PIP ELCGL01D Data Sheet for Electrical Design Criteria

PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities, this Practice has been prepared from the technical requirements in the existing standards of major industrial users, contractors, or standards organizations. By harmonizing these technical requirements into a single set of Practices, administrative, application, and engineering costs to both the purchaser and the manufacturer should be reduced. While this Practice is expected to incorporate the majority of requirements of most users, individual applications may involve requirements that will be appended to and take precedence over this Practice. Determinations concerning fitness for purpose and particular matters or application of the Practice to particular project or engineering situations should not be made solely on information contained in these materials. The use of trade names from time to time should not be viewed as an expression of preference but rather recognized as normal usage in the trade. Other brands having the same specifications are equally correct and may be substituted for those named. All Practices or guidelines are intended to be consistent with applicable laws and regulations including OSHA requirements. To the extent these Practices or guidelines should conflict with OSHA or other applicable laws or regulations, such laws or regulations must be followed. Consult an appropriate professional before applying or acting on any material contained in or suggested by the Practice.

This Practice is subject to revision at any time by the responsible Function Team and will be reviewed every 5 years. This Practice will be revised, reaffirmed, or withdrawn. Information on whether this Practice has been revised may be found at www.pip.org.

Process Industry Practices (PIP), Construction Industry Institute, The University of Texas at Austin, 3925 West Braker Lane (R4500), Austin, Texas 78759. PIP member companies and subscribers may copy this Practice for their internal use. Changes, overlays, addenda, or modifications of any kind are not permitted within any PIP Practice without the express written authorization of PIP.

PIP will not consider requests for interpretations (inquiries) for this Practice.

Not printed with State funds

ASSOC. PIP: ELCGL01

DATA SHEET FOR ELECTRICAL DESIGN CRITERIA

ELCGLO1D
PAGE 1 OF 8 November 2002

Client: Project Title: Project Location: Project No.:

Engineering Org.: Location: Contract No.: Specifier Name:

Specification No.: Date: Equipment No.: Telephone No.: Purchaser Order No.:

Refer to PIP ELCGL01 for General Requirements.


3. System Design Criteria 3.2 Other Applicable Codes:

3.3 System Studies ! Load Flow ! Short Circuit ! Motor Starting ! Harmonic ! Transient Stability ! Underground Cable Thermal ! Ground Grid ! Load Summary ! Device Coordination Software: ___________________________________________________________________________________

3.4 Utility Interface Parameters Max. Voltage: _________________ Min. Voltage: _________________ Frequency: _________________ Max. Short Circuit MVA 3-Phase: ________ Min. Short Circuit MVA 3-Phase: ________ X/R: ______ Max Short Circuit MVA L-G: ________ Min. Short Circuit MVA L-G: ________ X/R: ______

3.5 Three-Phase System Voltage Parameters Bus Voltage Transformer Secondary Connection ! 13800 ! Wye ! Delta ! 12470 ! Wye ! Delta ! Wye ! Delta ! Wye ! Delta ! Wye ! Delta ! Wye ! Delta ! Wye 1-Phase ! 1-Phase ! 3-Phase ! Wye ! Delta

Grounding Method ! Solid ! Low Resistance ! High Resistance ! Solid ! Low Resistance ! High Resistance ! Solid ! Low Resistance ! High Resistance ! Solid ! Low Resistance ! High Resistance ! Solid ! Low Resistance ! High Resistance ! Solid ! High Resistance ! Ungrounded Solid Solid ! ! ! ! Solid Low Resistance High Resistance Ungrounded

Motor Horsepower Range _________ through _________

_________ through _________

! 7200

_________ through _________

! 4160

_________ through _________

! 2400

_________ through _________

! 480

_________ through _________

! 120/208 ! 120/240 Other Voltages ! ________

Less than ___________ hp

_______ through _________

ASSOC. PIP: ELCGL01

DATA SHEET FOR ELECTRICAL DESIGN CRITERIA

ELCGLO1D
PAGE 2 OF 8 November 2002

3.7 Motor-Starting Voltage Drop ! Required ! Not Required 3.7.2 Acceleration Study ! >600 Volts and 5000 Volts Motor-Rated Voltage Required System Starting Voltage at Bus: ! 90% ! ________% 3.7.3 600 Volts ! 85% ! ________% 3.7.6 >600 Volts and 5000 Volts >5000 Volts ! 85% ! ________% Motor-Rated Voltage Required System-Starting Voltage at Motor Terminals: ! 80% ! ________% 3.7.7 >600 Volts and 5000 Volts >5000 Volts ! 80% ! ________% ! Soft Start ! Other ______ 3.7.5 600-Volt Reduced Voltage Starting Method ! Captive Xfmr ! Soft Start ! Auto-Transformer 3.7.8 >600-Volt Reduced Voltage Starting Method

! >5000 Volts

! Other ___________

3.8 Design Allowance Feeder Cable Ampacity 3.8.1 Spare Capacity Transformer Capacity Above NEC Requirements Switchgear Bus Ampacity MCC Bus Ampacity MV Starters 3.8.2 Spare Devices MV Switchgear Circuit Breaker or Fused Switches Low-Voltage Switchgear Circuit Breakers Low-Voltage Starters (per MCC) 3.8.3 Equipped Spaces MV Starters (per Line-up) Low-Voltage Switchgear Circuit Breakers MV Switchgear Circuit Breakers MV Starters (per Line-up) Low-Voltage Switchgear Circuit Breakers MV Switchgear Circuit Breakers or Fused Switches Low-Voltage Starters (per MCC)

! 20% ! 20%

! _______% ! _______%

! 20% ! _______% ! 20% ! _______% _______ ! 2 Per Line-up ! 2 Per Sub _______ ! 2 Per Line-up ! 2 Per Sub _______ ! 2 Per Line-up ! 2 Per Sub Size 1 ________ Size 4 ________ Size 2 ________ Size 5 ________

! 2 Total Project ! 2 Total Project ! 2 Total Project Size 3 _________ Size 6 __________

Feeder Breakers: _________ Fused Switches: _________ ______ ! 2 Per Line-up ! 2 Per Bldg ! 2 Total Project ______ ! 2 Per Line-up ! 2 Per Bldg ______ ! 2 Per Line-up ! 2 Per Bldg ______ ! 2 Per Line-up ! 2 Per Bldg ______ ! 2 Per Line-up ! 2 Per Bldg ______ ! 2 Per Line-up ! 2 Per Bldg ! 2 Total Project ! 2 Total Project ! 2 Total Project ! 2 Total Project ! 2 Total Project

Unequipped Spaces

3.8.4 Future Unit Spaces

Size 1 _________ Size 2 _________ Size 3 ___________ Size 4 _________ Size 5 _________ Size 6 _____________ Feeder Breakers _________ Fused Switches _________

3.9 Power Factor Power Factor Correction Required: ! No ! Yes Minimum System Power Factor ______% ! At Utility Interface or ! Other _______________ Method(s) of Power Factor Correction: ! Capacitors ! On Major Power Bus ! On MCC Bus ! At Motor ! Fixed ! Other_________________________________________________________

! Switched

3.11 3.11.1 3.11.3

Electrical Equipment Rooms ! 2 or more doors ! No Locks

! 1 Door if Allowable per NEC ! Locks with Night Latch Feature

! Other ______ ! Other ______

4. Area Classification 4.1 " Per PIP ELEHA01 4.2 " Division Method

" Other_______________ " Zone Method

ASSOC. PIP: ELCGL01

DATA SHEET FOR ELECTRICAL DESIGN CRITERIA

ELCGLO1D
PAGE 3 OF 8 November 2002

5. Power Distribution 5.1 System Configuration ! Primary Loop ! Simple Radial ! Expanded ! Primary System System System Radial System Selective Configuration System Arrangements ! One Line Attached Document Number ________________________________

! Secondary Selective System

5.2 Utility Interface and Unit Substations 5.2.3 Primary or Utility Interface Substation ! Outdoor ! Open Bus ! ! Indoor ! Prefabricated Power ! Center HVAC Required ! Yes ! Elevation ! At Grade ! Unit Substations ! Outdoor ! NEMA 3R Walk-in ! ! Indoor ! Prefabricated Power ! Center HVAC Required ! Yes ! Pressurized ! Yes ! Elevation ! At Grade ! 5.2.4 Single-Ended Substation Expansion ! One Direction ! Two Directions 5.2.5 Future Conversion of Single-Ended to Double-Ended Substation ! Required ! Not Required 5.2.6 Double-Ended Substation Expansion ! One Direction ! Two Directions

! NEMA 3R Non-Walk-in Pressurization Required ! Yes ! No No Internal Temperature Range _______________ Elevated ________ Feet NEMA 3R Non-Walk-in Fabricated ! NEMA 3R ! NEMA 3R Non-Walk-in Building Walk-in No Internal Temperature Range _______________ No Elevated ________ Feet NEMA 3R Walk-in Fabricated in Place Building Number of Sections ______ ! None Required

Number of Sections ______

! None Required

5.3 Transformers 5.3.1 Power Transformers ! Liquid Filled ! Indoor ! Dry Type ! Indoor ! Cast Coil ! Indoor 5.3.2 Transformer Size Based On ! 650C Rise ! 550C Rise 5.3.4 ! Liquid Type: _________ ! Outdoor 5.3.5 Power Transformer Location ! PIP ELSTR01 5.3.5 Outdoor Transformer Spec ! PIP ELSTR03 5.3.5 Indoor Transformer Spec 5.3.6 Control Power and Lighting Transformers 5.3.7 Outdoor Control Power and Lighting Transformers

! Outdoor ! Outdoor ! Outdoor ! Other _________ ! ! ! ! ! Other _________ PIP ELSTR04 Other _________ 800C / 2200C Epoxy-Encapsulated

! Other __________ ! Other __________ ! Other __________

5.4 Metering, Monitoring, and Relaying 5.4.1 Metering " Voltmeter " Ammeter " Power Factor Meter " Watt-Hour Meter " kW Demand Meter " Microprocessor-Based " Other _____________ " Analog Meters with " Individual Phase Analog Meters Multifunction Metering Selector Switches 5.4.2 Communications Type: " None " RS232 " RS422 " RS485 " Other_____ Devices Monitored: " Circuit Breaker Protective Relays " Circuit Breaker " Multifunction Metering " Other_____ Trip Units Devices 5.4.3 Relay Selection " Microprocessor-Based Relay(s) " Solid State Relays " Electro-Mechanical Relays

ASSOC. PIP: ELCGL01

DATA SHEET FOR ELECTRICAL DESIGN CRITERIA

ELCGLO1D
PAGE 4 OF 8 November 2002

5.5 Switchgear 5.5.1 Low-Voltage Switchgear 5.5.2 Medium-Voltage Switchgear 5.5.3 Control Voltage

" MCCB Panelboard " Metal-Enclosed Drawout (PIP ELSSG01) " Metal-Clad " Metal-Enclosed " Metal-Enclosed (PIP ELSSG03) for (PIP ELSSG02) (PIP ELSSG03) Transformer Main Only LV Metal-Enclosed " 125 VDC Trip " Captrip Trip " 125 VDC Close " AC Close MV Metal-Clad " 125 VDC Trip " Captrip Trip " 125 VDC Close " AC Close MV Metal-Enclosed " 125 VDC Trip " Captrip Trip " 125 VDC Close " AC Close

5.6

Switchgear / Substation Batteries

" Flooded-Cell Lead-Acid per PIP ELSAP11

! Other _______________

5.7 Switchgear Rooms " Power Center per PIP ELSSG11 " Built-in-Place Block Walls

" NEMA 3R Walk-in per PIP ELSSG12 " Other ______________

" Built-in-Place Metal Walls

6.

Motors

" Installed per PIP ELIMT000

" Other _______________

7. 7.2 7.2.1

Motor Control 480-Volt Motor Control " Fused Disconnect Switch " Molded-Case Circuit " Motor Circuit Protector " Other _______ MCC Type (PIP ELSMC12) Breaker (PIP ELSMC13) (PIP ELSMC13) " NEMA 1 Gasketed " NEMA 12 7.2.2 MCC Indoor Enclosure Type " NEMA 3R " NEMA 4X " Other _________________ 7.2.4 MCC Outdoor Enclosure Type " Front Only " Back-to-Back 7.2.5 MCC Enclosure Arrangement " 20% Growth " Other _________________ 7.2.6 Indoor MCC Floor Space " NEMA 4X " NEMA 3R " Other _________________ 7.2.8 Outdoor Starters (Non-Classified) " Bolted " Threaded " Other _________________ 7.2.9 Explosion-Proof Starter Enclosures " Size 1 " Other _________________ 7.2.11 Minimum Starter Size " Electronic 7.2.12 Overload Protection " Eutectic Alloy " Class 10 " Class 20 " Class 30 " Bi-Metallic " Class 10 " Class 20 " Class 30

7.3 Low-Voltage Adjustable Speed Drives

" Per PIP ELSMC20

" Other_____________________________

7.4 Medium-Voltage Motor Control 7.4.1 For 2.3-kV Motors: Circuit Breaker Used as Motor Starter at _______ hp and above For 4-kV Motors: Circuit Breaker Used as Motor Starter at _______ hp and above 7.4.2 " Drawout (Roll-out) Contactor " Stationary (Bolt-in) Contactor 7.4.4 " Medium-Voltage Starters per PIP ELSMC11 " Other _____________________ 7.4.5 " Medium-Voltage Adjustable Speed Drive per PIP ELSMC21 " Other _____________________ 7.4.6 Microprocessor-Based Motor Protection Relay Type _________________ 7.4.7 " Differential Protection 1500 hp " Differential Protection _____ hp

ASSOC. PIP: ELCGL01

DATA SHEET FOR ELECTRICAL DESIGN CRITERIA

ELCGLO1D
PAGE 5 OF 8 November 2002

8. 8.1 8.2 8.2.2 8.2.3

Grounding Ground Grid Conductor " Bare " Covered System Grounding (Also See 3.5) " 480-Volt Delta per PIP ELSGS02 " 480-Volt Wye per PIP ELSGS01 " Low Resistance - XFMR Wye Neutral Resistor per PIP ELSGS11 High Resistance per the Following: " 2400-Volt Wye per PIP ELSGS03 " 2400-Volt Delta per PIP ELSGS04 " 4160-Volt Wye per PIP ELSGS05 " 4160-Volt Delta per PIP ELSGS06 " XFMR Wye Neutral Resistor per 8.2.4 Distribution System Grounding PIP ELSGS11 Method " Other___________________

" Other _______________ " Low Resistance Other ______________

" Zig-Zag Transformer

8.3 Equipment Grounding 8.3.1 Equipment Grounding Primary: ! Equipment Grounding Conductor Run with Power Wiring ! Use Raceways and Cable Tray ! Any Method Permitted by NEC 8.3.2 Medium-Voltage Motor Supplemental Grounding " Adjacent Building or Structure Steel " Reinforcing Mesh or Bars in the Concrete Foundation ! Bare Copper Conductor ! Uninsulated Tin-Coated Copper Conductor 8.3.3 460-Volt Motor Supplemental Grounding " Adjacent Building or Structure Steel " Reinforcing Mesh or Bars in the Concrete Foundation ! Bare Copper Conductor ! Uninsulated Tin-Coated Copper Conductor

Secondary: ! Visible Ground Conductor to Ground Grid or Grounded Steel Structure ! Use Raceways and Cable Tray ! None " Adequately Sized Bare or Green-Colored, Covered Copper Conductor around the Equipment Foundation and Connected to at Least Two Ground Rods or Ground Grid ! Covered Copper Conductor ! Not Required ! Required " Adequately Sized Bare or Green-Colored, Covered Copper Conductor around the Equipment Foundation and Connected to at Least Two Ground Rods or Ground Grid ! Covered Copper Conductor

8.4 Plant Grounding 8.4.1 Plant Grounding System " Effectively Grounded Metal Structure " Ground Loop 8.4.5 Ground Loop Conductor " " " "

" Driven Electrode System

" Concrete-Encased Electrode System

" XHHW Ground Electrodes " Rebar Connections to Ground Loop Ground Conductor Minimum Depth (below Surface) 8.4.7 " Bare Underground Cables Shall Be Tin-Coated.

No. 2/0 Bare Insulated Driven Rods

" No. 4/0 " THW " Buried Plate " Compression _____________ Inches

" Other _______________ " Other _______________ " Other _______________ " Exothermic

ASSOC. PIP: ELCGL01

DATA SHEET FOR ELECTRICAL DESIGN CRITERIA

ELCGLO1D
PAGE 6 OF 8 November 2002

9. 9.1 9.2 9.2.1

Lighting ! Per API RP540 Illumination Level Luminaires and Circuits Luminaire Type Areas ! ! ! ! ! ! Fluorescent Incandescent Metal Halide Fluorescent Metal Halide High-Pressure Sodium

! Other __________ Voltage Rating ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! ! 120 208 277 120 208 277 480 120 208 277 480 120 208 277 480 120 208 277 480 120 208 277 ! Astronomical Clock ! Other ____________________

General Building / Office

Shops, Warehouse, etc.

Floodlights, Roadway Lighting, Parking Lots, etc. Outdoor Process

! Metal Halide ! High-Pressure Sodium ! Metal Halide ! High-Pressure Sodium ! Fluorescent ! Metal Halide ! High-Pressure Sodium ! Fluorescent ! Incandescent ! Other __________________ ! Dedicated Photoelectric Cells ! ! ! ! ! Incandescent Fluorescent High-Pressure Sodium Instant Restrike Battery

Indoor Process

Control Room

9.2.2 Photoelectric Cell Control 9.2.3 Standby

! Photoelectric Cell Controlled Panels ! ! ! ! 120 208 277 480

9.2.4 Emergency Lighting Locations

! Per 9.2.4

! Per 9.2.4 and Other __________

10. 10.1 10.1.1 10.1.4

Power Receptacles and Convenience Outlets Receptacles ! No Receptacles Allowed in Div. 1 Areas Max. Receptacle Distance from Equipment ! 50 feet ! Other ________ GFCI Protected Receptacle Locations and ! Other Locations:_____________________________ ! Per NEC Type Voltage Phase Current Rating 10.1.3 Convenience 120 1 ! 15A (5-15R) ! 20A (5-20R) ! 30A (5-30R) ! ______ A Power 480 3 ! Not Allowed ! 30A ! 60A ! ______ A 10.2.1 10.2.4 480-Volt Plug Type _______________________

11. Wiring Methods 11.1 Cable Tray ! Aluminum ! Hot-Dipped Galvanized Steel ! Stainless Steel ! Fiberglass (Polyester) ! Fiberglass (Vinyl-Ester)

11.1.6 11.1.7

Spare Space in Tray Cable Tray Class Cable Tray Type Cable Tray Rung Spacing Cable Tray Covers " Required ! Separate Trays for Each Voltage Class

! 20% ! 40% ! ____% " 12C " 16C " 20C " _________________ " Ladder " Trough " _________________ " 6 " 9 " 12 " _________________ " Not Required " Comments _______________________________ ! Other_____________

ASSOC. PIP: ELCGL01

DATA SHEET FOR ELECTRICAL DESIGN CRITERIA

ELCGLO1D
PAGE 7 OF 8 November 2002

11.2 Aboveground Conduit and Fittings 11.2.1 Acceptable Types of Conduit " Rigid Galvanized Steel (RGS) 11.2.1 Acceptable Conduit Sizes " 1/2 11.2.9 Aboveground Corrosive Areas

" Rigid Aluminum

" EMT (See Section 11.2.2) " 3 " 4 " 5 " 6 " PVC " Fiberglass

" 3/4 " 1 " 1-1/4 " 1-1/2 " 2 " 2-1/2 " RGS " Rigid Aluminum " PVC-Coated Steel

11.3 11.3.1 11.3.3 11.3.6 11.3.9

Underground Conduit and Duct Banks Duct Bank " Rigid Galvanized Steel Conduit " Schedule 40 PVC Conduit Acceptable Underground Conduit Sizes " 1 " 1-1/4 " 1-1/2 " 2 " 2-1/2 " 3 Minimum Depth (Below Surface) ____________________________ Spare " 20% " Other __________________

" 4

" 5

" 6

11.4 11.5 11.6

Direct Burial Overhead Pole Lines Messenger Cable

" Not Allowed " Armored Cable " Not Allowed " Open Wire Support Method __________________

" Non-Armored Cable " Messenger

12. Power and Control Wiring 12.3 Cable Construction Low-Voltage ! TC " THWN/PVC Cable " XHHW/PVC Composite Cable

" THWN/CPE " XHHW/CPE " Acceptable " Not Acceptable

" THWN/CSPE " XHHW/CSPE Max Conductor

" _______________ Ground Wires " Reqd " Not Reqd " No. 4 " No. 2 " ______________

! MC

" THWN/PVC " THWN/CPE " XHHW/PVC " XHHW/CPE " Continuous Corrugated Aluminum Composite Cable " Acceptable " Not Acceptable ASD Motor Feeder Cable

" THWN/CSPE " _______________ " XHHW/CSPE Ground Wires " Reqd " Not Reqd " Interlocked Aluminum " Interlocked Galvanized Steel Max Conductor " No. 4 " No. 2 " ______________

! MC Required " RHW

! MC Not Required " _______________

! 1/C Medium-Voltage Power Cable 3/C

" THWN

" XHHW

" Copper Conductors " XLPE/PVC " EPR/PVC " Armored " XLPE/PVC " EPR/PVC " XLPE/CPE " EPR/CPE " Galvanized Steel " XLPE/CPE " EPR/CPE

" Aluminum Conductors " XLPE/CSPE " EPR/CSPE " Aluminum " XLPE/CSPE " EPR/CSPE " Other _______________ Ground Wires: " Reqd " Not Reqd

1/C

" Other _______________

12.5 Multiconductor Minimum Size 12.6 Composite Power/Control Cable

" No. 14 " Allowed

" No. 16 " Not Allowed

" Other _______________

12.8 Power Cable Termination Methods 600-V Cable " Not Specified 5-kV Cable " Tape 15-kV Cable " Tape

" Tape " Cold Shrink " Cold Shrink

" Reusable Boot " Heat Shrink " Heat Shrink

" Other _______________ " Other _______________ " Other _______________

ASSOC. PIP: ELCGL01

DATA SHEET FOR ELECTRICAL DESIGN CRITERIA

ELCGLO1D
PAGE 8 OF 8 November 2002

14. Freeze Protection and Process Heat-Tracing Systems Process Heaters 120 V 1.8 kW 480 V > 1.8 kW Electric Heat Tracing Types Allowed Voltage Self-Limiting Cable ! 120 V ! 208 V ! 240 V Constant Wattage Cable ! 120 V ! 208 V ! 240 V ! 120 V ! 208 V ! 240 V ! 277 V ! 480 V

! 1-Phase ! 1-Phase ! 3-Phase Sheath Required ! Tinned Copper ! Stainless Steel ! _________ ! Tinned Copper ! Stainless Steel ! _________ ! Copper ! Stainless Steel ! Inconel ! Other _________

Outer Jacket Required ! Fluoropolymer ! Thermoplastic Rubber ! None ! _____________ ! Fluoropolymer ! Thermoplastic Rubber ! None ! _____________

Mineral Insulated Cable

Control Types Allowed Continuity Monitoring Ground Fault Protection

! 480 V ! ________ ! Mechanical Thermostats ! Electronic Controllers ! Upper Temperature Limit Required ! None ! Third-Wire Monitor Circuit ! End Lights ! Current Indication ! EPD Breaker ! Integral in Controller Impedance Heating

! Microprocessor-Based System ! Current Flow Detection ! Other ___________________ ! ____________________

16.

Uninterruptible / Standby Power

16.1 Critical Power Supply Requirements: ________________________________________________________________________ UPS Required ! No 16.2 ! Yes ! PWM ! Ferroresonant ! Other _________________________ Battery-Operating Time @ 25o C (77o F) _________ Minutes Battery Type: ! Flooded Cell per PIP ELSAP15 ! Valve Regulated per PIP ELSAP16 Generator Required ! Yes ! No 16.3 Alternate Utility/Plant Feeder: ! Yes ! No

17. Skid-Mounted or Packaged Equipment ! Other ___________________ ! Per PIP ELSPS01

Other Requirements: