Sunteți pe pagina 1din 4

Protocol Driver

Driver Version: 1.06 Document Revision: 3

FieldServer Driver - Fieldbus


FS8700-24

ControlNet
Description The ControlNet driver allows the FieldServer to transfer data to and from devices using ControlNet protocol. The SST-5136-CN-ISA Communications Adapter card is included with the FieldServer. The FieldServer can communicate using un-scheduled transfers with PCCC messages embedded in the ControlNet messages. When the FieldServer originates PCCC messages to communicate with PLC5 controllers, it uses connected messages. This provides fast reliable communication to the other node. When another device originates PCCC messaging, the FieldServer will emulate a PLC5 controller supporting connected or unconnected messages to files N7 through to N32.. Formal Driver Type Fieldbus Compatibility Matrix FieldServer Model FS-x2010 FS-x2011 FS-x40 FS-x30 Connection Information Connection type: Baud Rates: Hardware interface: Proprietary 5 Mbit/s SST-5136-CN-ISA Compatible with this driver No No Yes No

Proprietary Physical Interfaces Supported Fieldserver Model FS-x40 Devices tested Device SST-5136-CN-ISA Tested (FACTORY, SITE) Factory Adapter Model # SST-5136-CN-ISA Vendor Woodhead Canada Physical Medium 75 Co-ax

FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-9042 Toll-Free: 888-509-1970 Email: sales@fieldserver.com Website: www.fieldserver.com Page 1 of 4

Protocol Driver

Connection configurations

SST-5136-CN-ISA

FS-x40

75 O T-pieces

To ControlNet Network

75 O network terminators

(408)-262-2299

FIELDSERVER CONTROLNET CONNECTION DIAGRAM


BASE NAME: FILE NAME: FS8700-24 DATE: 11/4/05 BY: MC

Connection Notes Recommended cable is RG-6 quad shield Co-ax.

FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-9042 Toll-Free: 888-509-1970 Email: sales@fieldserver.com Website: www.fieldserver.com Page 2 of 4

Protocol Driver

Communications functions - Supported functions at a glance: Data Types Supported FieldServer Data Type 16-bit Integers ( Signed and Unsigned ) 32-bit Floats Bit Description (or Device Data Type) File arranged as words File arranged as floats File arranged as bits

Data Operations supported FieldServer as a Client Read file data Write file data FieldServer as a Server Provide file data to a Scanner Accept changes to file data from a Scanner

Unsupported Functions and Data Types Function Programming messages Scheduled Transfers Reason FieldServer is a data transfer device, and as such, programming messages are not required

FieldServer Technologies, 1991 Tarob Court, Milpitas, CA 95035 USA Tel: 408-262-2299, Fax: 408-262-9042 Toll-Free: 888-509-1970 Email: sales@fieldserver.com Website: www.fieldserver.com Page 3 of 4