POLYMER BUS-BAR SUPPORTS WITH FLEXIBLE AND RIGID FIXATION OF ALUMINIUM TUBES AND WIRES

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

AIZ-10-L...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV 1L,2L,3L - 1,2,3 - horizontal flat bus- bar 63-125 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-10-1L63-4 UHL1-AIZ-10-4L125-4 UHL1

ic.

ic.D

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-L...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

10 12 75

13
30 10 2

ic.

ic.C

30

31,5

1480

see table

BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ10-L...-4 UHL1
1274 hol. see table 13 The outdoor application of bus- bar supports AIZ-10-L are used for fixing the flat rigid bus- bars in horizontal position at 10 (20) kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-10-L are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.

Rigid bus- bar support type AIZ-10-1L63-4UHL1 AIZ-10-1L80-4UHL1 AIZ-10-1L100-4UHL1 AIZ-10-1L125-4UHL1 AIZ-10-2L63-4UHL1 AIZ-10-2L80-4UHL1 AIZ-10-2L100-4UHL1 AIZ-10-2L125-4UHL1 AIZ-10-3L63-4UHL1

Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125 4/63 4/80 4/100 4/125

Picture

Building height H, mm 318 322 326 328 338 342 346 348 358 362 366 368 378 382 386 388

Weight, kg 6,2 6,2 6,3 6,5 6,5 6,5 6,6 6,7 6,7 6,8 6,8 6,9 6,9 7,0 7,0 7,2

C C C C D D D D

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid

AIZ-10-3L80-4UHL1 AIZ-10-3L100-4UHL1 AIZ-10-3L125-4UHL1 AIZ-10-4L63-4UHL1 AIZ-10-4L80-4UHL1

Adhesion of coating layer to insulating body

AIZ-10-4L100-4UHL1 AIZ-10-4L125-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

229

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

AIZ-10-P...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV P - the box-shaped rigid bus- bars 100-250 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-10-P100-4UHL- AIZ-10-P250-4 UHL

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-P...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

10 12 75

13
30 10 2 30

13
31,5

4 hol.

159

1480

1 1274 hol. . 13 13 see table

127

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-10-P...-4 UHL1


The outdoor application of bus- bar supports AIZ-10-P are used for fixing the box-shaped rigid bus- bars at 10(20) kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231, TS3414-005-59116459-06. The bus- bar supports AIZ-10-P are included in the integrated rigid bus- bar project of substations. Useful service life30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

Rigid bus- bar support type AIZ-10-P100-4 UHL1 AIZ-10-P125-4 UHL1 AIZ-10-P150-4 UHL1 AIZ-10-P175-4 UHL1 AIZ-10-P200-4 UHL1 AIZ-10-P225-4 UHL1 AIZ-10-P250-4 UHL1

Width of box of bus- bar mm 100 125 150 175 200 225 250

Building height H, mm 412 437 462 487 512 537 562

Weight, kg 10,60 10,70 10,80 10,95 11,10 11,30 11,50

GOST R 52082-03, TS3494-005-59116459-05

329 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR FOR THE 10KV CURRENT AIZ-10-1M63-4 UHL1-AIZ-10-3M125-4 UHL1

AIZ-10-...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV 1M,2M,3M - 1,2,3 - flat vertical bus-bars 69-125 - width of vertical bus-bar in mm. 4 - pollution level according GOST 9920, IEC60815, IEC60694

UHL1 ic. ic.C

climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

10 12 75

13
30 10 2 30

13 4 hol. 159

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN
ic.

Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg

31,5

127

1480

see table 1274 hol. see table 13

BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ-10-...-4 UHL1
The outdoor application of bus- bar supports AIZ-10-M are used for fixing the flat rigid bus- bars in vertical position at 10 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-10-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.

TYPE TESTS FOR AIZ-10-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Rigid bus- bar support type AIZ-10-1M63-4UHL1 AIZ-10-1M80-4UHL1 AIZ-10-1M100-4UHL1 AIZ-10-1M125-4UHL1 AIZ-10-263-4UHL1 AIZ-10-280-4UHL1 AIZ-10-2100-4UHL1 AIZ-10-2125-4UHL1 AIZ-10-363-4UHL1 AIZ-10-380-4UHL1 AIZ-10-3100-4UHL1 AIZ-10-3125-4UHL1

Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125

Picture A A A A C C C C

Building height H, mm 362 380 400 425 362 380 400 425 362 380 400 425

Weight, kg 5,90 5,96 6,09 6,15 5,92 5,98 6,11 6,17 5,94 6,00 6,13 6,19

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

29

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-10-Z-4UHL1

AIZ-10-Z...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV Z -rigid connection of aluminium tubular bus-bar 30-250- diameter of aluminium tubular bus-bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV

10 12 75

ic.1

ic.2

Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm

13
30 10 2 30

13 4 hol.

Minimum creepage distance, cm

159

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

31,5

1480

127

Number of bus- bar mounted Bottom flange fitting dimensions, mm

1 1274 hol. see table 13

POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-10-Z....-4 UHL1


The outdoor bus- bar supports AIZ-10-Z are used for aluminum tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-10-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request

Weight, not more than, kg TYPE TESTS FOR AIZ-10-Z...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-10-Z30-4UHL1 AIZ-10-Z40-4UHL1 AIZ-10-Z50-4UHL1 AIZ-10-Z70-4UHL1 AIZ-10-Z80-4UHL1 AIZ-10-Z90-4UHL1 AIZ-10-Z100-4UHL1 AIZ-10-Z110-4UHL1 AIZ-10-Z120-4UHL1 AIZ-10-Z130-4UHL1 AIZ-10-Z140-4UHL1 AIZ-10-Z150-4UHL1 AIZ-10-Z170-4UHL1 AIZ-10-Z200-4UHL1 AIZ-10-Z250-4UHL1

ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1

Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 359 359 360 370 378 382 394 400 402 415 420 430 450 470 495 12,8 12,9 13,2 13,5 14,7 15,0 15,2 13,5 14,0 18,0 18,0 19,1 20,2 24,3 30,2

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

29

AIZ-10-SH...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 10- nominal voltage, kV SH - hinging of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-10-SH50-4UHL- AIZ-10-SH250-4 UHL

rotation angle

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

10 12 75

13
30 10 2 30

13 4 hol.

159

31,5

1480

1 1274 hol. see table 13

127
BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-10-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-10-SH are used for hinged fastening of tubular rigid bus-bar at 10 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-10-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus- bar support type AIZ-10-SH50-4UHL1 AIZ-10-SH60-4UHL1 AIZ-10-SH70-4UHL1 AIZ-10-SH80-4UHL1 AIZ-10-SH90-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 370 380 405 410 410 415 425 425 435 440 440 460 470 495 15,0 15,0 15,5 16,0 16,4 17,0 17,5 17,5 18,0 18,5 18,7 20,5 22,2 23,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-10-SH100-4UHL1 AIZ-10-SH110-4UHL1 AIZ-10-SH120-4UHL1 AIZ-10-SH130-4UHL1 AIZ-10-SH140-4UHL1 AIZ-10-SH150-4UHL1 AIZ-10-SH170-4UHL1 AIZ-10-SH200-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

AIZ-10-SH250-4UHL1

629

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARS AIZ-10-D...-4 UHL1

AIZ-10-D...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports

movement direction

10 - nominal voltage, kV D-movable fastening of aluminium tubular bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm

10 12 75 13

30 10 2 30

13 4 hol.

Minimum creepage distance, cm

159

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm

31,5

1480

127

1 1274 hol. see table 13

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-10-D...-4 UHL1


The outdoor bus- bar supports AIZ-10-D are used for flexible fitting of aluminium tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-10-D are included in the integrated rigid bus-bar project of substations.

Weight, not more than, kg TYPE TESTS FOR AIZ-10-D...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-10-D50-4UHL1 AIZ-10-D60-4UHL1 AIZ-10-D70-4UHL1 AIZ-10-D80-4UHL1 AIZ-10-D90-4UHL1 AIZ-10-D100-4UHL1 AIZ-10-D110-4UHL1 AIZ-10-D120-4UHL1 AIZ-10-D130-4UHL1 AIZ-10-D140-4UHL1 AIZ-10-D150-4UHL1 AIZ-10-D170-4UHL1 AIZ-10-D200-4UHL1 AIZ-10-D250-4UHL1

Diameter of rigid bus-bar tube, mm

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 370 380 405 410 410 415 425 425 435 440 440 460 470 495 15,0 15,0 15,5 16,0 16,4 17,0 17,5

50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

17,5 18,0 18,5 18,7 20,5 22,2 23,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

29

AIZ-10-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV - end fastening of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-10-50-4 UHL1 - AIZ-10-250-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

10 12 75

13
30 10 2

30

13 4 hol.

159

31,5

1480

127
1 1274 hol. see table 13

BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-10-...-4 UHL1


The outdoor bus- bar supports AIZ-10-K are used for end fixation of aluminium tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Rigid bus-bar support type AIZ-10-50-4UHL1 AIZ-10-60-4UHL1 AIZ-10-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 335 338 365 370 370 385 385 390 400 410 440 460 490 495 12,0 12,0 12,1 12,2 12,4 12,7 14,5 14,8 14,9 15,0 15,3 15,5 15,7 15,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-10-80-4UHL1 AIZ-10-90-4UHL1 AIZ-10-100-4UHL1 AIZ-10-110-4UHL1 AIZ-10-120-4UHL1 AIZ-10-130-4UHL1 AIZ-10-140-4UHL1 AIZ-10-150-4UHL1 AIZ-10-170-4UHL1 AIZ-10-200-4UHL1 AIZ-10-250-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

829

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE AIZ-10-I-4UHL1 AIZ-10-I...-4 UHL1

AIZ-10-I...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV I -movable connection of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar

movement direction

movement direction

4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

10 12 75 13
30 10 2 30

13 4 hol.

For specified surface conductivity of polluted layer, mkCm

159

Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm

31,5

127

1480

1 1274 hol. see table 13

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ-10-I...-4 UHL1


The outdoor bus- bar supports AIZ-10-I are used for flexible connection of aluminium tubular bus-bar support with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request. Weight, not more than, kg TYPE TESTS FOR AIZ -10-I...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-10-I50-4UHL1 AIZ-10-I60-4UHL1 AIZ-10-I70-4UHL1 AIZ-10-I80-4UHL1 AIZ-10-I90-4UHL1 AIZ-10-I100-4UHL1 AIZ-10-I110-4UHL1 AIZ-10-I120-4UHL1 AIZ-10-I130-4UHL1 AIZ-10-I140-4UHL1 AIZ-10-I150-4UHL1 AIZ-10-I170-4UHL1 AIZ-10-I200-4UHL1 AIZ-10-I250-4UHL1

Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 370 380 405 410 410 415 425 425 435 440 440 460 470 495

Weight, kg

18,0 18,0 18,5 19,0 19,4 20,0 20,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

20,5 21,0 21,5 21,7 23,5 25,2 26,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

29

AIZ-10-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-10-50-4 UHL1 - AIZ-10-250-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

10 12 75
H

13
30 10 2 30

13 4 hol.

159

31,5

1480

127

1 1274 hol. see table 13

BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ-10-...-4 UHL1


The outdoor bus- bar supports AIZ-10-E are used for double fixation of aluminium tube with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-E are included in the integrated rigid busbar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus- bar support type AIZ-10-50-4UHL1 AIZ-10-60-4UHL1 AIZ-10-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 360 370 370 378 394 400 400 402 415 430 430 450 470 470 13,0 13,0 13,1 13,2 13,4 13,7 15,5 15,8 15,9 16,0 16,3 16,5 16,7 16,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-10-80-4UHL1 AIZ-10-90-4UHL1 AIZ-10-100-4UHL1 AIZ-10-110-4UHL1 AIZ-10-120-4UHL1 AIZ-10-130-4UHL1 AIZ-10-140-4UHL1 AIZ-10-150-4UHL1 AIZ-10-170-4UHL1 AIZ-10-200-4UHL1 AIZ-10-250-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

10 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ-10-S...-4 UHL1

AIZ-10-S...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV S - for the installation of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar

movement D direction

movement direction

4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

10 12 75

L 13 4 hol.

13
30 10 2 30

159

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm

127

Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm

31,5

Installation choices for bus- bar. The arrows indicate the axis of the aluminum tubes of rigid bus- bar.

1480

1 1274 hol. see table 13

BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ-10-S...-4 UHL1


The outdoor bus- bar supports AIZ-10-S are used for installation of two aluminium tubes with 10 kV voltage on opened distribution devices of electric power stations and substations.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-S are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Please indicate and fill data sheet if it is necessary to install tubes with different diameter.The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Weight, not more than, kg TYPE TESTS FOR AIZ -10-C...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-10-50-4UHL1 AIZ-10-60-4UHL1 AIZ-10-70-4UHL1 AIZ-10-80-4UHL1 AIZ-10-90-4UHL1 AIZ-10-100-4UHL1 AIZ-10-110-4UHL1 AIZ-10-120-4UHL1 AIZ-10-130-4UHL1 AIZ-10-140-4UHL1 AIZ-10-150-4UHL1 AIZ-10-170-4UHL1 AIZ-10-200-4UHL1 AIZ-10-250-4UHL1

Size L, 870 870 870 870 870 870 870 870 870 870 870 870 870 870

Diameter Diameter of rigid bus-bar D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 620 630 655 660 660 665 675 685 685 690 690 710 740 780 30,5 31,6 32,0 33,0 34,2 35,0 35,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

47,0 40,0 41,0 42,0 45,0 111,0 119,0


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

11

29

AIZ-10-GL...-4 UHL1
CONDITIONAL DESIGNATION AIZ - brand of polymeric bus- bar supports 10- nominal voltage, kV GL - go with a flexible busbar on flat bus- bar 2/8-2/100 - modification of the cross section of bus- bar and wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

POLYMER BUS-BAR SUPPORTS INTENDED FOR TRANSITION FROM FLEXIBLE TO RIGID BUS-BARS AIZ-10-GL2/8-2/100-4 UHL1 - AIZ-10-GL2/24-4/125-4 UHL1

Contact plate for transition

Incorporated spacerAIZ-2, for wire maitainings

Horizontal flat bus- bar

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ -10-GL...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

10 12

L
75

13
30 10 2 30

13 4 hol.

159

31,5

1480

127
see table 1274 hol. see table 13

BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ-10-GL...-4 UHL1
The outdoor bus- bar supports AIZ-10-GL are used for transition from flexible to flat horizontal bus-bars with 10 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-10-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

Rigid bus- bar support type AIZ-10-GL2/8-2/100-2 UHL1 AIZ-10-GL2/12-3/125-2 UHL1 AIZ-10-GL2/12-4/125-2 UHL1 AIZ-10-GL2/16-3/125-2 UHL1 AIZ-10-GL2/16-4/125-2 UHL1 AIZ-10-GL2/20-3/125-2 UHL1 AIZ-10-GL2/20-4/125-2 UHL1

Number flexible wires bus- bar 2+8 2+12 2+12 2+16 2+16 2+20 2+20

Flat bus- bar mm


2bus-bar(100*10) 3bus-bar(125*10) 4bus-bar(125*10) 3bus-bar(125*10) 4bus-bar(125*10) 3bus-bar(125*10) 4bus-bar(125*10)

L 400 470 470 590 590 590 590

H 360 400 400 400 400 400 400

GOST R 52082-03, TS3494-005-59116459-05

12 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTANAIZ, +7-717-296-5353 LITHUANIA www.bus-bar.eu +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

AIZ-35-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ-35-...-4 UHL1

AIZ-35-...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports

35- nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 35 40,5 190

13
4 hol.

42

159

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

20 10
1

95

127

31,5

1480

B
POLYMER BUS-BAR SUPPORTS AIZ-35-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Busbar supports for the 10-220 kV voltage. The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in Siberia Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works.

Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-A...-4 UHL1 Assemblage

1 1274 hol. 14 13

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Wires according GOST 839-80, type

Wires according TS16-505.397-72 Diameter of wires, mm H max, mm

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

Type of flexible bus-bar support

, KP

S,SS, SP, ASK

PM
2

Nominal cross-section, kv, mm AIZ-35-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27

17,5 - 22,1

470

Failing load at bending (torsion ) Evaluation of partial discharge level

AIZ-35-2-4 UHL1

350; 400 450; 500

24,0 - 29,4

473
Hydrophobic resistance to water

AIZ-35-3-4 UHL1 AIZ-35-4-4 UHL1

500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -

240, 300 -

500

30,0 - 36,2 45,0

476 482

Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-07


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

13

29

AIZ-35-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 35 - nominal voltage, kV B - modification of bus-bar support for two wires 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA

AIZ-35-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--35-B...-4 UHL1

60

35 40,6 190

42

13
4 hol.

20 10 1 95

159

31,5

127
1480

Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-B...-4 UHL1 Assemblage

B
2 1274 hol. 13 14

POLYMER BUS-BAR SUPPORTS AIZ-35-B...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in Siberia. Advantages of bus-bar supports AIZ-35-B....UHL1 Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level

Wires according GOST 839-80, type

Wires according TS16-505.397-72 Diameter of wires, mm H max, mm

Type of flexible bus-bar support

, KP

S,SS, SP, ASK

PM
2

AIZ-35-B1-4 UHL1

Nominal cross-section, kv, mm 185/24; 185/29; 185; 240; 300 205/27; 240/32; 240/39
350; 400 450; 500 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27 -

17,5 - 22,1

470

AIZ-35-B2-4 UHL1
Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body

24,0 - 29,4

473

AIZ-35-B3-4 UHL1 AIZ-35-B4-4 UHL1

500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -

240, 300 -

500

30,0 - 36,2 45,0

476 485

GOST R 52082-03, TS3494-005-59116459-05

14 29

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ,RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

AIZ-35-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 35 - nominal voltage, kV G - modification for three hollow wires 1,2 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTIC Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 35 40,5 190

AIZ-35-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBLE BUS-BAR AIZ-35-G...-4 UHL1

Pic.1

Pic.2

42

For specified surface conductivity of polluted layer, mkCm


Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

20
10 1 95

13 4 hol.

159

31,5

127
1480

Number of bus- bar mounted

13

Bottom flange fitting dimensions, mm Weight, not more than, kg

1274 hol. see table

POLYMER BUS-BAR SUPPORTS AIZ-35-G...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in Siberia. Advantages of bus-bar supports AIZ-35-G....UHL1 Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury

TYPE TESTS FOR AIZ-35-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance Diameter between of wires, wires, L, mm, mm

H max, mm

Weight , kg

AIZ-35-G1-4 UHL1
Evaluation of partial discharge level Hydrophobic resistance to water

500

65

45,0

482

17,8

AIZ-35-G2-4 UHL1
Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body

500

120

45,0

502

18,0

AIZ-35-G3-4 UHL1
GOST R 52082-03, TS3494-005-59116459-05

500

200

45,0

502

18,0

15 29

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ,RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

AIZ-35-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ-35-V...-4 UHL1

AIZ-35-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 35 - nominal voltage, kV V- modification for two hollow wires

1,2 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTIC Nominal voltage, kV 35 40,5 190

Pic.1

Pic.2
Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm

42

20 10 1 95

13 4 hol.

Minimum failing load at bending, kN

159

Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA

31,5

127

Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

1480

Number of bus- bar mounted

2 1274 hol. see table 13

POLYMER BUS-BAR SUPPORTS AIZ-35-V...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. The monolithic core of insulator of bus-bar support eliminates possibility of internal discharge and breakdown, unlike tubes filled with foam, as well as leakage of current in internal cavity and on the wall of tube as consequence of condensation in contrast to hollow tubes. Flanges of bus-bar supports are made from cast high-strength aluminium alloys. Absence of welds in flanges allows applying insulators in the conditions of low temperature in Siberia. Advantages of bus-bar supports AIZ-35-V....UHL1 Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury

Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-V...-4 UHL1 Assemblage

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion )

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance between wires, L, mm,

Diameter of wires, mm

H max, mm

Weight , kg
Alternating short term test voltage in dry condition Failing load at bending (torsion )

AIZ-35-V1-4 UHL1

500

65

45,0

482

17,8

Evaluation of partial discharge level Hydrophobic resistance to water

AIZ-35-V2-4 UHL1

500

120

45,0

502

18,0
Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-35-V3-4 UHL1

500

200

45,0

502

18,0
GOST R 52082-03, TS3494-005-59116459-07

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 w ww.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

16

29

BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR FOR THE 35KV CURRENT AIZ-35-163-4 UHL1-AIZ-35-3125-4UHL1

AIZ-35-...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV 1M,2M,3M - 1,2,3 -flat vertical bus-bars 69-125 - width of vertical bus-bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694

UHL1 ic. ic.C

climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

35 40,5 190 42
20 10 1 95

13 4 hol. 159

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN
ic.

Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm

127

31,5

1480

see table 1274 hol. see table 13

BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ-35-...-4 UHL1
The outdoor application of bus- bar supports AIZ-35-M are used for fixing the flat rigid bus- bars in vertical position at 35 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-35-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.

Weight, not more than, kg TYPE TESTS FOR AIZ-35-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Rigid bus- bar support type AIZ-35-1M63-4UHL1 AIZ-35-1M80-4UHL1 AIZ-35-1M100-4UHL1 AIZ-35-1M125-4UHL1 AIZ-35-263-4UHL1 AIZ-35-280-4UHL1 AIZ-35-2100-4UHL1 AIZ-35-2125-4UHL1 AIZ-35-363-4UHL1 AIZ-35-380-4UHL1 AIZ-35-3100-4UHL1 AIZ-35-3125-4UHL1

Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125

Picture A A A A C C C C

Building height H, mm 482 500 520 545 482 500 520 545 482 500 520 545

Weight, kg 7,90 7,96 8,09 8,15 7,92 7,98 8,11 8,17 7,94 8,00 8,13 8,19

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-05


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

17

29

AIZ-35-L...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV 1L,2L,3L - 1,2,3 - flat horizontal bus- bar 63-125 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-35-1L63-4 UHL1 - AIZ-35-4L125-4 UHL1

ic.

ic.D

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-L...-4 UHL1 Assemblage External inspection ( outer view and marking )

35 40,5 190

42
20 10 1

ic.

ic.C

95

31,5

1480

see table

BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-35-L...-4 UHL1
1274 hol. see table 13 The outdoor application of bus- bar supports AIZ-35-L are used for fixing the flat rigid bus- bars in horizontal position at 35 kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-35-L are included in the integrated rigid bus- bar project of substations.Useful service life- 30 years.

Rigid bus- bar support type AIZ-35-1L63-4UHL1

Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125 4/63 4/80 4/100 4/125

Picture

Building height H, mm 438 442 446 448 458 452 456 468 478 482 486 488 498 502 506 508

Weight, kg 8,2 8,2 8,3 8,5 8,5 8,5 8,6 8,7 8,7 8,8 8,8 8,9 8,9 9,0 9,0 9,2

C C C C D D D D

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

AIZ-35-1L80-4UHL1 AIZ-35-1L100-4UHL1 AIZ-35-1L125-4UHL1 AIZ-35-2L63-4UHL1 AIZ-35-2L80-4UHL1 AIZ-35-2L100-4UHL1 AIZ-35-2L125-4UHL1 AIZ-35-3L63-4UHL1

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

AIZ-35-3L80-4UHL1
Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

AIZ-35-3L100-4UHL1 AIZ-35-3L125-4UHL1 AIZ-35-4L63-4UHL1 AIZ-35-4L80-4UHL1

Adhesion of coating layer to insulating body

AIZ-35-4L100-4UHL1 AIZ-35-4L125-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

18 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

POLYMER BUS-BAR SUPPORTSS INTENDED FOR TRANSITION FROM FLEXIBLE TO FLAT HORIZOTAL BUS-BARS AIZ-35-GL2/8-2/100-4 UHL1 - AIZ-35-GL2/24-4/125-4 UHL1

AIZ-35-GL...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35 - nominal voltage, kV GL - go with a flexible busbar on flat bus- bar

Contact plate for transition

Incorporated spacer AIZ-2, for wire maitaining

Horizontal flat bus- bar

2/8-2/100 - modification of the cross section of bus- bar and wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1

climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV

35 40,5 190 42
20 10 1 95

Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm

13 4 hol.

Minimum creepage distance, cm

159

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

31,5

1480

127

Number of bus- bar mounted Bottom flange fitting dimensions, mm

see table 1274 hol. see table 13

BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ-35-GL...-4 UHL1
The outdoor bus- bar supports AIZ-35-GL are used for transition from flexible to flat horizontal bus-bars with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.

Weight, not more than, kg TYPE TESTS FOR AIZ-35-GL...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating

Rigid bus- bar support type AIZ-35-GL2/8-2/100-2 UHL1 AIZ-35-GL2/12-3/125-2 UHL1 AIZ-35-GL2/12-4/125-2 UHL1 AIZ-35-GL2/16-3/125-2 UHL1 AIZ-35-GL2/16-4/125-2 UHL1 AIZ-35-GL2/20-3/125-2 UHL1 AIZ-35-GL2/20-4/125-2 UHL1

Number flexible wires bus- bar 2+8 2+12 2+12 2+16 2+16 2+20 2+20

Flat bus- bar mm


2bus-bar(100*10) 3bus-bar(125*10) 4bus-bar(125*10) 3bus-bar(125*10) 4bus-bar(125*10) 3bus-bar(125*10) 4bus-bar(125*10)

L 400 470 470 590 590 590 590

H 480 520 520 520 520 520 520

Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-05


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

19

29

AIZ-35-P...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV P - box shaped buses 100-250 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-35-P100-4 UHL1 - AIZ-35-P250-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-P...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

35 40,5 190

42
20 10 1 90

13 4 hol.

159

31,5

1480

1 1274 hol. . 13 13 see table

127

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-35-P...-4 UHL1


The outdoor application of bus- bar supports AIZ-35-P are used for fixing the box-shaped rigid bus- bars at 35 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231, TS3414-005-59116459-06. The bus- bar supports AIZ-35-P are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

Rigid bus- bar support type AIZ-35-P100-4 UHL1 AIZ-35-P125-4 UHL1 AIZ-35-P150-4 UHL1 AIZ-35-P175-4 UHL1 AIZ-35-P200-4 UHL1 AIZ-35-P225-4 UHL1 AIZ-35-P250-4 UHL1

Width of box of bus- bar mm 100 125 150 175 200 225 250

Building height H, mm 532 557 582 607 632 657 682

Weight, kg 12,60 12,70 12,80 12,95 13,10 13,30 13,50

GOST R 52082-03, TS3494-005-59116459-05

20 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-35-Z...-4 UHL

AIZ-35-Z...-4 UHL1
CONDITIONAL DESIGNATION AIZ -brand brandof ofpolymeric polymericbusbus-bar barsupports supports AIZ35 10-- nominal voltage, kV

D
Z -rigid -rigidfastening fasteningof ofaluminum aluminumtube tubebusbus-bar bar 30-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL UHL1 1climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS

ic.1

i.2

Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm

35 10 40,5 12 190 75 42 13
2 30 0 10 1 2 95 30

13 4 hol.

Minimum failing load at bending, kN

159

Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA

31,5 31,5

127

Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted

1480 1480

1 127 4 hol. 1274 hol. 13 see table see table 13

POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-35-Z...-4 UHL1


The outdoor bus- bar supports AIZ-35-Z are used for aluminum tubular bus-bar support with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-35-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request

Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-10-...-4 AIZ-35-Z...-4 UHL UHL1 1 Assemblage

External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-35-Z30-4UHL1 AIZ-35-Z40-4UHL1 AIZ-35-Z50-4UHL1 AIZ-35-Z70-4UHL1 AIZ-35-Z80-4UHL1 AIZ-35-Z90-4UHL1 AIZ-35-Z100-4UHL1 AIZ-35-Z110-4UHL1 AIZ-35-Z120-4UHL1 AIZ-35-Z130-4UHL1 AIZ-35-Z140-4UHL1 AIZ-35-Z150-4UHL1 AIZ-35-Z170-4UHL1 AIZ-35-Z200-4UHL1 AIZ-35-Z250-4UHL1

ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1

Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 519 519 520 530 538 542 554 560 562 575 580 590 610 630 655 16,1 16,2 16,5 16,8 18,0 18,3 18,5 18,7 19,3 21,3 21,3 22,4 23,5 27,5 33,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation Deviationangle anglecontrol controlat atbending bending ( (torsion torsion) )and and absence absenceof of plastic plasticdeformation deformationat atbending bending( (torsion torsion) ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

21

29

AIZ-35-SH...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports

BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-35-SH50-4 UHL1 - AIZ-35-SH250-4 UHL1

D
35- nominal voltage, kV SH - hinging of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

35 40,5 190

20 10 1 95

42

13 4 hol.

159

31,5

1480

127
1 1274 hol. see table 13

BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-35-SH...-4 UHL1
The bus- bar supports of outdoor application AIZ-35-SH are used for hinged fastening of tubular rigid bus-bar at 35 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-35-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus- bar support type AIZ-35-SH50-4UHL1 AIZ-35-SH60-4UHL1 AIZ-35-SH70-4UHL1 AIZ-35-SH80-4UHL1 AIZ-35-SH90-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 530 540 565 570 570 575 585 585 595 600 600 620 650 655 18,0 18,0 18,5 19,0 19,4 20,0 20,5 20,5 21,0 21,5 21,7 23,5 25,2 26,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-35-SH100-4UHL1 AIZ-35-SH110-4UHL1 AIZ-35-SH120-4UHL1 AIZ-35-SH130-4UHL1 AIZ-35-SH140-4UHL1 AIZ-35-SH150-4UHL1 AIZ-35-SH170-4UHL1 AIZ-35-SH200-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

AIZ-35-SH250-4UHL1

22 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARS AIZ-35-D...-4 UHL1

AIZ-35-D...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports

35- nominal voltage, kV D-movable fastening of aluminium tubular bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 35 40,5 190

42

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN

20 10 1 95

13 4 hol.

Minimum failing torsion moment, kNxm

159

Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted

31,5

1480

127

1 1274 hol. see table 13

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-35-D...-4 UHL1


The outdoor bus- bar supports AIZ-35-D are used for flexible fitting of aluminium tubular bus-bar support with 35 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-35-D are included in the integrated rigid bus-bar project of substations.

Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-D...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-35-D50-4UHL1 AIZ-35-D60-4UHL1 AIZ-35-D70-4UHL1 AIZ-35-D80-4UHL1 AIZ-35-D90-4UHL1 AIZ-35-D100-4UHL1 AIZ-35-D110-4UHL1 AIZ-35-D120-4UHL1 AIZ-35-D130-4UHL1 AIZ-35-D140-4UHL1 AIZ-35-D150-4UHL1 AIZ-35-D170-4UHL1 AIZ-35-D200-4UHL1 AIZ-35-D250-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 530 540 565 570 570 575 585 585 595 600 600 620 650 655

Weight, kg

18,0 18,0 18,5 19,0 19,4 20,0 20,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

20,5 21,0 21,5 21,7 23,5 25,2 26,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

23

29

AIZ-35-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV - end fastening of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ35-50-4 UHL1 -AIZ35-250-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

35 40,5 190

42

20 10 1 95

13 4 hol.

159

31,5

127
1480

1 1274 hol. see table 13

BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-35-...-4 UHL1


The outdoor bus- bar supports AIZ-35-K are used for end fixation of aluminium tubular bus-bar support with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Rigid bus- bar support type AIZ-35-50-4UHL1 AIZ-35-60-4UHL1 AIZ-35-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 495 498 525 530 530 545 545 550 560 570 600 620 650 655

Weight, kg

15,0 15,0 15,1 15,2 15,4 15,7 17,5 17,8 17,9 18,0 18,3 18,5 18,7 18,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-35-80-4UHL1 AIZ-35-90-4UHL1 AIZ-35-100-4UHL1 AIZ-35-110-4UHL1 AIZ-35-120-4UHL1 AIZ-35-130-4UHL1 AIZ-35-140-4UHL1 AIZ-35-150-4UHL1 AIZ-35-170-4UHL1 AIZ-35-200-4UHL1 AIZ-35-250-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

24 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE AIZ35-I...-4 UHL1

AIZ-35-I...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35 - nominal voltage, kV I -movable connection of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 35 40,5 190

13 4 hol.

159

50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN

42

20 10 1 95

Minimum failing torsion moment, kNxm

127

Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ- 35-I...-4 UHL1 Assemblage External inspection ( outer view and marking )

31,5

1480

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ35-I...-4 UHL1


The outdoor bus- bar supports AIZ-35-I are used for flexible connection of aluminium tubular bus-bar support with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

1 1274 hol. see table 13

Rigid bus- bar support type AIZ-35-I50-4UHL1 AIZ-35-I60-4UHL1 AIZ-35-I70-4UHL1 AIZ-35-I80-4UHL1 AIZ-35-I90-4UHL1 AIZ-35-I100-4UHL1 AIZ-35-I110-4UHL1 AIZ-35-I120-4UHL1 AIZ-35-I130-4UHL1 AIZ-35-I140-4UHL1 AIZ-35-I150-4UHL1 AIZ-35-I170-4UHL1 AIZ-35-I200-4UHL1 AIZ-35-I250-4UHL1

Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 530 540 565 570 570 575 585 585 595 600 600 620 650 655

Weight, kg

18,0 18,0 18,5 19,0 19,4 20,0 20,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

20,5 21,0 21,5 21,7 23,5 25,2 26,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

25

29

AIZ-35-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-35-50-4 UHL1 -AIZ35-250-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-35-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

35 40,5 190

42

20 10 1 95

13 4 hol.

159

31,5

127
1480

1 1274 hol. see table 13

BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ35-...-4 UHL1


The outdoor bus- bar supports AIZ-35-E are used for double fixation of aluminium tube with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-E are included in the integrated rigid busbar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus- bar support type AIZ-35-50-4UHL1 AIZ-35-60-4UHL1 AIZ-35-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 520 530 530 538 554 560 560 562 575 590 590 610 630 630

Weight, kg

16,0 16,0 16,1 16,2 16,4 16,7 18,5 18,8 18,9 19,0 19,3 19,5 19,7 19,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-35-80-4UHL1 AIZ-35-90-4UHL1 AIZ-35-100-4UHL1 AIZ-35-110-4UHL1 AIZ-35-120-4UHL1 AIZ-35-130-4UHL1 AIZ-35-140-4UHL1 AIZ-35-150-4UHL1 AIZ-35-170-4UHL1 AIZ-35-200-4UHL1 AIZ-35-250-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

26 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ35-S...-4 UHL1

AIZ-35-S...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 35 - nominal voltage, kV

S - for the installation of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV 35 40,5 1 90

L 13 4 hol.

159

Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm

42

20 10 1 95

127

Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm

Installation choices for bus- bar. The arrows indicate the axis of the aluminum tubes of rigid bus- bar.

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm

31,5

1480

1 1274 hol. see table 13

BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ35-S...-4 UHL1


The outdoor bus- bar supports AIZ-35-S are used for installation of two aluminium tubes with 35 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-35-S are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Please indicate and fill data sheet if it is necessary to install tubes with different diameter. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Weight, not more than, kg TYPE TESTS FOR AIZ-35-C...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-35-50-4UHL1 AIZ-35-60-4UHL1 AIZ-35-70-4UHL1 AIZ-35-80-4UHL1 AIZ-35-90-4UHL1 AIZ-35-100-4UHL1 AIZ-35-110-4UHL1 AIZ-35-120-4UHL1 AIZ-35-130-4UHL1 AIZ-35-140-4UHL1 AIZ-35-150-4UHL1 AIZ-35-170-4UHL1 AIZ-35-200-4UHL1 AIZ-35-250-4UHL1

Size L, 870 870 870 870 870 870 870 870 870 870 870 870 870 870

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 620 630 655 660 660 665 675 685 685 690 690 710 740 780

Weight, kg Weight, length of insulating part, fitting dimensions, armature spacing correspondence

33,5 34,6 35,0 36,0 37,2 38,0 38,5

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

40,0 43,0 44,0 45,0 48,0 114,0 122,0


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

27

29

AIZ-110-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ-110-A...-4 UHL1

AIZ-110-...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 110 - nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 110 126 450

18
H
4 hol.

110

220

For specified surface conductivity mkCm G, of polluted layer, Minimum failing load at GB, , bending, kN Minimum failing torsion , , moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

10 10 1 280

178

40

1480

Number of bus- bar mounted

1 1784 hol. 18 24

B
POLYMER BUS-BAR SUPPORTS AIZ-110-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury

Bottom flange fitting dimensions, mm

Weight, not more than, kg TYPE TESTS FOR AIZ-110-A...-4 UHL1 Assemblage

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating

Wires according GOST 839-80, type

Wires according TS16-505.397-72 Diameter of wires, mm H max, mm

Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

Type of flexible bus-bar support

, KP

S,SS, SP, ASK

PM
2

Nominal cross-section, kv, mm AIZ-110-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27

17,5 - 22,1

1130
Evaluation of partial discharge level

AIZ-110-2-4 UHL1

350; 400 450; 500

24,0 - 29,4

1133

Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

AIZ-110-3-4 UHL1 AIZ-110-4-4 UHL1

500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -

240, 300 -

500

30,0 - 36,2 45,0

1136 1142

Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-07

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

28

29

AIZ-110-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 110 - nominal voltage, kV B - modification of bus-bar support for two wires

AIZ-110-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--110-B...-4 UHL1

4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-B...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

110 126 450

1,2,3,4 - modification according cross section and type of wire

18
110

220

4 hol.

10 10 1 280

178
40

1480

2 1784 hol. see table 18

Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage.

POLYMER BUS-BAR SUPPORTS AIZ-110-B...-4 UHL1

Distance between wires, L, mm


60 60 60 120 120 120 200 200 200 400 400 400

Type of flexible bus-bar support

Wires according GOST 839-80, type , KP S, SS,SP, S


2

Nominal cross-section, mm AIZ-110-B1-4 UHL1 AIZ-110-B2-4 UHL1 AIZ-110-B3-4 UHL1 AIZ-110-B5-4 UHL1 AIZ-110-B6-4 UHL1 AIZ-110-B7-4 UHL1 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750

Diameter H max, Weight , kg mm of wires, mm


17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 1130 1133 1136 1147 1150 1153 1147 1150 1153 1147 1150 1153 24,8 24,8 24,9 25,3 25,2 25,1 25,5 25,6 25,8 26,8 27,1 27,4

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body

185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300

AIZ-110-B8-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 AIZ-110-B9-4 UHL1 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 AIZ-110-B10-4 UHL1 700; 750 650/79; 700/86; 240;300 AIZ-110-B11-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 AIZ-110-B12-4 UHL1 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 AIZ-110-B13-4 UHL1 700; 750 650/79; 700/86; 240;300
R

GOST R 52082-03, TS3494-005-59116459-05

29 29

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

AIZ-110-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--110-V...-4 UHL1

AIZ-110-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 110 - nominal voltage, kV V- modification for two hollow wires 1,2,3 - modification according cross section and type of wire

Pic.1

Pic.2

4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 110 126 450

18
4 hol.

50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

110

220
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion , , moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

10 10 1 280

178
Connection dimensions of bottom flange

40

1480

Number of bus- bar mounted Bottom flange fitting dimensions, mm

2 1784 hol.
see table

18

POLYMER BUS-BAR SUPPORTS AIZ-110-V .....UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

Weight, not more than, kg TYPE TESTS FOR AIZ-110-V...-4 UHL1 Assemblage

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance Diameter between of wires, wires, L, mm, mm

H max, mm

Weight , kg

Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

AIZ-110-1-4 UHL1

500

65

45,0

1142

27,8

Failing load at bending (torsion ) Evaluation of partial discharge level

AIZ-110-2-4 UHL1

500

120

45,0

1162

28,0
Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

AIZ-110-3-4 UHL1

500

200

45,0

1162

28,0
Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-07


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

30

29

AIZ-110-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 110 - nominal voltage, kV G - modification for three hollow wires 1,2,3 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

AIZ-110-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBLE BUS-BAR AIZ-110-G...-4 UHL1

110 126 450

110

10

18

10 1 280

4 hol.

220

40

178
1480

Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg

3 1784 hol. see table 18

Connection dimensions of bottom flange

POLYMER BUS-BAR SUPPORTS AIZ-110-G...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

TYPE TESTS FOR AIZ-110-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance Diameter between of wires, wires, L, mm, mm

H max, mm

Weight , kg

AIZ-110-G1-4 UHL1
Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body

500

65

45,0

1142

27,8

AIZ-110-G2-4 UHL1

500

120

45,0

1162

28,0

AIZ-110-G3-4 UHL1

500

200

45,0

1162

28,0

GOST R 52082-03, TS3494-005-59116459-05

31 29

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

AIZ-110-P...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 - nominal voltage, kV P - box shaped buses 100-250 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-110-P100-4 UHL1 -AIZ110-P250-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

110 126 450

110

10 1 280

10

18 4 hol.

220

40

1480

1 1274 hol 178 . . 18 13 see table

178

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ110-P...-4 UHL1


The outdoor application of bus- bar supports AIZ-110-P are used for fixing the box-shaped rigid bus- bars at 110 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231, TS3414-005-59116459-06. The bus- bar supports AIZ-110-P are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

Rigid bus- bar support type AIZ-110-P100-4 UHL1 AIZ-110-P125-4 UHL1 AIZ-110-P150-4 UHL1 AIZ-110-P175-4 UHL1 AIZ-110-P200-4 UHL1 AIZ-110-P225-4 UHL1 AIZ-110-P250-4 UHL1

Width of box of bus- bar mm 100 125 150 175 200 225 250

Building height H, mm 1232 1257 1282 1307 1332 1357 1382

Weight, kg 22,60 22,70 22,80 22,95 23,10 23,30 23,50

GOST R 52082-03, TS3494-005-59116459-05

32 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR FOR THE 110KV CURRENT AIZ110-163-4 UHL1-AIZ-110-3125-4UHL1

AIZ-110-...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 - nominal voltage, kV 1M,2M,3M - 1,2,3 -flat vertical bus- bar 69-125 -width vertical of the bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694

UHL1 i. i.C

climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

110 126 450 110

18 4 hol. 220

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN
i.

10 10 1 28

Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm

40

178

1480

see table 1784 hol. see table 18

BUS- BAR SUPPORTS FOR FLAT VERTICAL RIGID BUS- BAR AIZ110-...-4 UHL1
The outdoor application of bus- bar supports AIZ-110-M are used for fixing the flat rigid bus- bars in vertical position at 110 kV voltage open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-110-M are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.

Weight, not more than, kg TYPE TESTS FOR AIZ-110-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Rigid bus- bar support type AIZ-110-1M63-4UHL1 AIZ-110-1M80-4UHL1 AIZ-110-1M100-4UHL1 AIZ-110-1M125-4UHL1 AIZ-110-263-4UHL1 AIZ-110-280-4UHL1 AIZ-110-2100-4UHL1 AIZ-110-2125-4UHL1 AIZ-110-363-4UHL1 AIZ-35-380-4UHL1 AIZ-35-3100-4UHL1 AIZ-35-3125-4UHL1

Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125

Picture A A A A C C C C

Building height H, mm 1182 1200 1220 1245 1182 1200 1220 1245 1182 1200 1220 1245

Weight, kg 17,90 17,96 18,09 18,15 17,92 17,98 18,11 18,17 17,94 18,00 18,13 18,19

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

33

29

AIZ-110-L...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110- nominal voltage, kV 1L,2L,3L - 1,2,3 -flat horizontal bus- bar 63-125 - width of current-carrying mounting a bus- bar in mm 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ-110-1L63-4 UHL1 -AIZ-110-4L125-4 UHL1

i.

i.D

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-L...-4 UHL1 Assemblage External inspection ( outer view and marking )

110 126 450

110
10 10 1

i.

i.C

280

40

1480

see table 1784 hol. see table 18

BUS- BAR SUPPORTS FOR FLAT HORIZONTAL RIGID BUS- BAR AIZ110-L...-4 UHL1
The outdoor application of bus- bar supports AIZ-110-L are used for fixing the flat rigid bus- bars in horizontal position at 110 kV voltage open distribution devices of electric power stations and substations. Comply with GOST R 52082-03, TS3414-005-59116459-06. The bus- bar supports AIZ-110-L are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.

Rigid bus- bar support type AIZ-110-1L63-4UHL1

Quantity / width of bus- bar mm 1/63 1/80 1/100 1/125 2/63 2/80 2/100 2/125 3/63 3/80 3/100 3/125 4/63 4/80 4/100 4/125

Picture C C C C D D D D

Building height H, mm 1138 1142 1146 1148 1158 1152 1156 1168 1178 1182 1186 1188 1198 1202 1206 1208

Weight, kg 18,2 18,2 18,3 18,5 18,5 18,5 18,6 18,7 18,7 18,8 18,8 18,9 18,9 19,0 19,0 19,2

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

AIZ-110-1L80-4UHL1 AIZ-110-1L100-4UHL1 AIZ-110-1L125-4UHL1 AIZ-110-2L63-4UHL1 AIZ-110-2L80-4UHL1 AIZ-110-2L100-4UHL1

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

AIZ-110-2L125-4UHL1 AIZ-110-3L63-4UHL1 AIZ-110-3L80-4UHL1

Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-110-3L100-4UHL1 AIZ-110-3L125-4UHL1 AIZ-110-4L63-4UHL1 AIZ-110-4L80-4UHL1 AIZ-110-4L100-4UHL1 AIZ-110-4L125-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

34 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ35-Z...-4 UHL1

AIZ-110-Z...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 - nominal voltage, kV Z -rigid fastening of aluminum tube bus- bar 30-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694

Pic.1

i.2

UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm 110 126 450

18 4 hol. 220

110

10 10 1 280

Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm

178

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg

40

Connecting dimensions of bottom flange

1480

1 1784 hol. see table 18

POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ110-Z...-4 UHL1


The outdoor bus- bar supports AIZ-110-Z are used for aluminum tubular bus-bar support with 110 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-110-Z are included in the integrated rigid busbar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request TYPE TESTS FOR AIZ-110-Z...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Rigid bus- bar support type AIZ-110-Z30-4UHL1 AIZ-110-Z40-4UHL1 AIZ-110-Z50-4UHL1 AIZ-110-Z70-4UHL1 AIZ-110-Z80-4UHL1 AIZ-110-Z90-4UHL1 AIZ-110-Z100-4UHL1 AIZ-110-Z110-4UHL1 AIZ-110-Z120-4UHL1 AIZ-110-Z130-4UHL1 AIZ-110-Z140-4UHL1 AIZ-110-Z150-4UHL1 AIZ-110-Z170-4UHL1 AIZ-110-Z200-4UHL1 AIZ-110-Z250-4UHL1

ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1

Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 1179 1179 1180 1190 1198 1202 1214 1220 1222 1235 1240 1250 1270 1290 1315 26,1 26,2 26,5 26,8 28,0 28,3 28,5 28,7 29,3 31,3 31,3 32,4 33,5 37,5 43,5

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

35

29

AIZ-110-SH...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110- nominal voltage, kV SH - hinging of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-110-SH50-4 UHL1 -AIZ110-SH250-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

110 126 450

110

10 10 1 280

18 4 hol.

220

40

178
1480

1 1784 hol. see table 18

Connecting dimensions of bottom flange

The bus- bar supports of outdoor application AIZ-110-SH are used for hinged fastening of tubular rigid bus-bar at 110 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-110-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years.The factory can supply POLYMER BUSBAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ110-SH...-4 UHL1

Rigid bus- bar support type AIZ-110-SH50-4UHL1 AIZ-110-SH60-4UHL1 AIZ-110-SH70-4UHL1 AIZ-110-SH80-4UHL1 AIZ-110-SH90-4UHL1 AIZ-110-SH100-4UHL1 AIZ-110-SH110-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1190 1200 1225 1230 1230 1235 1245 1245 1255 1260 1260 1280 1310 1315

Weight, kg

28,0 28,0 28,5 29,0 29,4 30,0 30,5 30,5 31,0 31,5 31,7 33,5 35,2 36,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

AIZ-110-SH120-4UHL1 AIZ-110-SH130-4UHL1 AIZ-110-SH140-4UHL1 AIZ-110-SH150-4UHL1 AIZ-110-SH170-4UHL1

Adhesion of coating layer to insulating body

AIZ-110-SH200-4UHL1 AIZ-110-SH250-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

36 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARS AIZ110-D...-4 UHL1

AIZ-110-D...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110- nominal voltage, kV D-movable fastening of aluminium tubular bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 110 126 450

50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm

110

10 10 1 280

18 4 hol.

Minimum failing load at bending, kN

220

Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA

40

178

Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-D...-4 UHL1 Assemblage

1480

Connecting dimensions of bottom flange

1 1784 hol. see table 18

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ110-D...-4 UHL1


The outdoor bus- bar supports AIZ-110-D are used for flexible fitting of aluminium tubular bus-bar support with 110 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-110-D are included in the integrated rigid bus-bar project of substations.

External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-110-D50-4UHL1 AIZ-110-D60-4UHL1 AIZ-110-D70-4UHL1 AIZ-110-D80-4UHL1 AIZ-110-D90-4UHL1 AIZ-110-D100-4UHL1 AIZ-110-D110-4UHL1 AIZ-110-D120-4UHL1 AIZ-110-D130-4UHL1 AIZ-110-D140-4UHL1 AIZ-110-D150-4UHL1 AIZ-110-D170-4UHL1 AIZ-110-D200-4UHL1 AIZ-110-D250-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1190 1200 1225 1230 1230 1235 1245 1245 1255 1260 1260 1280 1310 1315

Weight, kg
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

28,0 28,0 28,5 29,0 29,4 30,0 30,5

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

30,5 31,0 31,5 31,7 33,5 35,2 36,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

37

29

AIZ-110-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110-nominal voltage, kV - end fastening of aluminum tube bus- bar 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ110-...-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

110 126 450

110

10 10 1 280

18 4 hol.

220

40

178
1480

1 1784 hol. see table 18

Connecting dimensions of bottom flange

BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ110-...-4 UHL1


The outdoor bus- bar supports AIZ-110-K are used for end fixation of aluminium tubular bus-bar support with 110 kV voltage on opened distribution devices of electric power stations and substations.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Rigid bus- bar support type AIZ-110-50-4UHL1 AIZ-110-60-4UHL1 AIZ-110-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1155 1158 1185 1190 1190 1205 1205 1210 1220 1230 1260 1280 1310 1315

Weight, kg

25,0 25,0 25,1 25,2 25,4 25,7 27,5 27,8 27,9 28,0 28,3 28,5 28,7 28,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-110-80-4UHL1 AIZ-110-90-4UHL1 AIZ-110-100-4UHL1 AIZ-110-110-4UHL1 AIZ-110-120-4UHL1 AIZ-110-130-4UHL1 AIZ-110-140-4UHL1 AIZ-110-150-4UHL1 AIZ-110-170-4UHL1 AIZ-110-200-4UHL1 AIZ-110-250-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

38 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE AIZ110-I...-4 UHL1

AIZ-110-I...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 -nominal voltage, kV I -movable connection of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm 110 126 450

18
4 hol.

110

220

10 10 1 280

178

Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted

Connecting dimensions of bottom flange

40

1480

1 1784 . see table 18

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ110-I...-4 UHL1


The outdoor bus- bar supports AIZ-110-I are used for flexible connection of aluminium tubular bus-bar support with 110 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ- 110-I...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-110-I50-4UHL1 AIZ-110-I60-4UHL1 AIZ-110-I70-4UHL1 AIZ-110-I80-4UHL1 AIZ-110-I90-4UHL1 AIZ-110-I100-4UHL1 AIZ-110-I110-4UHL1 AIZ-110-I120-4UHL1 AIZ-110-I130-4UHL1 AIZ-110-I140-4UHL1 AIZ-110-I150-4UHL1 AIZ-110-I170-4UHL1 AIZ-110-I200-4UHL1 AIZ-110-I250-4UHL1

Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520

Diameterof rigid Diameter bus-bar D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1190 1200 1225 1230 1230 1235 1245 1245 1255 1260 1260 1280 1310 1315

Weight, kg

28,0 28,0 28,5 29,0 29,4 30,0 30,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

30,5 31,0 31,5 31,7 33,5 35,2 36,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

39

29

AIZ-110-...-4 UHL1
DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ110-...-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

110 126 450

110

10 10 1 280

18 4 hol.

220

40

178
1480

1 1784 . see table 18

Connecting dimensions of bottom flange

BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ110-...-4 UHL1


The outdoor bus- bar supports AIZ-110-E are used for double fixation of aluminium tube with 110 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus- bar support type AIZ-110-50-4UHL1 AIZ-110-60-4UHL1 AIZ-110-70-4UHL1

Diameterof rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1180 1190 1190 1198 1214 1220 1220 1222 1235 1250 1250 1270 1290 1290

Weight, kg

26,0 26,0 26,1 26,2 26,4 26,7 28,5 28,8 28,9 29,0 29,3 29,5 29,7 29,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-110-80-4UHL1 AIZ-110-90-4UHL1 AIZ-110-100-4UHL1 AIZ-110-110-4UHL1 AIZ-110-120-4UHL1 AIZ-110-130-4UHL1 AIZ-110-140-4UHL1 AIZ-110-150-4UHL1 AIZ-110-170-4UHL1 AIZ-110-200-4UHL1 AIZ-110-250-4UHL1

GOST R 52082-03, TS3494-005-59116459-05

40 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ110-S...-4 UHL1

AIZ-110-S...-4 UHL1
CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports

110 -nominal voltage, kV S - for the installation of two aluminum tubes 50-250- rigid fastening of aluminum tube bus- bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS

L
Connecting dimensions of bottom flange

Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm

110 126 450

18
4 hol.

220

110

10 10 1 280

178
Installation choices for bus- bar. The arrows indicate the axis of aluminum tube rigid bus-bar.

Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted

40

1480

1 1784 . see table 18

BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ110-S...-4 UHL1


The outdoor bus- bar supports AIZ-110-S are used for installation of two aluminium tubes with 110 kV voltage on opened distribution devices of electric power stations and substations.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-S are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Please indicate and fill data sheet if it is necessary to install tubes with different diameter. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-C...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus- bar support type AIZ-110-50-4UHL1 AIZ-110-60-4UHL1 AIZ-110-70-4UHL1 AIZ-110-80-4UHL1 AIZ-110-90-4UHL1 AIZ-110-100-4UHL1 AIZ-110-110-4UHL1 AIZ-110-120-4UHL1 AIZ-110-130-4UHL1 AIZ-110-140-4UHL1 AIZ-110-150-4UHL1 AIZ-110-170-4UHL1 AIZ-110-200-4UHL1 AIZ-110-250-4UHL1

Size L, 870 870 870 870 870 870 870 870 870 870 870 870 870 870

Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1280 1290 1315 1320 1320 1325 1325 1335 1345 1350 1350 1370 1400 1440

Weight, kg

43,5 44,6 45,0 46,0 47,2 48,0 48,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

50,0 53,0 54,0 55,0 58,0 124,0 132,0


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TS3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

41

29

AIZ-110-GL...-4 UHL1
CONDITIONAL DESIGNATION AIZ- brand of polymeric bus- bar supports 110 - nominal voltage, kV GL- transition fromr 2/8-2/100 - modification of the cross section of bus- bar and wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

POLYMER BUS-BAR SUPPORTS INTENDED FOR TRANSITION FROM FLEXIBLE TO FLAT HORIZOTAL BUS-BARS AIZ110-GL2/8-2/100-4 UHL1 - AIZ35-GL2/24-4/125-4 UHL1

Contact plate for transition

Incorporated spacer AIZ-2, for wire maitaining

Horizontal flat bus- bar

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-110-GL...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

110 126 450

110

10 10 1

The of bottom flange


280

18 4 hol. 220

40

1480

see table 1784 hol. see table 18

178

BUS-BAR SUPPORTS FOR TRANSITION FROM FLEXIBLE TO HORIZONTAL BUS-BAR AIZ110-GL...-4 UHL1
The outdoor bus- bar supports AIZ-110-GL are used for transition from flexible to flat horizontal bus-bars with 110 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-110-GL are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. Bus-bar supports for the box-shaped buses have an increased rigidity and durability on break. Bus-bar supports endures short circuit currents, even more then it requires normative standards. An exploitation of monolith fibreglass rod with 800 kN (80 ts) real breaking load, reduces possibility and the risk of falling down the bus-bar on the ground. Application of silicon and stable to tracking and hydrophobic protective cover of insulator allows applying bus-bar supports on substations, opened distribution devices in conditions of high pollution degree, also it allows to exploit it in industrial objects, railway and in places with high pollution degree.

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

Rigid bus- bar support type AIZ-110-GL2/8-2/100-2 UHL1 AIZ-110-GL2/12-3/125-2 UHL1 AIZ-110-GL2/12-4/125-2 UHL1 AIZ-110-GL2/16-3/125-2 UHL1 AIZ-110-GL2/16-4/125-2 UHL1 AIZ-110-GL2/20-3/125-2 UHL1 AIZ-110-GL2/20-4/125-2 UHL1

Number flexible wires bus- bar 2+8 2+12 2+12 2+16 2+16 2+20 2+20

Flat bus- bar mm


2bus-bar(100*10) 3bus-bar(125*10) 4bus-bar(125*10) 3bus-bar(125*10) 4bus-bar(125*10) 3bus-bar(125*10) 4bus-bar(125*10)

L 400 470 470 590 590 590 590

H 1180 1220 1220 1220 1220 1220 1220

GOST R 52082-03, TS3494-005-59116459-05

42 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 w ww.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

AIZ-150-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ-150-...-4 UHL1

AIZ-150-...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 150 - nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 150 172 650

18
H
4 hol.

150

220

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

10 10 1 390

178

40

1480

Number of bus- bar mounted

1 1784 hol. 18 28

B
POLYMER BUS-BAR SUPPORTS AIZ-150-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-A...-4 UHL1 Assemblage

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Wires according GOST 839-80, type

Wires according TS16-505.397-72 Diameter of wires, mm H max, mm

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

Type of flexible bus-bar support

, KP

S,SS, SP, ASK

PM
2

Nominal cross-section, kv, mm AIZ-150-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27

17,5 - 22,1

1630

Failing load at bending (torsion ) Evaluation of partial discharge level

AIZ-150-2-4 UHL1

350; 400 450; 500

24,0 - 29,4

1633
Hydrophobic resistance to water

AIZ-150-3-4 UHL1 AIZ-150-4-4 UHL1

500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -

240, 300 -

500

30,0 - 36,2 45,0

1636 1642

Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-07


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 w ww.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

43

29

AIZ-150-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 150 - nominal voltage, kV B - modification of bus-bar support for two wires 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

AIZ-150-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--150-B...-4 UHL1

150 172 650

18
150

220

4 hol.

10 10 1 390

178
40

1480

Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-B...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

2 1784 hol. see table 18

POLYMER BUS-BAR SUPPORTS AIZ-150-B...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage.

Distance between wires, L, mm


60 60 60 120 120 120 200 200 200 400 400 400

Type of flexible bus-bar support

Wires according GOST 839-80, type , KP S, SS,SP, S


2

Nominal cross-section, mm AIZ-150-B1-4 UHL1 AIZ-150-B2-4 UHL1 AIZ-150-B3-4 UHL1 AIZ-150-B5-4 UHL1 AIZ-150-B6-4 UHL1 AIZ-150-B7-4 UHL1 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750

Diameter H max, Weight , kg mm of wires, mm


17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 1630 1633 1636 1647 1650 1653 1647 1650 1653 1647 1650 1653 28,8 28,8 28,9 29,3 29,2 29,1 29,5 29,6 29,8 30,8 31,1 31,4

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body

185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300

AIZ-150-B8-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 AIZ-150-B9-4 UHL1 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 AIZ-150-B10-4 UHL1 700; 750 650/79; 700/86; 240;300 AIZ-150-B11-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 AIZ-150-B12-4 UHL1 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 AIZ-150-B13-4 UHL1 700; 750 650/79; 700/86; 240;300
R

GOST R 52082-03, TS3494-005-59116459-05

29 44

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

AIZ-150-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ-150-V...-4 UHL1

AIZ-150-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 150 - nominal voltage, kV V- modification for two hollow wires 1,2,3 - modification according cross section and type of wire

Pic.1

Pic.2

4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 150 172 650

18
4 hol.

50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

150

220
For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

10 10 1 390

178
Connection dimensions of bottom flange

40

1480

Number of bus- bar mounted Bottom flange fitting dimensions, mm

2 1784 hol. see table 18

POLYMER BUS-BAR SUPPORTS AIZ-150-V...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

Weight, not more than, kg TYPE TESTS FOR AIZ-150-V...-4 UHL1 Assemblage

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance Diameter between of wires, wires, L, mm, mm

H max, mm

Weight , kg

Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

AIZ-150-1-4 UHL1

500

65

45,0

1642

31,8

Failing load at bending (torsion ) Evaluation of partial discharge level

AIZ-150-2-4 UHL1

500

120

45,0

1662

32,0
Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

AIZ-150-3-4 UHL1

500

200

45,0

1662

32,0
Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-07


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

45

29

AIZ-150-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 150 - nominal voltage, kV G - modification for three hollow wires 1,2,3 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

AIZ-35-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF BUS-BAR FIXATION AIZ-150-G...-4 UHL1

150 172 650

150

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA

10

18 H 4 hol. 220

10 1 390

40

178
1480

Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg

3 1784 hol. see table 18

Connection dimensions of bottom flange

POLYMER BUS-BAR SUPPORTS AIZ-150-G...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

TYPE TESTS FOR AIZ-150-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance Diameter between of wires, wires, L, mm, mm

H max, mm

Weight , kg

AIZ-150-G1-4 UHL1
Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body

500

65

45,0

1642

31,8

AIZ-150-G2-4 UHL1

500

120

45,0

1662

32,0

AIZ-150-G3-4 UHL1

500

200

45,0

1662

32,0

GOST R 52082-03, TS3494-005-59116459-05

46 29

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBESS AIZ-150-Z...-4 UHL1

AIZ -150-Z...-4 UHL1


CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 150 - nominal voltage, kV Z -rigid fastening of aluminum tube bus bar 30-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694

Pic.1

Pic.2

UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm 150 172 650

18 4 hol. 220

150

10 10 1 390

Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm

178

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg

40

Connecting dimensions of bottom flange

1480

1 1784 hol. see table 18

POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-150-Z...-4 UHL1


The outdoor bus- bar supports AIZ-150-Z are used for aluminum tubular bus-bar support with 1 50 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-150-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request TYPE TESTS FOR AIZ-150-Z...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Rigid bus bar support type AIZ-150-Z30-4UHL1 AIZ-150-Z40-4UHL1 AIZ-150-Z50-4UHL1 AIZ-150-Z70-4UHL1 AIZ-150-Z80-4UHL1 AIZ-150-Z90-4UHL1 AIZ-150-Z100-4UHL1 AIZ-150-Z110-4UHL1 AIZ-150-Z120-4UHL1 AIZ-150-Z130-4UHL1 AIZ-150-Z140-4UHL1 AIZ-150-Z150-4UHL1 AIZ-150-Z170-4UHL1 AIZ-150-Z200-4UHL1 AIZ-150-Z250-4UHL1

ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1

Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 1679 1679 1680 1690 1698 1702 1714 1720 1722 1735 1740 1750 1770 1790 1815 30,1 30,2 30,5 30,8 32,0 32,3 32,5 32,7 33,3 35,3 35,3 36,4 37,5 41,5 47,5

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TU3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

47

29

AIZ -150-SH...-4 UHL1


CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 150- nominal voltage, kV SH - hinging of aluminum tube bus-bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-150-SH50-4 UHL1 - AIZ-150-SH250-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

150 172 650

150

10 10 1 390

18 4 hol.

220

40

178
1480

1 1784 hol. see table 18

Connecting dimensions of bottom flange

BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-150-SH...


The bus- bar supports of outdoor application AIZ-150-SH are used for hinged fastening of tubular rigid bus-bar at 150 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-150-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus bar support type AIZ-150-SH50-4UHL1 AIZ-150-SH60-4UHL1 AIZ-150-SH70-4UHL1 AIZ-150-SH80-4UHL1 AIZ-150-SH90-4UHL1 AIZ-150-SH100-4UHL1 AIZ-150-SH110-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1690 1700 1725 1730 1730 1735 1745 1745 1755 1760 1760 1780 1810 1815

Weight, kg

32,0 32,0 32,5 33,0 33,4 34,0 34,5 34,5 35,0 35,5 35,7 37,5 39,2 40,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

AIZ-150-SH120-4UHL1 AIZ-150-SH130-4UHL1 AIZ-150-SH140-4UHL1 AIZ-150-SH150-4UHL1 AIZ-150-SH170-4UHL1

Adhesion of coating layer to insulating body

AIZ-150-SH200-4UHL1 AIZ-150-SH250-4UHL1

GOST R 52082-03, TU3494-005-59116459-05

48 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARS AIZ-150-D...-4 UHL1

AIZ -150-D...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 150-nominal voltage, kV D-movable fastening of aluminum tube bus-bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm 150 172 650

150

10 10 1 390

18 4 hol.

Minimum failing load at bending, kN

220

Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA

40

178

Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm

1480

Connecting dimensions of bottom flange

1 1784 hol. see table 18

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF RIGID BUS-BARS AIZ-150-D...-4 UHL1


The outdoor bus- bar supports AIZ-150-D are used for flexible fitting of aluminium tubular bus-bar support with 150 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-150-D are included in the integrated rigid bus-bar project of substations

Weight, not more than, kg TYPE TESTS FOR AIZ-150-D...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus bar support type AIZ-150-D50-4UHL1 AIZ-150-D60-4UHL1 AIZ-150-D70-4UHL1 AIZ-150-D80-4UHL1 AIZ-150-D90-4UHL1 AIZ-150-D100-4UHL1 AIZ-150-D110-4UHL1 AIZ-150-D120-4UHL1 AIZ-150-D130-4UHL1 AIZ-150-D140-4UHL1 AIZ-150-D150-4UHL1 AIZ-150-D170-4UHL1 AIZ-150-D200-4UHL1 AIZ-150-D250-4UHL1
R

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1690 1700 1725 1730 1730 1735 1745 1745 1755 1760 1760 1780 1810 1815

Weight, kg

32,0 32,0 32,5 33,0 33,4 34,0 34,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

34,5 35,0 35,5 35,7 37,5 39,2 46,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TU3494-005-59116459-05

AIZ- regis regist tra rat ted ed trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

49

29

AIZ -150-...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 150-nominal voltage, kV - end fastening of aluminum tube bus bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-150-...-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

150 172 650

150

10 10 1 390

18 4 hol.

220

40

178
1480

1 1784 hol. see table 18

Connecting dimensions of bottom flange

BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-150-...-4 UHL1


The outdoor bus- bar supports AIZ-150-K are used for end fixation of aluminium tubular bus-bar support with 150 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-150-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Rigid bus bar support type AIZ-150-50-4UHL1 AIZ-150-60-4UHL1 AIZ-150-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1655 1658 1685 1690 1690 1705 1705 1710 1720 1730 1760 1780 1810 1815

Weight, kg

29,0 29,0 29,1 29,2 29,4 29,7 29,5 31,8 31,9 32,0 32,3 32,5 32,7 32,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-150-80-4UHL1 AIZ-150-90-4UHL1 AIZ-150-100-4UHL1 AIZ-150-110-4UHL1 AIZ-150-120-4UHL1 AIZ-150-130-4UHL1 AIZ-150-140-4UHL1 AIZ-150-150-4UHL1 AIZ-150-170-4UHL1 AIZ-150-200-4UHL1 AIZ-150-250-4UHL1

GOST R 52082-03, TU3494-005-59116459-05

50 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE AIZ-150-I...-4 UHL1

AIZ -150-I...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ- brand of polymeric bus bar supports 150 -nominal voltage, kV I -movable connection of two aluminum tubes 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 150 172 650

150

18
4 hol.

220

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm

10 10 1 390

178

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm

40

Connecting dimensions of bottom flange

1480

1 1784 hol. see table 18

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ-150-I...-4 UHL1


The outdoor bus- bar supports AIZ-150-I are used for flexible connection of aluminium tubular bus-bar support with 150 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-150-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years.The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Weight, not more than, kg TYPE TESTS FOR AIZ- 150-I...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus bar support type AIZ-150-I50-4UHL1 AIZ-150-I60-4UHL1 AIZ-150-I70-4UHL1 AIZ-150-I80-4UHL1 AIZ-150-I90-4UHL1 AIZ-150-I100-4UHL1 AIZ-150-I110-4UHL1 AIZ-150-I120-4UHL1 AIZ-150-I130-4UHL1 AIZ-150-I140-4UHL1 AIZ-150-I150-4UHL1 AIZ-150-I170-4UHL1 AIZ-150-I200-4UHL1 AIZ-150-I250-4UHL1

Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520

Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1690 1700 1725 1730 1730 1735 1745 1745 1755 1760 1760 1780 1810 1815

Weight, kg

32,0 32,0 32,5 33,0 33,4 34,0 34,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

34,5 35,0 35,5 35,7 37,5 39,2 40,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TU3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

51

29

AIZ -150-...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 150- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-150-...-4 UHL1

L D

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-150-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

150 172 650

10 10 1 390

150

18 4 hol.

220

40

178
1480

1 1784 hol. see table 18

Connecting dimensions of bottom flange

BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ-150-...-4 UHL1


The outdoor bus- bar supports AIZ-150-E are used for double fixation of aluminium tube with 150 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-150-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus bar support type AIZ-150-50-4UHL1 AIZ-150-60-4UHL1 AIZ-150-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 1680 1690 1690 1698 1714 1720 1720 1722 1735 1750 1750 1770 1790 1790

Weight, kg

30,0 30,0 30,1 30,2 30,4 30,7 32,5 32,8 32,9 33,0 33,3 33,5 33,7 33,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-150-80-4UHL1 AIZ-150-90-4UHL1 AIZ-150-100-4UHL1 AIZ-150-110-4UHL1 AIZ-150-120-4UHL1 AIZ-150-130-4UHL1 AIZ-150-140-4UHL1 AIZ-150-150-4UHL1 AIZ-150-170-4UHL1 AIZ-150-200-4UHL1 AIZ-150-250-4UHL1

GOST R 52082-03, TU3494-005-59116459-05

52 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

AIZ-220-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ--220-...-4 UHL1

AIZ-220-...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 220 - nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire

4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

220 252 950

18
4 hol.

220

265

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm

10 8 2 570

225

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted

100

1480

1 2254 hol. 18
75

B
POLYMER BUS-BAR SUPPORTS AIZ-220-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-A...-4 UHL1 Assemblage

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Wires according GOST 839-80, type

Wires according TS16-505.397-72 Diameter of wires, mm H max, mm

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

Type of flexible bus-bar support

, KP

S,SS, SP, ASK

PM
2

Nominal cross-section, kv, mm AIZ-220-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27

17,5 - 22,1

2130

Failing load at bending (torsion ) Evaluation of partial discharge level

AIZ-220-2-4 UHL1

350; 400 450; 500

24,0 - 29,4

2133
Hydrophobic resistance to water

AIZ-220-3-4 UHL1 AIZ-220-4-4 UHL1

500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -

240, 300 -

500

30,0 - 36,2 45,0

2136 2142

Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-07


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

53

29

AIZ-220-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 220 - nominal voltage, kV B - modification of bus-bar support for two wires 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

AIZ-220-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBILE BUS-BAR FIXATION AIZ--220-B...-4 UHL1

220

18
252 950

265

4 hol.

220

10 8 1 570

225

100

1480

Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-B...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

2 2254 hol. see table 18

Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage.

POLYMER BUS-BAR SUPPORTS AIZ-220-B...-4 UHL1

Distance between wires, L, mm


60 60 60 120 120 120 200 200 200 400 400 400

Type of flexible bus-bar support

Wires according GOST 839-80, type , KP S, SS,SP, S


2

Nominal cross-section, mm AIZ-220-B1-4 UHL1 AIZ-220-B2-4 UHL1 AIZ-220-B3-4 UHL1 AIZ-220-B5-4 UHL1 AIZ-220-B6-4 UHL1 AIZ-220-B7-4 UHL1 AIZ-220-B8-4 UHL1 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750

Diameter H max, Weight , kg mm of wires, mm


17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 2130 2133 2136 2147 2150 2153 2147 2150 2153 2147 2150 2153 74,8 74,8 74,9 75,3 75,2 75,1 75,5 75,6 75,8 76,8 77,1 77,4

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body

185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300

AIZ-220-B9-4 UHL1 AIZ-220-B10-4 UHL1 AIZ-220-B11-4 UHL1 AIZ-220-B12-4 UHL1 AIZ-220-B13-4 UHL1

185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 700; 750 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 700; 750 650/79; 700/86; 240;300 185; 240; 300
R

GOST R 52082-03, TS3494-005-59116459-05

54 29

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

AIZ-220-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBLE BUS-BAR FIXATION AIZ--220-V...-4 UHL1

AIZ-220-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports

L
220 - nominal voltage, kV V- modification for two hollow wires
Pic.1 Pic.2

1,2,3 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

220 252 950

220

18
4 hol.

265

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm

10 8
2

570

225
Connection dimensions of bottom flange

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

100

1480

Number of bus- bar mounted Bottom flange fitting dimensions, mm

2 2254 hol. see table 18

POLYMER BUS-BAR SUPPORTS AIZ-220-V...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

Weight, not more than, kg TYPE TESTS FOR AIZ-220-V...-4 UHL1 Assemblage

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance Diameter between of wires, wires, L, mm, mm

H max, mm

Weight , kg

Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

AIZ-220-1-4 UHL1

500

65

45,0

2142

77,8

Failing load at bending (torsion ) Evaluation of partial discharge level

AIZ-220-2-4 UHL1

500

120

45,0

2162

78,0
Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

AIZ-220-3-4 UHL1

500

200

45,0

2162

78,0
Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-07


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

55

29

AIZ-220-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 220 - nominal voltage, kV G - modification for three hollow wires 1,2,3 - bus-bar fitting modification

AIZ-220-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBLE BUS-BAR AIZ--220-G1-4 UHL1, AIZ-220-G2-4 UHL1, AIZ-220-G3-4 UHL1

L
4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

220 252 950

18
4 hol.

265

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

10

220

225
8 2 570

Connection dimensions of bottom flange

100

1480

Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg

3 2254 hol. see table 18

POLYMER BUS-BAR SUPPORTS AIZ-220-G...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

TYPE TESTS FOR AIZ-220-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance Diameter between of wires, wires, L, mm, mm

H max, mm

Weight , kg

AIZ-220-G1-4 UHL1
Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body

500

65

45,0

2142

77,8

AIZ-220-G2-4 UHL1

500

120

45,0

2162

78,0

AIZ-220-G3-4 UHL1

500

200

45,0

2162

78,0

GOST R 52082-03, TS3494-005-59116459-05

56 29

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-220-Z...-4 UHL1

AIZ -220-Z...-4 UHL1


CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 10- nominal voltage, kV Z -rigid fastening of aluminum tube bus bar 30-250- rigid fastening of aluminum tube bus bar

Pic.1

Pic.2

4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV 220 252 950

18
4 hol.

265

Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm

220

225

10 8
2

Connecting dimensions of bottom flange

Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm

570

100

1480

1 2254 hol. see table 18

POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-220-Z...-4 UHL1


The outdoor bus- bar supports AIZ-220-Z are used for aluminum tubular bus-bar support with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-220-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request

Weight, not more than, kg TYPE TESTS FOR AIZ ()-10-Z...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus bar support type AIZ-220-Z30-4UHL1 AIZ-220-Z40-4UHL1 AIZ-220-Z50-4UHL1 AIZ-220-Z70-4UHL1 AIZ-220-Z80-4UHL1 AIZ-220-Z90-4UHL1 AIZ-220-Z100-4UHL1 AIZ-220-Z110-4UHL1 AIZ-220-Z120-4UHL1 AIZ-220-Z130-4UHL1 AIZ-220-Z140-4UHL1 AIZ-220-Z150-4UHL1 AIZ-220-Z170-4UHL1 AIZ-220-Z200-4UHL1 AIZ-220-Z250-4UHL1

ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1

Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 2179 2179 2180 2190 2198 2202 2214 2220 2222 2235 2240 2250 2270 2290 2315 76,1 76,2 76,5 76,8 78,0 78,3 78,5 78,7 79,3 81,3 81,3 82,4 83,5 87,5 83,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TU3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

57

29

AIZ -220-SH...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 220- nominal voltage, kV SH - hinging of aluminum tube bus-bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-220-SH50-4 UHL1 - AIZ-220-SH250-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

220 252 950

220

10 8

18 4 hol.

220

2 570

100

178

1480

Connecting dimensions of bottom flange

1 1784 hol. see table 18

BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-220-SH..


The bus- bar supports of outdoor application AIZ-220-SH are used for hinged fastening of tubular rigid bus-bar at 220 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-220-SH are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus bar support type AIZ-220-SH50-4UHL1 AIZ-220-SH60-4UHL1 AIZ-220-SH70-4UHL1 AIZ-220-SH80-4UHL1 AIZ-220-SH90-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 2190 2200 2225 2230 2230 2235 2245 2245 2255 2260 2260 2280 2310 2315

Weight, kg

78,0 78,0 78,5 79,0 79,4 80,0 80,5 80,5 81,0 81,5 81,7 83,5 85,2 86,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-220-SH100-4UHL1 AIZ-220-SH110-4UHL1 AIZ-220-SH120-4UHL1 AIZ-220-SH130-4UHL1 AIZ-220-SH140-4UHL1 AIZ-220-SH150-4UHL1 AIZ-220-SH170-4UHL1 AIZ-220-SH200-4UHL1

GOST R 52082-03, TU3494-005-59116459-05

AIZ-220-SH250-4UHL1

58 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-220-D...-4 UHL1

AIZ -220-D...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports

220-nominal voltage, kV D-movable fastening of aluminum tube bus-bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN 220 252 950

220

10 8 2 570

18 4 hol.

220

Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N

100

178

1480

Connecting dimensions of bottom flange

Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg

1 1784 hol. see table 18

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-220-D...-4 UHL1


The outdoor bus- bar supports AIZ-220-D are used for flexible fitting of aluminium tubular bus-bar support with 220 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-220-D are included in the integrated rigid bus-bar project of substations. TYPE TESTS FOR AIZ-220-D...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus bar support type AIZ-220-D50-4UHL1 AIZ-220-D60-4UHL1 AIZ-220-D70-4UHL1 AIZ-220-D80-4UHL1 AIZ-220-D90-4UHL1 AIZ-220-D100-4UHL1 AIZ-220-D110-4UHL1 AIZ-220-D120-4UHL1 AIZ-220-D130-4UHL1 AIZ-220-D140-4UHL1 AIZ-220-D150-4UHL1 AIZ-220-D170-4UHL1 AIZ-220-D200-4UHL1 AIZ-220-D250-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 2190 2200 2225 2230 2230 2235 2245 2245 2255 2260 2260 2280 2310 2315

Weight, kg
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

78,0 78,0 78,5 79,0 79,4 80,0 80,5

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

80,5 81,0 81,5 81,7 83,5 85,2 86,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TU3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

59

29

AIZ -220-...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 220-nominal voltage, kV

BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-220-...-4 UHL1

- end fastening of aluminum tube bus bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

220 252 950

220

10 8 2 570

18 4 hol.
H

220

100

178

1480

Connecting dimensions of bottom flange

1 1784 hol. see table 18

BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-220-...-4 UHL1


The outdoor bus- bar supports AIZ-220-K are used for end fixation of aluminium tubular bus-bar support with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-220-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Rigid bus bar support type AIZ-220-50-4UHL1 AIZ-220-60-4UHL1 AIZ-220-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 2155 2158 2185 2190 2190 2205 2205 2210 2220 2230 2260 2280 2310 2315

Weight, kg

75,0 75,0 75,1 75,2 75,4 75,7 75,5 77,8 77,9 78,0 78,3 78,5 78,7 78,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-220-80-4UHL1 AIZ-220-90-4UHL1 AIZ-220-100-4UHL1 AIZ-220-110-4UHL1 AIZ-220-120-4UHL1 AIZ-220-130-4UHL1 AIZ-220-140-4UHL1 AIZ-220-150-4UHL1 AIZ-220-170-4UHL1 AIZ-220-200-4UHL1 AIZ-220-250-4UHL1

GOST R 52082-03, TU3494-005-59116459-05

60 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE AIZ-220-I...-4 UHL1

AIZ -220-I...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ- brand of polymeric bus bar supports 220 -nominal voltage, kV I -movable connection of two aluminum tubes 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 220 252 950

220

18
4 hol.

220

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm

10 8 2 570

178

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm

100

Connecting dimensions of bottom flange

1480

1 1784 hol. see table 18

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ-220-I...-4 UHL1


The outdoor bus- bar supports AIZ-220-I are used for flexible connection of aluminium tubular bus-bar support with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06.The bus-bar supports AIZ-220-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Weight, not more than, kg TYPE TESTS FOR AIZ- 220-I...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus bar support type AIZ-220-I50-4UHL1 AIZ-220-I60-4UHL1 AIZ-220-I70-4UHL1 AIZ-220-I80-4UHL1 AIZ-220-I90-4UHL1 AIZ-220-I100-4UHL1 AIZ-220-I110-4UHL1 AIZ-220-I120-4UHL1 AIZ-220-I130-4UHL1 AIZ-220-I140-4UHL1 AIZ-220-I150-4UHL1 AIZ-220-I170-4UHL1 AIZ-220-I200-4UHL1 AIZ-220-I250-4UHL1

Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520

Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 2190 2200 2225 2230 2230 2235 2245 2245 2255 2260 2260 2280 2210 2215

Weight, kg

78,0 78,0 78,5 79,0 79,4 80,0 80,5 80,5 81,0 81,5 81,7 83,5 85,2 86,9

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TU3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

61

29

AIZ -220-...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 220- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-220-...-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-220-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

220 252 950

220

10 8 2 570

18 4 hol.
H

220

100

178

1480

Connecting dimensions of bottom flange

1 1784 hol. see table 18

BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ-220-...-4 UHL1


The outdoor bus- bar supports AIZ-220-E are used for double fixation of aluminium tube with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-220-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus bar support type AIZ-220-50-4UHL1 AIZ-220-60-4UHL1 AIZ-220-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 2180 2190 2190 2198 2214 2220 2220 2222 2235 2250 2250 2270 2290 2290

Weight, kg

76,0 76,0 76,1 76,2 76,4 76,7 78,5 78,8 78,9 79,0 79,3 79,5 79,7 79,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-220-80-4UHL1 AIZ-220-90-4UHL1 AIZ-220-100-4UHL1 AIZ-220-110-4UHL1 AIZ-220-120-4UHL1 AIZ-220-130-4UHL1 AIZ-220-140-4UHL1 AIZ-220-150-4UHL1 AIZ-220-170-4UHL1 AIZ-220-200-4UHL1 AIZ-220-250-4UHL1

GOST R 52082-03, TU3494-005-59116459-05

62 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ-220-S...-4 UHL1

AIZ -220-S...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 220 -nominal voltage, kV

S - for the installation of two aluminum tubes 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV 220 252 950

L
Connecting dimensions of bottom flange

Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN

18
4 hol.

220

220

10 8 2 570

178
Installation choices for bus bar. The arrows indicate the axis aluminum tube rigid busbar

Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm

100

1480

1 1784 hol. see table 18

BUS-BAR SUPPORTS FOR INSTALATION OF TWO ALUMINIUM TUBES AIZ-220-S...-4 UHL1


The outdoor bus- bar supports AIZ-220-S are used for installation of two aluminium tubes with 220 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-220-S are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years.Please indicate and fill data sheet if it is necessary to install tubes with different diameter. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Weight, not more than, kg TYPE TESTS FOR AIZ-220-S...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Rigid bus bar support type AIZ-220-50-4UHL1 AIZ-220-60-4UHL1 AIZ-220-70-4UHL1 AIZ-220-80-4UHL1 AIZ-220-90-4UHL1 AIZ-220-100-4UHL1 AIZ-220-110-4UHL1 AIZ-220-120-4UHL1 AIZ-220-130-4UHL1 AIZ-220-140-4UHL1 AIZ-220-150-4UHL1 AIZ-220-170-4UHL1 AIZ-220-200-4UHL1 AIZ-220-250-4UHL1

Size L, 870 870 870 870 870 870 870 870 870 870 870 870 870 870

Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 2190 2200 2225 2230 2230 2235 2245 2245 2255 2260 2260 2280 2310 2315

Weight, kg

93,5 94,6 95,0 96,0 97,2 98,0 98,5

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

100,0 103,0 104,0 105,0 108,0 174,0 182,0


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TU3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

63

29

AIZ-330-A POLYMER BUS-BAR SUPPORTS FOR FLEXIBLE BUS-BARS AND WIRES FIXATION AIZ-330-...-4 UHL1

AIZ-330-...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 330 - nominal voltage, kV -modification of bus bar support for one wire 1,2,3,4 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTIC Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 330 363 1175

18
8 hol.

B
340

50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

315

For specified surface conductivity of polluted layer, mkCm


Minimum failing load at bending, kN

30
8

Minimum failing torsion moment, kNxm


Minimum creepage distance, cm

950
920

300

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

160

1480

Number of bus- bar mounted

1 3008 hol. 18 150

B
POLYMER BUS-BAR SUPPORTS AIZ-330-...-4 UHL1
Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR Assemblage AIZ-330-A...-4 UHL1

External inspection ( outer view and marking )


Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Wires according GOST 839-80, type

Wires according TS16-505.397-72 Diameter of wires, mm H max, mm

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

Type of flexible bus-bar support

, KP

S,SS, SP, ASK

PM
2

Nominal cross-section, kv, mm AIZ-330-1-4 UHL1 185; 240; 300 185/24; 185/29; 205/27; 240/32; 240/39 300/39; 300/48; 330/30; 330/43; 400/51; 400/64; 450/56; 500/27

17,5 - 22,1

2972

Failing load at bending (torsion ) Evaluation of partial discharge level

AIZ-330-2-4 UHL1

350; 400 450; 500

24,0 - 29,4

2975
Hydrophobic resistance to water

AIZ-330-3-4 UHL1 AIZ-330-4-4 UHL1

500/26; 500/64; 550; 600; 650; 550/71; 600/72; 700; 750 650/79; 700/86 -

240, 300 -

500

30,0 - 36,2 45,0

2978 2984

Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-07


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

64
mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

29

AIZ-330-B...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 330 - nominal voltage, kV B - modification of bus-bar support for two wires 1,2,3,4 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS
Nominal voltage, kV 330

AIZ-330-B POLYMER BUS-BAR SUPPORTS FOR TWO WIRES OF FLEXIBILE BUS-BAR FIXATION AIZ--330-B...-4 UHL1

Highest working voltage, kV Minimum lightning impulse withstand voltage, kV


50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

363 1175

315

18
8 hol.

B
340

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

30 8 950 920

300
160

1480

Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-330-B...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

3008 hol. see table

18

POLYMER BUS-BAR SUPPORTS AIZ-330-B...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage.

Distance between wires, L, mm


60 60 60 120 120 120 200 200 200 400 400 400

Type of flexible bus-bar support

Wires according GOST 839-80, type , KP S, SS,SP, S


2

Nominal cross-section, mm AIZ-330-B1-4 UHL1 AIZ-330-B2-4 UHL1 AIZ-330-B3-4 UHL1 AIZ-330-B5-4 UHL1 AIZ-330-B6-4 UHL1 AIZ-330-B7-4 UHL1 AIZ-330-B8-4 UHL1 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750 185; 240; 300 350; 400 450; 500 550; 600; 650; 700; 750

Diameter H max, Weight , kg mm of wires, mm


17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 17,5-22,1 24,0-29,4 30,0-36,2 2972 2975 2978 2989 2992 2995 2989 2992 2995 2989 2992 2995 154,8 154,8 154,9 155,3 155,2 155,1 155,5 155,6 155,8 156,8 157,1 157,4

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to coloring liquid Adhesion of coating layer to insulating body

185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 300/39; 300/48;330/30; 330/43 400/51; 400/64; 450/56; 500/27 500/26; 500/64;550/71; 600/72 650/79; 700/86; 240;300

AIZ-330-B9-4 UHL1 AIZ-330-B10-4 UHL1 AIZ-330-B11-4 UHL1 AIZ-330-B12-4 UHL1 AIZ-330-B13-4 UHL1

185; 240; 300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 700; 750 650/79; 700/86; 240;300 185/24; 185/29; 205/27; 205/27; 240/39 350; 400 300/39; 300/48;330/30; 330/43 450; 500 400/51; 400/64; 450/56; 500/27 550; 600; 650; 500/26; 500/64;550/71; 600/72 700; 750 650/79; 700/86; 240;300 185; 240; 300
R

GOST R 52082-03, TS3494-005-59116459-05

65 29

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

AIZ-330-V POLYMER BUS-BAR SUPPORTS FOR TWO EMTY WIRES OF FLEXIBILE BUS-BAR FIXATION AIZ--330-V...-4 UHL1

AIZ-330-V...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 330 - nominal voltage, kV

V- modification for two hollow wires 1,2,3 - modification according cross section and type of wire 4 - pollution level according GOST 9920, IEC60815, IEC60694

Pic.1

Pic.2

UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 330 363 1175

18
H
8 hol.

B
340

50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

315

For specified surface conductivity of polluted layer, mkCm


Minimum failing load at bending, kN

30
8

Minimum failing torsion moment, kNxm Minimum creepage distance, cm

950 920

300

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA

160

Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N Number of bus- bar mounted Bottom flange fitting dimensions, mm

1480

2 3008 hol. see table 18

POLYMER BUS-BAR SUPPORTS AIZ-330-V...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

Weight, not more than, kg TYPE TESTS FOR AIZ-330-V...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance Diameter between of wires, wires, L, mm, mm

H max, mm

Weight , kg

Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition

AIZ-330-1-4 UHL1

500

65

45,0

2142

157,8

Failing load at bending (torsion ) Evaluation of partial discharge level

AIZ-330-2-4 UHL1

500

120

45,0

2162

158,0
Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

AIZ-330-3-4 UHL1

500

200

45,0

2162

158,0
Adhesion of coating layer to insulating body

GOST R 52082-03, TS3494-005-59116459-07


AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

66

29

AIZ-330-G...-4 UHL1
CONDITIONAL DESIGNATION AIZ-brand of polymeric bus- bar supports 330 - nominal voltage, kV G - modification for three hollow wires 1,2,3 - bus-bar fitting modification 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 - according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV
50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

AIZ-330-G POLYMER BUS-BAR SUPPORTS FOR THREE EMTY WIRES OF FLEXIBILE BUS-BAR AIZ--330-G...-4 UHL1

330 363 1175

315

18
H
8 hol.

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm
The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA
Permissible tension of wires in horizontal plane of bus- bar supports for connecting of wires, N

30 8 950 920

340

300
160

1480

Connection dimensions of bottom flange

Number of bus- bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg

3 3008 hol. see table 18

POLYMER BUS-BAR SUPPORTS AIZ-330-G...-4 UHL1


Bus- bar supports are made on the basis of polymer rod insulators which are intended in applying in bus-bar supports. There was used special design and construction for the bus-bar support. Factory does not recommend applying the standard insulators as insulated supports of distribution devices. Bus-bar supports AIZ are applied for opened distribution devices of electric power stations and substations of alternative currents with 6-220 and kV voltage 50 Hz frequency. Insulators are made in accordance to IEC 62231standard and Technical specifications TS3494-005-59116459-05 ,,Bus-bar supports for the 10-220 kV voltage. Thanks to the silicone adhesive coating on the insulating body of the bus-bar support useful service life- 30 years; high firmness to influence of acids and alkalis, to an ultra-violet exposure; resistance to erosion and tracking; high hydrophobic properties; light weight; more resistible for acts of vandalicm; ensures safety conditions even during installation and exploitation works. The bus-bar support DOES NOT FALL TO THE GROUND in condition of overloads on bend, it just curves. That's why it eliminates possibility of personal injury.

TYPE TESTS FOR AIZ-330-G...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level

Type of flexible bus-bar support

Pic.

Wires according TS16-505.397-72


Nominal cross-section mm 2

Distance Diameter between of wires, wires, L, mm, mm

H max, mm

Weight , kg

AIZ-330-G1-4 UHL1

500

65

45,0

3014

157,8

AIZ-330-G2-4 UHL1
Hydrophobic resistance to water Hydrophobic resistance to coloring liquid

500

120

45,0

3034

158,0

AIZ-330-G3-4 UHL1
Adhesion of coating layer to insulating body

500

200

45,0

3034

158,0

GOST R 52082-03, TS3494-005-59116459-05

67 29

AIZ- regist rat - G ed trade mark of the group of companies GU AIZ U- www.insulators.ru mail@insulators.ru , +7-495-7412286 AIZ, RUSSIA www.bus-bar.ru mail@taiz.ru w w w . t a i z . r u mail@bus-bar.ru , U +7-495-7412286 +7-4872-316844 AIZ, BELARUS www .a b .y aai il l@ z. .bb +375-222 455264 m @a a ii z yy ww w i. z a. iz b ym , US +375-222 455264 AIZ, KAZAKHSTAN www .a i. z . k .z m aai il l@ z. .kk +7-717-296-5353 m @a a ii z zz w w w a i z k z , +7725-2-561716 AIZ, LITHUANIA www.bus-bar.eu mail@bus-bar.eu www.bus-bar.eu mail@bus-bar.eu , +370-62749925 +370-62749925
R

AIZ -330-...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports

BUS-BAR SUPPORTS FOR DOUBLE FIXATION OF ALUMINIUM TUBE AIZ-330-...-4 UHL1

330- nominal voltage, kV - double-grip of aluminum tube 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-330-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

330 363 1175

315

18
30 8 950 920
8 hol.

340

300
160

1480 1 3008 hol. see table 18

Connecting dimensions of bottom flange

BUS-BAR SUPPORT FOR DOUBLE FIXATION OF TUBE AIZ-330-...-4 UHL1


The outdoor bus- bar supports AIZ-330-E are used for double fixation of aluminium tube with 330 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-330-E are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus bar support type AIZ-330-50-4UHL1 AIZ-330-60-4UHL1 AIZ-330-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 3052 3062 3062 3070 3086 3092 3092 3094 3107 3122 3122 3142 3162 3162

Weight, kg

158,0 158,0 158,1 158,2 158,4 158,7 160,5 160,8 160,9 161,0 161,3 161,5 161,7 161,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-330-80-4UHL1 AIZ-330-90-4UHL1 AIZ-330-100-4UHL1 AIZ-330-110-4UHL1 AIZ-330-120-4UHL1 AIZ-330-130-4UHL1 AIZ-330-140-4UHL1 AIZ-330-150-4UHL1 AIZ-330-170-4UHL1 AIZ-330-200-4UHL1 AIZ-330-250-4UHL1

GOST R 52082-03, TU3494-005-59116459-05

68 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

RIGID BUS-BAR SUPPORTS FOR ALUMINIUM TUBES AIZ-330-Z...-4 UHL1

AIZ -330-Z...-4 UHL1


CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 330 - nominal voltage, kV Z -rigid fastening of aluminum tube bus bar

30-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 - climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS

Pic.1

Pic.2

Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV

330 363 1175

18
8 hol.

315

340

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm

30 8 950 920

300

The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm

160

1480

1 3008 hol. see table 18

POLYMER BUS-BAR SUPPORTS FOR RIGID BUS-BAR AIZ-330-Z


The outdoor bus- bar supports AIZ-330-Z are used for aluminum tubular bus-bar support with 330 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-330-Z are included in the integrated rigid bus- bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request

Weight, not more than, kg TYPE TESTS FOR AIZ-330-Z...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Rigid bus bar support type AIZ-330-Z30-4UHL1 AIZ-330-Z40-4UHL1 AIZ-330-Z50-4UHL1 AIZ-330-Z70-4UHL1 AIZ-330-Z80-4UHL1 AIZ-330-Z90-4UHL1 AIZ-330-Z100-4UHL1 AIZ-330-Z110-4UHL1 AIZ-330-Z120-4UHL1 AIZ-330-Z130-4UHL1 AIZ-330-Z140-4UHL1 AIZ-330-Z150-4UHL1 AIZ-330-Z170-4UHL1 AIZ-330-Z200-4UHL1 AIZ-330-Z250-4UHL1

ic. 2 2 2 2 2 2 2 1 1 1 1 1 1 1 1

Diameter of rigid bus-bar tube, mm 30/25 40/35 50/45 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 30 40 50 70 80 90 100 110 120 130 140 150 170 200 250

Building Weight, kg height H, mm 3051 3051 3052 3062 3070 3074 3086 3092 3094 3107 3112 3122 3142 3162 3187 156,1 156,2 156,5 156,8 158,0 158,3 158,5 158,7 159,3 161,3 161,3 162,4 163,5 167,5 163,5

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

GOST R 52082-03, TU3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

69

29

AIZ -330-SH...-4 UHL1


CONVENTIONAL MARKING

BUS-BAR SUPPORTS FOR HINGE FASTENING OF TUBULAR RIGID BUS-BARS AIZ-330-SH50-4 UHL1 - AIZ-330-SH250-4 UHL1

AIZ - brand of polymeric bus bar supports 330- nominal voltage, kV SH - hinging of aluminum tube bus-bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-330-SH...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

330 363 1175

315

18
H
30 8 950 920
8 hol.

340

300
160

1480

Connecting dimensions of bottom flange

1 3008 hol. see table 18

BUS-BAR SUPPORTS FOR HINGED FASTENING OF TUBULAR RIGID BUS-BAR AIZ-330-SH


The bus- bar supports of outdoor application AIZ-330-SH are used for hinged fastening of tubular rigid bus-bar at 330 kV voltage in open distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231 standard, TS3414-005-59116459-06. The bus- bar supports AIZ-330-SH are included in the integrated rigid bus- bar project of substations.Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request.

Rigid bus bar support type AIZ-330-SH50-4UHL1 AIZ-330-SH60-4UHL1 AIZ-330-SH70-4UHL1 AIZ-330-SH80-4UHL1 AIZ-330-SH90-4UHL1 AIZ-330-SH100-4UHL1 AIZ-330-SH110-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 3062 3072 3097 3102 3102 3107 3117 3117 3127 3132 3132 3152 3182 3187

Weight, kg

160,0 160,0 160,5 161,0 161,4 162,0 162,5 162,5 163,0 163,5 163,7 165,5 167,2 168,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

AIZ-330-SH120-4UHL1 AIZ-330-SH130-4UHL1 AIZ-330-SH140-4UHL1 AIZ-330-SH150-4UHL1 AIZ-330-SH170-4UHL1

Adhesion of coating layer to insulating body

AIZ-330-SH200-4UHL1 AIZ-330-SH250-4UHL1

GOST R 52082-03, TU3494-005-59116459-05

70 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-330-D...-4 UHL1

AIZ -330-D...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING

AIZ - brand of polymeric bus bar supports 330-nominal voltage, kV D-movable fastening of aluminum tube bus-bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 climate desing and category of spasing UHL1 according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 330 363 1175

315

18
8 hol.

340

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg

30 8 950 920

300

160

Connecting dimensions of bottom flange

1480

1 3008 hol. see table 18

BUS-BAR SUPPORTS FOR FLEXIBLE FITTING OF TUBULAR BUS-BAR AIZ-330-D...-4 UHL1


The outdoor bus- bar supports AIZ-330-D are used for flexible fitting of aluminium tubular bus-bar support with 330 kV voltage on opened distribution devices of electric power stations and substations. The design allows to carry out horizontal movement of bus holder after thermal expansion of the bus.Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. Useful service life- 30 years. The bus-bar supports AIZ-330-D are included in the integrated rigid bus-bar project of substations.

TYPE TESTS FOR AIZ-330-D...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Rigid bus bar support type AIZ-330-D50-4UHL1 AIZ-330-D60-4UHL1 AIZ-330-D70-4UHL1 AIZ-330-D80-4UHL1 AIZ-330-D90-4UHL1 AIZ-330-D100-4UHL1 AIZ-330-D110-4UHL1 AIZ-330-D120-4UHL1 AIZ-330-D130-4UHL1 AIZ-330-D140-4UHL1 AIZ-330-D150-4UHL1 AIZ-330-D170-4UHL1 AIZ-330-D200-4UHL1 AIZ-330-D250-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 3062 3072 3097 3102 3102 3107 3117 3117 3127 3132 3132 3152 3182 3187

Weight, kg

160,0 160,0 160,5 161,0 161,4 162,0 162,5

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

162,5 163,0 163,5 163,7 165,5 167,2 168,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TU3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

71

29

AIZ -330-...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ - brand of polymeric bus bar supports 330-nominal voltage, kV - end fastening of aluminum tube bus bar 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068

BUS-BAR SUPPORTS FOR END FIXATION OF ALUMINIUM TUBULAR RIGID BUS-BAR AIZ-330-...-4 UHL1

TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm Weight, not more than, kg TYPE TESTS FOR AIZ-330-...-4 UHL1 Assemblage External inspection ( outer view and marking )
Weight, length of insulating part, fitting dimensions, armature spacing correspondence

330 363 1175

315

18
8 hol.

30 8 950 920

340

300
160

1480

Connecting dimensions of bottom flange

1 3008 hol. see table 18

BUS-BAR SUPPORTS FOR THE END FIXATION OF BUS-BAR AIZ-330-...-4 UHL1


The outdoor bus- bar supports AIZ-330-K are used for end fixation of aluminium tubular bus-bar support with 330 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06.The bus-bar supports AIZ-330-K are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with adjusting sizes of bottom flange according clients request.

Rigid bus bar support type AIZ-330-50-4UHL1 AIZ-330-60-4UHL1 AIZ-330-70-4UHL1

Diameter of rigid bus-bar tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230

Diameter D, 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 3027 3030 3057 3062 3062 3077 3077 3082 3092 3102 3132 3152 3182 3187

Weight, kg

157,0 157,0 157,1 157,2 157,4 157,7 157,5 159,8 159,9 160,0 160,3 160,5 160,7 160,9

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion ) Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid Adhesion of coating layer to insulating body

AIZ-330-80-4UHL1 AIZ-330-90-4UHL1 AIZ-330-100-4UHL1 AIZ-330-110-4UHL1 AIZ-330-120-4UHL1 AIZ-330-130-4UHL1 AIZ-330-140-4UHL1 AIZ-330-150-4UHL1 AIZ-330-170-4UHL1 AIZ-330-200-4UHL1 AIZ-330-250-4UHL1

GOST R 52082-03, TU3494-005-59116459-05

72 29

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF ALUMINIUM TUBE AIZ-330-I...-4 UHL1

AIZ -330-I...-4 UHL1


CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING CONVENTIONAL MARKING AIZ- brand of polymeric bus bar supports 330 -nominal voltage, kV I -movable connection of two aluminum tubes 50-250- rigid fastening of aluminum tube bus bar 4 - pollution level according GOST 9920, IEC60815, IEC60694 UHL1 climate desing and category of spasing according GOST 15150, IEC60721, IEC60068 TECHNICAL CHARACTERISTICS Nominal voltage, kV Highest working voltage, kV Minimum lightning impulse withstand voltage, kV 50%- discharge voltage of industrial frequency at polluted and humid conditions, kV 330 363 1175

315

18
8 hol.

340

For specified surface conductivity of polluted layer, mkCm Minimum failing load at bending, kN Minimum failing torsion moment, kNxm Minimum creepage distance, cm The highest peak of the nominal short-term withstand current (current of the electrodynamic stability), kA Permissible tension of wires in horizontal plane of bus bar supports for connecting of wires, N Number of bus bar mounted Bottom flange fitting dimensions, mm

30 8 950 920

300

160

Connecting dimensions of bottom flange

1480

1 3008 hol. see table 18

BUS-BAR SUPPORTS FOR FLEXIBLE CONNECTION OF BUSES AIZ-330-I...-4 UHL1


The outdoor bus- bar supports AIZ-330-I are used for flexible connection of aluminium tubular bus-bar support with 330 kV voltage on opened distribution devices of electric power stations and substations. Bus-bar supports are made in accordance to IEC 62231standard, TS3414-005-59116459-06. The bus-bar supports AIZ-330-I are included in the integrated rigid bus-bar project of substations. Useful service life- 30 years. The factory can supply POLYMER BUS-BAR SUPPORTS with incorporated diagnostic system of high voltage isolation and also with adjusting sizes of bottom flange according clients request

Weight, not more than, kg TYPE TESTS FOR AIZ- 330-I...-4 UHL1 Assemblage External inspection ( outer view and marking )

Rigid bus bar support type AIZ-330-I50-4UHL1 AIZ-330-I60-4UHL1 AIZ-330-I70-4UHL1 AIZ-330-I80-4UHL1 AIZ-330-I90-4UHL1 AIZ-330-I100-4UHL1 AIZ-330-I110-4UHL1 AIZ-330-I120-4UHL1 AIZ-330-I130-4UHL1 AIZ-330-I140-4UHL1 AIZ-330-I150-4UHL1 AIZ-330-I170-4UHL1 AIZ-330-I200-4UHL1 AIZ-330-I250-4UHL1

Size L, 360 360 400 400 420 420 450 460 460 460 480 500 520 520

Diameter of rigid bus-bar Diameter D, tube, mm 50/45 60/54 70/64 80/72 90/80 100/90 110/100 120/110 130/116 140/120 150/136 170/156 200/180 250/230 50 60 70 80 90 100 110 120 130 140 150 170 200 250

Building height H, mm 3062 3072 3097 3102 3102 3107 3117 3117 3127 3132 3132 3152 3182 3187

Weight, kg

160,0 160,0 160,5 161,0 161,4 162,0 162,5

Weight, length of insulating part, fitting dimensions, armature spacing correspondence

Quality and thickness of armatures anticorrosional coating Testing load at bending ( torsion ) 1 min. withstand. Deviation angle control at bending ( torsion ) and absence of plastic deformation at bending ( torsion ) Alternating short term test voltage in dry condition Failing load at bending (torsion )

162,5 163,0 163,5 163,7 165,5 167,2 168,9


Adhesion of coating layer to insulating body Evaluation of partial discharge level Hydrophobic resistance to water Hydrophobic resistance to colouring liquid

GOST R 52082-03, TU3494-005-59116459-05

AIZ- registrated trade mark of the group of companies AIZ www.bus-bar.ru AIZ, RUSSIA +7-495-7412286 w w w. a i z . b y AIZ, BELARUS +375-222455264 www.aiz.kz AIZ, KAZAKHSTAN +7-717-296-5353 www.bus-bar.eu AIZ, LITHUANIA +370-62749925

mail@bus-bar.ru mail@aiz.by mail@aiz.kz mail@bus-bar.eu

73

29