Sunteți pe pagina 1din 22

Catalogue

2013
Low voltage
EasyPact EZC
Moulded-case circuit breakers
from 15 to 630 A
LVED212091EN.indb 1 13-4-22 8:58
LVED212091EN.indb 2 13-4-22 8:58
1
EasyPact EZC
General contents
Presentation 2
Functions
and characteristics
A-1
Busbars B-1
Installation guide C-1
Catalogue numbers D-1
LVED212091EN.indb 1 13-4-22 8:58
2
So easy, so simple
With just three sizes of circuit breakers,
Schneider Electrics EasyPact
TM
EZC system is the
simple, universal solution to fit all low-voltage
protection needs.
> The fixed version is particularly adapted
to the OEM and Building markets, offering
optimum performance at a competitive price.
> The plug-in version offers an additional
function dedicated to the Marine market.
EasyPact
TM
EZC range complies
with worldwide standards :
IEC 60947-2
EN 60947-2
JISC8201-2-1/C8201-2-2 (annex 1 and 2)
GB 14048.2
NEMA-AB1
UL508
(1)
CSA22-2
(2)
IACS for Merchant Marine
(lnternational Association of Classifcation Societies:
ABS, BV, CCS, DNV, GL, KRS, LR, NK, RINA)**
(1) Only for the 250A and 400A models
(2) Only for the 100A and 250A models
With international certifications
and approvals by independent laboratories:
ASEFA, KEMA, TILVA, TV, UL
And compliance to RoHS Directive
(Restriction of Hazardous Substances)
Buildings
Marine
OEM
C
P
B
1
0
0
6
0
7
-
0
0
1
LVED212091EN.indb 2 13-4-22 8:58
3
Easy to choose
EasyPact
TM
EZC brings you easy solutions
> From 15 A to 630 A
> Up to 50 kA at 415 V
> Up to 4 poles
> In only three frame sizes
> With a complete range of auxiliaries: rotary
commands, auxiliaries, shunt trip, phase barrier,
terminal cover, undervoltage trip
EasyPact
TM
EZC:
Build your complete
solution with
Schneider Electric
Easy to install
> Fixed front mounting
> Plug-in mounting
> Front connexions
> Bare cables connected through cable lugs,
screwed inside the breaker
> Field-installable auxiliaries and accessories
> Built-in earth-leakage protection
> Interchangeable MCCB and ELCB
Easy to use
> A thermal calibration suitable for MCCB use
at 50 C without derating
> Positive contact indication for safety and
reliability
> A smaller case optimized for tight spaces
Timely
delivery,
wherever
you are
Schneider Electric
offers a world-
renowned logistics
network capable of
getting EasyPact
TM
EZC products to you
fast, wherever you
are.
EasyPact
TM
EZC 250 ELCB
Built-in Integrated Earth-Leakage Circuit
Breaker (ECLB) function
fully interchangeable with MCCB
same MCCB foot print and
panel cut
15 A
7.5
10
15
18
25
30
36
EZC100B
EZC100F
EZC100N
EZC250F
EZC250N
EZC250H
EZCV250N
EZCV250H EZC400N
EZC400H
EZC100H
50
Breaking capacity
Icu kA at 400/415 V AC
60 A 100 A 250 A 400 A
EZC630N
EZC630H
630 A
D
B
4
0
2
6
8
9
_
0
1
LVED212091EN.indb 3 13-4-22 8:58
4
Make the most of your energy
The new plug-in
accessory reduces
installation and
maintenance time.
Accessories
The ZOIVUL, designed for vertical installation, saves space
and reduces cabling time.
P
B
1
0
4
9
0
3
C
P
B
1
0
0
6
0
9
C
P
B
1
0
0
6
1
0
LVED212091EN.indb 4 13-4-22 8:58
A-1
EasyPact EZC
Functions and characteristics
Presentation II
General characteristics A-2
Selection table A-6
Electrical and mechanical accessories overview A-10
EasyPact EZC100 A-10
EasyPact EZC250 A-11
EasyPact EZCV250 A-12
EasyPact EZC400-630 A-13
Electrical auxiliaries 100-250AF
AX - AL - AXAL - ALV A-14
SHT - UVR - UVRN A-16
Direct rotary handle 100-250AF A-18
Extended rotary handle 100-250AF A-19
Plug-in
100 A A-20
Insulation of live parts A-21
250 A A-22
Insulation of live parts A-23
Power connections and cable lugs 100-250AF A-24
Power connections and insulation of live parts
100-250AF A-25
DIN rail adaptor, padlocking, sealing screws 100-250AF A-26
Accessories and auxiliaries of EZC400-630
Connection of devices A-28
Selection of auxiliaries A-30
Indication contacts A-31
Remote tripping A-32
Rotary handles escutcheons and protection collars A-33
Locks and sealing accessories A-34
Busbars B-1
Installation guide C-1
Catalogue numbers D-1

LVED212091EN.indb 1 13-4-22 8:58
A-2
Functions
and characteristics
Compliance with standards
EasyPact EZC circuit breakers and auxiliaries comply with the following international
standards:
b IEC 60947-1 - general rules
b IEC 60947-2 - low-voltage switchgear and controlgear, part 2 (circuit breakers)
b European (EN 60947-1 and EN 60947-2) and the corresponding national
standards
b GB 14048.2
b JIS C8201-2-1 Annex 1 and Annex 2, for molded case circuit breakers
b JIS C8201-2-2 Annex 1 and Annex 2, for earth-leakage circuit breakers
b NEMA-AB1 (High Interrupting Capacity): American standard
b UL508/CSA 22-2 no. 14.
ApprovaIs and Certications
b EC certifcation by independent laboratories (ASEFA, KEMA, TV)
b marking
b certifed by third party Tilva

b certifed by third party Underwriter Laboratories as a "Manual Motor
Controller (EZC250/EZCV250).
Vibration and shock withstand test
EasyPact EZC circuit breakers resist mechanical vibrations and shocks.
Tests are carried out in compliance with standard IEC 60068-2-6 for the levels
required by merchant-marine inspection organisation IACS:
nternational Association of Classifcation Societies up to 250 A (ABS, BV, DNV, GL,
LR, KRS, RNA, NK):
b 2 to 13.2 Hz: amplitude 1 mm
b 13.2 to 100 Hz: acceleraton 0.7 g.
Pollution degree
EasyPact EZC circuit breakers are certifed for operation in pollution-degree
environments as defned by EC standard 60947 (industrial environments).
Tropicalisation
EasyPact EZC circuit breakers have successfully passed the tests prescribed by the
following standards for extreme atmospheric conditions:
b IEC 60068-2-1 - dry cold (-55 C)
b IEC 60068-2-2 - dry heat (+85 C)
b IEC 60068-2-30 - damp heat (95 % relative humidity at 55 C)
b IEC 60068-2-52 - salt mist (severity level 2).
Positive contact indication
All EasyPact EZC circuit breakers are suitable for isolation as defned in EC
standard 60947-2:
b the isolation position corresponds to the O (OFF) position
b the operating handle cannot indicate the O (OFF) position ("green colour visible)
unless the contacts are effectively open
b padlocks may not be installed unless the contacts are open
b installation of a rotary handle does not alter the reliability of the position-indication
system.
The isolation function is certifed by tests guaranteeing:
b the mechanical reliability of the position indication system
b the absence of leakage currents
b overvoltage withstand capacity between upstream and downstream connections.
EasyPact EZC circuit breakers take into account important concerns for
environmental protection. Most components are recyclable and the parts are marked
as specifed in applicable standards.
Example for 250 A frame.
Standardised characteristics indicated on the rating plate:
Ui: rated insulation voltage
Uimp: rated impulse withstand voltage
Ue: rated operational voltage
Icu: ultimate breaking capacity, for various values of the
rated operational voltage Ue
Cat: utilisation category
Ics: service breaking capacity
In: rated current
suitability for isolation
General characteristics0

C
D
B
5
0
0
6
1
1
C
D
B
5
0
0
6
1
2
C
D
B
5
0
0
6
1
3
C
P
B
1
0
0
6
0
2
Ui=690Va 50/60Hz Uimp=6kV Cat.A 40C
IEC 60947-2 Ue (V) Icu/Ics (kA)
JIS C8201-2-1 230/240a 85 / 43
400/415a 36 / 18
440 a 25 / 13
550 a 10 / 5
250 c 30 / 15
NEMA - AB1 U (V) HIC (kAmps)
240 a 85
277/480a 25
DL 06253
EasyPact
TM
EasyPact EZC 250
LVED212091EN.indb 2 13-4-22 8:58
A-3
Ambient temperature
b EasyPact EZC circuit breakers has been particularly designed to hold 100 % In at
50 C without tripping in normal condition (except for earth-leakage circuit breakers).
b EasyPact EZC circuit breakers may be used between -25 C and +70 C.
b The permissible storage-temperature range for EasyPact EZC circuit breakers in
the original packing is -35 C to +85 C.

Installation
EasyPact EZC circuit breakers are designed for easy installation in the various types
of switchboards. They may be mounted vertically, horizontally or fat on their back
without any derating of characteristics.
Installation positions.


Reverse feeding.
Power supply
EasyPact EZC circuit breaker can be supplied from either the top or the bottom
(reverse feeding) without any reduction in performance. For earth-leakage circuit
breakers, reverse feeding is possible only up to 240 V AC.
This capability facilitates connection when installed in a switchboard.
Degree of protection
As per standards IEC 60529 (IP degree of protection) and EN 50102
(K degree of protection against external mechanical impacts).
Bare circuit breaker with terminal shields

With toggle IP20 K07

With direct rotary handle standard IP40 K07
Circuit breaker installed in a switchboard

With toggle IP40 K07

With direct rotary handle
standard/VDE MCC
IP54 K07

With extended rotary handle IP54 K08
D
B
1
1
6
3
7
4
D
B
1
1
6
3
7
5
D
B
1
1
6
3
7
6
D
B
1
1
6
3
7
7
D
B
1
1
6
3
7
8
D
B
1
1
6
3
8
0
D
B
1
1
6
3
8
1
D
B
1
1
6
3
7
9
LVED212091EN.indb 3 13-4-22 8:58
A-4
Functions
and characteristics
Earth-leakage protection
EasyPact EZC circuit breakers have a specifc version including earth-leakage
protection.
This protection is fully integrated inside the breaker and does not require any
additional space.
EasyPact EZC circuit breakers and earth-leakage circuit breakers are fully
interchangeable.
Compliance with standards
EasyPact EZC earth-leakage circuit breakers comply with all the international
standards listed page A-2:
b IEC 60947-1
b IEC 60947-2
b EN 60947-1
b EN 60947-2
b GB 14048.2
b JIS C8201-2-2 Annex 1 and Annex 2
b NEMA-AB1 (High Interrupting Capacity)
b UL508/CSA 22-2 no. 14.
They also comply with:
b VDE 664, operation down to -25 C
b IEC 60255-4 and IEC 60801-2 to 60801-5 covering protection against nuisance
tripping due to transient overvoltages, lightning strikes, switching of devices on the
distribution system, electrostatic discharges, radiofrequency interference.
Power supply
Reverse feeding
EasyPact EZC earth-leakage circuit breakers can be supplied from either the top or
the bottom for voltages up to 300 V AC. For voltages over 300 V AC, only supply
from the top is possible (Line-Load indication on the cover of the breaker).
Power supply of the electronics
EasyPact EZC earth-leakage circuit breakers are self-supplied by the distribution-
system voltage and therefore do not require any external source. They fully comply
with new IEC requirements (Annex B): they are powered from the three phases and
continue to function even if one phase is missing.
Dielectric tests
EasyPact EZC earth-leakage circuit breakers are equipped with a disconnecting
switch in order to protect the electronics during dielectric tests.
When the disconnecting switch is activated, the circuit breaker is automatically
tripped. It is mechanically impossible to switch on the circuit breaker, until the
earth-leakage function is re-energised.
Tripping features
Tripping indications:
b EasyPact EZC earth-leakage circuit breakers have a yellow mechanical indicator
to locally signal tripping due to an earth fault.
b EasyPact EZC earth-leakage circuit breakers may be equipped with an earth-
leakage alarm switch (ALV) to remotely signal tripping due to an earth fault.
Resetting
EasyPact EZC earth-leakage circuit breakers are fully reset by the operating handle.
After resetting, tripping indicators (mechanical and ALV) come to normal position.

1 Line-Load (Ue > 300 V AC)
2 Mechanical indicator (ELCB)
3 Adjustable settings IDn and time delay
4 ELCB test button
5 Push to trip button (MCCB)
6 Dielectric tests: disconnecting switch
ELCB protection characteristics
Sensitivity IDn (A)
adjustable 0.1 - 0.3 - 0.5 - 1
Time delay Intentional delay (ms) adjustable 0 - 200 - 500 - 1000
Max. breaking time (s) 0.15 0.4 1 - 2
Rated voltage AC 50/60 Hz (V) 100440
General characteristics (cont.) 0

C
P
B
1
0
0
6
1
1
D
B
1
2
5
8
0
3
LVED212091EN.indb 4 13-4-22 8:58
A-5
Earth-leakage circuit breakers
With three built-in protections:
b overload
b short-circuit
b earth-leakage.
From 63 A to 250 A
With adjustable sensibility and time delay
Up to 36 kA at 415 V
In 3 poles and 4 poles
EasyPact
TM

D
B
1
2
5
8
0
5
LVED212091EN.indb 5 13-4-22 8:58
A-6
Functions
and characteristics
EZC100-1P.
EasyPact EZC circuit breakers
Fixed version
Plug-in version
Number of poles
Rated current (A) In at 40 C
Rated insulation voltage (V) Ui
Rated impulse withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Electrical characteristics as per IEC 60947-2, EN 60947-2, JIS C8201-2-1
Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz 110/130 V
220/230/240 V
380 V
400/415 V
440 V
550 V
DC 125 V (1P)
250 V
(2P in series)
Rated service breaking capacity (kA rms) Ics % Icu 110-400 V
415-550 V
Suitability for isolation
EZC100-2P. Utilisation category
Pollution degree
Endurance (C-O cycles) Mechanical
Electrical In/415 V
Electrical characteristics as per NEMA-AB1
Breaking capacity (kA rms) HIC AC 50/60 Hz 240 V
277/480 V
Protection
Overload protection Bimetal
Instantaneous protection Magnetic Fixed (20 %)
Auxiliaries
Indication contacts Auxiliary switch AX
Alarm switch AL
EZC100-3P. Combined AX + AL AXAL
Voltage releases Shunt trip release SHT
Undervoltage release UVR
Installation
Connection Crimp lugs/bars
Accessories Box lugs for bare cables
Rotary handles Direct
Extended
Terminal extensions
Spreaders
Phase barriers
Terminal shields
Padlocking system
EZC100-4P. DIN rail adaptor
Dimension and weight
Dimensions (mm) D x H
W
Weight (kg)
EZC250-3P.
Selection table
C
P
B
1
0
0
6
0
0
C
P
B
1
0
0
6
0
1
C
P
B
1
0
0
6
0
2
C
P
B
1
0
0
6
0
3
C
P
B
1
0
0
6
0
4
LVED212091EN.indb 6 13-4-22 8:58
A-7
EZC100B EZC100F EZC100N EZC100H EZC250F EZC250N EZC250H
b b b b b b b b b
b b
- b
(4)
- b
(4) b b b
3 3 1 3-4 1 2-3-4 3 3 2-3
15, 16, 20, 25,
30, 32, 40, 45,
50, 60
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
15, 16, 20, 25,
30, 32, 40, 45,
50, 60, 63, 75,
80, 100
100, 125, 150,
160, 175, 200,
225, 250
100, 125, 150,
160, 175, 200,
225, 250
100, 125, 150,
160, 175, 200,
225, 250
690 690 690 690 690 690 690 690 690
6 6 6 6 6 6 6 6 6
550 550 415 550 415 550 550 550 550
- 250 125 250 125 250 250 250 250
10 25 25 25 50 100 25 50 85
10 25 18 25 25 100
(1)
25 50 85
7.5 10 2.5 18 5 30 18 25 36
7.5 10 2.5 15 5 30 18 25 36
5 7.5 - 10 - 20 15 20 25
2.5 5 - 5 - 10 5 8 10
- 5 5 5 10 10 5 20 30
- 5 - 5 - 10 5 20 30
25 % 50 % 50 % 50 % 50 % 50 % 50 % 50 % 50 %
25 % 50 % 50 % 50 % 50 % 25 % 50 % 50 % 50 %
b b b b b b b b b
A A A A A A A A A
3 3 3 3 3 3 3 3 3
8 500 8 500 8 500 8 500 8 500 8 500 10 000 10 000 10 000
1 500 1 500 1 500 1 500 1 500 1 500 5 000 5 000 5 000
- - 10 25 18 100 25 50 85
- - 10
(2)
10 18
(2)
18
(3)
15 18 25
(3)
fxed fxed fxed fxed fxed fxed fxed fxed fxed
fxed fxed fxed fxed fxed fxed 10 In 10 In 10 In
b b
-
b
-
b b b b
b b
-
b
-
b b b b
b b
-
b
-
b b b b
b b
-
b
-
b b b b
b b
-
b
-
b b b b
b b b b b b b b b
b b b b b b b b b
b b
-
b
- b
(3) b b b
b b
-
b
- b
(3) b b b
- - - - - -
b b b
b b
-
b
-
b b b b
b b b b b b b b b
b b
-
b
- b
(3) b b b
b b b b b b b b b
b b b b b b
- - -
60 x 130 60 x 130 60 x 130 60 x 130 60 x 130 60 x 130 60 x 165 60 x 165 60 x 165
75 75 25 75 (3P)
100 (4P)
25 50 (2P)
75 (3P)
100 (4P)
105 105 105
0.78 0.78 0.28 0.78 (3P)
1.0 (4P)
0.28 0.6 (2P)
0.78 (3P)
1.0 (4P)
1.3 1.3 1.1 (2P)
1.3 (3P)
(1) 50 kA for 2 poles.
(2) For 277 V only.
(3) For 3 and 4 poles only.
(4) For 3P only.

LVED212091EN.indb 7 13-4-22 8:58
A-8
Functions
and characteristics
EasyPact EZC circuit breakers
Fixed version
Plug-in version
Number of poles
Rated current (A) In at 40 C
Rated insulation voltage (V) Ui
Rated impulse withstand voltage (kV) Uimp
Rated operational voltage (V) Ue AC 50/60 Hz
DC
Electrical characteristics as per IEC 60947-2, EN 60947-2 and JIS C8201-2-1/C8201-2-2
EZC250-4P. Ultimate breaking capacity (kA rms) Icu AC 50/60 Hz 220/230 V
380 V
400/415 V
440 V
550 V
DC 125 V (1P)
250 V
(2P in series)
Rated service breaking capacity
(kA rms)
Ics % Icu
Suitability for isolation
Utilisation category
Pollution degree
Endurance (C-O cycles) Mechanical
Electrical In/415 V
Electrical characteristics as per NEMA-AB1
EZCV250-4P. Breaking capacity (kA rms) HIC AC 50/60 Hz 240 V
277/480 V
Protection
Overload protection Bimetal
Instantaneous protection Magnetic fxed ( 20 %)
Earth-leakage protection
Sensitivity (A) IAn adjustable
Time-delay (ms) At adjustable
Max. breaking time (s) at 2 An
Auxiliaries
Indication contacts Auxiliary switch OF/AX
Alarm switch SD/AL
Combined AX + AL AXAL
Earth-alarm switch ALV
Voltage releases Shunt trip release MX/SHT
Undervoltage release MN/UVR
Installation
EZC400-3P. Connection Crimp lugs / bars
Accessories Box lugs for bare cables
Rotary handles Direct
Extended
Terminal extensions
Spreaders
Phase barriers
Terminal shields
Padlocking system
Dimension and weight
Dimensions (mm) D x H
W
Weight (kg)
Selection table (cont.) 0

C
P
B
1
0
0
6
0
5
C
P
B
1
0
0
6
0
6
C
P
B
1
0
0
6
0
7
LVED212091EN.indb 8 13-4-22 8:58
A-9
EZC250N EZC250H EZCV250N EZCV250H EZC400N EZC400H EZC630N EZC630H
b b b b b b b b
b b b b
- - - -
4 4 3-4 3-4 3-4 3-4 3-4 3-4
63, 80, 100, 125,
150, 160, 175,
200, 225, 250
63, 80, 100, 125,
150, 160, 175,
200, 225, 250
63, 80, 100, 125,
150, 160, 175,
200, 225, 250
63, 80, 100, 125,
150, 160, 175, 200,
225, 250
320, 350, 400 320, 350, 400 400, 500, 600 400, 500, 600
690 690 440 440 690 690 690 690
6 6 6 6 6 6 6 6
550 550 440 440 440 440 440 440
250 250 - - 250 250 250 250

50 85 85 100 40 70 40 70
25 36 25 36 36 50 36 50
25 36 25 36 36 50 36 50
20 25 20 25 36 50 36 50
8 10 - - - - - -
20 30 - - - - - -
20 30 - - - - - -
50 % 50 % 50 % 50 % 50 % 50 % 100% (220-415V)
50% (440V)
100% (220-415V)
50% (440V)
b b b b b b b b
A A A A A A A A
3 3 3 3 3 3 3 3
10 000 10 000 10 000 10 000 10 000 10 000 10 000 10 000
5 000 5 000 5 000 5 000 4 000 4 000 3 000 3 000
50 85 50 85 50 85 50 85
18 25 - - 25 35 25 35

fxed fxed fxed fxed fxed fxed fxed fxed
10 In 10 In 10 In 10 In 10 In 10 In 10 In (400/500A)
5000A (600A)
10 In (400/500A)
5000A (600A)

- - 0.1/0.3/0.5/1 0.1/0.3/0.5/1 - - - -
- - 0/200/500/1000 0/200/500/1000 - - - -
- - 0.15/0.4/1/2 0.15/0.4/1/2 - - - -

b b b b b b b b
b b b b b b b b
b b b b
- - - -
- -
b b
- - - -
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b
b b b b b b b b

68 x 165 68 x 165 68 x 165 68 x 165 140 x 255 140 x 255 140 x 255 140 x 255
140 140 105 (3P)
140 (4P)
105 (3P)
140 (4P)
140 (3P)
185 (4P)
140 (3P)
185 (4P)
140 (3P)
185 (4P)
140 (3P)
185 (4P)
1.8 1.8 1.6 (3P)
2.1 (4P)
1.6 (3P)
2.1 (4P)
4.8 (3P)
6.4 (4P)
4.8 (3P)
6.4 (4P)
4.8 (3P)
6.4 (4P)
4.8 (3P)
6.4 (4P)
LVED212091EN.indb 9 13-4-22 8:58
A-10
Functions
and characteristics
Electrical and mechanical
accessories overview
EasyPact EZC100

EasyPact EZC circuit breaker EZC100 comes with a full range of accessories to
fulfll different application requirements and make it easy for the end-user.

Terminal shield Phase
barriers
Plug-in
Din rail
adaptor
Cable lugs
> 50 A
Spreaders
Cable lugs
> 50 A
Sealing screws
Shunt trip (SHT)
Under voltage release (UVR)
Auxiliary switch (AX)
Alarm switch (AL)
Auxiliary/Alarm switch
(AX + AL)
Padlocking system
Cable lugs
> 50 A Spreaders
Cable lugs
> 50 A
Fishbone
connectors
Plug-in
connectors
Short terminal
shield
Terminal shield
Phase
barriers
Sealing screws
Direct rotary handles
Extended rotary handles
Short terminal
shield
P
B
1
0
4
9
0
9
LVED212091EN.indb 10 13-4-22 8:58
A-11
EasyPact EZC circuit breaker EZC250 comes with a full range of accessories to
fulfll different application requirements and make it easy for the end-user.
EasyPactTM


EasyPact EZC250

Terminal shield Phase
barriers
Spreaders
Cable lugs
Terminal
extensions
Direct rotary handles
Extended rotary handles
Terminal shield
Phase
barriers
Plug-in
connectors
Short terminal
shield
Short terminal
shield
Plug-in
Shunt trip (SHT)
Under voltage
release (UVR)
Auxiliary switch (AX)
Alarm switch (AL)
Auxiliary/Alarm switch
(AX + AL)
Spreaders
Cable lugs
Terminal
extensions
Padlocking
system
Under voltage release (UVR)
Plug-in
connectors
P
B
1
0
6
4
1
0
_
1
7
6
LVED212091EN.indb 11 13-4-22 8:58
A-12
Functions
and characteristics
EasyPact EZC circuit breaker EZCV250 comes with a full range of accessories to
fulfll different application requirements and make it easy for the end-user.

Electrical and mechanical
accessories overview
EasyPact EZCV250

Terminal shield Phase
barriers
Plug-in
Spreaders
Cable lugs
Earth-leakage
alarm switch (ALV)
Auxiliary
switch (AX)
Alarm
switch (AL)
Auxiliary/
Alarm switch
(AX + AL)
Padlocking
system
Cable lugs
Spreaders
Plug-in
connectors
Short terminal
shield
Terminal shield
Phase
barriers
Direct rotary handles
Extended rotary handles
Short terminal
shield
Shunt trip
(SHT)
Under
voltage
release
(UVR)
Terminal
extensions
Plug-in
connectors
Terminal
extensions
P
B
1
0
6
4
1
1
_
1
7
6
LVED212091EN.indb 12 13-4-22 8:58
A-13
EasyPact EZC circuit breaker EZC400-630 comes with a full range of accessories to
fulfll different application requirements and make it easy for the end-user.

EasyPact EZC400-630


D
B
4
0
0
0
0
1
_
1
Interphase barriers
Sealable terminal
shields
Indication contact
Voltage release
Cable connectors
Cable connectors
Rear connectors
Direct rotary handle Extended rotary handle
Terminal
extensions
Insulation accessories
Connection
Electrical auxiliaries
Control accessories
LVED212091EN.indb 13 13-4-22 8:58
A-14
Functions
and characteristics
Plug-in location: AX - AL - AXAL - ALV
EZC100


EZC100-2P. EZC100-3P. EZC100-4P.
EZC250

EZC100.
EZC250-3P. EZC250-4P.
EZCV250

EZCV250-3P. EZCV250-4P.
AXAL and AX electrical auxiliaries on EZC100.
Indication contacts
Provide remote circuit breaker status information.
They can be used for indications, electrical locking, relaying, etc.
Common-point changeover contacts.
Auxiliary switch (ON/OFF)
AX indicates the position of the circuit breaker contacts.
Alarm switch (trip indication)
b AL indicates that the circuit breaker has tripped due to:
v an overload
v a short-circuit
v operation of a voltage release.
b ALV indicates that the circuit breaker has tripped due to an of earth-leakage fault.

They return to de-energised state when the circuit breaker is reset.
AXAL electrical auxiliaries on EZC250.
Characteristics
Contacts
Rated thermal current (A) 5
Minimum load 10 mA at 24 V
Utilisation category (IEC 60947-5-1) AC12 AC15 DC12 DC14
Operational current (A) 24 V 5 5 4 3
48 V 5 5 2.5 1
125 V 5 3 0.4 0.4
250 V 3 2 0.2 0.2
Connections
Connection wire length 450 mm
Cross-section EZC100: 1 mm
2
,
EZC250/EZCV250: 1.5 mm
2
AXAL, AX and ALV electrical auxiliaries on EZCV250.
Electrical auxiliaries
100-250AF
AX - AL - AXAL - ALV
C
P
B
1
0
0
6
1
2
C
D
B
5
0
0
6
0
3
C
D
B
5
0
0
6
0
4
C
D
B
5
0
0
6
0
5
D
B
1
1
6
8
3
2
D
B
1
1
6
8
3
3
D
B
1
1
6
8
3
4
D
B
1
1
6
8
3
5
AL or
AX or
AXAL
AL or
AX or
AXAL
AL or
AX or
AXAL
AL or
AX or
AXAL
AL or
AX or
AXAL
AL or
AX or
AXAL
AL or
AX or
AXAL
LVED212091EN.indb 14 13-4-22 8:59
A-15

Auxiliary switch (AX)
EZAUX10.
Auxiliary switch (AX)
EZEAX.
All EasyPact EZC
electrical auxiliaires
are "snapped in place

P
B
1
0
1
8
6
2
-
2
1
P
B
1
0
1
8
7
6
-
2
1
D
B
1
1
6
3
8
6
P
B
1
0
1
8
9
3
-
2
8
Earth-leakage alarm switch
(ALV).
LVED212091EN.indb 15 13-4-22 8:59
A-16
Functions
and characteristics
Plug-in location : SHT - UVR - UVRN
EZC100


EZC100-2P. EZC100-3P. EZC100-4P.
EZC250

EZC250.
EZC250-3P. EZC250-4P.
EZCV250

EZCV250-3P. EZCV250-4P.
SHT and UVR releases on EZC100.
Remote tripping
Shunt Trip (SHT) or Under Voltage Release (UVR/UVRN).
Shunt Trip (SHT)
b This release trips the circuit breaker when the control voltage rises above 0.7 x Un
b Control signals can be of the impulse type (u 20 ms) or maintained.
Under Voltage Release (UVR/UVRN)
b This release trips the circuit breaker when the control voltage drops below a
tripping threshold
b Tripping threshold between 0.35 and 0.7 times the rated voltage
b Circuit breaker closing is possible only if the voltage exceeds 0.85 times the rated
voltage.
Operation
When the circuit breaker has been tripped by an SHT or UVR/UVRN release, it must
be reset locally:
b SHT or UVR/UVRN tripping takes priority over manual closing
b in the presence of a standing trip order, closing of the contacts, even temporary, is
not possible.
Circuit breaker tripping by an SHT/UVR/UVRN release meets the requirements of
standard IEC 60947-2.
Characteristics
SHT and UVR releases on EZC250.
Mechanical
Mechanical endurance 10 % of MCCB mechnical endurance
Electrical EZC100 EZC250/EZCV250
AC/DC AC DC
SHT pick-up consumption < 30 VA < 30 VA < 35 W
response time < 50 ms < 50 ms < 100 ms
UVR seal-in consumption < 5 VA < 5 VA < 10 W
response time < 50 ms < 50 ms < 100 ms
UVRN seal-in consumption < 5 VA < 5 VA < 10 W
response time < 50 ms < 50 ms < 100 ms
UVRN release on EZCV250. Connections EZC100 EZC250/EZCV250
SHT pre-wired (1 mm
2
) pre-wired (0.5 mm
2
)
UVR pre-wired (1 mm
2
) screws (< 2 mm
2
)
UVRN pre-wired (1 mm
2
) pre-wired (0.5 mm
2
)
Electrical auxiliaries
100-250AF 0
SHT - UVR - UVRN
C
P
B
1
0
0
6
1
6
C
D
B
5
0
0
6
0
6
C
D
B
5
0
0
6
0
7
C
D
B
5
0
0
6
0
8
D
B
1
1
6
8
3
6
D
B
1
1
6
8
3
7
D
B
1
1
6
8
3
8
D
B
1
1
6
8
3
9
UVR SHT
SHT or
UVR
SHT or
UVR
SHT or
UVRN
LVED212091EN.indb 16 13-4-22 8:59