation
results. in
approach described
next section
was taken
order to develop
that could
performance of a solar
collector is
AcFRUL(Ti-Ta)
[3.9J
The major reason that stratified systems perform better than mixed tank systems is the temperature reduction of the fluid flowing into hand side the collector. The first term on the right the
is the
absorbed energy,
and the
second is
81
But for
a collector
no thermal
increasing the collector area implies that absorption, the useful i.e.,
Stratification
system by term
decreasing the
of the
equation. a method
in useful energy
stratification can be correlated and behave correctly in the extremes of the parameters.
assuming the preheat tank needed to have the fSDHW systems having from a
stratified
preheat
The solar
fraction
stratified system can be obtained system with coefficient. obtained a installed in a fully-mixed tank For example,
if a
a mixing
device is will be
solar fraction
82
reduced.
However, it
can
aqain be
raised
to 55%
solar
The collector heat removal factor collector loss coefficient. shown in The
is a function of the
heat removal factor of one and causes the heat The removal
coefficient
is a
collector
coefficient.
stratification modification to
the f-Chart
The f-Chart method includes the collector losses in the X parameter, and the heat removal factor in both parameters. Figure 3.8 is an expanded view of a liquid f-Chart. The
dashed line on
liquid f-Chart of a mixed tank system. fraction can be obtained from Xmix and Ymix*
with coordinates
collector has
the ratio
0.9 0.8 0.7 0.6 0.5 0.4 0.3 0.2 0.1 0 0 2 4 6 8 Collector Loss Coefficient (W/m2-C)
Figure 3.7 The Relationship Between the Collector eat Removal Facto and the Collector Loss Coefficient. A = 4.2u , M = 10 kg/hr-m ,h=30OW/mZoC, W = 0.15 m, d i = 0.009 m, d o = S.01,6p = 0.501. c
84
0.95
0.9 0.85
L 4,
f:.7
0 L 0 0.
A c(Tm)HTN/L"
[3.10 UL line in Figure 3.8 is the system that has no thermal always be system with
The stratified
between the
and the mixed solar fraction is that which would be obtained if the collector loss coefficient were varied from the
original value to zero, and correspondingly the heat removal factor was varied from the original value to one. The
slight curve in this line is due to the relationship between FR and UL" The equation relating the collector heat removal factor to the collector loss coefficient (Figure 3.7) is
shown
established
stratified, and mixed performances, shown in Figure 3.9. this figure, the maximum and mixed The X and Y
parameters are
shown as before.
z
0 0 ..J -j
Ymax
mU
mm 0 U) >II
Ystr Ymix
Xstr
Xmix
*8
12
16
three sets of f-Chart parameters can be expressed as AX AXmax Xmi x Xstr ------ =13
111
Xmix Ystr -Ymix Ymax Ymix Y parameters can be obtained from the (3.12)
The
mixed X
and
known, be
stratified equations
parameters 3.5,
calculated stratified
yielding
the
3.3.2 Results
The
relationship between
monthlyA
average collector to load flow, computer program was written simulation data collector
to determine AX/AX
using
flowrates ranging
and
daily load flows ranging from 200 to 400 /day. The program calculated the collector heat removal factor
88 analytically 1121, and Chart parameters. are constrained by solved for the mixed and maximum f-
X and Y parameters
and maximum
In this
parameters are
and the
shown in
be
A general relationship between IX/AXmax and M /ML can c 1M Lca seen in Figure 3.10 . The largest values of points where the system and occurs when performance difference the mixed system is
the daily
collector
systems approach each other since the temperature difference between the top and bottom of the stratified tank is
decreasing due
to recirculation.
The heat
removal factor
becomes small and A/Xmax approaches zero as the flowrate approaches zero. The upper limit low The limits on AX/AXmax are one and zero. is approached for high rates, where the solar fractions and collector inlet
recirculation
~1
A>
0.9-
0.80.7x
+ + +
E
x
0.60.5-
+
0
C3
C
0 C0
0i
xS
0.40.3-
Feb
0.20.1 0 -t 0
A
Apr
Jun
Aug
Mc/ML
Fiqure 3.10 Simulation Results of AX/AXmax Versus Mc/ML for Madison, 200 i/day Load, and the Base Case System.
90 as if the mains water is connected directly to the collector inlet ("once-through" design). The ratio AX/AXmax is a function load flow ratio and solar fraction. of the collector to An equation that
exhibits the behavior discussed in the previous paragraph is of the form X(X 2 + 1.) Other formulae that can fit the above criteria include but X*exp(-X). it produced This higher The equation residuals was and
simulations near
simulation results
for very
low collector
flowrates.
equation will overpredict AX/AXmaxfor low values of Mc/ML There are equations that would better follow these low
itself
collector flowrates are not a desirable operating region. A nonlinear coefficients simulations regression routine the RMS method was used to find the
TRNSYS the
with
correction
formula.
Evans, et al.
91
is computationally easier to solve. The X parameter
max
,is C1iM
2=2
2
3 131
+1
EC2 M + C3 f + C4f
12
Cl, C2, C3, C4 are coefficients from the regression routine, f the solar fraction from a mixed storage system, and M The solar a correlation for the collector to load flow fraction from a stratified system was tried in
place of the mixed solar fraction, about the same, using the
stratified solar
was 3.74% annually and 5.55% monthly with a bias of 0.63%. The data that exhibited a low collector flowrates, 2.5 high error included the very 7.5 kg/hr*m 2 . The form of not fit
low flowrates.
form of equation
flowrates in error all have a collector to load flow of less than one, indicating that they are operating at an undesirable collector to load ratio. Equation 3.13 is
for
flows, as
Figure 3.11
If only
range of flowrates from 10 - 60 kg/hr*m 2 is considered, the annual RMS error the bias is is 3.15%, the monthly error High residuals were is 5.49%, and also noted for
0.54%.
Seattle. location.
to Seattle's
radiation in the winter and high utilizability. The set of coefficients that gave the lowest RMS error
C4 = -2.760
Equation
3.13 with
the these
coefficients
is plotted
in
Figure 3.12 .
Because of
the nature
of equation
3.13, a
to load flow
ratio near one can give AX/AXmax greater than one. For these cases, AX/LX should be set equal to one. A plot of annual solar fractions from simulation results and the f-
0.5
0.4-0
V) 00 00
H 0
L
0 0 0
2 0.2
a 13
010
03
Flqre3-LI
Aua FomIractions fr 11Snal vrm the f -Cat Non NMtled with the ftratiflstmm COrree ism for N les1s thi 0.3C
10.9f=--0.7 0.80.7x
f=0.5
2 fIure 3.12
6 imnt
10
3.4 EXAMPLE
low-flow system
will be analyzed for the month of June. and design parameters step in the procedure
value for
fraction of a mixed system to be used in Equations 3.7. f-Chart method is employed using the actual
collector loss
coefficient, giving an X parameter of 2.59, a Y parameter of 0.77, and daily a solar fraction load of 50.2%. flow ratio to be The monthly-average can 1.40 equal be evaluated
.
collector to and it
by
is found
From to
Figure
equation to the
0.632 of
Going back
with an
X parameter
2.59(1-0.632) or 0.954 and a Y parameter of 0.942, the solar fraction for a stratified system is found to be 71.9%.
96
-r-
0.90.8 0.70.6-
z
Z. L-
0.50.4 0.3 0.2 0.1 0.1 0.3 0.5 F (FCHART) 0.7 0.9
Figure 3.13
Annual Solar Fractions from TRNSYS Simulations Versus the f-Chart Method Modified with the Stratification Correction, for Mc=10-60 kg/hrm2 and all Locations, Loads, and Systems.
97
Table 3.1 Parameter Values for System in f-Chart Example )cation Lc ME ateorological Madison, Wisconsin June H=17.07 MJ/m 2 Ta=19.6O C
K t =*513 Cc llectors
slope=latitude=43. 10 pr eheat Tank Volume=0.30 m 3 Heiqht=l.5 m U=0.42 W/m 2 C ixiliary Tank AL )t Hc Water Load negligible losses Demand=300 /day TM=10 C T =60 C Tc=20 C
98
CHAPTER FOUR: MODIFICATION TO THE 0,F-CHART METHOD FOR THERMALLY STRATIFIED SDHW SYSTEMS
method is a
utilizability critical
useful for
level.
was created
restrictions.
T,f-Chart
originally developed for closed-loop Figure 1.3. method system Braun, et al.
to open-loop shown in
designs,
as the
standard have
SDHW mass
These
designs
and storage.
Open-loop systems
that is characterized by
temperature from
storage is less than the set temperature. The method for estimatinq the solar fraction of openThe
loop systems by the 4,f-Chart method is as useful energy for a solar system is given by Q
=
follows.
a350.kJ/m2 oc
X = AcFRUL(100C)AT/L
Z = L/(MLCp(1000C))
Mt ML
mass of fluid in the preheat tank monthly mass of fluid removed from the system by the hot water demand
monthly energy removed from the system by the hot water demand
The term
Pmax is the
utilizability function
the monthly-average delivery temperature, Td. average delivery temperature is the average
the fluid going from the preheat tank to the auxiliary tank. The second part the of equation 4.1 corrects for is not always Z, is equal the fact that to Td. The
inlet temperature
dimensionless parameter,
important for
systems that
100
An equation for the storage losses is E4.21 at for the the average average 4.2 has tank tank been
temperature. temperature,
Ttank' to
in equation
determined by Braun, et al. to be Ttank = Td + g(ekf where, g = 0.2136 h = -4.002 .tCP/A M 35. kJ/m 2 c 004
-
1)(ehZ
E43
4.702.
minimum of the load and the delivered energy QS = min[MLCp(Td-Tmain)vL] The solar fraction section 1.2.1, hot water load f = QS-[4.5) L A monthly energy balance on the SDHW system, assuming that employed in this study, [4.4) as discussed in to the
is the ratio of
101
QU-
QLS
QS
0[4.6]
indicate that the monthly tl% of the
useful energy, for systems having typical storage volumes. The open-loop solution of q,f-Chart method involves to 4.6 for Td. value an iterative For monthly the
simulations,
initial
for Td is
solution from the previous month. Similar to tool is accurate the f-Chart method, the the p,f-Chart design SDHW
for predicting
performance of It
systems with
tank.
system that
storage tank.
4.2
storage was similar to the modification used for the f-Chart method. Chart A correlation for AX/AXmax was obtained in the fcorrection. The AX/AX max modifies the collector
102
f-Chart correction, the heat removal factor also is modified so that the stratified state is colinear on the liquid fthe mixed
E47J
4.81
AX
max
From the f-Chart correction, it was shown that AX AXmax Ystr-Ymix4 Ymax-Ymix
Substituting the definition of the Y parameter into equation 4.9 and solving for the stratified heat removal factor
yields
103 AX
(FR)st r = + (1.- -
AX
) (FR)mix [4.10)
Xmax and 4.10 can once is a be used in relationship The the O,f-Chart for form the of
AX/Axmax equation
equation is
of collector
flow ratio and solar fraction, it intersects the origin, has a maximum at an Mc/M L value of about one, and is asymptotic
4.3
.TS
package to
that
gradient of the
search
was employed
minimize
squares between TRNSYS simulations and the 0,f-Chart method modified with a stratification correction. AX/AXmax equation is similar stratified tank correction AX AXmC2 max where, C1 M 2 M + C3 f]2 + 1. [4.I111 to that used in The form of the the f-Chart
104
fm
fraction from
a mixed
storage system,
using a
monthly-average
utilizability
developed by Klein
As mentioned before, this equation than Evans' correlation, but range of critical radiation
levels.
program that
impliments the
*,f-Chart method,
such as F-CHART4.1, requires the evaluation of the variables in equation 1.16. For these programs, evaluation of equation 1.16 is not difficult, since most of the input variables are previously calculated. The same range of parameters used in the f-Chart method were used here; three locations, three systems, three
locations, ten flowrates 3240 pieces of data. ambient Evans' temperature utilizability The
a total of
The initial run used the day and night in the critical level equation and
collector
operating
time equation.
monthly, with a bias of 0.29%. When Erbs' was used, no daytime ambient change in the temperature equation were observed. 1.20 This
errors
105
indicates temperature
that using
the
average the
day and
night
ambient a good
in evaluating
critical
level is
approxmation. utilizability
The
negligible
difference or the
in
the
evaluated with
the ambient
daylight
temperature is consistent with findings from Reference E131. If Mitchell's collector operating time equation is used to estimate the collector to load flow ratio, the error
decreases negligibly to 2.60% annually, 3.88% monthly, and a bias of 0.21%. obtained from This would indicate that the solar fraction with equation
correct.
This is caused by
The slope of
system, and consequently 8XIAXmax of the using collector to load flow the mains is
ratio. in
the critical
evaluation
insensitivity at
high collector in
TRNSYS simulations
cover a
wide range,
of them
106
discussed caused a
the due
low
collector the
form of
The error without these very low flows are listed the flowrates
4.1. The annual RMS error for 2. 10-60 kg/hr-m is only 2.07%, with no bias. eliminated since the AX/AXmax tends to flowrates.
overpredict solar
operating range.
coefficients for
C3 = -0.1657
AX/AXmax from
Equation
4.11
is
plotted
versus
the
collector to load flow ratio in Figure 4.1 . A comparison solar of TRNSYS simulation results and annual with
the V,f-Chart in
method modified
.
shown
The
difference reasonably in
method points
simulations is highest
with the
RMS error
systems with
107
Table 4.1 The Error of the Stratified Desiqn Method for Varying Ranges of Collector Flowrate Collector Flowrateg (kg/hrm RMS Error (%) Annual Monthly Bias (%)
2.60
3.93
0.27
2.55
3.89
0.24
2.51
3.81
0.18
2.07
3.45
0.03
1 0.90.80.7a
"
X~~~ 0.60.5-
--0.8
0.4
4 Mc/ML
10
1 w.e 4.1
AX/Axlbu
tbdl
109
1 0.9
t 0 0.8
_4-
0.7
'o
40"0
0.6 0.5
E
0
4-
0
4J
L
I.
. 01
0
0
Ficrure 4.2
0.2
0.4
0.6
0.8
Solar Fraction from TRNSYS Annual Solar Fractions from TRNSYS Simulations Versus the 4f-Chart Method Modified with the Stratification Correction, for Mc=10-60 kcr/hrm2 and all Locations, Loads, and Systems.
110 stratified preheat tank appears to simulations. agree well with detailed
4.4 EXAMPLE
An
example
of
estimating
the
performance
of
method is the
system having
estimated for as
April.
outlined in Reference [121. R=l.01 r t,n =0.131 Rn=l.02 The monthly total load is L=MdCp (Tw-Tm)N =1.886 GJ
First, the mixed-tank solar fraction is obtained. FR for the use conditions FR(use)/FR(test)=0.841 FRUL = 3.98 W/m 2 C
FR(To)=0.677
Modifying
An initial
guess of 300 C
is used for
the monthly-average
delivery temperature
ill
Table 4.2._Parameter Values for System in *, f-Chart Example Lc )cation Me teorological Madison, Wisconsin April
2 H=14.90 MJ/m
FR( o)n=0.805 (Xt)/(T(X)/ (tor)=.913 FRUL=4 .7 3 W/m 2 C Mc(test)=71.5 kq/hr m 2 a Mc(use)=10 kc/hr m 2 slope=latitude=43.10
Pr-eheat Tank
n =.925
Volume=0.30 m 3
Heiqht=l.5 m
Tank
112
QS
L
(300)(4.19)(30-10) (300)(4.19)(60-10) =0.40
Ic =UL(Td-Ta)/(T(X)
=(3.98)(30-8.7)/((.677)(.925))
2 =135.5 W/m
From
this
critical
level,
using
Klein's
correlation,
equation 1.11, the maximum utilizability is max =0.691 The useful energy is calculated from equation 4.1 Qmax
=
maxAcFR(T()HtN
MtCp/Ac tP 350.kJ/m 2 OC
-0.76
=0.50
Q.- = Qmax a(e b f -l .) (l.-eCX) (edZ)L =29.7-.0169Eexp(3.85-0.4)-1J.
113 El-exp(-.15*2.30)]exp(-l.959-0.5) (1,886)/30 =29.29 MJ The tank lossed are estimated from equation 4.2 and 4.3
MtCp/A C
g =0.2136
-0"704
2oME
350.kJ/m2
=0.239 C Ttank = Td + J(ekfl.)(e)hZ =30+(.239)E(exp(4.702*0.4)-Jexp(-4.002*0.50) =30.7 C QLS = (UA)tank(Ttank- T env =(2.75) (30.2-20) (24) (3600) =2.41 MJ A new guess of the delivery temperature can be obtained by
averacring the initial supply temperature with the calculated supply temperature
QS
QU - QLS
114
=25.14 MJ
=
QS, 2
(25.14 + 26.88)/2
=26.01 MJ Td,2 =TmainQs /MLCp =10 + 26,O10/(3004.19) =30.69 C Repeating the procedure with the new delivery temperature
=.677
"1
Qmax=2 9
MJ
Qu = 2 8 .64MJ
QLS =2.42 MJ Td, 2 =3 0.78 C Since there was little change in the iterations, it is not
115
necessary to iterate further. The next step is to calculate the monthly-average daily collector to load flow ratio from equation 1.15 or 1.16
c-ML
-E[A
ML =(10)(4.2)/300)(-.875)E-0.514+(-.990)(1.02/1.01))-
[1+2(0.330)(0.086)3(1.01)/1(0.131)(1.02)) =E(42kg/hr)/(300kg/day)]10.67 hrs/day =1.49 Then tX/AXmax can be determined from equation 4.11
AX 6Xmax
=2
0.6078 M
The
stratified
tank
heat removal
factor
and
tank
loss
(FRUL)st r =
(FRULstr
(FRUL)mix(1.-
mix
=(3.98)(l-.549)
116 =1.80
AX
R)st
=AXmax
IFR( (X))str = (0.549)(.913)+(i-0.549)(0.677) =0.807 Going back to the O,f-Chart method f=0.40
2 I =51.4 W/m
QLS=5.0 MJ Td,2=36,7 C
After a few iterations, Tmin= 4 0e 9 C f=0.619 An increase of 20% from the mixed-tank solar fraction. The
117
5.1 SUMMARY
The objective of this research method heating tanks. that could systems A high be that used for have
solar
thermally
designs
achieve
a performance
Present
design methods were developed assuming that the preheat tank is fully mixed, a good assumption with high collector
flowrates.
methods to underpredict the solar fraction from a stratified tank system. A number developed to tank systems. since of analytically try to predict These the derived equations the performance be have been
equations cannot
methods
assumptions necessary
in
solving
differential equations give them limited applicability. solar fraction differnce between a mixed-tank and
118
stratified tank
This
dependence upon a number of variables. A modification to the f-Chart method 141 that corrected for stratified tanks reason that was presented in Chapter 3. A primary better than
collector.
temperature reduces the thermal losses correction that correspondingly, This correction is collector to
of the collector.
a function of the
RMS error of the f-Chart method corrected with the collector loss coefficient modification compared to detailed
simulations is 3.15% annually. The O,f-Chart can be used for design method was stratified that modified so A that it correction was
factor
similar to
used for
employed.
The solar
fraction error
modified
research can
the tank walls, inlet For some systems, effects may not between
mixing, and conduction through the fluid. such as those be negligible. with horizontal tanks, these Systems with
collector flowrates
A correction should
performance of the plug-flow model to assertain the accuracy of the model over a wide range of system configurations. This study examined two-tank SDHW systems. Other
the stratified
high collector flowrates due to the increased heat exchanger efficiency and since in tank thermal stratification 123. two tanks in the heat exchangers tend to reduce Single tank set-ups can be
treated as
mixed storage
f-Chart method
investigated further for stratified single tank of the has an in-tank heating the
the location
element
will influence
120 degree of stratification. be simulated and Other collector types should also the stratified tank design
compared to
method.
121 REFERENCES 1 Cole, R.L. and Belliner, J.0., "National Thermal Stratification in Tanks," Arcronne National Lab, 82-7 (February 1982). Fanney, A.H. and Klein, S.A., "Performance of Solar Domestic Hot Water Systems at the National Bureau of Standards Measurements and Predictions" ASME Journal of Solar Energy Engineering, 105, p. 311 (August 1983). TRNSYS 12.1, Engineering Experiment Station Report 38-12, Solar Energy Laboratory, University of Wisconsin-Madison (1983). Klein, S.A., Beckman, W.A. and Duffie, J.A., "A Design Procedure For Solar Heating Systems," Solar Energy, 18, 113 (1976). Klein, S.A., and Beckman W.A., "A General Design Method for Closed-Loop Solar Energy Systems," Solar Energy, 22, 269 (1979). Buckles, W.E., and Klein, S.A., "Analysis of Solar Domestic Hot Water Heaters", Solar Energy, 25 (May 1980). Hottel, H.C., and Woertz, B.B., Flat-plate Solar Heat Collectors," 91 (1942). "Performance of Trans. ASME, 64,
Hottel, H.C., and Whillier, A., "Evalution of FlatPlate Collector Performance," Transactions of Conference on Use of Solar Energy, Part 1, p. 74, University of Arizona Press (1958). Bliss, R.W., "The Deriviation of Several Plate Efficiency Factors Useful in the Design of Flat-Plate Solar Heat Collectors." Solar Energy, 3, 55 (1959). Liu, B.Y.H., and Jordan, R.C., "The Interrelationship and Characteristic Distribution of Direct, Diffuse, and Total Solar Radiation", Solar Energy, 6 (1960).
10
122
11
Klein, S.A. "Calculation of Flat-Plate Collector Utilizability," Solar Energy, 21, 393 (1978). Duffie, J.A., and Beckman W.A., "Solar Engineering of Thermal Processes", Wiley-Interscience, New York (1980). Evans, D.L., Rule, T.T., and Wood, B.D., "A New Look at Long Term Collector Performance and Utilizability," Solar Energy, 28, 13 (1982). Mitchell, J.C., Theilacker, J.C. and Klein, S.A., "Calculation of Monthly Average Collector Operating Time and Parasitic Energy Requirements," Solar Energy, 26, 555 (1981). F-Chart 4.1, Engineering Experiment Station Report 50, Solar Energy Laboratory, University of WisconsinMadison (1980). Erbs, D.G., Klein, S.A., and Beckman W.A., "Estimation of Degree-Days and Ambient Temperature Bin Data From Monthly-Average Temperatures" ASHRAE Journal, June (1983). Phillips, W.F., "Effects of Stratification on the Performance of Solar Air Heating Systems." Solar Energy, 26, 175 (1981). Hoerger, C.R., Phillips, W.F., "An Analytical Model for the Integrated Daily Performance of Solar Air Heating Systems." ASME Solar Conference (1984). Phillips, W.F., and Dave R.N., "Effects of Stratification on the Performance of Liquid-Based Solar Heating Systems" Solar Energy, 29, No 2, pp. 111-120, (1982). Veltkamp, W.B., "Thermal Stratification in Heat Storage," In C. den Ouden, Thermal Storage of Solar Energy , Martinus Nijhoff, The Hague, 2, 47 (1980). Von Koppen, C.W.F., et al., "The Actual Benefits of Thermally Stratified Storage in A Small and A Medium Size Solar System," Proceedings ISES, Atlanta (1979).
12
13
14
15
16
17
18
19
20
21
123
22
Wuestling, M.D., Duffie, J.A., Klein, S.A. and Braun, J.E., "Investigation of Promising Control Alternatives for Solar Water Heating Systems," Proceedings of the ASES 1983 Annual Meeting, Minneapolis, Minnesota, Vol. 6, p. 229. Turner, J.S., Buoyancy Effects in Fluids, Internal Mixing Processes, Cambridge University Press, pp. 313-337 (1973). Lavan, Z., and Tompson, J., "Experimental Study of Thermally Stratified Hot Water Storage Tanks." Solar Energy, 19, 519 (1977). Fanney, A.H., written dated January 31, 1984 communication to S.A. Klein
23
24
25 26
Morrison, G.L. and Braun, J.E., "System Modelling and Operation Characteristics of Thermosyphon Solar Water Heaters," submitted to Solar Energy (1984). Mutch, J.J., "Residential Water Consumption Economics and Public Department R1498, NSF (1974). Heating, Policy, Fuel RAND,
27
28
Fischer, R.A., and Fanney, A.H., "Thermal Performance Comparisons for a Solar Hot Water System subjected to Various Hot Water Load Profiles", to be published in ASME Journal of Solar Energy Engineering. Wuestlinq, M.D., "Investigation of Promising Control Alternatives For Solar Water Heating Systems," M.S. Thesis University of Wisconsin-Madison (1983). Hall, I.J., et al., "Generation of Meteorological Year," Sandia National Report SAND 78-1601 (1979). a Typical Laboratory,
29
30
31
Solar Rating and Certification Corporation, Directory of S.R.C.C. Certified Solar Collector Ratings, Washington D.C., Fall 1983 Edition. Braun, J.E., Fanney, A.H., "Design and Evaluation of Thermosiphon Solar Hot Water Heating Systems", Proceedings of the ASES 1983 Annual Meeting, Minneapolis, Minnesota, Vol. 6, pp. 283-288.
32
124 33 34 "Energy Conservation in New Buldincr Dessign," ASHRAE Standard 90A-1980, New York (1980). Braun, J.E., Klein, S.A., and Pearson K.A., "An Improved Design Method for Solar Water Heating Systems", Solar Energy, 31, 597 (1983).