QUANTUM VS.

QUANTUM LX
Feature Software
Capacity Control Maximum of 2 of the following options: Suction Pressure, Process Temperature, Discharge Pressure, User Selectable Input X X X X X X X 19 Available 50 Available X X X X X X X X X X X X X X X Time based switching between Mode 1 and Mode 2 of selected Capacity control option X X X X 4 1 4 1 Analog Output integrated with Digital Step #4 4 User Defined Modes (Any Defined Analog Input can be used for Control)

Quantum

Quantum LX

Oil Pump Control No pump Demand (Includes Prelube and Cycling) Full Time Dual pumps Shaft Driven Shaft with Auxiliary Balance Piston Control Alarms Current Display History / Freeze Display Dual Discharge Pressure Control (Swing Compressor) Electric Motor Drive Constant Speed Electric Motor Drive Variable Speed (wired) Vyper Electric Motor Drive Variable Speed (Comm) Engine Drive Turbine Drive Discharge Safeties High Suction Safeties Oil Safeties Main Oil Injection Control Liquid Injection Control (TX valve, EZ Cool) Oil Filter Safeties Hot Gas By-Pass Control Slide Valve 1 Control Slide Valve 2 Control Economizer Control Setback 8 Digital Input Auxiliaries 10 Analog Input Auxiliaries Pumpdown Control DX Circuit Control PID User Defined Analog Output (Re-Transmit) Condenser Control Digital Steps Analog Control

X X X X

X 21 Available 128 Available X X X X X X X X X X X X X X X X Time based switching between 4 user defined modes X X X X 8 Analog Outputs Total 8 Analog Outputs Total 4 1 PID loop Upto 24 Compressors, 3 suction pressure systems with 8 compressors each via Ethernet communications. Interlocking between suction systems is available also. All compressors must have Quantum LX controllers X X X X 3 User Levels of access available User Level 0 Basic - Most graphical displays, very limited access to setpoints (capacity control only). User Level 1 Advanced Less graphical displays, access to setpoints, and trending. User Level 2 Service Less graphical displays, access to setpoints, trending, compressor configuration, diagnostics.

Multiple Compressor Sequencing

Upto 4 Frick compressors on a common suction pressure via serial communications

Permissive Start Input Mode Selection Pull Down PhD Vibration Monitoring

X X X X 3 levels available: No Access Prevents operator from changing any setpoint or password. Moderate Access Allows operator to change setpoints, but prevents changing safety setpoints and passwords. Full Access Allows operator to change all setpoints and passwords.

Security

2/16/2006

QUANTUM VS. QUANTUM LX


Feature
Slide Valve and Slide Stop Calibration Language Temperature Displays Pressure Displays Trending Setpoint Saving Serial Communications Protocols Comm #1 Comm #2

Quantum
Manual Calibration via on screen instructions English,Danish,German,Spanish,French Fahrenheit, Celsius PSIA, PSIG, Bar, BarA, kpaA X Yes, via CF card with Frick program

Quantum LX
Automatic calibration started by user English,French, Portugues,Spanish,Polish, Mandarin Chinese, Traditional Chinese Fahrenheit, Celsius PSIA, PSIG, Bar, BarA, kpaA X File downloadable via USB drive or Ethernet file transfer Yes, via USB drive Frick #, Frick $, Modbus ASCII & RTU, Allen Bradley DF1, Vyper, DBS Frick #, Frick $, Modbus ASCII & RTU, Allen Bradley DF1, Vyper, DBS Frick #, Frick $, Modbus ASCII & RTU, Allen Bradley DF1, Vyper, DBS Modbus TCP, Ethernet/IP(A-B), Profinet, BACnet Via Ethernet using any Internet Browser (No special software Required). Full access to Quantum LX. 35 available refrigerants plus user defined

Frick #, Frick $, Frick #, Frick $, Modbus ASCII, Allen Bradley DF1, York ISN Not Used

Comm #3 Ethernet Protocols Remote Screen Display

Via Frick Qtalk Software (serial), limited screens available. 16 available refrigerants plus user defined

Refrigerant List

Hardware
10.4 VGA Display 300 Mhx Processor Enclosure (18 x 22 x 10) Keypad (Door Mounted) Power Supply (Condor DC) Analog Board (2 max) Inputs Outputs Digital Boards (2 max) Inputs Outputs Serial Communication Ports X X X X 38 Keys X 24 to 48 4 to 8 X 8 brd #1 / 11 brd #2 16 brd #1 / 13 brd #2 2 Serial ports are available. Both ports are configurable for RS-422,RS485, or RS-232. X X X X 27 Keys X 24 to 48 8 to 16 X 8 brd #1 / 11 brd #2 16 brd #1 / 13 brd #2 3 Serial ports are available. Two ports are configurable for RS-422,RS485, or RS-232. One port is fixed for RS232(485 available with converter). X

Ethernet Port Flash Card (Installation) Flash Card (Setpoint Saver) Flash Card (Program Run) USB (Thumb Drive)

Used To Update/Install Program Used to Save Setpoints Program Runs From Card Updates Program / Saves Setpoints

2/16/2006