Sunteți pe pagina 1din 3

Technical datasheet

A pressure sensor, digital VAV controller and damper actuator all in one, providing a VAV-Compact solution with a communications capability for pressureindependent VAV and CAV systems in the comfort zone Control function: VAV-CAV / Open-Loop Control: DC 2...10 V / 0...10 V / MP-bus With additional connection facility for sensors or switches (not available for LMV-D2-MFT-RM) Specially integration into VAV Room Control Module T24-V42(-V02)... + T24-MP Service button and LEDs for servicing and commissioning Diagnostic socket for operating devices

VAV-Compact

LMV-D2-MFT-RM (LMV-D2-MP)

NMV-D2-MP

Brief Description Brief description


Application

Pressure measurement Control function VAV variable air volume

CAV constant air volume Bus function

Test function / test display

Operating and service devices Assembly and connection


Subject to technical change V3.0 07082009

OEM factory settings

The digital VAV-Compact has PI control characteristics and is used for pressure-independent control of VAV units in the comfort zone. Maintenance-free, dynamic, differential pressure sensor technology, proven in a wide range of applications, suitablefor use in offices, hospital wards, alpine hotels or cruise liners. VAV-CAV or open-loop operation (actuator/volumetric flow sensor) for integration in an external VAV control circuit.Feedback of damper position forfan optimisation For variable air volume applications based on a modulating reference variable, e.g. supplied by a room temperature controller or a DDC or bus system. It facilitates demand-related, power-saving ventilation in individual rooms or in zones of air conditioning systems. The Vmin ... Vmax working range can be subdivided by selecting a mode. The following operating modes are available: DC 2...10 V / 0...10 V / adjustable / bus. For constant air volume applications, e.g. in step mode, controlledby means of a switch. The following operating modes areavailable: CLOSE / Vmin / Vmid / Vmax / OPEN Upto eight Belimo MP devices (VAV / damper actuator / valve) can be connected together over the MP-Bus and integrated into the following systems: LONWORKS applications with Belimo UK24LON interface Communication functions with Belimo T24-V42(-V02)... + T24-MP DDC controller with integrated MP-Bus protocol Fan optimiser applications with optimisation COU24-A-MP A sensor (0...10 V or passive, e.g. a temperature sensor) or a switch can optionally be integrated into the higher-level DDC or bus system via the MP-Bus. The VAV-Compact features an LED with a ready display for commissioning and functional checking as well as a service mode with air shortage, excess air and setpoint = actual value display with LEDs. Belimo PC-Tool, remote control or ZTH-VAV, plugged into the VAV-Compact Via MP-Bus The VAV-Compact, which is assembled on the unit by the OEM, is connected using the prefabricated connecting cable. The VAV-Compact is mounted on the VAV unit by the unit manufacturer, who adjusts and tests it according to the application. The VAV-Compact is sold exclusively via the OEM channel for this reason. * Type LMV-D2-MFT-RM, same functionally as the LMV-D2-MP but without a position indicator and additional connection facility for sensors or switches

Overview Overview of types


Type LMV-D2-MFT-RM (LMV-D2-MP) NMV-D2-MP 10 Nm 3.5 W 5.5VA (max. 5 A @ 5 ms) approx. 700 g Torque 5 Nm Power consumption 3W For wire sizing 5VA (max. 5 A @ 5 ms) Weight approx. 500 g

Technical datasheet

VAV-Compact

Technical data
Supply Nominal voltage Power supply range Differential pressure sensor Operating pressure Characterising Installation position Operating medium (see Materials) Materials Measuring air conditions Control function VAV and CAV applications

AC 24 V, 50 / 60 Hz DC 24 V AC 19.2 ... 28.8 V DC 21.6 ... 28.8 V 2 ... 300 Pa (OEM-specific) max. 1000 Pa OEM-specific Differential pressure sensor Linearisation Any, no reset necessary Suppl y and exhaus t air in the com fort zone and in application s with sensor compatible media PC + ABS to UL94-V0; stainless steel, DIN 1.4301 X 10CrNiS1810; PP Santoprene 0... +50C / 5... 95% r.h., non-condensing VAV-CAV Open-loop operation Supply/exhaust air units in stand-alone operation / master-slave / parallel connection for rooms with positive/negative pressure or neutral air pressure Mixing units OEM-specific nominal volumetric flow setting, matches VAV box . 30 ... 100% of Vnom . 0 ... 100% of V.nom . 0 ... 100% of ( V min ... V max ) DC 2... 10 V / (4... 20 mA with 500 resistance) DC 0... 10 V / (0... 20 mA with 500 resistance) Input resistance min. 100 k Ohm Adjustable DC 0... 10 V DC 2... 10 V max. 0.5 mA DC 0... 10 V Adjustable DC 0... 10 V . . . C LOSE / V min / V mid */ V max / OPEN * (* only with AC 24 V supply)

Operating volumetric flow . V nom . V max . V min . V mid Classic control Mode for reference value input w (connection 3) Mode for actual volumetric flow signal U5 (connection 5) Operating modes for constant air volume Communication control A d dress in bus operation DDC controllor Fan optimiser Sensor integration (not available for LMV-D2-MFT-RM) Communication (BACnet or LonWork) Operation and servicing Communication Button LED indicator Actuator Direction of rotation Adaptation Manual disengagement Sound power level Angle of rotation Po sition indication S p indle driver Connection Safety Protection class Degree of protection EMC Mode of operation

MP1... 8 (classic control: PP) DDC controller / PLC, from various manufacturers, with integrated MP interface With BELIMO optimiser COU24-A-MP Passive (Pt1000, Ni1000 etc) and active sensors (0...10 V) e.g. temperature, humidity 2-point signal (switching capacity 16mA @ 24 V), e.g. switches, occupancy switches With BELIMO T24-V42(-V02)... + T24-MP Only MP2 or 3 addressing available Pluggable / PC-Tool (V3.1 or higher) / ZTH-VAV hand-operated device PP / MP-Bus, max. DC 15V, 1200 baud Adaptation / addressing / service function 24 V feed Status / service / bus function Brushless, non-blocking actuator with currentreduction ccw / cw Setting range recording and resolution to control range Push button, self-resetting without affecting functions max. 35dB 95 , with adjustable mechanical or electronic limiting Mechanical with pointer (not available for LMV-D2-MFT-RM) Clamp, for round spindles 10... 20 mm / square spindles 8... 16 mm Positive fit, wide range of versions, e.g. 8 x 8 mm Cable, 4 x 0.75 mm2, terminals III Safety extra-low voltage IP 54 CE according to 89/336/EEC Type 1 (to EN 60730-1)

Technical datasheet
Technical data
Safety

VAV-Compact

(continued)
0.5 kV (to EN 60730-1) 2 (to EN 60730-1) 0 ... +50C 20 ... +80C 5...95% r.h., non-condensating (to EN 60730-1) Maintenance-free

Rated impulse voltage Control pollution degree Ambient conditions Non-operating temperature Ambient humidity range Maintenance

Dimensions [mm]
LMV-D2-MFT-RM (LMV-D2-MP) NMV-D2-MP

Tool connection 1
Local connection via the service socket on the MP actuator with ZK1-GEN cable
USB 2.0 cable with A to B plug

USB
BELIMO PC-Tool

RJ11 (4/6)

ZK1-GEN

USB

24 V GND
2 1

Note The mode switch must be set to MA (master).

Tool connection 2
Local connection via the service socket on the MP actuator with ZK2-GEN cable
USB
BELIMO PC-Tool
USB 2.0 cable with A to B plug

RJ11 (4/6) ZK2-GEN


MP white = GND GND green = MP blue not connected

USB
1
LMV-D2-MFT-RM (LMV-D2-MP) NMV-D2-MP

Note The mode switch must be set to MA (master).

For more details informaiton, please refer to tool connection guild.

~ T ~ T _ +

AC 24 V _ + DC 24 V

5
U5 / MP

S-ar putea să vă placă și