AIZ-10-L...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV 1L,2L,3L - 1,2,3 - horizontal flat bus- bar 63-125 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-10-1L63-4 UHL1-AIZ-10-4L125-4 UHL1
ic.
ic.D
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-L...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
10 12 75
13
30 10 2
ic.
ic.C
30
31,5
1480
see table
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ10-L...-4 UHL1
1274 hol. see table 13 The outdoor application of bus- bar supports AIZ-10-L are used for fixing the flat rigid bus- bars in horizontal position at 10 (20) kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-10-L are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
Rigid bus- bar support type AIZ-10-1L63-4UHL1 AIZ-10-1L80-4UHL1 AIZ-10-1L100-4UHL1 AIZ-10-1L125-4UHL1 AIZ-10-2L63-4UHL1 AIZ-10-2L80-4UHL1 AIZ-10-2L100-4UHL1 AIZ-10-2L125-4UHL1 AIZ-10-3L63-4UHL1
Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125 4/63 4/80 4/100 4/125
Picture
Building height H, mm 318 322 326 328 338 342 346 348 358 362 366 368 378 382 386 388
Weight, kg 6,2 6,2 6,3 6,5 6,5 6,5 6,6 6,7 6,7 6,8 6,8 6,9 6,9 7,0 7,0 7,2
C C C C D D D D
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid
AIZ-10-4L100-4UHL1 AIZ-10-4L125-4UHL1
229
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-10-P...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV P - the box-shaped rigid bus- bars 100-250 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-P...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
10 12 75
13
30 10 2 30
13
31,5
4 hol.
159
1480
127
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
Rigid bus- bar support type AIZ-10-P100-4 UHL1 AIZ-10-P125-4 UHL1 AIZ-10-P150-4 UHL1 AIZ-10-P175-4 UHL1 AIZ-10-P200-4 UHL1 AIZ-10-P225-4 UHL1 AIZ-10-P250-4 UHL1
Width of box of bus- bar mm 100 125 150 175 200 225 250
329 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR FOR THE 10KV CURRENT AIZ-10-1M63-4 UHL1-AIZ-10-3M125-4 UHL1
AIZ-10-...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV 1M,2M,3M - 1,2,3 - flat vertical bus-bars 69-125 - width of vertical bus-bar in mm. 4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
10 12 75
13
30 10 2 30
13 4 hol. 159
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN
ic.
Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg
31,5
127
1480
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ-10-...-4 UHL1
The outdoor application of bus- bar supports AIZ-10-M are used for fixing the flat rigid bus- bars in vertical position at 10 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-10-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
TYPE TESTS FOR AIZ-10-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Rigid bus- bar support type AIZ-10-1M63-4UHL1 AIZ-10-1M80-4UHL1 AIZ-10-1M100-4UHL1 AIZ-10-1M125-4UHL1 AIZ-10-263-4UHL1 AIZ-10-280-4UHL1 AIZ-10-2100-4UHL1 AIZ-10-2125-4UHL1 AIZ-10-363-4UHL1 AIZ-10-380-4UHL1 AIZ-10-3100-4UHL1 AIZ-10-3125-4UHL1
Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125
Picture A A A A C C C C
Building height H, mm 362 380 400 425 362 380 400 425 362 380 400 425
Weight, kg 5,90 5,96 6,09 6,15 5,92 5,98 6,11 6,17 5,94 6,00 6,13 6,19
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
29
AIZ-10-Z...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV Z -rigid connection of aluminium tubular bus-bar 30-250- diameter of aluminium tubular bus-bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV
10 12 75
ic.1
ic.2
Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm
13
30 10 2 30
13 4 hol.
159
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
31,5
1480
127
Weight, not more than, kg TYPE TESTS FOR AIZ-10-Z...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus- bar support type AIZ-10-Z30-4UHL1 AIZ-10-Z40-4UHL1 AIZ-10-Z50-4UHL1 AIZ-10-Z70-4UHL1 AIZ-10-Z80-4UHL1 AIZ-10-Z90-4UHL1 AIZ-10-Z100-4UHL1 AIZ-10-Z110-4UHL1 AIZ-10-Z120-4UHL1 AIZ-10-Z130-4UHL1 AIZ-10-Z140-4UHL1 AIZ-10-Z150-4UHL1 AIZ-10-Z170-4UHL1 AIZ-10-Z200-4UHL1 AIZ-10-Z250-4UHL1
ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1
Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 359 359 360 370 378 382 394 400 402 415 420 430 450 470 495 12,8 12,9 13,2 13,5 14,7 15,0 15,2 13,5 14,0 18,0 18,0 19,1 20,2 24,3 30,2
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
29
AIZ-10-SH...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV SH - hinging of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-10-SH50-4UHL- AIZ-10-SH250-4 UHL
rotation angle
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
10 12 75
13
30 10 2 30
13 4 hol.
159
31,5
1480
127
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-10-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-10-SH are used for hinged fastening of tubular rigid bus-bar at 10 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-10-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
Rigid bus- bar support type AIZ-10-SH50-4UHL1 AIZ-10-SH60-4UHL1 AIZ-10-SH70-4UHL1 AIZ-10-SH80-4UHL1 AIZ-10-SH90-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 370 380 405 410 410 415 425 425 435 440 440 460 470 495 15,0 15,0 15,5 16,0 16,4 17,0 17,5 17,5 18,0 18,5 18,7 20,5 22,2 23,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-10-SH250-4UHL1
629
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-10-D...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports
movement direction
10 - nominal voltage, kV D-movable fastening of aluminium tubular bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm
10 12 75 13
30 10 2 30
13 4 hol.
159
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm
31,5
1480
127
Weight, not more than, kg TYPE TESTS FOR AIZ-10-D...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus- bar support type AIZ-10-D50-4UHL1 AIZ-10-D60-4UHL1 AIZ-10-D70-4UHL1 AIZ-10-D80-4UHL1 AIZ-10-D90-4UHL1 AIZ-10-D100-4UHL1 AIZ-10-D110-4UHL1 AIZ-10-D120-4UHL1 AIZ-10-D130-4UHL1 AIZ-10-D140-4UHL1 AIZ-10-D150-4UHL1 AIZ-10-D170-4UHL1 AIZ-10-D200-4UHL1 AIZ-10-D250-4UHL1
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 370 380 405 410 410 415 425 425 435 440 440 460 470 495 15,0 15,0 15,5 16,0 16,4 17,0 17,5
50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
29
AIZ-10-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV - end fastening of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-10-50-4 UHL1 - AIZ-10-250-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
10 12 75
13
30 10 2
30
13 4 hol.
159
31,5
1480
127
1 1274 hol. see table 13
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 335 338 365 370 370 385 385 390 400 410 440 460 490 495 12,0 12,0 12,1 12,2 12,4 12,7 14,5 14,8 14,9 15,0 15,3 15,5 15,7 15,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-10-80-4UHL1 AIZ-10-90-4UHL1 AIZ-10-100-4UHL1 AIZ-10-110-4UHL1 AIZ-10-120-4UHL1 AIZ-10-130-4UHL1 AIZ-10-140-4UHL1 AIZ-10-150-4UHL1 AIZ-10-170-4UHL1 AIZ-10-200-4UHL1 AIZ-10-250-4UHL1
829
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE AIZ-10-I-4UHL1 AIZ-10-I...-4 UHL1
AIZ-10-I...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV I -movable connection of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar
movement direction
movement direction
4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
10 12 75 13
30 10 2 30
13 4 hol.
159
Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm
31,5
127
1480
Rigid bus- bar support type AIZ-10-I50-4UHL1 AIZ-10-I60-4UHL1 AIZ-10-I70-4UHL1 AIZ-10-I80-4UHL1 AIZ-10-I90-4UHL1 AIZ-10-I100-4UHL1 AIZ-10-I110-4UHL1 AIZ-10-I120-4UHL1 AIZ-10-I130-4UHL1 AIZ-10-I140-4UHL1 AIZ-10-I150-4UHL1 AIZ-10-I170-4UHL1 AIZ-10-I200-4UHL1 AIZ-10-I250-4UHL1
Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 370 380 405 410 410 415 425 425 435 440 440 460 470 495
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
29
AIZ-10-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-10-50-4 UHL1 - AIZ-10-250-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
10 12 75
H
13
30 10 2 30
13 4 hol.
159
31,5
1480
127
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 360 370 370 378 394 400 400 402 415 430 430 450 470 470 13,0 13,0 13,1 13,2 13,4 13,7 15,5 15,8 15,9 16,0 16,3 16,5 16,7 16,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-10-80-4UHL1 AIZ-10-90-4UHL1 AIZ-10-100-4UHL1 AIZ-10-110-4UHL1 AIZ-10-120-4UHL1 AIZ-10-130-4UHL1 AIZ-10-140-4UHL1 AIZ-10-150-4UHL1 AIZ-10-170-4UHL1 AIZ-10-200-4UHL1 AIZ-10-250-4UHL1
10 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-10-S...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV S - for the installation of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar
movement D direction
movement direction
4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
10 12 75
L 13 4 hol.
13
30 10 2 30
159
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm
127
Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm
31,5
Installation choices for bus- bar. The arrows indicate the axis of the aluminum tubes of rigid bus- bar.
1480
Weight, not more than, kg TYPE TESTS FOR AIZ -10-C...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus- bar support type AIZ-10-50-4UHL1 AIZ-10-60-4UHL1 AIZ-10-70-4UHL1 AIZ-10-80-4UHL1 AIZ-10-90-4UHL1 AIZ-10-100-4UHL1 AIZ-10-110-4UHL1 AIZ-10-120-4UHL1 AIZ-10-130-4UHL1 AIZ-10-140-4UHL1 AIZ-10-150-4UHL1 AIZ-10-170-4UHL1 AIZ-10-200-4UHL1 AIZ-10-250-4UHL1
Size L, 870 870 870 870 870 870 870 870 870 870 870 870 870 870
Diameter Diameter of rigid bus-bar D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 620 630 655 660 660 665 675 685 685 690 690 710 740 780 30,5 31,6 32,0 33,0 34,2 35,0 35,5
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
11
29
AIZ-10-GL...-4 UHL1
CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV GL - go with a flexible busbar on flat bus- bar 2/8-2/100 - modification of the cross section of bus- bar and wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
POLYMER BUS-BAR SUPPORTS INTENDED FOR TRANSITION FROM FLEXIBLE TO RIGID BUS-BARS AIZ-10-GL2/8-2/100-4 UHL1 - AIZ-10-GL2/24-4/125-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ -10-GL...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
10 12
L
75
13
30 10 2 30
13 4 hol.
159
31,5
1480
127
see table 1274 hol. see table 13
BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ-10-GL...-4 UHL1
The outdoor bus- bar supports AIZ-10-GL are used for transition from flexible to flat horizontal bus-bars with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
Rigid bus- bar support type AIZ-10-GL2/8-2/100-2 UHL1 AIZ-10-GL2/12-3/125-2 UHL1 AIZ-10-GL2/12-4/125-2 UHL1 AIZ-10-GL2/16-3/125-2 UHL1 AIZ-10-GL2/16-4/125-2 UHL1 AIZ-10-GL2/20-3/125-2 UHL1 AIZ-10-GL2/20-4/125-2 UHL1
Number flexible wires bus- bar 2+8 2+12 2+12 2+16 2+16 2+20 2+20
12 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTANAIZ, +7-717-296-5353 LITHUANIA www.bus-bar.eu +370-62749925
AIZ-35-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ-35-...-4 UHL1
AIZ-35-...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports
35- nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 35 40,5 190
13
4 hol.
42
159
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
20 10
1
95
127
31,5
1480
B
POLYMER BUS-BAR SUPPORTS AIZ-35-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Busbar supports for the 10-220 kV voltage. The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in Siberia Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works.
Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-A...-4 UHL1 Assemblage
1 1274 hol. 14 13
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
, KP
PM
2
Nominal cross-section, kv, mm AIZ-35-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27
17,5 - 22,1
470
AIZ-35-2-4 UHL1
24,0 - 29,4
473
Hydrophobic resistance to water
500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -
240, 300 -
500
476 482
13
29
AIZ-35-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 35 - nominal voltage, kV B - modification of bus-bar support for two wires 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
AIZ-35-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--35-B...-4 UHL1
60
35 40,6 190
42
13
4 hol.
20 10 1 95
159
31,5
127
1480
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-B...-4 UHL1 Assemblage
B
2 1274 hol. 13 14
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level
, KP
PM
2
AIZ-35-B1-4 UHL1
Nominal cross-section, kv, mm 185/24; 185/29; 185; 240; 300 205/27; 240/32; 240/39
350; 400 450; 500 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27 -
17,5 - 22,1
470
AIZ-35-B2-4 UHL1
Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body
24,0 - 29,4
473
500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -
240, 300 -
500
476 485
14 29
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ,RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
AIZ-35-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 35 - nominal voltage, kV G - modification for three hollow wires 1,2 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTIC Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 35 40,5 190
AIZ-35-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBLE BUS-BAR AIZ-35-G...-4 UHL1
Pic.1
Pic.2
42
20
10 1 95
13 4 hol.
159
31,5
127
1480
13
TYPE TESTS FOR AIZ-35-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
Pic.
H max, mm
Weight , kg
AIZ-35-G1-4 UHL1
Evaluation of partial discharge level Hydrophobic resistance to water
500
65
45,0
482
17,8
AIZ-35-G2-4 UHL1
Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body
500
120
45,0
502
18,0
AIZ-35-G3-4 UHL1
GOST R 52082-03, TS3494-005-59116459-05
500
200
45,0
502
18,0
15 29
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ,RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
AIZ-35-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ-35-V...-4 UHL1
AIZ-35-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 35 - nominal voltage, kV V- modification for two hollow wires
1,2 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTIC Nominal voltage, kV 35 40,5 190
Pic.1
Pic.2
Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm
42
20 10 1 95
13 4 hol.
159
Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
31,5
127
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
1480
Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-V...-4 UHL1 Assemblage
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )
Pic.
Diameter of wires, mm
H max, mm
Weight , kg
Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ-35-V1-4 UHL1
500
65
45,0
482
17,8
AIZ-35-V2-4 UHL1
500
120
45,0
502
18,0
Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-35-V3-4 UHL1
500
200
45,0
502
18,0
GOST R 52082-03, TS3494-005-59116459-07
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 w ww.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
16
29
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR FOR THE 35KV CURRENT AIZ-35-163-4 UHL1-AIZ-35-3125-4UHL1
AIZ-35-...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV 1M,2M,3M - 1,2,3 -flat vertical bus-bars 69-125 - width of vertical bus-bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694
climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
35 40,5 190 42
20 10 1 95
13 4 hol. 159
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN
ic.
Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm
127
31,5
1480
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ-35-...-4 UHL1
The outdoor application of bus- bar supports AIZ-35-M are used for fixing the flat rigid bus- bars in vertical position at 35 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-35-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
Weight, not more than, kg TYPE TESTS FOR AIZ-35-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Rigid bus- bar support type AIZ-35-1M63-4UHL1 AIZ-35-1M80-4UHL1 AIZ-35-1M100-4UHL1 AIZ-35-1M125-4UHL1 AIZ-35-263-4UHL1 AIZ-35-280-4UHL1 AIZ-35-2100-4UHL1 AIZ-35-2125-4UHL1 AIZ-35-363-4UHL1 AIZ-35-380-4UHL1 AIZ-35-3100-4UHL1 AIZ-35-3125-4UHL1
Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125
Picture A A A A C C C C
Building height H, mm 482 500 520 545 482 500 520 545 482 500 520 545
Weight, kg 7,90 7,96 8,09 8,15 7,92 7,98 8,11 8,17 7,94 8,00 8,13 8,19
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
17
29
AIZ-35-L...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV 1L,2L,3L - 1,2,3 - flat horizontal bus- bar 63-125 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-35-1L63-4 UHL1 - AIZ-35-4L125-4 UHL1
ic.
ic.D
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-L...-4 UHL1 Assemblage External inspection ( outer view and marking )
35 40,5 190
42
20 10 1
ic.
ic.C
95
31,5
1480
see table
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-35-L...-4 UHL1
1274 hol. see table 13 The outdoor application of bus- bar supports AIZ-35-L are used for fixing the flat rigid bus- bars in horizontal position at 35 kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-35-L are included in the integrated rigid bus- bar project of substations.Useful service life- 30 years.
Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125 4/63 4/80 4/100 4/125
Picture
Building height H, mm 438 442 446 448 458 452 456 468 478 482 486 488 498 502 506 508
Weight, kg 8,2 8,2 8,3 8,5 8,5 8,5 8,6 8,7 8,7 8,8 8,8 8,9 8,9 9,0 9,0 9,2
C C C C D D D D
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ-35-3L80-4UHL1
Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid
AIZ-35-4L100-4UHL1 AIZ-35-4L125-4UHL1
18 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
POLYMER BUS-BAR SUPPORTSS INTENDED FOR TRANSITION FROM FLEXIBLE TO FLAT HORIZOTAL BUS-BARS AIZ-35-GL2/8-2/100-4 UHL1 - AIZ-35-GL2/24-4/125-4 UHL1
AIZ-35-GL...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35 - nominal voltage, kV GL - go with a flexible busbar on flat bus- bar
2/8-2/100 - modification of the cross section of bus- bar and wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1
climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
35 40,5 190 42
20 10 1 95
Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm
13 4 hol.
159
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
31,5
1480
127
BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ-35-GL...-4 UHL1
The outdoor bus- bar supports AIZ-35-GL are used for transition from flexible to flat horizontal bus-bars with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
Weight, not more than, kg TYPE TESTS FOR AIZ-35-GL...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Rigid bus- bar support type AIZ-35-GL2/8-2/100-2 UHL1 AIZ-35-GL2/12-3/125-2 UHL1 AIZ-35-GL2/12-4/125-2 UHL1 AIZ-35-GL2/16-3/125-2 UHL1 AIZ-35-GL2/16-4/125-2 UHL1 AIZ-35-GL2/20-3/125-2 UHL1 AIZ-35-GL2/20-4/125-2 UHL1
Number flexible wires bus- bar 2+8 2+12 2+12 2+16 2+16 2+20 2+20
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
19
29
AIZ-35-P...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV P - box shaped buses 100-250 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-35-P100-4 UHL1 - AIZ-35-P250-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-P...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
35 40,5 190
42
20 10 1 90
13 4 hol.
159
31,5
1480
127
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
Rigid bus- bar support type AIZ-35-P100-4 UHL1 AIZ-35-P125-4 UHL1 AIZ-35-P150-4 UHL1 AIZ-35-P175-4 UHL1 AIZ-35-P200-4 UHL1 AIZ-35-P225-4 UHL1 AIZ-35-P250-4 UHL1
Width of box of bus- bar mm 100 125 150 175 200 225 250
20 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-35-Z...-4 UHL1
CONDITIONAL DESIGNATION AIZ -brand brandof ofpolymeric polymericbusbus-bar barsupports supports AIZ35 10-- nominal voltage, kV
D
Z -rigid -rigidfastening fasteningof ofaluminum aluminumtube tubebusbus-bar bar 30-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL UHL1 1climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS
ic.1
i.2
Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm
35 10 40,5 12 190 75 42 13
2 30 0 10 1 2 95 30
13 4 hol.
159
Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
31,5 31,5
127
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted
1480 1480
Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-...-4 AIZ-35-Z...-4 UHL UHL1 1 Assemblage
Rigid bus- bar support type AIZ-35-Z30-4UHL1 AIZ-35-Z40-4UHL1 AIZ-35-Z50-4UHL1 AIZ-35-Z70-4UHL1 AIZ-35-Z80-4UHL1 AIZ-35-Z90-4UHL1 AIZ-35-Z100-4UHL1 AIZ-35-Z110-4UHL1 AIZ-35-Z120-4UHL1 AIZ-35-Z130-4UHL1 AIZ-35-Z140-4UHL1 AIZ-35-Z150-4UHL1 AIZ-35-Z170-4UHL1 AIZ-35-Z200-4UHL1 AIZ-35-Z250-4UHL1
ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1
Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 519 519 520 530 538 542 554 560 562 575 580 590 610 630 655 16,1 16,2 16,5 16,8 18,0 18,3 18,5 18,7 19,3 21,3 21,3 22,4 23,5 27,5 33,5
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation Deviationangle anglecontrol controlat atbending bending ( (torsion torsion) )and and absence absenceof of plastic plasticdeformation deformationat atbending bending( (torsion torsion) ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
21
29
AIZ-35-SH...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-35-SH50-4 UHL1 - AIZ-35-SH250-4 UHL1
D
35- nominal voltage, kV SH - hinging of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
35 40,5 190
20 10 1 95
42
13 4 hol.
159
31,5
1480
127
1 1274 hol. see table 13
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-35-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-35-SH are used for hinged fastening of tubular rigid bus-bar at 35 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-35-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
Rigid bus- bar support type AIZ-35-SH50-4UHL1 AIZ-35-SH60-4UHL1 AIZ-35-SH70-4UHL1 AIZ-35-SH80-4UHL1 AIZ-35-SH90-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 530 540 565 570 570 575 585 585 595 600 600 620 650 655 18,0 18,0 18,5 19,0 19,4 20,0 20,5 20,5 21,0 21,5 21,7 23,5 25,2 26,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-35-SH250-4UHL1
22 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-35-D...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports
35- nominal voltage, kV D-movable fastening of aluminium tubular bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 35 40,5 190
42
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN
20 10 1 95
13 4 hol.
159
Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted
31,5
1480
127
Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-D...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus- bar support type AIZ-35-D50-4UHL1 AIZ-35-D60-4UHL1 AIZ-35-D70-4UHL1 AIZ-35-D80-4UHL1 AIZ-35-D90-4UHL1 AIZ-35-D100-4UHL1 AIZ-35-D110-4UHL1 AIZ-35-D120-4UHL1 AIZ-35-D130-4UHL1 AIZ-35-D140-4UHL1 AIZ-35-D150-4UHL1 AIZ-35-D170-4UHL1 AIZ-35-D200-4UHL1 AIZ-35-D250-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 530 540 565 570 570 575 585 585 595 600 600 620 650 655
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
23
29
AIZ-35-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV - end fastening of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ35-50-4 UHL1 -AIZ35-250-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
35 40,5 190
42
20 10 1 95
13 4 hol.
159
31,5
127
1480
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 495 498 525 530 530 545 545 550 560 570 600 620 650 655
Weight, kg
15,0 15,0 15,1 15,2 15,4 15,7 17,5 17,8 17,9 18,0 18,3 18,5 18,7 18,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-35-80-4UHL1 AIZ-35-90-4UHL1 AIZ-35-100-4UHL1 AIZ-35-110-4UHL1 AIZ-35-120-4UHL1 AIZ-35-130-4UHL1 AIZ-35-140-4UHL1 AIZ-35-150-4UHL1 AIZ-35-170-4UHL1 AIZ-35-200-4UHL1 AIZ-35-250-4UHL1
24 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-35-I...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35 - nominal voltage, kV I -movable connection of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 35 40,5 190
13 4 hol.
159
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN
42
20 10 1 95
127
Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ- 35-I...-4 UHL1 Assemblage External inspection ( outer view and marking )
31,5
1480
Rigid bus- bar support type AIZ-35-I50-4UHL1 AIZ-35-I60-4UHL1 AIZ-35-I70-4UHL1 AIZ-35-I80-4UHL1 AIZ-35-I90-4UHL1 AIZ-35-I100-4UHL1 AIZ-35-I110-4UHL1 AIZ-35-I120-4UHL1 AIZ-35-I130-4UHL1 AIZ-35-I140-4UHL1 AIZ-35-I150-4UHL1 AIZ-35-I170-4UHL1 AIZ-35-I200-4UHL1 AIZ-35-I250-4UHL1
Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 530 540 565 570 570 575 585 585 595 600 600 620 650 655
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
25
29
AIZ-35-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-35-50-4 UHL1 -AIZ35-250-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
35 40,5 190
42
20 10 1 95
13 4 hol.
159
31,5
127
1480
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 520 530 530 538 554 560 560 562 575 590 590 610 630 630
Weight, kg
16,0 16,0 16,1 16,2 16,4 16,7 18,5 18,8 18,9 19,0 19,3 19,5 19,7 19,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-35-80-4UHL1 AIZ-35-90-4UHL1 AIZ-35-100-4UHL1 AIZ-35-110-4UHL1 AIZ-35-120-4UHL1 AIZ-35-130-4UHL1 AIZ-35-140-4UHL1 AIZ-35-150-4UHL1 AIZ-35-170-4UHL1 AIZ-35-200-4UHL1 AIZ-35-250-4UHL1
26 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-35-S...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35 - nominal voltage, kV
S - for the installation of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
L 13 4 hol.
159
Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm
42
20 10 1 95
127
Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
Installation choices for bus- bar. The arrows indicate the axis of the aluminum tubes of rigid bus- bar.
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm
31,5
1480
Weight, not more than, kg TYPE TESTS FOR AIZ-35-C...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus- bar support type AIZ-35-50-4UHL1 AIZ-35-60-4UHL1 AIZ-35-70-4UHL1 AIZ-35-80-4UHL1 AIZ-35-90-4UHL1 AIZ-35-100-4UHL1 AIZ-35-110-4UHL1 AIZ-35-120-4UHL1 AIZ-35-130-4UHL1 AIZ-35-140-4UHL1 AIZ-35-150-4UHL1 AIZ-35-170-4UHL1 AIZ-35-200-4UHL1 AIZ-35-250-4UHL1
Size L, 870 870 870 870 870 870 870 870 870 870 870 870 870 870
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 620 630 655 660 660 665 675 685 685 690 690 710 740 780
Weight, kg Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
27
29
AIZ-110-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ-110-A...-4 UHL1
AIZ-110-...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 110 - nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 110 126 450
18
H
4 hol.
110
220
For specified surface conductivity mkCm G, of polluted layer, Minimum failing load at GB, , bending, kN Minimum failing torsion , , moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
10 10 1 280
178
40
1480
1 1784 hol. 18 24
B
POLYMER BUS-BAR SUPPORTS AIZ-110-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury
Weight, not more than, kg TYPE TESTS FOR AIZ-110-A...-4 UHL1 Assemblage
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
, KP
PM
2
Nominal cross-section, kv, mm AIZ-110-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27
17,5 - 22,1
1130
Evaluation of partial discharge level
AIZ-110-2-4 UHL1
24,0 - 29,4
1133
500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -
240, 300 -
500
1136 1142
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
28
29
AIZ-110-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 110 - nominal voltage, kV B - modification of bus-bar support for two wires
AIZ-110-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--110-B...-4 UHL1
4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-B...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
18
110
220
4 hol.
10 10 1 280
178
40
1480
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage.
Nominal cross-section, mm AIZ-110-B1-4 UHL1 AIZ-110-B2-4 UHL1 AIZ-110-B3-4 UHL1 AIZ-110-B5-4 UHL1 AIZ-110-B6-4 UHL1 AIZ-110-B7-4 UHL1 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body
185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300
AIZ-110-B8-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 AIZ-110-B9-4 UHL1 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 AIZ-110-B10-4 UHL1 700; 750 650/79; 700/86; 240;300 AIZ-110-B11-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 AIZ-110-B12-4 UHL1 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 AIZ-110-B13-4 UHL1 700; 750 650/79; 700/86; 240;300
R
29 29
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
AIZ-110-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--110-V...-4 UHL1
AIZ-110-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 110 - nominal voltage, kV V- modification for two hollow wires 1,2,3 - modification according cross section and type of wire
Pic.1
Pic.2
4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 110 126 450
18
4 hol.
110
220
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion , , moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
10 10 1 280
178
Connection dimensions of bottom flange
40
1480
2 1784 hol.
see table
18
Weight, not more than, kg TYPE TESTS FOR AIZ-110-V...-4 UHL1 Assemblage
Pic.
H max, mm
Weight , kg
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
AIZ-110-1-4 UHL1
500
65
45,0
1142
27,8
AIZ-110-2-4 UHL1
500
120
45,0
1162
28,0
Hydrophobic resistance to water Hydrophobic resistance to colouring liquid
AIZ-110-3-4 UHL1
500
200
45,0
1162
28,0
Adhesion of coating layer to insulating body
30
29
AIZ-110-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 110 - nominal voltage, kV G - modification for three hollow wires 1,2,3 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
AIZ-110-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBLE BUS-BAR AIZ-110-G...-4 UHL1
110
10
18
10 1 280
4 hol.
220
40
178
1480
Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg
TYPE TESTS FOR AIZ-110-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
Pic.
H max, mm
Weight , kg
AIZ-110-G1-4 UHL1
Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body
500
65
45,0
1142
27,8
AIZ-110-G2-4 UHL1
500
120
45,0
1162
28,0
AIZ-110-G3-4 UHL1
500
200
45,0
1162
28,0
31 29
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
AIZ-110-P...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 - nominal voltage, kV P - box shaped buses 100-250 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-110-P100-4 UHL1 -AIZ110-P250-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
110
10 1 280
10
18 4 hol.
220
40
1480
178
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
Rigid bus- bar support type AIZ-110-P100-4 UHL1 AIZ-110-P125-4 UHL1 AIZ-110-P150-4 UHL1 AIZ-110-P175-4 UHL1 AIZ-110-P200-4 UHL1 AIZ-110-P225-4 UHL1 AIZ-110-P250-4 UHL1
Width of box of bus- bar mm 100 125 150 175 200 225 250
32 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR FOR THE 110KV CURRENT AIZ110-163-4 UHL1-AIZ-110-3125-4UHL1
AIZ-110-...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 - nominal voltage, kV 1M,2M,3M - 1,2,3 -flat vertical bus- bar 69-125 -width vertical of the bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694
UHL1 i. i.C
climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
18 4 hol. 220
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN
i.
10 10 1 28
Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm
40
178
1480
BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ110-...-4 UHL1
The outdoor application of bus- bar supports AIZ-110-M are used for fixing the flat rigid bus- bars in vertical position at 110 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-110-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
Weight, not more than, kg TYPE TESTS FOR AIZ-110-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Rigid bus- bar support type AIZ-110-1M63-4UHL1 AIZ-110-1M80-4UHL1 AIZ-110-1M100-4UHL1 AIZ-110-1M125-4UHL1 AIZ-110-263-4UHL1 AIZ-110-280-4UHL1 AIZ-110-2100-4UHL1 AIZ-110-2125-4UHL1 AIZ-110-363-4UHL1 AIZ-35-380-4UHL1 AIZ-35-3100-4UHL1 AIZ-35-3125-4UHL1
Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125
Picture A A A A C C C C
Building height H, mm 1182 1200 1220 1245 1182 1200 1220 1245 1182 1200 1220 1245
Weight, kg 17,90 17,96 18,09 18,15 17,92 17,98 18,11 18,17 17,94 18,00 18,13 18,19
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
33
29
AIZ-110-L...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110- nominal voltage, kV 1L,2L,3L - 1,2,3 -flat horizontal bus- bar 63-125 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-110-1L63-4 UHL1 -AIZ-110-4L125-4 UHL1
i.
i.D
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-L...-4 UHL1 Assemblage External inspection ( outer view and marking )
110
10 10 1
i.
i.C
280
40
1480
BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ110-L...-4 UHL1
The outdoor application of bus- bar supports AIZ-110-L are used for fixing the flat rigid bus- bars in horizontal position at 110 kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-110-L are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.
Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125 4/63 4/80 4/100 4/125
Picture C C C C D D D D
Building height H, mm 1138 1142 1146 1148 1158 1152 1156 1168 1178 1182 1186 1188 1198 1202 1206 1208
Weight, kg 18,2 18,2 18,3 18,5 18,5 18,5 18,6 18,7 18,7 18,8 18,8 18,9 18,9 19,0 19,0 19,2
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
34 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-110-Z...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 - nominal voltage, kV Z -rigid fastening of aluminum tube bus- bar 30-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694
Pic.1
i.2
UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm 110 126 450
18 4 hol. 220
110
10 10 1 280
Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
178
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg
40
1480
Rigid bus- bar support type AIZ-110-Z30-4UHL1 AIZ-110-Z40-4UHL1 AIZ-110-Z50-4UHL1 AIZ-110-Z70-4UHL1 AIZ-110-Z80-4UHL1 AIZ-110-Z90-4UHL1 AIZ-110-Z100-4UHL1 AIZ-110-Z110-4UHL1 AIZ-110-Z120-4UHL1 AIZ-110-Z130-4UHL1 AIZ-110-Z140-4UHL1 AIZ-110-Z150-4UHL1 AIZ-110-Z170-4UHL1 AIZ-110-Z200-4UHL1 AIZ-110-Z250-4UHL1
ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1
Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 1179 1179 1180 1190 1198 1202 1214 1220 1222 1235 1240 1250 1270 1290 1315 26,1 26,2 26,5 26,8 28,0 28,3 28,5 28,7 29,3 31,3 31,3 32,4 33,5 37,5 43,5
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
35
29
AIZ-110-SH...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110- nominal voltage, kV SH - hinging of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-110-SH50-4 UHL1 -AIZ110-SH250-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
110
10 10 1 280
18 4 hol.
220
40
178
1480
The bus- bar supports of outdoor application AIZ-110-SH are used for hinged fastening of tubular rigid bus-bar at 110 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-110-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.The factory can supply POLYMER BUSBAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ110-SH...-4 UHL1
Rigid bus- bar support type AIZ-110-SH50-4UHL1 AIZ-110-SH60-4UHL1 AIZ-110-SH70-4UHL1 AIZ-110-SH80-4UHL1 AIZ-110-SH90-4UHL1 AIZ-110-SH100-4UHL1 AIZ-110-SH110-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1190 1200 1225 1230 1230 1235 1245 1245 1255 1260 1260 1280 1310 1315
Weight, kg
28,0 28,0 28,5 29,0 29,4 30,0 30,5 30,5 31,0 31,5 31,7 33,5 35,2 36,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid
AIZ-110-SH200-4UHL1 AIZ-110-SH250-4UHL1
36 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-110-D...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110- nominal voltage, kV D-movable fastening of aluminium tubular bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 110 126 450
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm
110
10 10 1 280
18 4 hol.
220
Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
40
178
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-D...-4 UHL1 Assemblage
1480
Rigid bus- bar support type AIZ-110-D50-4UHL1 AIZ-110-D60-4UHL1 AIZ-110-D70-4UHL1 AIZ-110-D80-4UHL1 AIZ-110-D90-4UHL1 AIZ-110-D100-4UHL1 AIZ-110-D110-4UHL1 AIZ-110-D120-4UHL1 AIZ-110-D130-4UHL1 AIZ-110-D140-4UHL1 AIZ-110-D150-4UHL1 AIZ-110-D170-4UHL1 AIZ-110-D200-4UHL1 AIZ-110-D250-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1190 1200 1225 1230 1230 1235 1245 1245 1255 1260 1260 1280 1310 1315
Weight, kg
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
37
29
AIZ-110-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110-nominal voltage, kV - end fastening of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ110-...-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
110
10 10 1 280
18 4 hol.
220
40
178
1480
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1155 1158 1185 1190 1190 1205 1205 1210 1220 1230 1260 1280 1310 1315
Weight, kg
25,0 25,0 25,1 25,2 25,4 25,7 27,5 27,8 27,9 28,0 28,3 28,5 28,7 28,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-110-80-4UHL1 AIZ-110-90-4UHL1 AIZ-110-100-4UHL1 AIZ-110-110-4UHL1 AIZ-110-120-4UHL1 AIZ-110-130-4UHL1 AIZ-110-140-4UHL1 AIZ-110-150-4UHL1 AIZ-110-170-4UHL1 AIZ-110-200-4UHL1 AIZ-110-250-4UHL1
38 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-110-I...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 -nominal voltage, kV I -movable connection of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm 110 126 450
18
4 hol.
110
220
10 10 1 280
178
Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted
40
1480
Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ- 110-I...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus- bar support type AIZ-110-I50-4UHL1 AIZ-110-I60-4UHL1 AIZ-110-I70-4UHL1 AIZ-110-I80-4UHL1 AIZ-110-I90-4UHL1 AIZ-110-I100-4UHL1 AIZ-110-I110-4UHL1 AIZ-110-I120-4UHL1 AIZ-110-I130-4UHL1 AIZ-110-I140-4UHL1 AIZ-110-I150-4UHL1 AIZ-110-I170-4UHL1 AIZ-110-I200-4UHL1 AIZ-110-I250-4UHL1
Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520
Diameterof rigid Diameter bus-bar D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1190 1200 1225 1230 1230 1235 1245 1245 1255 1260 1260 1280 1310 1315
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
39
29
AIZ-110-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
110
10 10 1 280
18 4 hol.
220
40
178
1480
Diameterof rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1180 1190 1190 1198 1214 1220 1220 1222 1235 1250 1250 1270 1290 1290
Weight, kg
26,0 26,0 26,1 26,2 26,4 26,7 28,5 28,8 28,9 29,0 29,3 29,5 29,7 29,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-110-80-4UHL1 AIZ-110-90-4UHL1 AIZ-110-100-4UHL1 AIZ-110-110-4UHL1 AIZ-110-120-4UHL1 AIZ-110-130-4UHL1 AIZ-110-140-4UHL1 AIZ-110-150-4UHL1 AIZ-110-170-4UHL1 AIZ-110-200-4UHL1 AIZ-110-250-4UHL1
40 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-110-S...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports
110 -nominal voltage, kV S - for the installation of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS
L
Connecting dimensions of bottom flange
Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm
18
4 hol.
220
110
10 10 1 280
178
Installation choices for bus- bar. The arrows indicate the axis of aluminum tube rigid bus-bar.
Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted
40
1480
Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-C...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus- bar support type AIZ-110-50-4UHL1 AIZ-110-60-4UHL1 AIZ-110-70-4UHL1 AIZ-110-80-4UHL1 AIZ-110-90-4UHL1 AIZ-110-100-4UHL1 AIZ-110-110-4UHL1 AIZ-110-120-4UHL1 AIZ-110-130-4UHL1 AIZ-110-140-4UHL1 AIZ-110-150-4UHL1 AIZ-110-170-4UHL1 AIZ-110-200-4UHL1 AIZ-110-250-4UHL1
Size L, 870 870 870 870 870 870 870 870 870 870 870 870 870 870
Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1280 1290 1315 1320 1320 1325 1325 1335 1345 1350 1350 1370 1400 1440
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
41
29
AIZ-110-GL...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 - nominal voltage, kV GL- transition fromr 2/8-2/100 - modification of the cross section of bus- bar and wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
POLYMER BUS-BAR SUPPORTS INTENDED FOR TRANSITION FROM FLEXIBLE TO FLAT HORIZOTAL BUS-BARS AIZ110-GL2/8-2/100-4 UHL1 - AIZ35-GL2/24-4/125-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-GL...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
110
10 10 1
18 4 hol. 220
40
1480
178
BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ110-GL...-4 UHL1
The outdoor bus- bar supports AIZ-110-GL are used for transition from flexible to flat horizontal bus-bars with 110 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
Rigid bus- bar support type AIZ-110-GL2/8-2/100-2 UHL1 AIZ-110-GL2/12-3/125-2 UHL1 AIZ-110-GL2/12-4/125-2 UHL1 AIZ-110-GL2/16-3/125-2 UHL1 AIZ-110-GL2/16-4/125-2 UHL1 AIZ-110-GL2/20-3/125-2 UHL1 AIZ-110-GL2/20-4/125-2 UHL1
Number flexible wires bus- bar 2+8 2+12 2+12 2+16 2+16 2+20 2+20
42 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 w ww.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-150-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ-150-...-4 UHL1
AIZ-150-...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 150 - nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 150 172 650
18
H
4 hol.
150
220
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
10 10 1 390
178
40
1480
1 1784 hol. 18 28
B
POLYMER BUS-BAR SUPPORTS AIZ-150-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-A...-4 UHL1 Assemblage
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
, KP
PM
2
Nominal cross-section, kv, mm AIZ-150-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27
17,5 - 22,1
1630
AIZ-150-2-4 UHL1
24,0 - 29,4
1633
Hydrophobic resistance to water
500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -
240, 300 -
500
1636 1642
43
29
AIZ-150-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 150 - nominal voltage, kV B - modification of bus-bar support for two wires 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
AIZ-150-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--150-B...-4 UHL1
18
150
220
4 hol.
10 10 1 390
178
40
1480
Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-B...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Nominal cross-section, mm AIZ-150-B1-4 UHL1 AIZ-150-B2-4 UHL1 AIZ-150-B3-4 UHL1 AIZ-150-B5-4 UHL1 AIZ-150-B6-4 UHL1 AIZ-150-B7-4 UHL1 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body
185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300
AIZ-150-B8-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 AIZ-150-B9-4 UHL1 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 AIZ-150-B10-4 UHL1 700; 750 650/79; 700/86; 240;300 AIZ-150-B11-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 AIZ-150-B12-4 UHL1 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 AIZ-150-B13-4 UHL1 700; 750 650/79; 700/86; 240;300
R
29 44
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
AIZ-150-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ-150-V...-4 UHL1
AIZ-150-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 150 - nominal voltage, kV V- modification for two hollow wires 1,2,3 - modification according cross section and type of wire
Pic.1
Pic.2
4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 150 172 650
18
4 hol.
150
220
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
10 10 1 390
178
Connection dimensions of bottom flange
40
1480
Weight, not more than, kg TYPE TESTS FOR AIZ-150-V...-4 UHL1 Assemblage
Pic.
H max, mm
Weight , kg
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
AIZ-150-1-4 UHL1
500
65
45,0
1642
31,8
AIZ-150-2-4 UHL1
500
120
45,0
1662
32,0
Hydrophobic resistance to water Hydrophobic resistance to colouring liquid
AIZ-150-3-4 UHL1
500
200
45,0
1662
32,0
Adhesion of coating layer to insulating body
45
29
AIZ-150-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 150 - nominal voltage, kV G - modification for three hollow wires 1,2,3 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
AIZ-35-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF BUS-BAR FIXATION AIZ-150-G...-4 UHL1
150
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
10
18 H 4 hol. 220
10 1 390
40
178
1480
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg
TYPE TESTS FOR AIZ-150-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
Pic.
H max, mm
Weight , kg
AIZ-150-G1-4 UHL1
Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body
500
65
45,0
1642
31,8
AIZ-150-G2-4 UHL1
500
120
45,0
1662
32,0
AIZ-150-G3-4 UHL1
500
200
45,0
1662
32,0
46 29
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
Pic.1
Pic.2
UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm 150 172 650
18 4 hol. 220
150
10 10 1 390
Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
178
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg
40
1480
Rigid bus bar support type AIZ-150-Z30-4UHL1 AIZ-150-Z40-4UHL1 AIZ-150-Z50-4UHL1 AIZ-150-Z70-4UHL1 AIZ-150-Z80-4UHL1 AIZ-150-Z90-4UHL1 AIZ-150-Z100-4UHL1 AIZ-150-Z110-4UHL1 AIZ-150-Z120-4UHL1 AIZ-150-Z130-4UHL1 AIZ-150-Z140-4UHL1 AIZ-150-Z150-4UHL1 AIZ-150-Z170-4UHL1 AIZ-150-Z200-4UHL1 AIZ-150-Z250-4UHL1
ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1
Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 1679 1679 1680 1690 1698 1702 1714 1720 1722 1735 1740 1750 1770 1790 1815 30,1 30,2 30,5 30,8 32,0 32,3 32,5 32,7 33,3 35,3 35,3 36,4 37,5 41,5 47,5
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
47
29
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-150-SH50-4 UHL1 - AIZ-150-SH250-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
150
10 10 1 390
18 4 hol.
220
40
178
1480
Rigid bus bar support type AIZ-150-SH50-4UHL1 AIZ-150-SH60-4UHL1 AIZ-150-SH70-4UHL1 AIZ-150-SH80-4UHL1 AIZ-150-SH90-4UHL1 AIZ-150-SH100-4UHL1 AIZ-150-SH110-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1690 1700 1725 1730 1730 1735 1745 1745 1755 1760 1760 1780 1810 1815
Weight, kg
32,0 32,0 32,5 33,0 33,4 34,0 34,5 34,5 35,0 35,5 35,7 37,5 39,2 40,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid
AIZ-150-SH200-4UHL1 AIZ-150-SH250-4UHL1
48 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
150
10 10 1 390
18 4 hol.
220
Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
40
178
Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm
1480
Weight, not more than, kg TYPE TESTS FOR AIZ-150-D...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus bar support type AIZ-150-D50-4UHL1 AIZ-150-D60-4UHL1 AIZ-150-D70-4UHL1 AIZ-150-D80-4UHL1 AIZ-150-D90-4UHL1 AIZ-150-D100-4UHL1 AIZ-150-D110-4UHL1 AIZ-150-D120-4UHL1 AIZ-150-D130-4UHL1 AIZ-150-D140-4UHL1 AIZ-150-D150-4UHL1 AIZ-150-D170-4UHL1 AIZ-150-D200-4UHL1 AIZ-150-D250-4UHL1
R
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1690 1700 1725 1730 1730 1735 1745 1745 1755 1760 1760 1780 1810 1815
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- regis regist tra rat ted ed trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
49
29
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-150-...-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
150
10 10 1 390
18 4 hol.
220
40
178
1480
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1655 1658 1685 1690 1690 1705 1705 1710 1720 1730 1760 1780 1810 1815
Weight, kg
29,0 29,0 29,1 29,2 29,4 29,7 29,5 31,8 31,9 32,0 32,3 32,5 32,7 32,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-150-80-4UHL1 AIZ-150-90-4UHL1 AIZ-150-100-4UHL1 AIZ-150-110-4UHL1 AIZ-150-120-4UHL1 AIZ-150-130-4UHL1 AIZ-150-140-4UHL1 AIZ-150-150-4UHL1 AIZ-150-170-4UHL1 AIZ-150-200-4UHL1 AIZ-150-250-4UHL1
50 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
150
18
4 hol.
220
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
10 10 1 390
178
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm
40
1480
Weight, not more than, kg TYPE TESTS FOR AIZ- 150-I...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus bar support type AIZ-150-I50-4UHL1 AIZ-150-I60-4UHL1 AIZ-150-I70-4UHL1 AIZ-150-I80-4UHL1 AIZ-150-I90-4UHL1 AIZ-150-I100-4UHL1 AIZ-150-I110-4UHL1 AIZ-150-I120-4UHL1 AIZ-150-I130-4UHL1 AIZ-150-I140-4UHL1 AIZ-150-I150-4UHL1 AIZ-150-I170-4UHL1 AIZ-150-I200-4UHL1 AIZ-150-I250-4UHL1
Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520
Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1690 1700 1725 1730 1730 1735 1745 1745 1755 1760 1760 1780 1810 1815
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
51
29
L D
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
10 10 1 390
150
18 4 hol.
220
40
178
1480
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 1680 1690 1690 1698 1714 1720 1720 1722 1735 1750 1750 1770 1790 1790
Weight, kg
30,0 30,0 30,1 30,2 30,4 30,7 32,5 32,8 32,9 33,0 33,3 33,5 33,7 33,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-150-80-4UHL1 AIZ-150-90-4UHL1 AIZ-150-100-4UHL1 AIZ-150-110-4UHL1 AIZ-150-120-4UHL1 AIZ-150-130-4UHL1 AIZ-150-140-4UHL1 AIZ-150-150-4UHL1 AIZ-150-170-4UHL1 AIZ-150-200-4UHL1 AIZ-150-250-4UHL1
52 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ-220-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ--220-...-4 UHL1
AIZ-220-...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 220 - nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire
4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
18
4 hol.
220
265
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
10 8 2 570
225
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted
100
1480
1 2254 hol. 18
75
B
POLYMER BUS-BAR SUPPORTS AIZ-220-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-A...-4 UHL1 Assemblage
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
, KP
PM
2
Nominal cross-section, kv, mm AIZ-220-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27
17,5 - 22,1
2130
AIZ-220-2-4 UHL1
24,0 - 29,4
2133
Hydrophobic resistance to water
500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -
240, 300 -
500
2136 2142
53
29
AIZ-220-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 220 - nominal voltage, kV B - modification of bus-bar support for two wires 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
AIZ-220-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBILE BUS-BAR FIXATION AIZ--220-B...-4 UHL1
220
18
252 950
265
4 hol.
220
10 8 1 570
225
100
1480
Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-B...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage.
Nominal cross-section, mm AIZ-220-B1-4 UHL1 AIZ-220-B2-4 UHL1 AIZ-220-B3-4 UHL1 AIZ-220-B5-4 UHL1 AIZ-220-B6-4 UHL1 AIZ-220-B7-4 UHL1 AIZ-220-B8-4 UHL1 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body
185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300
AIZ-220-B9-4 UHL1 AIZ-220-B10-4 UHL1 AIZ-220-B11-4 UHL1 AIZ-220-B12-4 UHL1 AIZ-220-B13-4 UHL1
185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 700; 750 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 700; 750 650/79; 700/86; 240;300 185; 240; 300
R
54 29
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
AIZ-220-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--220-V...-4 UHL1
AIZ-220-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports
L
220 - nominal voltage, kV V- modification for two hollow wires
Pic.1 Pic.2
1,2,3 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
220
18
4 hol.
265
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
10 8
2
570
225
Connection dimensions of bottom flange
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
100
1480
Weight, not more than, kg TYPE TESTS FOR AIZ-220-V...-4 UHL1 Assemblage
Pic.
H max, mm
Weight , kg
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
AIZ-220-1-4 UHL1
500
65
45,0
2142
77,8
AIZ-220-2-4 UHL1
500
120
45,0
2162
78,0
Hydrophobic resistance to water Hydrophobic resistance to colouring liquid
AIZ-220-3-4 UHL1
500
200
45,0
2162
78,0
Adhesion of coating layer to insulating body
55
29
AIZ-220-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 220 - nominal voltage, kV G - modification for three hollow wires 1,2,3 - bus-bar fitting modification
AIZ-220-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBLE BUS-BAR AIZ--220-G1-4 UHL1, AIZ-220-G2-4 UHL1, AIZ-220-G3-4 UHL1
L
4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
18
4 hol.
265
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
10
220
225
8 2 570
100
1480
Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg
TYPE TESTS FOR AIZ-220-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
Pic.
H max, mm
Weight , kg
AIZ-220-G1-4 UHL1
Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body
500
65
45,0
2142
77,8
AIZ-220-G2-4 UHL1
500
120
45,0
2162
78,0
AIZ-220-G3-4 UHL1
500
200
45,0
2162
78,0
56 29
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
Pic.1
Pic.2
4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV 220 252 950
18
4 hol.
265
Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm
220
225
10 8
2
Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm
570
100
1480
Weight, not more than, kg TYPE TESTS FOR AIZ ()-10-Z...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus bar support type AIZ-220-Z30-4UHL1 AIZ-220-Z40-4UHL1 AIZ-220-Z50-4UHL1 AIZ-220-Z70-4UHL1 AIZ-220-Z80-4UHL1 AIZ-220-Z90-4UHL1 AIZ-220-Z100-4UHL1 AIZ-220-Z110-4UHL1 AIZ-220-Z120-4UHL1 AIZ-220-Z130-4UHL1 AIZ-220-Z140-4UHL1 AIZ-220-Z150-4UHL1 AIZ-220-Z170-4UHL1 AIZ-220-Z200-4UHL1 AIZ-220-Z250-4UHL1
ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1
Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 2179 2179 2180 2190 2198 2202 2214 2220 2222 2235 2240 2250 2270 2290 2315 76,1 76,2 76,5 76,8 78,0 78,3 78,5 78,7 79,3 81,3 81,3 82,4 83,5 87,5 83,5
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
57
29
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-220-SH50-4 UHL1 - AIZ-220-SH250-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
220
10 8
18 4 hol.
220
2 570
100
178
1480
Rigid bus bar support type AIZ-220-SH50-4UHL1 AIZ-220-SH60-4UHL1 AIZ-220-SH70-4UHL1 AIZ-220-SH80-4UHL1 AIZ-220-SH90-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 2190 2200 2225 2230 2230 2235 2245 2245 2255 2260 2260 2280 2310 2315
Weight, kg
78,0 78,0 78,5 79,0 79,4 80,0 80,5 80,5 81,0 81,5 81,7 83,5 85,2 86,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-220-SH250-4UHL1
58 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
220-nominal voltage, kV D-movable fastening of aluminum tube bus-bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN 220 252 950
220
10 8 2 570
18 4 hol.
220
Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N
100
178
1480
Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg
Rigid bus bar support type AIZ-220-D50-4UHL1 AIZ-220-D60-4UHL1 AIZ-220-D70-4UHL1 AIZ-220-D80-4UHL1 AIZ-220-D90-4UHL1 AIZ-220-D100-4UHL1 AIZ-220-D110-4UHL1 AIZ-220-D120-4UHL1 AIZ-220-D130-4UHL1 AIZ-220-D140-4UHL1 AIZ-220-D150-4UHL1 AIZ-220-D170-4UHL1 AIZ-220-D200-4UHL1 AIZ-220-D250-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 2190 2200 2225 2230 2230 2235 2245 2245 2255 2260 2260 2280 2310 2315
Weight, kg
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
59
29
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-220-...-4 UHL1
- end fastening of aluminum tube bus bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
220
10 8 2 570
18 4 hol.
H
220
100
178
1480
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 2155 2158 2185 2190 2190 2205 2205 2210 2220 2230 2260 2280 2310 2315
Weight, kg
75,0 75,0 75,1 75,2 75,4 75,7 75,5 77,8 77,9 78,0 78,3 78,5 78,7 78,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-220-80-4UHL1 AIZ-220-90-4UHL1 AIZ-220-100-4UHL1 AIZ-220-110-4UHL1 AIZ-220-120-4UHL1 AIZ-220-130-4UHL1 AIZ-220-140-4UHL1 AIZ-220-150-4UHL1 AIZ-220-170-4UHL1 AIZ-220-200-4UHL1 AIZ-220-250-4UHL1
60 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
220
18
4 hol.
220
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
10 8 2 570
178
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm
100
1480
Weight, not more than, kg TYPE TESTS FOR AIZ- 220-I...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus bar support type AIZ-220-I50-4UHL1 AIZ-220-I60-4UHL1 AIZ-220-I70-4UHL1 AIZ-220-I80-4UHL1 AIZ-220-I90-4UHL1 AIZ-220-I100-4UHL1 AIZ-220-I110-4UHL1 AIZ-220-I120-4UHL1 AIZ-220-I130-4UHL1 AIZ-220-I140-4UHL1 AIZ-220-I150-4UHL1 AIZ-220-I170-4UHL1 AIZ-220-I200-4UHL1 AIZ-220-I250-4UHL1
Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520
Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 2190 2200 2225 2230 2230 2235 2245 2245 2255 2260 2260 2280 2210 2215
Weight, kg
78,0 78,0 78,5 79,0 79,4 80,0 80,5 80,5 81,0 81,5 81,7 83,5 85,2 86,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
61
29
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
220
10 8 2 570
18 4 hol.
H
220
100
178
1480
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 2180 2190 2190 2198 2214 2220 2220 2222 2235 2250 2250 2270 2290 2290
Weight, kg
76,0 76,0 76,1 76,2 76,4 76,7 78,5 78,8 78,9 79,0 79,3 79,5 79,7 79,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-220-80-4UHL1 AIZ-220-90-4UHL1 AIZ-220-100-4UHL1 AIZ-220-110-4UHL1 AIZ-220-120-4UHL1 AIZ-220-130-4UHL1 AIZ-220-140-4UHL1 AIZ-220-150-4UHL1 AIZ-220-170-4UHL1 AIZ-220-200-4UHL1 AIZ-220-250-4UHL1
62 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
S - for the installation of two aluminum tubes 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
L
Connecting dimensions of bottom flange
Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN
18
4 hol.
220
220
10 8 2 570
178
Installation choices for bus bar. The arrows indicate the axis aluminum tube rigid busbar
Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm
100
1480
Weight, not more than, kg TYPE TESTS FOR AIZ-220-S...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Rigid bus bar support type AIZ-220-50-4UHL1 AIZ-220-60-4UHL1 AIZ-220-70-4UHL1 AIZ-220-80-4UHL1 AIZ-220-90-4UHL1 AIZ-220-100-4UHL1 AIZ-220-110-4UHL1 AIZ-220-120-4UHL1 AIZ-220-130-4UHL1 AIZ-220-140-4UHL1 AIZ-220-150-4UHL1 AIZ-220-170-4UHL1 AIZ-220-200-4UHL1 AIZ-220-250-4UHL1
Size L, 870 870 870 870 870 870 870 870 870 870 870 870 870 870
Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 2190 2200 2225 2230 2230 2235 2245 2245 2255 2260 2260 2280 2310 2315
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
63
29
AIZ-330-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ-330-...-4 UHL1
AIZ-330-...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 330 - nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTIC Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 330 363 1175
18
8 hol.
B
340
315
30
8
950
920
300
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
160
1480
B
POLYMER BUS-BAR SUPPORTS AIZ-330-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.
Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR Assemblage AIZ-330-A...-4 UHL1
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
, KP
PM
2
Nominal cross-section, kv, mm AIZ-330-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27
17,5 - 22,1
2972
AIZ-330-2-4 UHL1
24,0 - 29,4
2975
Hydrophobic resistance to water
500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -
240, 300 -
500
2978 2984
64
mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu
29
AIZ-330-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 330 - nominal voltage, kV B - modification of bus-bar support for two wires 1,2,3,4 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS
Nominal voltage, kV 330
AIZ-330-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBILE BUS-BAR FIXATION AIZ--330-B...-4 UHL1
363 1175
315
18
8 hol.
B
340
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
30 8 950 920
300
160
1480
Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-330-B...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
18
Nominal cross-section, mm AIZ-330-B1-4 UHL1 AIZ-330-B2-4 UHL1 AIZ-330-B3-4 UHL1 AIZ-330-B5-4 UHL1 AIZ-330-B6-4 UHL1 AIZ-330-B7-4 UHL1 AIZ-330-B8-4 UHL1 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body
185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300
AIZ-330-B9-4 UHL1 AIZ-330-B10-4 UHL1 AIZ-330-B11-4 UHL1 AIZ-330-B12-4 UHL1 AIZ-330-B13-4 UHL1
185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 700; 750 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 700; 750 650/79; 700/86; 240;300 185; 240; 300
R
65 29
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
AIZ-330-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBILE BUS-BAR FIXATION AIZ--330-V...-4 UHL1
AIZ-330-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 330 - nominal voltage, kV
V- modification for two hollow wires 1,2,3 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694
Pic.1
Pic.2
UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 330 363 1175
18
H
8 hol.
B
340
315
30
8
950 920
300
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
160
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm
1480
Weight, not more than, kg TYPE TESTS FOR AIZ-330-V...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Pic.
H max, mm
Weight , kg
Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition
AIZ-330-1-4 UHL1
500
65
45,0
2142
157,8
AIZ-330-2-4 UHL1
500
120
45,0
2162
158,0
Hydrophobic resistance to water Hydrophobic resistance to colouring liquid
AIZ-330-3-4 UHL1
500
200
45,0
2162
158,0
Adhesion of coating layer to insulating body
66
29
AIZ-330-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 330 - nominal voltage, kV G - modification for three hollow wires 1,2,3 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
AIZ-330-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBILE BUS-BAR AIZ--330-G...-4 UHL1
315
18
H
8 hol.
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N
30 8 950 920
340
300
160
1480
Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg
TYPE TESTS FOR AIZ-330-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level
Pic.
H max, mm
Weight , kg
AIZ-330-G1-4 UHL1
500
65
45,0
3014
157,8
AIZ-330-G2-4 UHL1
Hydrophobic resistance to water Hydrophobic resistance to coloring liquid
500
120
45,0
3034
158,0
AIZ-330-G3-4 UHL1
Adhesion of coating layer to insulating body
500
200
45,0
3034
158,0
67 29
AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R
330- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-330-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
315
18
30 8 950 920
8 hol.
340
300
160
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 3052 3062 3062 3070 3086 3092 3092 3094 3107 3122 3122 3142 3162 3162
Weight, kg
158,0 158,0 158,1 158,2 158,4 158,7 160,5 160,8 160,9 161,0 161,3 161,5 161,7 161,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-330-80-4UHL1 AIZ-330-90-4UHL1 AIZ-330-100-4UHL1 AIZ-330-110-4UHL1 AIZ-330-120-4UHL1 AIZ-330-130-4UHL1 AIZ-330-140-4UHL1 AIZ-330-150-4UHL1 AIZ-330-170-4UHL1 AIZ-330-200-4UHL1 AIZ-330-250-4UHL1
68 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
30-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS
Pic.1
Pic.2
Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV
18
8 hol.
315
340
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
30 8 950 920
300
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm
160
1480
Weight, not more than, kg TYPE TESTS FOR AIZ-330-Z...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Rigid bus bar support type AIZ-330-Z30-4UHL1 AIZ-330-Z40-4UHL1 AIZ-330-Z50-4UHL1 AIZ-330-Z70-4UHL1 AIZ-330-Z80-4UHL1 AIZ-330-Z90-4UHL1 AIZ-330-Z100-4UHL1 AIZ-330-Z110-4UHL1 AIZ-330-Z120-4UHL1 AIZ-330-Z130-4UHL1 AIZ-330-Z140-4UHL1 AIZ-330-Z150-4UHL1 AIZ-330-Z170-4UHL1 AIZ-330-Z200-4UHL1 AIZ-330-Z250-4UHL1
ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1
Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250
Building Weight, kg height H, mm 3051 3051 3052 3062 3070 3074 3086 3092 3094 3107 3112 3122 3142 3162 3187 156,1 156,2 156,5 156,8 158,0 158,3 158,5 158,7 159,3 161,3 161,3 162,4 163,5 167,5 163,5
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
69
29
BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-330-SH50-4 UHL1 - AIZ-330-SH250-4 UHL1
AIZ - brand of polymeric bus bar supports 330- nominal voltage, kV SH - hinging of aluminum tube bus-bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-330-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
315
18
H
30 8 950 920
8 hol.
340
300
160
1480
Rigid bus bar support type AIZ-330-SH50-4UHL1 AIZ-330-SH60-4UHL1 AIZ-330-SH70-4UHL1 AIZ-330-SH80-4UHL1 AIZ-330-SH90-4UHL1 AIZ-330-SH100-4UHL1 AIZ-330-SH110-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 3062 3072 3097 3102 3102 3107 3117 3117 3127 3132 3132 3152 3182 3187
Weight, kg
160,0 160,0 160,5 161,0 161,4 162,0 162,5 162,5 163,0 163,5 163,7 165,5 167,2 168,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid
AIZ-330-SH200-4UHL1 AIZ-330-SH250-4UHL1
70 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
AIZ - brand of polymeric bus bar supports 330-nominal voltage, kV D-movable fastening of aluminum tube bus-bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 330 363 1175
315
18
8 hol.
340
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg
30 8 950 920
300
160
1480
TYPE TESTS FOR AIZ-330-D...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
Rigid bus bar support type AIZ-330-D50-4UHL1 AIZ-330-D60-4UHL1 AIZ-330-D70-4UHL1 AIZ-330-D80-4UHL1 AIZ-330-D90-4UHL1 AIZ-330-D100-4UHL1 AIZ-330-D110-4UHL1 AIZ-330-D120-4UHL1 AIZ-330-D130-4UHL1 AIZ-330-D140-4UHL1 AIZ-330-D150-4UHL1 AIZ-330-D170-4UHL1 AIZ-330-D200-4UHL1 AIZ-330-D250-4UHL1
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 3062 3072 3097 3102 3102 3107 3117 3117 3127 3132 3132 3152 3182 3187
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
71
29
BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-330-...-4 UHL1
TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-330-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence
315
18
8 hol.
30 8 950 920
340
300
160
1480
Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230
Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 3027 3030 3057 3062 3062 3077 3077 3082 3092 3102 3132 3152 3182 3187
Weight, kg
157,0 157,0 157,1 157,2 157,4 157,7 157,5 159,8 159,9 160,0 160,3 160,5 160,7 160,9
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body
AIZ-330-80-4UHL1 AIZ-330-90-4UHL1 AIZ-330-100-4UHL1 AIZ-330-110-4UHL1 AIZ-330-120-4UHL1 AIZ-330-130-4UHL1 AIZ-330-140-4UHL1 AIZ-330-150-4UHL1 AIZ-330-170-4UHL1 AIZ-330-200-4UHL1 AIZ-330-250-4UHL1
72 29
AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925
315
18
8 hol.
340
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm
30 8 950 920
300
160
1480
Weight, not more than, kg TYPE TESTS FOR AIZ- 330-I...-4 UHL1 Assemblage External inspection ( outer view and marking )
Rigid bus bar support type AIZ-330-I50-4UHL1 AIZ-330-I60-4UHL1 AIZ-330-I70-4UHL1 AIZ-330-I80-4UHL1 AIZ-330-I90-4UHL1 AIZ-330-I100-4UHL1 AIZ-330-I110-4UHL1 AIZ-330-I120-4UHL1 AIZ-330-I130-4UHL1 AIZ-330-I140-4UHL1 AIZ-330-I150-4UHL1 AIZ-330-I170-4UHL1 AIZ-330-I200-4UHL1 AIZ-330-I250-4UHL1
Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520
Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250
Building height H, mm 3062 3072 3097 3102 3102 3107 3117 3117 3127 3132 3132 3152 3182 3187
Weight, kg
Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )