Form 58TUA-6PD
home heating requirements. This furnace family provides the widest range of heating capacities available. The superior attention to cabinet detail is obvious. The Carrier WeatherMaker 8000 two-speed features 1-piece, seamless, wraparound construction. There are no spot welds on the exterior surfaces of the WeatherMaker 8000 Two-Speed Furnace. There is also double protection for the cabinet. First, a galvanized steel substrate provides resistance to rusting. Then the cabinet is constructed of prepainted steelthe same high-quality finish found on refrigerators and dishwashers. Perhaps the most advanced feature of the WeatherMaker 8000 two-speed
is the state-of-the-art microprocessor control center which shows true leadership in furnace technology. The simplified electronics in this control provide high reliability while performing many of the functions of older, electro-mechanical devices in other furnaces. Advanced features of the control show Carriers true leadership in furnace technology. The control provides blower delay at start-up and shutdown, while monitoring furnace operations and functions. In the unlikely event of a service call, in less than a minute, the technician can use the self-test feature to determine if a major component has failed. The control will check itself, then the low and high inducers, silicon
carbide ignition, and low-, medium-, and high-speed blower. The control also features a 3-amp fuse that protects the transformer and control. Best of all, the Carrier WeatherMaker 8000 two-speed is easily installed. Many features make this furnace the easy choice for replacement or new construction markets. Left and right connections are provided for gas and electrical supplies. An easy-to-remove bottom, heating and cooling blower speed selector, cased or uncased cooling coils, low-voltage humidifier, and electronic air cleaner terminal connections are among other features.
COM
PR2
EAC-2
4 1
5 2
6 3 PR1 HI-COOL
EAC-1
L2
PARK
LO-GAS -HEAT
HI-GAS -HEAT
L1
SEC-1
FU1 3 10 11 7 4 1 8 5 2 12 9 6 3 MASTER SLAVE 1 TWIN TEST LED 1 W2 COM 24 V OFF ON W/W1 1 2 3 4 Y/Y2 R G HUM SEC-2
A89217
A93150
A92074
HEAT EXCHANGER
Input Capacity 040 40,000 Btuh 060 60,000 Btuh 080 80,000 Btuh 100 100,000 Btuh 120 120,000 Btuh 135 133,000 Btuh
Cooling Size (Airflow) (400 CFM per 12,000 Btuh) 08 1800 CFM 12 1200 CFM 14 1400 CFM 16 1500 CFM 20 2000 CFM Series Number
1 9 2 3 14 4
10
13 5 15 7
11 12
A93147
NOTE: The 58TUA Furnaces are for use with natural gas, but can be field-converted for propane gas with a factory-authorized and listed accessory conversion kit. NOTE: Control location and actual control may be different than shown above.
1 2 3 4 5 6 7 8
Relief Box Gas Valve Control Knob (On/Off) 2-Stage Gas Valve Gas Burner Hot Surface Ignitor. Blower Door Safety Switch. Blower and Blower Motor Draft Safeguard Tube and Switch
9 10 11 12 13 14 15
Rating Plate Gas Manifold Filter Retainer Air Filter Flame Sensor Manual Reset Flame Rollout Switch Status LED Light and Control
Carrier accessories*
5
FILTER FRAME
FILTER
B C
FILTER
FILTER
B FURNACE
A FURNACE DOOR
A93067
A93068
A95432
A91365
RETURN-AIR PLENUM
Custom-made return-air plenum can be mounted on either side of the furnace. Includes washable filters .
A B C
A B C
UNIT SIZE AIR CLEANER HUMIDIFIER THERMOSTAT RETURN-AIR PLENUM (With Washable Filters) SIDE FILTER RACK (Accepts one 16 x 25 x 1 Filter) TWINNING KIT HIGH-ALTITUDE PRESSURE SWITCH KIT GAS CONVERSION KIT* NATURAL-TO-PROPANE PROPANE-TO-NATURAL
040-12
060-08 and 12
100-12 and 16
120-16 and 20
135-20
Model ARIA, KEACA, 31MF, or MECH Model 49BF, 49BG, 49FH, 49FP, or 49WS See Master Price Pages KGARP0201ALL KGAFR0201ALL KGATW0401HSI KGAHA5501PSW KGANP24012SP KGAPN20012SP
* Factory authorized and field installed. Gas conversion kits are A.G.A. recognized. 16 and 20 models only. 5500 ft and higher above sea level.
Physical data
UNIT SIZE OUTPUT CAPACITY (BTUH) Nonweatherized ICS GAS INPUT (BTUH)* SHIPPING WEIGHT (LB) CERTIFIED TEMP RISE RANGE (F) High Stage Low Stage Cooling AIRFLOW CFM LIMIT CONTROL HEATING BLOWER CONTROL INDUCER BURNERS (Monoport) GAS CONNECTION SIZE GAS VALVE (Redundant) Manufacturer Minimum Inlet Pressure (In. wc) Maximum Inlet Pressure (In. wc) IGNITION DEVICE 2 3 4 1/2-in. NPT White-Rodgers 4.5 (Natural Gas) 13.6 (Natural Gas) Hot Surface Heating High/Low Cooling High Stage Low Stage High Stage Low Stage 040-12 32,000 21,000 40,000 26,000 124 15-45 5-35 0.10 0.5 1140/980 1250 060-08 49,000 31,000 60,000 39,000 132 45-75 30-60 0.12 0.5 740/600 880 060-12 49,000 31,000 60,000 39,000 134 25-55 15-45 0.12 0.5 1195 080-14 65,000 42,000 80,000 52,000 150 35-65 20-50 0.15 0.5 1360 080-16 65,000 42,000 80,000 52,000 154 30-60 15-45 0.15 0.5 1740 100-12 81,000 52,000 100,000 65,000 160 50-80 30-60 0.20 0.5 1205 100-16 81,000 52,000 100,000 65,000 166 40-70 20-50 0.20 0.5 1575 100-20 81,000 52,000 100,000 65,000 184 25-55 15-45 0.20 0.5 2210 120-16 98,000 63,000 120,000 78,000 178 45-75 30-60 0.20 0.5 1620 120-20 98,000 63,000 120,000 78,000 194 40-70 25-55 0.20 0.5 1980 135-20 108,000 73,000 133,000 91,000 204 45-75 30-60 0.20 0.5 1905
1140/990 1170/1010 1445/1260 1185/1015 1410/1265 1720/1515 1415/1260 1730/1525 1695/1500 SPST (Auto-Reset) Solid-State Time Operation 2-Speed 5 6 7
* Gas input ratings are certified for elevations to 2000 ft. For elevations above 2000 ft, reduce ratings 4% for each 1000 ft above sea level. Refer to National Fuel Gas Code Table F4. In Canada, derate the unit 10% for elevations 2000 ft to 4500 ft above sea level. Tentative capacity and AFUE in accordance with U.S. Government DOE test procedures. Air delivery above 1800 CFM requires that both sides, or a combination of 1 side and bottom, or bottom only of the furnace be used for return air. A filter is required for each return-air supply. ICS Isolated Combustion System
Dimensions
CLEARANCES (In.)
UNIT SIZE Furnace SidesSingle-Wall Vent Type B-1, Double-Wall Vent Furnace Back Top of Plenum Vent ConnectorSingle-Wall Type B-1, Double-Wall Furnace Front*Single-Wall Type B-1, Double-Wall Vent Service 040 and 060 1 0 0 1 6 1 6 3 30 080135 0 0 0 1 6 1 6 3 30
* A minimum 3-in. front clearance is needed for combustion-air and ventilation-air entry.
A D
2 116
1316
19 OUTLET
1316
1 5 38 5
1316 78-IN.
78-IN.
1116
39 78
2 38 2
38
DIA ACCESSORY
SIDE INLET
TYP 1
SIDE INLET
1412
134
1116
1116
1116
58 TYP
NOTES: 1. Two additional 78-in. dia holes are located in the top plate. 2. Minimum return-air opening at furnace: a. For 800 CFM16-in. round or 1412 x 12-in. rectangle. b. For 1200 CFM20-in. round or 1412 x 1912-in. rectangle. c. For 1600 CFM22-in. round or 1412 x 2314-in. rectangle. d. For airflow requirements above 1800 CFM, use both side inlets, a combination of 1 side inlet and the bottom, or the bottom only.
A88367
NOTES: 1. A factory-supplied panel covers the back side of the accessory return-air plenum that extends above the furnace. 2. Refer to the furnace Installation Instructions for proper venting procedures.
DIMENSIONS (In.)
UNIT SIZE 040-12 060-08 060-12 080-14 080-16 100-12 100-16 100-20 120-16 120-20 135-20 A 14-3/16 14-3/16 14-3/16 17-1/2 21 17-1/2 21 24-1/2 21 24-1/2 24-1/2 D 12-9/16 12-9/16 12-9/16 15-7/8 19-3/8 15-7/8 19-3/8 22-7/8 19-3/8 22-7/8 22-7/8
E
12-11/16 12-11/16 12-11/16 16 19-1/2 16 19-1/2 23 19-1/2 23 23
VENT CONNECTION 4 4 4 4 4 4 4 4 5 5 5
Performance data
UNIT SIZE DIRECT-DRIVE MOTOR Hp (PSC) MOTOR FULL LOAD AMPS RPM (Nominal) SPEEDS BLOWER WHEEL DIAMETER X WIDTHS (In.) WASHABLE 16 x 25 x 1-in. FILTER QTY WASHABLE 20 x 25 x 1-in. FILTER QTY 040-12 1/3 5.8 1075-4 10 x 6 1 060-08 1/5 2.9 1075-4 10 x 6 1 060-12 1/3 5.8 1075-4 10 x 6 1 080-14 1/3 5.8 1075-4 10 x 7 1 080-16 1/2 7.9 1075-4 10 x 8 1 100-12 1/3 5.8 1075-4 10 x 7 1 100-16 1/2 7.9 1075-4 10 x 8 1 100-20 3/4 11.1 1075-4 11 x 10 2 120-16 1/2 7.9 1075-4 10 x 8 1 120-20 3/4 11.1 1075-4 11 x 10 2 135-20 3/4 11.1 1075-4 11 x 10 2
EFFICIENCY
UNIT SIZE CAPACITY* AFUE %* Nonweatherized ICS High Stage Low Stage 040-12 32,000 21,000 80.0 060-08 49,000 31,000 80.0 060-12 49,000 31,000 80.0 080-14 65,000 42,000 80.0 080-16 65,000 42,000 80.0 100-12 81,000 52,000 80.0 100-16 81,000 52,000 80.0 100-60 81,000 52,000 80.0 120-16 98,000 63,000 80.0 120-20 98,000 63,000 80.0 135-20 108,000 73,000 80,000
*Tentative capacity and AFUE in accordance with U.S. Government DOE test procedures. ICS Isolated Combustion System
060-08
060-12
080-14
080-16
100-12
100-16
100-20
120-16
120-20
135-20
* Air delivery above 1800 CFM requires that both sides, or a combination of 1 side and bottom, or bottom only of the furnace be used for return air. A filter is required for each return-air supply opening. Indicates unstable operating conditions.
ama
A PP R O VED R
OPTIONAL
Y/Y2
Y1
W2
W1
Y2
Y1
Electrical data
UNIT SIZE UNIT VOLTSHERTZPHASE MINIMUM WIRE SIZE MAXIMUM WIRE LENGTH (Ft)* MAXIMUM UNIT AMPS OPERATING VOLTAGE RANGE (MinMax) MAX FUSE SIZE OR HACR-TYPE CKT BKR (Amps) TRANSFORMER (24v) EXTERNAL CONTROL POWER AVAILABLE AIR CONDITIONING BLOWER RELAY Heating Cooling 15 15 15 15 15 14 34 10.9 14 45 8.2 14 32 11.4 14 31 11.7 14 27 13.5 040-12 060-08 060-12 080-14 080-16 100-12 115601 14 35 10.5 104127 15 40va 19va 35va Standard 15 20 15 20 20 14 28 13.2 12 30 19.0 14 28 13.2 12 31 18.2 12 33 17.4 100-16 100-20 120-16 120-20 135-20
* Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop. Permissible limits of the voltage range at which the unit will operate satisfactorily. Time-delay fuse is recommended.
Typical installations
CONDENSING UNIT
HUMIDIFIER
A89242
SERVICE TRAINING
Packaged Service Training programs are an excellent way to increase your knowledge of the equipment discussed in this manual, including: Unit Familiarization Maintenance Installation Overview Operating Sequence A large selection of product, theory, and skills programs is available, using popular video-based formats and materials. All include video and/or slides, plus companion book. Classroom Service Training plus "hands-on" the products in our labs can mean increased confidence that really pays dividends in faster troubleshooting, fewer callbacks. Course descriptions and schedules are in our catalog. CALL FOR FREE CATALOG 1-800-962-9212 [ ] Packaged Service Training [ ] Classroom Service Training
A94328
8-96
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations. Book Tab 1 4 Page 8 Catalog No. 525-849 Printed in U.S.A. PC 101 Form 58TUA-6PD Replaces: 58TUA-5PD