Documente Academic
Documente Profesional
Documente Cultură
Made In Japan
The KASUGA Overcurrent Relay is specially designed to monitor and detect current in each phase of a 3-phase system and provide a relay operation when an overcurrent condition occurs. This relay is simple in design, robust in construction and small in size.
SPECIFICATIONS
1. 2. 3. 4. 5. Type Supply Voltage Current Setting Delay Time Setting Operating Time
6. Reset Current value 7. Output 8. Indication 9. Life 10 Protection Structure 11. Enclosure : Standard DIN case Material Weight
RAS70-3B Knob (:R) AC 230V, 50/60Hz - 15 ~ +10% 2 ~ 7 A. 0 ~ 1.0 sec. With 105% Input < 300 msec With more than 200% Input < 100 msec. More than 90% of operating value. 2C. AC 250V, 5 A (cos 0 = 1) Approval : UL and CSA recognised. Knob Green LED (auxiliary power supply). (time setting) Red LED (relay tripped). Electrical : > 100,000 operation. Mechanical : > 100,000 operation. Green LED IP50 (dust protection) (power supply) DIN 96x96x98mm. ABS resin complying with UL94VO. Approx. 500g.
Knob (:T)
PANEL CUTOUT
92 0.5
92 0.5
DIMENSIONS (mm)
96
108 80
90
RAS 70 - 3
R S T N
L K L K L K L
RAS 703
sec. 6 1.0
0.9
70
80
90
100
110
120
100
200
300
400
500
600
700
Overcurrent (%)
CT power consumption
0.5 (A)
sec. 6 1.0
-20
20
40
60
80
10
Temperature (C)
Current (A)
Exclusive Agent: