Sunteți pe pagina 1din 4

Instrument transformers

Outdoor bushing current transformer


Single and multi-ratio, externally mounted

Product features
Single and multi-ratio
Externally mounted
50-60 Hz
600 V class
Application
Outdoor bushing current transformers are used for relaying on
existing power transformers or circuit breakers. Installation time
is minimum since it is not necessary to remove bushings or
open the tank for mounting.
Due to varying bushing dimensions, it is recommended that the
power transformer or circuit breaker manufacturer determine
if the bushing strike distance will be affected by the size of the
bushing current transformer being installed.
Construction features
The core and coil assemblies are housed in an aluminum case and
filled with polyurethane. The aluminum case has a shielding effect,
protecting the winding in case of bushing flashover. A secondary
junction box with three conduit fittings is standard on every unit.
Curves
Saturation, overcurrent, ratio correction factor, and phase-angle
curves are available upon request.
Test reports
IEEE test reports are stored electronically and can be e-mailed
in various formats at the time of shipment.
Standards
This unit meets all applicable IEEE and NEMA standards.

Installation notes
Remove bushing flange nuts (4 total as shown) and assemble
mounting brackets.
Remove bushing gaps to allow clearance for lowering current
transformer over bushing.
Maintain 3/8" clearance between current transformer housing
and bushing tap socket.
Caution: When mounting current transformer, care must be
taken to see that the inside wall of the current transformer
clears and does not touch any metal parts of bushing or
mounting, so as not to complete a ground circuit around
current transformer housing.
Maximum K (bushing shed diameter) is F - 1/8"
Maximum L (for voltage tap socket clearance) is F/2 - 3/8"
Minimum M (bushing flange height) is J + 1/4"

BOLT CIRCLE
DIAMETER

Selection guide
Inside diameter (in.)

IEEE relaying accuracy

IEEE metering accuracy

Continuous rating factor

Style number

Nominal ratio 600:5 MR


12

C400

0.3B-0.5

1.33

7881A86G01

18

C400

0.6B-0.5

1.33

7881A86G02

22

C400

0.6B-0.5

1.33

7881A86G03

32

C400

0.6B-0.2

1.33

7881A86G04

Nominal ratio 1200:5 MR


12

C800

0.3B-2.0

1.33

7881A86G05

18

C800

0.3B-0.5

1.33

7881A86G06

22

C800

0.3B-0.5

1.33

7881A86G07

32

C800

0.3B-0.2

1.33

7881A86G08

Nominal ratio 2000:5 MR


12

C800

0.3B-2.0

1.33

7881A86G09

18

C800

0.3B-2.0

1.33

7881A86G10

22

C800

0.3B-2.0

1.33

7881A86G11

32

C800

0.3B-0.5

1.33

7881A86G12

Nominal ratio 3000:5 MR


12

C800

0.3B-2.0

1.33

7881A86G51

18

C800

0.3B-2.0

1.33

7881A86G52

22

C800

0.3B-2.0

1.33

7881A86G53

32

C800

0.3B-2.0

1.33

7881A86G54

Additional styles available upon request. Contact your ABB sales representative or call +1-252-827-3212 for more information.

Mounting bracket selection guide


IEEE bushing flange characteristics
Inside diameter (in.)

Bolt circle diameter (in.)

Number of bolts

Bolt size (in.)

Style number

12

7.25

0.6875

589A864G01

12

8.25

0.6875

589A864G01

12

9.25

0.875

589A864G02

18

9.25

0.875

589A864G04

22

13.25

1.25

589A864G03

22

13.25

1.25

589A864G04

22

15.75

1.25

589A864G05

32

21.00

12

1.25

589A864G06

2 Outdoor bushing current transformer | ABB product bulletin

Unit dimensions
Note: metric dimensions are displayed in [mm].
SECONDARY JUNCTION
BOX WITH CONDUIT CONN.
ON THREE SIDES

NAMEPLATE

PRIMARY
POLARITY
MARKER

2.19
[56]

THIS SURFACE
TO BE MOUNTED
DOWN

B.C.

HOLES FOR
.63 MTG
BOLTS
4-TOTAL

GO.D.

LIFTING LUG
4-TOTAL

F I.D.

45

.38
[10]

45

Dimensions (in)
Style number

7881A86G01

26.53

12.06

14.47

12.53

22.88

12.0

24.13

6.0

6.38

Weight (lb)
240

7881A86G02

33.03

15.19

17.84

15.91

29.13

18.0

30.38

6.0

6.38

330

7881A86G03

37.28

17.25

20.03

18.09

33.25

22.0

34.50

6.0

6.38

400

7881A86G04

47.56

22.31

25.25

23.31

43.38

32.0

44.63

6.0

6.38

550

7881A86G05

26.53

12.06

14.47

12.53

22.88

12.0

24.13

6.0

6.38

240

7881A86G06

33.03

15.19

17.84

15.91

29.13

18.0

30.38

6.0

6.38

330

7881A86G07

37.28

17.25

20.03

18.09

33.25

22.0

34.50

6.0

6.38

400

7881A86G08

47.56

22.25

25.25

23.31

43.38

32.0

44.63

6.0

6.38

550

7881A86G09

25.88

11.75

14.13

12.19

22.25

12.0

23.50

4.56

4.94

155

7881A86G10

32.34

14.84

17.50

15.56

28.44

18.0

29.69

4.56

4.94

210

7881A86G11

36.44

16.84

19.59

17.66

32.44

22.0

33.69

4.56

4.94

245

7881A86G12

46.75

21.91

24.84

22.91

42.56

32.0

43.81

4.56

4.94

340

7881A86G51

24.94

11.31

13.63

11.69

21.38

12.0

22.63

4.38

4.75

125

7881A86G52

31.03

14.22

16.81

14.88

27.19

18.0

28.44

4.19

4.56

160

7881A86G53

35.34

16.31

19.03

17.09

31.38

22.0

32.63

4.19

4.56

190

7881A86G54

45.66

21.38

24.28

22.34

41.50

32.0

42.75

4.19

4.56

200

Weight (kg)

Dimensions (mm)
Style number

7881A86G01

674

306

368

318

581

305

613

152

162

109

7881A86G02

839

386

453

404

740

457

772

152

162

150

7881A86G03

947

438

509

459

845

559

876

152

162

181

7881A86G04

1208

567

641

592

1102

813

1134

152

162

249

7881A86G05

674

306

368

318

581

305

613

152

162

109

7881A86G06

839

386

453

404

740

457

772

152

162

150

7881A86G07

947

438

509

459

845

559

876

152

162

181
249

7881A86G08

1208

565

641

592

1102

813

1134

152

162

7881A86G09

657

298

359

310

565

305

597

116

125

70

7881A86G10

821

377

445

395

722

457

754

116

125

95

7881A86G11

926

428

498

449

824

559

856

116

125

111

7881A86G12

1187

556

631

582

1081

813

1113

116

125

154

7881A86G51

633

287

346

297

543

305

575

111

121

57

7881A86G52

788

361

427

378

691

457

722

106

116

73

7881A86G53

898

414

483

434

797

559

829

106

116

86

7881A86G54

1160

543

617

567

1054

813

1086

106

116

91

ABB product bulletin | Outdoor bushing current transformer 3

ABB Inc.
Medium Voltage Distribution Components
3022 NC 43 North
Pinetops, NC 27864
USA
Phone: +1 252 827 3212
Fax: +1 252 827 4286
www.abb.com/mediumvoltage

Note:
We reserve the right to make technical changes or modify the contents of this
document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any responsibility whatsoever for
potential errors or possible lack of information in this document. We reserve
all rights in this document and in the subject matter and illustrations contained
therein. Any reproductionin whole or in partsis forbidden without ABBs prior
written consent.
Copyright 2011 ABB.
All rights reserved.

1VAP428581-DB May 2011 Rev. A

For more information please contact:

S-ar putea să vă placă și