Documente Academic
Documente Profesional
Documente Cultură
Revision 1 Revision 2
Revision 3
Revision 4
Approved by the Board of Directors 02-01-1993 Page 23 Added Top Chord Fillers-Design Check for Required Weld Length Approved by the Board of Directors 09-09-1993 Page 8(A) Added Shear Capacity Check of Chord Members (Page originally dated 06-17-1992 and revised 09-23-1992; also shows Issued 04-01-1993) Approved by the Board of Directors 09-01-2000 Page 8(B) Added Bearing Capacity Check of the Outstanding Leg of the Compression Chord of the Joist Girder under the Reaction of the Joist Bearing on it (Page originally dated 02-01-2000) Approved by the Board of Directors 11-07-2006 Complete document revised to be in accordance with the 2005 Standard Specifications for Joist Girders (ANSI SJI JG-1.1)
1 of 60
Table of Contents
Section 1 2 3 3.1 3.2 3.3 4 Description GENERAL INFORMATION GLOSSARY OF TERMS EXAMPLES OF JOIST GIRDER DESIGN CHECKS EXAMPLE 1A EXAMPLE 1B REFERENCES PRESENTATION OF ENGINEERING DATA Page 4 6 10 10 32 57 58
2 of 60
STEEL JOIST INSTITUTE ENGINEERING DESIGN GUIDE AND STANDARD DESIGN FORMAT FOR JOIST GIRDERS As approved by the Board of Directors of the Steel Joist Institute on November 7, 2006 The following comments and sample calculations are offered to: 1) Aid the satisfactory presentation of design data; and 2) Assist in the efficient review of these data by the Consulting Engineer of the Steel Joist Institute. A member company of the Steel Joist Institute is responsible for updating its design program and/or design in accordance with specification changes. The revised design must be approved within eighteen months of written notification from the Managing Director of the required change, or as otherwise specified by the Board of Directors.
3 of 60
Q=
Fc 0.6 Fy w 63.3 t Fy
for
144 w 25 Fy t
b. c. a.
Use 2005 AISC Specification Equations to determine the chord available strength. Use a resistance factor, , of 0.9 and a safety factor, , of 1.67. Use the 2001 AISI Standard North American Specification for the Design of Cold-Formed Steel Structural Members with 2004 Supplement for the calculation of nominal strength. Use a resistance factor, , of 0.85 and safety factor, , of 1.765.
b.
4 of 60
a. b. c.
Determine Q values based on the equation given in Section 1, Part C, Item 1a. Use 2005 AISC Specification Equations to determine the web available strength. Use a resistance factor, , of 0.9 and a safety factor, , of 1.67. a. Use the AISI Specifications for the calculation of nominal strength. b.Use a resistance factor, , of 0.85 and safety factor, , of 1.765.
D. General Remarks 1) Joist Girders shall be designed as simply-supported primary members. All loads shall be applied through steel joists, and will be equal in magnitude and evenly spaced along the Joist Girder top chord. 2) The examples that follow indicate the general and specific data that is to be shown or is necessary for arriving at the final design. 3) Requests for clarification of points regarding either design or physical tests should be directed to the Managing Director, Technical Director or to the Consulting Engineer of the SJI. 4) Design of the end bearing is the responsibility of the applicant and is not included. Sizes of plates should not be shown. 5) Weld design is the responsibility of the applicant and weld sizes are not to be shown. Designs of Joist Girders, submitted for Steel Joist Institute design check, must be in accordance with the Standard Specifications shown in the current edition of the Institutes catalog. The principles involved in the design of the chords, webs and welds are explained in the accompanying material in a typical example. It is not to be inferred that the applicant must use the modified Warren configuration of the illustrative example, or panel lengths, or chord sizes used therein. The example is merely presented in order to help illustrate the general engineering principles as applied to Joist Girders which are accepted as the basis of the design by the Steel Joist Institute. An applicant submitting a design for Joist Girders must verify the chords and webs as outlined in Section 3. The stress of the top chord must be calculated at all critical panel points and mid-panel points in accordance with the Steel Joist Institute specifications. If the panel lengths are varied within a Joist Girder, panels other than the end or center may be critical.
5 of 60
6 of 60
Factored Load. Product of a load factor and the nominal load. Filler. A rod, plate or angle welded between a two angle web member or between a top or bottom chord panel to tie them together, usually located at the middle of the member. Gravity Load. Load, such as that produced by dead and live loads, acting in the downward direction. Instability. Limit state reached in the loading of a structural component, frame or structure in which a slight disturbance in the loads or geometry produces large displacements. Joist. A structural load-carrying member with an open web system which supports floors and roofs utilizing hot-rolled or cold-formed steel and is designed as a simple span member. Currently, the SJI has the following joist designations: K-Series including KCS, LH-Series and DLH-Series. Joist Girder. A primary structural load-carrying member with an open web system designed as a simple span supporting equally spaced concentrated loads of a floor or roof system acting at the panel points of the member and utilizing hot-rolled or cold-formed steel. Limit State. Condition in which a structure or component becomes unfit for service and is judged either to be no longer useful for its intended function (serviceability limit state) or to have reached its ultimate load-carrying capacity (strength limit state). Load. Force or other action that results from the weight of building materials, occupants and their possessions, environmental effects, differential movement, or restrained dimensional changes. Load Effect. Forces, stresses, and deformations produced in a structural component by the applied loads. Load Factor. Factor that accounts for deviations of the nominal load from the actual load, for uncertainties in the analysis that transforms the load into a load effect, and for the probability that more than one extreme load will occur simultaneously. LRFD (Load and Resistance Factor Design). Method of proportioning structural components such that the design strength equals or exceeds the required strength of the component under the action of the LRFD load combinations. LRFD Load Combination. Load combination in the applicable building code intended for strength design (Load and Resistance Factor Design). Nominal Load. Magnitude of the load specified by the applicable building code.
7 of 60
Nominal Strength. Strength of a structure or component (without the resistance factor or safety factor applied) to resist the load effects, as determined in accordance with these Standard Specifications. Required Strength. Forces, stress, and deformations produced in a structural component, determined by either structural analysis, for the LRFD or ASD load combinations, as appropriate, or as specified by these Standard Specifications. Resistance Factor, . Factor that accounts for unavoidable deviations of the nominal strength from the actual strength and for the manner and consequences of failure. Safety Factor, . Factor that accounts for deviations of the actual strength from the nominal strength, deviations of the actual load from the nominal load, uncertainties in the analysis that transforms the load into a load effect and for the manner and consequences of failure. Service Load. Load under which serviceability limit states are evaluated. Serviceability Limit State. Limiting condition affecting the ability of a structure to preserve its appearance, maintainability, durability, or the comfort of its occupants or function of machinery, under normal usage. Slenderness Ratio. The ratio of the effective length of a column to the radius of gyration of the column about the same axis of bending. Span. The centerline-to-centerline distance between structural steel supports such as a beam, column or Joist Girder or the clear span distance plus four inches onto a masonry or concrete wall. Specified Minimum Yield Stress. Lower limit of yield stress specified for a material as defined by ASTM. Stability. Condition reached in the loading of a structural component, frame or structure in which a slight disturbance in the loads or geometry does not produce large displacements. Standard Specifications. Documents developed and maintained by the Steel Joist Institute for the design and manufacture of open web steel joists and Joist Girders. The term SJI Standard Specifications encompass by reference the following: ANSI/SJI-K1.1 Standard Specification for Open Web Steel Joists, K-Series; ANSI/SJI-LH/DLH-1.1 Standard Specifications for Longspan Steel Joists, LH-Series and Deep Longspan Steel Joists, DLH-Series; and ANSI/SJI-JG-1.1 Standard Specifications for Joist Girders. Strength Limit State. Limiting condition affecting the safety of the structure, in which the ultimate load-carrying capacity is reached.
8 of 60
Tensile Strength (of material). Maximum tensile stress that a material is capable of sustaining as defined by ASTM. Webs. The vertical or diagonal members joined at the top and bottom chords of a joist or Joist Girder to form triangular patterns. Yield Point. First stress in a material at which an increase in strain occurs without an increase in stress as defined by ASTM. Yield Strength. Stress at which a material exhibits a specified limiting deviation from the proportionality of stress to strain as defined by ASTM. Yield Stress. Generic term to denote either yield point or yield strength, as appropriate for the material.
9 of 60
The Joist Girder designation for this example: 40G7N11.6F @ 35-0 span; LRFD Design, Modified Warren Geometry
GIVEN:
Designation: Length: Working Length: All Material: Weld Electrode: Chord Spacing: Dead load Live load Factored load Resistance Factors Design Stress
REQUIRED:
40G 7N 11.6F 35.00 ft. 34.67 ft. Fy = 50,000 psi E70XX 1 in. Back to Back 3000 lb (includes weight of girder) 5000 lb 1.4 D = 4200 lb 1.2 D + 1.6 L = 11,600 lb
t = 0.90 c = 0.90 tFy = 0.90 x 50 ksi = 45 ksi (Tension members)
= = = =
required stress, ksi nominal stress, ksi resistance factor design stress, ksi
See also, Steel Joist Institute Standard Specification for Joist Girders 10 of 60
4.835 ' 2
5.000 ' 5
5.000 ' 8
10
5.000 ' 11
13
5.000 ' 14
16
5.000 ' 17
19
4.835 ' 20
22
d= 38.52 "
3 2.335 ' 2.500 ' 6 9 12 15 18 21
34.670 '
R = 3.5P
R = 3.5P
P(17.335) 2
= 2.40 in.2
And
d = D ( y TC + y BC ) = 40 (0.740 + 0.740) = 38.52 in. Calculate maximum B.C. force: Occurs at point directly below panel point 10.
M 10 d
MAX FORCE BC = 106,622 lb Force BC 106,622 = = 2.37 in.2 t Fy 0.9x50,000 2L 2 x 2 x 5/16, Area = 2.93 in.2 Therefore, trial section axial stress is OK Calculate maximum T.C. force: Occurs at panel point 11. Calculate moment at panel point 12. MAX FORCE TC = 106,622 lb Trial TC section = 2L 2 x 2 x 5/16 Io = 0.849 in.4; A = 1.46 in.2; rx = 0.761 in.; rz = 0.489 in.; Q = 1.0 Io-o = Io + Ax2 = 0.849 + 1.46(0.5 + 0.740)2 = 3.094 in.4
ry y = I o o 3.094 = = 1.456 in. A 1.46
lz = 15 in. (TC Fillers); lx = 30 in.; ly-y = 60 in. (l/r)z = 15/0.489 = 30.67 (l/r)x = 30/0.761 = 39.42 (l/r)y-y = 60/1.456 = 41.21 Check critical stress: 4.71 E QFy
6 = 4.71 29 x10
Governs 90
1.0 50,000
( )
Fe = 168,536 psi
1.0 ( 50 , 000 ) 0.658 168,536 50,000 = 44,161 psi Fcr = Fn = 1.0
12 of 60
3
POSSIBLE SHEAR FAILURE PLANE
b t
V T or C
13 of 60
CHECK BOTTOM CHORD AT PANEL POINT 3: V = Shear force across chord section, kips T = Tension force in the chord section, kips C = Compression force in the chord section, kips A = Chord area, in.2 EDL = 2.335 ft = 28.02 in. VAR = 2.500 ft = 30.00 in. PNL = 5.000 ft = 60.00 in. d = 38.52 in. b = 2.5 in. t = 0.3125 in. V = 3P = 3 x 11.6 = 34.8 kips T = V/(d/EDL) = 34.8/(38.52/28.02) = 25.3 kips A = 2.93 in.2
Required Stress: Shear Tensile fuv = V / (2*t*b) = 34.8 / (2*0.3125*2.5) = 22.27 ksi fut = T / A = 25.3 / 2.93 = 8.63 ksi
CHECK TOP CHORD AT PANEL POINT 4: d = 40-2(0.740) = 38.52 in. b = 2.5 in. t = 0.3125 in. V = 3P = 3 x 11.6 = 34.8 kips C = 3P(EDL+VAR)/d = 52.4 kips A = 2.93 in.2 Required Stress: Shear fuv = V / (2*t*b) = 34.8 / (2*0.3125*2.5) = 22.27 ksi
14 of 60
Compressive
CHECK BOTTOM CHORD AT PANEL POINT 6: d = 40-2(0.740) = 38.52 in. b = 2.5 in. t = 0.3125 in. V = 2P = 2 x 11.6 = 23.2 kips T = [3P(EDL+VAR+1/2 PNL) P(1/2 PNL)]/d = 70.5 kips A = 2.93 in.2 Required Stress: Shear Tensile fuv = V / (2*t*b) = 23.2 / (2*0.3125*2.5) = 14.85 ksi fut = T / A = 70.5 / 2.93 = 24.06 ksi
BY INSPECTION, SHEAR CAPACITY AT PANEL POINTS 7, 9, 10, AND 12 DOES NOT GOVERN DESIGN.
CHECK THE BEARING CAPACITY OF THE OUTSTANDING LEG OF THE COMPRESSION CHORD OF THE JOIST GIRDER UNDER THE REACTION OF THE JOIST BEARING ON IT (Galambos, 2000).
15 of 60
TC = 2L 2 x 2 x 5/16 t = 0.3125 in. b = 2.5 in. Q = 1.0 K-distance = 0.625 in. Pu = Factored girder panel load = 11,600 lb Adjusted T.C. force = 106,622 lb
f uTC = 106,622 lb = 36,514 psi 2(1.46 in 2 )
Width of joist bearing seat: g = 5.0 in. The allowable reaction is the lesser of:
f Pp and Pp 1.6 uTC QFy where, = 0.9
Pp =
2(b K )
t 2 Fy
[g + 5.66(b K )]
16 of 60
0.31252 50 [5 + 5.66(2.5 0.625)] = 20.33 kips Pp = 2(2.5 0.625) Pp = 18.3 kips f 36.514 = 14.43 kips Pp 1.6 uTC = 18.31.6 0.9 1.0 50 QFy The controlling value is 14.43 kips. The required reaction is of the joist girder panel point load of 11.6 kips.
Check Span/ry-y 575:
l/ry-y 240 lmax = 240(ry-y) = 240(1.456)/12 lmax = 29.12 ft. USE ONE BC BRACE NEAR MIDSPAN
Calculate Chord/Web Forces: TOP CHORD: BETWEEN PANEL POINTS 1-2; 2-4; 19-20; 20-22:
FTC =
FTC =
FTC =
FTC =
FBC =
FBC =
FBC =
= 44,092 lb
BETWEEN PANEL POINTS 4-6; 19-18: V = 2P
= +14,697 lb
BETWEEN PANEL POINTS 9-10; 15-13: V=P
19 of 60
TOP CHORD FORCES (lb) 1-2; 2-4 -25,314 4-5; 5-7 -70,485 7-8; 8-10 -97,588 10-11; 11-13 -106,622 13-14; 14-16 -97,588 16-17; 17-19 -70,485 19-20; 20-22 -25,314
BOTTOM CHORD FORCES (lb) 3-6 +52,416 6-9 +88,554 9-12 +106,622 12-15 +106,622 15-18 +88,554 18-21 +52,416 -----
WEB MEMBER 2-3; 5-6; 8-9; 11-12; 14-15; 17-18; 20-21 1-3; 22-21 3-4; 21-19 4-6; 19-18 6-7; 18-16 7-9; 16-15 9-10; 15-13 10-12; 13-12
FORCES (lb) REQD COMP FORCE (lb)* -2,132 --+43,048 -44,092 +29,394 -29,394 +14,697 -14,697 +12,860 -10,762 ---7,349 ---3,674 ---3,215
20 of 60
TRY L 1 x 1 x 1/8 (crimped ends) l = 38.52 in.; rz = 0.246 in.; A = 0.297 in.2; Q = 1.0 Force = -2,132 lb fu = -2,132/0.297 = 7,178 psi (l/r)z = 38.52/0.246 = 156.59 200 Check critical stress: 4.71 E QFy
6 = 4.71 29 x10
1.0 50,000
( lr )
2E
2
Fe = 11,673 psi Fcr = Fn = 0.877(11,671) = 10,237 psi Design Stress: c Fn = 0.9(10,237) = 9,213 psi > fu Weld: 2,132 = 0.8 in. 1392(2) OK use L 1 x 1 x 1/8
Use 2 of 1/8 weld each end of angle (1 min. each leg of each end)
21 of 60
Try 2L 1 x 1 x 3/16 l = 47.63 in.; rz = 0.293 in.; rx = 0.457 in.; A2L = 1.054 in.2; Q = 1.0 (l/r)z = 47.63/0.293 = 162.56 (no fillers) 240 Check compression: Force = -10,762 lb fu = -10,762/1.054 = 10,211 psi Check critical stress:
4.71 E
6 = 4.71 29x10
QFy
1.0 50,000
( )
2 E 2 l r
22 of 60
1 .0 50 ,000
( )
Design Stress: c Fn = 0.9(22,597) = 20,337 psi > fu Weld: 43,048 = 10.3 in. 1392(3) Use 2L 1 x 1 x 3/16 w/ filler
Try 2L 2 x 2 x 3/16 l = 48.82 in.; rz = 0.394 in.; rx = 0.617 in.; A2L = 1.430 in.2; Q = 1.0 Force = -44,092 lb fu = -44,092/1.430 = 30,834 psi (l/r)x = 48.82/0.617 = 79.12 (One filler at mid-length) 200
23 of 60
1.0 50,000
( )
Fe = 45,722 psi Fcr = Fn = 31,636 psi Design Stress: c Fn = 0.9(31,636) = 28,472 psi < fu Try 2L 2 x 2 x 1/4 l = 48.82 in.; rz = 0.391 in.; rx = 0.609 in.; A2L = 1.876 in.2; Q = 1.0 Force = -44,092 lb fu = -44,092/1.876 = 23,503 psi (l/r)x = 48.82/0.609 = 80.16 (One filler at mid-length) 200 Check critical stress: 4.71 E QFy
6 = 4.71 29 x10
1.0 50,000
( )
Design Stress: c Fn = 0.9(31,256) = 28,130 psi > fu Weld: 44,092 = 10.6 in. 1392(3) OK Use 2L 2 x 2 x 1/4 w/ filler
Try 1L 2 x 2 x 3/16 l = 48.82 in.; rz = 0.394 in.; rx = 0.617 in.; A = 0.715 in.2; Q = 1.0 (l/r)z = 48.82/0.394 = 123.91 (no fillers) 240 Check compression: Force = -7,349 lb fu = -7,349/0.715 = 10,278 psi Check critical stress:
4.71 E QFy
6 = 4.71 29 x10
1.0 50,000
( )
2 E 2 l r
25 of 60
Design Stress: c Fn = 0.9(16,349) = 14,714 psi > fu Weld: 29,394 = 7.1 in. 1392(3) OK
Use 7 1/2 of 3/16 weld each end of angle (3 3/4 min. each leg of each angle)
Try 2L 2 x 2 x 0.143 l = 48.82 in.; rz = 0.396 in.; rx = 0.624 in.; A = 1.104 in.2; Q = 0.898 Force = -29,394 lb fu = -29,394/1.104 = 26,625 psi (l/r)x = 48.82/0.624 = 78.24 (One filler at mid-length) 200 Check critical stress: 4.71 E QFy
6 = 4.71 29 x10
0.898 50,000
( )
26 of 60
Design Stress: c Fn = 0.9(30,039) = 27,035 psi > fu Weld: 29,394 = 10.6 in. 1392(2) OK
Try 1L 1 x 1 x 3/16 l = 48.82 in.; rz = 0.293 in.; rx = 0.457 in.; A = 0.527 in.2; Q = 1.0 (l/r)z = 48.82/0.293 = 166.62 (no fillers) 240 Check compression: Force = -3,683 lb fu = -3,683/0.527 = 6,989 psi Check critical stress:
4.71 E
6 = 4.71 29x10
QFy
1.0 50,000
( )
2 E 2 l r
27 of 60
Design Stress: c Fn = 0.9(9,042) = 8,138 psi > fu Weld: 14,697 = 3.5 in. 1392(3) OK
Use 3 1/2 of 3/16 weld each end of angle (1 3/4 min. each leg of each end)
BETWEEN PANEL POINTS 9-10; 15-13:
Try 2L 1 x 1 x 3/16 l = 48.82 in.; rz = 0.293 in.; rx = 0.457 in.; A = 1.054 in.2; Q = 1.0 Force = -14,732 lb fu = -14,732/1.054 = 13,977 psi (l/r)x = 48.82/0.457 = 106.83 (One filler at mid-length) 200 Check critical stress: 4.71 E QFy
6 = 4.71 29 x10
1.0 50,000
( )
28 of 60
Design Stress: c Fn = 0.9(21,705) = 19,535 psi > fu Weld: 14,697 = 3.5 in. 1392(3) OK
Try 1L 1 x 1 x 5/32 l = 48.82 in.; rz = 0.295 in.; rx = 0.461 in.; A = 0.444 in.2; Q = 1.0 (l/r)z = 48.82/0.295 = 165.49 240 Check compression: Force = -3,215 lb fu = -3,215/0.444 = 7,241 psi Check critical stress:
4.71 E QFy
6 = 4.71 29x10
1.0 50,000
( )
2 E 2 l r
29 of 60
Design Stress: c Fn = 0.9(9,166) = 8,249 psi > fu Weld: 12,860 = 4.6 in. 1392(2) OK
Use 5 of 1/8 weld each end of angle (2 1/2 min. each leg of each end) The design submittal shall provide details to demonstrate how the required weld length will be applied, as shown in Figures 5 and 6 below.
WEB 1-3
BOTTOM CHORD
Figure 5. Welding of Web Members (For illustrative purposes only; all joist connections must be shown)
30 of 60
CHORD
CHORD
Figure 6. Section A A DEFLECTION CHECK
LJG = 35 (34.67 working length); Assume joists are 40 ft. long. Live Load = 25 psf; 25 x 40 = 1.0 kip/ft LL Deflection at 1/360 of working length = 34.67 x 12 / 360 = 1.16 I JG AT AB d2 = IT + IB + AT + AB
IT = 0.849 in.4 IB = 0.849 in.4 AT = 2.93 in.2 AB = 2.93 in.2 d = 38.52 in. IJG = 2,177 in.4 1 4 1.15(5) (34.67 12) 1.15(5)(W ) L 12 = DEFLECTION = 384 EI JG 384 29,000 2,177
( )
4
Check for required weld length E70XX Electrodes Angle type filler (3/16 Material) Assume 3/16 in. fillet weld Fexx = 70,000 psi w = 0.75 Fnw = 0.6 Fexx Lw = required length of weld, in. P = chord force, lb Dw = weld size, in. wFnweld= weld design stress = 31,500 psi fuweld = required force of weld in shear = 2% of P P fuweld Lw = 106,622 lb = 106,622 x 0.02 = 2,132 lb f uweld 1.414 2,132 = 2 = = 0.509 in. w Fnweld D w 31,500 0.188 Given:
Use 2 3/16 welds 3/4 long (one weld on each chord angle)* * NOTE: Minimum allowable weld length is four times the weld thickness. Weld length for web fillers and/or ties must be calculated using same procedure.
32 of 60
3.2
EXAMPLE 1B
The Joist Girder designation for this example: 40G7N8K @ 35-0 span; ASD Design, Modified Warren Geometry
GIVEN:
Designation: Length: Working Length: All Material: Weld Electrode: Chord Spacing: Dead load Live load Allowable Stress
REQUIRED:
40G 7N 8K 35.00 ft. 34.67 ft. Fy = 50,000 psi E70XX 1 Back to Back 3000 lb (includes weight of girder) 5000 lb Fn/ = 0.6Fn= 0.6Fy= 30 ksi (Tension members)
f shall not exceed Fn/ for all members where, f Fn Fn/ = = = = required stress, ksi nominal stress, ksi safety factor 0.6Fn = allowable stress
See also, Steel Joist Institute Standard Specification for Joist Girders
33 of 60
C L
P/2 P P P P P P P/2
4.835 ' 2
5.000 ' 5
5.000 ' 8
5.000 ' 10 11
5.000 ' 13 14
5.000 ' 16 17
4.835 ' 19 20
22
d= 38.52 "
3 2.335 ' 2.500 ' 6 9 12 15 18 21
34.670 '
R = 3.5P
R = 3.5P
Calculate Moment at Midspan of Girder: Where, P = 8.0 kips M CL = 3.5 P(17.335) P(2.5 + 7.5 + 12.5) = 29.505 P = 29.505 8 = 236.04 ft kips = 2,832,480 in lb ASSUME EFFECTIVE DEPTH = d = 38 in.
A req 'd = M 2,832,480 = d (0.6Fy ) (38)(0.6)(50,000)
P(17.335) 2
= 2.48 in.2
And
34 of 60
Calculate maximum B.C. force: Occurs at point directly below panel point 10.
P(14.835)(12) 1,0003.5P(14.835)(12) P(5 + 10)(12) M 10 2 = d 38.52 MAX FORCE BC = 73,533 lb Force BC 73,533 = = 2.45 in.2 0.6Fy 0.6(50,000) 2L 2 x 2 x 5/16, Area = 2.93 in.2 Therefore, trial section axial stress is OK Calculate maximum T.C. force: Occurs at panel point 11. Calculate moment at panel point 12. MAX FORCE TC = 73,533 lb Trial TC section = 2L 2 x 2 x 5/16 Io = 0.849 in.4; A = 1.46 in.2; rx = 0.761 in.; rz = 0.489 in.; Q = 1 Io-o = Io + Ax2 = 0.849 + 1.46(0.5 + 0.740)2 = 3.094 in.4
ry y = I o o 3.094 = = 1.456 in. A 1.46
lz = 15 in. (TC Fillers); lx = 30 in.; ly-y = 60 in. (l/r)z = 15/0.489 = 30.67 (l/r)x = 30/0.761 = 39.42 (l/r)y-y = 60/1.456 = 41.21
Governs 90
35 of 60
1.0 50,000
( )
Fe = 168,536 psi
1.0 ( 50 , 000 Fcr = Fn = 1.00.658 168,536 50,000 = 44,161 psi
Allowable Stress:
0.6Fn = 0.6( 44,161) = 26,497 psi
36 of 60
3
POSSIBLE SHEAR FAILURE PLANE
b t
V T or C
37 of 60
V = Shear force across chord section, kips T = Tension force in the chord section, kips C = Compression force in the chord section, kips A = Chord area, in.2 EDL = 2.335 ft = 28.02 in. VAR = 2.500 ft = 30.00 in. PNL = 5.000 ft = 60.00 in. d = 40-2(0.740) = 38.52 in. b = 2.5 in. t = 0.3125 in. V = 3P = 3 x 8.0 = 24.0 kips T = V/(d/EDL) = 24.0/(38.52/28.02) = 17.5 kips A = 2.93 in.2 Required Stress: Shear Tensile fv = V / (2*t*b) = 24 / (2*0.3125*2.5) = 15.36 ksi ft = T / A = 17.5 / 2.93 = 5.97 ksi
b = 2.5 in. t = 0.3125 in. V = 3P = 3 x 8.0 = 24.0 kips C = 3P(EDL+VAR)/d = 36.15 kips A = 2.93 in.2 Required Stress: Shear fv = V / (2*t*b) = 24.0 / (2*0.3125*2.5) = 15.36 ksi fc = C / A = 36.15 / 2.93 = 12.34 ksi
Compressive
38 of 60
d = 40-2(0.740) = 38.52 in. b = 2.5 in. t = 0.3125 in. V = 2P = 2 x 8.0 = 16.0 kips T = [3P(EDL+VAR+1/2 PNL) P(1/2 PNL)]/d = 48.61 kips A = 2.93 in.2 Required Stress: Shear Tensile fv = V / (2*t*b) = 16.0 / (2*0.3125*2.5) = 10.24 ksi ft = T / A = 48.61 / 2.93 = 16.59 ksi
BY INSPECTION, SHEAR CAPACITY AT PANEL POINTS 7, 9, 10, AND 12 DOES NOT GOVERN DESIGN.
CHECK THE BEARING CAPACITY OF THE OUTSTANDING LEG OF THE COMPRESSION CHORD OF THE JOIST GIRDER UNDER THE REACTION OF THE JOIST BEARING ON IT (Galambos, 2000).
39 of 60
TC = 2L 2 x 2 x 5/16 t = 0.3125 in. b = 2.5 in. Q = 1.0 K-distance = 0.625 in. P = 8,000 lb
f TC = 73,533 lb = 25,183 psi 2(1.46 in 2 )
Width of joist bearing seat: g = 5.0 in. The allowable reaction is the lesser of: f 0.6Pp and 0.6Pp 1.6 TC 0.6QFy
Pp =
2(b K )
t 2 Fy
[g + 5.66(b K )]
40 of 60
0.31252 50 [5 + 5.66(2.5 0.625)] = 20.33 kips Pp = 2(2.5 0.625) 0.6Pp = 12.20 kips f 25.183 0.6Pp 1.6 TC = 12.201.6 = 9.28 kips 0.6QFy 0.6 1.0 50 The controlling value is 9.28 kips. The required reaction is of the joist girder panel point load of 8.0 kips.
4.0 kips < 9.28 kips Therefore, the top chord angle is OK. Check Span/ry-y 575:
l/ry-y 240 lmax = 240(ry-y) = 240(1.456)/12 lmax = 29.12 ft. USE ONE BC BRACE NEAR MIDSPAN
Calculate Chord/Web Forces: TOP CHORD: BETWEEN PANEL POINTS 1-2; 2-4; 19-20; 20-22:
FTC =
FTC =
FTC =
FTC =
FBC =
FBC =
FBC =
= 30,408 lb
BETWEEN PANEL POINTS 4-6; 19-18: V = 2P
= +10,136 lb
BETWEEN PANEL POINTS 9-10; 15-13: V=P FWEB = V(CSC ) = (8.0)(1.267)(1,000)
= 10,136 lb
BETWEEN PANEL POINTS 10-12; 13-12:
43 of 60
TOP CHORD FORCES (lb) 1-2; 2-4 -17,458 4-5; 5-7 -48,611 7-8; 8-10 -67,302 10-11; 11-13 -73,533 13-14; 14-16 -67,302 16-17; 17-19 -48,611 19-20; 20-22 -17,458
BOTTOM CHORD FORCES (lb) 3-6 +36,150 6-9 +61,072 9-12 +73,533 12-15 +73,533 15-18 +61,072 18-21 +36,150 -----
WEB MEMBER 2-3; 5-6; 8-9; 11-12; 14-15; 17-18; 20-21 1-3; 22-21 3-4; 21-19 4-6; 19-18 6-7; 18-16 7-9; 16-15 9-10; 15-13 10-12; 13-12
FORCES (lb) REQD COMP FORCE (lb)* -1,471 --+29,688 -30,408 +20,272 -20,272 +10,136 -10,136 +8,869 -7,422 ---5,068 ---2,534 ---2,217
44 of 60
TRY L 1 x 1 x 1/8 (crimped ends) l = 38.52 in.; rz = 0.246 in.; A = 0.297 in.2; Q = 1.0 Force = -1,471 lb f = -1,471/0.297 = -4,953 psi (l/r)z = 38.52/0.246 = 156.59 200 Check critical stress:
4.71 E
6 = 4.71 29x10
QFy
1.0 50,000
( )
2 E 2 l r
Allowable Stress:
0.6Fn = 0.6(10,237) = 6,142 psi > f
OK use L 1 x 1 x 1/8
Weld:
Use 2 of 1/8 weld each end of angle (1 min. each leg of each end)
45 of 60
Design for tension: A req 'd = Force 29,712 = = 0.990 in.2 0.6Fn 0.6(50,000)
Try 2L 1 x 1 x 3/16 l = 47.63 in.; rz = 0.293 in.; rx = 0.457 in.; A2L = 1.054 in.2; Q = 1.0 (l/r)z = 47.63/0.293 = 162.56 (no fillers) 240 Check compression: Force = -7,422 lb f = -7,422/1.054 = 7,042 psi Check critical stress:
4.71 E
6 = 4.71 29x10
QFy
1.0 50,000
( )
Allowable Stress:
0.6Fn = 0.6(9,499) = 5,699 psi < f
46 of 60
1.0 50,000
( )
Weld:
Try 2L 2 x 2 x 3/16 l = 48.82 in.; rz = 0.394 in.; rx = 0.617 in.; A2L = 1.430 in.2; Q = 1.0 Force = -30,408 lb f = -30,408/1.430 = 21,264 psi (l/r)x = 48.82/0.617 = 79.12 200 (One filler at mid-length)
47 of 60
1.0 50,000
( )
N.G.
Try 2L 2 x 2 x 1/4 w/ filler l = 48.82 in.; rz = 0.391 in.; rx = 0.609 in.; A2L = 1.876 in.2; Q = 1.0 Force = -30,408lb f = -30,408/1.876 = 16,209 psi (l/r)x = 48.82/0.609 = 80.16 (One filler at mid-length) 200 Check critical stress:
4.71 E QFy
6 = 4.71 29x10
1.0 50,000
( )
48 of 60
Allowable Stress:
0.6Fn = 0.6(31,256) = 18,754 psi > f
Weld:
Try 1L 2 x 2 x 3/16 l = 48.82 in.; rz = 0.394 in.; rx = 0.617 in.; A = 0.715 in.2; Q = 1.0 (l/r)z = 48.82/0.394 = 123.91 240 (no fillers) Check compression: Force = -5,068 lb f = -5,068/0.715 = 7,088 psi Check critical stress:
4.71 E QFy
6 = 4.71 29 x10
1.0 50,000
( )
2 E 2 l r
49 of 60
Allowable Stress:
0.6Fn = 0.6(16,349) = 9,809 psi >f
OK
20,272 = 7.3 in. 928(3) Use 7 1/2 of 3/16 weld each end of angle (3 3/4 min. each leg of each end) Weld:
BETWEEN PANEL POINTS 6-7; 18-16:
Try 2L 2 x 2 x 0.163 l = 48.82 in.; rz = 0.396 in.; rx = 0.621 in.; A = 1.25 in.2; Q = .952 Force = -20,272 lb f = -20,272/1.25 = 16,218 psi (l/r)x = 48.82/0.621 = 78.62 200 (One filler at mid-length) Check critical stress: 4.71 E QFy
6 = 4.71 29x10
.952 50,000
( )
OK
Weld:
Try 1L 1 x 1 x 3/16 l = 48.82 in.; rz = 0.293 in.; rx = 0.457 in.; A = 0.527 in.2; Q = 1.0 (l/r)z = 48.82/0.293 = 166.62 240 Check compression: Force = -2,534 lb f = -2,534/0.527 = 4,808 psi Check critical stress:
4.71 E QFy
6 = 4.71 29x10
1.0 50,000
( )
2 E 2 l r
Allowable Stress:
0.6Fn = 0.6(9,042) = 5,425 psi >f
OK
Weld:
Use 4 of 3/16 weld each end of angle (2 min. each leg of each end)
51 of 60
Try 2L 1 x 1 x 3/16 l = 48.82 in.; rz = 0.293 in.; rx = 0.457 in.; A = 1.054 in.2; Q = 1.0; Force = -10,136 lb f = -10,136/1.054 = 9,617 psi (l/r)x = 48.82/0.457 = 106.83 (One filler at mid-length) 200 Check critical stress: 4.71 E QFy
6 = 4.71 29 x10
1.0 50,000
( )
OK
Weld:
52 of 60
Try 1L 1 x 1 x 5/32 l = 48.82 in.; rz = 0.295 in.; rx = 0.461 in.; A = 0.444 in.2; Q = 1.0 (l/r)z = 48.82/0.295 = 165.49 240 Check compression: Force = -2,217 lb f = -2,217/0.444 = 4,993 psi Check critical stress:
4.71 E QFy
6 = 4.71 29x10
1.0 50,000
( )
2 E 2 l r
Allowable Stress:
0.6Fn = 0.6(9,166) = 5,499 psi >f
OK
Weld:
Use 5 of 1/8 weld each end of angle (2 1/2 min. each leg of each end)
53 of 60
The design submittal shall provide details to demonstrate how the required weld length will be applied, as shown in Figures 5 and 6 below.
WEB 1-3
BOTTOM CHORD
Figure 5. Welding of Web Members (For illustrative purposes only; all joist connections must be shown)
CHORD
CHORD
Figure 6. Section A A
54 of 60
DEFLECTION CHECK
LJG = 35 (34.67 working length); Assume joists are 40 long. Live Load = 25 psf; 25 x 40 = 1.0 kip/ft LL Deflection at 1/360 of working length= 34.67 x 12 / 360 = 1.16 I JG AT AB d2 = IT + IB + AT + AB
IT = 0.849 in.4 IB = 0.849 in.4 AT = 2.93 in.2 AB = 2.93 in.2 d = 38.52 in. IJG = 2,177 in.4 1 4 1.15(5) (34.67 12) 1.15(5)(W ) L 12 DEFLECTION = = 384 EI JG 384 29,000 2,177
( )
4
55 of 60
Check for required weld length Given: Fexx w Fnw Lw P Dw Fnweld/w fweld P fweld Lw E70XX Electrodes Angle type filler (3/16 Material) Assume 3/16 in. fillet weld = 70,000 psi = 2.0 = 0.6 Fexx = required length of weld, in. = chord force, lb = weld size, in. = weld allowable stress = 21,000 psi = required force of weld in shear = 2% of P = 73,533 lb = 73,533 x 0.02 = 1,471 lb f weld 1.414 1,471 = 2 = = 0.527 in. (Fnweld / w ) D w 21,000 0.188
Use 2 3/16 welds 3/4 long (one weld on each chord angle)* * NOTE: Minimum allowable weld length is four times the weld thickness. Weld length for web fillers and/or ties must be calculated using same procedure.
56 of 60
3.3
REFERENCES
Galambos, T.V. (2000) Joists Bearing on Joist Girders: The Performance and Design Checking of the Chord-Angle Legs in Joist Girders, Department of Civil and Mineral Engineering, University of Minnesota, Minneapolis, MN, Structural Engineering Section Report No.1, January 1983, Revised January, 2000.
57 of 60
B)
C)
Additional designs may be requested by the Consulting Engineer, or may be required if the above listed designations do not reflect all typical geometric configurations or types of construction. Welding data must be included. This information may be presented in the form of tables or a computer printout. The format for presenting the design data must be properly labeled and sufficiently detailed so that all relevant checking steps can be readily identified and verified by manual calculation. D) A complete design example of the above Joist Girder illustrating in detail the methods or procedures and logic used to arrive at the figures presented in the tables or on the computer printout. A statement that the design program was prepared in accordance with the SJI Standard Specifications of latest adoption by a registered professional engineer or by a person under the close supervision of a registered professional engineer. The signature and seal of this professional engineer must be included with the design submittal.
E)
The Consulting Engineer of the Steel Joist Institute will verify that the Joist Girder design scheme submitted will produce designs which fulfill all requirements of the SJI Standard Specifications, and this will be stated in the recommendation for approval. In order to expedite the approval process it is desirable to arrange for a personal interview between the Consulting Engineer and the professional engineer preparing the design program. The member company will be responsible for updating their designs in accordance with specification changes. The revised design must be approved within eighteen months, or as otherwise specified by the Board of Directors, or written notification from the Managing Director of the required change. The Steel Joist Institute retains the right to require any member company with a design to submit a complete design of any Joist Girder designation at any time. This design may be for any increment of span between the limits shown in the applicable Design Guide Weight Table for Joist Girders. The design information must be available to the SJI headquarters within 24 hours after notification is received by the member company concerned.
59 of 60
1.
A Chord Properties Table must be submitted with the design data. For nonstandard shapes such as cold-formed sections, not only must the geometric properties be shown, but also all dimensions necessary to describe the sections. All dimensions such as the radii of bends, the distance from the end of the joist to the center of the bend of the end bar, E0, and others, must be clearly indicated. The clearances from the outside surface of the chords to the back of the web bend must be indicated for all joists. Wherever the framing of a joint is too complex to be clearly defined, large scale drawings must be submitted. An example calculation for the design of a joist girder must accompany the design submittal. The specific joist girder designation will be chosen by the SJI Consulting Engineer.
2. 3. 4. 5.
The following shall be submitted: 1. A description of the program 2. Example printouts of one design length in both LRFD and ASD for each designation: a. Member sizes and properties b. Dimensions c. Required force (Fu) and allowable force (Fa) for each member if it is a LRFD or ASD design, respectively d. Check for bottom chord braces e. Joint eccentricities f. Combined stress check g. Deflection check h. Filler Table 3. Properly dimensioned drawings of Joist Girder configurations, end details and accessories 4. Cover letter affixed with P.E. Stamp
60 of 60