Documente Academic
Documente Profesional
Documente Cultură
Presented to
ADC
Flexible Duct Performance & Installation Standards (5th Edition)
Standard Length
25 Linear Feet
Diameter Range
2 12 (in 1 increments) 14 22 (in 2 increments)
Insulated Non Porous Inner Core Various types of Outer Vapor Barriers
Insulated Perforated Porous Inner Core Various types of Outer Vapor Barriers
Uninsulated
Uninsulated
Limited UL testing
What makes a good flexible duct installation? Key Points Design the flexible duct system per the requirements of ACCA Manual D. Use the flexible duct manufacturers air friction loss data to size the ducts whenever possible, otherwise use the chart in ACCA Manual D. Use the minimum length of flexible ducting needed to make the connections (Install fully extended). Keep bends greater than or equal to 1 duct diameter. Minimize sagging and snaking of the duct runs. Properly seal the flexible duct connections. Properly support the flexible ducting.
Key Point #1 Design the flexible duct system per the requirements of ACCA Manual D.
Represents a typical up-flow supply system for an approximate 1100 ft2 dwelling sized following the procedures in ACCA Manual D. Actual delivery was measured using an ALNOR Balometer.
Key Point #2
Use the flexible duct manufacturers air friction loss data to size the ducts whenever possible, otherwise use the chart in ACCA Manual D.
Key Point #3
Use the minimum length of flexible duct needed to make the connections. Install ducts extended to their fullest length without compression.
Compression causes increased pressure drop: 15% = approximate 2 times 30% = approximate 4 times 45% = approximate 6 to 8 times
Key Point #4
Keep bends greater than or equal to one (1) duct diameter. Minimize sagging and snaking of the duct runs.
Goals: 1. Make it easy for the air to change direction. 2. Reduce overall equivalent feet of the duct run.
45 = 10 equiv. ft.
Examples
If duct is 8 feet long then the total equivalent length = 28 feet.
For this installation the total equivalent length is nearly twice at approximately 50 feet.
Entrance & exit losses intentionally ignored for this demonstration.
The total pressure drop for any duct run equals the sum of the fitting (or bend) pressure drops and the pressure drop of the straight duct section.
Entrance fitting = Total duct length = 2 x 45 bends (2 x 10) = 1 x 90 bend (1 x 20) = Exit fitting = Total Equivalent Length =
Key Point #5
Properly seal the flexible duct connections.
Sleeves used to connect 2 flex duct pieces together shall be a minimum of 4 inches in length and beaded on each end.
Use tapes or mastics listed to the UL181B Standard and marked UL181BFX for tape and UL181B-M for mastic. If non-metallic straps are used, the straps should be listed to the UL181B Standard and marked UL181B-C. Maximum pressure is limited to 6 inches W.C. with non-metallic straps.
or
Key Point #6
Properly support the flexible ducting. Goals: 1. Never use wire or other materials less than 1-1/2 2. Minimal compression of insulation = better R-Value 3. Less sag or snaking of duct = better air flow
Select the proper duct R-value for the job & the codes!
R-4.2
R-6.0
R-8.0
Thermal Performance
- 30%
- 47%
1 4 7 *
2 5 8 0
3 6 9 #
The End
Visit ATCO at www.atcoflex.com Visit ADC at www.flexibleduct.org