Sunteți pe pagina 1din 4

Overcurrent Relay RAS70-3B

Made In Japan

The KASUGA Overcurrent Relay is specially designed to monitor and detect current in each phase of a 3-phase system and provide a relay operation when an overcurrent condition occurs. This relay is simple in design, robust in construction and small in size.

Special Features of KASUGA Overcurrent Relay RAS70-3B


> RAS 70-3 Overcurrent Relay is designed based on the combination of RAS 70 with a timer. > Easy wiring constitution for compact panel mounting. > A manually test button is provided for periodical inspection and product checking. > Build-in delay timer with adjustable range of 0 ~ 1.0 second, optional : 0 - 10 sec. on request. > Adjustable current setting from 2 ~ 7 Amps. > Three Red and one Green LEDs are provided to indicate the status of each phase current and the auxiliary power supply. > A manually reset button is provided. > A lockable front cover is provided to ensure that unauthorized personnel cannot tamper with the set point.

SPECIFICATIONS
1. 2. 3. 4. 5. Type Supply Voltage Current Setting Delay Time Setting Operating Time

Red LED (0.C. trip) Red LED (0.C. trip)

Knob (:S) Red LED (0.C. trip)

6. Reset Current value 7. Output 8. Indication 9. Life 10 Protection Structure 11. Enclosure : Standard DIN case Material Weight

RAS70-3B Knob (:R) AC 230V, 50/60Hz - 15 ~ +10% 2 ~ 7 A. 0 ~ 1.0 sec. With 105% Input < 300 msec With more than 200% Input < 100 msec. More than 90% of operating value. 2C. AC 250V, 5 A (cos 0 = 1) Approval : UL and CSA recognised. Knob Green LED (auxiliary power supply). (time setting) Red LED (relay tripped). Electrical : > 100,000 operation. Mechanical : > 100,000 operation. Green LED IP50 (dust protection) (power supply) DIN 96x96x98mm. ABS resin complying with UL94VO. Approx. 500g.

Knob (:T)

RESET button TEST button

Overcurrent Relay RAS70-3B


CHARACTERISTICS
Voltage Accuracy Repeat Accuracy Setting Accuracy Temperature Accuracy Insulation resistance Overcurrent Withstand Power Consumption C.T. Power Consumption Voltage withstand Insulation IEC 255-5 2kV rms for 1 minute between all case terminals connected together and the case earth terminal. 2kV rms for 1 minute between independent circuit including contact circuits. Impulse test IEC 255-5 5 KV peak, 1.2/50s (0.5J) between all terminals and case, earth and between adjacent terminal. Environmental withstand Temperature IEC 68-2-1 / 68-2-2 Storage and transit - 25C to +70C Operating -25C to +55C Humidity IEC 68-2-3 56 days @ 93% RH and +40C Enclosure protection IEC 529 IP50 (dust protected) Vibration IEC 255-21-1 0.5g between 10 Hz and 150Hz Electromagnetic wave Non-operation for radio frequency at 130 ~ 180 MHz and 400 ~ 500 MHZ (by Walkie-talkie of 5W). 11 96 Less than 3% Less than1% Less than 5% of full scale Less than 5% at 20C >1000M 10 times for 3 sec. Approx. 2VA Approx. 0.5VA

PANEL CUTOUT
92 0.5

92 0.5

DIMENSIONS (mm)
96

108 80

90

Overcurrent Relay RAS70-3B


CONNECTION DIAGRAM
RASP18NB

RAS 70 - 3

R S T N

L K L K L K L

RAS 703

Voltage characteristics (7A, 1 sec.)


(A)

Operating time-overcurrent (1sec.) Operating time (sec.) Operating time (sec.)


1.1 1.0

Operating current (A)

sec. 6 1.0

0.9

70

80

90

100

110

120

100

200

300

400

500

600

700

Supply voltage (%)

Overcurrent (%)

Temperature characteristics (7A, 1 sec.) Operating current (A)


7 1.1

CT power consumption
0.5 (A)

Power consumption (VA)

Operating time (sec.)

0.4 0.3 0.2 0.1 0

sec. 6 1.0

-20

20

40

60

80

10

Temperature (C)

Current (A)

Exclusive Agent:

KASUGA ELECTRIC WORKS LTD


3-11 Shimorenjaku 8-Chome, Mitaka Tokyo 181-8518, Japan Tel: 0422-47-5881 Fax: 0422-44-6277 51 Kim Keat Road, Unit 05-02 Mun Hean Industrial Building, Singapore 328821 Tel: (65) 6250 0522 Fax: (65) 6253 6885/(65) 6253 5879 E-mail: munheansing@munhean.com.sg Website: http://www.munheansingapore.com