Objective:
Purpose of this Exercise is to learn and understand: Input, output Assigning using Signal Matrix tool Indication LED assigning in SMT tool Parameter Setting Tool and its interface with the Application Configuration Tool (CAP 531) Getting familiar to SMT & PST download and Upload possibilities.
VIRTUAL INPUT AND OUTPUT ASSIGNING Now you can find the SIGNAL MATRIX & GRAPHICAL DISPLAY EDITOR when you Right click on the Plant structure.
Binary output assigning: You will be having 12 output contacts in your Input Output module, out of that which contact you want to make high for which output can be mapped with the help of signal matrix.
Similarly, Input what you want take to the relay can also be mapped with the help of signal matrix tool. NOTE: In our Exercise we have not used any Binary INPUT.
You can also assign LED for your particular output. Totally 15 User configurable LEDs available for ANNUNCIATION purpose
You can also Read the INPUTS and OUTPUTS which is already assigned in the IED by clicking the READ FROM IED icon shown in the figure.
Similarly after modifying your input and output, you can write these changes to the IED with the help of WRITE TO IED icon as shown in figure
Start the Parameter setting for the IED that you have used in the Previous Exercise.
Goto Setting General setting Analog modules Analog Input 6I and 6U Right click on Analog Input 6I and 6U, and then select the Parameter Setting.
CT Ratios Primary and Secondary In this Exercise out of 12 Analog channels first four channels (Current Channels) we have used for used for Overcurrent function.
To get this indication During a Fault it has to be enabled in the Parameter setting which is shown below.
You can set the LED in different mode. In this Example we have set LED in LatchedReset S. It means until you reset the LED, it will glow and indicate that Relay has tripped on O/C.
Set the PRE_ FAULT AND POST_ FAULR recording time here.
Analog signal that is used as phase reference from Disturbance Recorder in its Report (RPH_CU).
Set now general trio signal OC_TRIP to trigger Disturbance recorder, other signals will just be shown on the HMI. Example here for signal one.
Setting the Analog signals of Disturbance recorder Function: Set the analog signals that you want to be recorded (the first four).
Set
1. IBase as 1000A 2. OpMode 1 out of 3 3. IP>> as 200% If the Current exceeds 2000 A in Primary Overcurrent relay will TRIP.
UPLOAD AND DOWNLOAD OF PARAMETERS: Right click on REL 670 IEC in the plant structure, and then click PARAMETER SETTING
You can read the parameter FROM the relay with help of READ PARAMETER FROM IED icon as shown in figure.
You will be getting Read parameters from REL 670 IEC pop up window as shown in figure. Click OK to Read setting from the IED.
The changes you want to make can be made in the PC field as shown in figure.
After modifying the setting you can write these values to the IED with the help of WRITE PARAMETERS TO THE IED as shown in figure.
You will be getting Write parameters to REL 670 IEC Pop up window as shown in figure.