STRUCTURAL ANALYSIS
**********************
SUBMITAL FOR BUILDING DEPARTMENT

CHAT PHAM RESIDENCE


9969 DAUNTLESS STREET
SAN DIEGO, CA 92126

1ST SUBMITAL: SEPTEMBER 18, 2012


VERTICAL, LATERAL
DESIGNED BY: TUNG VO, M.S., P.E.

Job
Plan

PRIMARY ROOF LOADING


Pitch
K = Increase for pitch
Truss(24" O/C)
Plywood(1/2")
1/2" Gyp. Board
Conc. Tile
Sprinkler
Misc.(Insul.,Elect.,ETC)

: 66927-200
:1

SECONDARY ROOF LOADING

xK
xK
xK

Snow Load
Live Load
Dead Load

4.0:12
1.05
2.53
1.63
2.20
10.54
1.00
2.09

Pitch
K = Increase for pitch

0.00
20.00
20.00

Snow Load
Live Load
Dead Load

Rafter(2x6 16" O/C) Joist(No Ceil'G Joists )

Plywood(1/2")
Shingle
Sprinkler
Misc.(Insul.,Elect.,ETC)

xK
xK
xK

3.0:12
1.03
1.94
1.60
0.00
3.09
1.00
2.37
0.00
20.00
10.00

PRIMARY FLOOR LOADING


Joist(2x12 16" O/C)
Plywood(3/4")
1/2" Gyp. Board
Carpet
None Covering
Sprinkler
Misc.(Insul.,Elect.,ETC)
Partition

3.81
2.25
2.20
1.00
0.00
1.00
4.00
0.00

Live Load
Dead Load

40.00
15.00

DESIGN CRITERIA:
A. Code: CBC 2010, Wind: C, 85 mph, Category: D
B. Wood Species: Douglas Fir Larch with maximum 19% moisture content
prior to Installation of Finish Material
4X Members: No.2 or Better
6X, 8X Beams and Headers: No.1 or Better
2X Joists and Rafters: No.2 or Better
Plates and Blocking: Standard Grade or Better
Studs: Stud Grade or Better
Mud Sills: Pressure Treated Utility Grade or Better

IBC9.7

GOUVIS ENGINEERING CONSULTING GROUP


LATERAL ANALYSIS
CBC 2010
POURING NON MONO

SHEET
JOB NO.
CLIENT
PLAN NO.
DATE

:
:
:
:
:

L-1
66927
Mr. Nguyen Mai Han
1
5/14/2012(Ver400)

Y DIRECTION SECTION 1Y
BLDG DIMENSION (FT): BASE HT=0.5, SLOPE ROOF HT=23.0, GABLE MEAN ROOF HT=23.0, L=62.0, B=39.0
FLOOR HT (FT): 1-FLR=8.0, 2-FLR=18.0
WIND PARAMETERS: WIND SPEED=85 MPH, WIND EXPOSURE=C
=1.00
COEFFICIENTS: Kd=0.85, Kzt=1.00, G=0.85, GCpi= 0.18,
INTERPOLATION: L/B YES, h/L YES, YES, qh=14.40
WIND HEIGHT (FT):
15
20
25
UPLIFT (AVE.)
WALL PRESSUREP (PSF): 13.75 14.32 14.78
7.11
ROOF: 39.00(WW)/18.00/18.43, 39.00(LW)/18.00/18.43; OVERHANGS: 39.00/2.00
WIND LOAD ROOF (PLF): MINIMUM LOAD=(10*5.00*1.00)+63.47=113.47
WIND LOAD FLOOR (PLF): 1-FLR=112.31(R)
MAX TOTAL=225.79
Ry= 6.5, SITE CLASS: D, S DS=2FaSs/3=2x1.10x1.09/3=0.799, S D1=2FvS1/3=2x1.60x0.40/3=0.427, S DC=D, k=1.0000
V=SDSIW/1.4Ry=(0.799)(1.00)W/(1.4*6.5)=
0.0878W
ROOF:
DL ROOF =
20.0x42.0 =
840.00 PLF
DL EXT WALL =
15.0[2.0(18.00-13.50)] =
135.00 PLF
DL INT WALL =
10.0[2.5(18.00-13.50)] =
112.50 PLF
SHEAR =
0.0878(840.00+135.00+112.50) = 0.0878(1087.50) =
95.52 PLF
1-FLR:
DL FLOOR =
15.0x44.0 =
660.00 PLF
DL EXT WALL =
15.0[2.0(13.50-9.00)+2.0(8.00-4.00)] =
255.00 PLF
DL INT WALL =
10.0[2.5(13.50-9.00)+1.5(8.00-4.00)] =
172.50 PLF
SHEAR =
0.0878(660.00+255.00+172.50) = 0.0878(1087.50) =
95.52 PLF
TOTAL SEISMIC LOAD =
95.52+95.52 =
191.05 PLF
REDISTRIB.:
1087.5x18.0+1087.5x8.0 = 28275.0
SHEAR ROOF =
191.05 x 1087.50 x 18.00 / 28275.00 =
132.27 PLF
(132.27 PLF)
SHEAR 1-FLR =
191.05 x 1087.50 x 8.00 / 28275.00 =
58.78 PLF
(124.18 PLF)
ROOF : 132.27 PLF SEISMIC GOVERN
(DIAPH.ONLY)
1-FLR: 225.79 PLF WIND GOVERN
ROOF DIAPHRAGM V = 132.27 =
132.27 PLF
MAX SHEAR =
132.27 x 39.00 / (2 x 38.00) =
67.87 PLF
USE: 15/32" CDX RATED UNBLKED 32/16 W/8d COMMON NAILS AT 6", 6", 12" O.C.
CHORD FORCE =
132.27 x 39.00 x 39.00 / (8 x 38.00) =
661.76 LBS
SPLICE W/ MINI (5)16d SINKER NAILS EACH SIDE OF SPLICE @ 8 IN. O.C. (STANDARD CONSTRUCTION)
1-FLR DIAPHRAGM V =
124.18 PLF
ALIGN
MAX SHEAR =
124.18 x 20.00 / (2 x 44.00) =
28.22 PLF
USE: 23/32" CDX RATED UNBLKED W/10d COMMON NAILS AT 6", 6", 12" O.C.
CHORD FORCE =
124.18 x 20.00 x 20.00 / (8 x 44.00) =
141.12 LBS
SPLICE W/ MINI (5)16d SINKER NAILS EACH SIDE OF SPLICE @ 8 IN. O.C. (STANDARD CONSTRUCTION)

GOUVIS ENGINEERING CONSULTING GROUP


LATERAL ANALYSIS
CBC 2010
POURING NON MONO

SHEET
JOB NO.
CLIENT
PLAN NO.
DATE

:
:
:
:
:

L-2
66927
Mr. Nguyen Mai Han
1
5/14/2012(Ver400)

Y DIRECTION SECTION 2Y
BLDG DIMENSION (FT): BASE HT=0.5, SLOPE ROOF HT=22.0, GABLE MEAN ROOF HT=22.0, L=62.0, B=39.0
FLOOR HT (FT): 1-FLR=18.0
WIND PARAMETERS: WIND SPEED=85 MPH, WIND EXPOSURE=C
=1.00
COEFFICIENTS: Kd=0.85, Kzt=1.00, G=0.85, GCpi= 0.18,
INTERPOLATION: L/B YES, h/L YES, YES, qh=14.40
WIND HEIGHT (FT):
15
20
25
UPLIFT (AVE.)
WALL PRESSUREP (PSF): 13.75 14.32 14.78
5.76
ROOF: 19.00(WW)/15.00/18.43; OVERHANGS: 2.00/18.00
WIND LOAD ROOF (PLF): MINIMUM LOAD=(10*4.00*1.00)+83.47=123.47
MAX TOTAL=123.47
Ry= 6.5, SITE CLASS: D, S DS=2FaSs/3=2x1.10x1.09/3=0.799, S D1=2FvS1/3=2x1.60x0.40/3=0.427, S DC=D, k=1.0000
V=SDSIW/1.4Ry=(0.799)(1.00)W/(1.4*6.5)=
0.0878W
ROOF:
DL ROOF =
20.0x16.0 =
320.00 PLF
DL EXT WALL =
15.0[1.0(18.00-9.00)] =
135.00 PLF
DL INT WALL =
10.0[1.0(18.00-9.00)] =
90.00 PLF
SHEAR =
0.0878(320.00+135.00+90.00) = 0.0878(545.00) =
47.87 PLF
TOTAL SEISMIC LOAD =
47.87 =
47.87 PLF
(62.23 PLF)
ROOF : 123.47 PLF WIND GOVERN
(DIAPH.ONLY)
ROOF DIAPHRAGM V =
123.47 PLF
MAX SHEAR =
123.47 x 19.00 / (2 x 15.00) =
78.20 PLF
USE: 15/32" CDX RATED UNBLKED 32/16 W/8d COMMON NAILS AT 6", 6", 12" O.C.
CHORD FORCE =
123.47 x 19.00 x 19.00 / (8 x 15.00) =
371.43 LBS
SPLICE W/ MINI (5)16d SINKER NAILS EACH SIDE OF SPLICE @ 8 IN. O.C. (STANDARD CONSTRUCTION)

GOUVIS ENGINEERING CONSULTING GROUP


LATERAL ANALYSIS
CBC 2010
POURING NON MONO

SHEET
JOB NO.
CLIENT
PLAN NO.
DATE

:
:
:
:
:

L-3
66927
Mr. Nguyen Mai Han
1
5/14/2012(Ver400)

X DIRECTION SECTION 1X
BLDG DIMENSION (FT): BASE HT=0.5, SLOPE ROOF HT=23.0, GABLE MEAN ROOF HT=23.0, L=39.0, B=62.0
FLOOR HT (FT): 1-FLR=8.0, 2-FLR=18.0
WIND PARAMETERS: WIND SPEED=85 MPH, WIND EXPOSURE=C
=1.00
COEFFICIENTS: Kd=0.85, Kzt=1.00, G=0.85, GCpi= 0.18,
INTERPOLATION: L/B YES, h/L YES, YES, qh=14.40
WIND HEIGHT (FT):
15
20
25
UPLIFT (AVE.)
WALL PRESSUREP (PSF): 15.19 15.76 16.22
7.93
ROOF: 37.00(WW)/19.50/18.43, 37.00(LW)/19.50/18.43; OVERHANGS: 37.00/2.50
WIND LOAD ROOF (PLF): MINIMUM LOAD=(10*5.00*1.00)+69.97=119.97
WIND LOAD FLOOR (PLF): 1-FLR=144.73
MAX TOTAL=264.70
Rx= 6.5, SITE CLASS: D, S DS=2FaSs/3=2x1.10x1.09/3=0.799, S D1=2FvS1/3=2x1.60x0.40/3=0.427, S DC=D, k=1.0000
V=SDSIW/1.4Rx=(0.799)(1.00)W/(1.4*6.5)=
0.0878W
ROOF:
DL ROOF =
20.0x42.0 =
840.00 PLF
DL EXT WALL =
15.0[2.0(18.00-13.50)] =
135.00 PLF
DL INT WALL =
10.0[2.5(18.00-13.50)] =
112.50 PLF
SHEAR =
0.0878(840.00+135.00+112.50) = 0.0878(1087.50) =
95.52 PLF
1-FLR:
DL FLOOR =
15.0x37.0 =
555.00 PLF
DL EXT WALL =
15.0[2.0(13.50-9.00)+2.0(8.00-4.00)] =
255.00 PLF
DL INT WALL =
10.0[2.5(13.50-9.00)+2.0(8.00-4.00)] =
192.50 PLF
SHEAR =
0.0878(555.00+255.00+192.50) = 0.0878(1002.50) =
88.06 PLF
TOTAL SEISMIC LOAD =
95.52+88.06 =
183.58 PLF
REDISTRIB.:
1087.5x18.0+1002.5x8.0 = 27595.0
SHEAR ROOF =
183.58 x 1087.50 x 18.00 / 27595.00 =
130.23 PLF
(130.23 PLF)
SHEAR 1-FLR =
183.58 x 1002.50 x 8.00 / 27595.00 =
53.36 PLF
(114.48 PLF)
ROOF : 130.23 PLF SEISMIC GOVERN
(DIAPH.ONLY)
1-FLR: 264.70 PLF WIND GOVERN
ROOF DIAPHRAGM V = 130.23 =
130.23 PLF
MAX SHEAR =
130.23 x 37.00 / (2 x 39.00) =
61.77 PLF
USE: 15/32" CDX RATED UNBLKED 32/16 W/8d COMMON NAILS AT 6", 6", 12" O.C.
CHORD FORCE =
130.23 x 37.00 x 37.00 / (8 x 39.00) =
571.42 LBS
SPLICE W/ MINI (5)16d SINKER NAILS EACH SIDE OF SPLICE @ 8 IN. O.C. (STANDARD CONSTRUCTION)
1-FLR DIAPHRAGM V =
144.73 PLF
ALIGN
MAX SHEAR =
144.73 x 18.00 / (2 x 37.00) =
35.20 PLF
USE: 23/32" CDX RATED UNBLKED W/10d COMMON NAILS AT 6", 6", 12" O.C.
CHORD FORCE =
144.73 x 18.00 x 18.00 / (8 x 37.00) =
158.42 LBS
SPLICE W/ MINI (5)16d SINKER NAILS EACH SIDE OF SPLICE @ 8 IN. O.C. (STANDARD CONSTRUCTION)

GOUVIS ENGINEERING CONSULTING GROUP


LATERAL ANALYSIS
CBC 2010
POURING NON MONO

SHEET
JOB NO.
CLIENT
PLAN NO.
DATE

:
:
:
:
:

L-4
66927
Mr. Nguyen Mai Han
1
5/14/2012(Ver400)

X DIRECTION SECTION 2X
BLDG DIMENSION (FT): BASE HT=0.5, SLOPE ROOF HT=22.0, GABLE MEAN ROOF HT=22.0, L=39.0, B=62.0
FLOOR HT (FT): 1-FLR=18.0
WIND PARAMETERS: WIND SPEED=85 MPH, WIND EXPOSURE=C
=1.00
COEFFICIENTS: Kd=0.85, Kzt=1.00, G=0.85, GCpi= 0.18,
INTERPOLATION: L/B YES, h/L YES, YES, qh=14.40
WIND HEIGHT (FT):
15
20
25
UPLIFT (AVE.)
WALL PRESSUREP (PSF): 15.19 15.76 16.22
6.02
ROOF: 15.00(WW)/9.50/18.43, 15.00(LW)/9.50/18.43
WIND LOAD ROOF (PLF): MINIMUM LOAD=(10*4.00*1.00)+138.53=178.53
MAX TOTAL=178.53
Rx= 6.5, SITE CLASS: D, S DS=2FaSs/3=2x1.10x1.09/3=0.799, S D1=2FvS1/3=2x1.60x0.40/3=0.427, S DC=D, k=1.0000
V=SDSIW/1.4Rx=(0.799)(1.00)W/(1.4*6.5)=
0.0878W
ROOF:
DL ROOF =
20.0x22.0 =
440.00 PLF
DL EXT WALL =
15.0[2.0(18.00-9.00)] =
270.00 PLF
SHEAR =
0.0878(440.00+270.00) = 0.0878(710.00) =
62.37 PLF
TOTAL SEISMIC LOAD =
62.37 =
62.37 PLF
(81.08 PLF)
ROOF : 178.53 PLF WIND GOVERN
(DIAPH.ONLY)
ROOF DIAPHRAGM V =
178.53 PLF
MAX SHEAR =
178.53 x 15.00 / (2 x 19.00) =
70.47 PLF
USE: 15/32" CDX RATED UNBLKED 32/16 W/8d COMMON NAILS AT 6", 6", 12" O.C.
CHORD FORCE =
178.53 x 15.00 x 15.00 / (8 x 19.00) =
264.28 LBS
SPLICE W/ MINI (5)16d SINKER NAILS EACH SIDE OF SPLICE @ 8 IN. O.C. (STANDARD CONSTRUCTION)

Tung Thanh Vo, M.S., P.E.

SHEARWALS
DESIGN

2010-CBC

Job : 66927-200
Plan : 1

Wind: 2213 Seismic: 2579

wind
seismic

Wind:

113.5
132.3
1Y_ROOF
39.0

0 Seismic: 222

wind
seismic

0.0
0.0

0.0
47.9
2Y_ROOF
19.0

20.0

1 @Left of Elevation 2ND Floor

Exterior Wall(Y Dir.)

Wind 2213(Uplift on Roof=7.2 PSF)


Seismic 2970= 2801+ 169

B
9.0

2.8

4.0

6.5

4.3

1.3

4.0

1.5

4.0

7.8

Strap(E)
557

162

A
0.0

A
36.0

6.8

13.2

24.3

28.3

745

639

Drag Force Analysis


A: Simpson ST22 (1192 LB)
ALT (10) # 16d sinker per top plate splice
Total Wall Length = 36.00(FT) Total Panel Length = 10.50(FT)
= 1.00
Shear Diaphragm = 2970/ 36.00 = 82(PLF)
Use (7 A35) or (5 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(S) = 2970/10.50= 283(PLF)(Flexible ,SW V_allow(Seismic) Ajusted for H/W Ratio) Max. Drag = 745(LB)

Use TYPE 2
Max. Panel Deflection:
Dead Loads:
Wall
Roof_P

M = (4.0/1.0) x

s x 1.4 = 1.159" <= 0.02 x 108.0 = 2.160"

135.0= 15 * 9.0'
120.0= 20 *12.0/2 FROM 0.0' TO 0.0'

OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 2452(LB) C= 2665(LB)
Right Side : T= 2452(LB) C= 2665(LB)

(2)CS16/(2)2x4 ****
(2)CS16/(2)2x4 ****

Use (2)CS16/(2)2x4 on both ends


Panel

Left Side
: T= 2615(LB) C= 2746(LB)
Right Side : T= 2615(LB) C= 2746(LB)

(2)CS16/(2)2x4 ****
(2)CS16/(2)2x4 ****

Use (2)CS16/(2)2x4 on both ends

**** Plywood shear wall to be nailed to all studs receiving holdowns


IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 2213 Seismic: 2579

wind
seismic

Wind:

113.5
132.3
1Y_ROOF
39.0

0 Seismic: 688

wind
seismic

0.0
47.9
2Y_ROOF
19.0

0.0
0.0
|

20.0

2 @Right of Elevation 2ND Floor

Exterior Wall(Y Dir.)

Wind 2213(Uplift on Roof=6.8 PSF)


Seismic 3581= 3267+ 313

B
9.0

2.3 2.0
Strap(E)

13.5

6.0

Blocked Opening UseTYPE 2

2.3

8.0

0.5 2.3

4.0

4.0

13.8

on BOT(/TOP) of Opening See Detail on Plans

1086

A
39.0

0.0

17.8

58.5

34.0

1500

Drag Force Analysis


A: Simpson ST22 (1192 LB)
ALT (10) # 16d sinker per top plate splice
B: Simpson ST6224(2134 LB)
ALT (16) # 16d sinker per top plate splice
Total Wall Length = 58.50(FT) Total Panel Length = 14.00(FT)

Shear Diaphragm = 3581/ 58.50 = 61(PLF)


Use (9 A35) or (6 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(S)=331(PLF)(on Opening A & B ) Max. Drag= 1500(LB)

= 1.00

Use TYPE 2
Max. Panel Deflection:
Dead Loads:
Wall
Roof_P

M = (4.0/1.0) x

s x 1.4 = 0.745" <= 0.02 x 108.0 = 2.160"

135.0= 15 * 9.0'
120.0= 20 *12.0/2 FROM 0.0' TO 0.0'

OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 1510(LB) C= 2019(LB)
Right Side : T= 0(LB) C= 0(LB)

CS16/2x4
No Sign. Uplift()

Use CS16/2x4 @ L.
Panel

Blocked! Force @ Edge of Opening is 372(LB)


Left Side
: T= 0(LB) C= 0(LB)
No Sign. Uplift()
Right Side : T= 1505(LB) C= 2019(LB)
CS16/2x4

Use CS16/2x4 @ R.

IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 2399 Seismic: 2605

wind
seismic

120.0
130.2
1X_ROOF
40.0

3 @Rear of Elevation 2ND Floor

Exterior Wall(X Dir.)

Wind 2399(Uplift on Roof=6.8 PSF)


Seismic 2781= 2605+ 176

B
9.0

4.0

5.0

6.3

5.3

3.3

5.0

5.0

5.3

Strap(E)
642

A
0.0

A
39.0

9.0

15.2

20.5

368
742

23.7

1087

Drag Force Analysis


A: Simpson ST22 (1192 LB)
ALT (10) # 16d sinker per top plate splice
Total Wall Length = 39.00(FT) Total Panel Length = 9.50(FT)
= 1.00
Shear Diaphragm = 2781/ 39.00 = 71(PLF)
Use (7 A35) or (5 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(S) = 2781/ 9.50= 293(PLF)(Flexible ,SW V_allow(Seismic) Ajusted for H/W Ratio) Max. Drag = 1087(LB)

Use TYPE 3
Max. Panel Deflection:
Dead Loads:
Wall
Roof_P

M = (4.0/1.0) x

s x 1.4 = 1.121" <= 0.02 x 108.0 = 2.160"

135.0= 15 * 9.0'
200.0= 20 *20.0/2 FROM 0.0' TO 0.0'

OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 2559(LB) C= 2763(LB)
Right Side : T= 2559(LB) C= 2763(LB)

(2)CS16/(2)2x4 ****
(2)CS16/(2)2x4 ****

Use (2)CS16/(2)2x4 on both ends


Panel

Left Side
: T= 2788(LB) C= 2894(LB)
Right Side : T= 2788(LB) C= 2894(LB)

(2)CS16/(2)2x4 ****
(2)CS16/(2)2x4 ****

Use (2)CS16/(2)2x4 on both ends

**** Plywood shear wall to be nailed to all studs receiving holdowns


IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 2219 Seismic: 2409

wind
seismic

120.0
130.2
1X_ROOF
37.0

Wind: 1339 Seismic: 468

wind
seismic

178.5
62.4
2X_ROOF
15.0

4 @Front of Elevation 2ND Floor

Exterior Wall(X Dir.)

Wind 3558(Uplift on Roof=7.2 PSF)


Seismic 2941= 2877+ 64

B
9.0

6.8

9.5

4.0

18.8

Strap(E)
B

11.4
0.0

6.7

A
25.9

16.2

752
1618

39.0

20.2

1711

Drag Force Analysis


A: Simpson ST22 (1192 LB)
ALT (10) # 16d sinker per top plate splice
B: Simpson ST6224(2134 LB)
ALT (16) # 16d sinker per top plate splice
Total Wall Length = 39.00(FT) Total Panel Length = 10.75(FT)
= 1.00
Shear Diaphragm = 3558/ 39.00 = 91(PLF)
Use (9 A35) or (6 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(W) = 3558/10.75= 331(PLF)(Flexible ,SW V_allow(Seismic) Ajusted for H/W Ratio) Max. Drag = 1711(LB)

Use TYPE 2
Max. Panel Deflection:
Dead Loads:
Wall
Roof_P

M = (4.0/1.0) x

s x 1.4 = 1.093" <= 0.02 x 108.0 = 2.160"

135.0= 15 * 9.0'
300.0= 20 *30.0/2 FROM 0.0' TO 39.0'

OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 2614(LB) C= 3695(LB)
Right Side : T= 2614(LB) C= 3695(LB)

(2)CS16/(2)2x4 ****
(2)CS16/(2)2x4 ****

Use (2)CS16/(2)2x4 on both ends


Panel

Left Side
: T= 2924(LB) C= 3646(LB)
Right Side : T= 2924(LB) C= 3646(LB)

(2)CS16/(2)2x4 ****
(2)CS16/(2)2x4 ****

Use (2)CS16/(2)2x4 on both ends

**** Plywood shear wall to be nailed to all studs receiving holdowns


IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 1339 Seismic: 468

wind
seismic

178.5
62.4
2X_ROOF
15.0

5 @Front of Opening 2ND Floor

Exterior Wall(X Dir.)

Wind 1339(Uplift on Roof=7.2 PSF)


Seismic 563= 468+ 95

D
9.0

3.5
Strap(E)

Blocked Opening UseTYPE 1

1.5

3.8

1.5 2.5

2.5

3.8

on BOT(/TOP) of Opening See Detail on Plans


A
0.0

8.710.2

19.0

102

Drag Force Analysis


A: Simpson ST22 (1192 LB)

ALT (10) # 16d sinker per top plate splice

See Detail Information on Next Page

IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Total Wall Length = 19.00(FT) Total Panel Length = 13.50(FT)

Shear Diaphragm = 1339/ 19.00 = 70(PLF)


Use (4 A35) or (3 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(W) = 1339/13.50= 99(PLF)(Flexible ) Max. Drag = 102(LB)

Use TYPE 1
Max. Panel Deflection:

M = (4.0/1.0) x

Dead Loads:
Wall
135.0= 15 * 9.0'
OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 442(LB) C= 765(LB)
Right Side : T= 0(LB) C= 0(LB)

s x 1.4 = 0.175" <= 0.02 x 108.0 = 2.160"

Use CS16/2x4 @ L.

Panel

= 1.00

CS16/2x4
No Sign. Uplift()

Blocked! Force @ Edge of Opening is 131(LB)


Left Side
: T= 0(LB) C= 0(LB)
No Sign. Uplift()
Right Side : T= 441(LB) C= 765(LB)
CS16/2x4

Use CS16/2x4 @ R.

Panel

Left Side
: T= 363(LB) C= 660(LB)
Right Side : T= 0(LB) C= 0(LB)

Use CS16/2x4 @ L.

Panel

CS16/2x4
No Sign. Uplift()

Blocked! Force @ Edge of Opening is 188(LB)


Left Side
: T= 0(LB) C= 0(LB)
No Sign. Uplift()
Right Side : T= 349(LB) C= 660(LB)
CS16/2x4

Use CS16/2x4 @ R.

IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 1123 Seismic: 588

wind
seismic

112.3
58.8
1Y_1_FL
20.0

Load 1 @ 0.0' Start 0.0' to 37.0'(100%)

6 @Left of Elevation

1ST Floor 2-Pour

Exterior Wall(Y Dir.)

Wind
3336
Seismic 3922= 3727+ 195

B
8.0

3.8
3.0
8.0
Panel Edge on the above Story

Strap(E)

6.8

630

8.0

9.8

303

A
0.0

2.8

A
42.0

6.7

14.8

24.2

32.2

910

584

Drag Force Analysis


A: Simpson ST22 (1192 LB)
ALT (10) # 16d sinker per top plate splice
Total Wall Length = 42.00(FT) Total Panel Length = 16.00(FT) P.T./User Design
=
Shear Diaphragm = 3922/ 42.00 = 93(PLF)
Use (10 A35) or (7 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(S) =2665/ 8.00= 333(PLF)(Up_Floor ) Max. Drag = 910(LB)

1.00

Use TYPE 2
Max. Panel Deflection:
Dead Loads:
Wall

M = (4.0/1.0) x

s x 1.4 = 1.516" <= 0.02 x 96.0 = 1.920"

120.0= 15 * 8.0'

Load 1 @ 0.0' Start 0.0' to 37.0'(100%)


OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 3652(LB) C= 4700(LB)
Right Side : T= 3750(LB) C= 2035(LB)

HDU4/4x4
HDU4/4x4

Use HDU4/4x4 on both ends


w/(2)5/8" x 12" Anchor Bolt (@ 56" O.C. Max.)
Panel

Left Side
: T= 2912(LB) C= 4781(LB)
Right Side : T= 2912(LB) C= 2125(LB)

HDU2/4x4
HDU2/4x4

Use HDU2/4x4 on both ends


w/(2)5/8" x 12" Anchor Bolt (@ 56" O.C. Max.)

IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 2190 Seismic: 1146

wind
seismic

112.3
58.8
1Y_1_FL
39.0

7 @Right of Garage

1ST Floor 2-Pour

Exterior Wall(Y Dir.)

Wind
2190
Seismic 2034= 1863+ 172

A
8.0

18.0

3.5

8.0

17.0

2.5

3.0

Strap(E)
905

A
52.0

0.0

21.5

29.5

948

Drag Force Analysis


A: Simpson ST22 (1192 LB)
ALT (10) # 16d sinker per top plate splice
Total Wall Length = 52.00(FT) Total Panel Length = 8.00(FT) P.T./User Design

Shear Diaphragm = 2190/ 52.00 = 42(PLF)


Use (6 A35) or (4 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(W) = 2190/ 8.00= 274(PLF)(Flexible ) Max. Drag = 948(LB)

= 1.00

Use TYPE 2
Max. Panel Deflection:
Dead Loads:
Wall

M = (4.0/1.0) x

s x 1.4 = 1.088" <= 0.02 x 96.0 = 1.920"

120.0= 15 * 8.0'

OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 1985(LB) C= 2273(LB)
Right Side : T= 1985(LB) C= 2273(LB)

HDU2/4x4
HDU2/4x4

Use HDU2/4x4 on both ends


w/(2)5/8" x 12" Anchor Bolt (@ 56" O.C. Max.)

IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 1067 Seismic: 558

wind
seismic

112.3
58.8
1Y_1_FL
19.0

Load 2 @ -6.5' Start 0.0' to 58.5'(100%)

8 @Right of Elevation

1ST Floor 2-Pour

Exterior Wall(Y Dir.)

Wind
3280
Seismic 4713= 4452+ 261

C
8.0

6.5
Strap(E)

5.0
HD

8.0
1.8 2.5
Panel Edge on the above Story

3.8
2.5
5.5
2.5
3.0
MIN. 4x Post E.N. @ 3" O/C May Needed

2.8

7.3

1.5

5.5

935

A
0.0

A
43.3

11.5

19.5

23.8

27.5

256
601

30.0

773
976

58.0

35.5

1828

Drag Force Analysis


A: Simpson ST22 (1192 LB)
B: Simpson ST6224(2134 LB)

ALT (10) # 16d sinker per top plate splice


ALT (16) # 16d sinker per top plate splice

See Detail Information on Next Page

IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Total Wall Length = 58.00(FT) Total Panel Length = 17.25(FT) P.T./User Design
= 1.00
Shear Diaphragm = 4713/ 58.00 = 81(PLF)
Use (12 A35) or (8 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(S) = 4713/17.25= 273(PLF)(Flexible ,SW V_allow(Seismic) Ajusted for H/W Ratio) Max. Drag = 1828(LB)

Use TYPE 2
Max. Panel Deflection:

M = (4.0/1.0) x

Dead Loads:
Wall
120.0= 15 * 8.0'
Load 2 @ -6.5' Start 0.0' to 58.5'(100%)
OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 3325(LB) C= 2269(LB) **
Right Side : T= 2035(LB) C= 2269(LB)

s x 1.4 = 1.889" <= 0.02 x 96.0 = 1.920"

HDU4/4x4
HDU2/4x4

Use HDU4/4x4** @ L. & HDU2/4x4 @ R.


w/(2)5/8" x 12" Anchor Bolt (@ 48" O.C. Max.)

Panel

Left Side
: T= 2260(LB) C= 2522(LB)
Right Side : T= 3922(LB) C= 4389(LB)

HDU2/4x4
HDU4/4x4(I) w/DBL BLK'G

Left Side
: T= 1954(LB) C= 2367(LB)
Right Side : T= 2000(LB) C= 2308(LB)

HDU2/4x4
HDU2/4x4

Use HDU2/4x4 @ L. & HDU4/4x4(I) @ R.


w/(2)5/8" x 12" Anchor Bolt (@ 40" O.C. Max.)

Panel

Use HDU2/4x4 on both ends


w/(2)5/8" x 12" Anchor Bolt (@ 48" O.C. Max.)

** w/ Dead loads of adjacent element, use detail for connection of S.W. to trimmer
(I) Holdown inside of panel

IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 1628 Seismic: 600

wind
seismic

144.7
53.4
1X_1_FL
22.5

Load 3 @ 0.0' Start 0.0' to 39.0'(100%)

9 @Rear of Elevation

1ST Floor 2-Pour

Exterior Wall(X Dir.)

Wind
4028
Seismic 3630= 3557+ 73

B
8.0

2.0
HD

Strap(E)

8.8
4.5
Panel Edge on the above Story

5.0

1103

5.0

14.0

170

A
27.6

0.0

10.7

15.2

20.2

39.3

25.2

1437

343

Drag Force Analysis


A: Simpson ST22 (1192 LB)
ALT (10) # 16d sinker per top plate splice
B: Simpson ST6224(2134 LB)
ALT (16) # 16d sinker per top plate splice
Total Wall Length = 39.25(FT) Total Panel Length = 9.50(FT) P.T./User Design
=
Shear Diaphragm = 4028/ 39.25 = 103(PLF)
Use (10 A35) or (7 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(W) = 4028/ 9.50= 424(PLF)(Flexible ) Max. Drag = 1437(LB)

1.00

Use TYPE 3
Max. Panel Deflection:
Dead Loads:
Wall

M = (4.0/1.0) x

s x 1.4 = 1.721" <= 0.02 x 96.0 = 1.920"

120.0= 15 * 8.0'

Load 3 @ 0.0' Start 0.0' to 39.0'(100%)


OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 3648(LB) C= 3816(LB)
Right Side : T= 5805(LB) C= 6579(LB)

HDU8/4x4(I) w/DBL BLK'G


HDU8/4x4(I) w/DBL BLK'G

Use HDU8/4x4(I) @ L. & HDU8/4x4(I) @ R.


w/(2)5/8" x 12" Anchor Bolt (@ 32" O.C. Max.)
Panel

Left Side
: T= 4920(LB) C= 6662(LB)
Right Side : T= 5005(LB) C= 3859(LB)

HDU8/4x4(I) w/DBL BLK'G


HDU8/4x4(I) w/DBL BLK'G

Use HDU8/4x4(I) on both ends


w/(2)5/8" x 12" Anchor Bolt (@ 32" O.C. Max.)

(I) Holdown inside of panel


IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 3039 Seismic: 1121

wind
seismic

144.7
53.4
1X_1_FL
42.0

10 @Rear of Garage

1ST Floor 2-Pour

Exterior Wall(X Dir.)

Wind
3039
Seismic 1992= 1849+ 143

A
8.0

9.8

2.8

2.5

2.5

3.3

7.3

11.0

Strap(E)
2182

B
15.3

0.0

Drag Force Analysis

27.4
28.0

39.0

A: Simpson ST22 (1192 LB)


ALT (10) # 16d sinker per top plate splice
B: Simpson ST6224(2134 LB)
ALT (16) # 16d sinker per top plate splice
C: Simpson ST6236(3230 LB)
ALT (22) # 16d sinker per top plate splice
Total Wall Length = 39.00(FT) Total Panel Length = 11.00(FT) P.T./User Design

Shear Diaphragm = 3039/ 39.00 = 78(PLF)


Use (8 A35) or (6 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(W) = 3039/11.00= 276(PLF)(Flexible ) Max. Drag = 2182(LB)

= 1.00

Use TYPE 2
Max. Panel Deflection:
Dead Loads:
Wall

M = (4.0/1.0) x

s x 1.4 = 0.651" <= 0.02 x 96.0 = 1.920"

120.0= 15 * 8.0'

OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 1875(LB) C= 2271(LB)
Right Side : T= 1875(LB) C= 2271(LB)

HDU2/4x4
HDU2/4x4

Use HDU2/4x4 on both ends


w/(3)5/8" x 12" Anchor Bolt (@ 64" O.C. Max.)

IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 1881 Seismic: 694

wind
seismic

144.7
53.4
1X_1_FL
26.0

Load 4 @ 0.0' Start 0.0' to 0.0'(100%)

11 @Front of Garage

1ST Floor 2-Pour

Mixed Wall(X Dir.)

Wind
5440
Seismic 3801= 3698+ 103

B
8.0

1.0
Strap(I)

16.0
HD

Strap(E)

3.3

6.0

12.5

2563

2387
1720

B
8.5

0.0

C
15.2

C
23.2

17.0 Analysis
20.3
Drag Force

26.3

38.8

A: Simpson ST22 (1192 LB)


ALT (10) # 16d sinker per top plate splice
B: Simpson ST6224(2134 LB)
ALT (16) # 16d sinker per top plate splice
C: Simpson ST6236(3230 LB)
ALT (22) # 16d sinker per top plate splice
Total Wall Length = 38.75(FT) Total Panel Length = 15.75(FT) P.T./User Design
= 1.00
Shear Diaphragm = 5440/ 38.75 = 140(PLF)
Use (13 A35) or (10 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(W) = 5440/15.75= 345(PLF)(Flexible ,SW V_allow(Seismic) Ajusted for H/W Ratio) Max. Drag = 2563(LB)

Use TYPE 2
Max. Panel Deflection:
Dead Loads:
Wall

M = (4.0/1.0) x

s x 1.4 = 1.465" <= 0.02 x 96.0 = 1.920"

80.0 = 10 * 8.0'

Load 4 @ 0.0' Start 0.0' to 0.0'(100%)


OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 3188(LB) C= 3266(LB)
Right Side : T= 3188(LB) C= 3266(LB)

HDU4/4x4(I) w/DBL BLK'G


HDU4/4x4(I) w/DBL BLK'G

Use HDU4/4x4(I) on both ends


w/(2)5/8" x 12" Anchor Bolt (@ 32" O.C. Max.)
Panel

Left Side
: T= 2578(LB) C= 2878(LB)
Right Side : T= 2578(LB) C= 2878(LB)

HDU2/4x4(I) w/DBL BLK'G


HDU2/4x4(I) w/DBL BLK'G

Use HDU2/4x4(I) on both ends


w/(3)5/8" x 12" Anchor Bolt (@ 48" O.C. Max.)

(I) Holdown inside of panel


IBC9.7
IBC9.7

Job : 66927-200
Plan : 1

Wind: 580 Seismic: 203

wind
seismic

178.5
62.4
2X_ROOF
6.5

Load 5 @ 0.0' Start 0.0' to 0.0'(100%)

12 @Front of Porch

1ST Floor 2-Pour

Exterior Wall(X Dir.)

Wind 1919(Uplift on Roof=7.2 PSF)


Seismic 927= 861+ 66

B
8.0

2.3
- - - Blocked with the Header(See Plan)

Strap(E)

4.8

2.0

2.5

5.3

909

2.3

682
152

A
0.0

A
11.5
Drag Force 9.0
Analysis

16.8 19.0

A: Simpson ST22 (1192 LB)


ALT (10) # 16d sinker per top plate splice
Total Wall Length = 19.00(FT) Total Panel Length = 4.75(FT) P.T./User Design
= 1.00
Shear Diaphragm = 1919/ 19.00 = 101(PLF)
Use (5 A35) or (4 LS50) Along Line of Shear Panel or for Framing Clips Spacing See S.W. Schedule
Design Wall Shear(W) = 1919/ 4.75= 404(PLF)(Flexible ,SW V_allow(Seismic) Ajusted for H/W Ratio) Max. Drag = 909(LB)

Use TYPE 3
Max. Panel Deflection:
Dead Loads:
Wall

M = (4.0/1.0) x

s x 1.4 = 1.747" <= 0.02 x 96.0 = 1.920"

120.0= 15 * 8.0'

Load 5 @ 0.0' Start 0.0' to 0.0'(100%)


OVERTURN ANALYSIS
UPLIFT(T)
DOWN(C)
A
Panel
Left Side
: T= 3569(LB) C= 3659(LB)
Right Side : T= 3569(LB) C= 3659(LB)

HDU4/4x4
HDU4/4x4

Use HDU4/4x4 on both ends


w/(2)5/8" x 12" Anchor Bolt (@ 24" O.C. Max.)
Panel

Left Side
: T= 3633(LB) C= 3714(LB)
Right Side : T= 3633(LB) C= 3714(LB)

HDU4/4x4
HDU4/4x4

Blocked with the Header


Use HDU4/4x4 on both ends
w/(2)5/8" x 12" Anchor Bolt (@ 24" O.C. Max.)

IBC9.7
IBC9.7

Tung Thanh Vo, M.S., P.E.

BEAMS
DESIGN

2010-CBC

Job
Plan

: 66927-200
:1

Loads (Downward +)
40.0 PLF @
0.0' to the
36.5' Bath #3
Beam
ID: GT#1 Girder Truss
Over
Beam Weight
180 PLF= 9.0'x(20+20)/2 @ 0.00' to 36.50'
Primary Roof
36.50'

Down (DL+LL/Max.)
Up (DL+LL/Max.)

4015/4015
0/0

4015/4015
0/0

*** TRUSS DESIGNED BY OTHERS ***

Beam ID: GT#2 Girder Truss Over the Master Bath


Loads (Downward +)
40.0 PLF @ 0.0' to 36.5'
Beam Weight
190 PLF= 9.5'x(20+20)/2 @ 0.00' to 36.50'
Primary Roof
36.50'

Down (DL+LL/Max.)
Up (DL+LL/Max.)

4198/4198
0/0

4198/4198
0/0

*** TRUSS DESIGNED BY OTHERS ***

Beam ID: GT#3 Girder Truss @ Rear of the Master Bedroom


Loads (Downward +)
30.0 PLF from 0.0' to 15.0'
Beam Weight
80 PLF= 4.0'x(20+20)/2 @ 0.00' to 7.25'
Primary Roof
770 PLF=38.5'x(20+20)/2 @ 7.25' to 15.00'
Primary Roof
From left of BM GT#2 @ 7.25
Point Load(P1)
:Point Load Location
P1
15.00'
7.25'

Down (DL+LL/Max.)
Up (DL+LL/Max.)

4280/4280
0/0

6663/6663
0/0

*** TRUSS DESIGNED BY OTHERS ***

IBC9.7

Job
Plan

: 66927-200
:1

Beam ID: GT#4 Girder Truss @ Rear of the Master Bedroom


Loads (Downward +)
30.0 PLF from 0.0' to 18.8'
Beam Weight
80 PLF= 4.0'x(20+20)/2 @ 0.00' to 7.50'
Primary Roof
780 PLF=39.0'x(20+20)/2 @ 7.50' to 18.75'
Primary Roof
From right of BM GT#2 @ 7.50
Point Load(P1)
:Point Load Location
P1
18.75'
7.50'

Down (DL+LL/Max.)
Up (DL+LL/Max.)

5598/5598
0/0

7760/7760
0/0

*** TRUSS DESIGNED BY OTHERS ***

IBC9.7

Job
Plan

Beam ID: 1 Header @ Left of the Bed #3


Loads (Downward +)
20.0 PLF from 0.0' to 5.3'
Beam Weight
800 PLF=40.0'x(20+20)/2 @ 0.00' to 2.00'
Primary Roof
135 PLF= 9.0'x(10+20)/2 @ 2.00' to 5.25'
Secondary Roof
30 PLF= 2.0'x15.0 @ 0.00' to 5.25'
Exterior Wall
From left of BM GT#1 @ 2.00
Point Load(P1)
:Point Load Location

: 66927-200
:1

P1
5.25'
2.00'
3764

Reactions(DL+LL/Max. Load Combination)


Down
4048/4048
2268/2268
Up
0/0
0/0

Use TIMBERSTRAND 3 1/2x 9 1/2 1.5E(Fb=2325 Fv=310)


w/Left:2-2x4 trim./stud
Critical Shear

=3764

Critical Moment

=6396

Critical Deflection

= -0.070

LB @ 0.33' 1.5xShear/(FvxA)=0.438
Fv=388 A= 33.25
LBxFT @ 2.00' Ratio=0.491
Fb= 2969 S= 52.65
INCH @ 2.42'

Shear Diagram:DL + RF_L

6396

Moment Diagram:DL + RF_L

-0.070
Deflection Diagram:DL+LL

Beam ID: 2(Drop) Header @ Left of the Bonus


Loads (Downward +)
20.0 PLF @ 0.0' to 5.3'
Beam Weight
800 PLF=40.0'x(20+20)/2 @ 0.00' to
Primary Roof
30 PLF= 2.0'x15.0 @ 0.00' to 5.25'
Exterior Wall

5.25'

5.25'

1948

Reactions(DL+LL/Max. Load Combination)


Down
2231/2231
2231/2231
Up
0/0
0/0

Use DFL NO2 4 x 8(Fb= 900 Fv=180)


Critical Shear

=1948

Critical Moment

=2928

Critical Deflection

= -0.082

LB @ 0.33' 1.5xShear/(FvxA)=0.512
Fv=225 A= 25.38
LBxFT @ 2.67' Ratio=0.789
Fb= 1453 S= 30.66
INCH @ 2.67'

Shear Diagram:DL + RF_L

2928

Moment Diagram:DL + RF_L

-0.082
Deflection Diagram:DL+LL

IBC9.7

Job
Plan

Beam ID: 3(Drop) Clg Bm Over the Bed #3


Loads (Downward +)
20.0 PLF @ 0.0' to 9.0'
Beam Weight
760 PLF=38.0'x(20+20)/2 @ 0.00' to
Primary Roof

9.00'

9.00'

Reactions(DL+LL/Max. Load Combination)


Down
3510/3510
3510/3510
Up
0/0
0/0

: 66927-200
:1

3250

Use TIMBERSTRAND 3 1/2x 9 1/2 1.5E(Fb=2325 Fv=310)


w/Left:2-2x4 trim./stud
Right:2-2x4 trim./stud
Critical Shear

=3250

Critical Moment

=7898

Critical Deflection

=-0.307

LB @ 0.33' 1.5xShear/(FvxA)=0.378
Fv=388 A= 33.25
LBxFT @ 4.50' Ratio=0.634
Fb= 2837 S= 52.65
Inch @ 4.50' L/240=0.450

Shear Diagram:DL + RF_L

7898

Moment Diagram:DL + RF_L

-0.307
Deflection Diagram:DL+LL

Beam ID: 4(Drop) Header @ Rear of the Bonus


Loads (Downward +)
20.0 PLF @ 0.0' to 4.3'
Beam Weight
200 PLF=10.0'x(20+20)/2 @ 0.00' to 2.50'
Primary Roof
440 PLF=22.0'x(20+20)/2 @ 2.50' to 4.25'
Primary Roof
30 PLF= 2.0'x15.0 @ 0.00' to 4.25'
Exterior Wall
From left of BM GT#4 @ 2.50
Point Load(P1)
:Point Load Location

P1
4.25'
2.50'

Reactions(DL+LL/Max. Load Combination)


Down
3052/3052
4343/4343
Up
0/0
0/0

Use TIMBERSTRAND 3 1/2x9 1/2 1.5E(Fb=2325 Fv=310)


w/ Right:2-2x4 trim./stud
Critical Shear

=-4179

Critical Moment

=6849

Critical Deflection

= -0.048

LB @ 3.92' 1.5xShear/(FvxA)=0.487
Fv=388 A= 33.25
LBxFT @ 2.50' Ratio=0.535
Fb= 2919 S= 52.65
INCH @ 2.25'

-4179
Shear Diagram:DL + RF_L

6849

Moment Diagram:DL + RF_L

-0.048
Deflection Diagram:DL+LL

IBC9.7

Job
Plan

Beam ID: 5 Flush Bm Over the Living Room


Loads (Downward +)
20.0 PLF from 0.0' to 8.8'
Beam Weight
140 PLF= 7.0'x(20+20)/2 @ 6.75' to 8.75'
Primary Roof
800 PLF=40.0'x(20+20)/2 @ 0.00' to 1.75'
Primary Roof
From left of BM 1 @ 1.75
Point Load(P1)
From right of BM 1 @ 6.75
Point Load(P2)
74 PLF= 2.7'x(15+40)/2 @ 0.00' to 8.50'
Primary Floor
135 PLF= 9.0'x15.0 @ 0.00' to 8.75'
Exterior Wall
W= 1579 S= 1829 H= 9.0' @-4.5' L= 6.3' 3(A)
Shear Wall
:Point Load Location
:Edge of Shear Panel
Reactions(DL+LL/Max. Load Combination)
Down
6051/9866
3932/4790
Up
0/-3798
0/-206

: 66927-200
:1

P2

P1
8.75'
1.75'
6.75'
9545

Shear Diagram:(1.0+0.105xS_ds)xDL+0.75x(FL_L+RF_L+2.5xSEIS)*

15789

Use DFL NO1 6 x 12(Fb=1350 Fv=170)


w/Left:2-2x6 trim./stud
Critical Shear

=9545

Critical Moment

=15789

Critical Deflection

= -0.119

LB @ 0.33' 1.5xShear/(FvxA)=0.693
Fv=326 A= 63.25
LBxFT @ 1.75' Ratio=0.603
Fb= 2592 S= 121.23
INCH @ 4.25'

Moment Diagram:(1.0+0.105xS_ds)xDL+0.75x(FL_L+RF_L+2.5xSEIS)*

*Or Section ASCE 12.4.3.1 Exception Per NDS 4.3.3, Em = 2 x S.W. Capacity x HT

-0.119
Deflection Diagram:DL+LL

Beam ID: 6(Drop) Header @ Rear of the Kitchen


Loads (Downward +)
20.0 PLF @ 0.0' to 5.3'
Beam Weight
68 PLF= 4.5'x15.0 @ 0.00' to 5.25'
Exterior Wall
83 PLF= 3.0'x(15+40)/2 @ 0.00' to 5.25'
Primary Floor
From right of BM 2 @ 5.25
Point Load(P1)
From left of BM 2 @ 0.00
Point Load(P2)
:Point Load Location
Reactions(DL+LL/Max. Load Combination)
Down
2678/2520
2678/2520
Up
0/0
0/0

P2

P1
5.25'

390

Shear Diagram:DL + FL_L

586

Use DFL NO2 4 x 6(Fb= 900 Fv=180)


Critical Shear

=390

Critical Moment

=586

Critical Deflection

= -0.037

LB @ 0.33' 1.5xShear/(FvxA)=0.169
Fv=180 A= 19.25
LBxFT @ 2.67' Ratio=0.342
Fb= 1166 S= 17.65
INCH @ 2.67'
Moment Diagram:DL + FL_L

-0.037
Deflection Diagram:DL+LL

IBC9.7

Job
Plan

Beam ID: 7(Drop) Drop Bm @ Left of the Living Room


Loads (Downward +)
20.0 PLF from 0.0' to 12.5'
Beam Weight
646 PLF=23.5'x(15+40)/2 @ 0.00' to 12.50'
Primary Floor
15 PLF= 1.5'x10.0 @ 0.00' to 12.50'
Interior Wall

: 66927-200
:1

12.50'
4031

Reactions(DL+LL/Max. Load Combination)


Down
4258/4258
4258/4258
Up
0/0
0/0

Use DFL NO1 6 x 12(Fb=1350 Fv=170)


Critical Shear

=4031

Critical Moment

=13306

Critical Deflection

=-0.231

LB @ 0.33' 1.5xShear/(FvxA)=0.562
Fv=170 A= 63.25
LBxFT @ 6.25' Ratio=0.988
Fb= 1333 S= 121.23
Inch @ 6.25' L/480=0.313

Shear Diagram:DL + FL_L

13306

Moment Diagram:DL + FL_L

-0.231
Deflection Diagram:LL

Beam ID: 8(Drop) Drop Bm @ Right of the Living Room


Loads (Downward +)
20.0 PLF from 0.0' to 12.5'
Beam Weight
743 PLF=27.0'x(15+40)/2 @ 0.00' to 12.50'
Primary Floor
Reactions(DL+LL/Max. Load Combination)
Down
4715/4715
4715/4715
Up
0/0
0/0

12.50'
4464

Use GLB 24F V4 5 1/8 x 12(Fb=2400/1850 Fv=265)


Critical Shear

=4464

Critical Moment

=14734

Critical Deflection

=-0.220

LB @ 0.33' 1.5xShear/(FvxA)=0.411
Fv=265 A= 61.50
LBxFT @ 6.25' Ratio=0.610
Fb= 2355 S= 123.00
Inch @ 6.25' L/480=0.313

Shear Diagram:DL + FL_L

14734

Moment Diagram:DL + FL_L

-0.220
Deflection Diagram:LL

IBC9.7

Job
Plan

Beam ID: 9 Flush Bm Over the Stair


Loads (Downward +)
20.0 PLF from 0.0' to 9.5'
Beam Weight
413 PLF=15.0'x(15+40)/2 @ 0.00' to
Primary Floor
40 PLF= 4.0'x10.0 @ 0.00' to 9.50'
Interior Wall

: 66927-200
:1

9.50'

9.50'

2087

Reactions(DL+LL/Max. Load Combination)


Down
2244/2244
2244/2244
Up
0/0
0/0

Use DFL NO2 4 x 12(Fb= 900 Fv=180)


Critical Shear

=2087

Critical Moment

=5330

Critical Deflection

= -0.083

LB @ 0.33' 1.5xShear/(FvxA)=0.442
Fv=180 A= 39.38
LBxFT @ 4.75' Ratio=0.875
Fb= 990 S= 73.83
INCH @ 4.75'

Shear Diagram:DL + FL_L

5330

Moment Diagram:DL + FL_L

-0.083
Deflection Diagram:LL

Beam ID: 10 Flush Bm @ Front of the Stair


Loads (Downward +)
20.0 PLF from 0.0' to 7.8'
Beam Weight
83 PLF= 3.0'x(15+40)/2 @ 0.00' to
Primary Floor
From right of BM 9 @ 4.00
Point Load(P1)
:Point Load Location

P1

7.75'

7.75'
4.00'

Reactions(DL+LL/Max. Load Combination)


Down
1483/1483
1556/1556
Up
0/0
0/0

Use DFL NO2 4 x 12(Fb= 900 Fv=180)


Critical Shear

=-1521

Critical Moment

=5113

Critical Deflection

= -0.043

LB @ 7.42' 1.5xShear/(FvxA)=0.322
Fv=180 A= 39.38
LBxFT @ 4.00' Ratio=0.839
Fb= 990 S= 73.83
INCH @ 3.92'

-1521
Shear Diagram:DL + FL_L

5113

Moment Diagram:DL + FL_L

-0.043
Deflection Diagram:LL

IBC9.7

Job
Plan

Beam ID: 11 Flush Bm Over the Stair


Loads (Downward +)
30.0 PLF @ 0.0' to 18.8'
Beam Weight
80 PLF= 4.0'x(20+20)/2 @ 0.00' to 18.75'
Primary Roof
135 PLF= 9.0'x15.0 @ 0.00' to 18.75'
Exterior Wall

: 66927-200
:1

18.75'
1854

Reactions(DL+LL/Max. Load Combination)


Down
2297/2297
2297/2297
Up
0/0
0/0

Use DFL NO1 6 x 12(Fb=1350 Fv=170)


Critical Shear

=1854

Critical Moment

=9009

Critical Deflection

=-0.611

LB @ 0.33' 1.5xShear/(FvxA)=0.287
Fv=153 A= 63.25
LBxFT @ 9.42' Ratio=0.734
Fb= 1215 S= 121.23
Inch @ 9.42' L/240=0.938

Shear Diagram:DL

9009

Moment Diagram:DL

-0.611
Deflection Diagram:DL+LL

Beam ID: 12(Drop) Header @ Rear of the Elve


Loads (Downward +)
20.0 PLF @ 0.0' to 2.8'
Beam Weight
440 PLF=22.0'x(20+20)/2 @ 0.00' to 1.25'
Primary Roof
420 PLF=21.0'x(20+20)/2 @ 1.25' to 2.75'
Primary Roof
165 PLF=11.0'x15.0 @ 0.00' to 1.25'
Exterior Wall
30 PLF= 2.0'x15.0 @ 1.25' to 2.75'
Exterior Wall
From left of BM 11 @ 1.25
Point Load(P1)
@ 1.3(G= 0 W= -765 S= -322 Fr 5(A L)
Point Load
:Point Load Location
:Edge of Shear Panel
Reactions(DL+LL/Max. Load Combination)
Down
2049/2411
1734/2024
Up
0/0
0/0

P1
2.75'
1.25'
1411

Shear Diagram:DL

1616

Use DFL NO2 4 x 8(Fb= 900 Fv=180)


Critical Shear

=1411

Critical Moment

=1616

Critical Deflection

= -0.013

LB @ 0.33' 1.5xShear/(FvxA)=0.515
Fv=162 A= 25.38
LBxFT @ 1.25' Ratio=0.602
Fb= 1050 S= 30.66
INCH @ 1.33'

Moment Diagram:DL

-0.013
Deflection Diagram:DL+LL

IBC9.7

Job
Plan

Beam ID: 13(Drop) Header @ Front of the Garage


Loads (Downward +)
30.0 PLF @ 0.0' to 16.3'
Beam Weight
100 PLF= 5.0'x(20+20)/2 @ 0.00' to 16.25'
Primary Roof
Reactions(DL+LL/Max. Load Combination)
Down
1056/1056
1056/1056
Up
0/0
0/0

: 66927-200
:1

16.25'
1013

Use DFL NO2 4 x 10(Fb= 900 Fv=180)


Critical Shear

=1013

Critical Moment

=4291

Critical Deflection

=-0.552

LB @ 0.33' 1.5xShear/(FvxA)=0.209
Fv=225 A= 32.38
LBxFT @ 8.17' Ratio=0.790
Fb= 1306 S= 49.91
Inch @ 8.17' L/240=0.813

Shear Diagram:DL + RF_L

4291

Moment Diagram:DL + RF_L

-0.552
Deflection Diagram:DL+LL

Beam ID: 14 Flush Bm Over the Garage


Loads (Downward +)
30.0 PLF @ 0.0' to 19.8'
Beam Weight
60 PLF= 3.0'x(20+20)/2 @ 3.75' to 13.00'
Primary Roof
135 PLF= 9.0'x15.0 @ 3.75' to 13.00'
Exterior Wall
73 PLF= 2.7'x(15+40)/2 @ 0.00' to 19.75'
Primary Floor

19.75'
1866

Reactions(DL+LL/Max. Load Combination)


Down
2060/1900
1786/1669
Up
0/0
0/0

Use DFL NO1 6 x 12(Fb=1350 Fv=170)


Critical Shear

=1866

Critical Moment

=10660

Critical Deflection

=-0.711

Shear Diagram:DL + FL_L

10660

LB @ 0.33' 1.5xShear/(FvxA)=0.260
Fv=170 A= 63.25
LBxFT @ 9.42' Ratio=0.782
Fb= 1350 S= 121.23
Inch @ 9.75' L/280=0.846

Moment Diagram:DL + FL_L

-0.711
Deflection Diagram:DL+LL

IBC9.7

Job
Plan

Beam ID: 15 Flush Bm Over the Garage


Loads (Downward +)
30.0 PLF @ 0.0' to 19.8'
Beam Weight
800 PLF=40.0'x(20+20)/2 @ 0.00' to 3.75'
Primary Roof
200 PLF=10.0'x(20+20)/2 @12.75' to 19.75'
Primary Roof
135 PLF= 9.0'x15.0 @ 0.00' to 3.75'
Exterior Wall
135 PLF= 9.0'x15.0 @12.75' to 19.75'
Exterior Wall
W= 1324 S= 1094 H= 9.0' @ 0.0' L= 4.0' 4(B)
Shear Wall
W= 2234 S= 1847 H= 9.0' @13.0' L= 6.8' 4(A)
Shear Wall
193 PLF= 7.0'x(15+40)/2 @ 0.00' to 19.75'
Primary Floor
From left of BM 3 @ 3.75
Point Load(P1)
From right of BM 3 @13.00
Point Load(P2)
From right of BM GT#4 @ 0.00
Point Load(P3)
:Point Load Location
:Edge of Shear Panel

P3

: 66927-200
:1

P2

P1
19.75'
3.75'
13.00'

6125

Shear Diagram:DL + FL_L

25373

Reactions(DL+LL/Max. Load Combination)


Down
16071/18029
6846/9089
Up
0/0
0/-1647

Use GLB 24F V4 5 1/8 x 16 1/2(Fb=2400/1850 Fv=265)


w/Left:Design trim./post
Right:2-2x6 trim./stud
Critical Shear

=6125

Critical Moment

=25373

Critical Deflection

=-0.718

LB @ 0.33' 1.5xShear/(FvxA)=0.410
Fv=265 A= 84.56
LBxFT @ 11.58' Ratio=0.582
Fb= 2248 S= 232.55
Inch @ 9.92' L/280=0.846

Moment Diagram:DL + FL_L

-0.718
Deflection Diagram:DL+LL

IBC9.7