Storage tank for sub-frame installation BSO

GmbH Behlterbau

Huch Behlterbau Temnitz-Park-Chaussee 22 16818 Werder/Germany Tel.: +49 (0)33920 / 672-0 Fax: +49 (0)33920 / 672-72 or -68

GmbH Behlterbau

PRODUCT DESCRIPTION

II. Storage tank for sub-frame installation BSO


Product description
Upright storage tank made of steel S235JR with bare-tube heat exchanger Enamelling in accordance with DIN 4753 Part 3 on the inside, primer applied to the outside Magnesium protection anode of 1 provided for completion of the cathodic corrosion protection in accordance with DIN 4753 Part 6 The temperature probes can be placed in variable positions due to the use of sensor terminal blocks All the connections are led upwards/external threads are flat sealing Separate circulation connection CFC free soft PU foam insulation with a thickness of 70 mm and a PVC coating, bottom insulation included, in accordance with DIN 4753 Part 8, RAL colours 9006; 9010; 2002; 5015 Compressive strength 10 bar

KW RL

Z WW VL

Storage tank model


Capacity Diameter without insulation Diameter with insulation Insulation Height with insulation Tilted height Heating area Water content*** Volume flow*** Pressure loss*** Performance index* according to DIN 4708 Continuous output according to DIN 4708 (10 / 80 / 45) max. T / max. P portable water max. T / max. P*** Cold / hot water, external thread (KW / WW) Circulation, external thread (Z) Electric heating, internal thread (E-HZG) Nominal width of the inspection flange (RFL) Connections for sensors / regulators Thermometer connection Weight Gross price incl. insulation

BSO
[litre] [mm] [mm] [mm] [mm] [mm] [m] [litre] [m/h] [mbar]

120
120 500 640 70 880 960 0,8 5,0 1,0 50 1,1

150
150 500 640 70 1035 1115 0,9 5,7 1,2 60 1,6 650 95 / 10 160 / 25 G G G for all storage tanks: No option DN 140 for all storage tanks: No option

200
200 500 640 70 1298 1380 7,5 1,4 70 2,0 840 95 / 10 160 / 25 G G G DN 140
Subject to changes due to advancements. We assume no liability for any errata or falsity in this product information sheet. www.cap-pr.de

1,2

[l/h] [C / bar] [C / bar] [inches] [inches] [inches]

520 95 / 10 160 / 25 G G G DN 140

Heat exchangers, all externally threaded (VL / RL) [inches]

for all storage tanks: Sensor terminal block [kg] [/piece] 81 753,87 829,98 902,-

* In order to achieve the performance index given here the boiler output needs to be higher than the stated continuous output. ** The working medium of the heat exchanger is water in liquid state only. *** Heat exchanger

Item no./Order no.: see p. 44 ff

www.huch.com e-mail: info@huch.com phone: +49 (0) 33920 - 6 72-0 fax: +49 (0) 33920 - 6 72 - 72/-68