ATC Application Handbook Section 2 Issue Date 0500

AHU Control
Duct type 2-pipe cooling, electric heater & dehumidification

Equipment Wiring

Operation Description Proportional plus integral temperature controller (TC-1) together with remote duct temperature sensor (TE-1) provides modulating control for the motorized cooling valve (TV-1), so as to maintain the desired return air temperature. Temperature controller (TC-1) also provides comfort/ Standby mode selection button and set point dial. Electronic humidistat (HS-1) together with remote duct humidity transmitter (HE-1) provides dehumidification. Once the return air R.H. increases above the set point, the cooling valve (TV-1) will be driven to its fully open position. Electronic heating thermostat (TS-1) together with its associated stage modules (SM-1) and remote duct temperature sensor (TE-2) provide on-off control of the 3 stages electric heater bank to reheat the supply air. A high limit cutout thermostat with manual reset (HL-1) is installed to de-energise the electric heaters in the event of excessive high temperature built up in the supply air duct. Air flow switch (FS-1) provides safety interlock such that electric heaters can only be energised when the fan running. The controller interlocks with the supply fan status, so that on fan shut down, the controller will be switched off, the cooling valve will be driven to its closed position, and the heaters will be de-energised. The differential pressure switch (DPS-1) monitors the status of filter, when the set point is exceeded, a signal will be given to switch on 'filter change' indicating lamp on the control panel. The smoke detector (SD-1) monitors the smoke status. Once smoke is detected, the fan will be shut down.

AHU-3

ATC Application Handbook Section 2 Issue Date 0500

AHU Control
Duct type 2-pipe cooling, electric heater & dehumidification

Equipment List
Instr. No. TE-1 TC-1 TE-2 TS-1 SM-1 HL-1 FS-1 HE-1 HS-1 SD-1 DPS-1 X-1 TV-1 Code No. TS-9104-8220 TC-8903-1132-WK A99DY-200C A27A1N11 S27A1 A25AN-9 F62AA-8 HT-9000-1D1 W27N11 DH100ACDCP ST-3 P32AC-2 Y62HKL-40 Refer to Valve Schedule (Section 3) Description Duct type temp. sensor 12/28 C, PI analogue controller, remote sensor, 24V Duct temperature sensor -40/40 C, din-railmount electronic thermostat, 24VAC Din-railmount stage module,24VAC Hi-limit cutout, manual reset, 237mm Air flow switch Duct type humidity transmitter 10/90% din-railmount humidity controller,24VAC Duct type smoke detector (Photo) Sampling Tube 0/5" W.C. differential pressure switch Transformer, 40VA, 240/220/24V Valve & Valve Actuator with 24 VAC power supply

Note: 1. R: Relay contact interlock with blower. 2. Refer to DH100 wiring diagram for wiring the smoke detector. (Attached at the end of this section) 3. If 3 way mixing valve instead of 2-way valve is used, the wiring at terminals 2 & 3 of the actuator TV-1 should be interchanged. 4. More stage modules can be connected to TS-1, for details, please refer to system 27 catalogue. 5. The jumper setting for directed or reversed control in TS-1 , SM-1 and HS-1should be refer to installation sheet.

AHU-3