Moulded Case Circuit Breaker

31

Moulded Case Circuit Breaker


CONSTRUCTION

32

Loadline Moulded Case Circuit Breakers have precision formed moulded case and cover of high performance resin bonded thermoset material. The circuit breakers are designed to allow grouping in distribution panels or switchboards to present their operating handles and label escutcheons uniformly aligned in a single panel cut out. The switching mechanism is Quick make-Quick break type and is tripfree, i.e. the breaker trips internally even if the operating knob is held in ON position. The contact mechanism comprises of xed and moving contacts made of sintered silver alloy for reliability, long life and anti-welding properties. Arcing contacts are provided in higher frames, further increasing the contact life. The arc extinguishing device comprises of arc chutes having grid plates mounted in parallel between supports of insulating material. The arc is divided between these grid plates which helps in its fast quenching. The arc is thus conned, divided and extinguished in the arc chute. The excellent insulation between the conducting parts and better energy dissipiation after short circuit makes it possible to make the load and line connections on either side.

Contact Mechanism

Switching Mechanism

Arc Chute Push to trip

Trip Bar

Overload & short circuit adjustment

Trip Bar

Instantaneous trip release

The tripping mechanism comprises of a bimetal and heater element for overload protection and xed & moving core for magnetic protection in each pole coupled to a single trip bar unit to avoid single phasing. The overload and magnetic setting are front adjustable on site. Thermal Magnetic Type The overload protection is provided by a combination of the heater element and the bimetal strip in each phase which activates the trip mechanism. Short Circuit protection is provided by the magnetic circuit comprising of the xed and moving core. In the event of short circuit, the moving core is attracted towards the xed core due to the high electromagnetic forces developed which actuates the trip mechanism. The xed and moving contacts of Loadline MCCBs are so designed that an electromagnetic repulsive force is developed under high currents which is sufcient to overcome the spring tension holding the moving contacts, thereby initiating the contact opening resulting into faster opening of the contacts limiting the prospective short circuit current.

Moulded Case Circuit Breaker


TECHNICAL INFORMATION
Standard conformity Rated operational voltage Rated Insulation Voltage Type of release Utilisation Category Rated frequency Ambient temp Operating altitude Humidity Rated impulse voltage : : : : : : : : : : IEC 60947-2/IS:13947-2 415V AC 690V AC Thermomagnetic A 50/60 Hz 40oC (50oC on request) 2000 meters 0 - 90% 8 KV GS 1P / 3P / 4PwSN 25-125* Fixed A A A KA 240V 380V 415V 500V Kg Kg Kg Sq.mm mm Nm 500 800 1000 17 25 10 10 7.5 0.35 0.93 1.2 70 10 2.5 + + GN 1P / 3P / 4PwSN 25-125* Fixed 500 800 1000 32 25 16 16 12 0.35 0.93 1.2 70 10 2.5 + + GH 3P / 4PwSN 25-100* Fixed 500 800 1000 52.5 30 25 25 14 0.35 0.93 1.2 70 10 2.5 + +

G-FRAME

33

Frame No. of Poles Standard current range / rating (In) Thermal relelase setting Magnetic release setting for current rating : 25A - 50A 63A - 80A 100A - 125A Rated short circuit making capacity (Peak) Icm Rated ultimate short circuit breaking capacity(Icu), KA (at different voltages)

Weight SP TP 4PwSN Terminal capacity (cable) Bus bar (width) Recommended Torque Internal Accessories Auxiliary Switch (1 C/O or 2C/O) Shunt Trip Under Voltage Release External Accessories Earth Fault Relay Rotary Handle Back Studs Extended Terminals (above 63A) Dolly Extension Phase Barriers Terminal Shrouds Dolly pad locking Device

* Current Ratings - 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A Available, - Not Available, + Supplied alongwith the MCCB as standard.

1P - Single Pole 3P - Three Pole 4PwSN - Four Pole with Switched Neutral

Moulded Case Circuit Breaker


TECHNICAL INFORMATION AA-FRAME

34

Standard conformity Rated operational voltage Rated Insulation Voltage Type of release Utilisation Category Rated frequency Ambient temp Operating altitude Humidity Rated impulse voltage Frame No. of Poles

: : : : : : : : : :

IEC 60947-2/IS:13947-2 415V AC 690V AC Thermomagnetic A 50/60Hz 40oC (50oC on request) 2000 meters 0 - 90% 8 KV AAS 1P / 3P / 4PwSN (In) A 25-200* 70-100% of In 400A 800A 1600A AAN 1P / 3P / 4PwSN 25-250* 70-100% of In 400A 800A 1600A 32
(160-200A)

AAM 3P/4PwSN 50-250* 70-100% of In 800A 1600A 52.5


(160-250A)

Standard current range / ratings

Thermal release setting (Adjustable) Magnetic release setting for current rating : 25A - 63A 80A - 125A 160A - 250A 50A -125A 160A -250A AM Frame AM Frame

52.5
(25-125A)

Rated short circuit making capacity (Peak) Icm KA Rated ultimate short circuit breaking capacity(Icu), KA (at different voltages) 240V 380V 415V 500V Weight SP (Single Pole) TP (Triple Pole) Terminal capacity (Cable) (Bus bar width) Recommended Torque Internal Accessories Auxiliary Switch (1 C/O or 2C/O) Shunt Trip Under Voltage Release External Accessories Earth Fault Relay Rotary Handle Back Studs Extended Terminals (above 63A) Dolly Extension Phase Barriers Terminal Shrouds Dolly pad locking Device
* Current Ratings - 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A Available, - Not Available, + Supplied alongwith the MCCB above 63A..

73.5
(25-125A)

52.5
(50-250A)

40 35 25 18 0.7 1.8 2.4 mm

25 16 16 12

50 35 35 25 0.7 1.8 2.4

40 35 25 18

40 35 25 18 0.7 1.8 2.4

Kg Kg Sq.mm Nm

FPwSN(Four Pole Switched Neutral) Kg

70(upto 100A)/150 (125A-250A) 25 (125A-250A) 10 + + 10 + +


1P - Single Pole 3P - Three Pole 4PwSN - Four Pole with Switched Neutral

10 + +

Moulded Case Circuit Breaker


TECHNICAL INFORMATION
Standard conformity Rated operational voltage Rated Insulation Voltage Type of release Utilisation Category Rated frequency Ambient temp Operating altitude Humidity Rated impulse voltage Frame No. of Poles Standard Current ratings Thermal release setting Magnetic release setting for current rating 25A - 32A 40A - 80A 100A - 125A 160A - 250A Rated short circuit making capacity (Peak) Icm kA Rated ultimate short circuit breaking capacity(Icu), kA (at different voltages) 240V 380V 415V 500V Weight TP (Triple Pole) / FPwSN Terminal Type Terminal capacity Internal Accessories Auxiliary Switch (1 C/O or 2C/O) Shunt Trip Under Voltage Release Alarm Switch (1 C/O) # External Accessories Earth Fault Relay Rotary Handle Back Studs Extended Terminals (above 63A) Dolly Extension Phase Barriers Terminal Shrouds Dolly pad locking Device
* # Current Ratings - 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A Available, - Not Available, + Supplied alongwith the MCCB above 63A. Factory Fitted

F-FRAME

: : : : : : : : : :

IEC 60947-2/IS:13947-2 415V AC 690V AC Thermomagnetic A 50/60Hz 40oC (upto 55oC on request) 2000 meters 0 - 90% 8 kV F N 3P / 4PwSN (In) A 25-250* Fixed Fixed 500A 800A 1250A 1600A 73.5 50 35 35 25 2.9 / 3.8 M8 (Cable) Sq.mm (Bus bar width) mm 185 18 + +
3P - Three Pole 4PwSN - Four Pole with Switched Neutral

35

F H 3P / 4PwSN 25-250* Fixed Fixed 500A 800A 1250A 1600A 105 70 50 50 35 2.9 / 3.8 M8 185 18 + +

Kg

Moulded Case Circuit Breaker


TECHNICAL INFORMATION CN / CH / DN - FRAME

36

Standard conformity Rated operational voltage Rated Insulation Voltage Type of release Utilisation Category Rated frequency Ambient temp Operating altitude Humidity Rated impulse voltage Frame

: : : : : : : : : :

IEC 60947-2/IS:13947-2 415V AC 690V AC Thermomagnetic A 50/60Hz 40oC (50oC on request) 2000 meters 0 - 90% 8 KV CN 3P/4PwSN 160-800* 70-100% of In Adjustable 5-10 times In 4-10 times In 73.5 50 35 35 25 9.2 11.6 40 CH 3P/4PwSN 160-800* 70-100% of In Adjustable 5-10 times In 4-10 times In 105 70 50 50 35 9.2 11.6 40 DN 3P/4PwSN 800-1600* 70-100% of In Adjustable 4000-10,000A 105 70 50 50 35 17#/19** 22/25 45** upto 800A 45** upto 1000A 60** upto 1250A 65** upto 1600A 35.5# upto 1600A
3P - Triple Pole 4PwSN - Four Pole with Switched Neutral

No. of Poles Standard current ratings (In) A Thermal release setting (Adjustable) Magnetic release setting 160 - 315A CN/CH Frame 400 - 800A CN/CH Frame 800 - 1600A DN frame Rated short circuit making capacity (Peak) Icm KA Rated ultimate short circuit breaking capacity(Icu), KA 240V (at different voltages) 380V 415V 500V Weight TP (Triple Pole) FPwSN (Four Pole with Switched Neutral) Terminal capacity (cable) (Bus bar width) Kg Kg Sq.mm mm

Internal Accessories Auxiliary Switch (1 C/O or 2 C/O) Shunt Trip Under Voltage Release External Accessories Earth Fault Relay Rotary Handle Back Studs Extended Terminals Dolly Extension Phase Barriers Terminal Shrouds Dolly pad locking Device

+ +

* Current Ratings - 160A, 200A, 250A, 315A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1600A. Available, - Not Available, + Supplied alongwith the MCCB as standard. ** Terminals at Front # Terminals at back / rear

Moulded Case Circuit Breaker


TECHNICAL INFORMATION DC MCCBs
Standard conformity Rated operational voltage Rated Insulation Voltage Type of release Utilisation Category Ambient temp Operating altitude Humidity Frame No. of Poles Standard current ratings In Thermal release setting A : : : : : : : : IEC 60947-2/IS:13947-2 250V DC 690V AC Thermomagnetic A 40oC 2000 meters 0-90% GN 3P 25-125* Fixed AAN 3P 160-250* Adjustable (70-100% of In) 1600A 10 1.8 70(upto 100A)/150 (125A-250A) 25 CH 3P 160-800* Adjustable (70-100% of In) 5 - 10 times In 4 - 10 times In 20 9.2 40 DN 3P 800-1600* Adjustable (70-100% of In) 4000-10,000A 20 17#/19** 45** upto 800A 45** upto 1000A 60** upto 1250A 65** upto 1600A 35.5# upto 1600A

GN / AN / CH / DN - FRAME

37

Magnetic release setting for current rating : 25-50A GN Frame 63-80A GN Frame 100-125A GN Frame 160-200A AN Frame 160-315A CH Frame 400-800A CH Frame 800-1600A DN frame Rated ultimate short circuit KA breaking capacity (Icu), at 250V DC Weight Terminal capacity (cable) (bus bar width) Kg Sq.mm mm

500A 800A 1000A 5 0.93 70 10

Recommended Torque Internal Accessories Auxiliary Switch Shunt Trip External Accessories Earth Fault Relay Rotary Handle Back Studs Extended Terminals Dolly Extension Phase Barriers Terminal Shrouds Dolly pad locking Device

Nm

2.5 + +

10 + +

+ +

* Current Ratings - 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A, 160A, 200A, 250A, 315A, 400A, 500A, 630A, 800A, 1000A, 1250A, 1600A. Available, - Not Available, + Supplied alongwith the MCCB as standard. ** Terminals at Front, # Terminals at Rear.
Loadline DC MCCBs DC MCCBs are available in three pole version from 25A-1600A with breaking capacity of 5KA, 10KA & 20KA. The selection of the circuit breaker for DC applications depends on these criteria : Rated current of the equipment. Rated voltage, which determines the number of poles in series for breaking. For voltages upto 250V DC, two poles of the breaker are connected in series to form the positive pole and the third pole to be used as a negative pole or three poles can be used in series. The maximum short-circuit current at the point of installation, which determines the breaking capacity. The (L/R) ratio for the application should be < 15 ms.

Moulded Case Circuit Breaker


G FRAME SINGLE POLE MCCB

38
Current Rating (A) 25 32 40 50 63 80 100 125 Icu 10kA Cat. No. LGSS0025 LGSS0032 LGSS0040 LGSS0050 LGSS0063 LGSS0080 LGSS0100 LGSS0125 Icu 16kA Cat. No. LGNS0025 LGNS0032 LGNS0040 LGNS0050 LGNS0063 LGNS0080 LGNS0100 LGNS0125

G FRAME THREE POLE MCCB


Current Rating (A) 25 32 40 50 63 80 100 125 160 Icu 10kA Cat. No. LGST0025 LGST0032 LGST0040 LGST0050 LGST0063 LGST0080 LGST0100 LGST0125 LGST0160 Icu 16kA Cat. No. LGNT0025 LGNT0032 LGNT0040 LGNT0050 LGNT0063 LGNT0080 LGNT0100 LGNT0125 LGNT0160 Icu 25kA Cat. No. LGHT0025 LGHT0032 LGHT0040 LGHT0050 LGHT0063 LGHT0080 LGHT0100 ---

G FRAME FOUR POLE wSN MCCB


Current Rating (A) 25 32 40 50 63 80 100 125 Icu 10kA Cat. No. LGSF0025 LGSF0032 LGSF0040 LGSF0050 LGSF0063 LGSF0080 LGSF0100 -Icu 16kA Cat. No. LGNF0025 LGNF0032 LGNF0040 LGNF0050 LGNF0063 LGNF0080 LGNF0100 -Icu 25kA Cat. No. LGHF0025 LGHF0032 LGHF0040 LGHF0050 LGHF0063 LGHF0080 LGHF0100 --

Moulded Case Circuit Breaker


G FRAME ACCESSORIES
SHUNT TRIP

(Accessories are for 3P / 4P wSN)

39
Voltage 18-30Vac/12-36Vdc 110-110Vac 220-240Vac Cat No. LLSTG030 LLSTG110 LLSTG240

For Operating the Shunt Trip, one Changeover contact of the auxiliary switch would be used leaving one free.

UNDER VOLTAGE RELEASE

Voltage 110-120 Vac 220-240 Vac 380-440 Vac

Cat No. LUVRG110 LUVRG240 LUVRG440

The breaker trips if the supply voltage dips below 70% to 35% of the rated voltage. The breaker cannot be switched ON unless there is a supply to the UVR. (NVNC feature). Supplied with external mounting Power pack to operate on AC supplies. Additional transformer is supplied with LUVRG440 & LUVRG110. AUXILIARY SWITCH

Voltage

Current Rating (AC15) 3 3 3 3 Amps Amps Amps Amps

Cat No.

Config.

250Vac/250Vdc 250Vac/250Vdc 450Vac/250Vdc 450Vac/250Vdc

LLASG1C2 LLASG2C2 LLASG1C4 LLASG2C4

(1NO+1NC) 2(1NO+1NC) (1NO+1NC) 2(1NO+1NC)

ROTARY HANDLE

Cat No. With Door interlock and 300mm remote shaft LLRRHG30

Moulded Case Circuit Breaker


G FRAME ACCESSORIES (Accessories are for 3P / 3P wSN)

40

OTHER ACCESSORIES

Cat. No. Dolly Pad locking device Extended terminals Phase Barriers Terminal Shrouds Single Pole Three Pole Four Pole wSN LLDPG125 LLETG125 LLPBG125 LLTSGS00 LLTSGT00 LLTSGF00

DIMENSIONS (IN MM)

Single Pole

Three Pole

Three Pole with Extended Terminals

Four Pole with Switched Neutral

Moulded Case Circuit Breaker


DIMENSIONS (IN MM) - ROTARY HANDLE

41

Moulded Case Circuit Breaker


AA Frame Single Pole MCCB

42
Current Rating (A) 25 32 40 50 63 80 100 125 160 200 250 Icu 25kA Cat. No. LASS0025 LASS0032 LASS0040 LASS0050 LASS0063 LASS0080 LASS0100 LASS0125 LANS0160 LANS0200 LANS0250

AA Frame Three Pole MCCB


Current Rating (A) 25 32 40 50 63 80 100 125 160 200 250 Icu 16kA Cat. No. --------LAST0160 LAST0200 -Icu 25kA Cat. No. LAST0025 LAST0032 LAST0040 LAST0050 LAST0063 LAST0080 LAST0100 LAST0125 LANT0160 LANT0200 LANT0250 Icu 35kA Cat. No. LANT0025 LANT0032 LANT0040 LANT0050 LANT0063 LANT0080 LANT0100 LANT0125 ----

AA FRAME FOUR POLE wSN MCCB


Current Rating (A) 25 32 40 50 63 80 100 125 160 200 250 Icu 16kA Cat. No. --------LASF0160 LASF0200 -Icu 25kA Cat. No. LASF0025 LASF0032 LASF0040 LASF0050 LASF0063 LASF0080 LASF0100 LASF0125 LANF0160 LANF0200 LANF0250 Icu 35kA Cat. No. LANF0025 LANF0032 LANF0040 LANF0050 LANF0063 LANF0080 LANF0100 LANF0125 ----

Moulded Case Circuit Breaker


AM Frame Three Pole MCCB ( motor duty)

43
Current Rating (A) 50 63 80 100 125 160 200 250 Icu 25kA Cat. No. LAMT0050 LAMT0063 LAMT0080 LAMT0100 LAMT0125 LAMT0160 LAMT0200 LAMT0250

AM FRAME FOUR POLE wSN MCCB (MOTOR DUTY)


Current Rating (A) 50 63 80 100 125 160 200 250 Icu 25kA Cat. No. LAMF0050 LAMF0063 LAMF0080 LAMF0100 LAMF0125 LAMF0160 LAMF0200 LAMF0250

Moulded Case Circuit Breaker


AA/AM FRAME ACCESSORIES (Accessories are for 3P / 4P wSN)

44

SHUNT TRIP

Voltage 18-30Vac/12-36Vdc 100-110Vac 220-240Vac 380-415 Vac

Cat. No. LLSTA030 LLSTA110 LLSTA240 LLSTA415

UNDER VOLTAGE RELEASE

Voltage 110-120 Vac 220-240 Vac 380-440 Vac

Cat. No. LUVRA110 LUVRA240 LUVRA440

The breaker trips if the supply voltage dips below 70% to 35% of the rated voltage. The breaker cannot be switched ON unless there is a supply to the UVR. (NVNC feature). Supplied with external mounting Power pack to operate on AC supplies. Additional transformer is supplied with LUVRA440 & LUVRA110.

AUXILIARY SWITCH

Voltage

Current Rating (AC15) 4 4 4 4 Amps Amps Amps Amps

Cat. No.

Config.

250Vac/250Vdc 250Vac/250Vdc 450Vac/250Vdc 450Vac/250Vdc

LLASA1C2 LLASA2C2 LLASA1C4 LLASA2C4

(1NO+1NC) 2(1NO+1NC) (1NO+1NC) 2(1NO+1NC)

ROTARY HANDLE

Cat. No. With Door interlock and 300mm remote shaft LLRRHA30

Moulded Case Circuit Breaker


AA/AM FRAME ACCESSORIES
BACK STUDS

(Accessories are for 3P / 4P wSN)

45
Cat. No. Upto 250A LLBSA250

OTHER ACCESSORIES

Dolly Pad locking device Extended terminals Phase Barriers Terminal Shrouds Three Pole Four Pole wSN

Cat. No. LLDPA250 LLETA250 LLPBA250 LLTSAT00 LLTSAF00

Handle fixing details of A Frame are given on page 48

DIMENSIONS (IN MM)

Single Pole

Three Pole

Four Pole with Switched Neutral

Three Pole with Extended Terminals

Moulded Case Circuit Breaker


FN/FH Frame Three Pole / Four pole with switch neutral

46
Current Rating (A) 25 32 40 50 63 80 100 125 160 200 250 Icu 35kA Cat. No. Icu 50kA Cat. No. Icu 35kA Cat. No. Icu 50kA Cat. No. THREE POLE LFNT0025 LFHT0025 LFNT0032 LFHT0032 LFNT0040 LFHT0040 LFNT0050 LFHT0050 LFNT0063 LFHT0063 LFNT0080 LFHT0080 LFNT0100 LFHT0100 LFNT0125 LFHT0125 LFNT0160 LFHT0160 LFNT0200 LFHT0200 LFNT0250 LFHT0250 FOUR POLE LFNF0025 LFHF0025 LFNF0032 LFHF0032 LFNF0040 LFHF0040 LFNF0050 LFHF0050 LFNF0063 LFHF0063 LFNF0080 LFHF0080 LFNF0100 LFHF0100 LFNF0125 LFHF0125 LFNF0160 LFHF0160 LFNF0200 LFHF0200 LFNF0250 LFHF0250

FN/FH FRAME ACCESSORIES


SHUNT TRIP

(Accessories are for 3P / 4P wSN)

Voltage 18-30Vac/12-36Vdc 100-110Vac 220-240Vac 380-415 Vac

Cat No. LLSTF030 LLSTF110 LLSTF240 LLSTF415

UNDER VOLTAGE RELEASE

Voltage 110-120 Vac 220-240 Vac 380-440 Vac

Cat No. LUVRF110 LUVRF240 LUVRF440

The breaker trips if the supply voltage dips below 70% to 35% of the rated voltage. The breaker cannot be switched ON unless there is a supply to the UVR. (NVNC feature). Supplied with external mounting Power pack to operate on AC supplies. Additional transformer is supplied with LUVRF440 & LUVRF110.

AUXILIARY SWITCH

Voltage

Current Rating (AC15) 4 4 4 4 Amps Amps Amps Amps

Cat No

Config.

250Vac/250Vdc 250Vac/250Vdc 450Vac/250Vdc 450Vac/250Vdc

LLASF1C2 LLASF2C2 LLASF1C4 LLASF2C4

(1NO+1NC) 2(1NO+1NC) (1NO+1NC) 2(1NO+1NC)

Moulded Case Circuit Breaker


FN/FH FRAME ACCESSORIES
ROTARY HANDLE

(Accessories are for 3P / 4PwSN)

47
Cat. No. With Door interlock and 300mm remote shaft LLRRHF30

OTHER ACCESSORIES

Dolly Pad locking device Extended terminals LLETF250 Phase Barriers Terminal Shrouds Three Pole Four Pole with Switch Neutral

Cat. No. LLDPF250 LLPBF250 LLTSFT00 LLTSFF00

Handle fixing details of F Frame are given on page 48

DIMENSIONS (IN MM)

Four Pole with Switch Neutral

Three Pole

Moulded Case Circuit Breaker


DIMENSIONS (IN MM) - ROTARY HANDLE

48

Moulded Case Circuit Breaker


CN Frame Three Pole MCCB

49
Current Rating (A) 160 200 250 315 400 500 630 800 Icu 35kA Cat. No. LCNT0160 LCNT0200 LCNT0250 LCNT0315 LCNT0400 LCNT0500 LCNT0630 LCNT0800

CN FRAME FOUR POLE wSN MCCB


Current Rating (A) 160 200 250 315 400 500 630 800 Icu 35kA Cat. No. LCNF0160 LCNF0200 LCNF0250 LCNF0315 LCNF0400 LCNF0500 LCNF0630 LCNF0800

CH Frame Three Pole MCCB


Current Rating (A) 160 200 250 315 400 500 630 800 Icu 50kA Cat. No. LCHT0160 LCHT0200 LCHT0250 LCHT0315 LCHT0400 LCHT0500 LCHT0630 LCHT0800

CH FRAME FOUR POLE wSN MCCB


Current Rating (A) 160 200 250 315 400 500 630 800 Icu 50kA Cat. No. LCHF0160 LCHF0200 LCHF0250 LCHF0315 LCHF0400 LCHF0500 LCHF0630 LCHF0800

Moulded Case Circuit Breaker


CN/CH FRAME ACCESSORIES (Accessories are for 3P / 4PwSN)

50

SHUNT TRIP

Voltage 18-30Vac/12-36Vdc 100-110Vac 220-240Vac 380-415 Vac

Cat. No. LLSTC030 LLSTC110 LLSTC240 LLSTC415

UNDER VOLTAGE RELEASE

Voltage 110-120 Vac 220-240 Vac 380-440 Vac

Cat. No. LUVRC110 LUVRC240 LUVRC440

The breaker trips if the supply voltage dips below 70% to 35% of the rated voltage. The breaker cannot be switched ON unless there is a supply to the UVR. (NVNC feature). Supplied with external Power pack to operate on AC supplies. Additional transformer is supplied with LUVRC440 & LUVRC110. AUXILIARY SWITCH

Voltage

Current Rating (AC15) 4 4 4 4 Amps Amps Amps Amps

Cat. No.

Config.

250Vac/250Vdc 250Vac/250Vdc 450Vac/250Vdc 450Vac/250Vdc

LLASC1C2 LLASC2C2 LLASC1C4 LLASC2C4

(1NO+1NC) 2(1NO+1NC) (1NO+1NC) 2(1NO+1NC)

ROTARY HANDLE

Cat. No. With Door interlock and 300mm remote shaft LLRRHC30

Moulded Case Circuit Breaker


CN/CH Frame Accessories
BACK STUDS Cat. No. Upto 400A LLBSC400

51

OTHER ACCESSORIES Cat. No. Dolly Pad locking device Phase Barriers Dolly Extension LLDPC800 LLPBC800 LLDEC800

DIMENSIONS (IN MM)

Three Pole

Four Pole with Switched Neutral

Three Pole with Extended Terminals

Moulded Case Circuit Breaker


DIMENSIONS (IN MM) - ROTARY HANDLE

52

Moulded Case Circuit Breaker


DN Frame MCCB - Three Pole / FOUR POLE with switched neutral
THREE POLE Current Rating (A) 800 1000 1250 1600 Icu 50kA Cat. No. LDNT0800 LDNT1000 LDNT1250 LDNT1600

53

FOUR POLE Current Rating (A) 800 1000 1250 Icu 50kA Cat. No. LDNF0800 LDNF1000 LDNF1250

D Frame Accessories
SHUNT TRIP

Voltage 18-30Vac/12-36Vdc 100-110Vac 220-240Vac 380-415 Vac

Cat. No. LLSTD030 LLSTD110 LLSTD240 LLSTD415

UNDER VOLTAGE RELEASE

Voltage 110-120 Vac 220-240 Vac 380-440 Vac

Cat. No. LUVRD110 LUVRD240 LUVRD440

The breaker trips if the supply voltage dips below 70% to 35% of the rated voltage. The breaker cannot be switched ON unless there is a supply to the UVR. (NVNC feature). Supplied with external mounting Power pack to operate on AC supplies. Additional transformer is supplied with LUVRD440 & LUVRD110. AUXILIARY SWITCH

Voltage

Current Rating (AC15) 4 4 4 4 Amps Amps Amps Amps

Cat. No.

Config.

250Vac/250Vdc 250Vac/250Vdc 450Vac/250Vdc 450Vac/250Vdc

LLASD1C2 LLASD2C2 LLASD1C4 LLASD2C4

(1NO+1NC) 2(1NO+1NC) (1NO+1NC) 2(1NO+1NC)

Moulded Case Circuit Breaker


D FRAME ACCESSORIES

54

ROTARY HANDLE Cat. No. With Door interlock and 300mm remote shaft LLRRHD30

OTHER ACCESSORIES Dolly Pad locking device Dolly Extension Cat. No. LLDPD160 LLDED160

DIMENSIONS (IN MM)


THREE POLE FOUR POLE WITH SWITCHED NEUTRAL

S.No. 1. 2. 3. 4.

Rating 800A 1000A 1250A 1600A

A 70 70 82 87

B 45 45 60 65

T 6x2 15 15 18

Moulded Case Circuit Breaker


GN FRAME THREE POLE
Current Rating (A) 25 32 40 50 63 80 100 125

DC MCCB
Icu 5kA Cat. No. LDCGNT0025 LDCGNT0032 LDCGNT0040 LDCGNT0050 LDCGNT0063 LDCGNT0080 LDCGNT0100 LDCGNT0125

55

AN FRAME THREE POLE


Current Rating (A) 160 200 250

DC MCCB
Icu 10kA Cat. No. LDCANT0160 LDCANT0200 LDCANT0250

CH FRAME THREE POLE


Current Rating (A) 160 200 250 315 400 500 630 800

DC MCCB
Icu 20kA Cat. No. LDCCHT0160 LDCCHT0200 LDCCHT0250 LDCCHT0315 LDCCHT0400 LDCCHT0500 LDCCHT0630 LDCCHT0800

DN FRAME THREE POLE


Current Rating (A) 1000 1250 1600

DC MCCB
Icu 20kA Cat. No. LDCDNT1000 LDCDNT1250 LDCDNT1600

Moulded Case Circuit Breaker


EARTH FAULT RELAY

56

The Earth Fault Relay is a common accessory for use in conjuction with all MCCB frames. The Earth Fault detection system for use with Loadline MCCBs comprises of a core balance transformer (CT) coupled to an advanced RCD relay. The relay may be used to trip a circuit breaker via a shunt trip or an under voltage release in the event of an Earth Fault. The relay and one of the four available CTs is all that is required for a complete earth fault sensing system suitable for the control of a circuit breaker in a circuit upto 800A fitted with either a shunt trip or an under voltage release. The simple arrangement and a small number of inter-connections necessary ensure that EFR is easily selected and installed. The relay is suitable for 220-240V AC supply with the flexibility of choosing the sensitivity between 300mA to 2A and time delay in the range of 200m. sec - 5 sec. The required sensitivity and time delay should be selected by the DIP switches provided on the facia of the relay. FEATURES No nuisance tripping DIN rail mounting Adjustable time delay Choice of sensitivity from 300mA upto 1A Trip indication LED (Red) ON indication LED (Green) Test push button Reset push button

TECHNICAL INFORMATION
Supply Voltage Changeover contact Sensitivity Time delay (m. sec.) 220/240 V AC, 50/60 Hz 5A AC-15 250V 300mA, 500mA, 1A, NT 200, 500, 1000, 5000

Note: Option to By-Pass EFR in NT position available with dip switch.

Connection Diagram

CORE BALANCE CURRENT TRANSFORMER


Size MCCB Current Rating 25-100A 125-200A 250-400A 500-800A Internal Dimension 60mm 95mm 145mm 300 x 80 mm Shape

1. 2. 3. 4.

Circular Circular Circular Rectangular

Moulded Case Circuit Breaker


EARTH FAULT RELAY

57
MCCB Current Rating (A) 25 - 100 125-200 250-400 500-800 Cat. No. LEFR1100 LEFR2200 LEFR3400 LEFR4800

The earth fault relay is supplied with the CT based on the current rating. To operate the EFR, a shunt trip or an under voltage release is necessary which has to be ordered seperately.

DIMENSIONS (IN MM)

Moulded Case Circuit Breaker


GENERAL PURPOSE ENCLOSURE

58

Enclosures made of special grade CRCA steel are available for housing G, A and C Frame MCCBs upto 800A. They are manufactured with latest technology using CNC Punch and Brake presses to attain highest degree of perfection. The enclosures are painted with latest techniques in powder coating using epoxy polyester and polyester resin based powder paints to ensure smooth, scratch resistant surface coatings. They are suitable for wall mounting & adequate knockouts are provided for cable entry.

Description G Frame SP G Frame TP G Frame FP A Frame SP A Frame TP A Frame FP F Frame TP F Frame FP C Frame TP (400A) C Frame FP (400A) C Frame TP (800A) C Frame FP (800A)

Cat. No. DLE00GSP DLE00GTP DLE00GFP DLE00ASP DLE00ATP DLE00AFP DLE00FTP DLE00FFP DLE00CTP DLE00CFP DLE00CTS DLE00CFS

DIMENSIONS (IN MM)


Description G Frame AA Frame F Frame C Frame upto 400 A C Frame upto 800 A W 260 260 260 440 540 D 108 108 122 122 122 h 360 560 560 960 960 H 370 570 570 975 975 AxB 160x360 160x480 160x480 280x802 380x802

Moulded Case Circuit Breaker


LET THROUGH ENERGY (I2t) CHARACTERISTICS

59

I2t (A2SEC)

PROSPECTIVE CURRENT (A)

I2t (A2SEC)

PROSPECTIVE CURRENT (A)

I2t (A2SEC)

PROSPECTIVE CURRENT (A)

Moulded Case Circuit Breaker


TRIPPING CHARACTERISTICS

60

TIME (SECONDS)

RMS CURRENT (A)

TIME (SECONDS)

RMS CURRENT (A)

Moulded Case Circuit Breaker


TRIPPING CHARACTERISTICS

61

TIME (SECONDS)

TIME (SECONDS)

RMS CURRENT (A)

RMS CURRENT (A)

Moulded Case Circuit Breaker


TRIPPING CHARACTERISTICS
400A
10000

630A

62

1000

CN/CH Frame MCCB 400A-630A

100

TIME (SECONDS)

TIME (SECONDS)

10

0.1

0.01

100

1000

10000

RMS CURRENT (A)

RMS CURRENT (A)

TIME (SECONDS)

RMS CURRENT (A)

Moulded Case Circuit Breaker


AMBIENT TEMPERATURE COMPENSATION CHART (G, AA, C FRAME MCCBs)

63

COMPENSATION fACTOR (% OF CURRENT RATING, i)

AMBIENT TEMPERTURE (0C)

DISCRIMINATION DATA
IS : 13703 HBC Fuse - Upstream Device Product LOADLINE-AAS/AAN
LOADLINE MCCB DOWNSTREAM DEVICE (LOW SET)

Rating KA @ (A) 415V 25 32 40 50 63 80 100 125 160 200 25 25 25 25 25 25 25 25 25 25 50 50 50 50 50 50

80

100

125

160

Current Rating of HBC Fuses 200 250 315 400 4500 5500 4500 5500 4500 5500 4500 5500 4500 5500 4500 5500 4500 5500 4500 5500 1300 5500 1200 1300 1000

500

630

800

1200 1400 1200 1400 350 1400 300 1400 250 1400 300

1800 2400 3200 1800 2400 3200 1800 2400 3200 1800 2400 3200 1800 2400 3200 450 2400 3200 400 650 3200 550 3200 650

8000 12000 14000 23000 8000 12000 14000 23000 8000 12000 14000 23000 8000 12000 14000 23000 8000 12000 14000 23000 8000 12000 14000 23000 8000 12000 14000 23000 8000 12000 14000 23000 8000 12000 14000 23000 8000 12000 14000 23000 8000 12000 14000 23000 2000 12000 14000 23000 2500 14000 23000 3500 23000 5500 6000

LOADLINE CN/CH

250 315 400 500 630 800

LOADLINE DN

The above table gives fault currents in amperes till which level the downstream breakers shall act prior to the upstream fuse.

64

DISCRIMINATION DATA LOADLINE MCCB UPSTREAM DEVICE INSTANTANEOUS TRIP SET AT HIGH LOADLINE AAS/AAN
80 800 800 800 1600 1600 1600 2500 1600 1600 1600 2500 1600 1600 1600 2500 1600 1600 1600 2500 2500 2500 2500 4000 5000 5000 6300 6300 6300 3000 4000 5000 6300 3000 4000 5000 6300 3000 4000 5000 6300 3000 4000 5000 6300 3000 4000 5000 6300 3000 4000 5000 6300 3000 4000 5000 6300 100 125 160 200 ALL 250 315 400 500 630 800 600 800

Product AAM LOADLINE CN/CH LOADLINE DN

RATING

KA@

(A)

415V

25 32 40 50 63

1000 1250 1600

LOADLINE AAS/AAN

63

25

8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 8000 7400 8300 9200 9200 9200 7400 8300 9200 9200 9200 9200 9200 9200 9200 9200 9200

80

25

100

25

125

25

Moulded Case Circuit Breaker

160

25

200

25

LOADLINE AAM

ALL

16

LOADLINE CN/CH

315

50

400

50

500

50

630

50

800

50

LOADLINE MCCB DOWN STREAM DEVICE INSTANTANEOUS TRIP SET AT LOW

LOADLINE DN

800

50

1000

50

1250

50

1600

50

The above table gives fault currents in amperes till which level the downstream breakers shall act prior to the upstream breaker.

Moulded Case Circuit Breaker


SELECTION & APPLICATION
TRANSFORMER PROTECTION Primary side For the protection of transformer with a circuit breaker connected to the primary side (LT primary) the no load inrush current of the transformer must be considered. The peak value of the first current wave often reaches 10-15 times the rated current and may sometimes reach as high as 20-25 times. However, the transient decays very quickly (in a few m.sec.). Thus the MCCB selected should have a magnetic setting which will not be actuated by the momentary inrush current. Secondary side Loadline MCCBs can be used for protection of transformer on the LT side (secondary side) as an outgoing protective device. Ie = The rated current of the transformer is calculated as follows : kVA x 1000 Amps 3 x Ue

65

Ue is the Rated Voltage at the LT side The Breaking capacity of the breaker for protection can be calculated as : Ie Ib = x 10-3 Kiloamperes Z% Where Ib is the rated breaking capacity, Ie the rated current Z% is the percentage impedance of transformer (specified by the manufacturer)

Selection table For Transformer Protection


MCCB Rating in Amperes
Transformer Rating (KVA) 16 25 63 100 160 200 250 315 400 500 630 750 GS 10kA 25 40 100 GN 16kA 25 40 100 GH 25kA 25 40 100 AAS 25kA 25 40 100 160 250 AAN 25kA 25 40 100 160 250 AAN 35kA 25 40 100 160 250 CN 35kA CH 50kA DN 50kA

160 250 315 400 500 630 800

160 250 315 400 500 630 800 1000 1200

GENERATOR SET PROTECTION Loadline MCCBs can be used for the effective protection and control of Diesel Generating set against overload and short circuits. The Current rating of MCCB to be selected is calculated as follows : kVA = 3 Ue X Ie or kVA Ie = 3 x Ue Where, kVA = Rating of the DG Set Ue = Rated Voltage Ie = Rated Current The MCCB rating selected is greater than or equal to the rated current value

Selection Table for DG Set Protection DG Set Rating (KVA) 16 25 63 100 160 200 250 315 400 630 750 MCCB Rating (amperes) 25 40 100 160 250 315 400 500 630 1000 1200

Moulded Case Circuit Breaker


SELECTION & APPLICATION

66

FEEDER / CABLE PROTECTION An estimation of the prospective short-circuit current (psc) in an installation is an important consideration in the selection of the appropriate protective device. The magnitude of the short-circuit current (rms value of the AC component) at a point in the installation will depend upon; (A) Prospective short-circuit current at the origin of the installation. (B) The amount of resistance in the circuit between the origin of the installation and the point at which the short circuit occurs. (C) The type of short-circuit, phase to phase or phase to earth or phase to neutral. It is possible to arrive at a maximum prospective short circuit value at the origin by taking the transformer kVA rating and its impedance and calculating from the expression : SC kA= Transformer rating (kVA)x100 3xSecondary voltage x % impedance of transformer

The values assume a symmetrical fault across the three phases. In a single circuit, for line to neutral faults, take the cable resistance value from the table and double it. The selection of Loadline MCCB for feeder /cable protection depends on the total load to be protected and the prospective short-circuit current (psc) at the point of installation. PSC at A PSC at B resistance A to B (a) PSC at C +resistance A to B +resistance B to C1 approximately 27kA 0.30m = 25kA 0.30m 10.70m 11.00m = 12kA

PSC at D +resistance A to B +resistance B to C +resistance C to D

To calculate the resistance in the LV circuit, obtain details of lengths and sizes of cables between the source of supply and the point under calculation. Using the table provided, determine the sum of cable resistances and then simply read off the estimated fault current from the relevant transformer curve on the graph.

0.30m 10.70m 46.00m (b) 57.00m = 3kA

(a) 2 cables per phase divided by 2 (b) 2 core cable, multiplied by 2 The above calculations have an inbuilt safety margin as they assume a no impedance fault condition which would not be the case in practice.

Typical Installation

1000kVA transformer 10 meters 8sc 300mm2

B
70 meters 4c 120mm
2

20 meters 2c 16mm

Moulded Case Circuit Breaker


SELECTION & APPLICATION
Estimating the Prospective Short Circuit Current

67

40

2000kVA

1500kVA

30
Fault Current (kA)

1250kVA 1000kVA 800kVA

20
500kVA

10

315kVA 200kVA 100kVA

0.1

1.0

10
Total Circuit Resistance (mOhm)

100

Maximum Resistance of Copper Conductors at 20oC (Ohm) Nominal Cross-sectional Area (mm2) 5m 1 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 500 630 90.50 60.50 37.10 23.10 15.40 9.15 5.75 3.64 2.62 1.94 1.34 0.96 0.77 0.62 0.49 0.34 0.30 0.23 0.18 0.14 10m 181.00 121.00 37.10 46.10 30.80 18.30 11.50 7.27 5.24 3.87 2.68 1.93 1.53 1.24 1.00 0.75 0.63 0.47 0.37 0.28 15m 182.00 74.10 69.20 46.20 27.50 17.30 10.90 7.86 5.81 4.02 2.10 2.30 1.86 1.49 1.13 0.90 0.70 0.55 0.42 20m 30m

Cable 40m

Length 50m 60m 70m 80m 90m 100m

111.00 92.20 61.60 36.60 23.00 14.50 10.48 7.74 5.36 3.86 3.06 2.48 1.98 1.51 1.20 0.94 0.73 0.57

148.00 138.00 92.40 54.90 34.50 21.80 15.70 11.60 8.04 5.79 4.59 3.72 2.97 2.26 1.80 1.41 1.10 0.85

123.00 73.20 46.00 29.10 21.00 15.50 10.70 7.72 6.12 4.96 3.96 3.02 2.80 1.88 1.46 1.13

91.50 110.00 57.20 69.00 36.40 43.60 26.20 31.40 19.40 23.20 13.40 16.10 9.65 11.60 7.65 9.18 6.20 7.44 4.96 5.96 3.77 4.52 3.00 3.61 2.35 2.85 1.83 2.20 1.42 1.78

80.50 50.90 36.70 27.10 18.80 13.60 10.70 8.68 6.94 5.28 4.21 3.29 2.56 2.15

103.50 58.20 41.90 31.00 21.40 15.40 12.20 9.92 7.93 6.03 4.81 3.76 2.93 2.51

65.40 47.20 34.80 24.10 17.40 13.80 11.20 8.92 6.79 5.41 4.23 3.29 2.88

72.70 52.40 38.70 26.80 19.30 15.30 12.40 9.91 7.54 6.01 4.70 3.66 3.25

Moulded Case Circuit Breaker


SELECTION & APPLICATION

68

MOTOR CONTROL Loadline MCCBs can be used for motor protection. Selection of MCCBs has to be done taking into consideration the starting inrush current, and the system fault levels. Further the selection is also based on type of starting, i.e. DOL or Star Delta. DOL Starting Care is to be taken to avoid nuisance tripping during starting of Squirrel Cage Motors since the inrush current will be in the order of 600 to 800% of the full load current of the motor. The overload setting is chosen such that it does not trip during starting.

Star-Delta Starting In Star Delta starting of motors, since there is a reduction in the starting current due to reduced voltage, the MCCBs do not have a problem in the overload setting. But the transient currents can go upto 12 times the rated current during change over from star to delta which will cause the instantaneous magnetic release to trip the breaker. So proper selection of magnetic pickup level is important for prevention of nuisance tripping during change over from Star to Delta. It is always recommended to select an MCCB in co-ordination with Contactor and Over Load Relay so as to have the best and optimum benefit of all the devices.

Selection table for Motor Protection


Motor Rating HP 10 12.5 15 20 25 30 40 50 60 75 100 125 150 175 200 220 250 300 350 400 KW 7.5 9 11 15 19 22 30 37 45 55 75 90 112 130 149 160 186 224 261 298 Approx. Full Load Current (A) at 415V 14 17 21 28 35 41 52 69 80 97 125 156 190 225 255 275 320 375 449 505 Direct On Line M C C B R a t i n g / Ty p e AAN AAM CN/CH 25 25 25 32 40 50 80 100 50 63 80 100 125 160 250 315 315 315 400 400 500 630 630 Star/Delta M C C B R a t i n g / Ty p e AAM CN/CH DN 50 63 80 100 125 160 200 250 315 315 400 500 500 630 630 600 600 600 600

AAN 25 25 25 32 40 50 63 80 100 125 160 -

The gures shown are based on following motor starting conditions : Direct online 7 X full load current for 5 seconds. Star/Delta 4 X full load current for 12 seconds.

Moulded Case Circuit Breaker


SELECTION & APPLICATION
CAPACITOR CONTROL When a capacitor circuit is opened, it exhibits characteristics It is therefore necessary to select a circuit breaker with current rating not less than 1.5 - 2.0 times the rated current of the capacitor. DC CONTROL MCCBs though not separately designed for DC applications are suitably modified to be able to operate on DC systems also upto 500V DC / 250V DC. This is achieved by modifying for: i) Current carrying capacity ii) Over current and short circuit protection iii) Short circuit breaking capacity (with L/R time constant limitations) Current Carrying Capacity The continuous current carrying capacity is generally a function limited by the temperature rise of various internal components of MCCBs. distinctly differently from inductor loads due to the effects of residual electric charge in the capacitor. The recovery voltage appears across the contacts immediately after the circuit is opened is equal to the difference between the capacitor residual voltage and supply voltage. Therefore half a cycle after the circuit opens, the voltage between the contacts of the switch rises to twice the supply voltage or higher. In a three phase circuit the recovery voltage appearing between the contacts in the first interrupted phase could rise to as high as 2.5 times the supply voltage. Unless the breaker contacts are fully open for at least cycle after the capacitor current is interrupted, restrike of arc is likely to occur. If the restrike arc is repeated, the voltage could continue to rise to the dielectric breakdown point of the capacitor. Hence, fast interrupting, quick make, quick-break circuit breakers should be used for this type of circuit. When a capacitor circuit is closed a condenser charge q = CU which corresponds to the instantaneous value U of the supply voltage at closing time, must be instantaneously supplied, causing a large inrush current to flow through it. If the capacitor circuit is closed in the voltage phase at which the inrush current is maximum, the maximum value of the inrush current is approximately, C Ip = xU L The maximum time duration during which the maximum current flows is about 0.5 ms. Selection of a MCCB for capacitor circuit duty must therefore consider the effects of higher short circuit and inrush currents. This will affect the choice of instantaneous trip current rating. In practice, an MCCB which satisfies the following equations should be chosen. Ir > 1.5 X Ic Iinst Where Ir Ic Iinst Ip : = = = = The AC rating of MCCBs is expressed as RMS value. The DC rating is Average value. The RMS and average value can be related by a Form Factor which is 1.1. Hence, an AC MCCB can be assigned a 10% higher DC current rating. But in practice the use of DC MCCB ratings are equal to AC ratings and thereby, temperature rise is restricted within limits. Overload Release & Overload Protection The overload release are generally thermal type with a BimetalHeater system. The heating effect which can be expressed by the factor integral I2t varies for AC and DC. The integral (I2t) for AC will be 1.21 times integral (I2avt) for DC, thus an AC MCCB when used in DC circuit will trip slower. For example a 100A AC MCCB when used in DC circuit for 100A will sense a 20% overload only from 133A onwards. To retain the same Overload characteristics as AC, it is important to separately calibrate the MCCBs for DC ratings and overload tripping characteristics need to be suitably modified. Short Circuit Release & Short Circuit Protection The short circuit release is actuated by the peak value of the AC sine wave. Since no such peak exists in DC, DC tripping will be slower. Hence to achieve the same short circuit pick up level in DC, the short circuit release will be calibrated specially. Short Circuit Breaking Capacity In AC the breaking of the short circuit current usually occurs within the first current zero, by the current limiting effect. No such current zero exists in DC. Arc breaking and ultimate quenching of arc depends on the rapid dissipation of the inductive Energy Li2 This energy dissipation is dependent on L/R or time constant of the circuit. The L/R values should be limited to 10-15 milli seconds to achieve satisfactory performance. This is achieved usually by splitting the DC arc voltage over 2 or 3 poles by connecting them in series, depending upon on the DC voltage.

69

I > P 2

Rated current of MCCBs Rated current of capacitor Short circuit pick up setting of the MCCB Maximum capacitor inrush current