Relay Identifier (39 Characters) RID = Terminal Identifier (59 Characters) TID = Enable Winding 1 in Differential Element (Y, N, Y1) Enable Winding 2 in Differential Element (Y, N, Y1) Enable Winding 3 in Differential Element (Y, N, Y1) Enable Winding 1 O/C Elements and Dmd Thresholds (Y, N) Enable Winding 2 O/C Elements and Dmd Thresholds (Y, N) Enable Winding 3 O/C Elements and Dmd Thresholds (Y, N) Enable Combined O/C Elements (Y, N) Enable Volts/Hertz Protection (Y, N) Enable Undervoltage Protection (Y, N) Enable Overvoltage Protection (Y, N) Enable Frequency Protection (N, 16) Enable SELOGIC Control Equations Set 1 (Y, N) Enable SELOGIC Control Equations Set 2 (Y, N) Enable SELOGIC Control Equations Set 3 (Y, N)
E87W1 E87W2 E87W3 EOC1 EOC2 EOC3 EOCC E24 E27 E59 E81 ESLS1 ESLS2 ESLS3
= = = = = = = = = = = = = =
GENERAL DATA
Winding 1 CT Connection (D, Y) Winding 2 CT Connection (D, Y) Winding 3 CT Connection (D, Y) Winding 1 CT Ratio (150000) Winding 2 CT Ratio (150000) Winding 3 CT Ratio (150000) Maximum Power Transformer Capacity (OFF, 0.25000 MVA) Define Internal CT Connection Compensation (Y, N) Winding 1 CT Conn. Compensation (0, 1, , 12) Winding 2 CT Conn. Compensation (0, 1, , 12) Winding 3 CT Conn. Compensation (0, 1, , 12) Winding 1 Line-to-Line Voltage (11000 kV)
Date Code 20090205
W1CT W2CT W3CT CTR1 CTR2 CTR3 MVA ICOM W1CTC W2CTC W3CTC VWDG1
= = = = = = = = = = = =
DIFFERENTIAL ELEMENTS
Note: TAP1TAP3 are auto-set by relay if MVA setting is not OFF. Winding 1 Current Tap (0.5155.0 A secondary) (5 A) (0.131.0 A secondary) (1 A) Winding 2 Current Tap (0.5155.0 A secondary) (5 A) (0.131.0 A secondary) (1 A) Winding 3 Current Tap (0.5155.0 A secondary) (5 A) (0.131.0 A secondary) (1 A) Restrained Element Operating Current PU ((0.101.00) multiple of tap) Restraint Slope 1 Percentage (5100%) Restraint Slope 2 Percentage (OFF, 25200%) Restraint Current Slope 1 Limit ((120) multiple of tap) Unrestrained Element Current PU ((120) multiple of tap) Second-Harmonic Blocking Percentage (OFF, 5100%) Fourth-Harmonic Blocking Percentage (OFF, 5100%) Fifth-Harmonic Blocking Percentage (OFF, 5100%) Fifth-Harmonic Alarm Threshold (OFF, (0.023.20) multiple of tap) Fifth-Harmonic Alarm TDPU (08000 cycles) DC Ratio Blocking (Y, N) Harmonic Restraint (Y, N) Independent Harmonic Blocking (Y, N) TAP3 O87P SLP1 SLP2 IRS1 U87P PCT2 PCT4 PCT5 TH5P TH5D DCRB HRSTR IHBL = = = = = = = = = = = = = = TAP2 = TAP1 =
50Q11P 50Q11D
= =
50Q12P
= = = =
50N11P 50N11D
= =
50N12P
= = = =
DATC1
QDEM1P =
NDEM1P =
50P23P
50P24P
= = = =
50Q21P 50Q21D
= =
50Q22P
= = = =
50N21P 50N21D
= =
50N22P
= = = =
DATC2
PDEM2P
QDEM2P =
NDEM2P =
SEL-387E Settings Sheets Group Settings (SET Command) WINDING 3 O/C ELEMENTS
WINDING 3 PHASE O/C ELEMENTS Phase Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Level 1 O/C Delay (016000 cycles) 50P31 Torque Control (SELOGIC control equation) 50P31TC = Phase Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50P32 Torque Control (SELOGIC control equation) 50P32TC = Phase Inst. O/C Level 3 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Inst. O/C Level 4 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Phase Inv.-Time O/C Curve (U1U5, C1C5) Phase Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Phase Inv.-Time O/C EM Reset (Y, N) 51P3 Torque Control (SELOGIC control equation) 51P3TC = WINDING 3 NEGATIVE-SEQUENCE O/C ELEMENTS Note: All negative-sequence element pickup settings are in terms of 3I2. Neg.-Seq. Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Neg.-Seq. Level 1 O/C Delay (0.516000.0 cycles)
Date Code 20090205
50P31P 50P31D
= =
50P32P
50P33P
50P34P
= = = =
50Q31P 50Q31D
= =
50Q32P
= = = =
50N31P 50N31D
= =
50N32P
= = = =
DATC3
QDEM3P =
NDEM3P =
= = = = = = = = = = = = =
27 ELEMENTS
Level 1 Phase U/V PU (OFF, 0.1300.0 V secondary) Level 2 Phase U/V PU (OFF, 0.1300.0 V secondary) Level 1 Phase-Phase U/V PU (OFF, 0.1520.0 V secondary) Level 2 Phase-Phase U/V PU (OFF, 0.1520.0 V secondary) Pos.-Seq. U/V PU (OFF, 0.1100.0 V secondary) 27P1P 27P2P 27PP1 27PP2 27V1P = = = = =
59 ELEMENTS
Level 1 Phase O/V PU (OFF, 0.0300.0 V secondary) Level 2 Phase O/V PU (OFF, 0.0300.0 V secondary) Level 1 Residual O/V PU (OFF, 0.0300.0 V secondary) Level 2 Residual O/V PU (OFF, 0.0300.0 V secondary) Neg.-Seq. U/V PU (OFF, 0.0100.0 V secondary) Level 1 Phase-Phase O/V PU (OFF, 0.0520.0 V secondary) Level 2 Phase-Phase O/V PU (OFF, 0.0520.0 V secondary) Pos.-Seq.(V1) O/V PU (OFF, 0.0100.0 V secondary) 59P1P 59P2P 59G1P 59G2P 59QP 59PP1 59PP2 59V1P = = = = = = = =
= = = = = = = = = = = = =
MISCELLANEOUS TIMERS
Minimum Trip Duration Time Delay (48000 cycles) Close Failure Logic Time Delay (OFF, 08000 cycles) TDURD CFD = =
S1V1PU S1V1DO
= =
S1V2PU S1V2DO
= =
S1V3PU S1V3DO
= =
S2V1PU S2V1DO
= =
S2V2PU S2V2DO
= =
S2V3PU S2V3DO
= =
S3V1PU S3V1DO
= =
S3V2PU S3V2DO
= =
S3V3PU S3V3DO
= =
S3V5PU S3V5DO
= =
S3V6PU S3V6DO
= =
S3V7PU S3V7DO
= =
S3V8PU S3V8DO
= =
TRIP LOGIC
TR1 TR2 TR3 TR4 ULTR1 ULTR2 ULTR3 ULTR4 = = = = = = = =
CLOSE LOGIC
52A1 52A2 52A3 CL1 CL2 = = = = =
Page 18 of 28 Date
BATTERY MONITOR
DC Battery Voltage Level 1 (OFF, 20300 Vdc) DC Battery Voltage Level 2 (OFF, 20300 Vdc) DC Battery Voltage Level 3 (OFF, 20300 Vdc) DC Battery Voltage Level 4 (OFF, 20300 Vdc) DC1P DC2P DC3P DC4P = = = =
BREAKER 1 MONITOR
BKR1 Trigger Equation (SELOGIC control equation) BKMON1 = Close/Open Set Point 1 max (165000 operations) kA Interrupted Set Point 1 min (0.1999.0 kA primary) Close/Open Set Point 2 max (165000 operations) kA Interrupted Set Point 2 min (0.1999.0 kA primary) Close/Open Set Point 3 max (165000 operations) kA Interrupted Set Point 3 min (0.1999.0 kA primary) B1COP1 B1KAP1 B1COP2 B1KAP2 B1COP3 B1KAP3 = = = = = =
BREAKER 2 MONITOR
BKR2 Trigger Equation (SELOGIC control equation) BKMON2 = Close/Open Set Point 1 max (165000 operations) kA Interrupted Set Point 1 min (0.1999.0 kA primary) Close/Open Set Point 2 max (165000 operations) kA Interrupted Set Point 2 min (0.1999.0 kA primary) B2COP1 B2KAP1 B2COP2 B2KAP2 = = = =
Page 19 of 28 Date
BREAKER 3 MONITOR
BKR3 Trigger Equation (SELOGIC control equation) BKMON3 = Close/Open Set Point 1 max (165000 operations) kA Interrupted Set Point 1 min (0.1999.0 kA primary) Close/Open Set Point 2 max (165000 operations) kA Interrupted Set Point 2 min (0.1999.0 kA primary) Close/Open Set Point 3 max (165000 operations) kA Interrupted Set Point 3 min (0.1999.0 kA primary) B3COP1 B3KAP1 B3COP2 B3KAP2 B3COP3 B3KAP3 = = = = = =
ISQT
SEL-387E Settings Sheets Global Settings (SET G Command) SETTING GROUP SELECTION
Select Setting Group 1 (SELOGIC control equation) SS1 = Select Setting Group 2 (SELOGIC control equation) SS2 = Select Setting Group 3 (SELOGIC control equation) SS3 = Select Setting Group 4 (SELOGIC control equation) SS4 = Select Setting Group 5 (SELOGIC control equation) SS5 = Select Setting Group 6 (SELOGIC control equation) SS6 =
Page 20 of 28 Date
FRONT PANEL
Energize LEDA (SELOGIC control equation) LEDA = Energize LEDB (SELOGIC control equation) LEDB = Energize LEDC (SELOGIC control equation) LEDC = Show Display Point 1 (SELOGIC control equation) DP1 = DP1 Label 1 (16 characters) (Enter NA to Null) DP1 Label 0 (16 characters) (Enter NA to Null) Show Display Point 2 (SELOGIC control equation) DP2 = DP2 Label 1 (16 characters) (Enter NA to Null) DP2 Label 0 (16 characters) (Enter NA to Null) Show Display Point 3 (SELOGIC control equation) DP3 = DP3 Label 1 (16 characters) (Enter NA to Null) DP3 Label 0 (16 characters) (Enter NA to Null) DP3_1 DP3_0 = = DP2_1 DP2_0 = = DP1_1 DP1_0 = =
Page 21 of 28 Date
Page 22 of 28 Date
TEXT LABELS
Local Bit LB1 Name (14 characters) (Enter NA to Null) Clear Local Bit LB1 Label (7 characters) (Enter NA to Null) Set Local Bit LB1 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB1 Label (7 characters) (Enter NA to Null) Local Bit LB2 Name (14 characters) (Enter NA to Null) Clear Local Bit LB2 Label (7 characters) (Enter NA to Null) Set Local Bit LB2 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB2 Label (7 characters) (Enter NA to Null) Local Bit LB3 Name (14 characters) (Enter NA to Null) Clear Local Bit LB3 Label (7 characters) (Enter NA to Null) Set Local Bit LB3 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB3 Label (7 characters) (Enter NA to Null)
Date Code 20090205
NLB1 CLB1 SLB1 PLB1 NLB2 CLB2 SLB2 PLB2 NLB3 CLB3 SLB3 PLB3
= = = = = = = = = = = =
Page 23 of 28 Date = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =
NLB4 CLB4 SLB4 PLB4 NLB5 CLB5 SLB5 PLB5 NLB6 CLB6 SLB6 PLB6 NLB7 CLB7 SLB7 PLB7 NLB8 CLB8 SLB8 PLB8 NLB9 CLB9 SLB9 PLB9 NLB10 CLB10 SLB10 PLB10 NLB11 CLB11 SLB11 PLB11 NLB12
Page 24 of 28 Date
SEL-387E Settings Sheets Sequential Events Recorder Settings (SET R Command) TRIGGER CONDITIONS
Trigger SER (24 Relay Word bits per SERn equation, 96 total) SER1 SER2 SER3 SER4 = = = =
Page 25 of 28 Date
Page 26 of 28 Date
Note: RTSCTS setting does not appear if PROTO=LMD or DNP. PREFIX, ADDR, and SETTLE do not appear if PROTO=SEL or DNP. Only TPORT and TIDLE settings appear if PROTO=TELNET. See Appendix C: SEL Distributed Port Switch Protocol (LMD) for details on LMD protocol and see Appendix G: Distributed Network Protocol (DNP3) for details on DNP protocol. To enable Telnet-to-relay communications on PORT 5 and PORT 6, the PORT 1 PROTO setting must be set to TELNET. Setting PROTO = TELNET disabled PORT 1 for EIA-485 communications.
Page 27 of 28 Date
Page 28 of 28 Date
= = = =
TPORTC TIDLE
= =
EFTPSERV =
= = =
E61850 EGSE
= =