PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
505E DIGITAL GOVERNOR UNTUK EXTRACTION STEAM TURBINE Umum Berbasis 32 bit Microprocessor Dapat di program , Satu desain Berdiri sendiri / di hubungkan dengan alat lain
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Operator Control Panel ( OCP ) Integrated dalam satu paket 2 Line (masing-masing 24 karakter ) 30 fungsi tombol
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Fitur Tambahan First Out Trip Critical speed (2 speed Band) Auto Start Seq. (Hot & Cold) Peak Speed Indikasi (Overspeed trip)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Normal Operating Mode Program Mode Run Mode Service Mode Password Program Mode : 1113 Service Mode : 1111
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Program Mode Program Mode digunakan untuk memilih opsi-opsi yang diperlukan untuk mengkonfigurasi control spesifik turbin aplikasi.
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Run Mode Run Mode digunakan untuk memonitor parameter parameter operasional saat turbine beroperasi dari start-up dan proses shutdown. Service Mode Service Mode digunakan untuk meningkatkan kinerja sistem operasi sementara unit sedang berjalan.
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Control Input 2 Speed Input 6 Analog Input 12 Contact Input 4 Function Key
Terminasi
Dedicated
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Control Output Dua Actuator Output Enam 4 20 mA Output Enam Relay Output
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol Scroll
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol Select
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol Adjust
Tombol Run Sebagai perintah start ketika unit dalam kondisi Ready to Start
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol Stop Memberi perintah control turbine shutdown (Run Mode), Perintah stop dapat di disable melalui Setting Service Mode (dibawah key option)
Tombol Reset Untuk mereset Run Mode alarm dan shutdown. Dengan menekan ini akan mengembalikan control ke status (Controlling Parameter/Push Run or Program) saat shutdown
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol 2/ACTR (Actuator) Memasukan angka 2 atau posisi actuator (Run Mode)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol 3/CONT (Control) Memasukan angka 3 atau menampilkan parameter yang sedang di kontrol (Run Mode)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol 4/CAS (Cascade) Memasukan angka 4 atau menampilkan informasi Cascade kontrol (Run Mode)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol 5/RMT (Remote) Memasukan angka 5 atau menampilkan informasi Remote Speed Setpoint (Run Mode)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol 6/LMTR (Limiter) Memasukan angka 6 atau menampilkan informasi valve limiter (Run Mode)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol 7/SPEED Memasukan angka 7 atau menampilkan informasi speed control (Run Mode)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol 8/AUX (Auxiliary) Memasukan angka 8 atau menampilkan informasi auxiliary control (Run Mode)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol 9/KW (Load) Memasukan angka 9 atau menampilkan KW/Load atau informasi first stage pressure (Run Mode)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol ENTER Memasukan nilai baru dalam program mode, dan memasukan secara langsung spesifik nilai setpoint dalan run mode
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol DYNAMIC (+/-) Mengakses dynamic setting kontrol parameter dalam posisi Run Mode
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol ALARM (F1) Menampilkan sebuah kondisi alarm ketika indikator LED tombol menyala (tekan tombol scroll untuk melihat alarm lainnya)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol OVERSPEED TEST ENABLE (F2) Mengijinkan speed reference di naikan melebihi maksimum kontrol speed setpoint untuk melakukan test electrical atau mekanikal overspeed test.
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Tombol F3 dan F4 (Function Key) Tombol yang dapat diprogram untuk fungsi yang lain
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
KOLOM KONFIGURASI UTAMA Turbine Start Start mode, Idle/rated,Auto start sequence Speed Control MPU dan Speed control dynamic setting Speed Setpoint Value Speed setpoint, overspeed Trip
setpoint, Remote setpoint dan Critical band Operating Parameter Aplikasi generator, Local/Remote Extraction/Adm Cntrl. Extraction/adm Control Driver Configuration Driver Output (ACT) Turbine Performance Value Ratio/Limiter, Steam Map Analog Input Analog Input Option Contact Input Contact input option
Worksheet
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
KOLOM KONFIGURASI TAMBAHAN Function Key F3 dan F4 Function Key Auxiliary Control Auxiliary Control Cascade Control Cascade control Read Outs Analog Read Out Relay Relay Function Communication Modbus Comminication
Worksheet
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
RESTROKE ACTUATOR Syarat Control harus kondisi shutdown (Emergency shutdown swicth close) Yakinkan TTV harus kondisi Close
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Restroke
Arus Maksimum actuator tidak dapat di adjust di bawah dari pada arus minimum actuator Arus Minimum actuator tidak dapat di adjust lebih besar dari pada arus maksimum actuator.
Driver Over current Under Current Max Output Current range Max Output Impedance Min Stop Adjust Range Max Stop Adjust Range 20-160 mA range 217 mA 5 mA 10-200 mA 45 ohms 10-80 mA 100-200 mA 4-20 mA range 26 mA 0.6 mA 2-24 mA 360 ohms 2-20 mA 10-24 mA
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
TURBINE START MODE Manual start mode Semi automatic start mode Automatic start mode STRAT PERMISSIVE Sebuah contact input dapat diprogram sebagai sebuah Start permissive bila diperlukan Setelah di tekan RUN maka contact start permissive tidak diperlukan lagi Biasanya diambil dari contact limit switch TTV
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
ZERO SPEED SIGNAL OVERRIDE 505E dapat di konfigurasi manual atau auto Bila auto maka lamanya zero override berdasarkan timer Status logic zero override dapat ditampilkan di service mode
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
START TURBINE Contact external shutdown harus close Contact permissive start harus close (bila di konfigurasi)
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Critical Speed Avoidance 2 range critical speed Speed setpoint tidak dapat di stop bila ada di critical speed Idle / Rated Setpoint akan ramp ke nilai idle speed set point Setpoint akan ramp ke rated speed setpoint jika perintah rated di berikan
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
AUTOMATIC START SEQUENCE Hot start ramp rate dan Hold time di pakai jika perintah RUN di berikan dan turbine telah shutdown dengan waktu lebih kecil dari setting waktu HOT START Cold start ramp rate dan Hold time dipakai jika perintah RUN di berikan dan turbine telah shutdown dengan waktu lebih lama dari setting waktu COLD START Bila perintah RUN di berikan dan lamanya shutdown di antara setting waktu HOT START dan COLD START, maka kontrol akan menetukan starting rate dan hold time diluar setting
Work sheet
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
AUTOMATIC START SEQUENCE Apabila unit telah trip selama 12 Jam, 505E akan menambah parameter diantara Hot dan Cold dan memakai rate dan delay seperti berikut ini : Low Idle Delay Rate To Hi Idle Hi Idle Delay Rate To Rated Hours Since Trip ( HRS ) = = = = = 20 10 10 15 12 MIN RPM/SEC MIN RPM/SEC HRS
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Speed Control
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Extraction Control
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
TURBINE START
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
STEAM MAP Steam map adalah sebuah bentuk grafik yang mewakili untuk range operasi dan pembatas pada sebuah ekstraksi dan atau Admission steam turbin. Saat turbin normal operasi dia harus berada didalam garis steam amplop.
Ketentuan Sebuah Map harus linear (semua garis harus lurus) Garis ekstraksi/admission flow = 0% dan ekstaksi/admission flow = 100% harus di parallel, dan garis LP valve = 0% dan LP valve 100% harus diparallel.
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
Nilai MAX POWER adalah beban dimana S = 100 garis silang pada sumbu S (sekitar 13498 KW dalam contoh gambar diatas. Nilai MAX HP FLOW adalah flow dimana HP = 100 garis silang pada sumbu HP (sekitar 95 T/H). Titik A adalah dimana perpotongan garis P = 0 dan LP = 100 (MAX POWER @ MIN EXTRACTION ; HP FLOW @ MIN EXTRACTION). Titik B adalah dimana perpotongan garis LP = 0 dan P = 100 (MIN POWER @ MAX EXTRACTION ; HP FLOW @ MAX EXTRACTION). Titik C adalah dimana perpotongan garis LP = 0 dan P = 0 (MIN POWER @ MIN EXTRACTION ; MIN HP FLOW @ MIN EXTRACTION ).
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
PELATIHAN DIGITAL GOVERNOR CONTROL POKJA HAR APPI BANDUNG, 5 - 9 APRIL 2010
S = HP = S = HP = S = HP = S = HP = S = HP = S = HP = S = HP = S = HP =
P LP P LP P LP P LP P LP P LP P LP P LP
= = = = = = = = = = = = = = = =