SEL-387E Settings Sheets Group Settings (SET Command) CONFIGURATION SETTINGS

Relay Identifier (39 Characters) RID = Terminal Identifier (59 Characters) TID = Enable Winding 1 in Differential Element (Y, N, Y1) Enable Winding 2 in Differential Element (Y, N, Y1) Enable Winding 3 in Differential Element (Y, N, Y1) Enable Winding 1 O/C Elements and Dmd Thresholds (Y, N) Enable Winding 2 O/C Elements and Dmd Thresholds (Y, N) Enable Winding 3 O/C Elements and Dmd Thresholds (Y, N) Enable Combined O/C Elements (Y, N) Enable Volts/Hertz Protection (Y, N) Enable Undervoltage Protection (Y, N) Enable Overvoltage Protection (Y, N) Enable Frequency Protection (N, 16) Enable SELOGIC Control Equations Set 1 (Y, N) Enable SELOGIC Control Equations Set 2 (Y, N) Enable SELOGIC Control Equations Set 3 (Y, N)

Page 1 of 28 Date Group

E87W1 E87W2 E87W3 EOC1 EOC2 EOC3 EOCC E24 E27 E59 E81 ESLS1 ESLS2 ESLS3

= = = = = = = = = = = = = =

GENERAL DATA
Winding 1 CT Connection (D, Y) Winding 2 CT Connection (D, Y) Winding 3 CT Connection (D, Y) Winding 1 CT Ratio (150000) Winding 2 CT Ratio (150000) Winding 3 CT Ratio (150000) Maximum Power Transformer Capacity (OFF, 0.25000 MVA) Define Internal CT Connection Compensation (Y, N) Winding 1 CT Conn. Compensation (0, 1, , 12) Winding 2 CT Conn. Compensation (0, 1, , 12) Winding 3 CT Conn. Compensation (0, 1, , 12) Winding 1 Line-to-Line Voltage (11000 kV)
Date Code 20090205

W1CT W2CT W3CT CTR1 CTR2 CTR3 MVA ICOM W1CTC W2CTC W3CTC VWDG1

= = = = = = = = = = = =

SEL-387E Settings Sheets Group Settings (SET Command)


Winding 2 Line-to-Line Voltage (11000 kV) Winding 3 Line-to-Line Voltage (11000 kV) PT Ratio (16500) Compensation Angle (0360 degrees) Voltage-Current Winding (1, 2, 3, 12) Three-Phase Voltage Input (Y, N) VWDG2 VWDG3 PTR COMPANG VIWDG TPVI

Page 2 of 28 Date Group = = = = = =

DIFFERENTIAL ELEMENTS
Note: TAP1TAP3 are auto-set by relay if MVA setting is not OFF. Winding 1 Current Tap (0.5155.0 A secondary) (5 A) (0.131.0 A secondary) (1 A) Winding 2 Current Tap (0.5155.0 A secondary) (5 A) (0.131.0 A secondary) (1 A) Winding 3 Current Tap (0.5155.0 A secondary) (5 A) (0.131.0 A secondary) (1 A) Restrained Element Operating Current PU ((0.101.00) multiple of tap) Restraint Slope 1 Percentage (5100%) Restraint Slope 2 Percentage (OFF, 25200%) Restraint Current Slope 1 Limit ((120) multiple of tap) Unrestrained Element Current PU ((120) multiple of tap) Second-Harmonic Blocking Percentage (OFF, 5100%) Fourth-Harmonic Blocking Percentage (OFF, 5100%) Fifth-Harmonic Blocking Percentage (OFF, 5100%) Fifth-Harmonic Alarm Threshold (OFF, (0.023.20) multiple of tap) Fifth-Harmonic Alarm TDPU (08000 cycles) DC Ratio Blocking (Y, N) Harmonic Restraint (Y, N) Independent Harmonic Blocking (Y, N) TAP3 O87P SLP1 SLP2 IRS1 U87P PCT2 PCT4 PCT5 TH5P TH5D DCRB HRSTR IHBL = = = = = = = = = = = = = = TAP2 = TAP1 =

RESTRICTED EARTH FAULT


Enable 32I (SELOGIC control equation) E32I =
Date Code 20090205

SEL-387E Settings Sheets Group Settings (SET Command)


Operating Quantity from W 1, W 2 (1, 2, 12) Positive-Sequence Current Restraint Factor, I0/I1 (0.020.50) Residual Current Sensitivity Threshold (0.2515.00 A secondary) (5 A) (0.053.00 A secondary) (1 A) 50GP 32IOP a0

Page 3 of 28 Date Group = =

WINDING 1 O/C ELEMENTS


WINDING 1 PHASE O/C ELEMENTS Phase Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Level 1 O/C Delay (016000 cycles) 50P11 Torque Control (SELOGIC control equation) 50P11TC = Phase Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50P12 Torque Control (SELOGIC control equation) 50P12TC = Phase Inst. O/C Level 3 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Inst. O/C Level 4 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Phase Inv.-Time O/C Curve (U1U5, C1C5) Phase Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Phase Inv.-Time O/C EM Reset (Y, N) 51P1 Torque Control (SELOGIC control equation) 51P1TC = 51P1P 51P1C 51P1TD 51P1RS = = = = 50P14P = 50P13P = 50P12P = 50P11P 50P11D = =

Date Code 20090205

SEL-387E Settings Sheets Group Settings (SET Command)


WINDING 1 NEGATIVE-SEQUENCE O/C ELEMENTS Note: All negative-sequence element pickup settings are in terms of 3I2. Neg.-Seq. Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Neg.-Seq. Level 1 O/C Delay (0.516000 cycles) 50Q11 Torque Control (SELOGIC control equation) 50Q11TC = Neg.-Seq. Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50Q12 Torque Control (SELOGIC control equation) 50Q12TC = Neg.-Seq. Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Neg.-Seq. Inv.-Time O/C Curve (U1U5, C1C5) Neg.-Seq. Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Neg.-Seq. Inv.-Time O/C EM Reset (Y, N) 51Q1 Torque Control (SELOGIC control equation) 51Q1TC = WINDING 1 RESIDUAL O/C ELEMENTS Residual Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Residual Level 1 O/C Delay (016000 cycles) 50N11 Torque Control (SELOGIC control equation) 50N11TC = Residual Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50N12 Torque Control (SELOGIC control equation) 50N12TC =
Date Code 20090205

Page 4 of 28 Date Group

50Q11P 50Q11D

= =

50Q12P

51Q1P 51Q1C 51Q1TD 51Q1RS

= = = =

50N11P 50N11D

= =

50N12P

SEL-387E Settings Sheets Group Settings (SET Command)


Residual Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Residual Inv.-Time O/C Curve (U1U5, C1C5) Residual Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Residual Inv.-Time O/C EM Reset (Y, N) 51N1 Torque Control (SELOGIC control equation) 51N1TC = WINDING 1 DEMAND METERING Demand Ammeter Time Constant (OFF, 5255 min) Phase Demand Ammeter Threshold (0.516.0 A secondary) (5 A) (0.13.2 A secondary) (1 A) Neg.-Seq. Demand Ammeter Threshold (0.516.0 A secondary) (5 A) (0.13.2 A secondary) (1 A) Residual Demand Ammeter Threshold (0.516.0 A secondary) (5 A) (0.13.2 A secondary) (1 A) PDEM1P 51N1P 51N1C 51N1TD 51N1RS

Page 5 of 28 Date Group

= = = =

DATC1

QDEM1P =

NDEM1P =

WINDING 2 O/C ELEMENTS


WINDING 2 PHASE O/C ELEMENTS Phase Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Level 1 O/C Delay (016000 cycles) 50P21 Torque Control (SELOGIC control equation) 50P21TC = Phase Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50P22 Torque Control (SELOGIC control equation) 50P22TC = 50P22P = 50P21P 50P21D = =

Date Code 20090205

SEL-387E Settings Sheets Group Settings (SET Command)


Phase Inst. O/C Level 3 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Inst. O/C Level 4 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Phase Inv.-Time O/C Curve (U1U5, C1C5) Phase Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Phase Inv.-Time O/C EM Reset (Y, N) 51P2 Torque Control (SELOGIC control equation) 51P2TC = WINDING 2 NEGATIVE-SEQUENCE O/C ELEMENTS Note: All negative-sequence element pickup settings are in terms of 3I2. Neg.-Seq. Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Neg.-Seq. Level 1 O/C Delay (0.516000 cycles) 50Q21 Torque Control (SELOGIC control equation) 50Q21TC = Neg.-Seq. Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50Q22 Torque Control (SELOGIC control equation) 50Q22TC = Neg.-Seq. Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Neg.-Seq. Inv.-Time O/C Curve (U1U5, C1C5) Neg.-Seq. Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Neg.-Seq. Inv.-Time O/C EM Reset (Y, N)
Date Code 20090205

Page 6 of 28 Date Group

50P23P

50P24P

51P2P 51P2C 51P2TD 51P2RS

= = = =

50Q21P 50Q21D

= =

50Q22P

51Q2P 51Q2C 51Q2TD 51Q2RS

= = = =

SEL-387E Settings Sheets Group Settings (SET Command)


51Q2 Torque Control (SELOGIC control equation) 51Q2TC = WINDING 2 RESIDUAL O/C ELEMENTS Residual Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Residual Level 1 O/C Delay (016000 cycles) 50N21 Torque Control (SELOGIC control equation) 50N21TC = Residual Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50N22 Torque Control (SELOGIC control equation) 50N22TC = Residual Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Residual Inv.-Time O/C Curve (U1U5, C1C5) Residual Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Residual Inv.-Time O/C EM Reset (Y, N) 51N2 Torque Control (SELOGIC control equation) 51N2TC = WINDING 2 DEMAND METERING Demand Ammeter Time Constant (OFF, 5255 min) Phase Demand Ammeter Threshold (0.516.0 A secondary) (5 A) (0.13.2 A secondary) (1 A) Neg.-Seq. Demand Ammeter Threshold (0.516.0 A secondary) (5 A) (0.13.2 A secondary) (1 A) Residual Demand Ammeter Threshold (0.516.0 A secondary) (5 A) (0.13.2 A secondary) (1 A)
Date Code 20090205

Page 7 of 28 Date Group

50N21P 50N21D

= =

50N22P

51N2P 51N2C 51N2TD 51N2RS

= = = =

DATC2

PDEM2P

QDEM2P =

NDEM2P =

SEL-387E Settings Sheets Group Settings (SET Command) WINDING 3 O/C ELEMENTS
WINDING 3 PHASE O/C ELEMENTS Phase Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Level 1 O/C Delay (016000 cycles) 50P31 Torque Control (SELOGIC control equation) 50P31TC = Phase Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50P32 Torque Control (SELOGIC control equation) 50P32TC = Phase Inst. O/C Level 3 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Inst. O/C Level 4 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Phase Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Phase Inv.-Time O/C Curve (U1U5, C1C5) Phase Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Phase Inv.-Time O/C EM Reset (Y, N) 51P3 Torque Control (SELOGIC control equation) 51P3TC = WINDING 3 NEGATIVE-SEQUENCE O/C ELEMENTS Note: All negative-sequence element pickup settings are in terms of 3I2. Neg.-Seq. Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Neg.-Seq. Level 1 O/C Delay (0.516000.0 cycles)
Date Code 20090205

Page 8 of 28 Date Group

50P31P 50P31D

= =

50P32P

50P33P

50P34P

51P3P 51P3C 51P3TD 51P3RS

= = = =

50Q31P 50Q31D

= =

SEL-387E Settings Sheets Group Settings (SET Command)


50Q31 Torque Control (SELOGIC control equation) 50Q31TC = Neg.-Seq. Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50Q32 Torque Control (SELOGIC control equation) 50Q32TC = Neg.-Seq. Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Neg.-Seq. Inv.-Time O/C Curve (U1U5, C1C5) Neg.-Seq. Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Neg.-Seq. Inv.-Time O/C EM Reset (Y, N) 51Q3 Torque Control (SELOGIC control equation) 51Q3TC = WINDING 3 RESIDUAL O/C ELEMENTS Residual Def.-Time O/C Level 1 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) Residual Level 1 O/C Delay (016000 cycles) 50N31 Torque Control (SELOGIC control equation) 50N31TC = Residual Inst. O/C Level 2 PU (OFF, 0.25100.00 A secondary) (5 A) (OFF, 0.0520.00 A secondary) (1 A) 50N32 Torque Control (SELOGIC control equation) 50N32TC = Residual Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) Residual Inv.-Time O/C Curve (U1U5, C1C5) Residual Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) Residual Inv.-Time O/C EM Reset (Y, N)
Date Code 20090205

Page 9 of 28 Date Group

50Q32P

51Q3P 51Q3C 51Q3TD 51Q3RS

= = = =

50N31P 50N31D

= =

50N32P

51N3P 51N3C 51N3TD 51N3RS

= = = =

SEL-387E Settings Sheets Group Settings (SET Command)


51N3 Torque Control (SELOGIC control equation) 51N3TC = WINDING 3 DEMAND METERING Demand Ammeter Time Constant (OFF, 5255 min) Phase Demand Ammeter Threshold (0.516.0 A secondary) (5 A) (0.13.2 A secondary) (1 A) Neg.-Seq. Demand Ammeter Threshold (0.516.0 A secondary) (5 A) (0.13.2 A secondary) (1 A) Residual Demand Ammeter Threshold (0.516.0 A secondary) (5 A) (0.13.2 A secondary) (1 A) PDEM3P

Page 10 of 28 Date Group

DATC3

QDEM3P =

NDEM3P =

COMBINED O/C ELEMENTS


Note: The combined overcurrent elements uses a normalization factor which scales the secondary current magnitude to the larger of the two winding CT Ratios. See 51PC1 and 51NC1 Combined Overcurrent Elements in Section 3 for details and examples of the combined overcurrent elements. W1W2 PHASE O/C ELEMENT W1W2 Phase Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) W1W2 Phase Inv.-Time O/C Curve (U1U5, C1C5) W1W2 Phase Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) W1W2 Phase Inv.-Time O/C EM Reset (Y, N) W1W2 RESIDUAL O/C ELEMENT W1W2 Residual Inv.-Time O/C PU (OFF, 0.516.0 A secondary) (5 A) (OFF, 0.13.2 A secondary) (1 A) W1W2 Residual Inv.-Time O/C Curve (U1U5, C1C5) W1W2 Residual Inv.-Time O/C Time-Dial (US 0.515.0, IEC 0.051.00) W1W2 Residual Inv.-Time O/C EM Reset (Y, N) 51NC1P 51NC1C 51NC1TD 51NC1RS = = = = 51PC1P 51PC1C 51PC1TD 51PC1RS = = = =

Date Code 20090205

SEL-387E Settings Sheets Group Settings (SET Command) 24 ELEMENTS


Protected Winding L-L Voltage (0.20800.00 kV primary) Transformer Winding Connection (D, Y) Level 1 Volts/Hertz Pickup (100200%) Level 1 Time Delay (0.04400.00 seconds) Level 2 Composite Curve Shape (OFF, DD, ID, I, U) Level 2 Inv.-Time Pickup (100200%) Level 2 Inv.-Time Curve (0.5, 1.0, 2.0) Level 2 Inv.-Time Factor (0.110.0 seconds) Level 2 Pickup One (100200%) Level 2 Time Delay One (0.04400.00 seconds) Level 2 Pickup Two (101200%) Level 2 Time Delay Two (0.04400.00 seconds) Level 2 Reset Time (0.00400.00 seconds) 24 Element Torque-Control (SELOGIC control equation) 24TC = VNOM 24WDG 24D1P 24D1D 24CCS 24IP 24IC 24ITD 24D2P1 24D2D1 24D2P2 24D2D2 24CR

Page 11 of 28 Date Group

= = = = = = = = = = = = =

27 ELEMENTS
Level 1 Phase U/V PU (OFF, 0.1300.0 V secondary) Level 2 Phase U/V PU (OFF, 0.1300.0 V secondary) Level 1 Phase-Phase U/V PU (OFF, 0.1520.0 V secondary) Level 2 Phase-Phase U/V PU (OFF, 0.1520.0 V secondary) Pos.-Seq. U/V PU (OFF, 0.1100.0 V secondary) 27P1P 27P2P 27PP1 27PP2 27V1P = = = = =

59 ELEMENTS
Level 1 Phase O/V PU (OFF, 0.0300.0 V secondary) Level 2 Phase O/V PU (OFF, 0.0300.0 V secondary) Level 1 Residual O/V PU (OFF, 0.0300.0 V secondary) Level 2 Residual O/V PU (OFF, 0.0300.0 V secondary) Neg.-Seq. U/V PU (OFF, 0.0100.0 V secondary) Level 1 Phase-Phase O/V PU (OFF, 0.0520.0 V secondary) Level 2 Phase-Phase O/V PU (OFF, 0.0520.0 V secondary) Pos.-Seq.(V1) O/V PU (OFF, 0.0100.0 V secondary) 59P1P 59P2P 59G1P 59G2P 59QP 59PP1 59PP2 59V1P = = = = = = = =

Date Code 20090205

SEL-387E Settings Sheets Group Settings (SET Command) 81 ELEMENTS


Undervoltage Block (20.0150.0 V secondary) Level 1 Pickup (OFF, 40.1065.00 Hz) Level 1 Time Delay (0.04300.00 seconds) Level 2 Pickup (OFF, 40.1065.00 Hz) Level 2 Time Delay (0.04300.00 seconds) Level 3 Pickup (OFF, 40.1065.00 Hz) Level 3 Time Delay (0.04300.00 seconds) Level 4 Pickup (OFF, 40.1065.00 Hz) Level 4 Time Delay (0.04300.00 seconds) Level 5 Pickup (OFF, 40.1065.00 Hz) Level 5 Time Delay (0.04300.00 seconds) Level 6 Pickup (OFF, 40.1065.00 Hz) Level 6 Time Delay (0.04300.00 seconds) 27B81P 81D1P 81D1D 81D2P 81D2D 81D3P 81D3D 81D4P 81D4D 81D5P 81D5D 81D6P 81D6D

Page 12 of 28 Date Group

= = = = = = = = = = = = =

MISCELLANEOUS TIMERS
Minimum Trip Duration Time Delay (48000 cycles) Close Failure Logic Time Delay (OFF, 08000 cycles) TDURD CFD = =

SELOGIC CONTROL EQUATIONS SET 1


Set 1 Variable 1 (SELOGIC control equation) S1V1 = S1V1 Timer Pickup (0999999 cycles) S1V1 Timer Dropout (0999999 cycles) Set 1 Variable 2 (SELOGIC control equation) S1V2 = S1V2 Timer Pickup (0999999 cycles) S1V2 Timer Dropout (0999999 cycles) Set 1 Variable 3 (SELOGIC control equation) S1V3 = S1V3 Timer Pickup (0999999 cycles) S1V3 Timer Dropout (0999999 cycles) Set 1 Variable 4 (SELOGIC control equation) S1V4 =
Date Code 20090205

S1V1PU S1V1DO

= =

S1V2PU S1V2DO

= =

S1V3PU S1V3DO

= =

SEL-387E Settings Sheets Group Settings (SET Command)


S1V4 Timer Pickup (0999999 cycles) S1V4 Timer Dropout (0999999 cycles) Set 1 Latch Bit 1 SET Input (SELOGIC control equation) S1SLT1 = Set 1 Latch Bit 1 RESET Input (SELOGIC control equation) S1RLT1 = Set 1 Latch Bit 2 SET Input (SELOGIC control equation) S1SLT2 = Set 1 Latch Bit 2 RESET Input (SELOGIC control equation) S1RLT2 = Set 1 Latch Bit 3 SET Input (SELOGIC control equation) S1SLT3 = Set 1 Latch Bit 3 RESET Input (SELOGIC control equation) S1RLT3 = Set 1 Latch Bit 4 SET Input (SELOGIC control equation) S1SLT4 = Set 1 Latch Bit 4 RESET Input (SELOGIC control equation) S1RLT4 =

Page 13 of 28 Date Group S1V4PU = S1V4DO =

SELOGIC Control Equations Set 2


Set 2 Variable 1 (SELOGIC control equation) S2V1 = S2V1 Timer Pickup (0999999 cycles) S2V1 Timer Dropout (0999999 cycles) Set 2 Variable 2 (SELOGIC control equation) S2V2 = S2V2 Timer Pickup (0999999 cycles) S2V2 Timer Dropout (0999999 cycles) Set 2 Variable 3 (SELOGIC control equation) S2V3 = S2V3 Timer Pickup (0999999 cycles) S2V3 Timer Dropout (0999999 cycles) Set 2 Variable 4 (SELOGIC control equation) S2V4 =
Date Code 20090205

S2V1PU S2V1DO

= =

S2V2PU S2V2DO

= =

S2V3PU S2V3DO

= =

SEL-387E Settings Sheets Group Settings (SET Command)


S2V4 Timer Pickup (0999999 cycles) S2V4 Timer Dropout (0999999 cycles) Set 2 Latch Bit 1 SET Input (SELOGIC control equation) S2SLT1 = Set 2 Latch Bit 1 RESET Input (SELOGIC control equation) S2RLT1 = Set 2 Latch Bit 2 SET Input (SELOGIC control equation) S2SLT2 = Set 2 Latch Bit 2 RESET Input (SELOGIC control equation) S2RLT2 = Set 2 Latch Bit 3 SET Input (SELOGIC control equation) S2SLT3 = Set 2 Latch Bit 3 RESET Input (SELOGIC control equation) S2RLT3 = Set 2 Latch Bit 4 SET Input (SELOGIC control equation) S2SLT4 = Set 2 Latch Bit 4 RESET Input (SELOGIC control equation) S2RLT4 =

Page 14 of 28 Date Group S2V4PU = S2V4DO =

SELOGIC CONTROL EQUATIONS SET 3


Set 3 Variable 1 (SELOGIC control equation) S3V1 = S3V1 Timer Pickup (0999999 cycles) S3V1 Timer Dropout (0999999 cycles) Set 3 Variable 2 (SELOGIC control equation) S3V2 = S3V2 Timer Pickup (0999999 cycles) S3V2 Timer Dropout (0999999 cycles) Set 3 Variable 3 (SELOGIC control equation) S3V3 = S3V3 Timer Pickup (0999999 cycles) S3V3 Timer Dropout (0999999 cycles) Set 3 Variable 4 (SELOGIC control equation) S3V4 =
Date Code 20090205

S3V1PU S3V1DO

= =

S3V2PU S3V2DO

= =

S3V3PU S3V3DO

= =

SEL-387E Settings Sheets Group Settings (SET Command)


S3V4 Timer Pickup (0999999 cycles) S3V4 Timer Dropout (0999999 cycles) Set 3 Variable 5 (SELOGIC control equation) S3V5 = S3V5 Timer Pickup (0999999 cycles) S3V5 Timer Dropout (0999999 cycles) Set 3 Variable 6 (SELOGIC control equation) S3V6 = S3V6 Timer Pickup (0999999 cycles) S3V6 Timer Dropout (0999999 cycles) Set 3 Variable 7 (SELOGIC control equation) S3V7 = S3V7 Timer Pickup (0999999 cycles) S3V7 Timer Dropout (0999999 cycles) Set 3 Variable 8 (SELOGIC control equation) S3V8 = S3V8 Timer Pickup (0999999 cycles) S3V8 Timer Dropout (0999999 cycles) Set 3 Latch Bit 1 SET Input (SELOGIC control equation) S3SLT1 = Set 3 Latch Bit 1 RESET Input (SELOGIC control equation) S3RLT1 = Set 3 Latch Bit 2 SET Input (SELOGIC control equation) S3SLT2 = Set 3 Latch Bit 2 RESET Input (SELOGIC control equation) S3RLT2 = Set 3 Latch Bit 3 SET Input (SELOGIC control equation) S3SLT3 = Set 3 Latch Bit 3 RESET Input (SELOGIC control equation) S3RLT3 = Set 3 Latch Bit 4 SET Input (SELOGIC control equation) S3SLT4 =

Page 15 of 28 Date Group S3V4PU = S3V4DO =

S3V5PU S3V5DO

= =

S3V6PU S3V6DO

= =

S3V7PU S3V7DO

= =

S3V8PU S3V8DO

= =

Date Code 20090205

SEL-387E Settings Sheets Group Settings (SET Command)


Set 3 Latch Bit 4 RESET Input (SELOGIC control equation) S3RLT4 = Set 3 Latch Bit 5 SET Input (SELOGIC control equation) S3SLT5 = Set 3 Latch Bit 5 RESET Input (SELOGIC control equation) S3RLT5 = Set 3 Latch Bit 6 SET Input (SELOGIC control equation) S3SLT6 = Set 3 Latch Bit 6 RESET Input (SELOGIC control equation) S3RLT6 = Set 3 Latch Bit 7 SET Input (SELOGIC control equation) S3SLT7 = Set 3 Latch Bit 7 RESET Input (SELOGIC control equation) S3RLT7 = Set 3 Latch Bit 8 SET Input (SELOGIC control equation) S3SLT8 = Set 3 Latch Bit 8 RESET Input (SELOGIC control equation) S3RLT8 =

Page 16 of 28 Date Group

TRIP LOGIC
TR1 TR2 TR3 TR4 ULTR1 ULTR2 ULTR3 ULTR4 = = = = = = = =

CLOSE LOGIC
52A1 52A2 52A3 CL1 CL2 = = = = =

Date Code 20090205

SEL-387E Settings Sheets Group Settings (SET Command)


CL3 ULCL1 ULCL2 ULCL3 = = = =

Page 17 of 28 Date Group

EVENT REPORT TRIGGERING


ER =

OUTPUT CONTACT LOGIC (STANDARD OUTPUTS)


OUT101 OUT102 OUT103 OUT104 OUT105 OUT106 OUT107 = = = = = = =

OUTPUT CONTACT LOGIC (EXTRA INTERFACE BOARD 2 OR 6)


OUT201 OUT202 OUT203 OUT204 OUT205 OUT206 OUT207 OUT208 OUT209 OUT210 OUT211 OUT212 = = = = = = = = = = = =

OUTPUT CONTACT LOGIC (EXTRA INTERFACE BOARD 4)


OUT201 OUT202 OUT203 OUT204 = = = =

Date Code 20090205

SEL-387E Settings Sheets Global Settings (SET G Command) RELAY SETTINGS


Length of Event Report (15, 29, 60 cycles) Length of Pre-fault in Event Report (1 to (LER-1)) Nominal Frequency (50, 60 Hz) Phase Rotation (ABC, ACB) Phase Potential Connection (D, Y) Date Format (MDY, YMD) Display Update Rate (160 seconds) (160) Front Panel Time-out (030 minutes) Group Change Delay (0900 seconds) LER PRE NFREQ PHROT DELTA_Y DATE_F SCROLD FP_TO TGR = = = = = = = = =

Page 18 of 28 Date

BATTERY MONITOR
DC Battery Voltage Level 1 (OFF, 20300 Vdc) DC Battery Voltage Level 2 (OFF, 20300 Vdc) DC Battery Voltage Level 3 (OFF, 20300 Vdc) DC Battery Voltage Level 4 (OFF, 20300 Vdc) DC1P DC2P DC3P DC4P = = = =

BREAKER 1 MONITOR
BKR1 Trigger Equation (SELOGIC control equation) BKMON1 = Close/Open Set Point 1 max (165000 operations) kA Interrupted Set Point 1 min (0.1999.0 kA primary) Close/Open Set Point 2 max (165000 operations) kA Interrupted Set Point 2 min (0.1999.0 kA primary) Close/Open Set Point 3 max (165000 operations) kA Interrupted Set Point 3 min (0.1999.0 kA primary) B1COP1 B1KAP1 B1COP2 B1KAP2 B1COP3 B1KAP3 = = = = = =

BREAKER 2 MONITOR
BKR2 Trigger Equation (SELOGIC control equation) BKMON2 = Close/Open Set Point 1 max (165000 operations) kA Interrupted Set Point 1 min (0.1999.0 kA primary) Close/Open Set Point 2 max (165000 operations) kA Interrupted Set Point 2 min (0.1999.0 kA primary) B2COP1 B2KAP1 B2COP2 B2KAP2 = = = =

Date Code 20090205

SEL-387E Settings Sheets Global Settings (SET G Command)


Close/Open Set Point 3 max (165000 operations) kA Interrupted Set Point 3 min (0.1999.0 kA primary) B2COP3 B2KAP3 = =

Page 19 of 28 Date

BREAKER 3 MONITOR
BKR3 Trigger Equation (SELOGIC control equation) BKMON3 = Close/Open Set Point 1 max (165000 operations) kA Interrupted Set Point 1 min (0.1999.0 kA primary) Close/Open Set Point 2 max (165000 operations) kA Interrupted Set Point 2 min (0.1999.0 kA primary) Close/Open Set Point 3 max (165000 operations) kA Interrupted Set Point 3 min (0.1999.0 kA primary) B3COP1 B3KAP1 B3COP2 B3KAP2 B3COP3 B3KAP3 = = = = = =

THROUGH-FAULT EVENT MONITOR


Enable Through-Fault Event Winding (N, 1, 2, 3) ETHRU = Note: Changing setting ETHRU resets/clears through-fault event information. Through-Fault Event Trigger (SELOGIC control equation) THRU = Through-Fault I t Alarm Threshold 2 (OFF, 04294967 (kA) seconds)
2

ISQT

ANALOG INPUT LABELS


Rename Current Input IAW1 (14 characters) Rename Current Input IBW1 (14 characters) Rename Current Input ICW1 (14 characters) Rename Current Input IAW2 (14 characters) Rename Current Input IBW2 (14 characters) Rename Current Input ICW2 (14 characters) Rename Current Input IAW3 (14 characters) Rename Current Input IBW3 (14 characters) Rename Current Input ICW3 (14 characters) Rename Voltage Input VAWX (14 characters) Rename Voltage Input VBWX (14 characters) Rename Voltage Input VCWX (14 characters) IAW1 IBW1 ICW1 IAW2 IBW2 ICW2 IAW3 IBW3 ICW3 VAWX VBWX VCWX = = = = = = = = = = = =

Date Code 20090205

SEL-387E Settings Sheets Global Settings (SET G Command) SETTING GROUP SELECTION
Select Setting Group 1 (SELOGIC control equation) SS1 = Select Setting Group 2 (SELOGIC control equation) SS2 = Select Setting Group 3 (SELOGIC control equation) SS3 = Select Setting Group 4 (SELOGIC control equation) SS4 = Select Setting Group 5 (SELOGIC control equation) SS5 = Select Setting Group 6 (SELOGIC control equation) SS6 =

Page 20 of 28 Date

FRONT PANEL
Energize LEDA (SELOGIC control equation) LEDA = Energize LEDB (SELOGIC control equation) LEDB = Energize LEDC (SELOGIC control equation) LEDC = Show Display Point 1 (SELOGIC control equation) DP1 = DP1 Label 1 (16 characters) (Enter NA to Null) DP1 Label 0 (16 characters) (Enter NA to Null) Show Display Point 2 (SELOGIC control equation) DP2 = DP2 Label 1 (16 characters) (Enter NA to Null) DP2 Label 0 (16 characters) (Enter NA to Null) Show Display Point 3 (SELOGIC control equation) DP3 = DP3 Label 1 (16 characters) (Enter NA to Null) DP3 Label 0 (16 characters) (Enter NA to Null) DP3_1 DP3_0 = = DP2_1 DP2_0 = = DP1_1 DP1_0 = =

Date Code 20090205

SEL-387E Settings Sheets Global Settings (SET G Command)


Show Display Point 4 (SELOGIC control equation) DP4 = DP4 Label 1 (16 characters) (Enter NA to Null) DP4 Label 0 (16 characters) (Enter NA to Null) Show Display Point 5 (SELOGIC control equation) DP5 = DP5 Label 1 (16 characters) (Enter NA to Null) DP5 Label 0 (16 characters) (Enter NA to Null) Show Display Point 6 (SELOGIC control equation) DP6 = DP6 Label 1 (16 characters) (Enter NA to Null) DP6 Label 0 (16 characters) (Enter NA to Null) Show Display Point 7 (SELOGIC control equation) DP7 = DP7 Label 1 (16 characters) (Enter NA to Null) DP7 Label 0 (16 characters) (Enter NA to Null) Show Display Point 8 (SELOGIC control equation) DP8 = DP8 Label 1 (16 characters) (Enter NA to Null) DP8 Label 0 (16 characters) (Enter NA to Null) Show Display Point 9 (SELOGIC control equation) DP9 = DP9 Label 1 (16 characters) (Enter NA to Null) DP9 Label 0 (16 characters) (Enter NA to Null) Show Display Point 10 (SELOGIC control equation) DP10 = DP10 Label 1 (16 characters) (Enter NA to Null) DP10 Label 0 (16 characters) (Enter NA to Null) Show Display Point 11 (SELOGIC control equation) DP11 = DP11 Label 1 (16 characters) (Enter NA to Null) DP11 Label 0 (16 characters) (Enter NA to Null) DP11_1 DP11_0 = = DP10_1 DP10_0 = = DP9_1 DP9_0 = = DP8_1 DP8_0 = = DP7_1 DP7_0 = = DP6_1 DP6_0 = = DP5_1 DP5_0 = = DP4_1 DP4_0 = =

Page 21 of 28 Date

Date Code 20090205

SEL-387E Settings Sheets Global Settings (SET G Command)


Show Display Point 12 (SELOGIC control equation) DP12 = DP12 Label 1 (16 characters) (Enter NA to Null) DP12 Label 0 (16 characters) (Enter NA to Null) Show Display Point 13 (SELOGIC control equation) DP13 = DP13 Label 1 (16 characters) (Enter NA to Null) DP13 Label 0 (16 characters) (Enter NA to Null) Show Display Point 14 (SELOGIC control equation) DP14 = DP14 Label 1 (16 characters) (Enter NA to Null) DP14 Label 0 (16 characters) (Enter NA to Null) Show Display Point 15 (SELOGIC control equation) DP15 = DP15 Label 1 (16 characters) (Enter NA to Null) DP15 Label 0 (16 characters) (Enter NA to Null) Show Display Point 16 (SELOGIC control equation) DP16 = DP16 Label 1 (16 characters) (Enter NA to Null) DP16 Label 0 (16 characters) (Enter NA to Null) DP16_1 DP16_0 = = DP15_1 DP15_0 = = DP14_1 DP14_0 = = DP13_1 DP13_0 = = DP12_1 DP12_0 = =

Page 22 of 28 Date

TEXT LABELS
Local Bit LB1 Name (14 characters) (Enter NA to Null) Clear Local Bit LB1 Label (7 characters) (Enter NA to Null) Set Local Bit LB1 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB1 Label (7 characters) (Enter NA to Null) Local Bit LB2 Name (14 characters) (Enter NA to Null) Clear Local Bit LB2 Label (7 characters) (Enter NA to Null) Set Local Bit LB2 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB2 Label (7 characters) (Enter NA to Null) Local Bit LB3 Name (14 characters) (Enter NA to Null) Clear Local Bit LB3 Label (7 characters) (Enter NA to Null) Set Local Bit LB3 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB3 Label (7 characters) (Enter NA to Null)
Date Code 20090205

NLB1 CLB1 SLB1 PLB1 NLB2 CLB2 SLB2 PLB2 NLB3 CLB3 SLB3 PLB3

= = = = = = = = = = = =

SEL-387E Settings Sheets Global Settings (SET G Command)


Local Bit LB4 Name (14 characters) (Enter NA to Null) Clear Local Bit LB4 Label (7 characters) (Enter NA to Null) Set Local Bit LB4 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB4 Label (7 characters) (Enter NA to Null) Local Bit LB5 Name (14 characters) (Enter NA to Null) Clear Local Bit LB5 Label (7 characters) (Enter NA to Null) Set Local Bit LB5 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB5 Label (7 characters) (Enter NA to Null) Local Bit LB6 Name (14 characters) (Enter NA to Null) Clear Local Bit LB6 Label (7 characters) (Enter NA to Null) Set Local Bit LB6 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB6 Label (7 characters) (Enter NA to Null) Local Bit LB7 Name (14 characters) (Enter NA to Null) Clear Local Bit LB7 Label (7 characters) (Enter NA to Null) Set Local Bit LB7 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB7 Label (7 characters) (Enter NA to Null) Local Bit LB8 Name (14 characters) (Enter NA to Null) Clear Local Bit LB8 Label (7 characters) (Enter NA to Null) Set Local Bit LB8 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB8 Label (7 characters) (Enter NA to Null) Local Bit LB9 Name (14 characters) (Enter NA to Null) Clear Local Bit LB9 Label (7 characters) (Enter NA to Null) Set Local Bit LB9 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB9 Label (7 characters) (Enter NA to Null) Local Bit LB10 Name (14 characters) (Enter NA to Null) Clear Local Bit LB10 Label (7 characters) (Enter NA to Null) Set Local Bit LB10 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB10 Label (7 characters) (Enter NA to Null) Local Bit LB11 Name (14 characters) (Enter NA to Null) Clear Local Bit LB11 Label (7 characters) (Enter NA to Null) Set Local Bit LB11 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB11 Label (7 characters) (Enter NA to Null) Local Bit LB12 Name (14 characters) (Enter NA to Null)
Date Code 20090205

Page 23 of 28 Date = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = = =

NLB4 CLB4 SLB4 PLB4 NLB5 CLB5 SLB5 PLB5 NLB6 CLB6 SLB6 PLB6 NLB7 CLB7 SLB7 PLB7 NLB8 CLB8 SLB8 PLB8 NLB9 CLB9 SLB9 PLB9 NLB10 CLB10 SLB10 PLB10 NLB11 CLB11 SLB11 PLB11 NLB12

SEL-387E Settings Sheets Global Settings (SET G Command)


Clear Local Bit LB12 Label (7 characters) (Enter NA to Null) Set Local Bit LB12 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB12 Label (7 characters) (Enter NA to Null) Local Bit LB13 Name (14 characters) (Enter NA to Null) Clear Local Bit LB13 Label (7 characters) (Enter NA to Null) Set Local Bit LB13 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB13 Label (7 characters) (Enter NA to Null) Local Bit LB14 Name (14 characters) (Enter NA to Null) Clear Local Bit LB14 Label (7 characters) (Enter NA to Null) Set Local Bit LB14 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB14 Label (7 characters) (Enter NA to Null) Local Bit LB15 Name (14 characters) (Enter NA to Null) Clear Local Bit LB15 Label (7 characters) (Enter NA to Null) Set Local Bit LB15 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB15 Label (7 characters) (Enter NA to Null) Local Bit LB16 Name (14 characters) (Enter NA to Null) Clear Local Bit LB16 Label (7 characters) (Enter NA to Null) Set Local Bit LB16 Label (7 characters) (Enter NA to Null) Pulse Local Bit LB16 Label (7 characters) (Enter NA to Null) CLB12 SLB12 PLB12 NLB13 CLB13 SLB13 PLB13 NLB14 CLB14 SLB14 PLB14 NLB15 CLB15 SLB15 PLB15 NLB16 CLB16 SLB16 PLB16 = = = = = = = = = = = = = = = = = = =

Page 24 of 28 Date

Date Code 20090205

SEL-387E Settings Sheets Sequential Events Recorder Settings (SET R Command) TRIGGER CONDITIONS
Trigger SER (24 Relay Word bits per SERn equation, 96 total) SER1 SER2 SER3 SER4 = = = =

Page 25 of 28 Date

RELAY WORD BIT ALIASES


Syntax: 'Relay-Word Bit' 'Up to 15 characters'. Use NA to disable setting. ALIAS1 ALIAS2 ALIAS3 ALIAS4 ALIAS5 ALIAS6 ALIAS7 ALIAS8 ALIAS9 ALIAS10 ALIAS11 ALIAS12 ALIAS13 ALIAS14 ALIAS15 ALIAS16 ALIAS17 ALIAS18 ALIAS19 ALIAS20 = = = = = = = = = = = = = = = = = = = =

Date Code 20090205

SEL-387E Settings Sheets Port Settings (SET P Command)

Page 26 of 28 Date

Note: RTSCTS setting does not appear if PROTO=LMD or DNP. PREFIX, ADDR, and SETTLE do not appear if PROTO=SEL or DNP. Only TPORT and TIDLE settings appear if PROTO=TELNET. See Appendix C: SEL Distributed Port Switch Protocol (LMD) for details on LMD protocol and see Appendix G: Distributed Network Protocol (DNP3) for details on DNP protocol. To enable Telnet-to-relay communications on PORT 5 and PORT 6, the PORT 1 PROTO setting must be set to TELNET. Setting PROTO = TELNET disabled PORT 1 for EIA-485 communications.

PORT 1 (SET P 1) REAR PANEL, EIA-485 PLUS IRIG-B


Port Protocol (SEL, LMD, DNP, TELNET) LMD Prefix (@, #, $, %, &) LMD Address (199) LMD Settling Time (030 seconds) Baud (300, 1200, 2400, 4800, 9600, 19200) Data Bits (7, 8) Parity Odd, Even, or None (O, E, N) Stop Bits (1, 2) Time-out (for inactivity) (030 minutes) Send auto messages to port (Y, N) Enable hardware handshaking (Y, N) Fast Operate Enable (Y, N) Telnet Port for Relay Access (165534) Telnet Port Timeout (130 minutes) PROTO PREFIX ADDR SETTLE SPEED BITS PARITY STOP T_OUT AUTO RTSCTS FASTOP TPORT TIDLE = = = = = = = = = = = = = =

PORT 2 (SET P 2) REAR PANEL, EIA-232 WITH IRIG-B


Port Protocol (SEL, LMD, DNP) LMD Prefix (@, #, $, %, &) LMD Address (199) LMD Settling Time (030 seconds) Baud (300, 1200, 2400, 4800, 9600, 19200) Data Bits (7, 8) Parity Odd, Even, or None (O, E, N) Stop Bits (1, 2) Time-out (for inactivity) (030 minutes) Send auto messages to port (Y, N) PROTO PREFIX ADDR SETTLE SPEED BITS PARITY STOP T_OUT AUTO = = = = = = = = = =

Date Code 20090205

SEL-387E Settings Sheets Port Settings (SET P Command)


Enable hardware handshaking (Y, N) Fast Operate Enable (Y, N) RTSCTS FASTOP = =

Page 27 of 28 Date

PORT 3 (SET P 3) REAR PANEL, EIA-232


Port Protocol (SEL, LMD, DNP) LMD Prefix (@, #, $, %, &) LMD Address (199) LMD Settling Time (030 seconds) Baud (300, 1200, 2400, 4800, 9600, 19200) Data Bits (7, 8) Parity Odd, Even, or None (O, E, N) Stop Bits (1, 2) Time-out (for inactivity) (030 minutes) Send auto messages to port (Y, N) Enable hardware handshaking (Y, N) Fast Operate Enable (Y, N) PROTO PREFIX ADDR SETTLE SPEED BITS PARITY STOP T_OUT AUTO RTSCTS FASTOP = = = = = = = = = = = =

PORT 4 (SET P 4) FRONT PANEL, EIA-232


Port Protocol (SEL, LMD, DNP) LMD Prefix (@, #, $, %, &) LMD Address (199) LMD Settling Time (030 seconds) Baud (300, 1200, 2400, 4800, 9600, 19200) Data Bits (7, 8) Parity Odd, Even, or None (O, E, N) Stop Bits (1, 2) Time-out (for inactivity) (030 minutes) Send auto messages to port (Y, N) Enable hardware handshaking (Y, N) Fast Operate Enable (Y, N) PROTO PREFIX ADDR SETTLE SPEED BITS PARITY STOP T_OUT AUTO RTSCTS FASTOP = = = = = = = = = = = =

Date Code 20090205

SEL-387E Settings Sheets Port Settings (SET P Command)

Page 28 of 28 Date

PORT 5 (SET P 5) REAR PANEL ETHERNET (WHEN EQUIPPED)


IP Address (xxx.xxx.xxx.xxx) Subnet Mask (xxx.xxx.xxx.xxx) Default Router (xxx.xxx.xxx.xxx) Enable TCP Keep-Alive (Y, N) If ETCPKA = Y TCP Keep-Alive Idle Range (120 s) TCP Keep-Alive Interval Range (120 s) TCP Keep-Alive Count Range (120 s) Enable Telnet (Y, N) If ETELNET = Y Telnet Port for Card Access (165534) Telnet Port Time-out (130 minutes) Enable FTP Server (Y, N) If EFTPSERV = Y FTP User Name (20 characters) FTP Connect Banner FTP Idle Time-out (5255 minutes) If IEC 61850 is Available Enable IEC 61850 Protocol (Y, N) Enable IEC 61850 GSE (Y, N) IPADDR SUBNETM DEFRTR ETCPKA = = = =

KAIDLE KAINTV KACNT ETELNET

= = = =

TPORTC TIDLE

= =

EFTPSERV =

FTPUSER FTPCBAN FTPIDLE

= = =

E61850 EGSE

= =