Panels supplied for different types of HT motors by BHEL Bhopal generally consist of MICOM P220 relay make AREVA. These relays are numerical relays and consist of all types of motor protections. Testing of these relays before commissioning of motors is required at site. In these relays there is locked rotor protection which is checked during the relay testing at site. There are two types of protection are incorporated, these are LOCKED ROTOR, EXCESS LONG START.
So this function simply depends on the current taken by motor. As during locked rotor condition current of the motor goes on increasing as the current reaches the setting value the protection act and trip the motor. NOTE: Motor Stalled protection will act after the time delay obtained by the addition of delay time provided in the setting of locked rotor during start up and the time delay setting provided for rotor stalled during normal run.
Testing Procedure:
The EXCES LONG START function protects the motor if the starting phase lasts too long. To do this, it uses a starting current threshold Istart> and a starting time delay tIstart. This threshold and this time delay can be adjusted to allow the starting current to pass. The MiCOM P220 relay uses following things for motor start-up detection: Closure of the contactor/circuit breaker, or Closure of the contactor/circuit breaker and overshoot of the starting current threshold [Istart]. Here in GIPCL SLPP Mangrol we have done setting of both breaker contact and over shoot of the starting current (52A+I). It is deactivated on expiry of the starting current time delay tIstart.If, on expiry of the time delay tIstart, the current consumed by the motor has not fallen below the threshold Istart> again, a prolonged start signal .LONG START t Istart will be generated and it will trip the breaker. For testing Excess Long start protection on Micom P220 relay we have to feed Threshold current setting value along with breaker contact to relay terminal for start up detection. The detection of breaker closed state should be provided within 90 milliseconds along with threshold value of current otherwise it will not detect the start up condition of motor. For providing breaker closing status within 90 millisecond we have to loop positive terminal of 220 volts with binary input of omicron kit to terminal 22 of the relay and negative of 220 volts is fed directly terminal 24 as shown below in diagram 1.0. Here in SLPP Mangrol breaker contact looping with relay terminal 22 and 24 was not provided, this was done on site for taking this protection on line.
(+)1 10 volts
(-)1 10 volts A)
DIAGRAM 1.0