Company Business Zamil Air Conditioners was founded in 1974, and is the first major business venture in manufacturing sector for the Al Zamil group of Companies. It is also the first manufacturing unit for air conditioners to be established in Saudi Arabia. Zamil Air conditioners manufactures both consumer and central range of air conditioners and has sales operations in over 55 countries in the Middle East, Europe, America, Africa, Australia and the Far East. The companys operations are structured into four Strategic Business Units (SBUs) supporting six in - house product and service brands as well as a number of international brands under the OEM sales. The six in-house brands are Classic, Cooline, CoolCare, Clima Tech, Geoclima and Kessler Clima Tech. The four SBUs are: 1. Consumer Business unit supporting Classic, Cooline, GE and OEM brands for consumer range of air conditioners. 2. Unitary & Applied Business unit supporting Classic, Cooline, GE and OEM brands for commercial range of air conditioners. 3. Zamil CoolCare - service and maintenance provider. 4. Geoclima srl - independent business and supporting other SBUs for their requirement of Chillers & Double skin AHUs. The first three SBUs - Consumer Products, Unitary & Applied Products and Zamil CoolCare direct their business operations from the corporate headquarters at Dammam, Saudi Arabia. The production facilities at Dammam are shared by Consumer Products and Unitary & Applied Products. Geoclima has its own production and functional departments located at Monfalcone, Italy. All the four SBUs, while operating independently, supplement each others activities in a way that makes synergy work at its best and achieve the corporate goals of increased productivity and efficiently. Factories and Productions Zamil Air Conditioners has its prime manufacturing base at Dammam, Saudi Arabia and has one speciality production facility in Italy operated by Geoclima. The company can produce up to 440,000 room air conditioners, 60,000 mini-split systems and 36,500 central air-conditioning systems per year. Quality & Product Certificates The Quality systems and policies at Zamil Air Conditioners comply with the required ISO 9001:2000 certification. Zamil Air Conditioners is the first company in Saudi Arabia to receive the SASO (Saudi Arabias Standard Organization) certificate for room air conditioners. Its products and services are also certified with: 1. 2. 3. 4. 5. 6. CE (Council of European Community) UL (Underwriters Laboratory) AHAM certificate (Association of Home Appliance Manufacturers) Eurovent DEMKO ETL
Other awards include the prestigious Engineering Excellence Award of General Electric, and the inaugural Prince Mohammed bin Fahd Al Saud Award for Factory Safety. Our Products In addition to the consumer products such as the Room Air Conditioners (RAC) and the Mini Splits, Zamil Air Conditioners manufacturers a host of residential and commercial air conditioners. This board range extends from the concealed units up to 5 ton, the ducted splits up to 30 tons, the packaged units up to 70 tons. The single and double skin air handling units up to 130,000 CFM and the water chillers up to 487 ton cooling capacity.
INDEX
Contents Page
Model decoding ........................................................................................................................................ 2 Introduction ........................................................................................................................................... 3-5 Unit features, standard specifications & options .................................................................................... 6-9 Physical data ..................................................................................................................................... 10-11 Selection procedure .......................................................................................................................... 12-13 Ethylene glycol solution capacity correction ........................................................................................... 14 Performance data .............................................................................................................................. 15-18 Electrical data ......................................................................................................................................... 19 Water side pressure drop ....................................................................................................................... 20 Unit dimensions ................................................................................................................................ 21-22 Typical schematic wiring diagram ........................................................................................................... 23 Microprocessor controller ....................................................................................................................... 24 Application guidelines ........................................................................................................................ 25-29 Rigging instructions ................................................................................................................................ 30 Installation clearance .............................................................................................................................. 31 Mounting location ................................................................................................................................... 32 Load distribution ..................................................................................................................................... 33
CONTINUING RESEARCH RESULTS IN STEADY IMPROVEMENTS. THEREFORE, THESE SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT NOTICE.
MODEL DECODING
7 REFRIGERANT C : R-407c H : 208/230-3-60 A : ALUMINUM FIN B : PRE-COATED ALUMINUM FIN C : COPPER FIN (SEE NOTE # 1 BELOW) B : OPTIONAL ASME B : HGBP (OPTIONAL) STAMPED WITH VICTAULIC CONN.** A: COMPRESSOR CIRCUIT BREAKER A : STANDARD UNIT WITHOUT HGBP A : STANDARD WITH VICTAULIC CONN.* M: 380-3-60 (4 WIRE) F : 460-3-60 8 ELECTRICAL SUPPLY ( V-Ph-Hz ) 9 CONDENSER COIL SEE NOTE # 2 BELOW 10 CIRCUIT BREAKER 11 COOLER OPTIONS 13 & 14 OPTIONS & ACCESSORIES 12 HGBP OPTIONS
ALY
010
015
020
025
030
035
040
045
050
055
065
070
2
- UNIT DISCONNECT SWITCH - WATER FLOW SWITCH - SPRING ISOLATOR etc...
NOTES:
* NOT APPLICABLE FOR MODELS ALY010C TO ALY055C, MPT (MALE PIPE THREAD) CONNECTION ONLY.
2. COMPUTER SELECTED DIGITS (FROM 'AA' TO 'ZZ') DESCRIBING OTHER OPTIONS & ACCESSORIES OR COMBINATIONS THEREOF, SUCH AS: - CHILLER GUARD
INTRODUCTION
Zamil Air cooled scroll chillers (ALY series) are the heart of most central Air Conditioning systems for medium size buildings. They consist of one or more hermetic scroll compressors, air-cooled condenser coils with condenser fan(s) and motor(s), insulated liquid cooler, expansion device, interconnecting refrigerant piping, oil & refrigerant charge, control panel, wiring and other auxiliaries. ALY series, The new generation of air cooled packaged liquid chillers. ALY series air cooled scroll chillers are available in capacity range 10 TR (35 kW) to 70 TR (246 kW) at ARI conditions, in one single enclosure. Utilizing refrigerant R-407c as working fluid with option of three different power supply ratings. ALY series chillers have been designed and manufactured to meet the requirements of the Gulfs severe climatic conditions and specifically for outdoor installation, on roofs or ground level. ALY series are factory assembled, leak tested, evacuated, internally wired, fully charged with refrigerant. Each ALY series chillers are fully factory tested before delivery and are ready for installation. All that is required on site is to connect chilled water pipes and main power supply. ALY series chillers are rated in accordance with ARI-550/590.
Scroll Compressor:
The scroll compressors consist of two involutes or Archimedean spirals (Figure-1). One spiral is positioned inside the other to form a series of recent-shaped pockets. During compression the upper spiral remains stationary and the lower one, being eccentrically mounted on the drive shaft, describes an orbital rather than a simple rotary motion.
Compression in the scroll is created by the interaction of an orbiting spiral and a stationary spiral. A refrigerant enters the outer openings as one of the spirals orbits.
The open passages are sealed off as gas is drawn into the spiral.
As the spiral continues to orbit, the gas is compressed into two increasingly smaller pockets.
By the time the gas arrives at the center port, discharge pressure has been reached.
Actually, during operation, all six gas passages are in various stages of compression at all times, resulting in nearly continuous suction and discharge.
Refrigerant enters the compressor at the suction connection and flows around the motors housing and enters at the bottom side through the openings. Oil droplets separate from the refrigerant and fall into the oil sump. All suction refrigerant passes through the electrical motor, ensuring full motor cooling. After that the refrigerant enters the scroll elements.
COOLERS
Compact Design Shell and Tube Water Coolers: The DX shell and tube cooler with removable U shaped bundled tubes are made of internally grooved copper tubes expanded into heavy steel tubular sheets. The cooler housing and baffles are constructed steel and brass respectively. The coolers are insulated with heavy closed cellular foam insulation (3/4 thick). All coolers are fitted with vent, drain connection and Victaulic type water pipe connections as standard.
WATER SIDE UNIT MODEL COOLER
STD ASME (option) DESIGN PRESSURE, (BAR/PSIG) 16/235 10/147 TEST PRESSURE, (BAR/PSIG) 22.8/335 11.3/165
REFRIGERANT SIDE
DESIGN PRESSURE, (BAR/PSIG) 29/426 15.5/228 TEST PRESSURE, (BAR/PSIG) 41.5/610 23.3/342
FEATURES
These ALY series, packaged air cooled water chillers are designed to provide engineering excellence in comfort air conditioning and industrial cooling with a superior combination of energy saving, performance, application flexibility, ease of service & maintenance and withstanding extremely high ambient temperatures. These chillers incorporate a wide range of features including:
* * * * * * * * * * * *
Microprocessor controller, which monitors analog and digital inputs to achieve precise control & protective functions of the air cooled water chiller units. The microprocessor controller is complete with all the hardware and software necessary to control the chiller unit and ensures its efficiency and reliability. Compact unit design and excellent serviceability. All units incorporate separate subcooler circuit which is integral to the condenser surface. This additional subcooling circuit provides superior system performance. High Energy Efficiency Ratio (EER) hermetic scroll compressors. Single point power connection to minimize job site installation cost and time. Completely wired control panel with the advanced microprocessor controller that provides all the necessary operations and safety controls. Made ready connection for remote ON/OFF switch and General Alarm output. Independent refrigeration circuits. Compressor connections are Direct On Line (DOL) for all models (see electrical data). Low noise condenser fans, direct drive at 1000 RPM with rolled form venturi design to eliminate airflow recycling & short circuiting . All fans are die cast aluminum propeller type with aerodynamic design, top discharge, provided with protective grille mounted on top panel within the unit casing. All condenser fan motors are totally enclosed air over type (TEAO) with class ''F'' winding insulation.
STANDARD SPECIFICATIONS
CAPACITY CONTROL
The Zamil air cooled scroll water chillers incorporate stepped load shedding as required by most energy management systems. Modulation of capacity in response to system load requirements is affected by the microprocessor controller which monitors the leaving water temperature. Capacity control is achieved by cycling compressors ON/OFF and sequential operation of compressors which provides optimal part load capacities for chillers with multiple compressors. See the following table for the standard and optional capacity control for each unit.
MODEL NUMBER
ALY010C - ALY015C ALY020C - ALY040C ALY045C - ALY070C
OPTIONAL
100-HGBP-OFF 100-50-HGBP-OFF 100-75-50-25-HGBP-OFF
NOTES: 1. HGBP = Hot gas bypass available on lead compressor for all models (optional). 2. HGBP modulates to approximately 50% of compressor step capacity. Example: ALY045 with HGBP (25% x 0.5=12.5% minimum capacity).
6
CONDENSER COILS
Vertical & V-configurations condenser coils are corrugated fin and tube type, constructed of seamless 3/8" dia. & 0.014" (0.35 mm) thick copper tubes, mechanically bonded to aluminum fins for maximum heat transfer efficiency. As an option, copper fins or acrylic coated aluminum fins or other coated coils may be provided. The fins have full self spacing collars which completely cover each tube. The staggered tube design improves the thermal efficiency. End plates support sheets are 14 gauge galvanized steel, formed to provide structural strength. Each coil is pressure tested in the factory at not less than 450 psi air pressure.
CABINET
All units are of heavy gauge (G-90) galvanized steel. Steel sheet panels are zinc coated and galvanized by hot dip process of lock-forming quality conforming to ASTM A 653 commercial weight G-90 followed by backed on electrostatic polyester dry powder coat. Removable access panels are provided for easy maintenance purpose.
CONTROL PANEL
The control panel design is equivalent to NEMA 4 (IP55) with hinged door for easy access ensuring dust and weatherproof construction. Internal power and control wiring is neatly routed, adequately anchored and all wires identified with cable markers as per NEC standards applicable to HVAC industry. The electrical controls used in the control panel are UL approved and are reliable in operation at high ambient conditions for a long period.
MICROPROCESSOR CONTROLLER
A new compact electronic controller with a complete management for air cooled water chiller control capability. This controller manages the analog and digital inputs to achieve precise operation and safety function of the chiller unit. A user friendly display interface allows to access the operating condition, control set point & alarm of the unit that are clearly visible on its 3 digits display board. The controller is equipped with a compressor rotation operation to allow the compressor running hours to be balanced. The controller has feasibility to be connected to a supervisor network via RS485 serial line for Remote Monitoring and Remote configuration of the unit parameters. The controller consists of the following hardware: 1. Control board - complete control of function and safety operation of one compressor. 2. Aux. Board - Expansion Board to control 2 or more compressor. 3. Remote Monitoring System (optional) - Remote Monitoring & Configuration of the unit. 4. User interface Board/Remote Terminal (optional) - Provided with a simple to use push button to access the operating condition, control set point and alarm of the unit. Access of the following status on the display: 1. Water inlet / Outlet Temperature 2. Compressor Status 3. Fan Status 4. Alarms 5. SI or English Unit System protection: 1. Compressor Winding High Temperature / Overloading 2. Low / High Pressure 3. Freeze Protection 4. Sensor Error 5. Time Delay - Anti recycle time for compressor 6. No Water Flow or Trip Pump condition
CONDENSER FANS
Condenser fans are constructed of die cast aluminum blades/hubs with direct driven motors. All fans are statically and dynamically balanced to operate at minimum noise and vibration. Fan blades are designed with appropriate pitch angle which result in maximum airflow through the condenser coil.
STANDARD ACCESSORIES
UNIT ON-OFF SWITCH: ON-OFF switch is provided for manually switching the unit control circuit. INDICATOR LIGHTS: LED lights indicates power ON to the units, MENU adjustment and FAULT indications due to trip on safety devices. THERMAL EXPANSION VALVE: Thermal expansion valve is used to regulate the refrigerant flow to the water cooler and maintain a constant superheat. REPLACEABLE FILTER DRIER: Refrigerant circuits are kept free of harmful moisture, sludge, acids and oil contaminating particles by the filter drier. CONTROL CIRCUIT TRANSFORMER: A factory mounted and wired control circuit transformer is furnished eliminating the need for running a separate 220 volt power supply to the unit control circuit. SIGHT GLASS: A moisture indicating sight glass installed in the liquid line. An easy-to-read color indicator shows moisture contents and provides a mean for checking the system refrigerant charge. LIQUID LINE SOLENOID VALVE: Closes when the compressor is off to prevent any liquid refrigerant from accumulating in the water cooler during the off cycle.
8
OPTIONS
HOT GAS BYPASS SYSTEM: Hot gas bypass is provided on the lead circuit to permit operation of the system down to 50% of its unloaded capacity. Under low ambient condition, it controls temperature by eliminating the need to cycle the compressor on and off, ensuring narrow temperature swing and lengthen the life span of the compressor. WATER FLOW SWITCH: Paddle type field adjustable flow switch for water cooler circuits. Interlock into unit safety circuits so that the unit will remain off until water flow is determine. SUCTION AND DISCHARGE VALVES: To isolate the compressor in order to facilitate servicing or compressor replacement. UNIT MOUNT SPRING ISOLATORS: These housed spring assemblies have a neoprene friction pad on the bottom to prevent vibration transmission. LIQUID COOLERS: ASME code stamped liquid cooler (for models ALY040C to ALY070C only). PRESSURE GAUGES: Suction & discharge pressures gauges. SAFETY VALVE: This valve protects the unit against high discharge pressure in the system due to malfunction of high pressure switches. NON-FUSED MAIN DISCONNECT SWITCHES: To disconnect power supply of the unit for servicing and repair works. This as well equipped with door interlock device. CHILLER GUARD: Protect the condenser, cooler & compressor from vandalism. COOLER HEATER WRAPPED: Prevent freezing up of water on low ambient temperature. COPPER FINS/TUBES CONDENSER COILS: For seashore salty corrosive environments. COATED COPPER OR ALUMINUM FINS/TUBES CONDENSER COILS: For seashore salty corrosive environments. BMS: BACNET, MODBUS, LON works and remote monitoring display.
PHYSICAL DATA
UNIT SIZE ALY010C ALY015C ALY020C ALY025C ALY030C ALY035C
COMPRESSOR
PART NUMBER 208/230V-3Ph-60Hz 380V-3Ph-60Hz 460V-3Ph-60Hz NUMBER OF COMPRESSORS OIL CHARGE PER COMPRESSOR, Liters % FULL LOAD CAPACITY CONTROL MOTOR OVERLOAD PROTECTION (INTERNAL) OIL LUBRICATION REFRIGERANT EXPANSION VALVE DEVICE CONTROL VOLTAGE
800-692-00 800-692-01 800-692-02 800-692-06 800-692-07 800-692-08 800-692-00 (2) 800-692-01 (2) 800-692-02 (2) 800-692-06 800-692-03 800-692-07 800-692-04 800-692-08 800-692-05 800-692-06 (2) 800-692-07 (2) 800-692-08 (2) 800-692-09 (2) 800-692-10 (2) 800-692-11 (2)
1 3.125 100-0
1 3.977 100-0
2 3.125 100-50-0
2 3.977/3.125 100-50-0
2 3.977 100-50-0
2 4.489 100-50-0
CONDENSER
CONDENSER COIL Tube Dia.- Rows - Fins per inch Total face area, Sq. ft. AIRFLOW, CFM NUMBER OF FAN/FAN DIA.,mm FAN MOTOR RPM @ 230/380/460-3-60 3/8314 13.9 10529 1/800 3/8314 27.8 13251 1/800 3/8214 44.4 26538 2/800 3/8314 44.4 25170 2/800 3/8314 44.4 25170 2/800 3/8414 44.4 23950 2/800
COOLER
COOLER PART NUMBER SHELL DIAMETER, mm LENGTH, mm TOTAL WATER HOLDING VOLUME, Liters WATER IN/OUT PIPE DIA.mm 800-516-39 N.A. N.A. N.A. 38 800-516-39 N.A. N.A. N.A. 38 800-620-07 168 1281 15.3 64 800-620-09 168 1431 17.2 64 800-620-11 168 1631 19.8 64 800-620-13 168 1781 21.7 64
GENERAL
REFRIGERANT CHARGE PER COMP., kg (COMP. 1/2) SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg SHIPPING /OPERATING WEIGHTS (Copper coils), kg NOTES: 8 68.9/65.4/60.1 416/426 447/457 12 66.7/63.2/57.9 506/516 568/578 8 71.9/68.4/63.1 795/810 858/873 12/10 69.2/65.7/60.4 889/906 986/1003 12 69.7/66.2/60.9 949/969 1047/1067 14 72.6/69.1/63.8 1049/1071 1191/1213
1. All compressors operate at 3500 RPM @ 60Hz. 2. Sound pressure level : 2dBA.
10
PHYSICAL DATA
UNIT SIZE ALY040C ALY045C ALY050C ALY055C ALY065C ALY070C
COMPRESSOR
PART NUMBER 208/230V-3Ph-60Hz 380V-3Ph-60Hz 460V-3Ph-60Hz NUMBER OF COMPRESSORS OIL CHARGE PER COMPRESSOR, Liters % FULL LOAD CAPACITY CONTROL MOTOR OVERLOAD PROTECTION (INTERNAL) OIL LUBRICATION REFRIGERANT EXPANSION VALVE DEVICE CONTROL VOLTAGE
800-692-12 (2) 800-692-13 (2) 800-692-14 (2) 800-692-03 (4) 800-692-04 (4) 800-692-05 (4) 800-692-06 (2) 800-692-03 (2) 800-692-07 (2) 800-692-04 (2) 800-692-08 (2) 800-692-05 (2) 800-692-06 (4) 800-692-07 (4) 800-692-08 (4) 800-692-09 (2) 800-692-06 (2) 800-692-10 (2) 800-692-07 (2) 800-692-11 (2) 800-692-08 (2) 800-692-09 (4) 800-692-10 (4) 800-692-11 (4)
2 5.682 100-50-0
4 3.125
4 3.977/3.125
4 3.977
4 4.489/3.977
4 4.489
100-75-50-25-0 100-75-50-25-0 100-75-50-25-0 100-75-50-25-0 100-75-50-25-0 ELECTRONIC CENTRIFUGAL ACTION R-407c THERMOSTATIC 220V-1Ph-60Hz
CONDENSER
CONDENSER COIL Tube Dia.- Rows - Fins per inch Total face area, Sq. ft. AIRFLOW, CFM NUMBER OF FAN/FAN DIA.,mm FAN MOTOR RPM @ 230/380/460-3-60 3/8314 88.9 26000 4/762 3/8314 88.9 50340 4/800 3/8314 88.9 50340 4/800 3/8314 88.9 50340 4/800
3/8414 3/8314
COOLER
COOLER PART NUMBER SHELL DIAMETER, mm LENGTH, mm TOTAL WATER HOLDING VOLUME, Liters WATER IN/OUT PIPE DIA.mm 800-620-15 194 1815 30 75 800-695-06 194 1815 30 75 800-620-82 219 1820 41.8 75 800-620-82 219 1820 41.8 75 800-620-86 273 1850 62.7 100 800-620-86 273 1850 62.7 100
GENERAL
REFRIGERANT CHARGE PER COMP., kg (COMP. 1/2) SOUND PRESSURE LEVEL, dBA (3m./5m./10m.) SHIPPING /OPERATING WEIGHTS (Aluminum coils), kg SHIPPING /OPERATING WEIGHTS (Copper coils), kg NOTES: 17 74.9/71.4/66.1 1541/1571 1737/1767 10 71.6/68.1/62.8 1571/1601 1766/1796 12/10 72.2/68.7/63.4 1728/1770 1924/1966 12 72.7/69.2/63.9 1845/1887 2040/2082 14/12 74.4/70.9/65.6 2013/2076 2253/2316 14 75.6/72.1/66.8 2108/2171 2392/2455
1. All compressors operate at 3500 RPM @ 60Hz. 2. Sound pressure level : 2dBA.
11
TABLE - 1
POWER ARI FOULING CAPACITY CORRECTION INPUT STANDARDS 2 0 FACTOR (HR-FT - F/BTU) FACTOR FACTOR
0.00010 0.00025 0.00050 0.00075 0.00100 1.000 0.992 0.978 0.965 0.951 1.000 0.997 0.990 0.984 0.978 ARI-550/590-98 ARI-590-86 ARI-590-81
TABLE - 2
STEP-1: UNIT SELECTION Entering the capacity performance data at given LCWT and ambient temperature. ALY035 chiller unit at sea level will produce 35.1 tons and 36.9 kW compressor power input at 440F leaving chilled water temperature with 100F water temperature difference and 950F ambient temperature. For the conditions required, the unit actual cooling capacity when corrected for altitude (0.99) and fouling factor (1.0). Capacity = 35.1x0.99x1.0 = 34.7 Tons, which then exceeds the requirements. So the selection is correct. STEP-2: CHILLED WATER FLOW (GPM): Water GPM = Required capacity (Tons) x 24 = 33 x 24 = 79.2 GPM
10
15
20
TABLE - 3
Cooling Range, T 100F Referring to pressure drop chart (page # 20), pressure drop at 79.2 GPM = 18.9 ft. of water for selected model. STEP-3: ELECTRICAL Refer to electrical data at 380V-3Ph-60Hz, the main power wire size for ALY035 is to be sized at a minimum circuit ampacity (MCA) of 92 Amps and the main branch protection device is to be sized at a maximum over current protection (MOCP) of 129 Amps. STEP-4: CHILLED WATER PUMP SELECTION For chilled water pump selection, add all pressure drop in the closed chilled water loop piping to the pressure drop calculated in step 2. STEP-5: LCWT CORRECTION Refer to table-3: Add correction factor to design leaving chilled water temperature (LCWT) when chilled water temperature range is above 100F and subtract correction from design leaving chilled water temperature (LCWT) when water temperature range is below 100F. EXAMPLE: If LCWT rise is 12.50F, enter correction curve at 12.50F and read the correction factor of 0.2. The corrected LCWT is 44+0.2 = 44.20F. NOTE: 1. When the chilled water temperature rise is less than 50F, the high water flow rate will result to excessive pressure drop. In such cases, contact factory for special selection of a cooler with wider baffle spacing. 2.Please refer to water pressure drop curves.
12
TABLE - 1
POWER ARI FOULING CAPACITY CORRECTION INPUT STANDARDS FACTOR (M2-0C/W) FACTOR FACTOR
0.000018 0.000044 0.000088 0.000132 0.000176 1.000 0.992 0.978 0.965 0.951 1.000 0.997 0.990 0.984 0.978 ARI-550/590-98 ARI-590-86 ARI-590-81
TABLE - 2
STEP-1: UNIT SELECTION Entering the capacity performance data at given LCWT and ambient temperature. ALY035 chiller unit at sea level will produce 121 kW and 36.7 kW compressor power input at 60C leaving chilled water temperature with 60C water temperature difference and 350C ambient temperature. For the conditions required, the unit actual cooling capacity when corrected for altitude (0.99) and fouling factor (1.0). Capacity = 121x0.99x1.0 = 119.8 kW, which then exceeds the requirements. So the selection is correct. STEP-2: CHILLED WATER FLOW (LPS): Water LPS = Required capacity (kW) x 0.239 Cooling Range, T = 118 x 0.239 60C = 4.7 LPS
10
TABLE - 3
Referring to pressure drop chart (page # 20), pressure drop 4.7 LPS = 52 kPa for selected model. STEP-3: ELECTRICAL Refer to electrical data at 380V-3Ph-60Hz, the main power wire size for ALY035 is to be sized at a minimum circuit ampacity (MCA) of 92 Amps and the main branch protection device is to be sized at a maximum over current protection (MOCP) of 129 Amps. STEP-4: CHILLED WATER PUMP SELECTION For chilled water pump selection, add all pressure drop in the closed chilled water loop piping to the pressure drop calculated in step 2. STEP-5: LCWT CORRECTION Refer to table-3: Add correction factor to design leaving chilled water temperature (LCWT) when chilled water temperature range is above 60C and subtract correction from design leaving chilled water temperature (LCWT) when water temperature range is below 60C. EXAMPLE: If LCWT rise is 7.40C, enter correction curve at 7.40C and read the correction factor of 0.11. The corrected LCWT is 60C+0.11 = 6.110C. NOTE: 1. When the chilled water temperature rise is less than 30C, the high water flow rate will result to excessive pressure drop. In such cases, contact factory for special selection of a cooler with wider baffle spacing. 2.Please refer to water pressure drop curves.
13
0%
00C (320F) 8.30C (470F) 1.0 1.0 1.0
12%
-50C (230F) 3.30C (380F) 0.985 1.02 1.07
22%
-100C (140F) -1.70C (290F) 0.980 1.04 1.11
30%
-150C (50F) -6.70C (200F) 0.974 1.075 1.18
EXAMPLE: English system- Determine Ethylene glycol percentage by weight and correction factors at 380F ambient temperature. From the above table, Ethylene glycol water solution concentration (percentage by weight) corresponding to 380F ambient temperature is 12% by weight. Find the correction factors corresponding to 380F ambient temperature from the table. Cooling capacity correction factor is 0.985, Flow correction factor is 1.02, Pressure drop correction factor is 1.07. Apply these correction factors for corrected system performance values. TONS (E.G. SOLUTION) = Tons (water) x Cooling capacity correction factor. BRINE (E.G. SOLUTION) FLOW (GPM) = Flow (water) x Flow correction factor. BRINE (E.G. SOLUTION) PRESSURE DROP = Water pressure drop (Ft.) x Pressure drop correction factor. EXAMPLE: Metric system- Determine Ethylene glycol percentage by weight and correction factors where 3.30C ambient temperature. From the above table, Ethylene glycol water solution concentration (percentage by weight) corresponding to 3.30C ambient temperature is 12% by weight. Find the correction factors corresponding to 3.30C ambient temperature from the table. Cooling capacity correction factor is 0.985, Flow correction factor is 1.02, Pressure drop correction factor is 1.07. Apply these correction factors for corrected system performance values. KW (E.G. SOLUTION) = KW (water) x Cooling capacity correction factor. BRINE (E.G. SOLUTION) FLOW (L/S) = KW (water) x Flow correction factor. BRINE (E.G. SOLUTION) PRESSURE DROP = Water pressure drop (kPa) x Pressure drop correction factor. Note: Correction factors apply to published chilled water performance rating from 400F to 500F (4.40C to 100C) LCWT.
14
1050F AMBIENT TEMPERATURE CAP. (Tons) EER EER EER COMP. kW WATER FLOW (GPM) CAP. (Tons) COMP. kW CAP. (Tons) COMP. kW WATER FLOW (GPM) WATER FLOW (GPM)
UNIT SIZE
CAP. (Tons)
ALY 010C
9.1
ALY 015C
13.1
17.9 23.9
ALY 030C
26.2
40 F
ALY 035C
32.2
ALY 040C
39.2
ALY 045C
43.2
45.8 49.2
ALY 065C
59.7
ALY 070C
65.5
ALY 010C
9.5
ALY 015C
13.7
19.0 25.0
ALY 030C
27.2
42 F
ALY 035C
33.7
40.8 45.1
47.4 50.7
15
28.3 36.9 44.5 45.2 50.8 56.4 65.8 74.4 10.5 171.9 67.0 84.6 8.7 10.6 10.4 10.7 124.3 133.7 157.0 48.8 52.6 61.5 57.2 63.8 74.5 9.0 8.8 9.0 117.2 126.3 147.6 160.9 10.6 10.3 10.4 10.6 67.8 84.1 101.3 112.1 26.6 32.7 39.7 44.0 32.0 42.0 50.0 50.7 8.9 8.6 8.8 9.0 63.9 78.5 95.2 105.5 25.0 30.1 36.9 41.2 45.8 49.5 57.3 61.9
44 0F
ALY 070C
71.6
LEGEND:
NOTES: 1. Packaged chillers are rated with ARI standard 550/590. 2. Performance data are based on 100F water range in evaporator. 3. Ratings are based on 0.00010 (hr-ft2-0F/Btu) fouling factor for evaporator. 4. Direct interpolation is permissible. Do not extrapolate. 5. kW power input is for compressor only. 6. EER for entire unit. Refer to electrical data for fan kW.
kW
GPM
EER
1050F AMBIENT TEMPERATURE CAP. (Tons) CAP. (Tons) CAP. (Tons) EER COMP. kW
8.9 13.1 17.6 23.6 25.9 31.3 38.4 42.8 47.8 51.7 58.8 63.6 9.2 13.5 18.7 24.7 27.0 32.6 40.0 44.7 49.2 53.2 59.8 64.9 9.4 13.8 19.2 25.5 85.6 97.6 12.3 65.5 73.4 57.5 57.9 48.9 36.8 24.2 32.8 17.8 12.3 97.1 85.2 65.0 72.9 57.3 56.8 48.4 36.5 23.9 32.4 17.7 12.2
1150F AMBIENT TEMPERATURE COMP. kW WATER FLOW (GPM) WATER FLOW (GPM)
CAP. (Tons)
ALY 010C
10.2
ALY 015C
14.8
20.4 26.7
ALY 030C
29.3
46 F
ALY 035C
36.4
ALY 040C
43.8
ALY 045C
48.5
54.2 58.5
ALY 065C
67.3
ALY 070C
73.7
ALY 010C
10.4
ALY 015C
15.2
21.1 28.0
ALY 030C
30.5
48 F
ALY 035C
37.8
45.6 50.6
55.9 60.4
16
29.3 38.3 46.3 46.5 52.4 58.3 67.1 76.2 11.0 184.4 71.8 86.4 9.2 11.7 11.5 11.2 140.6 151.6 167.9 55.2 59.5 65.6 59.0 65.8 75.9 9.9 9.7 9.4 132.4 142.9 157.5 172.3 11.6 11.1 11.1 11.6 77.2 93.6 113.2 126.0 30.3 36.4 44.3 49.4 33.1 43.4 51.8 52.2 9.9 9.3 9.5 9.9 72.8 87.4 106.4 118.7 28.4 33.5 41.3 46.3 51.7 55.8 60.9 66.2
50 0F
ALY 070C
76.8
LEGEND:
NOTES: 1. Packaged chillers are rated with ARI standard 550/590. 2. Performance data are based on 100F water range in evaporator. 3. Ratings are based on 0.00010 (hr-ft2-0F/Btu) fouling factor for evaporator. 4. Direct interpolation is permissible. Do not extrapolate. 5. kW power input is for compressor only. 6. EER for entire unit. Refer to electrical data for fan kW.
kW
GPM
EER
400C AMBIENT TEMPERATURE CAP. (kW) COP COP COP COMP. kW WATER FLOW (LPS) CAP. (kW) COMP. kW CAP. (kW) COMP. kW WATER FLOW (LPS) WATER FLOW (LPS)
UNIT SIZE
CAP. (kW)
ALY 010C
31.4
ALY 015C
45.7
58.4 80.9
ALY 030C
91.3
4 C
ALY 035C
110.7
ALY 040C
134.9
ALY 045C
148.6
165.9 178.7
ALY 065C
207.3
ALY 070C
227.5
ALY 010C
32.8
ALY 015C
47.3
65.6 86.8
ALY 030C
94.0
5 0C
ALY 035C
116.6
141.4 156.2
161.5 173.1
17
28.2 36.7 44.2 45.0 50.3 55.8 65.4 74.0 3.0 9.9 233.2 83.0 2.6 3.0 3.0 3.1 7.0 7.5 9.0 165.6 178.1 213.8 56.0 62.4 73.2 2.6 2.5 2.6 6.6 7.1 8.5 9.3 3.0 3.0 3.0 3.1 3.9 4.8 5.8 6.4 92.4 113.7 138.0 152.9 31.5 41.2 49.2 50.0 2.6 2.5 2.6 2.7 3.7 4.5 5.5 6.1 86.3 104.0 127.7 142.4 155.1 167.2 198.2 214.1
6 0C
ALY 070C
247.4
LEGEND:
NOTES: 1. Packaged chillers are rated with ARI standard 550/590. 2. Performance data are based on 60C water range in evaporator. 3. Ratings are based on 0.000018 (m2 -0C/W) fouling factor for evaporator. 4. Direct interpolation is permissible. Do not extrapolate. 5. kW power input is for compressor only. 6. COP for entire unit. Refer to electrical data for fan kW.
kW
LPS
COP
- Coefficient of Performance
400C AMBIENT TEMPERATURE CAP. (kW) COP COP COP COMP. kW WATER FLOW (LPS) CAP. (kW) COMP. kW CAP. (kW) COMP. kW WATER FLOW (LPS) WATER FLOW (LPS)
UNIT SIZE
CAP. (kW)
ALY 010C
35.4
ALY 015C
50.9
69.9 91.8
ALY 030C
100.9
7 C
ALY 035C
125.2
ALY 040C
150.6
ALY 045C
166.7
186.1 200.5
ALY 065C
233.4
ALY 070C
255.7
ALY 010C
36.2
ALY 015C
52.5
72.4 95.2
ALY 030C
104.3
8 0C
ALY 035C
129.6
155.8 172.7
192.5 207.8
18
29.3 38.3 46.4 46.6 52.5 58.4 67.2 76.3 3.2 10.8 255.2 85.4 2.7 3.4 3.4 3.3 8.2 8.9 9.8 195.9 211.3 233.1 58.3 65.1 75.1 3.0 2.9 2.8 7.8 8.4 9.3 10.2 3.4 3.3 3.3 3.4 4.5 5.5 6.6 7.4 107.6 129.4 157.4 175.6 32.7 42.9 51.3 51.6 3.0 2.8 2.8 3.0 4.3 5.2 6.3 7.0 100.3 118.5 145.9 163.7 182.4 197.0 215.3 233.8
10 0C
ALY 070C
271.2
LEGEND:
NOTES: 1. Packaged chillers are rated with ARI standard 550/590. 2. Performance data are based on 60C water range in evaporator. 3. Ratings are based on 0.000018 (m2 -0C/W) fouling factor for evaporator. 4. Direct interpolation is permissible. Do not extrapolate. 5. kW power input is for compressor only. 6. COP for entire unit. Refer to electrical data for fan kW.
kW
LPS
COP
- Coefficient of Performance
ELECTRICAL DATA
COMPRESSOR TYPE-1 CRANKCASE HEATER Volts Qty. FCA COMPRESSOR TYPE-2 CONDENSER FAN MOTORS Max.
UNIT SIZE
SUPPLY VOLTAGE
Min.
ALY010C
ALY015C
ALY020C
ALY025C
ALY030C
ALY035C
ALY040C
19
NOTES: 4. All field wiring must be in accordance with NEC and local standards. 6. Neutral line required on 380V-3Ph-60Hz power supply only.
ALY045C
ALY050C
ALY055C
ALY065C
ALY070C
Nominal (V-Ph-Hz) 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 208/230-3-60 380-3-60 460-3-60 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 253 418 506 CB CB RLA LRA MCA MOCP Qty. (each) (each) Poles MTA Qty. 48 81 1 33.3 239 3 53 1 29 49 1 20.1 145 3 32 1 24 41 1 16.6 125 3 27 1 66 115 1 48.3 425 3 77 1 40 69 1 29.2 239 3 47 1 34 58 1 24.1 187 3 39 1 87 120 2 33.3 239 3 53 2 52 72 2 20.1 145 3 32 2 44 61 2 16.6 125 3 27 2 73 121 1 48.3 425 3 77 1 44 73 1 29.2 239 3 47 1 37 61 1 24.1 187 3 39 1 121 169 2 48.3 425 3 77 2 73 102 2 29.2 239 3 47 2 61 85 2 24.1 187 3 39 2 165 233 2 67.8 505 3 108 2 92 129 2 37.6 280 3 60 2 77 108 2 31.1 225 3 50 2 188 262 2 74.4 500 3 119 2 113 158 2 45.0 305 3 72 2 95 132 2 37.2 250 3 60 2 179 216 4 36.4 245 3 58 4 108 130 4 22.0 145 3 35 4 91 110 4 18.2 125 3 29 4 206 254 2 48.3 425 3 77 2 124 153 2 29.2 239 3 47 2 105 129 2 24.1 187 3 39 2 230 278 4 48.3 425 3 77 4 138 167 4 29.2 239 3 47 4 116 141 4 24.1 187 3 39 4 274 341 2 67.8 505 3 108 2 157 195 2 37.6 280 3 60 2 132 163 2 31.1 225 3 50 2 313 380 4 67.8 505 3 108 4 174 211 4 37.6 280 3 60 4 146 177 4 31.1 225 3 50 4 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 FLA (each) 6.1 3.5 3.5 6.1 3.5 3.5 6.1 3.5 3.5 6.1 3.5 3.5 6.1 3.5 3.5 6.1 3.5 3.5 5.1 2.9 2.8 6.1 3.5 3.5 6.1 3.5 3.5 6.1 3.5 3.5 6.1 3.5 3.5 6.1 3.5 3.5 6.1 3.52 3.5 6.1 3.52 3.5 12.2 7.04 7 12.2 7.04 7 12.2 7.04 7 12.2 7.04 7 20.2 11.72 11.12 24.4 14.08 14 24.4 14.08 14 24.4 14.08 14 24.4 14.08 14 24.4 14.08 14 CB (Qty.) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 2 230 380 460 230 380 460 230 380 460 230 380 460 230 380 460 230 380 460 230 380 460 230 380 460 230 380 460 230 380 460 230 380 460 230 380 460 Total Watts 90 61 90 70 45 70 180 122 180 160 135 160 140 90 140 240 240 240 300 300 300 360 360 360 320 270 320 280 180 280 380 330 380 480 480 480 Total Amps 0.39 0.16 0.20 0.30 0.12 0.15 0.78 0.32 0.39 0.70 0.36 0.35 0.61 0.24 0.30 1.04 0.63 0.52 1.30 0.79 0.65 1.57 0.95 0.78 1.39 0.71 0.70 1.22 0.47 0.61 1.65 0.87 0.83 2.09 1.26 1.04 Total kW 1.91 1.91 2.10 1.91 1.91 2.10 3.82 3.82 4.20 3.82 3.82 4.20 3.82 3.82 4.20 3.82 3.82 4.20 4.40 4.40 4.40 7.64 7.64 8.40 7.64 7.64 8.40 7.64 7.64 8.40 7.64 7.64 8.40 7.64 7.64 8.40 CB CB RLA LRA Qty. (each) (each) Poles MTA Qty. 1 36.4 245 3 58 1 1 22.0 145 3 35 1 1 18.2 125 3 29 1 2 36.4 245 3 58 2 2 22.0 145 3 35 2 2 18.2 125 3 29 2 2 48.3 425 3 77 2 2 29.2 239 3 47 2 2 24.1 187 3 39 2 -
187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414 187 342 414
1. Main power must be supplied from a single field supplied and mounted fused disconnects, using dual element time delay fuse or circuit breaker. 2. The maximum incoming wire size is 500 mcm. On units having MCA greater than the ampacity of 500 mcm wire, the factory supplied power terminal block will accept two parallel field wires per phase. 3. The compressor crankcase heaters must be energized for 12 hours before the unit is initially started or after a prolonged power disconnection. 5. Minimum and maximum unit supply voltages are shown in the tabulated data above (see also note # 7). 7. The 10% voltage variation from the nominal is allowed for a short time only, not permanent.
LEGEND: MCA - Minimum Circuit Ampacity per NEC 430-24 MOCP - Maximum Over Current Protection RLA - Rated Load Amps LRA - Locked Rotor Amps CB - Circuit Breaker MTA - Must Trip Amps FLA - Full Load Amps FCA - Total Fan Circuit Amps
1
60 70 80 90 100
234
6 7
8 9 10
20
30
40
50
10
20
30
40
50
60
70
80
90 100
200
300
400
500
1500
CONVERSION FACTOR: GPM = 0.063 Liters per second. Feet of water = 2.989 Kilo Pascal (kpa). NOTE: If an application requires certain water flow rate outside these limits, please check with your nearest dealer/sales office.
20
DIMENSIONS
ALY010C & ALY015C
DIMENSIONS
MODEL ALY010C A 466 393 B 144 217 C 318 206
275
1245
1025
ALY015C
1640
DIMENSIONS
MODEL ALY020C ALY025C
1335
ALY030C ALY035C
275
235
A 2287
21
246
2000
DIMENSIONS
ALY040C
100
2675
1530 2287
220
260
DIMENSIONS
MODEL ALY045C ALY050C ALY055C ALY065C ALY070C
2675
275
260
A 2287
220
22
2000
2000
COMP 1
CONTROL PANEL
FAN1
B1/B2 C1/C2 CB COMP CC CCA CWP D1/ID.. ETB FLS FM FMC F G/GO HPS HVTB MB NO1/1O S1 SB SSPS SH TK tLAN TRANS UVM ---
ANALOG INPUT COMMON CIRCUIT BREAKER COMPRESSOR COMPRESSOR CONTACTOR COMPRESSOR CONTACTOR AUXILIARY CHILLED WATER PUMP DIGITAL INPUT 1 EARTH TERMINAL BLOCK FLOW SWITCH FAN MOTOR FAN MOTOR CONTACTOR FUSE POWER INPUT HIGH PRESSURE SWITCH HIGH VOLTAGE TERMINAL BLOCK MASTER BOARD DIGITAL OUT 1 CONTROL SWITCH SLAVE BOARD SOLID STATE PROTECTION SYSTEM SHIELD CONDENSER FAN THERMAL CONTACT LOCAL NETWORK PORT TRANSFORMER UNDER VOLTAGE MONITOR TERMINAL BLOCK FIELD WIRING FIELD SUPPLY
NOTES
1. POWER SUPPLY, REFER TO UNIT NAMEPLATE. 2. FUSES TO BE DUAL ELEMENT TYPE. 3. USE COPPER CONDUCTORS ONLY. 4. ALL FIELD WIRING TO COMPLY WITH LOCAL CODES. 5. FUSED DISCONNECT SWITCH OR CIRCUIT BREAKER TO BE PROVIDED BY END USER WITH RATING AS RECOMMENDED BY MANUFACTURER. 6. POWER MUST BE SUPPLIED TO CRANKCASE HEATER FOR MINIMUM OF 12 HOURS PRIOR TO SYSTEM START UP. IF POWER IS OFF 6 HOURS OR MORE, CRANKCASE HEATER MUST BE ON FOR 12 HOURS BEFORE OPERATING THE SYSTEM. FAILURE TO FOLLOW THESE INSTRUCTIONS MAY RESULT IN COMPRESSOR DAMAGE. 7. NEUTRAL LINE REQUIRED ON 380V-3Ph-60Hz POWER SUPPLY ONLY.
23
MICROPROCESSOR CONTROLLER
CONTROLLER SEQUENCE OF OPERATION
For initial start-up, the following condition must be met: All power supplied to the unit shall be continuously energized for 12 hours.
All safety conditions are satisfied. Chilled water pump is running normal and chilled water flow switch contact is closed. Customer control or remote ON/OFF is switch to run mode, if any.
Staging ON and OFF sequence is accomplished based on controlled water temperature. The controller works to maintain the required demand as constant as possible. Below sequence of operation belongs to chiller unit with 2 scroll compressors. For 4 scroll compressors chiller unit the operation will be the same. Only that the capacity change to 25% per compressor. For single scroll compressor unit the capacity change to 100%.
FAN - ON/OFF
The fan will switch ON & OFF together with the compressor ON and OFF operation respectively.
24
APPLICATION GUIDELINES
INTRODUCTION
These guidelines should be considered when designing systems and their installation utilizing Zamil ALY series liquid chillers. Stable operation, performance and reliability of units is often dependent upon proper compliance with these recommendations. When any application varies from these guidelines, it should be referred with Zamil Air Conditioners for specific recommendations.
UNIT SELECTION/SIZING
Unit selection procedure and capacities are provided in this catalog for proper selection. The Zamil electronic selection program may also be utilized for this purpose. Over sizing chillers beyond a maximum limit of 5 10 % in order to assure adequate capacity or considering future expansions is not recommended. Over sizing adversely affects the operating efficiency due to erratic system operation and excessive compressor cycling which also results in reduced compressor life. It should be noted that, units operate more efficiently when fully loaded rather than larger equipment operating at partial capacities. In addition, an oversized unit is usually more costly to purchase, install and operate.
26
The units longitudinal axis should be parallel to the prevailing wind direction in order to ensure a balanced air flow
through the condenser coils. Consideration should also be given to the possibility of down-drafts caused by adjacent buildings, which may cause recirculation or uneven unit airflow. For locations where significant cross winds are expected, an enclosure of solid or louver type is recommended to prevent wind turbulence interfering with the unit airflow. When units are installed in an enclosure, the enclosure height should not exceed the height of the unit.
The location should be selected for minimum sun exposure and away from hot air sources, steam, exhaust vents and
sources of airborne chemicals that could attack the condenser coils and steel parts of the unit. Avoid locations where the sound output and air discharge from the units may be objectionable.
If the location is an area which is accessible to unauthorized persons, steps must be taken to prevent access to the unit
by means of a protective fence. This will help to prevent the possibility of vandalism, accidental damage or possible harm caused by unauthorized removal of panels or protective guards exposing rotating or high voltage components.
The unit must be installed on a ONE-PIECE, FLAT and LEVELLED {within 1/2'' (13 mm) over its length and width} /
CONCRETE BASE that extends fully to support the unit. The carrying or supporting structure should be capable of handling complete operating weight of the unit as given in the Physical Data tables in this Catalog.
For ground level installations, it must be ensured that the concrete base is stable and does not settle or dislocate upon
installation of the unit which can strain the refrigerant lines resulting in leaks and may also cause compressor oil return problems. It is recommended that the concrete slab is provided with appropriate footings. The slab should not be connected to the main building foundation to avoid noise and vibration transmission.
For rooftop installations, choose a place with adequate structural strength to safely support the entire operating weight
of the unit. The unit shall be mounted on a concrete slab similar to ground installations. The roof must be reinforced for supporting the individual point loads at the mounting isolator locations. It must be checked and ensured that the concrete base is perfectly horizontal and levelled, especially if the roof has been pitched to aid in water removal. It should be determined prior to installation if any special treatment is required to assure a levelled installation else it could lead to the above mentioned problems.
Vibration isolators are necessary for installing these chillers in order to minimize the transmission of vibrations. The
two types of vibration isolators generally utilized for mounting these units are Neoprene Pads and Spring Isolators. Neoprene Pads are recommended for ground level normal installations jobs where vibration isolation is not critical and job costs must be kept to a minimum. Spring Isolators are recommended for ground level installations which are noisesensitive areas or exposed to wind loads and all roof top installations. For critical installations (extremely noise and vibration sensitive areas), follow the recommendations of structural and acoustical consultants.
Based on the specific project requirements, choose the type of vibration isolators best suited for the application.
Carefully select the vibration isolators models / configuration based on the respective point loads and place each mount in its correct position following the Load Distribution Data and Mounting Drawings provided in this Catalog. Refer to the Schematic Mounting Layout drawings provided in the IOM manual of these chillers for further details in this regard.
Water piping must be connected correctly to the unit i.e., water must enter from the inlet connection on the cooler and
leave from the outlet connection.
A flow switch must be installed in the field piping at the outlet of the cooler (in horizontal piping) and wired back to the
unit control panel using shielded cable. There should be a straight run of piping of at least five pipe diameters on either side of the flow switch. Paddle type flow switches can be obtained from Zamil which are supplied as optional items.
The chilled water pump(s) installed in the piping system should discharge directly into the unit cooler. The pump(s)
may be controlled external to the unit - but an interlock must be wired to the unit control panel (as shown in the wiring diagram) so that the unit can start only upon proof of pump operation.
27
Flexible connections suitably selected for the fluid and pressure involved should be provided as mandatory in order to
minimize transmission of vibrations to the piping / building as some movement of the unit can be expected during normal operation. The piping and fittings must be separately supported to prevent any loading on the cooler.
The cooler must be protected by a strainer, preferably of 20 mesh, fitted as close as possible to the liquid inlet connection, and provided with a means of local isolation.
Thermometer and pressure gauge connections should be provided on the inlet and outlet connections of each cooler.
Pressure gauges are recommended to check the water pressure before and after the cooler and to determine if any variations occur in the cooler and system. When installing pressure taps to measure the amount of pressure drop across the water side of the cooler, the taps should be located in the water piping a minimum of 24 inches downstream from any connection (flange etc.) but as near to the cooler as possible.
Drain and air vent connections should be provided at all low and high points in the piping system to permit complete
drainage of the cooler and piping as well as to vent any air in the pipes. Hand shut-off valves are recommended for use in all lines to facilitate servicing.
The system water piping must be flushed thoroughly before connecting to the unit cooler. The cooler must not be
exposed to flushing velocities or debris released during flushing. It is recommended that a suitably sized bypass and valve arrangement is installed to allow flushing of the piping system. The bypass can be used during maintenance to isolate the cooler without disrupting flow to other units.
The following is a suggested piping arrangement at the chiller for single unit installations. For multiple chiller installations, each unit should be piped as shown:
OUT IN
Isolating Valve - Normally Open Isolating Valve - Normally Closed Balancing Valve Flow meter Strainer
Pressure tapping Flow Switch Connection (flanged / Victaulic) Pipe work Flexible connection
28
TANK SCHEMATIC
29
RIGGING INSTRUCTIONS
ATTENTION TO RIGGERS Hook rigging sling thru holes on the lifting plates, as shown below. Lifting plates or holes in base rail are centered around the unit center of gravity. Center of gravity is not unit center line. Ensure center of gravity aligns with the main lifting point before lifting. Use spreader bar when rigging, to prevent the slings from damaging the unit. CAUTION All panels should be in place when rigging. Care must be taken to avoid damage to the coils during handling. Insert packing material between coils & slings as necessary. MODELS: ALY010C - ALY015C
30
INSTALLATION CLEARANCE
WALL
FIGURE - 2 CORNER WALL NOTE: 1. All dimensions are in mm. 2. Pit installations are not recommended. Re-circulation of hot condenser air in combination with surface air turbulence can not be predicted, hot air re-circulation will severely affect unit efficiency (EER) and can cause high pressure or fan motor temperature trips.
31
MOUNTING LOCATION
MODELS: ALY010C - ALY015C
32
33
PL-AP-ALC-07-2M-E