Documente Academic
Documente Profesional
Documente Cultură
PSYCHROMETRICS
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
Thermodynamics Fundamentals
The physical quantities used to describe air are referred to as variables. The most important of these variables are
Temperature
Humidity
Pressure
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
Absolute Humidity (x): The amount of water in grams (g) per kilogram (kg) of air. (g/kg or grains/ lb) [7000 grains make a pound]
Relative Humidity () : Ratio of water vapour carried at a specified atmospheric temperature and condition to the water vapour that can be carried by air at the same temperature when saturated.
= Relative Humidity
x = 100% xS
x = Water vapour in g/kg Xs = Water vapour for saturated air in g/kg Expressed always in %
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
Thermodynamics Fundamentals
VARIABLES Density () : Mass per unit volume, expressed in kg/M3 The density of dry air = 1.293 kg/m3 The density of water vapour = 0.804 kg/m3 Specifc Heat (c):The specific heat c of a solid, liquid or gaseous material is the amount of heat required to heat up a mass of 1 kg of the material by 1 K. Specific heat increases with increasing temperature of the material and for gases also with increasing pressure. As a result, for gases, we distinguish between cP, the specific heat at constant pressure and cV, the specific heat at constant volume. Tables generally specify the values for cP at 20 C and 1013 mbar air pressure. These values are also suitable for calculations in heating, ventilation and air-conditioning systems and hold for: Dry air: cP = 1.01 kJ/(kg*K) : Water vapor: cP = 1.86 kJ/(kg*K)
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
Thermodynamics Fundamentals
VARIABLES
Thermal capacity or enthalpy (h) Kj/kg. Absolutely dry air having a theoretical water content of 0 g/kg at a temperature of 0C has an enthalpy defined as h=0kj/kg Differences in enthalpy h between the beginning and end state of an air modification, can be depicted graphically on a psychrometric chart. If we multiply the mass [kg] of the air to be processed with the graphicallydetermined enthalpy difference h, the result is the required quantity of heat for this state change.
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
Thermodynamics Fundamentals
VARIABLES
Pressure: Mass per unit area. The weight of the air on the surface of the earth is called atmosphere pressure. At sea level the average value is 1.013 bar or 760 mm Hg. The pressure unit in the international system of units (Sl units) is: 1 Newton/m2 = 1 N/m2 = 1 Pa (Pascal) 1 bar = 1000 mbar (millibar) = 105 N/m2 = 105 Pa
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
Mass flow :
Kg/s or Kg/h
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
PSYCHROMETRICS Dry air exists only in theory. Atmospheric air is always a mixture of dry air and water vapour.
To keep the air under desired, favourable conditions, air has to be treated. To what levels this air has to be treated can be calculated (in order to maintain desired, favourable conditions) using the PSYCHROMETRIC CHART
PSYCHROMETRICSSekar R
PSYCHROMETRICS
ABSOLUTE HUMIDITY (KG/KG)
50 c
SATURATION LINE
-15 c
25c
DRY BULB TEMPERATURE
PSYCHROMETRICSSekar R
PSYCHROMETRICS
Relative Humidity Lines
ABSOLUTE HUMIDITY (KG/KG)
20 G/KG 10 G/KG
50 c
lpy tha En
SATURATION LINE
50
RH %
-15 c
25c
Wet Bulb Lines
DRY BULB TEMPERATURE
PSYCHROMETRICSSekar R
PSYCHROMETRICS
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
PSYCHROMETRICS
Dew point Temperature That temperature at which further cooling of air causes condensation. If we have to de-humidify a water - vapour air mixture, we have to cool it below the dew point temperature.The lower the temperature to which the mixture is cooled, the greater is the dehumidifying effect. Wet-bulb Temperature The temperature measured by a wet wick thermometer while exposed to a rapid flow of air. The difference between the Dry bulb temperature and the wet bulb temperature is known as the wet bulb depression. Drier the air, larger is the wet bulb depression. When the rh of air approaches saturation values, the wet bulb temperature approaches Dry bulb temperature. At saturation, the air cannot hold any more moisture, the Dry bulb, the wet bulb and the dew point temperature are the same
PSYCHROMETRICSSekar R
1 (tD C)
Is a Direct Measure of Heat Added
4 Fan
(t H C)
5 - Air 3 thermometer with bulb covered with wet wick Due to air movement, thermometer 3 is cooled by the evaporation of moisture The degree to which thermometer 3 can be cooled depends on the dryness of the air. Drier the air, greater is the temperature difference between 2 and 3
B22-4
Aspirating Thermometer
PSYCHROMETRICSSekar R
PSYCHROMETRICS - PROCESSES
The state of a given atmosphere is represented by a point on the chart, known as the status point. If any two of the three commonly available characteristics DBT, WBT and RH are known, the others can be read from the chart
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
PSYCHROMETRICS
0.55 0.60
ENTHALPY-50 KJ/KG
WBT 18 DEG C
25 DEG C, DBT
PSYCHROMETRICSSekar R
PSYCHROMETRICS
From Psychromteric Chart identify the values of all other important parameters for condition of air defined at 30 Deg C, 40% RH.
Moisture content (ABS HUM) : 10.5 grams / kg Dry air WBT : 20 deg c DPT : 14.9 deg c Enthalpy : 57.5 Kj / KG
0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 1.00
PSYCHROMETRICSSekar R
PSYCHROMETRICS - PROCESSES
Psychrometric processes, ie, changes in the condition of the atmosphere, can be represented by the movement of this status point in the following ways
Sensible Heating
No Moisture Addition Dry bulb Temperature Increases Wet Bulb Increases RH Decreases Enthalpy Increases
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
PSYCHROMETRICS - PROCESSES
Psychrometric processes, ie, changes in the condition of the atmosphere, can be represented by the movement of this status point in the following ways
Dehumidification by Cooling
At some stage, continuous cooling causes the status point to meet the saturation line. The DBT corresponding to this point is called as the DEW POINT TEMPERATURE
From hereon further cooling causes condensation resulting in moisture being pulled out from air (reduction in absolute humidity dehumidification)
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
PSYCHROMETRICS - PROCESSES
Psychrometric processes, ie, changes in the condition of the atmosphere, can be represented by the movement of this status point in the following ways
PSYCHROMETRICS - PROCESSES
Psychrometric processes, ie, changes in the condition of the atmosphere, can be represented by the movement of this status point in the following ways
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
PSYCHROMETRICS - PROCESSES
Psychrometric processes, ie, changes in the condition of the atmosphere, can be represented by the movement of this status point in the following ways
Mixing Process
Mixing
The status point of the final air mixture always lies on the line connecting the status points of the initial conditions of the two airstreams The location of the final status point is inversely proportional to their masses. (If m1 is greater than m2, the final point is closer to m1)
PSYCHROMETRICS - PROCESSES
Steam Humidification
Evaporative Cooling
Sensible Cooling
Sensible Heating
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
Psychrometrics
PSYCHROMETRICSSekar R
PSYCHROMETRICS - PROCESSES
Initial Condition Final Condition Find Final RH Moisture Added Enthalpy Added
~ 80% RH
0.55
10 C / 50% rh 30 C / 27 C WBT
~ 21.5 g/kg
kj /k g
85 -1 9. 8= 65 .2
17.7 g/kg
~ 3.81g/kg
PSYCHROMETRICSSekar R
= 27C
PSYCHROMETRICSSekar R
0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 1.00
PSYCHROMETRICSSekar R
INTERNAL
Number of People / activity of People Equipment and nature of heat dissipation (dry heat / moisture) Machines Leakages
OTHER
Ventilation Requirement Process Requirement
PSYCHROMETRICSSekar R
IMPORTANT EQUATIONS
SENSIBLE HEAT : 1.08 X CFM X T(F) LATENT HEAT : 0.68 X CFM X W (gr/LB) TOTAL HEAT : 4.45 X CFM X H (BTU/LB) (Btu/Hr)
1.23 X M3/S X T(C) 3010 X M3/S X W(kg/kg) 1.20 X M3/S X H(KJ/KG) (Kw)
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
PSYCHROMETRICS
1.2 = density of air in kg/m3 1.006 specific heat of dry air kj/kgK w = absolute humidity = kg/kg (=0.01kg/kg for most A/C applications) 1.84 = specific heat of water vapour kj/kgK 3010 kj/kg = 1.2 x 2500, where 2500 is the approximate heat content of 50% rh vapour at 24C, less the heat content of water at 10C. 50%rh / 24C is a common design point for conditioned space, and 10C is normal condensate temperature for cooling & dehumidifying coils.
DERIVATION OF AIR CONSTANTS Sensible Heat = 1.20 (1.006+1.84W) x m3/s x t(C) ~ 1.23 x M3/S x t(C) Latent heat = 3010 x m3/s x W (kg/kg) Total Heat = 1.20 x m3/s x H(kj/kg)
PSYCHROMETRICSSekar R
DERIVATION OF CONSTANTS
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
PSYCHROMETRICS
DERIVATION OF AIR CONSTANTS 1.08 = 0.244 X 60 13.5 0.68 = 60 X 1076 13.5 7000 4.45 = 60 13.5
0.244 = specific heat of moist air at 70F db and 50%rh Btu/lb F 60 = min/hour 13.5 = specific volume of moist air at 70F db and 50%rh (Ft3/lb) 1076 = average heat removal required to condense one pound of water vapour from the room air (Btu/lb) 7000 = grains / pound
PSYCHROMETRICSSekar R
Conditioned space
Exposed
3.8 M
Conditioned space
3.8 M
Exposed
PSYCHROMETRICSSekar R
PSYCHROMETRICSSekar R
Enthalpy of air Entering room = 34.8 kj/kg Room Design Enthalpy = 45.8 kj/kg Enthalpy gain in room = 1.2 x 154 x (45.8-34.8) = 2033 watts
RSHF = 0.89
PSYCHROMETRICSSekar R PSYCHROMETRICSSekar R
The Cooling Process on the PSYCH Chart Example with Addition of 1 ACPH Fresh Air for Ventilation
Process through Coil ADD 1 ACPH OA FOR VENTILATION
He = 49.2 kj/kg
0.55
OA
0.60 0.65
14 deg C
The Cooling Process on the PSYCH Chart Example with Addition of 1 ACPH Fresh Air for Ventilation
H = 46 kj/kg
He = 49.2 kj/kg
0.55 0.60 0.65
Latent Heat removed by coil : 1.2 x 167 x (49.2 - 46) = 641 Sensible Heat removed by coil : 1.2 x 167 x (46 - 34.8) = 2244 Coil GSHF = 2244 / (2244 + 641) = 0.79
PSYCHROMETRICSSekar R
The Cooling Process on the PSYCH Chart Example with Addition of 1 ACPH Fresh Air for Ventilation
Cross verify Air Leaving Temperature = {(24.7 9.9) x 0.277} + 9.9 = 14 deg C (matches exactly With our earlier values) Apparatus Dew Point Temp (ADP) = 9.9 deg C
0.55 0.60 0.65 0.70 0.75 0.80 0.85 0.90 0.95 1.00
The ratio of air that does not make contact with cooling coil (bypass). In our example this is approximately 27.7%
PSYCHROMETRICSSekar R
IMPORTANT POINTS
A High Sensible Load application often requires large airflow quantity to off set the loads Increasing the number of rows of cooling coil decreases bypass factor and increases contact over the coil. High latent loads require more rows of cooling coil. SHF approaches 1, when the sensible heat gets higher and higher Greater the Latent Load, larger is the deviation of SHF from Unity. High Latent Load Application often results in a low ADP. It may not be possible to achieve such a low ADP with a normal chilled water application. We have to select an ADP within permissible levels. In doing so, the equipment must be selected with a re-heat coil as well as additional air quantity to offset this reheat.
PSYCHROMETRICSSekar R
PSYCHROMETRICSSekar R