Geberit Installation Instruction

Art.No.224.383.00.1
All measurements in cm (1 cm = 10 mm) 0 = FFL = Finished oor level Hf = Height of ush pipe,dimension to WC suppliers specication
Note:Add necessary precautions in case of condensation risk!

882 184 00 0 IN 230v/50Hz/100mA OUT 3.5-4.2V=/500mA F1 2A/250V TH V DE

Netzteil NTWC 03

964.338.00 .0 SY03/03

SEV

Pages 1 to 3 of this installation instruction shows only the basic layout for front access cistern installation. Page 5 shows additional schematic layout for rear access installation options. Page 6 shows the basic layout for front access brick installation. The cistern and HyTronic actuator can be installed in several different positions. Conrm with the bathroom designer the required installation details or alternatively refer to product brochure. Provision for a sufciently sized removable service panel is strictly required. This removable panel has to provide full access to the service opening of the cistern. Also consider that the service personnel require sufcient room to perform maintenance through the service opening.

1 Layout
230-240V 50-60Hz

See electronic components montage sheet for additional information

46-60 9 0-4 45 85 55 465 103 59 5


Install a removable access or cover plate centered over the service opening of the cistern. Minimum size W28cm x H14cm.

45

If cavity is deeper than 9 cm keep front part of the access opening ush with studs at the front. If cavity is 9 cm deep keep back of cistern ush with back of stud wall. Cistern can also be rev erse mounted .
FFL Waste
Waste

9 0-4

8 7 16-29

8 5

16-29
Waste position to WC suppliers specication. Waste ttings by others.

Hf FFL

Hf

FFL

2 Fasten cistern
Assemble and install rail as shown below.

46-60
10 59
3

48

Left rail in front of right rail.


If cavity is 9cm deep back of cistern ush with back of studs.

16-2

9
0 FL F

Bend supplied metal straps and install as required.

48 9

Hf
Hf = Height of ush pipe, dimension to WC suppliers specication

42

If cavity is deeper than 9cm keep front part of the access opening ush with studs at the front.

170.586.00.0(00)

-1-

Geberit Installation Instruction


3 Flush pipe preparation
This procedure is only for the supplied black ush pipe bend and not for the ush pipe adaptor kit

D
5 16-29 5

Hf

Cut ush pipe bend to required length

Chamfer the inside edge of the cut.

Lubricate o-ring (lubricant supplied)

Push ush pipe over cistern spiggot. Allow for 2 cm clearance when ush pipe bend is adjusted to the required installation eight Hf . This will also provide for an additional 2 cm adjustment (up or down) if required later.

4 Flush pipe installation

1
Secure ush pipe bend with supplied bracket "A". Pipe to be held rmly but should still be moveable up or down if so required later.

3-23

For a longer ush pipe than the minimum length of 16 cm increase the 9 minimum distance of the 16-2 rail by the same amount. eg.: ush pipe 17 cm = rail distance 14 cm

Hf

0 FFL

Assemble and install rail as shown below.

46-60

Ensure that ush pipe bend is installed plumb.

Hf

34

36

Left rail in front of right rail.

FFL

5 Stop valve installation


Flush line befor connecting hose Remove service cover Use supplied grommet

Hexagon of tube bush to be inside the cistern.

Max. 65
Fully open

90

90

1/2" female tube bush ( not supplied )

-2-

Geberit Installation Instruction


6 Testing
Before the wall is closed cistern must be tested. 1. Open stop valve (Fig.1). 2. Fill cistern and install inner cover (Fig.2A). 3. Check water tightness. Insert protection plug into the ush bend opening and secure it with tape. Leave cistern under test (refer to standard) (Fig.3B). 4. Final water tightness test. Remove protection plug and empty the cistern completely. (lift ush valve) Insert protection plug and secure it with tape (Fig.4).

Fig. 1

Fig. 2

Fig. 3

Fig. 4

B A

7 Fit tiling template

8
Wall sheeting and tiles shall be cut up to the edge of the tiling template.

Fit styrofoam tiling template

Do a nal check on the required ush pipe height Hf.

Hf

0 FFL

9 Kee seal
The cistern is supplied with two different sized kee seals. The kee seal with an outside diameter of 6 cm seals ush pipe holes in the ceramic sized 5.3 cm to maximum 5.7cm. The kee seal with an outside diameter of 6.7 cm seals ush pipe holes in the ceramic sized 5.6 cm to maximum 6.2 cm.

Flush pipes
The cistern is supplied with a 18 cm long ush pipe for concealed installations. As an accessory longer ush pipes for in-duct installations are available. For installations with an exposed ush pipe there are also a variety of nishes and materials available. Enquire with your supplier.

Access plate
This installation requires an access plate. For product selection refer to product brochure.

-3-

Geberit Installation Instruction


10 Flush pipe adaptor kit
If the 224.383.00.1 is installed elevated and requires a longer ush pipe use the supplied Adaptor kit. To fabricate the required length see (Fig.A & B). The adaptor kit includes only the adaptor socket & spacer, the required 40mm DWV pipe & bend are not supplied. Note: With 40 mm DWV PVC pipe the supplied Geberit kee seals will seal 0.1 cm less than the maximum diameters stated on page 3 in section 10 of the 224.383.00.1 installation instructions. If the adaptor kit is used then the supplied black ush pipe bend and ush pipe are no longer required. Do not attempt to join these parts to PVC.

Adaptor supplied

40 DW V P V C Pipe not supplied

Hf

Push ush pipe adaptor over cistern spiggot. Allow for 3 cm clearance when ush pipe is adjusted to the required installation height Hf . This will also provide for an additional 1 cm adjustment (up or down) if required later on in the construction.

Outlet spigot 224.383 cistern

40 DWV PVC bend not supplied 40 DWV PVC Pipe connection to toilet not supplied g.A

Lubricate o- rings lubricant supplied

40 DWV PVC pipe work jointed this side

Adaptor Kit

Art.No.225.057.00.1

Install black spacer between PVC pipe and pipe bracket

Pipe bracket supplied with cistern

g. B

-4-

Geberit Installation Instruction


Further Installation Examples
The 224.383.00.1 cistern allows for greater exibility in the positioning of cistern and HyTronic actuator. See following installation examples. Conrm with the bathroom designer the required installation details or alternatively refer to product brochure. Provision for a sufciently sized removable service panel is strictly required.

Stud wall installation with rear access (for oor mounted wall faced pan)
Cavity depth 9 cm
Note all other installation dimensions and steps are as 2 to 10 on page 1 to 3. The only exception is to swivel ush pipe bend 180 .

Side view
9 45 85 55 465
7 5

Rear view
Brackets supplied
46-60

If cavity is deeper than 9 cm keep front part of the service opening ush with studs at the rear. Install a removable access panel centred over the service opening of the cistern. Minimum size W 28cm x H 14cm. If cavity is 9 cm deep keep back of cistern ush with front of stud wall.

Side view
9

103

Bathroom this side

Adjacent room this side, service opening this side (rear access).

Bathroom this side


8

45

59
7

16-29

16-29

Turn ush pipe bend to this side.

Hf

FFL

Hf

FFL

FFL Waste
Waste

Hf= Height of ush pipe, dimension to WC suppliers specication

Install hoses & hardware for Control Panel in preferred location: A, B or C


(see also HyTronic installation instructions)

View from Bathroom

View from Bathroom


B

View from Bathroom

or Left

A Right

Note: Children may have problems reaching the button.

C
Right or Left

FFL

FFL

HyTronic side mounted

HyTronic top mounted

HyTronic corner mounted

-5-

Geberit Installation Instruction


In-ceiling installation, separate ceiling access.
Side View
Cistern service opening

Front View
Water connection male

Ceiling Void

Service Panel or alternative access


Min. 90mm

Max. 3.5m

Use extension set Art. No. 117.041.00.1 where necessary (max. 3.3m)

PVC Adaptor Flush pipe 40mm DWV PVC (not provided)

Approx. 1m

Max.45 bend

Hf
FFL Waste

Hf

Hf= Height of ush pipe, dimension to WC suppliers specication order Art.No.813.362.00.1 with cistern

Brick wall installation (with oor mounted wall faced pan)

1
Removable access cover plate of panel has to be provided

Allow for sufcient block out for cistern installation


Use package tube Art. No: 225.056.00.1 (not supplied)

Fasten cistern and ush pipe to brick wall Install Styrofoam Packing Art.No. 813.362.00.1
Note: All other installation dimension are as per stud wall inst alla tion an d are Wastemeasured from the nished oor

FFL

0 Hf

Hf=Height of Flush pipe connection depends on the to toilet model.

Fill in space between cistern and wall

Fix rendering mesh

Render and tile

a Tape g

ps

Note:

All construction dimensions, material, methods and details shown are indicative only. The nal sizing, material used and construction methods must be determined by Project Architects, Builder, Engineer and local standard. This edition ; Date:27.8.2009; File name: supercedes all previous editions.