Sunteți pe pagina 1din 94

Motorpact IEC

Instructions for use


46032-700-09F
Retain for future use.

46032-700-09F.fm

Contents

General information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Marking . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Standard tightening torques . . . . . . . . . . . . . . . . . . . . . . . . . . Non-greased screws and bolts . . . . . . . . . . . . . . . . . . . . . . Application methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

7 7 7 7 7

General description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Full voltage non-reversing starter (FVNR) . . . . . . . . . . . . . . . . 9 Full voltage reversing bidirectional starter (FVR), dual voltage transfer starter (FVS), 2-Speed, 1-Winding (2S1W), and Star Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 2-Speed, 2-Winding (2S2W) . . . . . . . . . . . . . . . . . . . . . . . . . 11 FVNR starter with Merlin Gerin Propivar power factor correction capacitor (PFCC) . . . . . . . . . . . . . . . . . . . . . . . . . 12 Reduced voltage soft starter (RVSS) soft start section . . . . . 13 Dual disconnect section (DDS). . . . . . . . . . . . . . . . . . . . . . . . 14 Reduced voltage autotransformer (RVAT) section . . . . . . . . . 15 Incoming cable section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 FVNR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 FVR bidirectional, FVS, 2S1W, 2S2W, and Star Delta . . . 18 Front operator panel description . . . . . . . . . . . . . . . . . . . . . . 19 Procedure pictogram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19 Instructions for access to the inside of the section . . . . . . . 21 Accessing the busbar compartment FVNR. . . . . . . . . . . . . . . . . 21 Steps to access the busbar compartment from the rear of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Steps to access the busbar compartment from the front of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Accessing the MV compartment . . . . . . . . . . . . . . . . . . . . . . 22 Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Access to LV cabinet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22 Accessing the medium voltage compartment FVNR . . . . . . . 23 Opening the medium voltage compartment door . . . . . . . 23 Accessing the medium voltage compartments RVAT or RVSS soft start section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Steps to OPEN the RVAT or RVSS soft start section MV doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Steps to CLOSE the RVAT or RVSS soft start section MV doors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Accessing the busbar compartmentsRVAT or RVSS soft start section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Steps to access the busbar compartment from the front of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25 Accessing the busbar compartmentDDS . . . . . . . . . . . . . . 26 Steps to access the busbar compartment . . . . . . . . . . . . 26 Accessing the reduced voltage soft starting MV cable connector compartment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Steps to access the reduced voltage soft starting MV cable connector compartment from the front of the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27 Installation and operation recommendation . . . . . . . . . . . . . Switchgear aging resistance . . . . . . . . . . . . . . . . . . . . . . . . . Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps for tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Safety rules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preliminary operation check . . . . . . . . . . . . . . . . . . . . . . .
46032-700-09F.fm

29 29 29 30 30 30
3

Contents

Operating instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Disconnector operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Opening the disconnector. . . . . . . . . . . . . . . . . . . . . . . . . . . . Closing the disconnector . . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage presence on MV cables . . . . . . . . . . . . . . . . . . . . . . . Section equipped with VPIS voltage indicator boxes . . . . Instructions for use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MV cable test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to test conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . Voltage injections on MV outgoing cable heads . . . . . . . . Replacing the voltage indicator box . . . . . . . . . . . . . . . . . . . . Steps for removing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps for placing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Operating the contactor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to CLOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing or installing the contactor. . . . . . . . . . . . . . . . . . . . Starting status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to remove the contactor. . . . . . . . . . . . . . . . . . . . . . Steps to install the contactor . . . . . . . . . . . . . . . . . . . . . . . Back light assembly (optional) . . . . . . . . . . . . . . . . . . . . . . . . Battery replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable earthing switch operation (optional) . . . . . . . . . . . . . . . Instructions for use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cable earthing switch operating condition. . . . . . . . . . . . . Closing the cable earthing switch . . . . . . . . . . . . . . . . . . . . . . Opening the cable earthing switch . . . . . . . . . . . . . . . . . . . . . Removing and installing fuses . . . . . . . . . . . . . . . . . . . . . . . . Steps to remove fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to install fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fuse tool (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to install rear and middle fuses . . . . . . . . . . . . . . . . Steps to install front fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . Blown fuse indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to remove fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing and installing fuses of the Merlin Gerin PFCC inside Motorpact enclosures . . . . . . . . . . . . . . . . . . . . . . . . . Steps to remove fuses. . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to install fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing and installing VT primary fuses . . . . . . . . . . . . . . . Steps to replace fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to disassemble the fuse tube. . . . . . . . . . . . . . . . . . Steps to assemble the fuse tube . . . . . . . . . . . . . . . . . . . . Steps to place back into operation . . . . . . . . . . . . . . . . . . Locking using padlocks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Number of possible padlocks per section type . . . . . . . . . Padlocking the disconnector . . . . . . . . . . . . . . . . . . . . . . . Padlocking the cable earthing switch . . . . . . . . . . . . . . . . Padlocking the incoming cable section doors . . . . . . . . . . Locking using keylocks (optional) . . . . . . . . . . . . . . . . . . . . . . Number of possible locks per section type . . . . . . . . . . . . Keylocking the disconnector . . . . . . . . . . . . . . . . . . . . . . . . . . Locking the disconnector open or closed with 1 keylock. . Locking the disconnector open or closed with 2 keylocks. . . Locking the cable earthing switch open or closed . . . . . . . FVR (full voltage reversing bidirectional). . . . . . . . . . . . . . FVS (dual voltage transfer starter) . . . . . . . . . . . . . . . . . .
4

32 32 33 34 35 35 35 35 35 35 36 36 36 37 37 37 38 38 38 39 40 40 41 41 41 42 42 43 43 44 45 45 48 50 51 52 52 52 53 53 53 53 53 54 54 54 55 55 56 56 56 56 56 57 58 59

46032-700-09F.fm

Contents

Redundant smart sequence starter . . . . . . . . . . . . . . . . . . . . DDS (dual disconnect section) . . . . . . . . . . . . . . . . . . . . . . . . 2-Speed, 1-Winding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-Speed, 2-Winding . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Star Delta . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . RVAT (reduced voltage autotransformer). . . . . . . . . . . . . . . . Limited duty cycle rating . . . . . . . . . . . . . . . . . . . . . . . . . . Keylocks on an RVAT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Keylocking with disconnector (without cable earthing switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Keylocking (with cable earthing switch). . . . . . . . . . . . . . . RVAT operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Autotransformers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Relay setting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Tap setting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to CLOSE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to OPEN . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Reduced voltage soft starter (RVSS) soft start section . . . . . Keylocks on an RVSS soft start section . . . . . . . . . . . . . . . . . Keylocking with disconnector (without cable earthing switch) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Keylocking with cable earthing switch . . . . . . . . . . . . . . . . Keylocking with redundant S3 . . . . . . . . . . . . . . . . . . . . . . Keylocking with redundant S3 with dual disconnect section (DDS) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Removing a contactor from an RVAT or RVSS soft start section . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preliminary steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to remove a start, run, or bypass contactor . . . . . . . . . Installing a contactor in an RVAT or RVSS soft start section . Preliminary steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steps to install a start, run, or bypass contactor. . . . . . . . . . . Using a lift truck (optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . MDT107 thermal diagnostic system (optional) . . . . . . . . . . . . Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Wiring and operation for MDT107 . . . . . . . . . . . . . . . . . . . Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . MDT107 module location . . . . . . . . . . . . . . . . . . . . . . . . . . . . MDT107 sensors location . . . . . . . . . . . . . . . . . . . . . . . . . . . . Setting the temperature rise thresholds. . . . . . . . . . . . . . . Setting the ambient temperature correction . . . . . . . . . . . Troubleshooting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Preventative maintenance . . . . . . . . . . . . . . . . . . . . . . . . . Environmental conditions . . . . . . . . . . . . . . . . . . . . . . . . . Inspecting the equipment . . . . . . . . . . . . . . . . . . . . . . . . . . .

60 61 63 64 65 66 66 67 67 67 68 68 68 68 69 69 70 71 71 71 71 71 72 72 72 73 73 73 74 75 76 78 78 78 79 80 80 81 82 82 82 84 85

Replacement parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89 Glossary . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91

46032-700-09F.fm

46032-700-09F.fm

General information

Marking

It is strictly forbidden to walk on the parts bearing this marking.

It is strictly forbidden to remove the parts bearing this marking when the equipment is energized.

Standard tightening torques


Non-greased screws and bolts
Screw 6 8 10 12 14 Busbar torque in Nm

Mech. torque in Nm 10 20 35 55 120

28 50 75

Application methods

The conical washers placed on the external sides of the busbars ensure better distribution of stress regarding bolts tightened to the recommended torques.

46032-700-09F.fm

46032-700-09F.fm

General description

Full voltage non-reversing starter (FVNR)


A. MV power cable entry plate (optional upper entry) B. internal arc vent cover (optional) C. LV control cable entry plate D. LV cabinet door E. Diagnostic thermal detection module (optional) F. Operation and locking panel G. VPIS indicator box (optional) H. Interlock shuttle I. Blown fuse indicator (optional) J. Cable earthing switch, load connection lug pads K. MV power fuses L. MV compartment door M. Vacuum contactor N. Fuseholder, control power transformer (CPT), and voltage transformer (VT) O. LV inter-unit top wireway P. Main busbar barrier Q. Disconnector R. Main busbars S. Main earthing terminal T. Surge arresters (optional) U. Current transformers (CTs) V. MV cable support clamps (bottom entry) W. Voltage transformer (VT) X. LV cable entry plate (bottom entry)

A B C O D P

Q E R S F G H I J K

U V

M W

Load connection lug pad not required for smart start sequence application.

N X

46032-700-09F.fm

General description

Full voltage reversing bidirectional starter (FVR), dual voltage transfer starter (FVS), 2-Speed, 1-Winding (2S1W), and Star Delta
A. B. C. D. E. F. G. H. I. J. K. L. M. N. O. P. Q. R. S. T. MV power cable entry plate Internal arc vent cover (optional) LV control cable entry plate LV compartment door Diagnostic thermal detection module (optional) Operation and locking panel VPIS indicator box (optional) Interlock shuttle Blown fuse indicator (optional) Cable earthing switch, load connection lug pads MV power fuses MV compartment door See table below See table below Fuseholder, control power transformer (CPT), and voltage transformer (VT) LV inter-unit top wireway Main busbar barrier Disconnector Main busbars Main earthing terminal
C D B A

P Q

E F G H I

S T

J K

M N

Starter Type FVR bidirectional FVS dual voltage transfer starter 2S1W Star Delta

M Forward contactor Main contactor Slow-speed contactor Star-connection contactor

N Reverse contactor Soft start contactor Shorted contactor Delta-connection contactor

10

46032-700-09F.fm

General description

2-Speed, 2-Winding (2S2W)


A. B. C. D. E. F. G. H. I. J. K. L. M. N. O. P. Q. R. S. T. U. MV power cable entry plate Internal arc vent cover (optional) LV control cable entry plate LV compartment door Diagnostic thermal detection module (optional) Operation and locking panel VPIS indicator box (optional) Interlock shuttle Blown fuse indicator (optional) Cable earthing switch load connection lug pads (cables for fast speed winding) MV power fuses MV compartment door Fast-speed contactor Slow-speed contactor Fuseholder, control power transformer (CPT), and voltage transformer (VT) LV inter-unit top wireway Main busbar barrier Disconnector Main busbars Main earthing terminal Load connection lug pads (cables for slow speed winding)
C B A

D P Q

E F G H I J K

S T

M N

46032-700-09F.fm

11

General description

FVNR starter with Merlin Gerin Propivar power factor correction capacitor (PFCC)
A. B. C. D. E. F. G. H. I. J. K. L. LV cabinet door Operation and locking panel MV compartment door Cable earthing switch, load connection lug pads MV power fuses Vacuum contactor Fuseholder, control power transformer (CPT), and voltage transformer (VT) Disconnector Main busbars Main earthing terminal PFCC fuses PFCC

H B C D E L I J K

12

46032-700-09F.fm

General description

Reduced voltage soft starter (RVSS) soft start section


A. B. C. D. E. F. G. H. I. J. K. L. M. N. O. P. Q. R. S. T. Internal arc vent cover (optional) LV control entry plate MV compartment door LV door Human machine interface (HMI) soft start control interface modules Soft start power compartment door Heater (optional) LV control entry plate Customer conduit wireway Bypass contactor or PLC mounted (depending on application) Ground fault board (optional) D Terminal control board E Main busbar compartment Main earthing terminal Control power, central processing unit (CPU) boards, RTD board (optional) F Main busbar access cover LV cabinet Door interlock Ring transformers Silicon control rectifier stacks
A B I C J K L M N O P Q R S T S

G H

46032-700-09F.fm

13

General description

Dual disconnect section (DDS)


A. B. C. D. E. F. G. H. I. J. K. L. M. N. O. P. Reduced voltage MV cable entry plate Internal arc vent cover (optional) LV cable entry plate LV cabinet door Access cover plate for reduced voltage soft starting MV cable connectors Main busbar access cover plate Access cover plate for reduced voltage soft starting MV cable connectors Operation and locking panel MV compartment door Heater (optional) LV inner-unit top wireway Top entry main earthing terminal Reduced voltage soft starting MV cable terminals Main busbars Disconnectors Bottom entry main earthing terminal
B C D K A

L M

O M

I J

14

46032-700-09F.fm

General description

Reduced voltage autotransformer (RVAT) section


A. B. C. D. E. F. G. H. I. J. K. L. M. Internal arc vent cover (optional) LV control cable entry plate MV compartment door Run contactor Start contactor LV door Autotransformer door Surge arresters Main busbar access cover Door interlock Main busbar compartment Main earthing terminal Autotransformer
B A

D E

H I J K

46032-700-09F.fm

15

General description

Incoming cable section


A. B. C. D. E. F. G. H. I. J. K. L. M. N. O. Internal arc vent cover (optional) LV control cable entry plate MV upper barrier MV upper door MV lower door Voltage presence indicator system (VPIS) indicator box (optional) MV lower barrier LV inter-section top wireway Capacitive divider, VPIS (optional) Surge arresters (optional) Main earthing terminal Main busbar lug pad Earth riser connection Current transformers (CTs) (optional) MV cable support clamps (bottom entry)
A B

C H D I J

K L M

16

46032-700-09F.fm

General description

Identification
FVNR
A. Name of starter or section B. Viewing port, disconnector C. Characteristics, designations, and serial number D. Interlock shuttle E. Status window, blown fuse indicator (see page 50) F. Status window, cable earthing switch (see page 41) G. Status window, contactor contactor H. Characteristics, designations, and serial number I. Status indicator

B D E F

H G I

46032-700-09F.fm

17

General description

FVR bidirectional, FVS, 2S1W, 2S2W, and Star Delta


A. Name of starter or section B. Viewing port, disconnector C. Characteristics, designations, and serial number D. Interlock shuttle E. Status window, blown fuse indicator (see page 50) F. Status window, cable earthing switch (see page 41) G. Status window, contactor Contactor H. Characteristics, designations, and serial number I. Status indicator
B D A

E F

18

46032-700-09F.fm

General description

Front operator panel description


A. Contactor control panel B. Voltage presence indicator system (VPIS) C. Pushbutton for back light (optional) D. Disconnector viewing port E. Disconnector status indicator F. Location for cable earthing switch operation padlock G. Disconnector operating access port H. Cable earthing switch operating access port I. Location for disconnector operation padlock J. Procedure pictogram K. Interlock shuttle
A B

C D E F H I K G J

Procedure pictogram
Steps for closing of circuit
1. MV compartment door position, close and latch 2. If the cable earthing switch is not supplied, skip to step 5. If the cable earthing switch is supplied, move the cable earthing switch access port from the locked to unlocked position. This requires the interlock shuttle to be in the right-hand position. See Cable earthing switch operation (optional). 3. OPEN or un-earth the cable earthing switch 4. Move the cable earthing switch access port from the unlocked to locked position; then move the interlock shuttle from the right-hand to left-hand position. See Disconnector operation. 5. Move the disconnector access port from the locked to unlocked position 6. CLOSE the disconnector 7. Move the disconnector access port from the unlocked to locked position 8. CLOSE the contactor

46032-700-09F.fm

19

20

46032-700-09F.fm

Instructions for access to the inside of the section

All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. Always remove all power from the section and use a properly rated testing device to confirm there is no voltage present. Always look through the rear viewing window to verify that the MV compartment door is OPEN, before removing the MV cable compartment cover.

Accessing the busbar compartment FVNR

Steps to access the busbar compartment from the rear of the enclosure

Remove the upper MV cable compartment cover. 4 M10x20 screws.

Remove the rear main busbar cover. 4 M10x20 screws.

The busbar compartment is now accessible.

Steps to access the busbar compartment from the front of the enclosure

Main busbar access cover

Remove the main busbar access cover in the floor of the LV cabinet. 8 M10x20 screws.

The busbar compartment is now accessible.

After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 35 Nm.
46032-700-09F.fm 21

Instructions for access to the inside of the section


0

Accessing the MV compartment (cables, busbars, CT, cable earthing switch, surge arresters, fuses, contactor, transformers)
Safety rules
All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. cables See Accessing the medium voltage compartment FVNR and Accessing the medium voltage compartments RVAT or RVSS soft start section.

See "cable connections" in the installation instruction guide. See "installing busbars" in the installation instruction guide. See General descriptionfor the mounting locations. See Cable earthing switch operation (optional). See General descriptionfor the mounting locations. See Removing and installing fuses. See Removing or installing the contactor. See General descriptionfor the mounting locations.

busbars

CT (current transformer) cable earthing switch surge arresters fuses contactor transformers

Access to LV cabinet (instrument components, relays, and communication modules)


All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. See "accessing the low voltage compartment" in the installation instruction guide.

22

46032-700-09F.fm

Instructions for access to the inside of the section

Accessing the medium voltage compartment FVNR


Always look through the viewing window to verify the actual position of the disconnector switch blades before trying to open the MV compartment door. Motorpact motor starters are shipped with the disconnector in the earthed/OPEN position. The disconnector must be in the earthed/OPEN position to open the medium voltage compartment door. See Disconnector operation.

The cable earthing switch (optional) must be in the earthed/CLOSED position to open the medium voltage compartment door. See Cable earthing switch operation (optional).

Opening the medium voltage compartment door

Door closed, rotate handle 90

Handle rotated

Door open

Accessing the cable compartment FVNR


All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. Always remove all power from the section and use a properly rated testing device to confirm there is no voltage present. Always look through the rear viewing window to verify that the MV compartment door is OPEN, before removing the MV cable compartment cover.
46032-700-09F.fm

Steps to access the cable compartment of an FVNR section

Verify through the rear viewing window that the MV compartment door is OPEN, the power has been removed from the section, and the load connections have been properly earthed. Remove the lower MV cable compartment cover. 4 M10x20 screws.

MV compartment door (opened 90) MV compartment door viewing window

After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 35 Nm

Rear view

23

Instructions for access to the inside of the section


0

Accessing the medium voltage compartments RVAT or RVSS soft start section

The contactor and autotransformer compartments of an RVAT and the contactor and soft start power compartments of an RVSS soft start section are key interlocked with the main contactor disconnector or the cable earthing switch, if supplied. If the optional dual disconnect section (DDS) is being used, the RVSS will also be key interlocked with the DDS. For a description of key interlock operation, refer to the Keylocks on an RVATor Keylocks on an RVSS soft start sectionsection.

Steps to OPEN the RVAT or RVSS soft start section MV doors

OPEN the middle LV doors to gain access to the key interlock. Insert and turn the interlock key to release the door latching mechanism. Insert the disconnector operating handle as shown below. Rotate counter-clockwise to release the MV doors.

Door latch keylock

Operating handle

Steps to CLOSE the RVAT or RVSS soft start section MV doors

CLOSE all MV doors. For RVAT, right side doors must be closed before the left side doors. Push the release button next to the operator port to latch the MV doors. Insert the disconnector operating handle as shown below. Rotate clockwise to lock the MV doors. Turn the interlock key to lock the door latching mechanism. Remove the key, and return it to disconnector or cable earthing switch, if supplied. Close and latch the middle LV doors.

Door latch keylock Operating handle

Release button
24 46032-700-09F.fm

Instructions for access to the inside of the section

Accessing the busbar compartmentsRVAT or RVSS soft start section

The RVAT or RVSS soft start section main busbar compartment can be accessed only from the front due to the cable arrangement in the rear of these sections.

Steps to access the busbar compartment from the front of the enclosure

Main busbar access cover

Main busbar access cover

Remove the M6x10 screws holding the main busbar access covers. The RVAT shown will have 2 covers. RVSS soft start section will have only 1 cover.

The busbar compartment is now accessible. After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 6 Nm max.

46032-700-09F.fm

25

Instructions for access to the inside of the section


0

Accessing the busbar compartmentDDS

The DDS main busbar compartment can be accessed only from the front due to the busbars being enclosed in a busbar tunnel.

Steps to access the busbar compartment

Main busbar access cover

Remove the M10x20 screws holding the main busbar access covers.

The busbar compartment is now accessible. After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 25 Nm max.

26

46032-700-09F.fm

Instructions for access to the inside of the section

Accessing the reduced voltage soft starting MV cable connector compartment

The reduced voltage MV cable connector compartment can be accessed from the front or the back of the unit. To access this compartment from the front of the unit, refer to the images below.

Steps to access the reduced voltage soft starting MV cable connector compartment from the front of the enclosure

Reduced voltage soft starting MV cable connector access cover

Remove the M10x20 screws holding the access cover.

The compartment is now accessible. After installation or maintenance, ensure all covers are replaced using the original hardware. tightening torque: 25 Nm max.

46032-700-09F.fm

27

28

46032-700-09F.fm

Installation and operation recommendation

Switchgear aging resistance

The switchgears resistance to aging depends upon 3 factors.

Ventilation control: Provide area ventilation, heating, and air conditioning to maintain the ambient temperature around the equipment between - 5 C and 40 C.

The necessity of correct implementation of connections: New cold-shrink or slip-on technology offers ease of installation. The effect of the relative humidity factor: Heating resistor installation is essential in climates with a high rate of relative humidity and with significant temperature differentials.

Operation

It is strongly advised to periodically carry out (minimum every 2 years) a few operation cycles on operating devices. Outside normal conditions of use (between - 5 C and 40 C, absence of dust, corrosive gas, etc.), it is recommended to verify the steps to be taken in order to ensure correct functioning of the installation. Contact the Schneider Electric Service Center for help to do so.

The Service Center is able to assist you at any time to offer you:

installation diagnostics. suitable maintenance operations. maintenance contracts. adaptations.

46032-700-09F.fm

29

Installation and operation recommendation


0

Steps for tests


Safety rules
Carry out electric tests in compliance with the standards in force. All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. It is recommended that prior to start-up and after maintenance on this equipment, the 1 minute dielectric test is always performed. See "steps to be taken for test and inspections" in the installation instruction guide.

Preliminary operation check


If any operation checks provide unacceptable results, DO NOT ENERGIZE THE EQUIPMENT. Contact your local field sales office or distributor.

Verify that a 1 minute dielectric test has been performed recently. If a


dielectric test is required, see "hi-pot dielectric test" in the installation instruction guide.

Operate the disconnector a minimum of 5 operations. See


Disconnector operation

Operate the cable earthing switch (if supplied) a minimum of 5


operations. see Cable earthing switch operation (optional)

With the disconnector in the CLOSED position, verify the MV


compartment door cannot be opened.

If supplied, verify all key interlocks function properly according to


the drawing.

Verify that all low voltage plugs are connected. Verify all tools and/or hardware have been removed from the MV
compartment.

Replace all devices, doors, and covers with their original


mounting hardware.

30

46032-700-09F.fm

46032-700-09F.fm

31

Operating instructions

Disconnector operation

Operating handle

Description
The disconnector is the isolation means between the main busbar and the line side of the primary fuses. When the disconnector is in the earthed or OPEN position, it disconnects or isolates the contactor from the supply voltage. Moving the disconnector to the OPEN position earths the switch blades and the load side power circuit down to the line side of the contactor. In the earthed/OPEN position, the disconnector does not earth the load side of the contactor, cables, or any other components that are connected to the load side of the contactor. The disconnector operating handle is stored on the rightor left-hand end sheet.

OPEN (earth)

CLOSED

switch blades Interlock shuttle An interlock shuttle is provided on all FVNR starters with a cable earthing switch. This shuttle must be in the left-hand position to operate the disconnector. Always look through the viewing window to verify the actual position of the disconnector switch blades.

32

46032-700-09F.fm

Operating instructions

Opening the disconnector


The interlock system requires the following conditions to be met before the disconnector can be OPENED:

If a cable earthing switch is supplied, the interlock shuttle must be in the left-hand position to allow disconnector operation. The optional cable earthing switch must be in the OPEN position. The contactor must be in the OPEN position. The MV compartment door must be closed and latched. The cable earthing switch access port, if equipped, must be closed. When the conditions above have been satisfied:

Position indicator CLOSED

Slide the disconnector operating access port to the right to open. Insert the operating handle, and rotate counter-clockwise to open or earth.

Closed position

Open disconnector access port

After putting the disconnector in the OPEN position: Position indicator OPEN

Open position

Remove the operating handle. Slide the disconnector operating access port to the left to close. If the access port cannot be closed, open the disconnector further, then close the access port. After completely opening the disconnector and closing the cable earthing switch, if supplied, the MV compartment door can be opened.

46032-700-09F.fm

33

Operating instructions

Closing the disconnector


The interlock system requires the following conditions to be met before the disconnector can be CLOSED:

If a cable earthing switch is supplied, the interlock shuttle must be in the left-hand position to allow disconnector operation. The optional cable earthing switch must be in the OPEN position. The contactor must be in the OPEN position. The MV compartment door must be closed and latched. The cable earthing switch access port, if equipped, must be closed.

When the conditions above have been satisfied: Position indicator OPEN (earth)

Slide the disconnector operating access port to the right to open. Insert the operating handle, and rotate clockwise to close.

Open position

Open disconnector access port

Position indicator CLOSED

After putting the disconnector in the CLOSED position:


Closed position

Remove the operating handle. Slide the disconnector operating access port to the left to close. If the access port cannot be closed, close the disconnector further, then close the access port. After the disconnector is completely closed, the contactor can be closed.

34

46032-700-09F.fm

Operating instructions

Voltage presence on MV cables


Section equipped with VPIS voltage indicator boxes
VPIS: The Voltage Presence Indicating System is a box with three integrated lamps. The definite "voltage presence" indication is ensured on the voltage range stipulated by IEC 61958.

Instructions for use


VPIS must not be used as a VDS (Voltage Detecting System). Use a properly rated testing device to confirm there is no voltage present.
B A

The indication of a VPIS alone will not ensure the system is de-energized. If the operation rules require this, then suitable voltage detectors in compliance with IEC 61243 must be used.

A. Voltage presence indicator light (1 for each phase) B. Connection points enabling a phase concordance unit to be connected. Once the cables are energized, the voltage indicator lights should illuminate.

MV cable test
Steps to test conditions Voltage injections on MV outgoing cable heads

Open the cable earthing switch.

The cables are connected to injection tools.

Check voltage absence. The voltage indicator lights are not illuminated.

Close the cable earthing switch. See Closing the cable earthing switch.

46032-700-09F.fm

35

Operating instructions

Open MV compartment door. See Accessing the medium voltage compartment FVNR.

Cable lugs

Connect the voltage injection circuit to the cable lugs. Open the cable earthing switch. See Cable earthing switch operation (optional)then carry out the tests.

At the end of the tests:


Close the cable earthing switch. Remove the accessories.

Replacing the voltage indicator box


Steps for removing
All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. Caution: a static voltage will be present if the indicator box is replaced while the equipment is energized.

Remove the 2 fastening screws (A) from the voltage indicator box.

Remove the voltage indicator box, and disconnect the connector. Place the new voltage indicator box in the reverse order of removal.

Steps for placing

Verify that the characteristics label (B) on the new box corresponds to the rated voltage of your network. example: 3 kV to 7.2 kV

tightening torque: 0.1 mdaN


46032-700-09F.fm

36

Operating instructions

Operating the contactor


All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. Contact fingers Control terminal blocks Vacuum interrupter Status indicator Auxiliary contacts

Truck handle

Operator panel

For more information, see Schneider Electric bulletin 46032-700-02 (200 A / 400 A / 450 A vacuum contactors).

Description
The contactor is typically electrically maintained. However, an optional mechanical latching mechanism is added to latched contactors to lock the contactor CLOSED. This latched contactor can be opened at the operator panel or by pressing a reset button located on the MV compartment door.

Steps to CLOSE

OPEN or un-earth the cable earthing switch, if supplied. See Cable earthing switch operation (optional). CLOSE the disconnector. See Disconnector operation. Press the START or CLOSE pushbutton on the operator panel.

Status window

Steps to OPEN

Press the STOP or OPEN pushbutton on the operator panel. A latched contactor can also be opened by pressing the reset button on the MV compartment door.

Reset button

46032-700-09F.fm

37

Operating instructions

Removing or installing the contactor


Starting status

Cubicle + contactor

Steps to remove the contactor

OPEN the contactor by pressing the STOP or OPEN pushbutton on the operating panel. For a mechanically-latched contactor, verify that the contactor is in the OPEN position. If necessary, press the trip button. OPEN the disconnector to the earthed position. See Disconnector operation. CLOSE the cable earthing switch, if supplied, to the earthed position. See Cable earthing switch operation (optional).

Open the MV compartment door.

See Accessing the medium voltage compartment FVNR.

Pull the contactor rail down. This will disengage the contactor from the line and load busbar connections.

Roll the contactor out of the enclosure. Lift to remove (25 kg).

38

46032-700-09F.fm

Operating instructions

Steps to install the contactor

Verify the disconnector is in the OPEN and earthed position. See Disconnector operation. If supplied, verify the cable earthing switch is in the CLOSED and earthed position. See Cable earthing switch operation (optional). Open the MV compartment door. See Accessing the medium voltage compartment FVNR.

Pull the contactor rail down.

Wheel stop

Seat the contactor truck wheels onto the contactor rail. By gripping the handles (A) shown, slowly roll the contactor into the enclosure until it reaches the wheel stop.

Lift the contactor rail to the vertical position, engaging the contactor.

46032-700-09F.fm

39

Operating instructions

Back light assembly (optional)


The back light assembly consists of LEDs, a pushbutton, and batteries. It is used to help view the inside of the disconnector and the MV compartment. When the back light pushbutton is pressed, the light illuminates. A. The inside of the disconnector for viewing the switch blade position. B. The inside of the MV compartment for viewing the indicators of the cable earthing switch and the blown fuse indicator, if supplied. All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. Operator panel Back light pushbutton Operator cover
A

Tie channel

Battery replacement

The batteries should be replaced every 4 years to maintain proper operation. Two AA alkaline batteries are required. Steps for removal

Left battery

Negative

Front Right battery

Positive

Remove all power from the section. See Operating instructions. After opening the MV compartment door, remove 2 screws holding the bottom of the operator cover to the tie channel. Open the LV door, and remove the 2 screws holding the top of the operator cover to the operator panel. Remove the cover. The back light assembly can now be accessed to replace the batteries. Remove the batteries by pulling them straight down from their spring clips. When replacing batteries, insert the left-side battery with the negative end nearest to the operator and the right-side battery with the positive end nearest to the operator. Replace the operator cover (4 M6 screws). tightening torque: 10 Nm. Complete these operations in reverse order. See Operating instructions. Complete these electric tests in compliance with the standards in force.
46032-700-09F.fm

Steps to place back into operation

40

Operating instructions

Cable earthing switch operation (optional)

Operating handle Status window Earthing bar Un-earthed position Earthed position

The indicator for the cable earthing switch can be viewed through a status window in the MV compartment door.

The cable earthing switch operating handle is stored on the right- or left-hand end sheet.

Description
The cable earthing switch is used to earth the customer load connection cables when the switch is in the CLOSED or discharged position. It is mechanically interlocked with the disconnector and is actuated by using the same operating handle. Connection to earth is accomplished when the spring operated earthing bar is connected across all three phases of the customer load terminals.

Instructions for use

The cable earthing switch has no interrupting capability and is not capable of closing on the full fault current available on the system. When used with a power transformer, key interlocks should be used between the main secondary disconnect device and the cable earthing switch to ensure proper sequencing of operation.

Cable earthing switch operating condition

The interlock system requires the following conditions to be met before the cable earthing switch can be operated:

The interlock shuttle must be in the right-hand position. The contactor must be in the OPEN position. The disconnector must be in the DISCONNECTED and EARTHED position. The MV compartment door must be closed and latched.

Interlock shuttle An interlock shuttle is provided on all FVNR starters with a cable earthing switch. This shuttle must be in the right-hand position to operate the cable earthing switch.
46032-700-09F.fm 41

Operating instructions

Closing the cable earthing switch


When the cable earthing switch operating conditions have been satisfied:

Slide the cable earthing switch access port down.

Access port Open position

Insert and rotate the handle counter-clockwise approximately 10 turns, or until the handle stops. The mechanism makes a sharp sound when it trips, and the position indicator moves upward to the earthing position. The MV compartment door can now be opened.

Closed position

Opening the cable earthing switch


The interlock system requires the MV compartment door to be shut and latched. See Cable earthing switch operating condition. For performing cable injection testing, the cable earthing switch can be opened with the MV compartment door open, however the cable earthing switch must be returned to the closed position to allow the MV compartment door to be closed. See MV cable test. When the cable earthing switch operating conditions have been satisfied:

Slide the cable earthing switch access port down.

Access port Closed position

Open position

Insert and rotate the handle clockwise approximately 10 turns to charge and latch the mechanism back in the open or unearthed position. Continue rotating the handle until it stops. The cable earthing switch access port may now be closed, allowing the disconnector and the contactor to be operated.
46032-700-09F.fm

42

Operating instructions

Removing and installing fuses


All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. Always remove all power from the section, and use a properly rated testing device to confirm there is no voltage present. An optional fuse tool is available to help in the removal and installation of power fuses. Contact a field sales representative or distributor. See Fuse tool (optional).

Steps to remove fuses

Always remove the lower end of the fuse first. Twist the fuse while pulling the ferrule out of the lower fuse clip. Pull the fuse down to remove it from the upper fuse clip. See Accessing the medium voltage compartment FVNR.

IEC standard 60282-1:8.4.2 states that all of the MV fuses should be changed whenever one fuse is blown.

46032-700-09F.fm

43

Operating instructions

All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. Always remove all power from the section and use a properly rated testing device to confirm there is no voltage present. Fuse characteristics The fuse characteristics and direction of mounting are printed on the fuse. When replacing the fuse, turn it so that the label is in the front, and the striker pin is at the top.

Steps to install fuses

Always insert the upper end of the fuse first. Grasp the fuse by the upper ferrule, insert it into the upper fuse clip, and twist it while pushing upward. Insert the lower end into the lower fuse clip. Rotate the fuse so that the label is facing the front.

IEC standard 60282-1:8.4.2 states that all of the MV fuses should be changed whenever one fuse is blown. To ease installation, lubricate fuse clips with red Mobilgrease 28.

44

46032-700-09F.fm

Operating instructions

Fuse tool (optional)

The fuse tool is an ergonomic aid for inserting and extracting fuses in de-energized Motorpact motor starters. It does not protect the operator in any way from contacting live parts. hook

handle pusher

hinge

lifting rod

Steps to install rear and middle fuses


NOTE: Always wear gloves when working with fuses. The fuses could be hot and will burn unprotected hands. The photos on these pages are factory demonstrations.

The process is the same for installing fuses in the rear and middle fuseholders. Begin by installing the rear fuses.

Align the fuse tool so that the hook and the pusher are toward the handle end of the tool.

pusher handle hook

Insert the hinge in the narrow vertical space in front of the fuseholder, between the fuse holder and the fuse tray. In some cases, this may be a tight fit. The handle should be horizontal and extend towards the door.

hinge lifting rod handle

fuse holder fuse tray

46032-700-09F.fm

45

Operating instructions

Bring the fuse into the enclosure. With the upper end of the fuse behind the upper fuse holder, bring the lower end of the fuse to rest on the lifting rod.

Upper fuse holder Upper end of fuse

Fuse clip

Lower end of fuse

Visually align the upper end of the fuse with the upper fuse clip, and raise the tool handle to push the fuse into the upper clip. Verify that the fuse is fully inserted into the upper clip. Upper fuse clip

Handle

Lower the handle. If the fuse was fully inserted at the top, the lower end will naturally swing into place against the opening of the lower fuse clip.

Lower end of fuse Lower fuse clip

46

46032-700-09F.fm

Operating instructions

Rotate the pusher into position toward the hinge.

Pusher Hinge

Raise the handle again to push the fuse into the lower fuse clip.

Handle Fuse

Lower fuse clip

46032-700-09F.fm

47

Operating instructions

Steps to install front fuses


NOTE: Always wear gloves when working with fuses. The fuses could be hot and will burn unprotected hands. The photos on these pages are factory demonstrations.

Align the fuse tool so that the hook is toward the handle end and the pusher is in the opposite position, toward the hinge. Insert the hinge in the narrow vertical space in front of the fuseholder, between the holder and the fuse tray. In some cases, this may be a tight fit. The tool should rest on the fuse tray, and the handle should hang down.

Pusher Handle

Fuse tray

Bring the fuse into the enclosure. With the upper end of the fuse behind the upper fuseholder, bring the lower end of the fuse to rest on the V-notch in the pusher. The bulk of the fuse should be on the hinge side of the pusher.

Fuse end resting on V-notch Pusher

48

46032-700-09F.fm

Operating instructions

Visually align the upper end of the fuse with the upper clip, and raise the tool handle to push the fuse into the upper clip. Verify that the fuse is fully inserted into the upper clip. Lower the handle. If the fuse was fully inserted at the top, the lower end will naturally swing into place against the opening of the lower fuse clip.

Fuse

Lower fuse clip Fuse tool

Raise the handle again to push the fuse into the lower fuse clip.

Handle

46032-700-09F.fm

49

Operating instructions

Blown fuse indicator


The blown fuse indicator assembly is located on the line side of the MV power fuses. Should a blown fuse occur, the power fuse striker pin will pop up and activate the assembly. When activated, a flag is operated that is visible through the upper window of the contactor door. Two sets of contacts change state when the assembly is triggered. One set of contacts sends a direct trip signal to the contactor. The second set of contacts is available for remote indication.

Blown fuse Flag indicator

Good fuse

Flag indicator

Striker pin, top of fuse

50

46032-700-09F.fm

Operating instructions

Steps to remove fuses


NOTE: Always wear gloves when working with fuses. The fuses could be hot and will burn unprotected hands. The photos on these pages are factory demonstrations.

This process is the same for all fuses.


Align the fuse tool so that the hook is toward the hinge end of the tool and the pusher rests in the opposite direction, toward the handle. Insert the hinge in the narrow vertical space in front of the fuseholder, between the holder and the fuse tray. In some cases, this may be a tight fit. Support the handle in one hand, and place the hook around the back of the fuse as low as possible.

hook

Lower the handle to extract the fuse from the lower fuse clip. Manually pull the fuse from the upper fuse clip.

46032-700-09F.fm

51

Operating instructions

Removing and installing fuses of the Merlin Gerin Propivar power factor correction capacitors (PFCC) inside Motorpact enclosures
All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. Always remove all power from the section and use a properly rated testing device to confirm there is no voltage present. Always wear gloves when working with fuses. The body of a fuse that has blown or carried load current can be extremely hot and will burn unprotected hands.

Steps to remove fuses


IEC standard 60282-1:8.4.2 states that all of the MV fuses should be changed whenever one fuse is blown.

Remove and replace each fuse individually to avoid swapping wires.


Remove and retain the screw from the top of the connector. Remove and retain the washer. Remove and retain the connector from the top of the fuse. Loosen the jam nut at the bottom of the fuse. Unscrew the fuse from the PFCC threaded rod.

Screw Wire lug Connector

Washer

Fuse

PFCC threaded rod Jam nut PFCC

Steps to install fuses

Screw the fuse onto the PFCC threaded rod. Torque the fuse following fuse supplier specifications. Torque the jam nut against the fuse according to the fuse supplier specifications. Screw the connector on the fuse. Torque the connector according to the fuse supplier specifications. Install the wire lug, the washer, and the screw at the top of the connector as shown in the figure. Torque the screw to 3 Nm.
46032-700-09F.fm

52

Operating instructions

Removing and installing VT primary fuses


All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person. Always remove all power from the section and use a properly rated testing device to confirm there is no voltage present.

Steps to replace fuses

Remove the load from the contactor. See Operating the contactor. OPEN the disconnector to the earthed position. See Opening the disconnector. CLOSE the cable earthing switch, if supplied, to the earthed position. See Closing the cable earthing switch. Open the MV compartment door. See Opening the medium voltage compartment door.

C B

Steps to disassemble the fuse tube

Push tube end A, and rotate counter-clockwise Loosen screw holding fuse retainer plate B. Remove fuse C. Replace fuse C. Tighten screw holding fuse retainer plate B to a 1 Nm torque. Align tube A in housing slot; push and rotate clockwise. Complete these operations in the reverse order of removal. See Operating instructions Complete these electric tests in compliance with the standards in force.

Steps to assemble the fuse tube

Steps to place back into operation

46032-700-09F.fm

53

Operating instructions

Locking using padlocks

The pictogram on the operator cover is a reminder of the operations.

Number of possible padlocks per section type


Use 6 to 8 padlocks.

1 padlock on each disconnectorfor preventing operation. 1 padlock on each cable earthing switchfor preventing operation.

1 padlock on each incoming cable section doorfor preventing access.

Padlocking the disconnector

Place 1 padlock on the disconnector operating access port. This lock can be used to prevent operation of the disconnector in either the CLOSED or OPEN/earthed position.

54

46032-700-09F.fm

Operating instructions

Padlocking the cable earthing switch

Place 1 padlock on the cable earthing switch operating access port. This lock can be used to prevent operation of the cable earthing switch in either the CLOSED/earthed or OPEN position.

Padlocking the incoming cable section doors

Place 1 padlock on each padlockable incoming cable section door, upper and lower. This lock can be used to prevent MV access whenever a key lock is not requested.

46032-700-09F.fm

55

Operating instructions

Locking using keylocks (optional)


Motorpact can be provided with various keylock schemes based on customer needs. The typical keylock arrangement is shown. However, for the actual arrangement, see "equipment drawings" provided with each line-up.

Number of possible locks per section type

1 or 2 keylocks on each disconnectorfor preventing operation 1 keylock on each cable earthing switchfor preventing operation 1 keylock on each RVSS soft start section or RVAT sectionfor preventing access

Keylocking the disconnector


Locking the disconnector open or closed with 1 keylock

A keylock used to lock the disconnector OPEN or CLOSED Disconnector locked OPEN: Can be keyed to allow RVSS soft start section or RVAT MV compartment door to be opened. Can be keyed to allow cable earthing switch operation, if supplied Disconnector locked CLOSED Can be keyed to prevent disconnector from being OPENED Can be keyed to be OPENED only if power source is de-energized

Locking the disconnector open or closed with 2 keylocks

B double keylock used to lock the disconnector OPEN or CLOSED Disconnector locked OPEN: Can be keyed to allow cable earthing switch operation, if supplied Can be keyed to allow RVSS soft start section or RVAT MV compartment door to be opened Disconnector locked CLOSED: Can be keyed to prevent disconnector from being OPENED Can be keyed to be OPENED only if power source is de-energized

56

46032-700-09F.fm

Operating instructions

Locking the cable earthing switch open or closed

C keylock used to lock the cable earthing switch OPEN or CLOSED Cable earthing switch locked OPEN: Can be keyed to allow disconnector operation Cable earthing switch locked CLOSED: Can be keyed to allow RVSS soft start section or RVAT MV compartment door to be opened

46032-700-09F.fm

57

Operating instructions

FVR (full voltage reversing bidirectional)


Description
The full voltage reversing (FVR) starter is a full voltage, bidirectional motor starter with an operating range of 23007200 V. This product will deliver the highest starting torque (about 150% of full load torque) to the motor terminals in either direction: forward or reverse. This starter bases interrupting ratings on fused applications.

Forward contactor Reverse contactor

58

46032-700-09F.fm

Operating instructions

FVS (dual voltage transfer starter)


Description
The dual voltage transfer starter (FVS) is designed to operate as part of a smart sequence starter application or multiple motor soft starting application. A smart sequence starter application is a system to start multiple motors, one at a time, with a predetermined minimum start time between each motor start. The FVS is part of a line-up that also includes a full voltage non-reversing starter (FVNR) and an RVSS. One FVS is required per motor.

Main contactor Soft start contactor

Full voltage bus

Soft start flexible connector (600 A max.)

Soft start protection relay

Sepam protection relay

Sepam protection relay

Sepam protection relay

FVNR

RVSS
M

FVS
M

FVS
M

FVS

46032-700-09F.fm

59

Operating instructions

Redundant smart sequence starter


Description
The redundant smart sequence starter application takes the smart sequence starter and adds a second RVSS soft start section. The second RVSS section can be used as a back up to the first RVSS section or motor starting can be toggled betweeen the two RVSS soft start sections to allow one to cool down while the other is starting motors. The second RVSS section also allows for one remote line-up of dual voltage transfer starters (FVS) to be connected in addition to the close coupled FVS line-up. Full voltage bus Soft start flexible connector (600 A max.)

FVNR

RVSS

FVNR

RVSS

FVS

FVS

60

46032-700-09F.fm

Operating instructions

DDS (dual disconnect section)


Description
The dual disconnect section (DDS) is designed to operate as part of a redundant smart sequence starter application or multiple motor soft starting application. A smart sequence starter application is a system to start multiple motors, one at a time, with a predetermined minimum start time between each motor start. The optional DDS is part of a line-up that includes two full voltage non-reversing starters (FVNR), two RVSS soft start sections, and multiple dual voltage starters (FVS). The DDS is located between the RVSS and FVS sections in order to provide isolation between these sections when maintenance is being done on the RVSS sections. The DDS also provides cable landing for up to four remote FVS line-ups, as well as a close coupled FVS line-up.

46032-700-09F.fm

61

Operating instructions

Full voltage bus

Soft start flexible connector (600 A max.)

FVNR

RVSS

FVNR

RVSS

DDS

62

46032-700-09F.fm

Operating instructions

2-Speed, 1-Winding
Description
The 2-speed, 1-winding starter (2S1W) is designed for the control of two-speed AC motors that have a single winding. Since the motor is single winding, the speed change is accomplished by changing the wiring configuration using a third contactor. The 2S1W is part of a line-up that also includes a full voltage non-reversing starter (FVNR).

Slow-speed contactor Shorted contactor

46032-700-09F.fm

63

Operating instructions

2-Speed, 2-Winding
Description
The 2-speed, 2-winding starter (2S2W) is designed for the control of AC motors that have separate windings for high- and low-speed operation. Two interlocked contactors are used, with overload protection included for each motor winding.

Fast-speed contactor Slow-speed contactor

64

46032-700-09F.fm

Operating instructions

Star Delta
Description
Star Delta starters are designed for the reduced voltage starting of medium voltage motors by changing the configuration of the motor windings from a Star to a Delta AC configuration without lowering the current. The Star Delta is part of a line-up that also includes a full voltage non-reversing starter (FVNR).

Star-connection contactor Delta-connection contactor

46032-700-09F.fm

65

Operating instructions

RVAT (reduced voltage autotransformer)


Description
The Reduced Voltage Autotransformer (RVAT) is used to provide a reduced voltage to the motor terminals during starting. This is achieved by the use of an autotransformer. Typically two types of autotransformers are available.

Tappedpermits changing taps to change the output voltage to the motor terminals Non-tappedspecifically designed for the application and motor

In this manual, the tapped autotransformer is shown and discussed. For an application using a non-tapped autotransformer, all information provided is applicable other than the instruction for changing the tap settings. The section size of an RVAT is dependent upon the transformer rating. The RVAT is always controlled from a main contactor section adjacent to the left and the motor cable connections are made in this line contactor section. Each RVAT section is equipped with the following:

run contactor start contactor autotransformer surge arresters

Start contactor Run contactor

Door latch keylock Autotransformer

RVAT exterior

RVAT interior The reduced voltage starters contain an autotransformer with a limited duty cycle rating. Unless otherwise noted, these devices are rated per IEC 60076-11. Longer start times or more frequent starts will shorten the life of this device.

Limited duty cycle rating

66

46032-700-09F.fm

Operating instructions

Keylocks on an RVAT
Keylocking with disconnector (without cable earthing switch)
The RVAT section is supplied with key interlocks between the disconnector in the main contactor section and the start and run contactor compartments and the autotransformer compartment. With the disconnector in the CLOSED position, the key is held captive. During maintenance, the disconnector can be OPENED/ earthed and the key removed for access to the RVAT section. See Disconnector operation and Accessing the medium voltage compartments RVAT or RVSS soft start section.

Keylocking (with cable earthing switch)

When a cable earthing switch is supplied, the RVAT section is supplied with key interlocks between the cable earthing switch in the main contactor section and the start and run contactor compartments, and the autotransformer compartment. With the cable earthing switch in the OPEN or unearthed position, the key is held captive. During maintenance, the cable earthing switch can be CLOSED/earthed and the key removed for access to the RVAT section. See Cable earthing switch operation (optional) and Accessing the medium voltage compartments RVAT or RVSS soft start section. A spare key is supplied with every RVAT section. For safe operation, only 1 key should be used. The spare key should be stored away from the equipment and only used if 1 key is lost. Using both keys could give access to live parts and could cause death or serious injury.

46032-700-09F.fm

67

Operating instructions

RVAT operation
All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

Autotransformer taps

Autotransformers

Autotransformers are normally tapped at 50%65%80%. The standard factory setting used is 65%. Standard reduced-voltage starters make the transition from reduced to full voltage based on the operation of a current transition relay. As the motor accelerates, the current drawn will decrease. When the motor is near full speed, the relay will sense the drop in current and initiate the transition to full voltage. Transition based on a simple timing relay is not recommended. Increased loads may be placed on the power system, starter, motor, and driven equipment if a transition occurs before the motor is up to speed. If this method is used, refer to the electrical schematics provided with the line-up.

Relay setting

The current transition relay setting is user selectable with 100% being the recommended default setting. An incomplete sequence timer will open the starter if the current relay has not initiated transition before the timer times out. The timer should be set to a maximum of 30 seconds. The current relay setting may be increased to its maximum value of 120% if transition does not occur. If the starter does not transition in 30 seconds with the current relay set at its maximum of 120%, the motor does not have sufficient starting torque for the connected load. The motor must be unloaded or the starting torque increased. To increase starting torque, the autotransformer must be moved from the 65% tap setting to the 80% tap setting. steps to change tap settings

Tap setting

OPEN the main contactor controlling the equipment by pressing the STOP or OPEN pushbutton on the operating panel of the main contactor. See Operating the contactor. OPEN the disconnector in the main contactor to the earthed position. See Disconnector operation. If supplied, CLOSE the cable earthing switch to the earthed position. See Cable earthing switch operation (optional). Using the key from the main disconnector or cable earthing switch if supplied, OPEN the keylock allowing access to the MV compartments. See Accessing the medium voltage compartments RVAT or RVSS soft start section. Change tap setting cable connections as needed. See "autotransformer cable connections" in the installation instruction guide.
46032-700-09F.fm

68

Operating instructions

All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

The transition between the start and run contactors is made through the electrical control package; therefore, the operational steps are the same as an FVNR.

4#

4" "

+ 40

34*

$( 4 $

Operator panel main contactor section

Steps to CLOSE

OPEN or unearth the cable earthing switch, if supplied. See Cable earthing switch operation (optional). CLOSE the disconnector. See Disconnector operation. Press the START or CLOSE pushbutton on the operator panel.

Operator panel

Steps to OPEN

Press the STOP or OPEN pushbutton on the operator panel.

Main contactor

RVAT

46032-700-09F.fm

69

Operating instructions

Reduced voltage soft starter (RVSS) soft start section


Description
The RVSS soft start section is designed with heavy duty components to provide a soft motor start suitable form most demanding applications. Typical applications are as follows:

conveyor motor fans pumps mining equipment crushers grinders chillers compressors

Like the RVAT section, the soft start section is always controlled from an FVNR starter adjacent to the left of the RVSS soft start section. All motor cable connections are made in this main FVNR. See "loadbox cable connection" in the installation instruction guide for cable connection information. For specific detailed instruction on ratings, operation, programming, control connections, start-up, maintenance, replacement parts and troubleshooting, see Schneider Electric bulletin 46032-700-10_. Each RVSS soft start section is equipped with the following:

bypass contactor silicon starter rectifier microprocessor-based control system digital display Bypass contactor or PLC (depending on application) Digital display

Microprocessor based control system RVSS soft start section exterior

SCR assembly RVSS soft start section interior

Door latch keylock

70

46032-700-09F.fm

Operating instructions

Keylocks on an RVSS soft start section


Keylocking with disconnector (without cable earthing switch)
The RVSS soft start section is supplied with key interlocks between the disconnector in the main contactor section and the bypass contactor compartment. With the disconnector in the CLOSED position, the key is held captive. During maintenance, the disconnector can be OPENED/ earthed and the key removed for access to the RVSS soft start section. See Disconnector operation and Accessing the busbar compartmentsRVAT or RVSS soft start section.

Keylocking with cable earthing switch

When a cable earthing switch is supplied, the RVSS soft start section is supplied with key interlocks between the cable earthing switch in the main contactor section and the bypass contactor compartment and soft start power compartment. With the cable earthing switch in the OPEN or unearthed position, the key is held captive. During maintenance, the cable earthing switch can be CLOSED/earthed and the key removed for access to the RVSS soft start section. See Cable earthing switch operation (optional) and Accessing the medium voltage compartments RVAT or RVSS soft start section. A spare key is supplied with every RVSS soft start section. For safe operation, only 1 key should be used. The spare key should be stored away from the equipment and only used if 1 key is lost. Using both keys could give access to live parts and could cause death or serious injury.

Keylocking with redundant S3

The RVSS soft start sections in a redundant S3 line-up are supplied with key interlocks between the disconnectors in the main contactor sections and the FVS sections. It is important that the key interlocking scheme agreed upon between the customer and Schneider Electric is followed to make sure the RVSS soft start section MV doors cannot be opened unless the disconnectors in both main contactors and the FVS sections are all open. The RVSS soft start sections in a redundant S3 line-up are supplied with key interlocks between the disconnectors in the main contactor sections and the DDS. It is important that the key interlocking scheme agreed upon between the customer and Schneider Electric is followed to make sure the RVSS soft start section MV doors cannot be opened unless the disconnectors in both main contactors and the DDS are all open.

Keylocking with redundant S3 with dual disconnect section (DDS)

46032-700-09F.fm

71

Operating instructions

Removing a contactor from an RVAT section or RVSS soft start section


All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

Preliminary steps

OPEN the main contactor section controlling the equipment by pressing the STOP or OPEN pushbutton on the operating panel of the main contactor section. See Operating the contactor. OPEN the disconnector in the main contactor section to the earthed position. See Disconnector operation. If supplied, CLOSE the cable earthing switch to the earthed position. See Cable earthing switch operation (optional). Using the key from the main disconnector or cable earthing switch if supplied, OPEN the keylock allowing access to the MV compartments. See Accessing the medium voltage compartments RVAT or RVSS soft start section.

Steps to remove a start, run, or bypass contactor


An RVAT section is shown. However, the process is the same for RVSS soft start sections. Use extreme caution wile handling the contactor (25 kg) during this process. An optional lift truck is available. See "using a lift truck."

Pull the contactor rail down. This will disengage the contactor from the line and load busbar connections.

Contactor rail

Guide Wheel slot

Roll the contactor slowly out of the section until it rests in the wheel slot at the end of the contactor rail. Carefully lift the contactor out of the guide holding the rear wheel, and off of the contactor rail.

72

46032-700-09F.fm

Operating instructions

Installing a contactor in an RVAT section or RVSS soft start section


All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

Preliminary steps

OPEN the main contactor section controlling the equipment by pressing the STOP or OPEN pushbutton on the operating panel of the main contactor. See Operating the contactor. OPEN the disconnector in the main contactor to the earthed position. See Disconnector operation. If supplied, CLOSE the cable earthing switch to the earthed position. See Cable earthing switch operation (optional). Using the key from the main disconnector or cable earthing switch if supplied, OPEN the keylock allowing access to the MV compartments. See Accessing the medium voltage compartments RVAT or RVSS soft start section.

Steps to install a start, run, or bypass contactor


An RVAT section is shown; however, the process is the same for RVSS soft start section. A locking plate is used to prevent a contactor from being installed in the wrong section. If insertion is blocked, verify that the amperage and contactor type are correct. Use extreme caution while handling the contactor (25 kg) during this process. An optional lift truck is available. See "using a lift truck."

Pull the contactor rail down.

Wheel stop Contactor Guide rail Seat the rear wheel of the contactor between the contactor rail and the guide. Rest the front of the contactor onto the contactor rails. Slowly roll the contactor into the section until it reaches the wheel stop.

Lift

the contactor rail to the vertical position, engaging the contactor.

46032-700-09F.fm

73

Operating instructions

Using a lift truck (optional)

A lift truck is available for removing or installing contactors in an RVAT section or RVSS soft start section. Contact your local field sales office or distributor. Use this device with all guidelines and processes explained in:

Removing a contactor from an RVAT section or RVSS soft start section

contactor

lift truck

Removing contactor with a lift truck

74

46032-700-09F.fm

Operating instructions

MDT107 thermal diagnostic system (optional)


Description

The MDT107 Thermal Diagnostic System is mounted in the equipment at the factory for shipping. Wiring connections must be completed and tested on site before putting the equipment into service.

The MDT107 Thermal Diagnostic system is used to measure the temperature of medium voltage circuits. Using Schneider Electric patented technology, the MDT107 system provides:

continuous monitoring of temperature rise of power circuits at upper fuse holders and customer cable connections. triggering of a pre-alarm, then an alarm by activation of outputs on dry contacts. visual indication of the zone and phase in which a temperature rise exceeds a set threshold. An MDT107 electronic module mounted on a DIN rail in the LV cabinet of the Motorpact unit. The module transmits calibrated impulses to 1 or more circuits via optical fibers. The calculation of a circuits temperature is based on the impulses the circuit sends back to the module. 2 CFO733 temperature sensors. Each of these factory-built assemblies includes 3 sensor heads, 3 optical fibers, and the connector for connecting to the readout module. The sensor heads are made from a light-sensitive material whose fluorescence time depends on temperature. The connector incorporates an opticalelectric conversion circuit, eliminating the need for optical connections during installation. Accessories for factory installation of the sensors in the MV panel.

The MDT107 system includes:

46032-700-09F.fm

75

Operating instructions

Functions
Monitoring of temperature buildup in 2 zones

The MDT107 module performs the following functions: Each CFO733 sensor corresponds to a 3-point zone to be monitored in the panel, monitoring being based on temperature rise. The module measures the temperature at 3 points per zone, as well as the ambient temperature in order to calculate the temperature rise for each point. Given the temperature differences between the inside of the LV cabinet and the outside of the enclosure, correction of the ambient temperature measured by the module is configured by means of an additional setting. Comparison monitoring is used with a maximum temperature rise threshold, which may be adjusted separately for each zone and is common to the 3 measurement points. This form of monitoring is completed by a fixed maximum absolute sensor temperature threshold. Therefore, the module includes 3 settings, to which access is sealed after the ambient temperature settings are made on site.

Triggering of a pre-alarm

When the temperature rise at 1 of the 3 points reaches a first set point equal to 85% (1) of the preset threshold for the zone, or when 1 of the 3 points reaches the maximum absolute temperature of 115 C (239 F), a pre-alarm is generated that results in:
activation of the pre-alarm indication relay common to the 2 zones. activation in flashing mode of 1 of the 6 front panel indicators that identify the zone and related point.

Triggering of an alarm

When the temperature rise at 1 of the 3 points reaches the preset maximum threshold (2) for the zone, or when 1 of the 3 points reaches the maximum absolute temperature of 120 C (248 F), an alarm is generated that results in:
activation of the alarm power relay common to the 2 zones. activation in constant mode of 1 of the 6 front panel indicators that identify the zone and related point.

(1) This is a fixed value; it can not be modified. (2) These 7 setting values are defined at the factory. They are identified as A to G. See Wiring and operation for MDT107.

76

46032-700-09F.fm

Operating instructions

Self-monitoring of the module

The MDT107 module has internal self-tests and is equipped with an indicator that indicates availability:
each time the module is initialized. The indicator turns on in constant mode when the module is switched on and then turns off after the module initialization phase is successfully completed, unless the required sensors are missing (see Self-monitoring of sensorsbelow). in steady-state operation. If a fault is detected, the indicator turns on in constant mode.

Availability indicator

In both cases, the pre-alarm output contact is also activated when the indicator is steadily on. Self-monitoring of sensors The module provides continuous monitoring of the connected sensor(s). An Off position is included in the settings for each zone for the various situations that can occur:

If no sensors are connected to the module, the:


indicator is on and flashes pre-alarm output contact is activated 6 sensor identification indicators are off

If 1 of the 3 points of each sensor is detected as being faulty (cut or damaged fibers, malfunction of sensor-embedded electronics, etc.), the:
indicator is on and flashes pre-alarm output contact is activated indicator linked to the faulty measurement point flashes

When only 1 zone is connected, the unused zone should be set to Off. If this is not done, the 3 points of the related zone are detected as being faulty.

46032-700-09F.fm

77

Operating instructions

Wiring
Wiring and operation for MDT107
5 relay output, dry contact, connection terminals
Pre-alarm (1NO, 20-21) Alarm (1NCNO; 22-23-24)

Module grounding terminal via green/yellow wire (PE, safety of personnel)

24250 Vdc and 110240 Vac power supply connection terminals

Terminals 25 and 26 not used


off G A B C E off G F E D D A B C
Ambient T correction (C)

Zone B

Zone A
L3

Zone B

7
-18 -16 -14 -12 -10 -4 -6 -8

6 red indicators identifying the sensor (zone A or B) and the circuit/sensor at the origin of the alarm

Temperature rise threshold setting switches Ambient temperature correction setting switch

DT build-up setting

L2 L1

Zone A

on

Green power on indicator and red availability indicator


NOTE: The module's screw type connectors can receive 2 wires with maximum cross-section of 2.5 mm2 with or without fittings.

Ratings
Optical fiber probes CFO733 highest voltage for the equipment rated power frequency voltage impulse voltage maximum fiber/sensor temperature MDT107 module temperature rise setting operating and storage temperature absolute maximum threshold values Multi9 profile width module power supply dry contacts voltage continuous current consumption (standby to max.) AC DC factory set - 25 C to +70 C (-13 F to +158 F) pre-alarm = 115 C (239 F) alarm = 120 C (248 F) 10.5 cm (4.13 in.) 24/250 Vdc, 110/240 Vac 24, 48, 127, 220 Vdc, 100 to 240 Vac 5A permanent (pre-alarm) 8A permanent (trip) < 1.2 W (stby) to < 3.4 W (max) < 4.4 W (stby) to < 6.6 W (max) 17.5kV 38kV 95 kV 120 C (248 F)

78

46032-700-09F.fm

Operating instructions

MDT107 module location

Precaution: Use caution when working in the enclosure near the MDT107 sensors. The sensor heads can be damaged easily.

Field shapers

Load box

46032-700-09F.fm

79

Operating instructions

MDT107 sensors location

Field Shapers

Load Box

Setting the temperature rise thresholds


off A G F E D B C

The module is equipped with 2 mechanical selector switches for setting the temperature rise threshold for each zone. Each switch has 8 possible setting positions. The factory settings are shown in the table below. The selector switches are accessible from the front panel. They are protected by a sealed cover. To change the setting for a zone: Steps to set the temperature rise thresholds

Zone B
T build-up setting

off A G B C E D F

Zone A

Remove the protective cover. Insert the tip of a screwdriver into one of the arrow-shaped slots.
NOTE: Use a flathead screwdriver with a tip width of 0.15 in. (4 mm).

Turn the switch to the desired setting. Replace the protective cover.
Contactor rated current (A) Zone A field shapers connection Zone B load box connection

200 400 450 720

C E F G

B D D C

80

46032-700-09F.fm

Operating instructions

Setting the ambient temperature correction

The module contains a mechanical selector switch for correcting the ambient temperature measured on the MDT107 module. The switch has 8 possible setting positions. It is accessible from the front panel and is protected by a sealed cover. To change a setting: Steps to set the ambient temperature

Measure the temperature in the LV cabinet where the MDT107 module is located, then measure the ambient temperature outside the switchgear. Note the difference in temperature between the two locations. Remove the protective cover. Insert the tip of a screwdriver into the arrow-shaped slot.
NOTE: Use a flathead screwdriver with a blade width of 0.15 in. (4 mm).

Turn the switch to the setting closest to the temperature difference measured in step 1. Replace the protective cover.

-18
Ambient T correction (C)

-4 -6 -8

-16 -14 -12 -10

46032-700-09F.fm

81

Operating instructions

Troubleshooting

The following troubleshooting chart is provided to help minimize downtime. If the proposed solutions do not correct the problem, please contact the Schneider Electric Service Center.
Faulty devices Probable causes and solutions ensure the power supply is present and connected

Symptoms

green indicator is off

external power supply

insufficient voltage (out of range) MDT107 module is faulty and must be replaced

red indicator remains on after energizing

incorrect positioning of selector switches setting selection switches if indicators L1 (for example, 1or more switches is to L3 are flashing between 2 positions) indicators L1 to L3 Zones A and B are off probe connection probes or sensors MDT107 module is faulty and must be replaced the probe(s) are not connected, or the associated selector switch is in the "Off" position faulty probe or sensor that must be replaced

red indicator is flashing

Maintenance
Preventative maintenance
Inspect the equipment periodically to determine the conditions to which the units are subjected. After determining the environmental conditions according to the guidelines in this section (see Environmental conditionsbelow), perform inspections and maintenance according to the following table.

Recommended inspection/maintenance guidelines Component polyester disconnector housing housing interior (busbar and mechanism) housing See Environmental conditions for definitions. every 5 years every 2 years once per year Ideal conditions Standard conditions Aggressive conditions

Inspect the equipment immediately after abnormal or stressful operating conditions occur, or after the equipment experiences a fault current. These inspection/maintenance guidelines cover only the starter. If conditions cannot be established and documented, assume the operating conditions are aggressive. These inspection/maintenance guidelines do not warrant any field connections, field modifications, or supersede any maintenance procedures or schedules recommended by component manufacturers.

82

46032-700-09F.fm

46032-700-09F.fm

83

Maintenance

Environmental conditions
Ideal conditions

Unit is installed and commissioned in accordance with the manufacturers instructions. Humidity is below 40%, and there is no dripping water Indoor, protected from the weather Minimum of dust and air circulation Ambient temperature is between - 5 C and 40 C Altitude less than or equal to 1000 m, if above 1000 m, a derating coefficient will be applied (please consult us) No contact with any chemical agents (salt, H2S, etc.) No infestation of any animal life (rodents, insects, etc.) No contact with any plant life (mold, etc.) No earth movements No damage to the unit of any kind No operating problems of any kind No abnormally high number of operations No abnormally high number of faults No overvoltage or overcurrent (above ratings) Thermal scanning of the joints (where possible) at least once a year, or optional thermal diagnostics unit is installed Humidity below 60% The unit must not be subjected to regular extremes of temperatures greater than 40 C or less than - 30 C No regular thick covering of leaves or other debris Humidity above 60% Unit subjected to temperatures greater than 40 C or less than - 30 C

Standard conditions

Same as "ideal conditions" with the following exceptions:


Aggressive conditions

Any environmental conditions that have:


84

46032-700-09F.fm

Maintenance

Inspecting the equipment

All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

This product is warranted per Square D Conditions of Sale, see Schneider Electric document 0100PL0041, and has been tested under ideal laboratory conditions to the values listed below:

1000 mechanical no load operations 3 fuse fault transfer current operations (see IEC 62271-105C for application)

Motorpact has been designed and tested to IEC 60470 and related IEC standards. The mechanical life of the disconnector is 5000 operations. To verify the contact life of the contactor, see Schneider Electric bulletin 46032-700-02, Motorpact 200/400/450 A Vacuum Contactors. To ensure the starter is properly maintained, perform at least the following inspection procedures:

Busbar connections: De-energize the primary and secondary


circuits. Perform a standard hi-pot test to measure busbar insulation integrity (see "hi-pot dielectric test" in Schneider Electric bulletin 46032-700-08_, Motorpact IEC Installation Guide). Inspect the connections for symptoms that indicate overheating or weakened insulation. Remove dust from the surfaces of the busbars, connections, supports, and enclosures. Wipe clean with a solvent such as denatured alcohol. Vacuum the equipment. Do not use compressed air to blow dust from the surfaces inside the starter. Maintain the instruments, relays, and other devices according to the specific instructions supplied. Inspect the devices and their contacts for dust or dirt; wipe clean as necessary. The maintenance schedule for individual devices such as meters and relays should be based upon recommendations contained in the individual instruction guide for each device. Coordinate the various schedules with the overall maintenance program. Inspect control wiring connections for tightness and damage. Manually operate mechanical moving parts such as switch assemblies, interlocks, and doors. Make sure all busbar areas are well ventilated. Inspect grille work and air passages on starters to make sure they are free from obstruction and dirt accumulation. Verify all tools and/or hardware have been removed from the MV compartment. Replace all devices, doors, and covers with their original mounting hardware.

46032-700-09F.fm

85

86

46032-700-09F.fm

Replacement parts

Replacement parts
Corrective maintenance operations allow for malfunctioning subassemblies to be replaced. The operations mentioned in the summary table hereafter can be carried out by the customer or by Schneider Electric After Sales agents.
description
auxiliary switch (blown-fuse indicator) auxiliary switch-contacts (disconnector) auxiliary switch-terminal blocks (disconnector) control plugcontactor (female) control plugcontactor (male) control plug7 pin (female) control plug7 pin (male) control plug7 pin assembly frame control plug12 pin (female) control plug12 pin (male) control plug12 pin assembly frame fuse tool (removal, installation) handle, operator heater, one-high Mobilgrease 28, red VPIS/LLI module 25713203 S48198 S47074 MIP30F00830-359.0 MIP30M0000-0233 1925744 1925919 1852079 1925799 1925964 1852121 46033-250-51 3728693 46028-126-03 1615-100950 51193386F0 PR00620P70 PC18601P020 PC18601P121 PC18601P016 3Z9G0119G003 3Z9G0119G004 3Z9G0119G005 3Z9G0119G001 3Z9G0119G002 46032-243-01 PR01109P70

For any other intervention, call upon the nearest Schneider Electric group agents. After each maintenance, carry out electric tests in compliance with the standards in force.

Careful: During replacement, all the following accessories must absolutely be replaced by new equipment.
nylstop (self-locking nut) contact washer stop rings mechanical pin

part number

catalog number
AAF00956 AAF00955 AAF00955 AAF00950 AAF00950 AAF00952 AAF00952 AAF00951 AAF00953 AAF00953 AAF00951 AAF00174 AAF00954 AAF00006 consult us consult us consult us AAF00967 AAF00963 AAF00968 AAF00962 AAF00346 AAF00347 AAF00350 AAF00351 AAF00348 AAF00903 Included in latched-kit

contactor parts
auxiliary contact block-contactor (latched) closing coil kit-contactor (120/240 Vac) contact spring kit drive unit-contactor (printed circuit board) latched kit-contactor (24 Vdc) latched kit-contactor (32 Vdc) latched kit-contactor (48 Vdc) latched kit-contactor (125 Vdc) latched kit-contactor (250 Vdc) line/load connector opening spring-contactor replacement of main fuses replacement of VT fuses shunt lead kit-contactor trip coil-contactor (24 Vdc) trip coil-contactor (48 Vdc) trip coil-contactor (125 Vdc, standard) trip coil-contactor (250 Vdc) vacuum interrupter bottle-contactor wear gauge-contactor other electrical components 46032-700-09F.fm auxiliary contact block-contactor (magnetically held, standard) PC18601P012

consult a Schneider Electric representative consult us consult a Schneider Electric representative consult us PC18601P101SQ PC18601P015 PC18601P015 PC18601P003 PC18601P004 PC18601P007 PC18601P115 refer to specific order bill of materials 87 AAF00964 Included in latched-kit Included in latched-kit Included in latched-kit Included in latched-kit AAF00961 AAF00965

88

46032-700-09F.fm

Troubleshooting

Troubleshooting

All operations described hereafter must be carried out in compliance with the safety standards in force, under the responsibility of a competent person.

MV compartment door cannot be opened Disconnector cannot be operated

Check that the disconnector is in the OPEN/earthed position. Check that the disconnector access port is CLOSED. Check that the MV compartment door is CLOSED and the handle
latched. Check that the contactor is in the OPEN position. Check that the earthing switch (if supplied) is OPEN and the access port is CLOSED.

Disconnector access port cannot be CLOSED Disconnector access port cannot be OPENED Cable earthing switch cannot be operated

Check that the disconnector is fully OPEN or earthed. Check that the key interlock keys (if supplied) are in the proper position. Check that the disconnector is fully OPEN or earthed. Check that the key interlock keys (if supplied) are in the proper position. Check that the contactor is in the OPEN position. Check that the disconnector is in the OPEN/earthed position. Check that the MV compartment door is CLOSED and the handle is
latched. Check that the disconnector operating access port is OPEN.

Contactor will not CLOSE electrically

Check that the disconnector is CLOSED. Check that the disconnector access port is CLOSED. Check the control fuses. Check the closing coil circuit. Check for loose terminal connections. Check for a loose plug connection in the LV cabinet. Check the electrical interlocks. See "equipment drawings"
provided with each line-up.

Latched contactor will not OPEN electrically

Check the interlock linkage to the contactor. Check the control fuses. Check the trip coil circuit. Check for loose terminal connections. Check for loose plug connections in the LV cabinet. Check the electrical interlocks. See "equipment drawings"
provided with each line-up.

Voltage presence indicator does not illuminate

Test for voltage on 2 of the test ports on the indicating box. Verify the
MV voltage is truly present.

46032-700-09F.fm

89

90

46032-700-09F.fm

Glossary

auxiliary contacts

Sets of contacts mechanically operated by the disconnector or the contactor. A section that contains either low voltage or medium voltage components that require a different mounting than a typical starter section.

auxiliary section

busbar compartment

The compartment isolating the through or main busbars in a Motorpact switchboard line-up.
A sliding 2-position device (CLOSED position earthed). Designed to discharge the capacitance to earth up to a 5 kA fault. A capacitor attached to the phase busbar that is used to send a reduced voltage signal to a neon light for voltage presence indication. The mobile vacuum interrupting device used for establishing and interrupting the medium voltage power in the circuit. A transformer that reduces medium voltage to low voltage for control circuit use. An instrument transformer intended to have its primary winding connected in series with the conductor carrying the current to be measured or controlled. A rotating, 2-position switch that is used to connect the main power source in the closed position and to connect to the equipment earth in the open position. The external surface of a section that prevents access to the sections internal parts. A motor starter which connects the line voltage across the motor terminals in one step. A medium voltage fuse capable of interrupting all currents from the rated breaking capacity to the minimum breaking current I3. A cylindrical fuse terminal at the end of a cartridge fuse. An assembly of insulated fuse tubes that house the primary contacts of the medium voltage fuse connection for the CPT and VT fuses. A device intended to insulate and give rigid support to busbars throughout the equipment. A device actuated by the operation of some other device to govern succeeding operations. The interlocks are classified into three main divisions: mechanical, electrical, and key interlocks.

cable earthing switch

capacitive divider

contactor

control power transformer (CPT)

current transformer (CT)

disconnector

enclosure

full voltage starter

fuse, medium voltage

fuse ferrule fuseholder

insulator

interlocks

46032-700-09F.fm

91

Glossary

internal arc tunnel

An air chamber or compartment attached to the roof of the switchboard lineup. This compartment is designed for containing or distributing the gases should an internal arc event occur. A description for the added features of the enclosure which help in the withstand or containment of a gas discharge should an internal arc event occur. A device that transforms a medium voltage circuit current into a proportional low voltage signal. A switchboard compartment which houses any medium voltage devices. A device that counteracts the undesirable effects of electric loads which create a power factor less than 1. Any combination of Motorpact units shipped together. The combination of all the switching means necessary to start and stop a motor with suitable overload protection, i.e., a section mounting a contactor and fuses that is used for starting motors. Pre-manufactured insulated cable termination recommended for all incoming/outgoing and load connections. A device intended to protect equipment from electrical overvoltage. The VPIS is a light module mounted on the front of the equipment that gives an indication when voltage is present on the MV cables. Energy is provided from a capacitive divider (see definition for capacitive divider). An instrument transformer intended to have its primary winding connected in shunt with a power supply circuit for measuring the voltage. Pre-manufactured wiring bundles or connections.

internal arc withstand

low power current transformer (LPCT) medium voltage compartment power factor correction capacitor (PFCC) shipping section starter

stress cone

surge arrester voltage presence indication system (VPIS)

voltage transformer (VT)

wiring harness

92

46032-700-09F.fm

46032-700-09F.fm

93

The Schneider group service centers are at your service for: -engineering and technical assistance, -commissioning, -training, -preventive and corrective maintenance, -adaptation, and -spare parts. Contact your sales representative who will put you in touch with your nearest Schneider group service center or call us on 33 (0)4 76 57 60 60 (Grenoble, France).

Schneider Electric Industries SAS


35, rue Joseph Monier CS 30323 F - 92506 Rueil Malmaison Cedex (France) Tl. : +33 (0)1 41 29 70 00 RCS Nanterre 954 503 439 Capital social 896 313 776 www.schneider-electric.com

As standards, specifications, and designs change from time to time, please ask for confirmation of the information given in this publication. This document has been printed on ecological paper.

46032-700-09F

11/2011

46032-700-09F 20042011 Schneider Electric All rights reserved.

S-ar putea să vă placă și