Sunteți pe pagina 1din 12

September 2011

Jet Diffuser Model JD

Jet Diffuser

Model JD

Features G Jet nozzle can rotate through 360 G Adjustable over 60 for cooling or heating G Low noise Level G 2 or 3 Jets integrated into a single panel G Motorised version available

Grilles Diffusers Louvres Chilled Beams Ruskin Air Management Limited www.ruskinuk.co.uk

Jet Diffuser Model JD

Contents
Page Contents Introduction and Specification Quick Selection Guide Selection Guide Dimensions Installation Guide and Ordering Information Product Range Page 2 Page 3 Page 4 Page 5 Page 9 Page 10 Page 11

www.air-diffusion.co.uk

Jet Diffuser Model JD

Introduction
The aerodynamic design of the Model JD jet diffuser ensures a low noise level even with high outlet velocities, whilst also providing a long throw distance. The individual jet nozzles can be rotated through 360 and adjustment of 60 upwards or downwards, for heating or cooling modes, is possible either manually or by using a motorised version. Constructed from aluminium the Model JD is available with or without a flange for connection direct to exposed circular ductwork or to a wall surface. Multiple jet arrangements can be supplied with either 2 or 3 jet nozzles fitted into a single panel. In addition a motorised version is also available to automatically adjust the jet outlet. Developed for installation at high level or for large spaces the jet diffuser is suitable for applications such as shopping malls, concert halls, theatres, museums and airport areas.

Specification
Model JD Aluminium jet diffuser developed for large and high areas. Materials Aluminium. Construction All made out of aluminium and painted white (RAL9010). Type JD210 and JD310 are JD110 mounted on galvanised sheet steel and all painted white as above. Finish Standard finish is White (RAL9010). Alternative paint finishes to the relevant RAL colours are available on request. Fixing Different versions are possible. Type JD110: for wall fixing with screws directly on the duct. Type JD130: direct mounting on Circular ducts. Type JD210 and JD310: 2 or 3 jet diffusers mounted on a panel and the panel is fixed onto the duct with screws. Types available JD110 Jet Diffuser. JD120 As above but with flex duct connector. JD130 Jet Diffuser without flange, rear mounting onto circular ducts. JD 140 (B3) Jet Diffuser without flange having extension sleeve for motorisation using an LM24SR electric motor. JD210,310 2 or 3 JD110 pre-mounted on one panel to ease the mounting of different Jet Diffusers next to each other on the wall.

www.air-diffusion.co.uk 3

Jet Diffuser Model JD

Quick Selection Guide


Size Volume (m3/Hour) 150 200 250 160 300 350 400 450 300 350 400 450 200 500 550 600 650 700 300 400 500 600 250 700 800 900 1000 1100 1200 400 500 600 700 800 315 900 1000 1100 1200 1300 1400 1500 Volume (m3/sec.) 0.042 0.056 0.069 0.083 0.097 0.111 0.125 0.083 0.097 0.111 0.125 0.139 0.153 0.167 0.181 0.194 0.083 0.111 0.139 0.167 0.194 0.222 0.250 0.278 0.306 0.333 0.111 0.139 0.167 0.194 0.222 0.250 0.278 0.306 0.333 0.361 0.389 0.417 Nozzle Velocity (m/sec.) 8.7 11.6 14.5 17.4 20.3 23.1 26 10 11.7 13.4 15.1 16.7 18.4 20.1 21.8 23.4 6 8 10 12 14 16 18 20 22 24 4.3 5.4 6.5 7.6 8.7 9.8 10.8 11.9 13 14.1 15.2 16.3 Noise Rating (NR) 13 20 25 30 33 37 40 20 24 27 30 33 35 37 39 41 11 18 24 28 32 35 38 41 43 45 9 15 19 23 26 29 32 34 36 38 40 42 Pressure Loss (Pt) (Pa) 37 66 104 149 203 265 335 53 73 95 120 148 179 214 251 291 20 35 55 79 107 140 177 219 265 315 14 22 32 43 57 72 89 107 128 150 174 199 Throw to 0.5 m/sec. (m) 10 12.9 15.8 18.7 21.5 24.4 27.3 10.7 12.5 14.3 16.1 17.9 19.6 21.4 23.2 25 6.9 8.9 10.9 12.9 14.9 17 19 21 23 25 4.6 5.8 7 8.3 9.5 10.7 11.9 13.1 14.3 15.5 16.7 17.9 Throw is measured horizontally to terminal velocity 0.5 m/s, with nozzle set for horizontal distribution. No temperature effect on throw has been allowed for. Noise ratings do not include for room attenuation. For multiple nozzle units approximate combined noise rating use equivalent for single diffuser and add: JD210 + 3 NR JD310 + 3NR For multiple nozzle units approximate combined pressure drop use equivalent volume for single diffuser and multiply: JD210 x 2 = Pa JD310 x 3 = Pa Application The Jet Diffusers, Type JD are especially developed for large and high areas such as concert halls, theatres, galleries, airports, shopping centres, industrial plants etc. Through their aerodynamic design they ensure a reduced noise level and even a long throw at high outlet velocities. In all versions, the jet is adjustable over 360. As these jet diffusers handle different supply air temperatures, the jet can be oriented upwards or downwards (heating or cooling mode). Orientation manually or with an electric motor. Technical Information Characteristics

adjustable over 60 (cooling - heating)

oscillate over 360 high induction level available with 2 or 3 jet diffusers
integrated into one panel (JD210 and JD310)

panel includes Type JD110 jet diffusers motorised construction available.

www.air-diffusion.co.uk

Jet Diffuser Model JD

Selection Guide
Diagram 1. Horizontal Throw
V T (m/s)
0.8 0.7 0.6 0.5
0

V f (m/s)
60
0

0.9 1 1.2 1.4 1.6 50 40 30


16 20

0.4 0.3

0.2 0.15

31

25

0.25

20

10

40

5 4 3 2

40

30

20

15

10

3 0.03

0.05

0.1

L T (m)
120 200 300

q v (m 3/s)
500

0.2

0.3

0.4 0.5 0.6

0.8

400

600

7 8 1000

1500

2500 2000 3000

q v (m 3/h)

Horizontal Throw - isothermal - example

t s

VT 10 t L

Example: q v : 0.1m 3/s ; size 250 Diagram 1: v f : 7.8m/s; L T : 10m at a V T : 0.42 m/s Diagram 4: P t : 33 Pa; NR:17.

LT

Size Af

160
0.0048

200

Af = values (m2) 250


0.0139

Correction factors noise level 315


0.018

400
0.038

Angle between 0 and 25 between 25 and 30

Correction NR NR + 0 NR + 2

0.0083

www.air-diffusion.co.uk 5

Jet Diffuser Model JD

Selection Guide
Diagram 2. Throw correction by heating or cooling
LT ( m )
30 25 20 15
20 0 16 0

Vf (m/s)
60 50 40 30 20
25 0 31 5

10 8 6 4

10

40 0

5 4 3 2

y (m )
15 10 8 6 4

16 14 12 0.03 10 8 6 4 3 2 120

0.05

0.1

qv(m3/s)
500 600

0.2

0.3

0.4 0.5 0.6

0.8

200

300

400

7 8 1000

1500

qv(m3/h)

1500 2000 3000

ts (K) Heating or cooling

1 0.8 0.6 0.4

0.2

Example throw correction


LT

VT

ts

Example by heating: - qv = 0.1 m3/s; size 250; t s by heating of 10K. - Out of diagram nr. 1: vf = 7.8 m/s; LT = 10m at a vT = 0.42 m/s - Out of diagram nr. 2: t s = 10; y = 2 which means that the air stream will raise at that point of the throw with 2m. Example by cooling: - qv = 0.1 m3/s; size 250; t s by cooling of 10K. - Out of diagram nr. 1: vf = 7.8 m/s; LT = 10m at a vT = 0.42 m/s - Out of diagram nr. 2: t s = 10; y = 2 which means that the air stream will drop at that point of the throw with 2m. The drop or raise of the air stream can be corrected by modifying the outlet angle of the nozzle.

L T

VT

www.air-diffusion.co.uk

Jet Diffuser Model JD

Selection Guide
Diagram 3. Vertical Throw
t s ( K ) +10 15 20 25 30
0

+5

Vf ( m/s ) 60
16

50 40 30 20

25

20

10

40

31

5 4 3 2

30

20

15

10 9 8 7 6 5

3 0.03

0.05

0.1

LT ( m )

VT =0.25 m/s

qv (m3/s)

0.2

0.3 0.4 0.5 0.6 0.8

120

200

300

400

500 7 8 1000 600 qv (m3/h)

1500 2500 2000 3000

t s

- qv = 0.1 m3/s; size 250mm - Out of diagram nr. 3: vf = 7.8 m/s; t = +10; LT = 5.4m at a vT = 0.25 m/s - Out of diagram nr. 4: Pt = 33 Pa NR 17
LT

VT t L

www.air-diffusion.co.uk 7

Jet Diffuser Model JD

Selection Guide
Diagram 4. Pressure loss and noise levels
160 200 250 315

1000 800 600 500 400 300 200 150 30 100 80 60 50 40 30 20 15 10 15 20 25 40 NR 50 45

400

35

0.03 0.04 0.06 0.08 0.10 0.15 0.2

0.3
3/s

0.4 0.5 0.6 0.8

qv ( m
120 200

)
1500 2500 2000 3000

300 400 600 900 500 700 1000

qv ( m3/h )

Temperature quotient and induction Temperature quotient


0.30 0.25 0.20 0.15 0.10 0.08 0.06 10 0.04 8 6 5 0.02 2 3 4 5 6 8 10 12 14 20 25 30 4 2 3 4 5 6 8 10 12 14 20 25 30

Induction
60 50 40 30 25 20 15

16

0 40 5 31 0 25 0 20 0 16

20

25

0 31

5 40

LT ( m )

LT ( m )

www.air-diffusion.co.uk

Jet Diffuser Model JD

Dimensions
JD 110
C

JD 120
C

60

60

JD 130
N 160 200 250 315 400
H J N A K

A 85 110 140 175 220

B 248 298 345 415 600

C 120 150 190 255 290

D 51 66 81 90 120

E 225 270 320 390 475

F 200 245 295 360 450

G 101 116 131 155 190

H 110 125 140 165 200

110 196 140 238 180 288 245 355 280 440

JD 210
F A A 15

JD 310
D D D 15

B/2

B L1

B/2

F G

B/2

B L2

B/2

F G

Size 160 200 250

L1

L2

H 350 400 450 520 625

A 335 385 435 510 610

B 350 400 450 520 625

C 320 370 420 490 595

D 340 390 440 510 615

E 36 51 66 76 106

700 1050 800 1200 900 1350

134 170 164 215 204 270 269 345 304 410

315 1040 1560 400 1250 1875

JD 140B3 with Belimo motor LM24SR

Nom 160
Nom 60 C

A 271 283 293 315 340

B 110 140 180 245 280

C 196 238 288 355 440

200 250 315 400

www.air-diffusion.co.uk 9

Jet Diffuser Model JD

Jet Diffuser Installation Guide


The choice of three different constructions

JD130 Direct mounting on fixed circular ducts JD110 Duct fixing using screws directly to the side of the duct wall. Panel To ease the simultaneous mounting of different jet diffusers side by side on a wall or a duct, the possibility is given to get two or three jet diffusers pre-mounted on one panel. The panel is fixed by screws onto a wall or other panel.

JD110 Wall fixing with screws. Connection with flex ducts

Ordering Information
Example Model Type JD1 Arrangement 10 Accessory Size 250 Colour Finish 3

JD1 JET Diffuser only JD2 Panel with 2 Diffusers JD3 Panel with 3 Diffusers

10. 20. 30. 40.

Duct fixing direct on duct wall Wall fixing for flex duct connection For direct mounting on circular duct Motorised version (without motor)

: No Accessory B3 : LM24SR Electric Motor

160 200 250 315 400

3 - White RAL 9010

Important Note: All orders must be addressed to Air Diffusion, Ruskin Air Management Limited.
10 www.air-diffusion.co.uk

Jet Diffuser Model JD

Product Range

Modular Active Chilled Beams

Ceiling Swirl Diffusers

Displacement Ventilation Units High Induction Slot Diffusers Square Louvre Face Diffusers

Perforated Diffusers Linear Slot Diffusers

Fixed Blade Linear Diffusers

Cylinder Jet Diffusers Jet Nozzle Diffusers

Circular Adjustable and Fixed Diffusers

Air Valves

Panel Floor Grilles Linear Floor Grilles

Floor Swirl Diffusers

Wall and Ceiling Grilles

External Weather Louvres

Systempac Fan Coil Unit and Diffuser Package


www.air-diffusion.co.uk 11

Jet Diffuser Model JD

Ruskin Air Management Limited is a BS EN ISO 9001 registered company.


The statements made in this brochure or by our representatives in consequence of any enquiries arising out of this document are given for information purposes only. They are not intended to have any legal effect and the company is not to be regarded as bound thereby. The company will only accept obligations which are expressly negotiated for and agreed and incorporated into a written agreement made with its customers. Due to a policy of continuous product development the specification and details contained herein are subject to alteration without prior notice.

Comprehensive and detailed information is available for all Air Diffusion products. Visit our website at www.air-diffusion.co.uk

Ruskin Air Management Limited


Stourbridge Road, Bridgnorth, Shropshire, WV15 5BB England. Tel: 01746 761921 Fax: 01746 760127 Email: sales@air-diffusion.co.uk Website: www.air-diffusion.co.uk

S-ar putea să vă placă și