LIEBERT NX 3-PHASE UPS: 40-200KVA, 60HZ, 480VAC - SITE PLANNING DATA

The Liebert NX is a true on-line, double conversion, three-phase UPS system that delivers complete, centralized power protection for mission-critical systems.

General Specifications
INPUT Voltage Voltage Range w/o derating Frequency Range Current Distortion Current Limit Power Factor Surge Protection OUTPUT Voltage Voltage Adjustment Range Voltage Regulation Dynamic Regulation Transient Response Time Voltage Distortion Phasing Balance Frequency Regulation Load Power Factor Range Overload ENVIRONMENTAL Operating Temperature Non-Operating Temperature Relative Humidity Operating Altitude Acoustical Noise (full load) 80kVA 120kVA 200kVA STANDARDS Listed to UL 1778 UPS standards, and CSA certified. Meets current requirements for safe high performance UPS operation. 1 <67dB at 80-104F (27-40C) ambient; <61dB below 80F (27C) ambient <69dB at 80-104F (27-40C) ambient; <63dB below 80F (27C) ambient <74dB at 80-104F (27-40C) ambient; <68dB below 80F (27C) ambient UPS: 32 to 104F (0-40C); Battery: 68 to 86F (20-30C) -13 to 158F (-25 to 70C) 0-95% non-condensing Up to 6,500 ft. (2,000m) without derating 480VAC, 60Hz, 3-phase 3-wire plus ground 5% 1% for balanced load 2% for 100% unbalanced load 5% deviation for 100% load step; 1% for loss or return of AC input Recover to 5% of output voltage within 1/2 cycle For linear loads, 1% THD; Less than 4% THD for 100% nonlinear loads without kVA/kW derating 120 0.5 for balanced load; 120 1 for 100% unbalanced load 0.05% single module; 0.25% paralleled modules 0.5 lagging to 1.0 without derating 125% of full load for 10 minutes; 150% for 1 minute, with true sinusoidal waveform 480VAC, 60Hz, 3-phase 3-wire plus ground +15%, -20% 57-63Hz 3% maximum reflected THD at full load 125% of full load input current >0.99 lagging at full load; >0.98 lagging at half load Sustains input surges without damage, per criteria listed in IEC 61000-4-5

Site Planning Data - Single Input, 40-200kVA, 60Hz, 480VAC

Site Planning Data - Single Input, 40-200kVA, 60Hz, 480VAC


UPS Rating Voltage AC Input Rec. OCPD 80 150 150 175 225 300 350 5 Battery AC Output Dimensions WxDxH in. (mm) 25.5 x 39.0 x 78.7 (648 x 990 x 2000) Mechanical Data Weight lb. (kg) 1290 (585) Heat Dissipation Cooling Airflow BTU/hr (kWH) 12,200 (3.6) 15,400 (4.5) 20,600 (6.0) 19,700 (5.8) 41.0 x 39.0 x 78.7 1422 (1040 x 990 x 2000) (645) 64.4 x 39.0 x 78.7 2201 (1636 x 990 x 2000) (1000) 12, 13 12 24,300 (7.1) 28,700 (8.4) 35,900 (10.5) 47,000 (13.8) CFM (m3/hr) 620 (1050) 620 (1050) 620 (1050) 920 (1550) 920 (1550) 920 (1550) 1590 (2700) 1590 (2700) Current (A) Input Output Nom. Nom. Nom. Max. 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 480 48 71 94 94 117 140 186 234 1 60 89 118 118 147 175 233 293 2,3,7,11 Battery Current (A) Nom. Max. Disconnect VDC Discharge Rating Nom. OCPD 480 480 480 480 480 480 480 4 106 157 208 205 258 307 411 511 1,3,7,11 225 225 225 350 350 350 500 600 48 72 96 96 120 144 192 241 1,3,7,11 70 100 125 125 150 200 250 300 5

kVA 40 60 80 80 100 120 160 200

kW 36 54 72 72 90 108 144 180

110 / 125 480

See Notes for Table (below):

Notes for Table


1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Nominal (Nom) current is based on full rated output load at nominal input voltage. Maximum (Max) current is short duration for battery recharge conditions. UPS input cables must be run in separate conduit from output cables. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2. OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) plus 100% of recharge current (non-continuous) per NEC 215. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Wiring requirements: AC Input: 3-phase, 3-wire, plus ground AC Output: 3-phase, 3-wire, plus ground All wiring is to be in accordance with national and local electric codes. Minimum access clearance is 3 ft. (0.9m) front and 8 in. (203mm) above the UPS. Top or bottom cable entry through removable access plates. Punch plate to suit conduit size, then replace. Control wiring and power wiring must be run in separate conduit. Dimensions and weights in table do not include external battery cabinet. 80-200kVA UPS dimensions include UPS wiring section for installation without Liebert NX BDC. Deduct 15.5" from UPS width when a Liebert NX BDC will be used.

Additional Notes
Input and output wiring and breakers for a Liebert NX with Softscale technology should be sized for the maximum scalable capacity. For example, a 40kVA Liebert NX that is scalable to 80kVA should be installed with wiring and breakers rated for an 80kVA configuration. If site configuration includes a backup emergency generator, it is recommended that the engine generator set be properly sized and equipped for a UPS application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS-compatible regulator (generator voltage regulation). Consult generator manufacturer for required generator options and sizing. It is recommended that the transfer switch be equipped with auxiliary contacts for UPS on generator current limit. Consult transfer switch manufacturer for required transfer switch options and sizing. If site configuration requires an external isolated maintenance bypass circuit, it should be noted that utility AC input might not be in phase with the UPS AC output. Consult an Emerson Network Power sales representative or applications engineer. The UPS must be fed from a solidly grounded wye or delta AC source. Not for use with impedance-grounded systems, corner-grounded or high leg delta systems. For these applications, an isolation transformer must be installed between the AC feed and the UPS.

Site Planning Data - Dual Input, 40-200kVA, 60Hz, 480VAC

Site Planning Data - Dual Input, 40-200kVA, 60Hz, 480VAC


UPS Rating Voltage AC Input Bypass Input Current (A) Battery AC Output Dimensions WxDxH in. (mm) 25.5x39.0x78.7 (648x990x2000) Mechanical Data Heat Cooling Weight Dissipation Airflow lb. (kg) BTU/hr (kWH) CFM (m3/hr) 12,200 (3.6) 1290 (585) 15,400 (4.5) 20,600 (6.0) 19,700 (5.8) 41.0x39.0x78.7 1422 (1040x990x2000) (645) 24,300 (7.1) 28,700 (8.4) 620 (1050) 620 (1050) 620 (1050) 920 (1550) 920 (1550) 920 (1550) Current Out(A) put Nom. Nom. Max. 480 480 480 480 480 480 480 480 48 71 94 94 117 140 186 234 1 60 89 118 118 147 175 233 293 2,3,7,11 Battery Current Max. Dis(A) Rec. Nom. Dis- connect Nom. OCPD VDC charge Rating Nom. OCPD 48 72 96 96 120 144 192 241 70 110 125 125 150 200 250 300 480 480 480 480 480 480 480 480 4 106 157 208 205 258 307 411 511 1,3,7,11 225 225 225 350 350 350 500 600 48 72 96 96 120 144 192 241 1,3,7,11 70 110 125 125 150 200 250 300 5

kVA 40 60 80 80 100 120 160 200

kW 36 54 72 72 90 108 144 180

Input Nom. 480 480 480 480 480 480 480 480

Rec. OCPD 80 110/125 150 150 175 225 300 350 5

64.4x39.0x78.7 2201 (1636x990x2000) (1000) 47,000 (13.8) 1590 (2700) 12, 13 12

35,900 (10.5) 1590 (2700)

See Notes for Table (below):

Notes for Table


1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. Nominal (Nom) current is based on full rated output load at nominal input voltage. Maximum (Max) current is short duration for battery recharge conditions. UPS input and bypass cables must be run in separate conduit from output cables. Nominal battery voltage is shown at 2.0 volts/cell per NEC 480-2. OCPD = Overcurrent Protection Device. Recommended AC input and AC output overcurrent protection represents 125% of nominal full load current (continuous) plus 100% of recharge current (non-continuous) per NEC 215. Minimum-sized grounding conductors to be per NEC 250-122. Parity-sized ground conductors are recommended. Wiring requirements: AC Input: 3-phase, 3-wire, plus ground AC Output: 3-phase, 3-wire, plus ground All wiring is to be in accordance with national and local electric codes. Minimum access clearance is 3 ft. (0.9m) front and 8 in. (203mm) above the UPS. Top or bottom cable entry through removable access plates. Punch plate to suit conduit size, then replace. Control wiring and power wiring must be run in separate conduit. Dimensions and weights in table do not include external battery cabinet. 80-200kVA UPS dimensions include UPS wiring section for installation without Liebert NX BDC. Deduct 15.5" from UPS width when a Liebert NX BDC will be used. 3

Additional Notes
Input and output wiring and breakers for a Liebert NX with Softscale technology should be sized for the maximum scalable capacity. For example, a 40kVA Liebert NX that is scalable to 80kVA should be installed with wiring and breakers rated for an 80kVA configuration. If site configuration includes a backup emergency generator, it is recommended that the engine generator set be properly sized and equipped for a UPS application. Generator options would typically include an isochronous governor (generator frequency regulation) and a UPS-compatible regulator (generator voltage regulation). Consult generator manufacturer for required generator options and sizing. It is recommended that the transfer switch be equipped with auxiliary contacts for UPS on generator current limit. Consult transfer switch manufacturer for required transfer switch options and sizing. If site configuration requires an external isolated maintenance bypass circuit, it should be noted that utility AC input might not be in phase with the UPS AC output. Consult an Emerson Network Power sales representative or applications engineer. The UPS must be fed from a solidly grounded wye or delta AC source. Not for use with impedance-grounded systems, corner-grounded or high leg delta systems. For these applications, an isolation transformer must be installed between the AC feed and the UPS.

External Battery Cabinet

External Battery Cabinet


Battery Mfr. Battery Type Dimensions in. (mm) Weight lb. (kg.) Qty. Battery Cabinets 1 HX-205FR 33.5 x 39.0 x 78.7 (850 x 990 x 2000) 2620 (1188) 2 3 4 1 HX-300FR 3502 (1589) 2 3 4 1 Enersys HX-330FR 48.8 x 39.0 x 78.7 (1240 x 990 x 2000) HX-400FR 4302 (1952) 3942 (1788) 2 3 4 1 2 3 4 1 HX-500FR 5502 (2496) 2 3 4 Battery Run Time in Minutes by kVA 40 18 45 72 100 30 72 111 156 36 93 149 207 41 101 159 221 63 142 222 318 60 10 27 46 65 16 45 73 102 21 53 95 135 25 64 103 146 38 90 144 202 80 6 18 32 46 10 31 51 73 14 37 65 96 17 41 73 103 26 65 103 145 80 11 31 52 74 14 37 65 96 17 45 74 104 26 66 103 146 100 7 21 39 55 9 28 49 72 12 33 55 79 19 50 78 110 120 6 18 33 46 8 23 38 54 10 27 45 66 16 38 66 92 160 12 21 33 5 16 27 38 6 19 32 45 10 27 46 66 200 9 16 23 11 20 30 14 23 35 7 20 34 49

2008 Liebert Corporation Technical Support / Service United States All rights reserved throughout the world. Specifications subject to change without notice. 1050 Dearborn Drive 800-222-5877 (Outside U.S. 614-841-6755) Liebert is a registered trademark of Liebert Corporation. All names referred to are trademarks or registered trademarks of their respective owners. upstech@emersonnetworkpower.com P.O. Box 29186