AN-NAJAH NATIONAL UNIVERSITY FACULTY OF ENGINEERING ELECTRICAL ENGINEERING DEPARTMENT

ELECTRICAL MACHINE LAB2 63378 For Electrical Engineering Students Group #3 (Students name: Tamer T. Khateeb (10301127 (Kroom abo zaroor (10301005 (Ahmad Ordoniah (10302019 (Experiment #: (1
:Experiment Name

AC THREE-PHASE, FOUR-POLE SYNCHRONOUS GENERATOR ROTATING FIELD, DISTRIBUTED STATOR WINDING

Day: Saturday, Monday Date:1/7/2006 Time:12-3 :Instructors name Dr.Imad Break Eng.Sa'eed dwekat

:OBJECTIVES .To study open circuit test, load test, and short circuit test .1 .To study the regulation characteristics of the alternator .2 :EXPERIMENTAL PROCEDURE Make the circuit as in figure 1 as a three-phase, four-pole generator, delta .1 .connection, rotating field :Open-Circuit Characteristic Switch on the drive motor, bring its speed up to 1500 r.p.m and maintain at this .2 value throughout the test. Switch on the DC rotor supply, with no external load applied to the generator increase the DC current from zero to 4.0 Amp in steps (0.4 amp at each step ), take readings of AC line terminal voltage and rotor current at each .(step, then plot the no load characteristics(Line voltage and If

Figure # 1

Line "voltage"Vac Rotor (current"If"(A

0 0

27 4.

43 8.

60 1.2

80 1.6

100 2

115 2.4

125 2.8

140 3.2

150 3.6

O.C Char.
180 160 Line voltage 140 120 100 80 60 40 20 0 0 1 2 If(A) 3 4 5

:Short Circuit Characteristics In this test the three line terminals are shorted together through the AC ammeter as .3 shown in figure 2, and with the drive speed maintained at 1500 r.p.m, switch on the DC rotor supply and increase the current in steps from zero to 4.0 A, taking readings

of output current on short circuit and rotor current at each step. Then plot the graph of .short circuit current against field excitation current

Field (current(A

0.4 0.2

0.8 0.4

1.2 0.8

1.6 1

2.0 1.2

2.4 1.6

2.8 1.8

3.2 2

3.6 2.3

4.0 2.6

(Isc' (A'

S.C Char..
3 2.5 2 Iline 1.5 1 0.5 0 0 1 2 If 3 4 5

:Load Characteristics Connect a three-phase resistive load to the generator terminals as in figure 3, and .4 initially set to maximum value, vary the speed to give 1500 r.p.m, switch on the DC power supply and adjust the field current to give a terminal voltage equals to 60 V .(line to line) at no load, maintain speed and field current constant through the test

Vary the load resistor to minimum taking readings of load current and terminal .5 .voltage. Then plot the relation between terminal voltage and load current Load Case1 Line-line voltage 60 ((V (Load current (A 0.1 Case2 50 0.3 Case3 40 0.5 Case4 25 0.6

load Char..
70 60 50 Vline 40 30 20 10 0 0 0.1 0.2 0.3 IL 0.4 0.5 0.6 0.7

:Regulation Characteristics Adjust the field current to give no load voltage 60V, then at constant speed 1500 .6 r.p.m and constant terminal voltage 60V,(resistive load) vary the load resistor in steps, take readings of load current and field current. Plot the relation between field current .and load current Load Case1 Case2 Case3 Case4 Field current 1.2 1.4 2 2.6 ((A Load current 0.2 0.35 0.73 1.2 ((A Regulation Char..
1.4 1.2 1 IL 0.8 0.6 0.4 0.2 0 0 0.5 1 1.5 If 2 2.5 3

:NOTE Part (7&8)were not been done under your wise recommendations due to the insufficient capacitor

:Questions .Obtain the curve indicates the relation between Zs & If .1

Relation between Impedence & field current

3 Field 2 current (A) 1 0 0 200 Impedence (Ohm) 400

Series1

Assume the generator has an overall efficiency 50%, calculate the drive torque .2 .needed to maintain a speed of 1500 r.p.m when the generator supplying a 30 W load Efficiency= Pout/Pin** Pin/30=0.5 Pin=60W=>Pin=* =2**n*/60 =0.38N.m .Plot a graph of total power against IL .3
20 15 powe r 10 5 0 0 0.2 IL 0.4 0.6 1

?From the results, what is the effect of the load on .5 .A) Load characteristics .B) Regulation characteristics .a-the terminal voltage decreased** .b-the terminal voltage increased