Ceiling diffusers
Type DLQL
For clear room heights to approximately 4.0 m

The art of handling air

Contents Description
Description __________________________________ Construction Dimensions ______________________ Installation __________________________________ Directions of discharge ________________________ Nomenclature ________________________________ Quick selection ______________________________ 2 3 4 5 6 7 Acoustic data Supply air, top entry __________________________ 8 Supply air, side entry ________________________ 9 Extract air ________________________________10 Aerodynamic data ____________________________11 Order Details ________________________________12

DLQL...-H for side entry

DLQL...-V for top entry

Ceiling diffusers Type DLQL provide a comfortable air conditioning of rooms. The horizontal discharge takes place with high induction, which results in a rapid decay of supply air velocity and temperature differential over a short distance from the diffuser. Diffusers with one to four way discharge allow the best discharge configuration to be selected to match the room geometry and provide acceptable velocities in the occupied zone. The ceiling diffusers are suitable for all types of suspended ceiling systems. The frameless construction ideally blends with the design of the ceiling. For comfort conditioning of the occupied zone the diffusers can be used for room heights up to 4 m. Special characteristics Face plate made of powder-coated perforated sheet metal Face plate in various dimensions can be integrated into conventional ceiling systems Additional blanking plates to provide various air discharge directions 2

The ceiling diffusers consist of a sheet metal casing and a face plate made of perforated sheet metal. The construction with the side entry spigot is achieved using an additional universal plenum box. Supply air diffusers have a baffle plate on the rear of the perforated face plate.

Construction Dimensions
Characteristics
For supply or extract air Side or top entry spigot Recommended supply air temperature difference up to 10 K

Materials

Face plate made of perforated sheet metal for fitting into T-bar ceilings (T) or central fixing screw fastening for installation into grid or plasterboard ceilings (P) Supply air construction with baffle plate Spigot connection suitable for circular ducts according to EN 1506 or EN 13180 Option with groove for lip seal Additional blanking plates to provide various air discharge directions

Construction features

The DLQL...-H construction has an additional universal plenum box with side entry spigot. Plenum box suitable for DLQL Plenum box and flow rate control damper made of galvanised sheet steel Control damper for flow rate balancing (optional) See leaflet 2/16.4/EN/... for dimensions and technical data

Face plate made of galvanised perforated sheet steel, casing made of galvanised sheet steel Baffle plate made of acoustic non woven composite material Casing painted black (RAL 9005) Face plate powder-coated white (RAL9010)

Plenum box

DLQL...-H

DLQL...-V

50

9.5

B
H1

D2

Slot 6.4 11.4

D1

50

Nominal size 250 300 400 500 600

248 298 398 498 598

593 593 593 593 593

216 290 372 476 590

Dimensions in mm B C

198 272 354 458 572

111 111 131 156 189

D1 158 158 198 248 313

D2 123 158 198 248 313

258 258 303 353 418

H1

H2 28 34 44 55 64

DLQL...-H 2.8 4.0 6.5 13.8 9.6

Weight in kg

DLQL...-V 0.9 1.2 2.0 3.1 4.4

For P and T constructions the face plate size can be up to a max. of 623 mm Other dimensions for Q insert into item8 of order code

Plenum box AK

008 001 002 010 012

H2

Installation
The customer must install the ceiling diffusers, make all connections, and provide the hanging system, connection and sealing materials. Only trained expert personnel should install and make the appropriate connections. All legal regulations for site work must be complied with. The plenum box (side entry) has four suspension holes and the casing (top entry) has four hanging brackets for suspending the diffuser from the ceiling slab. Use only certified hanging systems.

Installation into grid and plasterboard ceilings Installation into T-bar ceilings

The face plate of the ceiling diffuser (DLQL-T) rests on the T-bar or on a similar profile. The casing rests on the back of the face plate but it must be supported separately from the ceiling slab.

The face plate of the ceiling diffuser (DLQL-P) is attached to the casing with a central fixing screw. In the case of large dimensions (above Q = 500 mm), the face plate is equipped with chamfered corners.

Grid ceiling DLQL...-P

Installation into suspended ceiling systems


DLQL...-H DLQL...-V

Hanging bracket

Suspension holes

Ceiling tile

Plasterboard ceiling DLQL...-P

Face plate

Plasterboard ceiling

T-bar ceiling DLQL...-T

Face plate

Ceiling tile placed on T-bar

Face plate

T-bar

Directions of discharge
Without blanking plates, the air is discharged horizontally and evenly on all sides (four-way). Alternative air discharge directions can be achieved with blanking plate accessories. A maximum of three blanking plates are placed in the ceiling diffuser. They can be arranged in any manner. Extract air ceiling diffusers have no blanking plates.

Directions of discharge

Air discharge four way

Blanking plate

Air discharge three way with one blanking plate

Air discharge two way with two blanking plates

Air discharge two way with two blanking plates

Air discharge one way with three blanking plates

Nomenclature
in m : Effective outlet area in l/s and m/h : Flow rate per diffuser in l/s and m/h : Flow rate for four way discharge diffuser For three, two and one way discharge enter diagram 11 using the following: three way: V = 1,33 V two way: V = 2,0 V one way: V = 4,0 V a, b in m : Spacing between two diffusers h in m : Distance between the ceiling and the occupied zone l in m : Distance from the diffuser l = x + h, l = a 2 or l = a 2 + h vl in m/s : Maximum time average air velocity at the wall at distance l = x + h or at the ceiling at distance a 2 vh1 in m/s : Maximum time average air velocity between two diffusers at distance l = a 2 + h
a V tZ

Aeff V V

Nomenclature

in K : Temperature difference between supply and room air th1 in K : Temperature difference between room air and core at distance l = a 2 + h tl in K : Temperature difference between room air and core at distance l = x +h pt in Pa : Total differential pressure LWA in dB(A) : A-weighted sound power level LWNC : NC rating of sound power level (LWNC = LWA 4 dB) Note the noise levels quoted are the dBA rating of sound power level LWA. To obtain typical room levels LPA LWA 5 dB.

tZ

l V tZ

vl

vh1 th1

vl tl

0.08 m

Quick selection
Supply air, top entry
Nominal size 250 300 400 500 600 l/s 16 25 36 6 9 Vmin m/h 23 33 58 91 Discharge one way 15 21 33 47 67 l/s V at 35 dB(A) m/h 120 168 239 55 76

Supply air, side entry


l/s V at 45 dB(A) m/h 105 162 228 320 77 pt 69 50 45 37 33 Nominal size 250 300 400 500 600 l/s 16 25 36 6 9 Vmin m/h 23 33 58 91

pt 35 26 25 20 19

Discharge one way 22 24 37 47 71 l/s V at 35 dB(A) m/h 133 167 255 80 85

21 29 45 63 89

pt 43 30 29 24 22

28 32 49 61 94

l/s

V at 45 dB(A) m/h 100 117 177 218 339

pt 68 57 51 40 39

131

131

Nominal size 250 300 400 500 600

13 18 32 50 73

l/s

Vmin

m/h 116 181 261 45 65

Discharge two way 25 34 111 55 74 l/s V at 35 dB(A) m/h 121 196 266 401 90

pt 28 23 21 17 17

35 45 144 71 97

l/s

V at 45 dB(A) m/h 124 162 256 349 518

pt 55 41 36 29 29

Nominal size 250 300 400 500 600

l/s

13 18 32 50 73

Vmin

m/h 116 181 261 45 65

Discharge two way l/s 30 36 58 77 V at 35 dB(A) m/h 109 130 210 277 420

pt

32 29 28 24 23

l/s

42 48 76

V at 45 dB(A) m/h 150 173 274 362 546

pt

62 52 47 40 39

117

100 152

Nominal size 250 300 400 500 600

19 27 109 48 76

l/s

Vmin

m/h 174 272 392 68 98

Discharge three way 34 44 159 74 99 l/s V at 35 dB(A) m/h 123 159 265 357 572 pt 26 23 19 16 17

47 128 202 58 96

l/s

V at 45 dB(A) m/h 168 209 345 460 726

pt 48 39 32 26 27

Nominal size 250 300 400 500 600

l/s

19 27 48 76

Vmin

m/h 174 272 392 68 98

Discharge three way l/s 36 44 76 V at 35 dB(A) m/h 131 158 272 362 568 pt 29 28 27 23 24

l/s

50 58 98

V at 45 dB(A) m/h 179 209 352 471 734

pt

55 49 46 39 40

109

101 158

131 204

Nominal size 250 300 400 500 600

25 101 145 36 65

l/s

Vmin

m/h 131 232 363 522 90

Discharge four way 41 120 198 56 91 l/s V at 35 dB(A) m/h 149 202 328 430 713

pt 24 22 18 16 16

116 151 252

56 73

l/s

V at 45 dB(A) m/h 200 261 427 545 908

pt 43 37 31 25 25

Nominal size 250 300 400 500 600

25 101 145 36 65

l/s

Vmin

m/h 131 232 363 522 90

Discharge four way 42 121 190 51 90 l/s V at 35 dB(A) m/h 150 182 324 435 683

pt 27 29 29 26 26

117 157 244

58 67

l/s

V at 45 dB(A) m/h 208 239 422 565 878

pt 52 50 48 44 43

Extract air, top connection


Nominal size 250 300 400 500 600 l/s V at 35 dB(A) m/h 260 416 753 882

Intake four way pt 24 28 27 21 23

Extract air, side connection


Nominal size 250 300 400 500 600 l/s V at 35 dB(A) m/h 327 375 605 824 pt 28 18 15 14 12

116 209 245 431

72

164 288 324 593

99

l/s

V at 45 dB(A) m/h 355 591

pt 45 56 50 37 43

Intake four way

Note the noise levels quoted are the dBA rating of sound power level LWA. To obtain typical room levels LPA LWA 5 dB.

1550

1036 1167 2136

104 168 229 385

91

122 145 228 304 519

l/s

V at 45 dB(A) m/h 438 523 820

pt 49 35 28 25 22

1387

1095 1867

Acoustic data
Supply air, top entry
Example 1
Given: Office Room width: 5.60 m Room depth: 2.80 m Room height: 3.00 m Total supply air flow rate to room: 200 l/s (720 m/h) Two ceiling diffusers, discharge four way, top entry Flow rate per diffuser: 100 l/s (360 m/h) Required sound power level per diffuser: 40 dB(A) Quick Selection: See page 7. DLQL...-V.../400 91 l/s at 35 dB(A) Result of selection: pt = 22 Pa (from Diagram 4) LWA = 38 dB(A) (from Diagram 4) For the aerodynamic data, see the continuation on page 11

Sound power level and total differential pressure


1
80 70 60 50 40 30 20 10 8 7 6

DLQL...-Z-V, discharge one way


Size 250
300 400
500

Total differential pressure pt in Pa

Total differential pressure pt in Pa

50

600

80 70 60 50 40 30 20

DLQL...-Z-V, discharge two way


Size 250
300 400

45

40

5 10

10

25

80 70 60 50 40 30 20

DLQL...-Z-V, discharge three way


Size 250
300 400

40

60

20

80 100

40

200

60

m /h 400
3

80 100

l/s

600

200

8 7 10

80 70 60 50 40 30 20

DLQL...-Z-V, discharge four way


Size 250
300

40

60

20

80 100

40

200

60

25

m /h 400
3

80 100

30

20

20

Total differential pressure pt in Pa

Total differential pressure pt in Pa

50

45

35 40 Lw in dB(A )

10

8 7 10

10

25

40

60 80 100

20

40

200 m /h 400
3

60 80 100

l/s

600

200

1000

300

8 7 20

80 100

40

200

60

80 100

20

20

400

l/s

25 3 Lw 0 35 in d B(A )
600 m /h 1000
3

30

200

40
300

45

50

500

600

400

35 4 Lw i n dB 0 (A)
l/s 600

30 Lw in d 35 B(A )

500

45
200
600

50

500

600

Acoustic data
Example 2
Given: Office Width: 5.60 m, depth: 2.80 m, height: 3.00 m Total supply air flow rate to room: 200 l/s (720 m/h) Two ceiling diffusers, discharge four way , side entry Take a flow rate control damper setting up to 45 into consideration. Flow rate per diffuser: 100 l/s (360 m/h) Required sound power level per diffuser: 40 dB(A) Quick Selection: See page 7. DLQL...-H.../400 90 l/s at 35 dB(A) Result of selection: pt = 36 Pa (from Diagram 8) Correction according to table: 36 1.1 = 40 Pa LWA = 39 dB(A) (from Diagram 8) Correction according to table 39 dB(A) + 1dB = 40 dB(A)

Supply air, side entry

Influence of flow rate control damper


Nominal size 250 300 400 500 600 45
pt

Correction values for diagrams 5 to 8 1.1 1.1 1.1 1.1 1.1 90 2 2 2 2 2 45 0 0 0

LWA

90

+1 +1

+1 +2 +1

Sound power level and total differential pressure


5
80 70 60 50 40 30 20

DLQL...-Z-H, discharge one way


Size 250 300
400 500

6
Total differential pressure pt in Pa

Total differential pressure pt in Pa

50

40 30 20

45

30

35 Lw i 40 nd B(A )

25

10

8 7 10

10 7 10 8 20 40 60

20

20
80 100

25

7
Total differential pressure pt in Pa

80 70 60 50 40 30 20

DLQL...-Z-H, discharge three way


Size 250
300 400

40

60

20

80 100

40

200

60

m /h 400
3

80 100

l/s

600

200

8
Total differential pressure pt in Pa

50

40 30 20

45

30 35 Lw in d 40 B(A )

25

20

10 7 20 8 40 60

10 8 720 40 60 80 100
l/s

80 100

200

m3/h 400

80 100

l/s

600 8001000

200

300

25

Lw
200 300

80 100

200

400

30

600 m3/h 1000

3 in d 5 B(A )

40

45

50

500

600

80 70 60 50

DLQL...-Z-H, discharge four way


Size 250 300

40

60

80 100

200

400

30 Lw i 35 nd B(A 40 )
400 l/s 600
200
500
600

45

50

600

80 70 60 50

DLQL...-Z-H, discharge two way


Size 250
300

400

500 600

Given: Office Extract air flow rate: 200 l/s (720 m/h) Required sound power level: 40 dB(A) One ceiling diffuser, top connection Quick Selection: DLQL...-V.../400 209 l/s at 35 dB(A)

Example 3

Acoustic data
Extract air

Result of selection: pt = 26 Pa (from Diagram 9) LWA = 34 dB(A) (from Diagram 9)

Influence of flow rate control damper


Nominal size 250 300 400 500 600 45 pt 90

Correction values for diagram 10 4.0 7.5 10.7 8.6 7.8 + 11 45

LWA

1.4 2.3 2.1 2.2 2.6

+8 +9 +8 +4

+ 15 + 12 + 14 + 12 + 11

90

Sound power level and total differential pressure


9
80 70 60 50 40 30 20

DLQL...-A - V

50

Size 250

300

400

Total differential pressure pt in Pa

Total differential pressure pt in Pa

500

600

10

80 70 60 50 40 30 20 10 8 7 6 5

DLQL...-A - H

Size 250

300

45

400

500

40

30 35 Lw i n dB (A)

8 7 V 40

10

25

20

200

60

80 100

400

600 8001000 m /h 2000


3

200

400 l/s 600 700

4 40

200

60

80 100

400

600 800 1000 m3/h 2000

200

20

25

10

Lw
400 l/s 600

30 35 in d B(A )

40

45

50

600

Aerodynamic data
Continuation of Examples 1 and 2
Given: Spacing between two diffusers: a = 2.8 m Distance between the ceiling and the occupied zone: h = 1.2 m Distance to wall: x = 1.40 m Result of selection: Flow rate for discharge four way V4 = V = 100 l/s Between two diffusers: a2 = 2.8 2 = 1.4 m vl = 0.45 m/s from Diagram 11 vh1 = 0.15 m/s from diagram 13 a 2 + h = 1.4 + 1.2 = 2.6 m tl tZ = 0.11 from Diagram 12

At the wall: l = x + h = 1.4 + 1.2 = 2.6 m vl = 0.27 m/s from Diagram 11 tl tZ = 0.11 from Diagram 12
Nominal size Aeff 250

Effective outlet area


0.0140

0.0103

300

0.0254

400

0.0360

500

0.0600

600

11

Air velocity vl at distance l

m No

a in

ize ls

25

30

0 40 0 50

60

vl

80 0.

60 0.

s m/

40 0.

V min

30 0.

20 0.

12

Temperature quotient
0.35 0.30 0.25 0.20 0.15 0.10
25 0 30

20 70

30 100

40 150

60 200

80 100 150 200 l/s 300 300 400 500 600 m/h 1000

13

Air velocity vh1 between two diffusers


2.0 1.6 1.2

2 3 Distance l (x + h or a 2) in m

No

tl tZ or th1 tZ

in al 0

40

h in m

50

siz e

60

1.0 0.8 0.6 0.4


0. 3

0. 4

0. 5

= 0. 0. 8 m 7 /s 0. 6

vl

0.05

Distance l (x + h or a 2 + h) in m

0.2

0.1

0.2

vh1 in m/s

0.3

0.4 0.5 0.6 0.7

11

Order Details

Supply air ceiling diffusers with a square perforated sheet metal face plate. Horizontal air discharge with high induction, which results in a rapid decay of supply air velocity and temperature differential over a short distance from the diffuser. Diffusers with one to four way discharge allow the best discharge configuration to be selected to match the room geometry. Special characteristics: Face plate made of powder-coated perforated sheet metal Face plate in various dimensions can be integrated into conventional ceiling systems Additional blanking plates to provide various air discharge directions Frameless construction, suitable for conventional grid and plasterboard ceilings. Consist of a sheet metal casing and face plate made of perforated sheet metal. Construction with side entry also has an additional universal plenum box. Supply air construction with baffle plate. Spigot connection with lip seal for circular connecting ducts according to EN 1506 or EN 13180.

Specification text*

Sound power level of the air-regenerated noise measured in accordance with EN ISO 5135. Materials Face plate made of galvanised perforated sheet steel; casing, sheet metal covers, plenum box, and flow rate control damper made of galvanised sheet steel. Baffle plate made of acoustic non woven composite material. Face plate powder-coated white (RAL9010) or another colour. Casing painted black (RAL 9005). Black baffle plate. Ceiling diffuser options: Frameless construction, suited for conventional T-bar ceilings. Plenum box with flow rate control damper for flow rate balancing Blanking plates for the configuration of the air discharge directions.
* Text for a DLQL for supply air and for grid or plasterboard ceilings, with plenum box for side entry and lip seal. Text for construction variants see our homepage.

Order code
DLQL - T - Z - H - M - L

500

618

P1

RAL 9006
10

Ceiling system -P Grid or plasterboard ceiling -T T-bar ceiling entilation system -Z Supply air -A Extract air

ype

Lip seal None, no entry required -L With lip seal Nominal size 250 300 400 500 600

10 Colour

Surface 0 Powder-coated, white (RAL 9010, gloss level 50 %) P1 Powder-coated RAL ... For P1 only RAL 9006 white aluminium, gloss level 30 % RAL ... other colours, gloss level 70 %

Connection -V Top entry -H Side entry


Subject to change All rights reserved TROX GmbH (2/2010)

Control damper for flow rate balancing None, no entry required -M With control damper

Size of face plate Dimensions P or T, no entry required ... Other dimensions

Side entry plenum only

Combination of white face plate with white baffle plate on request

Colours in RAL CLASSIC collection

Order example
Make: Type:

12

TROX DLQL -P -Z -H -M / 400 / P1 / RAL 9006

Order example: blanking plate


Make: Type: TROX DLQL-AB / 400