Sunteți pe pagina 1din 60

High Efficiency Water-to-Water

Water-Source Comfort System

2 through 6 Tons 60 HZ
20 Tons 60 HZ

WSHP-PRC009-EN

Introduction

The water-to-water WSHP product of


fering has now been expanded to in
clude an AxiomTM 20-ton system.
Similar to a small reverse cycle chiller,
a water-to-water heat pump contains a
source-side water-to-refrigerant heat
exchanger, and a load-side water-torefrigerant heat exchanger. The
source for the water-to-water heat
pump is typically connected to a boil
er/cooling tower, or a ground-source
loop system. During the refrigeration
cycle, heat is transferred from the
source-side heat exchanger to the
load-side heat exchanger, or vice ver
sa. The load-side heat exchanger pro
vides conditioned fluid (hot or cold) to
a mechanical device such as radiant
systems, hydronic fan coils or fresh air
ventilation systems. See Figure 1.
The units may be applied in a boiler/
cooling tower setting, in a geothermal
closed or open loop application, or in a
hybrid application.

A feature summary for the WPWD


units include:

Features for the EXWA 20-ton unit


include:

1 High efficiency scroll


compressor with vibration mount
ing isolation
2 Braze plate stainless steel heat exchanger
3 Small, rack-able units sizes that
range from 2 to 6-tons
4

50 VA transformer

Appliance grade finish

1 High efficiency scroll


Compressor with vibration
mounting isolation
2 Co-axial heat exchanger
(copper or cupro-nickel option is
available on the source-side of the
unit only)
3 Slender design allows unit to fit
through a 36-inch doorway
4 Rack-able, modular design

6 Thermal expansion metering designed for 25-120 F range

5 Low pressure drops

1-inch FPT swivel connections

Factory installed
desuperheater option

6 Microprocessor based 24-volt elec


tro-mechanical controls (with 100
VA transformer)

All units accommodate service access


to the controls, and other major com
ponents to contribute to greater ser
viceability and maintainability of the
unit.
Each unit is verified for total unit per
formance before shipping to insure
quality standards are inherent in every
unit.

Figure 1: Source-side vs. load-side


2004 American Standard Inc. All rights reserved

WSHP-PRC009-EN

Table of Contents

Introduction

Features and Benefits

Application Considerations

Selection Procedures

WSHP-PRC009-EN

14

About the ARI-ISO 13256-2 Standard

14

Model Number Description

15

General Data

17

Performance Data

18

Cool and Heat Performance

18

Electrical Performance

46

Antifreeze Correction Factors

47

Controls

48

Wiring

48

Dimensional Data

50

Accessories

54

Mechanical Specifications

55

2 through 6-Tons

55

20-Tons

57

Features and
Benefits
Unit Description
The cabinet, which allows easy access
for installation and service is con
structed of heavy gauge steel.
The finish for unit sizes 2 through 6tons is produced by a corrosion resis
tant electrostatic powder paint coating
in the color soft dove. The 20-ton unit
includes a galvanized metal finish for
maximum durability and corrosive re
sistive exterior.
Each cabinet design accommodates
modular racking of the equipment to
incorporate multiple unit installations
within a tight or constraining space.
Before shipment, each unit is leak test
ed, dehydrated, charged with refriger
ant and run tested for proper
operation.
The cabinet insulation meets UL 181
requirements.
Sound
All units are internally walled with 1/2inch thick neoprene backed, acoustical
fiberglass insulation to attenuate com
pressor noise.
Compressors are internally isolated to
reduce vibration. A compressor base
plate and full-length channel stiffeners
are installed to further reduce vibra
tion.
Compressor
All units are equipped with a high effi
ciency scroll compressor to aid in the
reduction of sound, increases reliabili
ty and to provide efficient operation.
Refrigeration Circuit
The 2 through 6-ton units incorporate
a single circuit refrigeration design. All
heat pump designs include: a revers
ing valve, thermal expansion valve,
two water-to-refrigerant heat exchanger (source and load), and a com
pressor selected for the optimal
efficiency of each circuit.
The 20-ton unit incorporates a dual cir
cuit refrigeration design, duplicating
the major components listed above.
The units copper tubing is created
from a 99% pure copper formation that
4

conforms to the American Society of


Testing (ASTM) B743 for seamless,
light-annealed processing.
The units copper refrigeration system
is designed to be free from contami
nants and conditions such as drilling
fragments, dirt, or oil. This excludes
the possibility of these contaminants
from damaging the compressor mo
tor.

desired heating or cooling. See


Figure 4.
Unlike cap-tube assemblies, the TXV
allows the exact amount of refrigerant
required to meet the heat exchanger
load demands. This precise metering
increases the overall efficiency of the
unit.

Filter Drier
Every 2 through 6-ton unit is equipped
with a bi-directional filter drier to dehydrate and clean the refrigeration
system, adding to the life of the equip
ment.
Water-to-Refrigerant Coil
The water-to-refrigerant coils for the
unit includes a brazed-plate design for
the 2 through 6-ton equipment, and a
co-axial design for the 20-ton equip
ment.

Figure 2: Braze-plate heat exchanger

The braze-plate design (found in the 2


through 6-ton equipment) is construct
ed from stainless steel, and provides a
large amount of surface area for heat
exchange between the water and the
refrigerant. See Figure 2.
The co-axial design (found in the 20ton design) is a seamless tube-withina-tube construction. The inner-water
tube contains a deep fluted curve to
enhance heat transfer and minimize
fouling and scaling. It is available in ei
ther a copper or cupro-nickel (selectable option) on the source-side heat
exchanger, and a copper only on the
load-side heat exchanger. The outer
refrigerant tube is made from steel
material. The coil is leak tested to assure there is no cross leakage between
the water tube and the refrigerant gas
(steel tube) coil. See Figure 3.

Figure 3: Co-axial heat exchanger

Figure 4: Thermal expansion valve

Expansion Valve
The refrigerant flow metering is made
through a thermal expansion valve
(TXV). The TXV allows the unit to oper
ate with an entering fluid temperature
from 25 F to 120 F on the source-side.
The valve precisely meters refrigerant
flow through the circuitry to achieve
WSHP-PRC009-EN

Features and
Benefits

SIDE
VIEW

Figure 5: Water connections location


for 2 through 6-ton
equipment

TOP
VIEW

Figure 6: Water connection location


for 20-ton unit

Figure 7: Reversing valve

Figure 8: Accessible control box


WSHP-PRC009-EN

Schrader Connections
The connections for the low and high
side of the refrigeration system are lo
cated conveniently on the units right
side for the 2 through 6-ton units, and
behind the front, refrigeration access
panel for the 20-ton unit.

be used to heat water, reducing the


amount of electricity or gas consumed
by your hot water heater. In summer
months, your hot water is virtually
free. Year-round, these systems make
abundant hot water abundant and are
up to 30% less expensive.

Water Connections
The water-in/water-out connections to
the water-to-refrigerant heat exchang
ers are located on the units right side
for the 2 through 6-ton units (See Fig
ure 5), and on opposite ends for the
20-ton equipment. The source-side,
water-to-refrigerant connection is lo
cated on the unit front, while the loadside, water-to-refrigerant connection
is located at the units back for the 20ton unit. See Figure 6.

Standard equipment employing the


desuperheater option includes: a des
uperheater heat exchanger, circulating
pump, entering water temperature de
tector (125 F stops pump), discharge
refrigerant temperature detector
(145 F starts pump), fuse, and a water
heater hook-up kit.

The fittings for the 2 through 6-ton


equipment include a 1-inch, brass
swivel, female pipe threaded connec
tion. Both the source and the load-side
water connections are located on the
units right side.
The 20-ton connections are located in
ternal to the unit to help alleviate damage to the water copper piping during
shipment or job storage of the units
prior to installation. Fittings for the
load-side and source-side connections
are FPT (female pipe threaded).
Reversing Valve
A system reversing valve (4-way
valve) is included with all heat pumps.
This valve is piped to be energized in
the cooling mode to allow the system
to provided heat if valve failure were
to occur. Once the valve is energized
for cooling, it will remain energized
until the control system is turned to
the OFF position, or a heating cycle is
initiated. See Figure 7.

The circulating pump moves water


through the double walled desuper
heater heat exchanger. It then returns
the heated water to the water tank.
This water is heated by the superheat
ed refrigerant discharge gas from the
compressor, allowing heat energy,
typically dissipated through a cooling
tower or ground loop, to be utilized as
a cost savings.
Accessible Unit Control Box
The unit control box is accessible
through the units front access panel
on the 20-ton unit, and through the re
moval of the diagonal top on the 2
through 6-ton equipment.
The 2 through 6-ton equipment is
equipped with 24-volt basic controls,
while the 20-ton unit is equipped with
the deluxe 24-volt control package.
Components are easily accessible for
service, maintenance and start-up.
24-volt thermostat connection is made
at the unit terminal strip located in the
left corner of the control box. See Fig
ure 8 for unit control box of the 20-ton
unit.

Domestic Water Heating Coil


(option)
A hot water heater connection or des
uperheater option is available on the 2

through 6-ton equipment. With this

option, excess heat that would nor

mally be rejected by the cooling tower,

or earth-coupled heat exchanger may

Features and Benefits


Basic Controls
Basic 24 Volt Controls
(2 through 6-ton equipment)
The basic 24 V electro-mechanical unit
control provides component protec
tion devices for maximum system reli
ability. Each device is factory
mounted, wired and tested in the unit.
The 24V basic control package in
cludes:

System safety devices are provided to


prevent compressor damage through
the use of low and high pressure
switches in the refrigeration circuit.
The low pressure switch prevents
compressor operation during low
charge, excessive loss of charge situa
tion, or during low temperature opera
tion. The switch is set to activate at
refrigerant pressures of 35 psig when
a 35 F low temperature detection
thermostat is applied. An optional 7
psig pressure switch is available when
using a 20 F low temperature detec
tion thermostat.
The high pressure switch prevents
compressor operation during high or
excessive discharge pressures that ex
ceed 395 psig.

Low Temperature Detection


Thermostat
The low water temperature detection
thermostat is provided to protect the
water-to-refrigerant heat exchanger
from freezing. This device prevents
compressor operation if leaving water
temperature is below 35 F. An option
al 20 F temperature thermostat may
be applied for low water temperatures
where an appropriate antifreeze solu
tion is used.
Thermostat Connection
Low voltage and high voltage knockouts are provided in the top half of the
unit. All control wiring to the unit
should be 24 Volt. See wiring schemat
ic on the unit for thermostat hook-up.

A lockout relay provides the mechani


cal communication of the low and high
pressure switches to prevent com
pressor operation if the unit is under
low or high refrigerant circuit pres
sure. The lockout relay may be reset at
the thermostat, or by cycling power to
the unit.

2 through 6-ton
control box location

WSHP-PRC009-EN

Features and Benefits


Deluxe Controls
Deluxe Controls
(20-ton equipment)
The deluxe 24-volt electronic controls
provide component protection devices
similar to the basic design, but with
upgraded features to maximize sys
tem performance on the larger ton
nage equipment. The deluxe control
offering is unique to Tranes watersource equipment and is designed to
control the unit as well as provide outputs for unit status and fault detection.
The microprocessor board is factory
wired to a terminal strip to provide all
necessary terminals for field connec
tions.
Deluxe 24-volt features include:

the Trane TracerTM Loop Control Panel


(TLC). The deluxe controls may be dai
sy-chained directly to the TLC to provide loop, tower and unit control.
Random Start
The random start relay provides a time
delay start-up of the compressor when
cycling in the occupied mode. A new
start delay time between 3 and 10 sec
onds is applied each time power is enable to the unit.
Anti-Short Cycle Timer
The anti-short cycle timer provides a
three minute time delay between
compressor stop and compressor
restart.
Brown-out Protection
The brown-out protection function
measures the input voltage to the
controller and halts the compressor
operation. Once a brown-out situation
has occurred, the anti-short cycle
timer will become energized. The
general fault contact will not be
affected by this condition. The voltage
will continue to be monitored until the
voltage increases. The compressors
will be enabled at this time if all startup time delays have expired, and all
safeties have been satisfied.
Compressor Disable
The compressor disable relay pro
vides a temporary disable in compres
sor operation. The signal would be
provided from a water loop controller
in the system. It would disable the
compressor because of low water
flow, peak limiting or if the unit goes
into an unoccupied state. Once the
compressor has been disabled, the
anti-short cycle time period will begin.
Once the compressor disable signal is
no longer present, and all safeties are
satisfied, the control will allow the
compressor to restart.

And because deluxe 24-volt controls


are offered on other Axiom products, a
full 24-volt safety detection system
may be applied to the building for
loop, tower and total unit control via
WSHP-PRC009-EN

(normally closed) will be provided for


the relay contacts.
Safety Control
The deluxe microprocessor receives
separate input signals from the refrig
erant high pressure switch or low suc
tion pressure switch.
In a high pressure situation, the
compressor contactor is de-energized,
which suspends compressor opera
tion. The control will go into soft lockout mode initializing a three minute
time delay and a random start of 3 to
10 second time delays. Once these delays have expired, the unit will be al
lowed to run. If a high pressure
situation occurs within one hour of the
first situation, the control will be
placed into a manual lockout mode,
halting compressor operation, and ini
tiating the general alarm.
In a low temperature situation, the
low pressure switch will transition
open after the compressor starts. If the
switch is open for 45 seconds during
compressor start, the unit will go into
soft lockout mode initializing a three
minute time delay and a random start
of 3 to 10 second time delays. Once
these delays have expired, the unit will
be allowed to run. If the low pressure
situation occurs again within 30 min
utes, and the device is open for more
than 45 seconds, the control will be
placed into a manual lockout mode,
halting compressor operation, and ini
tiating the general alarm.
The general alarm is initiated when
the control goes into a manual lockout
mode for either high pressure or low
pressure.

Generic Relay
The generic relay is provided for field
use. An external Class II 24VAC signal
will energize the relay coil on termi
nals R1 and R2. Terminals C (com
mon), NO (normally open), and NC
7

Application
Considerations
Flexibility
The high efficiency water-to-water
heat pump system is versatile for installation in boiler/cooling tower applications, as well as ground-source
(geothermal) applications. The system
design may employ either a central
pumping design, or a distributed
pumping design.
A central pumping design involves a
single pump design, usually located
within a basement or mechanical
room to fulfill pumping requirements
for the entire building system. An auxiliary pump is typically applied to lessen the likelihood of system downtime
if the main pump malfunctions.
A distributed pumping system contains a single pump module connected
directly to the units supply and return.
This module is field installed and
piped to the unit. This design requires
individual pump modules specifically
sized for each water-source heat
pump.
Advantages of Geothermal
The advantages of a geothermal heat
pump system can literally cut a busi
ness heating and cooling costs by 30
to 40-percent. The units are durable,
and typically last longer than conven
tional systems because they are pro
tected from harsh outdoor weather
conditions, because the unit is installed indoors and the loop underground. (According to ASHRAE, the
estimated service life for a com
mercial water-to-air heat pump is
19-years.)

A ground source (geothermal)


system consist of a:

A ground water heat pump

A closed loop ground heat exchanger made of high density


polyethylene pipe (guaranteed
25- years or more by many manufacturers); and

A low wattage circulating pump(s)

The fluctuating temperatures of fluid


from the earth are more stable than
air, allowing the equipment to operate
at a lower discharge pressure and use

fewer kilowatts. The constant earth


temperature will heat or cool the fluid
running through buried polyethylene
pipe to provide heating and cooling to
a building.

Horizontal loops require trenches in

the ground spanning a larger overall

land area.

Although external piping is the re-

sponsibility of the installer and/or pip

ing manufacturer, many electric

utilities and rural electric cooperatives

are offering monetary incentives to in-

stall geothermal systems. Utility com-

panies offer the incentives because of

reduced peak loads that flatten out

their demand curve over time, and

save them money. These savings are

ultimately transferred to the consum

er. See Figure 9 for geothermal energy

recovery loop.

A geothermal loop can be installed ei


ther horizontally or vertically. Vertical
loops require less overall land area to
reject (i.e., sink) the excess heat from
the building.

Geothermal heat pumps


have fewer mechanical com
ponents, making them
more reliable and less
prone to failure. Manufacturers
of the loop materials guarantee
their products for up to 25-years,
with no maintenance required.
Geothermal heat pumps work toward
the preservation of the environment
by reducing the environmental im
pacts of electric power generation.
8

Figure 9: Hybrid loop


WSHP-PRC009-EN

Application
Considerations
Source vs. Load
The water-to-water heat pump contains two water-to-refrigerant heat exchangers. The two heat exchangers
enable the system to be divided into a
source and load separation.
The source-side heat exchanger performs as a standard water-to-air heat
pump system. The source is typically
supplied through a cooling tower,
boiler, closed loop, or open well sys

tem. During the refrigeration cycle,

heat is transferred from the source-

side heat exchanger to the load-side

heat exchanger.

The load-side heat exchanger takes

the place of a DX (direct expansion) air

coil. It provides treated fluid (hot or

cold) to a mechanical device. These

mechanical devices include designs

such as radiant slab heating, hydronic

coils, or fresh air ventilation units.

See Figure 10 for a basic schematic of

source-side verses load-side of a wa

ter-to-water system.

Figure 10: Source vs. Load

WSHP-PRC009-EN

Application
Considerations
Unit Installation
Installation of the water-to-water is
made easier through its unique
compact design. The units are typi
cally racked in a mechanical room
or penthouse allowing easy access
to the units and other mechanical
equipment. See Figure 11 for
WPWD installation.
The diagonal split in the 2 through
6-ton cabinet allows access to all
unit components from the front
side. By removing two screws from
the bottom of the unit, the cabinet
front and top may easily be removed for maintenance and ser
vice.
The larger tonnage (20-tons) waterto-water may be installed using a
similar method as the WPWD units.
Service access to these units is
through the unit front panel for
most major components.

Figure 11: WPWD installation

10

WSHP-PRC009-EN

Application
Considerations
Geothermal Integrated System
The water-to-water heat pump is high
ly efficient in service station applica
tions. See Figure 12.
This integrated system design takes
advantage of the earths relatively con
stant temperature (45 F to 70 F) to
space condition the building. In addi
tion, appliances such as freezers, ice
makers and display coolers may be
added to the loop for further gains in
the reduction of consumed energy.

Cold climates may take an even great


er advantage of the heat rejected by
the stores refrigeration equipment and
space conditioning heat pumps. This
rejected heat may be used by Tranes
water-to-water heat pump(s) to heat
water for a car wash and melt ice off of
a driveway (allowing the car wash to
remain open all winter).
This integrated system also eliminates
thermal short circuits between the intakes and the exhausts of an air cooled
refrigeration system.

Typical Benefits include:


Annual energy savings means


lower operational costs.

Takes advantage of the earths con


stant temperature rather than
high fluctuation of ambient tem
perature.
Heat energy rejected from the
space conditioner can be utilized
for ice or snow melting of the
parking lot in colder climates.

Two or three year estimated payback on installation costs.

Figure 12: Geothermal design in a service station application

WSHP-PRC009-EN

11

Application
Considerations
Water-to-Water and Fresh Air
Ventilation
Geothermal energy systems take advantage of the fact that subsurface
earth temperatures are constant year
round, which makes the earth an ideal
heat source and heat sink for heat
pumps.
The design referenced in Figure 13
goes further than just space heating
and cooling. Fresh air ventilation is
achieved by using Tranes water-towater units teamed with a M-Series
Climate Changer air handler, and ex
haust air unit to meet total building re
quirements.
In the cooling season, the load-side
water from the heat pumps is circulat
ed through a hydronic coil in the M-Se
ries unit to provide cooling and
dehumidification. The source-side wa
ter is used to provide reheat en
ergy to temper the ventilated air
in accordance with the building
needs. After leaving the reheat
ed hydronic coil, the condenser
water is then returned to the building
loop for further heat rejection.

In heating, the water-to-water units


switch to hot water generation. The
water for ventilation air tempering cir
culates through the hydronic coil to
the exhaust unit to pick up heat from
the building exhaust airstream. The
water then circulates through the wa
ter-to-water heat pumps for further
heat introduction before being used
by the makeup air unit hydronic coil to
heat the makeup air to maintain build
ing requirements. This ventilation sys
tem incorporates its own circulating
pumps to pull system water off the
loop and return it. There is no need for
additional heat injection using boilers
for this system. See Page 13 for me
chanical schematic.

Typical Benefits include:

Annual energy savings means


lower energy costs.

Building comfort and climate


control

Energy recovery

Figure 13: Water-to-water and fresh air ventilation

12

WSHP-PRC009-EN

Application
Considerations
Fresh Air Ventilation Mechanical Schematic

WSHP-PRC009-EN

13

Selection

Procedure

Unit Selection Procedure


Unit performance for the WPWD and
EXWA equipment is tabulated under
ARI/ISO 13256-2. To select unit(s):
1

Determine the system design con

ditions for both the source and


load-side(s) of the equipment.
Note: entering liquid temperatures
for the source-side can be 30F to
120F, and for the load-side, 45F to
120F.

2 Define the selection parameters.


(i.e. entering water temperature
(EWT), fluid flow rate, and fluid
pressure drop.
3 Determine unit requirements. (i.e.
total cooling capacity/total heating
capacity).
4

Refer to the performance data ta

bles and select possible units.

Note: When making unit selections,


there are a few considerations that
need to be made. These include:

14

If unit capacity is greater than larg

est unit available in the perfor

mance section (pages 18 through


45), multiple units may be required
to fulfill capacity requirements.
When adding two or more togeth

er, the system pumping pressure


drop may be lowered, perhaps
lowering the pump horsepower.

Staging of capacity to satisfy cool

ing requirements.
Pressure drop reduction through
the load-side of multiple units,
even when a single unit might
meet capacity.
If source-side leaving water tem

perature falls below 35, antifreeze


will be required in the fluid loop.
See page 47 for antifreeze correc

tion factors.
Cooling Performance
Source Load Source Source Source Cool
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
60.0 45.0
8.9
8.3
64.9 18.3
60.0 53.6
3.8
1.5
72.4 19.8
60.0 53.6
7.0
5.1
66.7 20.1
60.0 53.6
8.9
8.3
65.3 20.2

Load 3.8 GPM


Power Heat EER
kW
Of
Reject
0.97
1.07
1.00
0.98

21.6
23.5
23.5
23.5

18.9
18.5
20.1
20.6

Load Load
LWT WPD
Ft
Head
35.4
1.7
43.2
1.6
43
1.6
43
1.6

Heating Performance
Source Load Source Source
EWT EWT GPM WPD
Ft
Head
60.0
60.0
8.9
8.3
60.0
80.0
3.8
1.5
60.0
80.0
7.0
5.1
60.0
80.0
8.9
8.3

Load 3.8 GPM


Source Heat Power Heat COP
LWT Cap
kW
Of
Mbtuh
Absorb
53.9
49.0
53.3
54.6

31.2
26.8
29.4
29.8

1.24
1.73
1.74
1.76

27.0
20.9
23.5
23.8

7.4
4.5
5.0
5.0

Load Load
LWT WPD
Ft
Head
76.4
1.5
94.1
1.3
95.5
1.3
95.7
1.3

WSHP-PRC009-EN

Model Number

WPWD 2 through 6-Tons

Water-to-Water Heat Pump


W P W D 042 1 0 B 2 2 1 0 0 T
5

10

DIGITS 1-3: UNIT


CONFIGURATION
WPW = Extra High Efficiency
Water-to-Water Heat Pump

DIGITS 9: UNIT ARRANGEMENT


0 = Water-to-Water

DIGIT 4: DEVELOPMENT
SEQUENCE D

DIGITS 11: FREEZE PROTECTION


(SOURCE-SIDE)
1 = Brazed Plate Heat Exchanger
with 35 F (1.67 C) Freezestat
2 = Brazed Plate Heat Exchanger
with 20 F (-6.67 C) Freezestat

15
DIGITS 13: DESUPERHEATER
0 = No Desuperheater
1 = With Desuperheater

DIGITS 10: DESIGN SEQUENCE C


DIGIT 14: OPEN DIGIT = 0

DIGITS 5-7: NOMINAL SIZE (MBH)


024 = 24.0 MBH
036 = 36.0 MBH
042 = 42.0 MBH
048 = 48.0 MBH
060 = 60.0 MBH
072 = 72.0 MBH
DIGIT 8: VOLTAGE (Volts/Hz/Phase)
1 = 208-230/60/1
3 = 208-230/60/3
4 = 460/60/3
5 = 575/60/3
6 = 220-240/50/1
7 = 265/60/1
9 = 380-415/50/3

WSHP-PRC009-EN

DIGIT 15: OPEN DIGIT = 0


DIGIT 16: STICKER OPTION
T = Trane

DIGITS 12: FREEZE PROTECTION


(LOAD-SIDE)
1 = Brazed Plate Heat Exchanger
with 35 F (1.67 C) Freezestat
2 = Brazed Plate Heat Exchanger
with 20 F (-6.67 C) Freezestat

15

Model Number

EXWA 20-Tons

Water-to-Water Heat Pump


E X W A 240 3 1 A 0 0 1 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 000
5

10

DIGITS 1-3: UNIT


CONFIGURATION
EXW = Extra High Efficiency
Water-to-Water Heat Pump
DIGIT 4: DEVELOPMENT
SEQUENCE A
DIGITS 5-7: NOMINAL SIZE (Tons)
240 = 20-Ton
DIGIT 8: VOLTAGE (Volts/Hz/Phase)
3 = 208/60/3 8 = 230/60/3
4 = 460/60/3
5 = 575/60/3
DIGITS 9: HEAT EXCHANGER
(SOURCE-SIDE)
1 = Copper-Water Coil
2 = Cupro-Nickel Water Coil
*Note: Heat Exchanger for the LoadSide is Copper-Water Coil
ONLY.
DIGITS 10: DESIGN SEQUENCE A
DIGITS 11: REFRIGERATION
CIRCUIT
0 = Heating and Cooling Circuit
DIGITS 12: BLOWER
CONFIGURATION
0 = No Blower Required in the Design
DIGIT 13: CUSTOMER CHANNEL
1 = Boiler/Tower Design for Trane
Commercial Group
2 = Geothermal Design for Trane
Commercial Group
5 = Trane International Group

15

20

25

30

34

DIGIT 16: RETURN-AIR


ARRANGEMENT
0 = No Return-Air Arrangement

DIGITS 29: PIPING


ARRANGEMENT
0 = Standard Piping Connection

DIGIT 17: CONTROL TYPES


D = Deluxe 24 V Controls

DIGITS 30-36: DOES NOT APPLY


TO EXWA

DIGITS 18: TSTAT LOCATION


0 = Wall Mounted Location

0000000 = Digits 30-36 are not


applicable to the
EXWA product

DIGITS 19: FAULT SENSORS


0 = No Fault Sensor
DIGITS 20: TEMPERATURE
SENSOR
0 = No Temperature Sensor
DIGITS 21: NIGHT SETBACK
CONTROL
0 = No Night Setback Relay
DIGITS 22: ELECTRIC HEAT
0 = No Electric Heat
DIGITS 23: UNIT MOUNTED
DISCONNECT
0 = No Unit Mounted Disconnect
DIGITS 24: FILTER TYPE
0 = No Filter
DIGITS 25: ACOUSTIC
ARRANGEMENT
0 = Standard Factory Configuration
DIGITS 26: FACTORY
CONFIGURATION
0 = Standard Factory Configuration
DIGITS 27: PAINT COLOR
0 = No Paint Selection Available

DIGIT 14: OPEN DIGIT = 0


DIGIT 15: SUPPLY-AIR
ARRANGEMENT
0 = No Supply Air Arrangement
16

DIGITS 28: OUTSIDE AIR


0 = No Outside Air Option Available

WSHP-PRC009-EN

General
Data
Table G1: General data about the units
Model
Unit Size

Width (in)
Width (in) with
water connections
Height (in)
Depth (in)

Compressor Type
Approximate Weight
Approximate Weight
Water in/out size (NPTI)

with Pallet (lb)


without Pallet (lb)
inches

WPWD 024
23"
24 13/16"

WPWD 036
23"
24 13/16"

WPWD 042
23"
24 13/16"

WPWD 048
23"
24 13/16"

24 5/16"
23 5/16"
Scroll
163
153
1

24 5/16"
23 5/16"
Scroll
183
173
1

24 5/16"
23 5/16"
Scroll
203
193
1

24 5/16"
23 5/16"
Scroll
214
204
1

WPWD 060
23"
24 13/16"

WPWD 072
23"
24 13/16"

EXWA 240
81 5/8"
81 5/8"

24 5/16"
23 5/16"
Scroll
244
234
1

24 5/16"
23 5/16"
Scroll
277
267
1

30"
31 1/2"
Scroll
1222
1156
2

Table G1: General data about the units (continued)


Model
Unit Size

Compressor Type
Approximate Weight
Approximate Weight
Water in/out sizes (FPT)

WSHP-PRC009-EN

Width (in)
Width (in) with
water connections
Height (in)
Depth (in)
with Pallet (lb)
without Pallet (lb)
inches

17

Performance Data
WPWD 024-Cooling
Table P-1: 024 Cooling Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Cool
EWT EWT GPM WPD LWT Cap
Ft
Mbtuh
Head
50.0 45.0
3.8
1.6
61.6 18.9
50.0 45.0
7.0
5.5
56.3 19.2
50.0 45.0
8.9
8.9
55.0 19.3
50.0 53.6
3.8
1.6
62.7 20.8
50.0 53.6
7.0
5.5
56.9 21.0
50.0 53.6
8.9
8.9
55.4 21.2
50.0 65.0
3.8
1.6
63.9 23.2
50.0 65.0
7.0
5.5
57.6 23.5
50.0 65.0
8.9
8.9
56.0 23.6
50.0 75.0
3.8
1.6
65.1 25.3
50.0 75.0
7.0
5.5
58.2 25.6
50.0 75.0
8.9
8.9
56.5 25.8
60.0 45.0
3.8
1.5
71.4 18.0
60.0 45.0
7.0
5.1
66.2 18.2
60.0 45.0
8.9
8.3
64.9 18.3
60.0 53.6
3.8
1.5
72.4 19.8
60.0 53.6
7.0
5.1
66.7 20.1
60.0 53.6
8.9
8.3
65.3 20.2
60.0 65.0
3.8
1.5
73.7 22.3
60.0 65.0
7.0
5.1
67.4 22.5
60.0 65.0
8.9
8.3
65.9 22.7
60.0 75.0
3.8
1.5
74.9 24.4
60.0 75.0
7.0
5.1
68.1 24.7
60.0 75.0
8.9
8.3
66.4 24.9
70.0 45.0
3.8
1.4
81.3 17.4
70.0 45.0
7.0
4.8
76.1 17.6
70.0 45.0
8.9
7.7
74.8 17.7
70.0 53.6
3.8
1.4
82.3 19.2
70.0 53.6
7.0
4.8
76.7 19.4
70.0 53.6
8.9
7.7
75.3 19.6
70.0 65.0
3.8
1.4
83.6 21.6
70.0 65.0
7.0
4.8
77.4 21.9
70.0 65.0
8.9
7.7
75.8 22.0
70.0 75.0
3.8
1.4
84.8 23.8
70.0 75.0
7.0
4.8
78.0 24.1
70.0 75.0
8.9
7.7
76.3 24.2
80.0 45.0
3.8
1.3
91.3 16.9
80.0 45.0
7.0
4.5
86.1 17.1
80.0 45.0
8.9
7.2
84.8 17.2
80.0 53.6
3.8
1.3
92.4 18.7
80.0 53.6
7.0
4.5
86.7 19.0
80.0 53.6
8.9
7.2
85.3 19.1
80.0 65.0
3.8
1.3
93.7 21.2
80.0 65.0
7.0
4.5
87.4 21.4
80.0 65.0
8.9
7.2
85.9 21.6
80.0 75.0
3.8
1.3
94.8 23.3
80.0 75.0
7.0
4.5
88.1 23.6
80.0 75.0
8.9
7.2
86.4 23.8

18

3.8 GPM
Power Heat EER
kW
Of
Reject
0.94
0.88
0.86
0.96
0.89
0.87
0.97
0.91
0.89
0.99
0.92
0.90
1.06
0.99
0.97
1.07
1.00
0.98
1.09
1.02
1.00
1.10
1.03
1.01
1.20
1.12
1.10
1.21
1.13
1.11
1.23
1.15
1.13
1.25
1.16
1.14
1.36
1.27
1.25
1.38
1.29
1.26
1.40
1.30
1.28
1.41
1.32
1.29

22.1
22.2
22.2
24.1
24.0
24.2
26.5
26.6
26.6
28.7
28.7
28.9
21.6
21.6
21.6
23.5
23.5
23.5
26.0
26.0
26.1
28.2
28.2
28.4
21.5
21.4
21.5
23.3
23.3
23.4
25.8
25.8
25.9
28.1
28.1
28.1
21.5
21.4
21.5
23.4
23.4
23.4
26.0
25.8
26.0
28.1
28.1
28.2

20.1
21.8
22.4
21.7
23.6
24.4
23.9
25.8
26.5
25.6
27.8
28.7
17.0
18.4
18.9
18.5
20.1
20.6
20.5
22.1
22.7
22.2
24.0
24.7
14.5
15.7
16.1
15.9
17.2
17.7
17.6
19.0
19.5
19.0
20.8
21.2
12.4
13.5
13.8
13.6
14.7
15.2
15.1
16.5
16.9
16.5
17.9
18.4

Load
Load Load Source Cool
LWT WPD LWT Cap
Ft
Mbtuh
Head
35.1
1.7
62.7 20.8
34.9
1.7
56.9 21.1
34.8
1.7
55.4 21.2
42.7
1.6
63.8 22.9
42.5
1.6
57.5 23.1
42.4
1.6
55.9 23.3
52.8
1.5
65.2 25.5
52.6
1.5
58.3 25.8
52.6
1.5
56.5 26.0
61.7
1.4
66.5 27.9
61.5
1.4
59.0 28.2
61.4
1.4
57.1 28.4
35.5
1.7
72.4 19.8
35.4
1.7
66.7 20.0
35.4
1.7
65.3 20.2
43.2
1.6
73.4 21.8
43
1.6
67.3 22.1
43
1.6
65.8 22.2
53.3
1.5
74.9 24.5
53.1
1.5
68.1 24.8
53
1.5
66.4 25.0
62.1
1.4
76.2 26.9
62
1.4
68.8 27.2
61.9
1.4
66.9 27.4
35.8
1.7
82.3 19.1
35.7
1.7
76.6 19.3
35.7
1.7
75.2 19.5
43.5
1.6
83.3 21.1
43.4
1.6
77.3 21.4
43.3
1.6
75.7 21.5
53.6
1.5
84.8 23.8
53.5
1.5
78.0 24.1
53.4
1.5
76.3 24.3
62.4
1.4
86.1 26.2
62.3
1.4
78.8 26.5
62.2
1.4
76.9 26.7
36.1
1.7
92.3 18.6
36
1.7
86.6 18.8
35.9
1.7
85.3 19.0
43.8
1.6
93.4 20.6
43.6
1.6
87.3 20.9
43.5
1.6
85.7 21.0
53.8
1.5
94.9 23.3
53.7
1.5
88.1 23.6
53.6
1.5
86.4 23.8
62.7
1.4
96.2 25.7
62.6
1.4
88.8 26.0
62.4
1.4
86.9 26.2

7.0 GPM
Power Heat EER
kW
Of
Reject
0.96
0.89
0.88
0.97
0.91
0.89
0.99
0.93
0.91
1.01
0.94
0.92
1.08
1.00
0.99
1.09
1.02
1.00
1.11
1.04
1.02
1.13
1.05
1.03
1.22
1.14
1.12
1.24
1.16
1.13
1.26
1.17
1.15
1.27
1.19
1.16
1.39
1.30
1.27
1.41
1.31
1.29
1.43
1.33
1.31
1.44
1.34
1.32

24.1
24.1
24.2
26.2
26.2
26.3
28.9
29.0
29.1
31.4
31.4
31.5
23.5
23.4
23.6
25.5
25.6
25.6
28.3
28.4
28.5
30.8
30.8
30.9
23.3
23.2
23.3
25.3
25.4
25.4
28.1
28.1
28.2
30.5
30.6
30.7
23.3
23.2
23.3
25.4
25.4
25.4
28.2
28.1
28.3
30.6
30.6
30.7

21.7
23.7
24.1
23.6
25.4
26.2
25.8
27.7
28.6
27.6
30.0
30.9
18.3
20.0
20.4
20.0
21.7
22.2
22.1
23.8
24.5
23.8
25.9
26.6
15.7
16.9
17.4
17.0
18.4
19.0
18.9
20.6
21.1
20.6
22.3
23.0
13.4
14.5
15.0
14.6
16.0
16.3
16.3
17.7
18.2
17.8
19.4
19.8

Load
Load Load Source Cool
LWT WPD LWT Cap
Ft
Mbtuh
Head
39.1
5.7
63.1 21.6
39.0
5.7
57.1 21.8
38.9
5.7
55.6 22.0
47.1
5.4
64.2 23.7
47.0
5.4
57.7 23.9
46.9
5.4
56.1 24.1
57.7
5.0
65.7 26.4
57.6
5.0
58.5 26.7
57.6
5.0
56.7 26.9
67.0
4.6
67.1 28.9
66.9
4.6
59.3 29.2
66.9
4.6
57.3 29.4
39.3
5.7
72.7 20.5
39.3
5.7
66.9 20.7
39.2
5.7
65.5 20.9
47.4
5.4
73.9 22.6
47.3
5.4
67.5 22.9
47.3
5.4
66.0 23.0
58.0
5.0
75.4 25.4
57.9
5.0
68.4 25.7
57.8
5.0
66.6 25.8
67.3
4.6
76.7 27.8
67.2
4.6
69.1 28.1
67.2
4.6
67.2 28.3
39.5
5.7
82.7 19.8
39.5
5.7
76.8 20.0
39.4
5.7
75.4 20.2
47.6
5.4
83.8 21.9
47.5
5.4
77.5 22.1
47.5
5.4
75.9 22.3
58.2
5.0
85.3 24.7
58.1
5.0
78.3 24.9
58.0
5.0
76.5 25.1
67.5
4.6
86.6 27.1
67.4
4.6
79.0 27.4
67.4
4.6
77.1 27.6
39.7
5.7
92.7 19.3
39.6
5.7
86.8 19.5
39.6
5.7
85.4 19.6
47.7
5.4
93.8 21.4
47.6
5.4
87.5 21.6
47.6
5.4
85.9 21.8
58.3
5.0
95.3 24.1
58.2
5.0
88.3 24.4
58.2
5.0
86.6 24.6
67.6
4.6
96.6 26.6
67.6
4.6
89.0 26.9
67.5
4.6
87.1 27.1

8.9 GPM
Power Heat EER
kW
Of
Reject
0.96
0.90
0.88
0.98
0.91
0.90
1.00
0.93
0.91
1.01
0.94
0.92
1.08
1.01
0.99
1.10
1.02
1.01
1.12
1.04
1.02
1.13
1.05
1.03
1.23
1.14
1.12
1.24
1.16
1.14
1.26
1.18
1.15
1.27
1.19
1.17
1.39
1.30
1.28
1.41
1.32
1.29
1.43
1.33
1.31
1.44
1.35
1.32

24.9
24.9
25.0
27.0
27.0
27.2
29.8
29.9
30.0
32.4
32.4
32.5
24.2
24.2
24.3
26.4
26.4
26.5
29.2
29.3
29.3
31.7
31.7
31.8
24.0
23.9
24.0
26.1
26.1
26.2
29.0
28.9
29.0
31.4
31.5
31.6
24.0
23.9
24.0
26.2
26.1
26.2
29.0
28.9
29.1
31.5
31.5
31.6

22.5
24.2
25.0
24.2
26.3
26.8
26.4
28.7
29.6
28.6
31.1
32.0
19.0
20.5
21.1
20.5
22.5
22.8
22.7
24.7
25.3
24.6
26.8
27.5
16.1
17.5
18.0
17.7
19.1
19.6
19.6
21.1
21.8
21.3
23.0
23.6
13.9
15.0
15.3
15.2
16.4
16.9
16.9
18.3
18.8
18.5
19.9
20.5

Load Load
LWT WPD
Ft
Head
40.1
9.2
40.1
9.2
40.1
9.2
48.3
8.7
48.2
8.7
48.2
8.7
59.1
8.0
59.0
8.0
58.9
8.0
68.5
7.5
68.4
7.5
68.4
7.5
40.4
9.2
40.3
9.2
40.3
9.2
48.5
8.7
48.5
8.7
48.4
8.7
59.3
8.0
59.2
8.0
59.2
8.0
68.7
7.5
68.7
7.5
68.6
7.5
40.6
9.2
40.5
9.2
40.5
9.2
48.7
8.7
48.6
8.7
48.6
8.7
59.4
8.0
59.4
8.0
59.4
8.0
68.9
7.5
68.8
7.5
68.8
7.5
40.7
9.2
40.6
9.2
40.6
9.2
48.8
8.7
48.7
8.7
48.7
8.7
59.6
8.0
59.5
8.0
59.5
8.0
69.0
7.5
68.9
7.5
68.9
7.5

WSHP-PRC009-EN

Performance Data
WPWD 024-Cooling
Table P-2: 024 Cooling Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Data shown in SHADED type is performance and multipliers at ARI/ISO 13256-2 WLHP conditions. Antifreeze correction factors may be
found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
90.0 45.0
3.8
1.2
90.0 45.0
7.0
4.2
90.0 45.0
8.9
6.7
90.0 53.6
3.8
1.2
90.0 53.6
7.0
4.2
90.0 53.6
8.9
6.7
90.0 65.0
3.8
1.2
90.0 65.0
7.0
4.2
90.0 65.0
8.9
6.7
90.0 75.0
3.8
1.2
90.0 75.0
7.0
4.2
90.0 75.0
8.9
6.7
100.0 45.0
3.8
1.2
100.0 45.0
7.0
3.9
100.0 45.0
8.9
6.3
100.0 53.6
3.8
1.2
100.0 53.6
7.0
3.9
100.0 53.6
8.9
6.3
100.0 65.0
3.8
1.2
100.0 65.0
7.0
3.9
100.0 65.0
8.9
6.3
100.0 75.0
3.8
1.2
100.0 75.0
7.0
3.9
100.0 75.0
8.9
6.3
110.0 45.0
3.8
1.1
110.0 45.0
7.0
3.6
110.0 45.0
8.9
5.9
110.0 53.6
3.8
1.1
110.0 53.6
7.0
3.6
110.0 53.6
8.9
5.9
110.0 65.0
3.8
1.1
110.0 65.0
7.0
3.6
110.0 65.0
8.9
5.9
110.0 75.0
3.8
1.1
110.0 75.0
7.0
3.6
110.0 75.0
8.9
5.9
120.0 45.0
3.8
1.0
120.0 45.0
7.0
3.4
120.0 45.0
8.9
5.5
120.0 53.6
3.8
1.0
120.0 53.6
7.0
3.4
120.0 53.6
8.9
5.5
120.0 65.0
3.8
1.0
120.0 65.0
7.0
3.4
120.0 65.0
8.9
5.5
120.0 75.0
3.8
1.0
120.0 75.0
7.0
3.4
120.0 75.0
8.9
5.5

WSHP-PRC009-EN

Load 3.8 GPM


Source Cool Power Heat EER
LWT Cap
kW
Of
Mbtuh
Reject
101.6
96.3
94.9
102.6
96.8
95.4
103.9
97.5
95.9
105.1
98.1
96.4
111.8
106.4
105.0
112.8
106.9
105.5
114.1
107.6
106.0
115.3
108.3
106.5
122.2
116.5
115.1
123.2
117.1
115.6
124.6
117.8
116.2
125.7
118.5
116.6
132.6
126.7
125.3
133.6
127.3
125.7
135.0
128.0
126.3
136.1
128.7
126.8

16.6
16.8
16.9
18.4
18.6
18.8
20.8
21.1
21.2
23.0
23.2
23.4
16.3
16.5
16.6
18.1
18.4
18.5
20.6
20.8
21.0
22.7
23.0
23.1
16.1
16.3
16.4
17.9
18.1
18.3
20.4
20.6
20.8
22.5
22.8
22.9
15.9
16.1
16.2
17.8
18.0
18.1
20.2
20.4
20.6
22.3
22.6
22.8

1.55
1.45
1.42
1.57
1.47
1.44
1.59
1.48
1.45
1.60
1.49
1.47
1.77
1.65
1.62
1.78
1.67
1.63
1.80
1.68
1.65
1.82
1.69
1.66
2.01
1.87
1.84
2.02
1.89
1.85
2.04
1.90
1.87
2.05
1.92
1.88
2.27
2.12
2.08
2.29
2.13
2.09
2.30
2.15
2.11
2.32
2.16
2.12

21.9
21.8
21.8
23.8
23.6
23.7
26.2
26.2
26.2
28.5
28.3
28.4
22.3
22.1
22.1
24.2
24.1
24.1
26.7
26.5
26.6
28.9
28.8
28.8
23.0
22.7
22.7
24.8
24.6
24.6
27.4
27.1
27.2
29.5
29.4
29.3
23.7
23.3
23.3
25.6
25.3
25.2
28.1
27.7
27.8
30.2
30.0
30.0

10.7
11.6
11.9
11.7
12.7
13.1
13.1
14.3
14.6
14.4
15.6
15.9
9.2
10.0
10.2
10.2
11.0
11.3
11.4
12.4
12.7
12.5
13.6
13.9
8.0
8.7
8.9
8.9
9.6
9.9
10.0
10.8
11.1
11.0
11.9
12.2
7.0
7.6
7.8
7.8
8.5
8.7
8.8
9.5
9.8
9.6
10.5
10.8

Load Load
LWT WPD
Ft
Head
36.3
1.7
36.2
1.7
36.1
1.7
43.9
1.6
43.8
1.6
43.7
1.6
54
1.5
53.9
1.5
53.8
1.5
62.9
1.4
62.8
1.4
62.7
1.4
36.4
1.7
36.3
1.7
36.3
1.7
44.1
1.6
43.9
1.6
43.9
1.6
54.1
1.5
54
1.5
53.9
1.5
63
1.4
62.9
1.4
62.8
1.4
36.5
1.7
36.4
1.7
36.4
1.7
44.2
1.6
44.1
1.6
44
1.6
54.3
1.5
54.1
1.5
54
1.5
63.1
1.4
63
1.4
62.9
1.4
36.6
1.7
36.5
1.7
36.5
1.7
44.2
1.6
44.1
1.6
44.1
1.6
54.4
1.5
54.3
1.5
54.1
1.5
63.2
1.4
63.1
1.4
63
1.4

Load 7.0 GPM


Source Cool Power Heat EER
LWT Cap
kW
Of
Mbtuh
Reject
102.5
96.8
95.3
103.6
97.3
95.8
105.0
98.2
96.4
106.3
98.8
97.0
112.8
106.9
105.4
113.9
107.5
105.9
115.4
108.3
106.5
116.6
109.0
107.1
123.1
117.0
115.6
124.2
117.7
116.0
125.7
118.4
116.6
126.9
119.2
117.2
133.5
127.3
125.7
134.7
127.9
126.2
136.1
128.7
126.8
137.4
129.4
127.4

18.2
18.5
18.6
20.3
20.5
20.6
22.9
23.2
23.4
25.3
25.6
25.8
18.0
18.2
18.3
20.0
20.2
20.4
22.7
22.9
23.1
25.0
25.3
25.5
17.7
17.9
18.1
19.7
20.0
20.1
22.4
22.7
22.8
24.8
25.1
25.2
17.5
17.7
17.9
19.6
19.8
19.9
22.2
22.5
22.7
24.6
24.9
25.0

1.58
1.48
1.45
1.60
1.49
1.47
1.62
1.51
1.48
1.63
1.52
1.50
1.80
1.68
1.65
1.82
1.70
1.67
1.84
1.72
1.68
1.85
1.73
1.70
2.05
1.91
1.87
2.06
1.92
1.89
2.08
1.94
1.91
2.09
1.96
1.92
2.31
2.16
2.12
2.33
2.17
2.13
2.35
2.19
2.15
2.36
2.20
2.16

23.6
23.6
23.6
25.8
25.6
25.6
28.4
28.4
28.5
30.9
30.8
30.9
24.1
23.9
23.9
26.2
26.0
26.1
29.0
28.8
28.8
31.3
31.2
31.3
24.7
24.4
24.5
26.7
26.6
26.6
29.5
29.3
29.3
31.9
31.8
31.8
25.4
25.1
25.1
27.6
27.2
27.2
30.2
30.0
30.0
32.7
32.4
32.4

11.5
12.5
12.8
12.7
13.8
14.0
14.1
15.4
15.8
15.5
16.8
17.2
10.0
10.8
11.1
11.0
11.9
12.2
12.3
13.3
13.8
13.5
14.6
15.0
8.6
9.4
9.7
9.6
10.4
10.6
10.8
11.7
11.9
11.9
12.8
13.1
7.6
8.2
8.4
8.4
9.1
9.3
9.4
10.3
10.6
10.4
11.3
11.6

Load Load
LWT WPD
Ft
Head
39.8
5.7
39.7
5.7
39.7
5.7
47.8
5.4
47.7
5.4
47.7
5.4
58.4
5.0
58.4
5.0
58.3
5.0
67.8
4.6
67.7
4.6
67.6
4.6
39.9
5.7
39.8
5.7
39.8
5.7
47.9
5.4
47.8
5.4
47.8
5.4
58.5
5.0
58.4
5.0
58.4
5.0
67.8
4.6
67.8
4.6
67.7
4.6
39.9
5.7
39.9
5.7
39.8
5.7
48.0
5.4
47.9
5.4
47.9
5.4
58.6
5.0
58.5
5.0
58.5
5.0
67.9
4.6
67.8
4.6
67.8
4.6
40.0
5.7
39.9
5.7
39.9
5.7
48.0
5.4
47.9
5.4
47.9
5.4
58.7
5.0
58.6
5.0
58.5
5.0
68.0
4.6
67.9
4.6
67.8
4.6

Load 8.9 GPM


Source Cool Power Heat EER
LWT Cap
kW
Of
Mbtuh
Reject
102.8
96.9
95.5
104.0
97.5
96.0
105.4
98.4
96.6
106.8
99.1
97.2
113.1
107.1
105.6
114.3
107.7
106.1
115.7
108.5
106.7
117.1
109.2
107.3
123.4
117.3
115.7
124.6
117.9
116.2
126.1
118.7
116.8
127.4
119.4
117.4
133.8
127.5
125.9
135.0
128.1
126.3
136.6
128.9
127.0
137.8
129.6
127.6

18.9
19.1
19.2
21.0
21.2
21.4
23.7
24.0
24.2
26.2
26.5
26.7
18.6
18.8
18.9
20.7
20.9
21.1
23.4
23.7
23.9
25.9
26.2
26.4
18.3
18.6
18.7
20.4
20.7
20.8
23.2
23.5
23.6
25.6
25.9
26.1
18.1
18.4
18.5
20.2
20.5
20.6
23.0
23.3
23.4
25.4
25.7
25.9

1.59
1.48
1.46
1.61
1.50
1.47
1.62
1.52
1.49
1.64
1.53
1.50
1.81
1.69
1.66
1.83
1.70
1.67
1.84
1.72
1.69
1.86
1.73
1.70
2.05
1.92
1.88
2.07
1.93
1.90
2.09
1.95
1.91
2.10
1.96
1.93
2.32
2.17
2.13
2.34
2.18
2.14
2.36
2.20
2.16
2.37
2.21
2.17

24.3
24.2
24.2
26.5
26.3
26.4
29.2
29.2
29.3
31.8
31.7
31.8
24.8
24.6
24.6
27.0
26.7
26.8
29.7
29.6
29.7
32.3
32.1
32.2
25.3
25.2
25.1
27.5
27.3
27.3
30.3
30.2
30.1
32.8
32.6
32.7
26.0
25.8
25.8
28.2
27.9
27.9
31.1
30.8
30.8
33.5
33.2
33.3

11.9
12.9
13.2
13.0
14.1
14.6
14.6
15.8
16.2
16.0
17.3
17.8
10.3
11.1
11.4
11.3
12.3
12.6
12.7
13.8
14.1
13.9
15.1
15.5
8.9
9.7
9.9
9.9
10.7
10.9
11.1
12.1
12.4
12.2
13.2
13.5
7.8
8.5
8.7
8.6
9.4
9.6
9.7
10.6
10.8
10.7
11.6
11.9

Load Load
LWT WPD
Ft
Head
40.8
9.2
40.7
9.2
40.7
9.2
48.9
8.7
48.8
8.7
48.8
8.7
59.7
8.0
59.6
8.0
59.6
8.0
69.1
7.5
69.0
7.5
69.0
7.5
40.8
9.2
40.8
9.2
40.8
9.2
48.9
8.7
48.9
8.7
48.9
8.7
59.7
8.0
59.7
8.0
59.6
8.0
69.2
7.5
69.1
7.5
69.1
7.5
40.9
9.2
40.8
9.2
40.8
9.2
49.0
8.7
48.9
8.7
48.9
8.7
59.8
8.0
59.7
8.0
59.7
8.0
69.2
7.5
69.2
7.5
69.1
7.5
40.9
9.2
40.9
9.2
40.8
9.2
49.1
8.7
49.0
8.7
49.0
8.7
59.8
8.0
59.8
8.0
59.7
8.0
69.3
7.5
69.2
7.5
69.2
7.5

19

Performance Data
WPWD 024-Heating
Table P-2: 024 Heating Performance
Performance data is tabulated under ARI/ISO 13256-2.
Data shown in SHADED type is performance and multipliers at ARI/ISO 13256-2 WLHP conditions. Antifreeze correction factors may be
found on page 47.
Load
Source Load Source Source Source Heat
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
30.0 60.0
3.8
1.9
20.3 22.3
30.0 60.0
7.0
6.3
24.1 24.5
30.0 60.0
8.9
10.2
25.3 24.8
30.0 80.0
3.8
1.9
21.7 21.3
30.0 80.0
7.0
6.3
24.9 23.3
30.0 80.0
8.9
10.2
25.9 23.7
30.0 100.0
3.8
1.9
23.0 20.6
30.0 100.0
7.0
6.3
25.6 22.5
30.0 100.0
8.9
10.2
26.5 22.8
30.0 120.0
3.8
1.9
24.3 19.9
30.0 120.0
7.0
6.3
26.3 21.8
30.0 120.0
8.9
10.2
27.1 22.2
40.0 60.0
3.8
1.7
29.4 24.1
40.0 60.0
7.0
5.9
33.6 26.4
40.0 60.0
8.9
9.5
34.9 26.8
40.0 80.0
3.8
1.7
30.9 23.0
40.0 80.0
7.0
5.9
34.4 25.2
40.0 80.0
8.9
9.5
35.6 25.6
40.0 100.0
3.8
1.7
32.2 22.2
40.0 100.0
7.0
5.9
35.2 24.3
40.0 100.0
8.9
9.5
36.1 24.7
40.0 120.0
3.8
1.7
33.5 21.6
40.0 120.0
7.0
5.9
35.9 23.6
40.0 120.0
8.9
9.5
36.7 23.9
50.0 60.0
3.8
1.6
38.5 26.0
50.0 60.0
7.0
5.5
43.0 28.5
50.0 60.0
8.9
8.9
44.4 28.9
50.0 80.0
3.8
1.6
40.0 24.8
50.0 80.0
7.0
5.5
43.9 27.2
50.0 80.0
8.9
8.9
45.1 27.6
50.0 100.0
3.8
1.6
41.4 24.0
50.0 100.0
7.0
5.5
44.7 26.3
50.0 100.0
8.9
8.9
45.8 26.6
50.0 120.0
3.8
1.6
42.7 23.3
50.0 120.0
7.0
5.5
45.4 25.5
50.0 120.0
8.9
8.9
46.3 25.9
60.0 60.0
3.8
1.5
47.4 28.1
60.0 60.0
7.0
5.1
52.4 30.8
60.0 60.0
8.9
8.3
53.9 31.2
60.0 80.0
3.8
1.5
49.0 26.8
60.0 80.0
7.0
5.1
53.3 29.4
60.0 80.0
8.9
8.3
54.6 29.8
60.0 100.0
3.8
1.5
50.4 25.9
60.0 100.0
7.0
5.1
54.1 28.4
60.0 100.0
8.9
8.3
55.3 28.8
60.0 120.0
3.8
1.5
51.9 25.1
60.0 120.0
7.0
5.1
54.9 27.5
60.0 120.0
8.9
8.3
55.9 27.9

20

3.8
GPM
Load 7.0
Power Heat COP Load Load Sourc Heat Power
kW
Of
LWT WPD
e
Cap
kW
Absorb
Ft
LWT Mbtuh
Head
1.14
18.4
5.7 71.7
1.5
20.1 22.3 1.04
1.15
20.6
6.2 72.9
1.5
24.0 24.5 1.05
1.16
20.8
6.3 73.1
1.5
25.2 24.8 1.06
1.61
15.8
3.9 91.2
1.3
21.4 21.3 1.47
1.62
17.8
4.2 92.3
1.3
24.8 23.3 1.48
1.64
18.1
4.2 92.5
1.3
25.8 23.7 1.49
2.11
13.4
2.9 110.9 1.2
22.6 20.6 1.93
2.12
15.3
3.1 111.9 1.2
25.5 22.5 1.94
2.14
15.5
3.1 112.1 1.2
26.4 22.8 1.96
2.63
10.9
2.2 130.6 1.0
23.8 19.9 2.40
2.64
12.8
2.4 131.6 1.0
26.1 21.8 2.41
2.67
13.1
2.4 131.8 1.0
26.9 22.2 2.44
1.18
20.1
6.0 72.7
1.5
29.2 24.1 1.07
1.18
22.4
6.6 73.9
1.5
33.5 26.4 1.08
1.19
22.7
6.6 74.1
1.5
34.8 26.8 1.09
1.66
17.3
4.1 92.1
1.3
30.6 23.0 1.52
1.67
19.5
4.4 93.3
1.3
34.3 25.2 1.53
1.69
19.8
4.4 93.5
1.3
35.4 25.6 1.54
2.18
14.8
3.0 111.8 1.2
31.9 22.2 1.99
2.19
16.8
3.3 112.9 1.2
35.0 24.3 2.00
2.21
17.2
3.3 113.1 1.2
36.0 24.7 2.01
2.71
12.4
2.3 131.5 1.0
33.1 21.6 2.47
2.72
14.3
2.5 132.6 1.0
35.7 23.6 2.49
2.75
14.5
2.5 132.7 1.0
36.6 23.9 2.51
1.20
21.9
6.3 73.7
1.5
38.3 26.0 1.10
1.21
24.4
6.9 75.0
1.5
42.9 28.5 1.10
1.22
24.7
6.9 75.2
1.5
44.4 28.9 1.11
1.70
19.0
4.3 93.1
1.3
39.7 24.8 1.55
1.71
21.4
4.7 94.4
1.3
43.7 27.2 1.56
1.73
21.7
4.7 94.6
1.3
45.0 27.6 1.58
2.23
16.4
3.2 112.7 1.2
41.0 24.0 2.03
2.24
18.7
3.4 113.9 1.2
44.5 26.3 2.04
2.26
18.9
3.4 114.1 1.2
45.6 26.6 2.06
2.77
13.9
2.5 132.4 1.0
42.3 23.3 2.53
2.79
16.0
2.7 133.6 1.0
45.2 25.5 2.55
2.81
16.3
2.7 133.8 1.0
46.2 25.9 2.57
1.23
23.9
6.7 74.8
1.5
47.2 28.1 1.12
1.23
26.6
7.3 76.2
1.5
52.3 30.8 1.13
1.24
27.0
7.4 76.4
1.5
53.9 31.2 1.14
1.73
20.9
4.5 94.1
1.3
48.7 26.8 1.58
1.74
23.5
5.0 95.5
1.3
53.1 29.4 1.59
1.76
23.8
5.0 95.7
1.3
54.5 29.8 1.61
2.27
18.2
3.3 113.7 1.2
50.1 25.9 2.07
2.28
20.6
3.6 115.0 1.2
53.9 28.4 2.08
2.30
21.0
3.7 115.3 1.2
55.1 28.8 2.10
2.83
15.4
2.6 133.4 1.0
51.4 25.1 2.58
2.84
17.8
2.8 134.6 1.0
54.7 27.5 2.60
2.87
18.1
2.8 134.9 1.0
55.7 27.9 2.62

GPM
Load
Heat COP Load Load Source Heat
Of
LWT WPD LWT
Cap
Absorb
Ft
Mbtuh
Head
18.8 6.3 66.4
5.1
20.1
22.3
20.9 6.8 67.0
5.1
24.0
24.5
21.2 6.9 67.1
5.1
25.2
24.8
16.3 4.2 86.1
4.5
21.4
21.3
18.3 4.6 86.7
4.5
24.7
23.3
18.6 4.7 86.8
4.5
25.8
23.7
14.0 3.1 105.9 3.9
22.5
20.6
15.9 3.4 106.5 3.9
25.4
22.5
16.1 3.4 106.6 3.9
26.3
22.8
11.7
2.4 125.8 3.4
23.7
19.9
13.6 2.7 126.3 3.4
26.1
21.8
13.9 2.7 126.4 3.4
26.8
22.2
20.5 6.6 66.9
5.1
29.2
24.1
22.7 7.2 67.5
5.1
33.5
26.4
23.1 7.2 67.7
5.1
34.8
26.8
17.8 4.4 86.6
4.5
30.5
23.0
20.0 4.8 87.2
4.5
34.2
25.2
20.3 4.9 87.3
4.5
35.4
25.6
15.4 3.3 106.4 3.9
31.8
22.2
17.5 3.6 107.0 3.9
34.9
24.3
17.8 3.6 107.1 3.9
36.0
24.7
13.2 2.6 126.2 3.4
33.0
21.6
15.1 2.8 126.8 3.4
35.6
23.6
15.3 2.8 126.9 3.4
36.5
23.9
22.3 6.9 67.4
5.1
38.2
26.0
24.8 7.6 68.1
5.1
42.9
28.5
25.1 7.6 68.3
5.1
44.3
28.9
19.5 4.7 87.1
4.5
39.6
24.8
21.9 5.1 87.8
4.5
43.7
27.2
22.2 5.1 87.9
4.5
45.0
27.6
17.1 3.5 106.9 3.9
40.9
24.0
19.3 3.8 107.6 3.9
44.4
26.3
19.6 3.8 107.7 3.9
45.6
26.6
14.7 2.7 126.7 3.4
42.2
23.3
16.8 2.9 127.4 3.4
45.1
25.5
17.1 3.0 127.5 3.4
46.1
25.9
24.3 7.4 68.0
5.1
47.1
28.1
26.9 8.0 68.8
5.1
52.3
30.8
27.3 8.0 68.9
5.1
53.8
31.2
21.4 5.0 87.7
4.5
48.7
26.8
24.0 5.4 88.4
4.5
53.1
29.4
24.3 5.4 88.5
4.5
54.5
29.8
18.8 3.7 107.4 3.9
50.0
25.9
21.3 4.0 108.2 3.9
53.9
28.4
21.6 4.0 108.3 3.9
55.1
28.8
16.3 2.9 127.3 3.4
51.3
25.1
18.6 3.1 127.9 3.4
54.6
27.5
19.0 3.1 128.1 3.4
55.7
27.9

8.9
GPM
Power Heat COP Load Load
kW
Of
LWT WPD
Absorb
Ft
Head
1.01 18.9 6.5 65.0
8.3
1.02 21.0 7.0 65.5
8.3
1.02 21.3 7.1 65.6
8.3
1.43 16.4 4.4 84.8
7.2
1.44 18.4 4.7 85.3
7.2
1.45 18.8 4.8 85.3
7.2
1.87 14.2 3.2 104.7 6.3
1.88 16.1 3.5 105.1 6.3
1.90 16.3 3.5 105.2 6.3
2.33 12.0 2.5 124.5 5.5
2.34 13.8 2.7 125.0 5.5
2.36 14.2 2.8 125.0 5.5
1.04 20.6 6.8 65.4
8.3
1.05 22.8 7.4 65.9
8.3
1.06 23.2 7.4 66.0
8.3
1.47 18.0 4.6 85.2
7.2
1.48 20.2 5.0 85.7
7.2
1.49 20.5 5.0 85.8
7.2
1.93 15.6 3.4 105.0 6.3
1.94 17.7 3.7 105.5 6.3
1.96 18.0 3.7 105.6 6.3
2.40 13.4 2.6 124.9 5.5
2.41 15.4 2.9 125.4 5.5
2.44 15.6 2.9 125.4 5.5
1.07 22.4 7.1 65.8
8.3
1.07 24.9 7.8 66.4
8.3
1.08 25.2 7.8 66.5
8.3
1.51 19.7 4.8 85.6
7.2
1.52 22.0 5.2 86.1
7.2
1.53 22.4 5.3 86.2
7.2
1.97 17.3 3.6 105.4 6.3
1.98 19.5 3.9 105.9 6.3
2.00 19.8 3.9 106.0 6.3
2.46 14.9 2.8 125.3 5.5
2.47 17.1 3.0 125.8 5.5
2.49 17.4 3.0 125.9 5.5
1.09 24.4 7.6 66.3
8.3
1.09 27.1 8.3 66.9
8.3
1.10 27.5 8.3 67.0
8.3
1.54 21.5 5.1 86.0
7.2
1.54 24.1 5.6 86.6
7.2
1.56 24.5 5.6 86.7
7.2
2.01 19.0 3.8 105.9 6.3
2.02 21.5 4.1 106.4 6.3
2.04 21.8 4.1 106.5 6.3
2.51 16.5 2.9 125.7 5.5
2.52 18.9 3.2 126.3 5.5
2.54 19.2 3.2 126.3 5.5

WSHP-PRC009-EN

Performance Data
WPWD 024-Heating
Table P-2: 024 Heating Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load 3.8
Source Load Source Sourc Sourc Heat Power
EWT EWT GPM
e
e
Cap
kW
WPD LWT Mbtuh
Ft
Head
70.0 60.0
3.8
1.4
56.2 30.4 1.25
70.0 60.0
7.0
4.8
61.7 33.3 1.25
70.0 60.0
8.9
7.7
63.4 33.7 1.26
70.0 80.0
3.8
1.4
57.9 29.0 1.76
70.0 80.0
7.0
4.8
62.6 31.7 1.77
70.0 80.0
8.9
7.7
64.1 32.2 1.79
70.0 100.0 3.8
1.4
59.4 28.0 2.31
70.0 100.0 7.0
4.8
63.5 30.6 2.32
70.0 100.0 8.9
7.7
64.8 31.1 2.34
70.0 120.0 3.8
1.4
60.9 27.1 2.87
70.0 120.0 7.0
4.8
64.3 29.7 2.89
70.0 120.0 8.9
7.7
65.4 30.2 2.91
80.0 60.0
3.8
1.3
65.0 32.8 1.26
80.0 60.0
7.0
4.5
70.9 35.9 1.27
80.0 60.0
8.9
7.2
72.8 36.4 1.28
80.0 80.0
3.8
1.3
66.7 31.3 1.79
80.0 80.0
7.0
4.5
71.9 34.3 1.80
80.0 80.0
8.9
7.2
73.6 34.8 1.81
80.0 100.0 3.8
1.3
68.3 30.2 2.34
80.0 100.0 7.0
4.5
72.8 33.1 2.35
80.0 100.0 8.9
7.2
74.3 33.5 2.37
80.0 120.0 3.8
1.3
69.8 29.3 2.91
80.0 120.0 7.0
4.5
73.7 32.1 2.93
80.0 120.0 8.9
7.2
75.0 32.5 2.96

WSHP-PRC009-EN

GPM
Load 7.0
GPM
Load 8.9
GPM
Heat COP Load Load Sourc Heat Power Heat COP Load Load Sourc Heat Power Heat COP Load Load
Of
LWT WPD
e
Cap
kW
Of
LWT WPD
e
Cap
kW
Of
LWT WPD
Absor
Ft
LWT Mbtuh
Absorb
Ft
LWT Mbtuh
Absorb
Ft
b
Head
Head
Head
26.1
29.0
29.4
23.0
25.7
26.1
20.1
22.7
23.1
17.3
19.8
20.3
28.5
31.6
32.0
25.2
28.2
28.6
22.2
25.1
25.4
19.4
22.1
22.4

7.1
7.8
7.8
4.8
5.2
5.3
3.6
3.9
3.9
2.8
3.0
3.0
7.6
8.3
8.3
5.1
5.6
5.6
3.8
4.1
4.1
3.0
3.2
3.2

76.0
77.5
77.7
95.3
96.7
97.0
114.8
116.2
116.5
134.4
135.8
136.1
77.3
78.9
79.2
96.5
98.1
98.4
116.0
117.5
117.7
135.6
137.1
137.3

1.5
1.5
1.5
1.3
1.3
1.3
1.2
1.2
1.2
1.0
1.0
1.0
1.5
1.5
1.5
1.3
1.3
1.3
1.2
1.2
1.2
1.0
1.0
1.0

56.0
61.6
63.3
57.6
62.5
64.0
59.0
63.3
64.6
60.4
64.1
65.3
64.7
70.9
72.7
66.4
71.8
73.4
67.9
72.6
74.1
69.3
73.4
74.7

30.4
33.3
33.7
29.0
31.7
32.2
28.0
30.6
31.1
27.1
29.7
30.2
32.8
35.9
36.4
31.3
34.3
34.8
30.2
33.1
33.5
29.3
32.1
32.5

1.14
1.14
1.15
1.61
1.62
1.63
2.11
2.12
2.14
2.62
2.64
2.66
1.15
1.16
1.17
1.63
1.64
1.66
2.14
2.15
2.17
2.66
2.67
2.70

26.5
29.4
29.8
23.5
26.2
26.6
20.8
23.4
23.8
18.2
20.7
21.1
28.9
31.9
32.4
25.7
28.7
29.1
22.9
25.8
26.1
20.2
23.0
23.3

7.8
8.6
8.6
5.3
5.7
5.8
3.9
4.2
4.3
3.0
3.3
3.3
8.4
9.1
9.1
5.6
6.1
6.1
4.1
4.5
4.5
3.2
3.5
3.5

68.7
69.5
69.6
88.3
89.1
89.2
108.1
108.8
108.9
127.8
128.6
128.7
69.4
70.3
70.4
89.0
89.8
90.0
108.7
109.5
109.6
128.5
129.3
129.4

5.1
5.1
5.1
4.5
4.5
4.5
3.9
3.9
3.9
3.4
3.4
3.4
5.1
5.1
5.1
4.5
4.5
4.5
3.9
3.9
3.9
3.4
3.4
3.4

55.9
61.6
63.3
57.5
62.5
64.0
58.9
63.2
64.6
60.3
64.0
65.2
64.7
70.8
72.7
66.3
71.7
73.4
67.8
72.5
74.1
69.2
73.4
74.7

30.4
33.3
33.7
29.0
31.7
32.2
28.0
30.6
31.1
27.1
29.7
30.2
32.8
35.9
36.4
31.3
34.3
34.8
30.2
33.1
33.5
29.3
32.1
32.5

1.10
1.11
1.12
1.56
1.57
1.58
2.04
2.05
2.07
2.55
2.56
2.58
1.12
1.13
1.14
1.58
1.59
1.61
2.07
2.08
2.10
2.58
2.60
2.62

26.7
29.5
29.9
23.7
26.3
26.8
21.0
23.6
24.0
18.4
21.0
21.4
29.0
32.0
32.5
25.9
28.9
29.3
23.1
26.0
26.3
20.5
23.2
23.6

8.1
8.8
8.8
5.4
5.9
6.0
4.0
4.4
4.4
3.1
3.4
3.4
8.6
9.3
9.4
5.8
6.3
6.3
4.3
4.7
4.7
3.3
3.6
3.6

66.8
67.5
67.6
86.5
87.1
87.3
106.3
106.9
107.0
126.2
126.8
126.9
67.4
68.1
68.2
87.1
87.7
87.8
106.8
107.5
107.6
126.7
127.3
127.4

8.3
8.3
8.3
7.2
7.2
7.2
6.3
6.3
6.3
5.5
5.5
5.5
8.3
8.3
8.3
7.2
7.2
7.2
6.3
6.3
6.3
5.5
5.5
5.5

21

Performance Data
WPWD 036-Cooling
Table P-3: 036 Cooling Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Cool
EWT EWT GPM WPD LWT Cap
Ft
Mbtuh
Head
50.0
45.0
4.6
2.4
63.8 27.5
50.0
45.0
8.5
8.1
57.5 27.9
50.0
45.0 10.8
13.1
55.9 28.0
50.0
53.6
4.6
2.4
65.0 30.2
50.0
53.6
8.5
8.1
58.2 30.6
50.0
53.6 10.8
13.1
56.4 30.8
50.0
65.0
4.6
2.4
66.6 33.7
50.0
65.0
8.5
8.1
59.0 34.1
50.0
65.0 10.8
13.1
57.1 34.4
50.0
75.0
4.6
2.4
68.0 36.8
50.0
75.0
8.5
8.1
59.8 37.3
50.0
75.0 10.8
13.1
57.7 37.5
60.0
45.0
4.6
2.2
73.7 26.5
60.0
45.0
8.5
7.6
67.4 26.9
60.0
45.0 10.8
12.2
65.8 27.0
60.0
53.6
4.6
2.2
74.9 29.2
60.0
53.6
8.5
7.6
68.1 29.6
60.0
53.6 10.8
12.2
66.4 29.8
60.0
65.0
4.6
2.2
76.5 32.8
60.0
65.0
8.5
7.6
68.9 33.1
60.0
65.0 10.8
12.2
67.0 33.4
60.0
75.0
4.6
2.2
77.8 35.9
60.0
75.0
8.5
7.6
69.7 36.3
60.0
75.0 10.8
12.2
67.6 36.5
70.0
45.0
4.6
2.1
83.6 25.6
70.0
45.0
8.5
7.1
77.3 25.9
70.0
45.0 10.8
11.4
75.8 26.1
70.0
53.6
4.6
2.1
84.8 28.3
70.0
53.6
8.5
7.1
78.0 28.6
70.0
53.6 10.8
11.4
76.3 28.8
70.0
65.0
4.6
2.1
86.3 31.8
70.0
65.0
8.5
7.1
78.9 32.2
70.0
65.0 10.8
11.4
77.0 32.4
70.0
75.0
4.6
2.1
87.7 34.9
70.0
75.0
8.5
7.1
79.6 35.3
70.0
75.0 10.8
11.4
77.6 35.6
80.0
45.0
4.6
1.9
93.6 24.7
80.0
45.0
8.5
6.6
87.3 25.0
80.0
45.0 10.8
10.6
85.8 25.2
80.0
53.6
4.6
1.9
94.7 27.4
80.0
53.6
8.5
6.6
88.0 27.7
80.0
53.6 10.8
10.6
86.3 27.9
80.0
65.0
4.6
1.9
96.3 30.9
80.0
65.0
8.5
6.6
88.8 31.3
80.0
65.0 10.8
10.6
87.0 31.5
80.0
75.0
4.6
1.9
97.7 34.0
80.0
75.0
8.5
6.6
89.6 34.4
80.0
75.0 10.8
10.6
87.5 34.6

22

4.6 GPM
Power Heat EER
kW
Of
Reject
1.27
1.19
1.16
1.29
1.20
1.18
1.31
1.22
1.20
1.32
1.23
1.21
1.44
1.35
1.32
1.46
1.36
1.34
1.48
1.38
1.36
1.50
1.40
1.37
1.64
1.53
1.50
1.66
1.55
1.52
1.68
1.57
1.54
1.70
1.59
1.56
1.86
1.73
1.70
1.88
1.76
1.72
1.91
1.78
1.75
1.93
1.80
1.77

31.8
32.0
32.0
34.6
34.7
34.8
38.2
38.3
38.5
41.3
41.5
41.6
31.4
31.5
31.5
34.2
34.2
34.4
37.9
37.8
38.0
41.0
41.1
41.2
31.2
31.1
31.2
34.0
33.9
34.0
37.5
37.6
37.7
40.7
40.7
40.9
31.1
30.9
31.0
33.8
33.7
33.8
37.4
37.4
37.5
40.6
40.5
40.6

21.7
23.4
24.1
23.4
25.5
26.1
25.7
28.0
28.7
27.9
30.3
31.0
18.4
19.9
20.5
20.0
21.8
22.2
22.2
24.0
24.6
23.9
25.9
26.6
15.6
16.9
17.4
17.0
18.5
18.9
18.9
20.5
21.0
20.5
22.2
22.8
13.3
14.5
14.8
14.6
15.7
16.2
16.2
17.6
18.0
17.6
19.1
19.5

Load
Load Load Source Cool
LWT WPD LWT Cap
Ft
Mbtuh
Head
33
2.5
65.1 30.3
32.9
2.5
58.2 30.7
32.8
2.5
56.5 30.9
40.5
2.3
66.4 33.3
40.3
2.3
58.9 33.7
40.2
2.3
57.0 33.9
50.3
2.1
68.1 37.2
50.2
2.1
59.8 37.6
50
2.1
57.8 37.9
59
2.0
69.7 40.6
58.7
2.0
60.7 41.1
58.7
2.0
58.4 41.3
33.5
2.5
74.9 29.2
33.3
2.5
68.1 29.6
33.3
2.5
66.4 29.8
40.9
2.3
76.2 32.2
40.7
2.3
68.8 32.6
40.6
2.3
66.9 32.8
50.7
2.1
78.0 36.1
50.6
2.1
69.7 36.5
50.5
2.1
67.7 36.8
59.4
2.0
79.4 39.5
59.2
2.0
70.6 40.0
59.1
2.0
68.3 40.2
33.9
2.5
84.8 28.2
33.7
2.5
78.0 28.5
33.7
2.5
76.3 28.7
41.3
2.3
86.1 31.1
41.2
2.3
78.7 31.5
41.1
2.3
76.9 31.7
51.2
2.1
87.8 35.0
51
2.1
79.7 35.5
50.9
2.1
77.6 35.7
59.8
2.0
89.3 38.5
59.6
2.0
80.5 38.9
59.5
2.0
78.3 39.2
34.3
2.5
94.7 27.2
34.1
2.5
87.9 27.5
34
2.5
86.2 27.7
41.7
2.3
96.0 30.1
41.6
2.3
88.6 30.5
41.5
2.3
86.8 30.7
51.6
2.1
97.7 34.0
51.4
2.1
89.6 34.4
51.3
2.1
87.6 34.7
60.2
2.0
99.3 37.5
60
2.0
90.4 37.9
59.9
2.0
88.2 38.2

8.5 GPM
Power Heat EER
kW
Of
Reject
1.30
1.21
1.19
1.31
1.23
1.20
1.33
1.24
1.22
1.35
1.26
1.23
1.47
1.37
1.35
1.49
1.39
1.36
1.51
1.41
1.38
1.53
1.43
1.40
1.67
1.56
1.53
1.69
1.58
1.55
1.72
1.60
1.57
1.73
1.62
1.59
1.89
1.77
1.73
1.92
1.79
1.76
1.95
1.82
1.78
1.97
1.83
1.80

34.7
34.8
35.0
37.8
37.9
38.0
41.7
41.8
42.1
45.2
45.4
45.5
34.2
34.3
34.4
37.3
37.3
37.4
41.3
41.3
41.5
44.7
44.9
45.0
33.9
33.8
33.9
36.9
36.9
37.0
40.9
41.0
41.1
44.4
44.4
44.6
33.7
33.5
33.6
36.7
36.6
36.7
40.7
40.6
40.8
44.2
44.2
44.3

23.3
25.4
26.0
25.4
27.4
28.3
28.0
30.3
31.1
30.1
32.6
33.6
19.9
21.6
22.1
21.6
23.5
24.1
23.9
25.9
26.7
25.8
28.0
28.7
16.9
18.3
18.8
18.4
19.9
20.5
20.3
22.2
22.7
22.3
24.0
24.7
14.4
15.5
16.0
15.7
17.0
17.4
17.4
18.9
19.5
19.0
20.7
21.2

Load
Load Load Source Cool
LWT WPD LWT Cap
Ft
Mbtuh
Head
37.9
8.4
65.6 31.4
37.8
8.4
58.4 31.8
37.7
8.4
56.7 32.0
45.8
7.9
66.9 34.4
45.7
7.9
59.2 34.8
45.6
7.9
57.3 35.1
56.2
7.3
68.7 38.5
56.1
7.3
60.2 38.9
56.1
7.3
58.0 39.2
65.4
6.8
70.3 42.0
65.3
6.8
61.0 42.5
65.3
6.8
58.7 42.8
38.1
8.4
75.4 30.3
38.0
8.4
68.3 30.6
38.0
8.4
66.6 30.8
46.0
7.9
76.7 33.3
45.9
7.9
69.1 33.7
45.9
7.9
67.2 33.9
56.5
7.3
78.5 37.3
56.4
7.3
70.1 37.8
56.3
7.3
67.9 38.0
65.7
6.8
80.1 40.9
65.6
6.8
70.9 41.4
65.5
6.8
68.6 41.6
38.4
8.4
85.2 29.2
38.3
8.4
78.2 29.5
38.2
8.4
76.5 29.7
46.3
7.9
86.5 32.2
46.2
7.9
79.0 32.6
46.1
7.9
77.1 32.8
56.8
7.3
88.4 36.3
56.6
7.3
79.9 36.7
56.6
7.3
77.8 36.9
65.9
6.8
89.9 39.8
65.8
6.8
80.8 40.3
65.8
6.8
78.5 40.5
38.6
8.4
95.1 28.1
38.5
8.4
88.1 28.5
38.5
8.4
86.4 28.7
46.5
7.9
96.5 31.2
46.4
7.9
88.9 31.6
46.4
7.9
87.0 31.8
57.0
7.3
98.3 35.2
56.9
7.3
89.9 35.6
56.8
7.3
87.8 35.9
66.2
6.8
99.8 38.8
66.1
6.8
90.7 39.2
66.0
6.8
88.5 39.5

10.8 GPM
Power Heat EER
kW
Of
Reject
1.30
1.21
1.19
1.32
1.23
1.21
1.34
1.25
1.22
1.35
1.26
1.24
1.48
1.38
1.35
1.50
1.40
1.37
1.52
1.42
1.39
1.53
1.43
1.40
1.68
1.56
1.53
1.70
1.58
1.55
1.72
1.61
1.58
1.74
1.62
1.59
1.90
1.77
1.74
1.93
1.80
1.76
1.95
1.82
1.79
1.97
1.84
1.81

35.8
35.9
36.1
38.9
39.0
39.2
43.1
43.2
43.4
46.6
46.8
47.0
35.4
35.3
35.4
38.4
38.5
38.6
42.5
42.7
42.7
46.1
46.3
46.4
34.9
34.8
34.9
38.0
38.0
38.1
42.2
42.2
42.3
45.7
45.8
45.9
34.6
34.5
34.6
37.8
37.7
37.8
41.9
41.8
42.0
45.5
45.5
45.7

24.2
26.3
26.9
26.1
28.3
29.0
28.7
31.1
32.1
31.1
33.7
34.5
20.5
22.2
22.8
22.2
24.1
24.7
24.5
26.6
27.3
26.7
29.0
29.7
17.4
18.9
19.4
18.9
20.6
21.2
21.1
22.8
23.4
22.9
24.9
25.5
14.8
16.1
16.5
16.2
17.6
18.1
18.1
19.6
20.1
19.7
21.3
21.8

Load Load
LWT WPD
Ft
Head
39.2 13.5
39.1 13.5
39.1 13.5
47.2 12.7
47.2 12.7
47.1 12.7
57.9 11.8
57.8 11.8
57.7 11.8
67.2 11.0
67.1 11.0
67.1 11.0
39.4 13.5
39.3 13.5
39.3 13.5
47.4 12.7
47.4 12.7
47.3 12.7
58.1 11.8
58.0 11.8
58.0 11.8
67.4 11.0
67.3 11.0
67.3 11.0
39.6 13.5
39.5 13.5
39.5 13.5
47.6 12.7
47.6 12.7
47.5 12.7
58.3 11.8
58.2 11.8
58.2 11.8
67.6 11.0
67.5 11.0
67.5 11.0
39.8 13.5
39.7 13.5
39.7 13.5
47.8 12.7
47.7 12.7
47.7 12.7
58.5 11.8
58.4 11.8
58.3 11.8
67.8 11.0
67.7 11.0
67.7 11.0

WSHP-PRC009-EN

Performance Data
WPWD 036-Cooling
Table P-3: 036 Cooling Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
90.0
45.0
4.6
1.8
90.0
45.0
8.5
6.2
90.0
45.0 10.8
9.9
90.0
53.6
4.6
1.8
90.0
53.6
8.5
6.2
90.0
53.6 10.8
9.9
90.0
65.0
4.6
1.8
90.0
65.0
8.5
6.2
90.0
65.0 10.8
9.9
90.0
75.0
4.6
1.8
90.0
75.0
8.5
6.2
90.0
75.0 10.8
9.9
100.0 45.0
4.6
1.7
100.0 45.0
8.5
5.7
100.0 45.0 10.8
9.3
100.0 53.6
4.6
1.7
100.0 53.6
8.5
5.7
100.0 53.6 10.8
9.3
100.0 65.0
4.6
1.7
100.0 65.0
8.5
5.7
100.0 65.0 10.8
9.3
100.0 75.0
4.6
1.7
100.0 75.0
8.5
5.7
100.0 75.0 10.8
9.3
110.0 45.0
4.6
1.6
110.0 45.0
8.5
5.4
110.0 45.0 10.8
8.7
110.0 53.6
4.6
1.6
110.0 53.6
8.5
5.4
110.0 53.6 10.8
8.7
110.0 65.0
4.6
1.6
110.0 65.0
8.5
5.4
110.0 65.0 10.8
8.7
110.0 75.0
4.6
1.6
110.0 75.0
8.5
5.4
110.0 75.0 10.8
8.7
120.0 45.0
4.6
1.5
120.0 45.0
8.5
5.0
120.0 45.0 10.8
8.1
120.0 53.6
4.6
1.5
120.0 53.6
8.5
5.0
120.0 53.6 10.8
8.1
120.0 65.0
4.6
1.5
120.0 65.0
8.5
5.0
120.0 65.0 10.8
8.1
120.0 75.0
4.6
1.5
120.0 75.0
8.5
5.0
120.0 75.0 10.8
8.1

WSHP-PRC009-EN

Load 4.6 GPM


Source Cool Power Heat EER
LWT Cap
kW
Of
Mbtuh
Reject
103.5
97.3
95.7
104.8
97.9
96.3
106.3
98.8
97.0
107.7
99.6
97.6
113.7
107.3
105.8
114.9
108.0
106.3
116.5
108.8
107.0
117.9
109.6
107.6
123.8
117.4
115.8
125.0
118.0
116.3
126.6
118.9
117.0
128.0
119.7
117.6
134.1
127.5
125.9
135.3
128.2
126.4
136.9
129.1
127.1
138.3
129.8
127.7

23.8
24.1
24.3
26.5
26.8
27.0
30.0
30.4
30.6
33.1
33.5
33.8
23.0
23.3
23.4
25.7
26.0
26.1
29.2
29.5
29.8
32.3
32.7
32.9
22.2
22.5
22.6
24.9
25.2
25.3
28.4
28.7
28.9
31.5
31.9
32.1
21.5
21.7
21.9
24.1
24.4
24.6
27.7
28.0
28.2
30.8
31.1
31.3

2.11
1.97
1.93
2.13
1.99
1.95
2.16
2.02
1.98
2.19
2.04
2.00
2.39
2.23
2.19
2.42
2.26
2.22
2.46
2.29
2.25
2.48
2.32
2.27
2.71
2.53
2.48
2.75
2.56
2.52
2.79
2.60
2.55
2.82
2.63
2.58
3.08
2.87
2.82
3.12
2.91
2.85
3.16
2.95
2.89
3.19
2.98
2.92

31.0
30.8
30.9
33.8
33.6
33.7
37.4
37.3
37.4
40.6
40.5
40.6
31.2
30.9
30.9
34.0
33.7
33.7
37.6
37.3
37.5
40.8
40.6
40.7
31.5
31.1
31.1
34.3
33.9
33.9
37.9
37.6
37.6
41.1
40.9
40.9
32.0
31.5
31.5
34.8
34.3
34.3
38.5
38.1
38.1
41.7
41.3
41.3

11.3
12.2
12.6
12.4
13.5
13.8
13.9
15.0
15.5
15.1
16.4
16.9
9.6
10.4
10.7
10.6
11.5
11.8
11.9
12.9
13.2
13.0
14.1
14.5
8.2
8.9
9.1
9.1
9.8
10.0
10.2
11.0
11.3
11.2
12.1
12.4
7.0
7.6
7.8
7.7
8.4
8.6
8.8
9.5
9.8
9.7
10.4
10.7

Load Load
LWT WPD
Ft
Head
34.7
2.5
34.5
2.5
34.4
2.5
42.1
2.3
41.9
2.3
41.9
2.3
51.9
2.1
51.8
2.1
51.7
2.1
60.6
2.0
60.4
2.0
60.3
2.0
35
2.5
34.9
2.5
34.8
2.5
42.4
2.3
42.3
2.3
42.3
2.3
52.3
2.1
52.2
2.1
52
2.1
60.9
2.0
60.8
2.0
60.7
2.0
35.4
2.5
35.2
2.5
35.2
2.5
42.8
2.3
42.6
2.3
42.6
2.3
52.6
2.1
52.5
2.1
52.4
2.1
61.3
2.0
61.1
2.0
61
2.0
35.7
2.5
35.6
2.5
35.5
2.5
43.1
2.3
43
2.3
42.9
2.3
52.9
2.1
52.8
2.1
52.7
2.1
61.6
2.0
61.4
2.0
61.4
2.0

Load 8.5 GPM


Source Cool Power Heat EER
LWT Cap
kW
Of
Mbtuh
Reject
104.6
97.9
96.2
106.0
98.6
96.8
107.7
99.6
97.6
109.3
100.4
98.2
114.7
107.9
106.2
116.1
108.6
106.8
117.8
109.6
107.6
119.3
110.4
108.2
124.9
118.0
116.3
126.2
118.7
116.9
128.0
119.7
117.6
129.5
120.5
118.3
135.1
128.1
126.4
136.5
128.8
126.9
138.3
129.8
127.7
139.8
130.6
128.4

26.2
26.6
26.7
29.2
29.5
29.7
33.1
33.5
33.7
36.5
36.9
37.2
25.3
25.6
25.8
28.3
28.6
28.8
32.2
32.5
32.8
35.6
36.0
36.3
24.5
24.8
24.9
27.4
27.7
27.9
31.3
31.7
31.9
34.7
35.1
35.4
23.6
23.9
24.1
26.6
26.9
27.1
30.5
30.8
31.0
33.9
34.3
34.5

2.15
2.01
1.97
2.18
2.03
1.99
2.21
2.06
2.02
2.23
2.08
2.04
2.44
2.27
2.23
2.47
2.30
2.26
2.50
2.34
2.29
2.53
2.36
2.32
2.77
2.58
2.53
2.80
2.61
2.57
2.84
2.65
2.60
2.87
2.68
2.63
3.14
2.93
2.87
3.18
2.97
2.91
3.22
3.01
2.95
3.26
3.04
2.98

33.5
33.5
33.4
36.6
36.4
36.5
40.6
40.5
40.6
44.1
44.0
44.2
33.6
33.4
33.4
36.7
36.5
36.5
40.7
40.5
40.6
44.2
44.1
44.2
34.0
33.6
33.5
37.0
36.6
36.7
41.0
40.7
40.8
44.5
44.3
44.4
34.3
33.9
33.9
37.5
37.0
37.0
41.5
41.1
41.1
45.0
44.7
44.7

12.2
13.2
13.6
13.4
14.5
14.9
15.0
16.3
16.7
16.4
17.7
18.2
10.4
11.3
11.6
11.5
12.4
12.7
12.9
13.9
14.3
14.1
15.3
15.6
8.8
9.6
9.8
9.8
10.6
10.9
11.0
12.0
12.3
12.1
13.1
13.5
7.5
8.2
8.4
8.4
9.1
9.3
9.5
10.2
10.5
10.4
11.3
11.6

Load Load
LWT WPD
Ft
Head
38.8
8.4
38.7
8.4
38.7
8.4
46.7
7.9
46.7
7.9
46.6
7.9
57.2
7.3
57.1
7.3
57.1
7.3
66.4
6.8
66.3
6.8
66.2
6.8
39.0
8.4
39.0
8.4
38.9
8.4
46.9
7.9
46.9
7.9
46.8
7.9
57.4
7.3
57.3
7.3
57.3
7.3
66.6
6.8
66.5
6.8
66.4
6.8
39.2
8.4
39.2
8.4
39.1
8.4
47.2
7.9
47.1
7.9
47.0
7.9
57.6
7.3
57.5
7.3
57.5
7.3
66.8
6.8
66.7
6.8
66.7
6.8
39.4
8.4
39.4
8.4
39.3
8.4
47.3
7.9
47.3
7.9
47.2
7.9
57.8
7.3
57.7
7.3
57.7
7.3
67.0
6.8
66.9
6.8
66.9
6.8

Load 10.8 GPM


Source Cool Power Heat EER
LWT Cap
kW
Of
Mbtuh
Reject
105.1
98.1
96.4
106.4
98.9
97.0
108.3
99.9
97.8
109.9
100.7
98.5
115.1
108.1
106.4
116.5
108.9
107.0
118.3
109.9
107.8
119.9
110.8
108.5
125.3
118.2
116.4
126.7
118.9
117.0
128.5
119.9
117.8
130.0
120.8
118.5
135.5
128.3
126.5
136.9
129.0
127.1
138.7
130.0
127.9
140.4
130.9
128.6

27.2
27.5
27.7
30.2
30.6
30.8
34.2
34.6
34.9
37.8
38.2
38.5
26.2
26.5
26.7
29.3
29.6
29.8
33.3
33.7
33.9
36.8
37.3
37.5
25.3
25.6
25.8
28.4
28.7
28.9
32.4
32.8
33.0
35.9
36.4
36.6
24.5
24.7
24.9
27.5
27.8
28.0
31.5
31.9
32.1
35.1
35.5
35.7

2.16
2.01
1.97
2.18
2.04
2.00
2.22
2.07
2.03
2.24
2.09
2.05
2.45
2.28
2.24
2.48
2.31
2.27
2.51
2.34
2.30
2.54
2.37
2.33
2.78
2.59
2.54
2.81
2.62
2.57
2.85
2.66
2.61
2.88
2.69
2.64
3.15
2.94
2.88
3.19
2.98
2.92
3.23
3.02
2.96
3.27
3.05
2.99

34.6
34.4
34.4
37.6
37.6
37.6
41.8
41.7
41.8
45.5
45.3
45.5
34.6
34.3
34.4
37.8
37.5
37.6
41.9
41.7
41.8
45.5
45.4
45.5
34.8
34.4
34.5
38.0
37.6
37.7
42.1
41.9
41.9
45.7
45.6
45.6
35.3
34.7
34.7
38.4
38.0
38.0
42.5
42.2
42.2
46.3
45.9
45.9

12.6
13.7
14.1
13.9
15.0
15.4
15.4
16.7
17.2
16.9
18.3
18.8
10.7
11.6
11.9
11.8
12.8
13.1
13.3
14.4
14.7
14.5
15.7
16.1
9.1
9.9
10.2
10.1
11.0
11.2
11.4
12.3
12.6
12.5
13.5
13.9
7.8
8.4
8.6
8.6
9.3
9.6
9.8
10.6
10.8
10.7
11.6
11.9

Load Load
LWT WPD
Ft
Head
40.0 13.5
39.9 13.5
39.9 13.5
48.0 12.7
47.9 12.7
47.9 12.7
58.7 11.8
58.6 11.8
58.5 11.8
68.0 11.0
67.9 11.0
67.9 11.0
40.1 13.5
40.1 13.5
40.1 13.5
48.2 12.7
48.1 12.7
48.1 12.7
58.8 11.8
58.8 11.8
58.7 11.8
68.2 11.0
68.1 11.0
68.0 11.0
40.3 13.5
40.3 13.5
40.2 13.5
48.3 12.7
48.3 12.7
48.2 12.7
59.0 11.8
58.9 11.8
58.9 11.8
68.3 11.0
68.2 11.0
68.2 11.0
40.5 13.5
40.4 13.5
40.4 13.5
48.5 12.7
48.5 12.7
48.4 12.7
59.2 11.8
59.1 11.8
59.0 11.8
68.5 11.0
68.4 11.0
68.4 11.0

23

Performance Data
WPWD 036-Heating
Table P-4: 036 Heating Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
30.0
60.0
4.6
2.7
30.0
60.0
8.5
9.3
30.0
60.0 10.8
15.0
30.0
80.0
4.6
2.7
30.0
80.0
8.5
9.3
30.0
80.0 10.8
15.0
30.0 100.0 4.6
2.7
30.0 100.0 8.5
9.3
30.0 100.0 10.8
15.0
30.0 120.0 4.6
2.7
30.0 120.0 8.5
9.3
30.0 120.0 10.8
15.0
40.0
60.0
4.6
2.5
40.0
60.0
8.5
8.7
40.0
60.0 10.8
14.0
40.0
80.0
4.6
2.5
40.0
80.0
8.5
8.7
40.0
80.0 10.8
14.0
40.0 100.0 4.6
2.5
40.0 100.0 8.5
8.7
40.0 100.0 10.8
14.0
40.0 120.0 4.6
2.5
40.0 120.0 8.5
8.7
40.0 120.0 10.8
14.0
50.0
60.0
4.6
2.4
50.0
60.0
8.5
8.1
50.0
60.0 10.8
13.1
50.0
80.0
4.6
2.4
50.0
80.0
8.5
8.1
50.0
80.0 10.8
13.1
50.0 100.0 4.6
2.4
50.0 100.0 8.5
8.1
50.0 100.0 10.8
13.1
50.0 120.0 4.6
2.4
50.0 120.0 8.5
8.1
50.0 120.0 10.8
13.1
60.0
60.0
4.6
2.2
60.0
60.0
8.5
7.6
60.0
60.0 10.8
12.2
60.0
80.0
4.6
2.2
60.0
80.0
8.5
7.6
60.0
80.0 10.8
12.2
60.0 100.0 4.6
2.2
60.0 100.0 8.5
7.6
60.0 100.0 10.8
12.2
60.0 120.0 4.6
2.2
60.0 120.0 8.5
7.6
60.0 120.0 10.8
12.2

24

Load 4.6
GPM
Load
Source Heat Power Heat COP Load Load Source Heat
LWT Cap
kW
Of
LWT WPD LWT
Cap
Mbtuh
Absorb
Ft
Mbtuh
Head
20.8 26.5 1.54 21.2 5.0 71.5
2.2
20.6
26.5
24.4 29.1 1.55 23.8 5.5 72.7
2.2
24.3
29.1
25.5 29.5 1.56 24.2 5.5 72.8
2.2
25.4
29.5
22.1 25.3 2.11 18.1 3.5 91.0
1.9
21.9
25.3
25.2 27.7 2.12 20.5 3.8 92.1
1.9
25.0
27.7
26.1 28.1 2.14 20.8 3.8 92.3
1.9
26.0
28.1
23.4 24.4 2.73 15.1 2.6 110.7 1.7
23.1
24.4
25.9 26.7 2.75 17.3 2.8 111.7 1.7
25.7
26.7
26.7 27.1 2.77 17.7 2.9 111.9 1.7
26.6
27.1
24.7 23.7 3.41 12.1 2.0 130.4 1.5
24.3
23.7
26.7 25.9 3.43 14.2 2.2 131.4 1.5
26.4
25.9
27.3 26.3 3.46 14.5 2.2 131.6 1.5
27.1
26.3
28.9 31.0 1.59 25.6 5.7 73.5
2.2
28.7
31.0
33.3 33.9 1.59 28.5 6.2 74.7
2.2
33.2
33.9
34.7 34.4 1.61 28.9 6.3 75.0
2.2
34.6
34.4
30.5 29.5 2.22 21.9 3.9 92.9
1.9
30.2
29.5
34.2 32.4 2.23 24.8 4.3 94.1
1.9
34.0
32.4
35.4 32.8 2.25 25.1 4.3 94.3
1.9
35.2
32.8
31.9 28.5 2.90 18.6 2.9 112.5 1.7
31.5
28.5
35.0 31.2 2.91 21.3 3.1 113.7 1.7
34.8
31.2
36.0 31.6 2.94 21.6 3.1 113.8 1.7
35.8
31.6
33.4 27.6 3.63 15.2 2.2 132.1 1.5
32.9
27.6
35.8 30.2 3.65 17.7 2.4 133.3 1.5
35.6
30.2
36.6 30.7 3.68 18.1 2.4 133.5 1.5
36.4
30.7
37.3 34.9 1.63 29.3 6.3 75.2
2.2
37.0
34.9
42.3 38.3 1.64 32.7 6.8 76.7
2.2
42.2
38.3
43.9 38.8 1.66 33.1 6.8 76.9
2.2
43.8
38.8
38.9 33.3 2.30 25.5 4.2 94.5
1.9
38.7
33.3
43.3 36.5 2.31 28.6 4.6 95.9
1.9
43.1
36.5
44.6 37.0 2.33 29.1 4.7 96.1
1.9
44.5
37.0
40.5 32.1 3.02 21.8 3.1 114.0 1.7
40.1
32.1
44.2 35.1 3.03 24.8 3.4 115.4 1.7
44.0
35.1
45.3 35.6 3.06 25.2 3.4 115.6 1.7
45.2
35.6
42.1 31.1 3.79 18.2 2.4 133.7 1.5
41.6
31.1
45.0 34.1 3.81 21.1 2.6 135.0 1.5
44.8
34.1
46.0 34.6 3.84 21.5 2.6 135.2 1.5
45.8
34.6
45.7 38.5 1.68 32.8 6.7 76.8
2.2
45.5
38.5
51.4 42.2 1.68 36.5 7.4 78.4
2.2
51.3
42.2
53.1 42.8 1.70 37.0 7.4 78.6
2.2
53.1
42.8
47.6 36.7 2.37 28.6 4.5 96.0
1.9
47.3
36.7
52.4 40.2 2.38 32.1 4.9 97.5
1.9
52.3
40.2
54.0 40.8 2.40 32.6 5.0 97.8
1.9
53.8
40.8
49.2 35.4 3.11 24.8 3.3 115.5 1.7
48.8
35.4
53.4 38.8 3.12 28.2 3.6 117.0 1.7
53.1
38.8
54.7 39.3 3.15 28.6 3.7 117.2 1.7
54.5
39.3
50.9 34.3 3.90 21.0 2.6 135.1 1.5
50.3
34.3
54.3 37.6 3.92 24.2 2.8 136.5 1.5
54.0
37.6
55.4 38.1 3.95 24.6 2.8 136.8 1.5
55.2
38.1

8.5
GPM
Load
Power Heat COP Load Load Source Heat
kW
Of
LWT WPD LWT
Cap
Absorb
Ft
Mbtuh
Head
1.41 21.7
5.5 66.2
7.6
20.5
26.5
1.41 24.3
6.0 66.9
7.6
24.3
29.1
1.43 24.6
6.0 66.9
7.6
25.4
29.5
1.93 18.7
3.8 86.0
6.6
21.8
25.3
1.94 21.1
4.2 86.5
6.6
25.0
27.7
1.96 21.4
4.2 86.6
6.6
26.0
28.1
2.50 15.9
2.9 105.8 5.7
23.0
24.4
2.51 18.1
3.1 106.3 5.7
25.7
26.7
2.53 18.5
3.1 106.4 5.7
26.5
27.1
3.11
13.1
2.2 125.6 5.0
24.2
23.7
3.13 15.2
2.4 126.2 5.0
26.4
25.9
3.16 15.5
2.4 126.3 5.0
27.1
26.3
1.45 26.1
6.3 67.3
7.6
28.6
31.0
1.45 29.0
6.9 68.0
7.6
33.2
33.9
1.47 29.4
6.9 68.1
7.6
34.5
34.4
2.02 22.6
4.3 87.0
6.6
30.1
29.5
2.03 25.5
4.7 87.6
6.6
34.0
32.4
2.05 25.8
4.7 87.7
6.6
35.2
32.8
2.64 19.5
3.2 106.8 5.7
31.4
28.5
2.66 22.1
3.4 107.4 5.7
34.7
31.2
2.68 22.5
3.5 107.5 5.7
35.8
31.6
3.31 16.3
2.4 126.6 5.0
32.8
27.6
3.33 18.8
2.7 127.2 5.0
35.5
30.2
3.36 19.2
2.7 127.3 5.0
36.4
30.7
1.49 29.8
6.9 68.2
7.6
37.0
34.9
1.50 33.2
7.5 69.0
7.6
42.1
38.3
1.51 33.7
7.5 69.1
7.6
43.7
38.8
2.10 26.1
4.6 87.9
6.6
38.6
33.3
2.11
29.3
5.1 88.6
6.6
43.1
36.5
2.13 29.7
5.1 88.7
6.6
44.5
37.0
2.75 22.7
3.4 107.6 5.7
40.0
32.1
2.77 25.7
3.7 108.3 5.7
43.9
35.1
2.79 26.1
3.7 108.4 5.7
45.1
35.6
3.46 19.3
2.6 127.4 5.0
41.4
31.1
3.47 22.3
2.9 128.1 5.0
44.7
34.1
3.50 22.7
2.9 128.2 5.0
45.7
34.6
1.53 33.3
7.4 69.1
7.6
45.4
38.5
1.54 36.9
8.0 69.9
7.6
51.3
42.2
1.55 37.5
8.1 70.1
7.6
53.0
42.8
2.16 29.3
5.0 88.7
6.6
47.2
36.7
2.17 32.8
5.4 89.5
6.6
52.2
40.2
2.19 33.3
5.5 89.6
6.6
53.8
40.8
2.84 25.7
3.7 108.4 5.7
48.7
35.4
2.85 29.1
4.0 109.2 5.7
53.1
38.8
2.88 29.5
4.0 109.3 5.7
54.5
39.3
3.56 22.2
2.8 128.2 5.0
50.2
34.3
3.58 25.4
3.1 129.0 5.0
53.9
37.6
3.61 25.8
3.1 129.1 5.0
55.1
38.1

10.8 GPM
Power Heat COP Load Load
kW
Of
LWT WPD
Absorb
Ft
Head
1.37 21.8
5.7 64.9 12.2
1.37 24.4
6.2 65.4 12.2
1.38 24.8
6.3 65.5 12.2
1.87 18.9
4.0 84.7 10.6
1.88 21.3
4.3 85.1 10.6
1.90 21.6
4.3 85.2 10.6
2.42 16.1
3.0 104.5 9.3
2.43 18.4
3.2 105.0 9.3
2.46 18.7
3.2 105.1 9.3
3.02 13.4
2.3 124.4 8.1
3.04 15.5
2.5 124.9 8.1
3.06 15.9
2.5 124.9 8.1
1.40 26.2
6.5 65.7 12.2
1.41 29.1
7.0 66.3 12.2
1.42 29.6
7.1 66.4 12.2
1.96 22.8
4.4 85.5 10.6
1.97 25.7
4.8 86.0 10.6
1.99 26.0
4.8 86.1 10.6
2.57 19.7
3.2 105.3 9.3
2.58 22.4
3.5 105.8 9.3
2.60 22.7
3.6 105.9 9.3
3.22 16.6
2.5 125.2 8.1
3.23 19.2
2.7 125.7 8.1
3.26 19.6
2.8 125.8 8.1
1.45 30.0
7.1 66.5 12.2
1.45 33.4
7.7 67.1 12.2
1.47 33.8
7.7 67.2 12.2
2.04 26.3
4.8 86.2 10.6
2.05 29.5
5.2 86.8 10.6
2.07 29.9
5.2 86.9 10.6
2.67 23.0
3.5 106.0 9.3
2.69 25.9
3.8 106.5 9.3
2.71 26.4
3.8 106.6 9.3
3.35 19.7
2.7 125.8 8.1
3.37 22.6
3.0 126.4 8.1
3.40 23.0
3.0 126.5 8.1
1.48 33.5
7.6 67.1 12.2
1.49 37.1
8.3 67.8 12.2
1.51 37.7
8.3 67.9 12.2
2.10 29.5
5.1 86.8 10.6
2.11
33.0
5.6 87.5 10.6
2.12 33.6
5.6 87.6 10.6
2.75 26.0
3.8 106.6 9.3
2.77 29.4
4.1 107.2 9.3
2.79 29.8
4.1 107.3 9.3
3.45 22.5
2.9 126.4 8.1
3.47 25.8
3.2 127.0 8.1
3.50 26.2
3.2 127.1 8.1

WSHP-PRC009-EN

Performance Data
WPWD 036-Heating
Table P-4: 036 Heating Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Heat
EWT EWT GPM WPD LWT Cap
Ft
Mbtuh
Head
70.0 60.0
4.6
2.1
54.3 41.8
70.0 60.0
8.5
7.1
60.6 45.8
70.0 60.0 10.8
11.4
62.5 46.5
70.0 80.0
4.6
2.1
56.2 39.9
70.0 80.0
8.5
7.1
61.7 43.7
70.0 80.0 10.8
11.4
63.3 44.3
70.0 100.0 4.6
2.1
58.0 38.4
70.0 100.0 8.5
7.1
62.6 42.1
70.0 100.0 10.8
11.4
64.1 42.7
70.0 120.0 4.6
2.1
59.7 37.3
70.0 120.0 8.5
7.1
63.6 40.8
70.0 120.0 10.8
11.4
64.9 41.4
80.0 60.0
4.6
1.9
63.0 44.9
80.0 60.0
8.5
6.6
69.8 49.2
80.0 60.0 10.8
10.6
71.8 49.9
80.0 80.0
4.6
1.9
65.0 42.8
80.0 80.0
8.5
6.6
70.9 46.9
80.0 80.0 10.8
10.6
72.7 47.6
80.0 100.0 4.6
1.9
66.8 41.3
80.0 100.0 8.5
6.6
72.0 45.2
80.0 100.0 10.8
10.6
73.6 45.9
80.0 120.0 4.6
1.9
68.6 40.0
80.0 120.0 8.5
6.6
72.9 43.9
80.0 120.0 10.8
10.6
74.3 44.5

WSHP-PRC009-EN

4.6
GPM
Load 8.5
GPM
Load 10.8 GPM
Power Heat COP Load Load Source Heat Power Heat COP Load Load Source Heat Power Heat COP Load Load
kW
Of
LWT WPD LWT
Cap
kW
Of
LWT WPD LWT
Cap
kW
Of
LWT WPD
Absorb
Ft
Mbtuh
Absorb
Ft
Mbtuh
Absorb
Ft
Head
Head
Head
1.71
36.0 7.2 78.2
2.2
54.1
41.8 1.56
36.5
7.9 69.8
7.6
54.1
41.8 1.52
36.6
8.1 67.7 12.2
1.72
39.9 7.8 79.9
2.2
60.5
45.8 1.57
40.4
8.5 70.8
7.6
60.4
45.8 1.52
40.6
8.8 68.5 12.2
1.73
40.6 7.9 80.2
2.2
62.4
46.5 1.58
41.1
8.6 70.9
7.6
62.4
46.5 1.54
41.2
8.8 68.6 12.2
2.42
31.6 4.8 97.4
1.9
55.9
39.9 2.21
32.4
5.3 89.4
6.6
55.8
39.9 2.14
32.6
5.5 87.4 10.6
2.43
35.4 5.3 99.1
1.9
61.5
43.7 2.22
36.1
5.8 90.3
6.6
61.4
43.7 2.15
36.4
6.0 88.1 10.6
2.45
35.9 5.3 99.3
1.9
63.2
44.3 2.24
36.7
5.8 90.5
6.6
63.2
44.3 2.17
36.9
6.0 88.2 10.6
3.18
27.6 3.5 116.8 1.7
57.6
38.4 2.90
28.5
3.9 109.1 5.7
57.5
38.4 2.81
28.8
4.0 107.2 9.3
3.19
31.2 3.9 118.4 1.7
62.4
42.1 2.91
32.2
4.2 110.0 5.7
62.4
42.1 2.83
32.4
4.4 107.8 9.3
3.22
31.7 3.9 118.7 1.7
63.9
42.7 2.94
32.7
4.3 110.1 5.7
63.9
42.7 2.85
33.0
4.4 108.0 9.3
3.98
23.7 2.7 136.4 1.5
59.2
37.3 3.64
24.9
3.0 128.9 5.0
59.0
37.3 3.53
25.3
3.1 127.0 8.1
4.01
27.1 3.0 137.9 1.5
63.3
40.8 3.66
28.3
3.3 129.7 5.0
63.2
40.8 3.55
28.7
3.4 127.6 8.1
4.04
27.6 3.0 138.2 1.5
64.7
41.4 3.69
28.8
3.3 129.9 5.0
64.6
41.4 3.58
29.2
3.4 127.8 8.1
1.74
39.0 7.6 79.5
2.2
62.8
44.9 1.59
39.5
8.3 70.6
7.6
62.7
44.9 1.54
39.6
8.5 68.3 12.2
1.75
43.2 8.2 81.4
2.2
69.7
49.2 1.60
43.7
9.0 71.6
7.6
69.6
49.2 1.55
43.9
9.3 69.1 12.2
1.76
43.9 8.3 81.7
2.2
71.8
49.9 1.61
44.4
9.1 71.7
7.6
71.7
49.9 1.56
44.6
9.4 69.2 12.2
2.46
34.4 5.1 98.7
1.9
64.6
42.8 2.24
35.2
5.6 90.1
6.6
64.6
42.8 2.18
35.4
5.8 87.9 10.6
2.47
38.5 5.6 100.5 1.9
70.7
46.9 2.26
39.2
6.1 91.1
6.6
70.7
46.9 2.19
39.4
6.3 88.7 10.6
2.49
39.1 5.6 100.8 1.9
72.6
47.6 2.28
39.8
6.1 91.2
6.6
72.6
47.6 2.21
40.1
6.3 88.8 10.6
3.23
30.3 3.7 118.1 1.7
66.4
41.3 2.95
31.2
4.1 109.8 5.7
66.3
41.3 2.86
31.5
4.2 107.7 9.3
3.25
34.1 4.1 119.8 1.7
71.7
45.2 2.96
35.1
4.5 110.7 5.7
71.6
45.2 2.87
35.4
4.6 108.4 9.3
3.27
34.7 4.1 120.1 1.7
73.4
45.9 2.99
35.7
4.5 110.9 5.7
73.3
45.9 2.90
36.0
4.6 108.6 9.3
4.05
26.2 2.9 137.6 1.5
68.1
40.0 3.70
27.4
3.2 129.5 5.0
67.9
40.0 3.59
27.8
3.3 127.5 8.1
4.07
30.0 3.2 139.3 1.5
72.6
43.9 3.72
31.2
3.5 130.5 5.0
72.5
43.9 3.61
31.6
3.6 128.2 8.1
4.11
30.5 3.2 139.6 1.5
74.1
44.5 3.75
31.7
3.5 130.6 5.0
74.0
44.5 3.64
32.1
3.6 128.3 8.1

25

Performance Data
WPWD 042-Cooling
Table P-5: 042 Cooling Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Cool
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
50.0
45.0
5.2
3.1
64.3
32.1
50.0
45.0
9.5
10.7
57.8
32.5
50.0
45.0 12.1
17.6
56.2
32.7
50.0
53.6
5.2
3.1
65.5
35.2
50.0
53.6
9.5
10.7
58.5
35.7
50.0
53.6 12.1
17.6
56.7
35.9
50.0
65.0
5.2
3.1
67.2
39.4
50.0
65.0
9.5
10.7
59.4
39.9
50.0
65.0 12.1
17.6
57.4
40.1
50.0
75.0
5.2
3.1
68.6
43.0
50.0
75.0
9.5
10.7
60.2
43.5
50.0
75.0 12.1
17.6
58.0
43.8
60.0
45.0
5.2
2.8
74.2
31.2
60.0
45.0
9.5
9.8
67.8
31.6
60.0
45.0 12.1
16.2
66.1
31.8
60.0
53.6
5.2
2.8
75.4
34.3
60.0
53.6
9.5
9.8
68.5
34.7
60.0
53.6 12.1
16.2
66.7
35.0
60.0
65.0
5.2
2.8
77.1
38.5
60.0
65.0
9.5
9.8
69.4
38.9
60.0
65.0 12.1
16.2
67.4
39.2
60.0
75.0
5.2
2.8
78.5
42.1
60.0
75.0
9.5
9.8
70.2
42.6
60.0
75.0 12.1
16.2
68.0
42.9
70.0
45.0
5.2
2.6
84.1
30.1
70.0
45.0
9.5
9.1
77.7
30.4
70.0
45.0 12.1
15.1
76.1
30.6
70.0
53.6
5.2
2.6
85.3
33.2
70.0
53.6
9.5
9.1
78.4
33.6
70.0
53.6 12.1
15.1
76.6
33.8
70.0
65.0
5.2
2.6
87.0
37.3
70.0
65.0
9.5
9.1
79.3
37.8
70.0
65.0 12.1
15.1
77.3
38.0
70.0
75.0
5.2
2.6
88.4
41.0
70.0
75.0
9.5
9.1
80.1
41.4
70.0
75.0 12.1
15.1
77.9
41.7
80.0
45.0
5.2
2.4
94.0
28.9
80.0
45.0
9.5
8.6
87.6
29.3
80.0
45.0 12.1
14.1
86.0
29.5
80.0
53.6
5.2
2.4
95.3
32.1
80.0
53.6
9.5
8.6
88.3
32.4
80.0
53.6 12.1
14.1
86.6
32.7
80.0
65.0
5.2
2.4
96.9
36.2
80.0
65.0
9.5
8.6
89.2
36.6
80.0
65.0 12.1
14.1
87.3
36.9
80.0
75.0
5.2
2.4
98.4
39.9
80.0
75.0
9.5
8.6
90.0
40.3
80.0
75.0 12.1
14.1
87.9
40.6

26

5.2 GPM
Power Heat EER Load
kW
Of
LWT
Reject
1.49
1.39
1.36
1.51
1.41
1.38
1.53
1.43
1.40
1.54
1.44
1.42
1.69
1.58
1.55
1.71
1.60
1.57
1.73
1.62
1.59
1.75
1.64
1.61
1.92
1.79
1.76
1.94
1.81
1.78
1.97
1.84
1.80
1.99
1.86
1.82
2.17
2.03
1.99
2.20
2.06
2.02
2.23
2.08
2.05
2.26
2.11
2.07

37.2
37.2
37.3
40.4
40.5
40.6
44.6
44.8
44.9
48.3
48.4
48.7
37.0
37.0
37.1
40.1
40.2
40.4
44.4
44.4
44.6
48.1
48.2
48.4
36.7
36.5
36.6
39.8
39.8
39.9
44.0
44.1
44.1
47.8
47.8
47.9
36.3
36.2
36.3
39.6
39.4
39.6
43.8
43.7
43.9
47.6
47.5
47.7

21.5
23.4
24.0
23.3
25.3
26.0
25.8
27.9
28.6
27.9
30.2
30.8
18.5
20.0
20.5
20.1
21.7
22.3
22.3
24.0
24.7
24.1
26.0
26.6
15.7
17.0
17.4
17.1
18.6
19.0
18.9
20.5
21.1
20.6
22.3
22.9
13.3
14.4
14.8
14.6
15.7
16.2
16.2
17.6
18.0
17.7
19.1
19.6

32.7
32.5
32.4
40.1
39.9
39.8
49.8
49.6
49.6
58.4
58.2
58.1
33
32.8
32.8
40.4
40.3
40.1
50.2
50
49.9
58.8
58.6
58.5
33.4
33.3
33.2
40.8
40.7
40.6
50.6
50.4
50.4
59.2
59
58.9
33.9
33.7
33.7
41.3
41.1
41
51.1
50.9
50.8
59.6
59.5
59.3

Load 9.5
Load Source Cool Power
WPD LWT
Cap
kW
Ft
Mbtuh
Head
3.2
65.6
35.3 1.52
3.2
58.5
35.7 1.42
3.2
56.7
36.0 1.39
3.0
67.0
38.8 1.54
3.0
59.3
39.2 1.44
3.0
57.3
39.5 1.41
2.7
68.7
43.3 1.56
2.7
60.3
43.8 1.46
2.7
58.1
44.1 1.43
2.5
70.3
47.3 1.57
2.5
61.1
47.9 1.47
2.5
58.8
48.2 1.44
3.2
75.5
34.3 1.72
3.2
68.5
34.7 1.61
3.2
66.7
34.9 1.58
3.0
76.8
37.7 1.74
3.0
69.2
38.2 1.63
3.0
67.3
38.4 1.60
2.7
78.6
42.3 1.77
2.7
70.2
42.8 1.65
2.7
68.0
43.1 1.62
2.5
80.2
46.3 1.79
2.5
71.1
46.8 1.67
2.5
68.7
47.2 1.64
3.2
85.3
33.0 1.95
3.2
78.4
33.4 1.82
3.2
76.6
33.7 1.79
3.0
86.7
36.5 1.98
3.0
79.1
36.9 1.85
3.0
77.2
37.2 1.81
2.7
88.5
41.1 2.01
2.7
80.1
41.5 1.87
2.7
78.0
41.8 1.84
2.5
90.0
45.1 2.03
2.5
81.0
45.6 1.89
2.5
78.7
45.9 1.86
3.2
95.2
31.8 2.22
3.2
88.3
32.2 2.07
3.2
86.5
32.4 2.03
3.0
96.6
35.3 2.24
3.0
89.1
35.7 2.10
3.0
87.1
35.9 2.06
2.7
98.4
39.8 2.28
2.7
90.1
40.3 2.13
2.7
87.9
40.6 2.09
2.5
99.9
43.8 2.30
2.5
90.9
44.3 2.15
2.5
88.6
44.6 2.11

GPM
Load
Heat EER Load Load Source Cool
Of
LWT WPD LWT
Cap
Reject
Ft
Mbtuh
Head
40.5 23.2 37.6 11.2
66.1
36.6
40.6 25.1 37.5 11.2
58.8
37.0
40.7 25.9 37.4 11.2
56.9
37.2
44.1 25.2 45.4 10.3
67.5
40.1
44.1 27.2 45.3 10.3
59.6
40.6
44.3 28.0 45.3 10.3
57.6
40.9
48.6 27.8 55.9
9.4
69.3
44.8
48.8 30.0 55.8
9.4
60.6
45.4
49.0 30.8 55.7
9.4
58.4
45.7
52.7 30.1 65.0
8.8
70.9
49.0
52.9 32.6 64.9
8.8
61.5
49.6
53.1 33.5 64.8
8.8
59.1
49.9
40.2 19.9 37.8 11.2
75.9
35.5
40.2 21.6 37.7 11.2
68.7
35.9
40.3 22.1 37.7 11.2
66.9
36.2
43.6 21.7 45.7 10.3
77.4
39.1
43.8 23.4 45.6 10.3
69.5
39.5
43.9 24.0 45.5 10.3
67.5
39.8
48.3 23.9 56.1
9.4
79.2
43.8
48.4 25.9 56.0
9.4
70.5
44.3
48.6 26.6 55.9
9.4
68.3
44.6
52.4 25.9 65.2
8.8
80.8
47.9
52.5 28.0 65.1
8.8
71.4
48.5
52.8 28.8 65.0
8.8
69.0
48.8
39.7 16.9 38.1 11.2
85.8
34.2
39.6 18.4 38.0 11.2
78.6
34.6
39.8 18.8 37.9 11.2
76.8
34.8
43.3 18.4 45.9 10.3
87.2
37.8
43.2 19.9 45.8 10.3
79.4
38.2
43.4 20.6 45.8 10.3
77.4
38.5
48.0 20.4 56.3
9.4
89.0
42.5
47.9 22.2 56.3
9.4
80.4
43.0
48.1 22.7 56.2
9.4
78.2
43.3
52.0 22.2 65.5
8.8
90.6
46.6
52.1 24.1 65.4
8.8
81.3
47.2
52.3 24.7 65.3
8.8
78.9
47.5
39.4 14.3 38.3 11.2
95.6
32.9
39.3 15.6 38.2 11.2
88.5
33.3
39.3 16.0 38.2 11.2
86.7
33.6
43.0 15.8 46.2 10.3
97.1
36.5
42.9 17.0 46.1 10.3
89.3
36.9
42.9 17.4 46.0 10.3
87.3
37.2
47.6 17.5 56.6
9.4
98.9
41.2
47.6 18.9 56.5
9.4
90.3
41.7
47.7 19.4 56.4
9.4
88.1
42.0
51.7 19.0 65.8
8.8
100.6 45.4
51.6 20.6 65.7
8.8
91.2
45.9
51.8 21.1 65.6
8.8
88.9
46.2

12.1 GPM
Power Heat EER Load Load
kW
Of
LWT WPD
Reject
Ft
Head
1.52 41.8 24.1 39.0 18.5
1.42 41.9 26.1 38.9 18.5
1.40 42.0 26.6 38.9 18.5
1.54 45.4 26.0 47.0 17.1
1.44 45.5 28.2 46.9 17.1
1.41 45.7 29.0 46.8 17.1
1.56 50.1 28.7 57.6 15.6
1.46 50.4 31.1 57.5 15.6
1.43 50.6 32.0 57.4 15.6
1.58 54.4 31.0 66.9 14.6
1.48 54.7 33.5 66.8 14.6
1.45 54.9 34.4 66.7 14.6
1.73 41.4 20.5 39.1 18.5
1.61 41.4 22.3 39.1 18.5
1.58 41.6 22.9 39.0 18.5
1.75 45.1 22.3 47.1 17.1
1.63 45.1 24.2 47.1 17.1
1.60 45.3 24.9 47.0 17.1
1.77 49.8 24.7 57.8 15.6
1.66 50.0 26.7 57.7 15.6
1.63 50.2 27.4 57.6 15.6
1.79 54.0 26.8 67.1 14.6
1.67 54.2 29.0 67.0 14.6
1.64 54.4 29.8 66.9 14.6
1.96 40.9 17.4 39.3 18.5
1.83 40.9 18.9 39.3 18.5
1.80 40.9 19.3 39.2 18.5
1.98 44.6 19.1 47.4 17.1
1.85 44.5 20.6 47.3 17.1
1.82 44.7 21.2 47.2 17.1
2.01 49.4 21.1 58.0 15.6
1.88 49.4 22.9 57.9 15.6
1.84 49.6 23.5 57.8 15.6
2.03 53.5 23.0 67.3 14.6
1.90 53.7 24.8 67.2 14.6
1.86 53.9 25.5 67.1 14.6
2.22 40.5 14.8 39.6 18.5
2.08 40.4 16.0 39.5 18.5
2.04 40.6 16.5 39.4 18.5
2.25 44.2 16.2 47.6 17.1
2.10 44.1 17.6 47.5 17.1
2.06 44.2 18.1 47.5 17.1
2.28 49.0 18.1 58.2 15.6
2.13 49.0 19.6 58.1 15.6
2.09 49.1 20.1 58.1 15.6
2.31 53.3 19.7 67.5 14.6
2.15 53.2 21.3 67.4 14.6
2.11 53.4 21.9 67.3 14.6

WSHP-PRC009-EN

Performance Data
WPWD 042-Cooling
Table P-5: 042 Cooling Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
90.0
45.0
5.2
2.3
90.0
45.0
9.5
8.1
90.0
45.0 12.1
13.4
90.0
53.6
5.2
2.3
90.0
53.6
9.5
8.1
90.0
53.6 12.1
13.4
90.0
65.0
5.2
2.3
90.0
65.0
9.5
8.1
90.0
65.0 12.1
13.4
90.0
75.0
5.2
2.3
90.0
75.0
9.5
8.1
90.0
75.0 12.1
13.4
100.0 45.0
5.2
2.2
100.0 45.0
9.5
7.7
100.0 45.0 12.1
12.7
100.0 53.6
5.2
2.2
100.0 53.6
9.5
7.7
100.0 53.6 12.1
12.7
100.0 65.0
5.2
2.2
100.0 65.0
9.5
7.7
100.0 65.0 12.1
12.7
100.0 75.0
5.2
2.2
100.0 75.0
9.5
7.7
100.0 75.0 12.1
12.7
110.0 45.0
5.2
2.1
110.0 45.0
9.5
7.4
110.0 45.0 12.1
12.2
110.0 53.6
5.2
2.1
110.0 53.6
9.5
7.4
110.0 53.6 12.1
12.2
110.0 65.0
5.2
2.1
110.0 65.0
9.5
7.4
110.0 65.0 12.1
12.2
110.0 75.0
5.2
2.1
110.0 75.0
9.5
7.4
110.0 75.0 12.1
12.2
120.0 45.0
5.2
2.0
120.0 45.0
9.5
7.1
120.0 45.0 12.1
11.7
120.0 53.6
5.2
2.0
120.0 53.6
9.5
7.1
120.0 53.6 12.1
11.7
120.0 65.0
5.2
2.0
120.0 65.0
9.5
7.1
120.0 65.0 12.1
11.7
120.0 75.0
5.2
2.0
120.0 75.0
9.5
7.1
120.0 75.0 12.1
11.7

WSHP-PRC009-EN

Load 5.2 GPM


Source Cool Power Heat EER
LWT Cap
kW
Of
Mbtuh
Reject
104.0
97.6
96.0
105.3
98.3
96.5
106.9
99.2
97.3
108.4
100.0
97.9
114.2
107.7
106.0
115.4
108.4
106.6
117.1
109.3
107.3
118.5
110.1
107.9
124.4
117.8
116.1
125.6
118.5
116.7
127.3
119.4
117.4
128.7
120.2
118.0
134.7
127.9
126.2
136.0
128.6
126.8
137.7
129.6
127.5
139.1
130.4
128.2

27.9
28.2
28.4
31.1
31.4
31.6
35.2
35.6
35.9
38.8
39.3
39.6
27.0
27.3
27.5
30.1
30.5
30.7
34.3
34.7
34.9
37.9
38.4
38.6
26.2
26.5
26.7
29.3
29.7
29.9
33.5
33.9
34.1
37.1
37.6
37.8
25.5
25.8
26.0
28.6
28.9
29.2
32.8
33.1
33.4
36.4
36.8
37.1

2.47
2.30
2.26
2.50
2.33
2.29
2.53
2.37
2.32
2.56
2.39
2.35
2.80
2.61
2.56
2.83
2.65
2.60
2.87
2.68
2.63
2.90
2.71
2.66
3.17
2.96
2.91
3.21
3.00
2.95
3.26
3.04
2.99
3.29
3.08
3.02
3.60
3.36
3.30
3.65
3.41
3.34
3.70
3.45
3.39
3.74
3.49
3.43

36.3
36.1
36.1
39.6
39.4
39.4
43.8
43.7
43.8
47.5
47.5
47.6
36.6
36.2
36.2
39.8
39.5
39.6
44.1
43.9
43.9
47.8
47.7
47.7
37.0
36.6
36.6
40.3
39.9
40.0
44.6
44.3
44.3
48.3
48.1
48.1
37.8
37.3
37.3
41.1
40.5
40.6
45.4
44.9
45.0
49.2
48.7
48.8

11.3
12.3
12.6
12.4
13.5
13.8
13.9
15.0
15.5
15.2
16.4
16.9
9.6
10.5
10.7
10.6
11.5
11.8
12.0
12.9
13.3
13.1
14.2
14.5
8.3
9.0
9.2
9.1
9.9
10.1
10.3
11.2
11.4
11.3
12.2
12.5
7.1
7.7
7.9
7.8
8.5
8.7
8.9
9.6
9.9
9.7
10.5
10.8

Load Load
LWT WPD
Ft
Head
34.3
3.2
34.2
3.2
34.1
3.2
41.6
3.0
41.5
3.0
41.4
3.0
51.4
2.7
51.3
2.7
51.2
2.7
60
2.5
59.9
2.5
59.7
2.5
34.6
3.2
34.5
3.2
34.4
3.2
42
3.0
41.9
3.0
41.8
3.0
51.8
2.7
51.6
2.7
51.6
2.7
60.4
2.5
60.2
2.5
60.1
2.5
34.9
3.2
34.8
3.2
34.7
3.2
42.3
3.0
42.2
3.0
42.1
3.0
52.1
2.7
51.9
2.7
51.9
2.7
60.7
2.5
60.5
2.5
60.4
2.5
35.2
3.2
35.1
3.2
35
3.2
42.6
3.0
42.5
3.0
42.4
3.0
52.4
2.7
52.3
2.7
52.1
2.7
61
2.5
60.8
2.5
60.7
2.5

Load 9.5 GPM


Source Cool Power Heat EER
LWT
Cap
kW
Of
Mbtuh
Reject
105.2
98.3
96.5
106.5
99.0
97.1
108.4
100.0
97.9
109.9
100.9
98.6
115.3
108.3
106.5
116.6
109.0
107.1
118.5
110.1
107.9
120.1
110.9
108.6
125.4
118.4
116.6
126.9
119.1
117.2
128.7
120.2
118.0
130.3
121.0
118.7
135.8
128.5
126.7
137.2
129.3
127.3
139.0
130.3
128.1
140.6
131.2
128.8

30.7
31.1
31.3
34.1
34.5
34.8
38.7
39.2
39.4
42.7
43.2
43.5
29.7
30.1
30.3
33.1
33.5
33.8
37.7
38.1
38.4
41.7
42.2
42.5
28.8
29.2
29.4
32.3
32.6
32.9
36.8
37.2
37.5
40.8
41.3
41.6
28.0
28.4
28.6
31.5
31.8
32.1
36.0
36.4
36.7
40.0
40.5
40.8

2.51
2.35
2.30
2.55
2.38
2.33
2.58
2.41
2.37
2.61
2.44
2.39
2.85
2.66
2.61
2.89
2.70
2.65
2.93
2.74
2.68
2.96
2.76
2.71
3.23
3.02
2.96
3.28
3.06
3.00
3.32
3.10
3.05
3.36
3.14
3.08
3.67
3.43
3.36
3.72
3.47
3.41
3.77
3.52
3.45
3.81
3.56
3.49

39.3
39.1
39.2
42.8
42.6
42.8
47.5
47.4
47.5
51.6
51.5
51.7
39.4
39.2
39.2
43.0
42.7
42.8
47.7
47.5
47.6
51.8
51.6
51.8
39.8
39.5
39.5
43.5
43.0
43.1
48.1
47.8
47.9
52.3
52.0
52.1
40.5
40.1
40.1
44.2
43.6
43.7
48.9
48.4
48.5
53.0
52.7
52.7

12.2
13.2
13.6
13.4
14.5
14.9
15.0
16.3
16.6
16.4
17.7
18.2
10.4
11.3
11.6
11.5
12.4
12.8
12.9
13.9
14.3
14.1
15.3
15.7
8.9
9.7
9.9
9.8
10.7
11.0
11.1
12.0
12.3
12.1
13.2
13.5
7.6
8.3
8.5
8.5
9.2
9.4
9.5
10.3
10.6
10.5
11.4
11.7

Load Load
LWT WPD
Ft
Head
38.5 11.2
38.5 11.2
38.4 11.2
46.4 10.3
46.3 10.3
46.3 10.3
56.8
9.4
56.7
9.4
56.7
9.4
66.0
8.8
65.9
8.8
65.8
8.8
38.7 11.2
38.7 11.2
38.6 11.2
46.6 10.3
46.5 10.3
46.5 10.3
57.1
9.4
57.0
9.4
56.9
9.4
66.2
8.8
66.1
8.8
66.0
8.8
38.9 11.2
38.9 11.2
38.8 11.2
46.8 10.3
46.7 10.3
46.7 10.3
57.2
9.4
57.2
9.4
57.1
9.4
66.4
8.8
66.3
8.8
66.2
8.8
39.1 11.2
39.0 11.2
39.0 11.2
47.0 10.3
46.9 10.3
46.8 10.3
57.4
9.4
57.3
9.4
57.3
9.4
66.6
8.8
66.5
8.8
66.4
8.8

Load 12.1 GPM


Source Cool Power Heat EER
LWT Cap
kW
Of
Mbtuh
Reject
105.6
98.5
96.7
107.0
99.3
97.3
108.9
100.3
98.1
110.5
101.2
98.8
115.7
108.5
106.7
117.1
109.3
107.3
119.0
110.4
108.2
120.6
111.3
108.9
125.9
118.6
116.8
127.3
119.4
117.4
129.2
120.5
118.2
130.9
121.4
118.9
136.2
128.7
126.9
137.6
129.6
127.5
139.5
130.6
128.3
141.2
131.5
129.1

31.8
32.2
32.4
35.3
35.8
36.0
40.1
40.5
40.8
44.2
44.7
45.0
30.7
31.1
31.3
34.3
34.7
35.0
39.0
39.5
39.8
43.2
43.7
44.0
29.8
30.2
30.4
33.4
33.8
34.0
38.1
38.6
38.8
42.3
42.7
43.0
29.0
29.3
29.6
32.6
33.0
33.2
37.3
37.7
38.0
41.4
41.9
42.2

2.52
2.36
2.31
2.55
2.39
2.34
2.59
2.42
2.37
2.62
2.44
2.40
2.86
2.67
2.62
2.90
2.71
2.66
2.94
2.74
2.69
2.97
2.77
2.72
3.25
3.03
2.98
3.29
3.07
3.01
3.33
3.11
3.06
3.37
3.15
3.09
3.68
3.44
3.38
3.73
3.48
3.42
3.78
3.53
3.47
3.82
3.57
3.50

40.4
40.3
40.3
44.0
44.0
44.0
48.9
48.8
48.9
53.1
53.0
53.2
40.5
40.2
40.2
44.2
44.0
44.1
49.0
48.9
49.0
53.3
53.2
53.3
40.9
40.5
40.6
44.6
44.3
44.3
49.5
49.2
49.2
53.8
53.5
53.6
41.6
41.0
41.1
45.3
44.9
44.9
50.2
49.8
49.8
54.4
54.1
54.2

12.6
13.6
14.0
13.8
15.0
15.4
15.5
16.7
17.2
16.9
18.3
18.8
10.7
11.6
11.9
11.8
12.8
13.2
13.3
14.4
14.8
14.5
15.8
16.2
9.2
10.0
10.2
10.2
11.0
11.3
11.4
12.4
12.7
12.6
13.6
13.9
7.9
8.5
8.8
8.7
9.5
9.7
9.9
10.7
11.0
10.8
11.7
12.1

Load Load
LWT WPD
Ft
Head
39.7 18.5
39.7 18.5
39.6 18.5
47.8 17.1
47.7 17.1
47.6 17.1
58.4 15.6
58.3 15.6
58.2 15.6
67.7 14.6
67.6 14.6
67.5 14.6
39.9 18.5
39.9 18.5
39.8 18.5
47.9 17.1
47.9 17.1
47.8 17.1
58.5 15.6
58.5 15.6
58.4 15.6
67.8 14.6
67.8 14.6
67.7 14.6
40.1 18.5
40.0 18.5
40.0 18.5
48.1 17.1
48.0 17.1
48.0 17.1
58.7 15.6
58.6 15.6
58.6 15.6
68.0 14.6
67.9 14.6
67.9 14.6
40.2 18.5
40.2 18.5
40.1 18.5
48.2 17.1
48.1 17.1
48.1 17.1
58.8 15.6
58.8 15.6
58.7 15.6
68.1 14.6
68.1 14.6
68.0 14.6

27

Performance Data
WPWD 042-Heating
Table P-6: 042 Heating Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Heat
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
30.0 60.0
5.2
3.9
20.0
31.7
30.0 60.0
9.5
13.6
24.0
34.6
30.0 60.0 12.1
22.4
25.2
35.1
30.0 80.0
5.2
3.9
21.6
30.2
30.0 80.0
9.5
13.6
24.8
33.0
30.0 80.0 12.1
22.4
25.9
33.5
30.0 100.0 5.2
3.9
23.0
29.1
30.0 100.0 9.5
13.6
25.6
31.8
30.0 100.0 12.1
22.4
26.5
32.3
30.0 120.0 5.2
3.9
24.3
28.2
30.0 120.0 9.5
13.6
26.3
30.9
30.0 120.0 12.1
22.4
27.1
31.3
40.0 60.0
5.2
3.4
28.2
36.9
40.0 60.0
9.5
11.9
32.8
40.4
40.0 60.0 12.1
19.6
34.3
41.0
40.0 80.0
5.2
3.4
29.8
35.2
40.0 80.0
9.5
11.9
33.7
38.5
40.0 80.0 12.1
19.6
35.0
39.1
40.0 100.0 5.2
3.4
31.3
33.9
40.0 100.0 9.5
11.9
34.6
37.1
40.0 100.0 12.1
19.6
35.7
37.7
40.0 120.0 5.2
3.4
32.8
32.9
40.0 120.0 9.5
11.9
35.4
36.0
40.0 120.0 12.1
19.6
36.3
36.5
50.0 60.0
5.2
3.1
36.5
41.6
50.0 60.0
9.5
10.7
41.8
45.5
50.0 60.0 12.1
17.6
43.4
46.2
50.0 80.0
5.2
3.1
38.2
39.7
50.0 80.0
9.5
10.7
42.8
43.4
50.0 80.0 12.1
17.6
44.2
44.0
50.0 100.0 5.2
3.1
39.8
38.3
50.0 100.0 9.5
10.7
43.7
41.8
50.0 100.0 12.1
17.6
45.0
42.4
50.0 120.0 5.2
3.1
41.4
37.1
50.0 120.0 9.5
10.7
44.6
40.6
50.0 120.0 12.1
17.6
45.7
41.2
60.0 60.0
5.2
2.8
44.9
45.9
60.0 60.0
9.5
9.8
50.8
50.2
60.0 60.0 12.1
16.2
52.7
50.9
60.0 80.0
5.2
2.8
46.8
43.8
60.0 80.0
9.5
9.8
51.9
47.9
60.0 80.0 12.1
16.2
53.5
48.6
60.0 100.0 5.2
2.8
48.5
42.2
60.0 100.0 9.5
9.8
52.9
46.1
60.0 100.0 12.1
16.2
54.3
46.8
60.0 120.0 5.2
2.8
50.1
40.9
60.0 120.0 9.5
9.8
53.8
44.8
60.0 120.0 12.1
16.2
55.1
45.4

28

5.2
GPM
Load 9.5
GPM
Load 12.1 GPM
Power Heat COP Load Load Source Heat Power Heat COP Load Load Source Heat Power Heat
kW
Of
LWT WPD LWT
Cap
kW
Of
LWT WPD LWT
Cap
kW
Of
Absorb
Ft
Mbtuh
Absorb
Ft
Mbtuh
Absorb
Head
Head
1.71
25.9
5.4 72.2 2.8
19.9
31.7 1.56
26.4
6.0 66.7 9.8
19.8
31.7 1.52
26.5
1.72
28.7
5.9 73.3 2.8
23.9
34.6 1.57
29.2
6.5 67.3 9.8
23.8
34.6 1.52
29.4
1.73
29.2
5.9 73.5 2.8
25.1
35.1 1.58
29.7
6.5 67.4 9.8
25.1
35.1 1.54
29.8
2.42
21.9
3.7 91.7 2.4
21.3
30.2 2.21
22.7
4.0 86.4 8.6
21.2
30.2 2.15
22.9
2.43
24.7
4.0 92.7 2.4
24.7
33.0 2.22
25.4
4.4 87.0 8.6
24.6
33.0 2.16
25.6
2.45
25.1
4.0 92.9 2.4
25.7
33.5 2.24
25.9
4.4 87.1 8.6
25.7
33.5 2.18
26.1
3.17
18.3
2.7 111.3 2.2
22.6
29.1 2.90
19.2
2.9 106.2 7.7
22.5
29.1 2.81
19.5
3.19
20.9
2.9 112.3 2.2
25.4
31.8 2.91
21.9
3.2 106.7 7.7
25.3
31.8 2.83
22.1
3.22
21.3
2.9 112.5 2.2
26.3
32.3 2.94
22.3
3.2 106.8 7.7
26.3
32.3 2.85
22.6
3.95
14.7
2.1 131.0 2.0
23.9
28.2 3.61
15.9
2.3 126.0 7.1
23.8
28.2 3.51
16.2
3.97
17.4
2.3 132.0 2.0
26.1
30.9 3.63
18.5
2.5 126.6 7.1
26.0
30.9 3.52
18.9
4.01
17.6
2.3 132.2 2.0
26.9
31.3 3.66
18.8
2.5 126.7 7.1
26.8
31.3 3.56
19.2
1.80
30.8
6.0 74.2 2.8
28.0
36.9 1.65
31.3
6.6 67.8 9.8
27.9
36.9 1.60
31.4
1.81
34.2
6.5 75.5 2.8
32.7
40.4 1.66
34.7
7.1 68.5 9.8
32.7
40.4 1.61
34.9
1.83
34.8
6.6 75.8 2.8
34.2
41.0 1.67
35.3
7.2 68.6 9.8
34.1
41.0 1.62
35.5
2.55
26.5
4.0 93.6 2.4
29.5
35.2 2.33
27.3
4.4 87.4 8.6
29.4
35.2 2.26
27.5
2.57
29.7
4.4 94.9 2.4
33.6
38.5 2.35
30.5
4.8 88.1 8.6
33.5
38.5 2.28
30.7
2.59
30.3
4.4 95.1 2.4
34.9
39.1 2.37
31.0
4.8 88.3 8.6
34.8
39.1 2.30
31.3
3.34
22.5
3.0 113.1 2.2
31.0
33.9 3.06
23.5
3.2 107.2 7.7
30.8
33.9 2.96
23.8
3.36
25.6
3.2 114.4 2.2
34.4
37.1 3.07
26.6
3.5 107.9 7.7
34.3
37.1 2.98
26.9
3.39
26.1
3.3 114.6 2.2
35.5
37.7 3.10
27.1
3.6 108.0 7.7
35.5
37.7 3.01
27.4
4.17
18.7
2.3 132.8 2.0
32.3
32.9 3.81
19.9
2.5 127.0 7.1
32.2
32.9 3.70
20.3
4.19
21.7
2.5 134.0 2.0
35.2
36.0 3.83
22.9
2.8 127.7 7.1
35.1
36.0 3.72
23.3
4.23
22.1
2.5 134.2 2.0
36.2
36.5 3.86
23.3
2.8 127.8 7.1
36.1
36.5 3.75
23.7
1.88
35.2
6.5 76.0 2.8
36.3
41.6 1.72
35.7
7.1 68.8 9.8
36.2
41.6 1.67
35.9
1.89
39.1
7.1 77.5 2.8
41.7
45.5 1.73
39.6
7.7 69.6 9.8
41.6
45.5 1.67
39.8
1.90
39.7
7.1 77.8 2.8
43.3
46.2 1.74
40.3
7.8 69.7 9.8
43.3
46.2 1.69
40.4
2.66
30.6
4.4 95.3 2.4
37.9
39.7 2.43
31.4
4.8 88.4 8.6
37.8
39.7 2.36
31.7
2.67
34.3
4.8 96.7 2.4
42.6
43.4 2.44
35.1
5.2 89.2 8.6
42.6
43.4 2.37
35.3
2.70
34.8
4.8 97.0 2.4
44.1
44.0 2.47
35.6
5.2 89.3 8.6
44.1
44.0 2.39
35.8
3.48
26.4
3.2 114.8 2.2
39.4
38.3 3.18
27.5
3.5 108.1 7.7
39.3
38.3 3.09
27.8
3.50
29.9
3.5 116.2 2.2
43.5
41.8 3.20
30.9
3.8 108.9 7.7
43.4
41.8 3.11
31.2
3.53
30.4
3.5 116.4 2.2
44.8
42.4 3.23
31.4
3.8 109.0 7.7
44.8
42.4 3.13
31.7
4.34
22.3
2.5 134.4 2.0
40.9
37.1 3.97
23.6
2.7 127.9 7.1
40.8
37.1 3.85
24.0
4.37
25.7
2.7 135.8 2.0
44.3
40.6 3.99
27.0
3.0 128.6 7.1
44.2
40.6 3.87
27.4
4.40
26.2
2.7 136.0 2.0
45.5
41.2 4.03
27.5
3.0 128.8 7.1
45.4
41.2 3.91
27.9
1.94
39.3
6.9 77.7 2.8
44.7
45.9 1.78
39.8
7.6 69.7 9.8
44.6
45.9 1.72
40.0
1.95
43.5
7.5 79.3 2.8
50.7
50.2 1.78
44.1
8.3 70.6 9.8
50.7
50.2 1.73
44.3
1.97
44.2
7.6 79.6 2.8
52.6
50.9 1.80
44.8
8.3 70.7 9.8
52.6
50.9 1.75
44.9
2.75
34.4
4.7 96.9 2.4
46.5
43.8 2.51
35.2
5.1 89.2 8.6
46.3
43.8 2.44
35.5
2.76
38.5
5.1 98.5 2.4
51.7
47.9 2.53
39.3
5.5 90.1 8.6
51.7
47.9 2.45
39.5
2.79
39.1
5.1 98.7 2.4
53.4
48.6 2.55
39.9
5.6 90.3 8.6
53.4
48.6 2.47
40.2
3.60
29.9
3.4 116.3 2.2
48.1
42.2 3.29
31.0
3.8 108.9 7.7
48.0
42.2 3.20
31.3
3.62
33.7
3.7 117.8 2.2
52.7
46.1 3.31
34.8
4.1 109.8 7.7
52.6
46.1 3.21
35.1
3.65
34.3
3.8 118.1 2.2
54.1
46.8 3.34
35.4
4.1 109.9 7.7
54.1
46.8 3.24
35.7
4.49
25.6
2.7 135.9 2.0
49.6
40.9 4.11
26.9
2.9 128.7 7.1
49.5
40.9 3.98
27.3
4.51
29.4
2.9 137.4 2.0
53.5
44.8 4.13
30.7
3.2 129.5 7.1
53.4
44.8 4.00
31.2
4.56
29.8
2.9 137.7 2.0
54.8
45.4 4.16
31.2
3.2 129.7 7.1
54.8
45.4 4.04
31.6

COP Load Load


LWT WPD
Ft
Head
6.1 65.2 16.2
6.7 65.7 16.2
6.7 65.8 16.2
4.1 85.0 14.1
4.5 85.5 14.1
4.5 85.6 14.1
3.0 104.8 12.7
3.3 105.3 12.7
3.3 105.4 12.7
2.4 124.7 11.7
2.6 125.2 11.7
2.6 125.2 11.7
6.8 66.1 16.2
7.4 66.7 16.2
7.4 66.8 16.2
4.6 85.8 14.1
4.9 86.4 14.1
5.0 86.5 14.1
3.4 105.6 12.7
3.6 106.2 12.7
3.7 106.3 12.7
2.6 125.5 11.7
2.8 126.0 11.7
2.9 126.1 11.7
7.3 66.9 16.2
8.0 67.5 16.2
8.0 67.6 16.2
4.9 86.6 14.1
5.4 87.2 14.1
5.4 87.3 14.1
3.6 106.4 12.7
3.9 107.0 12.7
4.0 107.1 12.7
2.8 126.2 11.7
3.1 126.8 11.7
3.1 126.9 11.7
7.8 67.6 16.2
8.5 68.3 16.2
8.5 68.4 16.2
5.3 87.3 14.1
5.7 87.9 14.1
5.8 88.1 14.1
3.9 107.0 12.7
4.2 107.7 12.7
4.2 107.8 12.7
3.0 126.8 11.7
3.3 127.5 11.7
3.3 127.6 11.7

WSHP-PRC009-EN

Performance Data
WPWD 042-Heating
Table P-6: 042 Heating Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Heat
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
70.0 60.0
5.2
2.6
53.4
49.9
70.0 60.0
9.5
9.1
60.0
54.5
70.0 60.0 12.1
15.1
62.0
55.3
70.0 80.0
5.2
2.6
55.4
47.6
70.0 80.0
9.5
9.1
61.1
52.0
70.0 80.0 12.1
15.1
62.9
52.8
70.0 100.0 5.2
2.6
57.2
45.8
70.0 100.0 9.5
9.1
62.1
50.1
70.0 100.0 12.1
15.1
63.7
50.8
70.0 120.0 5.2
2.6
58.9
44.5
70.0 120.0 9.5
9.1
63.1
48.6
70.0 120.0 12.1
15.1
64.5
49.3
80.0 60.0
5.2
2.4
62.0
53.6
80.0 60.0
9.5
8.6
69.1
58.6
80.0 60.0 12.1
14.1
71.3
59.4
80.0 80.0
5.2
2.4
64.1
51.1
80.0 80.0
9.5
8.6
70.3
55.9
80.0 80.0 12.1
14.1
72.3
56.7
80.0 100.0 5.2
2.4
66.0
49.2
80.0 100.0 9.5
8.6
71.4
53.8
80.0 100.0 12.1
14.1
73.1
54.6
80.0 120.0 5.2
2.4
67.8
47.8
80.0 120.0 9.5
8.6
72.4
52.2
80.0 120.0 12.1
14.1
73.9
53.0

WSHP-PRC009-EN

5.2
GPM
Load 9.5
GPM
Power Heat COP Load Load Sourc Heat Power Heat
kW
Of
LWT WPD
e
Cap
kW
Of
Absorb
Ft
LWT Mbtuh
Absorb
Head
2.00 43.1
7.3 79.2 2.8
53.2 49.9 1.83 43.7
2.01 47.6
7.9 81.0 2.8
59.8 54.5 1.84 48.2
2.03 48.4
8.0 81.3 2.8
61.9 55.3 1.85 49.0
2.83 37.9
4.9 98.4 2.4
55.1 47.6 2.59 38.8
2.84 42.3
5.4 100.1 2.4
60.9 52.0 2.60 43.1
2.87 43.0
5.4 100.4 2.4
62.7 52.8 2.62 43.9
3.71 33.1
3.6 117.7 2.2
56.8 45.8 3.39 34.2
3.73 37.4
3.9 119.4 2.2
61.9 50.1 3.41 38.5
3.76 38.0
4.0 119.7 2.2
63.5 50.8 3.44 39.1
4.62 28.7
2.8 137.3 2.0
58.4 44.5 4.22 30.1
4.64 32.8
3.1 138.9 2.0
62.8 48.6 4.25 34.1
4.69 33.3
3.1 139.2 2.0
64.3 49.3 4.28 34.7
2.05 46.6
7.7 80.6 2.8
61.8 53.6 1.87 47.2
2.06 51.6
8.3 82.6 2.8
69.0 58.6 1.88 52.2
2.08 52.3
8.4 82.9 2.8
71.2 59.4 1.90 52.9
2.90 41.2
5.2 99.7 2.4
63.8 51.1 2.65 42.1
2.92 45.9
5.6 101.6 2.4
70.1 55.9 2.67 46.8
2.94 46.7
5.7 101.9 2.4
72.1 56.7 2.69 47.5
3.80 36.2
3.8 119.0 2.2
65.6 49.2 3.47 37.4
3.82 40.8
4.1 120.8 2.2
71.2 53.8 3.49 41.9
3.85 41.5
4.2 121.1 2.2
72.9 54.6 3.52 42.6
4.74 31.6
3.0 138.6 2.0
67.3 47.8 4.33 33.0
4.76 36.0
3.2 140.3 2.0
72.1 52.2 4.35 37.4
4.80 36.6
3.2 140.6 2.0
73.7 53.0 4.39 38.0

Load 12.1 GPM


COP Load Load Source Heat Power Heat
LWT WPD LWT
Cap
kW
Of
Ft
Mbtuh
Absorb
Head
8.0 70.5 9.8
53.1
49.9 1.77 43.9
8.7 71.5 9.8
59.8
54.5 1.78 48.4
8.8 71.6 9.8
61.9
55.3 1.80 49.2
5.4 90.1 8.6
55.0
47.6 2.51 39.0
5.9 91.0 8.6
60.8
52.0 2.52 43.4
5.9 91.1 8.6
62.7
52.8 2.55 44.1
4.0 109.7 7.7
56.7
45.8 3.29 34.6
4.3 110.6 7.7
61.8
50.1 3.30 38.8
4.3 110.8 7.7
63.5
50.8 3.33 39.4
3.1 129.5 7.1
58.2
44.5 4.10 30.5
3.4 130.4 7.1
62.7
48.6 4.12 34.5
3.4 130.5 7.1
64.2
49.3 4.16 35.1
8.4 71.3 9.8
61.7
53.6 1.82 47.4
9.1 72.3 9.8
68.9
58.6 1.83 52.4
9.2 72.5 9.8
71.2
59.4 1.84 53.1
5.6 90.8 8.6
63.7
51.1 2.57 42.3
6.1 91.8 8.6
70.1
55.9 2.59 47.1
6.2 92.0 8.6
72.1
56.7 2.61 47.8
4.2 110.4 7.7
65.5
49.2 3.37 37.7
4.5 111.4 7.7
71.1
53.8 3.39 42.2
4.5 111.6 7.7
72.9
54.6 3.42 42.9
3.2 130.2 7.1
67.1
47.8 4.20 33.5
3.5 131.1 7.1
72.0
52.2 4.22 37.8
3.5 131.3 7.1
73.6
53.0 4.26 38.5

COP Load Load


LWT WPD
Ft
Head
8.3 68.3 16.2
9.0 69.0 16.2
9.0 69.1 16.2
5.6 87.9 14.1
6.0 88.6 14.1
6.1 88.8 14.1
4.1 107.6 12.7
4.4 108.3 12.7
4.5 108.5 12.7
3.2 127.4 11.7
3.5 128.1 11.7
3.5 128.2 11.7
8.6 68.9 16.2
9.4 69.7 16.2
9.5 69.8 16.2
5.8 88.5 14.1
6.3 89.3 14.1
6.4 89.4 14.1
4.3 108.2 12.7
4.6 109.0 12.7
4.7 109.1 12.7
3.3 128.0 11.7
3.6 128.7 11.7
3.6 128.9 11.7

29

Performance Data
WPWD 048-Cooling
Table P-7: 048 Cooling Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Cool
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
50.0
45.0
6.0
4.1
64.3
37.1
50.0
45.0
11.0
14.5
57.8
37.5
50.0
45.0
14.0
23.9
56.2
37.8
50.0
53.6
6.0
4.1
65.6
40.7
50.0
53.6
11.0
14.5
58.5
41.1
50.0
53.6
14.0
23.9
56.7
41.4
50.0
65.0
6.0
4.1
67.1
45.4
50.0
65.0
11.0
14.5
59.4
46.0
50.0
65.0
14.0
23.9
57.4
46.3
50.0
75.0
6.0
4.1
68.6
49.6
50.0
75.0
11.0
14.5
60.2
50.2
50.0
75.0
14.0
23.9
58.0
50.5
60.0
45.0
6.0
3.8
74.1
35.7
60.0
45.0
11.0
13.3
67.7
36.2
60.0
45.0
14.0
21.9
66.1
36.4
60.0
53.6
6.0
3.8
75.4
39.3
60.0
53.6
11.0
13.3
68.4
39.8
60.0
53.6
14.0
21.9
66.6
40.1
60.0
65.0
6.0
3.8
77.0
44.1
60.0
65.0
11.0
13.3
69.3
44.6
60.0
65.0
14.0
21.9
67.3
44.9
60.0
75.0
6.0
3.8
78.4
48.3
60.0
75.0
11.0
13.3
70.1
48.8
60.0
75.0
14.0
21.9
67.9
49.2
70.0
45.0
6.0
3.5
84.0
34.5
70.0
45.0
11.0
12.3
77.6
34.9
70.0
45.0
14.0
20.4
76.0
35.1
70.0
53.6
6.0
3.5
85.3
38.1
70.0
53.6
11.0
12.3
78.3
38.5
70.0
53.6
14.0
20.4
76.6
38.8
70.0
65.0
6.0
3.5
86.9
42.8
70.0
65.0
11.0
12.3
79.2
43.3
70.0
65.0
14.0
20.4
77.3
43.6
70.0
75.0
6.0
3.5
88.3
47.0
70.0
75.0
11.0
12.3
80.0
47.6
70.0
75.0
14.0
20.4
77.9
47.9
80.0
45.0
6.0
3.3
94.0
33.3
80.0
45.0
11.0
11.6
87.6
33.6
80.0
45.0
14.0
19.1
86.0
33.9
80.0
53.6
6.0
3.3
95.2
36.8
80.0
53.6
11.0
11.6
88.3
37.3
80.0
53.6
14.0
19.1
86.5
37.5
80.0
65.0
6.0
3.3
96.9
41.6
80.0
65.0
11.0
11.6
89.2
42.1
80.0
65.0
14.0
19.1
87.2
42.4
80.0
75.0
6.0
3.3
98.3
45.8
80.0
75.0
11.0
11.6
90.0
46.3
80.0
75.0
14.0
19.1
87.9
46.6

30

6.0 GPM
Load 11.0
Power Heat EER Load Load Source Cool Power
kW
Of
LWT WPD LWT
Cap
kW
Reject
Ft
Mbtuh
Head
1.72 43.0 21.6 32.6
4.3
65.6
40.8 1.76
1.61 43.0 23.3 32.5
4.3
58.5
41.3 1.64
1.58 43.2 23.9 32.4
4.3
56.7
41.6 1.61
1.75 46.7 23.3
40
4.0
66.9
44.7 1.78
1.63 46.7 25.2 39.9
4.0
59.3
45.3 1.66
1.60 46.9 25.9 39.8
4.0
57.3
45.6 1.63
1.77 51.4 25.6 49.8
3.6
68.7
50.0 1.81
1.66 51.7 27.7 49.6
3.6
60.3
50.6 1.69
1.63 51.9 28.4 49.5
3.6
58.1
50.9 1.66
1.79 55.7 27.7 58.4
3.4
70.3
54.6 1.83
1.68 55.9 29.9 58.2
3.4
61.1
55.2 1.71
1.64 56.1 30.8 58.1
3.4
58.8
55.6 1.68
1.95 42.4 18.3 33.1
4.3
75.4
39.3 1.99
1.82 42.4 19.9 32.9
4.3
68.4
39.8 1.86
1.79 42.5 20.3 32.9
4.3
66.6
40.1 1.82
1.98 46.1 19.8 40.5
4.0
76.7
43.3 2.02
1.85 46.1 21.5 40.3
4.0
69.2
43.8 1.89
1.82 46.3 22.0 40.2
4.0
67.2
44.1 1.85
2.01 51.0 21.9 50.3
3.6
78.5
48.5 2.05
1.88 51.0 23.7 50.1
3.6
70.1
49.1 1.91
1.84 51.2 24.4
50
3.6
68.0
49.4 1.88
2.03 55.2 23.8 58.9
3.4
80.1
53.1 2.07
1.90 55.3 25.7 58.7
3.4
71.0
53.7 1.94
1.86 55.6 26.5 58.6
3.4
68.7
54.1 1.90
2.21 42.0 15.6 33.5
4.3
85.2
37.9 2.26
2.07 42.0 16.9 33.4
4.3
78.3
38.4 2.11
2.03 42.0 17.3 33.3
4.3
76.5
38.6 2.07
2.25 45.8 16.9 40.9
4.0
86.6
41.9 2.29
2.10 45.7 18.3 40.8
4.0
79.1
42.4 2.14
2.06 45.8 18.8 40.7
4.0
77.1
42.7 2.10
2.28 50.6 18.8 50.7
3.6
88.4
47.1 2.32
2.13 50.6 20.3 50.6
3.6
80.0
47.7 2.17
2.09 50.7 20.9 50.5
3.6
77.9
48.0 2.13
2.31 54.9 20.3 59.3
3.4
89.9
51.7 2.35
2.15 54.9 22.1 59.1
3.4
80.9
52.3 2.20
2.11 55.1 22.7
59
3.4
78.6
52.7 2.15
2.51 41.9 13.3 33.9
4.3
95.1
36.6 2.56
2.34 41.6 14.4 33.8
4.3
88.2
37.0 2.39
2.30 41.8 14.7 33.7
4.3
86.5
37.3 2.35
2.55 45.5 14.4 41.3
4.0
96.5
40.5 2.60
2.38 45.4 15.7 41.2
4.0
89.0
41.0 2.42
2.33 45.5 16.1 41.1
4.0
87.1
41.3 2.38
2.58 50.4 16.1 51.1
3.6
98.3
45.8 2.64
2.41 50.3 17.5
51
3.6
90.0
46.3 2.46
2.37 50.5 17.9 50.9
3.6
87.9
46.6 2.41
2.61 54.7 17.5 59.7
3.4
99.9
50.4 2.67
2.44 54.6 19.0 59.5
3.4
90.9
51.0 2.49
2.40 54.8 19.4 59.4
3.4
88.5
51.3 2.44

GPM
Load 14.0
Heat EER Load Load Source Cool Power
Of
LWT WPD LWT
Cap
kW
Reject
Ft
Mbtuh
Head
46.8 23.2 37.6 15.2
66.1
42.2 1.76
46.9 25.2 37.5 15.2
58.8
42.7 1.65
47.1 25.8 37.4 15.2
56.9
43.0 1.62
50.8 25.1 45.5 14.0
67.5
46.3 1.79
51.0 27.3 45.4 14.0
59.6
46.9 1.67
51.2 28.0 45.3 14.0
57.5
47.2 1.64
56.2 27.6 55.9 12.8
69.3
51.7 1.82
56.4 29.9 55.8 12.8
60.6
52.3 1.69
56.6 30.7 55.7 12.8
58.3
52.7 1.66
60.9 29.8 65.0 12.0
70.9
56.5 1.84
61.0 32.3 64.9 12.0
61.5
57.2 1.71
61.3 33.1 64.9 12.0
59.0
57.6 1.68
46.1 19.7 37.9 15.2
75.8
40.7 2.00
46.2 21.4 37.8 15.2
68.7
41.2 1.87
46.3 22.0 37.7 15.2
66.8
41.5 1.83
50.2 21.4 45.7 14.0
77.2
44.8 2.03
50.3 23.2 45.6 14.0
69.4
45.3 1.89
50.4 23.8 45.6 14.0
67.4
45.6 1.86
55.5 23.7 56.2 12.8
79.1
50.2 2.06
55.6 25.7 56.1 12.8
70.4
50.8 1.92
55.8 26.3 56.0 12.8
68.2
51.2 1.89
60.2 25.7 65.3 12.0
80.7
55.0 2.08
60.3 27.7 65.2 12.0
71.3
55.6 1.94
60.6 28.5 65.1 12.0
68.9
56.0 1.91
45.6 16.8 38.1 15.2
85.7
39.3 2.27
45.6 18.2 38.0 15.2
78.5
39.7 2.12
45.7 18.6 38.0 15.2
76.7
40.0 2.08
49.7 18.3 46.0 14.0
87.1
43.3 2.30
49.7 19.8 45.9 14.0
79.3
43.9 2.14
49.9 20.3 45.8 14.0
77.4
44.2 2.10
55.0 20.3 56.4 12.8
89.0
48.8 2.33
55.1 22.0 56.3 12.8
80.3
49.3 2.18
55.3 22.5 56.3 12.8
78.2
49.7 2.14
59.7 22.0 65.6 12.0
90.6
53.5 2.36
59.8 23.8 65.5 12.0
81.2
54.2 2.20
60.0 24.5 65.4 12.0
78.9
54.5 2.16
45.3 14.3 38.3 15.2
95.6
37.9 2.57
45.2 15.5 38.3 15.2
88.5
38.3 2.40
45.3 15.9 38.2 15.2
86.7
38.6 2.35
49.4 15.6 46.2 14.0
97.0
42.0 2.60
49.3 16.9 46.1 14.0
89.2
42.4 2.43
49.4 17.4 46.1 14.0
87.3
42.7 2.39
54.8 17.3 56.7 12.8
98.9
47.4 2.64
54.7 18.8 56.6 12.8
90.3
47.9 2.47
54.8 19.3 56.5 12.8
88.1
48.3 2.42
59.5 18.9 65.8 12.0 100.5 52.1 2.67
59.5 20.5 65.7 12.0
91.2
52.7 2.50
59.6 21.0 65.7 12.0
88.8
53.1 2.45

GPM
Heat EER Load Load
Of
LWT WPD
Reject
Ft
Head
48.2 24.0 39.0 25.1
48.3 25.9 38.9 25.1
48.5 26.5 38.9 25.1
52.4 25.9 47.0 23.1
52.6 28.1 46.9 23.1
52.8 28.8 46.9 23.1
57.9 28.4 57.6 21.1
58.1 30.9 57.5 21.1
58.4 31.7 57.5 21.1
62.8 30.7 66.9 19.7
63.0 33.5 66.8 19.7
63.3 34.3 66.8 19.7
47.5 20.4 39.2 25.1
47.6 22.0 39.1 25.1
47.8 22.7 39.1 25.1
51.7 22.1 47.2 23.1
51.8 24.0 47.1 23.1
52.0 24.5 47.1 23.1
57.2 24.4 57.8 21.1
57.4 26.5 57.7 21.1
57.7 27.1 57.7 21.1
62.1 26.4 67.1 19.7
62.2 28.7 67.0 19.7
62.5 29.3 67.0 19.7
47.1 17.3 39.4 25.1
46.9 18.7 39.3 25.1
47.1 19.2 39.3 25.1
51.2 18.8 47.4 23.1
51.2 20.5 47.3 23.1
51.4 21.0 47.3 23.1
56.8 20.9 58.0 21.1
56.7 22.6 57.9 21.1
57.0 23.2 57.9 21.1
61.6 22.7 67.3 19.7
61.7 24.6 67.2 19.7
61.9 25.2 67.2 19.7
46.7 14.7 39.6 25.1
46.5 16.0 39.5 25.1
46.6 16.4 39.5 25.1
50.9 16.2 47.6 23.1
50.7 17.4 47.5 23.1
50.9 17.9 47.5 23.1
56.4 18.0 58.2 21.1
56.3 19.4 58.1 21.1
56.6 20.0 58.1 21.1
61.2 19.5 67.5 19.7
61.2 21.1 67.5 19.7
61.5 21.7 67.4 19.7

WSHP-PRC009-EN

Performance Data
WPWD 048-Cooling
Table P-7: 048 Cooling Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source Source


EWT EWT GPM WPD LWT
Ft
Head
90.0 45.0
6.0
3.1
104.0
90.0 45.0 11.0
11.0
97.6
90.0 45.0 14.0
18.1
96.0
90.0 53.6
6.0
3.1
105.3
90.0 53.6 11.0
11.0
98.3
90.0 53.6 14.0
18.1
96.5
90.0 65.0
6.0
3.1
106.9
90.0 65.0 11.0
11.0
99.2
90.0 65.0 14.0
18.1
97.2
90.0 75.0
6.0
3.1
108.3
90.0 75.0 11.0
11.0 100.0
90.0 75.0 14.0
18.1
97.9
100.0 45.0
6.0
3.0
114.1
100.0 45.0 11.0
10.4 107.6
100.0 45.0 14.0
17.2 106.0
100.0 53.6
6.0
3.0
115.4
100.0 53.6 11.0
10.4 108.3
100.0 53.6 14.0
17.2 106.5
100.0 65.0
6.0
3.0
117.0
100.0 65.0 11.0
10.4 109.2
100.0 65.0 14.0
17.2 107.3
100.0 75.0
6.0
3.0
118.5
100.0 75.0 11.0
10.4 110.0
100.0 75.0 14.0
17.2 107.9
110.0 45.0
6.0
2.8
124.3
110.0 45.0 11.0
10.0 117.7
110.0 45.0 14.0
16.5 116.0
110.0 53.6
6.0
2.8
125.5
110.0 53.6 11.0
10.0 118.4
110.0 53.6 14.0
16.5 116.6
110.0 65.0
6.0
2.8
127.2
110.0 65.0 11.0
10.0 119.3
110.0 65.0 14.0
16.5 117.3
110.0 75.0
6.0
2.8
128.6
110.0 75.0 11.0
10.0 120.1
110.0 75.0 14.0
16.5 117.9
120.0 45.0
6.0
2.7
134.5
120.0 45.0 11.0
9.6
127.8
120.0 45.0 14.0
15.8 126.1
120.0 53.6
6.0
2.7
135.8
120.0 53.6 11.0
9.6
128.5
120.0 53.6 14.0
15.8 126.7
120.0 65.0
6.0
2.7
137.5
120.0 65.0 11.0
9.6
129.4
120.0 65.0 14.0
15.8 127.4
120.0 75.0
6.0
2.7
138.9
120.0 75.0 11.0
9.6
130.2
120.0 75.0 14.0
15.8 128.1

WSHP-PRC009-EN

Load 6.0 GPM


Load 11.0
Cool Power Heat EER Load Load Source Cool Power
Cap
kW
Of
LWT WPD LWT
Cap
kW
Mbtuh
Reject
Ft
Mbtuh
Head
32.1 2.85 41.8 11.3 34.3 4.3
105.1 35.3 2.90
32.5 2.66 41.6 12.2 34.2 4.3
98.2
35.7 2.71
32.7 2.61 41.6 12.5 34.1 4.3
96.5
36.0 2.66
35.7 2.89 45.6 12.4 41.7 4.0
106.5 39.3 2.94
36.1 2.69 45.3 13.4 41.6 4.0
99.0
39.7 2.75
36.3 2.64 45.3 13.8 41.5 4.0
97.1
40.0 2.70
40.4 2.93 50.4 13.8 51.5 3.6
108.3 44.5 2.99
40.9 2.74 50.3 14.9 51.4 3.6
100.0 45.0 2.79
41.2 2.69 50.4 15.3 51.3 3.6
97.9
45.3 2.74
44.6 2.96 54.7 15.1 60.1 3.4
109.9 49.1 3.02
45.1 2.77 54.6 16.3 59.9 3.4
100.8 49.7 2.82
45.4 2.72 54.7 16.7 59.8 3.4
98.5
50.0 2.77
31.0 3.23 42.0 9.6 34.7 4.3
115.2 34.1 3.29
31.3 3.01 41.6 10.4 34.6 4.3
108.2 34.5 3.07
31.6 2.96 41.7 10.7 34.5 4.3
106.5 34.7 3.01
34.6 3.27 45.8 10.6 42.1 4.0
116.6 38.0 3.33
35.0 3.05 45.4 11.5 41.9 4.0
109.0 38.5 3.11
35.2 3.00 45.4 11.7 41.9 4.0
107.1 38.7 3.06
39.3 3.32 50.6 11.8 51.9 3.6
118.4 43.3 3.39
39.8 3.10 50.4 12.8 51.7 3.6
110.0 43.8 3.16
40.1 3.04 50.5 13.2 51.6 3.6
107.9 44.1 3.10
43.5 3.36 55.0 12.9 60.5 3.4
120.0 47.9 3.42
44.0 3.14 54.7 14.0 60.3 3.4
110.9 48.4 3.20
44.3 3.08 54.8 14.4 60.2 3.4
108.6 48.8 3.14
29.9 3.66 42.4 8.2
35
4.3
125.3 32.9 3.73
30.3 3.41 41.9 8.9 34.9 4.3
118.3 33.3 3.48
30.5 3.35 41.9 9.1 34.8 4.3
116.5 33.5 3.42
33.5 3.71 46.2 9.0 42.4 4.0
126.8 36.9 3.78
33.9 3.46 45.7 9.8 42.3 4.0
119.1 37.3 3.53
34.1 3.40 45.7 10.0 42.2 4.0
117.1 37.6 3.46
38.3 3.77 51.2 10.2 52.2 3.6
128.6 42.1 3.84
38.7 3.52 50.7 11.0 52.1 3.6
120.1 42.6 3.58
39.0 3.45 50.8 11.3 52
3.6
117.9 42.9 3.52
42.4 3.81 55.4 11.1 60.8 3.4
130.1 46.7 3.88
42.9 3.56 55.1 12.1 60.7 3.4
120.9 47.2 3.63
43.2 3.49 55.1 12.4 60.6 3.4
118.6 47.6 3.56
28.9 4.15 43.1 7.0 35.4 4.3
135.6 31.8 4.23
29.2 3.87 42.4 7.5 35.3 4.3
128.4 32.2 3.95
29.4 3.80 42.4 7.7 35.2 4.3
126.6 32.4 3.87
32.5 4.20 46.8 7.7 42.8 4.0
137.0 35.8 4.29
32.9 3.93 46.3 8.4 42.6 4.0
129.2 36.2 4.00
33.1 3.85 46.2 8.6 42.6 4.0
127.2 36.4 3.93
37.3 4.27 51.9 8.7 52.6 3.6
138.9 41.0 4.35
37.7 3.99 51.3 9.4 52.4 3.6
130.2 41.5 4.06
38.0 3.91 51.3 9.7 52.3 3.6
128.0 41.8 3.99
41.4 4.32 56.1 9.6 61.2 3.4
140.4 45.6 4.40
41.9 4.03 55.7 10.4 61
3.4
131.1 46.1 4.11
42.2 3.96 55.7 10.7 60.9 3.4
128.7 46.4 4.03

GPM
Load
Heat EER Load Load Source Cool
Of
LWT WPD LWT
Cap
Reject
Ft
Mbtuh
Head
45.2 12.2 38.6 15.2 105.5 36.5
45.0 13.2 38.5 15.2
98.5
37.0
45.1 13.5 38.5 15.2
96.6
37.2
49.3 13.4 46.5 14.0 107.0 40.6
49.1 14.4 46.4 14.0
99.2
41.1
49.2 14.8 46.3 14.0
97.3
41.4
54.7 14.9 56.9 12.8 108.9 46.1
54.5 16.1 56.8 12.8 100.3 46.6
54.7 16.5 56.8 12.8
98.1
46.9
59.4 16.3 66.1 12.0 110.5 50.8
59.3 17.6 65.9 12.0 101.2 51.4
59.5 18.1 65.9 12.0
98.8
51.8
45.3 10.4 38.8 15.2 115.6 35.3
45.0 11.2 38.7 15.2 108.5 35.7
45.0 11.5 38.7 15.2 106.6 35.9
49.4 11.4 46.7 14.0 117.0 39.4
49.1 12.4 46.6 14.0 109.2 39.8
49.1 12.6 46.6 14.0 107.3 40.1
54.9 12.8 57.1 12.8 118.9 44.8
54.6 13.9 57.0 12.8 110.3 45.3
54.7 14.2 57.0 12.8 108.1 45.6
59.6 14.0 66.3 12.0 120.5 49.5
59.3 15.1 66.2 12.0 111.2 50.1
59.5 15.5 66.1 12.0 108.8 50.5
45.6 8.8 39.0 15.2 125.8 34.1
45.2 9.6 38.9 15.2 118.5 34.5
45.2 9.8 38.9 15.2 116.7 34.7
49.8 9.8 46.9 14.0 127.2 38.2
49.4 10.6 46.8 14.0 119.3 38.6
49.4 10.9 46.8 14.0 117.3 38.9
55.2 11.0 57.3 12.8 129.1 43.6
54.8 11.9 57.2 12.8 120.3 44.1
54.9 12.2 57.2 12.8 118.1 44.4
59.9 12.0 66.5 12.0 130.7 48.3
59.6 13.0 66.4 12.0 121.2 48.9
59.8 13.4 66.3 12.0 118.9 49.2
46.2 7.5 39.2 15.2 136.0 32.9
45.7 8.2 39.1 15.2 128.6 33.3
45.6 8.4 39.1 15.2 126.8 33.5
50.4 8.3 47.1 14.0 137.4 37.0
49.9 9.1 47.0 14.0 129.4 37.4
49.8 9.3 47.0 14.0 127.4 37.7
55.9 9.4 57.5 12.8 139.3 42.4
55.4 10.2 57.4 12.8 130.4 42.9
55.4 10.5 57.4 12.8 128.2 43.2
60.6 10.4 66.7 12.0 141.0 47.2
60.1 11.2 66.6 12.0 131.4 47.7
60.2 11.5 66.5 12.0 128.9 48.1

14.0 GPM
Power Heat EER Load Load
kW
Of
LWT WPD
Reject
Ft
Head
2.91 46.4 12.5 39.8 25.1
2.72 46.3 13.6 39.7 25.1
2.67 46.3 13.9 39.7 25.1
2.95 50.7 13.8 47.8 23.1
2.76 50.5 14.9 47.7 23.1
2.70 50.6 15.3 47.7 23.1
3.00 56.3 15.4 58.4 21.1
2.80 56.2 16.6 58.3 21.1
2.75 56.3 17.1 58.3 21.1
3.03 61.1 16.8 67.7 19.7
2.83 61.1 18.2 67.6 19.7
2.78 61.3 18.6 67.6 19.7
3.30 46.6 10.7 40.0 25.1
3.08 46.2 11.6 39.9 25.1
3.02 46.2 11.9 39.9 25.1
3.35 50.8 11.8 48.0 23.1
3.12 50.5 12.8 47.9 23.1
3.07 50.6 13.1 47.9 23.1
3.40 56.4 13.2 58.6 21.1
3.17 56.1 14.3 58.5 21.1
3.11 56.2 14.7 58.5 21.1
3.44 61.2 14.4 67.9 19.7
3.21 61.1 15.6 67.8 19.7
3.15 61.3 16.0 67.8 19.7
3.74 46.9 9.1 40.1 25.1
3.49 46.4 9.9 40.1 25.1
3.43 46.4 10.1 40.0 25.1
3.79 51.1 10.1 48.1 23.1
3.54 50.7 10.9 48.1 23.1
3.48 50.8 11.2 48.0 23.1
3.85 56.7 11.3 58.8 21.1
3.60 56.4 12.3 58.7 21.1
3.53 56.5 12.6 58.7 21.1
3.90 61.6 12.4 68.1 19.7
3.64 61.3 13.4 68.0 19.7
3.57 61.4 13.8 68.0 19.7
4.24 47.4 7.8 40.3 25.1
3.96 46.8 8.4 40.2 25.1
3.89 46.8 8.6 40.2 25.1
4.30 51.7 8.6 48.3 23.1
4.01 51.1 9.3 48.3 23.1
3.94 51.2 9.6 48.2 23.1
4.37 57.3 9.7 58.9 21.1
4.08 56.8 10.5 58.9 21.1
4.00 56.9 10.8 58.8 21.1
4.42 62.3 10.7 68.2 19.7
4.12 61.8 11.6 68.2 19.7
4.05 61.9 11.9 68.1 19.7

31

Performance Data
WPWD 048-Heating
Table P-8: 048 Heating Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Heat
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
30.0 60.0
6.0
5.2
21.0
34.2
30.0 60.0 11.0
18.4
24.5
37.4
30.0 60.0 14.0
30.4
25.6
37.9
30.0 80.0
6.0
5.2
22.4
32.6
30.0 80.0 11.0
18.4
25.3
35.6
30.0 80.0 14.0
30.4
26.2
36.2
30.0 100.0 6.0
5.2
23.7
31.4
30.0 100.0 11.0
18.4
26.1
34.3
30.0 100.0 14.0
30.4
26.9
34.8
30.0 120.0 6.0
5.2
25.1
30.4
30.0 120.0 11.0
18.4
26.8
33.3
30.0 120.0 14.0
30.4
27.4
33.8
40.0 60.0
6.0
4.6
29.1
39.9
40.0 60.0 11.0
16.1
33.4
43.6
40.0 60.0 14.0
26.5
34.7
44.3
40.0 80.0
6.0
4.6
30.7
38.0
40.0 80.0 11.0
16.1
34.3
41.6
40.0 80.0 14.0
26.5
35.4
42.2
40.0 100.0 6.0
4.6
32.2
36.6
40.0 100.0 11.0
16.1
35.1
40.1
40.0 100.0 14.0
26.5
36.1
40.7
40.0 120.0 6.0
4.6
33.7
35.5
40.0 120.0 11.0
16.1
36.0
38.9
40.0 120.0 14.0
26.5
36.8
39.4
50.0 60.0
6.0
4.1
37.5
45.0
50.0 60.0 11.0
14.5
42.4
49.2
50.0 60.0 14.0
23.9
44.0
49.9
50.0 80.0
6.0
4.1
39.2
42.9
50.0 80.0 11.0
14.5
43.4
46.9
50.0 80.0 14.0
23.9
44.7
47.6
50.0 100.0 6.0
4.1
40.9
41.3
50.0 100.0 11.0
14.5
44.3
45.2
50.0 100.0 14.0
23.9
45.5
45.8
50.0 120.0 6.0
4.1
42.4
40.1
50.0 120.0 11.0
14.5
45.2
43.8
50.0 120.0 14.0
23.9
46.2
44.5
60.0 60.0
6.0
3.8
46.0
49.6
60.0 60.0 11.0
13.3
51.5
54.3
60.0 60.0 14.0
21.9
53.3
55.0
60.0 80.0
6.0
3.8
47.8
47.3
60.0 80.0 11.0
13.3
52.6
51.7
60.0 80.0 14.0
21.9
54.1
52.5
60.0 100.0 6.0
3.8
49.6
45.5
60.0 100.0 11.0
13.3
53.6
49.8
60.0 100.0 14.0
21.9
54.9
50.5
60.0 120.0 6.0
3.8
51.2
44.2
60.0 120.0 11.0
13.3
54.5
48.3
60.0 120.0 14.0
21.9
55.6
49.0

32

6.0
GPM
Load
Power Heat COP Load Load Source Heat
kW
Of
LWT WPD LWT Cap
Absorb
Ft
Mbtuh
Head
2.07
27.1 4.8 71.4
3.8
20.7 34.2
2.08
30.3 5.3 72.5
3.8
24.4 37.4
2.10
30.7 5.3 72.6
3.8
25.5 37.9
2.85
22.9 3.4 90.9
3.3
22.1 32.6
2.86
25.8 3.6 91.9
3.3
25.1 35.6
2.89
26.3 3.7 92.1
3.3
26.1 36.2
3.69
18.8 2.5 110.5 3.0
23.4 31.4
3.71
21.6 2.7 111.5 3.0
25.9 34.3
3.74
22.0 2.7 111.7 3.0
26.7 34.8
4.60
14.7 1.9 130.3 2.7
24.7 30.4
4.63
17.5 2.1 131.2 2.7
26.6 33.3
4.67
17.9 2.1 131.4 2.7
27.3 33.8
2.13
32.6 5.5 73.3
3.8
28.9 39.9
2.14
36.3 6.0 74.5
3.8
33.3 43.6
2.16
36.9 6.0 74.8
3.8
34.6 44.3
2.99
27.8 3.7 92.7
3.3
30.4 38.0
3.00
31.4 4.1 93.9
3.3
34.1 41.6
3.03
31.9 4.1 94.1
3.3
35.3 42.2
3.91
23.3 2.7 112.3 3.0
31.9 36.6
3.93
26.7 3.0 113.5 3.0
34.9 40.1
3.97
27.2 3.0 113.7 3.0
36.0 40.7
4.90
18.8 2.1 132.0 2.7
33.3 35.5
4.93
22.1 2.3 133.1 2.7
35.7 38.9
4.97
22.4 2.3 133.3 2.7
36.6 39.4
2.20
37.5 6.0 75.0
3.8
37.3 45.0
2.21
41.7 6.5 76.4
3.8
42.3 49.2
2.23
42.3 6.6 76.6
3.8
43.9 49.9
3.10
32.3 4.1 94.3
3.3
38.9 42.9
3.11
36.3 4.4 95.7
3.3
43.2 46.9
3.14
36.9 4.4 95.9
3.3
44.6 47.6
4.07
27.4 3.0 113.9 3.0
40.5 41.3
4.09
31.2 3.2 115.2 3.0
44.1 45.2
4.13
31.7 3.2 115.4 3.0
45.3 45.8
5.11
22.7 2.3 133.5 2.7
41.9 40.1
5.13
26.3 2.5 134.8 2.7
44.9 43.8
5.18
26.8 2.5 135.0 2.7
45.9 44.5
2.25
41.9 6.5 76.5
3.8
45.8 49.6
2.26
46.6 7.0 78.1
3.8
51.4 54.3
2.28
47.2 7.1 78.3
3.8
53.2 55.0
3.18
36.5 4.4 95.8
3.3
47.5 47.3
3.20
40.8 4.7 97.3
3.3
52.4 51.7
3.23
41.5 4.8 97.6
3.3
53.9 52.5
4.19
31.2 3.2 115.3 3.0
49.2 45.5
4.21
35.4 3.5 116.7 3.0
53.3 49.8
4.24
36.0 3.5 116.9 3.0
54.7 50.5
5.25
26.3 2.5 134.9 2.7
50.7 44.2
5.28
30.3 2.7 136.3 2.7
54.2 48.3
5.33
30.8 2.7 136.5 2.7
55.4 49.0

11.0 GPM
Load
Power Heat COP Load Load Source Heat
kW
Of
LWT WPD LWT Cap
Absorb
Ft
Mbtuh
Head
1.89 27.8 5.3 66.2 13.3 20.7 34.2
1.90 30.9 5.8 66.8 13.3 24.3 37.4
1.92 31.4 5.8 66.9 13.3 25.5 37.9
2.60 23.7 3.7 85.9 11.6
22.0 32.6
2.62 26.7 4.0 86.5 11.6
25.1 35.6
2.64 27.2 4.0 86.6 11.6
26.1 36.2
3.37 19.9 2.7 105.7 10.4 23.3 31.4
3.39 22.7 3.0 106.3 10.4 25.8 34.3
3.42 23.1 3.0 106.4 10.4 26.6 34.8
4.21 16.0 2.1 125.6 9.6
24.5 30.4
4.23 18.9 2.3 126.1 9.6
26.5 33.3
4.27 19.2 2.3 126.2 9.6
27.2 33.8
1.95 33.2 6.0 67.3 13.3 28.8 39.9
1.96 36.9 6.5 67.9 13.3 33.3 43.6
1.98 37.5 6.6 68.1 13.3 34.6 44.3
2.73 28.7 4.1 86.9 11.6
30.3 38.0
2.74 32.3 4.4 87.6 11.6
34.1 41.6
2.77 32.8 4.5 87.7 11.6
35.3 42.2
3.57 24.4 3.0 106.7 10.4 31.7 36.6
3.59 27.9 3.3 107.3 10.4 34.9 40.1
3.62 28.3 3.3 107.4 10.4 35.9 40.7
4.48 20.2 2.3 126.5 9.6
33.1 35.5
4.50 23.5 2.5 127.2 9.6
35.6 38.9
4.54 23.9 2.5 127.2 9.6
36.5 39.4
2.01 38.1 6.6 68.2 13.3 37.2 45.0
2.02 42.3 7.1 69.0 13.3 42.3 49.2
2.03 43.0 7.2 69.1 13.3 43.8 49.9
2.83 33.2 4.4 87.8 11.6
38.8 42.9
2.85 37.2 4.8 88.6 11.6
43.2 46.9
2.87 37.8 4.9 88.7 11.6
44.6 47.6
3.72 28.6 3.3 107.6 10.4 40.3 41.3
3.74 32.4 3.5 108.3 10.4 44.0 45.2
3.77 32.9 3.6 108.4 10.4 45.2 45.8
4.67 24.2 2.5 127.4 9.6
41.8 40.1
4.69 27.8 2.7 128.1 9.6
44.9 43.8
4.73 28.4 2.8 128.2 9.6
45.9 44.5
2.06 42.6 7.1 69.0 13.3 45.7 49.6
2.07 47.2 7.7 69.9 13.3 51.4 54.3
2.08 47.9 7.7 70.0 13.3 53.1 55.0
2.91 37.4 4.8 88.6 11.6
47.4 47.3
2.92 41.7 5.2 89.4 11.6
52.4 51.7
2.95 42.4 5.2 89.6 11.6
53.9 52.5
3.82 32.5 3.5 108.3 10.4 49.1 45.5
3.84 36.7 3.8 109.1 10.4 53.3 49.8
3.88 37.3 3.8 109.2 10.4 54.6 50.5
4.80 27.8 2.7 128.1 9.6
50.6 44.2
4.83 31.8 2.9 128.9 9.6
54.1 48.3
4.87 32.4 2.9 129.0 9.6
55.3 49.0

14.0 GPM
Power Heat COP Load Load
kW
Of
LWT WPD
Absorb
Ft
Head
1.83 28.0 5.5 64.9 21.9
1.84 31.1 6.0 65.3 21.9
1.86 31.6 6.0 65.4 21.9
2.52 24.0 3.8 84.7 19.1
2.54 26.9 4.1 85.1 19.1
2.56 27.5 4.1 85.2 19.1
3.27 20.2 2.8 104.5 17.2
3.29 23.1 3.1 104.9 17.2
3.32 23.5 3.1 105.0 17.2
4.08 16.5 2.2 124.4 15.8
4.10 19.3 2.4 124.8 15.8
4.14 19.7 2.4 124.9 15.8
1.89 33.5 6.2 65.7 21.9
1.90 37.1 6.7 66.2 21.9
1.92 37.8 6.8 66.3 21.9
2.65 29.0 4.2 85.4 19.1
2.66 32.5 4.6 86.0 19.1
2.69 33.0 4.6 86.0 19.1
3.47 24.8 3.1 105.3 17.2
3.48 28.2 3.4 105.8 17.2
3.52 28.7 3.4 105.9 17.2
4.34 20.7 2.4 125.1 15.8
4.37 24.0 2.6 125.6 15.8
4.41 24.4 2.6 125.7 15.8
1.95 38.3 6.8 66.4 21.9
1.96 42.5 7.4 67.0 21.9
1.97 43.2 7.4 67.1 21.9
2.75 33.5 4.6 86.1 19.1
2.76 37.5 5.0 86.7 19.1
2.79 38.1 5.0 86.8 19.1
3.61 29.0 3.4 105.9 17.2
3.63 32.8 3.6 106.5 17.2
3.66 33.3 3.7 106.6 17.2
4.53 24.6 2.6 125.8 15.8
4.55 28.3 2.8 126.3 15.8
4.59 28.8 2.8 126.4 15.8
1.99 42.8 7.3 67.1 21.9
2.00 47.5 8.0 67.8 21.9
2.02 48.1 8.0 67.9 21.9
2.82 37.7 4.9 86.8 19.1
2.84 42.0 5.3 87.4 19.1
2.86 42.7 5.4 87.5 19.1
3.71 32.8 3.6 106.5 17.2
3.73 37.1 3.9 107.2 17.2
3.76 37.7 3.9 107.3 17.2
4.66 28.3 2.8 126.4 15.8
4.68 32.3 3.0 127.0 15.8
4.72 32.9 3.0 127.1 15.8

WSHP-PRC009-EN

Performance Data
WPWD 048-Heating
Table P-8: 048 Heating Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Heat
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
70.0 60.0
6.0
3.5
54.6
53.9
70.0 60.0 11.0
12.3
60.7
58.9
70.0 60.0 14.0
20.4
62.6
59.8
70.0 80.0
6.0
3.5
56.6
51.3
70.0 80.0 11.0
12.3
61.8
56.2
70.0 80.0 14.0
20.4
63.5
57.0
70.0 100.0 6.0
3.5
58.3
49.5
70.0 100.0 11.0
12.3
62.8
54.1
70.0 100.0 14.0
20.4
64.3
54.9
70.0 120.0 6.0
3.5
60.1
48.0
70.0 120.0 11.0
12.3
63.8
52.5
70.0 120.0 14.0
20.4
65.0
53.3
80.0 60.0
6.0
3.3
63.3
57.9
80.0 60.0 11.0
11.6
69.9
63.3
80.0 60.0 14.0
19.1
71.9
64.2
80.0 80.0
6.0
3.3
65.3
55.2
80.0 80.0 11.0
11.6
71.1
60.3
80.0 80.0 14.0
19.1
72.9
61.2
80.0 100.0 6.0
3.3
67.2
53.1
80.0 100.0 11.0
11.6
72.1
58.1
80.0 100.0 14.0
19.1
73.7
59.0
80.0 120.0 6.0
3.3
69.0
51.5
80.0 120.0 11.0
11.6
73.1
56.4
80.0 120.0 14.0
19.1
74.5
57.2

WSHP-PRC009-EN

6.0
GPM
Load
Power Heat COP Load Load Source Heat
kW
Of
LWT WPD LWT Cap
Absorb
Ft
Mbtuh
Head
2.29
46.1 6.9 78.0
3.8
54.4 53.9
2.31
51.0 7.5 79.6
3.8
60.6 58.9
2.33
51.9 7.5 79.9
3.8
62.5 59.8
3.25
40.2 4.6 97.2
3.3
56.2 51.3
3.27
45.0 5.0 98.8
3.3
61.6 56.2
3.30
45.7 5.1 99.1
3.3
63.3 57.0
4.27
34.9 3.4 116.6 3.0
57.9 49.5
4.30
39.4 3.7 118.2 3.0
62.6 54.1
4.33
40.1 3.7 118.4 3.0
64.1 54.9
5.37
29.7 2.6 136.2 2.7
59.5 48.0
5.39
34.1 2.9 137.7 2.7
63.5 52.5
5.44
34.7 2.9 138.0 2.7
64.8 53.3
2.33
50.0 7.3 79.3
3.8
63.1 57.9
2.34
55.3 7.9 81.1
3.8
69.8 63.3
2.36
56.2 8.0 81.4
3.8
71.9 64.2
3.30
43.9 4.9 98.5
3.3
65.0 55.2
3.32
49.0 5.3 100.2 3.3
70.9 60.3
3.35
49.8 5.4 100.5 3.3
72.7 61.2
4.34
38.3 3.6 117.8 3.0
66.8 53.1
4.37
43.2 3.9 119.5 3.0
71.9 58.1
4.41
44.0 3.9 119.8 3.0
73.5 59.0
5.45
32.9 2.8 137.4 2.7
68.5 51.5
5.48
37.7 3.0 139.0 2.7
72.8 56.4
5.53
38.3 3.0 139.3 2.7
74.3 57.2

11.0 GPM
Load 14.0
Power Heat COP Load Load Source Heat Power
kW
Of
LWT WPD LWT
Cap
kW
Absorb
Ft
Mbtuh
Head
2.10
46.7 7.5 69.8 13.3
54.3
53.9 2.03
2.11
51.7 8.2 70.7 13.3
60.5
58.9 2.04
2.13
52.5 8.2 70.9 13.3
62.4
59.8 2.06
2.97
41.2 5.1 89.4 11.6
56.1
51.3 2.88
2.99
46.0 5.5 90.2 11.6
61.6
56.2 2.90
3.01
46.7 5.5 90.4 11.6
63.3
57.0 2.92
3.91
36.2 3.7 109.1 10.4
57.8
49.5 3.79
3.93
40.7 4.0 109.9 10.4
62.5
54.1 3.81
3.96
41.4 4.1 110.0 10.4
64.0
54.9 3.84
4.90
31.3 2.9 128.8 9.6
59.4
48.0 4.76
4.93
35.7 3.1 129.7 9.6
63.4
52.5 4.78
4.97
36.3 3.1 129.8 9.6
64.7
53.3 4.82
2.13
50.6 8.0 70.5 13.3
63.0
57.9 2.07
2.14
56.0 8.7 71.5 13.3
69.8
63.3 2.08
2.16
56.8 8.7 71.7 13.3
71.8
64.2 2.09
3.02
44.9 5.4 90.1 11.6
64.9
55.2 2.93
3.03
50.0 5.8 91.0 11.6
70.8
60.3 2.94
3.06
50.8 5.9 91.2 11.6
72.7
61.2 2.97
3.97
39.6 3.9 109.7 10.4
66.6
53.1 3.85
3.99
44.5 4.3 110.6 10.4
71.8
58.1 3.87
4.03
45.3 4.3 110.8 10.4
73.5
59.0 3.91
4.98
34.5 3.0 129.5 9.6
68.3
51.5 4.83
5.01
39.3 3.3 130.4 9.6
72.7
56.4 4.86
5.05
40.0 3.3 130.5 9.6
74.2
57.2 4.90

GPM
Heat COP Load Load
Of
LWT WPD
Absorb
Ft
Head
47.0 7.8 67.7 21.9
51.9 8.5 68.4 21.9
52.8 8.5 68.5 21.9
41.5 5.2 87.4 19.1
46.3 5.7 88.1 19.1
47.0 5.7 88.2 19.1
36.6 3.8 107.1 17.2
41.1 4.2 107.8 17.2
41.8 4.2 107.9 17.2
31.8 3.0 126.9 15.8
36.2 3.2 127.6 15.8
36.9 3.2 127.7 15.8
50.8 8.2 68.3 21.9
56.2 8.9 69.0 21.9
57.1 9.0 69.2 21.9
45.2 5.5 87.9 19.1
50.3 6.0 88.6 19.1
51.1 6.0 88.8 19.1
40.0 4.0 107.6 17.2
44.9 4.4 108.4 17.2
45.7 4.4 108.5 17.2
35.0 3.1 127.4 15.8
39.8 3.4 128.2 15.8
40.5 3.4 128.3 15.8

33

Performance Data
WPWD 060-Cooling
Table P-9: 060 Cooling Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Cool
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
50.0 45.0
7.6
6.7
64.5
47.4
50.0 45.0 14.0
23.9
57.9
47.9
50.0 45.0 17.8
39.3
56.2
48.3
50.0 53.6
7.6
6.7
65.7
52.0
50.0 53.6 14.0
23.9
58.5
52.6
50.0 53.6 17.8
39.3
56.8
53.0
50.0 65.0
7.6
6.7
67.4
58.1
50.0 65.0 14.0
23.9
59.4
58.7
50.0 65.0 17.8
39.3
57.5
59.2
50.0 75.0
7.6
6.7
68.8
63.4
50.0 75.0 14.0
23.9
60.2
64.1
50.0 75.0 17.8
39.3
58.1
64.6
60.0 45.0
7.6
6.2
74.3
45.7
60.0 45.0 14.0
21.9
67.7
46.2
60.0 45.0 17.8
36.1
66.1
46.5
60.0 53.6
7.6
6.2
75.5
50.3
60.0 53.6 14.0
21.9
68.4
50.9
60.0 53.6 17.8
36.1
66.7
51.2
60.0 65.0
7.6
6.2
77.2
56.4
60.0 65.0 14.0
21.9
69.3
57.0
60.0 65.0 17.8
36.1
67.4
57.4
60.0 75.0
7.6
6.2
78.6
61.7
60.0 75.0 14.0
21.9
70.1
62.4
60.0 75.0 17.8
36.1
68.0
62.9
70.0 45.0
7.6
5.7
84.2
44.1
70.0 45.0 14.0
20.4
77.7
44.6
70.0 45.0 17.8
33.6
76.1
44.9
70.0 53.6
7.6
5.7
85.4
48.6
70.0 53.6 14.0
20.4
78.4
49.2
70.0 53.6 17.8
33.6
76.6
49.6
70.0 65.0
7.6
5.7
87.1
54.7
70.0 65.0 14.0
20.4
79.3
55.4
70.0 65.0 17.8
33.6
77.3
55.8
70.0 75.0
7.6
5.7
88.5
60.1
70.0 75.0 14.0
20.4
80.1
60.8
70.0 75.0 17.8
33.6
77.9
61.2
80.0 45.0
7.6
5.4
94.1
42.5
80.0 45.0 14.0
19.1
87.6
43.0
80.0 45.0 17.8
31.5
86.0
43.3
80.0 53.6
7.6
5.4
95.4
47.1
80.0 53.6 14.0
19.1
88.3
47.6
80.0 53.6 17.8
31.5
86.6
48.0
80.0 65.0
7.6
5.4
97.1
53.2
80.0 65.0 14.0
19.1
89.2
53.8
80.0 65.0 17.8
31.5
87.3
54.2
80.0 75.0
7.6
5.4
98.5
58.5
80.0 75.0 14.0
19.1
90.0
59.2
80.0 75.0 17.8
31.5
87.9
59.6

34

7.6 GPM
Power Heat EER
kW
Of
Reject
2.24
2.09
2.05
2.27
2.12
2.08
2.32
2.17
2.13
2.36
2.20
2.16
2.51
2.35
2.30
2.55
2.38
2.34
2.60
2.43
2.38
2.64
2.46
2.42
2.85
2.66
2.61
2.89
2.69
2.64
2.94
2.74
2.69
2.98
2.78
2.73
3.25
3.03
2.97
3.28
3.06
3.01
3.33
3.11
3.05
3.37
3.15
3.09

55.1
55.0
55.3
59.8
59.8
60.1
66.0
66.1
66.5
71.5
71.6
72.0
54.3
54.2
54.4
59.0
59.0
59.2
65.3
65.3
65.5
70.7
70.8
71.2
53.8
53.7
53.8
58.5
58.4
58.6
64.7
64.8
65.0
70.3
70.3
70.5
53.6
53.3
53.4
58.3
58.0
58.3
64.6
64.4
64.6
70.0
70.0
70.2

21.2
22.9
23.6
22.9
24.8
25.5
25.0
27.1
27.8
26.9
29.1
29.9
18.2
19.7
20.2
19.7
21.4
21.9
21.7
23.5
24.1
23.4
25.4
26.0
15.5
16.8
17.2
16.8
18.3
18.8
18.6
20.2
20.7
20.2
21.9
22.4
13.1
14.2
14.6
14.4
15.6
15.9
16.0
17.3
17.8
17.4
18.8
19.3

Load
Load Load Source Cool
LWT WPD LWT
Cap
Ft
Mbtuh
Head
32.5
7.1
65.8
52.2
32.4
7.1
58.6
52.8
32.3
7.1
56.8
53.1
39.9
6.5
67.1
57.2
39.8
6.5
59.3
57.9
39.7
6.5
57.4
58.3
49.7
5.9
68.9
63.9
49.5
5.9
60.3
64.7
49.4
5.9
58.1
65.1
58.3
5.5
70.5
69.8
58.1
5.5
61.2
70.6
58
5.5
58.8
71.1
33
7.1
75.5
50.3
32.8
7.1
68.4
50.9
32.8
7.1
66.7
51.2
40.4
6.5
76.9
55.4
40.2
6.5
69.2
56.0
40.1
6.5
67.3
56.4
50.1
5.9
78.7
62.1
50
5.9
70.2
62.8
49.9
5.9
68.0
63.2
58.7
5.5
80.3
67.9
58.5
5.5
71.1
68.7
58.4
5.5
68.7
69.2
33.4
7.1
85.4
48.5
33.3
7.1
78.4
49.1
33.2
7.1
76.6
49.4
40.8
6.5
86.8
53.6
40.7
6.5
79.1
54.2
40.5
6.5
77.2
54.6
50.6
5.9
88.6
60.3
50.4
5.9
80.1
61.0
50.3
5.9
78.0
61.4
59.1
5.5
90.2
66.1
59
5.5
81.0
66.9
58.9
5.5
78.7
67.4
33.8
7.1
95.3
46.8
33.7
7.1
88.3
47.3
33.6
7.1
86.5
47.7
41.2
6.5
96.7
51.8
41.1
6.5
89.1
52.5
41
6.5
87.1
52.8
51
5.9
98.5
58.5
50.8
5.9
90.0
59.2
50.7
5.9
87.9
59.6
59.6
5.5
100.1 64.4
59.4
5.5
90.9
65.2
59.3
5.5
88.6
65.6

14.0 GPM
Power Heat EER
kW
Of
Reject
2.28
2.13
2.09
2.32
2.16
2.12
2.37
2.21
2.17
2.41
2.25
2.21
2.56
2.39
2.35
2.60
2.43
2.38
2.65
2.47
2.43
2.69
2.51
2.47
2.91
2.71
2.66
2.94
2.75
2.70
2.99
2.79
2.74
3.04
2.83
2.78
3.31
3.09
3.03
3.35
3.12
3.07
3.40
3.17
3.11
3.44
3.21
3.15

60.0
60.1
60.2
65.1
65.3
65.5
72.0
72.2
72.5
78.0
78.3
78.6
59.0
59.1
59.2
64.3
64.3
64.5
71.1
71.2
71.5
77.1
77.3
77.6
58.4
58.4
58.5
63.6
63.6
63.8
70.5
70.5
70.8
76.5
76.6
76.9
58.1
57.9
58.0
63.2
63.2
63.3
70.1
70.0
70.2
76.1
76.2
76.4

22.9
24.8
25.4
24.7
26.8
27.5
27.0
29.3
30.0
29.0
31.4
32.2
19.6
21.3
21.8
21.3
23.0
23.7
23.4
25.4
26.0
25.2
27.4
28.0
16.7
18.1
18.6
18.2
19.7
20.2
20.2
21.9
22.4
21.7
23.6
24.2
14.1
15.3
15.7
15.5
16.8
17.2
17.2
18.7
19.2
18.7
20.3
20.8

Load
Load Load Source Cool
LWT WPD LWT
Cap
Ft
Mbtuh
Head
37.5 25.1
66.3 54.0
37.5 25.1
58.8 54.6
37.4 25.1
57.0 55.0
45.4 23.1
67.7 59.2
45.3 23.1
59.6 59.9
45.3 23.1
57.6 60.3
55.9 21.1
69.6 66.2
55.7 21.1
60.6 66.9
55.7 21.1
58.4 67.4
65.0 19.7
71.2 72.2
64.9 19.7
61.5 73.1
64.8 19.7
59.1 73.6
37.8 25.1
76.0 52.1
37.7 25.1
68.7 52.7
37.7 25.1
66.9 53.0
45.7 23.1
77.4 57.3
45.6 23.1
69.5 58.0
45.5 23.1
67.5 58.4
56.1 21.1
79.3 64.2
56.0 21.1
70.5 65.0
56.0 21.1
68.3 65.4
65.3 19.7
80.9 70.3
65.2 19.7
71.4 71.1
65.1 19.7
69.0 71.6
38.1 25.1
85.9 50.2
38.0 25.1
78.6 50.8
37.9 25.1
76.8 51.1
45.9 23.1
87.3 55.4
45.9 23.1
79.4 56.1
45.8 23.1
77.4 56.5
56.4 21.1
89.1 62.4
56.3 21.1
80.4 63.1
56.2 21.1
78.2 63.5
65.5 19.7
90.8 68.4
65.4 19.7
81.3 69.3
65.3 19.7
78.9 69.7
38.3 25.1
95.8 48.4
38.2 25.1
88.5 49.0
38.2 25.1
86.7 49.3
46.2 23.1
97.2 53.6
46.1 23.1
89.3 54.3
46.1 23.1
87.3 54.7
56.6 21.1
99.1 60.6
56.5 21.1
90.3 61.3
56.5 21.1
88.2 61.7
65.8 19.7 100.7 66.7
65.7 19.7
91.2 67.5
65.6 19.7
88.9 67.9

17.8 GPM
Power Heat EER Load Load
kW
Of
LWT WPD
Reject
Ft
Head
2.29 61.8 23.6 38.9 41.3
2.13 61.9 25.6 38.9 41.3
2.09 62.1 26.3 38.8 41.3
2.32 67.1 25.5 46.9 38.1
2.17 67.3 27.6 46.9 38.1
2.13 67.6 28.3 46.8 38.1
2.37 74.3 27.9 57.6 34.7
2.22 74.5 30.1 57.5 34.7
2.17 74.8 31.1 57.4 34.7
2.42 80.5 29.8 66.9 32.5
2.26 80.8 32.3 66.8 32.5
2.21 81.1 33.3 66.7 32.5
2.57 60.9 20.3 39.1 41.3
2.40 60.9 22.0 39.1 41.3
2.36 61.1 22.5 39.0 41.3
2.61 66.2 22.0 47.2 38.1
2.44 66.3 23.8 47.1 38.1
2.39 66.6 24.4 47.0 38.1
2.66 73.3 24.1 57.8 34.7
2.48 73.5 26.2 57.7 34.7
2.44 73.7 26.8 57.6 34.7
2.70 79.5 26.0 67.1 32.5
2.52 79.7 28.2 67.0 32.5
2.47 80.0 29.0 66.9 32.5
2.92 60.2 17.2 39.4 41.3
2.72 60.1 18.7 39.3 41.3
2.67 60.2 19.1 39.3 41.3
2.95 65.5 18.8 47.4 38.1
2.76 65.5 20.3 47.3 38.1
2.71 65.8 20.8 47.3 38.1
3.00 72.6 20.8 58.0 34.7
2.80 72.7 22.5 57.9 34.7
2.75 72.9 23.1 57.9 34.7
3.05 78.8 22.4 67.3 32.5
2.84 79.0 24.4 67.2 32.5
2.79 79.2 25.0 67.2 32.5
3.32 59.7 14.6 39.6 41.3
3.10 59.6 15.8 39.5 41.3
3.04 59.7 16.2 39.5 41.3
3.36 65.1 16.0 47.6 38.1
3.13 65.0 17.3 47.5 38.1
3.08 65.2 17.8 47.5 38.1
3.41 72.2 17.8 58.2 34.7
3.18 72.2 19.3 58.1 34.7
3.12 72.4 19.8 58.1 34.7
3.45 78.5 19.3 67.5 32.5
3.22 78.5 21.0 67.4 32.5
3.16 78.7 21.5 67.4 32.5

WSHP-PRC009-EN

Performance Data
WPWD 060-Cooling
Table P-9: 060 Cooling Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
90.0 45.0
7.6
5.1
90.0 45.0 14.0
18.1
90.0 45.0 17.8
29.8
90.0 53.6
7.6
5.1
90.0 53.6 14.0
18.1
90.0 53.6 17.8
29.8
90.0 65.0
7.6
5.1
90.0 65.0 14.0
18.1
90.0 65.0 17.8
29.8
90.0 75.0
7.6
5.1
90.0 75.0 14.0
18.1
90.0 75.0 17.8
29.8
100.0 45.0
7.6
4.8
100.0 45.0 14.0
17.2
100.0 45.0 17.8
28.4
100.0 53.6
7.6
4.8
100.0 53.6 14.0
17.2
100.0 53.6 17.8
28.4
100.0 65.0
7.6
4.8
100.0 65.0 14.0
17.2
100.0 65.0 17.8
28.4
100.0 75.0
7.6
4.8
100.0 75.0 14.0
17.2
100.0 75.0 17.8
28.4
110.0 45.0
7.6
4.6
110.0 45.0 14.0
16.5
110.0 45.0 17.8
27.1
110.0 53.6
7.6
4.6
110.0 53.6 14.0
16.5
110.0 53.6 17.8
27.1
110.0 65.0
7.6
4.6
110.0 65.0 14.0
16.5
110.0 65.0 17.8
27.1
110.0 75.0
7.6
4.6
110.0 75.0 14.0
16.5
110.0 75.0 17.8
27.1
120.0 45.0
7.6
4.4
120.0 45.0 14.0
15.8
120.0 45.0 17.8
26.0
120.0 53.6
7.6
4.4
120.0 53.6 14.0
15.8
120.0 53.6 17.8
26.0
120.0 65.0
7.6
4.4
120.0 65.0 14.0
15.8
120.0 65.0 17.8
26.0
120.0 75.0
7.6
4.4
120.0 75.0 14.0
15.8
120.0 75.0 17.8
26.0

WSHP-PRC009-EN

Load 7.6 GPM


Source Cool Power Heat EER
LWT
Cap
kW
Of
Mbtuh
Reject
104.2
97.6
96.0
105.4
98.3
96.6
107.1
99.2
97.3
108.5
100.0
97.9
114.3
107.7
106.1
115.6
108.4
106.6
117.2
109.3
107.3
118.7
110.1
107.9
124.5
117.8
116.1
125.7
118.5
116.7
127.4
119.4
117.4
128.9
120.2
118.0
134.8
127.9
126.2
136.0
128.6
126.7
137.7
129.5
127.5
139.1
130.3
128.1

41.0
41.5
41.8
45.6
46.1
46.4
51.7
52.3
52.7
57.0
57.7
58.1
39.6
40.1
40.3
44.2
44.7
45.0
50.3
50.9
51.2
55.6
56.3
56.6
38.2
38.7
39.0
42.8
43.3
43.6
48.9
49.5
49.8
54.3
54.9
55.3
37.0
37.4
37.7
41.6
42.0
42.3
47.6
48.2
48.5
53.0
53.6
54.0

3.70
3.45
3.39
3.74
3.49
3.42
3.79
3.53
3.47
3.83
3.57
3.51
4.21
3.93
3.86
4.25
3.97
3.89
4.30
4.01
3.94
4.34
4.05
3.98
4.78
4.46
4.38
4.82
4.50
4.42
4.87
4.54
4.46
4.91
4.58
4.50
5.41
5.05
4.96
5.45
5.09
4.99
5.50
5.13
5.04
5.54
5.17
5.07

53.6
53.3
53.4
58.4
58.0
58.1
64.6
64.4
64.5
70.1
69.9
70.1
54.0
53.5
53.5
58.7
58.3
58.3
65.0
64.6
64.7
70.4
70.1
70.2
54.5
53.9
54.0
59.3
58.7
58.7
65.5
65.0
65.0
71.1
70.5
70.7
55.5
54.6
54.6
60.2
59.4
59.3
66.4
65.7
65.7
71.9
71.3
71.3

11.1
12.0
12.3
12.2
13.2
13.6
13.6
14.8
15.2
14.9
16.2
16.6
9.4
10.2
10.4
10.4
11.3
11.6
11.7
12.7
13.0
12.8
13.9
14.2
8.0
8.7
8.9
8.9
9.6
9.9
10.0
10.9
11.2
11.1
12.0
12.3
6.8
7.4
7.6
7.6
8.3
8.5
8.7
9.4
9.6
9.6
10.4
10.7

Load Load
LWT WPD
Ft
Head
34.2
7.1
34.1
7.1
34
7.1
41.6
6.5
41.5
6.5
41.4
6.5
51.4
5.9
51.2
5.9
51.1
5.9
60
5.5
59.8
5.5
59.7
5.5
34.6
7.1
34.4
7.1
34.4
7.1
42
6.5
41.8
6.5
41.8
6.5
51.7
5.9
51.6
5.9
51.5
5.9
60.3
5.5
60.2
5.5
60.1
5.5
34.9
7.1
34.8
7.1
34.7
7.1
42.3
6.5
42.2
6.5
42.1
6.5
52.1
5.9
52
5.9
51.9
5.9
60.7
5.5
60.5
5.5
60.4
5.5
35.3
7.1
35.2
7.1
35.1
7.1
42.7
6.5
42.5
6.5
42.5
6.5
52.5
5.9
52.3
5.9
52.2
5.9
61
5.5
60.9
5.5
60.8
5.5

Load 14.0 GPM


Load 17.8
Source Cool Power Heat EER Load Load Source Cool Power
LWT
Cap
kW
Of
LWT WPD LWT
Cap
kW
Mbtuh
Reject
Ft
Mbtuh
Head
105.3 45.1 3.77 58.0 12.0 38.6 25.1 105.8 46.7 3.79
98.3
45.7 3.52 57.7 13.0 38.5 25.1
98.5
47.3 3.53
96.5
46.0 3.46 57.8 13.3 38.4 25.1
96.7
47.6 3.47
106.7 50.2 3.81 63.2 13.2 46.4 23.1 107.2 52.0 3.82
99.0
50.8 3.56 63.0 14.3 46.3 23.1
99.3
52.6 3.57
97.1
51.1 3.49 63.0 14.6 46.3 23.1
97.3
52.9 3.50
108.5 56.9 3.86 70.1 14.7 56.9 21.1 109.1 58.9 3.87
100.0 57.6 3.60 69.9 16.0 56.8 21.1 100.3 59.6 3.61
97.9
58.0 3.53 70.1 16.4 56.7 21.1
98.1
60.0 3.55
110.1 62.8 3.90 76.1 16.1 66.0 19.7 110.7 65.0 3.92
100.9 63.5 3.64 75.9 17.4 65.9 19.7 101.2 65.7 3.65
98.6
64.0 3.57 76.2 17.9 65.8 19.7
98.9
66.2 3.59
115.4 43.6 4.30 58.3 10.1 38.8 25.1 115.8 45.1 4.31
108.3 44.1 4.01 57.8 11.0 38.7 25.1 108.5 45.6 4.02
106.5 44.4 3.93 57.8 11.3 38.7 25.1 106.7 46.0 3.95
116.8 48.6 4.33 63.4 11.2 46.7 23.1 117.3 50.3 4.35
109.1 49.2 4.04 63.0 12.2 46.6 23.1 109.3 50.9 4.06
107.1 49.6 3.97 63.2 12.5 46.5 23.1 107.3 51.3 3.98
118.6 55.3 4.38 70.3 12.6 57.1 21.1 119.2 57.3 4.40
110.1 56.0 4.09 70.0 13.7 57.0 21.1 110.3 57.9 4.10
107.9 56.4 4.01 70.1 14.1 56.9 21.1 108.2 58.3 4.03
120.2 61.2 4.43 76.3 13.8 66.2 19.7 120.8 63.4 4.44
110.9 61.9 4.13 76.0 15.0 66.1 19.7 111.2 64.1 4.14
108.6 62.4 4.05 76.2 15.4 66.1 19.7 108.9 64.5 4.07
125.6 42.1 4.88 58.8
8.6 39.0 25.1 126.0 43.6 4.89
118.4 42.6 4.55 58.1
9.4 38.9 25.1 118.6 44.1 4.57
116.6 42.9 4.47 58.2
9.6 38.9 25.1 116.8 44.4 4.48
127.0 47.2 4.92 64.0
9.6 46.9 23.1 127.4 48.8 4.93
119.1 47.7 4.59 63.4 10.4 46.8 23.1 119.4 49.4 4.60
117.2 48.0 4.50 63.4 10.7 46.7 23.1 117.4 49.7 4.52
128.8 53.9 4.96 70.8 10.9 57.3 21.1 129.3 55.7 4.98
120.1 54.5 4.63 70.3 11.8 57.2 21.1 120.4 56.4 4.65
118.0 54.9 4.55 70.4 12.1 57.1 21.1 118.2 56.8 4.56
130.4 59.7 5.01 76.8 11.9 66.5 19.7 131.0 61.8 5.02
121.0 60.4 4.67 76.3 12.9 66.4 19.7 121.3 62.5 4.69
118.7 60.9 4.59 76.6 13.3 66.3 19.7 118.9 63.0 4.60
135.8 40.7 5.52 59.5
7.4 39.2 25.1 136.2 42.1 5.54
128.5 41.2 5.15 58.8
8.0 39.1 25.1 128.7 42.6 5.17
126.7 41.5 5.06 58.8
8.2 39.1 25.1 126.8 42.9 5.07
137.2 45.7 5.56 64.7
8.2 47.1 23.1 137.7 47.3 5.58
129.3 46.3 5.19 64.0
8.9 47.0 23.1 129.5 47.9 5.20
127.3 46.6 5.09 64.0
9.2 46.9 23.1 127.5 48.2 5.11
139.1 52.5 5.61 71.7
9.4 57.5 21.1 139.6 54.3 5.63
130.3 53.1 5.23 71.0 10.2 57.4 21.1 130.5 54.9 5.25
128.1 53.4 5.13 70.9 10.4 57.4 21.1 128.3 55.3 5.15
140.7 58.3 5.65 77.6 10.3 66.7 19.7 141.2 60.4 5.67
131.1 59.0 5.27 77.0 11.2 66.6 19.7 131.4 61.1 5.29
128.8 59.4 5.17 77.1 11.5 66.5 19.7 129.0 61.5 5.19

GPM
Heat EER Load Load
Of
LWT WPD
Reject
Ft
Head
59.6 12.3 39.8 41.3
59.4 13.4 39.7 41.3
59.4 13.7 39.7 41.3
65.0 13.6 47.8 38.1
64.8 14.7 47.7 38.1
64.9 15.1 47.7 38.1
72.1 15.2 58.4 34.7
71.9 16.5 58.3 34.7
72.1 16.9 58.3 34.7
78.4 16.6 67.7 32.5
78.2 18.0 67.6 32.5
78.5 18.4 67.5 32.5
59.8 10.5 39.9 41.3
59.3 11.3 39.9 41.3
59.5 11.6 39.8 41.3
65.2 11.6 47.9 38.1
64.8 12.5 47.9 38.1
64.9 12.9 47.8 38.1
72.3 13.0 58.6 34.7
71.9 14.1 58.5 34.7
72.1 14.5 58.4 34.7
78.6 14.3 67.9 32.5
78.2 15.5 67.8 32.5
78.4 15.8 67.7 32.5
60.3 8.9 40.1 41.3
59.7 9.6 40.0 41.3
59.7 9.9 40.0 41.3
65.6 9.9 48.1 38.1
65.1 10.7 48.0 38.1
65.1 11.0 48.0 38.1
72.7 11.2 58.7 34.7
72.3 12.1 58.7 34.7
72.4 12.5 58.6 34.7
78.9 12.3 68.0 32.5
78.5 13.3 68.0 32.5
78.7 13.7 67.9 32.5
61.0 7.6 40.3 41.3
60.3 8.2 40.2 41.3
60.2 8.5 40.2 41.3
66.3 8.5 48.3 38.1
65.7 9.2 48.2 38.1
65.6 9.4 48.2 38.1
73.5 9.6 58.9 34.7
72.8 10.5 58.8 34.7
72.9 10.7 58.8 34.7
79.8 10.7 68.2 32.5
79.2 11.6 68.1 32.5
79.2 11.8 68.1 32.5

35

Performance Data
WPWD 060-Heating
Table P-10: 060 Heating Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Heat
EWT EWT GPM WPD LWT Cap
Ft
Mbtuh
Head
30.0 60.0
7.6
8.5
20.6 45.5
30.0 60.0 14.0
30.4
24.3 49.9
30.0 60.0 17.8
50.0
25.4 50.6
30.0 80.0
7.6
8.5
21.9 43.4
30.0 80.0 14.0
30.4
25.0 47.5
30.0 80.0 17.8
50.0
26.0 48.2
30.0 100.0 7.6
8.5
23.2 41.8
30.0 100.0 14.0
30.4
25.7 45.8
30.0 100.0 17.8
50.0
26.6 46.5
30.0 120.0 7.6
8.5
24.7 40.6
30.0 120.0 14.0
30.4
26.6 44.4
30.0 120.0 17.8
50.0
27.2 45.1
40.0 60.0
7.6
7.5
28.8 53.1
40.0 60.0 14.0
26.5
33.2 58.2
40.0 60.0 17.8
43.7
34.6 59.0
40.0 80.0
7.6
7.5
30.2 50.6
40.0 80.0 14.0
26.5
34.0 55.5
40.0 80.0 17.8
43.7
35.2 56.3
40.0 100.0 7.6
7.5
31.6 48.8
40.0 100.0 14.0
26.5
34.8 53.4
40.0 100.0 17.8
43.7
35.8 54.2
40.0 120.0 7.6
7.5
33.2 47.3
40.0 120.0 14.0
26.5
35.7 51.8
40.0 120.0 17.8
43.7
36.5 52.6
50.0 60.0
7.6
6.7
37.1 59.9
50.0 60.0 14.0
23.9
42.2 65.6
50.0 60.0 17.8
39.3
43.8 66.5
50.0 80.0
7.6
6.7
38.6 57.1
50.0 80.0 14.0
23.9
43.0 62.5
50.0 80.0 17.8
39.3
44.4 63.4
50.0 100.0 7.6
6.7
40.1 55.0
50.0 100.0 14.0
23.9
43.9 60.2
50.0 100.0 17.8
39.3
45.1 61.1
50.0 120.0 7.6
6.7
41.8 53.4
50.0 120.0 14.0
23.9
44.9 58.4
50.0 120.0 17.8
39.3
45.9 59.3
60.0 60.0
7.6
6.2
45.6 66.0
60.0 60.0 14.0
21.9
51.3 72.3
60.0 60.0 17.8
36.1
53.0 73.4
60.0 80.0
7.6
6.2
47.1 63.0
60.0 80.0 14.0
21.9
52.2 68.9
60.0 80.0 17.8
36.1
53.8 69.9
60.0 100.0 7.6
6.2
48.8 60.7
60.0 100.0 14.0
21.9
53.1 66.4
60.0 100.0 17.8
36.1
54.5 67.4
60.0 120.0 7.6
6.2
50.6 58.8
60.0 120.0 14.0
21.9
54.1 64.4
60.0 120.0 17.8
36.1
55.3 65.4

36

7.6
GPM
Load
Power Heat COP Load Load Source Heat
kW
Of
LWT WPD LWT
Cap
Absorb
Ft
Mbtuh
Head
2.88
35.7
4.6 72.0 6.2
20.4
45.5
2.90
40.0
5.0 73.1 6.2
24.2
49.9
2.92
40.6
5.1 73.3 6.2
25.3
50.6
3.67
30.9
3.5 91.5 5.4
21.6
43.4
3.69
34.9
3.8 92.5 5.4
24.9
47.5
3.72
35.5
3.8 92.7 5.4
25.9
48.2
4.67
25.9
2.6 111.1 4.8
22.8
41.8
4.69
29.8
2.9 112.1 4.8
25.5
45.8
4.73
30.4
2.9 112.3 4.8
26.4
46.5
5.94
20.3
2.0 130.8 4.4
24.2
40.6
5.97
24.0
2.2 131.8 4.4
26.3
44.4
6.02
24.6
2.2 132.0 4.4
27.0
45.1
3.04
42.7
5.1 74.0 6.2
28.5
53.1
3.06
47.8
5.6 75.3 6.2
33.0
58.2
3.08
48.5
5.6 75.5 6.2
34.5
59.0
3.87
37.4
3.8 93.4 5.4
29.8
50.6
3.89
42.2
4.2 94.6 5.4
33.8
55.5
3.92
42.9
4.2 94.9 5.4
35.0
56.3
4.92
32.0
2.9 112.9 4.8
31.2
48.8
4.95
36.5
3.2 114.1 4.8
34.6
53.4
4.99
37.2
3.2 114.4 4.8
35.7
54.2
6.26
25.9
2.2 132.6 4.4
32.7
47.3
6.29
30.3
2.4 133.8 4.4
35.4
51.8
6.35
30.9
2.4 134.0 4.4
36.3
52.6
3.17
49.1
5.5 75.8 6.2
36.8
59.9
3.19
54.7
6.0 77.3 6.2
42.0
65.6
3.21
55.5
6.1 77.5 6.2
43.7
66.5
4.03
43.4
4.2 95.1 5.4
38.3
57.1
4.05
48.7
4.5 96.5 5.4
42.9
62.5
4.09
49.4
4.5 96.7 5.4
44.3
63.4
5.13
37.5
3.1 114.6 4.8
39.7
55.0
5.16
42.6
3.4 115.9 4.8
43.7
60.2
5.20
43.4
3.4 116.2 4.8
45.0
61.1
6.53
31.1
2.4 134.2 4.4
41.3
53.4
6.56
36.0
2.6 135.5 4.4
44.6
58.4
6.62
36.7
2.6 135.8 4.4
45.7
59.3
3.28
54.8
5.9 77.4 6.2
45.3
66.0
3.30
61.0
6.4 79.0 6.2
51.1
72.3
3.33
62.0
6.5 79.3 6.2
52.9
73.4
4.17
48.8
4.4 96.6 5.4
46.8
63.0
4.19
54.6
4.8 98.2 5.4
52.0
68.9
4.23
55.5
4.8 98.4 5.4
53.6
69.9
5.31
42.6
3.3 116.1 4.8
48.4
60.7
5.33
48.2
3.7 117.6 4.8
52.9
66.4
5.38
49.0
3.7 117.9 4.8
54.3
67.4
6.75
35.8
2.6 135.7 4.4
50.0
58.8
6.78
41.3
2.8 137.1 4.4
53.8
64.4
6.85
42.0
2.8 137.4 4.4
55.0
65.4

14.0 GPM
Load
Power Heat COP Load Load Source Heat
kW
Of
LWT WPD LWT Cap
Absorb
Ft
Mbtuh
Head
2.63
36.5
5.1 66.5 21.9 20.3 45.5
2.65
40.9
5.5 67.1 21.9 24.1 49.9
2.67
41.5
5.6 67.2 21.9 25.3 50.6
3.35
32.0
3.8 86.2 19.1 21.5 43.4
3.37
36.0
4.1 86.8 19.1 24.8 47.5
3.40
36.6
4.2 86.9 19.1 25.9 48.2
4.26
27.3
2.9 106.0 17.2 22.7 41.8
4.28
31.2
3.1 106.6 17.2 25.5 45.8
4.32
31.8
3.2 106.7 17.2 26.4 46.5
5.42
22.1
2.2 125.9 15.8 24.0 40.6
5.45
25.8
2.4 126.4 15.8 26.2 44.4
5.50
26.3
2.4 126.5 15.8 27.0 45.1
2.78
43.6
5.6 67.6 21.9 28.5 53.1
2.79
48.7
6.1 68.3 21.9 33.0 58.2
2.82
49.4
6.1 68.4 21.9 34.4 59.0
3.53
38.6
4.2 87.3 19.1 29.8 50.6
3.55
43.4
4.6 88.0 19.1 33.8 55.5
3.58
44.1
4.6 88.1 19.1 35.0 56.3
4.49
33.5
3.2 107.0 17.2 31.1 48.8
4.52
38.0
3.5 107.7 17.2 34.5 53.4
4.56
38.6
3.5 107.8 17.2 35.6 54.2
5.72
27.8
2.4 126.8 15.8 32.5 47.3
5.75
32.2
2.6 127.5 15.8 35.3 51.8
5.80
32.8
2.7 127.6 15.8 36.2 52.6
2.89
50.0
6.1 68.6 21.9 36.8 59.9
2.91
55.7
6.6 69.4 21.9 42.0 65.6
2.94
56.5
6.6 69.5 21.9 43.6 66.5
3.68
44.5
4.5 88.2 19.1 38.2 57.1
3.70
49.9
4.9 89.0 19.1 42.8 62.5
3.73
50.7
5.0 89.1 19.1 44.3 63.4
4.68
39.0
3.4 107.9 17.2 39.6 55.0
4.71
44.1
3.7 108.7 17.2 43.6 60.2
4.75
44.9
3.8 108.8 17.2 44.9 61.1
5.96
33.1
2.6 127.7 15.8 41.1 53.4
5.99
38.0
2.9 128.4 15.8 44.5 58.4
6.04
38.7
2.9 128.6 15.8 45.6 59.3
2.99
55.8
6.5 69.4 21.9 45.2 66.0
3.01
62.0
7.0 70.3 21.9 51.1 72.3
3.04
63.0
7.1 70.5 21.9 52.9 73.4
3.81
50.0
4.8 89.0 19.1 46.7 63.0
3.83
55.8
5.3 89.9 19.1 52.0 68.9
3.86
56.7
5.3 90.0 19.1 53.6 69.9
4.85
44.2
3.7 108.7 17.2 48.2 60.7
4.87
49.8
4.0 109.5 17.2 52.8 66.4
4.91
50.6
4.0 109.7 17.2 54.3 67.4
6.16
37.8
2.8 128.5 15.8 49.9 58.8
6.20
43.2
3.0 129.3 15.8 53.7 64.4
6.25
44.1
3.1 129.5 15.8 55.0 65.4

17.8 GPM
Power Heat COP Load Load
kW
Of
LWT WPD
Absorb
Ft
Head
2.55 36.8
5.2 65.1 36.1
2.57 41.1
5.7 65.6 36.1
2.59 41.8
5.7 65.7 36.1
3.25 32.3
3.9 84.9 31.5
3.27 36.3
4.3 85.4 31.5
3.30 36.9
4.3 85.4 31.5
4.13 27.7
3.0 104.7 28.4
4.16 31.6
3.2 105.2 28.4
4.19 32.2
3.3 105.3 28.4
5.26 22.7
2.3 124.6 26.0
5.29 26.4
2.5 125.0 26.0
5.33 26.9
2.5 125.1 26.0
2.69 43.9
5.8 66.0 36.1
2.71 49.0
6.3 66.5 36.1
2.73 49.7
6.3 66.6 36.1
3.43 38.9
4.3 85.7 31.5
3.45 43.7
4.7 86.3 31.5
3.48 44.4
4.7 86.3 31.5
4.36 33.9
3.3 105.5 28.4
4.38 38.5
3.6 106.0 28.4
4.42 39.1
3.6 106.1 28.4
5.55 28.4
2.5 125.4 26.0
5.58 32.8
2.7 125.9 26.0
5.63 33.4
2.7 126.0 26.0
2.81 50.3
6.2 66.7 36.1
2.82 56.0
6.8 67.4 36.1
2.85 56.8
6.8 67.5 36.1
3.57 44.9
4.7 86.4 31.5
3.59 50.3
5.1 87.0 31.5
3.62 51.0
5.1 87.1 31.5
4.55 39.5
3.5 106.2 28.4
4.57 44.6
3.9 106.8 28.4
4.61 45.4
3.9 106.9 28.4
5.78 33.7
2.7 126.1 26.0
5.81 38.6
2.9 126.6 26.0
5.86 39.3
3.0 126.7 26.0
2.91 56.1
6.6 67.4 36.1
2.92 62.3
7.3 68.1 36.1
2.95 63.3
7.3 68.3 36.1
3.70 50.4
5.0 87.1 31.5
3.72 56.2
5.4 87.8 31.5
3.75 57.1
5.5 87.9 31.5
4.70 44.7
3.8 106.9 28.4
4.73 50.3
4.1 107.5 28.4
4.77 51.1
4.1 107.6 28.4
5.98 38.4
2.9 126.7 26.0
6.01 43.9
3.1 127.3 26.0
6.07 44.7
3.2 127.4 26.0

WSHP-PRC009-EN

Performance Data
WPWD 060-Heating
Table P-10: 060 Heating Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
70.0 60.0
7.6
5.7
70.0 60.0 14.0
20.4
70.0 60.0 17.8
33.6
70.0 80.0
7.6
5.7
70.0 80.0 14.0
20.4
70.0 80.0 17.8
33.6
70.0 100.0 7.6
5.7
70.0 100.0 14.0
20.4
70.0 100.0 17.8
33.6
70.0 120.0 7.6
5.7
70.0 120.0 14.0
20.4
70.0 120.0 17.8
33.6
80.0 60.0
7.6
5.4
80.0 60.0 14.0
19.1
80.0 60.0 17.8
31.5
80.0 80.0
7.6
5.4
80.0 80.0 14.0
19.1
80.0 80.0 17.8
31.5
80.0 100.0 7.6
5.4
80.0 100.0 14.0
19.1
80.0 100.0 17.8
31.5
80.0 120.0 7.6
5.4
80.0 120.0 14.0
19.1
80.0 120.0 17.8
31.5

WSHP-PRC009-EN

Load 7.6
GPM
Load
Source Heat Power Heat COP Load Load Source Heat
LWT Cap
kW
Of
LWT WPD LWT
Cap
Mbtuh
Absorb
Ft
Mbtuh
Head
54.1 71.7 3.37
60.2
6.2 78.9 6.2
53.9
71.7
60.4 78.5 3.39
66.9
6.8 80.7 6.2
60.3
78.5
62.3 79.7 3.42
68.0
6.8 81.0 6.2
62.2
79.7
55.8 68.4 4.29
53.8
4.7 98.1 5.4
55.5
68.4
61.4 74.9 4.31
60.2
5.1 99.8 5.4
61.2
74.9
63.1 76.0 4.35
61.2
5.1 100.1 5.4
63.0
76.0
57.5 65.9 5.46
47.3
3.5 117.5 4.8
57.1
65.9
62.3 72.2 5.49
53.5
3.9 119.1 4.8
62.1
72.2
63.9 73.2 5.54
54.3
3.9 119.4 4.8
63.7
73.2
59.4 63.9 6.95
40.2
2.7 137.0 4.4
58.8
63.9
63.4 70.0 6.98
46.2
2.9 138.6 4.4
63.1
70.0
64.7 71.0 7.04
47.0
3.0 138.9 4.4
64.5
71.0
62.8 77.1 3.46
65.3
6.5 80.3 6.2
62.5
77.1
69.6 84.4 3.48
72.5
7.1 82.2 6.2
69.5
84.4
71.7 85.6 3.51
73.6
7.1 82.5 6.2
71.6
85.6
64.6 73.5 4.40
58.5
4.9 99.4 5.4
64.2
73.5
70.6 80.4 4.42
65.3
5.3 101.2 5.4
70.5
80.4
72.5 81.6 4.46
66.4
5.4 101.5 5.4
72.4
81.6
66.4 70.8 5.60
51.7
3.7 118.8 4.8
65.9
70.8
71.6 77.5 5.63
58.3
4.0 120.5 4.8
71.4
77.5
73.3 78.6 5.68
59.2
4.1 120.8 4.8
73.1
78.6
68.3 68.7 7.12
44.4
2.8 138.3 4.4
67.7
68.7
72.7 75.2 7.16
50.8
3.1 140.0 4.4
72.4
75.2
74.2 76.3 7.22
51.7
3.1 140.3 4.4
73.9
76.3

14.0 GPM
Power Heat COP
kW
Of
Absorb
3.08
3.10
3.12
3.92
3.94
3.97
4.99
5.01
5.06
6.34
6.38
6.43
3.16
3.17
3.20
4.02
4.04
4.07
5.11
5.14
5.18
6.50
6.54
6.59

61.2
67.9
69.1
55.0
61.5
62.5
48.9
55.1
55.9
42.3
48.2
49.1
66.3
73.6
74.7
59.8
66.6
67.7
53.4
60.0
60.9
46.5
52.9
53.8

6.8
7.4
7.5
5.1
5.6
5.6
3.9
4.2
4.2
3.0
3.2
3.2
7.1
7.8
7.8
5.4
5.8
5.9
4.1
4.4
4.4
3.1
3.4
3.4

Load
Load Load Source Heat
LWT WPD LWT Cap
Ft
Mbtuh
Head
70.2 21.9 53.8 71.7
71.2 21.9 60.2 78.5
71.4 21.9 62.2 79.7
89.8 19.1 55.4 68.4
90.7 19.1 61.1 74.9
90.9 19.1 62.9 76.0
109.5 17.2 57.0 65.9
110.4 17.2 62.0 72.2
110.5 17.2 63.7 73.2
129.2 15.8 58.7 63.9
130.1 15.8 63.0 70.0
130.3 15.8 64.4 71.0
71.0 21.9 62.4 77.1
72.1 21.9 69.4 84.4
72.2 21.9 71.5 85.6
90.5 19.1 64.1 73.5
91.5 19.1 70.4 80.4
91.7 19.1 72.3 81.6
110.2 17.2 65.8 70.8
111.1 17.2 71.3 77.5
111.3 17.2 73.1 78.6
129.9 15.8 67.5 68.7
130.9 15.8 72.3 75.2
131.0 15.8 73.9 76.3

17.8 GPM
Power Heat COP Load Load
kW
Of
LWT WPD
Absorb
Ft
Head
2.99 61.5
7.0 68.1 36.1
3.01 68.2
7.6 68.8 36.1
3.03 69.4
7.7 69.0 36.1
3.80 55.4
5.3 87.7 31.5
3.82 61.9
5.7 88.4 31.5
3.86 62.8
5.8 88.6 31.5
4.84 49.4
4.0 107.5 28.4
4.86 55.6
4.4 108.2 28.4
4.91 56.4
4.4 108.3 28.4
6.15 42.9
3.0 127.3 26.0
6.19 48.9
3.3 128.0 26.0
6.24 49.7
3.3 128.1 26.0
3.06 66.7
7.4 68.7 36.1
3.08 73.9
8.0 69.5 36.1
3.11 75.0
8.1 69.6 36.1
3.90 60.2
5.5 88.3 31.5
3.92 67.0
6.0 89.1 31.5
3.95 68.1
6.1 89.2 31.5
4.96 53.9
4.2 108.0 28.4
4.99 60.5
4.6 108.8 28.4
5.03 61.4
4.6 108.9 28.4
6.31 47.2
3.2 127.8 26.0
6.34 53.6
3.5 128.5 26.0
6.40 54.5
3.5 128.7 26.0

37

Performance Data
WPWD 072-Cooling
Table P-10: 072 Cooling Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load
Source Load Source Source Source Cool
EWT EWT GPM WPD LWT
Cap
Ft
Mbtuh
Head
50.0 45.0
8.7
8.9
64.1
52.6
50.0 45.0 16.0
31.5
57.7
53.2
50.0 45.0 20.4
52.2
56.0
53.6
50.0 53.6
8.7
8.9
65.3
57.7
50.0 53.6 16.0
31.5
58.3
58.3
50.0 53.6 20.4
52.2
56.6
58.7
50.0 65.0
8.7
8.9
66.9
64.4
50.0 65.0 16.0
31.5
59.2
65.2
50.0 65.0 20.4
52.2
57.2
65.6
50.0 75.0
8.7
8.9
68.3
70.3
50.0 75.0 16.0
31.5
60.0
71.2
50.0 75.0 20.4
52.2
57.9
71.7
60.0 45.0
8.7
8.2
73.9
50.7
60.0 45.0 16.0
28.9
67.6
51.3
60.0 45.0 20.4
47.9
65.9
51.6
60.0 53.6
8.7
8.2
75.1
55.8
60.0 53.6 16.0
28.9
68.2
56.4
60.0 53.6 20.4
47.9
66.5
56.8
60.0 65.0
8.7
8.2
76.7
62.5
60.0 65.0 16.0
28.9
69.1
63.3
60.0 65.0 20.4
47.9
67.2
63.7
60.0 75.0
8.7
8.2
78.1
68.5
60.0 75.0 16.0
28.9
69.9
69.3
60.0 75.0 20.4
47.9
67.8
69.7
70.0 45.0
8.7
7.6
83.8
48.9
70.0 45.0 16.0
26.9
77.5
49.5
70.0 45.0 20.4
44.5
75.9
49.8
70.0 53.6
8.7
7.6
85.1
54.0
70.0 53.6 16.0
26.9
78.2
54.6
70.0 53.6 20.4
44.5
76.4
55.0
70.0 65.0
8.7
7.6
86.6
60.7
70.0 65.0 16.0
26.9
79.0
61.4
70.0 65.0 20.4
44.5
77.1
61.9
70.0 75.0
8.7
7.6
88.0
66.6
70.0 75.0 16.0
26.9
79.8
67.4
70.0 75.0 20.4
44.5
77.7
67.9
80.0 45.0
8.7
7.1
93.8
47.1
80.0 45.0 16.0
25.3
87.5
47.7
80.0 45.0 20.4
41.8
85.9
48.0
80.0 53.6
8.7
7.1
95.0
52.2
80.0 53.6 16.0
25.3
88.1
52.9
80.0 53.6 20.4
41.8
86.4
53.2
80.0 65.0
8.7
7.1
96.6
59.0
80.0 65.0 16.0
25.3
89.0
59.7
80.0 65.0 20.4
41.8
87.1
60.1
80.0 75.0
8.7
7.1
98.0
64.9
80.0 75.0 16.0
25.3
89.8
65.7
80.0 75.0 20.4
41.8
87.7
66.1

38

8.7 GPM
Load
Power Heat EER Load Load Source Cool
kW
Of
LWT WPD LWT
Cap
Reject
Ft
Mbtuh
Head
2.56 61.3 20.5 32.9 9.3
65.4
57.9
2.39 61.4 22.3 32.8 9.3
58.3
58.5
2.35 61.6 22.8 32.7 9.3
56.6
59.0
2.61 66.6 22.1 40.3 8.6
66.7
63.5
2.44 66.6 23.9 40.2 8.6
59.1
64.2
2.39 66.9 24.6 40.1 8.6
57.2
64.7
2.66 73.5 24.2 50.2 7.9
68.4
70.9
2.48 73.7 26.3
50
7.9
60.0
71.7
2.43 73.9 27.0 49.9 7.9
57.9
72.2
2.69 79.5 26.1 58.8 7.3
70.0
77.4
2.51 79.8 28.4 58.6 7.3
60.9
78.3
2.46 80.1 29.1 58.5 7.3
58.6
78.9
2.89 60.6 17.5 33.3 9.3
75.2
55.8
2.70 60.5 19.0 33.2 9.3
68.2
56.4
2.65 60.6 19.5 33.1 9.3
66.5
56.8
2.94 65.8 19.0 40.8 8.6
76.5
61.4
2.74 65.8 20.6 40.6 8.6
69.0
62.1
2.69 66.0 21.1 40.5 8.6
67.1
62.6
2.98 72.7 21.0 50.6 7.9
78.2
68.8
2.78 72.8 22.8 50.4 7.9
69.9
69.6
2.73 73.0 23.3 50.3 7.9
67.8
70.1
3.01 78.8 22.8 59.2 7.3
79.7
75.3
2.81 78.9 24.7
59
7.3
70.8
76.2
2.76 79.1 25.3 58.9 7.3
68.5
76.8
3.28 60.1 14.9 33.8 9.3
85.0
53.8
3.06 59.9 16.2 33.6 9.3
78.2
54.4
3.00 60.0 16.6 33.6 9.3
76.4
54.8
3.33 65.4 16.2 41.2 8.6
86.3
59.4
3.11 65.2 17.6
41
8.6
78.9
60.1
3.05 65.4 18.0
41
8.6
77.0
60.5
3.37 72.2 18.0
51
7.9
88.1
66.8
3.15 72.2 19.5 50.9 7.9
79.8
67.6
3.09 72.5 20.0 50.8 7.9
77.7
68.1
3.40 78.2 19.6 59.7 7.3
89.6
73.4
3.17 78.2 21.3 59.5 7.3
80.7
74.2
3.11 78.5 21.8 59.4 7.3
78.4
74.7
3.73 59.8 12.6 34.2 9.3
95.0
51.9
3.48 59.6 13.7
34
9.3
88.1
52.5
3.42 59.7 14.0
34
9.3
86.4
52.9
3.78 65.1 13.8 41.6 8.6
96.3
57.5
3.53 65.0 15.0 41.4 8.6
88.8
58.2
3.46 65.0 15.4 41.4 8.6
87.0
58.6
3.83 72.1 15.4 51.4 7.9
98.0
64.9
3.57 71.9 16.7 51.3 7.9
89.8
65.7
3.50 72.1 17.2 51.2 7.9
87.7
66.2
3.85 78.0 16.9
60
7.3
99.6
71.5
3.60 78.0 18.3 59.9 7.3
90.6
72.3
3.53 78.2 18.7 59.8 7.3
88.4
72.8

16.0 GPM
Load
Power Heat EER Load Load Source Cool
kW
Of
LWT WPD LWT
Cap
Reject
Ft
Mbtuh
Head
2.61 66.8 22.2 37.8 33.1
65.8
59.9
2.44 66.8 24.0 37.7 33.1
58.6
60.6
2.39 67.2 24.7 37.6 33.1
56.8
61.0
2.66 72.6 23.9 45.7 30.5
67.2
65.7
2.49 72.7 25.8 45.6 30.5
59.4
66.5
2.44 73.0 26.5 45.5 30.5
57.4
66.9
2.71 80.2 26.2 56.1 27.8
69.0
73.4
2.53 80.3 28.3 56.0 27.8
60.4
74.3
2.48 80.7 29.1 56.0 27.8
58.2
74.8
2.74 86.8 28.2 65.3 26.0
70.6
80.2
2.56 87.0 30.6 65.2 26.0
61.2
81.1
2.51 87.5 31.4 65.1 26.0
58.9
81.7
2.95 65.9 18.9 38.0 33.1
75.6
57.8
2.75 65.8 20.5 38.0 33.1
68.5
58.4
2.70 66.0 21.0 37.9 33.1
66.7
58.8
3.00 71.6 20.5 45.9 30.5
77.0
63.6
2.80 71.7 22.2 45.8 30.5
69.2
64.3
2.74 72.0 22.8 45.8 30.5
67.3
64.8
3.04 79.2 22.6 56.4 27.8
78.8
71.3
2.84 79.3 24.5 56.3 27.8
70.2
72.1
2.79 79.6 25.1 56.2 27.8
68.1
72.6
3.07 85.8 24.5 65.6 26.0
80.4
78.0
2.87 86.0 26.6 65.5 26.0
71.1
78.9
2.81 86.4 27.3 65.4 26.0
68.7
79.5
3.34 65.2 16.1 38.3 33.1
85.5
55.7
3.12 65.1 17.4 38.2 33.1
78.4
56.4
3.06 65.2 17.9 38.2 33.1
76.6
56.7
3.39 71.0 17.5 46.2 30.5
86.8
61.5
3.17 70.9 19.0 46.1 30.5
79.2
62.2
3.11 71.1 19.5 46.0 30.5
77.2
62.7
3.44 78.5 19.4 56.6 27.8
88.7
69.2
3.21 78.6 21.1 56.5 27.8
80.1
70.0
3.15 78.9 21.6 56.5 27.8
78.0
70.5
3.47 85.2 21.2 65.8 26.0
90.2
75.9
3.24 85.3 22.9 65.7 26.0
81.0
76.8
3.18 85.6 23.5 65.6 26.0
78.7
77.4
3.81 64.9 13.6 38.5 33.1
95.4
53.7
3.55 64.6 14.8 38.4 33.1
88.3
54.4
3.49 64.8 15.2 38.4 33.1
86.6
54.7
3.86 70.7 14.9 46.4 30.5
96.8
59.5
3.60 70.5 16.2 46.3 30.5
89.1
60.2
3.53 70.7 16.6 46.3 30.5
87.1
60.6
3.90 78.2 16.6 56.9 27.8
98.6
67.2
3.64 78.1 18.0 56.8 27.8
90.1
68.0
3.57 78.4 18.5 56.7 27.8
87.9
68.5
3.93 84.9 18.2 66.0 26.0 100.2 74.0
3.67 84.8 19.7 65.9 26.0
91.0
74.8
3.60 85.1 20.2 65.9 26.0
88.6
75.4

20.4 GPM
Power Heat EER Load Load
kW
Of
LWT WPD
Reject
Ft
Head
2.62 68.8 22.9 39.1 54.8
2.45 69.0 24.7 39.1 54.8
2.40 69.2 25.4 39.0 54.8
2.67 74.8 24.6 47.2 50.5
2.49 75.0 26.7 47.1 50.5
2.45 75.3 27.3 47.0 50.5
2.72 82.7 27.0 57.8 46.1
2.54 83.0 29.3 57.7 46.1
2.49 83.3 30.0 57.7 46.1
2.75 89.6 29.2 67.1 43.1
2.56 89.8 31.7 67.0 43.1
2.52 90.3 32.4 67.0 43.1
2.96 67.9 19.5 39.3 54.8
2.76 67.8 21.2 39.3 54.8
2.71 68.1 21.7 39.2 54.8
3.01 73.9 21.1 47.4 50.5
2.81 73.9 22.9 47.3 50.5
2.75 74.2 23.6 47.2 50.5
3.05 81.7 23.4 58.0 46.1
2.85 81.8 25.3 57.9 46.1
2.80 82.2 25.9 57.9 46.1
3.08 88.5 25.3 67.3 43.1
2.88 88.7 27.4 67.2 43.1
2.82 89.1 28.2 67.2 43.1
3.35 67.1 16.6 39.5 54.8
3.13 67.1 18.0 39.5 54.8
3.07 67.2 18.5 39.4 54.8
3.40 73.1 18.1 47.6 50.5
3.18 73.1 19.6 47.5 50.5
3.12 73.4 20.1 47.5 50.5
3.45 81.0 20.1 58.2 46.1
3.22 81.0 21.7 58.1 46.1
3.16 81.3 22.3 58.1 46.1
3.48 87.8 21.8 67.5 43.1
3.25 87.9 23.6 67.5 43.1
3.19 88.3 24.3 67.4 43.1
3.82 66.7 14.1 39.7 54.8
3.56 66.6 15.3 39.7 54.8
3.50 66.7 15.6 39.6 54.8
3.87 72.7 15.4 47.8 50.5
3.61 72.5 16.7 47.7 50.5
3.54 72.7 17.1 47.7 50.5
3.91 80.5 17.2 58.4 46.1
3.65 80.5 18.6 58.3 46.1
3.59 80.8 19.1 58.3 46.1
3.94 87.5 18.8 67.7 43.1
3.68 87.4 20.3 67.6 43.1
3.61 87.7 20.9 67.6 43.1

WSHP-PRC009-EN

Performance Data
WPWD 072-Cooling
Table P-10: 072 Cooling Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
90.0 45.0
8.7
6.7
90.0 45.0 16.0
23.9
90.0 45.0 20.4
39.6
90.0 53.6
8.7
6.7
90.0 53.6 16.0
23.9
90.0 53.6 20.4
39.6
90.0 65.0
8.7
6.7
90.0 65.0 16.0
23.9
90.0 65.0 20.4
39.6
90.0 75.0
8.7
6.7
90.0 75.0 16.0
23.9
90.0 75.0 20.4
39.6
100.0 45.0
8.7
6.4
100.0 45.0 16.0
22.7
100.0 45.0 20.4
37.7
100.0 53.6
8.7
6.4
100.0 53.6 16.0
22.7
100.0 53.6 20.4
37.7
100.0 65.0
8.7
6.4
100.0 65.0 16.0
22.7
100.0 65.0 20.4
37.7
100.0 75.0
8.7
6.4
100.0 75.0 16.0
22.7
100.0 75.0 20.4
37.7
110.0 45.0
8.7
6.1
110.0 45.0 16.0
21.7
110.0 45.0 20.4
36.0
110.0 53.6
8.7
6.1
110.0 53.6 16.0
21.7
110.0 53.6 20.4
36.0
110.0 65.0
8.7
6.1
110.0 65.0 16.0
21.7
110.0 65.0 20.4
36.0
110.0 75.0
8.7
6.1
110.0 75.0 16.0
21.7
110.0 75.0 20.4
36.0
120.0 45.0
8.7
5.9
120.0 45.0 16.0
20.9
120.0 45.0 20.4
34.6
120.0 53.6
8.7
5.9
120.0 53.6 16.0
20.9
120.0 53.6 20.4
34.6
120.0 65.0
8.7
5.9
120.0 65.0 16.0
20.9
120.0 65.0 20.4
34.6
120.0 75.0
8.7
5.9
120.0 75.0 16.0
20.9
120.0 75.0 20.4
34.6

WSHP-PRC009-EN

Load 8.7 GPM


Load
Source Cool Power Heat EER Load Load Source Cool
LWT
Cap
kW
Of
LWT WPD LWT
Cap
Mbtuh
Reject
Ft
Mbtuh
Head
103.9 45.5 4.25 60.0 10.7 34.5
9.3
105.0 50.1
97.5
46.0 3.97 59.6 11.6 34.4
9.3
98.1
50.7
95.9
46.3 3.89 59.6 11.9 34.4
9.3
96.4
51.0
105.1 50.6 4.30 65.3 11.8
42
8.6
106.3 55.7
98.2
51.2 4.01 64.9 12.8 41.8
8.6
98.8
56.3
96.4
51.5 3.94 65.0 13.1 41.8
8.6
96.9
56.7
106.7 57.3 4.34 72.1 13.2 51.8
7.9
108.1 63.1
99.0
58.0 4.05 71.8 14.3 51.7
7.9
99.8
63.9
97.1
58.4 3.98 72.0 14.7 51.6
7.9
97.7
64.3
108.1 63.3 4.37 78.2 14.5 60.4
7.3
109.6 69.6
99.8
64.0 4.08 77.9 15.7 60.3
7.3
100.6 70.4
97.7
64.4 4.00 78.1 16.1 60.2
7.3
98.4
70.9
114.0 43.9 4.83 60.4
9.1 34.9
9.3
115.1 48.3
107.5 44.4 4.51 59.8
9.8 34.8
9.3
108.1 48.9
105.9 44.7 4.43 59.8 10.1 34.7
9.3
106.4 49.2
115.2 49.0 4.88 65.7 10.0 42.3
8.6
116.4 53.9
108.2 49.6 4.55 65.1 10.9 42.2
8.6
108.9 54.6
106.4 49.9 4.47 65.2 11.2 42.1
8.6
107.0 55.0
116.8 55.8 4.92 72.6 11.3 52.2
7.9
118.2 61.4
109.1 56.4 4.60 72.1 12.3
52
7.9
109.8 62.1
107.1 56.8 4.51 72.2 12.6 51.9
7.9
107.7 62.5
118.2 61.7 4.95 78.6 12.5 60.8
7.3
119.7 67.9
109.8 62.4 4.62 78.2 13.5 60.6
7.3
110.7 68.7
107.7 62.8 4.54 78.3 13.8 60.5
7.3
108.4 69.2
124.2 42.4 5.48 61.1
7.7 35.3
9.3
125.2 46.7
117.6 42.9 5.11 60.3
8.4 35.1
9.3
118.2 47.2
116.0 43.2 5.02 60.3
8.6 35.1
9.3
116.4 47.6
125.4 47.5 5.52 66.3
8.6 42.7
8.6
126.6 52.3
118.3 48.1 5.16 65.7
9.3 42.5
8.6
118.9 52.9
116.5 48.4 5.06 65.7
9.6 42.5
8.6
117.0 53.3
127.0 54.2 5.57 73.2
9.7 52.5
7.9
128.3 59.7
119.2 54.9 5.20 72.7 10.6 52.4
7.9
119.9 60.4
117.2 55.3 5.10 72.7 10.8 52.3
7.9
117.8 60.8
128.4 60.2 5.60 79.3 10.8 61.1
7.3
129.9 66.2
119.9 60.9 5.22 78.7 11.7
61
7.3
120.7 67.0
117.8 61.3 5.13 78.8 11.9 60.9
7.3
118.4 67.5
134.4 41.0 6.18 62.1
6.6 35.6
9.3
135.5 45.1
127.7 41.5 5.77 61.2
7.2 35.5
9.3
128.3 45.6
126.1 41.7 5.66 61.0
7.4 35.4
9.3
126.5 45.9
135.7 46.1 6.23 67.4
7.4
43
8.6
136.8 50.7
128.4 46.6 5.82 66.5
8.0 42.9
8.6
129.0 51.3
126.6 46.9 5.71 66.4
8.2 42.8
8.6
127.1 51.7
137.3 52.8 6.28 74.2
8.4 52.8
7.9
138.6 58.1
129.3 53.4 5.86 73.4
9.1 52.7
7.9
130.0 58.8
127.3 53.8 5.75 73.4
9.4 52.6
7.9
127.9 59.2
138.7 58.7 6.31 80.2
9.3 61.5
7.3
140.2 64.7
130.1 59.4 5.89 79.5 10.1 61.3
7.3
130.9 65.4
127.9 59.8 5.78 79.5 10.3 61.2
7.3
128.5 65.9

16.0 GPM
Load
Power Heat EER Load Load Source Cool
kW
Of
LWT WPD LWT
Cap
Reject
Ft
Mbtuh
Head
4.33 64.9 11.6 38.7 33.1 105.4 51.8
4.04 64.5 12.5 38.7 33.1
98.3
52.4
3.97 64.6 12.8 38.6 33.1
96.5
52.8
4.38 70.7 12.7 46.6 30.5 106.8 57.6
4.09 70.3 13.8 46.6 30.5
99.1
58.3
4.01 70.4 14.1 46.5 30.5
97.1
58.7
4.43 78.2 14.2 57.1 27.8 108.6 65.3
4.13 78.0 15.5 57.0 27.8 100.1 66.1
4.06 78.2 15.8 57.0 27.8
97.9
66.6
4.46 84.8 15.6 66.3 26.0 110.2 72.1
4.16 84.6 16.9 66.2 26.0 100.9 72.9
4.08 84.8 17.4 66.1 26.0
98.6
73.4
4.93 65.1
9.8 39.0 33.1 115.5 50.0
4.60 64.6 10.6 38.9 33.1 108.3 50.6
4.51 64.6 10.9 38.9 33.1 106.6 51.0
4.98 70.9 10.8 46.9 30.5 116.8 55.8
4.64 70.4 11.8 46.8 30.5 109.1 56.5
4.56 70.6 12.1 46.7 30.5 107.2 56.9
5.02 78.5 12.2 57.3 27.8 118.7 63.5
4.69 78.1 13.2 57.2 27.8 110.1 64.3
4.60 78.2 13.6 57.2 27.8 107.9 64.7
5.05 85.1 13.4 66.5 26.0 120.3 70.3
4.71 84.8 14.6 66.4 26.0 111.0 71.1
4.62 85.0 15.0 66.3 26.0 108.6 71.6
5.58 65.7
8.4 39.2 33.1 125.6 48.3
5.21 65.0
9.1 39.1 33.1 118.4 48.9
5.11 65.0
9.3 39.1 33.1 116.6 49.2
5.63 71.5
9.3 47.1 30.5 127.0 54.1
5.26 70.9 10.1 47.0 30.5 119.2 54.8
5.16 70.9 10.3 46.9 30.5 117.2 55.1
5.68 79.1 10.5 57.5 27.8 128.9 61.8
5.30 78.5 11.4 57.4 27.8 120.2 62.5
5.20 78.6 11.7 57.4 27.8 118.0 63.0
5.71 85.7 11.6 66.7 26.0 130.5 68.6
5.33 85.2 12.6 66.6 26.0 121.0 69.4
5.23 85.4 12.9 66.5 26.0 118.7 69.9
6.31 66.6
7.1 39.4 33.1 135.9 46.7
5.89 65.7
7.7 39.3 33.1 128.5 47.2
5.78 65.6
7.9 39.3 33.1 126.7 47.6
6.36 72.4
8.0 47.3 30.5 137.3 52.5
5.93 71.5
8.7 47.2 30.5 129.3 53.1
5.82 71.6
8.9 47.1 30.5 127.3 53.5
6.40 79.9
9.1 57.7 27.8 139.1 60.2
5.97 79.2
9.8 57.6 27.8 130.3 60.9
5.86 79.2 10.1 57.6 27.8 128.1 61.3
6.43 86.7 10.1 66.9 26.0 140.7 66.9
6.00 85.9 10.9 66.8 26.0 131.2 67.7
5.89 86.0 11.2 66.7 26.0 128.8 68.2

20.4 GPM
Power Heat EER Load Load
kW
Of
LWT WPD
Reject
Ft
Head
4.35 66.7 11.9 39.9 54.8
4.06 66.3 12.9 39.9 54.8
3.98 66.4 13.3 39.8 54.8
4.40 72.6 13.1 48.0 50.5
4.11 72.3 14.2 47.9 50.5
4.03 72.5 14.6 47.8 50.5
4.44 80.5 14.7 58.6 46.1
4.15 80.3 15.9 58.5 46.1
4.07 80.5 16.4 58.5 46.1
4.47 87.4 16.1 67.9 43.1
4.17 87.1 17.5 67.8 43.1
4.10 87.4 17.9 67.8 43.1
4.94 66.9 10.1 40.1 54.8
4.61 66.3 11.0 40.0 54.8
4.53 66.5 11.3 40.0 54.8
4.99 72.8 11.2 48.1 50.5
4.66 72.4 12.1 48.1 50.5
4.57 72.5 12.5 48.0 50.5
5.04 80.7 12.6 58.8 46.1
4.70 80.3 13.7 58.7 46.1
4.61 80.4 14.0 58.6 46.1
5.07 87.6 13.9 68.1 43.1
4.73 87.2 15.0 68.0 43.1
4.64 87.4 15.4 68.0 43.1
5.60 67.4 8.6 40.3 54.8
5.23 66.8 9.3 40.2 54.8
5.13 66.7 9.6 40.2 54.8
5.65 73.4 9.6 48.3 50.5
5.28 72.8 10.4 48.2 50.5
5.18 72.8 10.6 48.2 50.5
5.70 81.3 10.8 58.9 46.1
5.32 80.7 11.7 58.9 46.1
5.22 80.8 12.1 58.8 46.1
5.73 88.2 12.0 68.3 43.1
5.34 87.6 13.0 68.2 43.1
5.24 87.8 13.3 68.1 43.1
6.33 68.3 7.4 40.4 54.8
5.91 67.4 8.0 40.4 54.8
5.80 67.4 8.2 40.3 54.8
6.38 74.3 8.2 48.5 50.5
5.95 73.4 8.9 48.4 50.5
5.84 73.4 9.2 48.4 50.5
6.42 82.1 9.4 59.1 46.1
5.99 81.3 10.2 59.0 46.1
5.88 81.4 10.4 59.0 46.1
6.45 88.9 10.4 68.4 43.1
6.02 88.3 11.2 68.3 43.1
5.91 88.4 11.5 68.3 43.1

39

Performance Data
WPWD 072-Heating
Table P-11: 072 Heating Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
30.0 60.0
8.7
11.3
30.0 60.0 16.0
40.1
30.0 60.0 20.4
66.4
30.0 80.0
8.7
11.3
30.0 80.0 16.0
40.1
30.0 80.0 20.4
66.4
30.0 100.0 8.7
11.3
30.0 100.0 16.0
40.1
30.0 100.0 20.4
66.4
30.0 120.0 8.7
11.3
30.0 120.0 16.0
40.1
30.0 120.0 20.4
66.4
40.0 60.0
8.7
9.9
40.0 60.0 16.0
35.0
40.0 60.0 20.4
58.0
40.0 80.0
8.7
9.9
40.0 80.0 16.0
35.0
40.0 80.0 20.4
58.0
40.0 100.0 8.7
9.9
40.0 100.0 16.0
35.0
40.0 100.0 20.4
58.0
40.0 120.0 8.7
9.9
40.0 120.0 16.0
35.0
40.0 120.0 20.4
58.0
50.0 60.0
8.7
8.9
50.0 60.0 16.0
31.5
50.0 60.0 20.4
52.2
50.0 80.0
8.7
8.9
50.0 80.0 16.0
31.5
50.0 80.0 20.4
52.2
50.0 100.0 8.7
8.9
50.0 100.0 16.0
31.5
50.0 100.0 20.4
52.2
50.0 120.0 8.7
8.9
50.0 120.0 16.0
31.5
50.0 120.0 20.4
52.2
60.0 60.0
8.7
8.2
60.0 60.0 16.0
28.9
60.0 60.0 20.4
47.9
60.0 80.0
8.7
8.2
60.0 80.0 16.0
28.9
60.0 80.0 20.4
47.9
60.0 100.0 8.7
8.2
60.0 100.0 16.0
28.9
60.0 100.0 20.4
47.9
60.0 120.0 8.7
8.2
60.0 120.0 16.0
28.9
60.0 120.0 20.4
47.9

40

Load 8.7
GPM
Load
Source Heat Power Heat COP Load Load Source Heat
LWT Cap
kW
Of
LWT WPD LWT Cap
Mbtuh
Absorb
Ft
Mbtuh
Head
19.3 56.7 3.00
46.5
5.5 73.0 8.2
19.1 56.7
23.5 62.0 3.02
51.7
6.0 74.3 8.2
23.4 62.0
24.9 62.9 3.04
52.5
6.1 74.5 8.2
24.8 62.9
20.9 54.0 4.25
39.5
3.7 92.5 7.1
20.6 54.0
24.4 59.2 4.27
44.6
4.1 93.7 7.1
24.3 59.2
25.6 60.0 4.31
45.3
4.1 93.8 7.1
25.4 60.0
22.4 52.1 5.56
33.1
2.7 112.1 6.4
22.0 52.1
25.3 57.0 5.58
38.0
3.0 113.2 6.4
25.1 57.0
26.2 57.8 5.64
38.6
3.0 113.4 6.4
26.1 57.8
23.8 50.5 6.92
26.9
2.1 131.7 5.9
23.4 50.5
26.1 55.3 6.96
31.6
2.3 132.9 5.9
25.8 55.3
26.9 56.1 7.02
32.1
2.3 133.0 5.9
26.6 56.1
28.1 62.6 3.16
51.8
5.8 74.4 8.2
27.9 62.6
32.8 68.5 3.18
57.7
6.3 75.8 8.2
32.7 68.5
34.3 69.5 3.21
58.5
6.3 76.0 8.2
34.2 69.5
29.8 59.6 4.48
44.3
3.9 93.7 7.1
29.5 59.6
33.8 65.3 4.50
49.9
4.3 95.1 7.1
33.6 65.3
35.0 66.2 4.54
50.7
4.3 95.3 7.1
34.9 66.2
31.4 57.5 5.86
37.5
2.9 113.3 6.4
31.0 57.5
34.7 62.9 5.89
42.8
3.1 114.6 6.4
34.4 62.9
35.7 63.8 5.94
43.5
3.1 114.8 6.4
35.6 63.8
32.9 55.8 7.30
30.9
2.2 133.0 5.9
32.4 55.8
35.5 61.0 7.34
36.0
2.4 134.2 5.9
35.2 61.0
36.4 61.9 7.41
36.6
2.4 134.4 5.9
36.2 61.9
36.7 69.0 3.30
57.7
6.1 75.9 8.2
36.5 69.0
42.0 75.6 3.32
64.3
6.7 77.4 8.2
41.8 75.6
43.6 76.7 3.35
65.3
6.7 77.6 8.2
43.5 76.7
38.5 65.8 4.67
49.9
4.1 95.2 7.1
38.2 65.8
43.0 72.1 4.69
56.1
4.5 96.6 7.1
42.8 72.1
44.4 73.1 4.73
57.0
4.5 96.9 7.1
44.3 73.1
40.2 63.4 6.11
42.6
3.0 114.7 6.4
39.8 63.4
44.0 69.4 6.14
48.4
3.3 116.1 6.4
43.7 69.4
45.2 70.4 6.20
49.2
3.3 116.3 6.4
45.0 70.4
41.8 61.5 7.61
35.5
2.4 134.3 5.9
41.3 61.5
44.8 67.4 7.65
41.3
2.6 135.7 5.9
44.6 67.4
45.9 68.3 7.72
42.0
2.6 135.9 5.9
45.7 68.3
45.1 76.2 3.41
64.6
6.5 77.5 8.2
44.9 76.2
51.0 83.4 3.43
71.7
7.1 79.2 8.2
50.9 83.4
52.9 84.6 3.46
72.8
7.2 79.5 8.2
52.8 84.6
47.1 72.6 4.83
56.1
4.4 96.7 7.1
46.8 72.6
52.1 79.5 4.85
63.0
4.8 98.3 7.1
51.9 79.5
53.7 80.7 4.90
64.0
4.8 98.6 7.1
53.6 80.7
48.9 70.0 6.32
48.4
3.2 116.2 6.4
48.4 70.0
53.1 76.6 6.35
54.9
3.5 117.7 6.4
52.9 76.6
54.5 77.7 6.41
55.8
3.6 118.0 6.4
54.3 77.7
50.6 67.9 7.87
41.0
2.5 135.8 5.9
50.0 67.9
54.1 74.3 7.91
47.3
2.8 137.3 5.9
53.8 74.3
55.3 75.4 7.98
48.2
2.8 137.5 5.9
55.0 75.4

16.0 GPM
Load 20.4
Power Heat COP Load Load Source Heat Power
kW
Of
LWT WPD LWT
Cap
kW
Absorb
Ft
Mbtuh
Head
2.74
47.4
6.1 67.1 28.9
19.1
56.7 2.66
2.75
52.6
6.6 67.8 28.9
23.4
62.0 2.67
2.78
53.4
6.6 67.9 28.9
24.7
62.9 2.70
3.88
40.8
4.1 86.8 25.3
20.5
54.0 3.76
3.90
45.9
4.4 87.4 25.3
24.2
59.2 3.78
3.93
46.6
4.5 87.5 25.3
25.4
60.0 3.82
5.07
34.8
3.0 106.6 22.7
21.9
52.1 4.92
5.10
39.6
3.3 107.2 22.7
25.0
57.0 4.95
5.15
40.2
3.3 107.3 22.7
26.0
57.8 4.99
6.32
28.9
2.3 126.4 20.9
23.2
50.5 6.13
6.36
33.6
2.5 127.0 20.9
25.7
55.3 6.17
6.41
34.2
2.6 127.1 20.9
26.6
56.1 6.22
2.89
52.7
6.3 67.8 28.9
27.8
62.6 2.80
2.91
58.6
6.9 68.6 28.9
32.6
68.5 2.82
2.93
59.5
6.9 68.7 28.9
34.1
69.5 2.84
4.09
45.6
4.3 87.5 25.3
29.4
59.6 3.97
4.11
51.3
4.7 88.2 25.3
33.5
65.3 3.99
4.15
52.0
4.7 88.3 25.3
34.9
66.2 4.02
5.35
39.2
3.1 107.2 22.7
30.9
57.5 5.19
5.38
44.5
3.4 107.9 22.7
34.4
62.9 5.22
5.43
45.3
3.4 108.0 22.7
35.5
63.8 5.27
6.67
33.0
2.5 127.1 20.9
32.3
55.8 6.47
6.70
38.1
2.7 127.7 20.9
35.2
61.0 6.50
6.76
38.8
2.7 127.8 20.9
36.1
61.9 6.56
3.01
58.7
6.7 68.6 28.9
36.4
69.0 2.92
3.03
65.3
7.3 69.5 28.9
41.8
75.6 2.94
3.06
66.3
7.3 69.6 28.9
43.5
76.7 2.96
4.26
51.3
4.5 88.2 25.3
38.1
65.8 4.13
4.28
57.5
4.9 89.0 25.3
42.8
72.1 4.16
4.32
58.4
5.0 89.2 25.3
44.2
73.1 4.19
5.58
44.4
3.3 108.0 22.7
39.7
63.4 5.41
5.61
50.3
3.6 108.7 22.7
43.7
69.4 5.44
5.66
51.1
3.6 108.9 22.7
44.9
70.4 5.49
6.95
37.8
2.6 127.8 20.9
41.1
61.5 6.74
6.99
43.5
2.8 128.5 20.9
44.5
67.4 6.78
7.05
44.2
2.8 128.6 20.9
45.6
68.3 6.84
3.12
65.6
7.2 69.5 28.9
44.8
76.2 3.02
3.13
72.7
7.8 70.4 28.9
50.9
83.4 3.04
3.16
73.8
7.8 70.6 28.9
52.7
84.6 3.07
4.41
57.6
4.8 89.1 25.3
46.7
72.6 4.28
4.43
64.4
5.3 90.0 25.3
51.9
79.5 4.30
4.47
65.4
5.3 90.1 25.3
53.5
80.7 4.34
5.77
50.3
3.6 108.8 22.7
48.3
70.0 5.60
5.80
56.8
3.9 109.6 22.7
52.8
76.6 5.63
5.85
57.7
3.9 109.8 22.7
54.3
77.7 5.68
7.19
43.4
2.8 128.6 20.9
49.9
67.9 6.97
7.23
49.6
3.0 129.4 20.9
53.7
74.3 7.01
7.29
50.5
3.0 129.5 20.9
55.0
75.4 7.07

GPM
Heat COP Load Load
Of
LWT WPD
Absorb
Ft
Head
47.6
6.2 65.6 47.9
52.9
6.8 66.1 47.9
53.7
6.8 66.2 47.9
41.2
4.2 85.3 41.8
46.3
4.6 85.8 41.8
47.0
4.6 85.9 41.8
35.3
3.1 105.1 37.7
40.1
3.4 105.6 37.7
40.8
3.4 105.7 37.7
29.6
2.4 125.0 34.6
34.2
2.6 125.5 34.6
34.9
2.6 125.6 34.6
53.0
6.6 66.1 47.9
58.9
7.1 66.7 47.9
59.8
7.2 66.8 47.9
46.1
4.4 85.9 41.8
51.7
4.8 86.4 41.8
52.5
4.8 86.5 41.8
39.8
3.2 105.7 37.7
45.1
3.5 106.2 37.7
45.8
3.5 106.3 37.7
33.7
2.5 125.5 34.6
38.8
2.7 126.1 34.6
39.5
2.8 126.1 34.6
59.0
6.9 66.8 47.9
65.6
7.5 67.4 47.9
66.6
7.6 67.5 47.9
51.7
4.7 86.5 41.8
57.9
5.1 87.1 41.8
58.8
5.1 87.2 41.8
44.9
3.4 106.3 37.7
50.8
3.7 106.8 37.7
51.7
3.8 106.9 37.7
38.5
2.7 126.1 34.6
44.3
2.9 126.7 34.6
45.0
2.9 126.8 34.6
65.9
7.4 67.5 47.9
73.0
8.0 68.2 47.9
74.1
8.1 68.3 47.9
58.0
5.0 87.1 41.8
64.8
5.4 87.8 41.8
65.9
5.4 87.9 41.8
50.9
3.7 106.9 37.7
57.4
4.0 107.6 37.7
58.3
4.0 107.7 37.7
44.1
2.9 126.7 34.6
50.4
3.1 127.4 34.6
51.3
3.1 127.5 34.6

WSHP-PRC009-EN

Performance Data
WPWD 072-Heating
Table P-11: 072 Heating Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source Source


EWT EWT GPM WPD LWT
Ft
Head
70.0 60.0
8.7
7.6
53.4
70.0 60.0 16.0
26.9
60.0
70.0 60.0 20.4
44.5
62.0
70.0 80.0
8.7
7.6
55.4
70.0 80.0 16.0
26.9
61.1
70.0 80.0 20.4
44.5
62.9
70.0 100.0 8.7
7.6
57.3
70.0 100.0 16.0
26.9
62.2
70.0 100.0 20.4
44.5
63.8
70.0 120.0 8.7
7.6
59.1
70.0 120.0 16.0
26.9
63.2
70.0 120.0 20.4
44.5
64.6
80.0 60.0
8.7
7.1
61.4
80.0 60.0 16.0
25.3
68.8
80.0 60.0 20.4
41.8
71.1
80.0 80.0
8.7
7.1
63.6
80.0 80.0 16.0
25.3
70.0
80.0 80.0 20.4
41.8
72.1
80.0 100.0 8.7
7.1
65.6
80.0 100.0 16.0
25.3
71.2
80.0 100.0 20.4
41.8
73.0
80.0 120.0 8.7
7.1
67.5
80.0 120.0 16.0
25.3
72.2
80.0 120.0 20.4
41.8
73.8

WSHP-PRC009-EN

Load 8.7
GPM
Load
Heat Power Heat COP Load Load Source Heat
Cap
kW
Of
LWT WPD LWT Cap
Mbtuh
Absorb
Ft
Mbtuh
Head
84.1 3.51
72.1
7.0 79.3 8.2
53.2 84.1
92.1 3.53
80.1
7.6 81.2 8.2
59.8 92.1
93.4 3.56
81.3
7.7 81.5 8.2
61.9 93.4
80.2 4.97
63.2
4.7 98.5 7.1
55.1 80.2
87.8 4.99
70.8
5.2 100.2 7.1
61.0 87.8
89.0 5.04
71.8
5.2 100.5 7.1
62.8 89.0
77.3 6.50
55.1
3.5 117.9 6.4
56.9 77.3
84.6 6.53
62.3
3.8 119.6 6.4
62.0 84.6
85.8 6.59
63.3
3.8 119.9 6.4
63.6 85.8
74.9 8.10
47.3
2.7 137.4 5.9
58.6 74.9
82.0 8.14
54.2
3.0 139.1 5.9
62.9 82.0
83.2 8.22
55.2
3.0 139.4 5.9
64.3 83.2
92.8 3.60
80.5
7.6 81.3 8.2
61.2 92.8
101.6 3.62
89.2
8.2 83.4 8.2
68.7 101.6
103.1 3.65
90.6
8.3 83.7 8.2
71.0 103.1
88.5 5.09
71.1
5.1 100.4 7.1
63.3 88.5
96.9 5.12
79.4
5.5 102.3 7.1
69.8 96.9
98.3 5.16
80.7
5.6 102.7 7.1
71.9 98.3
85.3 6.66
62.6
3.8 119.7 6.4
65.1 85.3
93.3 6.70
70.4
4.1 121.6 6.4
70.9 93.3
94.7 6.76
71.6
4.1 121.9 6.4
72.8 94.7
82.7 8.30
54.4
2.9 139.2 5.9
66.9 82.7
90.6 8.35
62.1
3.2 141.1 5.9
71.9 90.6
91.9 8.42
63.2
3.2 141.4 5.9
73.5 91.9

16.0 GPM
Load 20.4
Power Heat COP Load Load Source Heat Power
kW
Of
LWT WPD LWT
Cap
kW
Absorb
Ft
Mbtuh
Head
3.21
73.1
7.7 70.5 28.9
53.1
84.1 3.11
3.22
81.1
8.4 71.5 28.9
59.8
92.1 3.13
3.25
82.3
8.4 71.7 28.9
61.9
93.4 3.16
4.54
64.7
5.2 90.1 25.3
55.0
80.2 4.40
4.56
72.2
5.6 91.0 25.3
60.9
87.8 4.42
4.60
73.3
5.7 91.2 25.3
62.8
89.0 4.46
5.94
57.0
3.8 109.7 22.7
56.7
77.3 5.76
5.97
64.2
4.2 110.6 22.7
61.9
84.6 5.79
6.02
65.3
4.2 110.8 22.7
63.5
85.8 5.84
7.40
49.6
3.0 129.5 20.9
58.4
74.9 7.18
7.44
56.6
3.2 130.4 20.9
62.8
82.0 7.21
7.50
57.6
3.3 130.5 20.9
64.3
83.2 7.28
3.29
81.6
8.3 71.6 28.9
61.1
92.8 3.19
3.30
90.3
9.0 72.7 28.9
68.6 101.6 3.20
3.33
91.7
9.1 72.9 28.9
70.9 103.1 3.23
4.65
72.6
5.6 91.1 25.3
63.1
88.5 4.51
4.67
81.0
6.1 92.1 25.3
69.8
96.9 4.53
4.72
82.2
6.1 92.3 25.3
71.9
98.3 4.58
6.09
64.5
4.1 110.7 22.7
65.0
85.3 5.90
6.12
72.4
4.5 111.7 22.7
70.8
93.3 5.93
6.17
73.6
4.5 111.9 22.7
72.7
94.7 5.99
7.58
56.8
3.2 130.5 20.9
66.7
82.7 7.36
7.62
64.6
3.5 131.5 20.9
71.8
90.6 7.39
7.69
65.7
3.5 131.6 20.9
73.5
91.9 7.46

GPM
Heat COP Load Load
Of
LWT WPD
Absorb
Ft
Head
73.5
7.9 68.3 47.9
81.4
8.6 69.0 47.9
82.6
8.7 69.2 47.9
65.2
5.3 87.9 41.8
72.7
5.8 88.6 41.8
73.8
5.8 88.8 41.8
57.6
3.9 107.6 37.7
64.8
4.3 108.3 37.7
65.9
4.3 108.5 37.7
50.4
3.1 127.4 34.6
57.4
3.3 128.1 34.6
58.4
3.3 128.3 34.6
81.9
8.5 69.1 47.9
90.7
9.3 70.0 47.9
92.1
9.4 70.1 47.9
73.1
5.7 88.7 41.8
81.4
6.3 89.5 41.8
82.7
6.3 89.7 41.8
65.2
4.2 108.4 37.7
73.1
4.6 109.2 37.7
74.3
4.6 109.3 37.7
57.6
3.3 128.2 34.6
65.4
3.6 129.0 34.6
66.4
3.6 129.1 34.6

41

Performance Data
EXWA 240-Cooling
Table P-12: 240 Cooling Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.
Load 30.0 GPM
Source Load Source Source Source Cool Power Heat EER
EWT EWT GPM WPD LWT
Cap
kW
Of
Ft
Mbtuh
Reject
Head
50.0 45.0 30.0
3.7
64.0 174.5 10.27 209.6 17.0
50.0 45.0 55.0
10.1
57.6 176.5 9.59 209.2 18.4
50.0 45.0 70.0
15.1
56.0 177.7 9.41 209.8 18.9
50.0 53.6 30.0
3.7
65.7 199.7 10.68 236.2 18.7
50.0 53.6 55.0
10.1
58.6 202.0 9.97 236.0 20.3
50.0 53.6 70.0
15.1
56.8 203.4 9.78 236.8 20.8
50.0 65.0 30.0
3.7
68.1 233.1 11.12 271.1 21.0
50.0 65.0 55.0
10.1
59.9 235.9 10.38 271.3 22.7
50.0 65.0 70.0
15.1
57.8 237.5 10.19 272.3 23.3
50.0 75.0 30.0
3.7
70.1 262.5 11.44 301.5 22.9
50.0 75.0 55.0
10.1
61.0 265.5 10.68 302.0 24.9
50.0 75.0 70.0
15.1
58.7 267.4 10.48 303.2 25.5
60.0 45.0 30.0
3.4
73.9 168.9 11.50 208.2 14.7
60.0 45.0 55.0
9.2
67.6 170.8 10.74 207.5 15.9
60.0 45.0 70.0
13.9
65.9 172.0 10.54 208.0 16.3
60.0 53.6 30.0
3.4
75.7 194.1 11.90 234.7 16.3
60.0 53.6 55.0
9.2
68.5 196.4 11.11 234.3 17.7
60.0 53.6 70.0
13.9
66.7 197.7 10.90 234.9 18.1
60.0 65.0 30.0
3.4
78.0 227.5 12.33 269.6 18.5
60.0 65.0 55.0
9.2
69.8 230.2 11.51 269.5 20.0
60.0 65.0 70.0
13.9
67.7 231.8 11.30 270.4 20.5
60.0 75.0 30.0
3.4
80.0 256.9 12.63 300.0 20.3
60.0 75.0 55.0
9.2
70.9 259.9 11.79 300.1 22.0
60.0 75.0 70.0
13.9
68.6 261.7 11.57 301.2 22.6
70.0 45.0 30.0
3.1
83.7 162.0 12.84 205.8 12.6
70.0 45.0 55.0
8.6
77.5 163.9 11.99 204.8 13.7
70.0 45.0 70.0
13.0
75.9 165.0 11.77 205.2 14.0
70.0 53.6 30.0
3.1
85.5 187.2 13.25 232.4 14.1
70.0 53.6 55.0
8.6
78.4 189.4 12.37 231.6 15.3
70.0 53.6 70.0
13.0
76.6 190.7 12.14 232.1 15.7
70.0 65.0 30.0
3.1
87.9 220.7 13.68 267.4 16.1
70.0 65.0 55.0
8.6
79.7 223.2 12.77 266.8 17.5
70.0 65.0 70.0
13.0
77.7 224.8 12.53 267.6 17.9
70.0 75.0 30.0
3.1
89.9 250.0 13.98 297.7 17.9
70.0 75.0 55.0
8.6
80.8 252.9 13.05 297.4 19.4
70.0 75.0 70.0
13.0
78.5 254.7 12.81 298.4 19.9
80.0 45.0 30.0
2.9
93.6 153.8 14.33 202.7 10.7
80.0 45.0 55.0
8.1
87.3 155.6 13.38 201.3 11.6
80.0 45.0 70.0
12.2
85.8 156.7 13.13 201.5 11.9
80.0 53.6 30.0
2.9
95.3 179.1 14.77 229.5 12.1
80.0 53.6 55.0
8.1
88.3 181.2 13.79 228.3 13.1
80.0 53.6 70.0
12.2
86.6 182.4 13.53 228.6 13.5
80.0 65.0 30.0
2.9
97.7 212.5 15.21 264.4 14.0
80.0 65.0 55.0
8.1
89.6 215.0 14.21 263.5 15.1
80.0 65.0 70.0
12.2
87.6 216.5 13.94 264.1 15.5
80.0 75.0 30.0
2.9
99.7 241.8 15.52 294.8 15.6
80.0 75.0 55.0
8.1
90.7 244.7 14.49 294.2 16.9
80.0 75.0 70.0
12.2
88.5 246.4 14.22 294.9 17.3

42

Load 55.0
Load Load Source Cool Power
LWT WPD LWT
Cap
kW
Ft
Mbtuh
Head
33.4 3.9
65.2 191.7 10.42
33.2 3.9
58.3 193.9 9.73
33.2 3.9
56.5 195.3 9.55
40.3 3.6
67.1 219.4 10.83
40.1 3.6
59.3 222.0 10.11
40
3.6
57.4 223.5 9.92
49.4 3.3
69.6 256.1 11.28
49.3 3.3
60.7 259.1 10.53
49.1 3.3
58.5 260.9 10.34
57.5 3.0
71.9 288.4 11.60
57.3 3.0
62.0 291.7 10.83
57.1 3.0
59.4 293.8 10.63
33.7 3.9
75.0 185.5 11.67
33.6 3.9
68.2 187.7 10.89
33.5 3.9
66.4 189.0 10.69
40.7 3.6
77.0 213.3 12.07
40.5 3.6
69.2 215.7 11.27
40.4 3.6
67.3 217.2 11.06
49.8 3.3
79.5 250.0 12.51
49.6 3.3
70.7 252.9 11.68
49.5 3.3
68.4 254.7 11.46
57.8 3.0
81.7 282.2 12.81
57.6 3.0
71.9 285.5 11.96
57.5 3.0
69.4 287.5 11.74
34.2 3.9
84.9 178.0 13.03
34.1 3.9
78.1 180.1 12.16
34
3.9
76.4 181.3 11.94
41.1 3.6
86.8 205.7 13.44
41
3.6
79.1 208.1 12.55
40.9 3.6
77.2 209.6 12.32
50.3 3.3
89.4 242.4 13.88
50.1 3.3
80.5 245.3 12.96
50
3.3
78.3 247.0 12.71
58.3 3.0
91.6 274.7 14.18
58.1 3.0
81.8 277.9 13.24
58
3.0
79.3 279.8 12.99
34.7 3.9
94.6 169.0 14.54
34.6 3.9
87.9 171.0 13.57
34.6 3.9
86.2 172.2 13.32
41.7 3.6
96.6 196.7 14.98
41.5 3.6
89.0 199.0 13.99
41.4 3.6
87.1 200.4 13.73
50.8 3.3
99.1 233.5 15.43
50.7 3.3
90.4 236.2 14.41
50.6 3.3
88.2 237.8 14.14
58.8 3.0 101.4 265.7 15.74
58.6 3.0
91.6 268.8 14.70
58.5 3.0
89.2 270.7 14.42

GPM
Load 70.0 GPM
Heat EER Load Load Source Cool Power Heat EER
Of
LWT WPD LWT
Cap
kW
Of
Reject
Ft
Mbtuh
Reject
Head
227.3 18.4 38.0 10.6
65.5 196.5 10.43 232.1 18.8
227.1 19.9 38.0 10.6
58.4 198.8 9.74 232.0 20.4
227.9 20.5 37.9 10.6
56.7 200.2 9.56 232.8 20.9
256.4 20.3 45.6 9.7
67.5 225.0 10.84 262.0 20.8
256.5 22.0 45.5 9.7
59.5 227.6 10.12 262.1 22.5
257.4 22.5 45.5 9.7
57.5 229.2 9.94 263.1 23.1
294.6 22.7 55.7 8.9
70.1 262.6 11.29 301.1 23.3
295.0 24.6 55.6 8.9
61.0 265.7 10.55 301.7 25.2
296.2 25.2 55.5 8.9
58.7 267.6 10.35 302.9 25.9
328.0 24.9 64.5 8.3
72.4 295.7 11.62 335.4 25.4
328.7 26.9 64.4 8.3
62.2 299.1 10.85 336.1 27.6
330.1 27.6 64.3 8.3
59.6 301.2 10.64 337.5 28.3
225.3 15.9 38.3 10.6
75.3 190.2 11.68 230.1 16.3
224.9 17.2 38.2 10.6
68.4 192.5 10.91 229.7 17.6
225.5 17.7 38.1 10.6
66.6 193.8 10.70 230.3 18.1
254.5 17.7 45.8 9.7
77.3 218.7 12.08 259.9 18.1
254.2 19.1 45.8 9.7
69.4 221.2 11.28 259.7 19.6
255.0 19.6 45.7 9.7
67.5 222.8 11.07 260.6 20.1
292.7 20.0 55.9 8.9
79.9 256.3 12.52 299.0 20.5
292.8 21.7 55.8 8.9
70.9 259.3 11.69 299.2 22.2
293.8 22.2 55.7 8.9
68.6 261.1 11.47 300.3 22.8
325.9 22.0 64.7 8.3
82.2 289.4 12.82 333.2 22.6
326.3 23.9 64.6 8.3
72.1 292.8 11.97 333.7 24.5
327.6 24.5 64.5 8.3
69.6 294.8 11.75 334.9 25.1
222.5 13.7 38.5 10.6
85.2 182.5 13.04 227.0 14.0
221.6 14.8 38.5 10.6
78.2 184.6 12.18 226.2 15.2
222.1 15.2 38.4 10.6
76.5 185.9 11.95 226.7 15.6
251.6 15.3 46.1 9.7
87.1 210.9 13.46 256.8 15.7
250.9 16.6 46.0 9.7
79.3 213.4 12.56 256.3 17.0
251.7 17.0 46.0 9.7
77.4 214.9 12.33 257.0 17.4
289.8 17.5 56.2 8.9
89.8 248.6 13.89 296.0 17.9
289.5 18.9 56.1 8.9
80.8 251.5 12.97 295.8 19.4
290.4 19.4 56.0 8.9
78.5 253.3 12.73 296.8 19.9
323.1 19.4 65.0 8.3
92.0 281.6 14.19 330.0 19.8
323.1 21.0 64.9 8.3
82.0 284.9 13.25 330.1 21.5
324.1 21.5 64.8 8.3
79.5 286.9 13.00 331.3 22.1
218.6 11.6 38.9 10.6
94.9 173.3 14.55 223.0 11.9
217.3 12.6 38.8 10.6
88.1 175.3 13.59 221.7 12.9
217.7 12.9 38.7 10.6
86.4 176.5 13.33 222.0 13.2
247.8 13.1 46.4 9.7
96.9 201.7 15.00 252.9 13.4
246.8 14.2 46.4 9.7
89.2 204.1 14.00 251.9 14.6
247.3 14.6 46.3 9.7
87.2 205.5 13.74 252.4 15.0
286.2 15.1 56.5 8.9
99.5 239.4 15.45 292.1 15.5
285.4 16.4 56.4 8.9
90.6 242.2 14.43 291.5 16.8
286.1 16.8 56.3 8.9
88.4 243.9 14.16 292.2 17.2
319.4 16.9 65.3 8.3
101.8 272.4 15.76 326.2 17.3
319.0 18.3 65.2 8.3
91.9 275.6 14.71 325.8 18.7
319.9 18.8 65.1 8.3
89.4 277.5 14.44 326.8 19.2

Load Load
LWT WPD
Ft
Head
39.4 15.9
39.3 15.9
39.3 15.9
47.2 14.7
47.1 14.7
47.1 14.7
57.5 13.4
57.4 13.4
57.3 13.4
66.5 12.6
66.4 12.6
66.4 12.6
39.6 15.9
39.5 15.9
39.5 15.9
47.4 14.7
47.3 14.7
47.2 14.7
57.7 13.4
57.6 13.4
57.5 13.4
66.7 12.6
66.6 12.6
66.6 12.6
39.8 15.9
39.7 15.9
39.7 15.9
47.6 14.7
47.5 14.7
47.5 14.7
57.9 13.4
57.8 13.4
57.8 13.4
66.9 12.6
66.8 12.6
66.8 12.6
40.0 15.9
40.0 15.9
40.0 15.9
47.8 14.7
47.8 14.7
47.7 14.7
58.2 13.4
58.1 13.4
58.0 13.4
67.2 12.6
67.1 12.6
67.1 12.6

WSHP-PRC009-EN

Performance Data
EXWA 240-Cooling
Table P-12: 240 Cooling Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
90.0 45.0 30.0
2.8
90.0 45.0 55.0
7.7
90.0 45.0 70.0
11.6
90.0 53.6 30.0
2.8
90.0 53.6 55.0
7.7
90.0 53.6 70.0
11.6
90.0 65.0 30.0
2.8
90.0 65.0 55.0
7.7
90.0 65.0 70.0
11.6
90.0 75.0 30.0
2.8
90.0 75.0 55.0
7.7
90.0 75.0 70.0
11.6
100.0 45.0 30.0
2.6
100.0 45.0 55.0
7.3
100.0 45.0 70.0
11.0
100.0 53.6 30.0
2.6
100.0 53.6 55.0
7.3
100.0 53.6 70.0
11.0
100.0 65.0 30.0
2.6
100.0 65.0 55.0
7.3
100.0 65.0 70.0
11.0
100.0 75.0 30.0
2.6
100.0 75.0 55.0
7.3
100.0 75.0 70.0
11.0
110.0 45.0 30.0
2.5
110.0 45.0 55.0
7.0
110.0 45.0 70.0
10.5
110.0 53.6 30.0
2.5
110.0 53.6 55.0
7.0
110.0 53.6 70.0
10.5
110.0 65.0 30.0
2.5
110.0 65.0 55.0
7.0
110.0 65.0 70.0
10.5
110.0 75.0 30.0
2.5
110.0 75.0 55.0
7.0
110.0 75.0 70.0
10.5
120.0 45.0 30.0
2.4
120.0 45.0 55.0
6.7
120.0 45.0 70.0
10.1
120.0 53.6 30.0
2.4
120.0 53.6 55.0
6.7
120.0 53.6 70.0
10.1
120.0 65.0 30.0
2.4
120.0 65.0 55.0
6.7
120.0 65.0 70.0
10.1
120.0 75.0 30.0
2.4
120.0 75.0 55.0
6.7
120.0 75.0 70.0
10.1

WSHP-PRC009-EN

Load 30.0 GPM


Source Cool Power Heat EER Load Load
LWT Cap
kW
Of
LWT WPD
Mbtuh
Reject
Ft
Head
103.3 144.4 16.00 199.0 9.0 35.4 3.9
97.2 146.1 14.94 197.1 9.8 35.3 3.9
95.7 147.1 14.66 197.1 10.0 35.2 3.9
105.1 169.6 16.49 225.9 10.3 42.3 3.6
98.2 171.6 15.40 224.2 11.1 42.2 3.6
96.4 172.8 15.11 224.4 11.4 42.1 3.6
107.5 203.0 16.97 260.9 12.0 51.5 3.3
99.5 205.4 15.85 259.5 13.0 51.3 3.3
97.5 206.8 15.55 259.9 13.3 51.2 3.3
109.5 232.4 17.29 291.4 13.4 59.5 3.0
100.6 235.1 16.15 290.2 14.6 59.3 3.0
98.3 236.7 15.85 290.8 14.9 59.2 3.0
113.1 133.6 17.91 194.7 7.5 36.1 3.9
107.0 135.2 16.72 192.3 8.1
36
3.9
105.5 136.1 16.41 192.1 8.3 35.9 3.9
114.9 158.9 18.46 221.9 8.6
43
3.6
108.0 160.7 17.24 219.5 9.3 42.9 3.6
106.3 161.8 16.92 219.6 9.6 42.8 3.6
117.3 192.3 18.99 257.1 10.1 52.2 3.3
109.3 194.6 17.74 255.2 11.0
52
3.3
107.3 195.9 17.40 255.3 11.3 51.9 3.3
119.3 221.6 19.34 287.6 11.5 60.2 3.0
110.5 224.2 18.06 285.8 12.4
60
3.0
108.2 225.8 17.72 286.3 12.7 59.9 3.0
122.8 121.6 20.07 190.1 6.1 36.9 3.9
116.9 123.0 18.74 187.0 6.6 36.8 3.9
115.4 123.9 18.39 186.7 6.7 36.7 3.9
124.6 146.8 20.72 217.5 7.1 43.8 3.6
117.9 148.5 19.34 214.5 7.7 43.7 3.6
116.2 149.6 18.98 214.4 7.9 43.6 3.6
127.0 180.3 21.32 253.1 8.5
53
3.3
119.2 182.4 19.90 250.3 9.2 52.8 3.3
117.2 183.6 19.53 250.3 9.4 52.7 3.3
129.1 209.6 21.70 283.7 9.7
61
3.0
120.3 212.1 20.27 281.3 10.5 60.8 3.0
118.1 213.5 19.89 281.4 10.7 60.7 3.0
132.5 108.3 22.55 185.3 4.8 37.8 3.9
126.7 109.6 21.05 181.4 5.2 37.7 3.9
125.2 110.3 20.66 180.8 5.3 37.6 3.9
134.4 133.5 23.29 213.0 5.7 44.7 3.6
127.7 135.1 21.75 209.3 6.2 44.6 3.6
126.0 136.0 21.34 208.8 6.4 44.5 3.6
136.8 167.0 23.98 248.8 7.0 53.9 3.3
129.0 168.9 22.39 245.3 7.5 53.7 3.3
127.1 170.1 21.97 245.1 7.7 53.6 3.3
138.9 196.3 24.42 279.7 8.0 61.9 3.0
130.2 198.6 22.80 276.4 8.7 61.7 3.0
128.0 200.0 22.37 276.4 8.9 61.6 3.0

Load 55.0 GPM


Source Cool Power Heat EER Load Load
LWT Cap
kW
Of
LWT WPD
Mbtuh
Reject
Ft
Head
104.3 158.6 16.24 214.0 9.8 39.2 10.6
97.8 160.5 15.16 212.2 10.6 39.2 10.6
96.1 161.6 14.88 212.4 10.9 39.1 10.6
106.3 186.3 16.73 243.4 11.1 46.8 9.7
98.8 188.5 15.62 241.8 12.1 46.7 9.7
96.9 189.8 15.33 242.1 12.4 46.7 9.7
108.9 223.1 17.22 281.9 13.0 56.9 8.9
100.3 225.7 16.08 280.6 14.0 56.8 8.9
98.1 227.3 15.78 281.2 14.4 56.7 8.9
111.1 255.3 17.54 315.2 14.6 65.7 8.3
101.5 258.3 16.38 314.2 15.8 65.6 8.3
99.0 260.1 16.08 315.0 16.2 65.5 8.3
114.0 146.8 18.16 208.8 8.1 39.7 10.6
107.6 148.5 16.96 206.4 8.8 39.6 10.6
105.9 149.6 16.64 206.4 9.0 39.6 10.6
116.0 174.5 18.73 238.4 9.3 47.3 9.7
108.7 176.6 17.49 236.3 10.1 47.2 9.7
106.8 177.8 17.16 236.4 10.4 47.1 9.7
118.6 211.3 19.27 277.1 11.0 57.3 8.9
110.1 213.8 17.99 275.2 11.9 57.2 8.9
107.9 215.2 17.66 275.5 12.2 57.2 8.9
120.8 243.5 19.62 310.5 12.4 66.1 8.3
111.3 246.4 18.32 308.9 13.4 66.0 8.3
108.9 248.1 17.98 309.5 13.8 66.0 8.3
123.7 133.6 20.36 203.1 6.6 40.1 10.6
117.3 135.2 19.01 200.1 7.1 40.1 10.6
115.8 136.1 18.66 199.8 7.3 40.1 10.6
125.7 161.3 21.01 233.0 7.7 47.7 9.7
118.4 163.2 19.62 230.2 8.3 47.7 9.7
116.6 164.3 19.26 230.0 8.5 47.6 9.7
128.3 198.1 21.63 271.9 9.2 57.8 8.9
119.9 200.4 20.19 269.3 9.9 57.7 8.9
117.8 201.8 19.82 269.5 10.2 57.7 8.9
130.6 230.3 22.02 305.5 10.5 66.6 8.3
121.1 233.0 20.56 303.2 11.3 66.5 8.3
118.7 234.6 20.18 303.5 11.6 66.4 8.3
133.3 119.0 22.87 197.1 5.2 40.7 10.6
127.1 120.4 21.36 193.3 5.6 40.6 10.6
125.6 121.2 20.96 192.7 5.8 40.6 10.6
135.3 146.7 23.63 227.4 6.2 48.3 9.7
128.2 148.4 22.06 223.7 6.7 48.2 9.7
126.5 149.4 21.65 223.3 6.9 48.2 9.7
138.0 183.4 24.33 266.4 7.5 58.3 8.9
129.7 185.6 22.71 263.1 8.2 58.2 8.9
127.6 186.9 22.29 263.0 8.4 58.2 8.9
140.2 215.7 24.77 300.2 8.7 67.1 8.3
130.9 218.2 23.13 297.1 9.4 67.0 8.3
128.6 219.7 22.70 297.2 9.7 67.0 8.3

Load 70.0 GPM


Source Cool Power Heat EER Load Load
LWT Cap
kW
Of
LWT WPD
Mbtuh
Reject
Ft
Head
104.6 162.7 16.25 218.2 10.0 40.4 15.9
97.9 164.6 15.18 216.4 10.8 40.3 15.9
96.2 165.7 14.89 216.5 11.1 40.3 15.9
106.6 191.1 16.75 248.3 11.4 48.1 14.7
99.0 193.3 15.64 246.7 12.4 48.1 14.7
97.1 194.7 15.35 247.1 12.7 48.0 14.7
109.3 228.7 17.24 287.5 13.3 58.5 13.4
100.5 231.4 16.09 286.3 14.4 58.4 13.4
98.2 233.0 15.79 286.9 14.8 58.3 13.4
111.5 261.8 17.56 321.7 14.9 67.5 12.6
101.7 264.9 16.40 320.9 16.2 67.4 12.6
99.2 266.7 16.09 321.6 16.6 67.4 12.6
114.3 150.5 18.18 212.6 8.3 40.7 15.9
107.7 152.3 16.98 210.3 9.0 40.6 15.9
106.0 153.4 16.66 210.3 9.2 40.6 15.9
116.3 179.0 18.75 243.0 9.5 48.5 14.7
108.8 181.1 17.51 240.9 10.3 48.4 14.7
106.9 182.3 17.18 240.9 10.6 48.4 14.7
119.0 216.6 19.29 282.4 11.2 58.8 13.4
110.3 219.2 18.01 280.7 12.2 58.7 13.4
108.1 220.7 17.67 281.0 12.5 58.7 13.4
121.3 249.7 19.64 316.7 12.7 67.8 12.6
111.5 252.6 18.34 315.2 13.8 67.8 12.6
109.1 254.4 18.00 315.8 14.1 67.7 12.6
123.9 137.0 20.39 206.6 6.7 41.1 15.9
117.5 138.6 19.03 203.6 7.3 41.0 15.9
115.9 139.6 18.68 203.4 7.5 41.0 15.9
126.0 165.4 21.04 237.2 7.9 48.9 14.7
118.6 167.4 19.64 234.4 8.5 48.8 14.7
116.8 168.5 19.28 234.3 8.7 48.8 14.7
128.6 203.1 21.65 277.0 9.4 59.2 13.4
120.1 205.5 20.21 274.5 10.2 59.1 13.4
117.9 206.9 19.84 274.6 10.4 59.1 13.4
130.9 236.1 22.04 311.3 10.7 68.2 12.6
121.3 238.9 20.58 309.1 11.6 68.2 12.6
118.9 240.6 20.20 309.5 11.9 68.1 12.6
133.5 122.0 22.90 200.2 5.3 41.5 15.9
127.2 123.4 21.38 196.4 5.8 41.5 15.9
125.7 124.3 20.98 195.9 5.9 41.4 15.9
135.6 150.4 23.65 231.1 6.4 49.3 14.7
128.4 152.2 22.09 227.6 6.9 49.3 14.7
126.6 153.2 21.67 227.2 7.1 49.2 14.7
138.3 188.1 24.35 271.2 7.7 59.6 13.4
129.9 190.3 22.74 267.9 8.4 59.6 13.4
127.7 191.6 22.32 267.8 8.6 59.5 13.4
140.6 221.1 24.80 305.7 8.9 68.7 12.6
131.1 223.7 23.15 302.7 9.7 68.6 12.6
128.8 225.3 22.72 302.8 9.9 68.5 12.6

43

Performance Data
EXWA 240-Heating
Table P-13: 240 Heating Performance
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
30.0
60.0 30.0
4.6
30.0
60.0 55.0
12.6
30.0
60.0 70.0
18.9
30.0
80.0 30.0
4.6
30.0
80.0 55.0
12.6
30.0
80.0 70.0
18.9
30.0 100.0 30.0
4.6
30.0 100.0 55.0
12.6
30.0 100.0 70.0
18.9
30.0 120.0 30.0
4.6
30.0 120.0 55.0
12.6
30.0 120.0 70.0
18.9
40.0
60.0 30.0
4.1
40.0
60.0 55.0
11.1
40.0
60.0 70.0
16.7
40.0
80.0 30.0
4.1
40.0
80.0 55.0
11.1
40.0
80.0 70.0
16.7
40.0 100.0 30.0
4.1
40.0 100.0 55.0
11.1
40.0 100.0 70.0
16.7
40.0 120.0 30.0
4.1
40.0 120.0 55.0
11.1
40.0 120.0 70.0
16.7
50.0
60.0 30.0
3.7
50.0
60.0 55.0
10.1
50.0
60.0 70.0
15.1
50.0
80.0 30.0
3.7
50.0
80.0 55.0
10.1
50.0
80.0 70.0
15.1
50.0 100.0 30.0
3.7
50.0 100.0 55.0
10.1
50.0 100.0 70.0
15.1
50.0 120.0 30.0
3.7
50.0 120.0 55.0
10.1
50.0 120.0 70.0
15.1
60.0
60.0 30.0
3.4
60.0
60.0 55.0
9.2
60.0
60.0 70.0
13.9
60.0
80.0 30.0
3.4
60.0
80.0 55.0
9.2
60.0
80.0 70.0
13.9
60.0 100.0 30.0
3.4
60.0 100.0 55.0
9.2
60.0 100.0 70.0
13.9
60.0 120.0 30.0
3.4
60.0 120.0 55.0
9.2
60.0 120.0 70.0
13.9

44

Load 30.0 GPM


Load
Source Heat Power Heat COP Load Load Source Heat
LWT Cap
kW
Of
LWT WPD LWT
Cap
Mbtuh
Absor
Ft
Mbtuh
b
Head
21.5 165.3 10.88 128.2 4.5 71.0 3.4
21.3 165.3
24.8 180.9 11.02 143.3 4.8 72.1 3.4
24.7 180.9
25.9 183.5 11.19 145.3 4.8 72.2 3.4
25.8 183.5
22.3 163.1 14.06 115.1 3.4 90.9 2.9
22.1 163.1
25.3 178.5 14.23 129.9 3.7 91.9 2.9
25.1 178.5
26.2 181.0 14.45 131.7 3.7 92.1 2.9
26.1 181.0
23.4 160.9 18.07 99.2
2.6 110.8 2.6
23.0 160.9
25.9 176.1 18.29 113.7 2.8 111.8 2.6
25.7 176.1
26.7 178.6 18.58 115.2 2.8 112.0 2.6
26.6 178.6
24.6 158.7 22.98 80.3
2.0 130.7 2.4
24.2 158.7
26.6 173.7 23.26 94.3
2.2 131.7 2.4
26.3 173.7
27.3 176.2 23.63 95.6
2.2 131.9 2.4
27.1 176.2
29.7 193.2 11.51 153.9 4.9 72.9 3.4
29.5 193.2
33.8 211.4 11.65 171.6 5.3 74.1 3.4
33.6 211.4
35.0 214.5 11.84 174.1 5.3 74.3 3.4
34.9 214.5
30.7 189.7 14.62 139.8 3.8 92.7 2.9
30.4 189.7
34.3 207.5 14.80 157.0 4.1 93.9 2.9
34.1 207.5
35.5 210.5 15.04 159.2 4.1 94.1 2.9
35.3 210.5
31.8 186.1 18.61 122.6 2.9 112.5 2.6
31.5 186.1
34.9 203.7 18.83 139.4 3.2 113.7 2.6
34.7 203.7
36.0 206.6 19.13 141.3 3.2 113.9 2.6
35.8 206.6
33.2 182.6 23.52 102.3 2.3 132.3 2.4
32.7 182.6
35.7 199.8 23.81 118.5 2.5 133.5 2.4
35.4 199.8
36.6 202.7 24.19 120.1 2.5 133.7 2.4
36.4 202.7
38.0 221.9 12.08 180.7 5.4 74.8 3.4
37.7 221.9
42.7 242.8 12.23 201.1 5.8 76.2 3.4
42.6 242.8
44.2 246.3 12.42 203.9 5.8 76.4 3.4
44.1 246.3
39.0 217.0 15.14 165.3 4.2 94.5 2.9
38.7 217.0
43.3 237.4 15.32 185.1 4.5 95.9 2.9
43.1 237.4
44.6 240.9 15.57 187.8 4.5 96.1 2.9
44.5 240.9
40.2 212.1 19.11 146.9 3.3 114.2 2.6
39.8 212.1
44.0 232.1 19.34 166.1 3.5 115.6 2.6
43.8 232.1
45.2 235.4 19.64 168.4 3.5 115.8 2.6
45.0 235.4
41.7 207.2 24.04 125.2 2.5 134.0 2.4
41.2 207.2
44.8 226.7 24.33 143.7 2.7 135.3 2.4
44.5 226.7
45.8 230.0 24.71 145.7 2.7 135.5 2.4
45.6 230.0
46.1 251.3 12.60 208.3 5.8 76.8 3.4
45.9 251.3
51.6 275.0 12.75 231.5 6.3 78.3 3.4
51.4 275.0
53.3 278.9 12.95 234.7 6.3 78.6 3.4
53.2 278.9
47.2 245.1 15.62 191.8 4.6 96.4 2.9
46.9 245.1
52.2 268.1 15.81 214.1 5.0 97.9 2.9
52.0 268.1
53.8 272.0 16.06 217.2 5.0 98.2 2.9
53.7 272.0
48.5 238.8 19.58 172.0 3.6 116.0 2.6
48.1 238.8
53.0 261.3 19.81 193.7 3.9 117.5 2.6
52.7 261.3
54.4 265.1 20.13 196.4 3.9 117.8 2.6
54.2 265.1
50.1 232.5 24.53 148.8 2.8 135.7 2.4
49.6 232.5
53.8 254.4 24.82 169.7 3.0 137.2 2.4
53.6 254.4
55.1 258.1 25.22 172.0 3.0 137.4 2.4
54.9 258.1

55.0 GPM
Load
Power Heat COP Load Load Source Heat
kW
Of
LWT WPD LWT Cap
Absorb
Ft
Mbtuh
Head
9.95 131.3 4.9 66.0 9.2
21.2 165.3
10.07 146.5 5.3 66.6 9.2
24.6 180.9
10.23 148.6 5.3 66.7 9.2
25.7 183.5
12.85 119.2 3.7 85.9 8.1
22.0 163.1
13.00 134.1 4.0 86.5 8.1
25.1 178.5
13.21 135.9 4.0 86.6 8.1
26.1 181.0
16.51 104.6 2.9 105.9 7.3
22.9 160.9
16.71 119.1 3.1 106.4 7.3
25.6 176.1
16.98 120.7 3.1 106.5 7.3
26.5 178.6
21.00 87.0
2.2 125.8 6.7
24.1 158.7
21.25 101.2 2.4 126.4 6.7
26.2 173.7
21.59 102.5 2.4 126.5 6.7
27.0 176.2
10.52 157.3 5.4 67.0 9.2
29.4 193.2
10.64 175.1 5.8 67.7 9.2
33.6 211.4
10.81 177.6 5.8 67.8 9.2
34.9 214.5
13.36 144.1 4.2 86.9 8.1
30.3 189.7
13.52 161.4 4.5 87.6 8.1
34.1 207.5
13.74 163.6 4.5 87.7 8.1
35.3 210.5
17.00 128.1 3.2 106.8 7.3
31.3 186.1
17.21 145.0 3.5 107.5 7.3
34.7 203.7
17.48 146.9 3.5 107.6 7.3
35.8 206.6
21.49 109.3 2.5 126.7 6.7
32.6 182.6
21.75 125.6 2.7 127.4 6.7
35.4 199.8
22.10 127.3 2.7 127.5 6.7
36.3 202.7
11.04 184.2 5.9 68.1 9.2
37.6 221.9
11.17 204.7 6.4 68.8 9.2
42.5 242.8
11.35 207.6 6.4 69.0 9.2
44.0 246.3
13.84 169.8 4.6 87.9 8.1
38.6 217.0
14.00 189.6 5.0 88.7 8.1
43.1 237.4
14.23 192.3 5.0 88.8 8.1
44.5 240.9
17.46 152.5 3.6 107.8 7.3
39.7 212.1
17.67 171.8 3.8 108.5 7.3
43.7 232.1
17.95 174.1 3.8 108.6 7.3
45.0 235.4
21.96 132.3 2.8 127.6 6.7
41.0 207.2
22.23 150.8 3.0 128.3 6.7
44.4 226.7
22.58 152.9 3.0 128.5 6.7
45.6 230.0
11.51 212.0 6.4 69.1 9.2
45.8 251.3
11.65 235.2 6.9 70.0 9.2
51.4 275.0
11.84 238.5 6.9 70.1 9.2
53.1 278.9
14.27 196.4 5.0 88.9 8.1
46.8 245.1
14.44 218.8 5.4 89.8 8.1
52.0 268.1
14.67 221.9 5.4 89.9 8.1
53.6 272.0
17.89 177.7 3.9 108.7 7.3
48.0 238.8
18.10 199.5 4.2 109.6 7.3
52.7 261.3
18.39 202.3 4.2 109.7 7.3
54.2 265.1
22.41 156.0 3.0 128.6 6.7
49.4 232.5
22.68 177.0 3.3 129.4 6.7
53.5 254.4
23.04 179.5 3.3 129.5 6.7
54.8 258.1

70.0 GPM
Power Heat COP Load Load
kW
Of
LWT WPD
Absor
Ft
b
Head
9.65 132.4 5.0 64.7 13.9
9.77 147.6 5.4 65.2 13.9
9.92 149.6 5.4 65.2 13.9
12.46 120.6 3.8 84.7 12.2
12.61 135.5 4.1 85.1 12.2
12.82 137.3 4.1 85.2 12.2
16.02 106.2 2.9 104.6 11.0
16.21 120.8 3.2 105.1 11.0
16.47 122.4 3.2 105.1 11.0
20.38 89.1
2.3 124.6 10.1
20.62 103.3 2.5 125.0 10.1
20.95 104.7 2.5 125.1 10.1
10.21 158.4 5.5 65.5 13.9
10.33 176.1 6.0 66.0 13.9
10.49 178.7 6.0 66.1 13.9
12.97 145.4 4.3 85.4 12.2
13.12 162.7 4.6 85.9 12.2
13.33 165.0 4.6 86.0 12.2
16.50 129.8 3.3 105.4 11.0
16.69 146.7 3.6 105.9 11.0
16.96 148.7 3.6 105.9 11.0
20.85 111.4 2.6 125.3 10.1
21.11 127.8 2.8 125.8 10.1
21.44 129.5 2.8 125.9 10.1
10.71 185.4 6.1 66.3 13.9
10.84 205.8 6.6 66.9 13.9
11.01 208.7 6.6 67.0 13.9
13.42 171.2 4.7 86.2 12.2
13.59 191.0 5.1 86.8 12.2
13.80 193.8 5.1 86.9 12.2
16.94 154.3 3.7 106.1 11.0
17.14 173.6 4.0 106.7 11.0
17.42 176.0 4.0 106.8 11.0
21.31 134.5 2.8 126.0 10.1
21.57 153.1 3.1 126.6 10.1
21.91 155.2 3.1 126.6 10.1
11.17 213.2 6.6 67.2 13.9
11.30 236.4 7.1 67.9 13.9
11.49 239.7 7.1 68.0 13.9
13.85 197.8 5.2 87.0 12.2
14.01 220.3 5.6 87.7 12.2
14.24 223.4 5.6 87.8 12.2
17.35 179.6 4.0 106.9 11.0
17.56 201.4 4.4 107.5 11.0
17.84 204.2 4.4 107.6 11.0
21.75 158.3 3.1 126.7 10.1
22.01 179.3 3.4 127.4 10.1
22.36 181.8 3.4 127.5 10.1

WSHP-PRC009-EN

Performance Data
EXWA 240-Heating
Table P-13: 240 Heating Performance (continued)
Performance data is tabulated under ARI/ISO 13256-2.
Antifreeze correction factors may be found on page 47.

Source Load Source Source


EWT EWT GPM WPD
Ft
Head
70.0 60.0 30.0
3.1
70.0 60.0 55.0
8.6
70.0 60.0 70.0
13.0
70.0 80.0 30.0
3.1
70.0 80.0 55.0
8.6
70.0 80.0 70.0
13.0
70.0 100.0 30.0
3.1
70.0 100.0 55.0
8.6
70.0 100.0 70.0
13.0
70.0 120.0 30.0
3.1
70.0 120.0 55.0
8.6
70.0 120.0 70.0
13.0
80.0 60.0 30.0
2.9
80.0 60.0 55.0
8.1
80.0 60.0 70.0
12.2
80.0 80.0 30.0
2.9
80.0 80.0 55.0
8.1
80.0 80.0 70.0
12.2
80.0 100.0 30.0
2.9
80.0 100.0 55.0
8.1
80.0 100.0 70.0
12.2
80.0 120.0 30.0
2.9
80.0 120.0 55.0
8.1
80.0 120.0 70.0
12.2

WSHP-PRC009-EN

Load 30.0 GPM


Load
Source Heat Power Heat COP Load Load Source Heat
LWT Cap
kW
Of
LWT WPD LWT Cap
Mbtuh
Absorb
Ft
Mbtuh
Head
54.2 281.5 13.08 236.9 6.3 78.8 3.4
53.9 281.5
60.4 308.0 13.23 262.9 6.8 80.5 3.4
60.3 308.0
62.4 312.4 13.44 266.5 6.8 80.8 3.4
62.3 312.4
55.4 273.9 16.06 219.1 5.0 98.3 2.9
55.1 273.9
61.1 299.6 16.26 244.1 5.4 100.0 2.9
60.9 299.6
62.9 304.0 16.52 247.6 5.4 100.3 2.9
62.8 304.0
56.8 266.3 20.02 198.0 3.9 117.9 2.6
56.4 266.3
61.9 291.3 20.26 222.2 4.2 119.6 2.6
61.7 291.3
63.6 295.5 20.58 225.3 4.2 119.8 2.6
63.4 295.5
58.4 258.6 25.01 173.2 3.0 137.4 2.4
57.9 258.6
62.8 283.0 25.31 196.6 3.3 139.1 2.4
62.6 283.0
64.3 287.1 25.71 199.4 3.3 139.4 2.4
64.1 287.1
62.2 312.4 13.51 266.3 6.8 80.8 3.4
61.9 312.4
69.2 341.8 13.68 295.1 7.3 82.8 3.4
69.1 341.8
71.4 346.7 13.89 299.3 7.3 83.1 3.4
71.3 346.7
63.5 303.4 16.48 247.2 5.4 100.3 2.9
63.1 303.4
70.0 332.0 16.68 275.1 5.8 102.2 2.9
69.8 332.0
72.0 336.8 16.94 279.0 5.8 102.5 2.9
71.9 336.8
65.0 294.5 20.45 224.7 4.2 119.8 2.6
64.6 294.5
70.8 322.2 20.69 251.6 4.6 121.6 2.6
70.6 322.2
72.7 326.8 21.02 255.1 4.6 121.9 2.6
72.5 326.8
66.7 285.5 25.48 198.5 3.3 139.3 2.4
66.2 285.5
71.8 312.4 25.79 224.4 3.5 141.1 2.4
71.5 312.4
73.5 316.9 26.20 227.5 3.5 141.4 2.4
73.3 316.9

55.0 GPM
Power Heat COP
kW
Of
Absor
b
11.95 240.7 6.9
12.09 266.7 7.5
12.28 270.5 7.5
14.68 223.8 5.5
14.85 248.9 5.9
15.09 252.5 5.9
18.29 203.9 4.3
18.51 228.1 4.6
18.81 231.3 4.6
22.85 180.6 3.3
23.13 204.1 3.6
23.49 206.9 3.6
12.35 270.3 7.4
12.50 299.1 8.0
12.70 303.4 8.0
15.06 252.0 5.9
15.24 280.0 6.4
15.48 284.0 6.4
18.68 230.8 4.6
18.91 257.7 5.0
19.21 261.2 5.0
23.28 206.1 3.6
23.56 232.0 3.9
23.94 235.2 3.9

Load
Load Load Source Heat
LWT WPD LWT Cap
Ft
Mbtuh
Head
70.2 9.2
53.8 281.5
71.2 9.2
60.2 308.0
71.4 9.2
62.2 312.4
90.0 8.1
55.0 273.9
90.9 8.1
60.9 299.6
91.1 8.1
62.7 304.0
109.7 7.3
56.3 266.3
110.7 7.3
61.6 291.3
110.8 7.3
63.3 295.5
129.5 6.7
57.8 258.6
130.4 6.7
62.5 283.0
130.6 6.7
64.0 287.1
71.4 9.2
61.8 312.4
72.4 9.2
69.0 341.8
72.6 9.2
71.3 346.7
91.1 8.1
63.0 303.4
92.1 8.1
69.7 332.0
92.3 8.1
71.8 336.8
110.8 7.3
64.4 294.5
111.8 7.3
70.5 322.2
112.0 7.3
72.5 326.8
130.5 6.7
66.1 285.5
131.5 6.7
71.5 312.4
131.7 6.7
73.2 316.9

70.0 GPM
Power Heat COP Load Load
kW
Of
LWT WPD
Absorb
Ft
Head
11.59 241.9 7.1 68.0 13.9
11.73 268.0 7.7 68.8 13.9
11.92 271.7 7.7 68.9 13.9
14.24 225.3 5.6 87.8 12.2
14.41 250.4 6.1 88.6 12.2
14.64 254.0 6.1 88.7 12.2
17.75 205.7 4.4 107.7 11.0
17.96 230.0 4.8 108.4 11.0
18.25 233.2 4.7 108.5 11.0
22.17 182.9 3.4 127.5 10.1
22.44 206.4 3.7 128.2 10.1
22.80 209.3 3.7 128.3 10.1
11.98 271.5 7.6 68.9 13.9
12.12 300.4 8.3 69.8 13.9
12.32 304.7 8.2 69.9 13.9
14.61 253.5 6.1 88.7 12.2
14.79 281.5 6.6 89.5 12.2
15.02 285.5 6.6 89.7 12.2
18.13 232.6 4.8 108.5 11.0
18.35 259.6 5.1 109.3 11.0
18.64 263.2 5.1 109.4 11.0
22.59 208.4 3.7 128.3 10.1
22.86 234.4 4.0 129.0 10.1
23.23 237.6 4.0 129.2 10.1

45

Performance Data
Electrical
Table E-1: Electrical performance WPWD/EXWA
Model/MBH

WPWD024

WPWD036

WPWD042

WPWD048

WPWD060

WPWD072

EXWA240

46

VOLTS-AC/HZ/PH

208-230/60/1
220-240/50/1
265/60/1
208-230/60/1
208-230/60/3
220-240/50/1
265/60/1
380-415/50/3
460/60/3
208-230/60/1
208-230/60/3
220-240/50/1
265/60/1
380-415/50/3
460/60/3
208-230/60/1
208-230/60/3
380-415/50/3
460/60/3
208-230/60/1
208-230/60/3
380-415/50/3
460/60/3
575/60/3
208-230/60/1
208-230/60/3
380-415/50/3
460/60/3
575/60/3
208/60/3
230/60/3
460/60/3
575/60/3

Min.
Util.
Volt

Max
Util.
Volt

Compressor
Each
RLA

LRA

197
198
239
197
197
198
239
342
414
197
197
198
239
342
414
197
197
342
414
197
197
342
414
517
197
197
342
414
517
197
207
414
518

253
264
292
253
253
264
292
456
506
253
253
264
292
456
506
253
253
456
506
253
253
456
506
633
253
253
456
506
633
229
253
506
633

11.4
9.6
9.6
15.0
10.7
14.3
14.3
5.0
5.0
18.4
11.4
16.4
16.4
5.7
5.7
20.4
13.9
7.1
7.1
28.0
20.0
7.5
7.5
6.4
32.1
19.3
10.0
10.0
7.8
31.7
31.7
14.1
11.2

56.0
47.0
47.0
73.0
63.0
71.0
71.0
31.0
31.0
95.0
77.0
83.0
83.0
39.0
39.0
109.0
88.0
44.0
44.0
169.0
123.0
49.5
49.5
40.0
169.0
137.0
62.0
62.0
50.0
232.0
261.0
112.0
92.0

No.
of
Comp
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2

Without Desup
MCA
14.3
12.0
12.0
18.8
13.4
17.9
17.9
6.3
6.3
23.0
14.3
20.5
20.5
7.1
7.1
25.5
17.4
8.9
8.9
35.0
25.0
9.4
9.4
8.0
40.1
24.1
12.5
12.5
9.8
71.39
71.39
31.73
25.24

Max
Fuse
25
20
20
30
20
30
30
15.0
15
40
25
35
35
15.0
15
45
30
15.0
15
60
45
15.0
15
15
70
40
20.0
20
15
100
100
45
35

With Desup
Desup
RLA
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
0.4
-----

MCA
14.7
12.4
12.4
19.2
13.8
18.3
18.3
6.7
6.7
23.4
14.7
20.9
20.9
7.5
7.5
25.9
17.8
9.3
9.3
35.4
25.4
9.8
9.8
8.4
40.5
24.5
12.9
12.9
10.2
-----

Max
Fuse
25
20
20
30
20
30
30
15.0
15
40
25
35
35
15.0
15
45
30
15.0
15
60
45
15.0
15
15
70
40
20.0
20
15
-----

WSHP-PRC009-EN

Performance Data

Antifreeze Correction Factors

Table A1: Correction Factors for Antifreeze Solutions

Item
Cool
Capacity
Heat
Capacity
Pressure
Drop
Cool
Capacity
Heat
Capacity
Pressure
Drop
Cool
Capacity
Heat
Capacity
Pressure
Drop

Methanol
Concentration by Volume
10%
20%
30%
40%
50%
.9980 .9965 .9949 .9932 .9915
.9950

.9898

.9846

.9794

.9742

1.023

1.057

1.091

1.122

1.160

Ethylene Glycol
.9955 .9912 .9870

.9830

.9790

.9925

.9848

.9770

.9690

.9610

1.024

1.068

1.124

1.188

1.263

Propylene Glycol
.9934 .9869 .9804

.9739

.9681

.9863

.9732

.9603

.9477

.9350

1.040

1.098

1.174

1.273

1.405

Example 1 (Ethylene Glycol):


The antifreeze solution is 20% by volume of Ethylene
Glycol. Determine the cooling capacity and waterside
pressure drop for a WPWD 024 when the EWT for the
source-side is 80 F and the GPM is 7.0.
From the catalog data, the cooling capacity at these
conditions with 100% water is 20.6 MBTUH, and the
waterside pressure drop is 3.8 feet of head. At 20% Eth

ylene Glycol, the correction factor for cool capacity is


0.9912 and the pressure drop is 1.068.
The corrected cooling capacity (MBTUH) = 20.6 *
0.9912 = 20.42. The corrected water side pressure drop
(Ft. head) = 3.8 * 1.068 = 4.06.
Example 2 (Propylene Glycol):
The antifreeze solution is 30% by volume of Propylene
Glycol. Determine the corrected heating capacity and
waterside pressure drop for a EXWA 240 when the EWT for the source-side is 50 F and the GPM is 55.
From the catalog data, the heating capacity at these conditions with 100% water is 237.4 MBTUH, and the waterside pres

sure drop is 10.1 feet of head. At 30% Propylene Glycol, the correction factor for heat capacity is 0.9603 and the pressure
drop is 1.174.
The corrected cooling capacity (MBTUH) = 237.4 * 0.9603 = 228. The corrected water side pressure drop (Ft. head) = 10.1 *
1.174 = 11.86.
WSHP-PRC009-EN

47

Control Wiring
Basic 24V - 1 PH

48

WSHP-PRC009-EN

Control Wiring
Deluxe 24V - 3PH

WSHP-PRC009-EN

49

Dimensional Data

WPWD 024-036

50

WSHP-PRC009-EN

Dimensional Data

WPWD 042-072

WSHP-PRC009-EN

51

Dimensional Data

EXWA 240

52

WSHP-PRC009-EN

Accessories

Pump Module
The pump module and hose kit make a
complete self-contained pumping
package for distributed pumping sys
tems. These kits contain all the neces
sary components for the installation,
operation and maintenance of the wa
ter circuit of a closed loop geothermal
application. Standard pump module
features include insulated Grundfos
pumps, insulated cabinet, bronze
pump, and 3-way brass valves. The
module is factory piped, wired and
mounted. See Figure 14 for pump
module assembly. Literature number
WSHPC-IN-5 (72-9006-03) will provide
electrical and dimensional require
ments for the PMCA and PMBA prod
ucts.

Figure 14: Pump module

Motorized Water Valve


The motorized water valve is installed
on the return line of the water loop
system between the loop and the
loops pump module. This isolation
device is less expensive and a very ef
fective alternative to the water regulat
ing valve.

Figure 15: Pump module hose kit


Water Regulating Valve
Assembly
The water regulating valve assembly
consists of a direct acting valve and a
reverse acting valve installed on the
water-out side of the unit. The direct
acting vales opens in response to an
increase in discharge pressure during
the cooling cycle. The reverse acting
valve opens in response to a decrease
in suction pressure during the heating
cycle. Water regulating valves should
be used where low flow and low or
high fluid temperature conditions
could occur. This option is beneficial
with open loop systems, but not nec
essary. See Figure 16 for water regu
lating valve assembly.

Pump Module Hose Kit


The pump module hose kit consists of
two brass, 3/4 or 1-inch male pipe
thread (MPT) -by-barb fittings; two
brass 90 degree 1-inch, MPT-by-barb
elbows with pressure/temperature
ports; and 10 feet of rubber hose with
4 hose clamps. The pump module
hose kit is available separately from
the pump module. See Figure 15 for
pump module hose kit.

When the compressor begins running,


the valve will open, allowing water to
flow through the unit. As the compres
sor shuts down, the valve slowly clos
es off. The main purpose of the
motorized valve is to shut-off the flow
of water through the unit when the
unit is off, thus reducing water con
sumption. The motorized valve is fast
opening to prevent compressor tripout, and slow closing to prevent water
hammer. See Figure 17 for motorized
water valve.

Figure 17: Motorized water valve

Figure 16: Water regulating valve

WSHP-PRC009-EN

53

Accessories

Water Heater Hook-up Kit


The water heater hook-up kit provides
connection from the domestic hot wa
ter heater to the units desuperheater
option. The kit consist of piping con
nections and shut-off valve. See Fig
ure 18 for water heater hook-up kit.

Figure 18: Water heater hook-up


Hose Kits
Trane provides three hose kit selec
tions for equipment balancing.
Ball valve flow control
(manual)

of information to make the necessary


adjustments to the circuit setter.
For automatic system balancing of a
water-source heat pump, the
Mesurflo self balancing kit provides
a constant flow rate over the pressure
differential rage of 2 to 80 psid. As sys
tem pressure change (through further
addition of heat pumps, for example)
each individual flow control valve will
automatically adjust to the new sys
tem conditions. In variable water vol
ume applications, a self balancing
hose kit can provide continuous bal
ancing because of its ability to auto
matically adjust to the varying system
conditions. For more information per
taining to the automatic balancing
hose kits, see literature documenta
tion
WSHP-SLB005-EN. See Figure 19 for
the Mesurflo automatic hose kit.

Circuit setter flow control


(manual)
Automatic flow control
(automatic)
Each selection provides some accura
cy in equipment balancing. Range of
accuracy consist of 25% for the ball
valve method, 20% for the circuit set
ter method, and 10% for the automat
ic flow control method.
Utilizing the ball valve method, the
pressure/temperature measurement
on the leaving and entering side of the
heat pump is measured within the wa
ter piping. The ball valve is then throt
tled to change the amount of water
flow to the unit to reach the desired
temperature or pressure differential.
The circuit setter method combines
both the readout and the adjustment
feature in one device. In order to determine flow rate, the user must record
both handle position, and differential
pressure drop. Then, the user must
consult a chart containing both pieces
54

Figure 19: Mesurflo hose kit

WSHP-PRC009-EN

Mechanical Specifications
WPWD 2 through 6-Tons
General (2 through 6-Tons)
Equipment shall be completely assem
bled, piped, internally wired, and test
operated at the factory. National Pipe
threaded (NPT) female domestic water
inlet and outlet connections, NPT fe
male condensate connection, thermo
stat field interface terminal strip, and
all safety controls shall be furnished
and factory installed. The system wa
ter inlet and outlet connections shall
be a female NPT swivel quick connec
tor with stainless steel stop ring that
allows simplified field installation.
Equipment shall be UL listed.
All equipment shall have decals and
labels to aid in the service and indicate
caution areas.
WPWD Casing
The cabinet shall be constructed of
galvanized heavy-gauge steel with an
electrostatic powder paint finish for an
appliance grade finish.
The top, front half of the diagonal cab
inet shall be removable for access to
all of the internal components. All pan
els shall be insulated with 1/2-inch
thick, 1-1/2 lb. density, neoprene
backed, acoustical fiberglass insula
tion.
Refrigeration System
Compressor
The unit shall include a high efficiency,
scroll compressor with internal vibra
tion isolation that absorbs starting and
stopping energy. External vibration
isolation shall be provided by rubber
mounting devices located underneath
the mounting base of the compressor.
Internal thermal overload protection
shall be provided. Protection shall be
provided against excessive discharge
pressure operation by means of a high
pressure switch. Loss of charge pro
tection shall be provided by a low
pressure switch.
Water-to-Refrigerant
Heat Exchanger
The water-to-refrigerant heat exchanger is a high quality, stainless
steel brazed plate heat exchanger
WSHP-PRC009-EN

The stainless steel offers corrosion re


sistance comparable to the
cupro-nickel design. The coil shall
have a working pressure rating of 450
psig on both the refrigerant and water
sides. The coil shall have a bi-direc
tional liquid line filter drier to remove
any contaminants from entering the
circuit.

Electrical
A factory tested and installed control
box shall contain all necessary devices
to allow heating and cooling operation
of the equipment to occur from a remote wall thermostat. These devices
shall be as follows:

Freezestat and Lock Out Relay


A freezestat shall be included to pro
tect the unit from unusually cold fluid
flow or no fluid flow conditions. A 20 F
freezestat is for use on closed loop
systems with antifreeze solution. All
other types of systems typically use a
35 F freezestat.

Compressor controller shall be a


24 VAC contactor

A lockout relay circuit consisting of


three safety deviceslow pressure,
high pressure, and freezestat, shall
trigger the lockout relay to shut off the
compressor, the loop pumps, and the
desuperheater pump if a problem is
detected. A lockout relay may be reset
by cycling the power to the unit.
Reversing Valve
The reversing valve shall be a pilot op
erating sliding piston type with re
placeable encapsulated magnetic coil.
The reversing valve is energized in the
cooling cycle.
Refrigerant Tubing
Refrigerant tubing shall be copper.

All low temperature refrigerant lines

shall be insulated with an elastomeric

insulation that has a

3/8-inch thick wall with a flame spread

rating of less than 25 and smoke den

sity rating of less than 50, as tested in

accordance with ASTM-85. The elasto

meric insulation shall have a UL 94V-5

rating.

Refrigerant Metering
The equipment shall be provided with
a (TXV) thermal expansion valve to al
low operation from 25 F to 120 F enter
ing fluid temperatures.
Servicing
The equipment shall be provided with
both high and low pressure schrader
ports for servicing.

24 VAC, Energy Limiting Class II,


50VA breaker type transformer

Thermostat connections shall be


to a terminal strip having a
minimum of four terminals
located on the unit. This interface
shall provide the means of con
nection between the thermostat
and operating controls contained
within the unit.
An electrically operated safety
lockout relay shall be provided to
prevent cycling of the compressor
during adverse conditions of
operation. This device may be
reset either at a remote ther
mostat or by cycling power to the
unit.
A high pressure switch shall be
provided to help protect the com
pressor against operation at
refrigerant system pressures in
excess of 395 psig.
The low water temperature switch
shall be provided to help protect
the water-to-refrigerant heat
exchangers from freezing. This
device shall help prevent com
pressor operation at leaving water
temperatures below 35 F.
An optional 20 F temperature
switch may be applied for low
temperature or geothermal appli
cations, where an appropriate
antifreeze solution is used. This
device shall help prevent com
pressor operation at leaving fluid
temperatures below 20 F.

55

Mechanical Specifications
WPWD 2 through 6-Tons
A low pressure switch shall be
provided to help prevent com
pressor operation under low
charge or catastrophic loss of
charge situations. The low
pressure switch is set to activate
at refrigerant pressures of 35 psig
when a 35 F freezestat is used; 7
psig when a 20 F freezestat is
used.
Nameplate information shall be
provided within each unit to help
identify the units model number,
operating ranges, voltage ranges,
and electrical specifications.
Desuperheater (option)

A double-walled, vented, copper desu

perheater shall be factory installed

complete with circulating pump and

high limit thermostat. The desuper

heater will help to heat domestic hot

water while the unit is cooling or heat

ing. The desuperheater will not oper

ate until the compressor discharge

line reaches 145 F.

Water Regulating Valve (accessory)

The water regulating valve assembly

consists of a direct acting valve and a

reverse acting valve. The direct acting

valve opens in response to an increase

in discharge pressure during the cool

ing cycle. The reverse acting valve

opens in response to a decrease in

suction pressure during the heating

cycle. Water regulating valves should

be used where low flow, or low or high

fluid temperature conditions could oc

cur. This option should be used with

open loop systems.

Ball Valves (accessory)

Ball valves installed between the unit

and the loop pump module, on both

supply and return lines, allows the

loop to be isolated from the heat pump

for servicing.

Motorized Water Valve (accessory)

When extreme fluid temperature con

ditions do not exist with an open loop

system, a motorized water valve is a

much less expensive and very effec

tive alternative. It also prevents water

56

hammer by keeping the pressure up in


the loop system during off cycles.
Pump Module and Hose Kits
(accessory)
The pump module and the hose kit
make a complete self-contained
pumping package for the earth-cou
pled heat pump system.
These kits contain all the necessary
components for the installation, oper
ation, and maintenance of the water
circuit of a closed-loop geothermal ap
plication.
Standard pump module features in
clude an insulated cabinet, optional in
sulated, cast-iron or bronze pumps
available in one- or two-pump config
urations, and three-way brass valves.
The hose kit and the pump module are
no longer a single item. The hose kits
are available separately and include
two brass, 1-inch male pipe thread
(MPT)-by-barb fittings; two brass 90degree 1-inch, MPT-by-barb elbows
with pressure/temperature ports; and
10 feet of rubber hose with 4 hose
clamps.
Other accessories that may be ordered
are a 1-inch brass quick connect fitting;
1-inch MPT-by-barb fitting; 1-inch
brass MPT-by-barb, 90 degree elbow;
pressure/temperature ports, also
known as Petes plugs; and 10 feet of
rubber hose.
Note: A strainer device should be
used on all open loop applications.
Warranty
The unit shall be warranted by the
manufacturer against defects in material and factory workmanship for one
year. The entire refrigerant circuit in
cluding motor-compressor, expansion
device, all heat exchangers in contact
with refrigerants, and reversing valve
(less solenoid coil) shall be warranted
for that year (parts only). Optional extended warranties shall be made available through the local distributor.

WSHP-PRC009-EN

Mechanical Specifications
EXWA 20-Tons
General (EXWA 20-Ton)

Equipment shall be completely assem

bled, piped, internally wired, fully

charged with HCFC-22, and test oper

ated at the factory. A controls field in

terface terminal strip, and all safety

controls shall be furnished, installed

and tested by the unit manufacturer.

The unit shall be rated in accordance

with ISO-ARI 13256-2.

The system's water inlet and outlet for

the source and load-side connections

shall be female NPT composed of cop-

per. Service and caution labels shall be

placed on the unit in their appropriate

locations.

Cabinet
Unit casing shall be constructed of zinc
coated, heavy gauge, galvanized steel.
Access to the refrigerant and controls
shall be provided through the front
and side, access panels.
All panels shall be insulated with inch thick dual density bonded glass fi
ber. The insulation shall meet the ero
sion requirements of UL 181. It shall
have a flame spread of less than 25
and a smoke developed classification
of less than 50 per ASTME-84 and UL
723.
The unit shall be installed for proper
access. Procedures for proper access
inspection and cleaning of the unit
shall be included in the maintenance
manual.
Compressors
Vibration isolation shall be provided
through rubber mounting devices lo
cated underneath the compressor. In
ternal thermal overload protection
shall be provided. Protection against
excessive discharge pressure shall be
provided by means of a high-pressure
switch. A loss of charge shall be de
tected by a low-pressure safety.
Refrigerant Tubing
The refrigerant tubing shall be of 99%
pure copper. This system shall be free
from contaminants and conditions
such as drilling fragments, dirt and oil.

WSHP-PRC009-EN

Refrigerant Circuits
The refrigerant circuit shall contain a
thermal expansion device. Service
pressure ports shall be factory supplied on the high and low pressure
sides for easy refrigerant pressure or
temperature testing.
Reversing Valve
The reversing valve shall be a pilot op
erating, sliding piston type with a re
placeable, encapsulated magnetic coil.
The reversing valve shall be energized
in the cooling cycle.
Water-to-Refrigerant
Heat Exchangers
The water-to-refrigerant heat exchangers shall be of a high quality, co
axial coil for maximum heat transfer.
The source-side heat exchanger shall
be constructed of copper with an op
tion of cupro-nickel. The load-side
heat exchanger shall be constructed of
copper. Both heat exchangers shall be
deeply fluted to enhance heat transfer
and minimize fouling and scaling. The
coil shall have a working pressure of
500 psig on the refrigerant side, and
400 psig on the waterside.
Electrical
The unit control box shall contain the
necessary devices to allow heating
and cooling operation to occur from a
remote wall thermostat. These devices
shall be as follows:
A 24 VAC energy limiting class II
100 VA transformer
A 24 VAC compressor contactor
for compressor control
Field control connections shall
be provided for ease of hook-up
to a terminal strip located in the
unit's control box

A lockout relay, which controls


cycling of the compressor, shall
be provided to protect the com
pressor during adverse operat
ing conditions. This device shall
be capable of reset by interrupt
ing power to the 24 VAC control
circuit. Reset may be done ei

ther at a remote thermostat or


through a momentary main
power interruption.
A high-pressure switch shall be
provided to protect the com
pressor against operation at re
frigerant
system
pressure
exceeding 395 psig.
A low pressure switch shall provide freeze protection to the
compressor below 20 F suction.
Nameplate information shall be pro
vided for the application of either timedelay fuses or HACR circuit breakers
for branch circuit protection from the
primary source of power.
Deluxe Controls
The Deluxe control package shall pro-

vide a 100 VA transformer with a cir

cuit breaker. The controller shall

include a lockout relay, anti-short cy

cle compressor protection, random

start delay, brown-out protection, low

pressure time delay, compressor de-

lay on start and an open relay for ancil

lary controls request. Three LEDs,

Light Emitting Diodes, shall also be in

cluded for diagnostics of each refriger

ation circuit.

Ball Valves (accessory)

Ball valves shall be field installed be-

tween the unit and the supply and re-

turn lines of the loop to stop water

flow to the unit in a maintenance or

service situation.

Hoses (accessory)

Hoses shall consist of a stainless steel

outer braid with an inner core of tube

made of a non-toxic synthetic polymer

material. The hoses shall be suitable

for water temperatures ranging be-

tween 33 F and 211 F without the use

of glycol.

57

Mechanical Specifications
EXWA 20-Tons
Automatic Flow Devices
(accessory)
The automatic flow kit shall contain a
Hays Mesurflo automatic flow con
trol valve, two ball valves; two flexible
hoses, a high flow Y-strainer, and may
include a strainer blow-down and var
ious other accessories.
The automatic flow control valve shall
be factory set to a rated flow, and shall
automatically control the flow to within 10% of the rated value over a 40 to 1
differential pressure, operating range
(2 to 80 psid). Operational temperature
shall be rated from fluid freezing to
225 F. The valve body shall be con
structed from hot forged brass UNS
C37700 per ASTM B-283 latest revi
sion. For more information pertaining
to the automatic balancing hose kits,
see literature documentation WSHPSLB005-EN.
Warranty
The unit shall be warranted by the
manufacturer against defects in material and factory workmanship for one
year.
The refrigerant circuit including mo
tor-compressor, expansion device, all
heat exchangers in contact with refrig
erants, and reversing valve (less the
solenoid coil) shall be warranted for
that year (parts only).
Optional extended warranties shall be
made available.

58

WSHP-PRC009-EN

Top View
20-Ton Water-to-Water

LOAD SIDE
HEAT EXCHANGER

COMPRESSORS

CONTROL BOX
SOURCE-SIDE
HEAT EXCHANGER

WSHP-PRC009-EN

59

Literature Order Number

WSHP-PRC009-EN

Date

05/04

Supersedes

WSHP-PRC009-EN 11/02

Trane
A Business of American Standard Companies
www.trane.com
For more information, contact your local district
office or e-mail us at comfort@trane.com

Trane has a policy of continuous product and data improvement and reserves the right to change design
and specifications without notice.

S-ar putea să vă placă și