Documente Academic
Documente Profesional
Documente Cultură
Selection guides . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page 2/2 b General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/10 b Osiconcept: Offering Simplicity through Innovation . . . . . . . . . . . . . . . page 2/20
v Flush mountable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/22 v Non flush mountable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/26 v Flat, flush mountable and non flush mountable, forms E, C and D. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/30
Osiprox Optimum
b Flat, flush mountable, forms J and F . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/32 b Flat, flush mountable, forms E, C and D . . . . . . . . . . . . . . . . . . . . . . . . . page 2/34 b Cylindrical, flush mountable, increased range . . . . . . . . . . . . . . . . . . . . page 2/36 b Cylindrical, flush mountable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/38
Osiprox Technology
b Plastic, cylindrical, non flush mountable . . . . . . . . . . . . . . . . . . . . . . . . . page 2/42 b Basic v Plastic, cylindrical, non flush mountable . . . . . . . . . . . . . . . . . . . . . . . page 2/44 v Metal, cylindrical, flush and non flush mountable . . . . . . . . . . . . . . . . page 2/46 b Miniature, cylindrical, flush and non flush mountable . . . . . . . . . . . . . . . page 2/50 b Multivoltage with short-circuit protection . . . . . . . . . . . . . . . . . . . . . . . . page 2/52 b With 2 complementary outputs v Solid-state outputs NO + NC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/54 v Solid-state outputs PNP + NPN, NO/NC programmable . . . . . . . . . . page 2/56
Osiprox Application
b Osiconcept application for detection of passage of objects for machine tools conveyor system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/58 b For rotation monitoring and detection . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/60 b For rotation monitoring and detection with teach mode . . . . . . . . . . . . . page 2/62 b With analogue output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/64 b Fixed sensing distance detection for ferrous and non ferrous materials . . page 2/72 b Selective detection of ferrous materials and non ferrous materials . . . . page 2/76 b For assembly, packaging and light handling v Plastic case, 12 x 26 x 40 mm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/78 v Plastic case, form C, plug-in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/82 v Plastic case, form C, cubic 40, multi-position . . . . . . . . . . . . . . . . . . . page 2/86 v Flat sensor, increased range, 300 mA switching capacity, form D, DIN rail mounting, solid-state output . . . . . . . . . . . . . . . . . page 2/88 b For welding machine applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2/90
2/0
2/1
Selection guide
Proximity sensors
Inductive proximity sensors
Osiprox Universal
Case
18
30
12 18 Increased range
30
Flush mountability Dimensions (w x h x d) in mm Case Sensing distance Sn (mm) Connection Pre-cabled Connector Remote connector Supply c 3-wire z 2-wire Type reference Page(s)
Nickel plated brass 2.5 p p p 4 p p p (1) p (1) 8 p p p (1) p (1) 15 p p p (1) p (1)
XS6 18 B1/B1M
XS6 30 B1/B1M
2/2
Selection guide
Proximity sensors
Inductive proximity sensors
Osiprox Universal
Form C Osiconcept
Form D Osiconcept
XS8 E
2/30
XS8 C
XS8 D
2/3
Selection guide
Proximity sensors
Inductive proximity sensors
Osiprox Optimum
Case
Flush mountability Dimensions (w x h x d) in mm Case Sensing distance Sn (mm) Connection Pre-cabled Connector Remote connector Supply c 3-wire c 2-wire
Type reference
XS7 J
XS7 F
XS7 E
XS7 C
XS7 D
Page
2/32
2/32
2/34
2/34
2/4
Selection guide
Proximity sensors
Inductive proximity sensors
Osiprox Optimum
Standard range 8 12 18 30
XS1 N08pp349p
XS1 N12pp349p
XS1 N18pp349p
XS1 N30pp349p
XS5 08B1p
XS5 12B1p
XS5 18B1p
XS5 30B1p
2/5
Selection guide
Proximity sensors
Inductive proximity sensors
Osiprox Technology
Basic sensors
Miniature sensors
Developed in accordance with the needs expressed by our customers, these sensors provide a complete solution for specific application functions: rotation monitoring, selective detection, analogue control, etc.
Food and beverage Standard machines, clean processing, chemical industry, environment marine sector
Form
Threaded: M8, M12, M18, M30 Plain: 6.5 Plain: 4, 6.5 Threaded: M8, M12, M18, M30 Threaded: M5 Plastic Nickel plated brass or plastic (1) Brass or stainless steel (1) 1.5...10 (1) 4...15 (1) IP 67 p p p p 1...2.5 (1) 2.5 IP 67 p p
2.5... 15 (1) IP 67 or IP 68 p p p p
Non flush mountable in metal sensors Degree of protection Connection Pre-cabled Connector Remote connector c a z
Supply
Type reference
XS4 P
Page(s)
2/6
Selection guide
Proximity sensors
Inductive proximity sensors
Osiprox Technology
Solid-state outputs PNP + NPN, NO/NC programmable Simple machines or installations not having a low voltage Assembly machines, conveyor systems, materials handling, robotics DC supply
Threaded: M12, M18, M30 Nickel plated brass 2...10 4...15 IP 67 or IP 68 (1) p p p p
Plain: 6.5 Threaded: M8, M12, M18, M30 Nickel plated brass or stainless steel or plastic (1) 1.5...10 2.5...15
Threaded: M12, M18, M30 Nickel plated brass or plastic (1) 2...10 4...15
p p p
p p p p
XS1 M XS2 M
2/52 (1) Depending on model.
XS1ppppC410 XS2ppppC410
2/54
2/7
Proximity sensors
Inductive proximity sensors
Osiprox Application
Developed in accordance with the needs expressed by our customers, these sensors provide a complete solution for specific application functions: rotation monitoring, selective detection, analogue control, etc.
Form
Cylindrical
Threaded: M30
Block, dimensions (w x h x d) in mm
26 x 26 x 13 40 x 40 x 15
Case
Metal, cylindrical
PBT block
32 x 15 x 8 26 x 26 x 13 40 x 40 x 15 80 x 80 x 26 PBT block
5...18 (1)
10 10 IP 67
Supply
Connection
p p
p p p
p p p
p p
Type reference
XSA V
XS9 p11R
XS9 ppppA
Page(s)
2/61
2/63
2/69, 2/71
2/8
Selection guide
Proximity sensors
Inductive proximity sensors
Osiprox Application
Detection of metal objects: inductive sensors Factor 1 (Fe/Nfe) sensors Selective Sensors for assembly applications sensors Form G Form C Form cubic 40 Detection of ferrous and non ferrous materials without variation of sensing distance Selective detection of ferrous materials only or non ferrous materials only Applications for assembly machines, conveyor and materials handling systems
Sensors for food and beverage processing applications Cylindrical, Cylindrical, stainless steel plastic Detection of stainless steel and ferrous materials in food/beverage processing and pharmaceutical environments
Threaded: M18
40 x 117 x 41
12 x 40 x 26
40 x 117 x 41 40 x 40 x 40
80 x 80 x 40
Plastic
Metal, Stainless steel, cylindrical, grade 316 L threaded, Teflon coated 15 to 20 20 to 40 15 20 50 42 2, 3, 5,10 (1) 4, 10 (1) IP 67 7...22 (1)
Plastic, PPS
5, 6 or 10 (1) 2 4
7...22 (1)
p p
XS1 M
XS7 C40
XS7 G XS8 G
2/78
XS7 C XS8 C
2/82
XS7 T XS8 T
2/86
XS7 D
XSp M XSL C
2/90
XS2 ppSA
XS2 ppAA
2/72
2/74
2/76
2/88
2/9
General
Recommendations
The sensors detailed in this catalogue are designed for use in standard industrial applications relating to presence detection. These sensors do not incorporate the required redundant electrical circuit enabling their usage in safety applications. For safety applications, please refer to our Safety solutions using Preventa catalogue.
Quality control
Our inductive proximity sensors are subject to special precautions in order to guarantee their reliability in the most arduous industrial environments. b Qualification v The product characteristics stated in this catalogue are subject to a qualification procedure carried out in our laboratories. v In particular, the products are subjected to climatic cycle tests for 3000 hours whilst powered-up to verify their ability to maintain their characteristics over time. b Production v The electrical characteristics and sensing distances at both ambient temperature and extreme temperatures are 100% checked. v Products are randomly selected during the course of production and subjected to monitoring tests relating to all their qualified characteristics. b Customer returns If, in spite of all these precautions, defective products are returned to us, they are subject to systematic analysis and corrective actions are implemented to eliminate the risks of the fault recurring.
Temperature
50 25 0 - 25 0 2 4 6 8 10 12 14 16
80 60 20 0 18
- 25 + 70 C cycle, 95% RH
Temperature C Humidity as %
Relative humidity
C 75 70
% 100
Conformity to standards
All Telemecanique brand inductive proximity sensors conform to and are tested in accordance with the recommendations of standard IEC 60947-5-2.
Vibration resistance
The sensors are tested in accordance with standard IEC 60068-2-6, amplitude 2 mm, f = 1055 Hz, 25 gn at 55 Hz.
Insulation
Class 2 devices i
Electrical insulation conforming to standards IEC 61140 and NF C 20-030 relating to means of protection against electric shock.
2/10
General
Operating principle
b An inductive proximity sensor is solely for the detection of metal objects. It basically comprises an oscillator whose windings constitute the sensing face. An alternating magnetic field is generated in front of these windings.
Composition of an inductive proximity sensor b When a metal object is placed within the magnetic field generated by the sensor, the resulting currents induced form an additional load and the oscillations cease. This causes the output driver to operate and, depending on the sensor type, a normally open (NO) or normally closed (NC) output signal is produced.
Osiconcept
b Osi concept sensors are suitable for all metal environments (flush mountable or non flush mountable) since they ensure a maximum sensing distance, even if there is a metal background. Precise detection of the position of the object can be obtained using the teach mode. For further information, see pages 2/20 and 2/21.
LED indicator
NO output LED No object present NC output
Output LED
All Telemecanique brand inductive proximity sensors incorporate an output state LED indicator. Osiconcept sensors are fitted with a green LED that indicates Power on and also assists the user during setting-up (teach mode).
Object present
Output state
Metal
Object to be detected
Metal
b Side clearance required. Sensing distance greater than that for a standard flush mountable model. b The Osiconcept system eliminates the side clearance requirement. For further information, see pages 2/20 and 2/21.
Metal
Object to be detected
Metal
2 Sn
2/11
General
2
e
e (mm)
h (mm)
Standard sensors
If 2 standard sensors are mounted too close to each other they are likely to lock in the detection state due to interference between their respective oscillating frequencies. To avoid this condition, minimum mounting distances stated for the sensors should be adhered to or, alternatively, sensors with staggered oscillating frequencies should be used.
e
Mounting side by side e u 2 Sn Mounting face to face e u 10 Sn
Maximum tightening torque for the various sensor case materials Brass Brass Stainless steel Plastic
Short case model Form A model XS5 ppB1 XS6 ppB1 XS6 ppB2 XSA Vp 1.6 N.m 1.6 N.m 5 N.m 5 N.m 6 N.m 15 N.m 15 N.m 35 N.m 40 N.m 50 N.m Form A model XS1 pp XS2 pp 2 N.m 9 N.m 30 N.m 50 N.m 100 N.m All models XS4 P pp
2/12
General
Sensing distance
Standard metal target Output ON Su max. Sr max. Sn Sr min. Su min. Output OFF Su max. + H Sr max. + H Sn + H Sr min. + H Su min. + H H = differential travel
Definitions
In order to ensure that customers can make reliable product comparisons and selection, the standard IEC 60947-5-2 defines various sensing distances, such as: b Nominal sensing distance (Sn) The rated operating distance for which the sensor is designed. It does not take into account any variations (manufacturing tolerances, temperature, voltage). b Real sensing distance (Sr) The real sensing distance is measured at the rated voltage (Un) and the rated ambient temperature (Tn). It must be between 90% and 110% of the nominal sensing distance (Sn): 0.9 Sn Sr 1.1 Sn. b Usable sensing distance (Su) The usable sensing distance is measured at the limits of the permissible variations in the ambient temperature (Ta) and the supply voltage (Ub). It must be between 90% and 110% of the real sensing distance: 0.9 Sr Su 1.1 Sr. b Assured sensing distance (Sa). This is the operating zone of the sensor. The assured operating distance is between 0 and 81% of the nominal sensing distance (Sn): 0 Sa 0.9 x 0.9 x Sn
; ;
Sensing face Standard metal target Assured operating distance Sn 0.81 Sn
Sa = Assured detection
The standard IEC 60947-5-2 defines the standard metal target as a square mild steel (Fe 360) plate, 1 mm thick. The side dimension of the plate is either equal to the diameter of the circle engraved on the sensing face of the sensor or 3 times the nominal sensing distance (Sn).
Terminology
PE PR
Differential travel
The differential travel (H), or hysteresis, is the distance between the pick-up point, as the standard metal target moves towards the sensor, and the drop-out point, as it moves away. This hysteresis is essential for the stable operation of the sensor.
Frontal approach Sensing distance
Repeat accuracy
PE = pick-up point, the target is detected PR = drop-out point, the target is no longer detected
The repeat accuracy (R) is the repeatability of the sensing distance between successive operations. Readings are taken over a period of time whilst the sensor is subjected to voltage and temperature variations: 8 hours, 10 to 30 C, Un 5%. It is expressed as a percentage of Sr.
b By using sensitivity adjustment in teach mode, Osiconcept proximity sensors enable the position of an object to be detected as it approaches from the front or side. The teach mode can be used when the object is located in the zone known as the precision adjustment zone. When the object approaches from the front, the detection zone of the object ranges from the stored position down to zero.
Operating zone
2 1
b The operating zone relates to the area in front of the sensing face in which the detection of a metal object is certain. The values stated in the characteristics relating to the various types of sensor are for steel objects of a size equal to the sensing face of the sensor. For objects of a different nature (smaller than the sensing face of the sensor, other metals, etc.), it is necessary to apply a correction coefficient.
2/13
General
2
1,1 0,9
Temperature C
-25
20
50
70
Km 1 0,5
magn.
type type A37 UZ33 AU4G Cu 316 304 Stainless steel Steel Brass Alu. Copper Iron
Lead Bronze
Km 1 0,9 0,8 0,7 0,6 0,5 0,4 0,3 0,2 0,1 0,1 0,3 0,5 0,2 0,4 1,5 1
Calculation examples
2/14
General
Terminology
b Residual current (Ir) v The residual current (Ir) corresponds to the current flowing through the sensor when in the open state. v Characteristic of 2-wire type proximity sensors. b Voltage drop (Ud) v The voltage drop (Ud) corresponds to the voltage drop at the sensors terminals when in the closed state (value measured at nominal current rating of sensor).
XS Ud V XS
1 2
t
b First-up delay v The first-up delay corresponds to the time (t) between the connection of the power supply to the sensor and its fully operational state. 1 Supply voltage U on 2 Sensor operational at state 1 3 Sensor at state 0 b Delays v Response time (Ra): the time delay between the object to be detected entering the sensors operating zone and the subsequent change of output state. This parameter limits the speed and size of the object. v Recovery time (Rr): the time delay between an object to be detected leaving the sensors operating zone and the subsequent change of output state. This parameter limits the interval between successive objects.
Power supply
Outputs
2/15
General
Outputs (continued)
BN BU
BN BU
BN BU
+
BN PNP BK BU BN NPN BK
b v v v b v v v
Specific aspects These sensors comprise 2 wires for the d.c. supply and a 3rd wire for the output signal, PNP type: switching the positive side to the load, NPN type: switching the negative side to the load. Advantages Protection against supply reverse polarity, Protection against overload and short-circuit, No residual current, low voltage drop.
BU
+
BN PNP BK (NO) WH (NC) BU BN NPN BK (NO) WH (NC) BU
b Advantages v Protection against supply reverse polarity (+/-). v Protection against overload and short-circuit.
+
NPN
b Advantages v Protection against supply reverse polarity (+/-). v Protection against overload and short-circuit.
BU (NO), BN (NC)
b These sensors convert the approach of a metal object towards the sensing face into an output current variation which is proportional to the distance between the object and the sensing face. b Two models available: - 0...10 V (0...10 mA) output for 3-wire connection, - 4-20 mA output for 2-wire connection.
2/16
General
Types of case
b Cylindrical case v Fast installation and setting-up. v Pre-cabled and connector versions. v Small size facilitates mounting in locations with restricted access. v Interchangeability, provided by indexed fixing clamp : when assembled, becomes similar to a block type sensor.
2
.
b v v v Flat case Reduced size (sensor volume divided by 8). Fast installation by mounting on clip-on brackets. Precision detection using Osi concept teach mode.
XS7 J
XSp E
Electrical connection
1
Connection methods
1 Pre-cabled: factory fitted moulded cable, good protection against splashing liquids (IP 68). Example: machine tool. 2 Connector: easy installation and maintenance (IP 67). 3 Remote connector: easy installation and maintenance (IP 68 at sensor level and IP 67 at remote connector level).
Wiring advice
2
b Length of cable v No limitation up to 200 m or up to a line capacitance of < 100 nF (characteristics of sensor remain unaffected). v In this case, it is important to take into account the voltage drop on the line. b Separation of control and power circuit wiring v The sensors are immune to electrical interference encountered in normal industrial conditions. v Where extreme conditions of electrical noise could occur (large motors, spot welders, etc.), it is advisable to protect against transients in the normal way: - suppress interference at source, - separate power and control wiring from each other, - smooth the supply, - limit the length of cable. b Connect the sensor with supply switched off.
2/17
General
Setting-up precautions
Connection in series
2-wire type sensors b The following points should be taken into account: v Series wiring is only possible using sensors with wide voltage limits. Based on the assumption that each sensor has the same residual current value, each sensor, in the open state, will share the supply voltage, i.e. U supply . U sensor = n sensors
U sensor and U supply must remain within the sensors voltage limits. v If only one sensor in the circuit is in the open state, it will be supplied at a voltage almost equal to the supply voltage. v When in the closed state, a small voltage drop is present across each sensor. The resultant loss of voltage at the load will be the sum of the individual voltage drops and therefore, the load voltage should be selected accordingly. 3-wire type sensors This connection method is not recommended. b Correct operation of the sensors cannot be assured and, if this method is used, tests should be made before installation. The following points should be taken into account: v Sensor 1 carries the load current in addition to the no-load current consumption values of the other sensors connected in series. For certain models, this connection method is not possible unless a current limiting resistor is used. v When in the closed state, a small voltage drop is present across each sensor. The load should therefore be selected accordingly. v As sensor 1 closes, sensor 2 does not operate until a certain time (t) has elapsed (corresponding to the first-up delay) and likewise for the following sensors in the sequence. v The use of flywheel diodes is recommended when an inductive load is being switched. Sensors and devices in series with an external mechanical contact 2 and 3-wire type sensors b The following points should be taken into account: v When the mechanical contact is open, the sensor is not supplied. v When the contact closes, the sensor does not operate until a certain time (t) has elapsed (corresponding to the first-up delay).
Connection in parallel
2-wire type sensors This connection method is not recommended. b Should one of the sensors be in the closed state, the sensor in parallel will be shorted-out and no longer supplied. As the first sensor passes into the open state, the second sensor will become energised and will be subject to its first-up delay. b This configuration is only permissible where the sensors will be working alternately. b This method of connection can lead to irreversible damage of the units. 3-wire type sensors b No specific restrictions. The use of flywheel diodes is recommended when an inductive load (relay) is being switched.
a.c. supply
b 2-wire type sensors cannot be connected directly to an a.c. supply. v This would result in immediate destruction of the sensor and considerable danger to the user. v An appropriate load (refer to the instruction sheet supplied with the sensor) must always be connected in series with the sensor.
b On power-up, it is necessary to limit (by resistor) the charging current of the capacitive load C. v The voltage drop in the sensor can also be taken into account by subtracting it from the supply voltage for the calculation of R. U (supply) R= I max. (sensor)
2/18
General
Wiring error
Supply fault
False or erratic operation, with or without the presence of a metal object in the detection zone
Operating distance poorly defined for the object to be detected Influence of transient interference on the supply lines
Equipment prone to emitting electromagnetic interference Response time of the sensor too slow for the particular object being detected
Vibration, shock
2/19
General
Operating principle
In proposing the Osiconcept technology, Telemecanique brand offers simplicity through innovation. b With Osiconcept, a single product meets all metal object detection needs. By simply pressing the Teach mode pushbutton, the product automatically takes up an optimum configuration for all detection, flush mountability and environment requirements. b Other advantages of Osiconcept: vIncreased performance: - sensing distance guaranteed and optimized irrespective of the mounting configuration, the object, the environment or the background, - suitable for all metal environments. vSimplified use provided by: - the Osiconcept technology associated with the availability of the flattest, most compact sensors on the market ensuring that the sensor is fully built into the machine, thereby limiting risks of mechanical damage, - mechanical adjustments being eliminated through the use of the teach mode. v Lower costs due to: - adjustment times and complex supports being eliminated, - the elimination of flush mountable and non flush mountable versions which halves the number of references, - much easier and much quicker product selection.
GR
GR
GR
Sn
Precision side approach detection
Sn
Sn
Sn
Sn
Sn
Mounting accessories
Telemecanique brand proposes a complete, inexpensive range of mounting accessories (clamps, plates, brackets, etc.) providing solutions to all setting-up problems. b Fixing kits enable quick installation or replacement of Osi concept sensors. b No adjustment is required. Simple clipping-in enables the sensor to be fixed in position and ready for operation.
2/20
Presentation
Block type
Dimensions (mm) Sensing distance (mm) Sensor type Page XS8 E1A1 Flush mounted use Non flush mounted use 26 x 26 x 13 0...10 0...15 XS8 E1A1 2/30 40 x 40 x 15 0...15 0...25 XS8 C1A1 80 x 80 x 26 0...40 0...60 XS8 D1A1
XS8 C1A1
XS8 D1A1
Cylindrical type
Dimensions (mm) Sensing distance (mm) Sensor type Page Flush mounted use Non flush mounted use 12 0...3.4 0...5 XS6 12B2 2/58 18 0...6 0...9 XS6 18B2 30 0...11 0...18 XS6 30B2
XS6 12B2
XS6 18B2
XS6 30B2
2/21
References
801267
8, threaded M8 x 1
Sensing distance (Sn) mm 2.5 Function Output Connection Reference Weight kg 0.035 0.015 0.035 0.015 0.035 0.015 0.035 0.015
NO
PNP NPN
XS6 ppB1ppL2
Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6
NC
PNP NPN
Function
Output
Connection
Reference
NO
PNP NPN
Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6
NC
PNP NPN
XS6 ppB1ppM12
NO
PNP NPN
Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6
NC
PNP NPN
NO
PNP NPN
Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6 Pre-cabled (L = 2 m) (1) XS6 M12 connector XS6
NC
PNP NPN
Accessories (2)
Weight kg Fixing clamps 8 XSZ B108 0.006 12 XSZ B112 0.006 18 XSZ B118 0.010 30 XSZ B130 0.020 (1) For a 5 m long cable, replace L2 with L5, and for a 10 m long cable, replace L2 with L10. Example: XS6 08B1PAL2 becomes XS6 08B1PAL5 with a 5 m long cable. (2) For further information, see page 2/102. Description Reference
825994
XSZ Bppp
2/22
mm mm mm mm %
XS6 ppB1ppM12 UL, CSA, e M12 02 03.2 06.4 012 115 of real sensing distance (Sr) IP 67
2
IP 68 double insulation i (except 8: IP 67)
Storage temperature range Operating temperature range Materials Case Pre-cabled Vibration resistance Shock resistance Conforming to IEC 60068-2-6 Conforming to IEC 60068-2-27
- 40+ 85 - 25+ 70 Nickel plated brass except XS6 08: stainless steel grade 303 PvR 3 x 0.34 mm2 (except XS6 08: 3 x 0.11 mm 2) 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms LED (yellow), 4 viewing ports at 90 LED (yellow), annular c 1248 with protection against reverse polarity c 1058 200 with overload and short-circuit protection 2 10 2500 1000 500 10 0.2 for 8 and 12, 0.3 for 18, 0.6 for 30 0.2 for 8 and 12, 0.7 for 18, 1.4 for 30
Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching frequency Delays XS6 08B1pppp, XS6 12B1pppp XS6 18B1pppp XS6 30B1pppp First-up Response Recovery
V V mA V mA Hz Hz Hz ms ms ms
Wiring scheme
Connector
M12
4 3
Pre-cabled
BU : Blue BN : Brown BK : Black
PNP
BN/1 PNP BU/3
NPN
+
BK/4 (NO) BK/2 (NC)
+
BK/4 (NO) BK/2 (NC)
Setting-up
Minimum mounting distances (mm)
e e
Side by side e5 e8 e 16 e 30 Face to face e 30 e 50 e 100 e 180
8 12 18 30
Dimensions
XS6
(1)
XS6 8 12 18 30 Pre-cabled (mm) a b 50 42 50 42 60 51 60 51 Connector (mm) a b 61 40 61 42 72.2 51 72.2 51
b a
(1) LED
2/23
References
801277
NO
XS6 ppB1MpL2
NC
2
801278
Pre-cabled (L = 2 m) XS6 12B1MAL2 (2) Connector XS6 12B1MAU20 1/2" - 20UNF Pre-cabled (L = 2 m) XS6 12B1MBL2 (2) Connector XS6 12B1MBU20 1/2" - 20UNF
NO
NC
Pre-cabled (L = 2 m) XS6 18B1MAL2 (2) Connector XS6 18B1MAU20 1/2" - 20UNF Pre-cabled (L = 2 m) XS6 18B1MBL2 (2) Connector XS6 18B1MBU20 1/2" - 20UNF
NO
NC
825994
Pre-cabled (L = 2 m) XS6 30B1MAL2 (2) Connector XS6 30B1MAU20 1/2" - 20UNF Pre-cabled (L = 2 m) XS6 30B1MBL2 (2) Connector XS6 30B1MBU20 1/2" - 20UNF
XSZ B1pp
Accessories (3)
Description Fixing clamps Reference 12 XSZ B112 18 XSZ B118 30 XSZ B130 (1) Available in 8 plastic with double insulation, see page 2/42. (2) For a 5 m long cable, replace L2 with L5, and for a 10 m long cable, replace L2 with L10. Example: XS6 12B1MAL2 becomes XS6 12B1MAL5 with a 5 m long cable. (3) For further information, see page 2/102. Weight kg 0.006 0.010 0.020
2/24
Differential travel Degree of protection Conforming to IEC 60529 Storage temperature range Operating temperature range Materials Case Pre-cabled Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity XS6 12B1Mppp XS6 18B1Mppp, XS6 30B1Mppp
mm mm mm % C C
V V
XS6 ppB1MpU20 UL, CSA, e 1/2" - 20 UNF 03.2 06.4 012 115 of real sensing distance (Sr) IP 67 - 40+ 85 - 25+ 70 Nickel plated brass 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms LED (yellow): 4 viewing ports at 90 a or c 24240 (a 50/60 Hz) a or c 20264
IP 68 double insulation i
Voltage drop, closed state Residual current, open state Maximum switching XS6 12B2ppp,XS6 18B1M ppp frequency XS6 30B1Mppp Delays First-up Response Recovery
mA 5200 (1) mA a 5300 or c 5200 (1) V 5.5 mA 0.8 Hz a 25 or c 1000 Hz a 25 or c 500 ms 20 for XS6 12B1Mppp, 25 for XS6 18B1Mppp and XS6 30B1Mppp ms 0.5 ms 0.2 for XS6 12B1Mppp, 0.5 for XS6 18B1Mppp, 2 for XS6 30B1Mppp (1) It is essential to connect a 0.4 A quick-blow fuse in series with the load
Wiring scheme
Connector
1/2" - 20 UNF
1
Pre-cabled
BU: Blue BN: Brown +/- : 2 t :1 +/- : 3
2-wire a or c
N/O or N/C output
BN/2
/1
BU/3
Setting-up
Minimum mounting distances (mm)
e e
Side by side e8 e 16 e 30 Face to face e 50 e 90 e 180
12 18 30
Dimensions
XS6
(1)
b a
(1) LED Pre-cabled (mm) a b 50 42 60 51 60 51 Connector (mm) a b 61 42 72.2 51 72.2 51
XS6 12 18 30
2/25
References
Function NO
Output PNP
Connection
Reference
Pre-cabled (L = 2 m) XS6 12B4PAL2 (1) M12 connector XS6 12B4PAM12 Pre-cabled (L = 2 m) XS6 12B4NAL2 (1) M12 connector XS6 12B4NAM12 Pre-cabled (L = 2 m) XS6 12B4PBL2 (1) M12 connector XS6 12B4PBM12 Pre-cabled (L = 2 m) XS6 12B4NBL2 (1) M12 connector XS6 12B4NBM12
2
NC PNP NPN
DF534464
NC
DF52381
PNP
NPN
NPN
825994
NC
PNP
XSZ Bppp
NPN
Accessories (2)
Description Fixing clamps Reference 12 XSZ B112 18 XSZ B118 30 XSZ B130 (1) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS6 12B4PAL2 becomes XS6 12B4PAL5 with a 5 m long cable. (2) For further information, see page 2/102. Weight kg 0.006 0.010 0.020
2/26
Sensor type Product certifications/approvals Connection Connector Pre-cabled Operating zone 12 18 30 Differential travel Degree of protection Conforming to IEC 60529 Storage temperature Operating temperature Materials Case Cable Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching frequency Delays XS6 12B4pppp XS6 18B4pppp XS6 30B4pppp First-up Response Recovery
mm mm mm % C C
XS6 ppB4ppM12 UL, CSA, e M12 05.6 09.6 017.6 1...15 of real sensing distance (Sr) IP 67 - 40+ 85 - 25+ 70 Nickel plated brass 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms
V V mA V mA Hz Hz Hz ms ms ms
Yellow LED: 4 viewing ports at 90 Yellow LED: annular c 1248 with protection against reverse polarity c 1058 y 200 with overload and short-circuit protection y2 y 10 2500 1000 500 y 10 y 0.2 12, y 0.3 18, y 0.6 30 y 0.2 12, y 0.7 18, y 1.4 30
Wiring schemes
Connector
M12
4 3
Pre-cabled
BU: Blue BN: Brown BK: Black
PNP
BN/1 PNP BU/3
NPN
+
BK/4 (NO) BK/2 (NC)
+
BK/4 (NO) BK/2 (NC)
Setting-up
Minimum mounting distances (mm)
3 Sn
e e
Metal Metal
Object to be detected
12 18 30
Dimensions
XS6
(1)
XS6 12 18 30 Pre-cabled (mm) a b 55 41.5 60 43.5 62.5 41 Connector (mm) a b 65.5 41.5 71.5 43.5 74 41 c 5 8 13
b a
(1) LED
2/27
References
822109
XS6 ppB4MpL2 NC
2
30, threaded M30 x 1.5
523381
Function NO
Connection Pre-cabled (L = 2 m) (1) 1/2" - 20UNF connector Pre-cabled (L = 2 m) (1) 1/2" - 20UNF connector
NC XS6 ppB4MpU20
Accessories (2)
825994
Weight kg 0.010
30
XSZ B130
0.020
(1) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS6 18B4MAL2 becomes XS6 18B4MAL5 with a 5 m long cable. (2) For further information, see page 2/102.
2/28
XS6 ppB4MpU20 UL, CSA, e 1/2" - 20UNF 09.6 0...17.6 1...15 of real sensing distance (Sr) IP 67 - 40+ 85 - 25+ 70 Nickel plated brass 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED: 4 viewing ports at 90 a or c 24240 (a 50/60 Hz) a or c 20264 a 5300 or c 5200 (1)
XS6 ppB4MpL2
Length: 2 m
mm mm % C C
Vibration resistance Shock resistance Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity
Voltage drop, closed state Residual current, open state Maximum switching XS6 18B4Mppp frequency XS6 30B4Mppp Delays First-up Response Recovery
V y 5.5 mA y 0.8 Hz a 25 or c 1000 Hz a 25 or c 300 ms y 30 XS6 18B4M ppp and XS6 30B4Mppp ms y 0.5 ms y 0.5 XS6 18B4M ppp, y 2 XS6 30B4Mppp (1) It is essential to connect a 0.4 A quick-blow fuse in series with the load.
Wiring schemes
Connector
1/2" - 20UNF
1
Pre-cabled
BU: Blue BN: Brown AC/DC : 2 t :1 AC/DC : 3
2-wire a or c
NO output
BN/2
/1
BU/3
Setting-up
Minimum mounting distances (mm)
3 Sn
e e
Side by side e u 72 e u 120 Face to face e u 144 e u 264
18 30
Metal
Object to be detected
Dimensions
XS6
(1)
Metal
b a
(1) LED Pre-cabled (mm) a b 60 43.5 62.5 41
XS6 18 30
c 8 13
2/29
References
Flat, flush mountable and non flush mountable, forms E, C and D Two-wire, a.c. or d.c. supply Three-wire, d.c. supply, solid-state output
Flat, form E, 26 x 26 x 13 mm (2)
DF564224 DF564225
Reference
Weight kg 0.075 0.040 0.040 0.075 0.040 0.040 0.075 0.040 0.040 0.075 0.040 0.040 0.070 0.040 0.070 0.040 Weight kg 0.095 0.060 0.060 0.095 0.060 0.060 0.095 0.060 0.060 0.095 0.060 0.060 0.090 0.060 0.090 0.060 Weight kg 0.390 0.340 0.390 0.340 0.390 0.340 0.390 0.340 0.390 0.340 0.390 0.340
Three-wire c with overload and short-circuit protection NO PNP Pre-cabled (L = 2 m) (3) XS8 E1A1PAL2
M8 connector Remote M12 connector Pre-cabled (L = 2 m) (3) M8 connector Remote M12 connector Pre-cabled (L = 2 m) (3) M8 connector Remote M12 connector Pre-cabled (L = 2 m) (3) M8 connector Remote M12 connector XS8 E1A1PAM8 XS8 E1A1PAL01M12 XS8 E1A1NAL2 XS8 E1A1NAM8 XS8 E1A1NAL01M12 XS8 E1A1PBL2 XS8 E1A1PBM8 XS8 E1A1PBL01M12 XS8 E1A1NBL2 XS8 E1A1NBM8 XS8 E1A1NBL01M12
NPN
DF564226
NPN
Three-wire c with overload and short-circuit protection NO PNP Pre-cabled (L = 2 m) (3) XS8 C1A1PAL2
M8 connector Remote M12 connector Pre-cabled (L = 2 m) (3) M8 connector Remote M12 connector Pre-cabled (L = 2 m) (3) M8 connector Remote M12 connector Pre-cabled (L = 2 m) (3) M8 connector Remote M12 connector XS8 C1A1PAM8 XS8 C1A1PAL01M12 XS8 C1A1NAL2 XS8 C1A1NAM8 XS8 C1A1NAL01M12 XS8 C1A1PBL2 XS8 C1A1PBM8 XS8 C1A1PBL01M12 XS8 C1A1NBL2 XS8 C1A1NBM8 XS8 C1A1NBL01M12
XS8 C1A1ppL2
XS8 C1A1ppM8
NPN
NC
DF564229
PNP
NPN
DF564221
Three-wire c with overload and short-circuit protection NO PNP Pre-cabled (L = 2 m) (3) XS8 D1A1PAL2 (5) M12 connector XS8 D1A1PAM12 (5) XS8 D1A1NAL2 (5) NPN Pre-cabled (L = 2 m) (3) M12 connector XS8 D1A1NAM12 (5) XS8 D1A1PBL2 (5) NC PNP Pre-cabled (L = 2 m) (3) M12 connector XS8 D1A1PBM12 (5) XS8 D1A1NBL2 (5) NPN Pre-cabled (L = 2 m) (3) M12 connector XS8 D1A1NBM12 (5) Two-wire a or c unprotected (4) 60 NO Pre-cabled (L = 2 m) (3) XS8 D1A1MAL2 (5) 1/2" - 20 UNF connector XS8 D1A1MAU20 (5) XS8 D1A1MBL2 (5) NC Pre-cabled (L = 2 m) (3) 1/2" - 20 UNF connector XS8 D1A1MBU20 (5)
DF564222
DF564221
(1) For further information on Osiconcept , see page 2/20 (2) For accessories, see page 2/102. (3) For a 5 m long cable, replace L2 with L5, and for a 10 m long cable, replace L2 with L10. (4) It is essential to connect a 0.4 A quick-blow fuse in series with the load. (5) For clipping onto 35 mm omega rail or 80 x 80 x 40 mm format, add DIN to the end of the reference. Example: XS8 D1A1PAL2 DIN. XS8 D1A1ppM12DIN XS8 D1A1ppL2DIN
2/30
Flat, flush mountable and non flush mountable, forms E, C and D Two-wire, a.c. or d.c. supply Three-wire, d.c. supply, solid-state output
Connector
Pre-cabled XS8 E Nominal sensing dist. Sn Fine adjustment zone XS8 C Nominal sensing dist. Sn Fine adjustment zone XS8 D Nominal sensing dist. Sn Fine adjustment zone
Differential travel Degree of protection Conforming to IEC 60529 Storage temperature range Operating temperature range Materials Case Pre-cabled Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Indicator Output state Supply on and teach mode Rated 3-wire supply voltage 2-wire Voltage limits 3-wire (including ripple) 2-wire Current consumption, no-load 3-wire Residual current, open state 2-wire Switching capacity 3-wire 2-wire Voltage drop, closed state 3-wire 2-wire Maximum switching frequency Delays First-up Response Recovery
mm mm mm mm mm mm % C C
V V V V mA mA mA mA V V Hz ms ms ms
XS8 EpppppM8, XS8 EpppppL01M12, XS8 EpppppL2, XS8 CpppppM8, XS8 EpppppL01U20, XS8 CpppppL2, XS8 DpppppM12, XS8 CpppppL01M12, XS8 DpppppL2 XS8 DpppppU20 XS8 CpppppL01U20 UL, CSA, e M8 except 0.15 m flying lead with remote connec. XS8 ppppppL01M12: M12, XS8 pppppp M12: M12 XS8 ppppppL01U20: 1/2" 20UNF XS8 pppppp U20: 1/2" 20UNF Length: 2 m 015 non flush mounted configuration / 010 flush mounted configuration 515 non flush mounted configuration / 510 flush mounted configuration 025 non flush mounted configuration / 015 flush mounted configuration 825 non flush mounted configuration / 815 flush mounted configuration 060 non flush mounted configuration / 040 flush mounted configuration 2060 non flush mounted configuration / 2040 flush mounted configuration 115 of real sensing distance (Sr) IP 67 double insulation i (except for M8 connector: IP 67) IP 68 i - 40.+ 85 - 25.+ 70 PBT PvR 3 x 0.34 mm2 c and PvR 2 x 0.34 mm2 z 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED Green LED 1224 with protection against reverse polarity a or c 24240 (a 50/60 Hz) 1036 a or c 20264 y 10 y 1.5 y 100 XS8 E, y 200 XS8 C and XS8 D, with overload and short-circuit protection 5200 z XS8 E, 5300 a XS8 C and XS8 D, 5200 c XS8 C and XS8 D. y2 y 5.5 2000 XS8 E, 1000 XS8 C, 150 XS8 D y 10 XS8 E , XS8 C and XS8 D (3-wire), y 10 XS8 E and XS8 C, y 15 XS8 D (2-wire) y 0.3 y 0.8 XS8 E and XS8 C, y 6 XS8 D
Wiring scheme
Connector
M8 M12
Pre-cabled
3
1/2" - 20 UNF 1
PNP/M12 or M8
BN/1 PNP BU/3
NPN/M12 or M8
4 1 3
BU: Blue BN: Brown BK: Black See connection on page 9/45.
+
BK/4 (NO) BK/2 (NC)
+
BK/4 (NO) BK/2 (NC)
BN/2
BU/3
Setting-up
Minimum mounting distances (mm)
Side by side eu XS8 E XS8 C XS8 D Flush 40 60 200 mounted Non flush 150 125 600 mounted eu XS8 E XS8 C XS8 D Flush 80 120 400 mounted Non flush 300 250 Not recommounted mended eu XS8 E XS8 C XS8 D 10 15 40
Dimensions
XS8 C/D/E
C D
XS8 C/D
B E
XS8 E
(1)
B E F(3) E B A H
(1)
B
Face to face
F(3)
(2)
A (cable) 14 14 23 23
A (connector) 11 11 18 18
B 26 40 80 80
C 13 15 26 40
D 8,8 9,8 16 30
(1) LED (2) Teach mode button (3) For CHC type screws E F G H 20 3,5 6.8 6.6 33 4,5 8.3 13.6 65 5,5 8.5 37.8 65 5.1 22.5 37.8
2/31
References
501549_1
Three-wire c
Sensing distance (Sn) mm 2.5 Function Output Connection Reference Weight kg 0.060 0.040 0.060 0.040 0.060 0.040 0.060 0.040
NO
PNP
NPN
2
521029
NPN
Pre-cabled (L = 2 m) (3) XS7 J1A1PAL2 0.15 m flying lead with XS7 J1A1PAL01M8 M8 connector Pre-cabled (L = 2 m) (3) XS7 J1A1NAL2 0.15 m flying lead with XS7 J1A1NAL01M 8 M8 connector Pre-cabled (L = 2 m) (3) XS7 J1A1PBL2 0.15 m flying lead with XS7 J1A1PBL01M8 M8 connector Pre-cabled (L = 2 m) (3) XS7 J1A1NBL2 0.15 m flying lead with XS7 J1A1NBL01M8 M8 connector Connection Reference
Two-wire c
Sensing distance (Sn) mm 2.5 Function Output Weight kg 0.050 0.035 0.050 0.035
NO
NC XS7 J1A1ppL01M8
Pre-cabled (L = 2 m) (3) XS7 J1A1DAL2 0.15 m flying lead with XS7 J1A1DAL01M8 M8 connector Pre-cabled (L = 2 m) (3) XS7 J1A1DBL2 0.15 m flying lead with XS7 J1A1DBL01M8 M8 connector
NO
PNP
NPN
NC
PNP
XS7 F1A1ppL2
NPN
Pre-cabled (L = 2 m) (3) XS7 F1A1PAL2 0.15 m flying lead with XS7 F1A1PAL01M8 M8 connector Pre-cabled (L = 2 m) (3) XS7 F1A1NAL2 0.15 m flying lead with XS7 F1A1NAL01M8 M8 connector Pre-cabled (L = 2 m) (3) XS7 F1A1PBL2 0.15 m flying lead with XS7 F1A1PBL01M8 M8 connector Pre-cabled (L = 2 m) (3) XS7 F1A1NBL2 0.15 m flying lead with XS7 F1A1NBL01M8 M8 connector Connection Reference
Two-wire c
Sensing distance (Sn) mm 5 Function Output Weight kg 0.055 0.045 0.055 0.045
521030
NO
NC
Pre-cabled (L = 2 m) (3) XS7 0.15 m flying lead with XS7 M8 connector Pre-cabled (L = 2 m) (3) XS7 0.15 m flying lead with XS7 M8 connector
(1) For accessories, see page 2/102. (2) Sensors XS7 J include a basic fixing clamp with screw. (3) For a 5 m long cable, replace L2 with L5, and for a 10 m long cable, replace L2 with L10. For example XS7 J1A1PAL2 becomes XS7 J1A1PAL5 with a 5 m long cable.
XS7 F1A1ppL01M8
2/32
Flat, flush mountable, forms J and F Two-wire, d.c. supply Three-wire, d.c. supply, solid-state output
mm mm % C C
Vibration resistance Shock resistance Output state indication Rated supply voltage Voltage limits (including ripple) Current consumption, no-load 3-wire Residual current, open state 2-wire Switching capacity 3-wire 2-wire Voltage drop, closed state 3-wire 2-wire Maximum switching frequency 3-wire 2-wire Delays First-up
Case Pre-cabled Conforming to IEC 60068-2-6 Conforming to IEC 60068-2-27 V V mA mA mA mA V V kHz kHz ms ms ms ms ms ms
Response Recovery
XS7 JpppppL01M8 XS7 F pppppL01M8 XS7 JppppppL2, XS7 F ppppppL2 e UL, CSA, e 0.15 m flying lead with M8 connector Length: 2 m 02 04 115 of real sensing distance (Sr) IP 67 (XS7 J), IP 68 (XS7 F) - 40.+ 85 - 25.+ 70 PBT PvR 3 x 0.11 mm2 or 2 x 0.11 mm2 (XS7 F : 2 or 3 x 0,34 mm2) 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED c 1224 with protection against reverse polarity c 1036 y 10 y 0.5 100 with overload and short-circuit protection 1.5...100 with overload and short-circuit protection y2 y4 2 4 for XS7 J, 5 for XS7 F Three-wire: 5 Two-wire: 10 XS7 J, 5 XS7 F Three-wire: 0.1 Two-wire: 0.5 XS7 J, 5 XS7 F Three-wire: 0.1 Two-wire: 1 XS7 J, 5 XS7 F
Wiring scheme
Connector
M8
4 1 3
Pre-cabled
BU: Blue BN: Brown BK: Black
PNP, NO or NC
BN/1 PNP BU/3 BK/4
NPN, NO or NC
BN/1 NPN BK/4 BU/3
2-wire, NO
BN/3 NO BU/4
+/-/+
2-wire, N/C
BN/1 NC BU/4
Setting-up
Minimum mounting distances (mm)
e e e
XS7 J XS7 F
Side by side e1 e1
Face to face e6 e 12
Dimensions
XS7 F
8 15 9
XS7 J
(1)
8 8 4
(1)
32
16 3,5
(1) LED (2) For CHC type screws
3,5 (2)
22
2/33
References
DF564230
DF564232
NPN
DF564231
PNP
Two-wire c
10 NO Pre-cabled (L = 2 m) (4) XS7 E1A1DAL2 M8 connector XS7 E1A1DAM8 Remote M12 connector XS7 E1A1DAL01M12 NO Remote M12 connector XS7 E1A1CAL01M12 terminals 1 and 4 (2) Remote M12 connector (3) XS7 E1A1CAL08M12 NC Pre-cabled (L = 2 m) (4) XS7 E1A1DBL2 M8 connector XS7 E1A1DBM8 Remote M12 connector XS7 E1A1DBL01M12
15
NO
PNP
NPN
NC
PNP
NPN
Pre-cabled (L = 2 m) (4) M8 connector Remote M12 connector Pre-cabled (L = 2 m) (4) M8 connector Remote M12 connector Pre-cabled (L = 2 m) (4) M8 connector Remote M12 connector Pre-cabled (L = 2 m) (4) M8 connector Remote M12 connector
XS7 C1A1PAL2 XS7 C1A1PAM8 XS7 C1A1PAL01M12 XS7 C1A1NAL2 XS7 C1A1NAM8 XS7 C1A1NAL01M12 XS7 C1A1PBL2 XS7 C1A1PBM8 XS7 C1A1PBL01M12 XS7 C1A1NBL2 XS7 C1A1NBM8 XS7 C1A1NBL01M12
0.095 0.060 0.060 0.095 0.060 0.060 0.095 0.060 0.060 0.095 0.060 0.060 0.090 0.060 0.060 0.060 0.090 0.090 0.060 0.060
DF564235
Two-wire c
15 NO Pre-cabled (L = 2 m) (4) XS7 C1A1DAL2 M8 connector XS7 C1A1DAM8 Remote M12 connector XS7 C1A1DAL01M12 NO Remote M12 connector XS7 C1A1CAL01M12 terminals 1 and 4 (2) Remote M12 connector (3) XS7 C1A1CAL08M12 NC Pre-cabled (L = 2 m) (4) XS7 C1A1DBL2 M8 connector XS7 C1A1DBM8 Remote M12 connector XS7 C1A1DBL01M12
Three-wire c
40 NO PNP NPN NC PNP NPN Pre-cabled (L = 2 m) (4) M12 connector Pre-cabled (L = 2 m) (4) M12 connector Pre-cabled (L = 2 m) (4) M12 connector Pre-cabled (L = 2 m) (4) M12 connector XS7 D1A1PAL2 (5) XS7 D1A1PAM12 (5) XS7 D1A1NAL2 (5) XS7 D1A1NAM12 (5) XS7 D1A1PBL2 (5) XS7 D1A1PBM12 (5) XS7 D1A1NBL2 (5) XS7 D1A1NBM12 (5) 0,340 0,290 0,340 0,290 0,340 0,290 0,340 0,290
Two-wire c
40 XS7 D1A1ppM12DIN XS7 D1A1ppL2DIN (1) For accessories, see page 2/102. (2) The NO output is connected to terminals 1 and 4 of the M12 connector. (3) 0.8 m flying lead with remote connector. Pre-cabled (L = 2 m) (4) XS7 D1A1DAL2 (5) 0,340 M12 connector XS7 D1A1DAM12 (5) 0,290 NO terminals 1 and 4 (2) M12 connector XS7 D1A1CAM12 (5) 0,290 NC Pre-cabled (L = 2 m) (4) XS7 D1A1DBL2 (5) 0,340 M12 connector XS7 D1A1DBM12 (5) 0,290 (4) For a 5 m long cable, replace L2 with L5, and for a 10 m long cable, replace L2 with L10. Example: XS7 J1A1PAL2 becomes XS7 J1A1PAL5 with a 5 m long cable. (5) For clipping onto 35 mm omega rail or 80 x 80 x 40 mm format, add DIN to the end of the reference. Example: XS7 D1A1PAL2 becomes XS7 D1A1PAL2DIN. NO
2/34
Flat, flush mountable, forms E, C and D Two-wire, d.c. supply Three-wire, d.c. supply, solid-state output
Connector Pre-cabled XS7 E XS7 C XS7 D Conforming to IEC 60529 C C Case Pre-cabled Conforming to IEC 60068-2-6 Conforming to IEC 60068-2-27 V V mA mA mA mA V V kHz Hz ms ms ms ms ms ms
Operating zone
Differential travel Degree of protection Storage temperature range Operating temperature range Materials
mm mm mm %
Vibration resistance Shock resistance Output state indication Rated supply voltage Voltage limits (including ripple) Current consumption, no-load 3-wire Residual current, open state 2-wire Switching capacity 3-wire 2-wire Voltage drop, closed state 3-wire 2-wire Maximum switching frequency XS7 E, XS7 C XS7 D Delays First-up Response Recovery
XS7 EpppppM8, XS7 EpppppL01M12, XS7 CpppppM8, XS7 CpppppL01M12 XS7 DpppppM12 UL, CSA, e M8 except 0.15 m flying lead with remote connec., M12 on XS7 DpppppM12 M12 for XS7 pppppL01M12 08 012 032 115 of real sensing distance (Sr) IP 67 double insulation i (except for M8 connector: IP 67) - 40.+ 85 - 25.+ 70 PBT PvR 3 x 0.34 mm2 or 2 x 0.34 mm 2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED 1224 with protection against reverse polarity 1036 y 10 y 0.5 y 100 with overload and short-circuit protection 1.5...100 with overload and short-circuit protection y2 y4 1 100 10 for XS7 E and XS7 C, 30 for XS7 D 5 for XS7 E and XS7 D, 10 for XS7 D 2 for XS7 E and XS7 C, 5 for XS7 D 0.3 for XS7 E and XS7 D, 10 for XS7 D 6 for XS7 E, 5 XS7 C, 35 for XS7 D 0.7 for XS7 E and XS7 D, 10 for XS7 D
2
IP 68 i
Wiring scheme
Connector
M12
4 3 1 1 2
Pre-cabled
4 3
PNP/M12 or M8
BN/1 PNP BU/3
2-wire, NO / M12 or M8
2-wire, NC / M12 or M8
BN/1 NC
M8
+
BK/4 (NO) BK/2 (NC) NO
BN/3
+/-/+
BU/4
NPN/M12 or M8
BN/1 NPN BU/3
+
BK/4 (NO) BK/2 (NC) NO
BN/1
+/-/+
For M8 connector, NO and NC output on terminal 4.
BU/4
Setting-up
Minimum mounting distances (mm)
Side by side eu XS7 E 4 XS7 C XS7 D 5 40
Dimensions
XS7 C/D/E
C D
XS7 C/D
B E
XS7 E
(1) (1)
B
Face to face
eu
XS7 E 72
E B E B
F (2)
eu
XS7 E 30
F (2)
A (cable) 14 14 23 23 A (connector) 11 11 18 18 B 26 40 80 80
(1) LED (2) For CHC type screws C 13 15 26 40 D 8,8 9,8 16 30 E 20 33 65 65 F 3.5 4.5 5.5 5.1
2/35
References
Function
Output Connection
Reference
Weight kg
6 plain
801120
2.5
NO
PNP
NPN
2
XS1 L06pA349
NC
PNP NPN
Pre-cabled (L = M8 connector M12 connector Pre-cabled (L = M8 connector M12 connector Pre-cabled (L = M8 connector Pre-cabled (L = M8 connector
2 m) (1) XS1 L06PA349 XS1 L06PA349S XS1 L06PA349D 2 m) (1) XS1 L06NA349 XS1 L06NA349S XS1 L06NA349D 2 m) (1) XS1 L06PB349 XS1 L06PB349S 2 m) (1) XS1 L06NB349 XS1 L06NB349S
0.025 0.010 0.015 0.025 0.010 0.015 0.025 0.010 0.025 0.010
8, threaded M8 x 1
2.5
801231
NO
PNP
NPN
NC XS1 Npppp349
PNP
NPN
Pre-cabled (L = M8 connector M12 connector Pre-cabled (L = M8 connector M12 connector Pre-cabled (L = M8 connector M12 connector Pre-cabled (L = M8 connector M12 connector
2 m) (1) XS1 N08PA349 XS1 N08PA349S XS1 N08PA349D 2 m) (1) XS1 N08NA349 XS1 N08NA349S XS1 N08NA349D 2 m) (1) XS1 N08PB349 XS1 N08PB349S XS1 N08PB349D 2 m) (1) XS1 N08NB349 XS1 N08NB349S XS1 N08NB349D
0.035 0.015 0.020 0.035 0.015 0.020 0.035 0.015 0.020 0.035 0.015 0.020
PNP NPN
Pre-cabled (L = M12 connector Pre-cabled (L = M12 connector Pre-cabled (L = M12 connector Pre-cabled (L = M12 connector
2 m) (1) XS1 XS1 2 m) (1) XS1 XS1 2 m) (1) XS1 XS1 2 m) (1) XS1 XS1
801232
Accessories
8 12 18 30 (1) For further information, see page 2/102. Description mm Fixing clamps Reference XSZ B108 XSZ B112 XSZ B118 XSZ B130 Weight kg 0.006 0.006 0.010 0.020
XSZ B1pp
2/36
mm mm mm mm %
XS1 ppppp349D XS1 ppppp349S UL, CSA, e M12 connector M8 connector 02 03.2 08 016 1...15 of real sensing distance (Sr) IP 67 - 40+ 85 - 25+ 50 Nickel plated brass 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED, 4 viewing ports at 90 c 1224 with protection against reverse polarity c 1036 y 200 with overload and short-circuit protection y2 y 10 2500 1000 500 y5 y 0.2 for 8 and 12, y 0.3 for 18, y 0.6 for 30 y 0.2 for 8 and 12, y 0.7 for 18, y 1.4 for 30
Vibration resistance Shock resistance Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching frequency
Delays
Wiring schemes
Connector
M8
4 1 3 1 2
Pre-cabled
M12
4 3
PNP 3-wire
BN/1 PNP BU/3
NPN 3-wire
+
BK/4 (NO) BK/2 (NC)
+
BK/4 (NO) BK/2 (NC)
Setting-up
Minimum mounting distances (mm)
Sensor 6.5 8 12 18 30 Side by side eu5 eu5 eu8 e u 20 e u 40 Face to face e e e e e u 30 u 30 u 48 u 96 u 240 Facing a metal object e u 7.5 e u 7.5 e e u 12 e u 30 e u 60 Mounted in a metal support d u 10 h u 1.6 d d u 10 h u 1.6 d u 14 h u 2.4 d u 28 h u 3.6 d u 50 h u 6
h
Dimensions
Flush mountable in metal
Sensor 6.5 8 12 18 30 Pre-cabled a b 33 30 33 25 33 25 36.5 28 40.6 32 M8 connector a b 42 34 42 26 M12 connector a 45 45 48 48.6 52.7 b 24 23 29 28 32
b a
2/37
References
801267
8, threaded M8 x 1
Sensing distance (Sn) mm 1.5 XS5 ppB1ppL2 Function Output Connection Reference Weight kg 0.035 0.025 0.035 0.025 0.035 0.025 0.035 0.025
NO
PNP NPN
Pre-cabled (L = 2 m) (1) XS5 M8 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M8 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M8 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M8 connector XS5
NC
PNP NPN
NO
PNP NPN
Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5
XS5 ppB1ppM12
NC
PNP NPN
NO
PNP NPN
Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5
NC
PNP NPN
NO
PNP NPN
Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5 Pre-cabled (L = 2 m) (1) XS5 M12 connector XS5
NC
PNP NPN
Accessories (2)
Weight kg Fixing clamps 8 XSZ B108 0.006 12 XSZ B112 0.006 18 XSZ B118 0.010 30 XSZ B130 0.020 (1) For a 5 m long cable, replace L2 with L5, and for a 10 m long cable, replace L2 with L10. Example: XS5 08B1PAL2 becomes XS5 08B1PAL5 with a 5 m long cable. (2) For further information, see page 2/102. Description Reference
825994
XSZ B1 pp
2/38
Differential travel Degree of protection Conforming to IEC 60529 Storage temperature range Operating temperature range Materials Case Pre-cabled Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching XS5 08B1pppp, XS5 12B1pppp frequency XS5 18B1pppp XS5 30B1pppp Delays First-up Response Recovery
mm mm mm mm % C C
XS5 ppB1ppM8, XS5 ppB1ppM12 UL, CSA, e M8 on 8, M12 on 12, 18 and 30 01.2 01.6 04 08 115 of real sensing distance (Sr) IP 67 - 40+ 85 - 25+ 70 Nickel plated brass
IP 68 i (except 8: IP 67)
25 gn, amplitude 2 mm (f = 10 to 50 Hz) 50 gn, duration 11 ms LED (yellow): 4 viewing ports at 90 LED (yellow): annular c 1224 with protection against reverse polarity c 1036 200 with overload and short-circuit protection 2 10 5 2 1 10 0.1 for XS5 08B1pppp and XS5 12B1pppp, 0.15 for XS5 18B1pppp, 0.3 for XS5 30B1pppp 0.1 for XS5 08B1pppp and XS5 12B1pppp, 0.35 for XS5 18B1pppp, 0.7 for XS5 30B1pppp
Wiring scheme
Connector
M8
4 1 3 1 2
Pre-cabled
3
PNP
BN/1 PNP BU/3
NPN
M12
4
+
BK/4 (NO) BK/2 (NC)
+
BK/4 (NO) BK/2 (NC)
Setting-up
Minimum mounting distances (mm)
e e
Side by side e3 e4 e 10 e 20 Face to face e 18 e 24 e 60 e 120
8 12 18 30
Dimensions
XS5
(1)
XS5 8 12 18 30 Pre-cabled a 33 33 36.5 40.6 Connector a 42 48 48.6 52.7
b a
(1) LED
b 25 25 28 32
b 26 29 28 32
2/39
References
801267
8, threaded M8 x 1
Sensing distance (Sn) mm 1.5 Function NO Connection Reference Pre-cabled (L = 2 m) XS5 08B1DAL2 (1) M12 connector XS5 08B1DAM12 Weight kg 0.035 0.025 0.025 0.050 0.035 0.025
XS5 ppB1DpL2
NO M12 connector XS5 08B1CAM12 terminals 1 and 4 (2) Remote M12 XS5 08B1CAL08M12 connector (3) NC Pre-cabled (L = 2 m) XS5 08B1DBL2 (1) M12 connector XS5 08B1DBM12
Function NO
Connection
Reference
XS5 ppB1DpM12
NO M12 connector XS5 12B1CAM12 terminals 1 and 4 (2) Remote M12 XS5 12B1CAL08M12 connector (3) NC Pre-cabled (L = 2 m) XS5 12B1DBL2 (1) M12 connector XS5 12B1DBM12
NO M12 connector XS5 18B1CAM12 terminals 1 and 4 (2) Remote M12 XS5 18B1CAL08M12 connector (3) NC Pre-cabled (L = 2 m) XS5 18B1DBL2 (1) M12 connector XS5 18B1DBM12
825994
XSZ B1pp
NO M12 connector XS5 30B1CAM12 terminals 1 and 4 (2) Remote M12 XS5 30B1CAL08M12 connector (3) NC Pre-cabled (L = 2 m) XS5 30B1DBL2 (1) M12 connector XS5 30B1DBM12
Accessories (4)
Description Fixing clamps Reference 8 XSZ B108 12 XSZ B112 18 XSZ B118 30 XSZ B130 (1) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS5 08B1DAL2 becomes XS5 08B1DAL5 with a 5 m long cable. (2) The NO output is connected to terminals 1 and 4 of the M12 connector. (3) 0.8 m flying lead with M12 connector. (4) For further information, see page 2/102. Weight kg 0.006 0.006 0.010 0.020
2/40
XS5 ppB1CAL08M12
XS5 ppB1DpL2
Operating zone
mm mm mm mm %
1...15 of real sensing distance (Sr) IP 67 i IP 68 (except 8: IP 67) - 40+ 85 - 25+ 70 Nickel plated brass (except XS5 08: stainless steel, grade 303) PvR 2 x 0.34 mm2 (except XS5 08: 2 x 0.11 mm2)
Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Residual current, open state Maximum switching XS5 08B1Dppp, XS5 12B1Dppp frequency XS5 18B1Dppp XS5 30B1Dppp Delays First-up Response
V V mA V mA Hz Hz Hz ms ms
25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED: 4 viewing ports at 90 c 1248 c 1058 1.5100 with overload and short-circuit protection 4 0.5 4000 3000 2000 10 0.2 XS5 08B1pppp and XS5 12B1pppp, 0.15 XS5 18B1pppp, 0.3 XS5 30B1pppp 0.2 (except XS5 30B1pppp: 0.3)
Recovery
ms
Wiring schemes
Connector
M12
4 3
Pre-cabled
BU: Blue BN: Brown
XS5 ppB1DBppp
BN/1
BU/4
BU/4
Setting-up
Minimum mounting distances (mm)
e e
Side by side e3 e4 e 10 e 20 Face to face e 18 e 24 e 60 e 120 Facing a metal object e 4.5 e6 e 15 e 30
8 12 18 30
Dimensions
XS5
(1)
8 12 18 30 Pre-cabled (mm) a b 50 42 50 42 52.5 44 50 42 Connector (mm) a b 61 40 61 42 64.6 44 62.2 41
b a
(1) LED
2/41
References
801231
8, threaded M8 x 1
Three-wire c 12-24 V 2.5 NO NC XS4 Ppppp340 XS4 Ppppp370 XS4 Ppppp230 Three-wire c 12-48 V 2.5 NO PNP NPN PNP NPN Pre-cabled (L Pre-cabled (L Pre-cabled (L Pre-cabled (L Pre-cabled (L Pre-cabled (L Pre-cabled (L Pre-cabled (L =2 =2 =2 =2 =2 =2 =2 =2 m) (1) m) (1) m) (1) m) (1) m) (1) m) m) m) (2) (2) (2) (2) XS4 XS4 XS4 XS4 XS4 XS4 XS4 XS4 XS4 XS4 XS4 XS4 P08PA340 P08NA340 P08PB340 P08NB340 P08PA370 P08NA370 P08PB370 P08NB370 P08MA230 P08MA230K P08MB230 P08MB230K 0.025 0.025 0.025 0.025 0.030 0.030 0.030 0.030 0.030 0.020 0.030 0.020
801232
m) (1) (3) XS4 P12PA370 m) (1) (3) XS4 P12NA370 m) (1) (3) XS4 P12PB370 m) (3) XS4 P12NB370 XS4 XS4 XS4 XS4 P12MA230 P12MA230K P12MB230 P12MB230K
m) (1) (3) XS4 P18PA370 m) (1) (3) XS4 P18NA370 m) (1) (3) XS4 P18PB370 m) (3) XS4 P18NB370 XS4 XS4 XS4 XS4 P18MA230 P18MA230K P18MB230 P18MB230K
m) (1) (3) XS4 P30PA370 m) (1) (3) XS4 P30NA370 m) (3) XS4 P30PB370 m) (3) XS4 P30NB370
Pre-cabled (L = 2 m) (1) XS4 P30MA230 1/2"-20UNF connector XS4 P30MA230K NC Pre-cabled (L = 2 m) (1) XS4 P30MB230 1/2"-20UNF connector XS4 P30MB230K (1) For a 5 m long cable, add L1 to the reference and for a 10 m long cable, add L2. Example: XS4 P08PA340 becomes XS4 P08PA340L1 with a 5 m long (2) For an M8 connector, add S to the reference. Example: XS4 P08PA340 becomes XS4 P08PA340S with an M8 connector. (3) For an M12 connector, add D to the reference. Example: XS4 P12PA370 becomes XS4 P12PA370D with an M12 connector.
2/42
Plastic, cylindrical, non flush mountable Two-wire, a.c. or d.c. supply Three-wire, d.c. supply, solid-state output
Operating zone
mm mm mm mm %
Conforming to IEC 60529 C C Case Cable Conforming to IEC 60068-2-6 Conforming to IEC 60068-2-27
Vibration resistance Shock resistance Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity
XS4 Ppppp340p XS4 Ppppp370 p XS4 P ppMp230p UL, CSA, e Length: 2 m M8 on 8 1/2"-20UNF M12 on 12, 18 and 30 02 03.2 06.4 012 1...15 of real sensing distance (Sr) IP 68, double insulation i for pre-cabled version (except 8: IP 67) IP 67 for connector version - 40+ 85 - 25+ 70 PPS PvR 3 x 0.34 mm2 except 6.5 and 8: 3 x 0.11 mm2 PvR 2 x 0.34 mm2 except 8: 2 x 0.11 mm2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED: annular on pre-cabled version Yellow LED: 4 viewing ports at 90 on connector version c 1224 with protection c 1248 with protection against reverse polarity against reverse polarity c 1036 c 1058 y 200 with overload and short-circuit protection
V V mA
Voltage drop, closed state Residual current, open state Current consumption, no-load Maximum switching frequency
Delays
V mA mA Hz Hz Hz ms ms ms
y2 y 10 5000 2000 1000 y 10 y 0.1 for 8 and 12, y 0.15 for 18, y 0.3 for 30 y 0.1 for 8 and 12, y 0.35 for 18, y 0.7 for 30
a or c 24240 (50/60 Hz) a or c 20264 5100 for 8, 5200 for 12, 5200 c and 5300 a for 18 and 30 y 5.5 y 0.6 c 3000, a 25 c 2000, a 25 c 1000, a 25 y 40 y 0.2 y 0.2 for 8, 12 and 18, y 0.4 for 30
Wiring schemes
Connector
M8
4 1 3 1 2
Pre-cabled
M12
4 3
PNP
BN/1 PNP BU/3
NPN
2-wire a or c
+
BK/4 (NO) BK/2 (NC)
+
BK/4 (NO) BK/2 (NC)
BN/2
BU/3
1/2"-20UNF
z: 2 z: 3
Setting-up
Minimum mounting distances (mm)
Side by side 8 12 18 30 e e e e u 10 u 16 u 16 u 60 Face to face e e e e u 30 u 48 u 96 u 180 Facing a metal object e u 7.5 e u 12 e e u 24 e u 45 Mounted in a metal support d u 24 h u 5 d d u 36 h u 8 d u 54 h u16 d u 90 h u 30
h
Dimensions
3-wire c 12-24 V
Pre-cabled (mm) a b 33 26 33 26 33.5 26 40.5 33 Connector (mm) a b 42 26 48 27 48 29 50 34
b a
XS4 P 8 12 18 30
2/43
References
Connection
Reference
Weight kg
8, threaded M8 x 1
Three-wire c 12-24 V, non flush mountable 2.5 NO PNP Pre-cabled (L NPN Pre-cabled (L NC PNP Pre-cabled (L NPN Pre-cabled (L
801231
=2 =2 =2 =2
Three-wire c 12-24 V, non flush mountable 4 NO PNP Pre-cabled (L = 2 M12 connector NPN Pre-cabled (L = 2 M12 connector NC PNP Pre-cabled (L = 2 M12 connector NPN Pre-cabled (L = 2 M12 connector
Accessories (3)
Description
825994
Reference
Fixing clamps
XSZ B1 pp
8 XSZ B108 12 XSZ B112 18 XSZ B118 30 XSZ B130 (1) For a 5 m long cable replace L2 by L5. Example: XS2 08ALPAL2 becomes XS2 08ALPAL5 with a 5 m long cable. (2) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS2 18ALPAL2 becomes XS2 18ALPAL5 with a 5 m long cable. (3) For further information, see page 2/102.
2/44
mm mm mm mm % C C
Vibration resistance Shock resistance Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching frequency
XS2 ppALPpL2 XS2 ppALNpL2 UL, CSA, e Length: 2 m 02 03.2 06.4 012 1...15 of real sensing distance (Sr) IP 67 - 40+ 85 - 25+ 70 PPS PVC 3 x 0.34 mm2 except 8: 3 x 0.11 mm2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms
8 12 18 30 Delays First-up Response Recovery (1) Detection curves, see page 2/106.
Yellow LED, on rear Yellow LED: 4 viewing ports at 90 c 1224 with protection against reverse polarity c 1036 y 100 (except 8: y 50) with overload and short-circuit protection y2 y 10 3000 1000 250 60 y 5 (except 30 y 10) y 0.5 for 8, 12, y 1 for 18, y 2 for 30 y 1 for 8, y 0.5 for 12, y 2 for 18, y 6 for 30
Wiring schemes
Connector
M12
4 3
Pre-cabled
BU: Blue BN: Brown BK: Black
PNP
BN/1 PNP BU/3
NPN
+
BK/4 (NO) BK/2 (NC)
+
BK/4 (NO) BK/2 (NC)
Setting-up
Minimum mounting distances (mm)
d h
e e
Sensors 8 12 18 30 Side by side e > 10 e > 16 e > 16 e > 60 Face to face e > 30 e > 48 e > 96 e > 180
Mounted in a metal support d > 24 h > 5 d > 36 h > 8 d > 54 h > 16 d > 90 h > 30
Dimensions
Non flush mountable in metal
Sensors 8 12 18 30 XS2 08AL XS2 12AL XS2 18AL XS2 30AL Pre-cabled (mm) a 49 49 58.8 58.8 b 40 42 51.5 51.5 Connector (mm) a 61 70.3 70.3 b 42 51.5 51.5
b a
2/45
References
801120
Connection
Reference
Weight kg
6.5, plain
Three-wire c 12-24 V, flush mountable 1.5 NO PNP Pre-cabled (L NPN Pre-cabled (L NC PNP Pre-cabled (L NPN Pre-cabled (L =2 =2 =2 =2 m) (1) m) (1) m) (1) m) (1) XS1 XS1 XS1 XS1 06BLPAL2 06BLNAL2 06BLPBL2 06BLNBL2 0.030 0.030 0.030 0.030
801167
8, threaded M8 x 1
Three-wire c 12-24 V, flush mountable 1.5 NO PNP Pre-cabled (L = 2 M8 connector M12 connector NPN Pre-cabled (L = 2 M8 connector M12 connector NC PNP Pre-cabled (L = 2 M8 connector M12 connector NPN Pre-cabled (L = 2 M8 connector M12 connector Three-wire c 12-24 V, non flush mountable 2.5 NO PNP Pre-cabled (L = 2 M8 connector M12 connector NPN Pre-cabled (L = 2 M8 connector M12 connector NC PNP Pre-cabled (L = 2 M8 connector M12 connector NPN Pre-cabled (L = 2 M8 connector M12 connector m) (1) XS1 XS1 XS1 XS1 XS1 XS1 XS1 XS1 XS1 XS1 XS1 XS1 XS2 XS2 XS2 XS2 XS2 XS2 XS2 XS2 XS2 XS2 XS2 XS2 08BLPAL2 08BLPAM8 08BLPAM12 08BLNAL2 08BLNAM8 08BLNAM12 08BLPBL2 08BLPBM8 08BLPBM12 08BLNBL2 08BLNBM8 08BLNBM12 08BLPAL2 08BLPAM8 08BLPAM12 08BLNAL2 08BLNAM8 08BLNAM12 08BLPBL2 08BLPBM8 08BLPBM12 08BLNBL2 08BLNBM8 08BLNBM12 0.035 0.008 0.015 0.035 0.008 0.015 0.035 0.008 0.015 0.035 0.008 0.015 0.035 0.008 0.015 0.035 0.008 0.015 0.035 0.008 0.015 0.035 0.008 0.015
m) (1)
m) (1)
m) (1)
801220
m) (1)
m) (1)
m) (1)
m) (1)
XS1 12BLFAL2
Three-wire c 12-24 V, non flush mountable 4 NO PNP Pre-cabled (L = 2 m) (2) XS2 12BLPAL2 M12 connector XS2 12BLPAM12 NPN Pre-cabled (L = 2 m) (2) XS2 12BLNAL2 M12 connector XS2 12BLNAM12 NC PNP Pre-cabled (L = 2 m) (2) XS2 12BLPBL2 M12 connector XS2 12BLPBM12 NPN Pre-cabled (L = 2 m) (2) XS2 12BLNBL2 M12 connector XS2 12BLNBM12 (1) For a 5 m long cable replace L2 by L5. Example: XS1 06BLPAL2 becomes XS1 06BLPAL5 with a 5 m long cable. (2) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS1 12BLPAL2 becomes XS1 12BLPAL5 with a 5 m long cable.
801225
2/46
References (continued)
821938
XS1 18BLppM12
821936
XS1 18BLpppL2
822115
XS1 30BLppL2
822116
XS2 30BLppL2
Accessories (2)
825994
XSZ B1 pp
6.5 XSZ B165 8 XSZ B108 12 XSZ B112 18 XSZ B118 30 XSZ B130 (1) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS1 18BLPAL2 becomes XS1 18BLPAL5 with a 5 m long cable. (2) For further information, see page 2/102.
2/47
Characteristics, schemes
Osiprox Technology
Basic, cylindrical, metal, flush and non flush mountable Two-wire, a.c. supply Three-wire, d.c. supply, solid-state output
Characteristics
Sensor type Product certifications Connection XS1 ppBLP pL2 XS1 ppBLN pL2 UL, CSA, e Length 2 m XS1 ppBLPpMp XS2 ppBLPpL2 XS2 ppBLPpMp XS1 ppBLFAL2 XS1 ppBLNpMp XS2 ppBLNpL2 XS2 ppBLNpMp M8 on 8 M12 on 8, 12, 18 and 30 Length 2 m M8 on 8 M12 on 8, 12, 18 and 30 Length 2 m
Pre-cabled Connector
mm mm mm mm mm % C C
Case Cable
01.2 01.2 02 01.6 03.2 04 06.4 08 012 1...15 of real sensing distance (Sr) IP 67 - 40+ 85 - 25+ 70 Nickel plated brass PVC PVC 3 x 0.34 mm2 3 x 0.34 mm2 except 6.5 except 6.5 and 8: and 8: 3 x 0.11 mm2 3 x 0.11 mm2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms
01.6 04 08
Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Residual current, open state Maximum switching frequency
Yellow LED: Yellow LED, Yellow LED: 4 viewing ports on rear 4 viewing ports at 90 at 90 V c 1224 with protection against reverse polarity V c 1036 mA y 100 (except 6.5 and 8: y 50) with overload and short-circuit protection V y2 mA mA Hz Hz Hz Hz ms ms ms y 10 3000 2000 1000 2000 250 200 60 y 5 (except 30 y 10) y 0.5 for 8, 12, y 1 for 18, y 2 for 30 y 1 for 8, y 0.5 for 12, y 2 for 18, y 6 for 30
Yellow LED, on rear a 24240 a 20264 5300 (5200 for 12) (2) y 4.5 (y 7 for 12) 1.5 25 25 25 y 40 y 10 y 15
6.5, 8 12 18 30 Delays First-up Response Recovery (1) Detection curves, see page 2/106. (2) These sensors do not incorporate overload or short-circuit protection and therefore, it is essential to connect a 0.4 A quick-blow fuse in series with the load, see page 2/102.
Wiring schemes
Connector
M8
4 1 3 1 2
Pre-cabled
M12
4 3
PNP
BN/1 PNP BU/3
NPN
2-wire a
+
BK/4 (NO) BK/2 (NC)
+
BK/4 (NO) BK/2 (NC)
BN
BU
2/48
Setting-up, dimensions
Osiprox Technology
Basic, cylindrical, metal, flush and non flush mountable Two-wire, a.c. supply Three-wire, d.c. supply, solid-state output
Setting-up
Minimum mounting distances (mm)
e e
d h
Sensors 6.5 flush mountable 8 flush mountable 8 non flush mountable 12 flush mountable 12 non flush mountable 18 flush mountable 18 non flush mountable 30 flush mountable 30 non flush mountable
Side by side e u3 e u3 e u 10 e u4 e u 16 e u 10 e u 16 e u 20 e u 60
Mounted in a metal support d u 6,5 h u 0 du8 d u 24 d u 12 d u 36 d u 18 d u 54 d u 30 d u 90 hu0 hu5 hu0 hu8 hu0 h u 16 hu0 h u 30
Dimensions
Flush mountable in metal
Sensors Pre-cabled (mm) a 42 42 41.3 51.3 51.3 M8 connector (mm) a b 52.2 41.3 M12 connector (mm) a b 61.4 39 53 39 64 48.5 64 48.5
b a
6.5 8 12 18 30
06 08 12 18 30
8 12 18 30
08 12 18 30
c 4
c 4 5 8 13
2/49
References
4 plain (1)
801308
Function
Output
Connection (2)
Reference
Weight kg
801316
XS1 N05pp310
801315
Function
Output
Connection (2)
Reference
Weight kg
NPN
PNP NPN
801141
NPN
XSp L06pp340D (1) For accessories, see page 2/102. (2) For a 5 m long cable add L1 to the reference, for 10 m long cable add L2 to the reference. Example: XS1 L04PA310 becomes XS1 L04PA310L1 with a 5 m long cable.
2/50
XS1 pppppppp S; XS1 ppppppppD; XS1 ppppppp; XS2 L06pA340 XS2 L06pA340p Product certifications UL, CSA, e M8 on XS1 ppppppppS and Connection Connector M12 on XS1 ppppppppD Pre-cabled Length: 2 m mm 00.8 (brass), 00.6 (stainless steel) Operating zone (1) 4 mm 00.8 (brass), 00.6 (stainless steel) 5 mm 01.2 (stainless steel) 6.5 flush mountable mm 02 (stainless steel) 6.5 non flush mountable IP 67 Degree of protection Conforming to IEC 60529 C - 40+ 85 Storage temperature C - 25+ 70 Operating temperature Nickel plated brass or stainless steel grade 303 Materials Case PvR, 3 x 0.11 mm2 or 4 x 0.08 mm2 Pre-cabled Vibration resistance Conforming to IEC 60068-2-6 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Shock resistance Conforming to IEC 60068-2-27 Yellow LED, 4 viewing ports at 90 Yellow LED, annular Output state indication V c 524 for XS1 L04pppppp and XS1 N05pppppp Rated supply voltage c 1224 for XS p L06 pppppp V c 530 for XS1 L04pppppp and XS1 N05pppppp Voltage limits (including ripple) c 1038 for XS p L06 pppppp mA y 10 Current consumption, no-load mA y 100 with overload and short-circuit protection Switching capacity 3-wire PNP/NPN y 200 for XSp L06 with overload and short-circuit protection V y2 Voltage drop, closed state kHz 5 Maximum switching frequency ms y5 Delays First-up ms y 0.1 Response ms y 0.1 Recovery (1) Detection curves, see page 2/106
Wiring schemes
Connector
M8
4 1 3 1 2
Pre-cabled
3
PNP 3-wire
BN/1 PNP BU/3
NPN 3-wire
M12
4
+
BK/4 (NO) BK/2 (NC)
+
BK/4 (NO) BK/2 (NC)
Setting-up
Minimum mounting distances (mm)
Sensor 4 5 6.5 6.5, XS2 L06pA340p Side by side eu eu eu eu 2 2 3 5 Face to face e e e e u 12 u 12 u 18 u 30 Facing a metal object eu3 eu3 e e u 4.5 e u 7.5
d1 h d2 x
d1 u 4, h u 0 d1 u 5, h u 0 d1 u 3, h u 0 d1 u 10, h u 1.6
d2 u 6.5, x u 1.3
Tightening torque
Stainless steel: 2.2 N.m Brass: 1.6 N.m
Dimensions
Sensor 4 5 6.5 6.5, XS2 L06pA340p Pre-cabled a b 29 29 29 29 33 30 33 27 c 3 M8 connector a b 41 24 41 24 42 34 46 35 c 3 M12 connector a b 45 24 49 25 c 3
b a
2/51
References
Function
Connection
Reference
Weight kg
NC
XS1 Mpppp250
NC
DF532016
XS2 Mpppp250
NC
NO
Pre-cabled (L = 2 m) (1) XS2 M18MA250 1/2"-20UNF connector XS2 M18MA250K Pre-cabled (L = 2 m) (1) XS2 M18MB250 1/2"-20UNF connector XS2 M18MB250K
NC
Flush mountable
10 NO Pre-cabled (L = 2 m) (1) XS1 M30MA250 1/2"-20UNF connector XS1 M30MA250K Pre-cabled (L = 2 m) (1) XS1 M30MB250 1/2"-20UNF connector XS1 M30MB250K 0205 0.145 0205 0.145
801225
NC
XS2 Mpppp250K
NC
Accessories (2)
Weight kg 12 XSZ B112 0.006 18 XSZ B118 0.010 30 XSZ B130 0.020 (1) For a 5 m long cable, add L1 to the reference and for a 10 m long cable, add L2 to the reference. Example: XS1 M18MA250 becomes XS1 M18MA250L1 with a 5 m long cable. (2) For further information, see page 2/102.
825994
Reference
XSZ B1pp
2/52
12 flush mountable 12 non flush mountable 18 flush mountable 18 non flush mountable 30 flush mountable 30 non flush mountable Conforming to IEC 60529
Differential travel Degree of protection Storage temperature Operating temperature Materials Vibration resistance Shock resistance Indicators
mm mm mm mm mm mm % C C
Case Cable Conforming to IEC 60068-2-6 Conforming to IEC 60068-2-27 Output state Supply on V V mA V mA mA Hz 12 Hz 18 Hz 30 flush mountable 30 non flush mountable Hz ms First-up ms Response ms Recovery
XSp MppMp250K XSp MppMp250 UL, CSA, e 1/2"-20UNF connector Pre-cabled, length: 2 m 01.6 03.2 04 06.4 08 012 1...15 of real sensing distance (Sr) IP 67 IP 68, double insulation - 40+ 85 - 25+ 70 Nickel plated brass PvR 2 x 0.34 mm2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Red LED, 4 viewing ports at 90 Red LED Green LED: 4 viewing ports at 90 (only Green LED (only on 18 and 30) on 18 and 30) a 24240 (50/60 Hz) or c 24210 a or c 20264 a 5300 or c 5200 (except 12: a or c 5200) with overload and short-circuit protection y 5.5 y 1.5 a 25 or c 4000 a 25 or c 2000 a 25 or c 2000 a 25 or c 1000 y 70 y 0.2 for 12, y 2 for 18 and 30 y 0.2 for 12, y 4 for 18, y 5 for 30 flush mountable, y 10 for 30 non flush mountable
Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Residual current, open state Maximum switching frequency
Delays
Wiring schemes
1/2"-20UNF connector
1
Pre-cabled
BU: Blue BN: Brown
2-wire a or c
NO or NC output
BN/2
+/- : 2 t :1 +/- : 3
/1
BU/3
Setting-up
Minimum mounting distances (mm)
Sensor 12 flush mountable 12 non flush mountable 18 flush mountable 18 non flush mountable 30 flush mountable 30 non flush mountable Side by side eu4 e u 16 e u 10 e u 16 e u 20 e u 60 Face to face e e e e e e u 24 u 48 u 60 u 96 u 120 u 180 Facing a metal object eu6 e u 12 e e u 15 e u 24 e u 30 e u 45 Mounted in a metal support d u 12 h u 0 d d u 36 h u 8 d u 18 h u 0 d u 54 h u 16 d u 30 h u 0 d u 90 h u 30
h
Dimensions
Flush mountable in metal
Sensor Pre-cabled a b 55 47 60 51 60 51 Connector a 66 72 72 b 48 51 51
b a
12 18 30
2/53
References
801120
6.5 plain
Stainless steel case, flush mountable
1.5 NO + NC PNP NPN Pre-cabled (L = 2 m) (1) XS1 L06PC410 Pre-cabled (L = 2 m) (1) XS1 L06NC410 0.025 0.025
2
801231
8, threaded M8 x 1
XS1 L06pC410
XS1 ppppC410
801233
XS2 ppppC410
801232
DF532015
Accessories (3)
Weight kg 8 XSZ B108 0.006 12 XSZ B112 0.006 18 XSZ B118 0.010 30 XSZ B130 0.020 (1) For a 5 m long cable, add L1 to the reference and for a 10 m long cable, add L2 to the reference. Example: XS1 N12PC410 becomes XS1 N12PC410L1 with a 5 m long cable. (2) For a sensor with a plastic case, non flush mountable, replace 2N by 4P in the reference. Example: XS2 N12PC410 becomes XS4 P12PC410 with a plastic case. (3) For further information, see page 2/102. Description mm Fixing clamps
825994
Reference
XSZ B1pp
2/54
Cylindrical, metal and plastic, flush mountable and non flush mountable Four-wire, d.c. supply, solid-state NO + NC output
6.5 and 8 flush mtble. 8 non flush mountable 12 flush mountable 12 non flush mountable 18 flush mountable 18 non flush mountable 30 flush mountable 30 non flush mountable Conforming to IEC 60529
mm mm mm mm mm mm mm mm %
XSp ppppC410D UL, CSA, e M12 connector 01.2 02 01.6 03.2 04 06.4 08 012 1...15 of real sensing distance (Sr) IP 67
2
IP 68, double insulation (except 6.5 and 8: IP 67)
C C Case
Cable Vibration resistance Shock resistance Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching frequency Conforming to IEC 60068-2-6 Conforming to IEC 60068-2-27 V V mA V mA Hz Hz Hz ms ms ms
- 40+ 85 - 25+ 70 Nickel plated brass for XS1 N and XS2 N Stainless steel, grade 303, for XS1 L06, XS1 M08 and XS2 M08 Plastic, PPS, for XS4 P PvR 4 x 0.34 mm2 except 6.5 and 8: 4 x 0.08 mm2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED, 4 viewing ports at 90 Yellow LED, annular c 1224 with protection against reverse polarity c 1036 y 200 with overload and short-circuit protection y2 y 10 5000 2000 1000 y5 y 0.1 for 8 and 12, y 0.15 for 18, y 0.3 for 30 y 0.1 for 8 and 12, y 0.35 for 18, y 0.7 for 30
Delays
Wiring schemes
M12 connector
4 3
Pre-cabled
BU: Blue BN: Brown BK: Black WH: White
PNP 4-wire
BN/1 PNP BU/3 BK/4 (NO) WH/2 (NC)
NPN 4-wire
+
BK/4 (NO) WH/2 (NC)
Setting-up
Minimum mounting distances (mm)
Sensor 6.5 flush mountable XS1 L06 8 flush mountable XS1 M08 8 non flush mountable XS2 M08 12 flush mountable XS1 N12 12 non flush mtble XS1 N12 or XS4 P12 18 flush mountable XS1 N18 18 non flush mtble XS2 N18 or XS4 P18 30 flush mountable XS1 N30 30 non flush mtble XS2 N30 or XS4 P30 Side by side eu3 eu3 e u 10 eu4 e u 16 e u 10 e u 16 e u 20 e u 60 Face to face e e e e e e e e e u 18 u 18 u 30 u 24 u 48 u 60 u 96 u 120 u 180 Facing a metal object e u 4.5 e u 4.5 e e u 7.5 eu6 e u 12 e u 15 e u 24 e u 30 e u 45 Mounted in a metal support d u 6.5 h u 0 d du8hu0 d u 24 h u 5 d u 12 h u 0 d u 36 h u 8 d u 18 h u 0 d u 54 h u 16 d u 30 h u 0 d u 90 h u 30
h
Dimensions
Flush mountable in metal
Sensor Pre-cabled a b 50 47 50 42 33 25 36.5 28 40.6 32 Connector a b 61 42 48 29 48.6 28 52.7 32
b a
2/55
References
Cylindrical, metal and plastic, flush and non flush mountable Four-wire, d.c. supply, solid-state PNP + NPN NO/NC programmable output
Sensing distance Sn (mm)
822102
Function
Output
Connection
Reference
Weight kg
NO/NC PNP + NPN Pre-cabled (L = 2 m) XS4 P12KP340 programmable (1) M12 connector XS4 P12KP340D
0.075 0.025
NO/NC PNP + NPN Pre-cabled (L = 2 m) XS2 M18KP340 programmable (1) M12 connector XS2 M18KP340D
0.120 0.060
801225
825994
Accessories (2)
Description mm Fixing clamps XSZ B1pp Weight kg 12 XSZ B112 0.006 18 XSZ B118 0.010 30 XSZ B130 0.020 (1) For a 5 m long cable, add L1 to the reference and for a 10 m long cable, add L2 to the reference. Example: XS1 M12KP340 becomes XS1 M12KP340L1 with a 5 m long cable. (2) For further information, see page 2/102. Reference
2/56
Cylindrical, metal and plastic, flush and non flush mountable Four-wire, d.c. supply, solid-state PNP + NPN NO/NC programmable output
12 flush mountable 12 non flush mountable 18 flush mountable 18 non flush mountable 30 flush mountable 30 non flush mountable Conforming to IEC 60529
Differential travel Degree of protection Storage temperature Operating temperature Materials Vibration resistance Shock resistance Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching frequency
mm mm mm mm mm mm % C C
Case Cable Conforming to IEC 60068-2-6 Conforming to IEC 60068-2-27 V V mA V mA Hz 12 Hz 18 Hz 30 flush mountable 30 non flush mountable Hz ms First-up ms Response ms Recovery
XSp MppKP340D XSp MppKP340 UL, CSA, e M12 connector Pre-cabled, length: 2 m 01.6 03.2 04 06.4 08 012 1...15 of real sensing distance (Sr) IP 67 IP 68, double insulation - 40+ 85 - 25+ 70 Nickel plated brass for XS1 M and XS2 M, PPS for XS4 P PvR 4 x 0.34 mm2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED, 4 viewing ports at 90 Yellow LED, annular c 1224 with protection against reverse polarity c 1036 y 200 with overload and short-circuit protection y 2.6 y 10 5000 2000 1000 1000 y5 y 0.1 for 12, y 0.15 for 18, y 0.3 for 30 y 0.1 for 12, y 0.35 for 18, y 0.7 for 30
Delays
Wiring schemes
M12 connector
4 3
Pre-cabled
BU: Blue BN: Brown BK: Black WH: White
PNP + NPN
4-wire programmable, NO or NC output NO NC
BN/1 WH/2 BU/3
+
WH/2
+
BK/4 BN/1
BK/4
Setting-up
Minimum mounting distances (mm)
Sensor 12 flush mountable XS1 M12 12 non flush mountable XS2 M12 and XS4 P12 18 flush mountable XS1 M18 18 non flush mountable XS2 M18 and XS4 P18 30 flush mountable XS1 M30 30 non flush mountable XS2 M30 and XS4 P30 Side by side eu4 e u 16 Face to face e u 24 e u 48 e u 60 e u 96 e u 120 e u 180 Facing a metal object eu6 e u 12 e e u 15 e u 24 e u 30 e u 45 Mounted in a metal support d u 12 h u 0 d d u 36 h u 8
h
e u 10 e u 16 e u 20 e u 60
d u 18 h u 0 d u 54 h u 16 d u 30 h u 0 d u 90 h u 30
Dimensions
Flush mountable in metal
Sensor Pre-cabled a b 50 42 60 51 60 51 Connector a b 61 42 72 51 72 51
b a
12 12 18 18 30 30
2/57
References
NO
PNP NPN
0.15 m flying lead with XS6 12B2PAL01M12 M12 connector 0.15 m flying lead with XS6 12B2NAL01M12 M12 connector 0.15 m flying lead with XS6 12B2PBL01M12 M12 connector 0.15 m flying lead with XS6 12B2NBL01M12 M12 connector
2
XS6 ppB2ppL01M12
NC
PNP NPN
0.100 0.100
NO
PNP NPN
0.15 m flying lead with XS6 18B2PAL01M12 M12 connector 0.15 m flying lead with XS6 18B2NAL01M12 M12 connector 0.15 m flying lead with XS6 18B2PBL01M12 M12 connector 0.15 m flying lead with XS6 18B2NBL01M12 M12 connector
NC
520031
PNP NPN
0.140 0.140
NO
PNP NPN
0.15 m flying lead with XS6 30B2PAL01M12 M12 connector 0.15 m flying lead with XS6 30B2NAL01M12 M12 connector 0.15 m flying lead with XS6 30B2PBL01M12 M12 connector 0.15 m flying lead with XS6 30B2NBL01M12 M12 connector
XSZ BPM12
NC
PNP NPN
0.220 0.220
825994
Accessories (2)
Description Remote control fixing clamp XSZ Bppp Sensor fixing clamps 12 18 30 Reference XSZ BPM12 XSZ B112 XSZ B118 XSZ B130 Weight kg 0.015 0.006 0.010 0.020
(1) For further information on Osiconcept , see page 2/20. (2) For further information, see page 2/102.
2/58
18
30
Nominal sensing distance Sn Fine adjustment zone Nominal sensing distance Sn Fine adjustment zone Nominal sensing distance Sn Fine adjustment zone
mm mm mm mm mm mm %
XS6 ppB2ppL01M12 UL, CSA, e 0.15 m flying lead with M12 connector 05 non flush mounted configuration / 03.4 flush mounted configuration 1.75 non flush mounted configuration / 1.73.4 flush mounted configuration 09 non flush mounted configuration / 06 flush mounted configuration 39 non flush mounted configuration / 36 flush mounted configuration 018 non flush mounted configuration / 011 flush mounted configuration
Differential travel Degree of protection Conforming to IEC 60529 Storage temperature range Operating temperature range Materials Case Remote control Pre-cabled Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Indicator Output state Supply on and teach mode Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching frequency Delays First-up Response Recovery
618 non flush mounted configuration / 611 flush mounted configuration 115 of real sensing distance (Sr) IP 67 i C - 40+ 85 C - 25+ 70 Nickel plated brass PBT PvR - 4.2 mm 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED Green LED V c 1224 with protection against reverse polarity V c 1036 mA 100 with overload and short-circuit protection V 2 mA 10 Hz 1000 ms 10 ms 0.3 ms 0.7 (1) For further information on Osiconcept , see page 2/20.
Wiring scheme
Connector
M12
4 3
PNP
1
PNP
NPN
4(NO) 2(NC)
1
NPN
+
4(NO) 2(NC)
Setting-up
Minimum mounting distances (mm)
e e
12 18 30
e 3.4 e6 e 11
Dimensions
XS6
(2) (1)
20
M12
62
b a
c
(1)LED (2)Teach mode button
12 18 30
c 5 8 13
2/59
Sensors for rotation monitoring, slip detection, shaft overload detection Cylindrical type
Functions
These self-contained rotation speed monitoring sensors have the special feature of incorporating, in the same case, the pulse sensing and processing electronics as well as the output switching amplifier that are required to establish an integrated rotation monitoring device. The unit provides an economical solution for detecting slip, belt breakage, drive shaft shear and overloading, etc., in the following applications: conveyor belts, bucket elevators, Archemedian screws, grinders, crushers, pumps, centrifugal driers, mixers, etc.
2
822145
Operating principle
The output signal of this type of sensor is processed by an impulse comparator incorporated in the sensor. The impulse frequency Fc generated by the moving part to be monitored is compared to the frequency Fr preset on the sensor. The output switching circuit of the sensor is in the closed state for Fc > Fr and the open state for Fc < Fr.
(2)
(1)
Sensors XSA-V are particularly suitable for the detection of underspeed: when the speed of the moving part Fc falls below a preset threshold Fr, this causes the output circuit of the sensor to switch off. Note: following power-up, the operational status of the sensor is subject to a delay of 9 seconds in order for the moving part being monitored to run-up to its nominal speed. During this time, the output of the sensor remains in the closed state.
a (3)
b Adjustment of sensors frequency threshold: using potentiometer, 15 turns approximately. b To increase the frequency threshold: turn the adjustment screw clockwise (+). b To decrease the frequency threshold: turn the adjustment screw anti-clockwise (). Potentiometer LED Metal target Diameter of sensor a M30 46 mm
b 30 mm
c 60 mm
Potentiometer adjustment curves (for XSA V1p801 , 2-wire a or c sensors) Low speed version (6150 impulses/minute) High speed version (1203000 impulses/minute) Number of turns Number of turns
15 12 9 6 3 0 0,1 6 10 1 60 1 2,5 Hertz 150 Imp/min 0,4 Revs/s 15 12 9 6 3 0 2 120 0,5 10 600 0,1 50 Hertz 3000 Imp/min 0,02 Revs/s
Setting-up
Minimum mounting distances (mm) Side by side Face to face
e e
e 20 Facing a metal object e 120 Mounted in a metal support
d h
d 30, h 0
2/60
Sensors for rotation monitoring, slip detection, shaft overload detection Cylindrical type
b a
Lengths (mm): a = Overall b = Threaded section a = 81 b = 57 = M30 DC 10 mm 1203000 impulses/min AC/DC 10 mm 6150 impulses/min AC/DC 10 mm 1203000 impulses/min
References
3-wire c 2-wire Weight (kg) PNP / NC c or a / NC XSA V11373 0.300 XSA V12373 XSA V11801 XSA V12801
Characteristics
Connection Degree of protection conforming to IEC 60529 Operating zone Repeat accuracy Differential travel Operating temperature Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Residual current, open state Current consumption, no-load Maximum switching frequency Run-up delay following power-up Pre-cabled, 3 x 0.34 mm, length 2 m (1) IP 67 08 mm 3% of Sr 315% of Fr - 25+ 70 C Red LED c 1248 V with protection against reverse polarity c 1058 V 6 200 mA with overload and short-circuit protection 1.8 V Pre-cabled, 2 x 0.34 mm, length 2 m (1)
a 5350 mA or c 5200 mA (2) 5.7 V 1.5 mA 15 mA 000 impulses/min (for XSA V11ppp); 48 000 impulses/min (for XSA V12ppp)
Wiring schemes
3-wire c XSA V1p373 2-wire a or c XSA V1p801
+
BN PNP BU BK
BN
BU
(1) For a 5 m long cable add L05 to the reference, for a 10 m long cable add L10 to the reference. Example: XSA V11373 becomes XSA V11373L05 with a 5 m long cable. (2) These sensors do not incorporate overload or short-circuit protection and therefore, it is essential to connect a 0.4 A quickblow fuse in series with the load, see page 2/102. (3) For a sensor without a run-up delay following power-up, replace XSA V1 in the reference by XSA V0. Example: XSA V11801 becomes XSA V01801 without a run-up delay. For a reduced run-up delay of 3 s, replace XSA V1 in the reference by XSA V3.
2/61
b These inductive proximity sensors are designed for monitoring rotational speed or the speed of the flow of objects to be monitored or protected. They operate on the principle of comparing a speed threshold preset by the operator against the instantaneous measurement of the speed of the moving object to be protected. b They provide a simple, economical solution to the problems of detecting slip, belt breakage, coupling and overloading, etc. b They are commonly used in grinder/crusher, mixer, pump, centrifugal driver, conveyor belt, bucket elevator, Archimedian screw, etc. type applications.
Setting-up and positioning the sensor b In the positioning phase, the XS9 sensor can operate as a standard inductive sensor (Telemecanique patent pending). Operation in inductive mode enables validation of reliable detection of all the moving Reference objects to be monitored.
speed
b Through this system, the positioning is thus made 100 % reliable and able to be checked at any time without modifying the sensors adjustment.
Speed adjustment in teach mode b The normal or reference speed of the moving object (1) to be monitored is adjusted by simply pressing the teach mode button (2) and is then validated by the display LED. v If in doubt, the sensor can be reset at any time to the factory settings.
(1) To allow the moving object to reach its normal speed (machine inertia), the sensor holds its output closed for 9 seconds. (2) The sensors default drop-out underspeed corresponds to the preset speed - 30 %. Example: if the preset speed is 1000 rpm, the sensor drops out at underspeed when the speed of the moving object drops below 1000 - (1000 x 0.3) = 700 rpm. - 20 %, - 11 % and - 6 % threshold can be obtained by pressing the teach mode button.
u7s
Setting-up
Minimum mounting distances (mm)
Dimensions
XS9 E, XS9 C
C D
B E F (1)
Side by side e 40 e 60
F(1) E B 62
C 13 15
A
D 8.8 9.8
E 20 33
F 3.5 4.5
2/62
PBT case
10 mm 15 mm 66000 impulses/min
10 mm
15 mm
References
3-wire 2-wire Weight (kg) PNP / NC c or a / NC XS9 E11RPBL01M12 XS9 C11RPBL01M12 XS9 E11RMBL01U20 XS9 C11RMBL01U20 0.040 0.060 0.040 0.060 UL, CSA, e 0.15 m flying lead with M12 connector 08 mm 012 mm IP 67 double insulation i - 40+ 85 C - 25+ 70 C 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED Green LED c 1224 V c 1036 V y 100 mA (1) y 200 mA (1)
Characteristics
Product certifications Connection Operating zone Degree of protection Conforming to IEC 60529 Storage temperature range Operating temperature range Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Indicator Output state Supply on Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Residual current, open state Current consumption, no-load Maximum switching frequency Power on "run-up" delay 0.15 m flying lead with 1/2" - 20 UNF connector 08 mm 012 mm
y2V y 100 mA y 10 mA 48 000 impulses/min 9 seconds + 1/Fr (1) With overload and short-circuit protection. (2) It is essential to connect a 0.4 A quick-blow fuse in series with the load.
a or c 24240 V (50/60 Hz) a or c 20264 V a or c 5100 mA c 5200 mA, (2) a 5300 mA (2) y 5.5 V y 1.5 mA
Wiring scheme
Connector
M12
4 3
3-wire c
1/2" UNF
1
2-wire a or c
XS9 p11RMBL01U20
2
XS9 p11RPBL01M12
Accessory (1)
Description Remote control fixing clamp Reference XSZ BPM12 Weight kg 0.015
2/63
These analogue output proximity sensors are solid-state sensors designed for monitoring displacement. They are not measuring sensors. They are suitable for use in numerous sectors, particularly for applications involving: - deformation and displacement monitoring, - vibration amplitude and frequency monitoring, - control of dimensional tolerances, - position control, - concentricity or eccentricity monitoring.
Operating principle
The operating principle of the sensor is that of a damped oscillator. The degree of damping will depend on the distance of an object from the sensing face. The sensor will sense the distance and produce an output current with a value directly proportional to this distance.
12 mm
18 mm
30 mm
Is (mA)
Is (mA)
Is (mA)
0 0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 Sensor - object distance (mm)
12 mm
18 mm
30 mm
Is (mA)
Is (mA)
Is (mA)
0 0,4 0,8 1,2 1,6 2 2,4 2,8 3,2 3,6 4 4,4 4,8 5,2 Sensor - object distance (mm)
0 0,8 1,6 2,4 3,2 4 4,8 5,6 6,4 7,2 8 8,2 8,4 9,2 Sensor - object distance (mm)
0 1,5 3 4,5 6 7,5 9 10,5 12 13,5 15 16,5 18 19,5 Sensor - object distance (mm)
12 mm
12 mm
12 mm
Is (mA)
Is (mA)
Is (mA)
0 0,8 1,6 2,4 3,2 4 4,8 5,6 6,4 7,2 8 8,8 9,6 10,4 Sensor - object distance (mm)
0 1,5 3 4,5 6 7,5 9 10,5 12 13,5 15 16,5 18 19,5 Sensor - object distance (mm)
Wiring schemes
2-wire connection
BN/1 mA BK/4 BU/3 Is R
3-wire connection
+
Output current
+
Output voltage Us = R.Is
Load impedance Output current Load impedance Output voltage Load impedance value value value 12 V 420 mA R y 8.2 24 V 010 mA R y 1500 010 V R = 1000 24 V 420 mA R y 470 48 V 010 mA R y 3300 010 V R = 1000 Ensure a minimum of 10 V between the + and the - (terminal 3) Ensure a minimum of 5 V between the + and the sensor output (terminal 4). of the sensor. (1) Voltage range only obtained with a load impedance of 1000 . References: pages 2/65 to 2/67 Characteristics: pages 2/65 to 2/67
Output current
2/64
Sensor
b a
a = 50 b = 42 Metal case 2 mm
a = 50 b = 42 Plastic case 4 mm
a = 50 b = 42 Plastic case 4 mm
References
3-wire c 2-wire c Weight (kg) Output 010 V (2) Output 420 mA (2) XS1 M12AB120 0.075 XS4 P12AB120 0.065 XS4 P12AB110 0.065
Characteristics
Product certifications Connection Degree of protection conforming to IEC 60529 Operating zone Repeat accuracy Linearity error Ambient air temperature Rated supply voltage Voltage limits (including ripple) Output current drift Ambient temperature: - 25+ 70 C Current consumption, no-load Maximum operating rate e, UL, CSA Pre-cabled, PvR, 3 x 0.34 mm2, length 2 m IP 67
0.44 mm
0.44 mm
1V
c 12...24 V c 1038 V
c 2448 V c 1558 V
4 mA 1500 Hz (1) Voltage range only obtained with a load impedance of 1000 . (2) Output current range Is, see page 2/64.
Setting-up
Minimum mounting distances (mm) Side by side Face to face Facing a metal object Mounted in a metal support
d h
d 12, h 0 d 36, h 8 d 36, h 8
e e
XS1 M12AB120 flush mountable e4 XS4 P12AB110 non flush mountable e 16 XS4 P12AB120 non flush mountable e 16 Fixing nut tightening torque Other versions
e 24 e 48 e 48
e6 e 12 e 12
< 6 N.m (metal case), < 2 N.m (plastic case) Please consult your Regional Sales office.
2/65
Sensor
b a
Lengths (mm): a = Overall b = Threaded section c = For non flush mountable sensors Nominal sensing distance (Sn)
References
3-wire c 2-wire c Weight (kg) Output 010 V (2) Output 420 mA (2) XS1 M18AB120 0.120 XS4 P18AB120 0.080 XS4 P18AB110 0.080
Characteristics
Product certifications Connection Degree of protection conforming to IEC 60529 Operating zone Repeat accuracy Linearity error Ambient air temperature Rated supply voltage Voltage limits (including ripple) Output current drift Ambient temperature: - 25+ 70 C Current consumption, no-load Maximum operating rate e, UL, CSA Pre-cabled, PvR, 3 x 0.34 mm2, length 2 m IP 67
0.88 mm
0.88 mm
1V
c 12...24 V c 1038 V
c 2448 V c 1558 V
4 mA 500 Hz (1) Voltage range only obtained with a load impedance of 1000 . (2) Output current range Is, see page 2/64.
Setting-up
Minimum mounting distances (mm) Side by side Face to face Facing a metal object Mounted in a metal support
d h
d 18, h 0 d 54, h 16 d 54, h 16
e e
XS1 M18AB120 flush mountable e 10 XS4 P18AB110 non flush mountable e 32 XS4 P18AB120 non flush mountable e 32 Fixing nut tightening torque Other versions
e 60 e 96 e 96
e 15 e 24 e 24
< 15 N.m (metal case), < 5 N.m (plastic case) Please consult your Regional Sales office.
2/66
Sensor
b a
Lengths (mm): a = Overall b = Threaded section c = For non flush mountable sensors Nominal sensing distance (Sn)
References
3-wire c 2-wire c Weight (kg) Output 010 V (2) Output 420 mA (2) XS1 M30AB120 0.200 XS4 P30AB120 0.100 XS4 P30AB110 0.100
Characteristics
Product certifications Connection Degree of protection conforming to IEC 60529 Operating zone Repeat accuracy Linearity error Ambient air temperature Rated supply voltage Voltage limits (including ripple) Output current drift Ambient temperature: - 25+ 70 C Current consumption, no-load Maximum operating rate e, UL, CSA Pre-cabled, PvR, 3 x 0.34 mm2, length 2 m IP 67
1.515 mm
1.515 mm
1V
c 12...24 V c 1038 V
c 2448 V c 1558 V
4 mA 300 Hz (1) Voltage range only obtained with a load impedance of 1000 . (2) Output current range Is, see page 2/64.
Setting-up
Minimum mounting distances (mm) Side by side Face to face Facing a metal object Mounted in a metal support
d h
d 30, h 0 d 90, h 30 d 90, h 30
e e
XS1 M30AB120 flush mountable e 20 XS4 P30AB110 non flush mountable e 60 XS4 P30AB120 non flush mountable e 60 Fixing nut tightening torque Other versions
e 30 e 45 e 45
< 40 N.m (metal case), < 20 N.m (plastic case) Please consult your Regional Sales office.
2/67
These analogue output proximity sensors are solid-state sensors designed for monitoring displacement. They are not measuring sensors. They are suitable for use in numerous sectors, particularly for applications involving: v deformation and displacement monitoring, v vibration amplitude and frequency monitoring, v control of dimensional tolerances, v position control, v concentricity or eccentricity monitoring.
2
Operating principle
The operating principle of the sensor is that of a damped oscillator. The degree of damping will depend on the distance of an object from the sensing face. The sensor will sense the distance and produce an output current with a value directly proportional to this distance.
XS9 E
Sn = 110 mm
Us (V)
11 10 9 8 7 6 5 4 3 2 1 0 0 1 5 10 12
Sensor - object distance (mm)
XS9 C
Sn = 215 mm
Us (V)
XS9 D
Sn = 540 mm
Us (V)
11 10 9 8 7 6 5 4 3 2 1 0 0 5 20 40 45
Sensor - object distance (mm)
Wiring schemes
Connector
M8
4 1 3 1 2
Pre-cabled
M12
4 3
3-wire connection
BN/1 mA BK/4 BU/3 Is R
+
Output voltage
Us = R.Is
Output Load impedance Output Load impedance current value voltage value 24 V 010 mA R y 1400 010 V R = 1000 Note: ensure a minimum of 5 V between the + (terminal 1) and the sensor output (terminal 4). (1) Voltage range only obtained with a load impedance of 1000 .
2/68
PBT case
2
Nominal sensing distance (Sn) 5 mm XS9 F111A1L2 XS9 F111A1L01M8 0.060 0.040 10 mm XS9 E111A1L2 XS9 E111A1L01M12 0.075 0.055 15 mm XS9 C111A1L2 XS9 C111A1L01M12 0.095 0.075 40 mm XS9 D111A1L2 XS9 D111A1M12 0.340 0.320
References
3-wire c 010 V Weight (kg) Pre-cabled (L = 2 m) (2) Connector Pre-cabled (L = 2 m) (2) Connector
Characteristics
Product certifications Connection Pre-cabled Connector UL, CSA, e PvR, 3 x 0.34 mm2, length 2 m for XS9 p111ApL2 0.15 m flying lead with 0.15 m flying lead with M12 connector M8 connector 15 mm 110 mm 215 mm IP 68 IP 68, double insulation i IP 67 IP 67, double insulation i - 40+ 85 C - 25+ 70 C PBT case 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms No c 24 V c 1536 V 3% 1V y 4 mA with overload and short-circuit protection 2000 Hz 1000 Hz y 10% (throughout the operating temperature range) M12 540 mm
Pre-cabled Connector
Storage temperature Operating temperature Materials Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Output state indication Rated supply voltage Voltage limits (including ripple) Repeat accuracy Linearity error Current consumption, no-load Maximum operating frequency Output current drift
100 Hz
Dimensions
XS9 F
15 9
XS9 E/C/D
C D
XS9 C/D
B E F (2)
XS9 E
32
E B
(2) For CHC type screws Type XS9 E XS9 C XS9 D A (L2) 14 14 23 A (M12) 14 B 26 40 80 C 13 15 26 D 8.8 9.8 16 E 20 33 65 F 3.5 4.5 5.5 Facing a metal object e 15 e e 30 e 45 e 120
e e e e
36 72 110 300
(1) Voltage range only obtained with a load impedance of 1000 . (2) For a 5 m long cable replace L2 by L5, for a 10 m long cable replace L2 by L10. Example: XS9 C111A1L2 becomes XS9 C111A1L5 with a 5 m long cable. Accessories: page 2/102
B
F (2)
2/69
These analogue output proximity sensors are solid-state sensors designed for monitoring displacement. They are not measuring sensors. They are suitable for use in numerous sectors, particularly for applications involving: v deformation and displacement monitoring, v vibration amplitude and frequency monitoring, v control of dimensional tolerances, v position control, v concentricity or eccentricity monitoring.
2
Operating principle
The operating principle of the sensor is that of a damped oscillator. The degree of damping will depend on the distance of an object from the sensing face. The sensor will sense the distance and produce an output current with a value directly proportional to this distance.
XS9 E
Sn = 110 mm
Is (mA)
XS9 C
Sn = 215 mm
Is (mA)
XS9 D
Sn = 540 mm
Is (mA)
Wiring schemes
Connector
M8
4 1 3 1 2
Pre-cabled
M12
4 3
2-wire connection
BN/1 mA BK/4 BU/3 Is R
+
Output current
Output Load impedance current value 12 V 420 mA R y 8.2 24 V 420 mA R y 470 Note: ensure a minimum of 10 V between the + (terminal 1) and - (terminal 3) of the sensor.
2/70
PBT case
2
Nominal sensing distance (Sn) 5 mm XS9 F111A2L2 XS9 F111A2L01M8 0.060 0.040 10 mm XS9 E111A2L2 XS9 E111A2L01M12 0.075 0.055 15 mm XS9 C111A2L2 XS9 C111A2L01M12 0.095 0.075 40 mm XS9 D111A2L2 XS9 D111A2M12 0.340 0.320
References
2-wire c 420 mA Weight (kg) Pre-cabled (L = 2 m) (1) Connector Pre-cabled (L = 2 m) Connector
Characteristics
Product certifications Connection Pre-cabled Connector UL, CSA, e PvR, 3 x 0.34 mm2, length 2 m for XS9 p111ApL2 0.15 m flying lead with 0.15 m flying lead with M12 connector M8 connector 15 mm 110 mm 215 mm IP 68 IP 68, double insulation i IP 67 IP 67, double insulation i - 40+ 85 C - 25+ 70 C PBT case 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms No c 1224 V c 1036 V 3% 2 mA y 4 mA with overload and short-circuit protection 2000 Hz 1000 Hz y 10% (throughout the operating temperature range) M12 540 mm
Pre-cabled Connector
Storage temperature Operating temperature Materials Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Output state indication Rated supply voltage Voltage limits (including ripple) Repeat accuracy Linearity error Current consumption, no-load Maximum operating frequency Output current drift
100 Hz
Dimensions
XS9 F
15 9
XS9 E/C/D
C D
XS9 C/D
B E F (1)
XS9 E
32
E B
(1) For CHC type screws Type XS9 E XS9 C XS9 D A (L2) 14 14 23 Side by side A (M12) 14 B 26 40 80 C 13 15 26 D 8.8 9.8 16 E 20 33 65 F 3.5 4.5 5.5 Facing a metal object e 15 e 30 e e 45 e 120
e e e e
36 72 110 300
(1) For a 5 m long cable replace L2 by L5, for a 10 m long cable replace L2 by L10. Example: XS9 F111A2L2 becomes XS9 F111A2L5 with a 5 m long cable. Accessories: page 2/102
B
F (1)
2/71
Detection at fixed sensing distance. Factor 1 (Fe/Nfe) sensors (1). For ferrous and non ferrous materials Solid-state output
b a
References
4-wire c Weight (kg) PNP/PNP programmable NO/NC XS1 M18KPM40 0.120 XS1 M18KPM40D 0.060
Characteristics
Product certifications Connection Degree of protection Conforming to IEC 60529 Operating zone Repeat accuracy Differential travel Operating temperature Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching frequency Delays First-up Response Recovery e, UL, CSA Pre-cabled, PvR 4 x 0.34 mm2, length 2 m (2) M12 connector IP 68 IP 67 04 mm 3% of Sr 115% of Sr 0+ 50 C Yellow LED, annular Yellow LED, 4 viewing ports at 90 c 1224 V with protection against reverse polarity c 1038 V 0...200 mA with overload and short-circuit protection y 2.6 V y 15 mA 1000 Hz y 10 ms y 0.3 ms y 0.7 ms
Wiring schemes
M12 connector Pre-cabled 4-wire c, PNP/NPN programmable, NO or NC output
NO
4 3
NC
BU/3 WH/2 BK/4
BN/1
+
WH/2
+
BK/4 BN/1
BU/3
See connection on page 9/45. (1) The variation in sensing distance between ferrous and non ferrous materials is typically less than 5%. (2) Sensors available with other cable lengths: please consult your Regional Sales office.
2/72
Detection at fixed sensing distance. Factor 1 (Fe/Nfe) sensors (1). For ferrous and non ferrous materials Solid-state output
e, UL, CSA Pre-cabled, PvR 4 x 0.34 mm2, length 2 m (2) IP 68 08 mm 3% of Sr 115% of Sr 0+ 50 C Yellow LED, annular c 1224 V with protection against reverse polarity c 1038 V 0200 mA with overload and short-circuit protection y 2.6 V y 15 mA 1000 Hz y 5 ms y 0.3 ms y 0.7 ms
Setting-up
Minimum mounting distances (mm) Side by side Face to face Facing a metal object Mounted in a metal support
d h
d u 18, h u 0 d u 30, h u 0
e e
XS1 M18 flush mountable e u 10 XS1 M30 flush mountable e u 20 Fixing nut tightening torque: XS1 M18: < 35 N.m, XS1 M30 : < 100 N.m e u 60 e u 120 e u 15 e u 30
(1) The variation in sensing distance between ferrous and non ferrous materials is typically less than 5%. (2) Sensors available with other cable lengths: please consult your Regional Sales office.
2/73
References, characteristics
Osiprox Application
Fixed sensing distance detection, Factor 1 (Fe/Nfe) sensors (1). For ferrous and non ferrous materials Solid-state output
Flush mountable in metal
Sensor
2
Nominal sensing distance (Sn) 15 mm PNP/NPN/NO/NC programmable XS7 C40KPM40 0.220 e, CSA, UL Conforming to IEC 60529 IP 67 0+ 50 C Screw terminals, clamping capacity: 4 x 0.34 mm2 (2) 012 mm 3% of Sr 115% of Sr Yellow LED c 1224 V with protection against reverse polarity c 1038 V y 15 mA 0200 mA with overload and short-circuit protection y 2.6 V 1000 Hz First-up Response Recovery y 5 ms y 0.3 ms y 0.7 ms (1) The variation in sensing distance between ferrous and non ferrous materials is typically less than 5%. (2) Cable gland not included with sensor. For suitable 13P cable gland (XSZ PE13), see page 2/102.
References
4-wire c Weight (kg)
Characteristics
Product certifications Degree of protection Operating temperature Connection Operating zone Repeat accuracy Differential travel Output state indication Rated supply voltage Voltage limits (including ripple) Current consumption, no-load Switching capacity Voltage drop, closed state Maximum switching frequency Delays
2/74
Fixed sensing distance detection, Factor 1 (Fe/Nfe) sensors (1). For ferrous and non ferrous materials Solid-state output
Dimensions
XS7 C40KPM40
40
40
20
117
(1)
(2)
16 24 41
(1) Output LED. (2) 1 tapped entry for 13P cable gland. (3) 2 elongated holes 5.3 x 7.
30 40
Setting-up
Minimum mounting distances (mm)
e e e
60
25
(3)
XS7 C40KPM40
Side by side e u 40
Tightening torque of cover fixing screws and clamp screws: < 1.2 N.m
Wiring schemes
PNP/NPN
4-wire c programmable, NO or NC output NO output
1 2 4
NC output
3
+
2
+
4 1
2/75
Selective detection of ferrous materials Selective detection of non ferrous materials Cylindrical type, solid-state output
5 mm
References
3-wire, ferrous version Insensitive to non ferrous materials 3-wire, non ferrous version Insensitive to ferrous materials Weight (kg) PNP PNP NO NO XS1 M18PAS40 XS1 M18PAS20 0.120
Characteristics
Product certifications Connection Operating zone Degree of protection conforming to IEC 60529 Operating temperature range Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Residual current, open state Current consumption, no-load Maximum switching frequency Delays First-up Response Recovery UL, CSA, e Pre-cabled (PvR) 3 x 0.34 mm2, length 2 m (1) 04 mm IP 68 - 25+ 70 C Yellow LED, annular c 1224 V with protection against reverse polarity c 1038 V 0200 mA with overload and short-circuit protection y 2.6 V y 15 mA 1000 Hz y 10 ms y 0.3 ms y 0.7 ms (1) Sensors available pre-cabled with other cable lengths: please consult your Regional Sales Office
Wiring scheme
3-wire c PNP
BN/1
Dimensions
XS1 M
+
PNP BK/4
a (mm) 60
b (mm) 51.5
BU/3
b a
Setting-up
Minimum mounting distances (mm)
d e e e h
Side by side XS1 M18 e 10 Face to face e 60 Facing a metal object e 15 Mounted in a metal support d 18, h 0 (ferrous metal) d 18, h 5 (non ferrous metal) Accessories: pages 2/102
2/76
5 mm
References
3-wire, ferrous version Insensitive to non ferrous materials 3-wire, non ferrous version Insensitive to ferrous materials Weight (kg) PNP PNP NO NO XS1 M18PAS40D XS1 M18PAS20D 0.060
Characteristics
Product certifications Connection Degree of protection conforming to IEC 60529 Operating zone Operating temperature range Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Residual current, open state Current consumption, no-load Maximum switching frequency Delays First-up Response Recovery UL, CSA, e M12 connector IP 67 04 mm - 25+ 70 C Yellow LED, 4 viewing ports at 90 c 1224 V with protection against reverse polarity c 1038 V 0200 mA with overload and short-circuit protection y 2.6 V y 15 mA 1000 Hz y 10 ms y 0.3 ms y 0.7 ms
Wiring scheme
M12 connector
4 3
Dimensions
3-wire c PNP
BN/1
XS1 M
+
PNP BK/4
a (mm) 70
b (mm) 51.5
2
BU/3
b a
Setting-up
Minimum mounting distances (mm)
d e e e h
Side by side XS1 M18 e 10 Face to face e 60 Facing a metal object e 15 Mounted in a metal support d 18, h 0 (ferrous metal) d 18, h 5 (non ferrous metal) Accessories: pages 2/102
2/77
References, characteristics
Osiprox Application
For assembly, packaging and light handling Plastic case: 12 x 26 x 40 mm dc supply, solid-state output
Sensor
2 mm
4 mm
References
3-wire c PNP NPN 4-wire c (complementary outputs) PNP NPN Weight (kg) NO NO NO + NC NO + NC XS7 G12PA140 XS7 G12NA140 0.100 CSA, UL, e Pre-cabled Connector Operating zone Repeat accuracy Differential travel Degree of protection Storage temperature range Operating temperature range Materials Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Output state indication Rated supply voltage Voltage limits (including ripple) Current consumption, no-load Switching capacity Voltage drop, closed state Maximum switching frequency Delays First-up Response Recovery 3 x 0.34 mm2, length 2 m (1) 01.6 mm 10 % of Sr 3...20 % of Sr IP 67 -40+85 C -25+70 C Case: PBT, cable: PVC 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED, on top of case c 1224 V c 1030 V y 10 mA 0100 mA (2) y 1.8 V y y y y 2 kHz 4 ms 0.5 ms 1 ms 0200 mA (2) y 2.6 V 0100 mA (2) y 1.8 V 0100 mA (2) y 1.8 V y 1 kHz 0200 mA (2) y 2.6 V 0100 mA (2) y 1.8 mA c 1248 V c 1058 V c 1224 V c 1030 V c 1224 V c 1030 V c 1248 V c 1058 V c 1224 V c 1030 V 4 x 0.34 mm2, length 2 m (1) M8 3 x 0.34 mm 2, length 2 m (1) 03.2 mm 4 x 0.34 mm2, length 2 m (1) M8 XS7 G12PC440 XS7 G12NC440 0.100 XS7 G12PA140S XS8 G12PA140 XS7 G12NA140S XS8 G12NA140 0.030 0.100 XS8 G12PC440 XS8 G12NC440 0.100 XS8 G12PA140S XS8 G12NA140S 0.030
Characteristics
Product certifications Connection
(1) Sensors available pre-cabled with other cable lengths: Length of cable Suffix to be added to references stated above for 2 m pre-cabled sensors 5m L1 10 m L2 Example: sensor XS7 G12PA140 with 5 m cable becomes XS7 G12PA140L1. (2) With overload and short-circuit protection
2/78
For assembly, packaging and light handling Plastic case: 12 x 26 x 40 mm dc supply, solid-state output
Dimensions
XSp G12pA140, XS p G12pC440
Rear view
26 4 4 18 4 12
(3)
(1)
10 16
40
32
(2)
XSp G12pA140S
Rear view
26 4 4 18 4 12
30
(2)
(1)
10 30 16
e
40
32
M8 31
Setting-up
Minimum mounting distances (mm)
e
45
Face to face e u 15 e u 60
Wiring scheme
3-wire c , NO output
BN/1 PNP BK/4 BN/1 NPN BK/4 BU/3 BU/3 BU
4-wire c , NO + NC output
BN BK(NO) PNP WH(NC) NPN BK(NO) WH(NC) BU BN
Connector
M8
4 1 3
2/79
References, characteristics
Osiprox Application
For assembly, packaging and light handling Plastic case: 12 x 26 x 40 mm a.c. or d.c. supply
Flush mountable in metal Non flush mountable in metal
Sensor
2 mm
4 mm
References
2-wire c or a NO NC Weight (kg) XS7 G12MA230 XS7 G12MB230 0.100 CSA, UL, e Pre-cabled 2 x 0.34 mm2, length 2 m (1) 01.6 mm 10 % of Sr 3...20 % of Sr IP 67 - 40+ 85 C - 25+ 70 C Case: PBT, cable: PVC 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED, on top of case a 24240 V (50/60 Hz) or c 24210 V a or c 20264 V 5200 mA (2) y 5.5 V y 0.8 mA / 24 V, 1.5 mA / 120 V a 25 Hz or c 250 Hz First-up Response Recovery y 40 ms y 1 ms y 2 ms (1) Sensors available pre-cabled with other cable lengths: Length of cable Suffix to be added to references stated above Weight increase for 2 m pre-cabled sensors 5m L1 0.120 kg 10 m L2 0.320 kg Example: sensor XS7 G12MA230 with 5 m cable becomes XS7 G12MA230L1. (2) As these sensors do not incorporate overload or short-circuit protection, it is essential to connect a 0.4 A quick-blow fuse in series with the load. 03.2 mm XS8 G12MA230 XS8 G12MB230 0.100
Characteristics
Product certifications Connection Operating zone Repeat accuracy Differential travel Degree of protection Storage temperature range Operating temperature range Materials Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Residual current, open state Maximum switching frequency Delays
2/80
For assembly, packaging and light handling Plastic case: 12 x 26 x 40 mm a.c. or d.c. supply
Dimensions
XSp G12Mp230
Rear view
26 4 4 18 4 12
(3)
(1)
10 16
40
32
(2)
Setting-up
Minimum mounting distances (mm)
e e
30
Face to face e u 15 e u 60
Wiring scheme
2-wire a or c , NO or NC output
BN BU
2/81
References, characteristics
Osiprox Application
Plastic case, form C, plug-in 5 position turret head d.c. supply
Sensor
2
Nominal sensing distance (Sn) 15 mm Increased range model 20 mm XS7 C40PC449 XS7 C40NC449 0.220 15 mm 20 mm Increased range model 40 mm XS8 C40PC449 XS8 C40NC449 0.220 20 mm
References
4-wire c (complementary outputs) PNP NPN 2-wire c (non polarised) NO NO or NC programmable Weight (kg) NO + NC NO + NC XS7 C40PC440 XS7 C40NC440 0.220 UL, CSA, e IP 67 - 25+ 70 C Screw terminals, clamping capacity: 2 or 4 x 1.5 mm2 (1) 012 mm 016 mm 012 mm 016 mm 032 mm 016 mm XS7 C40DA210 XS7 C40DP210 0.220 XS8 C40PC440 XS8 C40NC440 0.220 XS8 C40DA210 XS8 C40DP210 0.220
Characteristics
Product certifications Degree of protection conforming to IEC 60529 Operating temperature Connection Operating zone Repeat accuracy Differential travel Status indication Rated supply voltage Voltage limits (including ripple) Current consumption, no-load Switching capacity Residual current, open state Voltage drop, closed state Maximum switching frequency Delays First-up Response Recovery
Output Supply on
3% of real sensing distance (Sr) 3 20% of real sensing distance (Sr) Yellow LED Yellow LED Green LED c 1248 V with protection against reverse polarity c 1058 V y 10 mA
Yellow LED
0200 mA 1.5100 mA With overload and short-circuit protection y 0.5 mA y2V 1000 Hz y 5 ms y 0.3 ms y 0.7 ms y4V 1500 Hz y 5 ms y 2 ms y 5 ms
(1) Cable gland not included with sensor. For suitable 13P cable gland (XSZ PE13), see page 2/102.
2/82
Dimensions
XS7 C40Dp210, XS8 C40Dp210
40
20
40
40
20
25
117
117
60
(1)
(2)
(1)
(2)
(3)
16 24 41
30 40
= 41
16 24
30 40
(1) Output LED. (2) 1 tapped entry for 13P cable gland. (3) 2 elongated holes 5.3 x 7.
(1) Output LED. (2) Supply LED. (3) 1 tapped entry for 13P cable gland. (4) 2 elongated holes 5.3 x 7.
Setting-up
Minimum mounting distances (mm)
e e e
XS7 XS7 increased range model XS8 XS8 increased range model
60
25
(3)
(4)
Tightening torque of cover fixing screws and clamp screws: < 1.2 N.m
Wiring schemes
2-wire c (non polarised), NO or NC output depending on position of link 4-wire c, NO + NC output
+
5
+
1 NPN 3 4 (NO) 2 (NC)
+/
/+
NO
NO
NC
NC
2/83
References, characteristics
Osiprox Application
Plastic case, form C, plug-in 5 position turret head a.c. or d.c. supply
Flush mountable in metal Non flush mountable in metal
Sensor
2
Nominal sensing distance (Sn) AC 15 mm AC/DC AC 20 mm AC/DC
References
2-wire a 2-wire a or c universal model Weight (kg) NO or NC programmable NO or NC programmable XS7 C40FP260 0.220 UL, CSA, e IP 67 - 25+ 70 C Screw terminals, clamping capacity: 2 x 1.5 mm2 (1) 012 mm 3% of real sensing distance (Sr) 3...20% of real sensing distance (Sr) Yellow LED a 24240 V, 50/60 Hz a 20264 V 5500 mA (2) (2 A inrush) y 1.5 mA y 5.5 V 25 Hz First-up Response Recovery y 120 ms y 30 ms y 20 ms (1) Cable gland not included with sensor. For suitable 13P cable gland (XSZ PE13), see page 2/102. (2) These sensors do not incorporate overload or short-circuit protection and therefore, it is essential to connect a quick-blow fuse in series with the load, see page 2/102. a 25 Hz, c 50 Hz 25 Hz a 25 Hz, c 50 Hz a 5300 mA or c 5200 mA (2) 0.8 mA on 24 V 1.5 mA on 120 V 5500 mA (2) (2 A inrush) y 1.5 mA a 5300 mA or c 5200 mA (2) 0.8 mA on 24 V 1.5 mA on 120 V a 24240 V, 50/60 Hz or c 24210 V a or c 20264 V a 24240 V, 50/60 Hz a 20264 V a 24240 V, 50/60 Hz or c 24210 V a or c 20264 V 016 mm XS7 C40MP230 0.220 XS8 C40FP260 0.220 XS8 C40MP230 0.220
Characteristics
Product certifications Degree of protection conforming to IEC 60529 Operating temperature Connection Operating zone Repeat accuracy Differential travel Output state indication Rated supply voltage with protection against reverse polarity Voltage limits (including ripple) Current consumption, no-load Switching capacity Residual current, open state Voltage drop, closed state Maximum switching frequency Delays
2/84
Plastic case, form C, plug-in 5 position turret head a.c. or d.c. supply
Dimensions
XS7 C40FP260, XS7 C40MP230, XS8 C40FP260, XS8 C40MP230
40
40
20
117
(1)
(2)
16 24 41
(1) Output LED. (2) 1 tapped entry for 13P cable gland. (3) 2 elongated holes 5.3 x 7.
30 40
Setting-up
Minimum mounting distances (mm)
60
25
(3)
Side by side e u 40 e u 80
Tightening torque of cover fixing screws and clamp screws: < 1.2 N.m
Wiring schemes
2-wire a programmable, NO or NC output depending on position of link
5
NO
NO
NC
NC
2/85
References, characteristics
Osiprox Application
Plastic case, form C, cubic 40, multi-position d.c. supply
Sensor
2
Nominal sensing distance (Sn) 15 mm 20 mm
References
2-wire c (non polarised) 4-wire c (complementary outputs) Weight (kg) NO PNP NO + NC XS7 T4DA210 XS7 T4DA214LD XS7 T4DA214LD01 XS7 T4PC440 XS7 T4NC440 0.265 0.220 XS7 T4PC440LD XS7 T4NC440LD 0.220 0.200 XS8 T4PC440 XS8 T4PC440LD XS8 T4NC440 XS8 T4NC440LD 0.265 0.220
Characteristics
Product certifications Degree of protection Conforming to IEC 60529 Operating temperature Connection Pre-cabled Remote M12 connector Operating zone Repeat accuracy Differential travel Supply/output state indication Rated supply voltage Voltage limits (including ripple) Current consumption, no-load Switching capacity Residual current, open state Voltage drop, closed state Maximum switching frequency Delays First-up Response Recovery
2 x 0.5 mm2 4 x 0.34 mm2 length 2 m (1) length 2 m (1) Cable: length 0.8 m 012 mm 3 % of real sensing distance (Sr) 320 % of real sensing distance (Sr) Yellow LED, rear mounted c 1248 V with protection against reverse polarity c 1058 V y 10 mA y 10 mA 1.5100 mA 0200 mA 1.5100 mA 0200 mA With overload and short-circuit protection y 0.7 mA y 0.1 mA y 0.7 mA y 0.1 mA y 5.2 V 150 Hz y 5 ms y 2 ms y 5 ms y2V 1000 Hz y 7 ms y 0.3 ms y 0.7 ms y 5.2 V 150 Hz y 5 ms y 2 ms y 5 ms y2V 1000 Hz y 7 ms y 0.3 ms y 0.7 ms
(1) Sensors pre-cabled with other cable lengths : Length of cable Suffix to be added to references stated above for 2 m pre-cabled sensors Weight increase 5m L1 0.120 kg 10 m L2 0.320 kg Example: sensor XS7 T4DA210 with 5 m cable becomes XS7 T4DA210L1 Other versions Inductive proximity sensors specifically designed for other operating temperatures. Please consult your Regional Sales Office.
2/86
Dimensions
XSp T4ppppp, XSp T4pppppLD, XS7 T4pppppLD01
Plate mounted Bracket mounted
40
40
40
40
24
53
= 31 = 30 =
45
55
(1) LED.
30
25
M3 x 6 CHC screw
M3 x 6 CHC screw
Setting-up
Minimum mounting distances (mm)
e
Side by side e u 40 e u 40 e u 60
Wiring schemes
Connector
4 3
Pre-cabled
BU : Blue BN : Brown BK : Black WH : White
2-wire c, NO output
BN/1
4-wire c, NO + NC output
BN/1 PNP BU/3 BK/4 (NO) WH/2 (NC) BN/1 NPN BU/3
55
(1)
(1)
43
40
44
40
+
BK/4 (NO) WH/2 (NC)
BU/4
2/87
References, characteristics
Osiprox Application
Flat sensor, flush mountable, increased range, 300 mA switching capacity Form D, DIN rail mounting, solid-state output
Flush mountable in metal
Sensor
2
Dimensions (mm) Nominal sensing distance (Sn) 80 x 80 x 40 50 mm (not flush mounted: 42 mm)
References
2-wire c (non polarised) Weight (kg) NO XS7 D1A3CAM12DIN 0.374 e, CSA, UL: pending Conforming to IEC 60529 Operation Storage Vibration resistance Shock resistance Connection Operating zone Repeat accuracy Differential travel Output state indication Rated supply voltage Voltage limits (including ripple) Residual current, open state Switching capacity Voltage drop, closed state Maximum switching frequency Delays First-up Response Recovery Conforming to IEC 60068-2-6 IP 67 double insulation i - 25+ 70 C - 40+ 85 C 25 gn, amplitude 2 mm (f = 10 to 55 Hz)
Characteristics
Product certifications Degree of protection Temperature
Conforming to IEC 60068-2-27 50 gn, duration 11 ms M12 connector 040 mm (not flush mounted: 035 mm) 3% of Sr 115% of Sr Yellow LED c 1248 V with protection against reverse polarity c 1058 V y 0.5 mA 1.5300 mA with overload and short-circuit protection y 4.5 V 100 Hz y 10 ms y 2 ms y 5 ms
2/88
Flat sensor, flush mountable, increased range, 300 mA switching capacity Form D, DIN rail mounting, solid-state output
Dimensions
XS7 D1A3CAM12DIN
40 30 80 65
(1)
80
5,1 (2)
Setting-up
Minimum mounting distances (mm)
Face to face Side by side Back to back Facing a metal object
18
65
e e
450 450
140 180
90 180
150 150
Wiring schemes
2-wire NO/M12 XS7 D1A3CAM12DIN
4 3
NO BK/4 BN/1
+/-/+
d > 10 mm
Sn 42 mm
Su 35 mm
Sn 50 mm
Su 40 mm
2/89
Sensors for welding machine applications (1) Cylindrical type. Metal case, Teflon coated steel, threaded
2
b a
2
Lengths (mm): a = Overall b = Threaded section c = For non flush mountable sensors a = 60 b = 40 = M12 x 1 Teflon front face 2 mm a = 60 b = 40 = M18 x 1 Teflon front face 5 mm
References
3-wire c Weight (kg) PNP, NO XS1 M12PAW01D 0.025 XS1 M18PAW01D 0.060
Characteristics
Product certifications Connection Degree of protection Conforming to IEC 60529 Operating zone Repeat accuracy Differential travel Operating temperature Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Immunity to electromagnetic fields Maximum switching frequency Delays First-up Response Recovery e, UL, CSA M12 connector IP 67 01.6 mm 04 mm 3% of Sr 120% of Sr - 25+ 70 C Yellow LED, 4 viewing ports at 90 c 1224 V with protection against reverse polarity c 1036 V 0...250 mA with overload and short-circuit protection y 2.5 V y 15 mA y 140 mT 1000 Hz 500 Hz y 10 ms y 10 ms y 0.1 ms y 0.2 ms y 0.4 ms y 0.6 ms
Wiring schemes
M12 connector
4 3
+
4 (NO)
See connection on page 9/45. (1) Sensors particularly resistant to welding machine electromagnetic fields.
2/90
Sensors for welding machine applications (1) Cylindrical type. Metal case, Teflon coated steel, threaded
2
a = 60 b = 40 = M30 x 1.5 Teflon front face 10 mm a = 60 b = 36 c=4 = M12 x 1 Teflon front face 4 mm
e, UL, CSA M12 connector IP 67 08 mm 3% of Sr 120% of Sr - 25+ 70 C Yellow LED, 4 viewing ports at 90 c 1224 V with protection against reverse polarity c 1036 V 0250 mA with overload and short-circuit protection y 2.5 V y 15 mA y 140 mT 250 Hz y 10 ms y 0.7 ms y 5 ms
03.2 mm
Setting-up
Minimum mounting distances (mm) Side by side Face to face Facing a metal object Mounted in a metal support
d h
d u 12, h d u 18, h d u 30, h d u 36, h u0 u0 u0 u8
e e
XS1 M12 flush mountable eu0 eu7 XS1 M18 flush mountable eu0 e u 16 XS1 M30 flush mountable eu0 e u 20 XS2 M12 non flush mountable e u 15 eu9 Fixing nut tightening torque: XS1 M12, XS2 M12: < 15 N.m, XS1 M18 : < 35 N.m, XS1 M30 : < 50 N.m
e e e e
u6 u9 u 20 u 11
2/91
Sensors for welding machine applications Cylindrical type. Metal case, plain, with shoulder
b a
Lengths (mm) : a = Overall b = To shoulder c = Removal d = shoulder Nominal sensing distance (Sn)
= 12 a = 55 b = 50 c = 9 (threaded) d = 15 hexagonal 3 mm 3 mm 3 mm
References
2-wire c (non polarised) Supply to terminals Weight (kg) 1-4 NO XSL C1401393L1 XSL C1401393L3 XSL C1401393L4
0.050
0.065
0.050
Characteristics
Connection Degree of protection conforming to IEC 60529 Operating zone Repeat accuracy Differential travel Operating temperature Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Residual current, open state Current consumption, no load Maximum switching frequency Delays Remote M12 connector, Remote M12 connector, length of cable: 1.2 m length of cable: 0.8 m IP 67 02.4 mm 3 % of Sr 115 % of Sr - 25+ 80 C LED (yellow), annular c 1248 V c 1058 V 1.5100 mA with overload and short-circuit protection 4V 0.5 mA 800 Hz First-up : 5 ms ; response : 0.5 ms ; recovery : 0.5 ms Remote M12 connector, length of cable: 0.15 m
Wiring schemes
2-wire c , non polarised, NO output
BN/1
+/ /+
BK/4
2/92
XSL C1401392L1
XSL C1401405L3
XSL C1401405L4
0.100
0.065
0.050
Remote M12 connector, length of cable: 1.2 m IP 67 05 mm 3 % of Sr 115 % of Sr - 25+ 70 C LED (yellow), annular c 1248 V c 1058 V 1.5100 mA with overload and short-circuit protection 4V 0.5 mA 100 Hz First-up : 10 ms ; response : 10 ms ; recovery : 2 ms
Setting up
Minimum mounting distances (mm)
Side by side Face to face Facing a metal object Mounted in a metal support
e e h
d = 12, h = 0
d e
XSL C
e 10 e 16
e 60 e 96
e 15 e 24
d = 54, h = 16
2/93
References
DF532016
XS2 ppSAppL2
NPN
DF532015
Function NO
Output PNP
Connection
Reference
Pre-cabled (L = 2 m) XS2 18SAPAL2 (1) M12 connector XS2 18SAPAM12 Pre-cabled (L = 2 m) XS2 18SANAL2 (1) M12 connector XS2 18SANAM12
NPN
18, plain
XS2 L2SAppL2
822116
Function NO
Output PNP
Connection
Reference
Pre-cabled (L = 2 m) XS2 L2SAPAL2 (1) M12 connector XS2 L2SAPAM12 Pre-cabled (L = 2 m) XS2 L2SANAL2 (1) M12 connector XS2 L2SANAM12
NPN
XS2 30SAppL2
503663
Accessories (2)
Description Plastic fixing clamp, 24.1 mm centres, with locking screw XSZ BS12
805817
Weight kg 0.007
Connecting cables
Description XUZ A118 Pre-wired M12 connectors Female, 4-pin, stainless steel clamping ring Type Straight Cable length m 2 5 10 2 5 10 2 5 Reference XZC PA1141L2 XZC PA1141L5 XZC PA1141L10 XZC PA1241L2 XZC PA1241L5 XZC PA1241L10 XZC RA151140A2 XZC RA151140A5 Weight kg 0.090 0.210 0.410 0.090 0.210 0.410 0.095 0.200
503663
Elbowed
M12 jumper cable Male, 3-pin, stainless steel clamping ring XSZ BS30
Straight
(1) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS2 12SAPAL2 becomes XS2 12SAPAL5 with a 5 m long cable. (2) For further information, see page 2/102.
2/94
Cylindrical, stainless steel, non flush mountable Three-wire, d.c. supply, solid-state output
Sensor type Product certifications/approvals Connection Connector Pre-cabled Operating zone 12 18 30 Differential travel Degree of protection Conforming to IEC 60529 DIN 40050 Storage temperature Operating temperature Materials Case Cable Vibration resistance Conforming to IEC 60068-2-6 Shock resistance Conforming to IEC 60068-2-27 Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity Voltage drop, closed state Current consumption, no-load Maximum switching XS2 12SApppp frequency XS2 18SApppp and XS2 L2pppp XS2 30SApppp Delays First-up Response Recovery
XS2 ppSAppM12 XS2 ppSAppL2 UL, CSA, e M12 Length: 2 m mm 05.6 mm 09.6 mm 017.6 % 1...15 of real sensing distance (Sr) IP 67 IP 68, double insulation i IP 69 K C - 40+ 85 (1) C - 25+ 85 Stainless steel, grade 316 L Non-poisonous PVC, 3 x 0.34 mm2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED: 4 viewing ports at 90 Yellow LED: annular V c 1224 with protection against reverse polarity V c 1036 mA y 200 with overload and short-circuit protection V y2 mA y 10 Hz 2500 Hz 1000 Hz 500 ms y 10 ms y 0.2 12, y 0.3 18, y 0.6 30 ms y 0.2 12, y 0.7 18, y 1.4 30 (1) + 100 C for cleaning and sterilization phases whilst not in service.
Wiring schemes
Connector
M12
4 3
Pre-cabled
BU: Blue BN: Brown BK: Black
PNP
BN/1 PNP BU/3
NPN
+
BK/4 (NO)
+
BK/4 (NO)
Setting-up
Minimum mounting distances (mm)
3 Sn
e e
Metal Metal
Object to be detected
12 18 30
Dimensions
XS2
(1)
7,9
XSZ BS12
XUZ A118
2,5 18,2
XSZ BS30
3,18 = 50 = 38,10 2,36 15 7,92 32,54 6,35 44,45
b a
11,1 22,4
28
35
28,6
(1) LED
XS2 12 18 30
Connector (mm) a b 61 37 70 42 70 36
16,5
1 6,5 60,33
c 5 8 13
30,2
10 = 6,5
20
2/95
References
523361
XS2 18SAMpL2
0.060
523362
XS2 18SAMpU20
0.145
523218
805817
Accessories
Description Stainless steel fixing bracket XUZ A118 For use with 18 sensor 30 sensor Reference XUZ A118 XSZ BS30 Weight kg 0.045 0.080
523364
(1) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS2 18SAMAL2 becomes XS2 18SAMAL5 with a 5 m long cable. (2) For further information, see page 2/102.
XSZ BS30
2/96
Cylindrical, stainless steel, non flush mountable Two-wire, a.c. or d.c. supply
XS2 ppSAMpU20 XS2 ppSAMpL2 UL, CSA, e 1/2" - 20UNF Length: 2 m mm 09.6 mm 0...17.6 % 1...15 of real sensing distance (Sr) IP 67 IP 68, double insulation i IP 69 K C - 40+ 85 (1) C - 25+ 85 Stainless steel, grade 316 L Non-poisonous PVC, 2 x 0.34 mm2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED: 4 viewing ports at 90 Yellow LED: annular V a or c 24240 (a 50/60 Hz) V a or c 20264 mA a 5300 or c 5200 (2) V y 5.5 mA y 0.8 Hz a 25 or c 1000 Hz a 25 or c 300 ms y 30 ms y 0.5 ms y 0.5 XS2 18SAM ppp, y 2 XS2 30SAMppp (1) + 100 C for cleaning and sterilization phases whilst not in service. (2) It is essential to connect a 0.4 A quick-blow fuse in series with the load.
Wiring schemes
Connector
1/2" - 20UNF
1
Pre-cabled
BU: Blue BN: Brown AC/DC : 2 t :1 AC/DC : 3
2-wire a or c
NO output
BN/2
/1
BU/3
Setting-up
Minimum mounting distances (mm)
3 Sn
e e
Metal Metal
Object to be detected
18 30
Dimensions
XS2
(1)
XSZ A118
2,5 50 18,2
XSZ BS30
b a
(1) LED XS2 18 30
3,18
35
c
28
= 38,10
7,92 2,36
6,5
10
32,54
6,5
20
: 2 elongated holes 7.14 x 29.36
60,33
16,5
Connector (mm) a b 72 44 74 40
c 8 13
15 1
2/97
References
DF535159
Function NO
Output PNP
Connection
Reference
Pre-cabled (L = 2 m) XS2 12AAPAL2 (1) M12 connector XS2 12AAPAM12 Pre-cabled (L = 2 m) XS2 12AANAL2 (1) M12 connector XS2 12AANAM12
2
18, threaded M18 x 1
Sensing dist. (Sn) mm 12
801167
Function NO
Output PNP
Connection
Reference
Pre-cabled (L = 2 m) XS2 18AAPAL2 (1) M12 connector XS2 18AAPAM12 Pre-cabled (L = 2 m) XS2 18AANAL2 (1) M12 connector XS2 18AANAM12
Function NO
Output PNP
Connection
Reference
Pre-cabled (L = 2 m) XS2 30AAPAL2 (1) M12 connector XS2 30AAPAM12 Pre-cabled (L = 2 m) XS2 30AANAL2 (1) M12 connector XS2 30AANAM12
Accessories (2)
Description Fixing clamps
825994
XSZ Bppp
Connecting cables
Description Pre-wired M12 connectors Female, 4-pin, stainless steel clamping ring Type Straight Cable length m 2 5 10 Elbowed 2 5 10 Reference XZC PA1141L2 XZC PA1141L5 XZC PA1141L10 XZC PA1241L2 XZC PA1241L5 XZC PA1241L10 Weight kg 0.090 0.190 0.370 0.090 0.190 0.370
Straight
2 5
0.090 0.190
(1) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS2 12AAPAL2 becomes XS2 12AAPAL5 with a 5 m long cable. (2) For further information, see page 2/102.
2/98
Cylindrical, plastic, non flush mountable Three-wire, d.c. supply, solid-state output
mm mm mm %
Conforming to IEC 60529 DIN 40050 C C Case Cable Conforming to IEC 60068-2-6 Conforming to IEC 60068-2-27
1...15 of real sensing distance (Sr) IP 67 IP 68, double insulation i IP 69 K - 40+ 85 - 25+ 85 PPS PvR and 3 x 0.34 mm2 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED: annular c 1248 for T - 25+ 70 C c 1224 for T + 70+ 85 C c 1058 for T - 25+ 70 C c 1036 for T + 70+ 85 C y 200 with overload and short-circuit protection y2 y 10 2500 1000 500 y 10 y 0.2 12, y 0.3 18, y 0.6 30 y 0.2 12, y 0.7 18, y 1.4 30
V V V V mA V mA Hz Hz Hz ms ms ms
Wiring schemes
Connector
M12
4 3
Pre-cabled
BU: Blue BN: Brown BK: Black
PNP
BN/1 PNP BU/3
NPN
+
BK/4 (NO)
+
BK/4 (NO)
Setting-up
Minimum mounting distances (mm)
3 Sn
e
Metal Metal
e
Side by side e u 48 e u 72 e u 120 Face to face e u 84 e u 144 e u 264 Facing a metal object e u 21 e u 36 e u 66
Object to be detected
12 18 30
Dimensions
XS2
Pre-cabled (mm) a b 50 42 60 51 60 51 Connector (mm) a b 61 43 70 52 70 52
b a
XS2 12 18 30
2/99
References
535156
XS2 ppAAMpL2
0.040
523382
0.080
XS2 ppAAMpU20
Accessories (2)
Description
535158
Fixing clamps
Weight kg 0.010
30
XSZ B130
0.020
XS2 30AAMpL2
Connecting cables
Description Pre-wired connectors 1/2" - 20UNF 3-pin female, stainless steel 316 L clamping ring Type Straight Cable length m 5 Reference XZC PA1865L5 Weight kg 0.180
10
XZC PA1865L10
0.350
825994
XZC PA1965L5
0.180
10
XZC PA1965L10
0.350
(1) For a 5 m long cable replace L2 by L5; for a 10 m long cable replace L2 by L10. Example: XS2 18AAMAL2 becomes XS2 18AAMAL5 with a 5 m long cable. (2) For further information, see page 2/102.
2/100
Cylindrical, plastic case, non flush mountable Two-wire, a.c. or d.c. supply
XS2 ppAAMpU20 UL, CSA, e 1/2" - 20UNF 09.6 0...17.6 1...15 of real sensing distance (Sr) IP 67 IP 69K - 40+ 85 - 25+ 85 PPS 25 gn, amplitude 2 mm (f = 10 to 55 Hz) 50 gn, duration 11 ms Yellow LED: annular a or c 24240 (a 50/60 Hz) a or c 20264 a 5300 or c 5200 (1)
XS2 ppAAMpL2
Length: 2 m
mm mm %
Vibration resistance Shock resistance Output state indication Rated supply voltage Voltage limits (including ripple) Switching capacity
Voltage drop, closed state Residual current, open state Maximum switching XS2 18AAMppp frequency XS2 30AAMppp Delays First-up Response Recovery
V y 5.5 mA y 0.8 Hz a 25 or c 1000 Hz a 25 or c 300 ms y 30 ms y 0.5 ms y 0.5 XS2 18AAMppp, y 2 XS2 30AAMppp (1) It is essential to connect a 0.4 A quick-blow fuse in series with the load.
Wiring schemes
Connector
1/2" - 20UNF
1
Pre-cabled
BU: Blue BN: Brown AC/DC : 2 t :1 AC/DC : 3
2-wire a or c
NO output
BN/2
/1
BU/3
Setting-up
Minimum mounting distances (mm)
3 Sn
e e
Metal Metal
Object to be detected
18 30
Dimensions
XS2
(1)
b a
(1) LED Pre-cabled (mm) a b 60 51 60 51
XS2 18 30
Connector (mm) a b 70 52 70 52
2/101
References
XSZ Bp00
XSZ Bp90
2
520695 520694
XSZ BC10
XSZ BE10
For use with sensors Type Clip mounting plate XSp J Mounting possible without XSp F clip on tapped holes XSp E XSp C Clip 90 mounting XSp J bracket XSp F Mounting possible without XSp E clip on tapped holes XSp C Replacement bracket XSp E Replaced: XS7 T2, XS8 T2, XSE XSp C Replaced: XS7 T4, XS7 C40, XS8 T4, XS8 C40 and XSC XSp D (for XSD) (1) Fixing clamp for XS9, XS6pppB2 remote control Fixing clamps XS1 XS1, XS2 XS1, XS2, XS4, XS5, XS6 XS1, XS2, XS4, XS5, XS6, XT1, XT4 XT1, XT4 Set of 2 fixing nuts, metal XS1 nickel chromed XS1, XS2, XS5, XS6 XS1, XS2, XT1, XS5, XS6 Set of 2 fixing nuts, stainless steel XS1, XS2, XS5, XS6 XS1, XS2, XT1, XS5, XS6 XS4 XS4, XT4
Description
Unit reference Diameter (mm) XSZ XSZ XSZ XSZ XSZ XSZ XSZ XSZ XSZ BJ00 BF00 BE00 BC00 BJ90 BF90 BE90 BC90 BE10
Weight kg 0.003 0.005 0.025 0.060 0.003 0.005 0.025 0.060 0.060
XSZ BC10
0.110
4 (smooth) 5 (M5 x 0.5) 6.5 (smooth) 8 (M8 x 1) 12 (M12 x 1) 18 (M18 x 1) 30 (M30 x 1.5) 32 (smooth) 5 (M5 x 0.5) 8 (M8 x 1) 12 (M12 x 1) 18 (M18 x 1) 30 (M30 x 1.5) 8 (M8 x 1) 12 (M12 x 1) 18 (M18 x 1) 30 (M30 x 1.5) 8 (M8 x 1) 12 (M12 x 1) 18 (M18 x 1) 30 (M30 x 1.5) 18 (M18 x 1) 30 (M30 x 1.5)
XSZ BD10 XSZ BPM12 XSZ B104 XSZ B105 XSZ B165 XSZ B108 XSZ B112 XSZ B118 XSZ B130 XUZ B32 XSZ E105 XSZ E108 XSZ E112 XSZ E118 XSZ E130 XSZ E308 XSZ E312 XSZ E318 XSZ E330 XSZ E208 XSZ E212 XSZ E218 XSZ E230 XSZ A020 XSZ A034
0.065 0.015 0.005 0.005 0.005 0.006 0.006 0.010 0.020 0.050 0.010 0.015 0.015 0.020 0.050 0.015 0.015 0.020 0.050 0.002 0.003 0.004 0.005 0.005 0.005 0.005 0.005 0.010 0.100 0.035 0.010 0.020
562271
XSZ BD10
562270
XSZ BPM12
825994
XSZ B1pp
825995
825996
XSZ A0pp
Adaptor collar
20 34
Protection accessories
12 (M12 18 (M18 30 (M30 Outer cover (IP 68) XT7 C Thread adaptor XSp, XTp 30 (M30 No. 13 plastic cable gland Clamping capacity 9 to 12 mm Protective cover M12 universal connectors Sold in lots of 50 Cable sleeve adaptor (CNOMO type) x 1) XSZ P112 x 1) XSZ P118 x 1.5) XSZ P130 XSC Z01 x 1.5) XTA Z30 XSZ PE13 XSZ F10
825997
Mounting parts
Thread inserts for rear fixing XSC Z01 XSpE XSpC XSpD Type M3 M4 M5 XSZ VF03 XSZ VF04 XSZ VF05 0.002 0.005 0.006
520935
XSZ F10
XTA Z30
2/102
Dimensions
XSZ BJ00
5,1 M3 9,9 19 12 M3
XSZ BF00
7 6,1 20 M3
5,5
22,5
15
34,5
27,5
M3
XSZ BE00
11,9 M3 10
XSZ BC00
M5 16
(1)
27,4
17
42
30
5,5
(1)
48,5
10
4,5 12
(1) 2 M3 x 12 screws supplied. (1) 4 M4 x 14 screws supplied.
77,2
XSZ BJ90
10,5 8 14 22,5 4
XSZ BF90
34,5 15 32
16
4,5
5,1
12 M3
M3
18,5
6,1 M3 M3
20
XSZ BE90
30,8 23,9
XSZ BC90
16
9 M3
(1)
(1)
27,4
17
10
30 M5
10
M3
42
2/103
Dimensions (continued)
XSZ BE10
XSZ BC10
M5 M3 35
42,5
30 2,8 41 55
2
25 39 42
XSZ BPM12
2 9 13,3 18 26
11
83,7 65 80
1,5
14
80
XSZ-B104, B105
15 6,7 8
12,5
41
3 8,5 12,3 = 9 = 4
XSZ B104 4 B105 5 Note: for saddle clamps XSZ B118 and XSZ B130, see setting-up recommendations page 2/17.
b2
(1)
a1 a
22
2/104
b1 3,5
Dimensions (continued)
XSZ B32
(2) (2)
25(1) 40
XSZ A0pp
a a1
20
= 15
50 60
=
XSZ A020 A034 a 18 30 a1 20 34
(1) Maximum value (2) 2 holes 5.5 Clamp supplied with two M5 screws, HM head
XSC Z01
(1)
34
= 69
XTA Z30
60 50,8 25,4 9,4 44,4
33,3
31
1,5
M30 x 1,5
2/105
22
49
Detection curves
3 2
3 2
2
mm 6 4 3 2
1 1
0,5
Sensor (mm) Standard steel target (mm) Operating zone (mm) 4 5x5x1 00.8 5 5x5x1 00.8 6.5 8x8x1 01.2 8 8x8x1 01.2 12 12 x 12 x 1 01.6 pick-up points drop-out points (object approaching from the side) 1 4 (plain) XS1 and 5 (M5 x 0.5) XS1 2 6.5 (plain) XS1 and 8 (M8 x 1) XS5 3 12 (M12 x 1) XS5
4 6 mm
1 15
10 8
Sensor (mm) Standard steel target (mm) Operating zone (mm) 18 18 x 18 x 1 04 30 30 x 30 x 1 08 pick-up points drop-out points (object approaching from the side) 1 18 (M18 x 1) XS5 2 30 (M30 x 1.5) XS5
5 2,5
mm15
10
7,5
2,5
2,5
7,5 10
15mm
Sensor (mm) Standard steel target (mm) Operating zone (mm) 12 12 x 12 x 1 03.2 pick-up points drop-out points (object approaching from the side) 1 12 (M12 x 1) XS4
1 0,5 mm 6 4 3 2 1 15 0 1 2 3 4 6 mm
10
8 5 2,5
Sensor (mm) Standard steel target (mm) Operating zone (mm) 18 24 x 24 x 1 06.4 30 45 x 45 x 1 012 pick-up points drop-out points (object approaching from the side) 1 18 (M18 x 1), XS4 2 30 (M30 x 1.5), XS4
mm15
10
7,5
2,5
2,5
7,5
10
15mm
Sensor (mm) Standard steel target (mm) Operating zone (mm) 6.5 8x8x1 02 pick-up points drop-out points (object approaching from the side) 1 6.5 (plain) XS1 L06pp349
1
2
1 0,5
mm 4
4 mm
2/106
Sensor (mm) Standard steel target (mm) Operating zone (mm) XS7 J1A1D 5x5x1 0...2 pick-up points drop-out points (object approaching from the side)
2
0 1 2 3 4 mm
mm -4 -3
-2
-1
5 4 3 2 1
Sensor (mm) Standard steel target (mm) Operating zone (mm) XS7 F1A1D 5x5x1 0...4 pick-up points drop-out points (object approaching from the side)
mm -8 -6
-4
-2
8 mm
12 10 8 6 4 2
Sensor (mm) Standard steel target (mm) Operating zone (mm) XS7 E1A1D 8x8x1 0...8 XS7 E1A1C 8x8x1 0...8 pick-up points drop-out points (object approaching from the side)
mm-10
-5
0
sensing distance (mm)
10 mm
16 14 12 10 8 6 4 2 mm -15 -10 -5 0 5 10 15 20 mm
Sensor (mm) Standard steel target (mm) Operating zone (mm) XS7 C1A1D 18 x 18 x 1 0...12 XS7 C1A1C 18 x 18 x 1 0...12 pick-up points drop-out points (object approaching from the side)
Sensor (mm) Standard steel target (mm) Operating zone (mm) XS7 D1A1D 30 x 30 x 1 0...32 XS7 D1A1C 30 x 30 x 1 0...32 pick-up points drop-out points (object approaching from the side)
2/107
Substitution table
Sensors with closest functionalities
2 2
Old sensor
Old sensor
Old sensor
(1) For the new (2) For the new (3) For the new (4) For the new
sensor an integral M12 connector replaces the M12 connector on a 0.80 m flying lead. sensor an M12 connector replaces the M8 connector. sensor an M8 connector replaces the M12 connector. Osiprox sensor the metal case replaces the plastic case.
2/108
Substitution table
Sensors with closest functionalities
0
0 0
Old sensor
Old sensor
Old sensor
(1) For the new sensor an integral M12 connector replaces the M12 connector on a 0.80 m flying lead. (2) For the new sensor an M12 connector replaces the M8 connector. (4) For the new Osiprox sensor the metal case replaces the plastic case. (6) For the new Osiprox sensor the length of the product is different. (8) For the new sensor, Sn = 10 mm instead of 8 mm.
2/109
Substitution table
Sensors with closest functionalities
0
0 0
Old sensor
Old sensor
Old sensor
XS3P18PA370L1 XS3P18PA370L2
(1) For the new (4) For the new (5) For the new (9) For the new
sensor an integral M12 connector replaces the M12 connector on a 0.80 m flying lead. Osiprox sensor the metal case replaces the plastic case. sensor, Sn = 15 mm instead of 20 mm. sensor, Sn = 20 mm instead of 15 mm.
2/110
Substitution table
Sensors with closest functionalities
0
0 0
Old sensor
Old sensor
Old sensor
(4) For the new Osiprox sensor the metal case replaces the plastic case. (5) For the new sensor, Sn = 15 mm instead of 20 mm. (7) For the new sensor, Sn = 8 mm instead of 10 mm.
2/111