Calculation for 9000 Gallons Roof Tank Cooling System

Description Tank Volume, Gallons Water Temperature Required Incoming Water Temperature Desired Temperature Difference Formulae Q = m x Cp x (T2-T1) Cooling Capacity kW Sp, Specific heat of water T, initial cooling period = Volume of Water lits x Sp x (T2-T1) oC / 860 x T = = 1.0 Kcal / Kg. x oC 6 hours COOLING LOAD T2 (Incoming water temp.) T1 (reqd. water temp.) T2-T1 Therefore, kW = = = = = 43 o C 28 o C 15o C 34,000 x 1 x 15/ 860 x 6 98.85 kW In Summer 9000 (34,000 lits) 28 deg C/ 43 deg C 15 oC

To cool in 6 hour, TR Note:

28.25 Tons (98.85 kW)

Total water flow rate can be calculated by = Total tank volume / cooling time i.e. 34000/6 = 5667 Lit/hr

Units suggested 2 units of 50 kW each with flow 2.9 m3/hr and T 15C.

Calculation for 16000 Gallons Roof Tank Cooling System


Description Tank Volume, Gallons Water Temperature Required Incoming Water Temperature Desired Temperature Difference Formulae Q = m x Cp x (T2-T1) Cooling Capacity kW Sp, Specific heat of water T, initial cooling period = Volume of Water lits x Sp x (T2-T1) oC / 860 x T = = 1.0 Kcal / Kg. x oC 6 hours COOLING LOAD T2 (Incoming water temp.) T1 (reqd. water temp.) T2-T1 Therefore, kW = = = = = 43 o C 28 o C 15o C 60,600 x 1 x 15/ 860 x 6 176.20 kW In Summer 16000 (60,600 lits) 28 deg C/ 43 deg C 15 oC

To cool in 6 hour, TR Note:

50.50 Tons (176.50 kW)

Total water flow rate can be calculated by = Total tank volume / cooling time i.e. 60,600/6 = 10,100 Lit/hr

Units suggested 2 units of 80 kW each with flow 4.6 m3/hr and T 15C.